Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2167.48 | 448.28 | 448.28 |
Net Site Energy | 2167.48 | 448.28 | 448.28 |
Total Source Energy | 4115.38 | 851.14 | 851.14 |
Net Source Energy | 4115.38 | 851.14 | 851.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1319.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 847.73 | 1319.75 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1319.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.32 | 272.95 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 175.33 | 272.95 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.32 | 272.95 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 175.33 | 272.95 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 847.731 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 847.731 | 100.00 |
Total On-Site and Utility Electric Sources | 847.731 | 100.00 |
Total Electricity End Uses | 847.731 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 64.50 |
Time Setpoint Not Met During Occupied Cooling | 2.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1976.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUL-14:39 | 07-FEB-08:09 | - | - | - | 12-AUG-11:00 |
Heating | 0.00 | 409264.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14988.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6099.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1766.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 68587.12 | 409264.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 409264.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14988.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3794.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1766.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1430.61 | 0.00 | 0.00 | 0.00 |
Cooling | 52.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 188.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2684.76 | 1430.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 295.88 | 0.00 | 0.00 | 0.00 |
Cooling | 10.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 555.26 | 295.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 295.88 | 0.00 | 0.00 | 0.00 |
Cooling | 10.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 555.26 | 295.88 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.04 |
ZONE2 FINE STORAGE DIRECT AIR | 2.39 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.50 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.50 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 222623.42 |
PSZ-OFFICE HEATING COIL | 27702.23 |
PSZ-FINE STORAGE HEATING COIL | 84772.23 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 222623.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-FINE STORAGE | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 1.00 | 1.00 | 2.39 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.04 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.39 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 18640.26 | 27702.23 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.39 | 2.39 | 2.39 | 2.39 | 54964.93 | 84772.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.04 | 0.518790 | 1.04 | 18156.10 | 18640.26 | 9320.13 | 18640.26 | 0.769767 | 0.769770 | 0.769770 | 0.769770 |
PSZ-FINE STORAGE COOLING COIL | 2.39 | 1.19 | 2.39 | 52586.73 | 54964.93 | 27482.47 | 54964.93 | 0.695175 | 0.695180 | 0.695180 | 0.695180 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.04 | 1182.96 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.39 | 2611.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.72529422E-12 | -0.16659653E-15 | 0.22267608E-14 | 0.12345853E-15 |
13 | 3 | -0.36555712E-03 | 0.52642428E-06 | -0.52844486E-04 | 0.13919492E-12 |
14 | 2 | 1.6938492 | 0.11754276E-01 | 1.1057222 | -0.70081836E-04 |
15 | 1 | -7.1898979 | 0.30855302 | -16.875743 | 0.32460476 |
16 | 0 | 6.0151594 | 0.19843725 | 16.288819 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22267608E-14 | -0.16659653E-15 | 0.72529422E-12 | 0.12345853E-15 |
85 | 3 | -0.52844486E-04 | 0.52642428E-06 | -0.36555712E-03 | 0.13919492E-12 |
86 | 2 | 1.1057222 | 0.11754276E-01 | 1.6938492 | -0.70081836E-04 |
87 | 1 | -16.875743 | 0.30855302 | -7.1898979 | 0.32460476 |
88 | 0 | 16.288819 | 0.19843725 | 6.0151594 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10245.85806 | 12295.02967 | 0.86465 | 1.03758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33455E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13189.87459 | 15827.84950 | 0.37992 | 0.45590 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 30220.84580 | 36265.01496 | 1.98822 | 2.38586 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33455E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 66393.64112 | 79672.36934 | 1.60993 | 1.93191 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30000 | 1.33455E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 185519.50239 | 222623.40287 | 4.58021 | 5.49625 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -16.30000 | 9.24091E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15179.11 | 1.03758 | 1.03758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14698.33 | 0.45590 | 0.45590 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 43170.43 | 2.38586 | 2.38586 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 71678.90 | 1.93191 | 1.93191 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03758 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38586 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.49625 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.49625 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 222623.42286 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 222623.40287 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03758 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03758 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03758 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03758 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03758 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.03758 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38586 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38586 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38586 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38586 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38586 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.38586 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.03758 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.38586 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03758 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03758 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03758 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03758 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03758 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03758 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51879 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03758 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18156.09972 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18640.26000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9320.13000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18640.26000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76977 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76977 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76977 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76977 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18640.26000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27702.22864 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03758 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1182.95817 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27702.22864 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38586 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38586 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38586 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38586 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.38586 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38586 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19293 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38586 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 52586.73281 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54964.93000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27482.46500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 54964.93000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69517 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69518 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69518 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69518 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54964.93000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 84772.22899 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38586 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2611.34204 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 84772.22899 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17834.9 | 11.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 53111.1 | 13.39 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2195288363 | 0.1959789615 | Pass | Pass | 1.5427935025 | 6.8657710067 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6719017640 | 0.6514119283 | Pass | Pass | 1.0886204659 | 3.8630981151 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.7485169620E-005 | 7.4360947212E-005 | Pass | Pass | 3.1723011875E-002 | 2.3478421785E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.67 | 83.67 | 123.40 | |
Exterior Lighting Total | 7857.24 | 123.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18640.26 | 14348.71 | 4291.55 | 0.77 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 54964.93 | 38210.52 | 16754.41 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17834.9 | 11.23 | ||||
PSZ-FINE STORAGE COOLING COIL | 53111.1 | 13.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 222623.42 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27702.23 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 84772.23 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.50 | 510.66 | 92.91 | 1.00 | 3.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.04 | 1182.96 | 1140.11 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.39 | 2611.34 | 1094.51 | 1.00 | 1.26 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10245.86 | 12295.03 | 51.90 | 0.865 | 1.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00838 | 29.00 | 0.01335 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30220.85 | 36265.01 | 26.03 | 1.988 | 2.386 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00875 | 30.30 | 0.01335 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00387 | 30.30 | 0.01335 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13189.87 | 15827.85 | 66.82 | 0.380 | 0.456 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00725 | -16.30 | 0.00092 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 66393.64 | 79672.37 | 57.18 | 1.610 | 1.932 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00553 | -16.30 | 0.00092 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 185519.50 | 222623.40 | 69.46 | 4.580 | 5.496 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00782 | -16.30 | 0.00092 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.04 | 1.04 | 0.46 | 0.46 | 1.0376 | 1.0376 | 1.0376 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.39 | 2.39 | 1.93 | 1.93 | 2.3859 | 2.3859 | 2.3859 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 222623.423 | 222623.423 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 222623.42 | 222623.42 | 5.496250 | 5.31 | 5.31 | 0.00659562 | 43.33 | 26.78 | 0.01600000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 9.98 | 0.00782148 | 99.9997 | 222623.40 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18640.260 | 0.000 | 1.037580 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18640.26 | 16159.85 | 1.037580 | 24.40 | 16.56 | 0.00886582 | 12.00 | 11.03 | 0.00800000 | 29.00 | 0.01334551 | 21.43 | 9.8580 | 23.90 | 0.00837592 | 44.2331 | 10245.86 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27702.229 | 27702.229 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27702.23 | 27702.23 | 1.037583 | 12.67 | 9.02 | 0.00583376 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.8580 | 21.10 | 0.00725391 | 45.4997 | 13189.87 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 54964.930 | 0.000 | 2.385860 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 54964.93 | 44677.52 | 2.385860 | 27.34 | 18.12 | 0.00956634 | 12.00 | 11.03 | 0.00800000 | 30.30 | 0.01334551 | 21.80 | 17.8012 | 26.70 | 0.00874791 | 39.0893 | 28986.20 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 84772.229 | 84772.229 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84772.23 | 84772.23 | 2.385865 | 8.55 | 5.52 | 0.00452077 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.8012 | 15.54 | 0.00553428 | 49.3183 | 66393.64 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 222623.423 | 222623.423 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1739 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.496250 | 6.45218671 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 222623.42 | 222623.42 | 1.0000 | 6.45218671 | 5.496250 | 5.31 | 5.31 | 0.00659562 | 21898.0 | 43.33 | 26.78 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 222623.42 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 9.98 | 0.00782148 | 9.98 | 0.00782148 | 99.9997 | 222623.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18640.260 | 0.000 | 1.037580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3211 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18640.26 | 16159.85 | 1.0000 | 1.21804143 | 1.037580 | 24.40 | 16.56 | 0.00886582 | 47094.8 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18640.26 | 29.00 | 0.01334551 | 21.43 | 0.10228487 | 9.8580 | 23.90 | 0.00837592 | 23.90 | 0.00837592 | 44.2331 | 10245.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27702.229 | 27702.229 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.037583 | 1.21804447 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27702.23 | 27702.23 | 1.0000 | 1.21804447 | 1.037583 | 12.67 | 9.02 | 0.00583376 | 27457.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27702.23 | -16.30 | 0.00092409 | -16.30 | 0.10228487 | 9.8580 | 21.05 | 0.00725391 | 21.10 | 0.00725391 | 45.4997 | 13189.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54964.930 | 0.000 | 2.385860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6233 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 54964.93 | 44677.52 | 1.0000 | 2.80082145 | 2.385860 | 27.34 | 18.12 | 0.00956634 | 51882.3 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54964.93 | 30.30 | 0.01334551 | 21.80 | 0.42471267 | 17.8012 | 26.70 | 0.00874791 | 26.70 | 0.00874791 | 39.0893 | 28986.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 84772.229 | 84772.229 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.385865 | 2.80082698 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84772.23 | 84772.23 | 1.0000 | 2.80082698 | 2.385865 | 8.55 | 5.52 | 0.00452077 | 19966.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84772.23 | -16.30 | 0.00092409 | -16.30 | 0.42471267 | 17.8012 | 15.55 | 0.00553428 | 15.54 | 0.00553428 | 49.3183 | 66393.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.39 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2559.00 | 2748.83 | 1976.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2559.00 | 2748.83 | 1976.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 129.50 | 62.00 | 64.50 | 2.83 |
ZONE2 FINE STORAGE | 615.50 | 8.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 719.17 | 68.83 | 64.50 | 2.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.345 | 0.305 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
Electricity:Building | 621.97 | 4992.32 | 01-JAN-00:10 | 48037.94 | 27-JUN-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 422.37 | 2759.73 | 01-JAN-00:10 | 33963.13 | 27-JUN-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.04 | 483.00 | 04-JAN-20:00 | 2760.65 | 13-FEB-12:50 |
WaterSystems:Electricity | 27.04 | 483.00 | 04-JAN-20:00 | 2760.65 | 13-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 27.04 | 483.00 | 04-JAN-20:00 | 2760.65 | 13-FEB-12:50 |
Fans:Electricity | 59.52 | 0.00 | 11-JAN-18:40 | 6099.59 | 14-JUL-14:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity | 0.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
ElectricityPurchased:Facility | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
ElectricityPurchased:Plant | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
Cogeneration:ElectricityPurchased | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
ElectricityNet:Plant | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
Cogeneration:ElectricityNet | 847.73 | 5475.32 | 12-MAR-09:20 | 68587.12 | 19-JUL-14:40 |
Electricity:HVAC | 75.32 | 0.00 | 11-JAN-18:40 | 19720.30 | 19-JUL-15:10 |
General:Fans:Electricity | 58.79 | 0.00 | 11-JAN-18:40 | 4304.96 | 10-JAN-11:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 16.53 | 0.00 | 01-JAN-00:10 | 15926.00 | 19-JUL-15:10 |
ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1319.75 | 0.00 | 11-JAN-18:40 | 409264.49 | 07-FEB-08:10 |
Gas:HVAC | 1319.75 | 0.00 | 11-JAN-18:40 | 409264.49 | 07-FEB-08:10 |
Heating:Gas | 1319.75 | 0.00 | 11-JAN-18:40 | 409264.49 | 07-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2102.65 | 0.00 | 11-JAN-18:40 | 640108.17 | 13-FEB-06:10 |
EnergyTransfer:Building | 1035.70 | 0.00 | 11-JAN-18:40 | 319875.10 | 13-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 64.90 | 0.00 | 01-JAN-00:40 | 24267.76 | 06-FEB-07:10 |
Heating:EnergyTransfer | 987.93 | 0.00 | 11-JAN-18:40 | 319875.10 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 44.11 | 0.00 | 01-JAN-00:40 | 24267.76 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 47.77 | 0.00 | 01-JAN-00:10 | 35212.23 | 19-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.79 | 0.00 | 01-JAN-00:10 | 8969.22 | 17-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 300.44 | 0.00 | 01-JAN-00:40 | 87115.04 | 13-FEB-07:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 273.47 | 0.00 | 01-JAN-00:40 | 87115.04 | 13-FEB-07:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.98 | 0.00 | 01-JAN-00:10 | 27183.66 | 19-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 670.35 | 0.00 | 06-JAN-10:50 | 223825.15 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 670.35 | 0.00 | 06-JAN-10:50 | 223825.15 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1066.95 | 0.00 | 11-JAN-18:40 | 323009.51 | 07-FEB-08:10 |
HeatingCoils:EnergyTransfer | 1004.42 | 0.00 | 11-JAN-18:40 | 323009.51 | 07-FEB-08:10 |
CoolingCoils:EnergyTransfer | 62.53 | 0.00 | 01-JAN-00:10 | 57292.37 | 19-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 44.113 | -20.788 | 0.000 | 0.000 | 3.954 | 30.994 | 31.946 | 8.517 | 0.000 | 0.358 | 0.000 | 0.000 | -10.547 | 0.000 | -26.700 | -61.847 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 273.467 | -26.977 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.930 | 0.002 | 0.000 | 0.000 | 0.000 | -232.396 | -151.680 |
ZONE3 BULK STORAGE | 670.350 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 29.808 | 0.000 | 8.520 | 0.000 | 0.000 | -21.368 | 0.000 | -812.201 | -296.756 |
Total Facility | 670.350 | 0.000 | 317.580 | -47.764 | 0.000 | 0.000 | 3.954 | 481.960 | 139.282 | 38.325 | 0.000 | 9.808 | 0.002 | 0.000 | -31.915 | 0.000 | -1071.298 | -510.283 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-AUG-17:43 | 0.00 | 0.00 | 0.00 | -16889.04 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 1636.28 | 0.00 | 0.00 | 14277.50 | 0.00 | -0.00 | 0.00 | -57.45 | 0.00 |
ZONE2 FINE STORAGE | 04-AUG-17:10 | 0.00 | 0.00 | 0.00 | -45544.06 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 866.04 | 43478.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-17:08 | 0.00 | 0.00 | 0.00 | -57668.71 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5029.58 | 0.00 | 937.36 | 50140.40 | 0.00 | 0.00 | 0.00 | -5480.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-NOV-06:01 | 0.00 | 0.00 | 28000.94 | 0.00 | 0.00 | 0.00 | 53.73 | 586.44 | 573.75 | 15.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -34.46 | -29195.98 |
ZONE2 FINE STORAGE | 13-FEB-06:01 | 0.00 | 0.00 | 92545.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -39986.34 | -53759.35 |
ZONE3 BULK STORAGE | 06-FEB-10:00 | 223826.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1314.42 | 0.00 | -210778.82 | -43391.32 |
Total Facility | 13-FEB-06:01 | 210656.08 | 0.00 | 117756.91 | 0.00 | 0.00 | 0.00 | 58.01 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3165.55 | 0.00 | -209131.50 | -123343.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0376 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0376 | 0.0986 | 1.0000 | 0.1023 | 0.0986 | ||
PSZ-FINE STORAGE | 2.3859 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3859 | 0.1780 | 1.0000 | 0.4247 | 0.1780 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0376 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0376 | 1.0000 | 1.0000 | 0.1023 | 0.0986 | ||
PSZ-FINE STORAGE | 2.3859 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3859 | 1.0000 | 1.0000 | 0.4247 | 0.1780 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0376 | 1.0376 | 1.0376 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3859 | 2.3859 | 2.3859 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0376 | 1.0376 | 1.0376 | 1.0376 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3859 | 2.3859 | 2.3859 | 2.3859 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0376 | 1.0376 | 1.0376 | 0.1023 | 0.2244 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3859 | 2.3859 | 2.3859 | 0.4247 | 0.2198 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0376 | 1.0376 | 1.0376 | 1.0376 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3859 | 2.3859 | 2.3859 | 2.3859 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 64.50 |
Number of hours cooling loads not met | 2.83 |
Number of hours not met | 67.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1319.75 | 409264.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 16.53 | 15926.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.40 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.72 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.79 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.04 | 2760.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 847.73 |
Natural Gas | 0.00 | 1319.75 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2167.48 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 3.42 |
Fans (All) | 12.31 |
Service Water Heating | 5.59 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 175.33 |
Subtotal | 175.33 |
Natural Gas [MJ/m2] | |
Space Heating | 272.95 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 272.95 |
Subtotal | 272.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.24 |
Space Heating | 60.89 |
Space Cooling | 0.76 |
Fans (All) | 2.75 |
Service Water Heating | 1.25 |
Receptacle Equipment | 6.43 |
Miscellaneous | 5.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352933E+12 |
February | 0.000 | 0.357516E+12 |
March | 0.000 | 0.153802E+12 |
April | 0.000 | 0.398507E+11 |
May | 0.000 | 0.161810E+10 |
June | 0.000 | 0.287282E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.674678E+08 |
October | 0.000 | 0.113209E+11 |
November | 0.000 | 0.682311E+11 |
December | 0.000 | 0.334386E+12 |
Annual Sum or Average | 0.131975E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.357516E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.194914E+09 | 236.59 | 14-JAN-08:20 | 3.50 | 2.70 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.6 | 0.179287E+09 | 236.59 | 09-FEB-11:09 | -2.7 | -3.2 |
March | 19101708.41 | 1237.49 | 15-MAR-15:10 | 25.50 | 16.17 | 0.214598E+09 | 301.58 | 16-MAR-15:09 | 18.77 | 15.57 |
April | 5786855.78 | 563.62 | 08-APR-14:40 | 19.80 | 13.31 | 0.200499E+09 | 304.45 | 08-APR-14:39 | 19.80 | 13.31 |
May | 0.505130E+09 | 6256.25 | 27-MAY-18:00 | 18.90 | 10.28 | 0.237024E+09 | 301.60 | 31-MAY-15:00 | 22.20 | 14.45 |
June | 0.396447E+10 | 16367.45 | 30-JUN-17:43 | 23.40 | 12.21 | 0.257100E+09 | 301.61 | 22-JUN-13:30 | 20.60 | 15.20 |
July | 0.676309E+10 | 16636.71 | 06-JUL-18:23 | 22.20 | 13.24 | 0.248869E+09 | 301.61 | 12-JUL-15:20 | 22.03 | 15.82 |
August | 0.655108E+10 | 16888.98 | 01-AUG-17:43 | 23.40 | 14.39 | 0.268632E+09 | 301.61 | 19-AUG-15:00 | 22.80 | 16.32 |
September | 0.281339E+10 | 14072.49 | 18-SEP-00:03 | 14.50 | 11.50 | 0.245565E+09 | 301.60 | 21-SEP-14:30 | 25.85 | 16.61 |
October | 0.161781E+09 | 1924.54 | 11-OCT-16:00 | 21.70 | 14.50 | 0.210234E+09 | 302.92 | 03-OCT-12:00 | 17.80 | 12.68 |
November | 4480891.81 | 1752.01 | 25-NOV-07:05 | -1.5 | -2.5 | 0.188392E+09 | 276.14 | 04-NOV-15:20 | 18.30 | 13.64 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.06 | 0.194924E+09 | 236.59 | 12-DEC-16:00 | -0.6 | -0.8 |
Annual Sum or Average | 0.207883E+11 | 0.264004E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.6 | 0.179287E+09 | 236.59 | -2.7 | -3.2 | ||
Maximum of Months | 0.676309E+10 | 16888.98 | 25.50 | 16.17 | 0.268632E+09 | 304.45 | 25.85 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 10802327.76 | 4063.26 | 14-FEB-15:40 | 0.73 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.396633E+09 | 5040.57 | 24-MAR-12:35 | -0.8 | -3.6 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.692888E+09 | 3431.09 | 17-APR-12:10 | 3.58 | -0.1 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.584182E+09 | 6588.12 | 05-MAY-06:10 | 10.10 | 5.75 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.373173E+10 | 34363.48 | 27-JUN-17:10 | 26.52 | 22.65 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.103771E+11 | 42856.05 | 18-JUL-17:08 | 28.03 | 19.75 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.855688E+10 | 45543.09 | 04-AUG-17:10 | 28.12 | 16.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.130775E+10 | 12406.71 | 16-SEP-13:40 | 27.20 | 19.69 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.903342E+09 | 3768.67 | 24-OCT-10:00 | 3.30 | 0.73 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.369070E+09 | 3097.66 | 18-NOV-12:00 | 4.40 | 1.19 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 47302022.25 | 3532.74 | 16-DEC-12:00 | 4.40 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.269777E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -3.6 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.103771E+11 | 45543.09 | 28.12 | 22.65 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.6 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -4.9 | -6.8 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.00 | 0.00 | 01-APR-00:03 | 4.10 | 3.71 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.06 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.8 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100412E+11 | 27218.02 | 23-JAN-06:31 | -4.6 |
February | 0.954055E+10 | 27299.05 | 23-FEB-06:32 | 2.60 |
March | 0.638380E+10 | 27393.81 | 14-MAR-05:01 | 11.78 |
April | 0.321254E+10 | 27319.62 | 07-APR-05:01 | 10.60 |
May | 0.794881E+09 | 26954.07 | 05-MAY-05:01 | 10.50 |
June | 26404167.85 | 4630.05 | 14-JUN-06:05 | 7.67 |
July | 3261095.92 | 1099.14 | 29-JUL-06:05 | 20.68 |
August | 4177504.48 | 809.01 | 07-AUG-06:10 | 20.68 |
September | 53989215.34 | 25740.06 | 30-SEP-05:02 | 7.20 |
October | 0.155246E+10 | 27356.42 | 26-OCT-05:01 | 15.50 |
November | 0.371715E+10 | 28000.65 | 27-NOV-06:01 | 18.30 |
December | 0.878299E+10 | 27230.73 | 01-DEC-06:01 | 10.10 |
Annual Sum or Average | 0.441134E+11 | |||
Minimum of Months | 3261095.92 | 809.01 | -4.6 | |
Maximum of Months | 0.100412E+11 | 28000.65 | 20.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656266E+11 | 92187.67 | 12-JAN-06:01 | -7.4 |
February | 0.658582E+11 | 92545.73 | 13-FEB-06:01 | -9.4 |
March | 0.339253E+11 | 88081.80 | 26-MAR-09:42 | -1.1 |
April | 0.140487E+11 | 87965.64 | 16-APR-09:02 | -3.3 |
May | 0.870673E+09 | 61802.30 | 02-MAY-05:05 | 7.30 |
June | 0.279900E+09 | 2679.98 | 03-JUN-07:00 | 11.70 |
July | 0.150769E+09 | 2490.98 | 15-JUL-07:00 | 22.80 |
August | 0.204443E+09 | 2675.04 | 24-AUG-07:00 | 15.00 |
September | 0.320433E+09 | 2756.21 | 28-SEP-07:00 | 12.20 |
October | 0.626086E+10 | 86549.50 | 30-OCT-04:42 | -0.1 |
November | 0.221399E+11 | 86765.65 | 25-NOV-06:42 | -1.7 |
December | 0.637815E+11 | 92175.11 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.273467E+12 | |||
Minimum of Months | 0.150769E+09 | 2490.98 | -12.2 | |
Maximum of Months | 0.658582E+11 | 92545.73 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189041E+12 | 223601.44 | 12-JAN-09:00 | -11.1 |
February | 0.194451E+12 | 223825.15 | 06-FEB-10:00 | -15.0 |
March | 0.731531E+11 | 123735.34 | 05-MAR-01:00 | -7.2 |
April | 0.113649E+11 | 85257.43 | 16-APR-06:51 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.151889E+09 | 19778.04 | 30-OCT-05:00 | 0.00 |
November | 0.233003E+11 | 52834.15 | 25-NOV-06:53 | -1.7 |
December | 0.178890E+12 | 200385.44 | 09-DEC-17:00 | -7.2 |
Annual Sum or Average | 0.670352E+12 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.194451E+12 | 223825.15 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451392E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453559E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4300113.06 | 0.310375E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209745E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3223951.40 | 0.126358E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61645776.35 | 0.809344E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163160E+09 | 0.371180E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116886E+09 | 0.541694E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8045089.06 | 0.895623E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489209.62 | 0.170207E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111111.05 | 0.243436E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443183E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.357861E+09 | 0.267004E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371180E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163160E+09 | 0.453559E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403918E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434076E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64163282.22 | 0.248283E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162037E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33056607.43 | 0.873478E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105964E+09 | 0.824975E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349198E+09 | 0.536848E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276773E+09 | 0.627572E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2059440.97 | 0.772460E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33944997.18 | 0.111383E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64832401.02 | 0.181435E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419296E+11 |
Annual Sum or Average | 0.136656E+12 | 0.929992E+09 | 0.232396E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536848E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349198E+09 | 0.434076E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7158797.79 | 0.101072E+12 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78315228.65 | 0.111719E+12 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171126E+10 | 0.575094E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682847E+09 | 0.322796E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400337E+09 | 0.246790E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178870E+09 | 0.294250E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2059613.44 | 0.260995E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1865858.54 | 0.281868E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262596E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974051E+09 | 0.278054E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220445E+10 | 0.328948E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138922E+09 | 0.102420E+12 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.638015E+10 | 0.600350E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246790E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220445E+10 | 0.111719E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 11607.17 | 12-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 12683.21 | 06-FEB-17:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 268.80 | 14-MAR-12:00 | 9362.75 | 07-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 6620.21 | 04-APR-17:00 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.88 | 14-MAY-15:00 | 4236.55 | 08-MAY-06:20 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.10 | 27-JUN-12:00 | 3943.92 | 13-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.35 | 20-JUL-16:10 | 2756.32 | 06-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1535.77 | 18-AUG-17:00 | 3075.48 | 03-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.01 | 15-SEP-12:00 | 3646.46 | 06-SEP-06:03 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 | 22-OCT-12:00 | 6063.42 | 17-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 27-NOV-06:00 | 6204.23 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11329.10 | 26-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756.32 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.35 | 12683.21 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 68048.62 | 12-JAN-09:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 63128.01 | 13-FEB-07:30 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.05 | 14-MAR-15:10 | 33752.27 | 03-MAR-18:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 31671.09 | 04-APR-17:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2719.86 | 14-MAY-15:00 | 15912.30 | 11-MAY-15:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3990.56 | 12-JUN-15:10 | 19146.88 | 13-JUN-15:03 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105.21 | 15-JUL-15:10 | 10137.62 | 06-JUL-02:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5098.93 | 13-AUG-13:00 | 11268.37 | 30-AUG-17:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.77 | 16-SEP-13:00 | 12627.60 | 29-SEP-15:05 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.59 | 22-OCT-12:00 | 16936.62 | 23-OCT-15:05 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2780.68 | 27-NOV-06:01 | 32172.33 | 17-NOV-09:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63744.20 | 09-DEC-17:30 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10137.62 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105.21 | 68048.62 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2649.30 | 11-JAN-16:00 | 170353.41 | 12-JAN-09:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8501.27 | 22-FEB-18:40 | 169058.34 | 07-FEB-11:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29418.56 | 14-MAR-14:00 | 79120.74 | 01-MAR-15:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14549.70 | 07-APR-14:00 | 58082.04 | 16-APR-06:52 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15005.45 | 14-MAY-15:00 | 40193.25 | 11-MAY-15:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6626.91 | 17-JUN-16:00 | 54770.99 | 13-JUN-12:05 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2006.85 | 15-JUL-13:55 | 34600.10 | 06-JUL-02:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.30 | 13-AUG-12:43 | 35082.58 | 30-AUG-15:55 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 37129.77 | 28-SEP-14:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15104.34 | 22-OCT-12:00 | 41186.49 | 23-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21343.29 | 27-NOV-06:01 | 49297.08 | 17-NOV-09:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14126.50 | 01-DEC-11:00 | 151209.96 | 09-DEC-15:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34600.10 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 29418.56 | 170353.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.95 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.80 |
March | 1237.49 | 15-MAR-15:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 | 0.00 |
April | 563.62 | 08-APR-14:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.49 |
May | 6256.25 | 27-MAY-18:00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.19 |
June | 16367.45 | 30-JUN-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 |
July | 16636.71 | 06-JUL-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.56 |
August | 16888.98 | 01-AUG-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 |
September | 14072.49 | 18-SEP-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.25 |
October | 1924.54 | 11-OCT-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.18 |
November | 1752.01 | 25-NOV-07:05 | 553.77 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.25 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16888.98 | 659.25 | 4283.58 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 | 906.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10741.37 |
February | 4063.26 | 14-FEB-15:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.02 |
March | 5040.57 | 24-MAR-12:35 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5119.28 |
April | 3431.09 | 17-APR-12:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6181.79 |
May | 6588.12 | 05-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2562.31 |
June | 34363.48 | 27-JUN-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.69 |
July | 42856.05 | 18-JUL-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.17 | 0.00 |
August | 45543.09 | 04-AUG-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.04 | 0.00 |
September | 12406.71 | 16-SEP-13:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.61 | 0.00 |
October | 3768.67 | 24-OCT-10:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2906.76 |
November | 3097.66 | 18-NOV-12:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4429.73 |
December | 3532.74 | 16-DEC-12:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45543.09 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.04 | 10741.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 16558.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21341.69 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28661.91 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25260.58 |
April | 0.00 | 01-APR-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6853.77 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4186.05 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.51 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14075.76 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9957.52 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12699.54 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8084.15 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11145.24 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13164.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4186.05 | |
Maximum of Months | 0.00 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28661.91 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.737181E+11 | 55563.57 | 13-JAN-16:00 | 0.352933E+12 | 407026.11 | 12-JAN-08:00 |
February | 0.665984E+11 | 52321.49 | 13-FEB-15:00 | 0.357516E+12 | 409264.49 | 07-FEB-08:09 |
March | 0.737030E+11 | 52447.35 | 15-MAR-14:50 | 0.153802E+12 | 226991.08 | 05-MAR-00:00 |
April | 0.670760E+11 | 52168.62 | 04-APR-14:00 | 0.398507E+11 | 175801.72 | 16-APR-03:49 |
May | 0.679537E+11 | 52428.71 | 10-MAY-14:00 | 0.161810E+10 | 31054.32 | 01-MAY-05:10 |
June | 0.692177E+11 | 66688.65 | 27-JUN-12:00 | 28728238.52 | 5372.65 | 14-JUN-06:10 |
July | 0.731473E+11 | 68587.12 | 19-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.759676E+11 | 65474.42 | 10-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.682160E+11 | 59218.42 | 16-SEP-13:39 | 67467793.68 | 6925.56 | 30-SEP-05:10 |
October | 0.693292E+11 | 51942.40 | 12-OCT-14:00 | 0.113209E+11 | 82954.17 | 30-OCT-05:10 |
November | 0.689017E+11 | 55556.66 | 30-NOV-16:49 | 0.682311E+11 | 131672.16 | 25-NOV-06:10 |
December | 0.739018E+11 | 55562.00 | 30-DEC-16:00 | 0.334386E+12 | 371413.12 | 09-DEC-16:00 |
Annual Sum or Average | 0.847731E+12 | 0.131975E+13 | ||||
Minimum of Months | 0.665984E+11 | 51942.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.759676E+11 | 68587.12 | 0.357516E+12 | 409264.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.129597E+11 | 0.115358E+11 | 0.00 | 0.674593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237333E+10 | 0.00 |
February | 0.366966E+11 | 0.108147E+11 | 0.105871E+11 | 0.00 | 0.632947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217053E+10 | 0.00 |
March | 0.423649E+11 | 0.107440E+11 | 0.123357E+11 | 0.00 | 0.580578E+10 | 0.00 | 0.00 | 12618534.97 | 0.00 | 0.00 | 0.00 | 0.244003E+10 | 0.00 |
April | 0.397216E+11 | 0.915526E+10 | 0.114862E+11 | 0.00 | 0.442683E+10 | 0.00 | 0.00 | 1215471.07 | 0.00 | 0.00 | 0.00 | 0.228490E+10 | 0.00 |
May | 0.412341E+11 | 0.836796E+10 | 0.119357E+11 | 0.00 | 0.393496E+10 | 0.00 | 0.00 | 0.176064E+09 | 0.00 | 0.00 | 0.00 | 0.230489E+10 | 0.00 |
June | 0.408524E+11 | 0.757124E+10 | 0.118862E+11 | 0.00 | 0.400311E+10 | 0.00 | 0.00 | 0.271150E+10 | 0.00 | 0.00 | 0.00 | 0.219334E+10 | 0.00 |
July | 0.401034E+11 | 0.803324E+10 | 0.115358E+11 | 0.00 | 0.443717E+10 | 0.00 | 0.00 | 0.686683E+10 | 0.00 | 0.00 | 0.00 | 0.217096E+10 | 0.00 |
August | 0.423649E+11 | 0.897140E+10 | 0.123357E+11 | 0.00 | 0.458527E+10 | 0.00 | 0.00 | 0.549805E+10 | 0.00 | 0.00 | 0.00 | 0.221231E+10 | 0.00 |
September | 0.397216E+11 | 0.986241E+10 | 0.114862E+11 | 0.00 | 0.378557E+10 | 0.00 | 0.00 | 0.123329E+10 | 0.00 | 0.00 | 0.00 | 0.212694E+10 | 0.00 |
October | 0.401034E+11 | 0.114653E+11 | 0.115358E+11 | 0.00 | 0.396956E+10 | 0.00 | 0.00 | 29369744.15 | 0.00 | 0.00 | 0.00 | 0.222584E+10 | 0.00 |
November | 0.385909E+11 | 0.122007E+11 | 0.110862E+11 | 0.00 | 0.482193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220194E+10 | 0.00 |
December | 0.401034E+11 | 0.132567E+11 | 0.115358E+11 | 0.00 | 0.667080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233512E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123403E+12 | 0.139282E+12 | 0.595164E+11 | 0.00 | 0.165289E+11 | 0.270401E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.757124E+10 | 0.105871E+11 | 0.00 | 0.378557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212694E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.132567E+11 | 0.123357E+11 | 0.00 | 0.674593E+10 | 0.00 | 0.00 | 0.686683E+10 | 0.00 | 0.00 | 0.00 | 0.244003E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.352933E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.357516E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.398507E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.161810E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 28728238.52 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 67467793.68 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113209E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.682311E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.334386E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131975E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.357516E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4304.96 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4304.96 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4304.96 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4304.96 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3794.30 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6099.59 | 27-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6099.59 | 14-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6099.59 | 04-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3794.30 | 14-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4304.96 | 30-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4304.96 | 03-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4304.96 | 01-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3794.30 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6099.59 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2747.55 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2760.65 | 13-FEB-12:50 | 0.00 |
March | 706.83 | 15-MAR-15:09 | 0.00 | 0.00 | 0.00 | 2748.54 | 01-MAR-12:00 | 0.00 |
April | 346.13 | 08-APR-14:39 | 0.00 | 0.00 | 0.00 | 2627.65 | 03-APR-11:50 | 0.00 |
May | 1165.38 | 27-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2435.93 | 01-MAY-11:30 | 0.00 |
June | 13080.74 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 2152.70 | 01-JUN-11:00 | 0.00 |
July | 15926.00 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1827.66 | 10-JUL-11:00 | 0.00 |
August | 12255.98 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1800.34 | 01-AUG-11:09 | 0.00 |
September | 7960.81 | 16-SEP-13:39 | 0.00 | 0.00 | 0.00 | 1851.13 | 26-SEP-11:39 | 0.00 |
October | 734.84 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2145.91 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2421.18 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2629.25 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1800.34 | 0.00 | ||
Maximum of Months | 15926.00 | 0.00 | 0.00 | 0.00 | 2760.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55563.57 | 13-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52321.49 | 13-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52447.35 | 15-MAR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3794.30 | 0.00 | 0.00 | 703.54 | 0.00 |
April | 52168.62 | 04-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52428.71 | 10-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3794.30 | 0.00 | 0.00 | 1094.48 | 0.00 |
June | 66688.65 | 27-JUN-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6099.59 | 0.00 | 0.00 | 13080.74 | 0.00 |
July | 68587.12 | 19-JUL-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6099.59 | 0.00 | 0.00 | 14988.82 | 0.00 |
August | 65474.42 | 10-AUG-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6099.59 | 0.00 | 0.00 | 11880.83 | 0.00 |
September | 59218.42 | 16-SEP-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3794.30 | 0.00 | 0.00 | 7960.81 | 0.00 |
October | 51942.40 | 12-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3794.30 | 0.00 | 0.00 | 636.28 | 0.00 |
November | 55556.66 | 30-NOV-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55562.00 | 30-DEC-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4304.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51942.40 | 31660.41 | 10112.62 | 0.00 | 0.00 | 3794.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68587.12 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6099.59 | 0.00 | 0.00 | 14988.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 407026.11 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 409264.49 | 07-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 226991.08 | 05-MAR-00:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 175801.72 | 16-APR-03:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 31054.32 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5372.65 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6925.56 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 82954.17 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 131672.16 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 371413.12 | 09-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 409264.49 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.33 | 16.49 | 10.50 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36.00 | 16.02 | 10.83 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.83 | 17.79 | 9.00 | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.50 | 19.63 | 8.33 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.83 | 20.29 | 2.83 | 20.29 | 0.17 | 24.46 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 24.55 | 0.67 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 24.61 | 0.83 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 24.59 | 1.17 | 24.53 |
September | 0.17 | 20.39 | 0.17 | 20.39 | 5.67 | 24.52 | 0.17 | 24.46 |
October | 5.17 | 20.10 | 5.17 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.50 | 19.52 | 8.00 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26.17 | 16.46 | 9.67 | 19.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.50 | 17.13 | 64.50 | 19.40 | 62.00 | 24.58 | 2.83 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.00 | 20.39 | 10.83 | 20.39 | 22.83 | 24.61 | 1.17 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.17 | 13.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 125.83 | 13.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86.50 | 14.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52.67 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.38 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23.33 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84.67 | 14.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121.17 | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 615.50 | 13.94 | 0.00 | 8.67 | 27.39 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 125.83 | 14.98 | 0.00 | 0.00 | 5.33 | 27.42 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.01 | 276.00 | 21.01 | 276.00 | 21.01 |
March | 324.00 | 21.22 | 292.83 | 21.04 | 292.83 | 21.04 |
April | 300.00 | 21.32 | 261.67 | 21.11 | 261.67 | 21.11 |
May | 312.00 | 22.62 | 88.67 | 21.21 | 88.67 | 21.21 |
June | 136.00 | 23.47 | 94.67 | 23.86 | 4.33 | 23.06 |
July | 13.83 | 23.78 | 238.33 | 23.90 | 0.67 | 23.90 |
August | 32.83 | 23.73 | 212.33 | 23.90 | 0.50 | 23.90 |
September | 166.17 | 23.37 | 45.67 | 23.70 | 3.33 | 21.16 |
October | 300.00 | 21.79 | 171.33 | 21.13 | 171.33 | 21.13 |
November | 288.00 | 21.12 | 277.50 | 21.08 | 277.50 | 21.08 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 2748.83 | 21.66 | 2559.00 | 21.71 | 1976.83 | 21.07 |
Minimum of Months | 13.83 | 21.01 | 45.67 | 21.01 | 0.50 | 21.01 |
Maximum of Months | 324.00 | 23.78 | 300.00 | 23.90 | 300.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 50577898.27 | 12618534.97 | 9.83 | 45394939.80 | 5182958.47 | 0.00 | 0.17 | 15-MAR-15:10 | 0.00 | 01-MAR-00:02 | 2835.97 | 15-MAR-15:10 | 2624.60 | 15-MAR-15:10 | 220.08 | 15-MAR-16:00 | 706.83 | 15-MAR-15:10 | 0.00 | 01-MAR-00:02 |
April | 4907289.36 | 1215471.07 | 3.17 | 4744401.52 | 162887.84 | 0.00 | 0.09 | 08-APR-14:40 | 0.00 | 01-APR-00:03 | 1407.62 | 08-APR-14:40 | 1348.21 | 08-APR-14:40 | 59.41 | 08-APR-14:40 | 346.13 | 08-APR-14:40 | 0.00 | 01-APR-00:03 |
May | 0.723205E+09 | 0.176064E+09 | 97.92 | 0.678626E+09 | 44578999.77 | 0.00 | 0.46 | 27-MAY-18:00 | 0.00 | 01-MAY-00:05 | 6824.45 | 27-MAY-18:00 | 6824.45 | 27-MAY-18:00 | 744.61 | 10-MAY-15:10 | 1707.12 | 27-MAY-18:00 | 0.00 | 01-MAY-00:05 |
June | 0.569697E+10 | 0.136552E+10 | 321.70 | 0.478476E+10 | 0.912204E+09 | 0.00 | 1.00 | 12-JUN-00:03 | 0.00 | 01-JUN-00:10 | 21385.40 | 19-JUN-00:02 | 18048.24 | 30-JUN-17:43 | 7650.78 | 19-JUN-00:02 | 4450.64 | 27-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.101973E+11 | 0.244181E+10 | 432.07 | 0.817059E+10 | 0.202676E+10 | 0.00 | 1.00 | 03-JUL-00:01 | 0.00 | 01-JUL-00:20 | 22557.07 | 17-JUL-00:01 | 18319.14 | 06-JUL-17:43 | 8852.54 | 17-JUL-00:07 | 4580.45 | 17-JUL-00:01 | 0.00 | 01-JUL-00:10 |
August | 0.916438E+10 | 0.220042E+10 | 431.08 | 0.782577E+10 | 0.133861E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:15 | 23075.69 | 14-AUG-00:01 | 18576.09 | 01-AUG-17:43 | 10129.09 | 14-AUG-00:06 | 4645.65 | 14-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.393003E+10 | 0.939630E+09 | 255.65 | 0.335906E+10 | 0.570966E+09 | 0.00 | 1.00 | 18-SEP-00:03 | 0.00 | 01-SEP-00:10 | 20110.65 | 18-SEP-00:03 | 15622.51 | 16-SEP-17:10 | 5048.10 | 18-SEP-00:03 | 4214.87 | 18-SEP-00:03 | 0.00 | 01-SEP-00:10 |
October | 0.120031E+09 | 29369744.15 | 23.00 | 0.109828E+09 | 10202425.21 | 0.00 | 0.19 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 | 3035.30 | 11-OCT-16:00 | 2845.58 | 11-OCT-16:00 | 508.01 | 12-OCT-15:00 | 734.84 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.298874E+11 | 0.716665E+10 | 1574.42 | 0.249788E+11 | 0.490867E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101973E+11 | 0.244181E+10 | 432.07 | 0.817059E+10 | 0.202676E+10 | 0.00 | 1.00 | 0.00 | 23075.69 | 18576.09 | 10129.09 | 4645.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.470076E+10 | 0.134598E+10 | 94.35 | 0.349689E+10 | 0.120387E+10 | 0.00 | 1.00 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 | 65200.05 | 27-JUN-17:10 | 38287.57 | 27-JUN-17:10 | 26912.49 | 27-JUN-17:10 | 16252.99 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.155121E+11 | 0.442502E+10 | 227.26 | 0.112341E+11 | 0.427806E+10 | 0.00 | 1.00 | 16-JUL-10:33 | 0.00 | 01-JUL-00:10 | 63332.91 | 16-JUL-10:33 | 46779.01 | 18-JUL-17:08 | 24273.44 | 16-JUL-10:33 | 16365.49 | 16-JUL-10:33 | 0.00 | 01-JUL-00:10 |
August | 0.114122E+11 | 0.329764E+10 | 198.64 | 0.926129E+10 | 0.215089E+10 | 0.00 | 1.00 | 06-AUG-14:43 | 0.00 | 01-AUG-00:10 | 63271.13 | 13-AUG-16:13 | 50024.14 | 04-AUG-17:10 | 24378.69 | 13-AUG-16:13 | 16497.32 | 13-AUG-14:53 | 0.00 | 01-AUG-00:10 |
September | 0.101889E+10 | 0.293658E+09 | 31.67 | 0.778967E+09 | 0.239923E+09 | 0.00 | 0.38 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 | 20355.27 | 16-SEP-13:40 | 15467.23 | 16-SEP-13:40 | 5909.60 | 15-SEP-11:40 | 5885.88 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.326440E+11 | 0.936230E+10 | 551.92 | 0.247712E+11 | 0.787275E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.155121E+11 | 0.442502E+10 | 227.26 | 0.112341E+11 | 0.427806E+10 | 0.00 | 1.00 | 0.00 | 65200.05 | 50024.14 | 26912.49 | 16497.32 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.95 | 12.24 | 39.72 | 8.55 | 207.45 | 0.00 | 0.00 | 744.00 |
February | 84.18 | 21.72 | 62.45 | 24.50 | 193.78 | 0.00 | 0.00 | 672.00 |
March | 132.34 | 56.89 | 75.44 | 90.61 | 124.35 | 0.00 | 0.00 | 744.00 |
April | 160.98 | 65.89 | 95.09 | 136.23 | 82.69 | 0.00 | 0.00 | 720.00 |
May | 190.02 | 85.79 | 104.23 | 187.77 | 57.23 | 0.00 | 0.00 | 744.00 |
June | 229.56 | 107.98 | 121.58 | 246.76 | 47.62 | 0.00 | 0.00 | 720.00 |
July | 204.99 | 89.73 | 115.26 | 232.92 | 35.90 | 0.00 | 0.00 | 744.00 |
August | 185.22 | 78.55 | 106.67 | 205.91 | 46.77 | 0.00 | 0.00 | 744.00 |
September | 145.86 | 63.03 | 82.83 | 143.40 | 69.77 | 0.00 | 0.00 | 720.00 |
October | 94.51 | 33.29 | 61.22 | 70.70 | 88.51 | 0.00 | 0.00 | 744.00 |
November | 55.55 | 15.77 | 39.78 | 26.66 | 116.26 | 0.00 | 0.00 | 720.00 |
December | 48.46 | 10.50 | 37.96 | 8.07 | 197.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.19 | 53.60 | 78.58 | 115.67 | 105.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 48.46 | 10.50 | 37.96 | 8.07 | 35.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 229.56 | 107.98 | 121.58 | 246.76 | 207.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.95 | 12.24 | 39.72 | 8.55 | 207.45 | 0.00 | 0.00 | 744.00 |
February | 84.18 | 21.72 | 62.45 | 24.50 | 193.78 | 0.00 | 0.00 | 672.00 |
March | 132.34 | 56.89 | 75.44 | 90.61 | 124.35 | 0.00 | 0.00 | 744.00 |
April | 160.98 | 65.89 | 95.09 | 136.23 | 82.69 | 0.00 | 0.00 | 720.00 |
May | 190.02 | 85.79 | 104.23 | 187.77 | 57.23 | 0.00 | 0.00 | 744.00 |
June | 229.56 | 107.98 | 121.58 | 246.76 | 47.62 | 0.00 | 0.00 | 720.00 |
July | 204.99 | 89.73 | 115.26 | 232.92 | 35.90 | 0.00 | 0.00 | 744.00 |
August | 185.22 | 78.55 | 106.67 | 205.91 | 46.77 | 0.00 | 0.00 | 744.00 |
September | 145.86 | 63.03 | 82.83 | 143.40 | 69.77 | 0.00 | 0.00 | 720.00 |
October | 94.51 | 33.29 | 61.22 | 70.70 | 88.51 | 0.00 | 0.00 | 744.00 |
November | 55.55 | 15.77 | 39.78 | 26.66 | 116.26 | 0.00 | 0.00 | 720.00 |
December | 48.46 | 10.50 | 37.96 | 8.07 | 197.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.19 | 53.60 | 78.58 | 115.67 | 105.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 48.46 | 10.50 | 37.96 | 8.07 | 35.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 229.56 | 107.98 | 121.58 | 246.76 | 207.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.26 | 0.00 | 19.26 | 0.04 | 129.06 | 0.00 | 0.00 | 744.00 |
February | 29.35 | 0.00 | 29.35 | 0.37 | 121.76 | 0.00 | 0.00 | 672.00 |
March | 35.60 | 0.00 | 35.60 | 8.93 | 80.34 | 0.00 | 0.00 | 744.00 |
April | 45.38 | 0.22 | 45.17 | 20.90 | 50.02 | 0.00 | 0.00 | 720.00 |
May | 52.72 | 2.26 | 50.45 | 34.14 | 32.44 | 0.00 | 0.00 | 744.00 |
June | 63.38 | 5.38 | 58.00 | 49.53 | 25.83 | 0.00 | 0.00 | 720.00 |
July | 59.03 | 4.01 | 55.02 | 55.13 | 19.31 | 0.00 | 0.00 | 744.00 |
August | 51.11 | 0.98 | 50.12 | 46.44 | 26.78 | 0.00 | 0.00 | 744.00 |
September | 38.74 | 0.02 | 38.72 | 26.20 | 41.75 | 0.00 | 0.00 | 720.00 |
October | 28.94 | 0.00 | 28.94 | 11.17 | 53.65 | 0.00 | 0.00 | 744.00 |
November | 19.45 | 0.00 | 19.45 | 3.46 | 70.69 | 0.00 | 0.00 | 720.00 |
December | 18.03 | 0.00 | 18.03 | 0.12 | 121.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.45 | 1.08 | 37.38 | 21.50 | 64.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.03 | 0.00 | 18.03 | 0.04 | 19.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.38 | 5.38 | 58.00 | 55.13 | 129.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.26 | 0.00 | 19.26 | 0.04 | 129.06 | 0.00 | 0.00 | 744.00 |
February | 29.35 | 0.00 | 29.35 | 0.37 | 121.76 | 0.00 | 0.00 | 672.00 |
March | 35.60 | 0.00 | 35.60 | 8.93 | 80.34 | 0.00 | 0.00 | 744.00 |
April | 45.38 | 0.22 | 45.16 | 20.90 | 50.02 | 0.00 | 0.00 | 720.00 |
May | 52.71 | 2.26 | 50.45 | 34.14 | 32.44 | 0.00 | 0.00 | 744.00 |
June | 63.38 | 5.38 | 58.00 | 49.52 | 25.83 | 0.00 | 0.00 | 720.00 |
July | 59.03 | 4.01 | 55.02 | 55.13 | 19.31 | 0.00 | 0.00 | 744.00 |
August | 51.10 | 0.98 | 50.12 | 46.44 | 26.78 | 0.00 | 0.00 | 744.00 |
September | 38.74 | 0.02 | 38.72 | 26.20 | 41.75 | 0.00 | 0.00 | 720.00 |
October | 28.94 | 0.00 | 28.94 | 11.17 | 53.65 | 0.00 | 0.00 | 744.00 |
November | 19.45 | 0.00 | 19.45 | 3.46 | 70.69 | 0.00 | 0.00 | 720.00 |
December | 18.03 | 0.00 | 18.03 | 0.12 | 121.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.45 | 1.08 | 37.37 | 21.50 | 64.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.03 | 0.00 | 18.03 | 0.04 | 19.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.38 | 5.38 | 58.00 | 55.13 | 129.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.22 | 73.90 | 34.67 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.06 | 45.87 | 19.67 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.19 | 42.89 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.32 | 44.07 | 9.50 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.22 | 44.15 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.94 | 52.23 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.33 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.30 | 54.06 | 14.83 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.75 | 121.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.32 | 119.13 | 34.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139147E+09 | 32773711.85 | 0.106374E+09 | 22901672.11 | 0.555635E+09 |
February | 0.203640E+09 | 52555155.11 | 0.151085E+09 | 59264935.30 | 0.468782E+09 |
March | 0.354452E+09 | 0.152382E+09 | 0.202070E+09 | 0.242703E+09 | 0.333056E+09 |
April | 0.417266E+09 | 0.170796E+09 | 0.246471E+09 | 0.353120E+09 | 0.214333E+09 |
May | 0.508940E+09 | 0.229778E+09 | 0.279162E+09 | 0.502913E+09 | 0.153290E+09 |
June | 0.595009E+09 | 0.279877E+09 | 0.315132E+09 | 0.639599E+09 | 0.123441E+09 |
July | 0.549058E+09 | 0.240342E+09 | 0.308716E+09 | 0.623856E+09 | 96150305.28 |
August | 0.496101E+09 | 0.210386E+09 | 0.285715E+09 | 0.551513E+09 | 0.125265E+09 |
September | 0.378075E+09 | 0.163375E+09 | 0.214700E+09 | 0.371703E+09 | 0.180832E+09 |
October | 0.253138E+09 | 89168764.44 | 0.163969E+09 | 0.189352E+09 | 0.237054E+09 |
November | 0.143991E+09 | 40882676.36 | 0.103108E+09 | 69113608.33 | 0.301336E+09 |
December | 0.129798E+09 | 28127843.80 | 0.101670E+09 | 21621878.31 | 0.529653E+09 |
Annual Sum or Average | 0.416861E+10 | 0.169044E+10 | 0.247817E+10 | 0.364766E+10 | 0.331883E+10 |
Minimum of Months | 0.129798E+09 | 28127843.80 | 0.101670E+09 | 21621878.31 | 96150305.28 |
Maximum of Months | 0.595009E+09 | 0.279877E+09 | 0.315132E+09 | 0.639599E+09 | 0.555635E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139147E+09 | 32773711.85 | 0.106374E+09 | 22901672.11 | 0.555635E+09 |
February | 0.203640E+09 | 52555155.11 | 0.151085E+09 | 59264935.30 | 0.468782E+09 |
March | 0.354452E+09 | 0.152382E+09 | 0.202070E+09 | 0.242703E+09 | 0.333056E+09 |
April | 0.417266E+09 | 0.170796E+09 | 0.246471E+09 | 0.353120E+09 | 0.214333E+09 |
May | 0.508940E+09 | 0.229778E+09 | 0.279162E+09 | 0.502913E+09 | 0.153290E+09 |
June | 0.595009E+09 | 0.279877E+09 | 0.315132E+09 | 0.639599E+09 | 0.123441E+09 |
July | 0.549058E+09 | 0.240342E+09 | 0.308716E+09 | 0.623856E+09 | 96150305.28 |
August | 0.496101E+09 | 0.210386E+09 | 0.285715E+09 | 0.551513E+09 | 0.125265E+09 |
September | 0.378075E+09 | 0.163375E+09 | 0.214700E+09 | 0.371703E+09 | 0.180832E+09 |
October | 0.253138E+09 | 89168764.44 | 0.163969E+09 | 0.189352E+09 | 0.237054E+09 |
November | 0.143991E+09 | 40882676.36 | 0.103108E+09 | 69113608.33 | 0.301336E+09 |
December | 0.129798E+09 | 28127843.80 | 0.101670E+09 | 21621878.31 | 0.529653E+09 |
Annual Sum or Average | 0.416861E+10 | 0.169044E+10 | 0.247817E+10 | 0.364766E+10 | 0.331883E+10 |
Minimum of Months | 0.129798E+09 | 28127843.80 | 0.101670E+09 | 21621878.31 | 96150305.28 |
Maximum of Months | 0.595009E+09 | 0.279877E+09 | 0.315132E+09 | 0.639599E+09 | 0.555635E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51596269.29 | 0.00 | 51596269.29 | 116808.86 | 0.345681E+09 |
February | 71005620.02 | 0.00 | 71005620.02 | 904224.92 | 0.294559E+09 |
March | 95351009.77 | 3228.27 | 95347781.49 | 23914915.32 | 0.215193E+09 |
April | 0.117631E+09 | 561515.66 | 0.117070E+09 | 54172548.88 | 0.129664E+09 |
May | 0.141194E+09 | 6063143.46 | 0.135131E+09 | 91432374.02 | 86881703.98 |
June | 0.164274E+09 | 13945088.33 | 0.150329E+09 | 0.128372E+09 | 66945381.94 |
July | 0.158098E+09 | 10735283.42 | 0.147363E+09 | 0.147666E+09 | 51725052.50 |
August | 0.136884E+09 | 2630971.38 | 0.134253E+09 | 0.124397E+09 | 71739143.12 |
September | 0.100407E+09 | 43211.73 | 0.100363E+09 | 67906660.97 | 0.108221E+09 |
October | 77524259.46 | 0.00 | 77524259.46 | 29918673.39 | 0.143702E+09 |
November | 50413882.42 | 0.00 | 50413882.42 | 8972244.53 | 0.183226E+09 |
December | 48292544.19 | 0.00 | 48292544.19 | 320264.63 | 0.324623E+09 |
Annual Sum or Average | 0.121267E+10 | 33982442.27 | 0.117869E+10 | 0.678094E+09 | 0.202216E+10 |
Minimum of Months | 48292544.19 | 0.00 | 48292544.19 | 116808.86 | 51725052.50 |
Maximum of Months | 0.164274E+09 | 13945088.33 | 0.150329E+09 | 0.147666E+09 | 0.345681E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51594504.64 | 0.00 | 51594504.64 | 116760.67 | 0.345682E+09 |
February | 71003202.49 | 0.00 | 71003202.49 | 903977.64 | 0.294561E+09 |
March | 95348039.10 | 3228.12 | 95344810.97 | 23913290.82 | 0.215194E+09 |
April | 0.117628E+09 | 561489.34 | 0.117066E+09 | 54169507.87 | 0.129664E+09 |
May | 0.141190E+09 | 6062859.28 | 0.135127E+09 | 91428860.49 | 86881487.42 |
June | 0.164270E+09 | 13944434.71 | 0.150325E+09 | 0.128368E+09 | 66944974.56 |
July | 0.158094E+09 | 10734780.25 | 0.147359E+09 | 0.147662E+09 | 51724547.38 |
August | 0.136879E+09 | 2630848.06 | 0.134249E+09 | 0.124393E+09 | 71738717.86 |
September | 0.100403E+09 | 43209.71 | 0.100360E+09 | 67903923.74 | 0.108220E+09 |
October | 77521739.66 | 0.00 | 77521739.66 | 29916858.20 | 0.143702E+09 |
November | 50412154.55 | 0.00 | 50412154.55 | 8971588.88 | 0.183226E+09 |
December | 48290854.31 | 0.00 | 48290854.31 | 320211.15 | 0.324624E+09 |
Annual Sum or Average | 0.121263E+10 | 33980849.46 | 0.117865E+10 | 0.678067E+09 | 0.202216E+10 |
Minimum of Months | 48290854.31 | 0.00 | 48290854.31 | 116760.67 | 51724547.38 |
Maximum of Months | 0.164270E+09 | 13944434.71 | 0.150325E+09 | 0.147662E+09 | 0.345682E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39704594.67 | 0.319080E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311607.92 | 0.281265E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222889E+09 | 0.197939E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318970E+09 | 0.118886E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429066E+09 | 0.114863E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485526E+09 | 0.114234E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466624E+09 | 0.118242E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388222E+09 | 0.139903E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154013E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164178E+09 | 0.144800E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81163999.29 | 0.142427E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741508.15 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298092E+10 | 0.213651E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741508.15 | 0.114234E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485526E+09 | 0.319080E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.92 | 666.75 | 142.43 | 24.47 | 117.96 | 0.00 | 0.00 |
February | 39.71 | 621.04 | 227.05 | 43.45 | 183.61 | 0.00 | 0.00 |
March | 186.11 | 396.41 | 335.87 | 113.79 | 222.08 | 0.00 | 0.00 |
April | 310.70 | 261.87 | 412.73 | 132.22 | 280.51 | 0.00 | 0.00 |
May | 442.82 | 178.35 | 485.46 | 176.11 | 309.36 | 0.00 | 0.00 |
June | 591.27 | 145.61 | 585.87 | 226.71 | 359.15 | 0.00 | 0.00 |
July | 575.08 | 109.39 | 528.04 | 187.48 | 340.56 | 0.00 | 0.00 |
August | 504.32 | 146.72 | 472.66 | 159.06 | 313.59 | 0.00 | 0.00 |
September | 337.22 | 221.05 | 369.20 | 126.09 | 243.10 | 0.00 | 0.00 |
October | 160.80 | 281.39 | 246.91 | 66.58 | 180.33 | 0.00 | 0.00 |
November | 56.03 | 369.67 | 150.00 | 31.55 | 118.46 | 0.00 | 0.00 |
December | 10.41 | 631.93 | 132.98 | 21.00 | 111.98 | 0.00 | 0.00 |
Annual Sum or Average | 270.06 | 334.45 | 341.28 | 109.36 | 231.92 | 0.00 | 0.00 |
Minimum of Months | 10.41 | 109.39 | 132.98 | 21.00 | 111.98 | 0.00 | 0.00 |
Maximum of Months | 591.27 | 666.75 | 585.87 | 226.71 | 359.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.24 | 1191.31 | 300.23 | 90.73 | 209.49 | 0.00 | 0.00 |
February | 344.38 | 1162.64 | 473.98 | 139.48 | 334.51 | 0.00 | 0.00 |
March | 832.17 | 739.02 | 737.33 | 382.14 | 355.18 | 0.00 | 0.00 |
April | 1230.59 | 458.66 | 969.70 | 515.03 | 454.66 | 0.00 | 0.00 |
May | 1601.95 | 428.85 | 1241.50 | 764.19 | 477.31 | 0.00 | 0.00 |
June | 1873.17 | 440.72 | 1436.48 | 899.78 | 536.70 | 0.00 | 0.00 |
July | 1742.17 | 441.47 | 1335.97 | 811.71 | 524.27 | 0.00 | 0.00 |
August | 1449.45 | 522.34 | 1136.34 | 631.12 | 505.22 | 0.00 | 0.00 |
September | 1035.95 | 594.18 | 841.26 | 456.09 | 385.18 | 0.00 | 0.00 |
October | 612.97 | 540.62 | 526.08 | 227.27 | 298.81 | 0.00 | 0.00 |
November | 313.13 | 549.49 | 303.54 | 93.90 | 209.64 | 0.00 | 0.00 |
December | 122.24 | 1085.93 | 263.89 | 57.59 | 206.30 | 0.00 | 0.00 |
Annual Sum or Average | 945.24 | 677.48 | 798.86 | 423.99 | 374.86 | 0.00 | 0.00 |
Minimum of Months | 122.24 | 428.85 | 263.89 | 57.59 | 206.30 | 0.00 | 0.00 |
Maximum of Months | 1873.17 | 1191.31 | 1436.48 | 899.78 | 536.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29238135.43 | 0.178583E+10 | 0.381485E+09 | 65547423.70 | 0.315938E+09 | 0.00 | 0.00 |
February | 96070382.03 | 0.150242E+10 | 0.549289E+09 | 0.105110E+09 | 0.444179E+09 | 0.00 | 0.00 |
March | 0.498483E+09 | 0.106175E+10 | 0.899602E+09 | 0.304770E+09 | 0.594832E+09 | 0.00 | 0.00 |
April | 0.805344E+09 | 0.678757E+09 | 0.106979E+10 | 0.342714E+09 | 0.727078E+09 | 0.00 | 0.00 |
May | 0.118604E+10 | 0.477698E+09 | 0.130026E+10 | 0.471682E+09 | 0.828581E+09 | 0.00 | 0.00 |
June | 0.153258E+10 | 0.377414E+09 | 0.151856E+10 | 0.587644E+09 | 0.930919E+09 | 0.00 | 0.00 |
July | 0.154028E+10 | 0.292993E+09 | 0.141431E+10 | 0.502154E+09 | 0.912153E+09 | 0.00 | 0.00 |
August | 0.135078E+10 | 0.392969E+09 | 0.126597E+10 | 0.426034E+09 | 0.839931E+09 | 0.00 | 0.00 |
September | 0.874076E+09 | 0.572964E+09 | 0.956959E+09 | 0.326836E+09 | 0.630123E+09 | 0.00 | 0.00 |
October | 0.430690E+09 | 0.753663E+09 | 0.661322E+09 | 0.178338E+09 | 0.482984E+09 | 0.00 | 0.00 |
November | 0.145239E+09 | 0.958192E+09 | 0.388808E+09 | 81765352.72 | 0.307043E+09 | 0.00 | 0.00 |
December | 27894876.33 | 0.169256E+10 | 0.356179E+09 | 56255687.60 | 0.299923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851672E+10 | 0.105472E+11 | 0.107625E+11 | 0.344885E+10 | 0.731369E+10 | 0.00 | 0.00 |
Minimum of Months | 27894876.33 | 0.292993E+09 | 0.356179E+09 | 56255687.60 | 0.299923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154028E+10 | 0.178583E+10 | 0.151856E+10 | 0.587644E+09 | 0.930919E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397045E+09 | 0.319080E+10 | 0.804130E+09 | 0.243022E+09 | 0.561108E+09 | 0.00 | 0.00 |
February | 0.833112E+09 | 0.281265E+10 | 0.114665E+10 | 0.337418E+09 | 0.809236E+09 | 0.00 | 0.00 |
March | 0.222889E+10 | 0.197939E+10 | 0.197485E+10 | 0.102353E+10 | 0.951326E+09 | 0.00 | 0.00 |
April | 0.318970E+10 | 0.118886E+10 | 0.251345E+10 | 0.133497E+10 | 0.117849E+10 | 0.00 | 0.00 |
May | 0.429066E+10 | 0.114863E+10 | 0.332524E+10 | 0.204681E+10 | 0.127842E+10 | 0.00 | 0.00 |
June | 0.485525E+10 | 0.114233E+10 | 0.372336E+10 | 0.233224E+10 | 0.139112E+10 | 0.00 | 0.00 |
July | 0.466624E+10 | 0.118242E+10 | 0.357827E+10 | 0.217408E+10 | 0.140419E+10 | 0.00 | 0.00 |
August | 0.388220E+10 | 0.139903E+10 | 0.304358E+10 | 0.169040E+10 | 0.135318E+10 | 0.00 | 0.00 |
September | 0.268519E+10 | 0.154013E+10 | 0.218055E+10 | 0.118218E+10 | 0.998376E+09 | 0.00 | 0.00 |
October | 0.164178E+10 | 0.144799E+10 | 0.140905E+10 | 0.608719E+09 | 0.800331E+09 | 0.00 | 0.00 |
November | 0.811640E+09 | 0.142427E+10 | 0.786768E+09 | 0.243386E+09 | 0.543382E+09 | 0.00 | 0.00 |
December | 0.327415E+09 | 0.290855E+10 | 0.706795E+09 | 0.154249E+09 | 0.552546E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298091E+11 | 0.213650E+11 | 0.251927E+11 | 0.133710E+11 | 0.118217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327415E+09 | 0.114233E+10 | 0.706795E+09 | 0.154249E+09 | 0.543382E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485525E+10 | 0.319080E+10 | 0.372336E+10 | 0.233224E+10 | 0.140419E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.3 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.73 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.65 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.46 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.38 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.38 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.41 | 11.22 | 4.10 | 7.07 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.35 | 4.97 | 4.79 | 0.12 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.71 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.35 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.3 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.38 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.13 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.16 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.04 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.42 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.82 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.22 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.71 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.23 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.51 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.12 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.84 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.40 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.16 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.71 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.2 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.3 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.4 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.82 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.76 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.17 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.74 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.41 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.22 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.95 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.40 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.96 | 4.80 | 10.49 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.96 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108013E+10 | -922983980.3 | 0.00 | 0.00 | 744.00 | 0.00 | -157150296.8 | 58.99 | 0.00 | 0.00 |
February | 0.100199E+10 | -860104253.5 | 0.00 | 0.00 | 672.00 | 0.00 | -141882142.4 | 58.99 | 0.00 | 0.00 |
March | 0.114613E+10 | -991584967.9 | 0.00 | 0.00 | 744.00 | 0.00 | -154543414.1 | 58.99 | 0.00 | 0.00 |
April | 0.103263E+10 | -884837950.3 | 0.00 | 0.00 | 720.00 | 0.00 | -147790596.0 | 58.99 | 0.00 | 0.00 |
May | 0.101131E+10 | -868065460.8 | 0.00 | 0.00 | 744.00 | 0.00 | -143242268.6 | 58.99 | 0.00 | 0.00 |
June | 0.941024E+09 | -811341212.5 | 0.00 | 0.00 | 720.00 | 0.00 | -129682904.8 | 58.99 | 0.00 | 0.00 |
July | 0.877637E+09 | -745940149.1 | 0.00 | 0.00 | 744.00 | 0.00 | -131697153.3 | 58.99 | 0.00 | 0.00 |
August | 0.918539E+09 | -786007199.6 | 0.00 | 0.00 | 744.00 | 0.00 | -132531599.7 | 58.99 | 0.00 | 0.00 |
September | 0.874442E+09 | -743973413.1 | 0.00 | 0.00 | 720.00 | 0.00 | -130468791.0 | 58.99 | 0.00 | 0.00 |
October | 0.932044E+09 | -783155254.9 | 0.00 | 0.00 | 744.00 | 0.00 | -148888352.8 | 58.99 | 0.00 | 0.00 |
November | 0.950273E+09 | -800546144.6 | 0.00 | 0.00 | 720.00 | 0.00 | -149726788.6 | 58.99 | 0.00 | 0.00 |
December | 0.104111E+10 | -884020524.4 | 0.00 | 0.00 | 744.00 | 0.00 | -157094130.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.118073E+11 | -.100826E+11 | 8760.00 | -.172470E+10 | 58.99 | |||||
Minimum of Months | 0.874442E+09 | -991584967.9 | 0.00 | 0.00 | 672.00 | 0.00 | -157150296.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114613E+10 | -743973413.1 | 0.00 | 0.00 | 744.00 | 0.00 | -129682904.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | ||||||||||
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120033E+11 | 27702.23 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114371E+11 | 27702.23 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750132E+10 | 27702.23 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357499E+10 | 27702.23 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723899E+09 | 27702.23 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18719108.08 | 5427.89 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44938085.89 | 27702.23 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167137E+10 | 27702.23 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428044E+10 | 27702.23 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105286E+11 | 27702.23 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517847E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120033E+11 | 27702.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.703803E+11 | 84772.23 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703931E+11 | 84772.23 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359880E+11 | 84772.23 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141214E+11 | 84772.23 | 01-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370835E+09 | 60834.97 | 02-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586382E+10 | 84772.23 | 16-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228393E+11 | 84772.23 | 02-NOV-17:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.678446E+11 | 84772.23 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287801E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.703931E+11 | 84772.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187710E+12 | 222623.42 | 12-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193241E+12 | 222623.42 | 06-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723380E+11 | 123224.70 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111292E+11 | 84747.19 | 16-APR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141398E+09 | 19266.99 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227082E+11 | 52323.50 | 25-NOV-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177569E+12 | 199874.34 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.664837E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193241E+12 | 222623.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 50577898.27 | 45394939.80 | 2835.97 | 15-MAR-15:10 | 2624.60 | 0.00 |
April | 0.00 | 0.00 | 4907289.36 | 4744401.52 | 1407.62 | 08-APR-14:40 | 1348.21 | 0.00 |
May | 0.00 | 0.00 | 0.723205E+09 | 0.678626E+09 | 6824.45 | 27-MAY-18:00 | 6824.45 | 0.00 |
June | 0.00 | 0.00 | 0.569697E+10 | 0.478476E+10 | 21385.40 | 19-JUN-00:02 | 13734.62 | 0.00 |
July | 0.00 | 0.00 | 0.101973E+11 | 0.817059E+10 | 22557.07 | 17-JUL-00:01 | 14214.94 | 0.00 |
August | 0.00 | 0.00 | 0.916438E+10 | 0.782577E+10 | 23075.69 | 14-AUG-00:01 | 13222.44 | 0.00 |
September | 0.00 | 0.00 | 0.393003E+10 | 0.335906E+10 | 20110.65 | 18-SEP-00:03 | 15062.56 | 0.00 |
October | 0.00 | 0.00 | 0.120031E+09 | 0.109828E+09 | 3035.30 | 11-OCT-16:00 | 2845.58 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.298874E+11 | 0.249788E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101973E+11 | 0.817059E+10 | 23075.69 | 15062.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.470076E+10 | 0.349689E+10 | 65200.05 | 27-JUN-17:10 | 38287.57 | 0.00 |
July | 0.00 | 0.00 | 0.155121E+11 | 0.112341E+11 | 63332.91 | 16-JUL-10:33 | 39059.47 | 0.00 |
August | 0.00 | 0.00 | 0.114122E+11 | 0.926129E+10 | 63271.13 | 13-AUG-16:13 | 38892.44 | 0.00 |
September | 0.00 | 0.00 | 0.101889E+10 | 0.778967E+09 | 20355.27 | 16-SEP-13:40 | 15467.23 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.326440E+11 | 0.247712E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155121E+11 | 0.112341E+11 | 65200.05 | 39059.47 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132973E+10 | 0.08 | 510.66 | 01-JAN-00:02 | 0.08 |
February | 0.120911E+10 | 0.08 | 510.66 | 01-FEB-00:02 | 0.08 |
March | 0.814450E+09 | 0.05 | 510.66 | 01-MAR-00:02 | 0.08 |
April | 0.235276E+09 | 0.01 | 510.66 | 01-APR-00:03 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 10356165.03 | 0.00 | 510.66 | 30-OCT-01:10 | 0.08 |
November | 0.591486E+09 | 0.03 | 510.66 | 02-NOV-20:25 | 0.08 |
December | 0.132046E+10 | 0.08 | 510.66 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.551087E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132973E+10 | 0.08 | 510.66 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134152E+10 | 0.71 | 1182.96 | 02-JAN-10:10 | 0.96 |
February | 0.124806E+10 | 0.72 | 1182.96 | 08-FEB-07:15 | 0.96 |
March | 0.135622E+10 | 0.56 | 1182.96 | 07-MAR-16:30 | 0.96 |
April | 0.121119E+10 | 0.42 | 1182.96 | 05-APR-15:30 | 0.96 |
May | 0.123293E+10 | 0.39 | 1182.96 | 01-MAY-08:20 | 0.96 |
June | 0.128630E+10 | 0.47 | 1182.96 | 02-JUN-06:40 | 0.95 |
July | 0.135394E+10 | 0.59 | 1182.96 | 24-JUL-06:20 | 0.95 |
August | 0.141800E+10 | 0.59 | 1182.96 | 05-AUG-06:10 | 0.95 |
September | 0.120034E+10 | 0.41 | 1182.96 | 02-SEP-08:65 | 0.95 |
October | 0.119133E+10 | 0.38 | 1182.96 | 02-OCT-13:40 | 0.95 |
November | 0.115964E+10 | 0.39 | 1182.96 | 02-NOV-10:40 | 0.96 |
December | 0.131130E+10 | 0.64 | 1182.96 | 02-DEC-09:20 | 0.96 |
Annual Sum or Average | 0.153108E+11 | 0.52 | |||
Minimum of Months | 0.115964E+10 | 0.38 | 1182.96 | 0.95 | |
Maximum of Months | 0.141800E+10 | 0.72 | 1182.96 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.407468E+10 | 0.82 | 2611.34 | 06-JAN-15:10 | 0.93 |
February | 0.387230E+10 | 0.82 | 2611.34 | 01-FEB-09:20 | 0.92 |
March | 0.363511E+10 | 0.76 | 2611.34 | 01-MAR-11:50 | 0.92 |
April | 0.298036E+10 | 0.64 | 2611.34 | 01-APR-06:10 | 0.92 |
May | 0.270203E+10 | 0.37 | 2611.34 | 02-MAY-06:10 | 0.92 |
June | 0.269951E+10 | 0.37 | 2611.34 | 02-JUN-12:50 | 0.91 |
July | 0.269344E+10 | 0.40 | 2611.34 | 03-JUL-10:20 | 0.91 |
August | 0.284981E+10 | 0.40 | 2611.34 | 01-AUG-12:10 | 0.91 |
September | 0.258523E+10 | 0.35 | 2611.34 | 14-SEP-13:20 | 0.91 |
October | 0.276787E+10 | 0.52 | 2611.34 | 18-OCT-06:20 | 0.92 |
November | 0.307080E+10 | 0.73 | 2611.34 | 02-NOV-07:00 | 0.92 |
December | 0.403904E+10 | 0.82 | 2611.34 | 01-DEC-07:50 | 0.92 |
Annual Sum or Average | 0.379702E+11 | 0.58 | |||
Minimum of Months | 0.258523E+10 | 0.35 | 2611.34 | 0.91 | |
Maximum of Months | 0.407468E+10 | 0.82 | 2611.34 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.18 | 0.01 |
February | 3.26 | 0.03 |
March | 2.84 | 0.01 |
April | 1.40 | 0.13 |
May | 0.21 | 0.97 |
June | 0.50 | 4.34 |
July | 0.11 | 0.00 |
August | 0.25 | 2.37 |
September | 1.00 | 4.34 |
October | 0.62 | 0.54 |
November | 2.61 | 0.02 |
December | 3.06 | 0.00 |
Annual Sum or Average | 20.03 | 0.40 |
Minimum of Months | 0.11 | 0.00 |
Maximum of Months | 4.18 | 4.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.41 | 0.00 |
February | 1.68 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 0.08 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.44 | 0.00 |
Annual Sum or Average | 2.77 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.68 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.39 | 0.00 |
August | 0.56 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.94 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.56 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.134152E+10 | 0.171611E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124806E+10 | 0.162936E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136884E+10 | 0.108301E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121240E+10 | 0.521083E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.140899E+10 | 0.105434E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265182E+10 | 28728238.52 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.379575E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.361842E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213997E+10 | 67467793.68 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122070E+10 | 0.244624E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115964E+10 | 0.626041E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131130E+10 | 0.150918E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224774E+11 | 0.744447E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115964E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.379575E+10 | 0.171611E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.407468E+10 | 0.989134E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.387230E+10 | 0.973843E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.363511E+10 | 0.516938E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.298036E+10 | 0.205967E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.270203E+10 | 0.563765E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.404550E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.711846E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.614744E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.287889E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.276787E+10 | 0.869628E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.307080E+10 | 0.333168E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.403904E+10 | 0.952329E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.473325E+11 | 0.406398E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.270203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.711846E+10 | 0.989134E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134152E+10 | 0.00 | 0.120033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124806E+10 | 0.00 | 0.114371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135622E+10 | 50577898.27 | 0.750132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121119E+10 | 4907289.36 | 0.357499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123293E+10 | 0.723205E+09 | 0.723899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128630E+10 | 0.569697E+10 | 18719108.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135394E+10 | 0.101973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141800E+10 | 0.916438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120034E+10 | 0.393003E+10 | 44938085.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119133E+10 | 0.120031E+09 | 0.167137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115964E+10 | 0.00 | 0.428044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131130E+10 | 0.00 | 0.105286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153108E+11 | 0.298874E+11 | 0.517847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141800E+10 | 0.101973E+11 | 0.120033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.407468E+10 | 0.00 | 0.703803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387230E+10 | 0.00 | 0.703931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363511E+10 | 0.00 | 0.359880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298036E+10 | 0.00 | 0.141214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270203E+10 | 0.00 | 0.370835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269951E+10 | 0.470076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269344E+10 | 0.155121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.284981E+10 | 0.114122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258523E+10 | 0.101889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276787E+10 | 0.00 | 0.586382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307080E+10 | 0.00 | 0.228393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403904E+10 | 0.00 | 0.678446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379702E+11 | 0.326440E+11 | 0.287801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407468E+10 | 0.155121E+11 | 0.703931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.134152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135622E+10 | 0.00 | 0.00 | 0.00 | 12618534.97 | 0.00 | 0.108301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121119E+10 | 0.00 | 0.00 | 0.00 | 1215471.07 | 0.00 | 0.521083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123293E+10 | 0.00 | 0.00 | 0.00 | 0.176064E+09 | 0.00 | 0.105434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128630E+10 | 0.00 | 0.00 | 0.00 | 0.136552E+10 | 0.00 | 28728238.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135394E+10 | 0.00 | 0.00 | 0.00 | 0.244181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141800E+10 | 0.00 | 0.00 | 0.00 | 0.220042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120034E+10 | 0.00 | 0.00 | 0.00 | 0.939630E+09 | 0.00 | 67467793.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119133E+10 | 0.00 | 0.00 | 0.00 | 29369744.15 | 0.00 | 0.244624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153108E+11 | 0.00 | 0.00 | 0.00 | 0.716665E+10 | 0.00 | 0.744447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.115964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141800E+10 | 0.00 | 0.00 | 0.00 | 0.244181E+10 | 0.00 | 0.171611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.407468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269951E+10 | 0.00 | 0.00 | 0.00 | 0.134598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269344E+10 | 0.00 | 0.00 | 0.00 | 0.442502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.284981E+10 | 0.00 | 0.00 | 0.00 | 0.329764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258523E+10 | 0.00 | 0.00 | 0.00 | 0.293658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379702E+11 | 0.00 | 0.00 | 0.00 | 0.936230E+10 | 0.00 | 0.406398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.258523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407468E+10 | 0.00 | 0.00 | 0.00 | 0.442502E+10 | 0.00 | 0.989134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334443E+10 | 0.00 | 0.00 | 0.15 |
February | 0.00 | 0.00 | 12567.78 | 0.00 | 0.00 | 0.319258E+10 | 0.00 | 19711.25 | 0.16 |
March | 90725927.37 | 1845982.13 | 0.00 | 1528.00 | 1910585.70 | 0.241531E+10 | 1235466.75 | 0.00 | 0.15 |
April | 0.257740E+09 | 0.00 | 0.00 | 1088.86 | 0.00 | 0.137728E+10 | 3675610.21 | 0.00 | 0.15 |
May | 0.585709E+09 | 5910756.23 | 0.00 | 773280.51 | 391957.03 | 0.258872E+09 | 0.222843E+09 | 0.00 | 0.14 |
June | 0.113180E+09 | 0.347428E+09 | 0.00 | 3704263.43 | 495050.11 | 17633403.01 | 0.412367E+09 | 0.00 | 0.16 |
July | 23448580.59 | 0.102488E+10 | 0.00 | 2589835.44 | 269890.93 | 0.00 | 71029434.01 | 0.00 | 0.16 |
August | 45660531.68 | 0.543785E+09 | 0.00 | 4542604.15 | 768614.81 | 0.00 | 0.169556E+09 | 0.00 | 0.16 |
September | 0.195207E+09 | 0.164666E+09 | 0.00 | 2982223.02 | 0.00 | 29670613.76 | 0.422608E+09 | 0.00 | 0.15 |
October | 0.657629E+09 | 0.00 | 0.00 | 116739.29 | 0.00 | 0.727902E+09 | 59471027.61 | 172.65 | 0.14 |
November | 84248410.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169031E+10 | 0.00 | 99910.46 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311041E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.205355E+10 | 0.208852E+10 | 12567.78 | 14711562.69 | 3836098.59 | 0.161644E+11 | 0.136278E+10 | 119794.36 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.657629E+09 | 0.102488E+10 | 12567.78 | 4542604.15 | 1910585.70 | 0.334443E+10 | 0.422608E+09 | 99910.46 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837498E+10 | 0.00 | 0.00 | 0.17 |
February | 91645380.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782799E+10 | 0.00 | 0.00 | 0.17 |
March | 0.126843E+10 | 0.00 | 0.00 | 0.00 | 53901582.73 | 0.455568E+10 | 0.00 | 0.00 | 0.19 |
April | 0.221561E+10 | 0.00 | 0.00 | 0.00 | 2460124.51 | 0.128838E+10 | 0.00 | 0.00 | 0.18 |
May | 0.265150E+10 | 0.00 | 0.00 | 0.00 | 13552550.79 | 6229284.16 | 0.00 | 0.00 | 0.19 |
June | 0.186767E+10 | 0.370258E+09 | 0.00 | 2123215.54 | 5604088.72 | 0.00 | 0.643425E+09 | 0.00 | 0.21 |
July | 0.342261E+09 | 0.142580E+10 | 0.00 | 3692275.77 | 0.00 | 0.00 | 0.110706E+10 | 0.00 | 0.24 |
August | 0.908426E+09 | 0.682408E+09 | 0.00 | 6423549.25 | 0.00 | 0.00 | 0.930620E+09 | 0.00 | 0.22 |
September | 0.231258E+10 | 78575840.85 | 0.00 | 496305.10 | 3292.68 | 0.00 | 0.267534E+09 | 0.00 | 0.20 |
October | 0.286126E+10 | 0.00 | 0.00 | 0.00 | 1029791.21 | 0.286724E+09 | 0.00 | 0.00 | 0.17 |
November | 0.127842E+10 | 0.00 | 0.00 | 0.00 | 7238634.06 | 0.264950E+10 | 0.00 | 0.00 | 0.17 |
December | 0.142897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759123E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.159407E+11 | 0.255704E+10 | 0.00 | 12735345.65 | 83790064.69 | 0.325807E+11 | 0.294864E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.286126E+10 | 0.142580E+10 | 0.00 | 6423549.25 | 53901582.73 | 0.837498E+10 | 0.110706E+10 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |