Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1248.96 | 258.31 | 258.31 |
Net Site Energy | 1248.96 | 258.31 | 258.31 |
Total Source Energy | 3238.69 | 669.82 | 669.82 |
Net Source Energy | 3238.69 | 669.82 | 669.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 344.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 67.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 904.86 | 344.10 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 344.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 67.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 59.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 33.10 | 71.17 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 187.14 | 71.17 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 33.10 | 71.17 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 187.14 | 71.17 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 904.859 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 904.859 | 100.00 |
Total On-Site and Utility Electric Sources | 904.859 | 100.00 |
Total Electricity End Uses | 904.859 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 28.67 |
Time Setpoint Not Met During Occupied Cooling | 8.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1009.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-06:10 | - | - | - | 27-JUL-11:30 |
Heating | 0.00 | 290949.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20426.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6788.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1710.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74657.47 | 290949.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 290949.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20426.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4482.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1710.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 373.00 | 0.00 | 0.00 | 0.00 |
Cooling | 212.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2865.69 | 373.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.14 | 0.00 | 0.00 | 0.00 |
Cooling | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 592.68 | 77.14 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.14 | 0.00 | 0.00 | 0.00 |
Cooling | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 592.68 | 77.14 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.15 |
ZONE2 FINE STORAGE DIRECT AIR | 2.90 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.63 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.63 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 145448.76 |
PSZ-OFFICE HEATING COIL | 29165.65 |
PSZ-FINE STORAGE HEATING COIL | 91803.47 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 145448.76 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-FINE STORAGE | 2.90 | 2.90 | 2.90 | 2.90 | 2.90 | 2.90 | 1.00 | 1.00 | 2.90 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.15 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.90 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 22171.97 | 29165.65 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.90 | 2.90 | 2.90 | 2.90 | 68197.59 | 91803.47 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.15 | 0.572775 | 1.15 | 21622.93 | 22171.97 | 11085.99 | 22171.97 | 0.745443 | 0.745440 | 0.745440 | 0.745440 |
PSZ-FINE STORAGE COOLING COIL | 2.90 | 1.45 | 2.90 | 65164.03 | 68197.59 | 34098.79 | 68197.59 | 0.690013 | 0.690010 | 0.690010 | 0.690010 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.15 | 1306.06 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.90 | 3176.70 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 28 | 1 | VerySmooth | 3.241 | 0.385 | 0.305 | 0.391 |
2 | SKYLIGHT_U_1.02_SHGC_0.39 | 29 | 1 | VerySmooth | 5.779 | 0.390 | 0.223 | 0.391 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11187.36426 | 13424.83711 | 0.95463 | 1.14555 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44457E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10916.53940 | 13099.84728 | 0.31784 | 0.38141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36356.52568 | 43627.83082 | 2.41867 | 2.90241 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44457E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 46658.95409 | 55990.74491 | 1.14412 | 1.37294 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 121207.29648 | 145448.75577 | 3.02633 | 3.63160 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -6.30000 | 2.29779E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17189.60 | 1.14555 | 1.14555 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12271.65 | 0.38141 | 0.38141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52604.32 | 2.90241 | 2.90241 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 48180.89 | 1.37294 | 1.37294 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14555 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.90241 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.63160 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.63160 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 145448.76388 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 145448.75577 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14555 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14555 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14555 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14555 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14555 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.14555 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.90241 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.90241 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.90241 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.90241 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.90241 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.90241 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.14555 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.90241 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14555 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14555 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14555 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14555 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14555 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14555 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57278 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14555 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21622.93465 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22171.97000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11085.98500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22171.97000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74544 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74544 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74544 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74544 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22171.97000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29165.64717 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14555 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1306.05629 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29165.64717 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.90241 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.90241 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.90241 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.90241 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.90241 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.90241 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.45121 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.90241 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 65164.03021 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 68197.59000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 34098.79500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 68197.59000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69001 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69001 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69001 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69001 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68197.59000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 91803.46842 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.90241 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3176.70200 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 91803.46842 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21282.6 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 65942.2 | 13.28 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.6444777041E-002 | 2.6622258672E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2677497962 | 0.3177980086 | Pass | Pass | 1.5993517446 | 10.9201548898 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.2107289826E-002 | 4.5089333958E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.494 | 0.497 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.385 | 0.391 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.510 | 0.512 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.77 | 83.77 | 123.55 | |
Exterior Lighting Total | 7857.24 | 123.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22171.97 | 16527.87 | 5644.10 | 0.75 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68197.59 | 47057.02 | 21140.57 | 0.69 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21282.6 | 10.32 | ||||
PSZ-FINE STORAGE COOLING COIL | 65942.2 | 13.28 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 145448.76 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29165.65 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 91803.47 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.63 | 337.41 | 92.91 | 1.00 | 3.27 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.15 | 1306.06 | 1140.11 | 1.00 | 1.33 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.90 | 3176.70 | 1094.51 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11187.36 | 13424.84 | 56.67 | 0.955 | 1.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00831 | 33.07 | 0.01445 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 36356.53 | 43627.83 | 31.31 | 2.419 | 2.902 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00919 | 33.07 | 0.01445 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00392 | 34.40 | 0.01445 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10916.54 | 13099.85 | 55.30 | 0.318 | 0.381 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00728 | -6.30 | 0.00230 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 46658.95 | 55990.74 | 40.18 | 1.144 | 1.373 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00557 | -6.30 | 0.00230 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 121207.30 | 145448.76 | 45.38 | 3.026 | 3.632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00792 | -6.30 | 0.00230 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.15 | 1.15 | 0.38 | 0.38 | 1.1456 | 1.1456 | 1.1456 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.90 | 2.90 | 1.37 | 1.37 | 2.9024 | 2.9024 | 2.9024 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 145448.764 | 145448.764 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 145448.76 | 145448.76 | 3.631595 | 6.34 | 6.34 | 0.00665799 | 43.33 | 26.63 | 0.01600000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 9.99 | 0.00791771 | 100.0000 | 145448.76 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22171.970 | 0.000 | 1.145550 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22171.97 | 19081.78 | 1.145550 | 24.86 | 16.68 | 0.00895382 | 12.00 | 10.94 | 0.00800000 | 33.07 | 0.01444567 | 23.16 | 10.5046 | 23.90 | 0.00830921 | 43.4010 | 11187.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29165.647 | 29165.647 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29165.65 | 29165.65 | 1.145553 | 12.42 | 8.67 | 0.00570637 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 10.5046 | 21.10 | 0.00727749 | 45.1408 | 10916.54 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 68197.590 | 0.000 | 2.902410 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 68197.59 | 57695.44 | 2.902410 | 27.63 | 17.86 | 0.00927130 | 12.00 | 10.94 | 0.00800000 | 34.30 | 0.01444567 | 23.48 | 12.1943 | 26.70 | 0.00918524 | 40.5667 | 36356.53 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 91803.468 | 91803.468 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 91803.47 | 91803.47 | 2.902408 | 9.92 | 6.36 | 0.00472401 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 12.1943 | 15.55 | 0.00556669 | 49.0442 | 46658.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 145448.764 | 145448.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1610 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.631595 | 4.21619662 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 145448.76 | 145448.76 | 1.0000 | 4.21619662 | 3.631595 | 6.34 | 6.34 | 0.00665799 | 23098.0 | 43.33 | 26.63 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 145448.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 9.99 | 0.00791771 | 9.99 | 0.00791771 | 100.0000 | 145448.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22171.970 | 0.000 | 1.145550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4847 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22171.97 | 19081.78 | 1.0000 | 1.32995668 | 1.145550 | 24.86 | 16.68 | 0.00895382 | 47789.5 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22171.97 | 33.07 | 0.01444567 | 23.16 | 0.12033533 | 10.5046 | 23.90 | 0.00830921 | 23.90 | 0.00830921 | 43.4010 | 11187.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29165.647 | 29165.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.145553 | 1.32996014 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29165.65 | 29165.65 | 1.0000 | 1.32996014 | 1.145553 | 12.42 | 8.67 | 0.00570637 | 26883.6 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29165.65 | -6.30 | 0.00229779 | -6.30 | 0.12033533 | 10.5046 | 21.05 | 0.00727749 | 21.10 | 0.00727749 | 45.1408 | 10916.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68197.590 | 0.000 | 2.902410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0749 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 68197.59 | 57695.44 | 1.0000 | 3.36962992 | 2.902410 | 27.63 | 17.86 | 0.00927130 | 51428.2 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68197.59 | 34.30 | 0.01444567 | 23.48 | 0.35392745 | 12.1943 | 26.70 | 0.00854767 | 26.70 | 0.00918524 | 40.5667 | 36356.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91803.468 | 91803.468 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.902408 | 3.36962813 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 91803.47 | 91803.47 | 1.0000 | 3.36962813 | 2.902408 | 9.92 | 6.36 | 0.00472401 | 21868.4 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91803.47 | -6.30 | 0.00229779 | -6.30 | 0.35392745 | 12.1943 | 15.55 | 0.00556669 | 15.55 | 0.00556669 | 49.0442 | 46658.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2407.67 | 1947.50 | 1009.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2407.67 | 1947.50 | 1009.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 35.00 | 247.33 | 28.67 | 8.33 |
ZONE2 FINE STORAGE | 202.00 | 91.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 229.67 | 298.67 | 28.67 | 8.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.404 | 0.397 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
Electricity:Building | 629.18 | 4992.32 | 01-JAN-00:10 | 48037.94 | 17-APR-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 429.58 | 2759.73 | 01-JAN-00:10 | 33963.13 | 17-APR-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.31 | 483.00 | 20-JAN-06:10 | 2196.42 | 30-JAN-12:50 |
WaterSystems:Electricity | 25.31 | 483.00 | 20-JAN-06:10 | 2196.42 | 30-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 25.31 | 483.00 | 20-JAN-06:10 | 2196.42 | 30-JAN-12:50 |
Fans:Electricity | 67.56 | 0.00 | 01-JAN-00:40 | 6788.05 | 17-APR-13:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.94 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-APR-13:50 |
Ventilation (simple):Fans:Electricity | 7.94 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-APR-13:50 |
ElectricityPurchased:Facility | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
ElectricityPurchased:Plant | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
Cogeneration:ElectricityPurchased | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
ElectricityNet:Plant | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
Cogeneration:ElectricityNet | 904.86 | 5475.32 | 01-JAN-08:00 | 74657.47 | 08-JUL-14:50 |
Electricity:HVAC | 126.82 | 0.00 | 01-JAN-00:40 | 26305.81 | 01-AUG-17:00 |
General:Fans:Electricity | 59.62 | 0.00 | 01-JAN-00:40 | 4820.17 | 03-JAN-10:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 67.20 | 0.00 | 01-JAN-00:10 | 21823.05 | 01-AUG-17:00 |
ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:50 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:50 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 344.10 | 4000.00 | 22-MAY-00:10 | 290949.51 | 12-FEB-06:10 |
Gas:HVAC | 344.10 | 4000.00 | 22-MAY-00:10 | 290949.51 | 12-FEB-06:10 |
Heating:Gas | 344.10 | 4000.00 | 22-MAY-00:10 | 290949.51 | 12-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 700.60 | 0.00 | 01-JAN-00:40 | 446904.89 | 12-FEB-06:10 |
EnergyTransfer:Building | 305.57 | 0.00 | 01-JAN-00:40 | 218923.33 | 12-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 65.14 | 0.00 | 01-JAN-00:10 | 22581.63 | 13-FEB-07:10 |
Heating:EnergyTransfer | 159.93 | 0.00 | 01-JAN-00:40 | 218923.33 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 14.31 | 0.00 | 01-JAN-00:10 | 22581.63 | 13-FEB-07:10 |
Cooling:EnergyTransfer | 145.64 | 0.00 | 01-JAN-00:10 | 45271.84 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 50.84 | 0.00 | 01-JAN-00:10 | 12973.49 | 17-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 158.48 | 0.00 | 01-JAN-00:40 | 69032.48 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 63.67 | 0.00 | 01-JAN-00:40 | 69032.48 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 94.80 | 0.00 | 01-JAN-00:10 | 35377.81 | 02-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 81.95 | 0.00 | 01-JAN-00:10 | 145975.89 | 12-FEB-05:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 81.95 | 0.00 | 01-JAN-00:10 | 145975.89 | 12-FEB-05:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 395.03 | 0.00 | 01-JAN-00:40 | 227981.56 | 12-FEB-06:10 |
HeatingCoils:EnergyTransfer | 162.57 | 0.00 | 01-JAN-00:40 | 227981.56 | 12-FEB-06:10 |
CoolingCoils:EnergyTransfer | 232.47 | 0.00 | 01-JAN-00:10 | 71293.13 | 03-AUG-16:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 14.309 | -50.834 | 0.000 | 0.000 | 3.779 | 30.994 | 31.946 | 12.547 | 0.000 | 2.396 | 0.000 | 0.000 | -7.590 | 0.000 | -16.038 | -21.508 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 63.673 | -94.800 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 5.689 | 0.004 | 0.000 | 0.000 | 0.000 | -103.744 | -7.474 |
ZONE3 BULK STORAGE | 81.948 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 41.342 | 0.000 | 7.787 | 0.005 | 0.000 | -17.724 | 0.000 | -531.659 | -3.339 |
Total Facility | 81.948 | 0.000 | 77.982 | -145.634 | 0.000 | 0.000 | 3.779 | 481.960 | 139.282 | 53.888 | 0.000 | 15.872 | 0.009 | 0.000 | -25.315 | 0.000 | -651.441 | -32.321 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-JUN-19:03 | 0.00 | 0.00 | 0.00 | -19720.45 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 1098.72 | 0.00 | 0.00 | 17672.38 | 0.00 | -0.00 | 0.00 | -83.35 | 0.00 |
ZONE2 FINE STORAGE | 11-JUN-12:43 | 0.00 | 0.00 | 0.00 | -57278.22 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 1840.46 | 54237.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-MAY-17:06 | 0.00 | 0.00 | 0.00 | -71118.53 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 6154.92 | 0.00 | 2100.86 | 70502.00 | 0.00 | 0.00 | 0.00 | -14681.61 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-FEB-06:01 | 0.00 | 0.00 | 28764.95 | 0.00 | 0.00 | 0.00 | 55.89 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.62 | 0.00 | -347.84 | -29427.57 |
ZONE2 FINE STORAGE | 14-FEB-00:42 | 0.00 | 0.00 | 89454.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13335.89 | -77318.59 |
ZONE3 BULK STORAGE | 12-FEB-05:43 | 146045.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2825.88 | 0.00 | -111315.56 | -34663.67 |
Total Facility | 12-FEB-06:13 | 145815.91 | 0.00 | 86502.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4129.34 | 0.00 | -147683.68 | -85497.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1456 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1456 | 0.1050 | 1.0000 | 0.1203 | 0.1050 | ||
PSZ-FINE STORAGE | 2.9024 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.9024 | 0.1219 | 1.0000 | 0.3539 | 0.1219 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1456 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1456 | 1.0000 | 1.0000 | 0.1203 | 0.1050 | ||
PSZ-FINE STORAGE | 2.9024 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.9024 | 1.0000 | 1.0000 | 0.3539 | 0.1219 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1456 | 1.1456 | 1.1456 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.9024 | 2.9024 | 2.9024 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1456 | 1.1456 | 1.1456 | 1.1456 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.9024 | 2.9024 | 2.9024 | 2.9024 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1456 | 1.1456 | 1.1456 | 0.1203 | 0.3155 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.9024 | 2.9024 | 2.9024 | 0.3539 | 0.2578 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1456 | 1.1456 | 1.1456 | 1.1456 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.9024 | 2.9024 | 2.9024 | 2.9024 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 28.67 |
Number of hours cooling loads not met | 8.33 |
Number of hours not met | 37.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 344.10 | 290949.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 67.20 | 21823.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.55 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 7.94 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 59.62 | 4820.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.31 | 2196.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 904.86 |
Natural Gas | 0.00 | 344.10 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1248.96 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 13.90 |
Fans (All) | 13.97 |
Service Water Heating | 5.23 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 187.14 |
Subtotal | 187.14 |
Natural Gas [MJ/m2] | |
Space Heating | 71.17 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 71.17 |
Subtotal | 71.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.59 |
Space Heating | 27.55 |
Space Cooling | 5.38 |
Fans (All) | 5.41 |
Service Water Heating | 2.03 |
Receptacle Equipment | 11.15 |
Miscellaneous | 9.89 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118212E+12 |
February | 0.000 | 0.762533E+11 |
March | 0.000 | 0.133943E+11 |
April | 0.000 | 0.107291E+11 |
May | 0.000 | 0.107314E+11 |
June | 0.000 | 0.103680E+11 |
July | 0.000 | 0.107136E+11 |
August | 0.000 | 0.107136E+11 |
September | 0.000 | 0.103680E+11 |
October | 0.000 | 0.110988E+11 |
November | 0.000 | 0.165245E+11 |
December | 0.000 | 0.449918E+11 |
Annual Sum or Average | 0.344098E+12 | |
Minimum of Months | 0.000 | 0.103680E+11 |
Maximum of Months | 0.000 | 0.118212E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8140774.09 | 568.00 | 21-JAN-13:40 | 7.93 | 4.31 | 0.197435E+09 | 297.51 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 91924797.56 | 3033.91 | 28-FEB-16:40 | 23.70 | 12.78 | 0.189477E+09 | 301.59 | 22-FEB-15:20 | 18.13 | 13.10 |
March | 0.897376E+09 | 12471.25 | 30-MAR-17:10 | 26.60 | 17.73 | 0.244333E+09 | 304.18 | 20-MAR-14:39 | 19.63 | 8.46 |
April | 0.289547E+10 | 19346.21 | 17-APR-00:02 | 16.10 | 12.77 | 0.242650E+09 | 301.61 | 18-APR-14:50 | 25.87 | 16.76 |
May | 0.579843E+10 | 18665.63 | 13-MAY-17:43 | 25.68 | 14.42 | 0.257929E+09 | 301.61 | 19-MAY-15:00 | 30.60 | 19.35 |
June | 0.925115E+10 | 19720.53 | 07-JUN-19:03 | 21.93 | 13.35 | 0.258802E+09 | 301.61 | 09-JUN-13:50 | 29.90 | 18.81 |
July | 0.992738E+10 | 17888.61 | 17-JUL-00:01 | 26.83 | 20.75 | 0.248946E+09 | 301.61 | 08-JUL-15:00 | 36.70 | 23.88 |
August | 0.110184E+11 | 17102.76 | 14-AUG-00:01 | 25.92 | 21.14 | 0.268867E+09 | 301.61 | 25-AUG-15:09 | 31.20 | 19.32 |
September | 0.749168E+10 | 18854.36 | 13-SEP-17:43 | 22.38 | 14.67 | 0.248752E+09 | 301.61 | 13-SEP-14:09 | 24.27 | 15.56 |
October | 0.283271E+10 | 17827.30 | 11-OCT-17:43 | 22.57 | 13.50 | 0.240247E+09 | 301.60 | 03-OCT-13:30 | 21.70 | 13.52 |
November | 0.553900E+09 | 4839.76 | 04-NOV-17:25 | 20.55 | 17.47 | 0.214384E+09 | 305.54 | 27-NOV-13:30 | 22.20 | 17.55 |
December | 68543217.89 | 1187.01 | 13-DEC-13:10 | 20.22 | 17.27 | 0.203850E+09 | 305.13 | 11-DEC-16:19 | 20.93 | 15.85 |
Annual Sum or Average | 0.508351E+11 | 0.281567E+10 | ||||||||
Minimum of Months | 8140774.09 | 568.00 | 7.93 | 4.31 | 0.189477E+09 | 297.51 | 18.13 | 8.46 | ||
Maximum of Months | 0.110184E+11 | 19720.53 | 26.83 | 21.14 | 0.268867E+09 | 305.54 | 36.70 | 23.88 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391223E+09 | 3515.18 | 26-JAN-13:10 | 0.00 | -3.7 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.182857E+09 | 2794.01 | 02-FEB-12:30 | 1.40 | -1.3 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.489292E+09 | 7916.58 | 30-MAR-15:10 | 27.80 | 17.12 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.253193E+10 | 37930.60 | 17-APR-17:10 | 28.03 | 16.52 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.849241E+10 | 54287.12 | 19-MAY-17:06 | 30.40 | 19.09 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.199825E+11 | 57283.07 | 11-JUN-12:43 | 29.72 | 18.58 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.239644E+11 | 51846.16 | 03-JUL-17:06 | 29.90 | 21.13 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.255654E+11 | 53934.07 | 25-AUG-17:06 | 30.92 | 19.41 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.109555E+11 | 51505.66 | 24-SEP-14:03 | 28.40 | 19.92 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.166326E+10 | 13373.08 | 09-OCT-14:35 | 27.60 | 19.51 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.318392E+09 | 5000.60 | 22-NOV-07:05 | -3.2 | -3.9 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.267360E+09 | 4936.59 | 04-DEC-07:05 | -3.3 | -4.9 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.948045E+11 | 0.00 | ||||||||
Minimum of Months | 0.182857E+09 | 2794.01 | -3.3 | -4.9 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.255654E+11 | 57283.07 | 30.92 | 21.13 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527479E+10 | 28759.34 | 19-JAN-06:01 | 12.30 |
February | 0.356012E+10 | 28764.70 | 11-FEB-06:01 | 12.20 |
March | 0.948326E+09 | 28355.26 | 24-MAR-05:01 | 11.52 |
April | 0.233068E+09 | 26939.41 | 07-APR-05:01 | 3.22 |
May | 31715027.48 | 3440.14 | 11-MAY-06:20 | 8.53 |
June | 3884829.18 | 948.70 | 19-JUN-06:10 | 20.68 |
July | 1063224.91 | 937.74 | 31-JUL-06:10 | 20.68 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 6312642.24 | 831.21 | 25-SEP-06:10 | 19.40 |
October | 0.237344E+09 | 27583.83 | 31-OCT-05:01 | 8.30 |
November | 0.117564E+10 | 28754.00 | 27-NOV-06:01 | 17.30 |
December | 0.283714E+10 | 28166.82 | 06-DEC-06:01 | 8.40 |
Annual Sum or Average | 0.143094E+11 | |||
Minimum of Months | 0.00 | 0.00 | 3.22 | |
Maximum of Months | 0.527479E+10 | 28764.70 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267837E+11 | 89298.72 | 25-JAN-20:02 | 3.72 |
February | 0.164597E+11 | 89454.97 | 14-FEB-00:42 | 3.40 |
March | 0.146756E+10 | 60343.43 | 23-MAR-05:05 | 6.10 |
April | 0.370460E+09 | 3077.02 | 07-APR-17:00 | 24.40 |
May | 45294971.34 | 1143.93 | 30-MAY-06:15 | 20.97 |
June | 28425203.82 | 1003.64 | 19-JUN-07:00 | 21.10 |
July | 15400972.99 | 884.47 | 27-JUL-06:10 | 21.70 |
August | 17854604.28 | 2386.07 | 19-AUG-06:05 | 24.60 |
September | 54059608.75 | 1421.23 | 30-SEP-15:15 | 17.97 |
October | 0.225190E+09 | 4065.97 | 26-OCT-06:10 | 2.20 |
November | 0.338368E+10 | 86976.61 | 22-NOV-05:42 | -3.2 |
December | 0.148216E+11 | 88981.10 | 02-DEC-06:52 | -2.2 |
Annual Sum or Average | 0.636729E+11 | |||
Minimum of Months | 15400972.99 | 884.47 | -3.2 | |
Maximum of Months | 0.267837E+11 | 89454.97 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463836E+11 | 108843.23 | 07-JAN-18:57 | -5.6 |
February | 0.292524E+11 | 146045.15 | 12-FEB-05:43 | -12.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 2735216.03 | 4162.41 | 22-NOV-06:40 | -3.3 |
December | 0.630946E+10 | 48377.94 | 03-DEC-07:00 | -3.3 |
Annual Sum or Average | 0.819483E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.463836E+11 | 146045.15 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330795E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2844415.18 | 0.252986E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19055734.83 | 0.176069E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78120294.75 | 0.110083E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188911E+09 | 0.661840E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580554E+09 | 0.255546E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590319E+09 | 0.178598E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672259E+09 | 93126124.87 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220784E+09 | 0.393816E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42152541.66 | 0.135960E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 917348.01 | 0.190176E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249417E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.239592E+10 | 0.160378E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93126124.87 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672259E+09 | 0.330795E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12704164.02 | 0.197455E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43283624.03 | 0.155122E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23909322.29 | 0.964377E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39022822.31 | 0.760362E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220584E+09 | 0.576261E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158353E+10 | 0.337013E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167141E+10 | 0.250271E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168149E+10 | 0.188999E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309703E+09 | 0.378492E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23993816.42 | 0.880958E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78400575.78 | 0.968036E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523677.13 | 0.154390E+11 |
Annual Sum or Average | 0.136656E+12 | 0.568856E+10 | 0.103744E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523677.13 | 0.188999E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168149E+10 | 0.197455E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106703E+10 | 0.423018E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126376E+10 | 0.328874E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779384E+09 | 0.273873E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244329E+09 | 0.261247E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818847.88 | 0.233098E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22420580.46 | 0.175006E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5356597.42 | 0.140528E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8257768.57 | 0.124202E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130401.67 | 0.183699E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66223962.26 | 0.299577E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992596E+09 | 0.251986E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776550E+09 | 0.292007E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.522685E+10 | 0.298711E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130401.67 | 0.124202E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126376E+10 | 0.423018E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 11908.89 | 27-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.94 | 26-FEB-13:00 | 13149.91 | 03-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.69 | 30-MAR-16:10 | 7457.71 | 06-MAR-08:00 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.42 | 17-APR-16:10 | 8142.64 | 06-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511.17 | 19-MAY-16:10 | 5411.90 | 11-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3972.23 | 06-JUN-17:00 | 4390.81 | 08-JUN-06:05 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.54 | 07-JUL-16:10 | 2080.75 | 28-JUL-17:00 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.53 | 01-AUG-17:00 | 2071.10 | 25-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2741.23 | 07-SEP-16:10 | 4385.24 | 14-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2138.49 | 10-OCT-16:10 | 7659.03 | 26-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.04 | 19-NOV-15:00 | 10183.30 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10812.97 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.10 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.53 | 13149.91 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1224.34 | 19-JAN-23:00 | 36856.67 | 07-JAN-18:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.69 | 26-FEB-13:00 | 41177.75 | 11-FEB-17:40 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.42 | 30-MAR-16:00 | 18377.71 | 18-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.55 | 15-APR-16:00 | 18796.17 | 05-APR-15:03 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3426.51 | 19-MAY-16:00 | 11651.12 | 10-MAY-08:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10109.24 | 06-JUN-15:10 | 10538.64 | 07-JUN-07:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6088.71 | 10-JUL-15:10 | 9495.63 | 28-JUL-17:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8595.24 | 01-AUG-17:00 | 5117.47 | 31-AUG-08:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3842.74 | 08-SEP-16:00 | 8904.56 | 28-SEP-17:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.13 | 10-OCT-16:00 | 17925.07 | 25-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2981.77 | 19-NOV-15:00 | 18969.14 | 21-NOV-09:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.03 | 24-DEC-10:00 | 32878.46 | 02-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.03 | 5117.47 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10109.24 | 41177.75 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17037.27 | 19-JAN-16:00 | 88443.69 | 07-JAN-10:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16537.01 | 16-FEB-17:00 | 88250.30 | 11-FEB-17:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9754.06 | 11-MAR-16:00 | 53901.10 | 18-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4856.37 | 07-APR-15:00 | 71356.22 | 05-APR-11:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.35 | 29-MAY-17:00 | 40214.18 | 10-MAY-08:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1551.99 | 25-JUN-15:55 | 44862.03 | 30-JUN-15:55 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.34 | 16-JUL-13:32 | 34042.96 | 28-JUL-14:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.61 | 01-AUG-17:00 | 22798.74 | 31-AUG-09:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.99 | 25-SEP-13:55 | 31475.07 | 28-SEP-14:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.11 | 10-OCT-16:00 | 57608.58 | 25-OCT-08:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14537.54 | 27-NOV-13:10 | 53015.71 | 20-NOV-09:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11363.01 | 11-DEC-14:00 | 67696.88 | 02-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 166.35 | 22798.74 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17037.27 | 88443.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 568.00 | 21-JAN-13:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.45 |
February | 3033.91 | 28-FEB-16:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 |
March | 12471.25 | 30-MAR-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 260.74 | 0.00 |
April | 19346.21 | 17-APR-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.27 |
May | 18665.63 | 13-MAY-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 0.00 |
June | 19720.53 | 07-JUN-19:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.35 |
July | 17888.61 | 17-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
August | 17102.76 | 14-AUG-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
September | 18854.36 | 13-SEP-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 |
October | 17827.30 | 11-OCT-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.86 |
November | 4839.76 | 04-NOV-17:25 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.36 |
December | 1187.01 | 13-DEC-13:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 568.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19720.53 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 260.74 | 317.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3515.18 | 26-JAN-13:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5201.70 |
February | 2794.01 | 02-FEB-12:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8467.07 |
March | 7916.58 | 30-MAR-15:10 | 0.00 | 8999.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1250.61 | 0.00 |
April | 37930.60 | 17-APR-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.02 | 0.00 |
May | 54287.12 | 19-MAY-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.19 | 0.00 |
June | 57283.07 | 11-JUN-12:43 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.46 | 0.00 |
July | 51846.16 | 03-JUL-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.99 | 0.00 |
August | 53934.07 | 25-AUG-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1788.21 | 0.00 |
September | 51505.66 | 24-SEP-14:03 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.46 | 0.00 |
October | 13373.08 | 09-OCT-14:35 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.21 | 0.00 |
November | 5000.60 | 22-NOV-07:05 | 0.00 | 28797.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16518.91 |
December | 4936.59 | 04-DEC-07:05 | 0.00 | 28797.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11280.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2794.01 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57283.07 | 0.00 | 28797.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.46 | 16518.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11393.81 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9007.78 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6915.18 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12728.77 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7130.50 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8251.43 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8489.83 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.48 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9898.18 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14597.75 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14527.02 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30944.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.48 | |
Maximum of Months | 0.00 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30944.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.718982E+11 | 52346.43 | 17-JAN-13:09 | 0.118212E+12 | 216888.90 | 07-JAN-18:49 |
February | 0.646893E+11 | 53106.43 | 28-FEB-15:20 | 0.762533E+11 | 290949.51 | 12-FEB-06:10 |
March | 0.729153E+11 | 58350.87 | 30-MAR-14:09 | 0.133943E+11 | 43287.87 | 22-MAR-06:10 |
April | 0.693546E+11 | 63029.82 | 17-APR-14:30 | 0.107291E+11 | 23143.78 | 06-APR-06:19 |
May | 0.756209E+11 | 67490.40 | 30-MAY-14:39 | 0.107314E+11 | 7972.67 | 10-MAY-06:30 |
June | 0.838001E+11 | 72023.72 | 06-JUN-14:50 | 0.103680E+11 | 4000.00 | 01-JUN-00:10 |
July | 0.866821E+11 | 74657.47 | 08-JUL-14:50 | 0.107136E+11 | 4000.00 | 01-JUL-00:10 |
August | 0.923502E+11 | 73597.07 | 02-AUG-14:00 | 0.107136E+11 | 4000.00 | 01-AUG-00:10 |
September | 0.769108E+11 | 70734.91 | 06-SEP-12:00 | 0.103680E+11 | 4000.00 | 01-SEP-00:10 |
October | 0.712362E+11 | 61721.42 | 11-OCT-13:00 | 0.110988E+11 | 31229.57 | 26-OCT-06:10 |
November | 0.679764E+11 | 53313.45 | 02-NOV-14:50 | 0.165245E+11 | 74733.74 | 22-NOV-07:10 |
December | 0.714252E+11 | 52818.61 | 13-DEC-13:09 | 0.449918E+11 | 126769.31 | 02-DEC-07:00 |
Annual Sum or Average | 0.904859E+12 | 0.344098E+12 | ||||
Minimum of Months | 0.646893E+11 | 52346.43 | 0.103680E+11 | 4000.00 | ||
Maximum of Months | 0.923502E+11 | 74657.47 | 0.118212E+12 | 290949.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.122290E+11 | 0.115358E+11 | 0.00 | 0.577308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225695E+10 | 0.00 |
February | 0.366966E+11 | 0.104376E+11 | 0.105871E+11 | 0.00 | 0.487390E+10 | 0.00 | 0.00 | 45020071.82 | 0.00 | 0.00 | 0.00 | 0.204910E+10 | 0.00 |
March | 0.423649E+11 | 0.106733E+11 | 0.123357E+11 | 0.00 | 0.483131E+10 | 0.00 | 0.00 | 0.433617E+09 | 0.00 | 0.00 | 0.00 | 0.227659E+10 | 0.00 |
April | 0.397216E+11 | 0.944755E+10 | 0.114862E+11 | 0.00 | 0.449401E+10 | 0.00 | 0.00 | 0.209143E+10 | 0.00 | 0.00 | 0.00 | 0.211381E+10 | 0.00 |
May | 0.412341E+11 | 0.899497E+10 | 0.119357E+11 | 0.00 | 0.516982E+10 | 0.00 | 0.00 | 0.616072E+10 | 0.00 | 0.00 | 0.00 | 0.212553E+10 | 0.00 |
June | 0.408524E+11 | 0.836796E+10 | 0.118862E+11 | 0.00 | 0.712322E+10 | 0.00 | 0.00 | 0.135496E+11 | 0.00 | 0.00 | 0.00 | 0.202080E+10 | 0.00 |
July | 0.401034E+11 | 0.877339E+10 | 0.115358E+11 | 0.00 | 0.782619E+10 | 0.00 | 0.00 | 0.164319E+11 | 0.00 | 0.00 | 0.00 | 0.201149E+10 | 0.00 |
August | 0.423649E+11 | 0.941454E+10 | 0.123357E+11 | 0.00 | 0.810945E+10 | 0.00 | 0.00 | 0.180709E+11 | 0.00 | 0.00 | 0.00 | 0.205474E+10 | 0.00 |
September | 0.397216E+11 | 0.994727E+10 | 0.114862E+11 | 0.00 | 0.540844E+10 | 0.00 | 0.00 | 0.835533E+10 | 0.00 | 0.00 | 0.00 | 0.199193E+10 | 0.00 |
October | 0.401034E+11 | 0.111919E+11 | 0.115358E+11 | 0.00 | 0.448508E+10 | 0.00 | 0.00 | 0.182504E+10 | 0.00 | 0.00 | 0.00 | 0.209509E+10 | 0.00 |
November | 0.385909E+11 | 0.116303E+11 | 0.110862E+11 | 0.00 | 0.436766E+10 | 0.00 | 0.00 | 0.214053E+09 | 0.00 | 0.00 | 0.00 | 0.208728E+10 | 0.00 |
December | 0.401034E+11 | 0.124459E+11 | 0.115358E+11 | 0.00 | 0.509347E+10 | 0.00 | 0.00 | 24984217.72 | 0.00 | 0.00 | 0.00 | 0.222179E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123554E+12 | 0.139282E+12 | 0.675556E+11 | 0.00 | 0.672025E+11 | 0.253051E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.836796E+10 | 0.105871E+11 | 0.00 | 0.436766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199193E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.124459E+11 | 0.123357E+11 | 0.00 | 0.810945E+10 | 0.00 | 0.00 | 0.180709E+11 | 0.00 | 0.00 | 0.00 | 0.227659E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.118212E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.762533E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.133943E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.107291E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.107314E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.103680E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.107136E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.107136E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.103680E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110988E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165245E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.449918E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344098E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.103680E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.118212E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4820.17 | 03-JAN-09:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4820.17 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4482.76 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6788.05 | 17-APR-13:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6788.05 | 18-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6788.05 | 23-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6788.05 | 08-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6788.05 | 08-AUG-10:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6788.05 | 09-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4482.76 | 02-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4482.76 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4820.17 | 02-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4482.76 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6788.05 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2196.42 | 30-JAN-12:50 | 0.00 |
February | 1160.69 | 28-FEB-16:49 | 0.00 | 0.00 | 0.00 | 2194.40 | 06-FEB-12:00 | 0.00 |
March | 6381.36 | 30-MAR-15:09 | 0.00 | 0.00 | 0.00 | 2073.63 | 08-MAR-12:00 | 0.00 |
April | 8945.35 | 17-APR-15:09 | 0.00 | 0.00 | 0.00 | 1856.40 | 03-APR-11:09 | 0.00 |
May | 13471.15 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1786.03 | 01-MAY-11:09 | 0.00 |
June | 19745.79 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1759.36 | 01-JUN-11:30 | 0.00 |
July | 21240.49 | 07-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1740.99 | 01-JUL-11:50 | 0.00 |
August | 21823.05 | 01-AUG-16:00 | 0.00 | 0.00 | 0.00 | 1739.06 | 31-AUG-11:20 | 0.00 |
September | 17645.24 | 07-SEP-15:50 | 0.00 | 0.00 | 0.00 | 1756.18 | 30-SEP-11:09 | 0.00 |
October | 9952.66 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 1782.78 | 31-OCT-11:20 | 0.00 |
November | 1461.96 | 04-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1818.41 | 28-NOV-12:50 | 0.00 |
December | 825.08 | 13-DEC-13:09 | 0.00 | 0.00 | 0.00 | 2037.17 | 21-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1739.06 | 0.00 | ||
Maximum of Months | 21823.05 | 0.00 | 0.00 | 0.00 | 2196.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52346.43 | 17-JAN-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4820.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53106.43 | 28-FEB-15:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 1102.12 | 0.00 |
March | 58350.87 | 30-MAR-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 6361.86 | 0.00 |
April | 63029.82 | 17-APR-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 8748.40 | 0.00 |
May | 67490.40 | 30-MAY-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 13240.20 | 0.00 |
June | 72023.72 | 06-JUN-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 17778.06 | 0.00 |
July | 74657.47 | 08-JUL-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 20426.29 | 0.00 |
August | 73597.07 | 02-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 19369.69 | 0.00 |
September | 70734.91 | 06-SEP-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 16500.73 | 0.00 |
October | 61721.42 | 11-OCT-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 9803.62 | 0.00 |
November | 53313.45 | 02-NOV-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 1349.22 | 0.00 |
December | 52818.61 | 13-DEC-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 825.08 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52346.43 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4482.76 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74657.47 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6788.05 | 0.00 | 0.00 | 20426.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 216888.90 | 07-JAN-18:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 290949.51 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 43287.87 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 23143.78 | 06-APR-06:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 7972.67 | 10-MAY-06:30 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 31229.57 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 74733.74 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 126769.31 | 02-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 4000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 290949.51 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 18.38 | 9.00 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.50 | 18.15 | 6.33 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 20.30 | 2.33 | 20.30 | 0.83 | 24.50 | 0.00 | 0.00 |
April | 0.67 | 20.42 | 0.67 | 20.42 | 7.17 | 24.52 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 24.59 | 0.50 | 24.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 24.71 | 1.17 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 24.73 | 2.17 | 24.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 77.33 | 24.70 | 3.50 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 24.63 | 0.83 | 24.56 |
October | 0.50 | 20.45 | 0.50 | 20.45 | 4.67 | 24.51 | 0.17 | 24.47 |
November | 2.83 | 20.21 | 2.83 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 19.42 | 7.00 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.00 | 18.89 | 28.67 | 19.75 | 247.33 | 24.68 | 8.33 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.67 | 20.45 | 9.00 | 20.45 | 77.33 | 24.73 | 3.50 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.00 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46.33 | 14.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.39 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.62 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.69 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.64 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.39 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57.00 | 14.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 202.00 | 14.37 | 0.00 | 91.17 | 27.61 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.00 | 14.91 | 0.00 | 0.00 | 30.00 | 27.69 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.16 | 275.83 | 21.06 | 275.83 | 21.06 |
February | 276.00 | 21.58 | 205.17 | 21.09 | 205.17 | 21.09 |
March | 305.00 | 22.49 | 107.83 | 21.21 | 105.50 | 21.15 |
April | 192.17 | 23.15 | 59.50 | 23.03 | 19.17 | 21.20 |
May | 53.83 | 23.38 | 183.33 | 23.90 | 0.17 | 23.90 |
June | 13.67 | 23.74 | 275.00 | 23.91 | 4.33 | 23.90 |
July | 8.17 | 23.90 | 297.67 | 23.91 | 8.17 | 23.90 |
August | 15.83 | 23.90 | 322.83 | 23.91 | 15.83 | 23.90 |
September | 13.83 | 23.54 | 245.83 | 23.90 | 1.67 | 23.90 |
October | 182.83 | 22.96 | 83.17 | 23.41 | 21.67 | 22.00 |
November | 286.17 | 22.40 | 112.17 | 21.15 | 112.17 | 21.15 |
December | 300.00 | 21.46 | 239.33 | 21.15 | 239.33 | 21.15 |
Annual Sum or Average | 1947.50 | 22.15 | 2407.67 | 22.78 | 1009.00 | 21.21 |
Minimum of Months | 8.17 | 21.16 | 59.50 | 21.06 | 0.17 | 21.06 |
Maximum of Months | 305.00 | 23.90 | 322.83 | 23.91 | 275.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.164680E+09 | 45020071.82 | 22.50 | 0.164680E+09 | 0.00 | 0.00 | 0.23 | 28-FEB-16:50 | 0.00 | 01-FEB-00:10 | 4311.64 | 28-FEB-16:50 | 4311.64 | 28-FEB-16:50 | 0.00 | 27-FEB-16:40 | 1160.69 | 28-FEB-16:50 | 0.00 | 01-FEB-00:10 |
March | 0.133480E+10 | 0.363427E+09 | 113.81 | 0.113859E+10 | 0.196216E+09 | 0.00 | 0.78 | 30-MAR-17:10 | 0.00 | 01-MAR-00:10 | 15781.20 | 30-MAR-17:10 | 14344.33 | 30-MAR-17:10 | 1615.74 | 30-MAR-12:10 | 4201.57 | 30-MAR-17:10 | 0.00 | 01-MAR-00:10 |
April | 0.404308E+10 | 0.110530E+10 | 248.01 | 0.361167E+10 | 0.431411E+09 | 0.00 | 1.00 | 17-APR-00:02 | 0.00 | 01-APR-00:10 | 24565.65 | 24-APR-00:03 | 21007.98 | 17-APR-17:08 | 8324.81 | 24-APR-00:03 | 5723.50 | 24-APR-00:03 | 0.00 | 01-APR-00:10 |
May | 0.869142E+10 | 0.236857E+10 | 383.58 | 0.714660E+10 | 0.154482E+10 | 0.00 | 1.00 | 05-MAY-17:08 | 0.00 | 01-MAY-00:10 | 25591.58 | 30-MAY-00:01 | 21087.12 | 13-MAY-17:43 | 9319.20 | 08-MAY-00:03 | 5899.60 | 30-MAY-00:01 | 0.00 | 01-MAY-00:10 |
June | 0.146121E+11 | 0.405424E+10 | 500.79 | 0.114698E+11 | 0.314226E+10 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:15 | 27017.44 | 19-JUN-00:01 | 21686.04 | 07-JUN-19:03 | 11396.86 | 19-JUN-00:06 | 6159.36 | 22-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.164308E+11 | 0.457420E+10 | 507.09 | 0.123171E+11 | 0.411368E+10 | 0.00 | 1.00 | 03-JUL-00:01 | 0.00 | 01-JUL-00:15 | 27877.73 | 31-JUL-00:01 | 19491.22 | 17-JUL-00:01 | 13092.74 | 31-JUL-00:04 | 6269.77 | 07-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.187157E+11 | 0.516318E+10 | 556.69 | 0.136856E+11 | 0.503019E+10 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 28292.58 | 21-AUG-00:01 | 19482.20 | 25-AUG-19:43 | 13332.19 | 21-AUG-00:06 | 6284.92 | 21-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.115709E+11 | 0.313018E+10 | 451.13 | 0.906307E+10 | 0.250780E+10 | 0.00 | 1.00 | 05-SEP-00:01 | 0.00 | 01-SEP-00:15 | 27233.64 | 05-SEP-00:01 | 20810.16 | 13-SEP-17:43 | 11114.67 | 05-SEP-00:07 | 6147.28 | 05-SEP-00:01 | 0.00 | 01-SEP-00:10 |
October | 0.409964E+10 | 0.110074E+10 | 235.69 | 0.331107E+10 | 0.788571E+09 | 0.00 | 1.00 | 02-OCT-00:02 | 0.00 | 01-OCT-00:10 | 26054.15 | 02-OCT-00:02 | 19676.28 | 11-OCT-17:43 | 11311.54 | 02-OCT-00:02 | 5973.61 | 02-OCT-00:02 | 0.00 | 01-OCT-00:10 |
November | 0.791025E+09 | 0.214053E+09 | 85.25 | 0.684009E+09 | 0.107015E+09 | 0.00 | 0.35 | 04-NOV-17:25 | 0.00 | 01-NOV-00:10 | 6716.83 | 04-NOV-17:25 | 5318.41 | 04-NOV-17:25 | 1440.30 | 04-NOV-16:00 | 1891.33 | 04-NOV-17:25 | 0.00 | 01-NOV-00:10 |
December | 92083872.38 | 24984217.72 | 14.17 | 65455756.54 | 26628115.85 | 0.00 | 0.15 | 12-DEC-15:00 | 0.00 | 01-DEC-00:03 | 3071.61 | 13-DEC-13:10 | 2259.58 | 12-DEC-15:00 | 1064.63 | 13-DEC-13:10 | 825.08 | 13-DEC-13:10 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.805462E+11 | 0.221439E+11 | 3118.70 | 0.626576E+11 | 0.178886E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.187157E+11 | 0.516318E+10 | 556.69 | 0.136856E+11 | 0.503019E+10 | 0.00 | 1.00 | 0.00 | 28292.58 | 21686.04 | 13332.19 | 6284.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.233207E+09 | 70189248.46 | 7.33 | 0.189571E+09 | 43636281.42 | 0.00 | 0.23 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 13978.88 | 30-MAR-14:00 | 11632.31 | 30-MAR-15:10 | 2905.81 | 30-MAR-13:30 | 4221.69 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.330414E+10 | 0.986125E+09 | 92.46 | 0.298051E+10 | 0.323631E+09 | 0.00 | 0.71 | 17-APR-17:10 | 0.00 | 01-APR-00:10 | 41818.84 | 17-APR-17:10 | 41818.84 | 17-APR-17:10 | 3466.27 | 19-APR-11:40 | 12442.74 | 17-APR-17:10 | 0.00 | 01-APR-00:10 |
May | 0.128817E+11 | 0.379215E+10 | 226.22 | 0.103530E+11 | 0.252869E+10 | 0.00 | 1.00 | 19-MAY-17:06 | 0.00 | 01-MAY-00:10 | 75751.15 | 21-MAY-14:13 | 60489.89 | 19-MAY-17:06 | 23241.44 | 21-MAY-14:13 | 19473.71 | 29-MAY-13:53 | 0.00 | 01-MAY-00:10 |
June | 0.318234E+11 | 0.949533E+10 | 349.61 | 0.240662E+11 | 0.775716E+10 | 0.00 | 1.00 | 04-JUN-11:03 | 0.00 | 01-JUN-00:10 | 80681.28 | 26-JUN-00:03 | 63970.44 | 11-JUN-12:43 | 33985.50 | 18-JUN-12:03 | 20602.12 | 25-JUN-13:02 | 0.00 | 01-JUN-00:10 |
July | 0.395401E+11 | 0.118577E+11 | 407.40 | 0.286702E+11 | 0.108699E+11 | 0.00 | 1.00 | 02-JUL-11:13 | 0.00 | 01-JUL-00:10 | 81100.63 | 23-JUL-10:23 | 57956.18 | 13-JUL-17:42 | 35061.53 | 23-JUL-10:23 | 20869.88 | 16-JUL-13:32 | 0.00 | 01-JUL-00:10 |
August | 0.436890E+11 | 0.129077E+11 | 436.03 | 0.306669E+11 | 0.130221E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 | 83077.75 | 20-AUG-11:03 | 60248.02 | 25-AUG-17:06 | 39412.25 | 20-AUG-11:03 | 20793.02 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 |
September | 0.179458E+11 | 0.522515E+10 | 262.91 | 0.132479E+11 | 0.469797E+10 | 0.00 | 1.00 | 03-SEP-15:13 | 0.00 | 01-SEP-00:10 | 78837.18 | 17-SEP-14:23 | 57057.66 | 24-SEP-14:03 | 30446.85 | 17-SEP-14:23 | 20192.18 | 03-SEP-15:13 | 0.00 | 01-SEP-00:10 |
October | 0.250334E+10 | 0.724297E+09 | 79.03 | 0.179889E+10 | 0.704447E+09 | 0.00 | 0.36 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 23689.67 | 11-OCT-14:00 | 17238.37 | 10-OCT-14:00 | 6609.16 | 18-OCT-14:30 | 6923.55 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.151921E+12 | 0.450586E+11 | 1861.00 | 0.111973E+12 | 0.399475E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.436890E+11 | 0.129077E+11 | 436.03 | 0.306669E+11 | 0.130221E+11 | 0.00 | 1.00 | 0.00 | 83077.75 | 63970.44 | 39412.25 | 20869.88 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.39 | 46.75 | 53.64 | 66.28 | 144.99 | 0.00 | 0.00 | 744.00 |
February | 114.56 | 53.55 | 61.01 | 96.95 | 119.24 | 0.00 | 0.00 | 672.00 |
March | 168.64 | 81.43 | 87.21 | 168.20 | 78.74 | 0.00 | 0.00 | 744.00 |
April | 189.71 | 86.76 | 102.95 | 205.87 | 73.48 | 0.00 | 0.00 | 720.00 |
May | 191.04 | 72.50 | 118.54 | 218.13 | 52.65 | 0.00 | 0.00 | 744.00 |
June | 201.10 | 77.69 | 123.40 | 253.81 | 35.10 | 0.00 | 0.00 | 720.00 |
July | 189.09 | 70.08 | 119.01 | 244.17 | 25.44 | 0.00 | 0.00 | 744.00 |
August | 185.37 | 69.32 | 116.05 | 242.46 | 21.57 | 0.00 | 0.00 | 744.00 |
September | 151.64 | 63.44 | 88.20 | 175.66 | 47.75 | 0.00 | 0.00 | 720.00 |
October | 134.14 | 69.45 | 64.69 | 134.66 | 90.19 | 0.00 | 0.00 | 744.00 |
November | 106.71 | 47.53 | 59.19 | 93.25 | 103.57 | 0.00 | 0.00 | 720.00 |
December | 88.70 | 38.85 | 49.85 | 62.33 | 120.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.95 | 64.83 | 87.12 | 163.82 | 75.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.70 | 38.85 | 49.85 | 62.33 | 21.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.10 | 86.76 | 123.40 | 253.81 | 144.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.39 | 46.75 | 53.64 | 66.28 | 144.99 | 0.00 | 0.00 | 744.00 |
February | 114.56 | 53.55 | 61.01 | 96.95 | 119.24 | 0.00 | 0.00 | 672.00 |
March | 168.64 | 81.43 | 87.21 | 168.20 | 78.74 | 0.00 | 0.00 | 744.00 |
April | 189.71 | 86.76 | 102.95 | 205.87 | 73.48 | 0.00 | 0.00 | 720.00 |
May | 191.04 | 72.50 | 118.54 | 218.13 | 52.65 | 0.00 | 0.00 | 744.00 |
June | 201.10 | 77.69 | 123.40 | 253.81 | 35.10 | 0.00 | 0.00 | 720.00 |
July | 189.09 | 70.08 | 119.01 | 244.17 | 25.44 | 0.00 | 0.00 | 744.00 |
August | 185.37 | 69.32 | 116.05 | 242.46 | 21.57 | 0.00 | 0.00 | 744.00 |
September | 151.64 | 63.44 | 88.20 | 175.66 | 47.75 | 0.00 | 0.00 | 720.00 |
October | 134.14 | 69.45 | 64.69 | 134.66 | 90.19 | 0.00 | 0.00 | 744.00 |
November | 106.71 | 47.53 | 59.19 | 93.25 | 103.57 | 0.00 | 0.00 | 720.00 |
December | 88.70 | 38.85 | 49.85 | 62.33 | 120.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.95 | 64.83 | 87.12 | 163.82 | 75.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.70 | 38.85 | 49.85 | 62.33 | 21.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.10 | 86.76 | 123.40 | 253.81 | 144.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.78 | 0.00 | 25.78 | 4.73 | 92.27 | 0.00 | 0.00 | 744.00 |
February | 28.58 | 0.00 | 28.58 | 12.19 | 74.26 | 0.00 | 0.00 | 672.00 |
March | 40.14 | 0.00 | 40.13 | 24.91 | 47.80 | 0.00 | 0.00 | 744.00 |
April | 48.58 | 0.24 | 48.34 | 40.32 | 43.28 | 0.00 | 0.00 | 720.00 |
May | 58.00 | 1.76 | 56.24 | 55.81 | 29.93 | 0.00 | 0.00 | 744.00 |
June | 63.57 | 3.91 | 59.66 | 75.00 | 19.23 | 0.00 | 0.00 | 720.00 |
July | 60.21 | 2.86 | 57.35 | 74.94 | 14.19 | 0.00 | 0.00 | 744.00 |
August | 53.71 | 0.66 | 53.06 | 70.13 | 12.10 | 0.00 | 0.00 | 744.00 |
September | 40.55 | 0.02 | 40.53 | 40.45 | 28.12 | 0.00 | 0.00 | 720.00 |
October | 30.81 | 0.00 | 30.81 | 19.37 | 54.08 | 0.00 | 0.00 | 744.00 |
November | 27.57 | 0.00 | 27.57 | 13.25 | 62.81 | 0.00 | 0.00 | 720.00 |
December | 23.84 | 0.00 | 23.84 | 5.66 | 74.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 41.85 | 0.79 | 41.06 | 36.53 | 45.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.84 | 0.00 | 23.84 | 4.73 | 12.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.57 | 3.91 | 59.66 | 75.00 | 92.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.78 | 0.00 | 25.78 | 4.73 | 92.27 | 0.00 | 0.00 | 744.00 |
February | 28.58 | 0.00 | 28.58 | 12.19 | 74.26 | 0.00 | 0.00 | 672.00 |
March | 40.14 | 0.00 | 40.13 | 24.91 | 47.80 | 0.00 | 0.00 | 744.00 |
April | 48.58 | 0.24 | 48.34 | 40.32 | 43.28 | 0.00 | 0.00 | 720.00 |
May | 57.99 | 1.76 | 56.23 | 55.81 | 29.93 | 0.00 | 0.00 | 744.00 |
June | 63.56 | 3.91 | 59.66 | 75.00 | 19.23 | 0.00 | 0.00 | 720.00 |
July | 60.21 | 2.86 | 57.35 | 74.94 | 14.19 | 0.00 | 0.00 | 744.00 |
August | 53.71 | 0.66 | 53.06 | 70.13 | 12.10 | 0.00 | 0.00 | 744.00 |
September | 40.54 | 0.02 | 40.53 | 40.45 | 28.12 | 0.00 | 0.00 | 720.00 |
October | 30.81 | 0.00 | 30.81 | 19.37 | 54.08 | 0.00 | 0.00 | 744.00 |
November | 27.57 | 0.00 | 27.57 | 13.25 | 62.81 | 0.00 | 0.00 | 720.00 |
December | 23.84 | 0.00 | 23.84 | 5.66 | 74.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 41.85 | 0.79 | 41.06 | 36.53 | 45.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.84 | 0.00 | 23.84 | 4.73 | 12.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.56 | 3.91 | 59.66 | 75.00 | 92.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.74 | 31.93 | 24.82 | 64.80 | 73.39 | 21.83 | 0.00 | 744.00 |
February | 68.60 | 42.21 | 26.39 | 85.78 | 62.97 | 48.00 | 0.00 | 672.00 |
March | 100.70 | 61.52 | 39.18 | 130.75 | 53.74 | 0.00 | 0.00 | 744.00 |
April | 125.54 | 76.99 | 48.55 | 166.24 | 58.75 | 0.50 | 0.00 | 720.00 |
May | 139.87 | 80.13 | 59.74 | 186.92 | 50.55 | 0.83 | 0.00 | 744.00 |
June | 149.27 | 87.25 | 62.02 | 203.72 | 48.27 | 0.00 | 0.00 | 720.00 |
July | 139.28 | 78.23 | 61.05 | 192.02 | 41.09 | 2.33 | 0.00 | 744.00 |
August | 128.38 | 69.77 | 58.61 | 178.16 | 40.52 | 0.00 | 0.00 | 744.00 |
September | 94.69 | 52.06 | 42.64 | 121.19 | 56.27 | 1.17 | 0.00 | 720.00 |
October | 82.58 | 55.59 | 26.99 | 104.17 | 64.69 | 12.83 | 0.00 | 744.00 |
November | 60.44 | 33.87 | 26.58 | 75.39 | 63.59 | 31.83 | 0.00 | 720.00 |
December | 50.44 | 27.63 | 22.82 | 61.01 | 61.11 | 38.50 | 0.00 | 744.00 |
Annual Sum or Average | 99.88 | 58.18 | 41.70 | 131.10 | 56.18 | 157.83 | 0.00 | 8760.00 |
Minimum of Months | 50.44 | 27.63 | 22.82 | 61.01 | 40.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 149.27 | 87.25 | 62.02 | 203.72 | 73.39 | 48.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268887E+09 | 0.125219E+09 | 0.143668E+09 | 0.177536E+09 | 0.388329E+09 |
February | 0.277148E+09 | 0.129556E+09 | 0.147592E+09 | 0.234541E+09 | 0.288475E+09 |
March | 0.451675E+09 | 0.218091E+09 | 0.233584E+09 | 0.450511E+09 | 0.210896E+09 |
April | 0.491726E+09 | 0.224885E+09 | 0.266840E+09 | 0.533616E+09 | 0.190466E+09 |
May | 0.511668E+09 | 0.194178E+09 | 0.317490E+09 | 0.584245E+09 | 0.141026E+09 |
June | 0.521241E+09 | 0.201384E+09 | 0.319858E+09 | 0.657886E+09 | 90983673.32 |
July | 0.506462E+09 | 0.187695E+09 | 0.318767E+09 | 0.653985E+09 | 68127252.16 |
August | 0.496504E+09 | 0.185663E+09 | 0.310841E+09 | 0.649403E+09 | 57776905.17 |
September | 0.393044E+09 | 0.164426E+09 | 0.228618E+09 | 0.455301E+09 | 0.123761E+09 |
October | 0.359283E+09 | 0.186022E+09 | 0.173261E+09 | 0.360680E+09 | 0.241552E+09 |
November | 0.276595E+09 | 0.123185E+09 | 0.153410E+09 | 0.241707E+09 | 0.268460E+09 |
December | 0.237573E+09 | 0.104059E+09 | 0.133515E+09 | 0.166940E+09 | 0.323216E+09 |
Annual Sum or Average | 0.479181E+10 | 0.204436E+10 | 0.274744E+10 | 0.516635E+10 | 0.239307E+10 |
Minimum of Months | 0.237573E+09 | 0.104059E+09 | 0.133515E+09 | 0.166940E+09 | 57776905.17 |
Maximum of Months | 0.521241E+09 | 0.224885E+09 | 0.319858E+09 | 0.657886E+09 | 0.388329E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268887E+09 | 0.125219E+09 | 0.143668E+09 | 0.177536E+09 | 0.388329E+09 |
February | 0.277148E+09 | 0.129556E+09 | 0.147592E+09 | 0.234541E+09 | 0.288475E+09 |
March | 0.451675E+09 | 0.218091E+09 | 0.233584E+09 | 0.450511E+09 | 0.210896E+09 |
April | 0.491726E+09 | 0.224885E+09 | 0.266840E+09 | 0.533616E+09 | 0.190466E+09 |
May | 0.511668E+09 | 0.194178E+09 | 0.317490E+09 | 0.584245E+09 | 0.141026E+09 |
June | 0.521241E+09 | 0.201384E+09 | 0.319858E+09 | 0.657886E+09 | 90983673.32 |
July | 0.506462E+09 | 0.187695E+09 | 0.318767E+09 | 0.653985E+09 | 68127252.16 |
August | 0.496504E+09 | 0.185663E+09 | 0.310841E+09 | 0.649403E+09 | 57776905.17 |
September | 0.393044E+09 | 0.164426E+09 | 0.228618E+09 | 0.455301E+09 | 0.123761E+09 |
October | 0.359283E+09 | 0.186022E+09 | 0.173261E+09 | 0.360680E+09 | 0.241552E+09 |
November | 0.276595E+09 | 0.123185E+09 | 0.153410E+09 | 0.241707E+09 | 0.268460E+09 |
December | 0.237573E+09 | 0.104059E+09 | 0.133515E+09 | 0.166940E+09 | 0.323216E+09 |
Annual Sum or Average | 0.479181E+10 | 0.204436E+10 | 0.274744E+10 | 0.516635E+10 | 0.239307E+10 |
Minimum of Months | 0.237573E+09 | 0.104059E+09 | 0.133515E+09 | 0.166940E+09 | 57776905.17 |
Maximum of Months | 0.521241E+09 | 0.224885E+09 | 0.319858E+09 | 0.657886E+09 | 0.388329E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69062318.19 | 0.00 | 69062318.19 | 12668157.33 | 0.247125E+09 |
February | 69140904.55 | 0.00 | 69140904.55 | 29496893.41 | 0.179644E+09 |
March | 0.107501E+09 | 5284.04 | 0.107495E+09 | 66727746.64 | 0.128040E+09 |
April | 0.125926E+09 | 630718.51 | 0.125295E+09 | 0.104522E+09 | 0.112175E+09 |
May | 0.155336E+09 | 4715057.98 | 0.150621E+09 | 0.149476E+09 | 80160895.82 |
June | 0.164763E+09 | 10122450.50 | 0.154641E+09 | 0.194411E+09 | 49835671.67 |
July | 0.161275E+09 | 7663395.74 | 0.153611E+09 | 0.200713E+09 | 38002219.62 |
August | 0.143870E+09 | 1758659.35 | 0.142111E+09 | 0.187836E+09 | 32410911.48 |
September | 0.105095E+09 | 40114.28 | 0.105055E+09 | 0.104849E+09 | 72881462.64 |
October | 82516533.76 | 0.00 | 82516533.76 | 51881152.60 | 0.144857E+09 |
November | 71467046.52 | 0.00 | 71467046.52 | 34348232.33 | 0.162809E+09 |
December | 63842976.20 | 0.00 | 63842976.20 | 15168036.86 | 0.199346E+09 |
Annual Sum or Average | 0.131980E+10 | 24935680.40 | 0.129486E+10 | 0.115210E+10 | 0.144729E+10 |
Minimum of Months | 63842976.20 | 0.00 | 63842976.20 | 12668157.33 | 32410911.48 |
Maximum of Months | 0.164763E+09 | 10122450.50 | 0.154641E+09 | 0.200713E+09 | 0.247125E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69060239.94 | 0.00 | 69060239.94 | 12667309.14 | 0.247125E+09 |
February | 69138923.38 | 0.00 | 69138923.38 | 29495710.72 | 0.179644E+09 |
March | 0.107498E+09 | 5283.80 | 0.107492E+09 | 66725140.48 | 0.128039E+09 |
April | 0.125922E+09 | 630688.95 | 0.125291E+09 | 0.104519E+09 | 0.112174E+09 |
May | 0.155332E+09 | 4714836.98 | 0.150617E+09 | 0.149472E+09 | 80160349.27 |
June | 0.164758E+09 | 10121976.05 | 0.154636E+09 | 0.194406E+09 | 49835024.24 |
July | 0.161270E+09 | 7663036.54 | 0.153607E+09 | 0.200709E+09 | 38001587.55 |
August | 0.143865E+09 | 1758576.92 | 0.142107E+09 | 0.187832E+09 | 32410226.94 |
September | 0.105092E+09 | 40112.40 | 0.105052E+09 | 0.104846E+09 | 72880653.60 |
October | 82514281.76 | 0.00 | 82514281.76 | 51879383.90 | 0.144857E+09 |
November | 71464888.97 | 0.00 | 71464888.97 | 34346723.26 | 0.162808E+09 |
December | 63841034.91 | 0.00 | 63841034.91 | 15166926.24 | 0.199346E+09 |
Annual Sum or Average | 0.131976E+10 | 24934511.64 | 0.129482E+10 | 0.115206E+10 | 0.144728E+10 |
Minimum of Months | 63841034.91 | 0.00 | 63841034.91 | 12667309.14 | 32410226.94 |
Maximum of Months | 0.164758E+09 | 10121976.05 | 0.154636E+09 | 0.200709E+09 | 0.247125E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151979E+09 | 85511855.19 | 66467502.99 | 0.173552E+09 | 0.196573E+09 |
February | 0.165964E+09 | 0.102115E+09 | 63848905.48 | 0.207527E+09 | 0.152330E+09 |
March | 0.269715E+09 | 0.164785E+09 | 0.104930E+09 | 0.350208E+09 | 0.143940E+09 |
April | 0.325410E+09 | 0.199565E+09 | 0.125845E+09 | 0.430903E+09 | 0.152270E+09 |
May | 0.374623E+09 | 0.214613E+09 | 0.160010E+09 | 0.500649E+09 | 0.135388E+09 |
June | 0.386899E+09 | 0.226148E+09 | 0.160751E+09 | 0.528032E+09 | 0.125129E+09 |
July | 0.373043E+09 | 0.209520E+09 | 0.163523E+09 | 0.514295E+09 | 0.110062E+09 |
August | 0.343851E+09 | 0.186868E+09 | 0.156983E+09 | 0.477189E+09 | 0.108519E+09 |
September | 0.245442E+09 | 0.134932E+09 | 0.110510E+09 | 0.314137E+09 | 0.145844E+09 |
October | 0.221181E+09 | 0.148897E+09 | 72283806.54 | 0.279001E+09 | 0.173264E+09 |
November | 0.156669E+09 | 87784718.78 | 68884703.31 | 0.195399E+09 | 0.164827E+09 |
December | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.163670E+09 |
Annual Sum or Average | 0.314988E+10 | 0.183474E+10 | 0.131515E+10 | 0.413430E+10 | 0.177181E+10 |
Minimum of Months | 0.135105E+09 | 73995792.94 | 61109490.69 | 0.163410E+09 | 0.108519E+09 |
Maximum of Months | 0.386899E+09 | 0.226148E+09 | 0.163523E+09 | 0.528032E+09 | 0.196573E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 131.54 | 464.02 | 252.35 | 93.50 | 158.85 | 0.00 | 0.00 |
February | 211.23 | 379.95 | 286.28 | 107.11 | 179.18 | 0.00 | 0.00 |
March | 383.80 | 250.66 | 417.54 | 162.86 | 254.69 | 0.00 | 0.00 |
April | 490.79 | 231.92 | 476.58 | 174.01 | 302.57 | 0.00 | 0.00 |
May | 547.45 | 164.73 | 498.06 | 148.52 | 349.54 | 0.00 | 0.00 |
June | 656.83 | 107.86 | 529.32 | 163.20 | 366.12 | 0.00 | 0.00 |
July | 637.52 | 78.56 | 498.61 | 145.88 | 352.73 | 0.00 | 0.00 |
August | 625.02 | 67.18 | 478.17 | 139.95 | 338.22 | 0.00 | 0.00 |
September | 431.73 | 151.25 | 384.37 | 126.90 | 257.46 | 0.00 | 0.00 |
October | 305.89 | 286.36 | 329.90 | 138.91 | 190.99 | 0.00 | 0.00 |
November | 210.05 | 329.81 | 268.57 | 95.05 | 173.52 | 0.00 | 0.00 |
December | 130.65 | 384.87 | 225.07 | 77.70 | 147.37 | 0.00 | 0.00 |
Annual Sum or Average | 397.85 | 240.69 | 387.59 | 131.23 | 256.36 | 0.00 | 0.00 |
Minimum of Months | 130.65 | 67.18 | 225.07 | 77.70 | 147.37 | 0.00 | 0.00 |
Maximum of Months | 656.83 | 464.02 | 529.32 | 174.01 | 366.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 647.97 | 733.92 | 567.43 | 319.26 | 248.16 | 0.00 | 0.00 |
February | 857.83 | 629.67 | 686.03 | 422.10 | 263.93 | 0.00 | 0.00 |
March | 1307.52 | 537.41 | 1007.00 | 615.24 | 391.76 | 0.00 | 0.00 |
April | 1662.43 | 587.46 | 1255.44 | 769.93 | 485.51 | 0.00 | 0.00 |
May | 1869.21 | 505.48 | 1398.68 | 801.27 | 597.41 | 0.00 | 0.00 |
June | 2037.16 | 482.75 | 1492.66 | 872.48 | 620.18 | 0.00 | 0.00 |
July | 1920.16 | 410.92 | 1392.78 | 782.26 | 610.53 | 0.00 | 0.00 |
August | 1781.62 | 405.15 | 1283.79 | 697.69 | 586.11 | 0.00 | 0.00 |
September | 1211.92 | 562.67 | 946.92 | 520.57 | 426.35 | 0.00 | 0.00 |
October | 1041.67 | 646.89 | 825.79 | 555.92 | 269.88 | 0.00 | 0.00 |
November | 753.85 | 635.91 | 604.43 | 338.68 | 265.76 | 0.00 | 0.00 |
December | 610.10 | 611.07 | 504.43 | 276.27 | 228.16 | 0.00 | 0.00 |
Annual Sum or Average | 1310.97 | 561.84 | 998.82 | 581.79 | 417.03 | 0.00 | 0.00 |
Minimum of Months | 610.10 | 405.15 | 504.43 | 276.27 | 228.16 | 0.00 | 0.00 |
Maximum of Months | 2037.16 | 733.92 | 1492.66 | 872.48 | 620.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.352329E+09 | 0.124283E+10 | 0.675897E+09 | 0.250439E+09 | 0.425458E+09 | 0.00 | 0.00 |
February | 0.511010E+09 | 0.919172E+09 | 0.692575E+09 | 0.259111E+09 | 0.433464E+09 | 0.00 | 0.00 |
March | 0.102798E+10 | 0.671379E+09 | 0.111835E+10 | 0.436193E+09 | 0.682156E+09 | 0.00 | 0.00 |
April | 0.127212E+10 | 0.601126E+09 | 0.123530E+10 | 0.451032E+09 | 0.784267E+09 | 0.00 | 0.00 |
May | 0.146629E+10 | 0.441222E+09 | 0.133400E+10 | 0.397786E+09 | 0.936218E+09 | 0.00 | 0.00 |
June | 0.170251E+10 | 0.279563E+09 | 0.137200E+10 | 0.423012E+09 | 0.948993E+09 | 0.00 | 0.00 |
July | 0.170754E+10 | 0.210408E+09 | 0.133547E+10 | 0.390716E+09 | 0.944753E+09 | 0.00 | 0.00 |
August | 0.167405E+10 | 0.179947E+09 | 0.128074E+10 | 0.374843E+09 | 0.905900E+09 | 0.00 | 0.00 |
September | 0.111904E+10 | 0.392027E+09 | 0.996276E+09 | 0.328932E+09 | 0.667344E+09 | 0.00 | 0.00 |
October | 0.819290E+09 | 0.766987E+09 | 0.883598E+09 | 0.372045E+09 | 0.511553E+09 | 0.00 | 0.00 |
November | 0.544448E+09 | 0.854875E+09 | 0.696121E+09 | 0.246370E+09 | 0.449751E+09 | 0.00 | 0.00 |
December | 0.349924E+09 | 0.103083E+10 | 0.602830E+09 | 0.208117E+09 | 0.394713E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125465E+11 | 0.759037E+10 | 0.122232E+11 | 0.413860E+10 | 0.808457E+10 | 0.00 | 0.00 |
Minimum of Months | 0.349924E+09 | 0.179947E+09 | 0.602830E+09 | 0.208117E+09 | 0.394713E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170754E+10 | 0.124283E+10 | 0.137200E+10 | 0.451032E+09 | 0.948993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173551E+10 | 0.196573E+10 | 0.151979E+10 | 0.855119E+09 | 0.664675E+09 | 0.00 | 0.00 |
February | 0.207527E+10 | 0.152330E+10 | 0.165964E+10 | 0.102115E+10 | 0.638489E+09 | 0.00 | 0.00 |
March | 0.350207E+10 | 0.143940E+10 | 0.269715E+10 | 0.164785E+10 | 0.104930E+10 | 0.00 | 0.00 |
April | 0.430903E+10 | 0.152270E+10 | 0.325410E+10 | 0.199565E+10 | 0.125845E+10 | 0.00 | 0.00 |
May | 0.500648E+10 | 0.135387E+10 | 0.374623E+10 | 0.214613E+10 | 0.160010E+10 | 0.00 | 0.00 |
June | 0.528032E+10 | 0.125128E+10 | 0.386899E+10 | 0.226148E+10 | 0.160751E+10 | 0.00 | 0.00 |
July | 0.514295E+10 | 0.110061E+10 | 0.373043E+10 | 0.209520E+10 | 0.163523E+10 | 0.00 | 0.00 |
August | 0.477188E+10 | 0.108516E+10 | 0.343851E+10 | 0.186868E+10 | 0.156983E+10 | 0.00 | 0.00 |
September | 0.314130E+10 | 0.145844E+10 | 0.245442E+10 | 0.134932E+10 | 0.110510E+10 | 0.00 | 0.00 |
October | 0.279001E+10 | 0.173264E+10 | 0.221181E+10 | 0.148897E+10 | 0.722838E+09 | 0.00 | 0.00 |
November | 0.195398E+10 | 0.164827E+10 | 0.156669E+10 | 0.877847E+09 | 0.688847E+09 | 0.00 | 0.00 |
December | 0.163410E+10 | 0.163670E+10 | 0.135105E+10 | 0.739958E+09 | 0.611095E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.413429E+11 | 0.177181E+11 | 0.314988E+11 | 0.183474E+11 | 0.131515E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163410E+10 | 0.108516E+10 | 0.135105E+10 | 0.739958E+09 | 0.611095E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528032E+10 | 0.196573E+10 | 0.386899E+10 | 0.226148E+10 | 0.163523E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.963352E+09 | -808231497.3 | 0.00 | 0.00 | 744.00 | 0.00 | -155120114.4 | 58.99 | 0.00 | 0.00 |
February | 0.880464E+09 | -744049323.8 | 0.00 | 0.00 | 672.00 | 0.00 | -136414190.0 | 58.99 | 0.00 | 0.00 |
March | 0.982755E+09 | -840332988.2 | 0.00 | 0.00 | 744.00 | 0.00 | -142421895.6 | 58.99 | 0.00 | 0.00 |
April | 0.862144E+09 | -730846451.9 | 0.00 | 0.00 | 720.00 | 0.00 | -131297849.1 | 58.99 | 0.00 | 0.00 |
May | 0.831572E+09 | -699066932.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132504624.8 | 58.99 | 0.00 | 0.00 |
June | 0.768634E+09 | -641061601.8 | 0.00 | 0.00 | 720.00 | 0.00 | -127572016.1 | 58.99 | 0.00 | 0.00 |
July | 0.718152E+09 | -587548610.2 | 0.00 | 0.00 | 744.00 | 0.00 | -130603275.1 | 58.99 | 0.00 | 0.00 |
August | 0.760415E+09 | -628947789.7 | 0.00 | 0.00 | 744.00 | 0.00 | -131467027.9 | 58.99 | 0.00 | 0.00 |
September | 0.740414E+09 | -613203774.1 | 0.00 | 0.00 | 720.00 | 0.00 | -127210686.6 | 58.99 | 0.00 | 0.00 |
October | 0.801134E+09 | -665347951.2 | 0.00 | 0.00 | 744.00 | 0.00 | -135786500.3 | 58.99 | 0.00 | 0.00 |
November | 0.834812E+09 | -695379213.3 | 0.00 | 0.00 | 720.00 | 0.00 | -139432330.7 | 58.99 | 0.00 | 0.00 |
December | 0.927998E+09 | -775896705.7 | 0.00 | 0.00 | 744.00 | 0.00 | -152101210.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.100718E+11 | -.842991E+10 | 8760.00 | -.164193E+10 | 58.99 | |||||
Minimum of Months | 0.718152E+09 | -840332988.2 | 0.00 | 0.00 | 672.00 | 0.00 | -155120114.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.982755E+09 | -587548610.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127210686.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | ||||||||||
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.631560E+10 | 29165.65 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411838E+10 | 29165.65 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100721E+10 | 29165.65 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239570E+09 | 29165.65 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11617727.23 | 3794.80 | 11-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244020E+09 | 29165.65 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130781E+10 | 29165.65 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323075E+10 | 29165.65 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164750E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.631560E+10 | 29165.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288473E+11 | 91803.47 | 02-JAN-02:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173284E+11 | 91803.47 | 01-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790914E+09 | 61705.01 | 23-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5882046.45 | 2313.29 | 06-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14674989.60 | 7153.85 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288042E+10 | 91803.47 | 21-NOV-03:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150704E+11 | 91803.47 | 01-DEC-00:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649380E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288473E+11 | 91803.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459604E+11 | 108505.83 | 07-JAN-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290116E+11 | 145448.76 | 12-FEB-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2339866.65 | 3824.90 | 22-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618021E+10 | 48040.43 | 03-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811545E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459604E+11 | 145448.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.164680E+09 | 0.164680E+09 | 4311.64 | 28-FEB-16:50 | 4311.64 | 0.00 |
March | 0.00 | 0.00 | 0.133480E+10 | 0.113859E+10 | 15781.20 | 30-MAR-17:10 | 14344.33 | 0.00 |
April | 0.00 | 0.00 | 0.404308E+10 | 0.361167E+10 | 24565.65 | 24-APR-00:03 | 16240.84 | 0.00 |
May | 0.00 | 0.00 | 0.869142E+10 | 0.714660E+10 | 25591.58 | 30-MAY-00:01 | 17484.25 | 0.00 |
June | 0.00 | 0.00 | 0.146121E+11 | 0.114698E+11 | 27017.44 | 19-JUN-00:01 | 15986.10 | 0.00 |
July | 0.00 | 0.00 | 0.164308E+11 | 0.123171E+11 | 27877.73 | 31-JUL-00:01 | 14909.15 | 0.00 |
August | 0.00 | 0.00 | 0.187157E+11 | 0.136856E+11 | 28292.58 | 21-AUG-00:01 | 15146.15 | 0.00 |
September | 0.00 | 0.00 | 0.115709E+11 | 0.906307E+10 | 27233.64 | 05-SEP-00:01 | 16614.38 | 0.00 |
October | 0.00 | 0.00 | 0.409964E+10 | 0.331107E+10 | 26054.15 | 02-OCT-00:02 | 14742.61 | 0.00 |
November | 0.00 | 0.00 | 0.791025E+09 | 0.684009E+09 | 6716.83 | 04-NOV-17:25 | 5318.41 | 0.00 |
December | 0.00 | 0.00 | 92083872.38 | 65455756.54 | 3071.61 | 13-DEC-13:10 | 2006.98 | 0.00 |
Annual Sum or Average | 0.805462E+11 | 0.626576E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187157E+11 | 0.136856E+11 | 28292.58 | 17484.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.233207E+09 | 0.189571E+09 | 13978.88 | 30-MAR-14:00 | 11260.41 | 0.00 |
April | 0.00 | 0.00 | 0.330414E+10 | 0.298051E+10 | 41818.84 | 17-APR-17:10 | 41818.84 | 0.00 |
May | 0.00 | 0.00 | 0.128817E+11 | 0.103530E+11 | 75751.15 | 21-MAY-14:13 | 52509.71 | 0.00 |
June | 0.00 | 0.00 | 0.318234E+11 | 0.240662E+11 | 80681.28 | 26-JUN-00:03 | 48294.99 | 0.00 |
July | 0.00 | 0.00 | 0.395401E+11 | 0.286702E+11 | 81100.63 | 23-JUL-10:23 | 46039.10 | 0.00 |
August | 0.00 | 0.00 | 0.436890E+11 | 0.306669E+11 | 83077.75 | 20-AUG-11:03 | 43665.50 | 0.00 |
September | 0.00 | 0.00 | 0.179458E+11 | 0.132479E+11 | 78837.18 | 17-SEP-14:23 | 48390.33 | 0.00 |
October | 0.00 | 0.00 | 0.250334E+10 | 0.179889E+10 | 23689.67 | 11-OCT-14:00 | 17165.53 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.151921E+12 | 0.111973E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.436890E+11 | 0.306669E+11 | 83077.75 | 52509.71 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.421588E+09 | 0.04 | 337.41 | 03-JAN-09:00 | 0.08 |
February | 0.239749E+09 | 0.02 | 337.41 | 01-FEB-06:38 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 391399.22 | 0.00 | 337.41 | 22-NOV-06:38 | 0.08 |
December | 0.128598E+09 | 0.01 | 337.41 | 02-DEC-04:44 | 0.08 |
Annual Sum or Average | 0.790326E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421588E+09 | 0.04 | 337.41 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135396E+10 | 0.46 | 1306.06 | 03-JAN-12:30 | 0.97 |
February | 0.123659E+10 | 0.45 | 1306.06 | 01-FEB-15:40 | 0.97 |
March | 0.141330E+10 | 0.41 | 1306.06 | 01-MAR-07:10 | 0.97 |
April | 0.133119E+10 | 0.43 | 1306.06 | 01-APR-08:20 | 0.97 |
May | 0.146792E+10 | 0.55 | 1306.06 | 02-MAY-08:10 | 0.96 |
June | 0.160795E+10 | 0.71 | 1306.06 | 01-JUN-06:40 | 0.96 |
July | 0.160430E+10 | 0.69 | 1306.06 | 01-JUL-07:00 | 0.96 |
August | 0.174826E+10 | 0.76 | 1306.06 | 14-AUG-06:50 | 0.96 |
September | 0.149632E+10 | 0.65 | 1306.06 | 01-SEP-06:20 | 0.96 |
October | 0.133886E+10 | 0.43 | 1306.06 | 04-OCT-09:00 | 0.97 |
November | 0.125447E+10 | 0.37 | 1306.06 | 01-NOV-07:50 | 0.96 |
December | 0.132677E+10 | 0.39 | 1306.06 | 01-DEC-10:50 | 0.97 |
Annual Sum or Average | 0.171799E+11 | 0.52 | |||
Minimum of Months | 0.123659E+10 | 0.37 | 1306.06 | 0.96 | |
Maximum of Months | 0.174826E+10 | 0.76 | 1306.06 | 0.97 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.399753E+10 | 0.74 | 3176.70 | 02-JAN-08:00 | 0.93 |
February | 0.339756E+10 | 0.59 | 3176.70 | 01-FEB-07:10 | 0.93 |
March | 0.341801E+10 | 0.40 | 3176.70 | 29-MAR-16:10 | 0.92 |
April | 0.315475E+10 | 0.36 | 3176.70 | 06-APR-06:50 | 0.93 |
May | 0.334431E+10 | 0.40 | 3176.70 | 24-MAY-15:00 | 0.92 |
June | 0.358454E+10 | 0.50 | 3176.70 | 01-JUN-10:30 | 0.92 |
July | 0.367474E+10 | 0.54 | 3176.70 | 01-JUL-07:20 | 0.91 |
August | 0.389878E+10 | 0.57 | 3176.70 | 01-AUG-06:40 | 0.91 |
September | 0.328126E+10 | 0.42 | 3176.70 | 01-SEP-09:00 | 0.92 |
October | 0.314622E+10 | 0.34 | 3176.70 | 02-OCT-12:40 | 0.92 |
November | 0.311280E+10 | 0.41 | 3176.70 | 13-NOV-07:50 | 0.93 |
December | 0.363810E+10 | 0.65 | 3176.70 | 02-DEC-07:30 | 0.93 |
Annual Sum or Average | 0.416486E+11 | 0.49 | |||
Minimum of Months | 0.311280E+10 | 0.34 | 3176.70 | 0.91 | |
Maximum of Months | 0.399753E+10 | 0.74 | 3176.70 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.55 | 0.00 |
February | 1.83 | 0.18 |
March | 0.94 | 2.80 |
April | 0.89 | 3.68 |
May | 0.61 | 4.46 |
June | 0.11 | 0.00 |
July | 0.17 | 0.00 |
August | 0.00 | 0.00 |
September | 0.17 | 0.53 |
October | 1.47 | 3.08 |
November | 0.68 | 0.64 |
December | 1.45 | 0.24 |
Annual Sum or Average | 10.87 | 1.32 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.55 | 4.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 6.09 | 0.00 |
July | 5.92 | 0.00 |
August | 6.36 | 0.00 |
September | 1.40 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 19.86 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.36 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135396E+10 | 0.909672E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128161E+10 | 0.594294E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177672E+10 | 0.147968E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.243650E+10 | 0.351871E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383649E+10 | 17821234.38 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.566219E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.617850E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.691144E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.462650E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.243960E+10 | 0.362328E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146853E+10 | 0.190689E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135175E+10 | 0.467444E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.393238E+11 | 0.238327E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128161E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.691144E+10 | 0.909672E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.399753E+10 | 0.416713E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.339756E+10 | 0.248238E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.348820E+10 | 0.120100E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.414087E+10 | 9229940.44 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.713646E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.130799E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.155324E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168065E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.850641E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.387052E+10 | 22883388.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.311280E+10 | 0.424676E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.363810E+10 | 0.219754E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.867072E+11 | 0.939503E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.311280E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168065E+11 | 0.416713E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135396E+10 | 0.00 | 0.631560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123659E+10 | 0.164680E+09 | 0.411838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141330E+10 | 0.133480E+10 | 0.100721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133119E+10 | 0.404308E+10 | 0.239570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146792E+10 | 0.869142E+10 | 11617727.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160795E+10 | 0.146121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160430E+10 | 0.164308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174826E+10 | 0.187157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149632E+10 | 0.115709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133886E+10 | 0.409964E+10 | 0.244020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125447E+10 | 0.791025E+09 | 0.130781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132677E+10 | 92083872.38 | 0.323075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171799E+11 | 0.805462E+11 | 0.164750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174826E+10 | 0.187157E+11 | 0.631560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.399753E+10 | 0.00 | 0.288473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339756E+10 | 0.00 | 0.173284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341801E+10 | 0.233207E+09 | 0.790914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315475E+10 | 0.330414E+10 | 5882046.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334431E+10 | 0.128817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358454E+10 | 0.318234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.367474E+10 | 0.395401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389878E+10 | 0.436890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328126E+10 | 0.179458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314622E+10 | 0.250334E+10 | 14674989.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311280E+10 | 0.00 | 0.288042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363810E+10 | 0.00 | 0.150704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416486E+11 | 0.151921E+12 | 0.649380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.399753E+10 | 0.436890E+11 | 0.288473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.135396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123659E+10 | 0.00 | 0.00 | 0.00 | 45020071.82 | 0.00 | 0.594294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141330E+10 | 0.00 | 0.00 | 0.00 | 0.363427E+09 | 0.00 | 0.147968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133119E+10 | 0.00 | 0.00 | 0.00 | 0.110530E+10 | 0.00 | 0.351871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146792E+10 | 0.00 | 0.00 | 0.00 | 0.236857E+10 | 0.00 | 17821234.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160795E+10 | 0.00 | 0.00 | 0.00 | 0.405424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160430E+10 | 0.00 | 0.00 | 0.00 | 0.457420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174826E+10 | 0.00 | 0.00 | 0.00 | 0.516318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149632E+10 | 0.00 | 0.00 | 0.00 | 0.313018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133886E+10 | 0.00 | 0.00 | 0.00 | 0.110074E+10 | 0.00 | 0.362328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125447E+10 | 0.00 | 0.00 | 0.00 | 0.214053E+09 | 0.00 | 0.190689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132677E+10 | 0.00 | 0.00 | 0.00 | 24984217.72 | 0.00 | 0.467444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171799E+11 | 0.00 | 0.00 | 0.00 | 0.221439E+11 | 0.00 | 0.238327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174826E+10 | 0.00 | 0.00 | 0.00 | 0.516318E+10 | 0.00 | 0.909672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.399753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341801E+10 | 0.00 | 0.00 | 0.00 | 70189248.46 | 0.00 | 0.120100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315475E+10 | 0.00 | 0.00 | 0.00 | 0.986125E+09 | 0.00 | 9229940.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334431E+10 | 0.00 | 0.00 | 0.00 | 0.379215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358454E+10 | 0.00 | 0.00 | 0.00 | 0.949533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.367474E+10 | 0.00 | 0.00 | 0.00 | 0.118577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389878E+10 | 0.00 | 0.00 | 0.00 | 0.129077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328126E+10 | 0.00 | 0.00 | 0.00 | 0.522515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314622E+10 | 0.00 | 0.00 | 0.00 | 0.724297E+09 | 0.00 | 22883388.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416486E+11 | 0.00 | 0.00 | 0.00 | 0.450586E+11 | 0.00 | 0.939503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.311280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.399753E+10 | 0.00 | 0.00 | 0.00 | 0.129077E+11 | 0.00 | 0.416713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233774E+10 | 0.00 | 0.00 | 0.17 |
February | 0.245235E+09 | 774470.04 | 0.00 | 120920.05 | 0.00 | 0.149420E+10 | 26185120.56 | 0.00 | 0.17 |
March | 0.628048E+09 | 42511180.08 | 0.00 | 699492.08 | 173853.53 | 0.421667E+09 | 0.178225E+09 | 0.00 | 0.18 |
April | 0.265122E+09 | 0.161080E+09 | 0.00 | 2196653.34 | 0.00 | 0.100839E+09 | 0.323494E+09 | 0.00 | 0.17 |
May | 71359444.34 | 0.701274E+09 | 0.00 | 3190003.15 | 1216700.78 | 9957789.55 | 0.139903E+09 | 0.00 | 0.18 |
June | 16970768.34 | 0.204525E+10 | 0.00 | 1994449.34 | 1120670.87 | 0.00 | 59723927.45 | 0.00 | 0.21 |
July | 0.00 | 0.277024E+10 | 0.00 | 792658.74 | 939957.92 | 0.00 | 465859.87 | 0.00 | 0.20 |
August | 0.00 | 0.331416E+10 | 0.00 | 59715.13 | 0.00 | 0.00 | 722470.08 | 0.00 | 0.22 |
September | 29326262.54 | 0.137265E+10 | 0.00 | 2434247.11 | 82230.20 | 0.00 | 77988854.23 | 0.00 | 0.19 |
October | 0.377248E+09 | 0.279872E+09 | 0.00 | 2896447.37 | 810230.99 | 0.122381E+09 | 0.425550E+09 | 0.00 | 0.17 |
November | 0.586436E+09 | 6664109.82 | 1693137.71 | 667166.33 | 113263.86 | 0.518407E+09 | 0.188454E+09 | 120808.32 | 0.16 |
December | 0.450357E+09 | 0.00 | 0.00 | 50922.73 | 341867.66 | 0.127186E+10 | 20802148.54 | 0.00 | 0.16 |
Annual Sum or Average | 0.279447E+10 | 0.106945E+11 | 1693137.71 | 15102675.38 | 4798775.81 | 0.627706E+10 | 0.144151E+10 | 120808.32 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.628048E+09 | 0.331416E+10 | 1693137.71 | 3190003.15 | 1216700.78 | 0.233774E+10 | 0.425550E+09 | 120808.32 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174072E+10 | 0.00 | 0.00 | 0.00 | 44002.08 | 0.439547E+10 | 0.00 | 11494.02 | 0.19 |
February | 0.134149E+10 | 0.00 | 0.00 | 0.00 | 8675284.46 | 0.279126E+10 | 0.00 | 0.00 | 0.19 |
March | 0.250411E+10 | 6660754.18 | 0.00 | 38399.91 | 17736625.63 | 0.194853E+09 | 4701859.40 | 0.00 | 0.17 |
April | 0.185231E+10 | 74659260.97 | 0.00 | 1368961.12 | 2698942.89 | 0.00 | 0.168497E+09 | 0.00 | 0.17 |
May | 0.890178E+09 | 0.985088E+09 | 0.00 | 2368639.37 | 0.00 | 0.00 | 0.376897E+09 | 0.00 | 0.17 |
June | 0.273603E+09 | 0.382810E+10 | 0.00 | 3800530.46 | 0.00 | 0.00 | 0.210714E+09 | 0.00 | 0.19 |
July | 0.134786E+09 | 0.549727E+10 | 0.00 | 1086927.15 | 103174.61 | 0.00 | 0.165353E+09 | 0.00 | 0.19 |
August | 80683798.01 | 0.628827E+10 | 0.00 | 804778.38 | 208395.33 | 0.00 | 93956313.58 | 0.00 | 0.20 |
September | 0.636175E+09 | 0.197793E+10 | 0.00 | 3315938.94 | 2440706.47 | 0.00 | 0.249844E+09 | 0.00 | 0.18 |
October | 0.223998E+10 | 0.204110E+09 | 0.00 | 779035.04 | 470977.64 | 20018018.27 | 0.307195E+09 | 0.00 | 0.16 |
November | 0.229894E+10 | 0.00 | 0.00 | 0.00 | 8796945.67 | 0.440796E+09 | 0.00 | 0.00 | 0.16 |
December | 0.206558E+10 | 0.00 | 0.00 | 0.00 | 13674598.02 | 0.176552E+10 | 0.00 | 8019.45 | 0.18 |
Annual Sum or Average | 0.160585E+11 | 0.188621E+11 | 0.00 | 13563210.37 | 54849652.80 | 0.960791E+10 | 0.157716E+10 | 19513.48 | 0.18 |
Minimum of Months | 80683798.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.250411E+10 | 0.628827E+10 | 0.00 | 3800530.46 | 17736625.63 | 0.439547E+10 | 0.376897E+09 | 11494.02 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |