Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3014.42 | 623.44 | 623.44 |
Net Site Energy | 3014.42 | 623.44 | 623.44 |
Total Source Energy | 5066.52 | 1047.86 | 1047.86 |
Net Source Energy | 5066.52 | 1047.86 | 1047.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2150.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 863.60 | 2150.82 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2150.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 71.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 24.61 | 444.83 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 178.61 | 444.83 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 24.61 | 444.83 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 178.61 | 444.83 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 863.603 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 863.603 | 100.00 |
Total On-Site and Utility Electric Sources | 863.603 | 100.00 |
Total Electricity End Uses | 863.603 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 77.50 |
Time Setpoint Not Met During Occupied Cooling | 1.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2115.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:50 | 09-DEC-06:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 565860.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19031.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6520.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1775.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73059.43 | 565860.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 565860.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19031.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4215.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1775.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2331.49 | 0.00 | 0.00 | 0.00 |
Cooling | 61.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 227.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2735.03 | 2331.49 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 482.20 | 0.00 | 0.00 | 0.00 |
Cooling | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 565.66 | 482.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 482.20 | 0.00 | 0.00 | 0.00 |
Cooling | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 565.66 | 482.20 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.72 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 8.13 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 8.13 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 322144.08 |
PSZ-OFFICE HEATING COIL | 29292.92 |
PSZ-FINE STORAGE HEATING COIL | 97282.29 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 322144.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-FINE STORAGE | 2.72 | 2.72 | 2.72 | 2.72 | 2.72 | 2.72 | 1.00 | 1.00 | 2.72 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.72 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 20184.47 | 29292.92 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.72 | 2.72 | 2.72 | 2.72 | 66219.68 | 97282.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.542100 | 1.08 | 19679.34 | 20184.47 | 10092.24 | 20184.47 | 0.757907 | 0.757910 | 0.757910 | 0.757910 |
PSZ-FINE STORAGE COOLING COIL | 2.72 | 1.36 | 2.72 | 63550.63 | 66219.68 | 33109.84 | 66219.68 | 0.681153 | 0.681150 | 0.681150 | 0.681150 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1236.11 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.72 | 2979.06 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10474.45917 | 12569.35100 | 0.90350 | 1.08420 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53444E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 15711.27782 | 18853.53338 | 0.46267 | 0.55521 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 31332.30910 | 37598.77092 | 2.10709 | 2.52851 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 91527.41559 | 109832.89871 | 2.26819 | 2.72183 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20000 | 1.53444E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 268453.38076 | 322144.05692 | 6.77267 | 8.12720 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15575.66 | 1.08420 | 1.08420 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 17721.98 | 0.55521 | 0.55521 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 45095.16 | 2.52851 | 2.52851 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 97282.29 | 2.72183 | 2.72183 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08420 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.72183 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.12720 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 8.12720 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 322144.08242 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 322144.05692 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08420 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08420 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08420 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08420 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08420 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.08420 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72183 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.72183 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.72183 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.72183 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.72183 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.72183 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.08420 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.72183 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08420 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08420 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08420 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08420 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08420 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08420 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54210 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08420 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19679.34136 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20184.47000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10092.23500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20184.47000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75791 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75791 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75791 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75791 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20184.47000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29292.91520 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08420 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1236.11211 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29292.91520 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.72183 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.72183 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.72183 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.72183 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.72183 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.72183 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.36092 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.72183 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 63550.63042 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 66219.68000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 33109.84000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 66219.68000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68115 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68115 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68115 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68115 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66219.68000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 97282.28736 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.72183 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2979.05607 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 97282.28736 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19342.8 | 10.27 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 64104.2 | 13.12 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2889082331 | 0.2651466555 | Pass | Pass | 7.5876143979 | 49.6278960876 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.8286407822 | 0.7995003238 | Pass | Pass | 0.9199623143 | 1.8949204995 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.8073111898E-005 | 1.9999043784E-004 | Pass | Pass | 2.1049064107E-002 | 2.2221241567E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.63 | 83.63 | 123.35 | |
Exterior Lighting Total | 7857.24 | 123.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20184.47 | 15298.01 | 4886.46 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66219.68 | 45105.54 | 21114.14 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19342.8 | 10.27 | ||||
PSZ-FINE STORAGE COOLING COIL | 64104.2 | 13.12 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 322144.08 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29292.92 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 97282.29 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 8.13 | 755.10 | 92.91 | 1.00 | 3.02 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.08 | 1236.11 | 1140.11 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.72 | 2979.06 | 1094.51 | 1.00 | 1.25 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10474.46 | 12569.35 | 53.06 | 0.904 | 1.084 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00852 | 29.72 | 0.01534 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 31332.31 | 37598.77 | 26.98 | 2.107 | 2.529 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00912 | 31.20 | 0.01534 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00396 | 31.20 | 0.01534 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15711.28 | 18853.53 | 79.59 | 0.463 | 0.555 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00724 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 91527.42 | 109832.90 | 78.82 | 2.268 | 2.722 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00565 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 268453.38 | 322144.06 | 100.52 | 6.773 | 8.127 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00799 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.56 | 0.56 | 1.0842 | 1.0842 | 1.0842 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.53 | 2.53 | 2.72 | 2.72 | 2.7218 | 2.7218 | 2.7218 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 322144.082 | 322144.082 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 322144.08 | 322144.08 | 8.127204 | 5.63 | 5.63 | 0.00707540 | 43.33 | 26.49 | 0.01600000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.98 | 0.00799263 | 100.0000 | 322144.06 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20184.470 | 0.000 | 1.084200 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20184.47 | 16816.94 | 1.084200 | 24.45 | 16.60 | 0.00915936 | 12.00 | 10.84 | 0.00800000 | 29.72 | 0.01534435 | 22.70 | 9.4341 | 23.90 | 0.00851508 | 43.9879 | 10474.46 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29292.915 | 29292.915 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29292.92 | 29292.92 | 1.084204 | 12.34 | 8.84 | 0.00597059 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 9.4341 | 21.10 | 0.00723734 | 44.4179 | 15711.28 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 66219.680 | 0.000 | 2.721830 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 66219.68 | 50553.02 | 2.721830 | 27.45 | 18.39 | 0.01016250 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01534436 | 23.10 | 15.6039 | 26.70 | 0.00911639 | 39.8352 | 30466.94 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 97282.287 | 97282.287 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 97282.29 | 97282.29 | 2.721828 | 9.03 | 5.97 | 0.00482248 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 15.6039 | 15.54 | 0.00564730 | 49.2430 | 91527.42 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 322144.082 | 322144.082 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1486 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 8.127204 | 9.33454758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 322144.08 | 322144.08 | 1.0000 | 9.33454758 | 8.127204 | 5.63 | 5.63 | 0.00707540 | 23424.3 | 43.33 | 26.49 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 322144.08 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.98 | 0.00799263 | 9.98 | 0.00799263 | 100.0000 | 322144.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20184.470 | 0.000 | 1.084200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8668 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20184.47 | 16816.94 | 1.0000 | 1.24526423 | 1.084200 | 24.45 | 16.60 | 0.00915936 | 47889.0 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20184.47 | 29.72 | 0.01534435 | 22.70 | 0.10228487 | 9.4341 | 23.90 | 0.00851508 | 23.90 | 0.00851508 | 43.9879 | 10474.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29292.915 | 29292.915 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.084204 | 1.24526923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29292.92 | 29292.92 | 1.0000 | 1.24526923 | 1.084204 | 12.34 | 8.84 | 0.00597059 | 27472.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29292.92 | -26.20 | 0.00036134 | -26.20 | 0.10228487 | 9.4341 | 21.05 | 0.00723734 | 21.10 | 0.00723734 | 44.4179 | 15711.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66219.680 | 0.000 | 2.721830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7316 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 66219.68 | 50553.02 | 1.0000 | 3.12617371 | 2.721830 | 27.45 | 18.39 | 0.01016250 | 53520.1 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66219.68 | 31.20 | 0.01534436 | 23.10 | 0.42471267 | 15.6039 | 26.70 | 0.00911639 | 26.70 | 0.00911639 | 39.8352 | 30466.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97282.287 | 97282.287 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.721828 | 3.12617180 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 97282.29 | 97282.29 | 1.0000 | 3.12617180 | 2.721828 | 9.03 | 5.97 | 0.00482248 | 21217.2 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97282.29 | -26.20 | 0.00036134 | -26.20 | 0.42471267 | 15.6039 | 15.55 | 0.00564730 | 15.54 | 0.00564730 | 49.2430 | 91527.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.72 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2731.33 | 2755.67 | 2115.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2731.33 | 2755.67 | 2115.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 273.17 | 56.83 | 77.50 | 1.50 |
ZONE2 FINE STORAGE | 798.67 | 14.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 18.00 | 0.00 | 0.00 | 0.00 |
Facility | 956.00 | 68.17 | 77.50 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.346 | 0.316 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
Electricity:Building | 622.06 | 4992.32 | 01-JAN-00:10 | 48037.94 | 26-JUN-10:00 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 422.47 | 2759.73 | 01-JAN-00:10 | 33963.13 | 26-JUN-10:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.61 | 483.00 | 02-JAN-06:00 | 2990.94 | 18-FEB-12:30 |
WaterSystems:Electricity | 27.61 | 483.00 | 02-JAN-06:00 | 2990.94 | 18-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 27.61 | 483.00 | 02-JAN-06:00 | 2990.94 | 18-FEB-12:30 |
Fans:Electricity | 71.92 | 0.00 | 18-MAR-17:10 | 6520.46 | 26-JUN-11:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.82 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
Ventilation (simple):Fans:Electricity | 0.82 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
ElectricityPurchased:Facility | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
ElectricityPurchased:Plant | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
Cogeneration:ElectricityPurchased | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
ElectricityNet:Plant | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
Cogeneration:ElectricityNet | 863.60 | 5475.32 | 19-MAR-09:20 | 73059.43 | 04-AUG-14:50 |
Electricity:HVAC | 90.58 | 0.00 | 18-MAR-17:10 | 24849.67 | 04-AUG-15:40 |
General:Fans:Electricity | 71.10 | 0.00 | 18-MAR-17:10 | 4970.27 | 19-JAN-06:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 19.48 | 0.00 | 01-JAN-00:10 | 20634.51 | 04-AUG-15:40 |
ExteriorLights:Electricity | 123.35 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.35 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2150.82 | 0.00 | 18-MAR-14:50 | 565860.77 | 09-DEC-06:10 |
Gas:HVAC | 2150.82 | 0.00 | 18-MAR-14:50 | 565860.77 | 09-DEC-06:10 |
Heating:Gas | 2150.82 | 0.00 | 18-MAR-14:50 | 565860.77 | 09-DEC-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3392.57 | 0.00 | 18-MAR-17:10 | 895446.26 | 09-DEC-06:10 |
EnergyTransfer:Building | 1672.58 | 0.00 | 18-MAR-17:10 | 446726.98 | 09-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 82.92 | 0.00 | 01-JAN-00:40 | 26193.36 | 06-MAR-07:20 |
Heating:EnergyTransfer | 1627.05 | 0.00 | 18-MAR-17:10 | 446726.98 | 09-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.11 | 0.00 | 01-JAN-00:40 | 26193.36 | 06-MAR-07:20 |
Cooling:EnergyTransfer | 45.54 | 0.00 | 01-JAN-00:10 | 38117.96 | 04-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 19.80 | 0.00 | 01-JAN-00:10 | 9508.02 | 05-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 435.06 | 0.00 | 01-JAN-00:40 | 100894.60 | 19-JAN-07:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 409.33 | 0.00 | 01-JAN-00:40 | 100894.60 | 19-JAN-07:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.73 | 0.00 | 01-JAN-00:10 | 29564.89 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1154.60 | 0.00 | 12-JAN-12:50 | 326034.63 | 09-DEC-08:40 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1154.60 | 0.00 | 12-JAN-12:50 | 326034.63 | 09-DEC-08:40 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1719.98 | 0.00 | 18-MAR-14:50 | 448719.28 | 09-DEC-06:10 |
HeatingCoils:EnergyTransfer | 1650.84 | 0.00 | 18-MAR-14:50 | 448719.28 | 09-DEC-06:10 |
CoolingCoils:EnergyTransfer | 69.15 | 0.00 | 01-JAN-00:10 | 69402.25 | 04-AUG-15:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 63.111 | -19.804 | 0.000 | 0.000 | 3.976 | 30.994 | 31.946 | 9.105 | 0.000 | 0.501 | 0.000 | 0.000 | -13.476 | 0.000 | -33.536 | -72.817 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 409.331 | -25.733 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 1.661 | 0.002 | 0.000 | 0.000 | 0.000 | -308.039 | -213.876 |
ZONE3 BULK STORAGE | 1154.601 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 29.238 | 0.000 | 13.329 | 0.000 | 0.000 | -28.940 | 0.000 | -1121.389 | -468.484 |
Total Facility | 1154.601 | 0.000 | 472.442 | -45.537 | 0.000 | 0.000 | 3.976 | 481.960 | 139.282 | 38.343 | 0.000 | 15.490 | 0.002 | 0.000 | -42.417 | 0.000 | -1462.964 | -755.178 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-SEP-17:43 | 0.00 | 0.00 | 0.00 | -17578.64 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 1829.17 | 0.00 | 0.00 | 14802.77 | 0.00 | -0.00 | 0.00 | -86.01 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:06 | 0.00 | 0.00 | 0.00 | -50734.15 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 49564.66 | 0.00 | -0.00 | 0.00 | -30.39 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:06 | 0.00 | 0.00 | 0.00 | -65795.79 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5822.65 | 0.00 | 115.64 | 168734.00 | 0.00 | 0.00 | 0.00 | -115918.85 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-MAR-05:31 | 0.00 | 0.00 | 29158.95 | 0.00 | 0.00 | 0.00 | 54.22 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -635.50 | 0.00 | -1800.76 | -27937.11 |
ZONE2 FINE STORAGE | 19-JAN-06:41 | 0.00 | 0.00 | 107223.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -41794.50 | -66628.63 |
ZONE3 BULK STORAGE | 09-DEC-08:35 | 326878.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20697.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3294.68 | 0.00 | -351083.82 | -1398.22 |
Total Facility | 18-JAN-18:14 | 322888.34 | 0.00 | 126128.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7505.38 | 0.00 | -352959.89 | -95593.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0842 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0842 | 0.0943 | 1.0000 | 0.1023 | 0.0943 | ||
PSZ-FINE STORAGE | 2.7218 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.7218 | 0.1680 | 1.0000 | 0.4247 | 0.1560 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0842 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0842 | 1.0000 | 1.0000 | 0.1023 | 0.0943 | ||
PSZ-FINE STORAGE | 2.7218 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.7218 | 1.0000 | 1.0000 | 0.4247 | 0.1560 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0842 | 1.0842 | 1.0842 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7218 | 2.7218 | 2.7218 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0842 | 1.0842 | 1.0842 | 1.0842 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7218 | 2.7218 | 2.7218 | 2.7218 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0842 | 1.0842 | 1.0842 | 0.1023 | 0.1842 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7218 | 2.7218 | 2.7218 | 0.4247 | 0.1560 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0842 | 1.0842 | 1.0842 | 1.0842 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7218 | 2.7218 | 2.7218 | 2.7218 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 77.50 |
Number of hours cooling loads not met | 1.50 |
Number of hours not met | 79.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 2150.82 | 565860.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 19.48 | 20634.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.35 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.82 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 71.10 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.61 | 2990.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 863.60 |
Natural Gas | 0.00 | 2150.82 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 3014.42 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 4.03 |
Fans (All) | 14.87 |
Service Water Heating | 5.71 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 178.61 |
Subtotal | 178.61 |
Natural Gas [MJ/m2] | |
Space Heating | 444.83 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 444.83 |
Subtotal | 444.83 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.99 |
Space Heating | 71.35 |
Space Cooling | 0.65 |
Fans (All) | 2.39 |
Service Water Heating | 0.92 |
Receptacle Equipment | 4.62 |
Miscellaneous | 4.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.622449E+12 |
February | 0.000 | 0.426410E+12 |
March | 0.000 | 0.245339E+12 |
April | 0.000 | 0.734123E+11 |
May | 0.000 | 0.402763E+10 |
June | 0.000 | 0.182768E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.328264E+10 |
October | 0.000 | 0.325596E+11 |
November | 0.000 | 0.257764E+12 |
December | 0.000 | 0.485395E+12 |
Annual Sum or Average | 0.215082E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.622449E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.194708E+09 | 236.59 | 21-JAN-13:20 | -5.7 | -6.5 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.179135E+09 | 236.59 | 09-FEB-11:09 | 0.87 | 0.26 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -11.9 | 0.210897E+09 | 266.99 | 25-MAR-15:30 | 18.35 | 10.44 |
April | 0.221107E+09 | 6045.06 | 15-APR-17:20 | 29.43 | 18.74 | 0.203542E+09 | 301.88 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.602434E+09 | 12637.78 | 31-MAY-17:10 | 28.62 | 19.69 | 0.238259E+09 | 303.14 | 15-MAY-09:00 | 17.20 | 15.12 |
June | 0.417111E+10 | 16666.17 | 19-JUN-17:43 | 21.10 | 13.73 | 0.253229E+09 | 301.60 | 19-JUN-13:39 | 19.80 | 13.46 |
July | 0.597688E+10 | 17396.38 | 24-JUL-00:02 | 12.38 | 11.36 | 0.248784E+09 | 301.61 | 22-JUL-15:00 | 21.10 | 14.72 |
August | 0.590287E+10 | 17292.43 | 16-AUG-17:43 | 22.48 | 15.24 | 0.268451E+09 | 301.61 | 17-AUG-15:00 | 25.60 | 16.71 |
September | 0.290027E+10 | 17578.90 | 01-SEP-17:43 | 22.07 | 14.31 | 0.235117E+09 | 302.03 | 07-SEP-07:10 | 18.35 | 15.25 |
October | 29365469.78 | 904.43 | 20-OCT-15:40 | 21.97 | 12.93 | 0.201796E+09 | 304.10 | 11-OCT-15:09 | 18.72 | 12.82 |
November | 478321.28 | 233.68 | 04-NOV-17:00 | 7.80 | 3.62 | 0.189292E+09 | 290.37 | 03-NOV-15:20 | 15.73 | 9.50 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -0.7 | -1.2 | 0.194872E+09 | 236.59 | 02-DEC-11:09 | 4.08 | 2.07 |
Annual Sum or Average | 0.198045E+11 | 0.261808E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.179135E+09 | 236.59 | -5.7 | -6.5 | ||
Maximum of Months | 0.597688E+10 | 17578.90 | 29.43 | 19.69 | 0.268451E+09 | 304.10 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37492.66 | 62.49 | 12-JAN-13:00 | 2.20 | 0.51 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 53811025.79 | 2320.03 | 25-FEB-14:40 | 5.40 | 2.61 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.137987E+09 | 2402.94 | 27-MAR-14:00 | 6.10 | 2.66 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.601570E+09 | 4851.30 | 22-APR-13:40 | 2.03 | -0.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.555704E+09 | 16538.45 | 31-MAY-17:33 | 27.77 | 19.29 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.609185E+10 | 48896.97 | 30-JUN-17:08 | 28.30 | 20.21 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.834034E+10 | 50738.89 | 05-JUL-17:06 | 26.70 | 20.63 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.624674E+10 | 42590.76 | 02-AUG-17:08 | 28.72 | 22.55 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.302633E+10 | 36318.21 | 08-SEP-17:10 | 28.43 | 18.17 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.592530E+09 | 3433.21 | 23-OCT-10:10 | 3.95 | 1.13 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 84205932.03 | 2512.79 | 04-NOV-08:40 | 4.47 | 1.99 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 2619500.55 | 830.90 | 02-DEC-15:20 | 5.93 | 3.29 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.257337E+11 | 0.00 | ||||||||
Minimum of Months | 37492.66 | 62.49 | 2.03 | -0.2 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.834034E+10 | 50738.89 | 28.72 | 22.55 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -11.9 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.14 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -0.7 | -1.2 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154959E+11 | 28587.06 | 27-JAN-06:31 | -17.9 |
February | 0.114779E+11 | 29001.05 | 13-FEB-06:31 | -5.0 |
March | 0.876669E+10 | 29159.11 | 23-MAR-05:31 | 2.20 |
April | 0.436602E+10 | 29021.82 | 24-APR-05:01 | 11.78 |
May | 0.984379E+09 | 28850.61 | 04-MAY-05:01 | 11.70 |
June | 0.148664E+09 | 28504.10 | 06-JUN-05:01 | 11.70 |
July | 8624554.73 | 802.79 | 05-JUL-06:10 | 19.60 |
August | 10528486.30 | 667.88 | 22-AUG-06:10 | 17.57 |
September | 0.497815E+09 | 28339.91 | 26-SEP-05:01 | 10.50 |
October | 0.250552E+10 | 28877.11 | 10-OCT-05:01 | 11.27 |
November | 0.677484E+10 | 28823.32 | 09-NOV-06:01 | 14.82 |
December | 0.120745E+11 | 28844.40 | 14-DEC-06:31 | -1.3 |
Annual Sum or Average | 0.631113E+11 | |||
Minimum of Months | 8624554.73 | 667.88 | -17.9 | |
Maximum of Months | 0.154959E+11 | 29159.11 | 19.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106414E+12 | 107222.84 | 19-JAN-06:41 | -27.8 |
February | 0.759757E+11 | 106534.21 | 28-FEB-06:01 | -16.7 |
March | 0.500828E+11 | 105938.13 | 06-MAR-06:01 | -14.1 |
April | 0.209548E+11 | 100105.21 | 25-APR-03:02 | 1.78 |
May | 0.223614E+10 | 98773.50 | 02-MAY-03:12 | 2.80 |
June | 0.321404E+09 | 3269.57 | 14-JUN-07:00 | 17.80 |
July | 0.231405E+09 | 2894.91 | 20-JUL-07:00 | 20.00 |
August | 0.276307E+09 | 2932.68 | 25-AUG-07:00 | 13.90 |
September | 0.204506E+10 | 97105.13 | 30-SEP-01:53 | 0.00 |
October | 0.144038E+11 | 100099.79 | 24-OCT-05:22 | 2.10 |
November | 0.513788E+11 | 104702.42 | 24-NOV-06:01 | -13.4 |
December | 0.850109E+11 | 105197.91 | 13-DEC-06:01 | -10.4 |
Annual Sum or Average | 0.409331E+12 | |||
Minimum of Months | 0.231405E+09 | 2894.91 | -27.8 | |
Maximum of Months | 0.106414E+12 | 107222.84 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351052E+12 | 323958.45 | 18-JAN-15:10 | -17.3 |
February | 0.235348E+12 | 308465.47 | 01-FEB-20:53 | -28.9 |
March | 0.124983E+12 | 230155.61 | 06-MAR-08:70 | -11.8 |
April | 0.284283E+11 | 132189.41 | 02-APR-24:00 | -5.6 |
May | 0.462361E+09 | 22327.08 | 02-MAY-03:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.669208E+10 | 40105.67 | 24-OCT-06:00 | 2.20 |
November | 0.136985E+12 | 224208.25 | 25-NOV-16:10 | -18.1 |
December | 0.270652E+12 | 326878.73 | 09-DEC-08:35 | -22.8 |
Annual Sum or Average | 0.115460E+13 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.351052E+12 | 326878.73 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659055E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491384E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295292.84 | 0.406338E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28693094.29 | 0.235569E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29264089.02 | 0.125508E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128132E+09 | 0.740917E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96707209.55 | 0.468331E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137624E+09 | 0.667087E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80023876.75 | 0.120337E+10 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212132E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377795E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537827E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.500739E+09 | 0.335358E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468331E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137624E+09 | 0.659055E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620255E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459974E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9740060.56 | 0.359952E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262837E+09 | 0.192055E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69171754.45 | 0.926043E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685831E+09 | 0.719950E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172103E+09 | 0.623637E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265365E+09 | 0.831964E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194016E+09 | 0.101155E+11 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1481046.72 | 0.161511E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360362E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514965E+11 |
Annual Sum or Average | 0.136656E+12 | 0.166054E+10 | 0.308039E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623637E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685831E+09 | 0.620255E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179905E+12 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125073E+12 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102258E+10 | 0.851534E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411640E+10 | 0.419999E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167535E+10 | 0.229301E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894982E+09 | 0.260048E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 852751.57 | 0.272640E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16514123.49 | 0.327583E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226568E+09 | 0.339945E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107165E+10 | 0.300839E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140395E+09 | 0.875816E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140949E+12 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.916529E+10 | 0.833698E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229301E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411640E+10 | 0.179905E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 16489.21 | 18-JAN-18:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16918.01 | 02-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 19-MAR-14:00 | 12298.74 | 06-MAR-08:00 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 977.49 | 18-APR-12:00 | 8817.90 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.54 | 31-MAY-17:00 | 5526.11 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1911.55 | 26-JUN-16:10 | 3949.14 | 02-JUN-06:05 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.04 | 25-JUL-16:10 | 2722.25 | 24-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2283.19 | 04-AUG-16:10 | 3566.93 | 07-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1860.74 | 06-SEP-16:10 | 5635.87 | 29-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6409.89 | 24-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10888.54 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15802.97 | 08-DEC-17:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.25 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2283.19 | 16918.01 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 94431.60 | 18-JAN-16:02 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 65959.93 | 04-FEB-17:55 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.93 | 19-MAR-16:00 | 67037.91 | 06-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7304.15 | 15-APR-15:10 | 41877.66 | 25-APR-06:10 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895.37 | 31-MAY-15:10 | 17724.07 | 02-MAY-03:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.37 | 11-JUN-15:10 | 14519.72 | 02-JUN-08:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4874.62 | 25-JUL-16:00 | 10617.12 | 10-JUL-15:10 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6091.56 | 04-AUG-16:15 | 13252.98 | 30-AUG-15:05 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5329.15 | 06-SEP-15:40 | 14713.83 | 18-SEP-16:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.57 | 20-OCT-15:10 | 28672.86 | 24-OCT-06:08 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 60878.98 | 25-NOV-16:10 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 94334.65 | 09-DEC-08:55 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10617.12 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.37 | 94431.60 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 240597.48 | 18-JAN-16:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 173499.04 | 28-FEB-10:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21105.69 | 25-MAR-15:00 | 158163.07 | 06-MAR-08:70 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47707.90 | 15-APR-15:00 | 75165.34 | 02-APR-24:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28583.38 | 04-MAY-14:00 | 52198.52 | 13-MAY-12:55 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21533.41 | 11-JUN-14:53 | 46772.76 | 02-JUN-08:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.61 | 26-JUL-18:00 | 43576.48 | 10-JUL-14:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1773.48 | 21-AUG-13:00 | 43097.59 | 30-AUG-14:55 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10229.47 | 06-SEP-14:00 | 46694.69 | 18-SEP-16:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20968.95 | 20-OCT-15:00 | 43698.02 | 24-OCT-07:10 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11926.53 | 20-NOV-10:00 | 170474.69 | 25-NOV-11:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 282786.21 | 09-DEC-08:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43097.59 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 47707.90 | 282786.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.14 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1764.67 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1983.79 |
April | 6045.06 | 15-APR-17:20 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 493.65 | 0.00 |
May | 12637.78 | 31-MAY-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 323.12 | 0.00 |
June | 16666.17 | 19-JUN-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.24 |
July | 17396.38 | 24-JUL-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.66 |
August | 17292.43 | 16-AUG-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.38 |
September | 17578.90 | 01-SEP-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.01 |
October | 904.43 | 20-OCT-15:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.41 |
November | 233.68 | 04-NOV-17:00 | 421.92 | 3110.70 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.17 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17578.90 | 659.25 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 493.65 | 1983.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62.49 | 12-JAN-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3533.45 |
February | 2320.03 | 25-FEB-14:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4275.78 |
March | 2402.94 | 27-MAR-14:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.56 |
April | 4851.30 | 22-APR-13:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.65 |
May | 16538.45 | 31-MAY-17:33 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.13 | 0.00 |
June | 48896.97 | 30-JUN-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998.56 | 0.00 |
July | 50738.89 | 05-JUL-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 |
August | 42590.76 | 02-AUG-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1904.52 | 0.00 |
September | 36318.21 | 08-SEP-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.92 | 0.00 |
October | 3433.21 | 23-OCT-10:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.78 |
November | 2512.79 | 04-NOV-08:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2700.53 |
December | 830.90 | 02-DEC-15:20 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62.49 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50738.89 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1904.52 | 4591.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 19318.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31063.00 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76233.15 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78901.32 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14328.54 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8434.64 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12433.76 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11002.47 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12213.88 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15016.71 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12514.37 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9483.48 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31919.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8434.64 | |
Maximum of Months | 0.00 | 0.00 | 19318.12 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78901.32 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.758728E+11 | 56236.07 | 21-JAN-16:00 | 0.622449E+12 | 564240.82 | 18-JAN-17:00 |
February | 0.678745E+11 | 53244.92 | 18-FEB-15:39 | 0.426410E+12 | 526336.33 | 01-FEB-20:00 |
March | 0.752929E+11 | 53238.56 | 01-MAR-15:30 | 0.245339E+12 | 434691.60 | 06-MAR-08:09 |
April | 0.681777E+11 | 57571.01 | 18-APR-14:09 | 0.734123E+11 | 259274.03 | 02-APR-23:49 |
May | 0.687561E+11 | 60152.76 | 31-MAY-14:00 | 0.402763E+10 | 81928.73 | 02-MAY-05:19 |
June | 0.718160E+11 | 68282.72 | 27-JUN-14:39 | 0.182768E+09 | 11264.24 | 05-JUN-05:10 |
July | 0.727879E+11 | 69227.58 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.763088E+11 | 73059.43 | 04-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.699121E+11 | 65093.71 | 08-SEP-13:00 | 0.328264E+10 | 50115.90 | 30-SEP-05:19 |
October | 0.703285E+11 | 52386.04 | 17-OCT-08:09 | 0.325596E+11 | 120852.24 | 24-OCT-05:30 |
November | 0.708567E+11 | 56225.96 | 28-NOV-16:40 | 0.257764E+12 | 411786.03 | 25-NOV-16:10 |
December | 0.756191E+11 | 56232.72 | 30-DEC-16:49 | 0.485395E+12 | 565860.77 | 09-DEC-06:10 |
Annual Sum or Average | 0.863603E+12 | 0.215082E+13 | ||||
Minimum of Months | 0.678745E+11 | 52386.04 | 0.00 | 0.00 | ||
Maximum of Months | 0.763088E+11 | 73059.43 | 0.622449E+12 | 565860.77 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.130304E+11 | 0.115358E+11 | 0.00 | 0.877496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242824E+10 | 0.00 |
February | 0.366966E+11 | 0.108571E+11 | 0.105871E+11 | 0.00 | 0.750760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222608E+10 | 0.00 |
March | 0.423649E+11 | 0.107581E+11 | 0.123357E+11 | 0.00 | 0.732530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250886E+10 | 0.00 |
April | 0.397216E+11 | 0.911754E+10 | 0.114862E+11 | 0.00 | 0.535884E+10 | 0.00 | 0.00 | 0.147777E+09 | 0.00 | 0.00 | 0.00 | 0.234577E+10 | 0.00 |
May | 0.412341E+11 | 0.829253E+10 | 0.119357E+11 | 0.00 | 0.442871E+10 | 0.00 | 0.00 | 0.501778E+09 | 0.00 | 0.00 | 0.00 | 0.236324E+10 | 0.00 |
June | 0.408524E+11 | 0.745809E+10 | 0.118862E+11 | 0.00 | 0.484133E+10 | 0.00 | 0.00 | 0.453441E+10 | 0.00 | 0.00 | 0.00 | 0.224366E+10 | 0.00 |
July | 0.401034E+11 | 0.794838E+10 | 0.115358E+11 | 0.00 | 0.463272E+10 | 0.00 | 0.00 | 0.635723E+10 | 0.00 | 0.00 | 0.00 | 0.221041E+10 | 0.00 |
August | 0.423649E+11 | 0.892425E+10 | 0.123357E+11 | 0.00 | 0.486041E+10 | 0.00 | 0.00 | 0.557628E+10 | 0.00 | 0.00 | 0.00 | 0.224726E+10 | 0.00 |
September | 0.397216E+11 | 0.983412E+10 | 0.114862E+11 | 0.00 | 0.435270E+10 | 0.00 | 0.00 | 0.235900E+10 | 0.00 | 0.00 | 0.00 | 0.215848E+10 | 0.00 |
October | 0.401034E+11 | 0.114983E+11 | 0.115358E+11 | 0.00 | 0.492268E+10 | 0.00 | 0.00 | 7781879.91 | 0.00 | 0.00 | 0.00 | 0.226061E+10 | 0.00 |
November | 0.385909E+11 | 0.122809E+11 | 0.110862E+11 | 0.00 | 0.666067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223802E+10 | 0.00 |
December | 0.401034E+11 | 0.133463E+11 | 0.115358E+11 | 0.00 | 0.825327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238034E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123346E+12 | 0.139282E+12 | 0.719192E+11 | 0.00 | 0.194843E+11 | 0.276110E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.745809E+10 | 0.105871E+11 | 0.00 | 0.435270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215848E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.133463E+11 | 0.123357E+11 | 0.00 | 0.877496E+10 | 0.00 | 0.00 | 0.635723E+10 | 0.00 | 0.00 | 0.00 | 0.250886E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.622449E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.426410E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.245339E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.734123E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.402763E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.182768E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.328264E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.325596E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.257764E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.485395E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215082E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.622449E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4970.27 | 19-JAN-06:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4970.27 | 01-FEB-12:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4970.27 | 01-MAR-10:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4970.27 | 27-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4970.27 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6520.46 | 26-JUN-11:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6520.46 | 03-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6520.46 | 01-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6520.46 | 07-SEP-15:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4970.27 | 17-OCT-07:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4970.27 | 29-NOV-15:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4970.27 | 01-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4970.27 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6520.46 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2967.62 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2990.94 | 18-FEB-12:30 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2983.90 | 02-MAR-12:20 | 0.00 |
April | 5653.57 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 2890.08 | 01-APR-11:39 | 0.00 |
May | 8756.16 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2697.58 | 01-MAY-11:00 | 0.00 |
June | 15273.08 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2411.59 | 01-JUN-11:00 | 0.00 |
July | 15751.25 | 26-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2119.87 | 03-JUL-11:09 | 0.00 |
August | 20634.51 | 04-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1899.53 | 28-AUG-11:00 | 0.00 |
September | 11991.32 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 2062.08 | 30-SEP-11:00 | 0.00 |
October | 534.59 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2306.16 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2605.00 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2822.77 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1899.53 | 0.00 | ||
Maximum of Months | 20634.51 | 0.00 | 0.00 | 0.00 | 2990.94 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56236.07 | 21-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53244.92 | 18-FEB-15:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53238.56 | 01-MAR-15:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57571.01 | 18-APR-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4215.17 | 0.00 | 0.00 | 5314.30 | 0.00 |
May | 60152.76 | 31-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4215.17 | 0.00 | 0.00 | 8390.71 | 0.00 |
June | 68282.72 | 27-JUN-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6520.46 | 0.00 | 0.00 | 14236.36 | 0.00 |
July | 69227.58 | 03-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6520.46 | 0.00 | 0.00 | 15185.49 | 0.00 |
August | 73059.43 | 04-AUG-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6520.46 | 0.00 | 0.00 | 19031.10 | 0.00 |
September | 65093.71 | 08-SEP-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6520.46 | 0.00 | 0.00 | 11102.15 | 0.00 |
October | 52386.04 | 17-OCT-08:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56225.96 | 28-NOV-16:40 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56232.72 | 30-DEC-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4970.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52386.04 | 31660.41 | 10112.62 | 0.00 | 0.00 | 4215.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73059.43 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6520.46 | 0.00 | 0.00 | 19031.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 564240.82 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 526336.33 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 434691.60 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 259274.03 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 81928.73 | 02-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 11264.24 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 50115.90 | 30-SEP-05:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 120852.24 | 24-OCT-05:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 411786.03 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 565860.77 | 09-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 565860.77 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.83 | 15.30 | 14.67 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54.83 | 15.76 | 13.83 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28.17 | 16.47 | 11.17 | 18.96 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11.50 | 17.76 | 7.00 | 19.62 | 0.17 | 24.48 | 0.00 | 0.00 |
May | 2.33 | 20.03 | 2.33 | 20.03 | 0.67 | 24.54 | 0.00 | 0.00 |
June | 0.33 | 20.39 | 0.33 | 20.39 | 12.17 | 24.60 | 0.33 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 24.63 | 0.33 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 24.58 | 0.50 | 24.49 |
September | 1.67 | 20.14 | 1.67 | 20.14 | 7.33 | 24.56 | 0.33 | 24.49 |
October | 7.17 | 19.96 | 7.17 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28.50 | 16.08 | 8.33 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46.83 | 15.64 | 11.00 | 18.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.17 | 15.95 | 77.50 | 19.13 | 56.83 | 24.60 | 1.50 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.83 | 20.39 | 14.67 | 20.39 | 19.00 | 24.63 | 0.50 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 175.33 | 12.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 131.50 | 13.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100.33 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62.00 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.33 | 14.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.56 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.46 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.00 | 0.00 |
September | 6.33 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66.33 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98.33 | 13.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 152.17 | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 798.67 | 13.34 | 0.00 | 14.00 | 27.50 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.33 | 14.61 | 0.00 | 0.00 | 7.17 | 27.56 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 9.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16.67 | 8.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.00 | 8.39 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 9.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.97 | 300.00 | 20.97 | 300.00 | 20.97 |
February | 276.00 | 20.99 | 276.00 | 20.99 | 276.00 | 20.99 |
March | 324.00 | 21.04 | 322.67 | 21.03 | 322.67 | 21.03 |
April | 295.17 | 21.42 | 238.83 | 21.08 | 238.67 | 21.07 |
May | 299.83 | 22.63 | 82.17 | 21.28 | 77.50 | 21.13 |
June | 126.00 | 23.01 | 137.83 | 23.65 | 15.00 | 21.54 |
July | 21.67 | 23.62 | 214.33 | 23.91 | 2.00 | 23.90 |
August | 46.83 | 23.60 | 218.67 | 23.90 | 7.67 | 23.90 |
September | 178.17 | 22.51 | 128.67 | 22.55 | 64.17 | 21.18 |
October | 300.00 | 21.39 | 249.50 | 21.11 | 249.50 | 21.11 |
November | 288.00 | 21.14 | 262.67 | 21.05 | 262.67 | 21.05 |
December | 300.00 | 21.01 | 300.00 | 21.01 | 300.00 | 21.01 |
Annual Sum or Average | 2755.67 | 21.54 | 2731.33 | 21.70 | 2115.83 | 21.06 |
Minimum of Months | 21.67 | 20.97 | 82.17 | 20.97 | 2.00 | 20.97 |
Maximum of Months | 324.00 | 23.62 | 322.67 | 23.91 | 322.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.389635E+09 | 0.108511E+09 | 27.17 | 0.305805E+09 | 83830312.22 | 0.00 | 0.48 | 15-APR-17:20 | 0.00 | 01-APR-00:10 | 8261.06 | 18-APR-15:10 | 7220.72 | 15-APR-17:20 | 2185.31 | 18-APR-12:00 | 2377.94 | 15-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.114928E+10 | 0.315830E+09 | 108.67 | 0.918657E+09 | 0.230619E+09 | 0.00 | 0.89 | 31-MAY-17:10 | 0.00 | 01-MAY-00:05 | 17360.01 | 31-MAY-17:10 | 14887.40 | 31-MAY-17:10 | 2472.61 | 31-MAY-17:10 | 4597.90 | 31-MAY-17:10 | 0.00 | 01-MAY-00:05 |
June | 0.646882E+10 | 0.175474E+10 | 311.80 | 0.518660E+10 | 0.128222E+10 | 0.00 | 1.00 | 12-JUN-00:02 | 0.00 | 01-JUN-00:10 | 24345.01 | 26-JUN-00:01 | 18242.99 | 19-JUN-17:43 | 10311.46 | 12-JUN-00:02 | 5532.74 | 26-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.937401E+10 | 0.250573E+10 | 400.14 | 0.728722E+10 | 0.208679E+10 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:15 | 24130.42 | 05-JUL-00:01 | 19080.30 | 18-JUL-17:08 | 9700.56 | 17-JUL-00:03 | 5582.07 | 26-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.930632E+10 | 0.249992E+10 | 398.25 | 0.726297E+10 | 0.204335E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:05 | 23247.47 | 28-AUG-00:02 | 19081.51 | 16-AUG-17:43 | 8418.25 | 14-AUG-00:02 | 5582.46 | 03-AUG-17:08 | 0.00 | 01-AUG-00:05 |
September | 0.400105E+10 | 0.110058E+10 | 218.73 | 0.356482E+10 | 0.436234E+09 | 0.00 | 1.00 | 06-SEP-17:08 | 0.00 | 01-SEP-00:10 | 21997.08 | 11-SEP-00:01 | 19371.03 | 01-SEP-17:43 | 4522.84 | 11-SEP-00:03 | 5256.07 | 06-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 28261109.95 | 7781879.91 | 7.17 | 27012657.17 | 1248452.78 | 0.00 | 0.12 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1950.84 | 20-OCT-15:00 | 1950.84 | 20-OCT-15:00 | 131.77 | 21-OCT-15:00 | 534.59 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.307174E+11 | 0.829310E+10 | 1471.91 | 0.245531E+11 | 0.616428E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.937401E+10 | 0.250573E+10 | 400.14 | 0.728722E+10 | 0.208679E+10 | 0.00 | 1.00 | 0.00 | 24345.01 | 19371.03 | 10311.46 | 5582.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.130288E+09 | 39265793.51 | 6.00 | 84767193.91 | 45520344.24 | 0.00 | 0.18 | 18-APR-15:00 | 0.00 | 01-APR-00:10 | 11342.03 | 18-APR-15:10 | 7461.18 | 18-APR-15:10 | 3880.85 | 18-APR-15:10 | 3401.44 | 18-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.612207E+09 | 0.185948E+09 | 13.56 | 0.459887E+09 | 0.152320E+09 | 0.00 | 0.40 | 31-MAY-17:33 | 0.00 | 01-MAY-00:05 | 22505.14 | 31-MAY-17:33 | 18236.93 | 31-MAY-17:33 | 4268.22 | 31-MAY-17:33 | 7077.26 | 31-MAY-17:33 | 0.00 | 01-MAY-00:05 |
June | 0.941887E+10 | 0.277967E+10 | 136.21 | 0.674127E+10 | 0.267760E+10 | 0.00 | 1.00 | 11-JUN-12:23 | 0.00 | 01-JUN-00:10 | 73777.91 | 18-JUN-14:03 | 53761.98 | 30-JUN-17:08 | 28064.47 | 11-JUN-16:23 | 20563.83 | 11-JUN-15:05 | 0.00 | 01-JUN-00:10 |
July | 0.134496E+11 | 0.385151E+10 | 194.08 | 0.940996E+10 | 0.403964E+10 | 0.00 | 1.00 | 02-JUL-11:03 | 0.00 | 01-JUL-00:10 | 77946.82 | 26-JUL-17:10 | 55274.26 | 05-JUL-17:06 | 35124.93 | 26-JUL-17:10 | 20066.51 | 26-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.106586E+11 | 0.307635E+10 | 158.96 | 0.730084E+10 | 0.335777E+10 | 0.00 | 1.00 | 03-AUG-17:08 | 0.00 | 01-AUG-00:05 | 76387.61 | 04-AUG-17:08 | 47069.67 | 02-AUG-17:08 | 30969.52 | 04-AUG-17:08 | 20029.77 | 03-AUG-17:08 | 0.00 | 01-AUG-00:05 |
September | 0.416043E+10 | 0.125841E+10 | 77.36 | 0.345658E+10 | 0.703847E+09 | 0.00 | 0.75 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 | 45248.63 | 08-SEP-17:10 | 39861.37 | 08-SEP-17:10 | 6940.05 | 11-SEP-10:40 | 13266.55 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.384300E+11 | 0.111912E+11 | 586.17 | 0.274533E+11 | 0.109767E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134496E+11 | 0.385151E+10 | 194.08 | 0.940996E+10 | 0.403964E+10 | 0.00 | 1.00 | 0.00 | 77946.82 | 55274.26 | 35124.93 | 20563.83 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.35 | 307.59 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.58 | 239.50 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 75.49 | 143.62 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 164.84 | 95.10 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 182.44 | 54.21 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 232.78 | 46.79 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 255.17 | 45.00 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 223.78 | 52.86 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 164.40 | 80.72 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 89.26 | 104.03 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.77 | 177.52 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 18.06 | 269.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 125.87 | 134.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 18.06 | 45.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 255.17 | 307.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.35 | 307.59 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.58 | 239.50 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 75.49 | 143.62 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 164.84 | 95.10 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 182.44 | 54.21 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 232.78 | 46.79 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 255.17 | 45.00 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 223.78 | 52.86 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 164.40 | 80.72 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 89.26 | 104.03 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.77 | 177.52 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 18.06 | 269.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 125.87 | 134.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 18.06 | 45.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 255.17 | 307.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 195.05 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.35 | 154.20 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.60 | 91.08 | 0.00 | 0.00 | 744.00 |
April | 42.51 | 0.29 | 42.22 | 19.48 | 58.12 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 40.67 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 64.59 | 5.83 | 58.76 | 55.43 | 25.58 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 52.40 | 24.82 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 46.76 | 30.24 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 27.50 | 48.21 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 10.00 | 63.68 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 2.07 | 110.23 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 167.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.99 | 82.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 24.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.59 | 5.83 | 58.76 | 55.43 | 195.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 195.05 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.35 | 154.20 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.60 | 91.08 | 0.00 | 0.00 | 744.00 |
April | 42.50 | 0.29 | 42.22 | 19.48 | 58.12 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 40.66 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 64.58 | 5.83 | 58.76 | 55.43 | 25.58 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 52.40 | 24.82 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 46.76 | 30.24 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 27.50 | 48.20 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 10.00 | 63.68 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 2.07 | 110.23 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 167.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.99 | 82.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 24.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.58 | 5.83 | 58.76 | 55.43 | 195.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.25 | 211.02 | 2.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.45 | 157.15 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.30 | 83.59 | 15.67 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 123.13 | 54.06 | 40.33 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 158.98 | 38.95 | 24.17 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 176.75 | 46.61 | 26.17 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 174.05 | 53.93 | 25.67 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 147.95 | 53.29 | 28.33 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 108.62 | 71.30 | 9.67 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.49 | 58.95 | 14.83 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.75 | 104.44 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.71 | 171.21 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 92.71 | 91.76 | 187.67 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.25 | 38.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 176.75 | 211.02 | 40.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51813796.55 | 0.823845E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119935E+09 | 0.579390E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.202186E+09 | 0.384684E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.427265E+09 | 0.246487E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.488650E+09 | 0.145198E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.603355E+09 | 0.121269E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683443E+09 | 0.120520E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.599365E+09 | 0.141582E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.426126E+09 | 0.209213E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.239082E+09 | 0.278645E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 79744093.08 | 0.460125E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 48366802.46 | 0.721387E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.396933E+10 | 0.423235E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 48366802.46 | 0.120520E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683443E+09 | 0.823845E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51813796.55 | 0.823845E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119935E+09 | 0.579390E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.202186E+09 | 0.384684E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.427265E+09 | 0.246487E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.488650E+09 | 0.145198E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.603355E+09 | 0.121269E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683443E+09 | 0.120520E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.599365E+09 | 0.141582E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.426126E+09 | 0.209213E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.239082E+09 | 0.278645E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 79744093.08 | 0.460125E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 48366802.46 | 0.721387E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.396933E+10 | 0.423235E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 48366802.46 | 0.120520E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683443E+09 | 0.823845E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51785475.02 | 0.00 | 51785475.02 | 0.00 | 0.522430E+09 |
February | 59300287.05 | 0.00 | 59300287.05 | 857292.24 | 0.373040E+09 |
March | 98412437.69 | 2555.31 | 98409882.39 | 20367536.99 | 0.243954E+09 |
April | 0.110175E+09 | 742859.63 | 0.109432E+09 | 50497524.70 | 0.150656E+09 |
May | 0.148348E+09 | 5729827.66 | 0.142618E+09 | 0.108921E+09 | 82731718.29 |
June | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.143685E+09 | 66311691.92 |
July | 0.162282E+09 | 10865282.36 | 0.151417E+09 | 0.140349E+09 | 66474744.48 |
August | 0.136413E+09 | 2828771.71 | 0.133584E+09 | 0.125239E+09 | 80999660.48 |
September | 0.100963E+09 | 65724.61 | 0.100898E+09 | 71291071.94 | 0.124947E+09 |
October | 77497403.21 | 0.00 | 77497403.21 | 26789905.49 | 0.170557E+09 |
November | 52461463.12 | 0.00 | 52461463.12 | 5376259.24 | 0.285728E+09 |
December | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 0.448149E+09 |
Annual Sum or Average | 0.120021E+10 | 35337833.27 | 0.116487E+10 | 0.693374E+09 | 0.261598E+10 |
Minimum of Months | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 66311691.92 |
Maximum of Months | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.143685E+09 | 0.522430E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51783807.94 | 0.00 | 51783807.94 | 0.00 | 0.522431E+09 |
February | 59298441.20 | 0.00 | 59298441.20 | 857136.77 | 0.373041E+09 |
March | 98409312.96 | 2555.19 | 98406757.77 | 20365959.71 | 0.243955E+09 |
April | 0.110172E+09 | 742824.81 | 0.109429E+09 | 50495534.18 | 0.150656E+09 |
May | 0.148344E+09 | 5729559.10 | 0.142614E+09 | 0.108916E+09 | 82731497.49 |
June | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.143680E+09 | 66311328.91 |
July | 0.162277E+09 | 10864773.09 | 0.151412E+09 | 0.140345E+09 | 66474125.17 |
August | 0.136409E+09 | 2828639.12 | 0.133580E+09 | 0.125235E+09 | 80999195.70 |
September | 0.100960E+09 | 65721.53 | 0.100895E+09 | 71288718.55 | 0.124947E+09 |
October | 77494965.54 | 0.00 | 77494965.54 | 26788198.17 | 0.170557E+09 |
November | 52459712.13 | 0.00 | 52459712.13 | 5375800.85 | 0.285729E+09 |
December | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 0.448149E+09 |
Annual Sum or Average | 0.120017E+10 | 35336176.94 | 0.116484E+10 | 0.693348E+09 | 0.261598E+10 |
Minimum of Months | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 66311328.91 |
Maximum of Months | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.143680E+09 | 0.522431E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22106028.07 | 0.565187E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68816502.35 | 0.380187E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.209708E+09 | 0.223890E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.319156E+09 | 0.140116E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.425811E+09 | 0.104315E+09 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.458153E+09 | 0.120826E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.466183E+09 | 0.144455E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.396259E+09 | 0.142734E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.281553E+09 | 0.184804E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.183434E+09 | 0.157900E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69328736.90 | 0.270705E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23349037.66 | 0.458570E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.292386E+10 | 0.289369E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22106028.07 | 0.104315E+09 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.466183E+09 | 0.565187E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.52 | 989.11 | 179.97 | 57.33 | 122.64 | 0.00 | 0.00 |
February | 78.89 | 766.43 | 254.55 | 100.81 | 153.74 | 0.00 | 0.00 |
March | 155.36 | 458.59 | 320.27 | 91.94 | 228.33 | 0.00 | 0.00 |
April | 364.20 | 301.99 | 444.78 | 178.37 | 266.41 | 0.00 | 0.00 |
May | 445.39 | 169.38 | 471.46 | 148.36 | 323.10 | 0.00 | 0.00 |
June | 574.53 | 142.85 | 551.71 | 194.39 | 357.33 | 0.00 | 0.00 |
July | 613.84 | 138.34 | 575.83 | 224.14 | 351.69 | 0.00 | 0.00 |
August | 540.40 | 165.53 | 498.16 | 183.35 | 314.81 | 0.00 | 0.00 |
September | 381.60 | 255.63 | 399.53 | 152.54 | 246.99 | 0.00 | 0.00 |
October | 193.27 | 330.17 | 282.96 | 100.34 | 182.62 | 0.00 | 0.00 |
November | 57.59 | 567.41 | 175.13 | 50.02 | 125.12 | 0.00 | 0.00 |
December | 23.90 | 861.09 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Annual Sum or Average | 288.72 | 427.33 | 357.50 | 127.63 | 229.87 | 0.00 | 0.00 |
Minimum of Months | 22.52 | 138.34 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Maximum of Months | 613.84 | 989.11 | 575.83 | 224.14 | 357.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 82.53 | 2110.17 | 339.02 | 147.87 | 191.15 | 0.00 | 0.00 |
February | 284.46 | 1571.54 | 464.36 | 232.38 | 231.98 | 0.00 | 0.00 |
March | 782.96 | 835.91 | 728.98 | 348.73 | 380.25 | 0.00 | 0.00 |
April | 1231.31 | 540.57 | 989.62 | 594.64 | 394.98 | 0.00 | 0.00 |
May | 1589.79 | 389.47 | 1188.87 | 667.90 | 520.96 | 0.00 | 0.00 |
June | 1767.52 | 466.15 | 1351.79 | 790.44 | 561.36 | 0.00 | 0.00 |
July | 1740.53 | 539.33 | 1362.23 | 837.91 | 524.32 | 0.00 | 0.00 |
August | 1479.46 | 532.91 | 1134.46 | 645.90 | 488.56 | 0.00 | 0.00 |
September | 1086.23 | 712.98 | 881.68 | 511.75 | 369.92 | 0.00 | 0.00 |
October | 684.86 | 589.53 | 560.36 | 277.85 | 282.51 | 0.00 | 0.00 |
November | 267.47 | 1044.39 | 334.43 | 123.92 | 210.51 | 0.00 | 0.00 |
December | 87.13 | 1712.10 | 230.15 | 113.23 | 116.92 | 0.00 | 0.00 |
Annual Sum or Average | 927.14 | 917.58 | 798.89 | 442.06 | 356.83 | 0.00 | 0.00 |
Minimum of Months | 82.53 | 389.47 | 230.15 | 113.23 | 116.92 | 0.00 | 0.00 |
Maximum of Months | 1767.52 | 2110.17 | 1362.23 | 837.91 | 561.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60309272.51 | 0.264923E+10 | 0.482020E+09 | 0.153541E+09 | 0.328480E+09 | 0.00 | 0.00 |
February | 0.190859E+09 | 0.185414E+10 | 0.615804E+09 | 0.243884E+09 | 0.371920E+09 | 0.00 | 0.00 |
March | 0.416127E+09 | 0.122830E+10 | 0.857814E+09 | 0.246255E+09 | 0.611559E+09 | 0.00 | 0.00 |
April | 0.943998E+09 | 0.782762E+09 | 0.115287E+10 | 0.462335E+09 | 0.690537E+09 | 0.00 | 0.00 |
May | 0.119294E+10 | 0.453666E+09 | 0.126276E+10 | 0.397373E+09 | 0.865383E+09 | 0.00 | 0.00 |
June | 0.148918E+10 | 0.370261E+09 | 0.143004E+10 | 0.503851E+09 | 0.926192E+09 | 0.00 | 0.00 |
July | 0.164411E+10 | 0.370524E+09 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
August | 0.144740E+10 | 0.443358E+09 | 0.133428E+10 | 0.491098E+09 | 0.843181E+09 | 0.00 | 0.00 |
September | 0.989103E+09 | 0.662593E+09 | 0.103558E+10 | 0.395393E+09 | 0.640190E+09 | 0.00 | 0.00 |
October | 0.517664E+09 | 0.884328E+09 | 0.757881E+09 | 0.268739E+09 | 0.489143E+09 | 0.00 | 0.00 |
November | 0.149273E+09 | 0.147074E+10 | 0.453948E+09 | 0.129647E+09 | 0.324301E+09 | 0.00 | 0.00 |
December | 64015861.82 | 0.230635E+10 | 0.348904E+09 | 0.132507E+09 | 0.216397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.910498E+10 | 0.134763E+11 | 0.112742E+11 | 0.402496E+10 | 0.724924E+10 | 0.00 | 0.00 |
Minimum of Months | 60309272.51 | 0.370261E+09 | 0.348904E+09 | 0.129647E+09 | 0.216397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164411E+10 | 0.264923E+10 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.221060E+09 | 0.565187E+10 | 0.908027E+09 | 0.396054E+09 | 0.511973E+09 | 0.00 | 0.00 |
February | 0.688165E+09 | 0.380186E+10 | 0.112338E+10 | 0.562168E+09 | 0.561213E+09 | 0.00 | 0.00 |
March | 0.209707E+10 | 0.223890E+10 | 0.195250E+10 | 0.934044E+09 | 0.101845E+10 | 0.00 | 0.00 |
April | 0.319156E+10 | 0.140116E+10 | 0.256510E+10 | 0.154131E+10 | 0.102379E+10 | 0.00 | 0.00 |
May | 0.425811E+10 | 0.104315E+10 | 0.318426E+10 | 0.178891E+10 | 0.139535E+10 | 0.00 | 0.00 |
June | 0.458140E+10 | 0.120826E+10 | 0.350385E+10 | 0.204882E+10 | 0.145503E+10 | 0.00 | 0.00 |
July | 0.466183E+10 | 0.144455E+10 | 0.364860E+10 | 0.224425E+10 | 0.140435E+10 | 0.00 | 0.00 |
August | 0.396258E+10 | 0.142734E+10 | 0.303854E+10 | 0.172997E+10 | 0.130857E+10 | 0.00 | 0.00 |
September | 0.281551E+10 | 0.184804E+10 | 0.228531E+10 | 0.132647E+10 | 0.958841E+09 | 0.00 | 0.00 |
October | 0.183434E+10 | 0.157900E+10 | 0.150086E+10 | 0.744182E+09 | 0.756674E+09 | 0.00 | 0.00 |
November | 0.693287E+09 | 0.270705E+10 | 0.866853E+09 | 0.321211E+09 | 0.545643E+09 | 0.00 | 0.00 |
December | 0.233364E+09 | 0.458570E+10 | 0.616440E+09 | 0.303282E+09 | 0.313158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292383E+11 | 0.289369E+11 | 0.251937E+11 | 0.139407E+11 | 0.112530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.221060E+09 | 0.104315E+10 | 0.616440E+09 | 0.303282E+09 | 0.313158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.466183E+10 | 0.565187E+10 | 0.364860E+10 | 0.224425E+10 | 0.145503E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.113470E+10 | -977145413.5 | 0.00 | 0.00 | 744.00 | 0.00 | -157555736.1 | 58.99 | 0.00 | 0.00 |
February | 0.105763E+10 | -915647642.3 | 0.00 | 0.00 | 672.00 | 0.00 | -141986245.1 | 58.99 | 0.00 | 0.00 |
March | 0.121534E+10 | -.105956E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155782580.2 | 59.00 | 0.00 | 0.00 |
April | 0.109352E+10 | -946407497.1 | 0.00 | 0.00 | 720.00 | 0.00 | -147110203.9 | 58.99 | 0.00 | 0.00 |
May | 0.106932E+10 | -926229541.5 | 0.00 | 0.00 | 744.00 | 0.00 | -143091425.3 | 58.99 | 0.00 | 0.00 |
June | 0.991478E+09 | -860525691.1 | 0.00 | 0.00 | 720.00 | 0.00 | -130951927.3 | 58.99 | 0.00 | 0.00 |
July | 0.916668E+09 | -784706574.6 | 0.00 | 0.00 | 744.00 | 0.00 | -131961263.7 | 58.99 | 0.00 | 0.00 |
August | 0.953495E+09 | -820477247.0 | 0.00 | 0.00 | 744.00 | 0.00 | -133017530.8 | 59.00 | 0.00 | 0.00 |
September | 0.906618E+09 | -773130490.6 | 0.00 | 0.00 | 720.00 | 0.00 | -133487769.0 | 58.99 | 0.00 | 0.00 |
October | 0.966606E+09 | -814216017.2 | 0.00 | 0.00 | 744.00 | 0.00 | -152390299.2 | 58.99 | 0.00 | 0.00 |
November | 0.986507E+09 | -835944697.4 | 0.00 | 0.00 | 720.00 | 0.00 | -150562519.7 | 58.99 | 0.00 | 0.00 |
December | 0.108651E+10 | -929155543.1 | 0.00 | 0.00 | 744.00 | 0.00 | -157357210.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.123784E+11 | -.106431E+11 | 8760.00 | -.173525E+10 | 58.99 | |||||
Minimum of Months | 0.906618E+09 | -.105956E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157555736.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121534E+10 | -773130490.6 | 0.00 | 0.00 | 744.00 | 0.00 | -130951927.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188756E+11 | 29292.92 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138256E+11 | 29292.92 | 01-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101085E+11 | 29292.92 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.490823E+10 | 29292.92 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888746E+09 | 29292.92 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124108E+09 | 29292.92 | 03-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.535049E+09 | 29292.92 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274501E+10 | 29292.92 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793750E+10 | 29292.92 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145180E+11 | 29292.92 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744664E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188756E+11 | 29292.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114475E+12 | 97282.29 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.813435E+11 | 97282.29 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526639E+11 | 97282.29 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214208E+11 | 97282.29 | 01-APR-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148585E+10 | 97282.29 | 01-MAY-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168873E+10 | 97282.29 | 29-SEP-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139751E+11 | 97282.29 | 08-OCT-00:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.535988E+11 | 97282.29 | 09-NOV-20:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.906829E+11 | 97282.29 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431335E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114475E+12 | 97282.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349030E+12 | 322144.08 | 18-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233564E+12 | 307710.39 | 01-FEB-20:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123473E+12 | 229399.84 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278342E+11 | 131434.36 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.436319E+09 | 21571.85 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638450E+10 | 39350.57 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135667E+12 | 223449.92 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.268646E+12 | 322144.08 | 08-DEC-16:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114504E+13 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349030E+12 | 322144.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.389635E+09 | 0.305805E+09 | 8261.06 | 18-APR-15:10 | 6302.07 | 0.00 |
May | 0.00 | 0.00 | 0.114928E+10 | 0.918657E+09 | 17360.01 | 31-MAY-17:10 | 14887.40 | 0.00 |
June | 0.00 | 0.00 | 0.646882E+10 | 0.518660E+10 | 24345.01 | 26-JUN-00:01 | 14760.51 | 0.00 |
July | 0.00 | 0.00 | 0.937401E+10 | 0.728722E+10 | 24130.42 | 05-JUL-00:01 | 15463.06 | 0.00 |
August | 0.00 | 0.00 | 0.930632E+10 | 0.726297E+10 | 23247.47 | 28-AUG-00:02 | 15023.24 | 0.00 |
September | 0.00 | 0.00 | 0.400105E+10 | 0.356482E+10 | 21997.08 | 11-SEP-00:01 | 17699.69 | 0.00 |
October | 0.00 | 0.00 | 28261109.95 | 27012657.17 | 1950.84 | 20-OCT-15:00 | 1950.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.307174E+11 | 0.245531E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.937401E+10 | 0.728722E+10 | 24345.01 | 17699.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.130288E+09 | 84767193.91 | 11342.03 | 18-APR-15:10 | 7461.18 | 0.00 |
May | 0.00 | 0.00 | 0.612207E+09 | 0.459887E+09 | 22505.14 | 31-MAY-17:33 | 18236.93 | 0.00 |
June | 0.00 | 0.00 | 0.941887E+10 | 0.674127E+10 | 73777.91 | 18-JUN-14:03 | 46373.57 | 0.00 |
July | 0.00 | 0.00 | 0.134496E+11 | 0.940996E+10 | 77946.82 | 26-JUL-17:10 | 42821.89 | 0.00 |
August | 0.00 | 0.00 | 0.106586E+11 | 0.730084E+10 | 76387.61 | 04-AUG-17:08 | 45418.09 | 0.00 |
September | 0.00 | 0.00 | 0.416043E+10 | 0.345658E+10 | 45248.63 | 08-SEP-17:10 | 39861.37 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.384300E+11 | 0.274533E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134496E+11 | 0.940996E+10 | 77946.82 | 46373.57 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202065E+10 | 0.08 | 755.10 | 01-JAN-00:01 | 0.08 |
February | 0.178359E+10 | 0.08 | 755.10 | 01-FEB-00:02 | 0.08 |
March | 0.150795E+10 | 0.06 | 755.10 | 01-MAR-00:02 | 0.08 |
April | 0.592657E+09 | 0.02 | 755.10 | 01-APR-00:10 | 0.08 |
May | 25824494.12 | 0.00 | 755.10 | 01-MAY-21:40 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.306496E+09 | 0.01 | 755.10 | 08-OCT-02:00 | 0.08 |
November | 0.131615E+10 | 0.05 | 755.10 | 01-NOV-00:10 | 0.08 |
December | 0.200978E+10 | 0.08 | 755.10 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.956310E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202065E+10 | 0.08 | 755.10 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154326E+10 | 0.83 | 1236.11 | 02-JAN-08:30 | 0.98 |
February | 0.134734E+10 | 0.77 | 1236.11 | 01-FEB-12:20 | 0.99 |
March | 0.146033E+10 | 0.65 | 1236.11 | 01-MAR-09:50 | 0.98 |
April | 0.128372E+10 | 0.48 | 1236.11 | 05-APR-15:30 | 0.98 |
May | 0.129192E+10 | 0.40 | 1236.11 | 01-MAY-11:30 | 0.98 |
June | 0.136012E+10 | 0.51 | 1236.11 | 01-JUN-12:25 | 0.97 |
July | 0.137006E+10 | 0.55 | 1236.11 | 01-JUL-11:13 | 0.97 |
August | 0.144603E+10 | 0.56 | 1236.11 | 01-AUG-13:50 | 0.97 |
September | 0.127635E+10 | 0.45 | 1236.11 | 01-SEP-08:70 | 0.97 |
October | 0.125392E+10 | 0.39 | 1236.11 | 02-OCT-06:10 | 0.98 |
November | 0.129447E+10 | 0.60 | 1236.11 | 02-NOV-06:50 | 0.98 |
December | 0.145198E+10 | 0.79 | 1236.11 | 01-DEC-12:10 | 0.98 |
Annual Sum or Average | 0.163795E+11 | 0.58 | |||
Minimum of Months | 0.125392E+10 | 0.39 | 1236.11 | 0.97 | |
Maximum of Months | 0.154326E+10 | 0.83 | 1236.11 | 0.99 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.521105E+10 | 0.83 | 2979.06 | 02-JAN-09:20 | 0.95 |
February | 0.437667E+10 | 0.84 | 2979.06 | 01-FEB-10:00 | 0.95 |
March | 0.435702E+10 | 0.80 | 2979.06 | 01-MAR-10:50 | 0.95 |
April | 0.348246E+10 | 0.66 | 2979.06 | 01-APR-06:30 | 0.94 |
May | 0.311096E+10 | 0.39 | 2979.06 | 01-MAY-06:50 | 0.94 |
June | 0.315685E+10 | 0.41 | 2979.06 | 09-JUN-13:00 | 0.93 |
July | 0.304267E+10 | 0.39 | 2979.06 | 01-JUL-08:20 | 0.93 |
August | 0.320841E+10 | 0.39 | 2979.06 | 01-AUG-09:00 | 0.92 |
September | 0.300604E+10 | 0.41 | 2979.06 | 01-SEP-13:50 | 0.94 |
October | 0.336226E+10 | 0.66 | 2979.06 | 05-OCT-15:40 | 0.94 |
November | 0.405005E+10 | 0.75 | 2979.06 | 01-NOV-07:00 | 0.94 |
December | 0.479151E+10 | 0.84 | 2979.06 | 01-DEC-11:30 | 0.94 |
Annual Sum or Average | 0.451559E+11 | 0.61 | |||
Minimum of Months | 0.300604E+10 | 0.39 | 2979.06 | 0.92 | |
Maximum of Months | 0.521105E+10 | 0.84 | 2979.06 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.43 | 0.01 |
February | 2.57 | 0.05 |
March | 3.28 | 0.02 |
April | 1.63 | 0.06 |
May | 0.20 | 0.05 |
June | 0.25 | 3.68 |
July | 0.17 | 2.50 |
August | 0.50 | 3.68 |
September | 0.42 | 2.74 |
October | 0.68 | 0.43 |
November | 2.25 | 0.00 |
December | 2.37 | 0.02 |
Annual Sum or Average | 16.73 | 0.30 |
Minimum of Months | 0.17 | 0.00 |
Maximum of Months | 3.28 | 3.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.40 | 0.00 |
February | 1.09 | 0.00 |
March | 0.04 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 1.20 | 0.00 |
Annual Sum or Average | 4.81 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.40 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.26 | 0.00 |
July | 1.51 | 0.00 |
August | 0.14 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.06 | 0.00 |
Annual Sum or Average | 1.97 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.51 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154326E+10 | 0.264149E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134734E+10 | 0.195299E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.146033E+10 | 0.145545E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.139224E+10 | 0.714475E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160775E+10 | 0.129642E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.311487E+10 | 0.182768E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.387578E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.394595E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.237693E+10 | 0.785670E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126171E+10 | 0.401620E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129447E+10 | 0.114214E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145198E+10 | 0.206140E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.246726E+11 | 0.105961E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.126171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.394595E+10 | 0.264149E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.521105E+10 | 0.155618E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.437667E+10 | 0.112162E+12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.435702E+10 | 0.749827E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.352172E+10 | 0.311454E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.329690E+10 | 0.218065E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.593652E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.689418E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.628476E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.426445E+10 | 0.249697E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.336226E+10 | 0.204872E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.405005E+10 | 0.751540E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.479151E+10 | 0.125795E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.563471E+11 | 0.600021E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.329690E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.689418E+10 | 0.155618E+12 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154326E+10 | 0.00 | 0.188756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134734E+10 | 0.00 | 0.138256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146033E+10 | 0.00 | 0.101085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128372E+10 | 0.389635E+09 | 0.490823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129192E+10 | 0.114928E+10 | 0.888746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136012E+10 | 0.646882E+10 | 0.124108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137006E+10 | 0.937401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144603E+10 | 0.930632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127635E+10 | 0.400105E+10 | 0.535049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125392E+10 | 28261109.95 | 0.274501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129447E+10 | 0.00 | 0.793750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145198E+10 | 0.00 | 0.145180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163795E+11 | 0.307174E+11 | 0.744664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154326E+10 | 0.937401E+10 | 0.188756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.521105E+10 | 0.00 | 0.114475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437667E+10 | 0.00 | 0.813435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435702E+10 | 0.00 | 0.526639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348246E+10 | 0.130288E+09 | 0.214208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311096E+10 | 0.612207E+09 | 0.148585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315685E+10 | 0.941887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.304267E+10 | 0.134496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320841E+10 | 0.106586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300604E+10 | 0.416043E+10 | 0.168873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336226E+10 | 0.00 | 0.139751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405005E+10 | 0.00 | 0.535988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479151E+10 | 0.00 | 0.906829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451559E+11 | 0.384300E+11 | 0.431335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.521105E+10 | 0.134496E+11 | 0.114475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.154326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128372E+10 | 0.00 | 0.00 | 0.00 | 0.108511E+09 | 0.00 | 0.714475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129192E+10 | 0.00 | 0.00 | 0.00 | 0.315830E+09 | 0.00 | 0.129642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136012E+10 | 0.00 | 0.00 | 0.00 | 0.175474E+10 | 0.00 | 0.182768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137006E+10 | 0.00 | 0.00 | 0.00 | 0.250573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144603E+10 | 0.00 | 0.00 | 0.00 | 0.249992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127635E+10 | 0.00 | 0.00 | 0.00 | 0.110058E+10 | 0.00 | 0.785670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125392E+10 | 0.00 | 0.00 | 0.00 | 7781879.91 | 0.00 | 0.401620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163795E+11 | 0.00 | 0.00 | 0.00 | 0.829310E+10 | 0.00 | 0.105961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154326E+10 | 0.00 | 0.00 | 0.00 | 0.250573E+10 | 0.00 | 0.264149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.521105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348246E+10 | 0.00 | 0.00 | 0.00 | 39265793.51 | 0.00 | 0.311454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311096E+10 | 0.00 | 0.00 | 0.00 | 0.185948E+09 | 0.00 | 0.218065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315685E+10 | 0.00 | 0.00 | 0.00 | 0.277967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.304267E+10 | 0.00 | 0.00 | 0.00 | 0.385151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320841E+10 | 0.00 | 0.00 | 0.00 | 0.307635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300604E+10 | 0.00 | 0.00 | 0.00 | 0.125841E+10 | 0.00 | 0.249697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451559E+11 | 0.00 | 0.00 | 0.00 | 0.111912E+11 | 0.00 | 0.600021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.300604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.521105E+10 | 0.00 | 0.00 | 0.00 | 0.385151E+10 | 0.00 | 0.155618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495099E+10 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372888E+10 | 0.00 | 0.00 | 0.16 |
March | 21353245.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281083E+10 | 0.00 | 0.00 | 0.16 |
April | 0.171472E+09 | 50905658.45 | 265427.70 | 103224.47 | 6351382.86 | 0.160117E+10 | 35889782.82 | 194.79 | 0.15 |
May | 0.472094E+09 | 72450750.85 | 0.00 | 405090.20 | 636903.97 | 0.267571E+09 | 0.144980E+09 | 0.00 | 0.14 |
June | 0.190150E+09 | 0.600031E+09 | 0.00 | 2149037.27 | 153998.21 | 48635356.16 | 0.182112E+09 | 0.00 | 0.16 |
July | 19806553.09 | 0.931908E+09 | 0.00 | 1996752.19 | 293774.77 | 0.00 | 70311730.88 | 0.00 | 0.15 |
August | 49560692.80 | 0.922841E+09 | 0.00 | 2570974.06 | 99825.58 | 0.00 | 84029633.69 | 0.00 | 0.16 |
September | 0.295799E+09 | 0.220655E+09 | 0.00 | 2275159.81 | 0.00 | 0.247980E+09 | 0.237376E+09 | 0.00 | 0.15 |
October | 0.363609E+09 | 0.00 | 0.00 | 12481.21 | 0.00 | 0.118357E+10 | 7022751.53 | 0.00 | 0.14 |
November | 0.163202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235559E+10 | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392783E+10 | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.174705E+10 | 0.279879E+10 | 265427.70 | 9512719.22 | 7535885.39 | 0.211230E+11 | 0.761722E+09 | 194.79 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.472094E+09 | 0.931908E+09 | 265427.70 | 2570974.06 | 6351382.86 | 0.495099E+10 | 0.237376E+09 | 194.79 | 0.17 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3782567.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123801E+11 | 0.00 | 0.00 | 0.17 |
February | 0.166511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903431E+10 | 0.00 | 0.00 | 0.18 |
March | 0.768441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584890E+10 | 0.00 | 0.00 | 0.19 |
April | 0.168967E+10 | 13068411.76 | 0.00 | 0.00 | 63604097.07 | 0.252432E+10 | 0.00 | 0.00 | 0.18 |
May | 0.204488E+10 | 80918798.64 | 0.00 | 4747.37 | 15500045.73 | 72490355.67 | 672457.10 | 0.00 | 0.19 |
June | 0.136402E+10 | 0.101604E+10 | 0.00 | 1598461.40 | 3764715.38 | 0.00 | 0.636824E+09 | 0.00 | 0.23 |
July | 0.629434E+09 | 0.148907E+10 | 0.00 | 2778164.40 | 897.00 | 0.00 | 0.760935E+09 | 0.00 | 0.22 |
August | 0.728927E+09 | 0.133938E+10 | 0.00 | 2178153.27 | 4769841.49 | 0.00 | 0.816665E+09 | 0.00 | 0.25 |
September | 0.197682E+10 | 0.418496E+09 | 0.00 | 880861.50 | 187971.08 | 0.102196E+09 | 0.161205E+09 | 0.00 | 0.19 |
October | 0.242166E+10 | 0.00 | 0.00 | 0.00 | 3280397.12 | 0.841594E+09 | 0.00 | 0.00 | 0.17 |
November | 0.880390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509880E+10 | 0.00 | 0.00 | 0.17 |
December | 22184399.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977181E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.126967E+11 | 0.435698E+10 | 0.00 | 7440387.94 | 91107964.87 | 0.456745E+11 | 0.237630E+10 | 0.00 | 0.19 |
Minimum of Months | 3782567.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.242166E+10 | 0.148907E+10 | 0.00 | 2778164.40 | 63604097.07 | 0.123801E+11 | 0.816665E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |