Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1307.91 | 270.50 | 270.50 |
Net Site Energy | 1307.91 | 270.50 | 270.50 |
Total Source Energy | 4027.19 | 832.90 | 832.90 |
Net Source Energy | 4027.19 | 832.90 | 832.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 318.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1252.72 | 55.19 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 318.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 39.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 127.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.03 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 259.09 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.03 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 259.09 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1252.720 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1252.720 | 100.00 |
Total On-Site and Utility Electric Sources | 1252.720 | 100.00 |
Total Electricity End Uses | 1252.720 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 51.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 337.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-14:00 | 01-JAN-00:10 | - | - | - | 21-AUG-11:20 |
Heating | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32137.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10986.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1579.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 90435.76 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32137.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8681.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1579.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 59.82 | 0.00 | 0.00 | 0.00 |
Cooling | 1009.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 526.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 72.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3967.37 | 59.82 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 208.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 108.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 820.53 | 12.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 208.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 108.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 820.53 | 12.37 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.23 |
ZONE2 FINE STORAGE DIRECT AIR | 3.81 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.814033 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.814033 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 33788.32 |
PSZ-OFFICE HEATING COIL | 28208.48 |
PSZ-FINE STORAGE HEATING COIL | 175924.22 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.000000 | 1.23 |
PSZ-FINE STORAGE | 3.81 | 3.81 | 3.81 | 3.81 | 3.81 | 3.81 | 1.00 | 1.00 | 3.81 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.23 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.81 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 25332.16 | 28208.48 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.81 | 3.81 | 3.81 | 3.81 | 93080.30 | 175924.22 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.23 | 0.613890 | 1.23 | 24752.53 | 25332.16 | 12666.08 | 25332.16 | 0.725972 | 0.725970 | 0.725970 | 0.725970 |
PSZ-FINE STORAGE COOLING COIL | 3.81 | 1.91 | 3.81 | 89146.26 | 93080.30 | 46540.15 | 93080.30 | 0.680397 | 0.680400 | 0.680400 | 0.680400 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.23 | 1399.81 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.81 | 7281.40 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12430.64670 | 14916.77604 | 1.02315 | 1.22778 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71339E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 2475.52320 | 2970.62784 | 6.59434E-002 | 0.12034 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 49533.40757 | 59440.08908 | 3.17860 | 3.81432 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71339E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.35393 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20000 | 1.71339E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19206.86 | 1.22778 | 1.22778 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 2896.22 | 0.12034 | 0.12034 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 71440.41 | 3.81432 | 3.81432 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 8518.29 | 0.35393 | 0.35393 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22778 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.81432 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 33788.32305 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22778 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22778 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22778 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22778 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22778 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.22778 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.81432 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.81432 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.81432 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.81432 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.81432 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.81432 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.22778 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.81432 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22778 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22778 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22778 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22778 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22778 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22778 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61389 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22778 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24752.52794 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25332.16000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12666.08000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25332.16000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72597 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72597 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72597 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72597 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25332.16000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28208.47997 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22778 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1399.80534 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28208.47997 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.81432 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.81432 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.81432 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.81432 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.81432 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.81432 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.90716 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.81432 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 89146.26206 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 93080.30000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 46540.15000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 93080.30000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68040 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68040 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68040 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68040 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 93080.30000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 175924.22423 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.81432 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7281.40328 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 175924.22423 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24378.6 | 10.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 90115.7 | 12.58 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 5.5561433529E-002 | 0.1173003074 | Pass | Pass | 2.7591818383E-002 | 0.1713149002 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2823177211 | 0.3052746442 | Pass | Pass | 0.7441859363 | 2.5024733166 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.7528630332E-002 | 0.1102887177 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.83 | 83.83 | 123.65 | |
Exterior Lighting Total | 7857.24 | 123.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25332.16 | 18390.39 | 6941.77 | 0.73 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 93080.30 | 63331.84 | 29748.46 | 0.68 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24378.6 | 10.41 | ||||
PSZ-FINE STORAGE COOLING COIL | 90115.7 | 12.58 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 33788.32 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28208.48 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 175924.22 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1399.81 | 1140.11 | 1.00 | 1.32 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.81 | 7281.40 | 1908.96 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12430.65 | 14916.78 | 62.97 | 1.023 | 1.228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 23.90 | 23.90 | 0.00826 | 34.46 | 0.01713 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 49533.41 | 59440.09 | 42.66 | 3.179 | 3.814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 26.70 | 26.70 | 0.00861 | 35.20 | 0.01713 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 35.20 | 0.01713 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 2475.52 | 2970.63 | 12.54 | 0.066 | 0.120 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.00 | 20.00 | 0.01176 | 20.10 | 0.01480 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.354 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 15.56 | 0.00800 | 20.10 | 0.01480 | 0.354 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 10.00 | 0.01600 | 20.10 | 0.01480 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.23 | 1.23 | 0.12 | 0.12 | 1.2278 | 1.2278 | 1.2278 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.81 | 3.81 | 0.35 | 0.35 | 3.8143 | 3.8143 | 3.8143 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 33788.323 | 33788.323 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 33788.32 | 33788.32 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 43.33 | 27.10 | 0.01600000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25332.160 | 0.000 | 1.227780 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 25332.16 | 21140.89 | 1.227780 | 24.93 | 17.23 | 0.00913048 | 12.00 | 11.25 | 0.00800000 | 34.46 | 0.01713393 | 25.62 | 9.8011 | 23.90 | 0.00826083 | 44.7346 | 12404.21 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28208.480 | 28208.480 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28208.48 | 28208.48 | 1.227781 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.8010 | 20.00 | 0.01176196 | 80.3480 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 93080.300 | 0.000 | 3.814320 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 93080.30 | 77012.61 | 3.814320 | 27.49 | 18.31 | 0.00940019 | 12.00 | 11.25 | 0.00800000 | 35.20 | 0.01713393 | 25.80 | 9.2789 | 26.70 | 0.00860919 | 39.4517 | 45770.73 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 175924.224 | 175924.224 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 175924.22 | 93159.70 | 3.814321 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.2789 | 15.56 | 0.00800000 | 72.7370 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33788.323 | 33788.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.814033 | 0.97976621 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 33788.32 | 33788.32 | 1.0000 | 0.97976621 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 50360.9 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33788.32 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 10.00 | 0.01600000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25332.160 | 0.000 | 1.227780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8131 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 25332.16 | 21140.89 | 1.0000 | 1.47774985 | 1.227780 | 24.93 | 17.23 | 0.00913048 | 48313.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25332.16 | 34.46 | 0.01713393 | 25.62 | 0.12033533 | 9.8011 | 23.90 | 0.00826083 | 23.90 | 0.00826083 | 44.7346 | 12404.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28208.480 | 28208.480 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.227781 | 1.47775114 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28208.48 | 28208.48 | 1.0000 | 1.47775114 | 1.227781 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28208.48 | 20.10 | 0.01479830 | 20.10 | 0.12033533 | 9.8010 | 21.10 | 0.00000000 | 20.00 | 0.01176196 | 80.3480 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 93080.300 | 0.000 | 3.814320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3145 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 93080.30 | 77012.61 | 1.0000 | 4.59089641 | 3.814320 | 27.49 | 18.31 | 0.00940019 | 51608.7 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93080.30 | 35.20 | 0.01713393 | 25.80 | 0.35392745 | 9.2789 | 26.70 | 0.00860919 | 26.70 | 0.00860919 | 39.4517 | 45770.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 175924.224 | 175924.224 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.814321 | 4.59089795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 175924.22 | 93159.70 | 1.0000 | 4.59089795 | 3.814321 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 175924.22 | 20.10 | 0.01479830 | 20.10 | 0.35392745 | 9.2789 | 0.00 | 0.00000000 | 15.56 | 0.00800000 | 72.7370 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3632.50 | 337.50 | 337.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3632.50 | 337.50 | 337.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 945.83 | 0.00 | 51.33 |
ZONE2 FINE STORAGE | 0.00 | 459.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1181.33 | 0.00 | 51.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.412 | 0.351 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
Electricity:Building | 660.45 | 4992.32 | 01-JAN-00:10 | 48037.94 | 02-JAN-09:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 460.86 | 2759.73 | 01-JAN-00:10 | 33963.13 | 02-JAN-09:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 22.83 | 483.00 | 19-MAR-12:40 | 1709.85 | 11-JAN-12:20 |
WaterSystems:Electricity | 22.83 | 483.00 | 19-MAR-12:40 | 1709.85 | 11-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 22.83 | 483.00 | 19-MAR-12:40 | 1709.85 | 11-JAN-12:20 |
Fans:Electricity | 166.23 | 0.00 | 01-JAN-00:20 | 10986.50 | 20-APR-12:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 39.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity | 39.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
ElectricityPurchased:Facility | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
ElectricityPurchased:Plant | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
Cogeneration:ElectricityPurchased | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
ElectricityNet:Plant | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
Cogeneration:ElectricityNet | 1252.72 | 5475.32 | 01-JAN-06:20 | 90435.76 | 06-MAY-15:00 |
Electricity:HVAC | 445.79 | 0.00 | 01-JAN-00:20 | 43073.48 | 06-MAY-15:20 |
General:Fans:Electricity | 127.02 | 0.00 | 01-JAN-00:20 | 8681.21 | 20-APR-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 318.77 | 0.00 | 01-JAN-00:20 | 34392.27 | 06-MAY-15:20 |
ExteriorLights:Electricity | 123.65 | 0.00 | 01-JAN-06:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.65 | 0.00 | 01-JAN-06:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 55.19 | 1750.00 | 03-MAR-15:10 | 1750.00 | 01-JAN-00:10 |
Gas:HVAC | 55.19 | 1750.00 | 03-MAR-15:10 | 1750.00 | 01-JAN-00:10 |
Heating:Gas | 55.19 | 1750.00 | 03-MAR-15:10 | 1750.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 21-AUG-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1658.10 | 0.00 | 01-JAN-00:20 | 176039.98 | 06-MAY-15:20 |
EnergyTransfer:Building | 578.02 | 0.00 | 01-JAN-00:20 | 67340.53 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 140.50 | 0.00 | 01-JAN-00:10 | 14939.25 | 15-MAY-00:10 |
Heating:EnergyTransfer | 0.03 | 0.00 | 01-JAN-00:10 | 3089.90 | 23-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 578.00 | 0.00 | 01-JAN-00:20 | 67340.53 | 06-MAY-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 140.50 | 0.00 | 01-JAN-00:10 | 14939.25 | 15-MAY-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 437.53 | 0.00 | 01-JAN-00:20 | 56037.38 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.03 | 0.00 | 01-JAN-00:10 | 3089.90 | 23-JAN-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 437.50 | 0.00 | 01-JAN-00:20 | 56037.38 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1080.08 | 0.00 | 01-JAN-00:20 | 112430.42 | 16-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 1080.08 | 0.00 | 01-JAN-00:20 | 112430.42 | 16-JUN-15:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.000 | -140.497 | 0.000 | 0.000 | 3.577 | 30.994 | 31.946 | 17.677 | 0.000 | 8.873 | 49.857 | 0.000 | -2.145 | 0.000 | -0.282 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.027 | -437.487 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 19.219 | 288.417 | 0.000 | 0.000 | 0.000 | -6.832 | 0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 44.155 | 0.000 | 1.637 | 2244.916 | 0.000 | -10.204 | 0.000 | -2702.150 | 0.000 |
Total Facility | 0.000 | 0.000 | 0.027 | -577.984 | 0.000 | 0.000 | 3.577 | 481.960 | 139.282 | 61.833 | 0.000 | 29.729 | 2583.189 | 0.000 | -12.349 | 0.000 | -2709.264 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JUL-00:01 | 0.00 | 0.00 | 0.00 | -20557.01 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 19808.78 | 0.00 | -284.47 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 22-JAN-17:03 | 0.00 | 0.00 | 0.00 | -71224.50 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 297.48 | 69727.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-FEB-18:08 | 0.00 | 0.00 | 0.00 | -88234.63 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 117.76 | 0.00 | 2567.39 | 159600.96 | 0.00 | -809.08 | 0.00 | -80284.74 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 21-AUG-06:05 | 0.00 | 0.00 | 4895.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -423.89 | -11670.80 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-06:05 | -6595.77 | 6595.77 | 4895.39 | -6595.77 | 0.00 | 0.00 | 69.73 | 24828.58 | 3006.28 | 0.88 | 0.00 | 88.76 | 0.00 | 0.00 | -50.50 | 0.00 | -1081.61 | -25161.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2278 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.2278 | 0.0980 | 1.0000 | 0.1203 | 0.0980 | ||
PSZ-FINE STORAGE | 3.8143 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.8143 | 0.0928 | 1.0000 | 0.3539 | 0.0928 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2278 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.2278 | 1.0000 | 1.0000 | 0.1203 | 0.0980 | ||
PSZ-FINE STORAGE | 3.8143 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.8143 | 1.0000 | 1.0000 | 0.3539 | 0.0928 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2278 | 1.2278 | 1.2278 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.8143 | 3.8143 | 3.8143 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2278 | 1.2278 | 1.2278 | 1.2278 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.8143 | 3.8143 | 3.8143 | 3.8143 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2278 | 1.2278 | 1.2278 | 0.1203 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.8143 | 3.8143 | 3.8143 | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2278 | 1.2278 | 1.2278 | 1.2278 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.8143 | 3.8143 | 3.8143 | 3.8143 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 51.33 |
Number of hours not met | 51.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 55.19 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 318.77 | 34392.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.65 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 39.21 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 127.02 | 8681.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.83 | 1709.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1252.72 |
Natural Gas | 0.00 | 55.19 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1307.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 65.93 |
Fans (All) | 34.38 |
Service Water Heating | 4.72 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 259.09 |
Subtotal | 259.09 |
Natural Gas [MJ/m2] | |
Space Heating | 11.41 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.41 |
Subtotal | 11.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.85 |
Space Heating | 4.22 |
Space Cooling | 24.37 |
Fans (All) | 12.71 |
Service Water Heating | 1.75 |
Receptacle Equipment | 10.65 |
Miscellaneous | 9.45 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109311E+11 | 20221.39 | 23-JAN-00:01 | 22.25 | 19.49 | 0.248948E+09 | 301.59 | 28-JAN-08:09 | 21.50 | 19.17 |
February | 0.105934E+11 | 19448.98 | 27-FEB-00:01 | 26.92 | 22.62 | 0.229042E+09 | 301.61 | 24-FEB-15:09 | 34.07 | 21.23 |
March | 0.130513E+11 | 18552.96 | 06-MAR-06:03 | 24.03 | 21.84 | 0.268889E+09 | 301.60 | 20-MAR-15:20 | 34.77 | 24.84 |
April | 0.125392E+11 | 17921.55 | 10-APR-05:23 | 25.25 | 23.83 | 0.248980E+09 | 301.59 | 08-APR-07:10 | 26.92 | 25.10 |
May | 0.130171E+11 | 18266.08 | 31-MAY-04:23 | 24.70 | 24.64 | 0.258934E+09 | 301.60 | 27-MAY-07:10 | 28.33 | 27.40 |
June | 0.133511E+11 | 18345.45 | 20-JUN-04:23 | 24.05 | 23.80 | 0.258936E+09 | 301.60 | 03-JUN-07:10 | 27.67 | 26.75 |
July | 0.117078E+11 | 20558.92 | 17-JUL-00:01 | 25.48 | 23.36 | 0.248982E+09 | 301.59 | 29-JUL-07:10 | 26.73 | 24.92 |
August | 0.123211E+11 | 17963.12 | 29-AUG-03:43 | 25.33 | 24.59 | 0.268881E+09 | 301.58 | 05-AUG-07:10 | 26.00 | 24.89 |
September | 0.114679E+11 | 18407.93 | 06-SEP-05:03 | 25.08 | 24.21 | 0.248973E+09 | 301.60 | 23-SEP-07:10 | 26.08 | 25.74 |
October | 0.107479E+11 | 18435.90 | 02-OCT-04:43 | 24.00 | 23.28 | 0.248967E+09 | 301.59 | 07-OCT-07:10 | 25.98 | 24.38 |
November | 0.103991E+11 | 19152.67 | 06-NOV-06:03 | 23.10 | 22.35 | 0.238996E+09 | 301.59 | 04-NOV-07:10 | 25.50 | 24.29 |
December | 0.103714E+11 | 18967.18 | 04-DEC-06:03 | 23.00 | 23.00 | 0.248939E+09 | 301.59 | 09-DEC-08:09 | 27.33 | 25.50 |
Annual Sum or Average | 0.140498E+12 | 0.301747E+10 | ||||||||
Minimum of Months | 0.103714E+11 | 17921.55 | 22.25 | 19.49 | 0.229042E+09 | 301.58 | 21.50 | 19.17 | ||
Maximum of Months | 0.133511E+11 | 20558.92 | 26.92 | 24.64 | 0.268889E+09 | 301.61 | 34.77 | 27.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315767E+11 | 71233.68 | 22-JAN-17:03 | 28.18 | 21.77 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.343206E+11 | 69991.95 | 22-FEB-18:08 | 30.72 | 20.90 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.436889E+11 | 67256.51 | 29-MAR-17:05 | 30.83 | 22.31 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.445135E+11 | 64634.80 | 02-APR-13:02 | 34.08 | 26.14 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.432761E+11 | 64254.25 | 07-MAY-12:22 | 34.75 | 26.12 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.453938E+11 | 64609.37 | 04-JUN-15:12 | 33.73 | 27.80 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.363348E+11 | 70733.42 | 16-JUL-15:43 | 24.92 | 23.40 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.350182E+11 | 60211.07 | 26-AUG-17:42 | 30.33 | 27.03 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.352917E+11 | 64211.25 | 13-SEP-17:06 | 31.83 | 25.54 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.300022E+11 | 62762.20 | 08-OCT-14:42 | 31.67 | 26.03 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.294601E+11 | 66574.27 | 05-NOV-16:33 | 28.90 | 24.54 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.286221E+11 | 68805.27 | 03-DEC-16:42 | 28.67 | 22.75 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.437499E+12 | 0.00 | ||||||||
Minimum of Months | 0.286221E+11 | 60211.07 | 24.92 | 20.90 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.453938E+11 | 71233.68 | 34.75 | 27.80 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4714481.93 | 3256.48 | 23-JAN-07:05 | 19.82 |
February | 1175576.62 | 2103.38 | 10-FEB-07:05 | 22.75 |
March | 898235.19 | 1585.92 | 18-MAR-06:05 | 26.00 |
April | 1540461.04 | 1964.88 | 21-APR-06:05 | 25.98 |
May | 1309520.65 | 1706.40 | 11-MAY-06:05 | 24.37 |
June | 405270.28 | 1350.90 | 02-JUN-06:05 | 26.12 |
July | 1197019.04 | 2095.11 | 21-JUL-06:05 | 24.50 |
August | 3215644.68 | 4895.33 | 21-AUG-06:05 | 24.25 |
September | 590308.83 | 1967.70 | 30-SEP-06:05 | 26.45 |
October | 1299302.40 | 1810.90 | 03-OCT-06:05 | 26.03 |
November | 879832.31 | 1248.15 | 09-NOV-07:07 | 25.50 |
December | 9554321.48 | 3857.17 | 15-DEC-07:05 | 21.83 |
Annual Sum or Average | 26779974.45 | |||
Minimum of Months | 405270.28 | 1248.15 | 19.82 | |
Maximum of Months | 9554321.48 | 4895.33 | 26.45 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616091E+09 | 66901257.69 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672903E+09 | 30460696.22 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990469E+09 | 16757593.13 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940578E+09 | 6753535.69 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100194E+10 | 4723529.49 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101542E+10 | 9589578.46 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595166E+09 | 12672544.25 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789848E+09 | 14137167.67 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642221E+09 | 11061545.98 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552973E+09 | 21619382.59 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560001E+09 | 24636989.41 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494916E+09 | 62230472.18 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.887253E+10 | 0.281544E+09 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494916E+09 | 4723529.49 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101542E+10 | 66901257.69 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887843E+09 | 0.106995E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144461E+10 | 0.413198E+09 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245148E+10 | 0.614820E+09 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249338E+10 | 0.124647E+09 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288576E+10 | 0.317857E+09 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262502E+10 | 0.291051E+09 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141803E+10 | 0.382202E+09 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162113E+10 | 0.689234E+09 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124578E+10 | 0.406583E+09 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877268E+09 | 0.624464E+09 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658948E+09 | 0.692264E+09 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609556E+09 | 0.120571E+10 |
Annual Sum or Average | 0.136656E+12 | 0.192188E+11 | 0.683199E+10 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609556E+09 | 0.124647E+09 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288576E+10 | 0.120571E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 0.977409E+10 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893573E+10 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64623201.88 | 0.156022E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9253229.57 | 0.112521E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13284122.75 | 0.117458E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1293348.77 | 0.124729E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102616E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27657148.43 | 0.132101E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935621E+10 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7742333.02 | 0.899807E+10 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904729.35 | 0.797640E+10 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570402.64 | 0.897651E+10 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.125329E+09 | 0.128562E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797640E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64623201.88 | 0.156022E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3606.62 | 04-JAN-13:00 | 1600.24 | 24-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.75 | 28-FEB-13:00 | 953.23 | 02-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.45 | 21-MAR-12:00 | 245.25 | 15-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.51 | 11-APR-16:10 | 145.20 | 09-APR-16:00 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.25 | 05-MAY-12:00 | 138.86 | 21-MAY-12:52 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.74 | 13-JUN-16:10 | 249.46 | 25-JUN-20:55 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.32 | 26-JUL-17:00 | 199.62 | 02-JUL-14:00 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3389.01 | 09-AUG-16:10 | 235.20 | 20-AUG-10:45 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.13 | 12-SEP-12:00 | 395.91 | 15-SEP-17:00 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.18 | 04-OCT-12:00 | 349.28 | 30-OCT-17:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2834.23 | 10-NOV-12:10 | 656.80 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2852.41 | 26-DEC-13:00 | 1947.16 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2834.23 | 138.86 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.25 | 1947.16 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4221.45 | 31-JAN-16:10 | 8920.56 | 07-JAN-05:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6531.43 | 28-FEB-16:05 | 2911.68 | 01-FEB-07:05 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9580.67 | 19-MAR-15:50 | 2484.09 | 14-MAR-21:50 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6781.86 | 11-APR-16:00 | 2054.71 | 14-APR-16:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11611.93 | 06-MAY-15:10 | 3806.82 | 08-MAY-22:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9309.38 | 16-JUN-15:30 | 4582.43 | 20-JUN-23:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5706.65 | 13-JUL-16:00 | 3171.83 | 19-JUL-19:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6519.50 | 09-AUG-16:00 | 3740.14 | 23-AUG-20:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6623.89 | 10-SEP-15:00 | 5993.21 | 15-SEP-17:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5679.96 | 29-OCT-13:08 | 2712.53 | 30-OCT-16:20 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3001.97 | 04-NOV-15:10 | 2548.83 | 25-NOV-08:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.81 | 13-DEC-16:10 | 3911.07 | 21-DEC-07:20 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.81 | 2054.71 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11611.93 | 8920.56 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 11-JAN-07:55 | 29723.28 | 07-JAN-05:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18769.43 | 28-FEB-12:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5117.73 | 03-MAR-14:52 | 19383.99 | 30-MAR-13:55 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.42 | 09-APR-14:00 | 18081.07 | 03-APR-13:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.10 | 21-MAY-10:53 | 29710.01 | 22-MAY-10:53 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.20 | 28-JUN-13:30 | 31960.54 | 16-JUN-14:53 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 25641.74 | 03-JUL-13:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.08 | 06-AUG-11:53 | 30717.56 | 24-AUG-13:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31541.80 | 11-SEP-13:53 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 895.12 | 26-OCT-12:10 | 16707.30 | 29-OCT-13:42 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.42 | 17-NOV-18:55 | 13167.11 | 24-NOV-11:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 737.64 | 29-DEC-18:55 | 20410.46 | 09-DEC-14:53 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13167.11 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5117.73 | 31960.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20221.39 | 23-JAN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 |
February | 19448.98 | 27-FEB-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 |
March | 18552.96 | 06-MAR-06:03 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
April | 17921.55 | 10-APR-05:23 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.75 | 0.00 |
May | 18266.08 | 31-MAY-04:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
June | 18345.45 | 20-JUN-04:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
July | 20558.92 | 17-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17963.12 | 29-AUG-03:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 |
September | 18407.93 | 06-SEP-05:03 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
October | 18435.90 | 02-OCT-04:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
November | 19152.67 | 06-NOV-06:03 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.98 |
December | 18967.18 | 04-DEC-06:03 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17921.55 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20558.92 | 217.55 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 67.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 71233.68 | 22-JAN-17:03 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.48 | 0.00 |
February | 69991.95 | 22-FEB-18:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.19 | 0.00 |
March | 67256.51 | 29-MAR-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2851.39 | 0.00 |
April | 64634.80 | 02-APR-13:02 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.92 | 0.00 |
May | 64254.25 | 07-MAY-12:22 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.87 | 0.00 |
June | 64609.37 | 04-JUN-15:12 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1422.19 | 0.00 |
July | 70733.42 | 16-JUL-15:43 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.66 |
August | 60211.07 | 26-AUG-17:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.22 | 0.00 |
September | 64211.25 | 13-SEP-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1364.58 | 0.00 |
October | 62762.20 | 08-OCT-14:42 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.16 | 0.00 |
November | 66574.27 | 05-NOV-16:33 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.37 | 0.00 |
December | 68805.27 | 03-DEC-16:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.81 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 60211.07 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71233.68 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2851.39 | 96.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.95 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2970.14 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4122.40 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3710.96 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2170.49 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4175.85 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.27 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4759.52 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2934.44 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.32 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.99 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1908.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.99 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4759.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.988675E+11 | 82503.06 | 04-JAN-13:20 | 0.468720E+10 | 1750.00 | 01-JAN-00:10 |
February | 0.937522E+11 | 85063.56 | 28-FEB-14:50 | 0.423360E+10 | 1750.00 | 01-FEB-00:10 |
March | 0.111869E+12 | 85971.71 | 21-MAR-13:50 | 0.468720E+10 | 1750.00 | 01-MAR-00:10 |
April | 0.109679E+12 | 86351.87 | 18-APR-14:30 | 0.453600E+10 | 1750.00 | 01-APR-00:10 |
May | 0.114002E+12 | 90435.76 | 06-MAY-14:00 | 0.468720E+10 | 1750.00 | 01-MAY-00:10 |
June | 0.114101E+12 | 89858.39 | 16-JUN-13:39 | 0.453600E+10 | 1750.00 | 01-JUN-00:10 |
July | 0.103150E+12 | 82813.39 | 26-JUL-14:20 | 0.468720E+10 | 1750.00 | 01-JUL-00:10 |
August | 0.109489E+12 | 86357.75 | 11-AUG-14:30 | 0.468720E+10 | 1750.00 | 01-AUG-00:10 |
September | 0.103527E+12 | 85423.95 | 06-SEP-14:20 | 0.453600E+10 | 1750.00 | 01-SEP-00:10 |
October | 0.100717E+12 | 83668.09 | 04-OCT-14:09 | 0.468720E+10 | 1750.00 | 01-OCT-00:10 |
November | 0.961720E+11 | 81987.05 | 18-NOV-13:09 | 0.453600E+10 | 1750.00 | 01-NOV-00:10 |
December | 0.973957E+11 | 80767.88 | 08-DEC-14:09 | 0.468720E+10 | 1750.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.125272E+13 | 0.551880E+11 | ||||
Minimum of Months | 0.937522E+11 | 80767.88 | 0.423360E+10 | 1750.00 | ||
Maximum of Months | 0.114101E+12 | 90435.76 | 0.468720E+10 | 1750.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.110127E+11 | 0.115358E+11 | 0.00 | 0.126344E+11 | 0.00 | 0.00 | 0.216347E+11 | 0.00 | 0.00 | 0.00 | 0.194646E+10 | 0.00 |
February | 0.366966E+11 | 0.979169E+10 | 0.105871E+11 | 0.00 | 0.122989E+11 | 0.00 | 0.00 | 0.226137E+11 | 0.00 | 0.00 | 0.00 | 0.176416E+10 | 0.00 |
March | 0.423649E+11 | 0.105083E+11 | 0.123357E+11 | 0.00 | 0.150080E+11 | 0.00 | 0.00 | 0.296776E+11 | 0.00 | 0.00 | 0.00 | 0.197411E+10 | 0.00 |
April | 0.397216E+11 | 0.992841E+10 | 0.114862E+11 | 0.00 | 0.154092E+11 | 0.00 | 0.00 | 0.312557E+11 | 0.00 | 0.00 | 0.00 | 0.187767E+10 | 0.00 |
May | 0.412341E+11 | 0.100840E+11 | 0.119357E+11 | 0.00 | 0.156426E+11 | 0.00 | 0.00 | 0.331732E+11 | 0.00 | 0.00 | 0.00 | 0.193204E+10 | 0.00 |
June | 0.408524E+11 | 0.964555E+10 | 0.118862E+11 | 0.00 | 0.157847E+11 | 0.00 | 0.00 | 0.340546E+11 | 0.00 | 0.00 | 0.00 | 0.187726E+10 | 0.00 |
July | 0.401034E+11 | 0.100463E+11 | 0.115358E+11 | 0.00 | 0.139109E+11 | 0.00 | 0.00 | 0.256507E+11 | 0.00 | 0.00 | 0.00 | 0.190263E+10 | 0.00 |
August | 0.423649E+11 | 0.101736E+11 | 0.123357E+11 | 0.00 | 0.142430E+11 | 0.00 | 0.00 | 0.284285E+11 | 0.00 | 0.00 | 0.00 | 0.194375E+10 | 0.00 |
September | 0.397216E+11 | 0.100981E+11 | 0.114862E+11 | 0.00 | 0.137781E+11 | 0.00 | 0.00 | 0.265750E+11 | 0.00 | 0.00 | 0.00 | 0.186836E+10 | 0.00 |
October | 0.401034E+11 | 0.107063E+11 | 0.115358E+11 | 0.00 | 0.128913E+11 | 0.00 | 0.00 | 0.235543E+11 | 0.00 | 0.00 | 0.00 | 0.192614E+10 | 0.00 |
November | 0.385909E+11 | 0.105696E+11 | 0.110862E+11 | 0.00 | 0.122968E+11 | 0.00 | 0.00 | 0.217580E+11 | 0.00 | 0.00 | 0.00 | 0.187053E+10 | 0.00 |
December | 0.401034E+11 | 0.110834E+11 | 0.115358E+11 | 0.00 | 0.123366E+11 | 0.00 | 0.00 | 0.203916E+11 | 0.00 | 0.00 | 0.00 | 0.194501E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123648E+12 | 0.139282E+12 | 0.166234E+12 | 0.00 | 0.318768E+12 | 0.228281E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.964555E+10 | 0.105871E+11 | 0.00 | 0.122968E+11 | 0.00 | 0.00 | 0.203916E+11 | 0.00 | 0.00 | 0.00 | 0.176416E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.110834E+11 | 0.123357E+11 | 0.00 | 0.157847E+11 | 0.00 | 0.00 | 0.340546E+11 | 0.00 | 0.00 | 0.00 | 0.197411E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551880E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10986.50 | 02-JAN-09:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10986.50 | 01-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10986.50 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10986.50 | 20-APR-12:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10986.50 | 01-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10986.50 | 01-JUN-07:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10986.50 | 01-JUL-07:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10986.50 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10986.50 | 01-SEP-06:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10986.50 | 02-OCT-07:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10986.50 | 01-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10986.50 | 01-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 10986.50 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 10986.50 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 24986.60 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 1709.85 | 11-JAN-12:20 | 0.00 |
February | 26704.92 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1709.31 | 01-FEB-12:50 | 0.00 |
March | 29017.06 | 20-MAR-15:30 | 0.00 | 0.00 | 0.00 | 1707.02 | 01-MAR-12:20 | 0.00 |
April | 29242.93 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 1702.92 | 01-APR-11:09 | 0.00 |
May | 34392.27 | 06-MAY-15:20 | 0.00 | 0.00 | 0.00 | 1698.25 | 02-MAY-11:50 | 0.00 |
June | 33302.08 | 13-JUN-15:39 | 0.00 | 0.00 | 0.00 | 1694.44 | 01-JUN-11:30 | 0.00 |
July | 24803.69 | 05-JUL-15:39 | 0.00 | 0.00 | 0.00 | 1692.69 | 31-JUL-11:09 | 0.00 |
August | 28924.54 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1695.13 | 31-AUG-11:00 | 0.00 |
September | 27060.53 | 06-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1698.97 | 30-SEP-11:20 | 0.00 |
October | 26010.73 | 04-OCT-15:30 | 0.00 | 0.00 | 0.00 | 1703.49 | 30-OCT-11:09 | 0.00 |
November | 23742.35 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1707.30 | 30-NOV-12:30 | 0.00 |
December | 22735.90 | 08-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1709.54 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22735.90 | 0.00 | 0.00 | 0.00 | 1692.69 | 0.00 | ||
Maximum of Months | 34392.27 | 0.00 | 0.00 | 0.00 | 1709.85 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 82503.06 | 04-JAN-13:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 24097.55 | 0.00 |
February | 85063.56 | 28-FEB-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 26682.45 | 0.00 |
March | 85971.71 | 21-MAR-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 27592.60 | 0.00 |
April | 86351.87 | 18-APR-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 27954.80 | 0.00 |
May | 90435.76 | 06-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 32137.22 | 0.00 |
June | 89858.39 | 16-JUN-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 31487.46 | 0.00 |
July | 82813.39 | 26-JUL-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 24422.87 | 0.00 |
August | 86357.75 | 11-AUG-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 27966.47 | 0.00 |
September | 85423.95 | 06-SEP-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 27030.48 | 0.00 |
October | 83668.09 | 04-OCT-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 25271.25 | 0.00 |
November | 81987.05 | 18-NOV-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 23672.62 | 0.00 |
December | 80767.88 | 08-DEC-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 22386.02 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 80767.88 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 22386.02 | 0.00 | |
Maximum of Months | 90435.76 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10986.50 | 0.00 | 0.00 | 32137.22 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1750.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1750.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1750.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1750.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1750.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1750.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1750.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1750.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 24.68 | 2.83 | 24.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 73.50 | 24.70 | 3.50 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 85.33 | 24.75 | 4.83 | 24.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 24.79 | 4.83 | 24.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 84.83 | 24.88 | 5.00 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 | 24.86 | 5.00 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 | 24.77 | 5.17 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 24.71 | 5.17 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 24.72 | 4.83 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 24.71 | 4.67 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 | 24.68 | 3.67 | 24.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 24.63 | 1.83 | 24.58 |
Annual Sum or Average | 0.00 | 0.00 | 945.83 | 24.74 | 51.33 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 24.63 | 1.83 | 24.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 24.88 | 5.17 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.72 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.71 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 27.72 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 27.69 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 27.69 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 27.69 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 27.66 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 27.65 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 27.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.67 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.66 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.76 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 459.33 | 27.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.65 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 27.76 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 23.90 | 298.17 | 23.91 | 3.33 | 23.90 |
February | 2.00 | 23.90 | 276.00 | 23.91 | 2.00 | 23.90 |
March | 5.50 | 23.90 | 324.00 | 23.91 | 5.50 | 23.90 |
April | 19.67 | 23.90 | 300.00 | 23.91 | 19.67 | 23.90 |
May | 60.83 | 23.90 | 312.00 | 23.91 | 60.83 | 23.90 |
June | 55.00 | 23.90 | 312.00 | 23.91 | 55.00 | 23.90 |
July | 12.00 | 23.90 | 300.00 | 23.91 | 12.00 | 23.90 |
August | 67.17 | 23.90 | 324.00 | 23.91 | 67.17 | 23.90 |
September | 42.33 | 23.90 | 300.00 | 23.91 | 42.33 | 23.90 |
October | 46.83 | 23.90 | 300.00 | 23.91 | 46.83 | 23.90 |
November | 18.33 | 23.90 | 288.00 | 23.91 | 18.33 | 23.90 |
December | 4.50 | 23.90 | 298.33 | 23.91 | 4.50 | 23.90 |
Annual Sum or Average | 337.50 | 23.90 | 3632.50 | 23.91 | 337.50 | 23.90 |
Minimum of Months | 2.00 | 23.90 | 276.00 | 23.91 | 2.00 | 23.90 |
Maximum of Months | 67.17 | 23.90 | 324.00 | 23.91 | 67.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.182450E+11 | 0.507077E+10 | 518.13 | 0.135685E+11 | 0.467657E+10 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:05 | 32167.12 | 02-JAN-00:01 | 21439.06 | 23-JAN-00:01 | 14087.97 | 02-JAN-00:06 | 7220.56 | 02-JAN-00:01 | 0.00 | 01-JAN-00:05 |
February | 0.175781E+11 | 0.493505E+10 | 478.87 | 0.131817E+11 | 0.439635E+10 | 0.00 | 1.00 | 01-FEB-18:08 | 0.00 | 01-FEB-00:07 | 31224.75 | 06-FEB-00:01 | 21487.90 | 22-FEB-22:03 | 12696.07 | 06-FEB-00:07 | 7125.99 | 21-FEB-00:01 | 0.00 | 01-FEB-00:03 |
March | 0.223785E+11 | 0.631391E+10 | 560.68 | 0.163429E+11 | 0.603562E+10 | 0.00 | 1.00 | 01-MAR-18:08 | 0.00 | 01-MAR-00:33 | 31494.70 | 27-MAR-00:01 | 20782.31 | 06-MAR-06:03 | 13270.83 | 27-MAR-00:08 | 7698.41 | 26-MAR-12:51 | 0.00 | 01-MAR-00:05 |
April | 0.227689E+11 | 0.640027E+10 | 522.81 | 0.157835E+11 | 0.698549E+10 | 0.00 | 1.00 | 01-APR-00:23 | 0.00 | 01-APR-00:13 | 31914.11 | 10-APR-00:01 | 20361.19 | 26-APR-23:03 | 14499.59 | 03-APR-00:07 | 7397.24 | 03-APR-00:01 | 0.00 | 01-APR-00:10 |
May | 0.253423E+11 | 0.704721E+10 | 552.29 | 0.164418E+11 | 0.890059E+10 | 0.00 | 1.00 | 01-MAY-00:01 | 0.00 | 01-MAY-00:32 | 32186.43 | 22-MAY-00:01 | 20671.32 | 31-MAY-04:23 | 18638.06 | 22-MAY-00:07 | 7441.69 | 08-MAY-00:01 | 0.00 | 01-MAY-00:01 |
June | 0.258405E+11 | 0.717837E+10 | 549.37 | 0.168061E+11 | 0.903440E+10 | 0.00 | 1.00 | 01-JUN-00:23 | 0.00 | 01-JUN-00:13 | 32426.32 | 05-JUN-00:01 | 20669.72 | 20-JUN-04:23 | 15188.74 | 05-JUN-00:06 | 7390.44 | 19-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.207555E+11 | 0.568987E+10 | 518.94 | 0.144959E+11 | 0.625956E+10 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:13 | 31714.55 | 03-JUL-00:01 | 22197.49 | 17-JUL-00:01 | 13448.65 | 03-JUL-00:06 | 7218.51 | 03-JUL-00:01 | 0.00 | 01-JUL-00:10 |
August | 0.243296E+11 | 0.662647E+10 | 560.92 | 0.154901E+11 | 0.883958E+10 | 0.00 | 1.00 | 01-AUG-00:23 | 0.00 | 01-AUG-00:13 | 32729.68 | 07-AUG-00:01 | 20491.37 | 01-AUG-00:23 | 17994.79 | 07-AUG-00:04 | 7354.21 | 14-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.217681E+11 | 0.595843E+10 | 523.07 | 0.143701E+11 | 0.739804E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:13 | 32650.55 | 25-SEP-00:01 | 20878.06 | 06-SEP-05:03 | 15282.90 | 25-SEP-00:05 | 7302.26 | 05-SEP-00:01 | 0.00 | 01-SEP-00:10 |
October | 0.205192E+11 | 0.557547E+10 | 522.45 | 0.134688E+11 | 0.705040E+10 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:03 | 32748.43 | 30-OCT-00:01 | 20632.42 | 02-OCT-04:43 | 16137.58 | 30-OCT-00:04 | 7291.06 | 30-OCT-00:01 | 0.00 | 01-OCT-00:03 |
November | 0.188511E+11 | 0.515508E+10 | 497.96 | 0.129617E+11 | 0.588939E+10 | 0.00 | 1.00 | 01-NOV-17:08 | 0.00 | 01-NOV-00:13 | 32546.93 | 13-NOV-00:01 | 21370.46 | 06-NOV-06:03 | 15486.75 | 13-NOV-00:05 | 7311.16 | 13-NOV-00:01 | 0.00 | 01-NOV-00:10 |
December | 0.176943E+11 | 0.488260E+10 | 511.94 | 0.129114E+11 | 0.478288E+10 | 0.00 | 1.00 | 01-DEC-18:10 | 0.00 | 01-DEC-00:33 | 31632.36 | 11-DEC-00:01 | 21159.31 | 04-DEC-06:03 | 13565.44 | 18-DEC-18:10 | 7189.68 | 26-DEC-00:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.256071E+12 | 0.708335E+11 | 6317.43 | 0.175822E+12 | 0.802489E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.175781E+11 | 0.488260E+10 | 478.87 | 0.129114E+11 | 0.439635E+10 | 0.00 | 1.00 | 0.00 | 31224.75 | 20361.19 | 12696.07 | 7125.99 | 0.00 | |||||||
Maximum of Months | 0.258405E+11 | 0.717837E+10 | 560.92 | 0.168061E+11 | 0.903440E+10 | 0.00 | 1.00 | 0.00 | 32748.43 | 22197.49 | 18638.06 | 7698.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.545525E+11 | 0.165640E+11 | 462.27 | 0.412785E+11 | 0.132741E+11 | 0.00 | 1.00 | 08-JAN-11:23 | 0.00 | 01-JAN-00:10 | 114486.79 | 09-JAN-00:06 | 84124.78 | 16-JAN-15:12 | 51775.80 | 09-JAN-00:06 | 28497.29 | 08-JAN-12:02 | 0.00 | 01-JAN-00:05 |
February | 0.577407E+11 | 0.176787E+11 | 465.46 | 0.439901E+11 | 0.137506E+11 | 0.00 | 1.00 | 05-FEB-10:32 | 0.00 | 01-FEB-00:07 | 109443.41 | 20-FEB-08:53 | 82633.93 | 22-FEB-18:08 | 41775.62 | 20-FEB-08:53 | 29265.49 | 26-FEB-15:52 | 0.00 | 01-FEB-00:03 |
March | 0.764015E+11 | 0.233637E+11 | 553.76 | 0.558879E+11 | 0.205136E+11 | 0.00 | 1.00 | 05-MAR-10:02 | 0.00 | 01-MAR-00:33 | 110962.70 | 20-MAR-00:01 | 81038.42 | 19-MAR-14:02 | 45401.90 | 20-MAR-00:01 | 29717.79 | 19-MAR-13:22 | 0.00 | 01-MAR-00:05 |
April | 0.816269E+11 | 0.248554E+11 | 563.88 | 0.567876E+11 | 0.248393E+11 | 0.00 | 1.00 | 01-APR-17:05 | 0.00 | 01-APR-00:13 | 111918.86 | 02-APR-21:43 | 78967.73 | 02-APR-13:42 | 49250.44 | 02-APR-22:23 | 29791.28 | 02-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.866142E+11 | 0.261260E+11 | 573.60 | 0.561262E+11 | 0.304881E+11 | 0.00 | 1.00 | 01-MAY-17:05 | 0.00 | 01-MAY-00:11 | 115205.47 | 29-MAY-23:43 | 78664.67 | 07-MAY-13:02 | 57124.11 | 19-MAY-21:03 | 30160.68 | 21-MAY-09:43 | 0.00 | 01-MAY-00:01 |
June | 0.894999E+11 | 0.268762E+11 | 571.29 | 0.582959E+11 | 0.312040E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:13 | 115360.80 | 11-JUN-07:03 | 74054.09 | 25-JUN-14:12 | 58434.86 | 10-JUN-01:03 | 30533.46 | 18-JUN-13:43 | 0.00 | 01-JUN-00:10 |
July | 0.665832E+11 | 0.199608E+11 | 553.23 | 0.468806E+11 | 0.197026E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 111861.30 | 02-JUL-14:23 | 79564.48 | 16-JUL-13:43 | 44752.29 | 02-JUL-09:03 | 29233.63 | 04-JUL-13:02 | 0.00 | 01-JUL-00:10 |
August | 0.740066E+11 | 0.218021E+11 | 518.88 | 0.465101E+11 | 0.274965E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 117111.29 | 07-AUG-00:08 | 73060.19 | 27-AUG-15:52 | 57653.33 | 13-AUG-07:43 | 30179.68 | 06-AUG-13:23 | 0.00 | 01-AUG-00:10 |
September | 0.691855E+11 | 0.206166E+11 | 532.80 | 0.460887E+11 | 0.230968E+11 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:13 | 110803.50 | 24-SEP-10:43 | 77294.45 | 10-SEP-13:52 | 44907.11 | 24-SEP-10:43 | 29702.11 | 24-SEP-12:43 | 0.00 | 01-SEP-00:10 |
October | 0.607359E+11 | 0.179788E+11 | 503.61 | 0.400882E+11 | 0.206477E+11 | 0.00 | 1.00 | 01-OCT-09:03 | 0.00 | 01-OCT-00:13 | 113370.63 | 29-OCT-17:03 | 76045.44 | 08-OCT-14:02 | 48335.13 | 29-OCT-17:03 | 29579.84 | 29-OCT-13:02 | 0.00 | 01-OCT-00:03 |
November | 0.556127E+11 | 0.166029E+11 | 466.79 | 0.389242E+11 | 0.166885E+11 | 0.00 | 1.00 | 02-NOV-17:08 | 0.00 | 01-NOV-00:10 | 112413.93 | 11-NOV-08:53 | 79829.36 | 05-NOV-13:53 | 48456.58 | 11-NOV-08:53 | 28902.71 | 11-NOV-14:52 | 0.00 | 01-NOV-00:10 |
December | 0.514492E+11 | 0.155090E+11 | 436.74 | 0.380396E+11 | 0.134097E+11 | 0.00 | 1.00 | 03-DEC-10:43 | 0.00 | 01-DEC-00:05 | 111019.30 | 25-DEC-09:33 | 81693.68 | 03-DEC-14:42 | 48601.68 | 24-DEC-09:43 | 28860.42 | 31-DEC-09:53 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.824009E+12 | 0.247934E+12 | 6202.29 | 0.568897E+12 | 0.255111E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.514492E+11 | 0.155090E+11 | 436.74 | 0.380396E+11 | 0.132741E+11 | 0.00 | 1.00 | 0.00 | 109443.41 | 73060.19 | 41775.62 | 28497.29 | 0.00 | |||||||
Maximum of Months | 0.894999E+11 | 0.268762E+11 | 573.60 | 0.582959E+11 | 0.312040E+11 | 0.00 | 1.00 | 0.00 | 117111.29 | 84124.78 | 58434.86 | 30533.46 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.31 | 20.90 | 38.41 | 191.38 | 36.26 | 0.00 | 0.00 | 744.00 |
February | 64.95 | 22.93 | 42.02 | 216.71 | 27.97 | 0.00 | 0.00 | 672.00 |
March | 72.73 | 28.62 | 44.11 | 248.57 | 19.98 | 0.00 | 0.00 | 744.00 |
April | 72.91 | 27.71 | 45.20 | 248.78 | 9.64 | 0.00 | 0.00 | 720.00 |
May | 62.19 | 18.32 | 43.87 | 217.75 | 11.01 | 0.00 | 0.00 | 744.00 |
June | 67.38 | 23.12 | 44.27 | 233.45 | 11.61 | 0.00 | 0.00 | 720.00 |
July | 57.51 | 13.49 | 44.02 | 188.07 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 62.51 | 18.41 | 44.09 | 191.68 | 16.41 | 0.00 | 0.00 | 744.00 |
September | 58.40 | 16.02 | 42.38 | 191.67 | 17.33 | 0.00 | 0.00 | 720.00 |
October | 54.94 | 14.05 | 40.89 | 166.65 | 22.94 | 0.00 | 0.00 | 744.00 |
November | 53.59 | 14.52 | 39.06 | 168.15 | 26.08 | 0.00 | 0.00 | 720.00 |
December | 55.00 | 18.01 | 36.99 | 176.21 | 39.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.75 | 19.64 | 42.10 | 203.07 | 21.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.59 | 13.49 | 36.99 | 166.65 | 9.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.91 | 28.62 | 45.20 | 248.78 | 39.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.31 | 20.90 | 38.41 | 191.38 | 36.26 | 0.00 | 0.00 | 744.00 |
February | 64.95 | 22.93 | 42.02 | 216.71 | 27.97 | 0.00 | 0.00 | 672.00 |
March | 72.73 | 28.62 | 44.11 | 248.57 | 19.98 | 0.00 | 0.00 | 744.00 |
April | 72.91 | 27.71 | 45.20 | 248.78 | 9.64 | 0.00 | 0.00 | 720.00 |
May | 62.19 | 18.32 | 43.87 | 217.75 | 11.01 | 0.00 | 0.00 | 744.00 |
June | 67.38 | 23.12 | 44.27 | 233.45 | 11.61 | 0.00 | 0.00 | 720.00 |
July | 57.51 | 13.49 | 44.02 | 188.07 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 62.51 | 18.41 | 44.09 | 191.68 | 16.41 | 0.00 | 0.00 | 744.00 |
September | 58.40 | 16.02 | 42.38 | 191.67 | 17.33 | 0.00 | 0.00 | 720.00 |
October | 54.94 | 14.05 | 40.89 | 166.65 | 22.94 | 0.00 | 0.00 | 744.00 |
November | 53.59 | 14.52 | 39.06 | 168.15 | 26.08 | 0.00 | 0.00 | 720.00 |
December | 55.00 | 18.01 | 36.99 | 176.21 | 39.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.75 | 19.64 | 42.10 | 203.07 | 21.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.59 | 13.49 | 36.99 | 166.65 | 9.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.91 | 28.62 | 45.20 | 248.78 | 39.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.68 | 0.00 | 17.68 | 57.91 | 21.07 | 0.00 | 0.00 | 744.00 |
February | 18.86 | 0.00 | 18.86 | 66.39 | 16.19 | 0.00 | 0.00 | 672.00 |
March | 19.38 | 0.01 | 19.37 | 73.46 | 11.42 | 0.00 | 0.00 | 744.00 |
April | 21.61 | 0.67 | 20.93 | 82.23 | 5.51 | 0.00 | 0.00 | 720.00 |
May | 28.22 | 4.09 | 24.13 | 103.61 | 6.33 | 0.00 | 0.00 | 744.00 |
June | 34.73 | 8.41 | 26.32 | 125.97 | 6.75 | 0.00 | 0.00 | 720.00 |
July | 29.21 | 3.81 | 25.39 | 96.48 | 11.71 | 0.00 | 0.00 | 744.00 |
August | 24.10 | 1.73 | 22.37 | 77.53 | 9.53 | 0.00 | 0.00 | 744.00 |
September | 19.94 | 0.05 | 19.89 | 70.51 | 10.14 | 0.00 | 0.00 | 720.00 |
October | 19.16 | 0.00 | 19.16 | 59.47 | 13.45 | 0.00 | 0.00 | 744.00 |
November | 18.13 | 0.00 | 18.13 | 58.33 | 15.26 | 0.00 | 0.00 | 720.00 |
December | 17.18 | 0.00 | 17.18 | 55.75 | 22.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.36 | 1.57 | 20.79 | 77.32 | 12.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.18 | 0.00 | 17.18 | 55.75 | 5.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.73 | 8.41 | 26.32 | 125.97 | 22.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.68 | 0.00 | 17.68 | 57.90 | 21.07 | 0.00 | 0.00 | 744.00 |
February | 18.86 | 0.00 | 18.86 | 66.39 | 16.19 | 0.00 | 0.00 | 672.00 |
March | 19.38 | 0.01 | 19.37 | 73.46 | 11.42 | 0.00 | 0.00 | 744.00 |
April | 21.61 | 0.67 | 20.93 | 82.23 | 5.51 | 0.00 | 0.00 | 720.00 |
May | 28.22 | 4.09 | 24.13 | 103.61 | 6.33 | 0.00 | 0.00 | 744.00 |
June | 34.72 | 8.41 | 26.32 | 125.97 | 6.75 | 0.00 | 0.00 | 720.00 |
July | 29.20 | 3.81 | 25.39 | 96.47 | 11.71 | 0.00 | 0.00 | 744.00 |
August | 24.10 | 1.73 | 22.37 | 77.53 | 9.53 | 0.00 | 0.00 | 744.00 |
September | 19.94 | 0.05 | 19.89 | 70.51 | 10.14 | 0.00 | 0.00 | 720.00 |
October | 19.16 | 0.00 | 19.16 | 59.47 | 13.45 | 0.00 | 0.00 | 744.00 |
November | 18.13 | 0.00 | 18.13 | 58.33 | 15.26 | 0.00 | 0.00 | 720.00 |
December | 17.18 | 0.00 | 17.18 | 55.74 | 22.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.36 | 1.57 | 20.79 | 77.31 | 12.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.18 | 0.00 | 17.18 | 55.74 | 5.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.72 | 8.41 | 26.32 | 125.97 | 22.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.36 | 48.48 | 52.88 | 128.26 | 38.17 | 8.83 | 0.00 | 744.00 |
February | 116.61 | 60.30 | 56.31 | 148.12 | 41.30 | 3.33 | 0.00 | 672.00 |
March | 135.34 | 79.17 | 56.17 | 171.26 | 37.25 | 0.00 | 0.00 | 744.00 |
April | 136.82 | 76.39 | 60.43 | 172.03 | 31.03 | 6.00 | 0.00 | 720.00 |
May | 114.70 | 49.68 | 65.02 | 143.53 | 28.11 | 162.67 | 0.00 | 744.00 |
June | 123.95 | 61.13 | 62.82 | 155.30 | 27.88 | 65.50 | 0.00 | 720.00 |
July | 104.43 | 34.48 | 69.95 | 132.57 | 29.55 | 16.33 | 0.00 | 744.00 |
August | 115.24 | 49.28 | 65.96 | 141.12 | 27.80 | 115.17 | 0.00 | 744.00 |
September | 106.59 | 41.26 | 65.33 | 134.72 | 28.52 | 53.33 | 0.00 | 720.00 |
October | 97.49 | 34.46 | 63.02 | 119.39 | 28.50 | 96.67 | 0.00 | 744.00 |
November | 92.86 | 34.98 | 57.89 | 116.48 | 32.26 | 69.17 | 0.00 | 720.00 |
December | 93.98 | 42.14 | 51.84 | 119.02 | 37.72 | 87.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.54 | 50.88 | 60.66 | 140.03 | 32.29 | 684.00 | 0.00 | 8760.00 |
Minimum of Months | 92.86 | 34.46 | 51.84 | 116.48 | 27.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.82 | 79.17 | 69.95 | 172.03 | 41.30 | 162.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158849E+09 | 55982360.59 | 0.102867E+09 | 0.512597E+09 | 97115959.55 |
February | 0.157130E+09 | 55469701.08 | 0.101660E+09 | 0.524263E+09 | 67663664.12 |
March | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.665779E+09 | 53524329.35 |
April | 0.188992E+09 | 71828623.30 | 0.117164E+09 | 0.644833E+09 | 24983045.02 |
May | 0.166569E+09 | 49066205.86 | 0.117503E+09 | 0.583214E+09 | 29489666.93 |
June | 0.174651E+09 | 59915364.64 | 0.114736E+09 | 0.605112E+09 | 30105060.03 |
July | 0.154028E+09 | 36129135.52 | 0.117899E+09 | 0.503724E+09 | 55292352.70 |
August | 0.167424E+09 | 49321519.30 | 0.118102E+09 | 0.513389E+09 | 43958663.96 |
September | 0.151382E+09 | 41525917.38 | 0.109856E+09 | 0.496803E+09 | 44910675.83 |
October | 0.147149E+09 | 37628021.32 | 0.109521E+09 | 0.446365E+09 | 61431411.44 |
November | 0.138895E+09 | 37640548.35 | 0.101254E+09 | 0.435834E+09 | 67606264.13 |
December | 0.147325E+09 | 48250125.10 | 99074415.80 | 0.471963E+09 | 0.105045E+09 |
Annual Sum or Average | 0.194719E+10 | 0.619420E+09 | 0.132778E+10 | 0.640388E+10 | 0.681126E+09 |
Minimum of Months | 0.138895E+09 | 36129135.52 | 99074415.80 | 0.435834E+09 | 24983045.02 |
Maximum of Months | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.665779E+09 | 0.105045E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158849E+09 | 55982360.59 | 0.102867E+09 | 0.512597E+09 | 97115959.55 |
February | 0.157130E+09 | 55469701.08 | 0.101660E+09 | 0.524263E+09 | 67663664.12 |
March | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.665779E+09 | 53524329.35 |
April | 0.188992E+09 | 71828623.30 | 0.117164E+09 | 0.644833E+09 | 24983045.02 |
May | 0.166569E+09 | 49066205.86 | 0.117503E+09 | 0.583214E+09 | 29489666.93 |
June | 0.174651E+09 | 59915364.64 | 0.114736E+09 | 0.605112E+09 | 30105060.03 |
July | 0.154028E+09 | 36129135.52 | 0.117899E+09 | 0.503724E+09 | 55292352.70 |
August | 0.167424E+09 | 49321519.30 | 0.118102E+09 | 0.513389E+09 | 43958663.96 |
September | 0.151382E+09 | 41525917.38 | 0.109856E+09 | 0.496803E+09 | 44910675.83 |
October | 0.147149E+09 | 37628021.32 | 0.109521E+09 | 0.446365E+09 | 61431411.44 |
November | 0.138895E+09 | 37640548.35 | 0.101254E+09 | 0.435834E+09 | 67606264.13 |
December | 0.147325E+09 | 48250125.10 | 99074415.80 | 0.471963E+09 | 0.105045E+09 |
Annual Sum or Average | 0.194719E+10 | 0.619420E+09 | 0.132778E+10 | 0.640388E+10 | 0.681126E+09 |
Minimum of Months | 0.138895E+09 | 36129135.52 | 99074415.80 | 0.435834E+09 | 24983045.02 |
Maximum of Months | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.665779E+09 | 0.105045E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47356040.84 | 0.00 | 47356040.84 | 0.155094E+09 | 56432868.20 |
February | 45627293.46 | 0.00 | 45627293.46 | 0.160618E+09 | 39164807.22 |
March | 51896300.46 | 18257.31 | 51878043.15 | 0.196757E+09 | 30588782.53 |
April | 56002884.19 | 1739798.02 | 54263086.17 | 0.213131E+09 | 14277236.55 |
May | 75582452.44 | 10962496.64 | 64619955.80 | 0.277514E+09 | 16967645.84 |
June | 90010081.75 | 21792916.29 | 68217165.47 | 0.326520E+09 | 17486465.38 |
July | 78223258.59 | 10211550.70 | 68011707.89 | 0.258404E+09 | 31361107.47 |
August | 64551330.50 | 4623618.60 | 59927711.90 | 0.207663E+09 | 25523795.76 |
September | 51686267.98 | 132783.94 | 51553484.04 | 0.182771E+09 | 26280871.95 |
October | 51311374.35 | 0.00 | 51311374.35 | 0.159278E+09 | 36030684.56 |
November | 46985672.13 | 0.00 | 46985672.13 | 0.151187E+09 | 39552395.24 |
December | 46005736.81 | 0.00 | 46005736.81 | 0.149309E+09 | 61041326.37 |
Annual Sum or Average | 0.705239E+09 | 49481421.49 | 0.655757E+09 | 0.243825E+10 | 0.394708E+09 |
Minimum of Months | 45627293.46 | 0.00 | 45627293.46 | 0.149309E+09 | 14277236.55 |
Maximum of Months | 90010081.75 | 21792916.29 | 68217165.47 | 0.326520E+09 | 61041326.37 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47354580.59 | 0.00 | 47354580.59 | 0.155091E+09 | 56431714.66 |
February | 45625938.29 | 0.00 | 45625938.29 | 0.160615E+09 | 39163492.69 |
March | 51894855.67 | 18256.46 | 51876599.22 | 0.196754E+09 | 30587549.15 |
April | 56001228.12 | 1739716.48 | 54261511.64 | 0.213127E+09 | 14276481.17 |
May | 75579760.18 | 10961982.81 | 64617777.37 | 0.277507E+09 | 16967087.05 |
June | 90006748.40 | 21791894.82 | 68214853.58 | 0.326512E+09 | 17485948.39 |
July | 78220373.67 | 10211072.07 | 68009301.60 | 0.258397E+09 | 31360308.25 |
August | 64549158.84 | 4623401.88 | 59925756.96 | 0.207658E+09 | 25523022.59 |
September | 51684612.67 | 132777.71 | 51551834.95 | 0.182767E+09 | 26280180.11 |
October | 51309699.92 | 0.00 | 51309699.92 | 0.159274E+09 | 36029995.79 |
November | 46984147.09 | 0.00 | 46984147.09 | 0.151184E+09 | 39551501.46 |
December | 46004288.51 | 0.00 | 46004288.51 | 0.149306E+09 | 61040191.94 |
Annual Sum or Average | 0.705215E+09 | 49479102.23 | 0.655736E+09 | 0.243819E+10 | 0.394697E+09 |
Minimum of Months | 45625938.29 | 0.00 | 45625938.29 | 0.149306E+09 | 14276481.17 |
Maximum of Months | 90006748.40 | 21791894.82 | 68214853.58 | 0.326512E+09 | 61040191.94 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271477E+09 | 0.129856E+09 | 0.141621E+09 | 0.343529E+09 | 0.102223E+09 |
February | 0.282099E+09 | 0.145882E+09 | 0.136217E+09 | 0.358328E+09 | 99914714.52 |
March | 0.362491E+09 | 0.212038E+09 | 0.150452E+09 | 0.458699E+09 | 99773073.80 |
April | 0.354642E+09 | 0.198002E+09 | 0.156640E+09 | 0.445901E+09 | 80433775.87 |
May | 0.307210E+09 | 0.133052E+09 | 0.174157E+09 | 0.384442E+09 | 75282570.60 |
June | 0.321289E+09 | 0.158459E+09 | 0.162830E+09 | 0.402531E+09 | 72270908.32 |
July | 0.279702E+09 | 92349691.10 | 0.187352E+09 | 0.355088E+09 | 79156634.15 |
August | 0.308663E+09 | 0.132003E+09 | 0.176660E+09 | 0.377967E+09 | 74461210.27 |
September | 0.276276E+09 | 0.106953E+09 | 0.169323E+09 | 0.349189E+09 | 73937064.69 |
October | 0.261111E+09 | 92304616.11 | 0.168806E+09 | 0.319772E+09 | 76331367.70 |
November | 0.240705E+09 | 90656844.38 | 0.150049E+09 | 0.301922E+09 | 83626272.03 |
December | 0.251727E+09 | 0.112872E+09 | 0.138855E+09 | 0.318779E+09 | 0.101020E+09 |
Annual Sum or Average | 0.351739E+10 | 0.160443E+10 | 0.191296E+10 | 0.441615E+10 | 0.101843E+10 |
Minimum of Months | 0.240705E+09 | 90656844.38 | 0.136217E+09 | 0.301922E+09 | 72270908.32 |
Maximum of Months | 0.362491E+09 | 0.212038E+09 | 0.187352E+09 | 0.458699E+09 | 0.102223E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 498.48 | 114.57 | 153.98 | 41.80 | 112.17 | 0.00 | 0.00 |
February | 566.19 | 88.31 | 167.62 | 45.86 | 121.77 | 0.00 | 0.00 |
March | 643.99 | 62.73 | 184.21 | 57.26 | 126.95 | 0.00 | 0.00 |
April | 661.81 | 30.10 | 189.04 | 56.77 | 132.27 | 0.00 | 0.00 |
May | 642.49 | 34.47 | 180.82 | 44.82 | 135.99 | 0.00 | 0.00 |
June | 718.53 | 36.40 | 204.21 | 63.05 | 141.17 | 0.00 | 0.00 |
July | 568.56 | 64.18 | 173.42 | 34.60 | 138.82 | 0.00 | 0.00 |
August | 538.07 | 51.53 | 173.22 | 40.28 | 132.94 | 0.00 | 0.00 |
September | 524.16 | 54.73 | 156.69 | 32.14 | 124.54 | 0.00 | 0.00 |
October | 451.97 | 72.51 | 148.19 | 28.10 | 120.09 | 0.00 | 0.00 |
November | 452.62 | 82.35 | 143.43 | 29.04 | 114.38 | 0.00 | 0.00 |
December | 463.83 | 123.94 | 144.36 | 36.03 | 108.33 | 0.00 | 0.00 |
Annual Sum or Average | 560.54 | 68.00 | 168.22 | 42.42 | 125.79 | 0.00 | 0.00 |
Minimum of Months | 451.97 | 30.10 | 143.43 | 28.10 | 108.33 | 0.00 | 0.00 |
Maximum of Months | 718.53 | 123.94 | 204.21 | 63.05 | 141.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1282.58 | 381.65 | 1013.58 | 484.83 | 528.75 | 0.00 | 0.00 |
February | 1481.18 | 412.99 | 1166.08 | 603.02 | 563.07 | 0.00 | 0.00 |
March | 1712.58 | 372.50 | 1353.38 | 791.66 | 561.72 | 0.00 | 0.00 |
April | 1720.29 | 310.30 | 1368.22 | 763.90 | 604.32 | 0.00 | 0.00 |
May | 1435.34 | 281.06 | 1146.99 | 496.76 | 650.23 | 0.00 | 0.00 |
June | 1552.97 | 278.81 | 1239.54 | 611.34 | 628.20 | 0.00 | 0.00 |
July | 1325.74 | 295.53 | 1044.29 | 344.79 | 699.49 | 0.00 | 0.00 |
August | 1411.16 | 277.98 | 1152.42 | 492.84 | 659.57 | 0.00 | 0.00 |
September | 1347.18 | 285.23 | 1065.88 | 412.63 | 653.25 | 0.00 | 0.00 |
October | 1193.89 | 284.97 | 974.88 | 344.63 | 630.25 | 0.00 | 0.00 |
November | 1164.82 | 322.63 | 928.65 | 349.76 | 578.89 | 0.00 | 0.00 |
December | 1190.18 | 377.16 | 939.84 | 421.42 | 518.43 | 0.00 | 0.00 |
Annual Sum or Average | 1400.35 | 322.93 | 1115.36 | 508.76 | 606.60 | 0.00 | 0.00 |
Minimum of Months | 1164.82 | 277.98 | 928.65 | 344.63 | 518.43 | 0.00 | 0.00 |
Maximum of Months | 1720.29 | 412.99 | 1368.22 | 791.66 | 699.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133514E+10 | 0.306856E+09 | 0.412409E+09 | 0.111965E+09 | 0.300445E+09 | 0.00 | 0.00 |
February | 0.136974E+10 | 0.213632E+09 | 0.405513E+09 | 0.110939E+09 | 0.294574E+09 | 0.00 | 0.00 |
March | 0.172487E+10 | 0.168022E+09 | 0.493395E+09 | 0.153361E+09 | 0.340035E+09 | 0.00 | 0.00 |
April | 0.171542E+10 | 78018397.52 | 0.489989E+09 | 0.147137E+09 | 0.342852E+09 | 0.00 | 0.00 |
May | 0.172085E+10 | 92316992.20 | 0.484300E+09 | 0.120057E+09 | 0.364243E+09 | 0.00 | 0.00 |
June | 0.186243E+10 | 94359726.21 | 0.529319E+09 | 0.163416E+09 | 0.365904E+09 | 0.00 | 0.00 |
July | 0.152284E+10 | 0.171898E+09 | 0.464500E+09 | 92680893.81 | 0.371819E+09 | 0.00 | 0.00 |
August | 0.144116E+10 | 0.138028E+09 | 0.463948E+09 | 0.107890E+09 | 0.356058E+09 | 0.00 | 0.00 |
September | 0.135861E+10 | 0.141848E+09 | 0.406134E+09 | 83317396.40 | 0.322817E+09 | 0.00 | 0.00 |
October | 0.121056E+10 | 0.194198E+09 | 0.396918E+09 | 75256042.65 | 0.321662E+09 | 0.00 | 0.00 |
November | 0.117319E+10 | 0.213464E+09 | 0.371759E+09 | 75281096.70 | 0.296478E+09 | 0.00 | 0.00 |
December | 0.124232E+10 | 0.331950E+09 | 0.386659E+09 | 96500250.19 | 0.290159E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.176771E+11 | 0.214459E+10 | 0.530484E+10 | 0.133780E+10 | 0.396704E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117319E+10 | 78018397.52 | 0.371759E+09 | 75256042.65 | 0.290159E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186243E+10 | 0.331950E+09 | 0.529319E+09 | 0.163416E+09 | 0.371819E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343527E+10 | 0.102222E+10 | 0.271477E+10 | 0.129856E+10 | 0.141621E+10 | 0.00 | 0.00 |
February | 0.358326E+10 | 0.999098E+09 | 0.282099E+10 | 0.145882E+10 | 0.136217E+10 | 0.00 | 0.00 |
March | 0.458698E+10 | 0.997705E+09 | 0.362491E+10 | 0.212038E+10 | 0.150452E+10 | 0.00 | 0.00 |
April | 0.445899E+10 | 0.804288E+09 | 0.354642E+10 | 0.198002E+10 | 0.156640E+10 | 0.00 | 0.00 |
May | 0.384442E+10 | 0.752796E+09 | 0.307210E+10 | 0.133052E+10 | 0.174157E+10 | 0.00 | 0.00 |
June | 0.402531E+10 | 0.722680E+09 | 0.321289E+10 | 0.158459E+10 | 0.162830E+10 | 0.00 | 0.00 |
July | 0.355085E+10 | 0.791556E+09 | 0.279702E+10 | 0.923497E+09 | 0.187352E+10 | 0.00 | 0.00 |
August | 0.377965E+10 | 0.744529E+09 | 0.308663E+10 | 0.132003E+10 | 0.176660E+10 | 0.00 | 0.00 |
September | 0.349188E+10 | 0.739322E+09 | 0.276276E+10 | 0.106953E+10 | 0.169323E+10 | 0.00 | 0.00 |
October | 0.319770E+10 | 0.763259E+09 | 0.261111E+10 | 0.923046E+09 | 0.168806E+10 | 0.00 | 0.00 |
November | 0.301920E+10 | 0.836258E+09 | 0.240705E+10 | 0.906568E+09 | 0.150049E+10 | 0.00 | 0.00 |
December | 0.318778E+10 | 0.101020E+10 | 0.251727E+10 | 0.112872E+10 | 0.138855E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.441613E+11 | 0.101839E+11 | 0.351739E+11 | 0.160443E+11 | 0.191296E+11 | 0.00 | 0.00 |
Minimum of Months | 0.301920E+10 | 0.722680E+09 | 0.240705E+10 | 0.906568E+09 | 0.136217E+10 | 0.00 | 0.00 |
Maximum of Months | 0.458698E+10 | 0.102222E+10 | 0.362491E+10 | 0.212038E+10 | 0.187352E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.653188E+09 | -522971229.5 | 0.00 | 0.00 | 744.00 | 0.00 | -130217051.5 | 58.99 | 0.00 | 0.00 |
February | 0.595193E+09 | -477409796.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117783610.0 | 58.99 | 0.00 | 0.00 |
March | 0.680490E+09 | -549218561.5 | 0.00 | 0.00 | 744.00 | 0.00 | -131271417.9 | 58.99 | 0.00 | 0.00 |
April | 0.625463E+09 | -499157971.3 | 0.00 | 0.00 | 720.00 | 0.00 | -126304625.4 | 58.99 | 0.00 | 0.00 |
May | 0.638263E+09 | -507775493.9 | 0.00 | 0.00 | 744.00 | 0.00 | -130487218.9 | 58.99 | 0.00 | 0.00 |
June | 0.625117E+09 | -498276206.5 | 0.00 | 0.00 | 720.00 | 0.00 | -126840733.7 | 58.99 | 0.00 | 0.00 |
July | 0.609152E+09 | -479128310.1 | 0.00 | 0.00 | 744.00 | 0.00 | -130023908.8 | 58.99 | 0.00 | 0.00 |
August | 0.649669E+09 | -518262629.5 | 0.00 | 0.00 | 744.00 | 0.00 | -131406401.1 | 58.99 | 0.00 | 0.00 |
September | 0.616357E+09 | -490046307.1 | 0.00 | 0.00 | 720.00 | 0.00 | -126310806.8 | 58.99 | 0.00 | 0.00 |
October | 0.632452E+09 | -502316844.2 | 0.00 | 0.00 | 744.00 | 0.00 | -130135562.8 | 58.99 | 0.00 | 0.00 |
November | 0.618661E+09 | -492732573.2 | 0.00 | 0.00 | 720.00 | 0.00 | -125928869.4 | 58.99 | 0.00 | 0.00 |
December | 0.650905E+09 | -520536077.2 | 0.00 | 0.00 | 744.00 | 0.00 | -130369068.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.759491E+10 | -.605783E+10 | 8760.00 | -.153708E+10 | 58.99 | |||||
Minimum of Months | 0.595193E+09 | -549218561.5 | 0.00 | 0.00 | 672.00 | 0.00 | -131406401.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.680490E+09 | -477409796.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117783610.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | ||||||||||
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182450E+11 | 0.135685E+11 | 32167.12 | 02-JAN-00:01 | 18487.36 | 0.00 |
February | 0.00 | 0.00 | 0.175781E+11 | 0.131817E+11 | 31224.75 | 06-FEB-00:01 | 19120.80 | 0.00 |
March | 0.00 | 0.00 | 0.223785E+11 | 0.163429E+11 | 31494.70 | 27-MAR-00:01 | 18932.49 | 0.00 |
April | 0.00 | 0.00 | 0.227689E+11 | 0.157835E+11 | 31914.11 | 10-APR-00:01 | 17917.23 | 0.00 |
May | 0.00 | 0.00 | 0.253423E+11 | 0.164418E+11 | 32186.43 | 22-MAY-00:01 | 14214.20 | 0.00 |
June | 0.00 | 0.00 | 0.258405E+11 | 0.168061E+11 | 32426.32 | 05-JUN-00:01 | 17583.39 | 0.00 |
July | 0.00 | 0.00 | 0.207555E+11 | 0.144959E+11 | 31714.55 | 03-JUL-00:01 | 18687.74 | 0.00 |
August | 0.00 | 0.00 | 0.243296E+11 | 0.154901E+11 | 32729.68 | 07-AUG-00:01 | 15265.58 | 0.00 |
September | 0.00 | 0.00 | 0.217681E+11 | 0.143701E+11 | 32650.55 | 25-SEP-00:01 | 17598.38 | 0.00 |
October | 0.00 | 0.00 | 0.205192E+11 | 0.134688E+11 | 32748.43 | 30-OCT-00:01 | 16850.46 | 0.00 |
November | 0.00 | 0.00 | 0.188511E+11 | 0.129617E+11 | 32546.93 | 13-NOV-00:01 | 17340.30 | 0.00 |
December | 0.00 | 0.00 | 0.176943E+11 | 0.129114E+11 | 31632.36 | 11-DEC-00:01 | 19068.46 | 0.00 |
Annual Sum or Average | 0.256071E+12 | 0.175822E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.175781E+11 | 0.129114E+11 | 31224.75 | 14214.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258405E+11 | 0.168061E+11 | 32748.43 | 19120.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.545525E+11 | 0.412785E+11 | 114486.79 | 09-JAN-00:06 | 62710.99 | 0.00 |
February | 0.00 | 0.00 | 0.577407E+11 | 0.439901E+11 | 109443.41 | 20-FEB-08:53 | 67667.78 | 0.00 |
March | 0.00 | 0.00 | 0.764015E+11 | 0.558879E+11 | 110962.70 | 20-MAR-00:01 | 65560.80 | 0.00 |
April | 0.00 | 0.00 | 0.816269E+11 | 0.567876E+11 | 111918.86 | 02-APR-21:43 | 63632.36 | 0.00 |
May | 0.00 | 0.00 | 0.866142E+11 | 0.561262E+11 | 115205.47 | 29-MAY-23:43 | 58778.03 | 0.00 |
June | 0.00 | 0.00 | 0.894999E+11 | 0.582959E+11 | 115360.80 | 11-JUN-07:03 | 59275.16 | 0.00 |
July | 0.00 | 0.00 | 0.665832E+11 | 0.468806E+11 | 111861.30 | 02-JUL-14:23 | 67651.77 | 0.00 |
August | 0.00 | 0.00 | 0.740066E+11 | 0.465101E+11 | 117111.29 | 07-AUG-00:08 | 60127.11 | 0.00 |
September | 0.00 | 0.00 | 0.691855E+11 | 0.460887E+11 | 110803.50 | 24-SEP-10:43 | 65896.38 | 0.00 |
October | 0.00 | 0.00 | 0.607359E+11 | 0.400882E+11 | 113370.63 | 29-OCT-17:03 | 65035.50 | 0.00 |
November | 0.00 | 0.00 | 0.556127E+11 | 0.389242E+11 | 112413.93 | 11-NOV-08:53 | 63957.34 | 0.00 |
December | 0.00 | 0.00 | 0.514492E+11 | 0.380396E+11 | 111019.30 | 25-DEC-09:33 | 66308.80 | 0.00 |
Annual Sum or Average | 0.824009E+12 | 0.568897E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.514492E+11 | 0.380396E+11 | 109443.41 | 58778.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.894999E+11 | 0.582959E+11 | 117111.29 | 67667.78 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168807E+10 | 0.68 | 1399.81 | 02-JAN-07:05 | 0.93 |
February | 0.156991E+10 | 0.70 | 1399.81 | 02-FEB-07:10 | 0.93 |
March | 0.188149E+10 | 0.74 | 1399.81 | 27-MAR-11:50 | 0.92 |
April | 0.178425E+10 | 0.71 | 1399.81 | 03-APR-11:40 | 0.92 |
May | 0.187389E+10 | 0.72 | 1399.81 | 01-MAY-06:30 | 0.92 |
June | 0.188329E+10 | 0.74 | 1399.81 | 07-JUN-16:10 | 0.92 |
July | 0.174629E+10 | 0.68 | 1399.81 | 01-JUL-06:20 | 0.92 |
August | 0.189480E+10 | 0.74 | 1399.81 | 01-AUG-06:15 | 0.92 |
September | 0.174549E+10 | 0.71 | 1399.81 | 01-SEP-06:10 | 0.92 |
October | 0.171978E+10 | 0.69 | 1399.81 | 02-OCT-06:05 | 0.93 |
November | 0.163436E+10 | 0.68 | 1399.81 | 01-NOV-06:30 | 0.92 |
December | 0.167074E+10 | 0.68 | 1399.81 | 01-DEC-07:20 | 0.92 |
Annual Sum or Average | 0.210924E+11 | 0.71 | |||
Minimum of Months | 0.156991E+10 | 0.68 | 1399.81 | 0.92 | |
Maximum of Months | 0.189480E+10 | 0.74 | 1399.81 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.822858E+10 | 1.02 | 7281.40 | 02-JAN-08:10 | 1.54 |
February | 0.787721E+10 | 1.14 | 7281.40 | 02-FEB-08:20 | 1.55 |
March | 0.949477E+10 | 1.22 | 7281.40 | 02-MAR-15:25 | 1.55 |
April | 0.934068E+10 | 1.29 | 7281.40 | 01-APR-06:50 | 1.54 |
May | 0.967014E+10 | 1.26 | 7281.40 | 01-MAY-15:30 | 1.54 |
June | 0.971020E+10 | 1.30 | 7281.40 | 06-JUN-07:10 | 1.54 |
July | 0.888196E+10 | 1.23 | 7281.40 | 01-JUL-09:45 | 1.54 |
August | 0.925215E+10 | 1.13 | 7281.40 | 01-AUG-10:25 | 1.54 |
September | 0.880146E+10 | 1.22 | 7281.40 | 06-SEP-07:30 | 1.54 |
October | 0.852500E+10 | 1.11 | 7281.40 | 02-OCT-09:00 | 1.55 |
November | 0.803396E+10 | 1.06 | 7281.40 | 01-NOV-11:30 | 1.55 |
December | 0.811359E+10 | 0.96 | 7281.40 | 01-DEC-08:15 | 1.54 |
Annual Sum or Average | 0.105930E+12 | 1.16 | |||
Minimum of Months | 0.787721E+10 | 0.96 | 7281.40 | 1.54 | |
Maximum of Months | 0.971020E+10 | 1.30 | 7281.40 | 1.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.19 | 0.00 |
April | 0.58 | 0.00 |
May | 0.58 | 0.00 |
June | 0.30 | 0.00 |
July | 0.61 | 0.00 |
August | 0.35 | 0.00 |
September | 0.08 | 0.00 |
October | 0.16 | 0.00 |
November | 0.07 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 3.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.61 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 5.44 | 0.00 |
February | 5.86 | 0.00 |
March | 6.59 | 0.00 |
April | 8.67 | 0.00 |
May | 8.69 | 0.00 |
June | 10.29 | 0.00 |
July | 9.92 | 0.00 |
August | 10.23 | 0.00 |
September | 7.95 | 0.00 |
October | 4.37 | 0.00 |
November | 6.22 | 0.00 |
December | 5.89 | 0.00 |
Annual Sum or Average | 90.10 | |
Minimum of Months | 4.37 | 0.00 |
Maximum of Months | 10.29 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.675884E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.650496E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.819540E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.818452E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.892109E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.906166E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.743616E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.852126E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.770393E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.729525E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.678943E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.655334E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.919258E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.650496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.906166E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.247925E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.255559E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.328585E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.341961E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.357961E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.365865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.288428E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310542E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.294180E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.265038E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246369E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.236226E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.353864E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.236226E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365865E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168807E+10 | 0.182450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156991E+10 | 0.175781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188149E+10 | 0.223785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178425E+10 | 0.227689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187389E+10 | 0.253423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188329E+10 | 0.258405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174629E+10 | 0.207555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189480E+10 | 0.243296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174549E+10 | 0.217681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171978E+10 | 0.205192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163436E+10 | 0.188511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167074E+10 | 0.176943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210924E+11 | 0.256071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156991E+10 | 0.175781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189480E+10 | 0.258405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.822858E+10 | 0.545525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787721E+10 | 0.577407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949477E+10 | 0.764015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.934068E+10 | 0.816269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.967014E+10 | 0.866142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.971020E+10 | 0.894999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888196E+10 | 0.665832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925215E+10 | 0.740066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.880146E+10 | 0.691855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852500E+10 | 0.607359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803396E+10 | 0.556127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.811359E+10 | 0.514492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105930E+12 | 0.824009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.787721E+10 | 0.514492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.971020E+10 | 0.894999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.168807E+10 | 0.00 | 0.00 | 0.00 | 0.507077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156991E+10 | 0.00 | 0.00 | 0.00 | 0.493505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188149E+10 | 0.00 | 0.00 | 0.00 | 0.631391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178425E+10 | 0.00 | 0.00 | 0.00 | 0.640027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187389E+10 | 0.00 | 0.00 | 0.00 | 0.704721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188329E+10 | 0.00 | 0.00 | 0.00 | 0.717837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174629E+10 | 0.00 | 0.00 | 0.00 | 0.568987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189480E+10 | 0.00 | 0.00 | 0.00 | 0.662647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174549E+10 | 0.00 | 0.00 | 0.00 | 0.595843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171978E+10 | 0.00 | 0.00 | 0.00 | 0.557547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163436E+10 | 0.00 | 0.00 | 0.00 | 0.515508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167074E+10 | 0.00 | 0.00 | 0.00 | 0.488260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210924E+11 | 0.00 | 0.00 | 0.00 | 0.708335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.156991E+10 | 0.00 | 0.00 | 0.00 | 0.488260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189480E+10 | 0.00 | 0.00 | 0.00 | 0.717837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.822858E+10 | 0.00 | 0.00 | 0.00 | 0.165640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787721E+10 | 0.00 | 0.00 | 0.00 | 0.176787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949477E+10 | 0.00 | 0.00 | 0.00 | 0.233637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.934068E+10 | 0.00 | 0.00 | 0.00 | 0.248554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.967014E+10 | 0.00 | 0.00 | 0.00 | 0.261260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.971020E+10 | 0.00 | 0.00 | 0.00 | 0.268762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888196E+10 | 0.00 | 0.00 | 0.00 | 0.199608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925215E+10 | 0.00 | 0.00 | 0.00 | 0.218021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.880146E+10 | 0.00 | 0.00 | 0.00 | 0.206166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852500E+10 | 0.00 | 0.00 | 0.00 | 0.179788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803396E+10 | 0.00 | 0.00 | 0.00 | 0.166029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.811359E+10 | 0.00 | 0.00 | 0.00 | 0.155090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105930E+12 | 0.00 | 0.00 | 0.00 | 0.247934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.787721E+10 | 0.00 | 0.00 | 0.00 | 0.155090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.971020E+10 | 0.00 | 0.00 | 0.00 | 0.268762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.323382E+10 | 0.00 | 49574.04 | 0.00 | 0.00 | 20998.36 | 0.00 | 0.20 |
February | 0.00 | 0.324843E+10 | 0.00 | 4602.40 | 0.00 | 0.00 | 3922.44 | 0.00 | 0.20 |
March | 0.00 | 0.428515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.510066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.610660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.629786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.433513E+10 | 0.00 | 1744.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.581213E+10 | 0.00 | 30751.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.519100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.470035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.396801E+10 | 0.00 | 387.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.336982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.556489E+11 | 0.00 | 87060.08 | 0.00 | 0.00 | 24920.80 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.323382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.629786E+10 | 0.00 | 49574.04 | 0.00 | 0.00 | 20998.36 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6004590.86 | 0.728263E+10 | 0.00 | 1693466.46 | 793231.63 | 0.00 | 59074653.47 | 0.00 | 0.19 |
February | 394762.64 | 0.780690E+10 | 0.00 | 624845.17 | 129009.04 | 0.00 | 16729522.05 | 0.00 | 0.20 |
March | 0.00 | 0.987968E+10 | 0.00 | 190606.13 | 1977203.08 | 0.00 | 2337940.34 | 0.00 | 0.22 |
April | 0.00 | 0.126770E+11 | 0.00 | 0.00 | 4078877.02 | 0.00 | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.149309E+11 | 0.00 | 0.00 | 2615977.81 | 0.00 | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.157457E+11 | 0.00 | 0.00 | 1726785.96 | 0.00 | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.104081E+11 | 0.00 | 0.00 | 2679528.81 | 0.00 | 0.00 | 0.00 | 0.20 |
August | 176744.56 | 0.132282E+11 | 0.00 | 52321.57 | 3526617.71 | 0.00 | 884066.27 | 0.00 | 0.21 |
September | 0.00 | 0.126062E+11 | 0.00 | 0.00 | 2409306.33 | 0.00 | 0.00 | 0.00 | 0.21 |
October | 306418.30 | 0.109082E+11 | 0.00 | 31004.55 | 3584909.38 | 0.00 | 1465236.72 | 0.00 | 0.19 |
November | 0.00 | 0.935172E+10 | 0.00 | 201440.51 | 484496.60 | 0.00 | 8097523.48 | 0.00 | 0.19 |
December | 9084603.11 | 0.765283E+10 | 0.00 | 930738.95 | 222180.43 | 0.00 | 32025655.47 | 0.00 | 0.18 |
Annual Sum or Average | 15967119.47 | 0.132478E+12 | 0.00 | 3724423.34 | 24228123.81 | 0.00 | 0.120615E+09 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.728263E+10 | 0.00 | 0.00 | 129009.04 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 9084603.11 | 0.157457E+11 | 0.00 | 1693466.46 | 4078877.02 | 0.00 | 59074653.47 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |