Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2379.71 | 492.17 | 492.17 |
Net Site Energy | 2379.71 | 492.17 | 492.17 |
Total Source Energy | 4065.34 | 840.79 | 840.79 |
Net Source Energy | 4065.34 | 840.79 | 840.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1666.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 55.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.78 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 713.27 | 1666.44 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1666.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 83.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 55.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.78 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.76 | 344.65 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.52 | 344.65 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.76 | 344.65 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.52 | 344.65 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 713.269 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 713.269 | 100.00 |
Total On-Site and Utility Electric Sources | 713.269 | 100.00 |
Total Electricity End Uses | 713.269 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 65.00 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2231.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.6875 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 18-JAN-17:00 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 468149.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13380.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28324.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5688.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1767.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 59215.09 | 468149.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 468149.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13380.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28324.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3382.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1767.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1806.42 | 0.00 | 0.00 | 0.00 |
Cooling | 40.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1257.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 265.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2258.92 | 1806.42 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 373.60 | 0.00 | 0.00 | 0.00 |
Cooling | 8.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 259.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 467.19 | 373.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 373.60 | 0.00 | 0.00 | 0.00 |
Cooling | 8.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 259.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 467.19 | 373.60 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.938534 |
ZONE2 FINE STORAGE DIRECT AIR | 2.19 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 6.78 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 6.78 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 268809.81 |
PSZ-OFFICE HEATING COIL | 26105.00 |
PSZ-FINE STORAGE HEATING COIL | 82271.62 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 268809.79 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.938534 | 0.938534 | 0.938534 | 0.938534 | 0.938534 | 0.938534 | 1.00 | 1.00 | 0.938534 |
PSZ-FINE STORAGE | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 1.00 | 1.00 | 2.19 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.938534 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.19 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.938534 | 0.938534 | 0.938534 | 0.938534 | 17516.02 | 26105.00 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.19 | 2.19 | 2.19 | 2.19 | 52902.74 | 82271.62 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.938530 | 0.469265 | 0.625687 | 17079.25 | 17516.02 | 8758.01 | 8758.01 | 0.757095 | 0.757100 | 0.757100 | 0.757100 |
PSZ-FINE STORAGE COOLING COIL | 2.19 | 1.10 | 1.46 | 50745.88 | 52902.74 | 26451.37 | 26451.37 | 0.682985 | 0.682980 | 0.682980 | 0.682980 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.938534 | 1039.11 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.19 | 2343.82 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 9.688 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.761 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2294.776 | 9.688 | 458.955 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2294.776 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 14248.610 | 10.226 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.610 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 20008.048 | 6.243 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.048 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4332 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.309 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.53503428E-11 | 0.43487872E-15 | 0.25437469E-15 | 0.0000000 |
5 | 1 | -5.2159992 | 0.41060176E-04 | -0.36984335E-04 | 0.68788638E-11 |
6 | 0 | 5.6491605 | 0.43312021 | 0.43319826 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.709 | 8.453E-004 | 5.521E-004 | 0.276 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9067.54589 | 10881.05507 | 0.78211 | 0.93853 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53444E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12716.15232 | 15259.38279 | 0.37436 | 0.44923 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27145.49376 | 32574.59251 | 1.82532 | 2.19039 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 58470.52489 | 70164.62987 | 1.44923 | 1.73907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20000 | 1.53444E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 224008.15720 | 268809.78863 | 5.65202 | 6.78242 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13575.66 | 0.93853 | 0.93853 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15403.28 | 0.44923 | 0.44923 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 39362.99 | 2.19039 | 2.19039 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 69536.93 | 1.73907 | 1.73907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93853 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.19039 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.78242 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 6.78242 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 268809.81170 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 268809.78863 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93853 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93853 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93853 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93853 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93853 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.93853 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.19039 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.19039 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.19039 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.19039 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.19039 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.19039 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.93853 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.19039 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93853 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93853 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93853 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93853 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93853 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93853 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46927 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62569 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17079.24611 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17516.02000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8758.01000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8758.01000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75710 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75710 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75710 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75710 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17516.02000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26104.99832 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93853 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1039.10633 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26104.99832 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.19039 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.19039 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.19039 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.19039 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.19039 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.19039 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09520 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46026 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 50745.87580 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 52902.74000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26451.37000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26451.37000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68299 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68298 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68298 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68298 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52902.74000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 82271.61942 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.19039 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2343.81626 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 82271.61942 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16787.4 | 11.69 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 51200.4 | 15.59 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2160938162 | 0.1858109905 | Pass | Pass | 0.5179206708 | 1.4696976819 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5846729156 | 0.5585821696 | Pass | Pass | 0.6997241084 | 0.7871005960 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.1593069245E-005 | 1.6004550836E-004 | Pass | Pass | 1.9709072042E-002 | 2.0833485244E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.409 | 0.433 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 9.6875 | 236.88 | 2294.78 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 58.77 | 168.00 | 50.30 | 0.0000 | Y | 21.67 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 10.2257 | 1393.41 | 14248.61 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 6.2431 | 3204.84 | 20008.05 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 56.71 | 0.0000 | Y | 212.98 |
Interior Lighting Total | 7.5596 | 4835.13 | 36551.43 | 396.93 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.05 | 2320.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 42.24 | 42.24 | 0.90 | |
EXTERIOR_LIGHTS_B | 6197.40 | AstronomicalClock | - | 83.63 | 71.21 | 82.84 | |
Exterior Lighting Total | 6311.20 | 83.75 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17516.02 | 13261.38 | 4254.64 | 0.76 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 52902.74 | 36131.51 | 16771.23 | 0.68 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16787.4 | 11.69 | ||||
PSZ-FINE STORAGE COOLING COIL | 51200.4 | 15.59 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 268809.81 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26105.00 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 82271.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 6.78 | 630.16 | 92.91 | 1.00 | 3.07 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1039.11 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.19 | 2343.82 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9067.55 | 10881.06 | 45.93 | 0.782 | 0.939 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00839 | 29.72 | 0.01534 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27145.49 | 32574.59 | 23.38 | 1.825 | 2.190 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00876 | 31.20 | 0.01534 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00396 | 31.20 | 0.01534 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12716.15 | 15259.38 | 64.42 | 0.374 | 0.449 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00748 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 58470.52 | 70164.63 | 50.35 | 1.449 | 1.739 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00589 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 224008.16 | 268809.79 | 83.88 | 5.652 | 6.782 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00799 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.94 | 0.94 | 0.45 | 0.45 | 0.9385 | 0.9385 | 0.9385 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.19 | 2.19 | 1.74 | 1.74 | 2.1904 | 2.1904 | 2.1904 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 268809.812 | 268809.812 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 268809.81 | 268809.81 | 6.782422 | 4.77 | 4.77 | 0.00689527 | 43.33 | 26.49 | 0.01600000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.98 | 0.00799466 | 100.0000 | 268809.79 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 8758.010 | 0.000 | 0.938530 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8758.01 | 7317.67 | 0.938530 | 24.53 | 16.62 | 0.00914626 | 12.00 | 10.84 | 0.00800000 | 29.72 | 0.01534435 | 22.70 | 10.8984 | 23.90 | 0.00838815 | 43.3393 | 9067.55 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26104.998 | 26104.998 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26105.00 | 26105.00 | 0.938534 | 10.29 | 7.79 | 0.00586085 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.8984 | 21.10 | 0.00748217 | 45.8977 | 12716.15 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 26451.370 | 0.000 | 2.190390 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26451.37 | 20510.04 | 2.190390 | 27.57 | 18.33 | 0.01003483 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01534436 | 23.10 | 19.3898 | 26.70 | 0.00875769 | 38.2864 | 26146.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 82271.619 | 82271.619 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82271.62 | 82271.62 | 2.190386 | 5.35 | 3.76 | 0.00454223 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.3899 | 15.55 | 0.00589322 | 51.3418 | 58470.52 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 268809.812 | 268809.812 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1486 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 6.782422 | 7.78999008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 268809.81 | 268809.81 | 1.0000 | 7.78999008 | 6.782422 | 4.77 | 4.77 | 0.00689527 | 22097.8 | 43.33 | 26.49 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 268809.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.98 | 0.00799466 | 9.98 | 0.00799466 | 100.0000 | 268809.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8758.010 | 0.000 | 0.938530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8424 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8758.01 | 7317.67 | 1.0000 | 1.07795410 | 0.938530 | 24.53 | 16.62 | 0.00914626 | 47943.1 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8758.01 | 29.72 | 0.01534435 | 22.70 | 0.10228487 | 10.8984 | 23.90 | 0.00838815 | 23.90 | 0.00838815 | 43.3393 | 9067.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26104.998 | 26104.998 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.938534 | 1.07795891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26105.00 | 26105.00 | 1.0000 | 1.07795891 | 0.938534 | 10.29 | 7.79 | 0.00586085 | 25110.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26105.00 | -26.20 | 0.00036134 | -26.20 | 0.10228487 | 10.8984 | 21.05 | 0.00748217 | 21.10 | 0.00748217 | 45.8977 | 12716.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26451.370 | 0.000 | 2.190390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4943 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26451.37 | 20510.04 | 1.0000 | 2.51578520 | 2.190390 | 27.57 | 18.33 | 0.01003483 | 53315.0 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26451.37 | 31.20 | 0.01534436 | 23.10 | 0.42471267 | 19.3898 | 26.70 | 0.00875769 | 26.70 | 0.00875769 | 38.2864 | 26146.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82271.619 | 82271.619 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.190386 | 2.51578028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82271.62 | 82271.62 | 1.0000 | 2.51578028 | 2.190386 | 5.35 | 3.76 | 0.00454223 | 16786.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82271.62 | -26.20 | 0.00036134 | -26.20 | 0.42471267 | 19.3899 | 15.55 | 0.00589322 | 15.55 | 0.00589322 | 51.3418 | 58470.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 0.94 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.19 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2830.33 | 2838.00 | 2231.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2830.33 | 2838.00 | 2231.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 151.17 | 46.83 | 65.00 | 3.50 |
ZONE2 FINE STORAGE | 587.17 | 10.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 18.33 | 0.00 | 0.00 | 0.00 |
Facility | 717.67 | 56.00 | 65.00 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.606 | 0.261 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
Electricity:Building | 534.44 | 4004.31 | 01-JAN-10:30 | 40683.64 | 08-DEC-15:50 |
Electricity:Zone:ZONE1 OFFICE | 51.39 | 810.73 | 01-JAN-10:30 | 3365.36 | 02-JAN-08:10 |
InteriorLights:Electricity | 396.93 | 3515.76 | 01-JAN-10:30 | 30629.63 | 08-DEC-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.67 | 322.19 | 01-JAN-10:30 | 1511.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 396.93 | 3515.76 | 01-JAN-10:30 | 30629.63 | 08-DEC-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 320.78 | 1768.71 | 01-JAN-10:30 | 25539.46 | 26-JUN-12:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 212.98 | 1768.71 | 01-JAN-10:30 | 17006.84 | 02-JAN-10:30 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.78 | 481.00 | 06-JAN-06:50 | 2938.66 | 18-FEB-12:40 |
WaterSystems:Electricity | 26.78 | 481.00 | 06-JAN-06:50 | 2938.66 | 18-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 26.78 | 481.00 | 06-JAN-06:50 | 2938.66 | 18-FEB-12:40 |
Fans:Electricity | 55.97 | 0.00 | 24-FEB-18:10 | 5688.22 | 30-JUN-10:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.46 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
Ventilation (simple):Fans:Electricity | 0.46 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
ElectricityPurchased:Facility | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
ElectricityPurchased:Plant | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
Cogeneration:ElectricityPurchased | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
ElectricityNet:Plant | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
Cogeneration:ElectricityNet | 713.27 | 4485.31 | 19-MAR-09:20 | 59215.09 | 04-AUG-15:00 |
Electricity:HVAC | 68.30 | 0.00 | 24-FEB-18:10 | 17496.97 | 04-AUG-15:40 |
General:Fans:Electricity | 55.51 | 0.00 | 24-FEB-18:10 | 4013.08 | 24-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12.79 | 0.00 | 01-JAN-00:10 | 14114.05 | 04-AUG-15:40 |
ExteriorLights:Electricity | 83.75 | 0.00 | 01-JAN-08:00 | 6311.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 83.75 | 0.00 | 01-JAN-08:00 | 6311.20 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1666.44 | 0.00 | 24-FEB-18:10 | 468149.09 | 18-JAN-18:00 |
Gas:HVAC | 1666.44 | 0.00 | 24-FEB-18:10 | 468149.09 | 18-JAN-18:00 |
Heating:Gas | 1666.44 | 0.00 | 24-FEB-18:10 | 468149.09 | 18-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2664.81 | 0.00 | 24-FEB-18:10 | 747282.70 | 09-DEC-06:20 |
EnergyTransfer:Building | 1315.17 | 0.00 | 24-FEB-18:10 | 375021.04 | 09-DEC-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 69.05 | 0.00 | 01-JAN-00:40 | 27238.35 | 02-FEB-07:10 |
Heating:EnergyTransfer | 1264.93 | 0.00 | 24-FEB-18:10 | 375021.04 | 09-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 49.68 | 0.00 | 01-JAN-00:40 | 27238.35 | 02-FEB-07:10 |
Cooling:EnergyTransfer | 50.25 | 0.00 | 01-JAN-00:10 | 30707.71 | 04-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 19.37 | 0.00 | 01-JAN-00:10 | 9138.42 | 05-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 263.70 | 0.00 | 01-JAN-00:40 | 84133.75 | 09-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 232.83 | 0.00 | 01-JAN-00:40 | 84133.75 | 09-DEC-06:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 30.87 | 0.00 | 01-JAN-00:10 | 23565.18 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 982.42 | 0.00 | 12-JAN-13:00 | 271775.53 | 09-DEC-08:20 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 982.42 | 0.00 | 12-JAN-13:00 | 271775.53 | 09-DEC-08:20 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1349.63 | 0.00 | 24-FEB-18:10 | 373935.52 | 18-JAN-18:00 |
HeatingCoils:EnergyTransfer | 1292.52 | 0.00 | 24-FEB-18:10 | 373935.52 | 18-JAN-18:00 |
CoolingCoils:EnergyTransfer | 57.12 | 0.00 | 01-JAN-00:10 | 56733.50 | 04-AUG-15:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 49.680 | -19.373 | 0.000 | 0.000 | 3.975 | 21.668 | 29.720 | 9.053 | 0.000 | 0.410 | 0.000 | 0.000 | -13.817 | 0.000 | -24.538 | -56.778 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 232.826 | -30.871 | 0.000 | 0.000 | 0.000 | 162.279 | 0.000 | 0.000 | 0.000 | 1.022 | 0.002 | 0.000 | 0.000 | 0.000 | -177.548 | -187.708 |
ZONE3 BULK STORAGE | 982.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 212.982 | 107.336 | 29.524 | 0.000 | 15.671 | 0.000 | 0.000 | -28.855 | 0.000 | -929.838 | -389.239 |
Total Facility | 982.419 | 0.000 | 282.505 | -50.244 | 0.000 | 0.000 | 3.975 | 396.929 | 137.056 | 38.578 | 0.000 | 17.103 | 0.002 | 0.000 | -42.671 | 0.000 | -1131.924 | -633.725 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-AUG-00:03 | 0.00 | 0.00 | 0.00 | -21007.20 | 0.00 | 0.00 | 0.00 | 413.06 | 488.55 | 0.00 | 0.00 | 0.00 | 21151.89 | 0.00 | -710.42 | 0.00 | -335.88 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-14:41 | 0.00 | 0.00 | 0.00 | -47985.53 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 47534.94 | 0.00 | -0.00 | 0.00 | -974.27 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-17:11 | 0.00 | 0.00 | 0.00 | -60185.08 | 0.00 | 0.00 | 0.00 | 3593.12 | 2538.58 | 5065.92 | 0.00 | 4.55 | 55998.23 | 0.00 | 0.00 | 0.00 | -7015.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 31-JAN-06:31 | 0.00 | 0.00 | 28553.98 | 0.00 | 0.00 | 0.00 | 56.99 | 451.48 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1832.90 | 0.00 | -2463.23 | -25322.49 |
ZONE2 FINE STORAGE | 19-JAN-06:01 | 0.00 | 0.00 | 88702.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -28165.93 | -61961.81 |
ZONE3 BULK STORAGE | 09-DEC-08:15 | 272308.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15006.04 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3434.33 | 0.00 | -283671.69 | -8408.29 |
Total Facility | 09-DEC-06:21 | 269447.50 | 0.00 | 111258.63 | 0.00 | 0.00 | 0.00 | 46.49 | 3877.14 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5334.02 | 0.00 | -283719.25 | -98182.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9385 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9385 | 0.1090 | 1.0000 | 0.1023 | 0.1090 | ||
PSZ-FINE STORAGE | 2.1904 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.1904 | 0.1939 | 1.0000 | 0.4247 | 0.1939 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9385 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9385 | 1.0000 | 1.0000 | 0.1023 | 0.1090 | ||
PSZ-FINE STORAGE | 2.1904 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.1904 | 1.0000 | 1.0000 | 0.4247 | 0.1939 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9385 | 0.9385 | 0.9385 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.1904 | 2.1904 | 2.1904 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9385 | 0.9385 | 0.9385 | 0.9385 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.1904 | 2.1904 | 2.1904 | 2.1904 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9385 | 0.9385 | 0.9385 | 0.1023 | 0.2277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.1904 | 2.1904 | 2.1904 | 0.4247 | 0.2442 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9385 | 0.9385 | 0.9385 | 0.9385 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.1904 | 2.1904 | 2.1904 | 2.1904 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 65.00 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 68.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1666.44 | 468149.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 12.79 | 14114.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 396.93 | 30629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 83.75 | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.46 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 55.51 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.78 | 2938.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 713.27 |
Natural Gas | 0.00 | 1666.44 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 2379.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 82.09 |
Space Heating | 0.00 |
Space Cooling | 2.64 |
Fans (All) | 11.58 |
Service Water Heating | 5.54 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 147.52 |
Subtotal | 147.52 |
Natural Gas [MJ/m2] | |
Space Heating | 344.65 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 344.65 |
Subtotal | 344.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.68 |
Space Heating | 70.03 |
Space Cooling | 0.54 |
Fans (All) | 2.35 |
Service Water Heating | 1.13 |
Receptacle Equipment | 5.76 |
Miscellaneous | 3.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3065. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.491819E+12 |
February | 0.000 | 0.336769E+12 |
March | 0.000 | 0.190848E+12 |
April | 0.000 | 0.529736E+11 |
May | 0.000 | 0.247781E+10 |
June | 0.000 | 0.678960E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.784172E+09 |
October | 0.000 | 0.158178E+11 |
November | 0.000 | 0.194535E+12 |
December | 0.000 | 0.380345E+12 |
Annual Sum or Average | 0.166644E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.491819E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.194877E+09 | 236.59 | 21-JAN-13:20 | -5.7 | -6.5 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.179292E+09 | 236.59 | 22-FEB-08:30 | -1.1 | -1.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -11.9 | 0.210702E+09 | 256.36 | 25-MAR-15:39 | 18.17 | 10.45 |
April | 0.142794E+09 | 12550.42 | 18-APR-17:41 | 24.18 | 17.52 | 0.202346E+09 | 301.59 | 18-APR-09:09 | 23.27 | 18.94 |
May | 0.474458E+09 | 14135.98 | 31-MAY-22:05 | 19.42 | 14.31 | 0.237669E+09 | 301.59 | 30-MAY-15:00 | 27.80 | 19.88 |
June | 0.386024E+10 | 16784.78 | 22-JUN-17:11 | 20.60 | 13.28 | 0.254319E+09 | 301.64 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.579579E+10 | 19069.85 | 24-JUL-00:02 | 12.38 | 11.36 | 0.248882E+09 | 301.62 | 15-JUL-15:39 | 23.67 | 17.82 |
August | 0.592857E+10 | 21012.91 | 07-AUG-00:03 | 9.40 | 8.21 | 0.268800E+09 | 301.64 | 12-AUG-14:39 | 22.80 | 17.77 |
September | 0.312169E+10 | 17790.61 | 15-SEP-18:01 | 20.03 | 12.34 | 0.237779E+09 | 301.62 | 08-SEP-07:49 | 20.77 | 17.29 |
October | 46537756.56 | 631.65 | 23-OCT-16:00 | 6.60 | 2.78 | 0.200745E+09 | 301.58 | 21-OCT-15:00 | 18.50 | 13.48 |
November | 4342125.49 | 446.74 | 04-NOV-17:00 | 7.80 | 3.62 | 0.188842E+09 | 280.35 | 03-NOV-15:30 | 15.55 | 9.46 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.2 | 0.194911E+09 | 236.59 | 08-DEC-08:30 | -5.3 | -5.8 |
Annual Sum or Average | 0.193744E+11 | 0.261916E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.179292E+09 | 236.59 | -5.7 | -6.5 | ||
Maximum of Months | 0.592857E+10 | 21012.91 | 24.18 | 17.52 | 0.268800E+09 | 301.64 | 27.80 | 19.88 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70785454.26 | 3455.11 | 12-JAN-13:00 | 2.20 | 0.51 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.245048E+09 | 3806.10 | 25-FEB-11:50 | 3.12 | 1.46 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.595098E+09 | 5141.57 | 15-MAR-11:15 | -0.7 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.130346E+10 | 5824.59 | 21-APR-11:00 | -1.1 | -1.4 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.960535E+09 | 7965.89 | 22-MAY-06:10 | 7.25 | 5.99 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.592663E+10 | 38712.86 | 28-JUN-19:11 | 25.93 | 19.00 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.856840E+10 | 47989.48 | 23-JUL-14:41 | 22.70 | 15.06 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.723326E+10 | 43570.62 | 09-AUG-17:21 | 26.15 | 16.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.391328E+10 | 45268.59 | 09-SEP-17:21 | 25.80 | 16.12 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.145207E+10 | 6845.00 | 21-OCT-06:10 | 10.28 | 8.14 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.506750E+09 | 5813.10 | 03-NOV-06:10 | 11.10 | 10.20 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 96973661.86 | 5656.46 | 01-DEC-11:35 | -1.9 | -3.7 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.308723E+11 | 0.00 | ||||||||
Minimum of Months | 70785454.26 | 3455.11 | -1.9 | -3.7 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.856840E+10 | 47989.48 | 26.15 | 19.00 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -11.9 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.14 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 | 15.93 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.2 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119232E+11 | 28553.93 | 31-JAN-06:31 | -30.6 |
February | 0.914342E+10 | 27238.35 | 02-FEB-07:10 | -36.7 |
March | 0.725143E+10 | 27808.59 | 21-MAR-05:31 | -7.2 |
April | 0.379186E+10 | 26770.93 | 03-APR-05:12 | -7.2 |
May | 0.799828E+09 | 26515.70 | 02-MAY-05:12 | 2.20 |
June | 0.105158E+09 | 25652.27 | 05-JUN-05:02 | 9.32 |
July | 16934598.64 | 1338.81 | 21-JUL-06:05 | 16.38 |
August | 35578117.97 | 1357.66 | 15-AUG-06:04 | 14.18 |
September | 0.287831E+09 | 26383.05 | 29-SEP-05:01 | 0.92 |
October | 0.205014E+10 | 26394.15 | 23-OCT-05:01 | -2.7 |
November | 0.519525E+10 | 28101.47 | 24-NOV-06:31 | -13.7 |
December | 0.907925E+10 | 27906.36 | 28-DEC-06:31 | -17.6 |
Annual Sum or Average | 0.496799E+11 | |||
Minimum of Months | 16934598.64 | 1338.81 | -36.7 | |
Maximum of Months | 0.119232E+11 | 28553.93 | 16.38 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.633471E+11 | 88702.80 | 19-JAN-06:01 | -27.8 |
February | 0.451834E+11 | 87888.52 | 28-FEB-06:01 | -16.7 |
March | 0.279645E+11 | 85162.59 | 12-MAR-16:02 | -1.8 |
April | 0.108356E+11 | 85106.36 | 02-APR-23:02 | -5.1 |
May | 0.110927E+10 | 82790.87 | 02-MAY-05:01 | 2.20 |
June | 0.180933E+09 | 2392.61 | 14-JUN-07:00 | 17.80 |
July | 0.139776E+09 | 2229.94 | 20-JUL-07:00 | 20.00 |
August | 0.169144E+09 | 2224.44 | 25-AUG-07:00 | 13.90 |
September | 0.447475E+09 | 58610.03 | 29-SEP-05:01 | 0.92 |
October | 0.536965E+10 | 82806.29 | 17-OCT-05:01 | 0.77 |
November | 0.275408E+11 | 85125.98 | 28-NOV-21:22 | -7.2 |
December | 0.505386E+11 | 85124.49 | 25-DEC-05:22 | -9.7 |
Annual Sum or Average | 0.232826E+12 | |||
Minimum of Months | 0.139776E+09 | 2224.44 | -27.8 | |
Maximum of Months | 0.633471E+11 | 88702.80 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298746E+12 | 270650.72 | 18-JAN-18:00 | -18.3 |
February | 0.201283E+12 | 261556.28 | 01-FEB-20:57 | -28.9 |
March | 0.108611E+12 | 194574.02 | 06-MAR-08:70 | -11.8 |
April | 0.247501E+11 | 112718.70 | 02-APR-24:00 | -5.6 |
May | 0.428210E+09 | 19637.47 | 02-MAY-02:53 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.414374E+10 | 29965.48 | 24-OCT-06:00 | 2.20 |
November | 0.115136E+12 | 187210.89 | 25-NOV-16:10 | -18.1 |
December | 0.229322E+12 | 272308.31 | 09-DEC-08:15 | -22.8 |
Annual Sum or Average | 0.982421E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.298746E+12 | 272308.31 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.188935E+10 | 1511.47 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.168970E+10 | 1511.47 | 10-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.187243E+10 | 1456.05 | 01-MAR-16:00 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.176186E+10 | 1456.05 | 10-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.178856E+10 | 1289.79 | 02-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.174638E+10 | 1345.21 | 05-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.175082E+10 | 1345.21 | 08-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.182916E+10 | 1345.21 | 16-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.176332E+10 | 1456.05 | 21-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.182850E+10 | 1511.47 | 21-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.181187E+10 | 1511.47 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.193611E+10 | 1511.47 | 01-DEC-16:30 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.216681E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.168970E+10 | 1289.79 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.193611E+10 | 1511.47 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.134983E+11 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138856E+11 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | ||||
Minimum of Months | 0.123544E+11 | 12111.32 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.183441E+11 | 17006.84 | 02-JAN-10:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.166170E+11 | 17006.84 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.186282E+11 | 17006.84 | 13-MAR-08:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.172626E+11 | 16349.24 | 01-APR-08:20 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.177173E+11 | 15691.65 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.174927E+11 | 15691.65 | 01-JUN-14:00 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.172086E+11 | 15691.65 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.182581E+11 | 16349.24 | 29-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.173805E+11 | 16349.24 | 21-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.179479E+11 | 17006.84 | 20-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.174897E+11 | 17006.84 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.186354E+11 | 17006.84 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.212982E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.166170E+11 | 15691.65 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.186354E+11 | 17006.84 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.188935E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483551E+10 |
February | 0.500553E+09 | 0.168970E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359942E+10 |
March | 0.587605E+09 | 0.187243E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 367052.55 | 0.297769E+10 |
April | 0.544079E+09 | 0.176186E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20639823.01 | 0.173493E+10 |
May | 0.565842E+09 | 0.178856E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24259394.94 | 0.934888E+09 |
June | 0.565842E+09 | 0.174638E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103078E+09 | 0.557297E+09 |
July | 0.544079E+09 | 0.175082E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81148230.91 | 0.325585E+09 |
August | 0.587605E+09 | 0.182916E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114786E+09 | 0.472705E+09 |
September | 0.544079E+09 | 0.176332E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65979485.10 | 0.910725E+09 |
October | 0.544079E+09 | 0.182850E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158594E+10 |
November | 0.522316E+09 | 0.181187E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271469E+10 |
December | 0.544079E+09 | 0.193611E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388813E+10 |
Annual Sum or Average | 0.659424E+10 | 0.216681E+11 | 0.297195E+11 | 0.410258E+09 | 0.245375E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.168970E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325585E+09 |
Maximum of Months | 0.587605E+09 | 0.193611E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114786E+09 | 0.483551E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352662E+11 |
February | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258310E+11 |
March | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9835331.95 | 0.202117E+11 |
April | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213523E+09 | 0.109198E+11 |
May | 0.00 | 0.138856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56826075.82 | 0.581556E+10 |
June | 0.00 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386222E+09 | 0.458816E+10 |
July | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97419332.19 | 0.387970E+10 |
August | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147782E+09 | 0.528766E+10 |
September | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108457E+09 | 0.669969E+10 |
October | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1636559.82 | 0.938782E+10 |
November | 0.00 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203492E+11 |
December | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293117E+11 |
Annual Sum or Average | 0.162279E+12 | 0.102170E+10 | 0.177548E+12 | ||||||
Minimum of Months | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387970E+10 |
Maximum of Months | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386222E+09 | 0.352662E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.183441E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142020E+12 |
February | 0.00 | 0.166170E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987214E+11 |
March | 0.00 | 0.186282E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107598E+10 | 0.668659E+11 |
April | 0.00 | 0.172626E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438242E+10 | 0.322457E+11 |
May | 0.00 | 0.177173E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224383E+10 | 0.159413E+11 |
June | 0.00 | 0.174927E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128382E+10 | 0.185111E+11 |
July | 0.00 | 0.172086E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28791128.18 | 0.208064E+11 |
August | 0.00 | 0.182581E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68798752.70 | 0.251891E+11 |
September | 0.00 | 0.173805E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355735E+09 | 0.269602E+11 |
October | 0.00 | 0.179479E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107711E+10 | 0.238152E+11 |
November | 0.00 | 0.174897E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166039E+09 | 0.689628E+11 |
December | 0.00 | 0.186354E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111302E+12 |
Annual Sum or Average | 0.212982E+12 | 0.107336E+12 | 0.106825E+11 | 0.651341E+12 | |||||
Minimum of Months | 0.00 | 0.166170E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159413E+11 |
Maximum of Months | 0.00 | 0.186354E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438242E+10 | 0.142020E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1511.47 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 14448.33 | 19-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1511.47 | 10-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 16533.65 | 02-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1456.05 | 01-MAR-16:00 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 19-MAR-14:00 | 10226.96 | 06-MAR-08:00 |
April | 659.25 | 01-APR-07:10 | 1456.05 | 10-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 884.09 | 18-APR-12:00 | 7749.14 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1289.79 | 02-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.69 | 31-MAY-12:00 | 4911.22 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1345.21 | 05-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.98 | 26-JUN-16:10 | 3486.91 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1345.21 | 08-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.68 | 26-JUL-16:10 | 2658.87 | 24-JUL-06:02 |
August | 659.25 | 01-AUG-07:10 | 1345.21 | 16-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.31 | 04-AUG-16:10 | 3560.20 | 07-AUG-06:01 |
September | 659.25 | 01-SEP-07:10 | 1456.05 | 21-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1649.88 | 06-SEP-16:10 | 5187.09 | 29-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1511.47 | 21-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5962.50 | 23-OCT-06:05 |
November | 659.25 | 01-NOV-07:10 | 1511.47 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9918.64 | 28-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1511.47 | 01-DEC-16:30 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13002.80 | 08-DEC-17:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1289.79 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.87 | |||||
Maximum of Months | 659.25 | 1511.47 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.31 | 16533.65 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 60019.87 | 18-JAN-18:00 |
February | 0.00 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37893.86 | 04-FEB-18:00 |
March | 0.00 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933.16 | 19-MAR-16:00 | 37243.38 | 06-MAR-08:00 |
April | 0.00 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5216.00 | 15-APR-17:00 | 23265.40 | 25-APR-06:10 |
May | 0.00 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1619.33 | 05-MAY-17:20 | 9861.23 | 01-MAY-23:47 |
June | 0.00 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4964.03 | 11-JUN-15:00 | 9821.88 | 02-JUN-08:00 |
July | 0.00 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2707.50 | 25-JUL-16:00 | 6937.90 | 10-JUL-15:10 |
August | 0.00 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3383.41 | 04-AUG-16:15 | 7660.53 | 30-AUG-15:10 |
September | 0.00 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2960.02 | 06-SEP-15:40 | 9393.36 | 18-SEP-23:00 |
October | 0.00 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.11 | 20-OCT-15:10 | 15929.40 | 24-OCT-06:10 |
November | 0.00 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 33821.74 | 25-NOV-16:10 |
December | 0.00 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63325.22 | 09-DEC-08:55 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6937.90 | |||
Maximum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5216.00 | 63325.22 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 17006.84 | 02-JAN-10:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 190046.83 | 18-JAN-16:00 |
February | 0.00 | 17006.84 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 136979.47 | 28-FEB-10:00 |
March | 0.00 | 17006.84 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20516.37 | 25-MAR-15:00 | 124872.26 | 06-MAR-08:70 |
April | 0.00 | 16349.24 | 01-APR-08:20 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45580.32 | 15-APR-15:00 | 59343.88 | 02-APR-24:00 |
May | 0.00 | 15691.65 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29295.63 | 04-MAY-14:00 | 38149.14 | 13-MAY-12:55 |
June | 0.00 | 15691.65 | 01-JUN-14:00 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21104.68 | 11-JUN-14:55 | 36037.61 | 02-JUN-08:00 |
July | 0.00 | 15691.65 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.57 | 25-JUL-16:00 | 35069.96 | 10-JUL-14:00 |
August | 0.00 | 16349.24 | 29-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3260.96 | 21-AUG-13:00 | 32438.98 | 30-AUG-14:55 |
September | 0.00 | 16349.24 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10100.98 | 06-SEP-14:00 | 36889.68 | 18-SEP-16:00 |
October | 0.00 | 17006.84 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18836.39 | 20-OCT-15:00 | 34500.73 | 24-OCT-07:10 |
November | 0.00 | 17006.84 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11063.78 | 20-NOV-10:00 | 134592.00 | 25-NOV-11:00 |
December | 0.00 | 17006.84 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 224907.31 | 09-DEC-08:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 15691.65 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32438.98 | ||||
Maximum of Months | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45580.32 | 224907.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.26 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 2891.42 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.39 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 2891.42 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.66 |
April | 12550.42 | 18-APR-17:41 | 0.00 | 2577.49 | 3908.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 | 0.00 |
May | 14135.98 | 31-MAY-22:05 | 0.00 | 826.12 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.15 |
June | 16784.78 | 22-JUN-17:11 | 0.00 | 2899.68 | 4396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.82 |
July | 19069.85 | 24-JUL-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 |
August | 21012.91 | 07-AUG-00:03 | 0.00 | 1652.24 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.88 |
September | 17790.61 | 15-SEP-18:01 | 0.00 | 3827.69 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
October | 631.65 | 23-OCT-16:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.38 |
November | 446.74 | 04-NOV-17:00 | 421.92 | 2394.80 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.26 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1652.24 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 826.12 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21012.91 | 659.25 | 3827.69 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 | 1103.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3455.11 | 12-JAN-13:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.04 |
February | 3806.10 | 25-FEB-11:50 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3188.59 |
March | 5141.57 | 15-MAR-11:15 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3087.48 |
April | 5824.59 | 21-APR-11:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4983.12 |
May | 7965.89 | 22-MAY-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2994.14 |
June | 38712.86 | 28-JUN-19:11 | 0.00 | 11398.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.54 |
July | 47989.48 | 23-JUL-14:41 | 0.00 | 14248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.27 |
August | 43570.62 | 09-AUG-17:21 | 0.00 | 12823.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.21 |
September | 45268.59 | 09-SEP-17:21 | 0.00 | 14248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.28 |
October | 6845.00 | 21-OCT-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2562.96 |
November | 5813.10 | 03-NOV-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.77 |
December | 5656.46 | 01-DEC-11:35 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4790.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3455.11 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.21 | |
Maximum of Months | 47989.48 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4983.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 10004.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24524.57 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 14005.63 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60186.88 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 14005.63 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62293.43 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11312.52 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6328.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8900.22 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8585.33 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9657.35 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11804.19 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10620.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7487.89 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8003.22 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25200.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6328.74 | |
Maximum of Months | 0.00 | 0.00 | 14005.63 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62293.43 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.631260E+11 | 49210.88 | 20-JAN-16:00 | 0.491819E+12 | 468149.09 | 18-JAN-17:00 |
February | 0.564533E+11 | 46831.41 | 08-FEB-15:00 | 0.336769E+12 | 423051.83 | 01-FEB-20:00 |
March | 0.623101E+11 | 46265.20 | 11-MAR-15:00 | 0.190848E+12 | 340846.06 | 06-MAR-08:09 |
April | 0.562491E+11 | 46588.71 | 18-APR-14:20 | 0.529736E+11 | 195722.80 | 02-APR-23:49 |
May | 0.565840E+11 | 48736.06 | 31-MAY-14:00 | 0.247781E+10 | 63055.54 | 02-MAY-05:10 |
June | 0.584148E+11 | 55049.19 | 27-JUN-14:39 | 67896036.63 | 6526.25 | 05-JUN-05:10 |
July | 0.593029E+11 | 56234.98 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.624666E+11 | 59215.09 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.575794E+11 | 51747.94 | 06-SEP-14:00 | 0.784172E+09 | 29379.64 | 30-SEP-05:10 |
October | 0.584554E+11 | 45581.09 | 30-OCT-08:39 | 0.158178E+11 | 72848.44 | 24-OCT-05:10 |
November | 0.589635E+11 | 49201.57 | 30-NOV-16:30 | 0.194535E+12 | 319754.65 | 25-NOV-16:10 |
December | 0.633641E+11 | 49207.56 | 29-DEC-16:40 | 0.380345E+12 | 465838.60 | 09-DEC-06:19 |
Annual Sum or Average | 0.713269E+12 | 0.166644E+13 | ||||
Minimum of Months | 0.562491E+11 | 45581.09 | 0.00 | 0.00 | ||
Maximum of Months | 0.633641E+11 | 59215.09 | 0.491819E+12 | 468149.09 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.337317E+11 | 0.914536E+10 | 0.113456E+11 | 0.00 | 0.655033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235305E+10 | 0.00 |
February | 0.306611E+11 | 0.752753E+10 | 0.104160E+11 | 0.00 | 0.568939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215936E+10 | 0.00 |
March | 0.347734E+11 | 0.732016E+10 | 0.121485E+11 | 0.00 | 0.563286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243507E+10 | 0.00 |
April | 0.323997E+11 | 0.604500E+10 | 0.113034E+11 | 0.00 | 0.416836E+10 | 0.00 | 0.00 | 57477935.48 | 0.00 | 0.00 | 0.00 | 0.227528E+10 | 0.00 |
May | 0.333914E+11 | 0.539416E+10 | 0.117471E+11 | 0.00 | 0.353879E+10 | 0.00 | 0.00 | 0.217866E+09 | 0.00 | 0.00 | 0.00 | 0.229468E+10 | 0.00 |
June | 0.330015E+11 | 0.481862E+10 | 0.117048E+11 | 0.00 | 0.392141E+10 | 0.00 | 0.00 | 0.278789E+10 | 0.00 | 0.00 | 0.00 | 0.218053E+10 | 0.00 |
July | 0.324577E+11 | 0.512839E+10 | 0.113456E+11 | 0.00 | 0.389639E+10 | 0.00 | 0.00 | 0.432802E+10 | 0.00 | 0.00 | 0.00 | 0.214682E+10 | 0.00 |
August | 0.343601E+11 | 0.584713E+10 | 0.121485E+11 | 0.00 | 0.408631E+10 | 0.00 | 0.00 | 0.384121E+10 | 0.00 | 0.00 | 0.00 | 0.218329E+10 | 0.00 |
September | 0.325190E+11 | 0.662058E+10 | 0.113034E+11 | 0.00 | 0.348661E+10 | 0.00 | 0.00 | 0.155563E+10 | 0.00 | 0.00 | 0.00 | 0.209420E+10 | 0.00 |
October | 0.332746E+11 | 0.791468E+10 | 0.113456E+11 | 0.00 | 0.373308E+10 | 0.00 | 0.00 | 252062.36 | 0.00 | 0.00 | 0.00 | 0.218721E+10 | 0.00 |
November | 0.322895E+11 | 0.858589E+10 | 0.109019E+11 | 0.00 | 0.501962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216668E+10 | 0.00 |
December | 0.340698E+11 | 0.939907E+10 | 0.113456E+11 | 0.00 | 0.624394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230577E+10 | 0.00 |
Annual Sum or Average | 0.396929E+12 | 0.837466E+11 | 0.137056E+12 | 0.559671E+11 | 0.00 | 0.127883E+11 | 0.267819E+11 | ||||||
Minimum of Months | 0.306611E+11 | 0.481862E+10 | 0.104160E+11 | 0.00 | 0.348661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209420E+10 | 0.00 |
Maximum of Months | 0.347734E+11 | 0.939907E+10 | 0.121485E+11 | 0.00 | 0.655033E+10 | 0.00 | 0.00 | 0.432802E+10 | 0.00 | 0.00 | 0.00 | 0.243507E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.491819E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.336769E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.190848E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.529736E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.247781E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 67896036.63 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.784172E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.158178E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194535E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.380345E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166644E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.491819E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30574.21 | 10-JAN-15:30 | 6311.20 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 4013.08 | 24-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30518.79 | 08-FEB-09:09 | 6311.20 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 4013.08 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30463.37 | 13-MAR-08:09 | 6311.20 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 4013.08 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29805.77 | 01-APR-08:20 | 6311.20 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 4013.08 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29037.33 | 04-MAY-08:09 | 6311.20 | 01-MAY-19:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 4013.08 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29092.75 | 05-JUN-08:09 | 6311.20 | 01-JUN-19:40 | 10054.01 | 01-JUN-07:10 | 0.00 | 5688.22 | 30-JUN-10:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29092.75 | 08-JUL-08:20 | 6311.20 | 01-JUL-19:00 | 10054.01 | 01-JUL-07:10 | 0.00 | 5688.22 | 03-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29694.93 | 29-AUG-08:09 | 6311.20 | 01-AUG-19:40 | 10054.01 | 01-AUG-07:10 | 0.00 | 5688.22 | 02-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 29805.77 | 21-SEP-08:09 | 6311.20 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 3382.92 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30463.37 | 20-OCT-08:09 | 6311.20 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 4013.08 | 16-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30574.21 | 08-NOV-15:30 | 6311.20 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 4013.08 | 10-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30629.63 | 08-DEC-15:50 | 6311.20 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 4013.08 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29037.33 | 6311.20 | 10054.01 | 0.00 | 3382.92 | 0.00 | 0.00 | |||||
Maximum of Months | 30629.63 | 6311.20 | 10054.01 | 0.00 | 5688.22 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2914.83 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2938.66 | 18-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2932.02 | 02-MAR-12:20 | 0.00 |
April | 2800.43 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 2835.38 | 01-APR-11:00 | 0.00 |
May | 5206.10 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2636.97 | 01-MAY-11:30 | 0.00 |
June | 9531.69 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2349.18 | 01-JUN-11:20 | 0.00 |
July | 10387.02 | 03-JUL-14:00 | 0.00 | 0.00 | 0.00 | 2064.25 | 01-JUL-11:50 | 0.00 |
August | 14114.05 | 04-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1818.75 | 28-AUG-11:00 | 0.00 |
September | 7835.52 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1967.54 | 28-SEP-11:00 | 0.00 |
October | 142.54 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2227.35 | 28-OCT-11:50 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2531.92 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2766.60 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1818.75 | 0.00 | ||
Maximum of Months | 14114.05 | 0.00 | 0.00 | 0.00 | 2938.66 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49210.88 | 20-JAN-16:00 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46831.41 | 08-FEB-15:00 | 30297.11 | 10054.01 | 0.00 | 0.00 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46265.20 | 11-MAR-15:00 | 29750.35 | 10054.01 | 0.00 | 0.00 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46588.71 | 18-APR-14:20 | 28324.31 | 10054.01 | 0.00 | 0.00 | 3382.92 | 0.00 | 0.00 | 2586.63 | 0.00 |
May | 48736.06 | 31-MAY-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 3382.92 | 0.00 | 0.00 | 5168.78 | 0.00 |
June | 55049.19 | 27-JUN-14:39 | 28324.31 | 10054.01 | 0.00 | 0.00 | 5688.22 | 0.00 | 0.00 | 9197.31 | 0.00 |
July | 56234.98 | 03-JUL-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 5688.22 | 0.00 | 0.00 | 10387.02 | 0.00 |
August | 59215.09 | 04-AUG-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 5688.22 | 0.00 | 0.00 | 13380.90 | 0.00 |
September | 51747.94 | 06-SEP-14:00 | 28981.91 | 10054.01 | 0.00 | 0.00 | 3382.92 | 0.00 | 0.00 | 7561.54 | 0.00 |
October | 45581.09 | 30-OCT-08:39 | 30463.37 | 10054.01 | 0.00 | 0.00 | 3382.92 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49201.57 | 30-NOV-16:30 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49207.56 | 29-DEC-16:40 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4013.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 45581.09 | 27203.97 | 10054.01 | 0.00 | 0.00 | 3382.92 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59215.09 | 30463.37 | 10054.01 | 6311.20 | 0.00 | 5688.22 | 0.00 | 0.00 | 13380.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 468149.09 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 423051.83 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 340846.06 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 195722.80 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 63055.54 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6526.25 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 29379.64 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 72848.44 | 24-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 319754.65 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 465838.60 | 09-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 468149.09 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.67 | 15.91 | 10.67 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30.83 | 16.16 | 9.67 | 19.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17.67 | 17.50 | 10.00 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10.00 | 18.51 | 7.83 | 19.48 | 0.17 | 24.48 | 0.00 | 0.00 |
May | 2.00 | 20.11 | 2.00 | 20.11 | 0.17 | 24.54 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 24.56 | 0.67 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.58 | 1.17 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 24.54 | 1.17 | 24.51 |
September | 0.67 | 20.27 | 0.67 | 20.27 | 7.00 | 24.54 | 0.50 | 24.54 |
October | 6.33 | 20.16 | 6.33 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.67 | 17.22 | 7.50 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27.33 | 16.52 | 10.33 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.17 | 16.82 | 65.00 | 19.38 | 46.83 | 24.55 | 3.50 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.67 | 20.27 | 10.67 | 20.27 | 16.33 | 24.58 | 1.17 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.17 | 13.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 106.17 | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86.33 | 14.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44.33 | 14.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3.33 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.35 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.34 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.00 | 0.00 |
September | 1.17 | 14.98 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 0.00 |
October | 21.00 | 14.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78.17 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121.50 | 13.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 587.17 | 14.05 | 0.00 | 10.00 | 27.34 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 125.17 | 14.98 | 0.00 | 0.00 | 5.17 | 27.35 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 9.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.17 | 8.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.33 | 8.46 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.17 | 9.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.01 | 300.00 | 21.01 | 300.00 | 21.01 |
February | 276.00 | 21.02 | 276.00 | 21.02 | 276.00 | 21.02 |
March | 324.00 | 21.05 | 324.00 | 21.05 | 324.00 | 21.05 |
April | 297.00 | 21.38 | 242.50 | 21.06 | 242.50 | 21.06 |
May | 300.33 | 22.61 | 71.67 | 21.44 | 69.33 | 21.36 |
June | 145.00 | 23.27 | 149.33 | 23.84 | 41.17 | 23.69 |
July | 62.17 | 23.87 | 258.33 | 23.90 | 51.83 | 23.90 |
August | 87.50 | 23.88 | 263.83 | 23.90 | 70.67 | 23.90 |
September | 158.00 | 22.65 | 133.00 | 23.00 | 44.67 | 21.21 |
October | 300.00 | 21.34 | 249.50 | 21.10 | 249.50 | 21.10 |
November | 288.00 | 21.14 | 262.17 | 21.06 | 262.17 | 21.06 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 2838.00 | 21.63 | 2830.33 | 21.82 | 2231.83 | 21.27 |
Minimum of Months | 62.17 | 21.01 | 71.67 | 21.01 | 41.17 | 21.01 |
Maximum of Months | 324.00 | 23.88 | 324.00 | 23.90 | 324.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.209635E+09 | 48018172.73 | 19.54 | 0.152884E+09 | 56750323.07 | 0.00 | 1.00 | 18-APR-17:41 | 0.00 | 01-APR-00:10 | 18882.01 | 18-APR-17:41 | 13788.33 | 18-APR-17:41 | 5093.68 | 18-APR-17:41 | 3973.95 | 18-APR-17:41 | 0.00 | 01-APR-00:10 |
May | 0.528138E+09 | 0.118988E+09 | 62.68 | 0.408132E+09 | 0.120005E+09 | 0.00 | 1.00 | 30-MAY-19:31 | 0.00 | 01-MAY-00:05 | 19086.79 | 30-MAY-19:31 | 14164.01 | 31-MAY-20:00 | 6404.12 | 30-MAY-19:38 | 3992.48 | 30-MAY-19:31 | 0.00 | 01-MAY-00:05 |
June | 0.503142E+10 | 0.108818E+10 | 235.84 | 0.367912E+10 | 0.135229E+10 | 0.00 | 1.00 | 08-JUN-17:20 | 0.00 | 01-JUN-00:10 | 21028.98 | 26-JUN-00:01 | 16258.99 | 20-JUN-17:11 | 10819.52 | 14-JUN-17:12 | 4282.30 | 26-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.807399E+10 | 0.170964E+10 | 297.60 | 0.550549E+10 | 0.256850E+10 | 0.00 | 1.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:05 | 21081.46 | 03-JUL-21:23 | 15852.92 | 18-JUL-17:10 | 11523.78 | 15-JUL-01:57 | 4298.92 | 03-JUL-21:03 | 0.00 | 01-JUL-00:05 |
August | 0.791541E+10 | 0.168976E+10 | 304.46 | 0.543850E+10 | 0.247690E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:05 | 21540.07 | 04-AUG-00:23 | 16353.06 | 07-AUG-17:10 | 12857.62 | 04-AUG-05:58 | 4357.67 | 04-AUG-00:23 | 0.00 | 01-AUG-00:05 |
September | 0.305807E+10 | 0.672668E+09 | 172.12 | 0.258136E+10 | 0.476711E+09 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:05 | 19250.94 | 12-SEP-02:50 | 16829.42 | 01-SEP-17:10 | 9594.07 | 12-SEP-03:30 | 4066.64 | 06-SEP-17:10 | 0.00 | 01-SEP-00:05 |
October | 1076198.35 | 252062.36 | 1.33 | 1076198.35 | 0.00 | 0.00 | 0.08 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 610.68 | 20-OCT-15:00 | 610.68 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 142.54 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.248177E+11 | 0.532750E+10 | 1093.56 | 0.177666E+11 | 0.705117E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.807399E+10 | 0.170964E+10 | 304.46 | 0.550549E+10 | 0.256850E+10 | 0.00 | 1.00 | 0.00 | 21540.07 | 16829.42 | 12857.62 | 4357.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 37911691.53 | 9459762.74 | 3.00 | 24349646.81 | 13562044.72 | 0.00 | 0.20 | 18-APR-15:00 | 0.00 | 01-APR-00:10 | 5565.66 | 18-APR-15:00 | 3651.59 | 18-APR-15:00 | 1914.06 | 18-APR-15:00 | 1389.20 | 18-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.398010E+09 | 98877915.94 | 12.50 | 0.304875E+09 | 93135043.71 | 0.00 | 0.53 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 14358.14 | 31-MAY-15:10 | 11759.31 | 31-MAY-15:10 | 2763.39 | 31-MAY-11:50 | 3575.55 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.724886E+10 | 0.169971E+10 | 147.93 | 0.515997E+10 | 0.208888E+10 | 0.00 | 1.00 | 24-JUN-17:41 | 0.00 | 01-JUN-00:10 | 61655.02 | 26-JUN-20:11 | 41716.91 | 26-JUN-17:08 | 26471.28 | 26-JUN-20:25 | 13983.73 | 25-JUN-14:43 | 0.00 | 01-JUN-00:10 |
July | 0.115924E+11 | 0.261839E+10 | 205.27 | 0.756689E+10 | 0.402549E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:05 | 64606.55 | 03-JUL-20:12 | 43789.73 | 18-JUL-17:11 | 33450.30 | 03-JUL-20:12 | 14077.98 | 03-JUL-19:51 | 0.00 | 01-JUL-00:05 |
August | 0.937228E+10 | 0.215145E+10 | 187.50 | 0.629150E+10 | 0.308078E+10 | 0.00 | 1.00 | 01-AUG-18:31 | 0.00 | 01-AUG-00:05 | 66077.91 | 03-AUG-19:24 | 45200.82 | 09-AUG-17:21 | 36623.07 | 03-AUG-19:24 | 14249.87 | 03-AUG-19:02 | 0.00 | 01-AUG-00:05 |
September | 0.364789E+10 | 0.882958E+09 | 91.89 | 0.307693E+10 | 0.570959E+09 | 0.00 | 1.00 | 08-SEP-18:11 | 0.00 | 01-SEP-00:05 | 58186.23 | 11-SEP-17:21 | 46252.13 | 09-SEP-17:21 | 18472.26 | 11-SEP-17:29 | 13158.69 | 11-SEP-17:21 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.322973E+11 | 0.746084E+10 | 648.09 | 0.224245E+11 | 0.987281E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.115924E+11 | 0.261839E+10 | 205.27 | 0.756689E+10 | 0.402549E+10 | 0.00 | 1.00 | 0.00 | 66077.91 | 46252.13 | 36623.07 | 14249.87 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.07 | 312.97 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.21 | 243.50 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 75.06 | 146.34 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 165.03 | 97.09 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 181.58 | 56.77 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 232.16 | 48.61 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 255.09 | 45.50 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 223.01 | 54.21 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 162.38 | 86.65 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 88.31 | 108.63 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.36 | 182.00 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 17.86 | 274.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 125.30 | 137.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 17.86 | 45.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 255.09 | 312.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.07 | 312.97 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.21 | 243.50 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 75.06 | 146.34 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 165.03 | 97.09 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 181.58 | 56.77 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 232.16 | 48.61 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 255.09 | 45.50 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 223.01 | 54.21 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 162.38 | 86.65 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 88.31 | 108.63 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.36 | 182.00 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 17.86 | 274.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 125.30 | 137.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 17.86 | 45.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 255.09 | 312.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 198.53 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.32 | 156.85 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.47 | 92.86 | 0.00 | 0.00 | 744.00 |
April | 42.51 | 0.29 | 42.22 | 19.64 | 59.37 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 40.22 | 32.43 | 0.00 | 0.00 | 744.00 |
June | 64.59 | 5.83 | 58.76 | 55.05 | 26.60 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 52.36 | 25.06 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 46.38 | 31.03 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 26.51 | 51.80 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 9.58 | 66.50 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 1.97 | 113.08 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 170.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.75 | 85.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 25.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.59 | 5.83 | 58.76 | 55.05 | 198.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 198.53 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.32 | 156.85 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.47 | 92.86 | 0.00 | 0.00 | 744.00 |
April | 42.50 | 0.29 | 42.22 | 19.64 | 59.37 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 40.21 | 32.43 | 0.00 | 0.00 | 744.00 |
June | 64.58 | 5.83 | 58.76 | 55.05 | 26.60 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 52.36 | 25.06 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 46.37 | 31.03 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 26.51 | 51.80 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 9.58 | 66.50 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 1.97 | 113.08 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 170.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.75 | 85.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 25.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.58 | 5.83 | 58.76 | 55.05 | 198.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.90 | 14.79 | 19.11 | 8.24 | 211.16 | 3.33 | 0.00 | 744.00 |
February | 46.44 | 23.24 | 23.20 | 28.48 | 157.25 | 0.00 | 0.00 | 672.00 |
March | 72.90 | 34.87 | 38.02 | 78.75 | 83.49 | 16.50 | 0.00 | 744.00 |
April | 98.96 | 59.46 | 39.50 | 124.54 | 53.20 | 47.17 | 0.00 | 720.00 |
May | 118.89 | 66.79 | 52.10 | 161.65 | 37.19 | 31.50 | 0.00 | 744.00 |
June | 135.18 | 79.04 | 56.14 | 179.42 | 44.53 | 38.33 | 0.00 | 720.00 |
July | 136.22 | 83.79 | 52.43 | 175.36 | 53.66 | 25.00 | 0.00 | 744.00 |
August | 113.45 | 64.59 | 48.86 | 149.10 | 53.36 | 31.00 | 0.00 | 744.00 |
September | 88.17 | 51.18 | 36.99 | 109.26 | 72.16 | 13.00 | 0.00 | 720.00 |
October | 56.04 | 27.78 | 28.25 | 68.82 | 59.43 | 13.67 | 0.00 | 744.00 |
November | 33.44 | 12.39 | 21.05 | 26.94 | 104.41 | 0.00 | 0.00 | 720.00 |
December | 23.02 | 11.32 | 11.69 | 8.70 | 171.37 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 44.21 | 35.68 | 93.62 | 91.48 | 220.00 | 0.00 | 8760.00 |
Minimum of Months | 23.02 | 11.32 | 11.69 | 8.24 | 37.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.22 | 83.79 | 56.14 | 179.42 | 211.16 | 47.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51085671.68 | 0.838258E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119042E+09 | 0.589077E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.201035E+09 | 0.391945E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.427746E+09 | 0.251663E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.486340E+09 | 0.152056E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.601748E+09 | 0.125985E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683232E+09 | 0.121870E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.597318E+09 | 0.145186E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.420879E+09 | 0.224589E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.236519E+09 | 0.290944E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 78690210.54 | 0.471746E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 47847931.71 | 0.734170E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.395148E+10 | 0.433749E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 47847931.71 | 0.121870E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683232E+09 | 0.838258E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51085671.68 | 0.838258E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119042E+09 | 0.589077E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.201035E+09 | 0.391945E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.427746E+09 | 0.251663E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.486340E+09 | 0.152056E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.601748E+09 | 0.125985E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683232E+09 | 0.121870E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.597318E+09 | 0.145186E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.420879E+09 | 0.224589E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.236519E+09 | 0.290944E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 78690210.54 | 0.471746E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 47847931.71 | 0.734170E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.395148E+10 | 0.433749E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 47847931.71 | 0.121870E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.683232E+09 | 0.838258E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51785475.02 | 0.00 | 51785475.02 | 0.00 | 0.531748E+09 |
February | 59300287.05 | 0.00 | 59300287.05 | 776122.94 | 0.379449E+09 |
March | 98412437.69 | 2555.31 | 98409882.39 | 19998731.48 | 0.248705E+09 |
April | 0.110175E+09 | 742859.63 | 0.109432E+09 | 50897657.89 | 0.153895E+09 |
May | 0.148348E+09 | 5729827.66 | 0.142618E+09 | 0.107715E+09 | 86864596.90 |
June | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.142686E+09 | 68936771.13 |
July | 0.162282E+09 | 10865282.36 | 0.151417E+09 | 0.140237E+09 | 67126583.66 |
August | 0.136413E+09 | 2828771.71 | 0.133584E+09 | 0.124212E+09 | 83116603.25 |
September | 0.100963E+09 | 65724.61 | 0.100898E+09 | 68705977.89 | 0.134267E+09 |
October | 77497403.21 | 0.00 | 77497403.21 | 25648958.00 | 0.178108E+09 |
November | 52461463.12 | 0.00 | 52461463.12 | 5095535.99 | 0.293116E+09 |
December | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 0.456345E+09 |
Annual Sum or Average | 0.120021E+10 | 35337833.27 | 0.116487E+10 | 0.685973E+09 | 0.268168E+10 |
Minimum of Months | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 67126583.66 |
Maximum of Months | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.142686E+09 | 0.531748E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51783807.94 | 0.00 | 51783807.94 | 0.00 | 0.531748E+09 |
February | 59298441.20 | 0.00 | 59298441.20 | 775970.61 | 0.379450E+09 |
March | 98409312.96 | 2555.19 | 98406757.77 | 19997173.66 | 0.248706E+09 |
April | 0.110172E+09 | 742824.81 | 0.109429E+09 | 50895688.94 | 0.153896E+09 |
May | 0.148344E+09 | 5729559.10 | 0.142614E+09 | 0.107711E+09 | 86864402.95 |
June | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.142681E+09 | 68936465.02 |
July | 0.162277E+09 | 10864773.09 | 0.151412E+09 | 0.140232E+09 | 67125972.57 |
August | 0.136409E+09 | 2828639.12 | 0.133580E+09 | 0.124209E+09 | 83116154.94 |
September | 0.100960E+09 | 65721.53 | 0.100895E+09 | 68703647.59 | 0.134267E+09 |
October | 77494965.54 | 0.00 | 77494965.54 | 25647294.41 | 0.178108E+09 |
November | 52459712.13 | 0.00 | 52459712.13 | 5095093.14 | 0.293116E+09 |
December | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 0.456345E+09 |
Annual Sum or Average | 0.120017E+10 | 35336176.94 | 0.116484E+10 | 0.685948E+09 | 0.268168E+10 |
Minimum of Months | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 67125972.57 |
Maximum of Months | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.142681E+09 | 0.531748E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90802662.93 | 39605375.32 | 51197287.61 | 22074398.03 | 0.565567E+09 |
February | 0.112338E+09 | 56216844.26 | 56121294.68 | 68903074.22 | 0.380410E+09 |
March | 0.195250E+09 | 93404374.13 | 0.101845E+09 | 0.210921E+09 | 0.223622E+09 |
April | 0.256510E+09 | 0.154131E+09 | 0.102379E+09 | 0.322817E+09 | 0.137893E+09 |
May | 0.318426E+09 | 0.178891E+09 | 0.139535E+09 | 0.432965E+09 | 99601517.91 |
June | 0.350385E+09 | 0.204882E+09 | 0.145503E+09 | 0.465068E+09 | 0.115412E+09 |
July | 0.364860E+09 | 0.224425E+09 | 0.140435E+09 | 0.469697E+09 | 0.143711E+09 |
August | 0.303854E+09 | 0.172997E+09 | 0.130857E+09 | 0.399354E+09 | 0.142908E+09 |
September | 0.228531E+09 | 0.132647E+09 | 95884072.80 | 0.283216E+09 | 0.187042E+09 |
October | 0.150086E+09 | 74418186.33 | 75667395.13 | 0.184332E+09 | 0.159179E+09 |
November | 86685340.10 | 32121077.36 | 54564262.75 | 69833637.91 | 0.270638E+09 |
December | 61643990.22 | 30328167.30 | 31315822.91 | 23327037.92 | 0.459004E+09 |
Annual Sum or Average | 0.251937E+10 | 0.139407E+10 | 0.112530E+10 | 0.295251E+10 | 0.288499E+10 |
Minimum of Months | 61643990.22 | 30328167.30 | 31315822.91 | 22074398.03 | 99601517.91 |
Maximum of Months | 0.364860E+09 | 0.224425E+09 | 0.145503E+09 | 0.469697E+09 | 0.565567E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.89 | 1006.74 | 179.97 | 57.33 | 122.64 | 0.00 | 0.00 |
February | 77.98 | 779.62 | 254.55 | 100.81 | 153.74 | 0.00 | 0.00 |
March | 154.10 | 467.43 | 320.27 | 91.94 | 228.33 | 0.00 | 0.00 |
April | 364.88 | 308.49 | 444.78 | 178.37 | 266.41 | 0.00 | 0.00 |
May | 442.79 | 177.61 | 471.46 | 148.36 | 323.10 | 0.00 | 0.00 |
June | 572.56 | 148.56 | 551.71 | 194.39 | 357.33 | 0.00 | 0.00 |
July | 613.65 | 139.89 | 575.83 | 224.14 | 351.69 | 0.00 | 0.00 |
August | 538.12 | 169.82 | 498.16 | 183.35 | 314.81 | 0.00 | 0.00 |
September | 375.44 | 274.57 | 399.53 | 152.54 | 246.99 | 0.00 | 0.00 |
October | 190.42 | 344.91 | 282.96 | 100.34 | 182.62 | 0.00 | 0.00 |
November | 56.49 | 582.02 | 175.13 | 50.02 | 125.12 | 0.00 | 0.00 |
December | 23.50 | 876.75 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Annual Sum or Average | 287.08 | 438.13 | 357.50 | 127.63 | 229.87 | 0.00 | 0.00 |
Minimum of Months | 21.89 | 139.89 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Maximum of Months | 613.65 | 1006.74 | 575.83 | 224.14 | 357.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 82.42 | 2111.59 | 339.02 | 147.87 | 191.15 | 0.00 | 0.00 |
February | 284.82 | 1572.46 | 464.36 | 232.38 | 231.98 | 0.00 | 0.00 |
March | 787.49 | 834.91 | 728.98 | 348.73 | 380.25 | 0.00 | 0.00 |
April | 1245.44 | 531.99 | 989.62 | 594.64 | 394.98 | 0.00 | 0.00 |
May | 1616.50 | 371.87 | 1188.87 | 667.90 | 520.96 | 0.00 | 0.00 |
June | 1794.24 | 445.26 | 1351.79 | 790.44 | 561.36 | 0.00 | 0.00 |
July | 1753.65 | 536.56 | 1362.23 | 837.91 | 524.32 | 0.00 | 0.00 |
August | 1491.02 | 533.56 | 1134.46 | 645.90 | 488.56 | 0.00 | 0.00 |
September | 1092.65 | 721.61 | 881.68 | 511.75 | 369.92 | 0.00 | 0.00 |
October | 688.22 | 594.31 | 560.36 | 277.85 | 282.51 | 0.00 | 0.00 |
November | 269.42 | 1044.13 | 334.43 | 123.92 | 210.51 | 0.00 | 0.00 |
December | 87.05 | 1713.73 | 230.15 | 113.23 | 116.92 | 0.00 | 0.00 |
Annual Sum or Average | 936.23 | 914.82 | 798.89 | 442.06 | 356.83 | 0.00 | 0.00 |
Minimum of Months | 82.42 | 371.87 | 230.15 | 113.23 | 116.92 | 0.00 | 0.00 |
Maximum of Months | 1794.24 | 2111.59 | 1362.23 | 837.91 | 561.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58623554.18 | 0.269646E+10 | 0.482020E+09 | 0.153541E+09 | 0.328480E+09 | 0.00 | 0.00 |
February | 0.188640E+09 | 0.188606E+10 | 0.615804E+09 | 0.243884E+09 | 0.371920E+09 | 0.00 | 0.00 |
March | 0.412733E+09 | 0.125197E+10 | 0.857814E+09 | 0.246255E+09 | 0.611559E+09 | 0.00 | 0.00 |
April | 0.945780E+09 | 0.799610E+09 | 0.115287E+10 | 0.462335E+09 | 0.690537E+09 | 0.00 | 0.00 |
May | 0.118596E+10 | 0.475699E+09 | 0.126276E+10 | 0.397373E+09 | 0.865383E+09 | 0.00 | 0.00 |
June | 0.148408E+10 | 0.385056E+09 | 0.143004E+10 | 0.503851E+09 | 0.926192E+09 | 0.00 | 0.00 |
July | 0.164361E+10 | 0.374668E+09 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
August | 0.144131E+10 | 0.454856E+09 | 0.133428E+10 | 0.491098E+09 | 0.843181E+09 | 0.00 | 0.00 |
September | 0.973136E+09 | 0.711681E+09 | 0.103558E+10 | 0.395393E+09 | 0.640190E+09 | 0.00 | 0.00 |
October | 0.510031E+09 | 0.923801E+09 | 0.757881E+09 | 0.268739E+09 | 0.489143E+09 | 0.00 | 0.00 |
November | 0.146430E+09 | 0.150858E+10 | 0.453948E+09 | 0.129647E+09 | 0.324301E+09 | 0.00 | 0.00 |
December | 62940095.53 | 0.234827E+10 | 0.348904E+09 | 0.132507E+09 | 0.216397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.905327E+10 | 0.138167E+11 | 0.112742E+11 | 0.402496E+10 | 0.724924E+10 | 0.00 | 0.00 |
Minimum of Months | 58623554.18 | 0.374668E+09 | 0.348904E+09 | 0.129647E+09 | 0.216397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164361E+10 | 0.269646E+10 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220744E+09 | 0.565567E+10 | 0.908027E+09 | 0.396054E+09 | 0.511973E+09 | 0.00 | 0.00 |
February | 0.689031E+09 | 0.380410E+10 | 0.112338E+10 | 0.562168E+09 | 0.561213E+09 | 0.00 | 0.00 |
March | 0.210920E+10 | 0.223622E+10 | 0.195250E+10 | 0.934044E+09 | 0.101845E+10 | 0.00 | 0.00 |
April | 0.322817E+10 | 0.137893E+10 | 0.256510E+10 | 0.154131E+10 | 0.102379E+10 | 0.00 | 0.00 |
May | 0.432965E+10 | 0.996015E+09 | 0.318426E+10 | 0.178891E+10 | 0.139535E+10 | 0.00 | 0.00 |
June | 0.465068E+10 | 0.115412E+10 | 0.350385E+10 | 0.204882E+10 | 0.145503E+10 | 0.00 | 0.00 |
July | 0.469697E+10 | 0.143711E+10 | 0.364860E+10 | 0.224425E+10 | 0.140435E+10 | 0.00 | 0.00 |
August | 0.399354E+10 | 0.142907E+10 | 0.303854E+10 | 0.172997E+10 | 0.130857E+10 | 0.00 | 0.00 |
September | 0.283214E+10 | 0.187042E+10 | 0.228531E+10 | 0.132647E+10 | 0.958841E+09 | 0.00 | 0.00 |
October | 0.184332E+10 | 0.159179E+10 | 0.150086E+10 | 0.744182E+09 | 0.756674E+09 | 0.00 | 0.00 |
November | 0.698336E+09 | 0.270638E+10 | 0.866853E+09 | 0.321211E+09 | 0.545643E+09 | 0.00 | 0.00 |
December | 0.233150E+09 | 0.459004E+10 | 0.616440E+09 | 0.303282E+09 | 0.313158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295249E+11 | 0.288499E+11 | 0.251937E+11 | 0.139407E+11 | 0.112530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220744E+09 | 0.996015E+09 | 0.616440E+09 | 0.303282E+09 | 0.313158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469697E+10 | 0.565567E+10 | 0.364860E+10 | 0.224425E+10 | 0.145503E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106525E+10 | -977157129.4 | 0.00 | 0.00 | 744.00 | 0.00 | -88094215.0 | 58.99 | 0.00 | 0.00 |
February | 0.995082E+09 | -915651273.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79430465.9 | 58.99 | 0.00 | 0.00 |
March | 0.114669E+10 | -.105957E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87126117.4 | 58.99 | 0.00 | 0.00 |
April | 0.102875E+10 | -946411935.7 | 0.00 | 0.00 | 720.00 | 0.00 | -82334112.6 | 58.99 | 0.00 | 0.00 |
May | 0.100601E+10 | -926228133.1 | 0.00 | 0.00 | 744.00 | 0.00 | -79786591.6 | 58.99 | 0.00 | 0.00 |
June | 0.933689E+09 | -860522029.2 | 0.00 | 0.00 | 720.00 | 0.00 | -73166974.2 | 58.99 | 0.00 | 0.00 |
July | 0.858756E+09 | -784694833.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74061122.4 | 58.99 | 0.00 | 0.00 |
August | 0.895008E+09 | -820492923.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74514859.8 | 58.99 | 0.00 | 0.00 |
September | 0.847094E+09 | -773125880.1 | 0.00 | 0.00 | 720.00 | 0.00 | -73968026.1 | 58.99 | 0.00 | 0.00 |
October | 0.898891E+09 | -814217456.5 | 0.00 | 0.00 | 744.00 | 0.00 | -84673400.1 | 58.99 | 0.00 | 0.00 |
November | 0.919967E+09 | -835944520.6 | 0.00 | 0.00 | 720.00 | 0.00 | -84022357.4 | 58.99 | 0.00 | 0.00 |
December | 0.101719E+10 | -929152211.2 | 0.00 | 0.00 | 744.00 | 0.00 | -88037685.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.116124E+11 | -.106432E+11 | 8760.00 | -969215928.1 | 58.99 | |||||
Minimum of Months | 0.847094E+09 | -.105957E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88094215.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114669E+10 | -773125880.1 | 0.00 | 0.00 | 744.00 | 0.00 | -73166974.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.95 | 0.88 | 01-JAN-10:30 | 121.43 | 9.09 | 0.00 | 30.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.95 | 0.88 | 03-FEB-11:30 | 130.42 | 9.21 | 0.00 | 58.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.92 | 0.88 | 01-MAR-08:00 | 213.84 | 11.75 | 0.00 | 164.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.92 | 0.88 | 02-APR-14:39 | 238.45 | 11.74 | 0.00 | 188.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.91 | 0.88 | 01-MAY-07:30 | 793.65 | 12.52 | 0.00 | 263.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.91 | 0.88 | 01-JUN-07:40 | 1977.93 | 12.86 | 0.00 | 281.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.91 | 0.88 | 01-JUL-07:00 | 1821.11 | 13.57 | 20.00 | 276.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.91 | 0.88 | 01-AUG-08:30 | 1096.91 | 12.96 | 14.67 | 259.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.92 | 0.88 | 01-SEP-07:40 | 211.37 | 11.64 | 0.00 | 160.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.94 | 0.88 | 02-OCT-09:20 | 161.78 | 10.26 | 0.00 | 92.17 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.94 | 0.88 | 01-NOV-10:09 | 138.62 | 9.73 | 0.00 | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.98 | 0.88 | 18-DEC-12:30 | 78.97 | 6.93 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.93 | 710.21 | 11.47 | 34.67 | 1825.33 | ||||||
Minimum of Months | 186.17 | 0.91 | 0.88 | 78.97 | 6.93 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.98 | 0.88 | 1977.93 | 13.57 | 20.00 | 281.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.83 | 0.78 | 01-JAN-10:30 | 812.15 | 23.05 | 72.83 | 111.67 | 785.37 | 22.80 | 91.67 | 191.00 |
February | 226.83 | 0.83 | 0.78 | 01-FEB-11:00 | 1288.33 | 22.81 | 71.17 | 135.17 | 1416.95 | 24.51 | 105.17 | 203.67 |
March | 334.33 | 0.81 | 0.78 | 01-MAR-09:09 | 629.97 | 19.33 | 59.00 | 203.50 | 1821.87 | 24.72 | 181.33 | 289.67 |
April | 285.17 | 0.81 | 0.78 | 02-APR-14:50 | 501.60 | 17.82 | 23.00 | 192.67 | 3483.26 | 25.99 | 148.33 | 319.50 |
May | 428.67 | 0.81 | 0.78 | 01-MAY-07:10 | 463.87 | 17.04 | 0.00 | 297.00 | 1928.57 | 22.59 | 203.83 | 373.00 |
June | 400.67 | 0.80 | 0.78 | 01-JUN-06:10 | 532.36 | 17.29 | 0.50 | 345.67 | 2539.03 | 23.13 | 206.00 | 379.50 |
July | 414.00 | 0.80 | 0.78 | 01-JUL-06:10 | 521.50 | 17.59 | 6.50 | 337.83 | 2887.71 | 23.47 | 216.50 | 389.00 |
August | 410.83 | 0.81 | 0.78 | 01-AUG-08:39 | 491.82 | 17.52 | 19.83 | 282.17 | 2350.77 | 23.95 | 211.50 | 355.50 |
September | 326.50 | 0.81 | 0.78 | 01-SEP-07:40 | 469.27 | 17.85 | 29.50 | 202.50 | 2501.04 | 25.84 | 168.17 | 307.83 |
October | 325.17 | 0.82 | 0.78 | 01-OCT-11:20 | 895.73 | 21.28 | 80.83 | 180.00 | 1409.35 | 24.29 | 155.00 | 254.67 |
November | 254.83 | 0.83 | 0.78 | 01-NOV-09:00 | 580.07 | 21.14 | 70.17 | 111.67 | 896.88 | 23.04 | 108.50 | 198.67 |
December | 186.17 | 0.85 | 0.78 | 01-DEC-14:09 | 560.10 | 21.45 | 48.50 | 57.50 | 562.76 | 20.24 | 27.33 | 131.67 |
Annual Sum or Average | 3807.33 | 0.81 | 616.31 | 19.04 | 481.83 | 2457.33 | 2023.86 | 23.80 | 1823.33 | 3393.67 | ||
Minimum of Months | 186.17 | 0.80 | 0.78 | 463.87 | 17.04 | 0.00 | 57.50 | 562.76 | 20.24 | 27.33 | 131.67 | |
Maximum of Months | 428.67 | 0.85 | 0.78 | 1288.33 | 23.05 | 80.83 | 345.67 | 3483.26 | 25.99 | 216.50 | 389.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143498E+11 | 26105.00 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108767E+11 | 26105.00 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.831219E+10 | 26105.00 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422148E+10 | 26105.00 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646880E+09 | 26105.00 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45761995.80 | 26105.00 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253365E+09 | 26105.00 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222414E+10 | 26105.00 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611127E+10 | 26105.00 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109391E+11 | 26105.00 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579807E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143498E+11 | 26105.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.724535E+11 | 82271.62 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.513336E+11 | 82271.62 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311601E+11 | 82271.62 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113912E+11 | 82271.62 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695664E+09 | 82271.62 | 02-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272253E+09 | 57797.58 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.514361E+10 | 82271.62 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304339E+11 | 82271.62 | 10-NOV-02:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571890E+11 | 82271.62 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260073E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.724535E+11 | 82271.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297058E+12 | 268809.81 | 18-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199791E+12 | 260926.15 | 01-FEB-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107338E+12 | 193943.38 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242463E+11 | 112088.65 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406141E+09 | 19007.40 | 02-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393071E+10 | 29335.22 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114049E+12 | 186580.91 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227645E+12 | 268809.81 | 08-DEC-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974464E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.297058E+12 | 268809.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209635E+09 | 0.152884E+09 | 18882.01 | 18-APR-17:41 | 13788.33 | 0.00 |
May | 0.00 | 0.00 | 0.528138E+09 | 0.408132E+09 | 19086.79 | 30-MAY-19:31 | 12761.22 | 0.00 |
June | 0.00 | 0.00 | 0.503142E+10 | 0.367912E+10 | 21028.98 | 26-JUN-00:01 | 10963.40 | 0.00 |
July | 0.00 | 0.00 | 0.807399E+10 | 0.550549E+10 | 21081.46 | 03-JUL-21:23 | 9997.30 | 0.00 |
August | 0.00 | 0.00 | 0.791541E+10 | 0.543850E+10 | 21540.07 | 04-AUG-00:23 | 9534.17 | 0.00 |
September | 0.00 | 0.00 | 0.305807E+10 | 0.258136E+10 | 19250.94 | 12-SEP-02:50 | 9772.09 | 0.00 |
October | 0.00 | 0.00 | 1076198.35 | 1076198.35 | 610.68 | 20-OCT-15:00 | 610.68 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.248177E+11 | 0.177666E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.807399E+10 | 0.550549E+10 | 21540.07 | 13788.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 37911691.53 | 24349646.81 | 5565.66 | 18-APR-15:00 | 3651.59 | 0.00 |
May | 0.00 | 0.00 | 0.398010E+09 | 0.304875E+09 | 14358.14 | 31-MAY-15:10 | 11759.31 | 0.00 |
June | 0.00 | 0.00 | 0.724886E+10 | 0.515997E+10 | 61655.02 | 26-JUN-20:11 | 35643.84 | 0.00 |
July | 0.00 | 0.00 | 0.115924E+11 | 0.756689E+10 | 64606.55 | 03-JUL-20:12 | 31156.26 | 0.00 |
August | 0.00 | 0.00 | 0.937228E+10 | 0.629150E+10 | 66077.91 | 03-AUG-19:24 | 29454.84 | 0.00 |
September | 0.00 | 0.00 | 0.364789E+10 | 0.307693E+10 | 58186.23 | 11-SEP-17:21 | 39797.54 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.322973E+11 | 0.224245E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115924E+11 | 0.756689E+10 | 66077.91 | 39797.54 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168706E+10 | 0.08 | 630.16 | 01-JAN-00:02 | 0.08 |
February | 0.149149E+10 | 0.08 | 630.16 | 01-FEB-00:01 | 0.08 |
March | 0.127223E+10 | 0.06 | 630.16 | 01-MAR-00:01 | 0.08 |
April | 0.502488E+09 | 0.02 | 630.16 | 01-APR-00:10 | 0.08 |
May | 21929493.04 | 0.00 | 630.16 | 01-MAY-21:30 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.212111E+09 | 0.01 | 630.16 | 08-OCT-05:03 | 0.08 |
November | 0.108560E+10 | 0.05 | 630.16 | 01-NOV-00:10 | 0.08 |
December | 0.167950E+10 | 0.08 | 630.16 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.795240E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168706E+10 | 0.08 | 630.16 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119505E+10 | 0.75 | 1039.11 | 02-JAN-09:20 | 0.96 |
February | 0.106449E+10 | 0.67 | 1039.11 | 01-FEB-07:30 | 0.96 |
March | 0.118512E+10 | 0.55 | 1039.11 | 01-MAR-07:06 | 0.96 |
April | 0.106365E+10 | 0.43 | 1039.11 | 01-APR-07:00 | 0.95 |
May | 0.108342E+10 | 0.38 | 1039.11 | 01-MAY-06:10 | 0.95 |
June | 0.120925E+10 | 0.45 | 1039.11 | 01-JUN-09:00 | 0.95 |
July | 0.134003E+10 | 0.49 | 1039.11 | 01-JUL-08:30 | 0.94 |
August | 0.141435E+10 | 0.53 | 1039.11 | 01-AUG-06:25 | 0.94 |
September | 0.114635E+10 | 0.42 | 1039.11 | 01-SEP-07:10 | 0.94 |
October | 0.104992E+10 | 0.38 | 1039.11 | 02-OCT-09:00 | 0.95 |
November | 0.104815E+10 | 0.49 | 1039.11 | 01-NOV-09:00 | 0.95 |
December | 0.113829E+10 | 0.61 | 1039.11 | 01-DEC-07:30 | 0.95 |
Annual Sum or Average | 0.139381E+11 | 0.51 | |||
Minimum of Months | 0.104815E+10 | 0.38 | 1039.11 | 0.94 | |
Maximum of Months | 0.141435E+10 | 0.75 | 1039.11 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.366823E+10 | 0.82 | 2343.82 | 02-JAN-08:00 | 0.92 |
February | 0.313341E+10 | 0.81 | 2343.82 | 01-FEB-07:10 | 0.93 |
March | 0.317551E+10 | 0.75 | 2343.82 | 01-MAR-07:10 | 0.92 |
April | 0.260222E+10 | 0.59 | 2343.82 | 01-APR-06:20 | 0.92 |
May | 0.243343E+10 | 0.37 | 2343.82 | 01-MAY-06:40 | 0.92 |
June | 0.250698E+10 | 0.39 | 2343.82 | 09-JUN-10:10 | 0.91 |
July | 0.243870E+10 | 0.37 | 2343.82 | 01-JUL-08:70 | 0.91 |
August | 0.253513E+10 | 0.37 | 2343.82 | 01-AUG-08:50 | 0.90 |
September | 0.234026E+10 | 0.37 | 2343.82 | 01-SEP-09:50 | 0.91 |
October | 0.247105E+10 | 0.53 | 2343.82 | 06-OCT-06:20 | 0.92 |
November | 0.288587E+10 | 0.69 | 2343.82 | 04-NOV-06:10 | 0.92 |
December | 0.342615E+10 | 0.81 | 2343.82 | 01-DEC-07:30 | 0.92 |
Annual Sum or Average | 0.336170E+11 | 0.57 | |||
Minimum of Months | 0.234026E+10 | 0.37 | 2343.82 | 0.90 | |
Maximum of Months | 0.366823E+10 | 0.82 | 2343.82 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.04 | 0.00 |
February | 3.21 | 0.00 |
March | 3.07 | 0.00 |
April | 1.70 | 0.22 |
May | 0.67 | 0.17 |
June | 11.02 | 0.06 |
July | 23.41 | 0.03 |
August | 20.85 | 0.02 |
September | 10.54 | 0.03 |
October | 0.47 | 0.56 |
November | 2.31 | 0.01 |
December | 3.01 | 0.02 |
Annual Sum or Average | 83.29 | 0.04 |
Minimum of Months | 0.47 | 0.00 |
Maximum of Months | 23.41 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.91 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.19 | 0.00 |
July | 1.05 | 0.00 |
August | 0.55 | 0.00 |
September | 0.39 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.64 | 0.00 |
Annual Sum or Average | 3.73 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.05 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.17 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119505E+10 | 0.201806E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106449E+10 | 0.153848E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118512E+10 | 0.120031E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111167E+10 | 0.616611E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.120241E+10 | 0.948947E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.229743E+10 | 67896036.63 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.304966E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310411E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181902E+10 | 0.375519E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105017E+10 | 0.328268E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.104815E+10 | 0.882269E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113829E+10 | 0.156003E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192656E+11 | 0.828327E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104815E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310411E+10 | 0.201806E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.366823E+10 | 0.100317E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.313341E+10 | 0.716454E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.317551E+10 | 0.446726E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.261168E+10 | 0.164995E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.253231E+10 | 0.102118E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.420670E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.505709E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.468658E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.322322E+10 | 0.408653E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.247105E+10 | 0.762176E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.288587E+10 | 0.431510E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.342615E+10 | 0.801889E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.410778E+11 | 0.365526E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.247105E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.505709E+10 | 0.100317E+12 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119505E+10 | 0.00 | 0.143498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106449E+10 | 0.00 | 0.108767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118512E+10 | 0.00 | 0.831219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106365E+10 | 0.209635E+09 | 0.422148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108342E+10 | 0.528138E+09 | 0.646880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120925E+10 | 0.503142E+10 | 45761995.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134003E+10 | 0.807399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141435E+10 | 0.791541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114635E+10 | 0.305807E+10 | 0.253365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104992E+10 | 1076198.35 | 0.222414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104815E+10 | 0.00 | 0.611127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113829E+10 | 0.00 | 0.109391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139381E+11 | 0.248177E+11 | 0.579807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141435E+10 | 0.807399E+10 | 0.143498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.366823E+10 | 0.00 | 0.724535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313341E+10 | 0.00 | 0.513336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317551E+10 | 0.00 | 0.311601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260222E+10 | 37911691.53 | 0.113912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.243343E+10 | 0.398010E+09 | 0.695664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250698E+10 | 0.724886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243870E+10 | 0.115924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.253513E+10 | 0.937228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234026E+10 | 0.364789E+10 | 0.272253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247105E+10 | 0.00 | 0.514361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288587E+10 | 0.00 | 0.304339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342615E+10 | 0.00 | 0.571890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336170E+11 | 0.322973E+11 | 0.260073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.234026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366823E+10 | 0.115924E+11 | 0.724535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.119505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106365E+10 | 0.00 | 0.00 | 0.00 | 48018172.73 | 0.00 | 0.616611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108342E+10 | 0.00 | 0.00 | 0.00 | 0.118988E+09 | 0.00 | 0.948947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120925E+10 | 0.00 | 0.00 | 0.00 | 0.108818E+10 | 0.00 | 67896036.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134003E+10 | 0.00 | 0.00 | 0.00 | 0.170964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141435E+10 | 0.00 | 0.00 | 0.00 | 0.168976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114635E+10 | 0.00 | 0.00 | 0.00 | 0.672668E+09 | 0.00 | 0.375519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104992E+10 | 0.00 | 0.00 | 0.00 | 252062.36 | 0.00 | 0.328268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139381E+11 | 0.00 | 0.00 | 0.00 | 0.532750E+10 | 0.00 | 0.828327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.104815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141435E+10 | 0.00 | 0.00 | 0.00 | 0.170964E+10 | 0.00 | 0.201806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.366823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260222E+10 | 0.00 | 0.00 | 0.00 | 9459762.74 | 0.00 | 0.164995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.243343E+10 | 0.00 | 0.00 | 0.00 | 98877915.94 | 0.00 | 0.102118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250698E+10 | 0.00 | 0.00 | 0.00 | 0.169971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243870E+10 | 0.00 | 0.00 | 0.00 | 0.261839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.253513E+10 | 0.00 | 0.00 | 0.00 | 0.215145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234026E+10 | 0.00 | 0.00 | 0.00 | 0.882958E+09 | 0.00 | 0.408653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336170E+11 | 0.00 | 0.00 | 0.00 | 0.746084E+10 | 0.00 | 0.365526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.234026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366823E+10 | 0.00 | 0.00 | 0.00 | 0.261839E+10 | 0.00 | 0.100317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368477E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285454E+10 | 0.00 | 0.00 | 0.13 |
March | 8055578.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228991E+10 | 0.00 | 0.00 | 0.13 |
April | 0.182937E+09 | 43954629.69 | 17324.46 | 60185.38 | 10905108.42 | 0.133035E+10 | 62106665.11 | 545.31 | 0.14 |
May | 0.506370E+09 | 54841199.39 | 0.00 | 340161.43 | 2519556.26 | 0.132173E+09 | 0.417213E+09 | 0.00 | 0.22 |
June | 0.163112E+09 | 0.744335E+09 | 0.00 | 3206613.03 | 31296.06 | 5585331.17 | 0.112458E+10 | 0.00 | 0.53 |
July | 7295916.29 | 0.124228E+10 | 0.00 | 4237659.91 | 126628.05 | 0.00 | 0.109322E+10 | 0.00 | 0.68 |
August | 9240596.19 | 0.116860E+10 | 0.00 | 5274577.88 | 4870096.63 | 0.00 | 0.136722E+10 | 0.00 | 0.74 |
September | 0.302982E+09 | 0.226705E+09 | 0.00 | 3438461.44 | 0.00 | 0.101454E+09 | 0.130777E+10 | 0.00 | 0.44 |
October | 0.407045E+09 | 0.00 | 0.00 | 884.46 | 0.00 | 0.933810E+09 | 4979281.81 | 0.00 | 0.13 |
November | 0.161164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189185E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305930E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.174820E+10 | 0.348072E+10 | 17324.46 | 16558543.53 | 18452685.41 | 0.162837E+11 | 0.537709E+10 | 545.31 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.506370E+09 | 0.124228E+10 | 17324.46 | 5274577.88 | 10905108.42 | 0.368477E+10 | 0.136722E+10 | 545.31 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121986E+11 | 0.00 | 0.00 | 0.17 |
February | 0.691425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851878E+10 | 0.00 | 0.00 | 0.18 |
March | 0.179211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486247E+10 | 0.00 | 0.00 | 0.19 |
April | 0.282539E+10 | 3270271.84 | 0.00 | 0.00 | 96025679.73 | 0.147960E+10 | 0.00 | 0.00 | 0.18 |
May | 0.235360E+10 | 64662879.52 | 0.00 | 8580.62 | 25959002.48 | 35345975.79 | 478575.25 | 0.00 | 0.19 |
June | 0.136776E+10 | 0.103502E+10 | 0.00 | 2509334.59 | 2754146.07 | 0.00 | 0.145146E+10 | 0.00 | 0.35 |
July | 0.503871E+09 | 0.207444E+10 | 0.00 | 5930336.54 | 0.00 | 0.00 | 0.201554E+10 | 0.00 | 0.47 |
August | 0.514517E+09 | 0.158065E+10 | 0.00 | 4455734.36 | 1038353.94 | 0.00 | 0.222924E+10 | 0.00 | 0.45 |
September | 0.220773E+10 | 0.426560E+09 | 0.00 | 1675622.00 | 0.00 | 19862040.86 | 0.861517E+09 | 0.00 | 0.26 |
October | 0.325094E+10 | 0.00 | 0.00 | 0.00 | 4328679.25 | 0.291508E+09 | 0.00 | 0.00 | 0.18 |
November | 0.154523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455713E+10 | 0.00 | 0.00 | 0.17 |
December | 0.371674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946145E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.176336E+11 | 0.518461E+10 | 0.00 | 14579608.10 | 0.130106E+09 | 0.414247E+11 | 0.655823E+10 | 0.00 | 0.25 |
Minimum of Months | 0.209329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.325094E+10 | 0.207444E+10 | 0.00 | 5930336.54 | 96025679.73 | 0.121986E+11 | 0.222924E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |