Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1781.28 | 368.40 | 368.40 |
Net Site Energy | 1781.28 | 368.40 | 368.40 |
Total Source Energy | 3745.67 | 774.68 | 774.68 |
Net Source Energy | 3745.67 | 774.68 | 774.68 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 910.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 871.23 | 910.06 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 910.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.19 | 188.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.19 | 188.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.19 | 188.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.19 | 188.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 871.226 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 871.226 | 100.00 |
Total On-Site and Utility Electric Sources | 871.226 | 100.00 |
Total Electricity End Uses | 871.226 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 51.50 |
Time Setpoint Not Met During Occupied Cooling | 3.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1733.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:09 | 06-FEB-00:00 | - | - | - | 28-JUN-11:00 |
Heating | 0.00 | 374316.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18398.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6309.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1734.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 72175.37 | 374316.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 374316.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18398.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4004.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1734.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 986.50 | 0.00 | 0.00 | 0.00 |
Cooling | 122.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 195.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2759.17 | 986.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 204.03 | 0.00 | 0.00 | 0.00 |
Cooling | 25.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 570.65 | 204.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 204.03 | 0.00 | 0.00 | 0.00 |
Cooling | 25.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 570.65 | 204.03 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.56 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.39 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.39 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 223950.02 |
PSZ-OFFICE HEATING COIL | 28881.02 |
PSZ-FINE STORAGE HEATING COIL | 86828.94 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 223950.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 1.00 | 1.00 | 2.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.06 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.56 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 20561.90 | 28881.02 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.56 | 2.56 | 2.56 | 2.56 | 60891.57 | 86828.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.529205 | 1.06 | 20072.36 | 20561.90 | 10280.95 | 20561.90 | 0.744273 | 0.744270 | 0.744270 | 0.744270 |
PSZ-FINE STORAGE COOLING COIL | 2.56 | 1.28 | 2.56 | 58335.32 | 60891.57 | 30445.78 | 60891.57 | 0.686473 | 0.686470 | 0.686470 | 0.686470 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1206.71 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.56 | 2797.63 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.71045622E-12 | 0.18350169E-15 | 0.20920636E-14 | 0.12692337E-15 |
13 | 3 | -0.36041595E-03 | 0.57471575E-06 | -0.52051292E-04 | 0.13635641E-12 |
14 | 2 | 1.6814491 | 0.12908092E-01 | 1.0963028 | -0.69095641E-04 |
15 | 1 | -7.2068525 | 0.34008243 | -16.815156 | 0.32221486 |
16 | 0 | 6.0979960 | 0.21924101 | 16.291138 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20920636E-14 | 0.18350169E-15 | 0.71045622E-12 | 0.12692337E-15 |
85 | 3 | -0.52051292E-04 | 0.57471575E-06 | -0.36041595E-03 | 0.13635641E-12 |
86 | 2 | 1.0963028 | 0.12908092E-01 | 1.6814491 | -0.69095641E-04 |
87 | 1 | -16.815156 | 0.34008243 | -7.2068525 | 0.32221486 |
88 | 0 | 16.291138 | 0.21924101 | 6.0979960 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 28 | 1 | VerySmooth | 3.241 | 0.385 | 0.305 | 0.391 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10715.63175 | 12858.75810 | 0.88201 | 1.05841 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.40969E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12872.18778 | 15446.62533 | 0.36158 | 0.43390 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33194.22598 | 39833.07118 | 2.13005 | 2.55606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 67994.67497 | 81593.60997 | 1.60802 | 1.92963 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10000 | 1.40969E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 186625.00215 | 223950.00258 | 4.49391 | 5.39269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -10.70000 | 1.50390E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16274.44 | 1.05841 | 1.05841 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14566.20 | 0.43390 | 0.43390 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47748.31 | 2.55606 | 2.55606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 68302.61 | 1.92963 | 1.92963 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05841 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.55606 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.39269 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.39269 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 223950.02246 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 223950.00258 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05841 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05841 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05841 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05841 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05841 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.05841 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55606 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.55606 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.55606 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55606 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.55606 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.55606 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.05841 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.55606 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05841 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05841 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05841 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05841 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05841 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05841 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52921 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05841 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20072.36391 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20561.90000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10280.95000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20561.90000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74427 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74427 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74427 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74427 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20561.90000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28881.01942 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05841 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1206.70646 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28881.01942 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.55606 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.55606 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.55606 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.55606 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.55606 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.55606 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27803 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.55606 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 58335.32023 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 60891.57000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 30445.78500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 60891.57000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68647 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68647 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68647 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68647 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 60891.57000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 86828.94260 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.55606 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2797.62627 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 86828.94260 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19740.1 | 10.33 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 58905.2 | 13.43 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3872314191 | 0.3884686474 | Pass | Pass | 0.7112507934 | 0.7322572671 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.2905690982 | 1.1383393157 | Pass | Pass | 0.6245470723 | 0.5736013757 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.5151670563E-004 | 2.8899368340E-004 | Pass | Pass | 2.4258778275E-002 | 1.9154959901E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.494 | 0.497 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.385 | 0.391 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.510 | 0.512 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.64 | 83.64 | 123.36 | |
Exterior Lighting Total | 7857.24 | 123.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20561.90 | 15303.61 | 5258.29 | 0.74 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 60891.57 | 41800.24 | 19091.33 | 0.69 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19740.1 | 10.33 | ||||
PSZ-FINE STORAGE COOLING COIL | 58905.2 | 13.43 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 223950.02 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28881.02 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 86828.94 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.39 | 501.04 | 92.91 | 1.00 | 3.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.06 | 1206.71 | 1140.11 | 1.00 | 1.35 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.56 | 2797.63 | 1094.51 | 1.00 | 1.25 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10715.63 | 12858.76 | 54.28 | 0.882 | 1.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00840 | 31.06 | 0.01410 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 33194.23 | 39833.07 | 28.59 | 2.130 | 2.556 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26.70 | 26.70 | 0.00879 | 32.10 | 0.01410 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 32.10 | 0.01410 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12872.19 | 15446.63 | 65.21 | 0.362 | 0.434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00698 | -10.70 | 0.00150 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 67994.67 | 81593.61 | 58.56 | 1.608 | 1.930 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00517 | -10.70 | 0.00150 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 186625.00 | 223950.00 | 69.88 | 4.494 | 5.393 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00763 | -10.70 | 0.00150 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.43 | 0.43 | 1.0584 | 1.0584 | 1.0584 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 1.93 | 1.93 | 2.5561 | 2.5561 | 2.5561 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 223950.022 | 223950.022 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 223950.02 | 223950.02 | 5.392692 | 6.86 | 6.86 | 0.00670365 | 43.33 | 27.10 | 0.01600000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 9.98 | 0.00762811 | 100.0000 | 223950.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20561.900 | 0.000 | 1.058410 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20561.90 | 17336.93 | 1.058410 | 24.71 | 17.08 | 0.00904442 | 12.00 | 11.25 | 0.00800000 | 31.06 | 0.01409688 | 22.82 | 11.3694 | 23.90 | 0.00839630 | 45.4602 | 10715.63 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28881.019 | 28881.019 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28881.02 | 28881.02 | 1.058412 | 12.24 | 8.61 | 0.00546243 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 11.3694 | 21.10 | 0.00698159 | 44.9206 | 12872.19 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 60891.570 | 0.000 | 2.556060 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 60891.57 | 49616.66 | 2.556060 | 27.45 | 18.39 | 0.00952140 | 12.00 | 11.25 | 0.00800000 | 32.10 | 0.01409687 | 23.10 | 13.8466 | 26.70 | 0.00878603 | 40.2501 | 31986.67 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 86828.943 | 86828.943 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 86828.94 | 86828.94 | 2.556064 | 10.73 | 6.75 | 0.00449435 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 13.8466 | 15.54 | 0.00516605 | 47.2352 | 67994.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 223950.022 | 223950.022 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.392692 | 6.49061703 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 223950.02 | 223950.02 | 1.0000 | 6.49061703 | 5.392692 | 6.86 | 6.86 | 0.00670365 | 23745.1 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 223950.02 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 9.98 | 0.00762811 | 9.98 | 0.00762811 | 100.0000 | 223950.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20561.900 | 0.000 | 1.058410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6531 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20561.90 | 17336.93 | 1.0000 | 1.27389696 | 1.058410 | 24.71 | 17.08 | 0.00904442 | 47868.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20561.90 | 31.06 | 0.01409688 | 22.82 | 0.12033533 | 11.3694 | 23.90 | 0.00839630 | 23.90 | 0.00839630 | 45.4602 | 10715.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28881.019 | 28881.019 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.058412 | 1.27389987 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28881.02 | 28881.02 | 1.0000 | 1.27389987 | 1.058412 | 12.24 | 8.61 | 0.00546243 | 26087.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28881.02 | -10.70 | 0.00150390 | -10.70 | 0.12033533 | 11.3694 | 21.05 | 0.00698159 | 21.10 | 0.00698159 | 44.9206 | 12872.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 60891.570 | 0.000 | 2.556060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5398 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 60891.57 | 49616.66 | 1.0000 | 3.07646099 | 2.556060 | 27.45 | 18.39 | 0.00952140 | 51876.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60891.57 | 32.10 | 0.01409687 | 23.10 | 0.35392745 | 13.8466 | 26.70 | 0.00878603 | 26.70 | 0.00878603 | 40.2501 | 31986.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 86828.943 | 86828.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.556064 | 3.07646600 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 86828.94 | 86828.94 | 1.0000 | 3.07646600 | 2.556064 | 10.73 | 6.75 | 0.00449435 | 22114.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86828.94 | -10.70 | 0.00150390 | -10.70 | 0.35392745 | 13.8466 | 15.55 | 0.00516605 | 15.54 | 0.00516605 | 47.2352 | 67994.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2700.33 | 2439.17 | 1733.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2700.33 | 2439.17 | 1733.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 83.83 | 114.33 | 51.50 | 3.00 |
ZONE2 FINE STORAGE | 491.33 | 33.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 544.33 | 139.67 | 51.50 | 3.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.406 | 0.420 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
Electricity:Building | 624.16 | 4992.32 | 01-JAN-00:10 | 48037.94 | 01-JUN-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 424.56 | 2759.73 | 01-JAN-00:10 | 33963.13 | 01-JUN-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.26 | 483.00 | 01-JAN-01:20 | 2540.42 | 10-FEB-12:40 |
WaterSystems:Electricity | 26.26 | 483.00 | 01-JAN-01:20 | 2540.42 | 10-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 26.26 | 483.00 | 01-JAN-01:20 | 2540.42 | 10-FEB-12:40 |
Fans:Electricity | 61.73 | 0.00 | 17-JAN-18:10 | 6309.63 | 01-JUN-13:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 21-JUL-12:00 |
Ventilation (simple):Fans:Electricity | 2.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 21-JUL-12:00 |
ElectricityPurchased:Facility | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
ElectricityPurchased:Plant | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
Cogeneration:ElectricityPurchased | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
ElectricityNet:Plant | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
Cogeneration:ElectricityNet | 871.23 | 5475.32 | 19-FEB-09:20 | 72175.37 | 04-AUG-14:10 |
Electricity:HVAC | 97.44 | 0.00 | 17-JAN-18:10 | 23324.78 | 19-JUN-12:00 |
General:Fans:Electricity | 58.81 | 0.00 | 17-JAN-18:10 | 4505.37 | 02-JAN-09:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 38.63 | 0.00 | 01-JAN-00:10 | 19320.45 | 19-JUN-12:00 |
ExteriorLights:Electricity | 123.36 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.36 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 910.06 | 5000.00 | 17-JAN-18:10 | 374316.44 | 06-FEB-01:00 |
Gas:HVAC | 910.06 | 5000.00 | 17-JAN-18:10 | 374316.44 | 06-FEB-01:00 |
Heating:Gas | 910.06 | 5000.00 | 17-JAN-18:10 | 374316.44 | 06-FEB-01:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1351.86 | 0.00 | 17-JAN-18:10 | 580622.95 | 06-FEB-01:00 |
EnergyTransfer:Building | 641.66 | 0.00 | 17-JAN-18:10 | 285507.96 | 06-FEB-01:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 67.56 | 0.00 | 01-JAN-00:40 | 25389.39 | 06-FEB-07:10 |
Heating:EnergyTransfer | 554.59 | 0.00 | 17-JAN-18:10 | 285507.96 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 34.24 | 0.00 | 01-JAN-00:40 | 25389.39 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 87.07 | 0.00 | 01-JAN-00:10 | 42464.91 | 18-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 33.32 | 0.00 | 01-JAN-00:10 | 11628.62 | 10-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 227.01 | 0.00 | 01-JAN-00:40 | 77563.31 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 173.26 | 0.00 | 01-JAN-00:40 | 77563.31 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 53.75 | 0.00 | 01-JAN-00:10 | 33076.28 | 18-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 347.09 | 0.00 | 02-JAN-11:00 | 202139.99 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 347.09 | 0.00 | 02-JAN-11:00 | 202139.99 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 710.20 | 0.00 | 17-JAN-18:10 | 295114.99 | 06-FEB-01:00 |
HeatingCoils:EnergyTransfer | 572.25 | 0.00 | 17-JAN-18:10 | 295114.99 | 06-FEB-01:00 |
CoolingCoils:EnergyTransfer | 137.95 | 0.00 | 01-JAN-00:10 | 67066.25 | 02-AUG-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 34.243 | -33.320 | 0.000 | 0.000 | 3.903 | 30.994 | 31.946 | 9.483 | 0.000 | 1.254 | 0.000 | 0.000 | -9.504 | 0.000 | -25.727 | -43.272 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 173.257 | -53.753 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 2.174 | 0.002 | 0.000 | 0.000 | 0.000 | -175.041 | -83.294 |
ZONE3 BULK STORAGE | 347.085 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 32.893 | 0.000 | 4.362 | 0.000 | 0.000 | -18.568 | 0.000 | -643.637 | -143.780 |
Total Facility | 347.085 | 0.000 | 207.500 | -87.072 | 0.000 | 0.000 | 3.903 | 481.960 | 139.282 | 42.376 | 0.000 | 7.790 | 0.002 | 0.000 | -28.072 | 0.000 | -844.405 | -270.347 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-SEP-00:02 | 0.00 | 0.00 | 0.00 | -19336.90 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 19169.08 | 0.00 | -561.68 | 0.00 | -303.20 | 0.00 |
ZONE2 FINE STORAGE | 20-AUG-13:23 | 0.00 | 0.00 | 0.00 | -54312.44 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 687.51 | 52425.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-17:06 | 0.00 | 0.00 | 0.00 | -70658.98 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 3808.61 | 0.00 | 2218.28 | 99883.98 | 0.00 | 0.00 | 0.00 | -42294.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JAN-06:01 | 0.00 | 0.00 | 28416.48 | 0.00 | 0.00 | 0.00 | 57.28 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -278.59 | 0.00 | -939.94 | -28415.43 |
ZONE2 FINE STORAGE | 03-JAN-06:42 | 0.00 | 0.00 | 86607.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15231.44 | -72575.91 |
ZONE3 BULK STORAGE | 06-FEB-00:51 | 202148.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3013.98 | 0.00 | -147034.42 | -56909.87 |
Total Facility | 06-FEB-00:51 | 202148.51 | 0.00 | 84123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4355.31 | 0.00 | -189242.11 | -99716.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0584 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0584 | 0.1137 | 1.0000 | 0.1203 | 0.1137 | ||
PSZ-FINE STORAGE | 2.5561 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.5561 | 0.1385 | 1.0000 | 0.3539 | 0.1385 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0584 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0584 | 1.0000 | 1.0000 | 0.1203 | 0.1137 | ||
PSZ-FINE STORAGE | 2.5561 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.5561 | 1.0000 | 1.0000 | 0.3539 | 0.1385 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0584 | 1.0584 | 1.0584 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5561 | 2.5561 | 2.5561 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0584 | 1.0584 | 1.0584 | 1.0584 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.5561 | 2.5561 | 2.5561 | 2.5561 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0584 | 1.0584 | 1.0584 | 0.1203 | 0.2773 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5561 | 2.5561 | 2.5561 | 0.3539 | 0.1834 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0584 | 1.0584 | 1.0584 | 1.0584 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.5561 | 2.5561 | 2.5561 | 2.5561 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 51.50 |
Number of hours cooling loads not met | 3.00 |
Number of hours not met | 54.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 910.06 | 374316.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 38.63 | 19320.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.36 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 2.92 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.81 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.26 | 2540.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 871.23 |
Natural Gas | 0.00 | 910.06 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1781.28 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 7.99 |
Fans (All) | 12.77 |
Service Water Heating | 5.43 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 180.19 |
Subtotal | 180.19 |
Natural Gas [MJ/m2] | |
Space Heating | 188.22 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 188.22 |
Subtotal | 188.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.06 |
Space Heating | 51.09 |
Space Cooling | 2.17 |
Fans (All) | 3.47 |
Service Water Heating | 1.47 |
Receptacle Equipment | 7.82 |
Miscellaneous | 6.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241562E+12 |
February | 0.000 | 0.228681E+12 |
March | 0.000 | 0.906471E+11 |
April | 0.000 | 0.274766E+11 |
May | 0.000 | 0.139291E+11 |
June | 0.000 | 0.129600E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133920E+11 |
September | 0.000 | 0.129600E+11 |
October | 0.000 | 0.142373E+11 |
November | 0.000 | 0.745182E+11 |
December | 0.000 | 0.166299E+12 |
Annual Sum or Average | 0.910055E+12 | |
Minimum of Months | 0.000 | 0.129600E+11 |
Maximum of Months | 0.000 | 0.241562E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 207502.22 | 1383.35 | 07-JAN-07:05 | 1.70 | -0.8 | 0.194952E+09 | 236.59 | 21-JAN-11:09 | 6.47 | 6.07 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -1.1 | -4.0 | 0.179353E+09 | 236.59 | 04-FEB-08:20 | 0.60 | 0.37 |
March | 17624986.67 | 1742.60 | 11-MAR-07:05 | 2.38 | -0.5 | 0.212191E+09 | 293.32 | 27-MAR-15:00 | 22.20 | 16.33 |
April | 0.239211E+09 | 3119.63 | 07-APR-16:00 | 25.60 | 16.11 | 0.210061E+09 | 303.03 | 26-APR-13:20 | 18.30 | 12.57 |
May | 0.156087E+10 | 16570.15 | 30-MAY-17:43 | 23.27 | 17.10 | 0.246838E+09 | 301.60 | 30-MAY-10:50 | 28.72 | 17.31 |
June | 0.623854E+10 | 18310.71 | 05-JUN-00:03 | 16.93 | 12.79 | 0.258727E+09 | 301.61 | 03-JUN-15:00 | 19.40 | 14.49 |
July | 0.881135E+10 | 17047.27 | 11-JUL-17:08 | 28.12 | 17.26 | 0.248934E+09 | 301.61 | 12-JUL-13:30 | 28.60 | 18.97 |
August | 0.963093E+10 | 17990.91 | 25-AUG-18:23 | 24.75 | 14.33 | 0.268846E+09 | 301.61 | 23-AUG-14:09 | 25.60 | 17.17 |
September | 0.529177E+10 | 19336.98 | 11-SEP-00:02 | 15.50 | 9.78 | 0.248052E+09 | 301.61 | 12-SEP-15:50 | 22.70 | 15.91 |
October | 0.150359E+10 | 7792.80 | 04-OCT-17:15 | 20.77 | 18.48 | 0.235678E+09 | 301.59 | 06-OCT-14:20 | 16.87 | 10.76 |
November | 25986060.99 | 881.71 | 04-NOV-14:10 | 16.78 | 12.90 | 0.193002E+09 | 301.58 | 04-NOV-14:09 | 16.78 | 12.90 |
December | 286341.04 | 1908.94 | 02-DEC-07:05 | 1.10 | -2.0 | 0.194955E+09 | 236.59 | 29-DEC-16:10 | 5.18 | 4.91 |
Annual Sum or Average | 0.333204E+11 | 0.269159E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.1 | -4.0 | 0.179353E+09 | 236.59 | 0.60 | 0.37 | ||
Maximum of Months | 0.963093E+10 | 19336.98 | 28.12 | 18.48 | 0.268846E+09 | 303.03 | 28.72 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173738E+09 | 2951.39 | 31-JAN-16:00 | -1.1 | -5.4 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.267923E+09 | 3089.62 | 03-FEB-14:00 | -0.6 | -4.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.573259E+09 | 4287.06 | 18-MAR-10:00 | 0.00 | -0.7 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.382406E+09 | 2900.65 | 12-APR-08:15 | 5.97 | 0.45 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.989265E+09 | 19439.20 | 29-MAY-13:30 | 26.65 | 17.20 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.860997E+10 | 49129.49 | 22-JUN-17:08 | 29.32 | 17.48 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.172772E+11 | 52033.52 | 11-JUL-17:08 | 28.12 | 17.26 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.189930E+11 | 54311.65 | 20-AUG-13:23 | 28.35 | 15.41 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.556526E+10 | 49477.37 | 04-SEP-13:23 | 26.10 | 18.38 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.525550E+09 | 6134.71 | 04-OCT-14:10 | 24.32 | 18.97 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.198111E+09 | 2225.75 | 20-NOV-11:00 | 4.40 | 2.31 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.198888E+09 | 3016.44 | 09-DEC-11:00 | 3.30 | 0.82 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.537546E+11 | 0.00 | ||||||||
Minimum of Months | 0.173738E+09 | 2225.75 | -1.1 | -5.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.189930E+11 | 54311.65 | 29.32 | 18.97 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.4 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -1.1 | -4.0 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 | 4.34 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.00 | 19.28 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 | 2.85 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820950E+10 | 28416.35 | 24-JAN-06:01 | 11.10 |
February | 0.804133E+10 | 27934.39 | 16-FEB-06:32 | 1.30 |
March | 0.519358E+10 | 28032.54 | 03-MAR-06:01 | 8.90 |
April | 0.224826E+10 | 28144.26 | 07-APR-05:01 | 14.82 |
May | 0.399637E+09 | 28059.13 | 08-MAY-05:01 | 12.83 |
June | 13050765.88 | 737.72 | 26-JUN-06:10 | 21.97 |
July | 873268.90 | 906.42 | 05-JUL-06:10 | 21.28 |
August | 2543827.71 | 838.13 | 21-AUG-06:10 | 20.87 |
September | 14840298.01 | 1322.49 | 13-SEP-06:05 | 21.70 |
October | 0.410163E+09 | 28129.06 | 30-OCT-05:01 | 11.93 |
November | 0.359314E+10 | 28099.36 | 10-NOV-06:01 | 14.60 |
December | 0.611644E+10 | 28100.08 | 07-DEC-06:31 | 0.40 |
Annual Sum or Average | 0.342434E+11 | |||
Minimum of Months | 873268.90 | 737.72 | 0.40 | |
Maximum of Months | 0.820950E+10 | 28416.35 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469120E+11 | 86613.20 | 03-JAN-06:42 | 5.33 |
February | 0.431678E+11 | 84376.36 | 24-FEB-19:22 | 2.75 |
March | 0.220688E+11 | 85037.26 | 13-MAR-00:52 | 1.10 |
April | 0.655688E+10 | 83724.73 | 21-APR-04:23 | 5.60 |
May | 0.400515E+09 | 15773.19 | 01-MAY-04:55 | 6.10 |
June | 80111067.88 | 1648.03 | 19-JUN-06:05 | 25.37 |
July | 12754086.28 | 1004.15 | 03-JUL-06:05 | 23.17 |
August | 18367280.51 | 1350.24 | 01-AUG-06:05 | 24.18 |
September | 0.105344E+09 | 1818.07 | 22-SEP-15:20 | 21.87 |
October | 0.482640E+09 | 30469.23 | 31-OCT-05:38 | 5.20 |
November | 0.178162E+11 | 84928.43 | 26-NOV-08:62 | 8.98 |
December | 0.356360E+11 | 86215.03 | 29-DEC-21:22 | 4.40 |
Annual Sum or Average | 0.173257E+12 | |||
Minimum of Months | 12754086.28 | 1004.15 | 1.10 | |
Maximum of Months | 0.469120E+11 | 86613.20 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114961E+12 | 174910.81 | 01-JAN-20:54 | -8.3 |
February | 0.109635E+12 | 202148.61 | 06-FEB-00:51 | -13.3 |
March | 0.277730E+11 | 109099.50 | 22-MAR-07:10 | -2.7 |
April | 0.105800E+10 | 27403.85 | 02-APR-05:55 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.229253E+11 | 114915.64 | 23-NOV-01:51 | -2.8 |
December | 0.707333E+11 | 175715.13 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.347086E+12 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.114961E+12 | 202148.61 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448677E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427396E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356654E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8628669.74 | 0.207803E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25764367.54 | 0.131009E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195368E+09 | 0.561191E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413285E+09 | 0.107022E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525280E+09 | 0.190725E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84192129.53 | 0.683223E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1423528.93 | 0.167246E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295227E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384453E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.125394E+10 | 0.257268E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107022E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525280E+09 | 0.448677E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315074E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287457E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2643616.26 | 0.211301E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55430657.15 | 0.118286E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29912799.12 | 0.808783E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339166E+09 | 0.667016E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637346E+09 | 0.273496E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103491E+10 | 0.322952E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74440011.48 | 0.637929E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109381E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179525E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258363E+11 |
Annual Sum or Average | 0.136656E+12 | 0.217385E+10 | 0.175041E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273496E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103491E+10 | 0.315074E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35534844.93 | 0.683508E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671912E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534263E+09 | 0.410615E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120008E+10 | 0.258843E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115750E+09 | 0.235920E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105848E+09 | 0.291907E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4982122.27 | 0.173756E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27822833.90 | 0.192177E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155098.10 | 0.262719E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12557727.89 | 0.328408E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83070833.20 | 0.365792E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4869498.33 | 0.505618E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.212493E+10 | 0.438117E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173756E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120008E+10 | 0.683508E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14700.51 | 31-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16414.55 | 06-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 12638.67 | 22-MAR-07:00 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 902.18 | 07-APR-17:00 | 7841.36 | 12-APR-07:00 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1962.18 | 30-MAY-12:00 | 5543.02 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.95 | 19-JUN-12:00 | 3945.39 | 02-JUN-06:05 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3497.90 | 07-JUL-12:00 | 1185.48 | 11-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.65 | 24-AUG-17:00 | 2506.58 | 08-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.85 | 14-SEP-16:10 | 4681.44 | 11-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.99 | 25-OCT-11:10 | 6802.88 | 18-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11190.13 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10730.15 | 22-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.48 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.95 | 16414.55 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 49629.42 | 14-JAN-17:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 44323.65 | 06-FEB-07:10 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.30 | 27-MAR-16:00 | 46838.52 | 22-MAR-07:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2226.38 | 16-APR-17:00 | 19972.50 | 21-APR-06:10 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1667.86 | 29-MAY-12:10 | 11716.75 | 11-MAY-16:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7675.71 | 19-JUN-17:00 | 12356.14 | 06-JUN-15:05 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6792.78 | 10-JUL-15:10 | 5519.17 | 15-JUL-08:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11165.88 | 24-AUG-17:00 | 6186.94 | 20-AUG-06:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3476.23 | 01-SEP-15:10 | 7869.68 | 23-SEP-07:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 18304.94 | 07-OCT-15:03 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32040.99 | 23-NOV-01:51 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 44471.53 | 31-DEC-21:51 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5519.17 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11165.88 | 49629.42 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3250.64 | 03-JAN-10:40 | 112510.94 | 14-JAN-17:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 108146.48 | 06-FEB-00:54 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18959.84 | 27-MAR-16:00 | 96756.39 | 22-MAR-07:10 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19369.00 | 07-APR-13:00 | 44223.60 | 12-APR-07:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5416.48 | 29-MAY-11:55 | 29091.85 | 11-MAY-16:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4072.95 | 19-JUN-10:55 | 34445.61 | 03-JUN-16:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 539.30 | 16-JUL-11:53 | 24640.81 | 11-JUL-08:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3433.62 | 04-AUG-18:53 | 28086.01 | 19-AUG-08:50 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.50 | 14-SEP-14:00 | 29087.22 | 23-SEP-09:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3326.60 | 25-OCT-11:00 | 50257.29 | 28-OCT-08:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.01 | 26-NOV-14:55 | 66819.01 | 23-NOV-01:51 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 880.94 | 25-DEC-08:55 | 100497.73 | 31-DEC-21:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24640.81 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19369.00 | 112510.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1383.35 | 07-JAN-07:05 | 553.77 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1390.87 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.88 |
March | 1742.60 | 11-MAR-07:05 | 553.77 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1681.13 |
April | 3119.63 | 07-APR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 200.74 | 0.00 |
May | 16570.15 | 30-MAY-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 |
June | 18310.71 | 05-JUN-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.69 |
July | 17047.27 | 11-JUL-17:08 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.58 | 0.00 |
August | 17990.91 | 25-AUG-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
September | 19336.98 | 11-SEP-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.20 |
October | 7792.80 | 04-OCT-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.70 |
November | 881.71 | 04-NOV-14:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 |
December | 1908.94 | 02-DEC-07:05 | 553.77 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1838.20 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19336.98 | 659.25 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.58 | 1838.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2951.39 | 31-JAN-16:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3089.62 | 03-FEB-14:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.20 |
March | 4287.06 | 18-MAR-10:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2900.65 | 12-APR-08:15 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5746.74 |
May | 19439.20 | 29-MAY-13:30 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.99 |
June | 49129.49 | 22-JUN-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.28 | 0.00 |
July | 52033.52 | 11-JUL-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.56 | 0.00 |
August | 54311.65 | 20-AUG-13:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.51 | 0.00 |
September | 49477.37 | 04-SEP-13:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.17 |
October | 6134.71 | 04-OCT-14:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.67 |
November | 2225.75 | 20-NOV-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3549.77 |
December | 3016.44 | 09-DEC-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2225.75 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54311.65 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.28 | 5746.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 27597.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80082.71 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22267.23 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8263.37 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9815.24 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4831.16 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8398.81 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9593.74 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6164.11 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7448.53 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19927.13 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11995.30 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15326.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4831.16 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80082.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.732280E+11 | 55758.75 | 14-JAN-16:00 | 0.241562E+12 | 338242.35 | 01-JAN-23:30 |
February | 0.660974E+11 | 52275.29 | 13-FEB-13:50 | 0.228681E+12 | 374316.44 | 06-FEB-00:00 |
March | 0.732750E+11 | 52171.54 | 16-MAR-14:00 | 0.906471E+11 | 239162.15 | 22-MAR-06:10 |
April | 0.669736E+11 | 52718.54 | 07-APR-14:00 | 0.274766E+11 | 82433.67 | 02-APR-05:00 |
May | 0.690248E+11 | 61438.98 | 31-MAY-13:50 | 0.139291E+11 | 27257.35 | 01-MAY-05:10 |
June | 0.739144E+11 | 71929.43 | 19-JUN-12:20 | 0.129600E+11 | 5000.00 | 01-JUN-00:10 |
July | 0.803291E+11 | 71302.37 | 08-JUL-12:09 | 0.133920E+11 | 5000.00 | 01-JUL-00:10 |
August | 0.850324E+11 | 72175.37 | 04-AUG-14:09 | 0.133920E+11 | 5000.00 | 01-AUG-00:10 |
September | 0.718378E+11 | 66999.19 | 14-SEP-13:00 | 0.129600E+11 | 5000.00 | 01-SEP-00:10 |
October | 0.698301E+11 | 56756.06 | 04-OCT-14:20 | 0.142373E+11 | 32340.66 | 31-OCT-06:10 |
November | 0.686401E+11 | 55751.62 | 30-NOV-16:00 | 0.745182E+11 | 229749.25 | 23-NOV-02:09 |
December | 0.730435E+11 | 55756.91 | 29-DEC-16:40 | 0.166299E+12 | 333323.24 | 31-DEC-22:10 |
Annual Sum or Average | 0.871226E+12 | 0.910055E+12 | ||||
Minimum of Months | 0.660974E+11 | 52171.54 | 0.129600E+11 | 5000.00 | ||
Maximum of Months | 0.850324E+11 | 72175.37 | 0.241562E+12 | 374316.44 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.127664E+11 | 0.115358E+11 | 0.00 | 0.649743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232499E+10 | 0.00 |
February | 0.366966E+11 | 0.107063E+11 | 0.105871E+11 | 0.00 | 0.598584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212159E+10 | 0.00 |
March | 0.423649E+11 | 0.107204E+11 | 0.123357E+11 | 0.00 | 0.547885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237519E+10 | 0.00 |
April | 0.397216E+11 | 0.924011E+10 | 0.114862E+11 | 0.00 | 0.422790E+10 | 0.00 | 0.00 | 84546954.84 | 0.00 | 0.00 | 0.00 | 0.221323E+10 | 0.00 |
May | 0.412341E+11 | 0.854239E+10 | 0.119357E+11 | 0.00 | 0.414221E+10 | 0.00 | 0.00 | 0.946709E+09 | 0.00 | 0.00 | 0.00 | 0.222362E+10 | 0.00 |
June | 0.408524E+11 | 0.773624E+10 | 0.118862E+11 | 0.00 | 0.462395E+10 | 0.00 | 0.00 | 0.670445E+10 | 0.00 | 0.00 | 0.00 | 0.211121E+10 | 0.00 |
July | 0.401034E+11 | 0.823124E+10 | 0.115358E+11 | 0.00 | 0.559677E+10 | 0.00 | 0.00 | 0.127679E+11 | 0.00 | 0.00 | 0.00 | 0.209401E+10 | 0.00 |
August | 0.423649E+11 | 0.908926E+10 | 0.123357E+11 | 0.00 | 0.610702E+10 | 0.00 | 0.00 | 0.130009E+11 | 0.00 | 0.00 | 0.00 | 0.213470E+10 | 0.00 |
September | 0.397216E+11 | 0.987655E+10 | 0.114862E+11 | 0.00 | 0.424151E+10 | 0.00 | 0.00 | 0.445198E+10 | 0.00 | 0.00 | 0.00 | 0.205994E+10 | 0.00 |
October | 0.401034E+11 | 0.113851E+11 | 0.115358E+11 | 0.00 | 0.397532E+10 | 0.00 | 0.00 | 0.670650E+09 | 0.00 | 0.00 | 0.00 | 0.215986E+10 | 0.00 |
November | 0.385909E+11 | 0.120546E+11 | 0.110862E+11 | 0.00 | 0.475163E+10 | 0.00 | 0.00 | 4224793.89 | 0.00 | 0.00 | 0.00 | 0.215259E+10 | 0.00 |
December | 0.401034E+11 | 0.130163E+11 | 0.115358E+11 | 0.00 | 0.610152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228650E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123365E+12 | 0.139282E+12 | 0.617299E+11 | 0.00 | 0.386314E+11 | 0.262574E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.773624E+10 | 0.105871E+11 | 0.00 | 0.397532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205994E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.130163E+11 | 0.123357E+11 | 0.00 | 0.649743E+10 | 0.00 | 0.00 | 0.130009E+11 | 0.00 | 0.00 | 0.00 | 0.237519E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.241562E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.228681E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.906471E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.274766E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.139291E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.133920E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.133920E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.129600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142373E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.745182E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.166299E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910055E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.129600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241562E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4505.37 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4505.37 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4505.37 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4505.37 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4004.33 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6309.63 | 01-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6309.63 | 03-JUL-11:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6309.63 | 01-AUG-09:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6309.63 | 01-SEP-10:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4004.33 | 03-OCT-13:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4505.37 | 18-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4505.37 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4004.33 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6309.63 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2535.53 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2540.42 | 10-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2509.82 | 01-MAR-12:50 | 0.00 |
April | 1351.20 | 07-APR-15:00 | 0.00 | 0.00 | 0.00 | 2345.16 | 01-APR-11:50 | 0.00 |
May | 10092.06 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 | 2060.86 | 01-MAY-11:00 | 0.00 |
June | 19320.45 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 1798.32 | 01-JUN-11:09 | 0.00 |
July | 17543.80 | 07-JUL-11:00 | 0.00 | 0.00 | 0.00 | 1777.58 | 01-JUL-11:39 | 0.00 |
August | 18562.54 | 02-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1769.35 | 31-AUG-11:50 | 0.00 |
September | 13502.66 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1783.74 | 30-SEP-11:09 | 0.00 |
October | 5267.29 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 1809.70 | 31-OCT-11:00 | 0.00 |
November | 319.46 | 04-NOV-13:39 | 0.00 | 0.00 | 0.00 | 2161.76 | 28-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2405.57 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1769.35 | 0.00 | ||
Maximum of Months | 19320.45 | 0.00 | 0.00 | 0.00 | 2540.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55758.75 | 14-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52275.29 | 13-FEB-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52171.54 | 16-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52718.54 | 07-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4004.33 | 0.00 | 0.00 | 1230.92 | 0.00 |
May | 61438.98 | 31-MAY-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4004.33 | 0.00 | 0.00 | 9975.18 | 0.00 |
June | 71929.43 | 19-JUN-12:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6309.63 | 0.00 | 0.00 | 18136.84 | 0.00 |
July | 71302.37 | 08-JUL-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6309.63 | 0.00 | 0.00 | 17519.54 | 0.00 |
August | 72175.37 | 04-AUG-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6309.63 | 0.00 | 0.00 | 18398.60 | 0.00 |
September | 66999.19 | 14-SEP-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6309.63 | 0.00 | 0.00 | 13247.24 | 0.00 |
October | 56756.06 | 04-OCT-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4004.33 | 0.00 | 0.00 | 5267.29 | 0.00 |
November | 55751.62 | 30-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55756.91 | 29-DEC-16:40 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4505.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52171.54 | 31660.41 | 10112.62 | 0.00 | 0.00 | 4004.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72175.37 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6309.63 | 0.00 | 0.00 | 18398.60 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 338242.35 | 01-JAN-23:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 374316.44 | 06-FEB-00:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 239162.15 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 82433.67 | 02-APR-05:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 27257.35 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 32340.66 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 229749.25 | 23-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 333323.24 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 5000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 374316.44 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.33 | 16.76 | 9.33 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23.33 | 16.66 | 9.17 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10.83 | 18.77 | 8.83 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.17 | 19.69 | 5.83 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.17 | 20.38 | 1.17 | 20.38 | 2.83 | 24.52 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.58 | 0.33 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 24.61 | 1.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 24.64 | 1.17 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.55 | 0.33 | 24.51 |
October | 0.83 | 20.37 | 0.83 | 20.37 | 1.67 | 24.49 | 0.00 | 0.00 |
November | 7.00 | 19.64 | 6.67 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.17 | 18.48 | 9.67 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.83 | 17.78 | 51.50 | 19.59 | 114.33 | 24.61 | 3.00 | 24.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.33 | 20.38 | 9.67 | 20.38 | 44.83 | 24.64 | 1.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.67 | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 107.33 | 13.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74.33 | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22.50 | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 15.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.36 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.35 | 0.00 | 0.00 |
October | 0.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61.83 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107.17 | 14.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 491.33 | 14.19 | 0.00 | 33.33 | 27.45 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.67 | 15.00 | 0.00 | 0.00 | 14.00 | 27.48 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.13 | 310.67 | 21.07 | 310.67 | 21.07 |
April | 300.00 | 21.77 | 200.33 | 21.10 | 200.33 | 21.10 |
May | 280.50 | 22.99 | 41.50 | 22.06 | 27.67 | 21.14 |
June | 28.17 | 23.73 | 230.50 | 23.90 | 6.67 | 23.81 |
July | 15.17 | 23.90 | 297.67 | 23.91 | 15.17 | 23.90 |
August | 10.33 | 23.90 | 293.50 | 23.90 | 9.50 | 23.90 |
September | 85.00 | 23.57 | 148.17 | 23.90 | 4.83 | 23.90 |
October | 232.00 | 22.77 | 65.83 | 22.18 | 46.83 | 21.48 |
November | 288.00 | 21.34 | 236.17 | 21.08 | 236.17 | 21.08 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 2439.17 | 21.71 | 2700.33 | 22.12 | 1733.83 | 21.13 |
Minimum of Months | 10.33 | 21.04 | 41.50 | 21.04 | 4.83 | 21.04 |
Maximum of Months | 324.00 | 23.90 | 310.67 | 23.91 | 310.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.308884E+09 | 84546954.84 | 39.33 | 0.281628E+09 | 27255436.39 | 0.00 | 0.27 | 07-APR-16:00 | 0.00 | 01-APR-00:10 | 4909.43 | 07-APR-16:00 | 4589.11 | 07-APR-16:00 | 597.27 | 10-APR-10:00 | 1351.20 | 07-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.216649E+10 | 0.587680E+09 | 177.52 | 0.190737E+10 | 0.259119E+09 | 0.00 | 1.00 | 30-MAY-00:02 | 0.00 | 01-MAY-00:10 | 21816.91 | 30-MAY-00:02 | 18333.61 | 30-MAY-17:43 | 6000.55 | 31-MAY-17:10 | 5126.42 | 30-MAY-00:02 | 0.00 | 01-MAY-00:10 |
June | 0.992323E+10 | 0.266080E+10 | 406.84 | 0.760188E+10 | 0.232135E+10 | 0.00 | 1.00 | 01-JUN-17:43 | 0.00 | 01-JUN-00:10 | 25516.54 | 19-JUN-00:01 | 19813.90 | 05-JUN-00:03 | 11517.17 | 19-JUN-00:06 | 5815.68 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.150893E+11 | 0.404351E+10 | 490.67 | 0.108546E+11 | 0.423464E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:05 | 26062.33 | 31-JUL-00:01 | 19408.63 | 11-JUL-17:08 | 12607.32 | 24-JUL-00:04 | 5974.64 | 10-JUL-00:01 | 0.00 | 01-JUL-00:05 |
August | 0.151934E+11 | 0.413150E+10 | 525.69 | 0.117956E+11 | 0.339781E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:15 | 24676.30 | 28-AUG-00:01 | 20101.12 | 25-AUG-18:23 | 10086.93 | 03-AUG-17:08 | 5804.08 | 04-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.779277E+10 | 0.207819E+10 | 360.66 | 0.626222E+10 | 0.153055E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:15 | 23773.71 | 13-SEP-17:10 | 20103.75 | 11-SEP-00:02 | 9611.39 | 13-SEP-17:10 | 5509.08 | 13-SEP-17:10 | 0.00 | 01-SEP-00:10 |
October | 0.219942E+10 | 0.585484E+09 | 157.61 | 0.169339E+10 | 0.506024E+09 | 0.00 | 0.61 | 04-OCT-17:15 | 0.00 | 01-OCT-00:10 | 11622.39 | 04-OCT-17:15 | 8513.01 | 04-OCT-17:15 | 3343.35 | 05-OCT-17:15 | 3086.51 | 04-OCT-17:15 | 0.00 | 01-OCT-00:10 |
November | 15285758.54 | 4224793.89 | 5.50 | 14143068.34 | 1142690.20 | 0.00 | 0.07 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 1158.13 | 04-NOV-13:40 | 1066.07 | 04-NOV-13:30 | 116.87 | 04-NOV-15:00 | 319.46 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.526888E+11 | 0.141759E+11 | 2163.82 | 0.404109E+11 | 0.122779E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.151934E+11 | 0.413150E+10 | 525.69 | 0.117956E+11 | 0.423464E+10 | 0.00 | 1.00 | 0.00 | 26062.33 | 20103.75 | 12607.32 | 5974.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.121849E+10 | 0.359030E+09 | 24.83 | 0.102332E+10 | 0.195175E+09 | 0.00 | 0.46 | 29-MAY-12:05 | 0.00 | 01-MAY-00:10 | 25580.74 | 31-MAY-14:00 | 21343.19 | 29-MAY-13:30 | 5827.52 | 31-MAY-13:50 | 7395.13 | 29-MAY-12:05 | 0.00 | 01-MAY-00:10 |
June | 0.140604E+11 | 0.404365E+10 | 234.88 | 0.102119E+11 | 0.384845E+10 | 0.00 | 1.00 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 | 73109.12 | 25-JUN-13:33 | 54537.63 | 22-JUN-17:08 | 31730.84 | 25-JUN-12:53 | 18677.18 | 19-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.306336E+11 | 0.872442E+10 | 343.49 | 0.206554E+11 | 0.997825E+10 | 0.00 | 1.00 | 02-JUL-12:43 | 0.00 | 01-JUL-00:05 | 73939.03 | 30-JUL-11:33 | 57134.08 | 11-JUL-17:08 | 33353.82 | 20-JUL-18:23 | 18785.97 | 09-JUL-12:43 | 0.00 | 01-JUL-00:05 |
August | 0.307425E+11 | 0.886937E+10 | 347.94 | 0.225137E+11 | 0.822883E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:10 | 73474.28 | 03-AUG-17:08 | 59363.62 | 20-AUG-13:23 | 32848.67 | 03-AUG-17:08 | 18832.10 | 04-AUG-19:43 | 0.00 | 01-AUG-00:10 |
September | 0.830847E+10 | 0.237379E+10 | 171.93 | 0.634936E+10 | 0.195911E+10 | 0.00 | 1.00 | 04-SEP-12:03 | 0.00 | 01-SEP-00:10 | 65045.92 | 04-SEP-12:03 | 53484.89 | 04-SEP-13:23 | 23981.85 | 07-SEP-17:10 | 16706.41 | 04-SEP-12:03 | 0.00 | 01-SEP-00:10 |
October | 0.299199E+09 | 85166043.52 | 12.67 | 0.209783E+09 | 89415979.20 | 0.00 | 0.19 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 | 10986.42 | 04-OCT-14:00 | 8043.00 | 04-OCT-14:00 | 3072.17 | 05-OCT-14:00 | 3127.14 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.852626E+11 | 0.244554E+11 | 1135.73 | 0.609634E+11 | 0.242992E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.307425E+11 | 0.886937E+10 | 347.94 | 0.225137E+11 | 0.997825E+10 | 0.00 | 1.00 | 0.00 | 73939.03 | 59363.62 | 33353.82 | 18832.10 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.43 | 26.47 | 37.96 | 28.23 | 184.47 | 0.00 | 0.00 | 744.00 |
February | 94.42 | 41.42 | 53.00 | 49.10 | 189.10 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 65.14 | 75.36 | 108.35 | 112.86 | 0.00 | 0.00 | 744.00 |
April | 152.43 | 65.08 | 87.35 | 137.96 | 79.76 | 0.00 | 0.00 | 720.00 |
May | 178.14 | 67.67 | 110.46 | 179.36 | 54.75 | 0.00 | 0.00 | 744.00 |
June | 194.95 | 78.80 | 116.16 | 217.58 | 37.14 | 0.00 | 0.00 | 720.00 |
July | 182.36 | 68.66 | 113.70 | 221.71 | 21.02 | 0.00 | 0.00 | 744.00 |
August | 201.63 | 93.27 | 108.37 | 247.77 | 29.37 | 0.00 | 0.00 | 744.00 |
September | 143.45 | 62.68 | 80.77 | 148.93 | 57.25 | 0.00 | 0.00 | 720.00 |
October | 141.69 | 68.78 | 72.91 | 132.47 | 89.45 | 0.00 | 0.00 | 744.00 |
November | 66.83 | 19.39 | 47.44 | 33.69 | 122.56 | 0.00 | 0.00 | 720.00 |
December | 59.36 | 25.72 | 33.64 | 27.23 | 165.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 135.30 | 57.06 | 78.25 | 128.27 | 94.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 59.36 | 19.39 | 33.64 | 27.23 | 21.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.63 | 93.27 | 116.16 | 247.77 | 189.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.43 | 26.47 | 37.96 | 28.23 | 184.47 | 0.00 | 0.00 | 744.00 |
February | 94.42 | 41.42 | 53.00 | 49.10 | 189.10 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 65.14 | 75.36 | 108.35 | 112.86 | 0.00 | 0.00 | 744.00 |
April | 152.43 | 65.08 | 87.35 | 137.96 | 79.76 | 0.00 | 0.00 | 720.00 |
May | 178.14 | 67.67 | 110.46 | 179.36 | 54.75 | 0.00 | 0.00 | 744.00 |
June | 194.95 | 78.80 | 116.16 | 217.58 | 37.14 | 0.00 | 0.00 | 720.00 |
July | 182.36 | 68.66 | 113.70 | 221.71 | 21.02 | 0.00 | 0.00 | 744.00 |
August | 201.63 | 93.27 | 108.37 | 247.77 | 29.37 | 0.00 | 0.00 | 744.00 |
September | 143.45 | 62.68 | 80.77 | 148.93 | 57.25 | 0.00 | 0.00 | 720.00 |
October | 141.69 | 68.78 | 72.91 | 132.47 | 89.45 | 0.00 | 0.00 | 744.00 |
November | 66.83 | 19.39 | 47.44 | 33.69 | 122.56 | 0.00 | 0.00 | 720.00 |
December | 59.36 | 25.72 | 33.64 | 27.23 | 165.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 135.30 | 57.06 | 78.25 | 128.27 | 94.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 59.36 | 19.39 | 33.64 | 27.23 | 21.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.63 | 93.27 | 116.16 | 247.77 | 189.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.15 | 0.00 | 18.15 | 0.14 | 115.57 | 0.00 | 0.00 | 744.00 |
February | 24.84 | 0.00 | 24.84 | 1.10 | 120.87 | 0.00 | 0.00 | 672.00 |
March | 34.45 | 0.00 | 34.45 | 8.11 | 71.76 | 0.00 | 0.00 | 744.00 |
April | 41.39 | 0.13 | 41.26 | 21.44 | 48.24 | 0.00 | 0.00 | 720.00 |
May | 55.10 | 1.99 | 53.11 | 39.65 | 31.55 | 0.00 | 0.00 | 744.00 |
June | 58.10 | 3.02 | 55.08 | 53.54 | 20.72 | 0.00 | 0.00 | 720.00 |
July | 56.37 | 2.13 | 54.24 | 63.45 | 11.92 | 0.00 | 0.00 | 744.00 |
August | 49.92 | 0.67 | 49.25 | 56.34 | 16.97 | 0.00 | 0.00 | 744.00 |
September | 37.59 | 0.02 | 37.57 | 28.70 | 34.46 | 0.00 | 0.00 | 720.00 |
October | 32.51 | 0.00 | 32.51 | 16.37 | 54.28 | 0.00 | 0.00 | 744.00 |
November | 22.80 | 0.00 | 22.80 | 4.05 | 75.47 | 0.00 | 0.00 | 720.00 |
December | 15.83 | 0.00 | 15.83 | 0.25 | 103.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 37.33 | 0.67 | 36.66 | 24.59 | 58.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.83 | 0.00 | 15.83 | 0.14 | 11.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.10 | 3.02 | 55.08 | 63.45 | 120.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.15 | 0.00 | 18.15 | 0.14 | 115.57 | 0.00 | 0.00 | 744.00 |
February | 24.84 | 0.00 | 24.84 | 1.10 | 120.87 | 0.00 | 0.00 | 672.00 |
March | 34.45 | 0.00 | 34.45 | 8.11 | 71.77 | 0.00 | 0.00 | 744.00 |
April | 41.39 | 0.13 | 41.26 | 21.44 | 48.24 | 0.00 | 0.00 | 720.00 |
May | 55.10 | 1.99 | 53.11 | 39.65 | 31.55 | 0.00 | 0.00 | 744.00 |
June | 58.09 | 3.02 | 55.07 | 53.54 | 20.72 | 0.00 | 0.00 | 720.00 |
July | 56.37 | 2.13 | 54.24 | 63.45 | 11.92 | 0.00 | 0.00 | 744.00 |
August | 49.92 | 0.67 | 49.25 | 56.34 | 16.97 | 0.00 | 0.00 | 744.00 |
September | 37.59 | 0.02 | 37.57 | 28.70 | 34.46 | 0.00 | 0.00 | 720.00 |
October | 32.51 | 0.00 | 32.51 | 16.37 | 54.28 | 0.00 | 0.00 | 744.00 |
November | 22.80 | 0.00 | 22.80 | 4.05 | 75.47 | 0.00 | 0.00 | 720.00 |
December | 15.83 | 0.00 | 15.83 | 0.25 | 103.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 37.33 | 0.67 | 36.66 | 24.59 | 58.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.83 | 0.00 | 15.83 | 0.14 | 11.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.09 | 3.02 | 55.07 | 63.45 | 120.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.07 | 13.28 | 18.79 | 27.52 | 93.32 | 40.50 | 0.00 | 744.00 |
February | 52.21 | 28.29 | 23.92 | 49.17 | 98.56 | 0.00 | 0.00 | 672.00 |
March | 77.96 | 43.21 | 34.74 | 95.19 | 51.79 | 9.50 | 0.00 | 744.00 |
April | 96.24 | 54.17 | 42.07 | 122.85 | 43.85 | 47.50 | 0.00 | 720.00 |
May | 121.35 | 65.71 | 55.64 | 160.16 | 38.90 | 19.33 | 0.00 | 744.00 |
June | 132.55 | 75.34 | 57.21 | 172.35 | 40.50 | 1.17 | 0.00 | 720.00 |
July | 127.86 | 69.58 | 58.27 | 171.08 | 35.85 | 10.00 | 0.00 | 744.00 |
August | 131.23 | 82.58 | 48.65 | 175.20 | 47.41 | 4.50 | 0.00 | 744.00 |
September | 90.05 | 52.56 | 37.50 | 111.08 | 55.73 | 3.67 | 0.00 | 720.00 |
October | 75.19 | 43.97 | 31.22 | 93.32 | 62.35 | 80.67 | 0.00 | 744.00 |
November | 40.85 | 16.29 | 24.56 | 44.16 | 62.86 | 26.17 | 0.00 | 720.00 |
December | 28.51 | 13.12 | 15.39 | 25.34 | 78.10 | 9.50 | 0.00 | 744.00 |
Annual Sum or Average | 84.03 | 46.63 | 37.41 | 104.31 | 58.87 | 252.50 | 0.00 | 8760.00 |
Minimum of Months | 28.51 | 13.12 | 15.39 | 25.34 | 35.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 132.55 | 82.58 | 58.27 | 175.20 | 98.56 | 80.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172563E+09 | 70902435.68 | 0.101660E+09 | 75601933.00 | 0.494081E+09 |
February | 0.228426E+09 | 0.100212E+09 | 0.128214E+09 | 0.118774E+09 | 0.457461E+09 |
March | 0.376335E+09 | 0.174483E+09 | 0.201852E+09 | 0.290195E+09 | 0.302295E+09 |
April | 0.395110E+09 | 0.168688E+09 | 0.226422E+09 | 0.357581E+09 | 0.206741E+09 |
May | 0.477120E+09 | 0.181255E+09 | 0.295865E+09 | 0.480394E+09 | 0.146646E+09 |
June | 0.505320E+09 | 0.204237E+09 | 0.301083E+09 | 0.563975E+09 | 96259915.43 |
July | 0.488432E+09 | 0.183906E+09 | 0.304525E+09 | 0.593818E+09 | 56304936.01 |
August | 0.540052E+09 | 0.249803E+09 | 0.290249E+09 | 0.663638E+09 | 78667975.13 |
September | 0.371824E+09 | 0.162459E+09 | 0.209365E+09 | 0.386025E+09 | 0.148400E+09 |
October | 0.379509E+09 | 0.184230E+09 | 0.195279E+09 | 0.354802E+09 | 0.239587E+09 |
November | 0.173230E+09 | 50262002.35 | 0.122968E+09 | 87317147.47 | 0.317678E+09 |
December | 0.158980E+09 | 68884314.80 | 90095590.66 | 72924903.87 | 0.443639E+09 |
Annual Sum or Average | 0.426690E+10 | 0.179932E+10 | 0.246758E+10 | 0.404505E+10 | 0.298776E+10 |
Minimum of Months | 0.158980E+09 | 50262002.35 | 90095590.66 | 72924903.87 | 56304936.01 |
Maximum of Months | 0.540052E+09 | 0.249803E+09 | 0.304525E+09 | 0.663638E+09 | 0.494081E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172563E+09 | 70902435.68 | 0.101660E+09 | 75601933.00 | 0.494081E+09 |
February | 0.228426E+09 | 0.100212E+09 | 0.128214E+09 | 0.118774E+09 | 0.457461E+09 |
March | 0.376335E+09 | 0.174483E+09 | 0.201852E+09 | 0.290195E+09 | 0.302295E+09 |
April | 0.395110E+09 | 0.168688E+09 | 0.226422E+09 | 0.357581E+09 | 0.206741E+09 |
May | 0.477120E+09 | 0.181255E+09 | 0.295865E+09 | 0.480394E+09 | 0.146646E+09 |
June | 0.505320E+09 | 0.204237E+09 | 0.301083E+09 | 0.563975E+09 | 96259915.43 |
July | 0.488432E+09 | 0.183906E+09 | 0.304525E+09 | 0.593818E+09 | 56304936.01 |
August | 0.540052E+09 | 0.249803E+09 | 0.290249E+09 | 0.663638E+09 | 78667975.13 |
September | 0.371824E+09 | 0.162459E+09 | 0.209365E+09 | 0.386025E+09 | 0.148400E+09 |
October | 0.379509E+09 | 0.184230E+09 | 0.195279E+09 | 0.354802E+09 | 0.239587E+09 |
November | 0.173230E+09 | 50262002.35 | 0.122968E+09 | 87317147.47 | 0.317678E+09 |
December | 0.158980E+09 | 68884314.80 | 90095590.66 | 72924903.87 | 0.443639E+09 |
Annual Sum or Average | 0.426690E+10 | 0.179932E+10 | 0.246758E+10 | 0.404505E+10 | 0.298776E+10 |
Minimum of Months | 0.158980E+09 | 50262002.35 | 90095590.66 | 72924903.87 | 56304936.01 |
Maximum of Months | 0.540052E+09 | 0.249803E+09 | 0.304525E+09 | 0.663638E+09 | 0.494081E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48610356.83 | 0.00 | 48610356.83 | 386250.15 | 0.309540E+09 |
February | 60083741.86 | 0.00 | 60083741.86 | 2663533.51 | 0.292403E+09 |
March | 92277162.48 | 5048.38 | 92272114.10 | 21712887.50 | 0.192215E+09 |
April | 0.107288E+09 | 348219.66 | 0.106940E+09 | 55576678.46 | 0.125041E+09 |
May | 0.147576E+09 | 5325434.76 | 0.142250E+09 | 0.106192E+09 | 84511322.08 |
June | 0.150586E+09 | 7828443.12 | 0.142757E+09 | 0.138775E+09 | 53694616.59 |
July | 0.150988E+09 | 5708750.82 | 0.145279E+09 | 0.169949E+09 | 31934436.36 |
August | 0.133717E+09 | 1802524.63 | 0.131914E+09 | 0.150913E+09 | 45464216.89 |
September | 97429074.52 | 44128.40 | 97384946.13 | 74384567.50 | 89310785.90 |
October | 87076035.77 | 0.00 | 87076035.77 | 43836422.07 | 0.145387E+09 |
November | 59105208.78 | 0.00 | 59105208.78 | 10486033.74 | 0.195625E+09 |
December | 42401163.38 | 0.00 | 42401163.38 | 666786.56 | 0.278275E+09 |
Annual Sum or Average | 0.117714E+10 | 21062549.77 | 0.115607E+10 | 0.775542E+09 | 0.184340E+10 |
Minimum of Months | 42401163.38 | 0.00 | 42401163.38 | 386250.15 | 31934436.36 |
Maximum of Months | 0.150988E+09 | 7828443.12 | 0.145279E+09 | 0.169949E+09 | 0.309540E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48608765.89 | 0.00 | 48608765.89 | 386125.81 | 0.309541E+09 |
February | 60081904.92 | 0.00 | 60081904.92 | 2663240.83 | 0.292404E+09 |
March | 92274370.58 | 5048.15 | 92269322.43 | 21711363.32 | 0.192216E+09 |
April | 0.107285E+09 | 348203.34 | 0.106937E+09 | 55574297.95 | 0.125040E+09 |
May | 0.147571E+09 | 5325185.15 | 0.142246E+09 | 0.106188E+09 | 84511056.39 |
June | 0.150581E+09 | 7828076.19 | 0.142753E+09 | 0.138770E+09 | 53694170.47 |
July | 0.150983E+09 | 5708483.24 | 0.145275E+09 | 0.169944E+09 | 31933887.89 |
August | 0.133713E+09 | 1802440.15 | 0.131910E+09 | 0.150910E+09 | 45463451.74 |
September | 97426208.27 | 44126.33 | 97382081.94 | 74382019.30 | 89310122.74 |
October | 87073469.39 | 0.00 | 87073469.39 | 43834487.63 | 0.145386E+09 |
November | 59103271.25 | 0.00 | 59103271.25 | 10485164.32 | 0.195625E+09 |
December | 42399804.38 | 0.00 | 42399804.38 | 666674.26 | 0.278274E+09 |
Annual Sum or Average | 0.117710E+10 | 21061562.54 | 0.115604E+10 | 0.775515E+09 | 0.184340E+10 |
Minimum of Months | 42399804.38 | 0.00 | 42399804.38 | 386125.81 | 31933887.89 |
Maximum of Months | 0.150983E+09 | 7828076.19 | 0.145275E+09 | 0.169944E+09 | 0.309541E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85909620.86 | 35581405.39 | 50328215.47 | 73707735.07 | 0.249944E+09 |
February | 0.126300E+09 | 68442452.43 | 57857359.09 | 0.118947E+09 | 0.238430E+09 |
March | 0.208795E+09 | 0.115737E+09 | 93057874.07 | 0.254946E+09 | 0.138712E+09 |
April | 0.249446E+09 | 0.140400E+09 | 0.109046E+09 | 0.318416E+09 | 0.113661E+09 |
May | 0.325032E+09 | 0.176006E+09 | 0.149026E+09 | 0.428961E+09 | 0.104177E+09 |
June | 0.343572E+09 | 0.195289E+09 | 0.148283E+09 | 0.446736E+09 | 0.104974E+09 |
July | 0.342451E+09 | 0.186374E+09 | 0.156077E+09 | 0.458210E+09 | 96017144.93 |
August | 0.351491E+09 | 0.221184E+09 | 0.130307E+09 | 0.469259E+09 | 0.126984E+09 |
September | 0.233417E+09 | 0.136229E+09 | 97188606.85 | 0.287930E+09 | 0.144451E+09 |
October | 0.201396E+09 | 0.117766E+09 | 83629938.35 | 0.249952E+09 | 0.167008E+09 |
November | 0.105876E+09 | 42223675.90 | 63651883.45 | 0.114473E+09 | 0.162920E+09 |
December | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 0.209188E+09 |
Annual Sum or Average | 0.265005E+10 | 0.147037E+10 | 0.117968E+10 | 0.328941E+10 | 0.185647E+10 |
Minimum of Months | 76361037.52 | 35137675.91 | 41223361.61 | 67870397.11 | 96017144.93 |
Maximum of Months | 0.351491E+09 | 0.221184E+09 | 0.156077E+09 | 0.469259E+09 | 0.249944E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.18 | 589.51 | 165.15 | 52.94 | 112.21 | 0.00 | 0.00 |
February | 86.41 | 605.94 | 238.52 | 82.85 | 155.67 | 0.00 | 0.00 |
March | 223.55 | 359.90 | 349.92 | 130.29 | 219.63 | 0.00 | 0.00 |
April | 316.00 | 253.21 | 387.65 | 130.43 | 257.22 | 0.00 | 0.00 |
May | 436.43 | 171.03 | 466.47 | 139.32 | 327.15 | 0.00 | 0.00 |
June | 541.50 | 114.96 | 506.10 | 163.63 | 342.47 | 0.00 | 0.00 |
July | 569.78 | 65.35 | 477.46 | 141.59 | 335.87 | 0.00 | 0.00 |
August | 607.89 | 92.34 | 503.11 | 187.88 | 315.23 | 0.00 | 0.00 |
September | 353.68 | 181.84 | 362.08 | 125.39 | 236.69 | 0.00 | 0.00 |
October | 293.52 | 283.32 | 348.41 | 137.57 | 210.84 | 0.00 | 0.00 |
November | 70.13 | 390.73 | 179.27 | 38.78 | 140.49 | 0.00 | 0.00 |
December | 45.10 | 529.21 | 150.37 | 51.44 | 98.94 | 0.00 | 0.00 |
Annual Sum or Average | 300.70 | 301.37 | 345.26 | 115.45 | 229.81 | 0.00 | 0.00 |
Minimum of Months | 45.10 | 65.35 | 150.37 | 38.78 | 98.94 | 0.00 | 0.00 |
Maximum of Months | 607.89 | 605.94 | 506.10 | 187.88 | 342.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.19 | 933.18 | 320.75 | 132.85 | 187.90 | 0.00 | 0.00 |
February | 491.68 | 985.58 | 522.07 | 282.91 | 239.16 | 0.00 | 0.00 |
March | 951.86 | 517.89 | 779.55 | 432.11 | 347.44 | 0.00 | 0.00 |
April | 1228.46 | 438.51 | 962.37 | 541.67 | 420.70 | 0.00 | 0.00 |
May | 1601.55 | 388.95 | 1213.53 | 657.13 | 556.40 | 0.00 | 0.00 |
June | 1723.52 | 404.99 | 1325.51 | 753.43 | 572.08 | 0.00 | 0.00 |
July | 1710.76 | 358.48 | 1278.57 | 695.84 | 582.72 | 0.00 | 0.00 |
August | 1752.01 | 474.10 | 1312.32 | 825.81 | 486.51 | 0.00 | 0.00 |
September | 1110.84 | 557.29 | 900.53 | 525.57 | 374.96 | 0.00 | 0.00 |
October | 933.21 | 623.54 | 751.92 | 439.69 | 312.24 | 0.00 | 0.00 |
November | 441.64 | 628.55 | 408.47 | 162.90 | 245.57 | 0.00 | 0.00 |
December | 253.40 | 781.02 | 285.10 | 131.19 | 153.91 | 0.00 | 0.00 |
Annual Sum or Average | 1043.06 | 588.68 | 840.32 | 466.25 | 374.07 | 0.00 | 0.00 |
Minimum of Months | 253.40 | 358.48 | 285.10 | 131.19 | 153.91 | 0.00 | 0.00 |
Maximum of Months | 1752.01 | 985.58 | 1325.51 | 825.81 | 582.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123676E+09 | 0.157894E+10 | 0.442344E+09 | 0.141805E+09 | 0.300539E+09 | 0.00 | 0.00 |
February | 0.209049E+09 | 0.146590E+10 | 0.577018E+09 | 0.200425E+09 | 0.376594E+09 | 0.00 | 0.00 |
March | 0.598750E+09 | 0.963957E+09 | 0.937222E+09 | 0.348976E+09 | 0.588245E+09 | 0.00 | 0.00 |
April | 0.819073E+09 | 0.656324E+09 | 0.100479E+10 | 0.338073E+09 | 0.666721E+09 | 0.00 | 0.00 |
May | 0.116894E+10 | 0.458088E+09 | 0.124939E+10 | 0.373161E+09 | 0.876227E+09 | 0.00 | 0.00 |
June | 0.140358E+10 | 0.297989E+09 | 0.131181E+10 | 0.424130E+09 | 0.887676E+09 | 0.00 | 0.00 |
July | 0.152610E+10 | 0.175045E+09 | 0.127883E+10 | 0.379230E+09 | 0.899604E+09 | 0.00 | 0.00 |
August | 0.162817E+10 | 0.247330E+09 | 0.134753E+10 | 0.503211E+09 | 0.844323E+09 | 0.00 | 0.00 |
September | 0.916735E+09 | 0.471339E+09 | 0.938503E+09 | 0.325007E+09 | 0.613496E+09 | 0.00 | 0.00 |
October | 0.786166E+09 | 0.758838E+09 | 0.933168E+09 | 0.368460E+09 | 0.564708E+09 | 0.00 | 0.00 |
November | 0.181776E+09 | 0.101278E+10 | 0.464668E+09 | 0.100524E+09 | 0.364144E+09 | 0.00 | 0.00 |
December | 0.120801E+09 | 0.141744E+10 | 0.402761E+09 | 0.137769E+09 | 0.264992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.948281E+10 | 0.950397E+10 | 0.108880E+11 | 0.364077E+10 | 0.724727E+10 | 0.00 | 0.00 |
Minimum of Months | 0.120801E+09 | 0.175045E+09 | 0.402761E+09 | 0.100524E+09 | 0.264992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162817E+10 | 0.157894E+10 | 0.134753E+10 | 0.503211E+09 | 0.899604E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.737077E+09 | 0.249943E+10 | 0.859096E+09 | 0.355814E+09 | 0.503282E+09 | 0.00 | 0.00 |
February | 0.118947E+10 | 0.238430E+10 | 0.126300E+10 | 0.684425E+09 | 0.578574E+09 | 0.00 | 0.00 |
March | 0.254945E+10 | 0.138712E+10 | 0.208795E+10 | 0.115737E+10 | 0.930579E+09 | 0.00 | 0.00 |
April | 0.318416E+10 | 0.113661E+10 | 0.249446E+10 | 0.140400E+10 | 0.109046E+10 | 0.00 | 0.00 |
May | 0.428960E+10 | 0.104177E+10 | 0.325032E+10 | 0.176006E+10 | 0.149026E+10 | 0.00 | 0.00 |
June | 0.446736E+10 | 0.104974E+10 | 0.343572E+10 | 0.195289E+10 | 0.148283E+10 | 0.00 | 0.00 |
July | 0.458210E+10 | 0.960164E+09 | 0.342451E+10 | 0.186374E+10 | 0.156077E+10 | 0.00 | 0.00 |
August | 0.469259E+10 | 0.126984E+10 | 0.351491E+10 | 0.221184E+10 | 0.130307E+10 | 0.00 | 0.00 |
September | 0.287929E+10 | 0.144450E+10 | 0.233417E+10 | 0.136229E+10 | 0.971886E+09 | 0.00 | 0.00 |
October | 0.249952E+10 | 0.167008E+10 | 0.201396E+10 | 0.117766E+10 | 0.836299E+09 | 0.00 | 0.00 |
November | 0.114473E+10 | 0.162920E+10 | 0.105876E+10 | 0.422237E+09 | 0.636519E+09 | 0.00 | 0.00 |
December | 0.678703E+09 | 0.209188E+10 | 0.763610E+09 | 0.351377E+09 | 0.412234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328940E+11 | 0.185646E+11 | 0.265005E+11 | 0.147037E+11 | 0.117968E+11 | 0.00 | 0.00 |
Minimum of Months | 0.678703E+09 | 0.960164E+09 | 0.763610E+09 | 0.351377E+09 | 0.412234E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469259E+10 | 0.249943E+10 | 0.351491E+10 | 0.221184E+10 | 0.156077E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.103144E+10 | -874658533.7 | 0.00 | 0.00 | 744.00 | 0.00 | -156783034.0 | 58.99 | 0.00 | 0.00 |
February | 0.953066E+09 | -811513137.1 | 0.00 | 0.00 | 672.00 | 0.00 | -141552997.8 | 58.99 | 0.00 | 0.00 |
March | 0.108143E+10 | -927077350.9 | 0.00 | 0.00 | 744.00 | 0.00 | -154351599.9 | 58.99 | 0.00 | 0.00 |
April | 0.961276E+09 | -817017948.5 | 0.00 | 0.00 | 720.00 | 0.00 | -144257604.1 | 58.99 | 0.00 | 0.00 |
May | 0.929880E+09 | -790959734.2 | 0.00 | 0.00 | 744.00 | 0.00 | -138920171.1 | 58.99 | 0.00 | 0.00 |
June | 0.859232E+09 | -730920189.7 | 0.00 | 0.00 | 720.00 | 0.00 | -128312246.1 | 58.99 | 0.00 | 0.00 |
July | 0.800209E+09 | -669094333.8 | 0.00 | 0.00 | 744.00 | 0.00 | -131114505.1 | 58.99 | 0.00 | 0.00 |
August | 0.840623E+09 | -708605142.9 | 0.00 | 0.00 | 744.00 | 0.00 | -132018074.4 | 58.99 | 0.00 | 0.00 |
September | 0.807943E+09 | -679583502.7 | 0.00 | 0.00 | 720.00 | 0.00 | -128359120.6 | 58.99 | 0.00 | 0.00 |
October | 0.866460E+09 | -726457736.8 | 0.00 | 0.00 | 744.00 | 0.00 | -140002195.0 | 58.99 | 0.00 | 0.00 |
November | 0.900062E+09 | -752103286.8 | 0.00 | 0.00 | 720.00 | 0.00 | -147958309.0 | 58.99 | 0.00 | 0.00 |
December | 0.993200E+09 | -836725625.3 | 0.00 | 0.00 | 744.00 | 0.00 | -156474230.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.110248E+11 | -.932472E+10 | 8760.00 | -.170010E+10 | 58.99 | |||||
Minimum of Months | 0.800209E+09 | -927077350.9 | 0.00 | 0.00 | 672.00 | 0.00 | -156783034.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.108143E+10 | -669094333.8 | 0.00 | 0.00 | 744.00 | 0.00 | -128312246.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | ||||||||||
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.987773E+10 | 28881.02 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.978451E+10 | 28881.02 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.624199E+10 | 28881.02 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255171E+10 | 28881.02 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351626E+09 | 28881.02 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.432860E+09 | 28881.02 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426568E+10 | 28881.02 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747824E+10 | 28881.02 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409843E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.987773E+10 | 28881.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.517326E+11 | 86828.94 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483457E+11 | 86828.94 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237368E+11 | 86828.94 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646095E+10 | 86828.94 | 02-APR-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12286986.73 | 16180.15 | 01-MAY-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134325E+09 | 31434.91 | 31-OCT-05:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189603E+11 | 86828.94 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387699E+11 | 86828.94 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188153E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.517326E+11 | 86828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113897E+12 | 174409.78 | 01-JAN-20:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108648E+12 | 201647.62 | 06-FEB-00:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272996E+11 | 108598.26 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101660E+10 | 26902.87 | 02-APR-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225696E+11 | 114414.65 | 23-NOV-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.696791E+11 | 175214.09 | 31-DEC-21:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343110E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113897E+12 | 201647.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.308884E+09 | 0.281628E+09 | 4909.43 | 07-APR-16:00 | 4589.11 | 0.00 |
May | 0.00 | 0.00 | 0.216649E+10 | 0.190737E+10 | 21816.91 | 30-MAY-00:02 | 17807.62 | 0.00 |
June | 0.00 | 0.00 | 0.992323E+10 | 0.760188E+10 | 25516.54 | 19-JUN-00:01 | 14138.46 | 0.00 |
July | 0.00 | 0.00 | 0.150893E+11 | 0.108546E+11 | 26062.33 | 31-JUL-00:01 | 13956.91 | 0.00 |
August | 0.00 | 0.00 | 0.151934E+11 | 0.117956E+11 | 24676.30 | 28-AUG-00:01 | 15613.86 | 0.00 |
September | 0.00 | 0.00 | 0.779277E+10 | 0.626222E+10 | 23773.71 | 13-SEP-17:10 | 14162.32 | 0.00 |
October | 0.00 | 0.00 | 0.219942E+10 | 0.169339E+10 | 11622.39 | 04-OCT-17:15 | 8513.01 | 0.00 |
November | 0.00 | 0.00 | 15285758.54 | 14143068.34 | 1158.13 | 04-NOV-13:40 | 1065.54 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.526888E+11 | 0.404109E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.151934E+11 | 0.117956E+11 | 26062.33 | 17807.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.121849E+10 | 0.102332E+10 | 25580.74 | 31-MAY-14:00 | 19758.28 | 0.00 |
June | 0.00 | 0.00 | 0.140604E+11 | 0.102119E+11 | 73109.12 | 25-JUN-13:33 | 41477.05 | 0.00 |
July | 0.00 | 0.00 | 0.306336E+11 | 0.206554E+11 | 73939.03 | 30-JUL-11:33 | 41273.05 | 0.00 |
August | 0.00 | 0.00 | 0.307425E+11 | 0.225137E+11 | 73474.28 | 03-AUG-17:08 | 40625.61 | 0.00 |
September | 0.00 | 0.00 | 0.830847E+10 | 0.634936E+10 | 65045.92 | 04-SEP-12:03 | 52915.85 | 0.00 |
October | 0.00 | 0.00 | 0.299199E+09 | 0.209783E+09 | 10986.42 | 04-OCT-14:00 | 8043.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.852626E+11 | 0.609634E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307425E+11 | 0.225137E+11 | 73939.03 | 52915.85 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106126E+10 | 0.06 | 501.04 | 01-JAN-00:01 | 0.08 |
February | 0.985260E+09 | 0.06 | 501.04 | 01-FEB-00:02 | 0.08 |
March | 0.471902E+09 | 0.03 | 501.04 | 01-MAR-00:03 | 0.08 |
April | 41365650.11 | 0.00 | 501.04 | 01-APR-05:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.354785E+09 | 0.02 | 501.04 | 18-NOV-03:50 | 0.08 |
December | 0.105093E+10 | 0.06 | 501.04 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.396550E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106126E+10 | 0.06 | 501.04 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131508E+10 | 0.57 | 1206.71 | 12-JAN-15:10 | 0.94 |
February | 0.121609E+10 | 0.59 | 1206.71 | 01-FEB-11:30 | 0.94 |
March | 0.134186E+10 | 0.44 | 1206.71 | 01-MAR-16:20 | 0.94 |
April | 0.121928E+10 | 0.38 | 1206.71 | 03-APR-10:50 | 0.94 |
May | 0.125855E+10 | 0.38 | 1206.71 | 26-MAY-08:15 | 0.93 |
June | 0.138074E+10 | 0.56 | 1206.71 | 06-JUN-09:50 | 0.92 |
July | 0.145407E+10 | 0.64 | 1206.71 | 01-JUL-06:10 | 0.92 |
August | 0.155623E+10 | 0.69 | 1206.71 | 01-AUG-06:05 | 0.93 |
September | 0.130396E+10 | 0.51 | 1206.71 | 01-SEP-06:20 | 0.92 |
October | 0.120295E+10 | 0.36 | 1206.71 | 02-OCT-06:10 | 0.93 |
November | 0.118772E+10 | 0.40 | 1206.71 | 03-NOV-07:20 | 0.93 |
December | 0.125347E+10 | 0.43 | 1206.71 | 23-DEC-11:50 | 0.93 |
Annual Sum or Average | 0.156900E+11 | 0.50 | |||
Minimum of Months | 0.118772E+10 | 0.36 | 1206.71 | 0.92 | |
Maximum of Months | 0.155623E+10 | 0.69 | 1206.71 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.412110E+10 | 0.79 | 2797.63 | 06-JAN-10:10 | 0.90 |
February | 0.378449E+10 | 0.78 | 2797.63 | 02-FEB-16:50 | 0.90 |
March | 0.366509E+10 | 0.73 | 2797.63 | 02-MAR-07:05 | 0.90 |
April | 0.296725E+10 | 0.51 | 2797.63 | 01-APR-06:20 | 0.90 |
May | 0.288366E+10 | 0.35 | 2797.63 | 01-MAY-06:10 | 0.90 |
June | 0.294888E+10 | 0.39 | 2797.63 | 30-JUN-11:30 | 0.89 |
July | 0.300334E+10 | 0.43 | 2797.63 | 01-JUL-07:20 | 0.88 |
August | 0.319276E+10 | 0.45 | 2797.63 | 15-AUG-06:10 | 0.88 |
September | 0.281125E+10 | 0.37 | 2797.63 | 08-SEP-08:20 | 0.88 |
October | 0.277237E+10 | 0.33 | 2797.63 | 03-OCT-13:10 | 0.89 |
November | 0.320913E+10 | 0.64 | 2797.63 | 25-NOV-09:20 | 0.90 |
December | 0.379713E+10 | 0.78 | 2797.63 | 02-DEC-09:40 | 0.90 |
Annual Sum or Average | 0.391564E+11 | 0.54 | |||
Minimum of Months | 0.277237E+10 | 0.33 | 2797.63 | 0.88 | |
Maximum of Months | 0.412110E+10 | 0.79 | 2797.63 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.54 | 0.00 |
February | 3.07 | 0.00 |
March | 2.52 | 0.05 |
April | 1.28 | 0.44 |
May | 0.50 | 3.30 |
June | 0.08 | 5.00 |
July | 0.20 | 0.00 |
August | 0.00 | 0.00 |
September | 1.10 | 3.74 |
October | 1.14 | 2.69 |
November | 2.15 | 0.25 |
December | 3.27 | 0.01 |
Annual Sum or Average | 17.87 | 0.59 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.27 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.35 | 0.00 |
February | 0.82 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 1.29 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.82 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 1.33 | 0.00 |
July | 4.89 | 0.00 |
August | 4.57 | 0.00 |
September | 0.56 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.35 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.89 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131508E+10 | 0.141301E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121609E+10 | 0.139300E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134186E+10 | 0.901169E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.130383E+10 | 0.372468E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.184623E+10 | 0.518187E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.404153E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.549758E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.568773E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.338214E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178843E+10 | 0.638912E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119194E+10 | 0.618753E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125347E+10 | 0.108028E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.298659E+11 | 0.589440E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119194E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.568773E+10 | 0.141301E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.412110E+10 | 0.728647E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.378449E+10 | 0.679856E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.366509E+10 | 0.344054E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.296725E+10 | 0.953180E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.324269E+10 | 18899338.68 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.699253E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.117278E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.120621E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518504E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.285754E+10 | 0.206394E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.320913E+10 | 0.273956E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.379713E+10 | 0.557371E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.636119E+11 | 0.268146E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.285754E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.120621E+11 | 0.728647E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131508E+10 | 0.00 | 0.987773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121609E+10 | 0.00 | 0.978451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134186E+10 | 0.00 | 0.624199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121928E+10 | 0.308884E+09 | 0.255171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125855E+10 | 0.216649E+10 | 0.351626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138074E+10 | 0.992323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145407E+10 | 0.150893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155623E+10 | 0.151934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130396E+10 | 0.779277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120295E+10 | 0.219942E+10 | 0.432860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118772E+10 | 15285758.54 | 0.426568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125347E+10 | 0.00 | 0.747824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156900E+11 | 0.526888E+11 | 0.409843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155623E+10 | 0.151934E+11 | 0.987773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.412110E+10 | 0.00 | 0.517326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378449E+10 | 0.00 | 0.483457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366509E+10 | 0.00 | 0.237368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296725E+10 | 0.00 | 0.646095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288366E+10 | 0.121849E+10 | 12286986.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294888E+10 | 0.140604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300334E+10 | 0.306336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319276E+10 | 0.307425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281125E+10 | 0.830847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277237E+10 | 0.299199E+09 | 0.134325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320913E+10 | 0.00 | 0.189603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379713E+10 | 0.00 | 0.387699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391564E+11 | 0.852626E+11 | 0.188153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412110E+10 | 0.307425E+11 | 0.517326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121928E+10 | 0.00 | 0.00 | 0.00 | 84546954.84 | 0.00 | 0.372468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125855E+10 | 0.00 | 0.00 | 0.00 | 0.587680E+09 | 0.00 | 0.518187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138074E+10 | 0.00 | 0.00 | 0.00 | 0.266080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145407E+10 | 0.00 | 0.00 | 0.00 | 0.404351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155623E+10 | 0.00 | 0.00 | 0.00 | 0.413150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130396E+10 | 0.00 | 0.00 | 0.00 | 0.207819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120295E+10 | 0.00 | 0.00 | 0.00 | 0.585484E+09 | 0.00 | 0.638912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118772E+10 | 0.00 | 0.00 | 0.00 | 4224793.89 | 0.00 | 0.618753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156900E+11 | 0.00 | 0.00 | 0.00 | 0.141759E+11 | 0.00 | 0.589440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155623E+10 | 0.00 | 0.00 | 0.00 | 0.413150E+10 | 0.00 | 0.141301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.412110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288366E+10 | 0.00 | 0.00 | 0.00 | 0.359030E+09 | 0.00 | 18899338.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294888E+10 | 0.00 | 0.00 | 0.00 | 0.404365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300334E+10 | 0.00 | 0.00 | 0.00 | 0.872442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319276E+10 | 0.00 | 0.00 | 0.00 | 0.886937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281125E+10 | 0.00 | 0.00 | 0.00 | 0.237379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277237E+10 | 0.00 | 0.00 | 0.00 | 85166043.52 | 0.00 | 0.206394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391564E+11 | 0.00 | 0.00 | 0.00 | 0.244554E+11 | 0.00 | 0.268146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.277237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412110E+10 | 0.00 | 0.00 | 0.00 | 0.886937E+10 | 0.00 | 0.728647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 399115.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301993E+10 | 0.00 | 5525.97 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299371E+10 | 0.00 | 0.00 | 0.18 |
March | 0.155912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229176E+10 | 0.00 | 0.00 | 0.18 |
April | 0.401856E+09 | 7522150.04 | 0.00 | 221235.00 | 0.00 | 0.104425E+10 | 85034406.04 | 0.00 | 0.17 |
May | 0.383857E+09 | 69093166.45 | 0.00 | 2000964.43 | 53270.12 | 0.123567E+09 | 0.412969E+09 | 0.00 | 0.17 |
June | 24805277.05 | 0.103921E+10 | 0.00 | 2546680.10 | 2957689.35 | 0.00 | 97313001.26 | 0.00 | 0.19 |
July | 0.00 | 0.252021E+10 | 0.00 | 859068.57 | 1772408.95 | 0.00 | 778553.79 | 0.00 | 0.19 |
August | 1781111.77 | 0.215575E+10 | 0.00 | 2182670.54 | 1284554.46 | 0.00 | 32717783.82 | 0.00 | 0.21 |
September | 70631688.97 | 0.627073E+09 | 0.00 | 3669019.37 | 1000895.55 | 0.00 | 0.305401E+09 | 0.00 | 0.18 |
October | 0.461797E+09 | 75368543.64 | 0.00 | 1383423.07 | 5159.04 | 0.173916E+09 | 0.317683E+09 | 0.00 | 0.16 |
November | 0.289658E+09 | 0.00 | 0.00 | 16006.66 | 0.00 | 0.162775E+10 | 19354898.47 | 0.00 | 0.16 |
December | 435387.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268982E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.179113E+10 | 0.649423E+10 | 0.00 | 12879067.74 | 7073977.46 | 0.139647E+11 | 0.127125E+10 | 5525.97 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.461797E+09 | 0.252021E+10 | 0.00 | 3669019.37 | 2957689.35 | 0.301993E+10 | 0.412969E+09 | 5525.97 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783558E+10 | 0.00 | 0.00 | 0.23 |
February | 0.960481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784312E+10 | 0.00 | 0.00 | 0.23 |
March | 0.219874E+10 | 0.00 | 0.00 | 0.00 | 8684420.98 | 0.339865E+10 | 0.00 | 0.00 | 0.20 |
April | 0.219161E+10 | 0.00 | 0.00 | 0.00 | 14389348.02 | 0.849497E+09 | 0.00 | 0.00 | 0.17 |
May | 0.223962E+10 | 0.109048E+09 | 0.00 | 94480.42 | 107091.78 | 4384166.89 | 28777975.76 | 0.00 | 0.17 |
June | 0.633923E+09 | 0.119028E+10 | 0.00 | 2665812.38 | 7084850.34 | 0.00 | 0.405608E+09 | 0.00 | 0.18 |
July | 59453194.33 | 0.399101E+10 | 0.00 | 1059752.00 | 0.00 | 0.00 | 92237807.82 | 0.00 | 0.18 |
August | 0.184281E+09 | 0.370689E+10 | 0.00 | 4398141.82 | 833944.74 | 0.00 | 0.181331E+09 | 0.00 | 0.19 |
September | 0.116892E+10 | 0.601284E+09 | 0.00 | 3319311.00 | 0.00 | 0.00 | 0.504182E+09 | 0.00 | 0.17 |
October | 0.235580E+10 | 6687374.34 | 0.00 | 107550.93 | 60629.01 | 61490935.69 | 21249214.76 | 0.00 | 0.16 |
November | 0.164033E+10 | 0.00 | 0.00 | 0.00 | 565166.90 | 0.269951E+10 | 0.00 | 14508.69 | 0.19 |
December | 0.899113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594143E+10 | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.153734E+11 | 0.960520E+10 | 0.00 | 11645048.55 | 31725451.76 | 0.286337E+11 | 0.123339E+10 | 14508.69 | 0.19 |
Minimum of Months | 59453194.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.235580E+10 | 0.399101E+10 | 0.00 | 4398141.82 | 14389348.02 | 0.784312E+10 | 0.504182E+09 | 14508.69 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |