Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1630.78 | 337.28 | 337.28 |
Net Site Energy | 1630.78 | 337.28 | 337.28 |
Total Source Energy | 3582.48 | 740.93 | 740.93 |
Net Source Energy | 3582.48 | 740.93 | 740.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 759.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 871.20 | 759.58 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 759.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.18 | 157.10 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.18 | 157.10 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.18 | 157.10 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.18 | 157.10 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 871.202 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 871.202 | 100.00 |
Total On-Site and Utility Electric Sources | 871.202 | 100.00 |
Total Electricity End Uses | 871.202 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 49.83 |
Time Setpoint Not Met During Occupied Cooling | 3.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1676.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:09 | 06-FEB-00:00 | - | - | - | 28-JUN-11:00 |
Heating | 0.00 | 376336.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18626.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1734.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 72406.07 | 376336.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 376336.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18626.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4006.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1734.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 823.38 | 0.00 | 0.00 | 0.00 |
Cooling | 122.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 195.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2759.10 | 823.38 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 170.29 | 0.00 | 0.00 | 0.00 |
Cooling | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 570.64 | 170.29 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 170.29 | 0.00 | 0.00 | 0.00 |
Cooling | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 570.64 | 170.29 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.56 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.39 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.39 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 223949.66 |
PSZ-OFFICE HEATING COIL | 28225.01 |
PSZ-FINE STORAGE HEATING COIL | 89093.70 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 223949.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 1.00 | 1.000000 | 2.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.06 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.56 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 20207.39 | 28225.01 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.56 | 2.56 | 2.56 | 2.56 | 62058.94 | 89093.70 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.530015 | 1.06 | 19713.01 | 20207.39 | 10103.69 | 20207.39 | 0.750257 | 0.750260 | 0.750260 | 0.750260 |
PSZ-FINE STORAGE COOLING COIL | 2.56 | 1.28 | 2.56 | 59530.25 | 62058.94 | 31029.47 | 62058.94 | 0.681727 | 0.681730 | 0.681730 | 0.681730 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1208.55 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.56 | 2798.28 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.71045622E-12 | 0.18350169E-15 | 0.20920636E-14 | 0.12692337E-15 |
13 | 3 | -0.36041595E-03 | 0.57471575E-06 | -0.52051292E-04 | 0.13635641E-12 |
14 | 2 | 1.6814491 | 0.12908092E-01 | 1.0963028 | -0.69095641E-04 |
15 | 1 | -7.2068525 | 0.34008243 | -16.815156 | 0.32221486 |
16 | 0 | 6.0979960 | 0.21924101 | 16.291138 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20920636E-14 | 0.18350169E-15 | 0.71045622E-12 | 0.12692337E-15 |
85 | 3 | -0.52051292E-04 | 0.57471575E-06 | -0.36041595E-03 | 0.13635641E-12 |
86 | 2 | 1.0963028 | 0.12908092E-01 | 1.6814491 | -0.69095641E-04 |
87 | 1 | -16.815156 | 0.34008243 | -7.2068525 | 0.32221486 |
88 | 0 | 16.291138 | 0.21924101 | 6.0979960 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10732.01117 | 12878.41340 | 0.88336 | 1.06003 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.40969E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12786.70628 | 15344.04753 | 0.35918 | 0.43101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33202.00633 | 39842.40759 | 2.13055 | 2.55666 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 67979.88883 | 81575.86660 | 1.60768 | 1.92921 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10000 | 1.40969E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 186624.70312 | 223949.64374 | 4.49390 | 5.39268 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -10.70000 | 1.50390E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16141.30 | 1.06003 | 1.06003 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13806.94 | 0.43101 | 0.43101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 48221.48 | 2.55666 | 2.55666 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 70537.24 | 1.92921 | 1.92921 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06003 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.55666 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.39268 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.39268 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 223949.66362 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 223949.64374 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06003 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06003 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06003 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06003 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06003 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.06003 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55666 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.55666 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.55666 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55666 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.55666 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.55666 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.06003 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.55666 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06003 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06003 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06003 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06003 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06003 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06003 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53002 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06003 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19713.00984 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20207.39000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10103.69500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20207.39000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75026 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75026 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75026 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75026 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20207.39000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28225.01334 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06003 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1208.55097 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28225.01334 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.55666 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.55666 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.55666 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.55666 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.55666 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.55666 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27833 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.55666 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 59530.24819 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 62058.94000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31029.47000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 62058.94000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68173 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68173 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68173 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68173 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62058.94000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89093.70061 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.55666 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2798.28200 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 89093.70061 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19384.4 | 10.30 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 60071.9 | 13.33 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3816666166 | 0.3831616241 | Pass | Pass | 0.7375814683 | 0.7601533742 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.2903994916 | 1.1413637975 | Pass | Pass | 0.6277393610 | 0.5756462985 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.5205979758E-004 | 2.8758327318E-004 | Pass | Pass | 2.4259012424E-002 | 1.9155138113E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.826 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.092 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.64 | 83.64 | 123.36 | |
Exterior Lighting Total | 7857.24 | 123.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20207.39 | 15160.80 | 5046.59 | 0.75 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62058.94 | 42307.44 | 19751.50 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19384.4 | 10.30 | ||||
PSZ-FINE STORAGE COOLING COIL | 60071.9 | 13.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 223949.66 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28225.01 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 89093.70 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.39 | 501.04 | 92.91 | 1.00 | 3.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.06 | 1208.55 | 1140.11 | 1.00 | 1.35 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.56 | 2798.28 | 1094.51 | 1.00 | 1.25 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10732.01 | 12878.41 | 54.37 | 0.883 | 1.060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00840 | 31.06 | 0.01410 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33202.01 | 39842.41 | 28.59 | 2.131 | 2.557 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26.70 | 26.70 | 0.00879 | 32.10 | 0.01410 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 32.10 | 0.01410 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12786.71 | 15344.05 | 64.78 | 0.359 | 0.431 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00697 | -10.70 | 0.00150 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 67979.89 | 81575.87 | 58.54 | 1.608 | 1.929 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00517 | -10.70 | 0.00150 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 186624.70 | 223949.64 | 69.88 | 4.494 | 5.393 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00763 | -10.70 | 0.00150 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.43 | 0.43 | 1.0600 | 1.0600 | 1.0600 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 1.93 | 1.93 | 2.5567 | 2.5567 | 2.5567 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 223949.664 | 223949.664 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 223949.66 | 223949.66 | 5.392683 | 6.24 | 6.24 | 0.00651876 | 43.33 | 27.10 | 0.01600000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 9.98 | 0.00762811 | 100.0000 | 223949.64 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20207.390 | 0.000 | 1.060030 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20207.39 | 17272.06 | 1.060030 | 24.59 | 16.95 | 0.00894589 | 12.00 | 11.25 | 0.00800000 | 31.06 | 0.01409688 | 22.82 | 9.6492 | 23.90 | 0.00839577 | 45.4574 | 10732.01 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28225.013 | 28225.013 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28225.01 | 28225.01 | 1.060030 | 13.51 | 9.43 | 0.00567606 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 9.6492 | 21.10 | 0.00697424 | 44.8739 | 12786.71 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 62058.940 | 0.000 | 2.556660 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 62058.94 | 49767.32 | 2.556660 | 27.59 | 18.56 | 0.00966813 | 12.00 | 11.25 | 0.00800000 | 32.10 | 0.01409687 | 23.10 | 16.6120 | 26.70 | 0.00878587 | 40.2494 | 31995.39 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 89093.701 | 89093.701 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89093.70 | 89093.70 | 2.556663 | 9.77 | 6.11 | 0.00435956 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 16.6120 | 15.54 | 0.00516570 | 47.2321 | 67979.89 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 223949.664 | 223949.664 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.392683 | 6.49060664 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 223949.66 | 223949.66 | 1.0000 | 6.49060664 | 5.392683 | 6.24 | 6.24 | 0.00651876 | 22645.3 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 223949.66 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 9.98 | 0.00762811 | 9.98 | 0.00762811 | 100.0000 | 223949.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20207.390 | 0.000 | 1.060030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4700 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20207.39 | 17272.06 | 1.0000 | 1.27584679 | 1.060030 | 24.59 | 16.95 | 0.00894589 | 47491.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20207.39 | 31.06 | 0.01409688 | 22.82 | 0.10228487 | 9.6492 | 23.90 | 0.00839577 | 23.90 | 0.00839577 | 45.4574 | 10732.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28225.013 | 28225.013 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.060030 | 1.27584709 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28225.01 | 28225.01 | 1.0000 | 1.27584709 | 1.060030 | 13.51 | 9.43 | 0.00567606 | 27917.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28225.01 | -10.70 | 0.00150390 | -10.70 | 0.10228487 | 9.6492 | 21.05 | 0.00697424 | 21.10 | 0.00697424 | 44.8739 | 12786.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62058.940 | 0.000 | 2.556660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8126 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 62058.94 | 49767.32 | 1.0000 | 3.07718315 | 2.556660 | 27.59 | 18.56 | 0.00966813 | 52403.8 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62058.94 | 32.10 | 0.01409687 | 23.10 | 0.42471267 | 16.6120 | 26.70 | 0.00878587 | 26.70 | 0.00878587 | 40.2494 | 31995.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89093.701 | 89093.701 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.556663 | 3.07718708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89093.70 | 89093.70 | 1.0000 | 3.07718708 | 2.556663 | 9.77 | 6.11 | 0.00435956 | 20798.4 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89093.70 | -10.70 | 0.00150390 | -10.70 | 0.42471267 | 16.6120 | 15.55 | 0.00516570 | 15.54 | 0.00516570 | 47.2321 | 67979.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2663.67 | 2405.33 | 1676.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2663.67 | 2405.33 | 1676.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 80.50 | 116.17 | 49.83 | 3.67 |
ZONE2 FINE STORAGE | 491.50 | 33.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 545.00 | 141.33 | 49.83 | 3.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.345 | 0.292 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
Electricity:Building | 624.16 | 4992.32 | 01-JAN-00:10 | 48037.94 | 01-JUN-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 424.57 | 2759.73 | 01-JAN-00:10 | 33963.13 | 01-JUN-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.26 | 483.00 | 01-JAN-01:20 | 2540.82 | 10-FEB-12:50 |
WaterSystems:Electricity | 26.26 | 483.00 | 01-JAN-01:20 | 2540.82 | 10-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.26 | 483.00 | 01-JAN-01:20 | 2540.82 | 10-FEB-12:50 |
Fans:Electricity | 61.70 | 0.00 | 17-JAN-18:10 | 6312.13 | 01-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 21-JUL-12:00 |
Ventilation (simple):Fans:Electricity | 2.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 21-JUL-12:00 |
ElectricityPurchased:Facility | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
ElectricityPurchased:Plant | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
Cogeneration:ElectricityPurchased | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
ElectricityNet:Plant | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
Cogeneration:ElectricityNet | 871.20 | 5475.32 | 19-FEB-09:20 | 72406.07 | 04-AUG-14:10 |
Electricity:HVAC | 97.42 | 0.00 | 17-JAN-18:10 | 23022.33 | 19-JUN-12:00 |
General:Fans:Electricity | 58.78 | 0.00 | 17-JAN-18:10 | 4507.87 | 04-JAN-16:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 38.63 | 0.00 | 01-JAN-00:10 | 19015.50 | 19-JUN-12:00 |
ExteriorLights:Electricity | 123.36 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.36 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 759.58 | 0.00 | 17-JAN-18:10 | 376336.14 | 06-FEB-01:00 |
Gas:HVAC | 759.58 | 0.00 | 17-JAN-18:10 | 376336.14 | 06-FEB-01:00 |
Heating:Gas | 759.58 | 0.00 | 17-JAN-18:10 | 376336.14 | 06-FEB-01:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1347.47 | 0.00 | 17-JAN-18:10 | 582620.55 | 06-FEB-01:00 |
EnergyTransfer:Building | 638.13 | 0.00 | 17-JAN-18:10 | 285475.39 | 06-FEB-01:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 62.58 | 0.00 | 01-JAN-00:40 | 22489.83 | 06-FEB-06:10 |
Heating:EnergyTransfer | 549.24 | 0.00 | 17-JAN-18:10 | 285475.39 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 29.16 | 0.00 | 01-JAN-00:40 | 22489.83 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 88.88 | 0.00 | 01-JAN-00:10 | 42281.83 | 18-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 33.42 | 0.00 | 01-JAN-00:10 | 11513.58 | 10-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 228.44 | 0.00 | 01-JAN-00:40 | 77976.94 | 01-JAN-20:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 172.98 | 0.00 | 01-JAN-00:40 | 77976.94 | 01-JAN-20:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 55.46 | 0.00 | 01-JAN-00:10 | 33081.27 | 18-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 347.10 | 0.00 | 02-JAN-11:00 | 202139.66 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 347.10 | 0.00 | 02-JAN-11:00 | 202139.66 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 709.35 | 0.00 | 17-JAN-18:10 | 297145.17 | 06-FEB-01:00 |
HeatingCoils:EnergyTransfer | 571.52 | 0.00 | 17-JAN-18:10 | 297145.17 | 06-FEB-01:00 |
CoolingCoils:EnergyTransfer | 137.83 | 0.00 | 01-JAN-00:10 | 67697.01 | 02-AUG-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 29.159 | -33.420 | 0.000 | 0.000 | 3.895 | 30.994 | 31.946 | 9.928 | 0.000 | 0.885 | 0.000 | 0.000 | -8.723 | 0.000 | -20.212 | -44.452 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 172.979 | -55.460 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 2.174 | 0.002 | 0.000 | 0.000 | 0.000 | -174.628 | -81.722 |
ZONE3 BULK STORAGE | 347.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 32.893 | 0.000 | 4.362 | 0.000 | 0.000 | -18.567 | 0.000 | -643.643 | -143.795 |
Total Facility | 347.104 | 0.000 | 202.139 | -88.880 | 0.000 | 0.000 | 3.895 | 481.960 | 139.282 | 42.821 | 0.000 | 7.421 | 0.002 | 0.000 | -27.290 | 0.000 | -838.483 | -269.969 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-SEP-00:02 | 0.00 | 0.00 | 0.00 | -18882.92 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 18679.89 | 0.00 | -524.71 | 0.00 | -304.96 | 0.00 |
ZONE2 FINE STORAGE | 20-AUG-13:23 | 0.00 | 0.00 | 0.00 | -55052.05 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 697.03 | 53155.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-17:08 | 0.00 | 0.00 | 0.00 | -70751.87 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 3864.78 | 0.00 | 2147.02 | 98861.76 | 0.00 | 0.00 | 0.00 | -41164.03 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-06:31 | 0.00 | 0.00 | 28448.54 | 0.00 | 0.00 | 0.00 | 54.34 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.42 | 0.00 | -1800.07 | -27384.58 |
ZONE2 FINE STORAGE | 12-JAN-04:02 | 0.00 | 0.00 | 87904.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15457.41 | -73646.71 |
ZONE3 BULK STORAGE | 06-FEB-00:51 | 202148.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3013.98 | 0.00 | -147034.42 | -56909.56 |
Total Facility | 06-FEB-00:51 | 202148.19 | 0.00 | 84200.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4258.83 | 0.00 | -189270.32 | -99862.30 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0600 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0600 | 0.0965 | 1.0000 | 0.1023 | 0.0965 | ||
PSZ-FINE STORAGE | 2.5567 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5567 | 0.1661 | 1.0000 | 0.4247 | 0.1661 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0600 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0600 | 1.0000 | 1.0000 | 0.1023 | 0.0965 | ||
PSZ-FINE STORAGE | 2.5567 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5567 | 1.0000 | 1.0000 | 0.4247 | 0.1661 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0600 | 1.0600 | 1.0600 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5567 | 2.5567 | 2.5567 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0600 | 1.0600 | 1.0600 | 1.0600 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5567 | 2.5567 | 2.5567 | 2.5567 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0600 | 1.0600 | 1.0600 | 0.1023 | 0.2373 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5567 | 2.5567 | 2.5567 | 0.4247 | 0.2201 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0600 | 1.0600 | 1.0600 | 1.0600 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5567 | 2.5567 | 2.5567 | 2.5567 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 49.83 |
Number of hours cooling loads not met | 3.67 |
Number of hours not met | 53.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 759.58 | 376336.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 38.63 | 19015.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.36 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 2.92 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.78 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.26 | 2540.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 871.20 |
Natural Gas | 0.00 | 759.58 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1630.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 7.99 |
Fans (All) | 12.76 |
Service Water Heating | 5.43 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 180.18 |
Subtotal | 180.18 |
Natural Gas [MJ/m2] | |
Space Heating | 157.10 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 157.10 |
Subtotal | 157.10 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 29.55 |
Space Heating | 46.58 |
Space Cooling | 2.37 |
Fans (All) | 3.78 |
Service Water Heating | 1.61 |
Receptacle Equipment | 8.54 |
Miscellaneous | 7.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.230887E+12 |
February | 0.000 | 0.219621E+12 |
March | 0.000 | 0.775222E+11 |
April | 0.000 | 0.141489E+11 |
May | 0.000 | 0.369890E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.646957E+09 |
November | 0.000 | 0.617935E+11 |
December | 0.000 | 0.154590E+12 |
Annual Sum or Average | 0.759580E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.230887E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.4 | 0.194953E+09 | 236.59 | 21-JAN-11:09 | 6.47 | 6.07 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -1.1 | -4.0 | 0.179356E+09 | 236.59 | 04-FEB-08:20 | 0.60 | 0.37 |
March | 11693829.96 | 663.96 | 29-MAR-15:00 | 7.20 | 5.19 | 0.212786E+09 | 295.43 | 27-MAR-15:00 | 22.20 | 16.33 |
April | 0.239359E+09 | 3114.15 | 07-APR-16:00 | 25.60 | 16.11 | 0.211730E+09 | 303.16 | 10-APR-08:39 | 20.00 | 15.69 |
May | 0.164161E+10 | 16583.66 | 30-MAY-17:43 | 23.27 | 17.10 | 0.248683E+09 | 302.27 | 01-MAY-15:09 | 15.50 | 7.51 |
June | 0.628984E+10 | 18222.61 | 05-JUN-00:03 | 16.93 | 12.79 | 0.258856E+09 | 301.60 | 23-JUN-10:00 | 28.90 | 18.39 |
July | 0.871664E+10 | 16918.55 | 11-JUL-17:08 | 28.12 | 17.26 | 0.248939E+09 | 301.61 | 12-JUL-13:00 | 28.30 | 19.50 |
August | 0.953686E+10 | 17740.00 | 25-AUG-18:23 | 24.75 | 14.33 | 0.268855E+09 | 301.60 | 22-AUG-10:00 | 29.40 | 18.78 |
September | 0.538731E+10 | 18882.99 | 11-SEP-00:02 | 15.50 | 9.78 | 0.248457E+09 | 301.61 | 12-SEP-12:39 | 22.20 | 15.60 |
October | 0.158167E+10 | 8104.78 | 04-OCT-17:15 | 20.77 | 18.48 | 0.237718E+09 | 301.59 | 06-OCT-14:20 | 16.87 | 10.76 |
November | 15883848.14 | 937.43 | 04-NOV-14:10 | 16.78 | 12.90 | 0.194366E+09 | 301.58 | 04-NOV-14:09 | 16.78 | 12.90 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 | 2.85 | 0.194981E+09 | 236.59 | 29-DEC-16:10 | 5.18 | 4.91 |
Annual Sum or Average | 0.334209E+11 | 0.269968E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.4 | 0.179356E+09 | 236.59 | 0.60 | 0.37 | ||
Maximum of Months | 0.953686E+10 | 18882.99 | 28.12 | 18.48 | 0.268855E+09 | 303.16 | 29.40 | 19.50 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255675E+09 | 3502.63 | 26-JAN-11:30 | 3.60 | 0.16 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.358859E+09 | 3583.94 | 22-FEB-12:00 | 3.30 | -1.2 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.832332E+09 | 5362.60 | 18-MAR-10:00 | 0.00 | -0.7 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.664713E+09 | 3608.45 | 12-APR-08:15 | 5.97 | 0.45 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.121397E+10 | 21871.05 | 29-MAY-12:10 | 28.62 | 18.18 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.866393E+10 | 49163.21 | 22-JUN-17:08 | 29.32 | 17.48 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.172924E+11 | 52571.73 | 11-JUL-17:08 | 28.12 | 17.26 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.190133E+11 | 55051.41 | 20-AUG-13:23 | 28.35 | 15.41 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.569724E+10 | 50081.53 | 04-SEP-13:23 | 26.10 | 18.38 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.811291E+09 | 6032.11 | 04-OCT-14:10 | 24.32 | 18.97 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.370961E+09 | 2995.61 | 20-NOV-11:00 | 4.40 | 2.31 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.287091E+09 | 3879.91 | 09-DEC-11:00 | 3.30 | 0.82 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.554618E+11 | 0.00 | ||||||||
Minimum of Months | 0.255675E+09 | 2995.61 | 0.00 | -1.2 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.190133E+11 | 55051.41 | 29.32 | 18.97 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.4 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -1.1 | -4.0 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 | 4.34 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.00 | 19.28 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 | 2.85 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.712708E+10 | 28451.62 | 03-JAN-06:31 | 5.07 |
February | 0.696833E+10 | 27740.34 | 01-FEB-06:32 | 2.03 |
March | 0.436537E+10 | 27628.61 | 11-MAR-06:32 | 2.03 |
April | 0.187509E+10 | 27616.47 | 25-APR-05:01 | 9.60 |
May | 0.311490E+09 | 27544.08 | 08-MAY-05:01 | 12.83 |
June | 7582087.17 | 708.76 | 06-JUN-06:10 | 18.30 |
July | 730620.62 | 829.33 | 05-JUL-06:10 | 21.28 |
August | 1417197.72 | 805.36 | 28-AUG-06:10 | 20.10 |
September | 11340875.76 | 1369.03 | 13-SEP-06:05 | 21.70 |
October | 0.283647E+09 | 27622.89 | 30-OCT-05:01 | 11.93 |
November | 0.298356E+10 | 27566.64 | 14-NOV-06:01 | 10.00 |
December | 0.522386E+10 | 27576.37 | 14-DEC-06:32 | 0.77 |
Annual Sum or Average | 0.291595E+11 | |||
Minimum of Months | 730620.62 | 708.76 | 0.77 | |
Maximum of Months | 0.712708E+10 | 28451.62 | 21.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468035E+11 | 87904.09 | 12-JAN-04:02 | 5.22 |
February | 0.433544E+11 | 85862.05 | 11-FEB-22:42 | 0.78 |
March | 0.221270E+11 | 86176.22 | 13-MAR-00:52 | 1.10 |
April | 0.653835E+10 | 85141.47 | 21-APR-04:53 | 5.60 |
May | 0.243510E+09 | 16153.99 | 01-MAY-04:55 | 6.10 |
June | 32767872.39 | 1593.06 | 19-JUN-06:05 | 25.37 |
July | 5952694.82 | 802.15 | 03-JUL-06:05 | 23.17 |
August | 8071370.01 | 943.23 | 11-AUG-06:15 | 23.17 |
September | 53373148.64 | 1692.90 | 01-SEP-06:05 | 25.00 |
October | 0.351619E+09 | 30429.77 | 31-OCT-05:38 | 5.20 |
November | 0.177996E+11 | 86613.44 | 26-NOV-08:62 | 8.98 |
December | 0.356617E+11 | 87615.51 | 29-DEC-21:22 | 4.40 |
Annual Sum or Average | 0.172980E+12 | |||
Minimum of Months | 5952694.82 | 802.15 | 0.78 | |
Maximum of Months | 0.468035E+11 | 87904.09 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114986E+12 | 174909.99 | 01-JAN-20:54 | -8.3 |
February | 0.109645E+12 | 202148.29 | 06-FEB-00:51 | -13.3 |
March | 0.277553E+11 | 109086.65 | 22-MAR-07:10 | -2.7 |
April | 0.105819E+10 | 27420.16 | 02-APR-05:55 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.229213E+11 | 114912.94 | 23-NOV-01:51 | -2.8 |
December | 0.707389E+11 | 175713.81 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.347105E+12 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.114986E+12 | 202148.29 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352642E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331723E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274889E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6568704.54 | 0.162520E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17453200.74 | 0.103296E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137417E+09 | 0.461855E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290614E+09 | 98046164.70 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373686E+09 | 0.159987E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58236535.65 | 0.554949E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 951081.83 | 0.135573E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231555E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301522E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.884927E+09 | 0.202120E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98046164.70 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373686E+09 | 0.352642E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315013E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287367E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2741712.49 | 0.210876E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55868408.12 | 0.117657E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29820817.18 | 0.799982E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339196E+09 | 0.665010E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637174E+09 | 0.273494E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103492E+10 | 0.322478E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74495134.58 | 0.634406E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108376E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179159E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258296E+11 |
Annual Sum or Average | 0.136656E+12 | 0.217421E+10 | 0.174628E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273494E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103492E+10 | 0.315013E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35550217.92 | 0.683494E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671907E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536814E+09 | 0.410623E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120149E+10 | 0.258601E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116113E+09 | 0.235729E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102330E+09 | 0.292327E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4975920.25 | 0.173800E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27837709.07 | 0.192132E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155124.34 | 0.262775E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12791540.65 | 0.328230E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83122137.36 | 0.365741E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4871004.74 | 0.505607E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.212605E+10 | 0.438097E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173800E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120149E+10 | 0.683494E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10059.03 | 31-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 11300.05 | 06-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 9097.90 | 22-MAR-07:00 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.19 | 07-APR-17:00 | 5395.40 | 12-APR-07:00 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.80 | 30-MAY-12:00 | 3612.05 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2859.57 | 19-JUN-12:00 | 2713.68 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.21 | 07-JUL-12:00 | 771.37 | 11-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2841.77 | 24-AUG-17:00 | 1643.09 | 08-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1453.19 | 14-SEP-16:10 | 3129.17 | 11-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.99 | 25-OCT-11:10 | 4633.90 | 27-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7761.64 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7119.48 | 01-DEC-17:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.37 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2859.57 | 11300.05 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 49629.42 | 14-JAN-17:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 44309.17 | 06-FEB-07:10 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.15 | 27-MAR-16:00 | 46838.51 | 22-MAR-07:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2241.10 | 16-APR-17:00 | 19972.51 | 21-APR-06:10 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.49 | 29-MAY-11:50 | 11511.95 | 11-MAY-17:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7675.70 | 19-JUN-17:00 | 12098.78 | 06-JUN-15:05 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6792.88 | 10-JUL-15:10 | 5422.83 | 15-JUL-08:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11165.93 | 24-AUG-17:00 | 6188.00 | 20-AUG-06:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3476.15 | 01-SEP-15:10 | 7758.92 | 23-SEP-07:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17948.51 | 28-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32041.42 | 23-NOV-01:51 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 44472.95 | 31-DEC-21:51 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5422.83 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11165.93 | 49629.42 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3250.55 | 03-JAN-10:40 | 112510.94 | 14-JAN-17:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 108146.48 | 06-FEB-00:54 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18961.71 | 27-MAR-16:00 | 96756.38 | 22-MAR-07:10 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19383.12 | 07-APR-13:00 | 44238.45 | 12-APR-07:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5425.98 | 29-MAY-11:55 | 29089.17 | 11-MAY-16:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.26 | 19-JUN-10:55 | 34443.21 | 03-JUN-16:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 539.24 | 16-JUL-11:53 | 24643.39 | 11-JUL-08:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3434.73 | 04-AUG-18:53 | 28085.64 | 19-AUG-08:50 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.54 | 14-SEP-14:00 | 29079.87 | 23-SEP-09:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3348.58 | 25-OCT-11:00 | 50230.45 | 28-OCT-08:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4577.89 | 26-NOV-14:55 | 66819.01 | 23-NOV-01:51 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 880.93 | 25-DEC-08:55 | 100497.73 | 31-DEC-21:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24643.39 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19383.12 | 112510.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.93 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.74 |
March | 663.96 | 29-MAR-15:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.24 |
April | 3114.15 | 07-APR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 163.60 | 0.00 |
May | 16583.66 | 30-MAY-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 |
June | 18222.61 | 05-JUN-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.70 |
July | 16918.55 | 11-JUL-17:08 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.40 | 0.00 |
August | 17740.00 | 25-AUG-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 | 0.00 |
September | 18882.99 | 11-SEP-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.96 |
October | 8104.78 | 04-OCT-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.83 |
November | 937.43 | 04-NOV-14:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18882.99 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 276.40 | 2037.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3502.63 | 26-JAN-11:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.65 |
February | 3583.94 | 22-FEB-12:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4368.89 |
March | 5362.60 | 18-MAR-10:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3608.45 | 12-APR-08:15 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5699.50 |
May | 21871.05 | 29-MAY-12:10 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.96 | 0.00 |
June | 49163.21 | 22-JUN-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.59 | 0.00 |
July | 52571.73 | 11-JUL-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.58 | 0.00 |
August | 55051.41 | 20-AUG-13:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.03 | 0.00 |
September | 50081.53 | 04-SEP-13:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.87 |
October | 6032.11 | 04-OCT-14:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.67 |
November | 2995.61 | 20-NOV-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3522.15 |
December | 3879.91 | 09-DEC-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2995.61 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55051.41 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.59 | 5699.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 27597.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80082.71 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22267.23 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8263.37 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9812.36 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.91 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8399.63 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9594.82 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6164.50 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7447.58 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19935.45 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11976.48 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15326.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.91 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80082.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.732102E+11 | 55761.24 | 14-JAN-16:00 | 0.230887E+12 | 339635.45 | 01-JAN-23:30 |
February | 0.660914E+11 | 52275.79 | 04-FEB-13:00 | 0.219621E+12 | 376336.14 | 06-FEB-00:00 |
March | 0.732691E+11 | 52173.67 | 16-MAR-14:00 | 0.775222E+11 | 232471.44 | 22-MAR-06:10 |
April | 0.669838E+11 | 52758.42 | 07-APR-14:00 | 0.141489E+11 | 75615.71 | 02-APR-05:00 |
May | 0.690717E+11 | 61596.81 | 31-MAY-13:00 | 0.369890E+09 | 21686.94 | 01-MAY-05:10 |
June | 0.738745E+11 | 72106.06 | 19-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.803121E+11 | 71659.45 | 08-JUL-12:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.850333E+11 | 72406.07 | 04-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.718133E+11 | 67071.34 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.698740E+11 | 56641.13 | 04-OCT-14:20 | 0.646957E+09 | 24934.06 | 31-OCT-06:10 |
November | 0.686372E+11 | 55754.00 | 30-NOV-16:49 | 0.617935E+11 | 228592.69 | 23-NOV-02:09 |
December | 0.730314E+11 | 55759.42 | 30-DEC-16:49 | 0.154590E+12 | 326571.32 | 31-DEC-22:10 |
Annual Sum or Average | 0.871202E+12 | 0.759580E+12 | ||||
Minimum of Months | 0.660914E+11 | 52173.67 | 0.00 | 0.00 | ||
Maximum of Months | 0.850333E+11 | 72406.07 | 0.230887E+12 | 376336.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.127664E+11 | 0.115358E+11 | 0.00 | 0.647962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232494E+10 | 0.00 |
February | 0.366966E+11 | 0.107063E+11 | 0.105871E+11 | 0.00 | 0.597978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212158E+10 | 0.00 |
March | 0.423649E+11 | 0.107204E+11 | 0.123357E+11 | 0.00 | 0.547311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237501E+10 | 0.00 |
April | 0.397216E+11 | 0.924011E+10 | 0.114862E+11 | 0.00 | 0.422839E+10 | 0.00 | 0.00 | 94416091.14 | 0.00 | 0.00 | 0.00 | 0.221306E+10 | 0.00 |
May | 0.412341E+11 | 0.854239E+10 | 0.119357E+11 | 0.00 | 0.414470E+10 | 0.00 | 0.00 | 0.991580E+09 | 0.00 | 0.00 | 0.00 | 0.222318E+10 | 0.00 |
June | 0.408524E+11 | 0.773624E+10 | 0.118862E+11 | 0.00 | 0.462785E+10 | 0.00 | 0.00 | 0.666059E+10 | 0.00 | 0.00 | 0.00 | 0.211127E+10 | 0.00 |
July | 0.401034E+11 | 0.823124E+10 | 0.115358E+11 | 0.00 | 0.559970E+10 | 0.00 | 0.00 | 0.127480E+11 | 0.00 | 0.00 | 0.00 | 0.209402E+10 | 0.00 |
August | 0.423649E+11 | 0.908926E+10 | 0.123357E+11 | 0.00 | 0.611043E+10 | 0.00 | 0.00 | 0.129984E+11 | 0.00 | 0.00 | 0.00 | 0.213469E+10 | 0.00 |
September | 0.397216E+11 | 0.987655E+10 | 0.114862E+11 | 0.00 | 0.424501E+10 | 0.00 | 0.00 | 0.442400E+10 | 0.00 | 0.00 | 0.00 | 0.205993E+10 | 0.00 |
October | 0.401034E+11 | 0.113851E+11 | 0.115358E+11 | 0.00 | 0.397824E+10 | 0.00 | 0.00 | 0.711859E+09 | 0.00 | 0.00 | 0.00 | 0.215958E+10 | 0.00 |
November | 0.385909E+11 | 0.120546E+11 | 0.110862E+11 | 0.00 | 0.474729E+10 | 0.00 | 0.00 | 6133313.49 | 0.00 | 0.00 | 0.00 | 0.215207E+10 | 0.00 |
December | 0.401034E+11 | 0.130163E+11 | 0.115358E+11 | 0.00 | 0.608909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228688E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123365E+12 | 0.139282E+12 | 0.617032E+11 | 0.00 | 0.386350E+11 | 0.262562E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.773624E+10 | 0.105871E+11 | 0.00 | 0.397824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205993E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.130163E+11 | 0.123357E+11 | 0.00 | 0.647962E+10 | 0.00 | 0.00 | 0.129984E+11 | 0.00 | 0.00 | 0.00 | 0.237501E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.230887E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.219621E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.775222E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.141489E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.369890E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.646957E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.617935E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.154590E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759580E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.230887E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4507.87 | 04-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4507.87 | 08-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4507.87 | 16-MAR-09:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4507.87 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4006.83 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6312.13 | 01-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6312.13 | 03-JUL-11:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6312.13 | 01-AUG-09:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6312.13 | 01-SEP-10:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4006.83 | 03-OCT-12:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4507.87 | 24-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4507.87 | 09-DEC-08:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4006.83 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6312.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2535.31 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2540.82 | 10-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2508.38 | 01-MAR-12:50 | 0.00 |
April | 1332.41 | 07-APR-15:00 | 0.00 | 0.00 | 0.00 | 2346.20 | 01-APR-11:00 | 0.00 |
May | 10130.56 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 | 2050.90 | 02-MAY-11:09 | 0.00 |
June | 19015.50 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 1798.46 | 01-JUN-11:09 | 0.00 |
July | 17874.13 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 1777.66 | 01-JUL-11:30 | 0.00 |
August | 18748.35 | 16-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1769.41 | 31-AUG-11:39 | 0.00 |
September | 13595.77 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1783.58 | 30-SEP-11:09 | 0.00 |
October | 5150.10 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 1812.49 | 30-OCT-11:09 | 0.00 |
November | 378.49 | 04-NOV-13:39 | 0.00 | 0.00 | 0.00 | 2171.33 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2417.90 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1769.41 | 0.00 | ||
Maximum of Months | 19015.50 | 0.00 | 0.00 | 0.00 | 2540.82 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55761.24 | 14-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52275.79 | 04-FEB-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52173.67 | 16-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52758.42 | 07-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4006.83 | 0.00 | 0.00 | 1216.06 | 0.00 |
May | 61596.81 | 31-MAY-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4006.83 | 0.00 | 0.00 | 10130.56 | 0.00 |
June | 72106.06 | 19-JUN-12:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6312.13 | 0.00 | 0.00 | 18310.97 | 0.00 |
July | 71659.45 | 08-JUL-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6312.13 | 0.00 | 0.00 | 17874.13 | 0.00 |
August | 72406.07 | 04-AUG-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6312.13 | 0.00 | 0.00 | 18626.83 | 0.00 |
September | 67071.34 | 14-SEP-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6312.13 | 0.00 | 0.00 | 13317.02 | 0.00 |
October | 56641.13 | 04-OCT-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4006.83 | 0.00 | 0.00 | 5150.10 | 0.00 |
November | 55754.00 | 30-NOV-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55759.42 | 30-DEC-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4507.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52173.67 | 31660.41 | 10112.62 | 0.00 | 0.00 | 4006.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72406.07 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6312.13 | 0.00 | 0.00 | 18626.83 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 339635.45 | 01-JAN-23:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 376336.14 | 06-FEB-00:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 232471.44 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 75615.71 | 02-APR-05:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 21686.94 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 24934.06 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 228592.69 | 23-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 326571.32 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 376336.14 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.67 | 16.75 | 9.33 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22.50 | 16.69 | 9.00 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10.17 | 19.06 | 8.83 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.00 | 19.77 | 5.67 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.00 | 20.42 | 1.00 | 20.42 | 3.00 | 24.52 | 0.17 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 24.58 | 0.67 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 24.62 | 1.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 24.66 | 1.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 24.55 | 0.67 | 24.49 |
October | 0.83 | 20.44 | 0.83 | 20.44 | 0.67 | 24.52 | 0.00 | 0.00 |
November | 7.33 | 19.46 | 6.67 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.00 | 18.50 | 8.50 | 19.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.50 | 17.82 | 49.83 | 19.61 | 116.17 | 24.62 | 3.67 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.50 | 20.44 | 9.33 | 20.44 | 45.33 | 24.66 | 1.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.33 | 13.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 107.00 | 13.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74.50 | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22.50 | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 14.99 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.37 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.36 | 0.00 | 0.00 |
October | 0.33 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62.33 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107.33 | 14.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 491.50 | 14.19 | 0.00 | 33.17 | 27.45 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.33 | 14.99 | 0.00 | 0.00 | 14.00 | 27.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.15 | 307.50 | 21.08 | 307.50 | 21.08 |
April | 300.00 | 21.85 | 193.00 | 21.12 | 193.00 | 21.12 |
May | 279.33 | 23.10 | 38.33 | 22.11 | 24.83 | 21.14 |
June | 22.00 | 23.85 | 224.83 | 23.90 | 0.67 | 23.89 |
July | 3.33 | 23.90 | 297.67 | 23.91 | 3.33 | 23.90 |
August | 1.83 | 23.88 | 294.17 | 23.91 | 1.33 | 23.90 |
September | 79.67 | 23.69 | 147.50 | 23.90 | 1.33 | 23.90 |
October | 231.17 | 22.92 | 56.33 | 22.17 | 39.83 | 21.45 |
November | 288.00 | 21.40 | 228.33 | 21.09 | 228.33 | 21.09 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 2405.33 | 21.74 | 2663.67 | 22.13 | 1676.17 | 21.09 |
Minimum of Months | 1.83 | 21.04 | 38.33 | 21.04 | 0.67 | 21.04 |
Maximum of Months | 324.00 | 23.90 | 307.50 | 23.91 | 307.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.345253E+09 | 94416091.14 | 42.92 | 0.317365E+09 | 27888399.23 | 0.00 | 0.27 | 07-APR-16:00 | 0.00 | 01-APR-00:10 | 4842.19 | 07-APR-16:00 | 4547.01 | 07-APR-16:00 | 602.55 | 10-APR-09:50 | 1332.41 | 07-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.233281E+10 | 0.632543E+09 | 189.04 | 0.207464E+10 | 0.258167E+09 | 0.00 | 1.00 | 30-MAY-00:02 | 0.00 | 01-MAY-00:10 | 21450.02 | 30-MAY-00:02 | 18374.85 | 30-MAY-17:43 | 5056.78 | 31-MAY-17:10 | 5039.85 | 30-MAY-00:02 | 0.00 | 01-MAY-00:10 |
June | 0.974340E+10 | 0.261769E+10 | 412.25 | 0.767027E+10 | 0.207313E+10 | 0.00 | 1.00 | 01-JUN-17:43 | 0.00 | 01-JUN-00:10 | 25082.20 | 19-JUN-00:01 | 19911.59 | 05-JUN-00:03 | 11205.46 | 19-JUN-00:06 | 5663.47 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.143565E+11 | 0.386638E+10 | 491.36 | 0.106835E+11 | 0.367300E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:05 | 25625.41 | 31-JUL-00:01 | 19209.07 | 11-JUL-17:08 | 12282.91 | 24-JUL-00:04 | 5872.29 | 10-JUL-00:01 | 0.00 | 01-JUL-00:05 |
August | 0.145440E+11 | 0.397246E+10 | 527.69 | 0.116237E+11 | 0.292032E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:15 | 24296.63 | 28-AUG-00:01 | 19819.77 | 25-AUG-18:23 | 9152.70 | 07-AUG-00:05 | 5638.20 | 04-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.777713E+10 | 0.207701E+10 | 367.48 | 0.641423E+10 | 0.136290E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:15 | 22942.67 | 05-SEP-00:01 | 19851.99 | 11-SEP-00:02 | 7939.74 | 13-SEP-17:10 | 5313.23 | 05-SEP-00:01 | 0.00 | 01-SEP-00:10 |
October | 0.237714E+10 | 0.633320E+09 | 173.22 | 0.188255E+10 | 0.494596E+09 | 0.00 | 0.62 | 04-OCT-17:15 | 0.00 | 01-OCT-00:10 | 11568.71 | 05-OCT-17:15 | 8898.32 | 04-OCT-17:15 | 2953.01 | 05-OCT-21:03 | 3066.82 | 05-OCT-17:15 | 0.00 | 01-OCT-00:10 |
November | 22219521.61 | 6133313.49 | 6.67 | 20986639.45 | 1232882.16 | 0.00 | 0.08 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 1375.08 | 04-NOV-13:40 | 1279.61 | 04-NOV-13:40 | 123.06 | 04-NOV-15:00 | 378.49 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.514984E+11 | 0.139000E+11 | 2210.63 | 0.406872E+11 | 0.108112E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.145440E+11 | 0.397246E+10 | 527.69 | 0.116237E+11 | 0.367300E+10 | 0.00 | 1.00 | 0.00 | 25625.41 | 19911.59 | 12282.91 | 5872.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.121913E+10 | 0.359038E+09 | 23.58 | 0.100979E+10 | 0.209340E+09 | 0.00 | 0.52 | 29-MAY-12:10 | 0.00 | 01-MAY-00:10 | 27308.38 | 29-MAY-12:10 | 24612.76 | 29-MAY-12:10 | 6324.37 | 31-MAY-13:40 | 8590.20 | 29-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.140580E+11 | 0.404290E+10 | 230.46 | 0.100688E+11 | 0.398920E+10 | 0.00 | 1.00 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 | 74585.44 | 25-JUN-13:33 | 54687.90 | 22-JUN-17:08 | 32806.82 | 25-JUN-12:53 | 19089.67 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.312310E+11 | 0.888165E+10 | 342.19 | 0.207075E+11 | 0.105235E+11 | 0.00 | 1.00 | 02-JUL-12:43 | 0.00 | 01-JUL-00:05 | 75432.11 | 30-JUL-11:33 | 57759.31 | 11-JUL-17:08 | 34477.07 | 20-JUL-18:23 | 19188.18 | 09-JUL-12:43 | 0.00 | 01-JUL-00:05 |
August | 0.313332E+11 | 0.902590E+10 | 346.34 | 0.225839E+11 | 0.874933E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:10 | 75225.65 | 03-AUG-17:08 | 60224.15 | 20-AUG-13:23 | 34442.94 | 03-AUG-17:08 | 19226.66 | 04-AUG-19:43 | 0.00 | 01-AUG-00:10 |
September | 0.821643E+10 | 0.234698E+10 | 166.44 | 0.618551E+10 | 0.203092E+10 | 0.00 | 1.00 | 04-SEP-12:03 | 0.00 | 01-SEP-00:10 | 66219.89 | 04-SEP-12:03 | 54011.29 | 04-SEP-13:23 | 24799.43 | 07-SEP-17:10 | 17012.68 | 04-SEP-12:03 | 0.00 | 01-SEP-00:10 |
October | 0.275699E+09 | 78539695.52 | 11.83 | 0.190563E+09 | 85135842.80 | 0.00 | 0.18 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 | 10733.11 | 04-OCT-14:00 | 7740.84 | 04-OCT-14:00 | 3106.72 | 05-OCT-14:00 | 3057.62 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.863334E+11 | 0.247350E+11 | 1120.85 | 0.607460E+11 | 0.255874E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.313332E+11 | 0.902590E+10 | 346.34 | 0.225839E+11 | 0.105235E+11 | 0.00 | 1.00 | 0.00 | 75432.11 | 60224.15 | 34477.07 | 19226.66 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.61 | 27.37 | 39.24 | 30.91 | 168.87 | 0.00 | 0.00 | 744.00 |
February | 97.63 | 42.83 | 54.80 | 53.25 | 172.60 | 0.00 | 0.00 | 672.00 |
March | 145.28 | 67.36 | 77.92 | 115.02 | 103.23 | 0.00 | 0.00 | 744.00 |
April | 157.61 | 67.29 | 90.32 | 144.40 | 73.12 | 0.00 | 0.00 | 720.00 |
May | 184.18 | 69.97 | 114.21 | 186.62 | 50.73 | 0.00 | 0.00 | 744.00 |
June | 201.57 | 81.47 | 120.10 | 224.61 | 34.36 | 0.00 | 0.00 | 720.00 |
July | 188.55 | 70.99 | 117.55 | 227.15 | 19.52 | 0.00 | 0.00 | 744.00 |
August | 208.47 | 96.43 | 112.04 | 253.58 | 27.30 | 0.00 | 0.00 | 744.00 |
September | 148.32 | 64.80 | 83.51 | 154.61 | 53.06 | 0.00 | 0.00 | 720.00 |
October | 146.50 | 71.12 | 75.38 | 138.64 | 82.97 | 0.00 | 0.00 | 744.00 |
November | 69.10 | 20.05 | 49.05 | 37.02 | 112.56 | 0.00 | 0.00 | 720.00 |
December | 61.37 | 26.59 | 34.78 | 29.75 | 151.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 139.89 | 58.99 | 80.90 | 133.54 | 87.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 61.37 | 20.05 | 34.78 | 29.75 | 19.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 208.47 | 96.43 | 120.10 | 253.58 | 172.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.61 | 27.37 | 39.24 | 30.91 | 168.87 | 0.00 | 0.00 | 744.00 |
February | 97.63 | 42.83 | 54.80 | 53.25 | 172.60 | 0.00 | 0.00 | 672.00 |
March | 145.28 | 67.36 | 77.92 | 115.02 | 103.23 | 0.00 | 0.00 | 744.00 |
April | 157.61 | 67.29 | 90.32 | 144.40 | 73.12 | 0.00 | 0.00 | 720.00 |
May | 184.18 | 69.97 | 114.21 | 186.62 | 50.73 | 0.00 | 0.00 | 744.00 |
June | 201.57 | 81.47 | 120.10 | 224.61 | 34.36 | 0.00 | 0.00 | 720.00 |
July | 188.55 | 70.99 | 117.55 | 227.15 | 19.52 | 0.00 | 0.00 | 744.00 |
August | 208.47 | 96.43 | 112.04 | 253.58 | 27.30 | 0.00 | 0.00 | 744.00 |
September | 148.32 | 64.80 | 83.51 | 154.61 | 53.06 | 0.00 | 0.00 | 720.00 |
October | 146.50 | 71.12 | 75.38 | 138.64 | 82.97 | 0.00 | 0.00 | 744.00 |
November | 69.10 | 20.05 | 49.05 | 37.02 | 112.56 | 0.00 | 0.00 | 720.00 |
December | 61.37 | 26.59 | 34.78 | 29.75 | 151.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 139.89 | 58.99 | 80.90 | 133.54 | 87.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 61.37 | 20.05 | 34.78 | 29.75 | 19.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 208.47 | 96.43 | 120.10 | 253.58 | 172.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.76 | 0.00 | 18.76 | 0.37 | 105.59 | 0.00 | 0.00 | 744.00 |
February | 25.68 | 0.00 | 25.68 | 1.52 | 109.96 | 0.00 | 0.00 | 672.00 |
March | 35.62 | 0.00 | 35.62 | 9.83 | 65.22 | 0.00 | 0.00 | 744.00 |
April | 42.80 | 0.14 | 42.66 | 23.56 | 44.06 | 0.00 | 0.00 | 720.00 |
May | 56.97 | 2.06 | 54.91 | 42.53 | 29.11 | 0.00 | 0.00 | 744.00 |
June | 60.07 | 3.12 | 56.95 | 56.08 | 19.17 | 0.00 | 0.00 | 720.00 |
July | 58.29 | 2.20 | 56.08 | 65.30 | 11.09 | 0.00 | 0.00 | 744.00 |
August | 51.62 | 0.70 | 50.92 | 57.95 | 15.74 | 0.00 | 0.00 | 744.00 |
September | 38.86 | 0.02 | 38.85 | 30.63 | 31.81 | 0.00 | 0.00 | 720.00 |
October | 33.61 | 0.00 | 33.61 | 18.18 | 50.18 | 0.00 | 0.00 | 744.00 |
November | 23.58 | 0.00 | 23.58 | 4.98 | 69.07 | 0.00 | 0.00 | 720.00 |
December | 16.37 | 0.00 | 16.37 | 0.42 | 95.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.59 | 0.69 | 37.90 | 26.12 | 53.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.37 | 0.00 | 16.37 | 0.37 | 11.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.07 | 3.12 | 56.95 | 65.30 | 109.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.76 | 0.00 | 18.76 | 0.37 | 105.59 | 0.00 | 0.00 | 744.00 |
February | 25.68 | 0.00 | 25.68 | 1.52 | 109.96 | 0.00 | 0.00 | 672.00 |
March | 35.62 | 0.00 | 35.62 | 9.83 | 65.22 | 0.00 | 0.00 | 744.00 |
April | 42.80 | 0.14 | 42.66 | 23.56 | 44.06 | 0.00 | 0.00 | 720.00 |
May | 56.97 | 2.06 | 54.91 | 42.53 | 29.11 | 0.00 | 0.00 | 744.00 |
June | 60.07 | 3.12 | 56.94 | 56.08 | 19.17 | 0.00 | 0.00 | 720.00 |
July | 58.28 | 2.20 | 56.08 | 65.30 | 11.09 | 0.00 | 0.00 | 744.00 |
August | 51.62 | 0.70 | 50.92 | 57.95 | 15.74 | 0.00 | 0.00 | 744.00 |
September | 38.86 | 0.02 | 38.85 | 30.63 | 31.81 | 0.00 | 0.00 | 720.00 |
October | 33.61 | 0.00 | 33.61 | 18.18 | 50.18 | 0.00 | 0.00 | 744.00 |
November | 23.58 | 0.00 | 23.58 | 4.98 | 69.07 | 0.00 | 0.00 | 720.00 |
December | 16.37 | 0.00 | 16.37 | 0.42 | 95.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.59 | 0.69 | 37.90 | 26.12 | 53.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.37 | 0.00 | 16.37 | 0.37 | 11.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.07 | 3.12 | 56.94 | 65.30 | 109.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 39.67 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.00 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.86 | 43.83 | 47.67 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.17 | 38.87 | 19.67 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.33 | 40.53 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.07 | 35.86 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.40 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 2.33 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.33 | 62.34 | 80.00 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.17 | 62.84 | 26.33 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.86 | 249.83 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178418E+09 | 73308484.09 | 0.105110E+09 | 82786611.83 | 0.452306E+09 |
February | 0.236178E+09 | 0.103613E+09 | 0.132565E+09 | 0.128817E+09 | 0.417553E+09 |
March | 0.389106E+09 | 0.180404E+09 | 0.208702E+09 | 0.308060E+09 | 0.276487E+09 |
April | 0.408518E+09 | 0.174412E+09 | 0.234106E+09 | 0.374281E+09 | 0.189535E+09 |
May | 0.493311E+09 | 0.187406E+09 | 0.305905E+09 | 0.499853E+09 | 0.135876E+09 |
June | 0.522467E+09 | 0.211167E+09 | 0.311300E+09 | 0.582192E+09 | 89056629.64 |
July | 0.505007E+09 | 0.190147E+09 | 0.314859E+09 | 0.608393E+09 | 52280674.04 |
August | 0.558379E+09 | 0.258280E+09 | 0.300099E+09 | 0.679186E+09 | 73109730.79 |
September | 0.384442E+09 | 0.167972E+09 | 0.216469E+09 | 0.400745E+09 | 0.137522E+09 |
October | 0.392388E+09 | 0.190482E+09 | 0.201906E+09 | 0.371324E+09 | 0.222216E+09 |
November | 0.179108E+09 | 51967625.15 | 0.127141E+09 | 95960111.79 | 0.291765E+09 |
December | 0.164375E+09 | 71221879.01 | 93152951.82 | 79687803.72 | 0.406792E+09 |
Annual Sum or Average | 0.441170E+10 | 0.186038E+10 | 0.255131E+10 | 0.421128E+10 | 0.274450E+10 |
Minimum of Months | 0.164375E+09 | 51967625.15 | 93152951.82 | 79687803.72 | 52280674.04 |
Maximum of Months | 0.558379E+09 | 0.258280E+09 | 0.314859E+09 | 0.679186E+09 | 0.452306E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178418E+09 | 73308484.09 | 0.105110E+09 | 82786611.83 | 0.452306E+09 |
February | 0.236178E+09 | 0.103613E+09 | 0.132565E+09 | 0.128817E+09 | 0.417553E+09 |
March | 0.389106E+09 | 0.180404E+09 | 0.208702E+09 | 0.308060E+09 | 0.276487E+09 |
April | 0.408518E+09 | 0.174412E+09 | 0.234106E+09 | 0.374281E+09 | 0.189535E+09 |
May | 0.493311E+09 | 0.187406E+09 | 0.305905E+09 | 0.499853E+09 | 0.135876E+09 |
June | 0.522467E+09 | 0.211167E+09 | 0.311300E+09 | 0.582192E+09 | 89056629.64 |
July | 0.505007E+09 | 0.190147E+09 | 0.314859E+09 | 0.608393E+09 | 52280674.04 |
August | 0.558379E+09 | 0.258280E+09 | 0.300099E+09 | 0.679186E+09 | 73109730.79 |
September | 0.384442E+09 | 0.167972E+09 | 0.216469E+09 | 0.400745E+09 | 0.137522E+09 |
October | 0.392388E+09 | 0.190482E+09 | 0.201906E+09 | 0.371324E+09 | 0.222216E+09 |
November | 0.179108E+09 | 51967625.15 | 0.127141E+09 | 95960111.79 | 0.291765E+09 |
December | 0.164375E+09 | 71221879.01 | 93152951.82 | 79687803.72 | 0.406792E+09 |
Annual Sum or Average | 0.441170E+10 | 0.186038E+10 | 0.255131E+10 | 0.421128E+10 | 0.274450E+10 |
Minimum of Months | 0.164375E+09 | 51967625.15 | 93152951.82 | 79687803.72 | 52280674.04 |
Maximum of Months | 0.558379E+09 | 0.258280E+09 | 0.314859E+09 | 0.679186E+09 | 0.452306E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50259931.64 | 0.00 | 50259931.64 | 998759.41 | 0.282811E+09 |
February | 62122661.82 | 0.00 | 62122661.82 | 3685092.72 | 0.266021E+09 |
March | 95408554.48 | 5219.70 | 95403334.78 | 26337816.19 | 0.174680E+09 |
April | 0.110929E+09 | 360036.37 | 0.110569E+09 | 61062280.86 | 0.114215E+09 |
May | 0.152584E+09 | 5506151.45 | 0.147077E+09 | 0.113910E+09 | 77967484.88 |
June | 0.155696E+09 | 8094098.49 | 0.147602E+09 | 0.145366E+09 | 49682029.02 |
July | 0.156111E+09 | 5902475.21 | 0.150209E+09 | 0.174911E+09 | 29702986.77 |
August | 0.138254E+09 | 1863692.65 | 0.136390E+09 | 0.155223E+09 | 42158329.74 |
September | 0.100735E+09 | 45625.88 | 0.100690E+09 | 79385777.19 | 82459681.30 |
October | 90030929.43 | 0.00 | 90030929.43 | 48686167.28 | 0.134399E+09 |
November | 61110922.58 | 0.00 | 61110922.58 | 12918448.51 | 0.179026E+09 |
December | 43840031.46 | 0.00 | 43840031.46 | 1134488.45 | 0.254617E+09 |
Annual Sum or Average | 0.121708E+10 | 21777299.75 | 0.119530E+10 | 0.823619E+09 | 0.168774E+10 |
Minimum of Months | 43840031.46 | 0.00 | 43840031.46 | 998759.41 | 29702986.77 |
Maximum of Months | 0.156111E+09 | 8094098.49 | 0.150209E+09 | 0.174911E+09 | 0.282811E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50258286.71 | 0.00 | 50258286.71 | 998506.41 | 0.282811E+09 |
February | 62120762.55 | 0.00 | 62120762.55 | 3684723.85 | 0.266022E+09 |
March | 95405667.84 | 5219.45 | 95400448.38 | 26336077.57 | 0.174681E+09 |
April | 0.110926E+09 | 360019.50 | 0.110566E+09 | 61059686.31 | 0.114215E+09 |
May | 0.152579E+09 | 5505893.37 | 0.147073E+09 | 0.113906E+09 | 77967199.09 |
June | 0.155691E+09 | 8093719.11 | 0.147597E+09 | 0.145361E+09 | 49681588.76 |
July | 0.156107E+09 | 5902198.55 | 0.150204E+09 | 0.174906E+09 | 29702469.59 |
August | 0.138250E+09 | 1863605.30 | 0.136387E+09 | 0.155220E+09 | 42157605.08 |
September | 0.100732E+09 | 45623.74 | 0.100687E+09 | 79383093.70 | 82459063.41 |
October | 90028275.96 | 0.00 | 90028275.96 | 48684031.13 | 0.134398E+09 |
November | 61108919.30 | 0.00 | 61108919.30 | 12917431.78 | 0.179026E+09 |
December | 43838626.34 | 0.00 | 43838626.34 | 1134322.18 | 0.254617E+09 |
Annual Sum or Average | 0.121705E+10 | 21776279.02 | 0.119527E+10 | 0.823590E+09 | 0.168774E+10 |
Minimum of Months | 43838626.34 | 0.00 | 43838626.34 | 998506.41 | 29702469.59 |
Maximum of Months | 0.156107E+09 | 8093719.11 | 0.150204E+09 | 0.174906E+09 | 0.282811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73708287.98 | 0.249943E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118948E+09 | 0.238428E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254949E+09 | 0.138711E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318442E+09 | 0.113612E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428993E+09 | 0.104122E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446675E+09 | 0.105049E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458202E+09 | 96035949.28 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469258E+09 | 0.126961E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287931E+09 | 0.144452E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249982E+09 | 0.166962E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114477E+09 | 0.162889E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 0.209187E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328944E+10 | 0.185635E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67872050.96 | 96035949.28 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469258E+09 | 0.249943E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.97 | 539.33 | 170.76 | 54.74 | 116.02 | 0.00 | 0.00 |
February | 96.93 | 552.51 | 246.61 | 85.66 | 160.95 | 0.00 | 0.00 |
March | 241.62 | 328.82 | 361.79 | 134.71 | 227.08 | 0.00 | 0.00 |
April | 333.49 | 231.96 | 400.81 | 134.86 | 265.95 | 0.00 | 0.00 |
May | 456.85 | 158.23 | 482.30 | 144.05 | 338.25 | 0.00 | 0.00 |
June | 560.67 | 106.34 | 523.27 | 169.18 | 354.09 | 0.00 | 0.00 |
July | 584.38 | 60.70 | 493.66 | 146.39 | 347.27 | 0.00 | 0.00 |
August | 622.76 | 85.77 | 520.18 | 194.25 | 325.93 | 0.00 | 0.00 |
September | 369.12 | 168.39 | 374.36 | 129.64 | 244.72 | 0.00 | 0.00 |
October | 310.11 | 262.77 | 360.23 | 142.24 | 217.99 | 0.00 | 0.00 |
November | 79.21 | 358.46 | 185.35 | 40.10 | 145.26 | 0.00 | 0.00 |
December | 51.26 | 484.80 | 155.48 | 53.18 | 102.29 | 0.00 | 0.00 |
Annual Sum or Average | 314.82 | 276.60 | 356.97 | 119.37 | 237.61 | 0.00 | 0.00 |
Minimum of Months | 51.26 | 60.70 | 155.48 | 40.10 | 102.29 | 0.00 | 0.00 |
Maximum of Months | 622.76 | 552.51 | 523.27 | 194.25 | 354.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.20 | 933.18 | 320.75 | 132.85 | 187.90 | 0.00 | 0.00 |
February | 491.68 | 985.57 | 522.07 | 282.91 | 239.16 | 0.00 | 0.00 |
March | 951.87 | 517.89 | 779.55 | 432.11 | 347.44 | 0.00 | 0.00 |
April | 1228.56 | 438.32 | 962.37 | 541.67 | 420.70 | 0.00 | 0.00 |
May | 1601.67 | 388.75 | 1213.53 | 657.13 | 556.40 | 0.00 | 0.00 |
June | 1723.28 | 405.28 | 1325.51 | 753.43 | 572.08 | 0.00 | 0.00 |
July | 1710.73 | 358.55 | 1278.57 | 695.84 | 582.72 | 0.00 | 0.00 |
August | 1752.01 | 474.02 | 1312.32 | 825.81 | 486.51 | 0.00 | 0.00 |
September | 1110.84 | 557.30 | 900.53 | 525.57 | 374.96 | 0.00 | 0.00 |
October | 933.32 | 623.36 | 751.92 | 439.69 | 312.24 | 0.00 | 0.00 |
November | 441.65 | 628.43 | 408.47 | 162.90 | 245.57 | 0.00 | 0.00 |
December | 253.40 | 781.01 | 285.10 | 131.19 | 153.91 | 0.00 | 0.00 |
Annual Sum or Average | 1043.07 | 588.64 | 840.32 | 466.25 | 374.07 | 0.00 | 0.00 |
Minimum of Months | 253.40 | 358.55 | 285.10 | 131.19 | 153.91 | 0.00 | 0.00 |
Maximum of Months | 1752.01 | 985.57 | 1325.51 | 825.81 | 582.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141884E+09 | 0.144455E+10 | 0.457355E+09 | 0.146617E+09 | 0.310738E+09 | 0.00 | 0.00 |
February | 0.234488E+09 | 0.133663E+10 | 0.596599E+09 | 0.207226E+09 | 0.389373E+09 | 0.00 | 0.00 |
March | 0.647156E+09 | 0.880698E+09 | 0.969026E+09 | 0.360819E+09 | 0.608207E+09 | 0.00 | 0.00 |
April | 0.864412E+09 | 0.601230E+09 | 0.103889E+10 | 0.349545E+09 | 0.689346E+09 | 0.00 | 0.00 |
May | 0.122363E+10 | 0.423800E+09 | 0.129179E+10 | 0.385824E+09 | 0.905961E+09 | 0.00 | 0.00 |
June | 0.145327E+10 | 0.275634E+09 | 0.135632E+10 | 0.438523E+09 | 0.917799E+09 | 0.00 | 0.00 |
July | 0.156521E+10 | 0.162578E+09 | 0.132223E+10 | 0.392099E+09 | 0.930132E+09 | 0.00 | 0.00 |
August | 0.166801E+10 | 0.229734E+09 | 0.139326E+10 | 0.520288E+09 | 0.872974E+09 | 0.00 | 0.00 |
September | 0.956753E+09 | 0.436456E+09 | 0.970351E+09 | 0.336036E+09 | 0.634315E+09 | 0.00 | 0.00 |
October | 0.830602E+09 | 0.703813E+09 | 0.964835E+09 | 0.380964E+09 | 0.583871E+09 | 0.00 | 0.00 |
November | 0.205301E+09 | 0.929126E+09 | 0.480437E+09 | 0.103935E+09 | 0.376501E+09 | 0.00 | 0.00 |
December | 0.137307E+09 | 0.129848E+10 | 0.416428E+09 | 0.142444E+09 | 0.273985E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.992803E+10 | 0.872273E+10 | 0.112575E+11 | 0.376432E+10 | 0.749320E+10 | 0.00 | 0.00 |
Minimum of Months | 0.137307E+09 | 0.162578E+09 | 0.416428E+09 | 0.103935E+09 | 0.273985E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166801E+10 | 0.144455E+10 | 0.139326E+10 | 0.520288E+09 | 0.930132E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.737083E+09 | 0.249942E+10 | 0.859096E+09 | 0.355814E+09 | 0.503282E+09 | 0.00 | 0.00 |
February | 0.118947E+10 | 0.238428E+10 | 0.126300E+10 | 0.684425E+09 | 0.578574E+09 | 0.00 | 0.00 |
March | 0.254949E+10 | 0.138711E+10 | 0.208795E+10 | 0.115737E+10 | 0.930579E+09 | 0.00 | 0.00 |
April | 0.318442E+10 | 0.113612E+10 | 0.249446E+10 | 0.140400E+10 | 0.109046E+10 | 0.00 | 0.00 |
May | 0.428992E+10 | 0.104122E+10 | 0.325032E+10 | 0.176006E+10 | 0.149026E+10 | 0.00 | 0.00 |
June | 0.446675E+10 | 0.105049E+10 | 0.343572E+10 | 0.195289E+10 | 0.148283E+10 | 0.00 | 0.00 |
July | 0.458202E+10 | 0.960352E+09 | 0.342451E+10 | 0.186374E+10 | 0.156077E+10 | 0.00 | 0.00 |
August | 0.469258E+10 | 0.126961E+10 | 0.351491E+10 | 0.221184E+10 | 0.130307E+10 | 0.00 | 0.00 |
September | 0.287931E+10 | 0.144452E+10 | 0.233417E+10 | 0.136229E+10 | 0.971886E+09 | 0.00 | 0.00 |
October | 0.249982E+10 | 0.166962E+10 | 0.201396E+10 | 0.117766E+10 | 0.836299E+09 | 0.00 | 0.00 |
November | 0.114476E+10 | 0.162889E+10 | 0.105876E+10 | 0.422237E+09 | 0.636519E+09 | 0.00 | 0.00 |
December | 0.678719E+09 | 0.209187E+10 | 0.763610E+09 | 0.351377E+09 | 0.412234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328943E+11 | 0.185635E+11 | 0.265005E+11 | 0.147037E+11 | 0.117968E+11 | 0.00 | 0.00 |
Minimum of Months | 0.678719E+09 | 0.960352E+09 | 0.763610E+09 | 0.351377E+09 | 0.412234E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469258E+10 | 0.249942E+10 | 0.351491E+10 | 0.221184E+10 | 0.156077E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.103138E+10 | -874659010.9 | 0.00 | 0.00 | 744.00 | 0.00 | -156720503.0 | 58.99 | 0.00 | 0.00 |
February | 0.953011E+09 | -811511127.0 | 0.00 | 0.00 | 672.00 | 0.00 | -141499584.5 | 58.99 | 0.00 | 0.00 |
March | 0.108129E+10 | -927072095.0 | 0.00 | 0.00 | 744.00 | 0.00 | -154216887.0 | 58.99 | 0.00 | 0.00 |
April | 0.961034E+09 | -817014882.0 | 0.00 | 0.00 | 720.00 | 0.00 | -144019345.7 | 58.99 | 0.00 | 0.00 |
May | 0.929621E+09 | -790963236.9 | 0.00 | 0.00 | 744.00 | 0.00 | -138657968.3 | 58.99 | 0.00 | 0.00 |
June | 0.859199E+09 | -730921984.5 | 0.00 | 0.00 | 720.00 | 0.00 | -128277439.8 | 58.99 | 0.00 | 0.00 |
July | 0.800194E+09 | -669097572.9 | 0.00 | 0.00 | 744.00 | 0.00 | -131096142.8 | 58.99 | 0.00 | 0.00 |
August | 0.840614E+09 | -708605838.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132008141.7 | 58.99 | 0.00 | 0.00 |
September | 0.807861E+09 | -679569455.1 | 0.00 | 0.00 | 720.00 | 0.00 | -128291729.4 | 58.99 | 0.00 | 0.00 |
October | 0.866194E+09 | -726460864.0 | 0.00 | 0.00 | 744.00 | 0.00 | -139732992.8 | 58.99 | 0.00 | 0.00 |
November | 0.899852E+09 | -752096439.1 | 0.00 | 0.00 | 720.00 | 0.00 | -147755873.4 | 58.99 | 0.00 | 0.00 |
December | 0.993104E+09 | -836729811.5 | 0.00 | 0.00 | 744.00 | 0.00 | -156374001.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.110234E+11 | -.932470E+10 | 8760.00 | -.169865E+10 | 58.99 | |||||
Minimum of Months | 0.800194E+09 | -927072095.0 | 0.00 | 0.00 | 672.00 | 0.00 | -156720503.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.108129E+10 | -669097572.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128277439.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | ||||||||||
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.834432E+10 | 28225.01 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.826562E+10 | 28225.01 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506308E+10 | 28225.01 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200698E+10 | 28225.01 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237778E+09 | 28225.01 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275538E+09 | 28225.01 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340063E+10 | 28225.01 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.619267E+10 | 28225.01 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337866E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.834432E+10 | 28225.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532413E+11 | 89093.70 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.501946E+11 | 89093.70 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246265E+11 | 89093.70 | 01-MAR-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.671947E+10 | 89093.70 | 02-APR-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13442533.44 | 16713.57 | 01-MAY-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155791E+09 | 31675.46 | 31-OCT-05:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196006E+11 | 89093.70 | 14-NOV-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400492E+11 | 89093.70 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194601E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532413E+11 | 89093.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113921E+12 | 174408.96 | 01-JAN-20:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108657E+12 | 201647.31 | 06-FEB-00:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272823E+11 | 108585.40 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101705E+10 | 26919.18 | 02-APR-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225661E+11 | 114411.94 | 23-NOV-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.696837E+11 | 175212.77 | 31-DEC-21:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343128E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113921E+12 | 201647.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.345253E+09 | 0.317365E+09 | 4842.19 | 07-APR-16:00 | 4547.01 | 0.00 |
May | 0.00 | 0.00 | 0.233281E+10 | 0.207464E+10 | 21450.02 | 30-MAY-00:02 | 17757.82 | 0.00 |
June | 0.00 | 0.00 | 0.974340E+10 | 0.767027E+10 | 25082.20 | 19-JUN-00:01 | 14049.11 | 0.00 |
July | 0.00 | 0.00 | 0.143565E+11 | 0.106835E+11 | 25625.41 | 31-JUL-00:01 | 13886.31 | 0.00 |
August | 0.00 | 0.00 | 0.145440E+11 | 0.116237E+11 | 24296.63 | 28-AUG-00:01 | 15502.78 | 0.00 |
September | 0.00 | 0.00 | 0.777713E+10 | 0.641423E+10 | 22942.67 | 05-SEP-00:01 | 17990.28 | 0.00 |
October | 0.00 | 0.00 | 0.237714E+10 | 0.188255E+10 | 11568.71 | 05-OCT-17:15 | 8671.15 | 0.00 |
November | 0.00 | 0.00 | 22219521.61 | 20986639.45 | 1375.08 | 04-NOV-13:40 | 1279.61 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.514984E+11 | 0.406872E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145440E+11 | 0.116237E+11 | 25625.41 | 17990.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.121913E+10 | 0.100979E+10 | 27308.38 | 29-MAY-12:10 | 24612.76 | 0.00 |
June | 0.00 | 0.00 | 0.140580E+11 | 0.100688E+11 | 74585.44 | 25-JUN-13:33 | 41873.33 | 0.00 |
July | 0.00 | 0.00 | 0.312310E+11 | 0.207075E+11 | 75432.11 | 30-JUL-11:33 | 41633.60 | 0.00 |
August | 0.00 | 0.00 | 0.313332E+11 | 0.225839E+11 | 75225.65 | 03-AUG-17:08 | 40782.72 | 0.00 |
September | 0.00 | 0.00 | 0.821643E+10 | 0.618551E+10 | 66219.89 | 04-SEP-12:03 | 53506.27 | 0.00 |
October | 0.00 | 0.00 | 0.275699E+09 | 0.190563E+09 | 10733.11 | 04-OCT-14:00 | 7740.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.863334E+11 | 0.607460E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.313332E+11 | 0.225839E+11 | 75432.11 | 53506.27 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106237E+10 | 0.06 | 501.04 | 01-JAN-00:01 | 0.08 |
February | 0.985519E+09 | 0.06 | 501.04 | 01-FEB-00:02 | 0.08 |
March | 0.471130E+09 | 0.03 | 501.04 | 01-MAR-00:03 | 0.08 |
April | 41120075.91 | 0.00 | 501.04 | 01-APR-05:09 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.354433E+09 | 0.02 | 501.04 | 18-NOV-03:50 | 0.08 |
December | 0.105133E+10 | 0.06 | 501.04 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.396590E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106237E+10 | 0.06 | 501.04 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131119E+10 | 0.56 | 1208.55 | 19-JAN-11:30 | 0.94 |
February | 0.121215E+10 | 0.57 | 1208.55 | 01-FEB-07:10 | 0.94 |
March | 0.134194E+10 | 0.44 | 1208.55 | 01-MAR-08:40 | 0.94 |
April | 0.122030E+10 | 0.38 | 1208.55 | 01-APR-06:20 | 0.93 |
May | 0.126058E+10 | 0.38 | 1208.55 | 01-MAY-06:10 | 0.93 |
June | 0.138464E+10 | 0.56 | 1208.55 | 01-JUN-06:05 | 0.93 |
July | 0.145612E+10 | 0.65 | 1208.55 | 01-JUL-06:10 | 0.92 |
August | 0.155926E+10 | 0.69 | 1208.55 | 01-AUG-06:40 | 0.92 |
September | 0.130781E+10 | 0.51 | 1208.55 | 01-SEP-06:05 | 0.92 |
October | 0.120507E+10 | 0.36 | 1208.55 | 26-OCT-06:40 | 0.94 |
November | 0.118777E+10 | 0.40 | 1208.55 | 01-NOV-06:50 | 0.93 |
December | 0.125231E+10 | 0.43 | 1208.55 | 01-DEC-09:10 | 0.94 |
Annual Sum or Average | 0.156991E+11 | 0.49 | |||
Minimum of Months | 0.118777E+10 | 0.36 | 1208.55 | 0.92 | |
Maximum of Months | 0.155926E+10 | 0.69 | 1208.55 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410606E+10 | 0.79 | 2798.28 | 04-JAN-16:30 | 0.90 |
February | 0.378211E+10 | 0.78 | 2798.28 | 08-FEB-12:20 | 0.90 |
March | 0.366004E+10 | 0.73 | 2798.28 | 04-MAR-09:00 | 0.90 |
April | 0.296698E+10 | 0.51 | 2798.28 | 01-APR-12:50 | 0.90 |
May | 0.288412E+10 | 0.35 | 2798.28 | 30-MAY-15:20 | 0.89 |
June | 0.294888E+10 | 0.39 | 2798.28 | 14-JUN-16:00 | 0.88 |
July | 0.300272E+10 | 0.43 | 2798.28 | 01-JUL-15:20 | 0.89 |
August | 0.319199E+10 | 0.45 | 2798.28 | 03-AUG-06:40 | 0.88 |
September | 0.281123E+10 | 0.37 | 2798.28 | 01-SEP-10:20 | 0.89 |
October | 0.277317E+10 | 0.33 | 2798.28 | 04-OCT-12:30 | 0.89 |
November | 0.320510E+10 | 0.64 | 2798.28 | 06-NOV-07:50 | 0.90 |
December | 0.378546E+10 | 0.78 | 2798.28 | 04-DEC-11:40 | 0.90 |
Annual Sum or Average | 0.391179E+11 | 0.54 | |||
Minimum of Months | 0.277317E+10 | 0.33 | 2798.28 | 0.88 | |
Maximum of Months | 0.410606E+10 | 0.79 | 2798.28 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.21 | 0.00 |
February | 3.38 | 0.00 |
March | 2.28 | 0.00 |
April | 0.51 | 0.35 |
May | 0.50 | 5.00 |
June | 0.00 | 0.00 |
July | 0.16 | 0.00 |
August | 0.00 | 0.00 |
September | 0.50 | 3.33 |
October | 0.58 | 2.61 |
November | 1.79 | 0.15 |
December | 2.71 | 0.01 |
Annual Sum or Average | 15.63 | 0.39 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.38 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.36 | 0.00 |
February | 0.77 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.17 | 0.00 |
November | 0.00 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 1.34 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.77 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 1.33 | 0.00 |
July | 4.89 | 0.00 |
August | 4.32 | 0.00 |
September | 0.56 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.10 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.89 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131119E+10 | 0.120641E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121215E+10 | 0.118994E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134194E+10 | 0.737093E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.131471E+10 | 0.294100E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.189312E+10 | 0.349202E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.400234E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.532250E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.553172E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.338482E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183839E+10 | 0.407454E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119390E+10 | 0.496691E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125231E+10 | 0.903275E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.295991E+11 | 0.490317E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119390E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.553172E+10 | 0.120641E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.410606E+10 | 0.750745E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.378211E+10 | 0.706143E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.366004E+10 | 0.357256E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.296698E+10 | 0.992453E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.324316E+10 | 20687440.10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.699178E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.118844E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.122179E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.515822E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.285171E+10 | 0.239502E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.320510E+10 | 0.283521E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.378546E+10 | 0.576285E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.638529E+11 | 0.277580E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.285171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122179E+11 | 0.750745E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131119E+10 | 0.00 | 0.834432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121215E+10 | 0.00 | 0.826562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134194E+10 | 0.00 | 0.506308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122030E+10 | 0.345253E+09 | 0.200698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126058E+10 | 0.233281E+10 | 0.237778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138464E+10 | 0.974340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145612E+10 | 0.143565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155926E+10 | 0.145440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130781E+10 | 0.777713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120507E+10 | 0.237714E+10 | 0.275538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118777E+10 | 22219521.61 | 0.340063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125231E+10 | 0.00 | 0.619267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156991E+11 | 0.514984E+11 | 0.337866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155926E+10 | 0.145440E+11 | 0.834432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410606E+10 | 0.00 | 0.532413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378211E+10 | 0.00 | 0.501946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366004E+10 | 0.00 | 0.246265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296698E+10 | 0.00 | 0.671947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288412E+10 | 0.121913E+10 | 13442533.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294888E+10 | 0.140580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300272E+10 | 0.312310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319199E+10 | 0.313332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281123E+10 | 0.821643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277317E+10 | 0.275699E+09 | 0.155791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320510E+10 | 0.00 | 0.196006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378546E+10 | 0.00 | 0.400492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391179E+11 | 0.863334E+11 | 0.194601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410606E+10 | 0.313332E+11 | 0.532413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122030E+10 | 0.00 | 0.00 | 0.00 | 94416091.14 | 0.00 | 0.294100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126058E+10 | 0.00 | 0.00 | 0.00 | 0.632543E+09 | 0.00 | 0.349202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138464E+10 | 0.00 | 0.00 | 0.00 | 0.261769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145612E+10 | 0.00 | 0.00 | 0.00 | 0.386638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155926E+10 | 0.00 | 0.00 | 0.00 | 0.397246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130781E+10 | 0.00 | 0.00 | 0.00 | 0.207701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120507E+10 | 0.00 | 0.00 | 0.00 | 0.633320E+09 | 0.00 | 0.407454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118777E+10 | 0.00 | 0.00 | 0.00 | 6133313.49 | 0.00 | 0.496691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156991E+11 | 0.00 | 0.00 | 0.00 | 0.139000E+11 | 0.00 | 0.490317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155926E+10 | 0.00 | 0.00 | 0.00 | 0.397246E+10 | 0.00 | 0.120641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.410606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288412E+10 | 0.00 | 0.00 | 0.00 | 0.359038E+09 | 0.00 | 20687440.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294888E+10 | 0.00 | 0.00 | 0.00 | 0.404290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300272E+10 | 0.00 | 0.00 | 0.00 | 0.888165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319199E+10 | 0.00 | 0.00 | 0.00 | 0.902590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281123E+10 | 0.00 | 0.00 | 0.00 | 0.234698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277317E+10 | 0.00 | 0.00 | 0.00 | 78539695.52 | 0.00 | 0.239502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391179E+11 | 0.00 | 0.00 | 0.00 | 0.247350E+11 | 0.00 | 0.277580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.277317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410606E+10 | 0.00 | 0.00 | 0.00 | 0.902590E+10 | 0.00 | 0.750745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256610E+10 | 0.00 | 4243.44 | 0.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254436E+10 | 0.00 | 0.00 | 0.15 |
March | 0.166629E+09 | 0.00 | 0.00 | 0.00 | 73095.30 | 0.192496E+10 | 0.00 | 0.00 | 0.15 |
April | 0.400688E+09 | 5870795.18 | 0.00 | 256158.20 | 0.00 | 0.839966E+09 | 84666786.81 | 0.00 | 0.14 |
May | 0.332742E+09 | 62074844.59 | 0.00 | 2159276.72 | 136622.66 | 81853794.58 | 0.379809E+09 | 0.00 | 0.14 |
June | 16748895.49 | 0.953340E+09 | 0.00 | 2476356.34 | 1134899.57 | 0.00 | 84755072.82 | 0.00 | 0.16 |
July | 0.00 | 0.224306E+10 | 0.00 | 760859.68 | 1602076.54 | 0.00 | 604839.41 | 0.00 | 0.17 |
August | 1089833.40 | 0.190633E+10 | 0.00 | 2236621.84 | 314139.74 | 0.00 | 27850685.66 | 0.00 | 0.18 |
September | 51053642.14 | 0.575552E+09 | 0.00 | 3732305.11 | 562512.71 | 0.00 | 0.270964E+09 | 0.00 | 0.15 |
October | 0.374203E+09 | 78444342.57 | 0.00 | 1483424.58 | 40690.48 | 0.117209E+09 | 0.323837E+09 | 0.00 | 0.14 |
November | 0.298784E+09 | 0.00 | 0.00 | 20626.57 | 0.00 | 0.135002E+10 | 18858376.07 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229825E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.164194E+10 | 0.582467E+10 | 0.00 | 13125629.03 | 3864036.99 | 0.117227E+11 | 0.119135E+10 | 4243.44 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.400688E+09 | 0.224306E+10 | 0.00 | 3732305.11 | 1602076.54 | 0.256610E+10 | 0.379809E+09 | 4243.44 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.991793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937165E+10 | 0.00 | 0.00 | 0.27 |
February | 0.113305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942212E+10 | 0.00 | 0.00 | 0.28 |
March | 0.257789E+10 | 0.00 | 0.00 | 0.00 | 8872681.60 | 0.409694E+10 | 0.00 | 0.00 | 0.24 |
April | 0.258164E+10 | 0.00 | 0.00 | 0.00 | 16995408.24 | 0.102415E+10 | 0.00 | 0.00 | 0.21 |
May | 0.263886E+10 | 0.126409E+09 | 0.00 | 90022.36 | 0.00 | 5256841.40 | 32173816.20 | 0.00 | 0.20 |
June | 0.772479E+09 | 0.138407E+10 | 0.00 | 2731515.28 | 5199188.84 | 0.00 | 0.486890E+09 | 0.00 | 0.22 |
July | 72075177.14 | 0.469438E+10 | 0.00 | 1065821.58 | 0.00 | 0.00 | 0.113763E+09 | 0.00 | 0.21 |
August | 0.224576E+09 | 0.438627E+10 | 0.00 | 4326768.06 | 1350424.87 | 0.00 | 0.210433E+09 | 0.00 | 0.23 |
September | 0.140973E+10 | 0.697868E+09 | 0.00 | 3327050.01 | 0.00 | 0.00 | 0.583659E+09 | 0.00 | 0.21 |
October | 0.279132E+10 | 6019988.53 | 0.00 | 129604.19 | 43751.01 | 68385127.12 | 25642375.79 | 0.00 | 0.19 |
November | 0.191479E+10 | 0.00 | 0.00 | 0.00 | 682868.91 | 0.325261E+10 | 0.00 | 16679.48 | 0.22 |
December | 0.106462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710842E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.181728E+11 | 0.112950E+11 | 0.00 | 11670781.47 | 33144323.46 | 0.343495E+11 | 0.145256E+10 | 16679.48 | 0.23 |
Minimum of Months | 72075177.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.279132E+10 | 0.469438E+10 | 0.00 | 4326768.06 | 16995408.24 | 0.942212E+10 | 0.583659E+09 | 16679.48 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |