Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 960.49 | 198.65 | 198.65 |
Net Site Energy | 960.49 | 198.65 | 198.65 |
Total Source Energy | 2961.93 | 612.59 | 612.59 |
Net Source Energy | 2961.93 | 612.59 | 612.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 80.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.96 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 922.11 | 38.38 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 67.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.96 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.67 | 7.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 190.71 | 7.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.67 | 7.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 190.71 | 7.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 922.111 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 922.111 | 100.00 |
Total On-Site and Utility Electric Sources | 922.111 | 100.00 |
Total Electricity End Uses | 922.111 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 23.00 |
Time Setpoint Not Met During Occupied Cooling | 15.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 845.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 28-JAN-06:10 | - | - | - | 25-SEP-11:30 |
Heating | 0.00 | 86606.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21647.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7610.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1710.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 76701.62 | 86606.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 86606.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21647.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5305.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1710.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 41.61 | 0.00 | 0.00 | 0.00 |
Cooling | 226.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2920.33 | 41.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.61 | 0.00 | 0.00 | 0.00 |
Cooling | 46.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 52.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 603.98 | 8.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.61 | 0.00 | 0.00 | 0.00 |
Cooling | 46.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 52.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 603.98 | 8.61 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.30 |
ZONE2 FINE STORAGE DIRECT AIR | 3.49 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.56 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.56 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 92120.51 |
PSZ-OFFICE HEATING COIL | 28764.89 |
PSZ-FINE STORAGE HEATING COIL | 98730.60 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 92120.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-FINE STORAGE | 3.49 | 3.49 | 3.49 | 3.49 | 3.49 | 3.49 | 1.00 | 1.000000 | 3.49 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.30 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 3.49 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 21611.88 | 28764.89 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.49 | 3.49 | 3.49 | 3.49 | 72435.13 | 98730.60 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.30 | 0.652420 | 1.30 | 21599.74 | 21611.88 | 10805.94 | 21611.88 | 0.798449 | 0.798450 | 0.798450 | 0.798450 |
PSZ-FINE STORAGE COOLING COIL | 3.49 | 1.74 | 3.49 | 65943.10 | 72435.13 | 36217.57 | 72435.13 | 0.724089 | 0.724090 | 0.724090 | 0.724090 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.30 | 1487.66 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.49 | 3817.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 28 | 1 | VerySmooth | 3.582 | 0.253 | 0.153 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.39 | 29 | 1 | VerySmooth | 5.779 | 0.390 | 0.223 | 0.391 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15304 | 0.57918 | 0.57918 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.81224E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11463.30854 | 13755.97025 | 1.08736 | 1.30484 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28000 | 6.82376E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9379.98402 | 11255.98083 | 0.30359 | 0.36431 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 39315.74267 | 47178.89121 | 2.90693 | 3.48832 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.82375E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 30874.62862 | 37049.55435 | 0.84174 | 1.01009 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10000 | 6.82375E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 76767.09014 | 92120.50817 | 2.13109 | 2.55731 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17629.99 | 1.30484 | 1.30484 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10062.12 | 0.36431 | 0.36431 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 58893.79 | 3.48832 | 3.48832 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 35161.04 | 1.01009 | 1.01009 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30484 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.48832 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.55731 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.55731 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 92120.51154 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 92120.50817 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30484 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30484 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30484 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30484 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30484 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.30484 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.48832 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.48832 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.48832 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.48832 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.48832 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.48832 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.30484 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.48832 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30484 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30484 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30484 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30484 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30484 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30484 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65242 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30484 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21599.73514 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21611.88000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10805.94000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21611.88000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79845 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79845 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79845 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79845 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21611.88000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28764.89263 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30484 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1487.65613 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28764.89263 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.48832 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.48832 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.48832 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.48832 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.48832 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.48832 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.74416 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.48832 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 65943.10115 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 72435.13000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 36217.56500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 72435.13000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72409 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72409 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72409 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72409 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 72435.13000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 98730.59570 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.48832 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3817.98571 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 98730.59570 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20599.4 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 69726.0 | 12.59 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.8194880962E-002 | 3.3790791839E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1408163261 | 0.1467967910 | Pass | Pass | 0.1316071473 | 0.7545334661 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.4994626576E-002 | 5.5079881512E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.037 | 0.450 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 3.582 | 0.253 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.244 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.77 | 83.77 | 123.55 | |
Exterior Lighting Total | 7857.24 | 123.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21611.88 | 17256.01 | 4355.87 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 72435.13 | 52449.55 | 19985.58 | 0.72 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20599.4 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 69726.0 | 12.59 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 92120.51 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28764.89 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 98730.60 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.56 | 237.60 | 92.91 | 1.00 | 3.44 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.30 | 1487.66 | 1140.11 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.49 | 3817.99 | 1094.51 | 1.00 | 1.22 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11463.31 | 13755.97 | 58.07 | 1.087 | 1.305 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00807 | 36.28 | 0.00682 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 39315.74 | 47178.89 | 33.86 | 2.907 | 3.488 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00792 | 38.10 | 0.00682 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00436 | 38.10 | 0.00682 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9379.98 | 11255.98 | 47.52 | 0.304 | 0.364 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00776 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30874.63 | 37049.55 | 26.59 | 0.842 | 1.010 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00651 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 76767.09 | 92120.51 | 28.74 | 2.131 | 2.557 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 9.99 | 0.00881 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.30 | 1.30 | 0.36 | 0.36 | 1.3048 | 1.3048 | 1.3048 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.49 | 3.49 | 1.01 | 1.01 | 3.4883 | 3.4883 | 3.4883 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 92120.512 | 92120.512 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 92120.51 | 92120.51 | 2.557306 | 4.19 | 4.19 | 0.00651861 | 43.33 | 25.24 | 0.01600000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 9.99 | 0.00881178 | 100.0000 | 92120.51 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21611.880 | 0.000 | 1.304840 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21611.88 | 21611.88 | 1.304840 | 24.88 | 14.77 | 0.00797175 | 12.00 | 10.00 | 0.00800000 | 36.45 | 0.00682375 | 17.60 | 7.8389 | 23.90 | 0.00806873 | 37.9230 | 11455.07 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28764.893 | 28764.893 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28764.89 | 28764.89 | 1.304836 | 13.68 | 9.05 | 0.00637210 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.8389 | 21.10 | 0.00776325 | 43.2775 | 9379.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 72435.130 | 0.000 | 3.488320 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 72435.13 | 72435.13 | 3.488320 | 28.09 | 15.70 | 0.00778482 | 12.00 | 10.00 | 0.00800000 | 38.10 | 0.00682375 | 18.10 | 12.1753 | 26.70 | 0.00791806 | 31.5119 | 39315.74 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 98730.596 | 98730.596 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 98730.60 | 98730.60 | 3.488320 | 6.83 | 4.35 | 0.00495481 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 12.1753 | 15.56 | 0.00651211 | 51.5117 | 30874.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 92120.512 | 92120.512 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0443 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.557306 | 2.67067602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 92120.51 | 92120.51 | 1.0000 | 2.67067602 | 2.557306 | 4.19 | 4.19 | 0.00651861 | 20563.3 | 43.33 | 25.24 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92120.51 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 9.99 | 0.00881178 | 9.99 | 0.00881178 | 100.0000 | 92120.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21611.880 | 0.000 | 1.304840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6591 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21611.88 | 21611.88 | 1.0000 | 1.36268582 | 1.304840 | 24.88 | 14.77 | 0.00797175 | 45310.5 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21611.88 | 36.45 | 0.00682375 | 17.60 | 0.10228487 | 7.8389 | 23.90 | 0.00806947 | 23.90 | 0.00806873 | 37.9230 | 11455.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28764.893 | 28764.893 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.304836 | 1.36268137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28764.89 | 28764.89 | 1.0000 | 1.36268137 | 1.304836 | 13.68 | 9.05 | 0.00637210 | 29845.0 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28764.89 | -5.20 | 0.00280840 | -5.20 | 0.10228487 | 7.8389 | 21.05 | 0.00776325 | 21.10 | 0.00776325 | 43.2775 | 9379.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 72435.130 | 0.000 | 3.488320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 72435.13 | 72435.13 | 1.0000 | 3.64296327 | 3.488320 | 28.09 | 15.70 | 0.00778482 | 48100.1 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72435.13 | 38.10 | 0.00682375 | 18.10 | 0.42471267 | 12.1753 | 26.70 | 0.00791806 | 26.70 | 0.00791806 | 31.5119 | 39315.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98730.596 | 98730.596 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.488320 | 3.64296356 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 98730.60 | 98730.60 | 1.0000 | 3.64296356 | 3.488320 | 6.83 | 4.35 | 0.00495481 | 19316.6 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98730.60 | -5.20 | 0.00280840 | -5.20 | 0.42471267 | 12.1753 | 15.56 | 0.00651211 | 15.56 | 0.00651211 | 51.5117 | 30874.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.30 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 3.49 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2242.83 | 1892.67 | 845.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2242.83 | 1892.67 | 845.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 23.00 | 18.50 | 23.00 | 15.50 |
ZONE2 FINE STORAGE | 90.17 | 149.50 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 109.00 | 168.00 | 23.00 | 15.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.958 | 0.261 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 922.11 | 5475.32 | 01-JAN-07:40 | 76701.62 | 15-JUN-15:00 |
Electricity:Building | 634.31 | 4992.32 | 01-JAN-00:10 | 48037.94 | 19-APR-13:40 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 434.71 | 2759.73 | 01-JAN-00:10 | 33963.13 | 19-APR-13:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.96 | 483.00 | 04-JAN-06:10 | 2052.83 | 27-JAN-12:10 |
WaterSystems:Electricity | 24.96 | 483.00 | 04-JAN-06:10 | 2052.83 | 27-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 24.96 | 483.00 | 04-JAN-06:10 | 2052.83 | 27-JAN-12:10 |
Fans:Electricity | 80.75 | 0.00 | 01-JAN-00:10 | 7610.94 | 05-JUL-10:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.06 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-SEP-17:40 |
Ventilation (simple):Fans:Electricity | 13.06 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-SEP-17:40 |
ElectricityPurchased:Facility | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
ElectricityNet:Plant | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 922.11 | 5475.32 | 30-APR-10:10 | 76701.62 | 15-JUN-15:00 |
Electricity:HVAC | 139.29 | 0.00 | 01-JAN-00:10 | 29061.67 | 15-JUN-15:10 |
General:Fans:Electricity | 67.68 | 0.00 | 01-JAN-00:10 | 5543.24 | 26-DEC-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 71.61 | 0.00 | 01-JAN-00:10 | 23756.03 | 15-JUN-15:10 |
ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 38.38 | 0.00 | 01-JAN-00:10 | 86606.73 | 28-JAN-06:10 |
Gas:HVAC | 38.38 | 0.00 | 01-JAN-00:10 | 86606.73 | 28-JAN-06:10 |
Heating:Gas | 38.38 | 0.00 | 01-JAN-00:10 | 86606.73 | 28-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 484.58 | 0.00 | 01-JAN-00:10 | 131290.47 | 28-JAN-06:10 |
EnergyTransfer:Building | 226.38 | 0.00 | 01-JAN-00:10 | 66173.54 | 28-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 56.95 | 0.00 | 01-JAN-00:10 | 15750.12 | 27-DEC-06:10 |
Heating:EnergyTransfer | 34.62 | 0.00 | 01-JAN-00:10 | 66173.54 | 28-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 7.32 | 0.00 | 01-JAN-00:10 | 15750.12 | 27-DEC-06:10 |
Cooling:EnergyTransfer | 191.76 | 0.00 | 01-JAN-00:10 | 54249.05 | 15-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 49.63 | 0.00 | 01-JAN-00:10 | 13318.30 | 03-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 167.63 | 0.00 | 01-JAN-00:10 | 43462.23 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.51 | 0.00 | 01-JAN-00:10 | 31779.34 | 09-FEB-01:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.13 | 0.00 | 01-JAN-00:10 | 43462.23 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1.79 | 0.00 | 01-JAN-00:10 | 36482.29 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1.79 | 0.00 | 01-JAN-00:10 | 36482.29 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 258.21 | 0.00 | 01-JAN-00:10 | 66273.45 | 15-JUN-15:10 |
HeatingCoils:EnergyTransfer | 26.09 | 0.00 | 01-JAN-00:10 | 65116.93 | 28-JAN-06:10 |
CoolingCoils:EnergyTransfer | 232.12 | 0.00 | 01-JAN-00:10 | 66273.45 | 15-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 7.321 | -49.630 | 0.000 | 0.000 | 3.714 | 30.994 | 31.946 | 10.861 | 0.000 | 2.088 | 0.000 | 0.000 | -8.815 | 0.000 | -9.192 | -19.288 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 25.506 | -142.119 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 10.739 | 35.939 | 0.000 | 0.000 | 0.000 | -66.722 | -0.004 |
ZONE3 BULK STORAGE | 1.793 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 51.248 | 0.000 | 13.158 | 33.159 | 0.000 | -20.545 | 0.000 | -500.459 | -0.013 |
Total Facility | 1.793 | 0.000 | 32.827 | -191.749 | 0.000 | 0.000 | 3.714 | 481.960 | 139.282 | 62.109 | 0.000 | 25.984 | 69.099 | 0.000 | -29.360 | 0.000 | -576.373 | -19.304 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-MAY-05:01 | 0.00 | 0.00 | 0.00 | -29288.09 | 0.00 | 0.00 | 31.43 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 29095.01 | 0.00 | -677.80 | 0.00 | -320.73 | 0.00 |
ZONE2 FINE STORAGE | 11-SEP-19:11 | 0.00 | 0.00 | 0.00 | -70836.66 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 70322.86 | 0.00 | -0.00 | 0.00 | -686.08 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 | -82554.09 | 0.00 | 0.00 | 23.12 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 85023.94 | 0.00 | -1105.42 | 0.00 | -8557.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-DEC-06:12 | 0.00 | 0.00 | 29221.53 | 0.00 | 0.00 | 0.00 | 46.49 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1043.19 | 0.00 | -1122.78 | -28262.25 |
ZONE2 FINE STORAGE | 31-DEC-06:42 | 0.00 | 0.00 | 99735.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10484.58 | -90450.72 |
ZONE3 BULK STORAGE | 31-DEC-07:00 | 36482.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1741.72 | 0.00 | -31874.12 | -5626.09 |
Total Facility | 30-DEC-06:01 | 24737.30 | 0.00 | 128142.95 | 0.00 | 0.00 | 0.00 | 57.41 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2681.02 | 0.00 | -28254.67 | -129171.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3048 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3048 | 0.0784 | 1.0000 | 0.1023 | 0.0784 | ||
PSZ-FINE STORAGE | 3.4883 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.4883 | 0.1218 | 1.0000 | 0.4247 | 0.1218 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3048 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3048 | 1.0000 | 1.0000 | 0.1023 | 0.0784 | ||
PSZ-FINE STORAGE | 3.4883 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.4883 | 1.0000 | 1.0000 | 0.4247 | 0.1218 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3048 | 1.3048 | 1.3048 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.4883 | 3.4883 | 3.4883 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3048 | 1.3048 | 1.3048 | 1.3048 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4883 | 3.4883 | 3.4883 | 3.4883 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3048 | 1.3048 | 1.3048 | 0.1023 | 0.2808 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.4883 | 3.4883 | 3.4883 | 0.4247 | 0.4205 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3048 | 1.3048 | 1.3048 | 1.3048 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4883 | 3.4883 | 3.4883 | 3.4883 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 23.00 |
Number of hours cooling loads not met | 15.50 |
Number of hours not met | 38.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 38.38 | 86606.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 71.61 | 23756.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.55 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.06 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.68 | 5543.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.96 | 2052.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 922.11 |
Natural Gas | 0.00 | 38.38 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 960.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 14.81 |
Fans (All) | 16.70 |
Service Water Heating | 5.16 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 190.71 |
Subtotal | 190.71 |
Natural Gas [MJ/m2] | |
Space Heating | 7.94 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 7.94 |
Subtotal | 7.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 50.18 |
Space Heating | 4.00 |
Space Cooling | 7.46 |
Fans (All) | 8.41 |
Service Water Heating | 2.60 |
Receptacle Equipment | 14.50 |
Miscellaneous | 12.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118032E+11 |
February | 0.000 | 0.643292E+10 |
March | 0.000 | 0.198284E+10 |
April | 0.000 | 0.283779E+08 |
May | 0.000 | 2144095.117 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.193617E+10 |
December | 0.000 | 0.161967E+11 |
Annual Sum or Average | 0.383824E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.161967E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16371503.25 | 1269.88 | 12-JAN-15:40 | 18.90 | 10.10 | 0.210374E+09 | 301.59 | 03-JAN-16:00 | 20.60 | 6.82 |
February | 0.117189E+09 | 2321.14 | 21-FEB-16:50 | 22.30 | 7.83 | 0.201331E+09 | 301.59 | 23-FEB-15:30 | 20.00 | 7.11 |
March | 0.723042E+09 | 3935.05 | 16-MAR-15:50 | 22.30 | 8.40 | 0.250863E+09 | 301.59 | 18-MAR-15:09 | 20.68 | 8.59 |
April | 0.343136E+10 | 25582.29 | 28-APR-05:03 | 14.22 | 8.84 | 0.247405E+09 | 301.61 | 25-APR-14:00 | 22.20 | 12.41 |
May | 0.648887E+10 | 29288.98 | 17-MAY-05:01 | 14.08 | 5.17 | 0.258815E+09 | 301.62 | 19-MAY-07:40 | 23.17 | 14.68 |
June | 0.860015E+10 | 28718.84 | 13-JUN-05:01 | 15.18 | 4.56 | 0.258947E+09 | 301.61 | 29-JUN-07:30 | 18.05 | 15.49 |
July | 0.854987E+10 | 22462.93 | 11-JUL-05:01 | 21.70 | 15.04 | 0.249080E+09 | 301.69 | 08-JUL-14:50 | 22.25 | 19.21 |
August | 0.878023E+10 | 24934.90 | 23-AUG-05:01 | 20.00 | 11.76 | 0.268946E+09 | 301.64 | 24-AUG-07:30 | 23.05 | 16.43 |
September | 0.740268E+10 | 29046.92 | 30-SEP-05:02 | 9.72 | 6.49 | 0.249021E+09 | 301.67 | 23-SEP-15:50 | 20.88 | 18.63 |
October | 0.445203E+10 | 26828.49 | 20-OCT-05:03 | 11.60 | 7.27 | 0.248670E+09 | 301.62 | 23-OCT-10:00 | 22.20 | 14.27 |
November | 0.105736E+10 | 5064.92 | 03-NOV-16:00 | 23.90 | 13.43 | 0.225693E+09 | 301.59 | 03-NOV-12:00 | 21.70 | 13.54 |
December | 11905480.50 | 985.62 | 16-DEC-16:00 | 15.00 | 4.15 | 0.210644E+09 | 301.59 | 15-DEC-16:30 | 15.30 | 5.98 |
Annual Sum or Average | 0.496311E+11 | 0.287979E+10 | ||||||||
Minimum of Months | 11905480.50 | 985.62 | 9.72 | 4.15 | 0.201331E+09 | 301.59 | 15.30 | 5.98 | ||
Maximum of Months | 0.878023E+10 | 29288.98 | 23.90 | 15.04 | 0.268946E+09 | 301.69 | 23.17 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384693E+09 | 2820.44 | 27-JAN-10:20 | 2.03 | -3.3 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.311609E+09 | 6680.22 | 21-FEB-07:10 | 4.68 | -0.0 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.335835E+09 | 7624.89 | 20-MAR-06:10 | 8.40 | 3.26 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.488382E+10 | 66535.26 | 30-APR-10:37 | 24.07 | 13.06 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.176565E+11 | 70227.43 | 21-MAY-08:21 | 23.35 | 10.21 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.318913E+11 | 68530.24 | 11-JUN-07:41 | 23.95 | 10.04 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.313862E+11 | 63910.12 | 16-JUL-04:51 | 25.00 | 15.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.282411E+11 | 68571.18 | 23-AUG-00:51 | 24.40 | 12.20 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.201268E+11 | 70835.38 | 11-SEP-19:11 | 23.30 | 11.87 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.599490E+10 | 70806.23 | 01-OCT-09:31 | 23.67 | 13.33 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.416248E+09 | 8455.58 | 17-NOV-07:10 | 0.55 | -2.0 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.496454E+09 | 3350.56 | 19-DEC-09:30 | 1.40 | -3.7 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.142125E+12 | 0.00 | ||||||||
Minimum of Months | 0.311609E+09 | 2820.44 | 0.55 | -3.7 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.318913E+11 | 70835.38 | 25.00 | 15.00 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 | 1.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 | 11.53 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.83 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.10 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202366E+10 | 29100.79 | 06-JAN-06:01 | 0.10 |
February | 0.145931E+10 | 29158.81 | 02-FEB-06:12 | -3.7 |
March | 0.880009E+09 | 29107.39 | 02-MAR-06:01 | -3.5 |
April | 0.112146E+09 | 13329.08 | 01-APR-05:03 | 11.10 |
May | 21100341.11 | 2757.29 | 19-MAY-06:05 | 20.28 |
June | 4798234.71 | 2828.77 | 01-JUN-06:05 | 19.37 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 2209718.46 | 2436.50 | 25-AUG-06:05 | 19.18 |
September | 397565.06 | 594.07 | 25-SEP-06:02 | 10.55 |
October | 68332208.57 | 1920.44 | 23-OCT-06:03 | 12.80 |
November | 0.662469E+09 | 29096.00 | 28-NOV-06:01 | 1.02 |
December | 0.208677E+10 | 29221.56 | 27-DEC-06:12 | -3.7 |
Annual Sum or Average | 0.732120E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.208677E+10 | 29221.56 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.701690E+10 | 99683.27 | 28-JAN-05:22 | -3.0 |
February | 0.432033E+10 | 99055.52 | 17-FEB-06:01 | 1.52 |
March | 0.214564E+10 | 99080.35 | 01-MAR-06:01 | 1.60 |
April | 0.544928E+09 | 3996.10 | 01-APR-13:10 | 27.88 |
May | 0.250766E+09 | 3700.04 | 01-MAY-07:00 | 15.00 |
June | 36368902.11 | 3548.08 | 01-JUN-06:12 | 19.83 |
July | 8594199.31 | 3370.80 | 05-JUL-06:15 | 18.33 |
August | 70099440.04 | 3956.01 | 05-AUG-06:05 | 23.98 |
September | 0.171105E+09 | 3583.21 | 30-SEP-06:10 | 8.95 |
October | 0.347881E+09 | 4062.63 | 13-OCT-07:00 | 14.40 |
November | 0.181729E+10 | 99027.38 | 28-NOV-06:01 | 1.02 |
December | 0.877638E+10 | 99735.59 | 31-DEC-06:42 | -2.8 |
Annual Sum or Average | 0.255063E+11 | |||
Minimum of Months | 8594199.31 | 3370.80 | -3.0 | |
Maximum of Months | 0.877638E+10 | 99735.59 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247537E+09 | 24375.59 | 28-JAN-06:00 | -3.3 |
February | 92478931.20 | 12336.57 | 02-FEB-06:54 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.145290E+10 | 36482.29 | 31-DEC-07:00 | -2.8 |
Annual Sum or Average | 0.179292E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.145290E+10 | 36482.29 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147232E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 631996.59 | 0.124846E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1857920.80 | 0.126709E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121589E+09 | 0.718049E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301623E+09 | 0.391754E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571992E+09 | 0.156919E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437784E+09 | 0.128379E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373510E+09 | 0.194590E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226051E+09 | 0.255297E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52551754.17 | 0.706914E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120368E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144806E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.208759E+10 | 0.919151E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128379E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571992E+09 | 0.147232E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907252E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17051392.03 | 0.791014E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61640.84 | 0.873332E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492596E+09 | 0.651715E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166458E+10 | 0.426710E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345210E+10 | 0.167604E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248790E+10 | 0.138853E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195397E+10 | 0.193122E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529673E+09 | 0.226374E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141176E+09 | 0.644531E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835943E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815767E+10 |
Annual Sum or Average | 0.136656E+12 | 0.107391E+11 | 0.667222E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138853E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345210E+10 | 0.907252E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76899927.77 | 0.208941E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687083E+09 | 0.191214E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400129E+09 | 0.244810E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918840E+09 | 0.226604E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79743888.69 | 0.209172E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174941E+09 | 0.109809E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86167844.49 | 0.976045E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37755158.06 | 0.113294E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963837.22 | 0.112362E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12846900.05 | 0.237982E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9888912.59 | 0.243291E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44738944.22 | 0.179878E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.253000E+10 | 0.217496E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963837.22 | 0.976045E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918840E+09 | 0.244810E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6070.57 | 27-JAN-07:03 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 19-FEB-14:00 | 5764.69 | 02-FEB-07:03 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.72 | 21-MAR-16:10 | 5214.20 | 02-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.24 | 21-APR-16:10 | 3720.17 | 12-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2649.03 | 19-MAY-17:00 | 3202.92 | 02-MAY-06:02 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3468.25 | 05-JUN-17:00 | 1447.20 | 29-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3333.96 | 03-JUL-17:00 | 1306.84 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2919.00 | 07-AUG-16:10 | 1550.60 | 31-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894.19 | 19-SEP-16:10 | 2829.48 | 25-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.62 | 05-OCT-16:10 | 3540.42 | 25-OCT-06:03 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4893.91 | 28-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5739.42 | 27-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.84 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3468.25 | 6070.57 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 17864.47 | 25-JAN-23:05 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.90 | 20-FEB-16:00 | 24508.83 | 08-FEB-17:55 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 03-MAR-16:00 | 20116.21 | 27-MAR-06:55 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11697.42 | 21-APR-15:10 | 23733.51 | 22-APR-07:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10100.83 | 19-MAY-17:00 | 11924.89 | 01-MAY-08:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 05-JUN-17:00 | 9669.53 | 28-JUN-02:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11467.32 | 03-JUL-17:00 | 6716.26 | 18-JUL-21:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.05 | 26-AUG-15:10 | 7893.90 | 14-AUG-01:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.33 | 18-SEP-17:00 | 7357.74 | 23-SEP-17:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4244.48 | 01-OCT-14:55 | 12291.35 | 06-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14519.62 | 10-NOV-16:03 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 20108.77 | 18-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6716.26 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 24508.83 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9659.96 | 03-JAN-17:00 | 30902.17 | 26-JAN-10:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10878.30 | 06-FEB-22:00 | 49578.50 | 09-FEB-01:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16748.67 | 03-MAR-16:00 | 52199.35 | 27-MAR-07:05 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18448.25 | 01-APR-15:00 | 71585.21 | 22-APR-07:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.95 | 14-MAY-14:53 | 43546.00 | 01-MAY-10:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.36 | 02-JUN-16:00 | 37000.72 | 28-JUN-02:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3466.16 | 02-JUL-21:53 | 27320.70 | 08-JUL-14:52 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.49 | 07-AUG-16:00 | 29684.07 | 14-AUG-01:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 10-SEP-14:45 | 21380.36 | 23-SEP-16:55 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1413.99 | 01-OCT-14:53 | 47430.20 | 06-OCT-09:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1723.23 | 23-NOV-16:00 | 38754.26 | 15-NOV-09:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3686.53 | 10-DEC-15:00 | 38749.20 | 18-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 21380.36 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18448.25 | 71585.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1269.88 | 12-JAN-15:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.96 |
February | 2321.14 | 21-FEB-16:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 |
March | 3935.05 | 16-MAR-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 |
April | 25582.29 | 28-APR-05:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.25 |
May | 29288.98 | 17-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.73 |
June | 28718.84 | 13-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.21 |
July | 22462.93 | 11-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.89 |
August | 24934.90 | 23-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.75 |
September | 29046.92 | 30-SEP-05:02 | 435.11 | 3518.66 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 |
October | 26828.49 | 20-OCT-05:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.15 |
November | 5064.92 | 03-NOV-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
December | 985.62 | 16-DEC-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 985.62 | 290.07 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | |
Maximum of Months | 29288.98 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2820.44 | 27-JAN-10:20 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.93 |
February | 6680.22 | 21-FEB-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2285.20 |
March | 7624.89 | 20-MAR-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3707.05 |
April | 66535.26 | 30-APR-10:37 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 |
May | 70227.43 | 21-MAY-08:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.57 |
June | 68530.24 | 11-JUN-07:41 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.14 |
July | 63910.12 | 16-JUL-04:51 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.39 |
August | 68571.18 | 23-AUG-00:51 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70835.38 | 11-SEP-19:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.08 |
October | 70806.23 | 01-OCT-09:31 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8455.58 | 17-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.85 |
December | 3350.56 | 19-DEC-09:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2820.44 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70835.38 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3707.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8111.32 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16224.09 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11402.18 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5229.96 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5290.90 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9452.92 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.72 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2522.76 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9397.20 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3790.22 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13232.13 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4462.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.72 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16224.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.715274E+11 | 52823.22 | 25-JAN-13:09 | 0.118032E+11 | 86606.73 | 28-JAN-06:10 |
February | 0.646889E+11 | 53490.08 | 21-FEB-15:00 | 0.643292E+10 | 61087.69 | 02-FEB-06:10 |
March | 0.734460E+11 | 54052.68 | 22-MAR-14:09 | 0.198284E+10 | 42872.91 | 02-MAR-06:10 |
April | 0.709237E+11 | 67415.87 | 21-APR-14:50 | 28377922.07 | 4617.23 | 01-APR-05:10 |
May | 0.803756E+11 | 71818.79 | 19-MAY-13:00 | 2144095.12 | 1610.72 | 27-MAY-05:49 |
June | 0.886424E+11 | 76701.62 | 15-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.887973E+11 | 75594.40 | 26-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.896274E+11 | 73738.26 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.807611E+11 | 70982.33 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.731183E+11 | 70035.42 | 03-OCT-13:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.684253E+11 | 55418.93 | 24-NOV-16:00 | 0.193617E+10 | 41476.20 | 28-NOV-06:10 |
December | 0.717776E+11 | 56544.84 | 16-DEC-16:00 | 0.161967E+11 | 86070.24 | 27-DEC-06:19 |
Annual Sum or Average | 0.922111E+12 | 0.383824E+11 | ||||
Minimum of Months | 0.646889E+11 | 52823.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.896274E+11 | 76701.62 | 0.161967E+11 | 86606.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.121347E+11 | 0.115358E+11 | 0.00 | 0.552648E+10 | 0.00 | 0.00 | 270.66 | 0.00 | 0.00 | 0.00 | 0.222706E+10 | 0.00 |
February | 0.366966E+11 | 0.103810E+11 | 0.105871E+11 | 0.00 | 0.498754E+10 | 0.00 | 0.00 | 16068073.17 | 0.00 | 0.00 | 0.00 | 0.202060E+10 | 0.00 |
March | 0.423649E+11 | 0.106686E+11 | 0.123357E+11 | 0.00 | 0.571582E+10 | 0.00 | 0.00 | 0.115647E+09 | 0.00 | 0.00 | 0.00 | 0.224542E+10 | 0.00 |
April | 0.397216E+11 | 0.949469E+10 | 0.114862E+11 | 0.00 | 0.551369E+10 | 0.00 | 0.00 | 0.262617E+10 | 0.00 | 0.00 | 0.00 | 0.208134E+10 | 0.00 |
May | 0.412341E+11 | 0.909868E+10 | 0.119357E+11 | 0.00 | 0.741298E+10 | 0.00 | 0.00 | 0.860352E+10 | 0.00 | 0.00 | 0.00 | 0.209058E+10 | 0.00 |
June | 0.408524E+11 | 0.844810E+10 | 0.118862E+11 | 0.00 | 0.959680E+10 | 0.00 | 0.00 | 0.158719E+11 | 0.00 | 0.00 | 0.00 | 0.198708E+10 | 0.00 |
July | 0.401034E+11 | 0.888654E+10 | 0.115358E+11 | 0.00 | 0.939638E+10 | 0.00 | 0.00 | 0.168933E+11 | 0.00 | 0.00 | 0.00 | 0.198199E+10 | 0.00 |
August | 0.423649E+11 | 0.949469E+10 | 0.123357E+11 | 0.00 | 0.907143E+10 | 0.00 | 0.00 | 0.143356E+11 | 0.00 | 0.00 | 0.00 | 0.202509E+10 | 0.00 |
September | 0.397216E+11 | 0.995669E+10 | 0.114862E+11 | 0.00 | 0.726552E+10 | 0.00 | 0.00 | 0.103630E+11 | 0.00 | 0.00 | 0.00 | 0.196810E+10 | 0.00 |
October | 0.401034E+11 | 0.111541E+11 | 0.115358E+11 | 0.00 | 0.554764E+10 | 0.00 | 0.00 | 0.270733E+10 | 0.00 | 0.00 | 0.00 | 0.207008E+10 | 0.00 |
November | 0.385909E+11 | 0.115171E+11 | 0.110862E+11 | 0.00 | 0.508821E+10 | 0.00 | 0.00 | 77374031.96 | 0.00 | 0.00 | 0.00 | 0.206552E+10 | 0.00 |
December | 0.401034E+11 | 0.123139E+11 | 0.115358E+11 | 0.00 | 0.562661E+10 | 0.00 | 0.00 | 638.82 | 0.00 | 0.00 | 0.00 | 0.219795E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123549E+12 | 0.139282E+12 | 0.807491E+11 | 0.00 | 0.716100E+11 | 0.249608E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.844810E+10 | 0.105871E+11 | 0.00 | 0.498754E+10 | 0.00 | 0.00 | 270.66 | 0.00 | 0.00 | 0.00 | 0.196810E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.123139E+11 | 0.123357E+11 | 0.00 | 0.959680E+10 | 0.00 | 0.00 | 0.168933E+11 | 0.00 | 0.00 | 0.00 | 0.224542E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.118032E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.643292E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198284E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 28377922.07 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2144095.12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.193617E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.161967E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383824E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.161967E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5543.24 | 27-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5543.24 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5305.64 | 01-MAR-12:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 7610.94 | 19-APR-13:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7610.94 | 08-MAY-11:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7610.94 | 01-JUN-08:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7610.94 | 05-JUL-10:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7610.94 | 01-AUG-08:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7610.94 | 22-SEP-10:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7610.94 | 03-OCT-11:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5305.64 | 01-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5543.24 | 26-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5305.64 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 7610.94 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.09 | 03-JAN-15:09 | 0.00 | 0.00 | 0.00 | 2052.83 | 27-JAN-12:09 | 0.00 |
February | 671.56 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2049.94 | 01-FEB-12:00 | 0.00 |
March | 1401.34 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1912.89 | 07-MAR-12:00 | 0.00 |
April | 14210.40 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1797.54 | 01-APR-11:09 | 0.00 |
May | 17584.91 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1773.14 | 01-MAY-11:30 | 0.00 |
June | 23756.03 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1747.96 | 01-JUN-11:09 | 0.00 |
July | 20563.11 | 26-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1730.80 | 01-JUL-11:20 | 0.00 |
August | 21560.91 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1731.07 | 31-AUG-11:50 | 0.00 |
September | 16220.57 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1748.37 | 30-SEP-11:20 | 0.00 |
October | 15080.86 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1772.99 | 31-OCT-11:09 | 0.00 |
November | 1731.13 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1799.27 | 30-NOV-12:30 | 0.00 |
December | 0.05 | 16-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1909.19 | 22-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.05 | 0.00 | 0.00 | 0.00 | 1730.80 | 0.00 | ||
Maximum of Months | 23756.03 | 0.00 | 0.00 | 0.00 | 2052.83 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52823.22 | 25-JAN-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5305.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53490.08 | 21-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5305.64 | 0.00 | 0.00 | 671.56 | 0.00 |
March | 54052.68 | 22-MAR-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5305.64 | 0.00 | 0.00 | 1247.23 | 0.00 |
April | 67415.87 | 21-APR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 12324.80 | 0.00 |
May | 71818.79 | 19-MAY-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 16776.97 | 0.00 |
June | 76701.62 | 15-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 21647.29 | 0.00 |
July | 75594.40 | 26-JUL-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 20551.87 | 0.00 |
August | 73738.26 | 08-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 18695.16 | 0.00 |
September | 70982.33 | 01-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 15933.73 | 0.00 |
October | 70035.42 | 03-OCT-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7610.94 | 0.00 | 0.00 | 14999.24 | 0.00 |
November | 55418.93 | 24-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5305.64 | 0.00 | 0.00 | 0.02 | 0.00 |
December | 56544.84 | 16-DEC-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5305.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52823.22 | 31660.41 | 10112.62 | 0.00 | 0.00 | 5305.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76701.62 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 7610.94 | 0.00 | 0.00 | 21647.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 86606.73 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 61087.69 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 42872.91 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 4617.23 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1610.72 | 27-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 41476.20 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 86070.24 | 27-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 86606.73 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 20.04 | 6.83 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.67 | 20.05 | 4.67 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.00 | 20.27 | 3.00 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.76 | 0.67 | 24.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.00 | 2.83 | 24.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.66 | 5.83 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.98 | 3.50 | 24.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.70 | 2.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.67 | 24.56 |
November | 1.50 | 20.16 | 1.50 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 19.99 | 6.50 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.00 | 20.08 | 23.00 | 20.08 | 18.50 | 25.60 | 15.50 | 24.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 20.52 | 6.83 | 20.52 | 7.00 | 25.98 | 5.83 | 24.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15.33 | 14.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.83 | 14.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.68 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 27.78 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 27.76 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 0.00 | 0.00 |
November | 4.50 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.17 | 14.72 | 0.00 | 149.50 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.33 | 14.82 | 0.00 | 0.00 | 43.17 | 27.78 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.78 | 211.83 | 21.24 | 211.83 | 21.24 |
February | 276.00 | 22.19 | 148.00 | 21.25 | 148.00 | 21.25 |
March | 324.00 | 22.84 | 105.83 | 21.28 | 105.83 | 21.28 |
April | 198.17 | 23.65 | 36.33 | 23.22 | 9.33 | 21.23 |
May | 50.17 | 23.77 | 160.00 | 23.90 | 0.17 | 24.64 |
June | 3.67 | 23.93 | 275.50 | 23.89 | 1.83 | 24.49 |
July | 39.67 | 23.98 | 300.00 | 23.91 | 39.67 | 23.98 |
August | 16.83 | 24.03 | 320.33 | 23.90 | 16.67 | 24.03 |
September | 22.33 | 23.91 | 273.83 | 23.90 | 19.50 | 23.94 |
October | 91.33 | 23.78 | 122.00 | 23.89 | 3.67 | 23.89 |
November | 270.50 | 22.93 | 75.67 | 21.26 | 75.67 | 21.26 |
December | 300.00 | 21.78 | 213.50 | 21.24 | 213.50 | 21.24 |
Annual Sum or Average | 1892.67 | 22.62 | 2242.83 | 23.00 | 845.67 | 21.51 |
Minimum of Months | 3.67 | 21.78 | 36.33 | 21.24 | 0.17 | 21.23 |
Maximum of Months | 324.00 | 24.03 | 320.33 | 23.91 | 213.50 | 24.64 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 971.64 | 270.66 | 2.17 | 971.64 | 0.00 | 0.00 | 0.00 | 03-JAN-15:10 | 0.00 | 01-JAN-00:10 | 0.32 | 03-JAN-15:10 | 0.32 | 03-JAN-15:10 | 0.00 | 03-JAN-15:20 | 0.09 | 03-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 58563270.03 | 16068073.17 | 25.92 | 58563270.03 | 0.00 | 0.00 | 0.14 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 | 2463.54 | 21-FEB-16:00 | 2463.54 | 21-FEB-16:00 | 0.00 | 18-FEB-15:10 | 671.56 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 |
March | 0.425186E+09 | 0.115647E+09 | 107.08 | 0.425186E+09 | 123.33 | 0.00 | 0.30 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 5210.95 | 14-MAR-16:00 | 5210.95 | 14-MAR-16:00 | 0.01 | 11-MAR-13:10 | 1401.34 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.323925E+10 | 0.906561E+09 | 200.57 | 0.323104E+10 | 8212573.88 | 0.00 | 1.00 | 20-APR-05:01 | 0.00 | 01-APR-00:10 | 20050.14 | 29-APR-05:01 | 19881.29 | 20-APR-05:01 | 2133.20 | 29-APR-05:02 | 4749.66 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.756499E+10 | 0.213051E+10 | 276.17 | 0.737163E+10 | 0.193352E+09 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 21600.64 | 23-MAY-05:01 | 20669.98 | 30-MAY-05:41 | 7612.85 | 25-MAY-05:02 | 5111.78 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.109637E+11 | 0.323530E+10 | 305.97 | 0.105130E+11 | 0.450734E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:01 | 22396.19 | 28-JUN-05:01 | 21046.41 | 17-JUN-05:01 | 8427.14 | 28-JUN-05:07 | 5280.73 | 28-JUN-05:01 | 0.00 | 01-JUN-00:01 |
July | 0.126263E+11 | 0.354091E+10 | 306.20 | 0.104887E+11 | 0.213758E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 25574.69 | 22-JUL-05:01 | 21707.14 | 03-JUL-05:01 | 14753.16 | 21-JUL-05:06 | 5935.48 | 16-JUL-18:30 | 0.00 | 01-JUL-00:05 |
August | 0.117436E+11 | 0.328055E+10 | 318.15 | 0.102372E+11 | 0.150639E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 24693.30 | 03-AUG-05:01 | 21482.99 | 24-AUG-05:01 | 11755.61 | 02-AUG-05:09 | 5708.87 | 03-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.946978E+10 | 0.260963E+10 | 274.15 | 0.831424E+10 | 0.115554E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 24100.88 | 22-SEP-05:01 | 22053.06 | 04-SEP-17:10 | 11939.72 | 22-SEP-05:47 | 5908.25 | 03-SEP-13:31 | 0.00 | 01-SEP-00:10 |
October | 0.388247E+10 | 0.104550E+10 | 204.55 | 0.353514E+10 | 0.347326E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 22788.22 | 04-OCT-05:01 | 21164.66 | 02-OCT-05:01 | 9901.38 | 04-OCT-05:15 | 5359.98 | 04-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.286942E+09 | 77371584.22 | 80.75 | 0.285260E+09 | 1681815.49 | 0.00 | 0.35 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 6551.91 | 03-NOV-16:00 | 6551.91 | 03-NOV-16:00 | 215.64 | 03-NOV-12:50 | 1731.13 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 2293.28 | 638.82 | 5.50 | 2293.28 | 0.00 | 0.00 | 0.00 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 | 0.19 | 16-DEC-15:00 | 0.19 | 16-DEC-15:00 | 0.00 | 09-DEC-15:30 | 0.05 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.602608E+11 | 0.169581E+11 | 2107.18 | 0.544599E+11 | 0.580082E+10 | 0.00 | ||||||||||||||
Minimum of Months | 971.64 | 270.66 | 2.17 | 971.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.19 | 0.00 | 0.05 | 0.00 | |||||||
Maximum of Months | 0.126263E+11 | 0.354091E+10 | 318.15 | 0.105130E+11 | 0.213758E+10 | 0.00 | 1.00 | 0.00 | 25574.69 | 22053.06 | 14753.16 | 5935.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.542664E+10 | 0.171961E+10 | 125.29 | 0.541079E+10 | 15845986.11 | 0.00 | 1.00 | 09-APR-14:41 | 0.00 | 01-APR-00:10 | 69500.54 | 30-APR-09:45 | 68357.47 | 30-APR-10:37 | 6974.28 | 30-APR-09:45 | 18368.80 | 30-APR-11:51 | 0.00 | 01-APR-00:10 |
May | 0.202975E+11 | 0.647301E+10 | 286.62 | 0.197549E+11 | 0.542584E+09 | 0.00 | 1.00 | 07-MAY-11:11 | 0.00 | 01-MAY-00:10 | 77243.14 | 28-MAY-09:02 | 67953.24 | 29-MAY-20:21 | 23874.00 | 28-MAY-08:41 | 20696.25 | 21-MAY-15:42 | 0.00 | 01-MAY-00:10 |
June | 0.380669E+11 | 0.126366E+11 | 404.39 | 0.367553E+11 | 0.131157E+10 | 0.00 | 1.00 | 01-JUN-00:06 | 0.00 | 01-JUN-00:01 | 80613.74 | 19-JUN-17:53 | 69232.59 | 24-JUN-18:21 | 31141.54 | 19-JUN-17:53 | 21440.49 | 18-JUN-16:02 | 0.00 | 01-JUN-00:01 |
July | 0.422736E+11 | 0.133524E+11 | 413.02 | 0.358778E+11 | 0.639583E+10 | 0.00 | 1.00 | 01-JUL-01:21 | 0.00 | 01-JUL-00:10 | 86164.60 | 21-JUL-20:41 | 67256.24 | 24-JUL-18:23 | 43278.20 | 21-JUL-20:48 | 22081.51 | 02-JUL-15:52 | 0.00 | 01-JUL-00:05 |
August | 0.350561E+11 | 0.110551E+11 | 384.49 | 0.312869E+11 | 0.376920E+10 | 0.00 | 1.00 | 01-AUG-00:21 | 0.00 | 01-AUG-00:15 | 82960.57 | 02-AUG-00:31 | 69148.82 | 25-AUG-21:50 | 38828.95 | 01-AUG-22:52 | 21472.57 | 06-AUG-15:22 | 0.00 | 01-AUG-00:10 |
September | 0.252846E+11 | 0.775339E+10 | 277.13 | 0.223087E+11 | 0.297588E+10 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:10 | 81517.38 | 03-SEP-08:21 | 69466.27 | 10-SEP-20:00 | 35764.63 | 03-SEP-07:41 | 20697.32 | 10-SEP-10:31 | 0.00 | 01-SEP-00:10 |
October | 0.545206E+10 | 0.166183E+10 | 136.66 | 0.486704E+10 | 0.585022E+09 | 0.00 | 1.00 | 01-OCT-09:31 | 0.00 | 01-OCT-00:10 | 79972.32 | 03-OCT-17:51 | 69171.84 | 22-OCT-14:01 | 27913.82 | 03-OCT-18:00 | 20474.56 | 03-OCT-17:51 | 0.00 | 01-OCT-00:10 |
November | 8114.17 | 2447.74 | 2.83 | 7460.72 | 653.45 | 0.00 | 0.00 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1.29 | 03-NOV-14:00 | 1.18 | 03-NOV-14:00 | 0.11 | 03-NOV-14:00 | 0.39 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171857E+12 | 0.546519E+11 | 2030.43 | 0.156261E+12 | 0.155959E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.422736E+11 | 0.133524E+11 | 413.02 | 0.367553E+11 | 0.639583E+10 | 0.00 | 1.00 | 0.00 | 86164.60 | 69466.27 | 43278.20 | 22081.51 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.57 | 37.54 | 29.03 | 72.79 | 134.33 | 0.00 | 0.00 | 744.00 |
February | 74.90 | 39.75 | 35.15 | 88.76 | 120.80 | 0.00 | 0.00 | 672.00 |
March | 102.06 | 54.65 | 47.41 | 133.70 | 108.14 | 0.00 | 0.00 | 744.00 |
April | 117.16 | 63.14 | 54.02 | 175.67 | 78.73 | 0.00 | 0.00 | 720.00 |
May | 126.17 | 67.36 | 58.81 | 210.73 | 57.94 | 0.00 | 0.00 | 744.00 |
June | 123.17 | 66.16 | 57.01 | 234.78 | 35.64 | 0.00 | 0.00 | 720.00 |
July | 109.39 | 54.38 | 55.01 | 206.86 | 31.97 | 0.00 | 0.00 | 744.00 |
August | 105.68 | 53.75 | 51.93 | 191.47 | 41.74 | 0.00 | 0.00 | 744.00 |
September | 108.36 | 60.40 | 47.95 | 185.64 | 70.01 | 0.00 | 0.00 | 720.00 |
October | 93.08 | 54.28 | 38.80 | 134.37 | 97.11 | 0.00 | 0.00 | 744.00 |
November | 77.69 | 47.11 | 30.57 | 92.39 | 132.47 | 0.00 | 0.00 | 720.00 |
December | 63.08 | 34.29 | 28.79 | 63.95 | 152.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 97.36 | 52.77 | 44.59 | 149.51 | 88.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.08 | 34.29 | 28.79 | 63.95 | 31.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 126.17 | 67.36 | 58.81 | 234.78 | 152.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.57 | 37.54 | 29.03 | 72.79 | 134.33 | 0.00 | 0.00 | 744.00 |
February | 74.90 | 39.75 | 35.15 | 88.76 | 120.80 | 0.00 | 0.00 | 672.00 |
March | 102.06 | 54.65 | 47.41 | 133.70 | 108.14 | 0.00 | 0.00 | 744.00 |
April | 117.16 | 63.14 | 54.02 | 175.67 | 78.73 | 0.00 | 0.00 | 720.00 |
May | 126.17 | 67.36 | 58.81 | 210.73 | 57.94 | 0.00 | 0.00 | 744.00 |
June | 123.17 | 66.16 | 57.01 | 234.78 | 35.64 | 0.00 | 0.00 | 720.00 |
July | 109.39 | 54.38 | 55.01 | 206.86 | 31.97 | 0.00 | 0.00 | 744.00 |
August | 105.68 | 53.75 | 51.93 | 191.47 | 41.74 | 0.00 | 0.00 | 744.00 |
September | 108.36 | 60.40 | 47.95 | 185.64 | 70.01 | 0.00 | 0.00 | 720.00 |
October | 93.08 | 54.28 | 38.80 | 134.37 | 97.11 | 0.00 | 0.00 | 744.00 |
November | 77.69 | 47.11 | 30.57 | 92.39 | 132.47 | 0.00 | 0.00 | 720.00 |
December | 63.08 | 34.29 | 28.79 | 63.95 | 152.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 97.36 | 52.77 | 44.59 | 149.51 | 88.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.08 | 34.29 | 28.79 | 63.95 | 31.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 126.17 | 67.36 | 58.81 | 234.78 | 152.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 2.51 | 83.61 | 0.00 | 0.00 | 744.00 |
February | 16.80 | 0.00 | 16.80 | 7.24 | 74.27 | 0.00 | 0.00 | 672.00 |
March | 22.00 | 0.00 | 21.99 | 13.65 | 66.01 | 0.00 | 0.00 | 744.00 |
April | 25.50 | 0.30 | 25.20 | 25.27 | 47.07 | 0.00 | 0.00 | 720.00 |
May | 30.28 | 2.34 | 27.94 | 40.60 | 32.34 | 0.00 | 0.00 | 744.00 |
June | 32.14 | 4.06 | 28.08 | 59.65 | 19.74 | 0.00 | 0.00 | 720.00 |
July | 29.60 | 2.88 | 26.72 | 54.44 | 17.86 | 0.00 | 0.00 | 744.00 |
August | 25.15 | 0.69 | 24.46 | 42.91 | 23.79 | 0.00 | 0.00 | 744.00 |
September | 21.80 | 0.02 | 21.78 | 31.95 | 41.16 | 0.00 | 0.00 | 720.00 |
October | 18.08 | 0.00 | 18.08 | 13.53 | 58.82 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 2.93 | 82.80 | 0.00 | 0.00 | 720.00 |
December | 13.65 | 0.00 | 13.65 | 1.45 | 95.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.97 | 0.86 | 21.11 | 24.76 | 53.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.65 | 0.00 | 13.65 | 1.45 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.14 | 4.06 | 28.08 | 59.65 | 95.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 2.51 | 83.61 | 0.00 | 0.00 | 744.00 |
February | 16.80 | 0.00 | 16.80 | 7.24 | 74.27 | 0.00 | 0.00 | 672.00 |
March | 22.00 | 0.00 | 21.99 | 13.65 | 66.01 | 0.00 | 0.00 | 744.00 |
April | 25.50 | 0.30 | 25.20 | 25.27 | 47.07 | 0.00 | 0.00 | 720.00 |
May | 30.28 | 2.34 | 27.94 | 40.60 | 32.34 | 0.00 | 0.00 | 744.00 |
June | 32.13 | 4.06 | 28.08 | 59.65 | 19.74 | 0.00 | 0.00 | 720.00 |
July | 29.60 | 2.88 | 26.72 | 54.44 | 17.86 | 0.00 | 0.00 | 744.00 |
August | 25.15 | 0.69 | 24.46 | 42.91 | 23.79 | 0.00 | 0.00 | 744.00 |
September | 21.80 | 0.02 | 21.78 | 31.95 | 41.16 | 0.00 | 0.00 | 720.00 |
October | 18.08 | 0.00 | 18.08 | 13.53 | 58.82 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 2.93 | 82.80 | 0.00 | 0.00 | 720.00 |
December | 13.65 | 0.00 | 13.65 | 1.45 | 95.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.97 | 0.86 | 21.11 | 24.76 | 53.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.65 | 0.00 | 13.65 | 1.45 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.13 | 4.06 | 28.08 | 59.65 | 95.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.68 | 70.65 | 1.50 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.65 | 69.44 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.50 | 71.06 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.27 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.67 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.83 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.11 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.24 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.98 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.58 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.09 | 81.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.51 | 65.13 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.09 | 40.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.58 | 6.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178306E+09 | 0.100558E+09 | 77747281.13 | 0.194972E+09 | 0.359799E+09 |
February | 0.181192E+09 | 96155890.82 | 85035801.96 | 0.214738E+09 | 0.292244E+09 |
March | 0.273356E+09 | 0.146381E+09 | 0.126975E+09 | 0.358104E+09 | 0.289654E+09 |
April | 0.303668E+09 | 0.163648E+09 | 0.140020E+09 | 0.455332E+09 | 0.204080E+09 |
May | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.564425E+09 | 0.155194E+09 |
June | 0.319260E+09 | 0.171488E+09 | 0.147771E+09 | 0.608562E+09 | 92366082.03 |
July | 0.292985E+09 | 0.145648E+09 | 0.147337E+09 | 0.554041E+09 | 85640606.51 |
August | 0.283060E+09 | 0.143971E+09 | 0.139088E+09 | 0.512832E+09 | 0.111798E+09 |
September | 0.280863E+09 | 0.156566E+09 | 0.124297E+09 | 0.481179E+09 | 0.181478E+09 |
October | 0.249316E+09 | 0.145390E+09 | 0.103926E+09 | 0.359901E+09 | 0.260100E+09 |
November | 0.201362E+09 | 0.122113E+09 | 79248559.55 | 0.239475E+09 | 0.343367E+09 |
December | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.171284E+09 | 0.409306E+09 |
Annual Sum or Average | 0.307027E+10 | 0.166420E+10 | 0.140607E+10 | 0.471484E+10 | 0.278503E+10 |
Minimum of Months | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.171284E+09 | 85640606.51 |
Maximum of Months | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.608562E+09 | 0.409306E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178306E+09 | 0.100558E+09 | 77747281.13 | 0.194972E+09 | 0.359799E+09 |
February | 0.181192E+09 | 96155890.82 | 85035801.96 | 0.214738E+09 | 0.292244E+09 |
March | 0.273356E+09 | 0.146381E+09 | 0.126975E+09 | 0.358104E+09 | 0.289654E+09 |
April | 0.303668E+09 | 0.163648E+09 | 0.140020E+09 | 0.455332E+09 | 0.204080E+09 |
May | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.564425E+09 | 0.155194E+09 |
June | 0.319260E+09 | 0.171488E+09 | 0.147771E+09 | 0.608562E+09 | 92366082.03 |
July | 0.292985E+09 | 0.145648E+09 | 0.147337E+09 | 0.554041E+09 | 85640606.51 |
August | 0.283060E+09 | 0.143971E+09 | 0.139088E+09 | 0.512832E+09 | 0.111798E+09 |
September | 0.280863E+09 | 0.156566E+09 | 0.124297E+09 | 0.481179E+09 | 0.181478E+09 |
October | 0.249316E+09 | 0.145390E+09 | 0.103926E+09 | 0.359901E+09 | 0.260100E+09 |
November | 0.201362E+09 | 0.122113E+09 | 79248559.55 | 0.239475E+09 | 0.343367E+09 |
December | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.171284E+09 | 0.409306E+09 |
Annual Sum or Average | 0.307027E+10 | 0.166420E+10 | 0.140607E+10 | 0.471484E+10 | 0.278503E+10 |
Minimum of Months | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.171284E+09 | 85640606.51 |
Maximum of Months | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.608562E+09 | 0.409306E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36857004.76 | 0.00 | 36857004.76 | 6727672.03 | 0.223931E+09 |
February | 40650861.33 | 0.00 | 40650861.33 | 17518199.33 | 0.179665E+09 |
March | 58918365.05 | 7469.43 | 58910895.62 | 36568537.36 | 0.176814E+09 |
April | 66098155.95 | 773908.19 | 65324247.76 | 65493488.24 | 0.122014E+09 |
May | 81110663.58 | 6280402.56 | 74830261.02 | 0.108744E+09 | 86615395.65 |
June | 83295495.23 | 10513332.86 | 72782162.37 | 0.154617E+09 | 51174120.91 |
July | 79290157.87 | 7712107.14 | 71578050.73 | 0.145823E+09 | 47845211.54 |
August | 67370407.03 | 1846240.70 | 65524166.33 | 0.114924E+09 | 63722624.74 |
September | 56505936.74 | 59249.37 | 56446687.36 | 82819320.72 | 0.106693E+09 |
October | 48422085.50 | 0.00 | 48422085.50 | 36246505.71 | 0.157535E+09 |
November | 37829908.95 | 0.00 | 37829908.95 | 7606447.23 | 0.214627E+09 |
December | 36571559.54 | 0.00 | 36571559.54 | 3889491.84 | 0.257019E+09 |
Annual Sum or Average | 0.692921E+09 | 27192710.26 | 0.665728E+09 | 0.780978E+09 | 0.168766E+10 |
Minimum of Months | 36571559.54 | 0.00 | 36571559.54 | 3889491.84 | 47845211.54 |
Maximum of Months | 83295495.23 | 10513332.86 | 74830261.02 | 0.154617E+09 | 0.257019E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36856015.13 | 0.00 | 36856015.13 | 6727198.77 | 0.223930E+09 |
February | 40649791.77 | 0.00 | 40649791.77 | 17517639.80 | 0.179664E+09 |
March | 58916844.09 | 7469.08 | 58909375.01 | 36567441.86 | 0.176812E+09 |
April | 66096528.93 | 773871.92 | 65322657.01 | 65492377.54 | 0.122013E+09 |
May | 81108515.27 | 6280108.19 | 74828407.08 | 0.108742E+09 | 86614137.72 |
June | 83293270.51 | 10512840.09 | 72780430.42 | 0.154615E+09 | 51173069.67 |
July | 79287954.77 | 7711745.67 | 71576209.10 | 0.145820E+09 | 47844381.23 |
August | 67368664.94 | 1846154.17 | 65522510.77 | 0.114923E+09 | 63721728.44 |
September | 56504568.91 | 59246.59 | 56445322.32 | 82818171.30 | 0.106691E+09 |
October | 48420839.83 | 0.00 | 48420839.83 | 36245549.13 | 0.157534E+09 |
November | 37828943.99 | 0.00 | 37828943.99 | 7606186.58 | 0.214626E+09 |
December | 36570544.81 | 0.00 | 36570544.81 | 3889197.86 | 0.257017E+09 |
Annual Sum or Average | 0.692902E+09 | 27191435.70 | 0.665711E+09 | 0.780964E+09 | 0.168764E+10 |
Minimum of Months | 36570544.81 | 0.00 | 36570544.81 | 3889197.86 | 47844381.23 |
Maximum of Months | 83293270.51 | 10512840.09 | 74828407.08 | 0.154615E+09 | 0.257017E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234855E+09 | 0.189234E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277368E+09 | 0.167979E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435248E+09 | 0.190332E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532062E+09 | 0.167351E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613305E+09 | 0.166764E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643070E+09 | 0.131335E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581448E+09 | 0.109351E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535178E+09 | 0.131543E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468018E+09 | 0.171689E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345708E+09 | 0.195461E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249487E+09 | 0.214055E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209145E+09 | 0.218751E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512489E+10 | 0.205384E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209145E+09 | 0.109351E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643070E+09 | 0.218751E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.83 | 427.10 | 160.66 | 75.09 | 85.58 | 0.00 | 0.00 |
February | 185.22 | 383.35 | 183.40 | 79.49 | 103.91 | 0.00 | 0.00 |
March | 289.56 | 343.17 | 248.11 | 109.31 | 138.80 | 0.00 | 0.00 |
April | 399.37 | 249.12 | 285.31 | 126.87 | 158.44 | 0.00 | 0.00 |
May | 501.93 | 179.83 | 312.91 | 139.42 | 173.50 | 0.00 | 0.00 |
June | 587.58 | 109.47 | 310.61 | 140.43 | 170.18 | 0.00 | 0.00 |
July | 521.37 | 98.44 | 277.98 | 114.52 | 163.47 | 0.00 | 0.00 |
August | 468.44 | 130.75 | 261.67 | 108.88 | 152.79 | 0.00 | 0.00 |
September | 434.50 | 221.67 | 260.31 | 120.85 | 139.46 | 0.00 | 0.00 |
October | 292.64 | 308.69 | 222.32 | 108.56 | 113.76 | 0.00 | 0.00 |
November | 182.08 | 421.98 | 184.56 | 94.22 | 90.34 | 0.00 | 0.00 |
December | 120.15 | 486.89 | 153.47 | 68.59 | 84.89 | 0.00 | 0.00 |
Annual Sum or Average | 344.40 | 279.51 | 238.66 | 107.27 | 131.39 | 0.00 | 0.00 |
Minimum of Months | 120.15 | 98.44 | 153.47 | 68.59 | 84.89 | 0.00 | 0.00 |
Maximum of Months | 587.58 | 486.89 | 312.91 | 140.43 | 173.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 876.85 | 706.52 | 701.79 | 492.46 | 209.34 | 0.00 | 0.00 |
February | 1146.52 | 694.36 | 897.92 | 635.15 | 262.77 | 0.00 | 0.00 |
March | 1625.03 | 710.62 | 1253.06 | 884.44 | 368.61 | 0.00 | 0.00 |
April | 2052.71 | 645.65 | 1557.83 | 1154.62 | 403.21 | 0.00 | 0.00 |
May | 2289.82 | 622.62 | 1717.74 | 1275.64 | 442.10 | 0.00 | 0.00 |
June | 2480.98 | 506.69 | 1814.07 | 1405.80 | 408.27 | 0.00 | 0.00 |
July | 2170.87 | 408.27 | 1569.93 | 1130.84 | 439.09 | 0.00 | 0.00 |
August | 1998.13 | 491.12 | 1467.71 | 1057.60 | 410.12 | 0.00 | 0.00 |
September | 1805.63 | 662.38 | 1344.11 | 1004.56 | 339.55 | 0.00 | 0.00 |
October | 1290.73 | 729.77 | 1014.64 | 736.70 | 277.94 | 0.00 | 0.00 |
November | 962.52 | 825.83 | 795.48 | 590.65 | 204.82 | 0.00 | 0.00 |
December | 780.86 | 816.72 | 650.84 | 433.69 | 217.15 | 0.00 | 0.00 |
Annual Sum or Average | 1625.09 | 651.27 | 1233.24 | 900.84 | 332.41 | 0.00 | 0.00 |
Minimum of Months | 780.86 | 408.27 | 650.84 | 433.69 | 204.82 | 0.00 | 0.00 |
Maximum of Months | 2480.98 | 825.83 | 1814.07 | 1405.80 | 442.10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379886E+09 | 0.114395E+10 | 0.430324E+09 | 0.201117E+09 | 0.229208E+09 | 0.00 | 0.00 |
February | 0.448091E+09 | 0.927399E+09 | 0.443684E+09 | 0.192312E+09 | 0.251372E+09 | 0.00 | 0.00 |
March | 0.775567E+09 | 0.919157E+09 | 0.664546E+09 | 0.292776E+09 | 0.371770E+09 | 0.00 | 0.00 |
April | 0.103518E+10 | 0.645716E+09 | 0.739531E+09 | 0.328843E+09 | 0.410687E+09 | 0.00 | 0.00 |
May | 0.134437E+10 | 0.481655E+09 | 0.838108E+09 | 0.373411E+09 | 0.464697E+09 | 0.00 | 0.00 |
June | 0.152302E+10 | 0.283739E+09 | 0.805108E+09 | 0.364003E+09 | 0.441105E+09 | 0.00 | 0.00 |
July | 0.139643E+10 | 0.263672E+09 | 0.744548E+09 | 0.306720E+09 | 0.437828E+09 | 0.00 | 0.00 |
August | 0.125467E+10 | 0.350197E+09 | 0.700858E+09 | 0.291635E+09 | 0.409223E+09 | 0.00 | 0.00 |
September | 0.112621E+10 | 0.574559E+09 | 0.674736E+09 | 0.313251E+09 | 0.361485E+09 | 0.00 | 0.00 |
October | 0.783808E+09 | 0.826783E+09 | 0.595475E+09 | 0.290780E+09 | 0.304695E+09 | 0.00 | 0.00 |
November | 0.471941E+09 | 0.109377E+10 | 0.478383E+09 | 0.244227E+09 | 0.234156E+09 | 0.00 | 0.00 |
December | 0.321796E+09 | 0.130410E+10 | 0.411066E+09 | 0.183708E+09 | 0.227357E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108610E+11 | 0.881469E+10 | 0.752637E+10 | 0.338278E+10 | 0.414358E+10 | 0.00 | 0.00 |
Minimum of Months | 0.321796E+09 | 0.263672E+09 | 0.411066E+09 | 0.183708E+09 | 0.227357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152302E+10 | 0.130410E+10 | 0.838108E+09 | 0.373411E+09 | 0.464697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234855E+10 | 0.189233E+10 | 0.187968E+10 | 0.131899E+10 | 0.560684E+09 | 0.00 | 0.00 |
February | 0.277366E+10 | 0.167979E+10 | 0.217226E+10 | 0.153656E+10 | 0.635703E+09 | 0.00 | 0.00 |
March | 0.435247E+10 | 0.190332E+10 | 0.335619E+10 | 0.236890E+10 | 0.987294E+09 | 0.00 | 0.00 |
April | 0.532062E+10 | 0.167351E+10 | 0.403789E+10 | 0.299277E+10 | 0.104512E+10 | 0.00 | 0.00 |
May | 0.613305E+10 | 0.166764E+10 | 0.460080E+10 | 0.341667E+10 | 0.118413E+10 | 0.00 | 0.00 |
June | 0.643069E+10 | 0.131335E+10 | 0.470207E+10 | 0.364384E+10 | 0.105823E+10 | 0.00 | 0.00 |
July | 0.581447E+10 | 0.109351E+10 | 0.420489E+10 | 0.302884E+10 | 0.117605E+10 | 0.00 | 0.00 |
August | 0.535178E+10 | 0.131540E+10 | 0.393113E+10 | 0.283268E+10 | 0.109845E+10 | 0.00 | 0.00 |
September | 0.468018E+10 | 0.171689E+10 | 0.348393E+10 | 0.260381E+10 | 0.880124E+09 | 0.00 | 0.00 |
October | 0.345708E+10 | 0.195461E+10 | 0.271760E+10 | 0.197317E+10 | 0.744430E+09 | 0.00 | 0.00 |
November | 0.249486E+10 | 0.214055E+10 | 0.206188E+10 | 0.153097E+10 | 0.530902E+09 | 0.00 | 0.00 |
December | 0.209145E+10 | 0.218751E+10 | 0.174322E+10 | 0.116161E+10 | 0.581615E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.512489E+11 | 0.205384E+11 | 0.388915E+11 | 0.284088E+11 | 0.104827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209145E+10 | 0.109351E+10 | 0.174322E+10 | 0.116161E+10 | 0.530902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.643069E+10 | 0.218751E+10 | 0.470207E+10 | 0.364384E+10 | 0.118413E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.32 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.73 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.69 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.47 | -2.7 | 4.72 | 3.37 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.20 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.01 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.90 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.10 | 12.00 | 3.28 | 15.47 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.80 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.00 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.23 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.89 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.89 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.90 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.36 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.84 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.49 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.18 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.19 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.18 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.16 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.85 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.82 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.87 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.43 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.94 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.94 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.16 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.3 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.4 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.3 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.5 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.97 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.40 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.97 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.88 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -2.9 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.0 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.4 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.97 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.15 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.74 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.71 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.10 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.18 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.87 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.16 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.64 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.62 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.55 | 03-NOV-13:20 | 22.07 | 7.93 | 2.10 | 9.59 | 80.17 | 943.83 |
December | 8.27 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.27 | 12.80 | -0.6 | 1.50 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.87 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 943.83 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.70 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.39 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.10 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.27 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.933430E+09 | -782885538.5 | 0.00 | 0.00 | 744.00 | 0.00 | -150544535.2 | 58.99 | 0.00 | 0.00 |
February | 0.852040E+09 | -718613651.8 | 0.00 | 0.00 | 672.00 | 0.00 | -133426430.2 | 58.99 | 0.00 | 0.00 |
March | 0.951621E+09 | -809046273.0 | 0.00 | 0.00 | 744.00 | 0.00 | -142574335.9 | 58.99 | 0.00 | 0.00 |
April | 0.829441E+09 | -701665574.8 | 0.00 | 0.00 | 720.00 | 0.00 | -127775852.4 | 58.99 | 0.00 | 0.00 |
May | 0.796763E+09 | -670065037.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126698285.1 | 58.99 | 0.00 | 0.00 |
June | 0.734999E+09 | -614642841.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120356613.5 | 58.99 | 0.00 | 0.00 |
July | 0.688144E+09 | -564850440.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123293521.1 | 58.99 | 0.00 | 0.00 |
August | 0.731657E+09 | -607208914.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124448063.7 | 58.99 | 0.00 | 0.00 |
September | 0.715714E+09 | -594511254.9 | 0.00 | 0.00 | 720.00 | 0.00 | -121202350.6 | 58.99 | 0.00 | 0.00 |
October | 0.776501E+09 | -646634602.7 | 0.00 | 0.00 | 744.00 | 0.00 | -129866270.8 | 58.99 | 0.00 | 0.00 |
November | 0.813308E+09 | -676110634.6 | 0.00 | 0.00 | 720.00 | 0.00 | -137197152.7 | 58.99 | 0.00 | 0.00 |
December | 0.904162E+09 | -753473209.3 | 0.00 | 0.00 | 744.00 | 0.00 | -150689024.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.972778E+10 | -.813971E+10 | 8760.00 | -.158807E+10 | 58.99 | |||||
Minimum of Months | 0.688144E+09 | -809046273.0 | 0.00 | 0.00 | 672.00 | 0.00 | -150689024.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.951621E+09 | -564850440.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120356613.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | ||||||||||
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167669E+10 | 28764.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110255E+10 | 28764.89 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602056E+09 | 28764.89 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18679504.84 | 13173.43 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1392113.59 | 2099.34 | 27-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439030E+09 | 28764.89 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181567E+10 | 28764.89 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565608E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181567E+10 | 28764.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.603478E+10 | 98730.60 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316408E+10 | 98730.60 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.739336E+09 | 98730.60 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.856737E+09 | 98730.60 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788166E+10 | 98730.60 | 26-DEC-01:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186766E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.788166E+10 | 98730.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243155E+09 | 24138.00 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88331352.24 | 12098.99 | 02-FEB-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142494E+10 | 36244.62 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175642E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142494E+10 | 36244.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 971.64 | 971.64 | 0.32 | 03-JAN-15:10 | 0.32 | 0.00 |
February | 0.00 | 0.00 | 58563270.03 | 58563270.03 | 2463.54 | 21-FEB-16:00 | 2463.54 | 0.00 |
March | 0.00 | 0.00 | 0.425186E+09 | 0.425186E+09 | 5210.95 | 14-MAR-16:00 | 5210.95 | 0.00 |
April | 0.00 | 0.00 | 0.323925E+10 | 0.323104E+10 | 20050.14 | 29-APR-05:01 | 18039.95 | 0.00 |
May | 0.00 | 0.00 | 0.756499E+10 | 0.737163E+10 | 21600.64 | 23-MAY-05:01 | 17397.96 | 0.00 |
June | 0.00 | 0.00 | 0.109637E+11 | 0.105130E+11 | 22396.19 | 28-JUN-05:01 | 14310.45 | 0.00 |
July | 0.00 | 0.00 | 0.126263E+11 | 0.104887E+11 | 25574.69 | 22-JUL-05:01 | 11779.26 | 0.00 |
August | 0.00 | 0.00 | 0.117436E+11 | 0.102372E+11 | 24693.30 | 03-AUG-05:01 | 14536.94 | 0.00 |
September | 0.00 | 0.00 | 0.946978E+10 | 0.831424E+10 | 24100.88 | 22-SEP-05:01 | 13136.46 | 0.00 |
October | 0.00 | 0.00 | 0.388247E+10 | 0.353514E+10 | 22788.22 | 04-OCT-05:01 | 13048.66 | 0.00 |
November | 0.00 | 0.00 | 0.286942E+09 | 0.285260E+09 | 6551.91 | 03-NOV-16:00 | 6551.91 | 0.00 |
December | 0.00 | 0.00 | 2293.28 | 2293.28 | 0.19 | 16-DEC-15:00 | 0.19 | 0.00 |
Annual Sum or Average | 0.602608E+11 | 0.544599E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 971.64 | 971.64 | 0.19 | 0.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126263E+11 | 0.105130E+11 | 25574.69 | 18039.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.542664E+10 | 0.541079E+10 | 69500.54 | 30-APR-09:45 | 62526.26 | 0.00 |
May | 0.00 | 0.00 | 0.202975E+11 | 0.197549E+11 | 77243.14 | 28-MAY-09:02 | 54114.32 | 0.00 |
June | 0.00 | 0.00 | 0.380669E+11 | 0.367553E+11 | 80613.74 | 19-JUN-17:53 | 49472.21 | 0.00 |
July | 0.00 | 0.00 | 0.422736E+11 | 0.358778E+11 | 86164.60 | 21-JUL-20:41 | 43153.57 | 0.00 |
August | 0.00 | 0.00 | 0.350561E+11 | 0.312869E+11 | 82960.57 | 02-AUG-00:31 | 45309.72 | 0.00 |
September | 0.00 | 0.00 | 0.252846E+11 | 0.223087E+11 | 81517.38 | 03-SEP-08:21 | 47581.78 | 0.00 |
October | 0.00 | 0.00 | 0.545206E+10 | 0.486704E+10 | 79972.32 | 03-OCT-17:51 | 52165.58 | 0.00 |
November | 0.00 | 0.00 | 8114.17 | 7460.72 | 1.29 | 03-NOV-14:00 | 1.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171857E+12 | 0.156261E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.422736E+11 | 0.367553E+11 | 86164.60 | 62526.26 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 4333832.48 | 0.00 | 237.60 | 27-JAN-06:48 | 0.09 |
February | 4098608.02 | 0.00 | 237.60 | 02-FEB-03:30 | 0.09 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 27834894.46 | 0.00 | 237.60 | 26-DEC-04:55 | 0.09 |
Annual Sum or Average | 36267334.96 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27834894.46 | 0.00 | 237.60 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150410E+10 | 0.43 | 1487.66 | 04-JAN-08:70 | 1.08 |
February | 0.137861E+10 | 0.43 | 1487.66 | 01-FEB-07:20 | 1.08 |
March | 0.160481E+10 | 0.46 | 1487.66 | 01-MAR-12:40 | 1.08 |
April | 0.147745E+10 | 0.42 | 1487.66 | 03-APR-11:10 | 1.08 |
May | 0.156624E+10 | 0.44 | 1487.66 | 01-MAY-08:40 | 1.08 |
June | 0.159022E+10 | 0.47 | 1487.66 | 02-JUN-06:50 | 1.08 |
July | 0.153957E+10 | 0.45 | 1487.66 | 01-JUL-05:01 | 1.07 |
August | 0.165784E+10 | 0.47 | 1487.66 | 11-AUG-06:08 | 1.07 |
September | 0.152980E+10 | 0.44 | 1487.66 | 02-SEP-06:30 | 1.06 |
October | 0.148534E+10 | 0.40 | 1487.66 | 05-OCT-06:10 | 1.07 |
November | 0.142368E+10 | 0.41 | 1487.66 | 01-NOV-13:30 | 1.07 |
December | 0.150447E+10 | 0.43 | 1487.66 | 01-DEC-08:00 | 1.08 |
Annual Sum or Average | 0.182621E+11 | 0.44 | |||
Minimum of Months | 0.137861E+10 | 0.40 | 1487.66 | 1.06 | |
Maximum of Months | 0.165784E+10 | 0.47 | 1487.66 | 1.08 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401804E+10 | 0.62 | 3817.99 | 06-JAN-08:00 | 1.04 |
February | 0.360483E+10 | 0.51 | 3817.99 | 01-FEB-08:50 | 1.04 |
March | 0.411102E+10 | 0.44 | 3817.99 | 02-MAR-08:40 | 1.04 |
April | 0.382863E+10 | 0.42 | 3817.99 | 01-APR-16:00 | 1.04 |
May | 0.424003E+10 | 0.51 | 3817.99 | 01-MAY-12:30 | 1.04 |
June | 0.460968E+10 | 0.63 | 3817.99 | 01-JUN-06:18 | 1.04 |
July | 0.459559E+10 | 0.62 | 3817.99 | 01-JUL-08:30 | 1.02 |
August | 0.467504E+10 | 0.60 | 3817.99 | 01-AUG-07:00 | 1.02 |
September | 0.410823E+10 | 0.48 | 3817.99 | 01-SEP-08:00 | 1.02 |
October | 0.383635E+10 | 0.40 | 3817.99 | 02-OCT-09:50 | 1.02 |
November | 0.366453E+10 | 0.42 | 3817.99 | 03-NOV-13:00 | 1.03 |
December | 0.409430E+10 | 0.66 | 3817.99 | 05-DEC-07:20 | 1.04 |
Annual Sum or Average | 0.493863E+11 | 0.52 | |||
Minimum of Months | 0.360483E+10 | 0.40 | 3817.99 | 1.02 | |
Maximum of Months | 0.467504E+10 | 0.66 | 3817.99 | 1.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.65 | 0.61 |
February | 0.76 | 0.83 |
March | 0.33 | 0.68 |
April | 1.23 | 0.04 |
May | 4.45 | 0.23 |
June | 5.93 | 0.23 |
July | 6.61 | 0.25 |
August | 5.68 | 0.26 |
September | 4.56 | 0.12 |
October | 2.48 | 0.19 |
November | 0.92 | 0.59 |
December | 0.78 | 1.20 |
Annual Sum or Average | 34.38 | 0.27 |
Minimum of Months | 0.33 | 0.04 |
Maximum of Months | 6.61 | 1.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.75 | 0.00 |
May | 2.85 | 0.00 |
June | 5.20 | 0.00 |
July | 7.96 | 0.00 |
August | 7.01 | 0.00 |
September | 4.70 | 0.00 |
October | 1.21 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 29.75 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.96 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 3.68 | 0.00 |
June | 9.85 | 0.00 |
July | 9.25 | 0.00 |
August | 10.27 | 0.00 |
September | 4.97 | 0.00 |
October | 0.58 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 38.61 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 10.27 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150410E+10 | 0.245624E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139468E+10 | 0.161224E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172046E+10 | 0.885108E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.238401E+10 | 28377922.07 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.369676E+10 | 2144095.12 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.482551E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.508048E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.493839E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.413943E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.253085E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150106E+10 | 0.645889E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.150447E+10 | 0.266004E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.352202E+11 | 0.829004E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508048E+10 | 0.266004E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.401804E+10 | 0.904018E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.360483E+10 | 0.470923E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.411102E+10 | 0.109774E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.554825E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107130E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172463E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179480E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.157301E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118616E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.549818E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.366453E+10 | 0.129028E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.409430E+10 | 0.117387E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104038E+12 | 0.278761E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.360483E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.179480E+11 | 0.117387E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150410E+10 | 971.64 | 0.167669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137861E+10 | 58563270.03 | 0.110255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160481E+10 | 0.425186E+09 | 0.602056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147745E+10 | 0.323925E+10 | 18679504.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156624E+10 | 0.756499E+10 | 1392113.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159022E+10 | 0.109637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153957E+10 | 0.126263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165784E+10 | 0.117436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152980E+10 | 0.946978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148534E+10 | 0.388247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142368E+10 | 0.286942E+09 | 0.439030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150447E+10 | 2293.28 | 0.181567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182621E+11 | 0.602608E+11 | 0.565608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137861E+10 | 971.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165784E+10 | 0.126263E+11 | 0.181567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.401804E+10 | 0.00 | 0.603478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360483E+10 | 0.00 | 0.316408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411102E+10 | 0.00 | 0.739336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382863E+10 | 0.542664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424003E+10 | 0.202975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.460968E+10 | 0.380669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.459559E+10 | 0.422736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467504E+10 | 0.350561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410823E+10 | 0.252846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383635E+10 | 0.545206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366453E+10 | 8114.17 | 0.856737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409430E+10 | 0.00 | 0.788166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493863E+11 | 0.171857E+12 | 0.186766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467504E+10 | 0.422736E+11 | 0.788166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.150410E+10 | 0.00 | 0.00 | 0.00 | 270.66 | 0.00 | 0.245624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137861E+10 | 0.00 | 0.00 | 0.00 | 16068073.17 | 0.00 | 0.161224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160481E+10 | 0.00 | 0.00 | 0.00 | 0.115647E+09 | 0.00 | 0.885108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147745E+10 | 0.00 | 0.00 | 0.00 | 0.906561E+09 | 0.00 | 28377922.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156624E+10 | 0.00 | 0.00 | 0.00 | 0.213051E+10 | 0.00 | 2144095.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159022E+10 | 0.00 | 0.00 | 0.00 | 0.323530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153957E+10 | 0.00 | 0.00 | 0.00 | 0.354091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165784E+10 | 0.00 | 0.00 | 0.00 | 0.328055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152980E+10 | 0.00 | 0.00 | 0.00 | 0.260963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148534E+10 | 0.00 | 0.00 | 0.00 | 0.104550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142368E+10 | 0.00 | 0.00 | 0.00 | 77371584.22 | 0.00 | 0.645889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150447E+10 | 0.00 | 0.00 | 0.00 | 638.82 | 0.00 | 0.266004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182621E+11 | 0.00 | 0.00 | 0.00 | 0.169581E+11 | 0.00 | 0.829004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137861E+10 | 0.00 | 0.00 | 0.00 | 270.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165784E+10 | 0.00 | 0.00 | 0.00 | 0.354091E+10 | 0.00 | 0.266004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.401804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382863E+10 | 0.00 | 0.00 | 0.00 | 0.171961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424003E+10 | 0.00 | 0.00 | 0.00 | 0.647301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.460968E+10 | 0.00 | 0.00 | 0.00 | 0.126366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.459559E+10 | 0.00 | 0.00 | 0.00 | 0.133524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467504E+10 | 0.00 | 0.00 | 0.00 | 0.110551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410823E+10 | 0.00 | 0.00 | 0.00 | 0.775339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383635E+10 | 0.00 | 0.00 | 0.00 | 0.166183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366453E+10 | 0.00 | 0.00 | 0.00 | 2447.74 | 0.00 | 0.129028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493863E+11 | 0.00 | 0.00 | 0.00 | 0.546519E+11 | 0.00 | 0.278761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.360483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467504E+10 | 0.00 | 0.00 | 0.00 | 0.133524E+11 | 0.00 | 0.117387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.630016E+09 | 0.00 | 0.00 | 21609.96 | 0.00 | 0.563425E+09 | 59663566.18 | 0.00 | 0.14 |
February | 0.594114E+09 | 0.00 | 0.00 | 195787.35 | 0.00 | 0.316016E+09 | 0.274616E+09 | 0.00 | 0.23 |
March | 0.550306E+09 | 206349.87 | 0.00 | 1152320.48 | 0.00 | 0.103918E+09 | 0.112040E+10 | 0.00 | 0.44 |
April | 75929793.56 | 92337306.03 | 0.00 | 3252456.64 | 0.00 | 0.00 | 0.171566E+10 | 0.00 | 0.55 |
May | 8574928.00 | 0.339074E+09 | 0.00 | 6256532.01 | 0.00 | 0.00 | 0.969015E+09 | 0.00 | 0.49 |
June | 463608.36 | 0.732048E+09 | 0.00 | 8461000.86 | 20782.11 | 0.00 | 0.249244E+09 | 0.00 | 0.35 |
July | 0.00 | 0.174441E+10 | 0.00 | 3214610.71 | 0.00 | 0.00 | 24136267.07 | 0.00 | 0.33 |
August | 0.00 | 0.101708E+10 | 0.00 | 7252544.39 | 44750.83 | 0.00 | 0.339093E+09 | 0.00 | 0.48 |
September | 2503926.29 | 0.764167E+09 | 0.00 | 6821573.25 | 0.00 | 0.00 | 0.670234E+09 | 0.00 | 0.49 |
October | 16040824.83 | 0.156884E+09 | 0.00 | 6234261.70 | 0.00 | 0.00 | 0.246224E+10 | 0.00 | 0.72 |
November | 0.393574E+09 | 0.00 | 0.00 | 1795795.03 | 0.00 | 94930135.40 | 0.158279E+10 | 0.00 | 0.43 |
December | 0.647805E+09 | 0.00 | 0.00 | 16132.74 | 0.00 | 0.632323E+09 | 55825340.08 | 0.00 | 0.13 |
Annual Sum or Average | 0.291933E+10 | 0.484621E+10 | 0.00 | 44674625.13 | 65532.94 | 0.171061E+10 | 0.952293E+10 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 16132.74 | 0.00 | 0.00 | 24136267.07 | 0.00 | 0.13 |
Maximum of Months | 0.647805E+09 | 0.174441E+10 | 0.00 | 8461000.86 | 44750.83 | 0.632323E+09 | 0.246224E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300214E+09 | 0.00 | 0.00 | 0.17 |
February | 0.251907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109033E+09 | 0.00 | 0.00 | 0.18 |
March | 0.269686E+10 | 0.00 | 0.00 | 0.00 | 1458756.50 | 38644465.85 | 0.00 | 0.00 | 0.19 |
April | 0.137061E+10 | 0.168977E+09 | 0.00 | 3238900.02 | 14002175.73 | 0.00 | 0.128517E+10 | 0.00 | 0.38 |
May | 0.280639E+09 | 0.915407E+09 | 0.00 | 9036378.69 | 0.00 | 0.00 | 0.203317E+10 | 0.00 | 0.50 |
June | 20902624.07 | 0.218404E+10 | 0.00 | 11157429.54 | 0.00 | 0.00 | 0.144118E+10 | 0.00 | 0.49 |
July | 11396619.63 | 0.389888E+10 | 0.00 | 6952848.52 | 3518.87 | 0.00 | 0.117604E+10 | 0.00 | 0.52 |
August | 54187321.60 | 0.243009E+10 | 0.00 | 12228118.48 | 0.00 | 0.00 | 0.219522E+10 | 0.00 | 0.58 |
September | 0.134510E+09 | 0.180414E+10 | 0.00 | 11252516.22 | 0.00 | 0.00 | 0.195057E+10 | 0.00 | 0.54 |
October | 0.131505E+10 | 0.323563E+09 | 0.00 | 5633323.21 | 0.00 | 0.00 | 0.326130E+10 | 0.00 | 0.50 |
November | 0.271246E+10 | 0.00 | 0.00 | 36416.22 | 0.00 | 45778371.85 | 86531286.46 | 0.00 | 0.18 |
December | 0.311542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375384E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.171370E+11 | 0.117251E+11 | 0.00 | 59535930.90 | 15464451.10 | 0.869054E+09 | 0.134292E+11 | 0.00 | 0.37 |
Minimum of Months | 11396619.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.311542E+10 | 0.389888E+10 | 0.00 | 12228118.48 | 14002175.73 | 0.375384E+09 | 0.326130E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |