Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2167.51 | 448.28 | 448.28 |
Net Site Energy | 2167.51 | 448.28 | 448.28 |
Total Source Energy | 4134.42 | 855.08 | 855.08 |
Net Source Energy | 4134.42 | 855.08 | 855.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1310.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 856.86 | 1310.65 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1310.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 23.24 | 271.07 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 177.22 | 271.07 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 23.24 | 271.07 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 177.22 | 271.07 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 856.861 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 856.861 | 100.00 |
Total On-Site and Utility Electric Sources | 856.861 | 100.00 |
Total Electricity End Uses | 856.861 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 70.33 |
Time Setpoint Not Met During Occupied Cooling | 1.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2229.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:50 | 05-JAN-17:49 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 420118.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15646.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6758.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1780.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 69917.61 | 420118.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 420118.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15646.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4452.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1780.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1420.74 | 0.00 | 0.00 | 0.00 |
Cooling | 45.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 223.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2713.68 | 1420.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 293.84 | 0.00 | 0.00 | 0.00 |
Cooling | 9.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 46.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 561.24 | 293.84 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 293.84 | 0.00 | 0.00 | 0.00 |
Cooling | 9.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 46.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 561.24 | 293.84 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.18 |
ZONE2 FINE STORAGE DIRECT AIR | 2.83 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.96 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.96 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 216706.76 |
PSZ-OFFICE HEATING COIL | 29022.58 |
PSZ-FINE STORAGE HEATING COIL | 92725.69 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 216706.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.00 | 1.00 | 1.18 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 1.00 | 1.00 | 2.83 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.18 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.83 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 1.18 | 19609.58 | 29022.58 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.83 | 2.83 | 2.83 | 2.83 | 55018.42 | 92725.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.18 | 0.592305 | 1.18 | 19609.50 | 19609.58 | 9804.79 | 19609.58 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.83 | 1.42 | 2.83 | 48312.72 | 55018.42 | 27509.21 | 55018.42 | 0.744533 | 0.744530 | 0.744530 | 0.744530 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.18 | 1350.59 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.83 | 3102.26 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10494.99767 | 12593.99720 | 0.98718 | 1.18461 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13979.24064 | 16775.08877 | 0.44898 | 0.53877 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32215.74866 | 38658.89840 | 2.36200 | 2.83439 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.26593E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 65897.58996 | 79077.10795 | 1.78135 | 2.13762 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 180588.95258 | 216706.74310 | 4.96996 | 5.96396 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15703.69 | 1.18461 | 1.18461 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16070.68 | 0.53877 | 0.53877 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47021.95 | 2.83439 | 2.83439 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 74698.92 | 2.13762 | 2.13762 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18461 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.83439 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.96396 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.96396 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 216706.76215 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 216706.74310 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.18461 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.18461 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.18461 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18461 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18461 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.18461 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.83439 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.83439 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.83439 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.83439 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.83439 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.83439 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.18461 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.83439 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18461 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18461 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18461 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18461 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.18461 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18461 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59231 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18461 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19609.50174 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19609.58000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9804.79000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19609.58000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19609.58000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29022.57643 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18461 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1350.59102 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29022.57643 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.83439 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.83439 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.83439 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.83439 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.83439 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.83439 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.41720 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.83439 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 48312.72439 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 55018.42000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27509.21000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 55018.42000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74453 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74453 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74453 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74453 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55018.42000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 92725.69377 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.83439 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3102.26040 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 92725.69377 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18690.4 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 52817.7 | 13.28 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2006922969 | 0.1959335527 | Pass | Pass | 3.2758621098 | 23.4640570350 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6715379510 | 0.6606439926 | Pass | Pass | 0.6960967984 | 0.8455320807 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.1608043810E-003 | 1.2545583675E-002 | Pass | Pass | 7.3031490073E-002 | 0.2171979066 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.57 | 83.57 | 123.26 | |
Exterior Lighting Total | 7857.24 | 123.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19609.58 | 15661.39 | 3948.19 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 55018.42 | 40962.86 | 14055.56 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18690.4 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 52817.7 | 13.28 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 216706.76 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29022.58 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 92725.69 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.96 | 554.11 | 92.91 | 1.00 | 3.10 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.18 | 1350.59 | 1140.11 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.83 | 3102.26 | 1094.51 | 1.00 | 1.24 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10495.00 | 12594.00 | 53.17 | 0.987 | 1.185 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00804 | 31.16 | 0.00627 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32215.75 | 38658.90 | 27.74 | 2.362 | 2.834 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00782 | 33.08 | 0.00627 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13979.24 | 16775.09 | 70.82 | 0.449 | 0.539 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00767 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 65897.59 | 79077.11 | 56.75 | 1.781 | 2.138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00639 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 180588.95 | 216706.74 | 67.62 | 4.970 | 5.964 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00873 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.18 | 1.18 | 0.54 | 0.54 | 1.1846 | 1.1846 | 1.1846 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 2.14 | 2.14 | 2.8344 | 2.8344 | 2.8344 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 216706.762 | 216706.762 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 216706.76 | 216706.76 | 5.963955 | 3.83 | 3.83 | 0.00735755 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.98 | 0.00873173 | 100.0000 | 216706.74 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19609.580 | 0.000 | 1.184610 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19609.58 | 19609.58 | 1.184610 | 24.53 | 14.67 | 0.00788965 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 8.6345 | 23.90 | 0.00804310 | 38.1227 | 10495.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29022.576 | 29022.576 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29022.58 | 29022.58 | 1.184615 | 11.81 | 8.23 | 0.00628023 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 8.6344 | 21.10 | 0.00767179 | 43.1367 | 13979.24 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 55018.420 | 0.000 | 2.834390 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 55018.42 | 55018.42 | 2.834390 | 27.68 | 15.49 | 0.00758476 | 12.00 | 10.08 | 0.00800000 | 33.24 | 0.00626593 | 16.25 | 14.9843 | 26.70 | 0.00781742 | 31.3782 | 32206.96 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 92725.694 | 92725.694 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 92725.69 | 92725.69 | 2.834395 | 6.98 | 4.77 | 0.00518848 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 14.9842 | 15.55 | 0.00639018 | 51.0013 | 65897.59 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 216706.762 | 216706.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.963955 | 6.28087933 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 216706.76 | 216706.76 | 1.0000 | 6.28087933 | 5.963955 | 3.83 | 3.83 | 0.00735755 | 22299.8 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 216706.76 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.98 | 0.00873173 | 9.98 | 0.00873173 | 100.0000 | 216706.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19609.580 | 0.000 | 1.184610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5065 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19609.58 | 19609.58 | 1.0000 | 1.24756003 | 1.184610 | 24.53 | 14.67 | 0.00788965 | 44736.6 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19609.58 | 31.16 | 0.00626593 | 15.56 | 0.10228487 | 8.6345 | 23.90 | 0.00804310 | 23.90 | 0.00804310 | 38.1227 | 10495.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29022.576 | 29022.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.184615 | 1.24756506 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29022.58 | 29022.58 | 1.0000 | 1.24756506 | 1.184615 | 11.81 | 8.23 | 0.00628023 | 27715.2 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29022.58 | -27.60 | 0.00034190 | -27.60 | 0.10228487 | 8.6344 | 21.05 | 0.00767179 | 21.10 | 0.00767179 | 43.1367 | 13979.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55018.420 | 0.000 | 2.834390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9397 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 55018.42 | 55018.42 | 1.0000 | 2.98500914 | 2.834390 | 27.68 | 15.49 | 0.00758476 | 47174.1 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55018.42 | 33.24 | 0.00626593 | 16.25 | 0.42471267 | 14.9843 | 26.70 | 0.00781728 | 26.70 | 0.00781742 | 31.3782 | 32206.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92725.694 | 92725.694 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.834395 | 2.98501393 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 92725.69 | 92725.69 | 1.0000 | 2.98501393 | 2.834395 | 6.98 | 4.77 | 0.00518848 | 20055.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92725.69 | -27.60 | 0.00034190 | -27.60 | 0.42471267 | 14.9842 | 15.55 | 0.00639018 | 15.55 | 0.00639018 | 51.0013 | 65897.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.18 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.83 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2476.67 | 3073.67 | 2229.33 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2476.67 | 3073.67 | 2229.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 188.33 | 54.50 | 70.33 | 1.50 |
ZONE2 FINE STORAGE | 687.33 | 18.83 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1.67 | 0.00 | 0.00 | 0.00 |
Facility | 822.33 | 65.67 | 70.33 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.351 | 0.306 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
Electricity:Building | 623.08 | 4992.32 | 01-JAN-00:10 | 48037.94 | 23-JUN-13:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 423.49 | 2759.73 | 01-JAN-00:10 | 33963.13 | 23-JUN-13:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.47 | 483.00 | 06-JAN-18:10 | 2906.52 | 18-FEB-12:10 |
WaterSystems:Electricity | 27.47 | 483.00 | 06-JAN-18:10 | 2906.52 | 18-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 27.47 | 483.00 | 06-JAN-18:10 | 2906.52 | 18-FEB-12:10 |
Fans:Electricity | 70.42 | 0.00 | 01-JAN-12:40 | 6758.15 | 17-JUL-16:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.84 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-19:20 |
Ventilation (simple):Fans:Electricity | 1.84 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-19:20 |
ElectricityPurchased:Facility | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
ElectricityPurchased:Plant | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
Cogeneration:ElectricityPurchased | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
ElectricityNet:Plant | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
Cogeneration:ElectricityNet | 856.86 | 5475.32 | 01-JAN-12:40 | 69917.61 | 17-JUL-14:50 |
Electricity:HVAC | 83.05 | 0.00 | 01-JAN-12:40 | 22791.31 | 17-JUL-16:00 |
General:Fans:Electricity | 68.58 | 0.00 | 01-JAN-12:40 | 5006.97 | 13-JAN-09:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.47 | 0.00 | 01-JAN-00:10 | 18338.46 | 17-JUL-16:00 |
ExteriorLights:Electricity | 123.26 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.26 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1310.65 | 0.00 | 01-JAN-12:40 | 420118.90 | 05-JAN-17:50 |
Gas:HVAC | 1310.65 | 0.00 | 01-JAN-12:40 | 420118.90 | 05-JAN-17:50 |
Heating:Gas | 1310.65 | 0.00 | 01-JAN-12:40 | 420118.90 | 05-JAN-17:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2073.01 | 0.00 | 01-JAN-12:40 | 647740.10 | 05-JAN-18:00 |
EnergyTransfer:Building | 1031.13 | 0.00 | 01-JAN-12:40 | 315608.71 | 05-JAN-18:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 65.57 | 0.00 | 01-JAN-00:40 | 25601.80 | 09-JAN-07:20 |
Heating:EnergyTransfer | 989.00 | 0.00 | 01-JAN-12:40 | 315608.71 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 49.06 | 0.00 | 01-JAN-00:40 | 25601.80 | 09-JAN-07:20 |
Cooling:EnergyTransfer | 42.13 | 0.00 | 01-JAN-00:10 | 43384.46 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.51 | 0.00 | 01-JAN-00:10 | 10425.25 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 314.54 | 0.00 | 01-JAN-00:40 | 90374.72 | 05-JAN-22:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 288.92 | 0.00 | 01-JAN-00:40 | 90374.72 | 05-JAN-22:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.62 | 0.00 | 01-JAN-00:10 | 33670.81 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 651.01 | 0.00 | 01-JAN-12:20 | 218894.44 | 05-JAN-15:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 651.01 | 0.00 | 01-JAN-12:20 | 218894.44 | 05-JAN-15:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1041.88 | 0.00 | 01-JAN-12:40 | 332132.67 | 05-JAN-17:50 |
HeatingCoils:EnergyTransfer | 993.42 | 0.00 | 01-JAN-12:40 | 332132.67 | 05-JAN-17:50 |
CoolingCoils:EnergyTransfer | 48.46 | 0.00 | 01-JAN-00:10 | 54058.74 | 17-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 49.061 | -16.508 | 0.000 | 0.000 | 3.987 | 30.994 | 31.946 | 9.667 | 0.000 | 0.548 | 0.000 | 0.000 | -12.749 | 0.000 | -25.691 | -71.255 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 288.921 | -25.622 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 2.226 | 0.001 | 0.000 | 0.000 | 0.000 | -212.942 | -189.239 |
ZONE3 BULK STORAGE | 651.014 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 31.290 | 0.000 | 21.410 | 0.000 | 0.000 | -27.397 | 0.000 | -714.539 | -383.423 |
Total Facility | 651.014 | 0.000 | 337.982 | -42.130 | 0.000 | 0.000 | 3.987 | 481.960 | 139.282 | 40.957 | 0.000 | 24.184 | 0.001 | 0.000 | -40.146 | 0.000 | -953.172 | -643.917 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JUL-00:01 | 0.00 | 0.00 | 0.00 | -18328.69 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 17708.46 | 0.00 | -278.04 | 0.00 | -134.44 | 0.00 |
ZONE2 FINE STORAGE | 19-JUL-17:06 | 0.00 | 0.00 | 0.00 | -47664.12 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 3600.71 | 42863.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUL-17:06 | 0.00 | 0.00 | 0.00 | -63873.13 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5239.09 | 0.00 | 4125.63 | 86442.18 | 0.00 | 0.00 | 0.00 | -38976.11 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-JAN-06:31 | 0.00 | 0.00 | 32182.25 | 0.00 | 0.00 | 0.00 | 57.97 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1661.44 | 0.00 | -2523.39 | -29215.59 |
ZONE2 FINE STORAGE | 06-JAN-06:41 | 0.00 | 0.00 | 100948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -29438.46 | -72710.03 |
ZONE3 BULK STORAGE | 05-JAN-16:05 | 218959.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20697.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2827.63 | 0.00 | -224555.52 | -20474.10 |
Total Facility | 05-JAN-22:12 | 217187.99 | 0.00 | 116232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5236.89 | 0.00 | -184706.25 | -150519.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1846 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1846 | 0.0863 | 1.0000 | 0.1023 | 0.0863 | ||
PSZ-FINE STORAGE | 2.8344 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.8344 | 0.1498 | 1.0000 | 0.4247 | 0.1498 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1846 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1846 | 1.0000 | 1.0000 | 0.1023 | 0.0863 | ||
PSZ-FINE STORAGE | 2.8344 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.8344 | 1.0000 | 1.0000 | 0.4247 | 0.1498 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1846 | 1.1846 | 1.1846 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8344 | 2.8344 | 2.8344 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1846 | 1.1846 | 1.1846 | 1.1846 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8344 | 2.8344 | 2.8344 | 2.8344 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1846 | 1.1846 | 1.1846 | 0.1023 | 0.1898 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8344 | 2.8344 | 2.8344 | 0.4247 | 0.1987 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1846 | 1.1846 | 1.1846 | 1.1846 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8344 | 2.8344 | 2.8344 | 2.8344 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 70.33 |
Number of hours cooling loads not met | 1.50 |
Number of hours not met | 71.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1310.65 | 420118.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 14.47 | 18338.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.26 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.84 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 68.58 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.47 | 2906.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 856.86 |
Natural Gas | 0.00 | 1310.65 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2167.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 2.99 |
Fans (All) | 14.56 |
Service Water Heating | 5.68 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 177.22 |
Subtotal | 177.22 |
Natural Gas [MJ/m2] | |
Space Heating | 271.07 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 271.07 |
Subtotal | 271.07 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.24 |
Space Heating | 60.47 |
Space Cooling | 0.67 |
Fans (All) | 3.25 |
Service Water Heating | 1.27 |
Receptacle Equipment | 6.43 |
Miscellaneous | 5.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.415562E+12 |
February | 0.000 | 0.229834E+12 |
March | 0.000 | 0.160874E+12 |
April | 0.000 | 0.379131E+11 |
May | 0.000 | 0.250646E+11 |
June | 0.000 | 0.181415E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.190714E+08 |
September | 0.000 | 0.343544E+10 |
October | 0.000 | 0.173740E+11 |
November | 0.000 | 0.129931E+12 |
December | 0.000 | 0.290459E+12 |
Annual Sum or Average | 0.131065E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.415562E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194881E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.8 | 0.179843E+09 | 274.80 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 236534.29 | 116.01 | 01-MAR-17:00 | 7.80 | 3.21 | 0.210727E+09 | 249.32 | 02-MAR-16:10 | 10.22 | 4.58 |
April | 1136034.31 | 600.25 | 25-APR-16:00 | 17.80 | 7.67 | 0.201224E+09 | 301.59 | 07-APR-14:39 | 22.23 | 9.13 |
May | 0.401290E+09 | 7461.22 | 19-MAY-17:15 | 25.93 | 14.38 | 0.223495E+09 | 301.59 | 20-MAY-10:00 | 22.20 | 13.60 |
June | 0.293421E+10 | 16890.94 | 26-JUN-00:02 | 17.02 | 11.92 | 0.253117E+09 | 301.61 | 22-JUN-13:09 | 27.12 | 17.18 |
July | 0.592420E+10 | 18328.68 | 17-JUL-00:01 | 22.93 | 13.94 | 0.248629E+09 | 301.61 | 01-JUL-15:00 | 24.40 | 16.74 |
August | 0.507752E+10 | 17309.99 | 07-AUG-00:01 | 19.90 | 10.61 | 0.267160E+09 | 301.60 | 01-AUG-14:09 | 19.68 | 13.66 |
September | 0.207781E+10 | 17910.10 | 05-SEP-00:01 | 21.32 | 13.63 | 0.233060E+09 | 301.59 | 05-SEP-15:00 | 22.20 | 14.11 |
October | 89169647.12 | 2801.42 | 18-OCT-16:00 | 24.40 | 10.99 | 0.211706E+09 | 301.59 | 28-OCT-15:39 | 19.27 | 9.37 |
November | 2924024.88 | 229.69 | 10-NOV-15:50 | 5.08 | 0.55 | 0.188952E+09 | 287.50 | 04-NOV-15:09 | 16.60 | 7.87 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.1 | 0.194905E+09 | 236.59 | 04-DEC-08:30 | 2.50 | -0.3 |
Annual Sum or Average | 0.165085E+11 | 0.260770E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.179843E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.592420E+10 | 18328.68 | 25.93 | 14.38 | 0.267160E+09 | 301.61 | 27.12 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1866977.15 | 539.43 | 02-JAN-14:00 | 6.70 | 1.57 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 79947480.20 | 3048.87 | 23-FEB-15:50 | -0.8 | -3.5 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.362733E+09 | 4204.38 | 25-MAR-11:00 | -0.6 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.340023E+09 | 3049.91 | 29-APR-13:00 | 3.30 | -1.9 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.504532E+09 | 7329.07 | 19-MAY-06:10 | 12.57 | 9.28 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.328995E+10 | 41320.32 | 30-JUN-17:08 | 29.90 | 14.48 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.100916E+11 | 47665.89 | 19-JUL-17:06 | 30.77 | 16.43 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.742829E+10 | 47342.67 | 08-AUG-17:06 | 30.50 | 16.30 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.274100E+10 | 46253.27 | 03-SEP-12:53 | 33.30 | 15.90 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.467995E+09 | 4306.09 | 13-OCT-06:10 | 12.12 | 6.47 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.291980E+09 | 3109.04 | 20-NOV-14:30 | 2.10 | -2.5 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 22869752.46 | 1562.06 | 09-DEC-13:30 | 5.25 | 1.64 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.256228E+11 | 0.00 | ||||||||
Minimum of Months | 1866977.15 | 539.43 | -0.8 | -3.5 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.100916E+11 | 47665.89 | 33.30 | 16.43 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:05 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119191E+11 | 32182.17 | 27-JAN-06:31 | -27.1 |
February | 0.777592E+10 | 29832.79 | 10-FEB-06:12 | -19.8 |
March | 0.685942E+10 | 31115.28 | 17-MAR-05:31 | 0.60 |
April | 0.351039E+10 | 29558.63 | 29-APR-05:12 | -7.6 |
May | 0.230673E+10 | 29685.21 | 08-MAY-05:12 | -2.8 |
June | 0.221224E+09 | 29290.23 | 17-JUN-05:01 | 2.35 |
July | 38677180.40 | 1688.47 | 28-JUL-06:03 | 12.48 |
August | 0.100115E+09 | 24769.05 | 18-AUG-05:02 | 7.30 |
September | 0.725047E+09 | 29313.84 | 19-SEP-05:01 | 2.20 |
October | 0.194227E+10 | 29473.11 | 11-OCT-05:12 | -0.4 |
November | 0.489662E+10 | 31860.62 | 27-NOV-06:31 | -14.0 |
December | 0.876597E+10 | 31631.03 | 26-DEC-06:31 | -8.1 |
Annual Sum or Average | 0.490615E+11 | |||
Minimum of Months | 38677180.40 | 1688.47 | -27.1 | |
Maximum of Months | 0.119191E+11 | 32182.17 | 12.48 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773940E+11 | 100948.51 | 06-JAN-06:41 | -25.5 |
February | 0.473539E+11 | 99307.42 | 04-FEB-06:01 | -19.5 |
March | 0.373834E+11 | 99421.26 | 06-MAR-06:01 | -16.3 |
April | 0.155825E+11 | 95456.97 | 15-APR-05:42 | -0.6 |
May | 0.962290E+10 | 95519.22 | 07-MAY-09:12 | -1.1 |
June | 0.512263E+09 | 18462.11 | 17-JUN-03:55 | 2.20 |
July | 0.264045E+09 | 2972.21 | 08-JUL-06:40 | 10.93 |
August | 0.419074E+09 | 3017.84 | 14-AUG-06:50 | 12.62 |
September | 0.256142E+10 | 93180.75 | 19-SEP-05:01 | 2.20 |
October | 0.897654E+10 | 95197.66 | 10-OCT-04:52 | -6.1 |
November | 0.316593E+11 | 99225.64 | 27-NOV-06:01 | -14.5 |
December | 0.571915E+11 | 98889.29 | 28-DEC-06:01 | -22.8 |
Annual Sum or Average | 0.288921E+12 | |||
Minimum of Months | 0.264045E+09 | 2972.21 | -25.5 | |
Maximum of Months | 0.773940E+11 | 100948.51 | 12.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225283E+12 | 218961.33 | 05-JAN-16:05 | -19.5 |
February | 0.117580E+12 | 147561.75 | 03-FEB-19:00 | -16.7 |
March | 0.762640E+11 | 155088.90 | 06-MAR-03:51 | -18.3 |
April | 0.861254E+10 | 71981.26 | 29-APR-04:51 | -7.8 |
May | 0.713165E+10 | 60967.50 | 08-MAY-05:50 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.215052E+10 | 41478.35 | 10-OCT-06:00 | -6.1 |
November | 0.613966E+11 | 137092.11 | 27-NOV-05:00 | -15.6 |
December | 0.152596E+12 | 212291.73 | 31-DEC-02:55 | -24.4 |
Annual Sum or Average | 0.651015E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.225283E+12 | 218961.33 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449539E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321215E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297091E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377391.12 | 0.183271E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12802445.93 | 0.178256E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94092888.23 | 0.980973E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224564E+09 | 0.527518E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171906E+09 | 0.765052E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42068889.54 | 0.129887E+10 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2502094.73 | 0.173871E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258358E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350288E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.548314E+09 | 0.256913E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527518E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224564E+09 | 0.449539E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382449E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267540E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239149E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6210747.24 | 0.139175E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56290162.29 | 0.137059E+11 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250287E+09 | 0.880066E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802329E+09 | 0.649228E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727124E+09 | 0.743297E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337743E+09 | 0.105460E+11 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46392478.91 | 0.123388E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209459E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298486E+11 |
Annual Sum or Average | 0.136656E+12 | 0.222638E+10 | 0.212942E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649228E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802329E+09 | 0.382449E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100234E+12 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513795E+09 | 0.588419E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32838399.88 | 0.528030E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165534E+10 | 0.276167E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190317E+10 | 0.296498E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332781E+09 | 0.279537E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224167E+09 | 0.269662E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278706E+09 | 0.298737E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111622E+10 | 0.339083E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215204E+10 | 0.272850E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136970E+10 | 0.427821E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249580E+09 | 0.686686E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.982835E+10 | 0.526583E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269662E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215204E+10 | 0.100234E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 13195.08 | 06-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 10958.50 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10109.18 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 16-APR-14:00 | 5937.76 | 28-APR-16:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.63 | 19-MAY-16:10 | 7730.14 | 22-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.12 | 29-JUN-16:10 | 4372.21 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2852.20 | 17-JUL-16:10 | 3077.28 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2025.29 | 09-AUG-17:00 | 3976.32 | 17-AUG-16:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.69 | 01-SEP-16:10 | 5102.32 | 18-SEP-16:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.99 | 15-OCT-14:00 | 6798.18 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9047.41 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 11502.75 | 28-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3077.28 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2852.20 | 13195.08 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 70384.10 | 05-JAN-16:05 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37807.40 | 01-FEB-17:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 32889.45 | 30-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.60 | 07-APR-19:00 | 23846.50 | 28-APR-16:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3355.29 | 20-MAY-16:00 | 43872.73 | 22-MAY-06:10 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.94 | 29-JUN-15:10 | 18011.50 | 06-JUN-16:53 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.48 | 25-JUL-15:10 | 11601.09 | 08-JUL-07:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7596.82 | 09-AUG-17:00 | 22973.74 | 17-AUG-15:03 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8172.97 | 02-SEP-15:10 | 21991.54 | 18-SEP-16:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2839.72 | 15-OCT-14:00 | 19527.01 | 31-OCT-16:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32367.05 | 28-NOV-08:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 36966.08 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11601.09 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.48 | 70384.10 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 181660.10 | 05-JAN-15:55 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10870.85 | 27-FEB-14:00 | 97813.60 | 01-FEB-15:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3939.29 | 14-MAR-12:10 | 79120.80 | 03-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21314.33 | 07-APR-14:00 | 56265.00 | 27-APR-11:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23902.87 | 13-MAY-14:00 | 88694.45 | 22-MAY-08:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5926.44 | 29-JUN-12:25 | 53357.08 | 26-JUN-13:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5221.63 | 09-JUL-15:00 | 41600.86 | 08-JUL-10:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6636.18 | 25-AUG-16:00 | 81092.32 | 17-AUG-12:05 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13971.46 | 23-SEP-14:00 | 63932.97 | 12-SEP-11:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23851.86 | 12-OCT-12:10 | 39895.32 | 03-OCT-09:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14697.02 | 17-NOV-17:00 | 73054.26 | 27-NOV-11:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14692.86 | 10-DEC-01:55 | 127307.32 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39895.32 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23902.87 | 181660.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.13 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.62 |
March | 116.01 | 01-MAR-17:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.02 |
April | 600.25 | 25-APR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.57 |
May | 7461.22 | 19-MAY-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 252.61 | 0.00 |
June | 16890.94 | 26-JUN-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.88 |
July | 18328.68 | 17-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.44 |
August | 17309.99 | 07-AUG-00:01 | 0.00 | 4130.60 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.41 |
September | 17910.10 | 05-SEP-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 |
October | 2801.42 | 18-OCT-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 | 0.00 |
November | 229.69 | 10-NOV-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.11 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1258.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18328.68 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 252.61 | 1404.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 539.43 | 02-JAN-14:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4273.36 |
February | 3048.87 | 23-FEB-15:50 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469.23 |
March | 4204.38 | 25-MAR-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3049.91 | 29-APR-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.66 |
May | 7329.07 | 19-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2278.34 |
June | 41320.32 | 30-JUN-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1259.03 | 0.00 |
July | 47665.89 | 19-JUL-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3600.71 | 0.00 |
August | 47342.67 | 08-AUG-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.42 | 0.00 |
September | 46253.27 | 03-SEP-12:53 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5809.83 | 0.00 |
October | 4306.09 | 13-OCT-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3562.60 |
November | 3109.04 | 20-NOV-14:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.60 |
December | 1562.06 | 09-DEC-13:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 539.43 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47665.89 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5809.83 | 4273.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7272.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.34 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11640.24 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14933.18 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15453.50 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.47 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11161.88 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8225.60 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9784.48 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20057.49 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.27 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 19318.12 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43258.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.47 | |
Maximum of Months | 0.00 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.34 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.753275E+11 | 56310.13 | 19-JAN-08:09 | 0.415562E+12 | 420118.90 | 05-JAN-17:49 |
February | 0.670690E+11 | 53188.07 | 18-FEB-15:39 | 0.229834E+12 | 282882.20 | 04-FEB-06:10 |
March | 0.749234E+11 | 53177.37 | 03-MAR-15:39 | 0.160874E+12 | 289191.95 | 06-MAR-04:19 |
April | 0.676979E+11 | 52872.53 | 28-APR-14:09 | 0.379131E+11 | 167201.76 | 29-APR-05:10 |
May | 0.687614E+11 | 55302.52 | 20-MAY-14:50 | 0.250646E+11 | 149551.23 | 08-MAY-05:19 |
June | 0.690813E+11 | 64827.74 | 29-JUN-14:00 | 0.181415E+09 | 13509.96 | 17-JUN-03:00 |
July | 0.728773E+11 | 69917.61 | 17-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.757868E+11 | 68286.07 | 10-AUG-14:00 | 19071365.11 | 6449.18 | 18-AUG-05:10 |
September | 0.694885E+11 | 66524.22 | 02-SEP-14:00 | 0.343544E+10 | 44038.48 | 20-SEP-05:10 |
October | 0.703012E+11 | 55735.01 | 31-OCT-07:10 | 0.173740E+11 | 112476.11 | 10-OCT-05:00 |
November | 0.704211E+11 | 56262.07 | 30-NOV-16:49 | 0.129931E+12 | 268563.56 | 27-NOV-06:10 |
December | 0.751259E+11 | 56304.92 | 26-DEC-08:09 | 0.290459E+12 | 373300.47 | 31-DEC-02:00 |
Annual Sum or Average | 0.856861E+12 | 0.131065E+13 | ||||
Minimum of Months | 0.670690E+11 | 52872.53 | 0.00 | 0.00 | ||
Maximum of Months | 0.757868E+11 | 69917.61 | 0.415562E+12 | 420118.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.133699E+11 | 0.115358E+11 | 0.00 | 0.791058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240794E+10 | 0.00 |
February | 0.366966E+11 | 0.110457E+11 | 0.105871E+11 | 0.00 | 0.653484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220469E+10 | 0.00 |
March | 0.423649E+11 | 0.107864E+11 | 0.123357E+11 | 0.00 | 0.695128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248510E+10 | 0.00 |
April | 0.397216E+11 | 0.898083E+10 | 0.114862E+11 | 0.00 | 0.518088E+10 | 0.00 | 0.00 | 1623735.34 | 0.00 | 0.00 | 0.00 | 0.232675E+10 | 0.00 |
May | 0.412341E+11 | 0.798610E+10 | 0.119357E+11 | 0.00 | 0.505106E+10 | 0.00 | 0.00 | 0.203295E+09 | 0.00 | 0.00 | 0.00 | 0.235108E+10 | 0.00 |
June | 0.408524E+11 | 0.705266E+10 | 0.118862E+11 | 0.00 | 0.479776E+10 | 0.00 | 0.00 | 0.225701E+10 | 0.00 | 0.00 | 0.00 | 0.223540E+10 | 0.00 |
July | 0.401034E+11 | 0.759952E+10 | 0.115358E+11 | 0.00 | 0.555479E+10 | 0.00 | 0.00 | 0.587651E+10 | 0.00 | 0.00 | 0.00 | 0.220737E+10 | 0.00 |
August | 0.423649E+11 | 0.869796E+10 | 0.123357E+11 | 0.00 | 0.563670E+10 | 0.00 | 0.00 | 0.450394E+10 | 0.00 | 0.00 | 0.00 | 0.224768E+10 | 0.00 |
September | 0.397216E+11 | 0.980112E+10 | 0.114862E+11 | 0.00 | 0.473317E+10 | 0.00 | 0.00 | 0.158755E+10 | 0.00 | 0.00 | 0.00 | 0.215881E+10 | 0.00 |
October | 0.401034E+11 | 0.116256E+11 | 0.115358E+11 | 0.00 | 0.474509E+10 | 0.00 | 0.00 | 37763361.25 | 0.00 | 0.00 | 0.00 | 0.225361E+10 | 0.00 |
November | 0.385909E+11 | 0.125684E+11 | 0.110862E+11 | 0.00 | 0.594554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223000E+10 | 0.00 |
December | 0.401034E+11 | 0.137423E+11 | 0.115358E+11 | 0.00 | 0.737854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236589E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123257E+12 | 0.139282E+12 | 0.704202E+11 | 0.00 | 0.144677E+11 | 0.274743E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.705266E+10 | 0.105871E+11 | 0.00 | 0.473317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215881E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.137423E+11 | 0.123357E+11 | 0.00 | 0.791058E+10 | 0.00 | 0.00 | 0.587651E+10 | 0.00 | 0.00 | 0.00 | 0.248510E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.415562E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.229834E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160874E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.379131E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.250646E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.181415E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 19071365.11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.343544E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.173740E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129931E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.290459E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131065E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.415562E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5006.97 | 13-JAN-09:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5006.97 | 08-FEB-11:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5006.97 | 09-MAR-08:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5006.97 | 29-APR-07:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5006.97 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6758.15 | 23-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6758.15 | 17-JUL-16:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6758.15 | 04-AUG-12:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6758.15 | 02-SEP-12:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 5006.97 | 10-OCT-08:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5006.97 | 13-NOV-09:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5006.97 | 01-DEC-11:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5006.97 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6758.15 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2887.80 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2906.52 | 18-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2897.51 | 03-MAR-12:09 | 0.00 |
April | 370.00 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 2806.61 | 01-APR-11:39 | 0.00 |
May | 4166.52 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2622.91 | 01-MAY-11:50 | 0.00 |
June | 11782.07 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2347.40 | 02-JUN-11:30 | 0.00 |
July | 18338.46 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2057.69 | 07-JUL-11:00 | 0.00 |
August | 14761.91 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1921.68 | 01-AUG-11:00 | 0.00 |
September | 13567.41 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1993.48 | 20-SEP-11:30 | 0.00 |
October | 1137.24 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2288.82 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2529.85 | 27-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2750.82 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1921.68 | 0.00 | ||
Maximum of Months | 18338.46 | 0.00 | 0.00 | 0.00 | 2906.52 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56310.13 | 19-JAN-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53188.07 | 18-FEB-15:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53177.37 | 03-MAR-15:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52872.53 | 28-APR-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55302.52 | 20-MAY-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4452.85 | 0.00 | 0.00 | 3170.71 | 0.00 |
June | 64827.74 | 29-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6758.15 | 0.00 | 0.00 | 10547.21 | 0.00 |
July | 69917.61 | 17-JUL-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6758.15 | 0.00 | 0.00 | 15646.79 | 0.00 |
August | 68286.07 | 10-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6758.15 | 0.00 | 0.00 | 14020.78 | 0.00 |
September | 66524.22 | 02-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6758.15 | 0.00 | 0.00 | 12258.55 | 0.00 |
October | 55735.01 | 31-OCT-07:10 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4452.85 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56262.07 | 30-NOV-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56304.92 | 26-DEC-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5006.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52872.53 | 31660.41 | 10112.62 | 0.00 | 0.00 | 4452.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69917.61 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6758.15 | 0.00 | 0.00 | 15646.79 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 420118.90 | 05-JAN-17:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 282882.20 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 289191.95 | 06-MAR-04:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 167201.76 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 149551.23 | 08-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 13509.96 | 17-JUN-03:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 6449.18 | 18-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 44038.48 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 112476.11 | 10-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 268563.56 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 373300.47 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 420118.90 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.00 | 15.45 | 10.50 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34.33 | 15.94 | 9.00 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23.83 | 16.73 | 10.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.83 | 19.30 | 8.00 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.17 | 19.64 | 6.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.33 | 20.40 | 0.33 | 20.40 | 8.17 | 24.65 | 0.17 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 24.70 | 0.67 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 24.67 | 0.17 | 24.48 |
September | 2.00 | 20.19 | 2.00 | 20.19 | 6.83 | 24.73 | 0.50 | 24.47 |
October | 5.33 | 20.08 | 5.33 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16.83 | 17.19 | 8.33 | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33.67 | 16.18 | 10.00 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.33 | 16.50 | 70.33 | 19.39 | 54.50 | 24.69 | 1.50 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.00 | 20.40 | 10.83 | 20.40 | 22.00 | 24.73 | 0.67 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 132.67 | 13.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98.33 | 13.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106.33 | 14.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66.00 | 14.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32.67 | 14.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.57 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.62 | 0.00 | 0.00 |
September | 7.67 | 14.69 | 0.00 | 0.00 | 3.83 | 27.65 | 0.00 | 0.00 |
October | 35.83 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 92.17 | 14.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115.67 | 13.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 687.33 | 13.87 | 0.00 | 18.83 | 27.59 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.67 | 14.69 | 0.00 | 0.00 | 8.33 | 27.65 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 8.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 8.89 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 8.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.05 | 275.17 | 21.05 | 275.17 | 21.05 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.37 | 266.17 | 21.15 | 266.17 | 21.15 |
May | 309.50 | 21.99 | 192.83 | 21.15 | 192.83 | 21.15 |
June | 219.67 | 23.26 | 52.33 | 22.79 | 21.00 | 21.14 |
July | 79.00 | 23.72 | 113.33 | 23.90 | 0.00 | 0.00 |
August | 147.83 | 23.54 | 69.00 | 23.81 | 2.33 | 21.19 |
September | 229.67 | 22.67 | 108.50 | 22.12 | 72.50 | 21.24 |
October | 300.00 | 21.87 | 195.83 | 21.18 | 195.83 | 21.18 |
November | 288.00 | 21.14 | 279.50 | 21.10 | 279.50 | 21.10 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3073.67 | 21.73 | 2476.67 | 21.37 | 2229.33 | 21.09 |
Minimum of Months | 79.00 | 21.02 | 52.33 | 21.02 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.72 | 324.00 | 23.90 | 324.00 | 21.24 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 5887339.52 | 1623735.34 | 1.67 | 5887339.52 | 0.00 | 0.00 | 0.09 | 06-APR-16:00 | 0.00 | 01-APR-00:05 | 1345.52 | 06-APR-16:00 | 1345.52 | 06-APR-16:00 | 0.00 | 01-APR-00:05 | 370.00 | 06-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.622560E+09 | 0.172173E+09 | 56.83 | 0.621437E+09 | 1123401.69 | 0.00 | 0.56 | 31-MAY-17:15 | 0.00 | 01-MAY-00:10 | 8479.17 | 19-MAY-17:15 | 8479.17 | 19-MAY-17:15 | 73.20 | 20-MAY-11:00 | 2424.62 | 19-MAY-17:15 | 0.00 | 01-MAY-00:10 |
June | 0.374246E+10 | 0.104176E+10 | 234.83 | 0.364186E+10 | 0.100595E+09 | 0.00 | 1.00 | 22-JUN-17:43 | 0.00 | 01-JUN-00:10 | 19313.19 | 26-JUN-00:02 | 19313.19 | 26-JUN-00:02 | 1535.43 | 20-JUN-17:10 | 4752.40 | 30-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.730532E+10 | 0.206820E+10 | 365.52 | 0.717278E+10 | 0.132538E+09 | 0.00 | 1.00 | 03-JUL-00:01 | 0.00 | 01-JUL-00:15 | 20387.63 | 17-JUL-00:01 | 20387.63 | 17-JUL-00:01 | 1640.81 | 19-JUL-07:10 | 5197.92 | 17-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.620515E+10 | 0.175286E+10 | 335.44 | 0.618107E+10 | 24080735.41 | 0.00 | 1.00 | 03-AUG-19:03 | 0.00 | 01-AUG-00:15 | 19397.46 | 07-AUG-00:01 | 19397.46 | 07-AUG-00:01 | 433.75 | 22-AUG-14:20 | 5028.49 | 05-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.254510E+10 | 0.703246E+09 | 162.62 | 0.243796E+10 | 0.107145E+09 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:10 | 20111.50 | 06-SEP-18:23 | 19955.98 | 05-SEP-00:01 | 3419.96 | 07-SEP-17:10 | 5027.78 | 02-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 0.138020E+09 | 37763361.25 | 19.67 | 0.138020E+09 | 0.00 | 0.00 | 0.26 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 4206.33 | 18-OCT-16:00 | 4206.33 | 18-OCT-16:00 | 0.00 | 19-OCT-14:50 | 1137.24 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.205645E+11 | 0.577764E+10 | 1176.58 | 0.201990E+11 | 0.365483E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.730532E+10 | 0.206820E+10 | 365.52 | 0.717278E+10 | 0.132538E+09 | 0.00 | 1.00 | 0.00 | 20387.63 | 20387.63 | 3419.96 | 5197.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 98335850.04 | 31121568.37 | 7.00 | 98335850.04 | 0.00 | 0.00 | 0.16 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 7167.17 | 20-MAY-16:00 | 7167.17 | 20-MAY-16:00 | 0.00 | 20-MAY-16:00 | 2336.92 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.396129E+10 | 0.121524E+10 | 84.25 | 0.384294E+10 | 0.118351E+09 | 0.00 | 0.93 | 30-JUN-17:08 | 0.00 | 01-JUN-00:10 | 45927.10 | 30-JUN-17:08 | 45927.10 | 30-JUN-17:08 | 2221.41 | 20-JUN-16:00 | 13370.30 | 30-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.122358E+11 | 0.380830E+10 | 220.28 | 0.120335E+11 | 0.202282E+09 | 0.00 | 1.00 | 14-JUL-17:06 | 0.00 | 01-JUL-00:10 | 56249.22 | 16-JUL-11:53 | 52092.83 | 16-JUL-19:13 | 6518.46 | 16-JUL-11:53 | 15747.95 | 17-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.875991E+10 | 0.275108E+10 | 162.49 | 0.874058E+10 | 19322986.53 | 0.00 | 1.00 | 05-AUG-17:08 | 0.00 | 01-AUG-00:10 | 51869.83 | 08-AUG-17:06 | 51869.83 | 08-AUG-17:06 | 1045.73 | 01-AUG-14:30 | 15508.41 | 06-AUG-15:53 | 0.00 | 01-AUG-00:10 |
September | 0.283569E+10 | 0.884307E+09 | 56.90 | 0.268876E+10 | 0.146932E+09 | 0.00 | 1.00 | 02-SEP-17:08 | 0.00 | 01-SEP-00:10 | 51180.80 | 04-SEP-13:33 | 51180.80 | 04-SEP-13:33 | 7137.21 | 07-SEP-15:00 | 15248.83 | 03-SEP-13:32 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.278910E+11 | 0.869006E+10 | 530.92 | 0.274041E+11 | 0.486887E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122358E+11 | 0.380830E+10 | 220.28 | 0.120335E+11 | 0.202282E+09 | 0.00 | 1.00 | 0.00 | 56249.22 | 52092.83 | 7137.21 | 15747.95 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.32 | 274.47 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.56 | 189.19 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 88.01 | 149.55 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.40 | 97.55 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.54 | 79.67 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 245.53 | 62.30 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 273.37 | 56.58 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 222.88 | 61.06 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 164.41 | 80.16 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.62 | 106.38 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.86 | 153.14 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.88 | 226.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 134.55 | 127.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.88 | 56.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 273.37 | 274.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.32 | 274.47 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.56 | 189.19 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 88.01 | 149.55 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.40 | 97.55 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.54 | 79.67 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 245.53 | 62.30 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 273.37 | 56.58 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 222.88 | 61.06 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 164.41 | 80.16 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.62 | 106.38 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.86 | 153.14 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.88 | 226.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 134.55 | 127.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.88 | 56.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 273.37 | 274.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.83 | 0.00 | 16.83 | 0.21 | 167.62 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.93 | 118.78 | 0.00 | 0.00 | 672.00 |
March | 38.60 | 0.00 | 38.59 | 9.11 | 90.25 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.08 | 57.99 | 0.00 | 0.00 | 720.00 |
May | 57.74 | 3.37 | 54.36 | 34.45 | 45.68 | 0.00 | 0.00 | 744.00 |
June | 67.20 | 7.67 | 59.53 | 50.70 | 32.64 | 0.00 | 0.00 | 720.00 |
July | 61.38 | 5.66 | 55.71 | 55.73 | 29.96 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 43.20 | 34.64 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.48 | 47.17 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.68 | 64.07 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.48 | 95.43 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.12 | 139.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.47 | 21.29 | 76.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.12 | 29.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.20 | 7.67 | 59.53 | 55.73 | 167.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.82 | 0.00 | 16.82 | 0.21 | 167.62 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.93 | 118.78 | 0.00 | 0.00 | 672.00 |
March | 38.59 | 0.00 | 38.59 | 9.11 | 90.26 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.07 | 57.99 | 0.00 | 0.00 | 720.00 |
May | 57.73 | 3.37 | 54.36 | 34.45 | 45.68 | 0.00 | 0.00 | 744.00 |
June | 67.19 | 7.67 | 59.53 | 50.70 | 32.64 | 0.00 | 0.00 | 720.00 |
July | 61.37 | 5.66 | 55.71 | 55.73 | 29.96 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 43.20 | 34.64 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.47 | 47.17 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.68 | 64.07 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.48 | 95.43 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.12 | 139.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.46 | 21.29 | 76.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.12 | 29.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.19 | 7.67 | 59.53 | 55.73 | 167.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.62 | 182.69 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 42.96 | 120.30 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.42 | 91.02 | 1.50 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 118.50 | 57.27 | 2.67 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 159.79 | 48.25 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 191.40 | 52.46 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 197.22 | 61.58 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 161.67 | 62.81 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 110.80 | 62.05 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.00 | 68.04 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.46 | 91.72 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.11 | 144.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 99.22 | 86.86 | 9.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.11 | 48.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 197.22 | 182.69 | 5.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 57105962.36 | 0.735151E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.156190E+09 | 0.457693E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.235730E+09 | 0.400567E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397615E+09 | 0.252844E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.555869E+09 | 0.213395E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.636407E+09 | 0.161480E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.732190E+09 | 0.151554E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.596952E+09 | 0.163536E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.426141E+09 | 0.207772E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.261472E+09 | 0.284918E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.134411E+09 | 0.396932E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 53239100.34 | 0.605989E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.424332E+10 | 0.403183E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 53239100.34 | 0.151554E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.732190E+09 | 0.735151E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 57105962.36 | 0.735151E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.156190E+09 | 0.457693E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.235730E+09 | 0.400567E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397615E+09 | 0.252844E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.555869E+09 | 0.213395E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.636407E+09 | 0.161480E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.732190E+09 | 0.151554E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.596952E+09 | 0.163536E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.426141E+09 | 0.207772E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.261472E+09 | 0.284918E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.134411E+09 | 0.396932E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 53239100.34 | 0.605989E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.424332E+10 | 0.403183E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 53239100.34 | 0.151554E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.732190E+09 | 0.735151E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45064288.41 | 0.00 | 45064288.41 | 558043.83 | 0.448960E+09 |
February | 57470429.67 | 0.00 | 57470429.67 | 7093135.92 | 0.287364E+09 |
March | 0.103373E+09 | 5154.92 | 0.103368E+09 | 24408956.50 | 0.241739E+09 |
April | 0.114392E+09 | 857486.23 | 0.113534E+09 | 52035632.07 | 0.150307E+09 |
May | 0.154641E+09 | 9033514.49 | 0.145607E+09 | 92278758.24 | 0.122362E+09 |
June | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.131426E+09 | 84598176.26 |
July | 0.164389E+09 | 15169360.03 | 0.149219E+09 | 0.149268E+09 | 80257475.08 |
August | 0.133290E+09 | 4794192.82 | 0.128496E+09 | 0.115699E+09 | 92789356.72 |
September | 95713512.75 | 81737.00 | 95631775.75 | 66032963.33 | 0.122257E+09 |
October | 72072435.85 | 0.00 | 72072435.85 | 25917329.86 | 0.171605E+09 |
November | 47415011.88 | 0.00 | 47415011.88 | 6418070.23 | 0.247360E+09 |
December | 37788945.48 | 0.00 | 37788945.48 | 316325.53 | 0.374254E+09 |
Annual Sum or Average | 0.119978E+10 | 49813360.58 | 0.114997E+10 | 0.671452E+09 | 0.242385E+10 |
Minimum of Months | 37788945.48 | 0.00 | 37788945.48 | 316325.53 | 80257475.08 |
Maximum of Months | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.149268E+09 | 0.448960E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45062835.23 | 0.00 | 45062835.23 | 557944.68 | 0.448960E+09 |
February | 57468698.97 | 0.00 | 57468698.97 | 7092729.65 | 0.287364E+09 |
March | 0.103370E+09 | 5154.68 | 0.103365E+09 | 24407075.75 | 0.241739E+09 |
April | 0.114389E+09 | 857446.04 | 0.113531E+09 | 52033177.88 | 0.150307E+09 |
May | 0.154636E+09 | 9033091.07 | 0.145603E+09 | 92274947.23 | 0.122362E+09 |
June | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.131421E+09 | 84597968.38 |
July | 0.164384E+09 | 15168649.02 | 0.149215E+09 | 0.149264E+09 | 80256854.53 |
August | 0.133286E+09 | 4793968.11 | 0.128492E+09 | 0.115696E+09 | 92788898.32 |
September | 95710774.52 | 81733.17 | 95629041.36 | 66030866.77 | 0.122257E+09 |
October | 72070253.22 | 0.00 | 72070253.22 | 25915983.23 | 0.171604E+09 |
November | 47413524.99 | 0.00 | 47413524.99 | 6417587.55 | 0.247359E+09 |
December | 37787710.35 | 0.00 | 37787710.35 | 316280.40 | 0.374253E+09 |
Annual Sum or Average | 0.119975E+10 | 49811025.76 | 0.114993E+10 | 0.671428E+09 | 0.242385E+10 |
Minimum of Months | 37787710.35 | 0.00 | 37787710.35 | 316280.40 | 80256854.53 |
Maximum of Months | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.149264E+09 | 0.448960E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33794309.86 | 0.489309E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.103935E+09 | 0.291030E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.228792E+09 | 0.243790E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.307164E+09 | 0.148456E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.427976E+09 | 0.129245E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.496097E+09 | 0.135968E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.528247E+09 | 0.164946E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.433019E+09 | 0.168235E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.287199E+09 | 0.160833E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174103E+09 | 0.182246E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 78961041.85 | 0.237747E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.387545E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.312904E+10 | 0.273935E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29750921.55 | 0.129245E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.528247E+09 | 0.489309E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 32.19 | 873.32 | 154.38 | 49.05 | 105.34 | 0.00 | 0.00 |
February | 124.64 | 605.61 | 252.05 | 100.66 | 151.39 | 0.00 | 0.00 |
March | 189.39 | 474.76 | 339.77 | 96.45 | 243.32 | 0.00 | 0.00 |
April | 344.26 | 308.38 | 430.45 | 151.83 | 278.63 | 0.00 | 0.00 |
May | 482.57 | 249.31 | 538.72 | 199.79 | 338.93 | 0.00 | 0.00 |
June | 589.90 | 187.31 | 594.52 | 226.57 | 367.95 | 0.00 | 0.00 |
July | 655.66 | 170.56 | 594.60 | 249.82 | 344.77 | 0.00 | 0.00 |
August | 531.38 | 190.63 | 499.38 | 199.28 | 300.10 | 0.00 | 0.00 |
September | 378.09 | 252.98 | 395.84 | 162.77 | 233.07 | 0.00 | 0.00 |
October | 210.08 | 336.38 | 284.38 | 114.61 | 169.77 | 0.00 | 0.00 |
November | 98.28 | 486.75 | 199.52 | 80.85 | 118.68 | 0.00 | 0.00 |
December | 30.38 | 722.36 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Annual Sum or Average | 306.54 | 404.26 | 368.98 | 139.96 | 229.02 | 0.00 | 0.00 |
Minimum of Months | 30.38 | 170.56 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Maximum of Months | 655.66 | 873.32 | 594.60 | 249.82 | 367.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.17 | 1826.87 | 283.29 | 117.94 | 165.35 | 0.00 | 0.00 |
February | 429.62 | 1203.00 | 467.44 | 257.22 | 210.23 | 0.00 | 0.00 |
March | 854.21 | 910.21 | 764.72 | 364.47 | 400.25 | 0.00 | 0.00 |
April | 1185.04 | 572.75 | 948.14 | 530.20 | 417.94 | 0.00 | 0.00 |
May | 1597.88 | 482.54 | 1216.64 | 693.94 | 522.70 | 0.00 | 0.00 |
June | 1913.95 | 524.57 | 1464.89 | 940.27 | 524.62 | 0.00 | 0.00 |
July | 1972.25 | 615.84 | 1516.66 | 1061.13 | 455.52 | 0.00 | 0.00 |
August | 1616.70 | 628.12 | 1263.13 | 861.18 | 401.95 | 0.00 | 0.00 |
September | 1108.02 | 620.50 | 877.08 | 556.25 | 320.83 | 0.00 | 0.00 |
October | 650.02 | 680.43 | 546.34 | 303.89 | 242.45 | 0.00 | 0.00 |
November | 304.63 | 917.23 | 330.79 | 162.84 | 167.95 | 0.00 | 0.00 |
December | 111.08 | 1446.93 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Annual Sum or Average | 992.21 | 868.64 | 827.17 | 496.08 | 331.09 | 0.00 | 0.00 |
Minimum of Months | 111.08 | 482.54 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Maximum of Months | 1972.25 | 1826.87 | 1516.66 | 1061.13 | 524.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 86210013.37 | 0.233910E+10 | 0.413500E+09 | 0.131364E+09 | 0.282136E+09 | 0.00 | 0.00 |
February | 0.301541E+09 | 0.146509E+10 | 0.609760E+09 | 0.243524E+09 | 0.366237E+09 | 0.00 | 0.00 |
March | 0.507266E+09 | 0.127160E+10 | 0.910051E+09 | 0.258341E+09 | 0.651710E+09 | 0.00 | 0.00 |
April | 0.892309E+09 | 0.799314E+09 | 0.111574E+10 | 0.393537E+09 | 0.722201E+09 | 0.00 | 0.00 |
May | 0.129252E+10 | 0.667742E+09 | 0.144291E+10 | 0.535123E+09 | 0.907791E+09 | 0.00 | 0.00 |
June | 0.152901E+10 | 0.485510E+09 | 0.154099E+10 | 0.587270E+09 | 0.953721E+09 | 0.00 | 0.00 |
July | 0.175612E+10 | 0.456834E+09 | 0.159257E+10 | 0.669131E+09 | 0.923443E+09 | 0.00 | 0.00 |
August | 0.142324E+10 | 0.510595E+09 | 0.133754E+10 | 0.533738E+09 | 0.803798E+09 | 0.00 | 0.00 |
September | 0.979999E+09 | 0.655711E+09 | 0.102602E+10 | 0.421900E+09 | 0.604117E+09 | 0.00 | 0.00 |
October | 0.562686E+09 | 0.900953E+09 | 0.761684E+09 | 0.306962E+09 | 0.454722E+09 | 0.00 | 0.00 |
November | 0.254732E+09 | 0.126166E+10 | 0.517165E+09 | 0.209556E+09 | 0.307609E+09 | 0.00 | 0.00 |
December | 81382232.68 | 0.193476E+10 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966703E+10 | 0.127489E+11 | 0.116363E+11 | 0.441382E+10 | 0.722246E+10 | 0.00 | 0.00 |
Minimum of Months | 81382232.68 | 0.456834E+09 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175612E+10 | 0.233910E+10 | 0.159257E+10 | 0.669131E+09 | 0.953721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337943E+09 | 0.489308E+10 | 0.758763E+09 | 0.315896E+09 | 0.442867E+09 | 0.00 | 0.00 |
February | 0.103935E+10 | 0.291030E+10 | 0.113083E+10 | 0.622256E+09 | 0.508579E+09 | 0.00 | 0.00 |
March | 0.228791E+10 | 0.243790E+10 | 0.204823E+10 | 0.976190E+09 | 0.107204E+10 | 0.00 | 0.00 |
April | 0.307164E+10 | 0.148456E+10 | 0.245757E+10 | 0.137428E+10 | 0.108329E+10 | 0.00 | 0.00 |
May | 0.427976E+10 | 0.129244E+10 | 0.325866E+10 | 0.185865E+10 | 0.140001E+10 | 0.00 | 0.00 |
June | 0.496096E+10 | 0.135968E+10 | 0.379700E+10 | 0.243718E+10 | 0.135982E+10 | 0.00 | 0.00 |
July | 0.528247E+10 | 0.164946E+10 | 0.406221E+10 | 0.284214E+10 | 0.122008E+10 | 0.00 | 0.00 |
August | 0.433018E+10 | 0.168235E+10 | 0.338316E+10 | 0.230658E+10 | 0.107658E+10 | 0.00 | 0.00 |
September | 0.287198E+10 | 0.160832E+10 | 0.227340E+10 | 0.144180E+10 | 0.831592E+09 | 0.00 | 0.00 |
October | 0.174102E+10 | 0.182245E+10 | 0.146332E+10 | 0.813939E+09 | 0.649377E+09 | 0.00 | 0.00 |
November | 0.789610E+09 | 0.237747E+10 | 0.857411E+09 | 0.422081E+09 | 0.435329E+09 | 0.00 | 0.00 |
December | 0.297508E+09 | 0.387545E+10 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.312903E+11 | 0.273935E+11 | 0.260856E+11 | 0.156442E+11 | 0.104414E+11 | 0.00 | 0.00 |
Minimum of Months | 0.297508E+09 | 0.129244E+10 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528247E+10 | 0.489308E+10 | 0.406221E+10 | 0.284214E+10 | 0.140001E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.111457E+10 | -957252131.1 | 0.00 | 0.00 | 744.00 | 0.00 | -157321776.2 | 59.00 | 0.00 | 0.00 |
February | 0.103629E+10 | -894730314.2 | 0.00 | 0.00 | 672.00 | 0.00 | -141555321.5 | 58.99 | 0.00 | 0.00 |
March | 0.119098E+10 | -.103499E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155988535.0 | 59.00 | 0.00 | 0.00 |
April | 0.107467E+10 | -926351773.4 | 0.00 | 0.00 | 720.00 | 0.00 | -148313683.9 | 58.99 | 0.00 | 0.00 |
May | 0.105741E+10 | -910531313.3 | 0.00 | 0.00 | 744.00 | 0.00 | -146874390.7 | 58.99 | 0.00 | 0.00 |
June | 0.983567E+09 | -851145288.8 | 0.00 | 0.00 | 720.00 | 0.00 | -132421540.5 | 58.99 | 0.00 | 0.00 |
July | 0.913482E+09 | -780887947.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132593811.4 | 58.99 | 0.00 | 0.00 |
August | 0.953623E+09 | -819645368.8 | 0.00 | 0.00 | 744.00 | 0.00 | -133977566.3 | 59.00 | 0.00 | 0.00 |
September | 0.907250E+09 | -772429832.8 | 0.00 | 0.00 | 720.00 | 0.00 | -134820374.6 | 58.99 | 0.00 | 0.00 |
October | 0.959913E+09 | -810592334.2 | 0.00 | 0.00 | 744.00 | 0.00 | -149320687.1 | 58.99 | 0.00 | 0.00 |
November | 0.977911E+09 | -827631423.1 | 0.00 | 0.00 | 720.00 | 0.00 | -150279556.7 | 58.99 | 0.00 | 0.00 |
December | 0.107165E+10 | -914641645.2 | 0.00 | 0.00 | 744.00 | 0.00 | -157010996.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.122413E+11 | -.105008E+11 | 8760.00 | -.174048E+10 | 58.99 | |||||
Minimum of Months | 0.907250E+09 | -.103499E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157321776.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.119098E+10 | -772429832.8 | 0.00 | 0.00 | 744.00 | 0.00 | -132421540.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132092E+11 | 29022.58 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841337E+10 | 29022.58 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723482E+10 | 29022.58 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337023E+10 | 29022.58 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214320E+10 | 29022.58 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102788E+09 | 29022.58 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12913471.93 | 25099.30 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564793E+09 | 29022.58 | 12-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174521E+10 | 29022.58 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.503698E+10 | 29022.58 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.958882E+10 | 29022.58 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514224E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132092E+11 | 29022.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823340E+11 | 92725.69 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.496872E+11 | 92725.69 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385814E+11 | 92725.69 | 01-MAR-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153238E+11 | 92725.69 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.900709E+10 | 92725.69 | 01-MAY-01:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18851463.07 | 17960.14 | 17-JUN-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175743E+10 | 92725.69 | 19-SEP-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.824495E+10 | 92725.69 | 08-OCT-01:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319868E+11 | 92725.69 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601898E+11 | 92725.69 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297131E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.823340E+11 | 92725.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223846E+12 | 216706.76 | 05-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116467E+12 | 147007.67 | 03-FEB-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752233E+11 | 154535.10 | 06-MAR-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834397E+10 | 71427.73 | 29-APR-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.697459E+10 | 60413.39 | 08-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209544E+10 | 40924.23 | 10-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606479E+11 | 136538.04 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151269E+12 | 211737.64 | 31-DEC-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644868E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.223846E+12 | 216706.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5887339.52 | 5887339.52 | 1345.52 | 06-APR-16:00 | 1345.52 | 0.00 |
May | 0.00 | 0.00 | 0.622560E+09 | 0.621437E+09 | 8479.17 | 19-MAY-17:15 | 8479.17 | 0.00 |
June | 0.00 | 0.00 | 0.374246E+10 | 0.364186E+10 | 19313.19 | 26-JUN-00:02 | 19313.19 | 0.00 |
July | 0.00 | 0.00 | 0.730532E+10 | 0.717278E+10 | 20387.63 | 17-JUL-00:01 | 20387.63 | 0.00 |
August | 0.00 | 0.00 | 0.620515E+10 | 0.618107E+10 | 19397.46 | 07-AUG-00:01 | 19397.46 | 0.00 |
September | 0.00 | 0.00 | 0.254510E+10 | 0.243796E+10 | 20111.50 | 06-SEP-18:23 | 17488.92 | 0.00 |
October | 0.00 | 0.00 | 0.138020E+09 | 0.138020E+09 | 4206.33 | 18-OCT-16:00 | 4206.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.205645E+11 | 0.201990E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.730532E+10 | 0.717278E+10 | 20387.63 | 20387.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 98335850.04 | 98335850.04 | 7167.17 | 20-MAY-16:00 | 7167.17 | 0.00 |
June | 0.00 | 0.00 | 0.396129E+10 | 0.384294E+10 | 45927.10 | 30-JUN-17:08 | 45927.10 | 0.00 |
July | 0.00 | 0.00 | 0.122358E+11 | 0.120335E+11 | 56249.22 | 16-JUL-11:53 | 49730.76 | 0.00 |
August | 0.00 | 0.00 | 0.875991E+10 | 0.874058E+10 | 51869.83 | 08-AUG-17:06 | 51869.83 | 0.00 |
September | 0.00 | 0.00 | 0.283569E+10 | 0.268876E+10 | 51180.80 | 04-SEP-13:33 | 51180.80 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.278910E+11 | 0.274041E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122358E+11 | 0.120335E+11 | 56249.22 | 51869.83 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143726E+10 | 0.08 | 554.11 | 01-JAN-00:03 | 0.09 |
February | 0.110992E+10 | 0.07 | 554.11 | 01-FEB-00:01 | 0.09 |
March | 0.103785E+10 | 0.06 | 554.11 | 01-MAR-00:10 | 0.09 |
April | 0.266579E+09 | 0.02 | 554.11 | 01-APR-00:05 | 0.09 |
May | 0.156526E+09 | 0.01 | 554.11 | 01-MAY-00:10 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 54957003.82 | 0.00 | 554.11 | 09-OCT-22:30 | 0.09 |
November | 0.746364E+09 | 0.05 | 554.11 | 02-NOV-04:05 | 0.09 |
December | 0.132454E+10 | 0.08 | 554.11 | 01-DEC-00:01 | 0.09 |
Annual Sum or Average | 0.613399E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143726E+10 | 0.08 | 554.11 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155419E+10 | 0.82 | 1350.59 | 02-JAN-09:20 | 1.07 |
February | 0.135705E+10 | 0.72 | 1350.59 | 01-FEB-07:20 | 1.07 |
March | 0.154485E+10 | 0.65 | 1350.59 | 01-MAR-08:50 | 1.07 |
April | 0.137986E+10 | 0.48 | 1350.59 | 01-APR-06:40 | 1.07 |
May | 0.142696E+10 | 0.47 | 1350.59 | 01-MAY-09:10 | 1.07 |
June | 0.144264E+10 | 0.50 | 1350.59 | 01-JUN-08:15 | 1.06 |
July | 0.148351E+10 | 0.60 | 1350.59 | 01-JUL-08:15 | 1.06 |
August | 0.155728E+10 | 0.59 | 1350.59 | 01-AUG-10:16 | 1.06 |
September | 0.138904E+10 | 0.49 | 1350.59 | 01-SEP-07:40 | 1.06 |
October | 0.136194E+10 | 0.43 | 1350.59 | 02-OCT-07:10 | 1.07 |
November | 0.135660E+10 | 0.55 | 1350.59 | 01-NOV-07:10 | 1.07 |
December | 0.148979E+10 | 0.75 | 1350.59 | 01-DEC-07:50 | 1.07 |
Annual Sum or Average | 0.173437E+11 | 0.59 | |||
Minimum of Months | 0.135660E+10 | 0.43 | 1350.59 | 1.06 | |
Maximum of Months | 0.155728E+10 | 0.82 | 1350.59 | 1.07 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.491913E+10 | 0.91 | 3102.26 | 02-JAN-08:70 | 1.03 |
February | 0.406787E+10 | 0.90 | 3102.26 | 03-FEB-07:10 | 1.03 |
March | 0.436858E+10 | 0.90 | 3102.26 | 07-MAR-16:00 | 1.03 |
April | 0.353444E+10 | 0.74 | 3102.26 | 26-APR-07:10 | 1.03 |
May | 0.346758E+10 | 0.57 | 3102.26 | 01-MAY-07:40 | 1.03 |
June | 0.321633E+10 | 0.42 | 3102.26 | 20-JUN-16:30 | 1.01 |
July | 0.321046E+10 | 0.45 | 3102.26 | 01-JUL-12:20 | 1.02 |
August | 0.340212E+10 | 0.45 | 3102.26 | 05-AUG-11:30 | 1.02 |
September | 0.318036E+10 | 0.47 | 3102.26 | 01-SEP-12:30 | 1.02 |
October | 0.332819E+10 | 0.60 | 3102.26 | 04-OCT-11:10 | 1.03 |
November | 0.384258E+10 | 0.85 | 3102.26 | 13-NOV-09:50 | 1.03 |
December | 0.456422E+10 | 0.92 | 3102.26 | 01-DEC-11:30 | 1.03 |
Annual Sum or Average | 0.451019E+11 | 0.68 | |||
Minimum of Months | 0.318036E+10 | 0.42 | 3102.26 | 1.01 | |
Maximum of Months | 0.491913E+10 | 0.92 | 3102.26 | 1.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.98 | 0.01 |
February | 2.42 | 0.00 |
March | 2.56 | 0.00 |
April | 1.01 | 0.06 |
May | 0.53 | 0.34 |
June | 0.31 | 0.84 |
July | 0.56 | 0.94 |
August | 0.22 | 1.73 |
September | 0.31 | 0.74 |
October | 0.65 | 0.27 |
November | 2.08 | 0.02 |
December | 2.36 | 0.00 |
Annual Sum or Average | 14.98 | 0.13 |
Minimum of Months | 0.22 | 0.00 |
Maximum of Months | 2.56 | 1.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.10 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.26 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.53 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.26 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.22 | 0.00 |
July | 1.54 | 0.00 |
August | 0.68 | 0.00 |
September | 0.22 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.54 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155419E+10 | 0.188395E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135705E+10 | 0.121606E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154485E+10 | 0.105538E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138148E+10 | 0.494623E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159913E+10 | 0.314165E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.248441E+10 | 0.152516E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.355171E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331014E+10 | 19071365.11 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209229E+10 | 0.832065E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.139971E+10 | 0.256944E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135660E+10 | 0.735502E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148979E+10 | 0.138948E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231213E+11 | 0.744647E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.355171E+10 | 0.188395E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.491913E+10 | 0.114267E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.406787E+10 | 0.707117E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.436858E+10 | 0.554011E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.353444E+10 | 0.224382E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.349870E+10 | 0.131222E+11 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.443158E+10 | 28898887.26 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.701876E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.615321E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.406467E+10 | 0.260337E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.332819E+10 | 0.121605E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.384258E+10 | 0.460490E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.456422E+10 | 0.856883E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.537919E+11 | 0.422470E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.332819E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.701876E+10 | 0.114267E+12 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155419E+10 | 0.00 | 0.132092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135705E+10 | 0.00 | 0.841337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154485E+10 | 0.00 | 0.723482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137986E+10 | 5887339.52 | 0.337023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142696E+10 | 0.622560E+09 | 0.214320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144264E+10 | 0.374246E+10 | 0.102788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148351E+10 | 0.730532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155728E+10 | 0.620515E+10 | 12913471.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138904E+10 | 0.254510E+10 | 0.564793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136194E+10 | 0.138020E+09 | 0.174521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135660E+10 | 0.00 | 0.503698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148979E+10 | 0.00 | 0.958882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173437E+11 | 0.205645E+11 | 0.514224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155728E+10 | 0.730532E+10 | 0.132092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.491913E+10 | 0.00 | 0.823340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406787E+10 | 0.00 | 0.496872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436858E+10 | 0.00 | 0.385814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353444E+10 | 0.00 | 0.153238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346758E+10 | 98335850.04 | 0.900709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321633E+10 | 0.396129E+10 | 18851463.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321046E+10 | 0.122358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340212E+10 | 0.875991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318036E+10 | 0.283569E+10 | 0.175743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.332819E+10 | 0.00 | 0.824495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384258E+10 | 0.00 | 0.319868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456422E+10 | 0.00 | 0.601898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451019E+11 | 0.278910E+11 | 0.297131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.491913E+10 | 0.122358E+11 | 0.823340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.155419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137986E+10 | 0.00 | 0.00 | 0.00 | 1623735.34 | 0.00 | 0.494623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142696E+10 | 0.00 | 0.00 | 0.00 | 0.172173E+09 | 0.00 | 0.314165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144264E+10 | 0.00 | 0.00 | 0.00 | 0.104176E+10 | 0.00 | 0.152516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148351E+10 | 0.00 | 0.00 | 0.00 | 0.206820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155728E+10 | 0.00 | 0.00 | 0.00 | 0.175286E+10 | 0.00 | 19071365.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138904E+10 | 0.00 | 0.00 | 0.00 | 0.703246E+09 | 0.00 | 0.832065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136194E+10 | 0.00 | 0.00 | 0.00 | 37763361.25 | 0.00 | 0.256944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173437E+11 | 0.00 | 0.00 | 0.00 | 0.577764E+10 | 0.00 | 0.744647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.135660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155728E+10 | 0.00 | 0.00 | 0.00 | 0.206820E+10 | 0.00 | 0.188395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.491913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346758E+10 | 0.00 | 0.00 | 0.00 | 31121568.37 | 0.00 | 0.131222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321633E+10 | 0.00 | 0.00 | 0.00 | 0.121524E+10 | 0.00 | 28898887.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321046E+10 | 0.00 | 0.00 | 0.00 | 0.380830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340212E+10 | 0.00 | 0.00 | 0.00 | 0.275108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318036E+10 | 0.00 | 0.00 | 0.00 | 0.884307E+09 | 0.00 | 0.260337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.332819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451019E+11 | 0.00 | 0.00 | 0.00 | 0.869006E+10 | 0.00 | 0.422470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.318036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.491913E+10 | 0.00 | 0.00 | 0.00 | 0.380830E+10 | 0.00 | 0.114267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288260E+10 | 0.00 | 0.00 | 0.12 |
February | 29813860.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201716E+10 | 0.00 | 0.00 | 0.13 |
March | 54985651.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192188E+10 | 0.00 | 0.00 | 0.13 |
April | 0.250640E+09 | 0.00 | 0.00 | 1888.54 | 0.00 | 0.105676E+10 | 3570975.68 | 0.00 | 0.13 |
May | 0.382790E+09 | 4790763.85 | 423851.13 | 423568.90 | 2506794.00 | 0.655306E+09 | 97823229.27 | 1118.45 | 0.14 |
June | 0.215885E+09 | 87825139.00 | 0.00 | 2456911.88 | 0.00 | 19804421.72 | 0.539994E+09 | 0.00 | 0.18 |
July | 16573301.40 | 0.192011E+09 | 0.00 | 3891408.70 | 0.00 | 0.00 | 0.478576E+09 | 0.00 | 0.18 |
August | 74528501.37 | 0.142425E+09 | 0.00 | 3500828.00 | 0.00 | 1720459.34 | 0.556634E+09 | 0.00 | 0.18 |
September | 0.313632E+09 | 58344815.53 | 0.00 | 1496947.96 | 0.00 | 0.190646E+09 | 0.455081E+09 | 0.00 | 0.17 |
October | 0.523273E+09 | 957571.07 | 0.00 | 94128.65 | 0.00 | 0.603468E+09 | 59419736.62 | 0.00 | 0.13 |
November | 0.154331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141010E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236474E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.201645E+10 | 0.486354E+09 | 423851.13 | 11865682.63 | 2506794.00 | 0.131242E+11 | 0.219110E+10 | 1118.45 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.523273E+09 | 0.192011E+09 | 423851.13 | 3891408.70 | 2506794.00 | 0.288260E+10 | 0.556634E+09 | 1118.45 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92378853.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925603E+10 | 0.00 | 0.00 | 0.17 |
February | 0.525852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564283E+10 | 0.00 | 0.00 | 0.17 |
March | 0.164523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393214E+10 | 0.00 | 0.00 | 0.19 |
April | 0.193244E+10 | 0.00 | 0.00 | 0.00 | 2329286.21 | 0.145798E+10 | 0.00 | 0.00 | 0.18 |
May | 0.237480E+10 | 5477337.41 | 0.00 | 5830.53 | 16314274.04 | 0.708710E+09 | 2777131.61 | 0.00 | 0.18 |
June | 0.194695E+10 | 0.194748E+09 | 0.00 | 1230494.56 | 2302079.49 | 0.00 | 0.227711E+09 | 0.00 | 0.20 |
July | 0.725839E+09 | 0.489449E+09 | 0.00 | 6834589.34 | 0.00 | 0.00 | 0.731383E+09 | 0.00 | 0.20 |
August | 0.122683E+10 | 0.389681E+09 | 0.00 | 3272335.50 | 0.00 | 0.00 | 0.669386E+09 | 0.00 | 0.22 |
September | 0.187977E+10 | 0.112641E+09 | 0.00 | 1276630.25 | 5534511.20 | 0.103691E+09 | 0.259030E+09 | 0.00 | 0.19 |
October | 0.221698E+10 | 0.00 | 0.00 | 0.00 | 9824019.22 | 0.630369E+09 | 0.00 | 0.00 | 0.18 |
November | 0.141384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278906E+10 | 0.00 | 0.00 | 0.17 |
December | 0.295090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690883E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.162760E+11 | 0.119200E+10 | 0.00 | 12619880.18 | 36304170.16 | 0.314296E+11 | 0.189029E+10 | 0.00 | 0.19 |
Minimum of Months | 92378853.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.237480E+10 | 0.489449E+09 | 0.00 | 6834589.34 | 16314274.04 | 0.925603E+10 | 0.731383E+09 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |