Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 971.13 | 200.85 | 200.85 |
Net Site Energy | 971.13 | 200.85 | 200.85 |
Total Source Energy | 3069.33 | 634.80 | 634.80 |
Net Source Energy | 3069.33 | 634.80 | 634.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 73.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 968.14 | 3.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 125.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 15.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.20 | 0.62 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 200.23 | 0.62 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.20 | 0.62 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 200.23 | 0.62 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 968.135 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 968.135 | 100.00 |
Total On-Site and Utility Electric Sources | 968.135 | 100.00 |
Total Electricity End Uses | 968.135 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.17 |
Time Setpoint Not Met During Occupied Cooling | 22.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 246.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-14:00 | 10-JAN-07:10 | - | - | - | 13-JUL-11:09 |
Heating | 0.00 | 32181.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21764.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6698.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1684.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75880.67 | 32181.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 32181.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21764.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4393.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1684.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.25 | 0.00 | 0.00 | 0.00 |
Cooling | 398.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 232.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3066.08 | 3.25 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Cooling | 82.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 634.13 | 0.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Cooling | 82.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 634.13 | 0.67 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.14 |
ZONE2 FINE STORAGE DIRECT AIR | 2.83 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.39 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.39 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 57511.19 |
PSZ-OFFICE HEATING COIL | 28191.09 |
PSZ-FINE STORAGE HEATING COIL | 89172.16 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 57511.19 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 1.00 | 1.00 | 2.83 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.14 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.83 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 22570.33 | 28191.09 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.83 | 2.83 | 2.83 | 2.83 | 70206.51 | 89172.16 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.14 | 0.569785 | 1.14 | 22034.93 | 22570.33 | 11285.17 | 22570.33 | 0.738281 | 0.738280 | 0.738280 | 0.738280 |
PSZ-FINE STORAGE COOLING COIL | 2.83 | 1.41 | 2.83 | 68254.94 | 70206.51 | 35103.25 | 70206.51 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.14 | 1299.23 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.83 | 3094.40 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 28 | 1 | VerySmooth | 4.149 | 0.255 | 0.127 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.12629 | 0.51106 | 0.51106 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.73817E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11533.35647 | 13840.02776 | 0.94964 | 1.13957 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7700.12274 | 9240.14728 | 0.21615 | 0.25938 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36703.87481 | 44044.64977 | 2.35601 | 2.82722 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65138E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 19235.49911 | 23082.59893 | 0.45521 | 0.54626 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 1.65138E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 47925.99277 | 57511.19133 | 1.15489 | 1.38587 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17493.93 | 1.13957 | 1.13957 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7984.23 | 0.25938 | 0.25938 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 53937.55 | 2.82722 | 2.82722 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 21768.96 | 0.54626 | 0.54626 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13957 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.82722 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38587 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.38587 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 57511.19305 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 57511.19133 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13957 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13957 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13957 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13957 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13957 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.13957 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.82722 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.82722 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.82722 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82722 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.82722 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.82722 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.13957 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.82722 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13957 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13957 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13957 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13957 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13957 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13957 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56979 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13957 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22034.92544 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22570.33000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11285.16500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22570.33000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73828 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73828 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73828 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73828 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22570.33000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28191.08562 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13957 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1299.23451 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28191.08562 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.82722 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.82722 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.82722 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.82722 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.82722 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.82722 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.41361 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.82722 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 68254.94424 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 70206.51000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 35103.25500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 70206.51000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 70206.51000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89172.15769 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.82722 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3094.40378 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 89172.15769 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21685.5 | 10.36 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 68008.9 | 13.32 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.6542801077E-002 | 3.5800622252E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1037156572 | 0.1346740091 | Pass | Pass | 8.8708991194E-002 | 0.6447468634 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.7841757676E-002 | 6.6744859569E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.229 | 0.450 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 4.149 | 0.255 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.382 | 0.478 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.73 | 83.73 | 123.49 | |
Exterior Lighting Total | 7857.24 | 123.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22570.33 | 16663.22 | 5907.11 | 0.74 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 70206.51 | 47465.22 | 22741.29 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21685.5 | 10.36 | ||||
PSZ-FINE STORAGE COOLING COIL | 68008.9 | 13.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 57511.19 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28191.09 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 89172.16 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.39 | 128.76 | 92.91 | 1.00 | 3.84 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.14 | 1299.23 | 1140.11 | 1.00 | 1.33 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.83 | 3094.40 | 1094.51 | 1.00 | 1.24 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11533.36 | 13840.03 | 58.43 | 0.950 | 1.140 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00831 | 32.79 | 0.01651 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36703.87 | 44044.65 | 31.61 | 2.356 | 2.827 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00858 | 33.90 | 0.01651 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 33.90 | 0.01651 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7700.12 | 9240.15 | 39.01 | 0.216 | 0.259 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00776 | 4.60 | 0.00526 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 19235.50 | 23082.60 | 16.57 | 0.455 | 0.546 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00679 | 4.60 | 0.00526 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 47925.99 | 57511.19 | 17.95 | 1.155 | 1.386 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00764 | 4.60 | 0.00526 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.14 | 1.14 | 0.26 | 0.26 | 1.1396 | 1.1396 | 1.1396 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 0.55 | 0.55 | 2.8272 | 2.8272 | 2.8272 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 57511.193 | 57511.193 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 57511.19 | 57511.19 | 1.385871 | 6.19 | 6.19 | 0.00595909 | 43.33 | 27.10 | 0.01600000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00763545 | 99.9999 | 57511.19 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22570.330 | 0.000 | 1.139570 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22570.33 | 19013.28 | 1.139570 | 24.70 | 17.07 | 0.00904961 | 12.00 | 11.25 | 0.00800000 | 32.79 | 0.01651377 | 24.82 | 8.9757 | 23.90 | 0.00831358 | 45.0016 | 11533.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28191.086 | 28191.086 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28191.09 | 28191.09 | 1.139570 | 14.54 | 11.05 | 0.00677556 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 8.9757 | 21.10 | 0.00776418 | 49.8649 | 7700.12 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 70206.510 | 0.000 | 2.827220 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 70206.51 | 55732.80 | 2.827220 | 27.78 | 18.69 | 0.00977352 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01651378 | 25.10 | 15.0223 | 26.70 | 0.00858198 | 39.3130 | 35625.65 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 89172.158 | 89172.158 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89172.16 | 89172.16 | 2.827216 | 7.04 | 6.27 | 0.00559788 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 15.0223 | 15.56 | 0.00678852 | 61.8283 | 19235.50 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 57511.193 | 57511.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2032 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.385871 | 1.66743469 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 57511.19 | 57511.19 | 1.0000 | 1.66743469 | 1.385871 | 6.19 | 6.19 | 0.00595909 | 21194.3 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57511.19 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00763545 | 10.00 | 0.00763545 | 99.9999 | 57511.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22570.330 | 0.000 | 1.139570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6628 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22570.33 | 19013.28 | 1.0000 | 1.37109290 | 1.139570 | 24.70 | 17.07 | 0.00904961 | 47865.0 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22570.33 | 32.79 | 0.01651377 | 24.82 | 0.10228487 | 8.9757 | 23.90 | 0.00831358 | 23.90 | 0.00831358 | 45.0016 | 11533.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28191.086 | 28191.086 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.139570 | 1.37109235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28191.09 | 28191.09 | 1.0000 | 1.37109235 | 1.139570 | 14.54 | 11.05 | 0.00677556 | 31738.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28191.09 | 4.60 | 0.00525715 | 4.60 | 0.10228487 | 8.9757 | 21.01 | 0.00776418 | 21.10 | 0.00776418 | 49.8649 | 7700.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 70206.510 | 0.000 | 2.827220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0085 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 70206.51 | 55732.80 | 1.0000 | 3.40161751 | 2.827220 | 27.78 | 18.69 | 0.00977352 | 52862.0 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70206.51 | 33.90 | 0.01651378 | 25.10 | 0.42471267 | 15.0223 | 26.70 | 0.00858198 | 26.70 | 0.00858198 | 39.3130 | 35625.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89172.158 | 89172.158 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.827216 | 3.40161306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89172.16 | 89172.16 | 1.0000 | 3.40161306 | 2.827216 | 7.04 | 6.27 | 0.00559788 | 21145.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89172.16 | 4.60 | 0.00525715 | 4.60 | 0.42471267 | 15.0223 | 15.56 | 0.00678852 | 15.56 | 0.00678852 | 61.8283 | 19235.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2516.50 | 1039.17 | 246.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2516.50 | 1039.17 | 246.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.17 | 446.33 | 3.17 | 22.50 |
ZONE2 FINE STORAGE | 1.17 | 151.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.33 | 546.17 | 3.17 | 22.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.344 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
Electricity:Building | 636.77 | 4992.32 | 01-JAN-00:10 | 48037.94 | 30-MAR-12:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 437.17 | 2759.73 | 01-JAN-00:10 | 33963.13 | 30-MAR-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.10 | 483.00 | 11-JAN-06:10 | 1781.14 | 23-JAN-12:30 |
WaterSystems:Electricity | 24.10 | 483.00 | 11-JAN-06:10 | 1781.14 | 23-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 11-JAN-06:10 | 1781.14 | 23-JAN-12:30 |
Fans:Electricity | 73.55 | 0.00 | 01-JAN-00:10 | 6698.93 | 10-MAY-11:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.53 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 15.53 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
ElectricityPurchased:Plant | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
Cogeneration:ElectricityPurchased | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
ElectricityNet:Plant | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
Cogeneration:ElectricityNet | 968.14 | 5475.32 | 01-JAN-07:30 | 75880.67 | 03-AUG-15:00 |
Electricity:HVAC | 183.78 | 0.00 | 01-JAN-00:10 | 28350.83 | 03-AUG-16:10 |
General:Fans:Electricity | 58.02 | 0.00 | 01-JAN-00:10 | 4393.64 | 02-JAN-08:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 125.75 | 0.00 | 01-JAN-00:10 | 23957.19 | 03-AUG-16:10 |
ExteriorLights:Electricity | 123.49 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.49 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 3.00 | 0.00 | 01-JAN-00:10 | 32181.14 | 10-JAN-07:10 |
Gas:HVAC | 3.00 | 0.00 | 01-JAN-00:10 | 32181.14 | 10-JAN-07:10 |
Heating:Gas | 3.00 | 0.00 | 01-JAN-00:10 | 32181.14 | 10-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 694.27 | 0.00 | 01-JAN-00:10 | 126689.67 | 03-AUG-16:10 |
EnergyTransfer:Building | 252.74 | 0.00 | 01-JAN-00:10 | 48336.79 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 83.84 | 0.00 | 01-JAN-00:10 | 13914.64 | 11-SEP-00:10 |
Heating:EnergyTransfer | 3.50 | 0.00 | 01-JAN-00:10 | 19709.45 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.76 | 0.00 | 01-JAN-00:10 | 11992.35 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 249.24 | 0.00 | 01-JAN-00:10 | 48336.79 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 82.08 | 0.00 | 01-JAN-00:10 | 13914.64 | 11-SEP-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 168.90 | 0.00 | 01-JAN-00:10 | 37730.77 | 03-AUG-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.75 | 0.00 | 01-JAN-00:10 | 19137.02 | 05-FEB-07:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 167.16 | 0.00 | 01-JAN-00:10 | 37730.77 | 03-AUG-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 441.53 | 0.00 | 01-JAN-00:10 | 78667.53 | 03-JUL-16:30 |
HeatingCoils:EnergyTransfer | 2.03 | 0.00 | 01-JAN-00:10 | 21914.86 | 10-JAN-07:10 |
CoolingCoils:EnergyTransfer | 439.50 | 0.00 | 01-JAN-00:10 | 78667.53 | 03-JUL-16:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.757 | -82.078 | 0.000 | 0.000 | 3.620 | 30.994 | 31.946 | 11.190 | 0.000 | 4.156 | 11.268 | 0.000 | -6.008 | 0.000 | -6.844 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.746 | -167.146 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 7.620 | 68.895 | 0.000 | 0.000 | 0.000 | -47.771 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 44.368 | 0.000 | 1.480 | 193.114 | 0.000 | -15.643 | 0.000 | -644.964 | -0.006 |
Total Facility | 0.000 | 0.000 | 3.502 | -249.224 | 0.000 | 0.000 | 3.620 | 481.960 | 139.282 | 55.557 | 0.000 | 13.256 | 273.277 | 0.000 | -21.651 | 0.000 | -699.579 | -0.006 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-OCT-00:01 | 0.00 | 0.00 | 0.00 | -19561.92 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 19293.22 | 0.00 | -504.58 | 0.00 | -259.42 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-12:23 | 0.00 | 0.00 | 0.00 | -55913.42 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 54850.19 | 0.00 | -0.00 | 0.00 | -136.65 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-17:06 | 0.00 | 0.00 | 0.00 | -71695.64 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5143.18 | 0.00 | 1276.49 | 103515.24 | 0.00 | 0.00 | 0.00 | -45281.62 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 27225.32 | 0.00 | 0.00 | 0.00 | 52.67 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -610.86 | 0.00 | -900.89 | -26926.44 |
ZONE2 FINE STORAGE | 05-FEB-07:43 | 0.00 | 0.00 | 57411.07 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15330.31 | -43280.65 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JAN-06:01 | 0.00 | 0.00 | 71044.56 | 0.00 | 0.00 | 0.00 | 54.04 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2520.90 | 0.00 | -24174.14 | -51573.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1396 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1396 | 0.0898 | 1.0000 | 0.1023 | 0.0898 | ||
PSZ-FINE STORAGE | 2.8272 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.8272 | 0.1502 | 1.0000 | 0.4247 | 0.1502 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1396 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1396 | 1.0000 | 1.0000 | 0.1023 | 0.0898 | ||
PSZ-FINE STORAGE | 2.8272 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.8272 | 1.0000 | 1.0000 | 0.4247 | 0.1502 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1396 | 1.1396 | 1.1396 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8272 | 2.8272 | 2.8272 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1396 | 1.1396 | 1.1396 | 1.1396 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8272 | 2.8272 | 2.8272 | 2.8272 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1396 | 1.1396 | 1.1396 | 0.1023 | 0.3943 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8272 | 2.8272 | 2.8272 | 0.4247 | 0.7775 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1396 | 1.1396 | 1.1396 | 1.1396 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8272 | 2.8272 | 2.8272 | 2.8272 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.17 |
Number of hours cooling loads not met | 22.50 |
Number of hours not met | 25.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 3.00 | 32181.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 125.75 | 23957.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.49 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 15.53 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.02 | 4393.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1781.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 968.14 |
Natural Gas | 0.00 | 3.00 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 971.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 26.01 |
Fans (All) | 15.21 |
Service Water Heating | 4.98 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 200.23 |
Subtotal | 200.23 |
Natural Gas [MJ/m2] | |
Space Heating | 0.62 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.62 |
Subtotal | 0.62 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 49.63 |
Space Heating | 0.31 |
Space Cooling | 12.95 |
Fans (All) | 7.57 |
Service Water Heating | 2.48 |
Receptacle Equipment | 14.34 |
Miscellaneous | 12.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.113709E+10 |
February | 0.000 | 0.840508E+09 |
March | 0.000 | 0.381265E+09 |
April | 0.000 | 2282467.622 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.318150E+08 |
December | 0.000 | 0.602973E+09 |
Annual Sum or Average | 0.299594E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.113709E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135235E+10 | 17197.32 | 02-JAN-00:01 | 17.17 | 16.96 | 0.233892E+09 | 301.60 | 28-JAN-16:00 | 22.00 | 14.38 |
February | 0.207551E+10 | 17873.95 | 27-FEB-00:02 | 17.77 | 17.47 | 0.220925E+09 | 301.60 | 09-FEB-15:30 | 21.65 | 14.47 |
March | 0.313928E+10 | 17313.51 | 06-MAR-00:02 | 19.87 | 18.29 | 0.260906E+09 | 301.90 | 10-MAR-16:49 | 14.00 | 10.83 |
April | 0.616709E+10 | 19240.40 | 17-APR-00:02 | 13.92 | 11.56 | 0.248421E+09 | 301.62 | 07-APR-07:10 | 18.72 | 17.56 |
May | 0.101794E+11 | 16932.42 | 06-MAY-19:03 | 25.40 | 20.61 | 0.258899E+09 | 301.59 | 13-MAY-07:10 | 24.08 | 21.89 |
June | 0.108286E+11 | 18171.04 | 12-JUN-00:01 | 25.50 | 21.64 | 0.258907E+09 | 301.61 | 10-JUN-15:30 | 33.60 | 21.59 |
July | 0.107714E+11 | 16845.88 | 24-JUL-00:01 | 28.30 | 26.22 | 0.248968E+09 | 301.59 | 15-JUL-07:10 | 26.38 | 24.59 |
August | 0.116709E+11 | 17335.55 | 03-AUG-21:03 | 24.42 | 19.04 | 0.268876E+09 | 301.59 | 30-AUG-15:39 | 35.10 | 23.38 |
September | 0.987479E+10 | 16867.40 | 02-SEP-17:08 | 23.02 | 21.56 | 0.248954E+09 | 301.59 | 02-SEP-07:10 | 25.97 | 24.30 |
October | 0.890055E+10 | 19563.48 | 02-OCT-00:01 | 19.95 | 15.67 | 0.248879E+09 | 301.61 | 17-OCT-15:09 | 23.67 | 16.32 |
November | 0.443968E+10 | 18230.81 | 06-NOV-00:01 | 20.95 | 18.49 | 0.237594E+09 | 301.60 | 14-NOV-16:00 | 17.20 | 13.07 |
December | 0.267936E+10 | 16266.89 | 11-DEC-00:01 | 21.17 | 19.25 | 0.239506E+09 | 301.60 | 04-DEC-15:30 | 19.00 | 13.50 |
Annual Sum or Average | 0.820789E+11 | 0.297473E+10 | ||||||||
Minimum of Months | 0.135235E+10 | 16266.89 | 13.92 | 11.56 | 0.220925E+09 | 301.59 | 14.00 | 10.83 | ||
Maximum of Months | 0.116709E+11 | 19563.48 | 28.30 | 26.22 | 0.268876E+09 | 301.90 | 35.10 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131120E+10 | 25379.15 | 01-JAN-14:25 | 25.50 | 18.22 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.204337E+10 | 22985.26 | 26-FEB-14:35 | 26.27 | 19.98 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.292602E+10 | 25878.57 | 26-MAR-13:25 | 29.70 | 20.03 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.954357E+10 | 52244.04 | 27-APR-17:08 | 29.22 | 21.95 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.230168E+11 | 54406.61 | 04-MAY-17:06 | 31.42 | 21.63 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.270356E+11 | 54955.51 | 12-JUN-17:06 | 32.02 | 21.32 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.280073E+11 | 52502.00 | 12-JUL-17:08 | 23.90 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.276619E+11 | 51146.26 | 30-AUG-17:06 | 34.67 | 23.09 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.211357E+11 | 52245.64 | 22-SEP-17:06 | 30.32 | 21.05 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.175250E+11 | 55917.80 | 01-OCT-12:23 | 26.60 | 18.42 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.420321E+10 | 38077.76 | 02-NOV-17:10 | 27.35 | 23.65 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.274755E+10 | 20537.27 | 10-DEC-13:50 | 27.00 | 20.21 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.167157E+12 | 0.00 | ||||||||
Minimum of Months | 0.131120E+10 | 20537.27 | 23.90 | 18.22 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.280073E+11 | 55917.80 | 34.67 | 23.65 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655696E+09 | 27165.85 | 11-JAN-06:01 | 8.00 |
February | 0.378088E+09 | 27225.30 | 07-FEB-06:01 | 8.62 |
March | 0.285657E+09 | 27012.08 | 13-MAR-05:01 | 6.68 |
April | 22120871.99 | 1675.37 | 11-APR-06:30 | 10.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 8387830.43 | 819.17 | 02-OCT-06:10 | 18.13 |
November | 43062948.02 | 4852.10 | 15-NOV-07:10 | 7.80 |
December | 0.363580E+09 | 26778.79 | 22-DEC-06:02 | 10.00 |
Annual Sum or Average | 0.175659E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.68 | |
Maximum of Months | 0.655696E+09 | 27225.30 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497757E+09 | 44292.62 | 10-JAN-06:01 | 3.00 |
February | 0.526104E+09 | 57411.07 | 05-FEB-07:43 | -3.4 |
March | 0.234168E+09 | 14288.68 | 12-MAR-06:45 | 6.70 |
April | 15942782.29 | 944.97 | 03-APR-10:35 | 22.73 |
May | 2538940.50 | 1933.84 | 01-MAY-06:05 | 25.18 |
June | 4479966.01 | 2428.38 | 23-JUN-06:10 | 25.78 |
July | 591919.27 | 2373.90 | 01-JUL-06:05 | 25.10 |
August | 1876441.36 | 1184.62 | 16-AUG-06:10 | 23.92 |
September | 2660852.80 | 1255.44 | 14-SEP-06:10 | 24.50 |
October | 20232995.10 | 1033.10 | 21-OCT-06:10 | 23.95 |
November | 0.169700E+09 | 2090.84 | 24-NOV-16:05 | 23.43 |
December | 0.269651E+09 | 28866.47 | 21-DEC-06:33 | 0.33 |
Annual Sum or Average | 0.174570E+10 | |||
Minimum of Months | 591919.27 | 944.97 | -3.4 | |
Maximum of Months | 0.526104E+09 | 57411.07 | 25.78 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13499120.51 | 0.157572E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22744356.70 | 0.105887E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59942826.38 | 0.120514E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190301E+09 | 0.460655E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646799E+09 | 26879581.49 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757458E+09 | 22363092.40 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695610E+09 | 15417980.51 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778973E+09 | 24480165.51 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412245E+09 | 58579351.76 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432199E+09 | 0.328751E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100413E+09 | 0.751677E+09 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46305696.55 | 0.131552E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.415649E+10 | 0.684405E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13499120.51 | 15417980.51 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778973E+09 | 0.157572E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12439302.72 | 0.801430E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12641444.67 | 0.603350E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27587571.78 | 0.752107E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204709E+09 | 0.404691E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106324E+10 | 0.124408E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123118E+10 | 0.806149E+09 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148465E+10 | 0.495813E+09 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158266E+10 | 0.119464E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103622E+10 | 0.182975E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890233E+09 | 0.404458E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47260520.30 | 0.518533E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26766589.64 | 0.735450E+10 |
Annual Sum or Average | 0.136656E+12 | 0.761959E+10 | 0.477706E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12439302.72 | 0.495813E+09 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158266E+10 | 0.801430E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117225E+09 | 0.245426E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60744597.35 | 0.190514E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9850927.96 | 0.270981E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14530.21 | 0.177986E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088017.69 | 0.106186E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33891.46 | 0.724285E+10 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1144165.83 | 0.655774E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5856637.31 | 0.102129E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30733514.60 | 0.127102E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39489.39 | 0.210963E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34540495.59 | 0.181562E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45850670.27 | 0.237626E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.307122E+09 | 0.198848E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14530.21 | 0.655774E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117225E+09 | 0.270981E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 736.45 | 02-JAN-13:00 | 8344.88 | 05-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.70 | 02-FEB-13:00 | 7818.21 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.13 | 30-MAR-12:00 | 8431.19 | 09-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3032.08 | 28-APR-16:10 | 5051.32 | 11-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3331.84 | 10-MAY-16:10 | 678.62 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3439.36 | 28-JUN-16:10 | 975.77 | 07-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.33 | 21-JUL-16:10 | 368.89 | 13-JUL-11:04 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.70 | 03-AUG-16:10 | 803.08 | 16-AUG-17:00 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.50 | 06-SEP-16:10 | 1571.87 | 07-SEP-16:54 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257.24 | 05-OCT-17:00 | 3796.71 | 27-OCT-06:05 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.53 | 02-NOV-12:00 | 5420.07 | 15-NOV-07:03 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.73 | 13-DEC-13:00 | 8536.56 | 20-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 736.45 | 368.89 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.70 | 8536.56 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.72 | 16-JAN-15:00 | 14437.02 | 03-JAN-09:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.76 | 20-FEB-15:00 | 17715.85 | 16-FEB-18:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.97 | 27-MAR-15:10 | 15208.44 | 09-MAR-09:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.57 | 28-APR-15:10 | 11761.88 | 15-APR-17:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.73 | 18-MAY-16:40 | 3576.19 | 05-MAY-06:20 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.81 | 08-JUN-15:10 | 4464.44 | 06-JUN-20:53 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.77 | 06-JUL-15:10 | 2443.91 | 30-JUL-11:10 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.63 | 03-AUG-16:40 | 4695.60 | 25-AUG-24:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7366.36 | 09-SEP-17:00 | 4788.76 | 19-SEP-18:53 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6844.92 | 09-OCT-13:55 | 10293.34 | 27-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.62 | 02-NOV-15:10 | 10795.20 | 09-NOV-07:03 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.08 | 13-DEC-16:10 | 12342.64 | 04-DEC-07:05 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.72 | 2443.91 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.63 | 17715.85 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3901.46 | 16-JAN-15:00 | 46462.05 | 03-JAN-09:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4233.68 | 20-FEB-15:00 | 54513.66 | 04-FEB-11:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.84 | 26-MAR-13:53 | 51068.40 | 09-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 15-APR-11:55 | 39786.94 | 01-APR-16:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.55 | 27-MAY-13:43 | 25859.49 | 26-MAY-15:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 | 25-JUN-12:52 | 21939.93 | 01-JUN-12:52 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.76 | 02-JUL-10:53 | 26666.85 | 31-JUL-11:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.62 | 20-AUG-13:53 | 18984.17 | 25-AUG-24:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.84 | 09-SEP-17:00 | 23465.97 | 12-SEP-20:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.63 | 06-OCT-08:55 | 41144.61 | 27-OCT-11:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3759.99 | 28-NOV-13:10 | 33475.59 | 09-NOV-08:10 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2601.40 | 31-DEC-11:00 | 42116.67 | 19-DEC-12:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 18984.17 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4233.68 | 54513.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17197.32 | 02-JAN-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.29 |
February | 17873.95 | 27-FEB-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17313.51 | 06-MAR-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 |
April | 19240.40 | 17-APR-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.43 |
May | 16932.42 | 06-MAY-19:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 | 0.00 |
June | 18171.04 | 12-JUN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.18 |
July | 16845.88 | 24-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
August | 17335.55 | 03-AUG-21:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 0.00 |
September | 16867.40 | 02-SEP-17:08 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 |
October | 19563.48 | 02-OCT-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.42 |
November | 18230.81 | 06-NOV-00:01 | 0.00 | 4130.60 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
December | 16266.89 | 11-DEC-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16266.89 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19563.48 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 | 259.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25379.15 | 01-JAN-14:25 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.53 |
February | 22985.26 | 26-FEB-14:35 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.41 |
March | 25878.57 | 26-MAR-13:25 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.59 | 0.00 |
April | 52244.04 | 27-APR-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.32 | 0.00 |
May | 54406.61 | 04-MAY-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.59 | 0.00 |
June | 54955.51 | 12-JUN-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.92 | 0.00 |
July | 52502.00 | 12-JUL-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.13 |
August | 51146.26 | 30-AUG-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.51 | 0.00 |
September | 52245.64 | 22-SEP-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.91 | 0.00 |
October | 55917.80 | 01-OCT-12:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.65 |
November | 38077.76 | 02-NOV-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.04 | 0.00 |
December | 20537.27 | 10-DEC-13:50 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20537.27 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55917.80 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.91 | 322.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8981.07 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3922.16 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6969.62 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7963.10 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.18 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2898.60 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2781.56 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.77 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.70 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 8279.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8971.84 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.62 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8461.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.70 | |
Maximum of Months | 0.00 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8981.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.708132E+11 | 58994.92 | 19-JAN-15:09 | 0.113709E+10 | 32181.14 | 10-JAN-07:10 |
February | 0.651944E+11 | 61975.87 | 27-FEB-15:30 | 0.840508E+09 | 31616.65 | 06-FEB-07:10 |
March | 0.748870E+11 | 64451.80 | 30-MAR-12:00 | 0.381265E+09 | 15034.23 | 09-MAR-07:10 |
April | 0.750641E+11 | 71875.06 | 28-APR-14:00 | 2282467.62 | 2690.45 | 11-APR-06:30 |
May | 0.890737E+11 | 72607.50 | 25-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.909081E+11 | 74637.53 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.920572E+11 | 75356.32 | 19-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.954858E+11 | 75880.67 | 03-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.864892E+11 | 73510.41 | 09-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.842677E+11 | 74316.90 | 06-OCT-12:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.713921E+11 | 68540.09 | 02-NOV-14:30 | 31814977.67 | 5804.89 | 15-NOV-07:19 |
December | 0.725029E+11 | 66340.39 | 15-DEC-13:00 | 0.602973E+09 | 31593.59 | 21-DEC-07:10 |
Annual Sum or Average | 0.968135E+12 | 0.299594E+10 | ||||
Minimum of Months | 0.651944E+11 | 58994.92 | 0.00 | 0.00 | ||
Maximum of Months | 0.954858E+11 | 75880.67 | 0.113709E+10 | 32181.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.118613E+11 | 0.115358E+11 | 0.00 | 0.437729E+10 | 0.00 | 0.00 | 0.813673E+09 | 0.00 | 0.00 | 0.00 | 0.212181E+10 | 0.00 |
February | 0.366966E+11 | 0.102443E+11 | 0.105871E+11 | 0.00 | 0.404387E+10 | 0.00 | 0.00 | 0.170121E+10 | 0.00 | 0.00 | 0.00 | 0.192130E+10 | 0.00 |
March | 0.423649E+11 | 0.106356E+11 | 0.123357E+11 | 0.00 | 0.476889E+10 | 0.00 | 0.00 | 0.264704E+10 | 0.00 | 0.00 | 0.00 | 0.213492E+10 | 0.00 |
April | 0.397216E+11 | 0.960783E+10 | 0.114862E+11 | 0.00 | 0.515906E+10 | 0.00 | 0.00 | 0.709398E+10 | 0.00 | 0.00 | 0.00 | 0.199538E+10 | 0.00 |
May | 0.412341E+11 | 0.931083E+10 | 0.119357E+11 | 0.00 | 0.761820E+10 | 0.00 | 0.00 | 0.169554E+11 | 0.00 | 0.00 | 0.00 | 0.201935E+10 | 0.00 |
June | 0.408524E+11 | 0.867439E+10 | 0.118862E+11 | 0.00 | 0.834283E+10 | 0.00 | 0.00 | 0.192180E+11 | 0.00 | 0.00 | 0.00 | 0.193430E+10 | 0.00 |
July | 0.401034E+11 | 0.914111E+10 | 0.115358E+11 | 0.00 | 0.854887E+10 | 0.00 | 0.00 | 0.207845E+11 | 0.00 | 0.00 | 0.00 | 0.194356E+10 | 0.00 |
August | 0.423649E+11 | 0.964083E+10 | 0.123357E+11 | 0.00 | 0.843275E+10 | 0.00 | 0.00 | 0.207223E+11 | 0.00 | 0.00 | 0.00 | 0.198939E+10 | 0.00 |
September | 0.397216E+11 | 0.100038E+11 | 0.114862E+11 | 0.00 | 0.702633E+10 | 0.00 | 0.00 | 0.163216E+11 | 0.00 | 0.00 | 0.00 | 0.192967E+10 | 0.00 |
October | 0.401034E+11 | 0.110551E+11 | 0.115358E+11 | 0.00 | 0.637431E+10 | 0.00 | 0.00 | 0.131809E+11 | 0.00 | 0.00 | 0.00 | 0.201823E+10 | 0.00 |
November | 0.385909E+11 | 0.112956E+11 | 0.110862E+11 | 0.00 | 0.443245E+10 | 0.00 | 0.00 | 0.399429E+10 | 0.00 | 0.00 | 0.00 | 0.199275E+10 | 0.00 |
December | 0.401034E+11 | 0.120169E+11 | 0.115358E+11 | 0.00 | 0.442322E+10 | 0.00 | 0.00 | 0.232162E+10 | 0.00 | 0.00 | 0.00 | 0.210202E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123488E+12 | 0.139282E+12 | 0.735481E+11 | 0.00 | 0.125755E+12 | 0.241026E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.867439E+10 | 0.105871E+11 | 0.00 | 0.404387E+10 | 0.00 | 0.00 | 0.813673E+09 | 0.00 | 0.00 | 0.00 | 0.192130E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.120169E+11 | 0.123357E+11 | 0.00 | 0.854887E+10 | 0.00 | 0.00 | 0.207845E+11 | 0.00 | 0.00 | 0.00 | 0.213492E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.113709E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.840508E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.381265E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2282467.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 31814977.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.602973E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299594E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.113709E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4393.64 | 02-JAN-08:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5162.07 | 27-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 6698.93 | 30-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6698.93 | 15-APR-11:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6698.93 | 10-MAY-11:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6698.93 | 03-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6698.93 | 03-JUL-11:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6698.93 | 05-AUG-16:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6698.93 | 09-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6698.93 | 12-OCT-12:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6698.93 | 07-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 6698.93 | 15-DEC-12:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4393.64 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6698.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7130.74 | 19-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1781.14 | 23-JAN-12:30 | 0.00 |
February | 9540.41 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1780.24 | 06-FEB-12:30 | 0.00 |
March | 10692.10 | 28-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1772.37 | 02-MAR-12:00 | 0.00 |
April | 18746.50 | 28-APR-15:50 | 0.00 | 0.00 | 0.00 | 1756.96 | 01-APR-11:09 | 0.00 |
May | 19061.46 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.53 | 01-MAY-11:39 | 0.00 |
June | 21480.27 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1721.04 | 01-JUN-11:39 | 0.00 |
July | 22281.40 | 18-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1710.30 | 01-JUL-11:30 | 0.00 |
August | 23957.19 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1714.54 | 31-AUG-11:50 | 0.00 |
September | 22992.39 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1728.70 | 30-SEP-11:39 | 0.00 |
October | 21125.19 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1747.61 | 31-OCT-11:20 | 0.00 |
November | 14389.24 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1764.73 | 30-NOV-12:09 | 0.00 |
December | 12170.15 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1777.79 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7130.74 | 0.00 | 0.00 | 0.00 | 1710.30 | 0.00 | ||
Maximum of Months | 23957.19 | 0.00 | 0.00 | 0.00 | 1781.14 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58994.92 | 19-JAN-15:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4393.64 | 0.00 | 0.00 | 7123.21 | 0.00 |
February | 61975.87 | 27-FEB-15:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5162.07 | 0.00 | 0.00 | 9341.02 | 0.00 |
March | 64451.80 | 30-MAR-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 10292.99 | 0.00 |
April | 71875.06 | 28-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 17731.19 | 0.00 |
May | 72607.50 | 25-MAY-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 18501.75 | 0.00 |
June | 74637.53 | 28-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 20518.79 | 0.00 |
July | 75356.32 | 19-JUL-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 21262.24 | 0.00 |
August | 75880.67 | 03-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 21764.58 | 0.00 |
September | 73510.41 | 09-SEP-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 19385.70 | 0.00 |
October | 74316.90 | 06-OCT-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 20180.24 | 0.00 |
November | 68540.09 | 02-NOV-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 14389.24 | 0.00 |
December | 66340.39 | 15-DEC-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 12170.15 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 58994.92 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4393.64 | 0.00 | 0.00 | 7123.21 | 0.00 | |
Maximum of Months | 75880.67 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6698.93 | 0.00 | 0.00 | 21764.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 32181.14 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 31616.65 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 15034.23 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2690.45 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 5804.89 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 31593.59 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 32181.14 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.40 | 1.50 | 20.40 | 1.67 | 24.55 | 0.00 | 0.00 |
February | 0.67 | 20.32 | 0.67 | 20.32 | 3.17 | 24.50 | 0.50 | 24.48 |
March | 0.67 | 20.40 | 0.67 | 20.40 | 5.83 | 24.51 | 0.50 | 24.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 24.58 | 0.83 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 24.63 | 1.83 | 24.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 24.66 | 3.67 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 24.69 | 4.67 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 24.69 | 4.67 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 24.66 | 3.17 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 24.65 | 2.50 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 24.51 | 0.00 | 0.00 |
December | 0.33 | 20.35 | 0.33 | 20.35 | 1.67 | 24.50 | 0.17 | 24.47 |
Annual Sum or Average | 3.17 | 20.38 | 3.17 | 20.38 | 446.33 | 24.65 | 22.50 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.50 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.40 | 1.50 | 20.40 | 83.33 | 24.69 | 4.67 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.99 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 0.00 |
February | 0.83 | 14.89 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.45 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.59 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.60 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.59 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.67 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.61 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.00 | 0.00 |
December | 0.17 | 15.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 14.92 | 0.00 | 151.33 | 27.60 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 15.00 | 0.00 | 0.00 | 33.50 | 27.67 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.17 | 22.73 | 94.17 | 22.14 | 65.17 | 21.35 |
February | 177.17 | 22.95 | 91.50 | 22.95 | 33.33 | 21.29 |
March | 183.67 | 23.00 | 113.00 | 23.24 | 27.83 | 21.21 |
April | 43.67 | 23.55 | 191.50 | 23.90 | 1.00 | 23.90 |
May | 10.83 | 23.90 | 311.67 | 23.91 | 10.83 | 23.90 |
June | 8.33 | 23.90 | 311.17 | 23.91 | 8.33 | 23.90 |
July | 15.00 | 23.90 | 299.83 | 23.91 | 15.00 | 23.90 |
August | 18.67 | 23.90 | 324.00 | 23.91 | 18.67 | 23.90 |
September | 10.83 | 23.90 | 300.00 | 23.91 | 10.83 | 23.90 |
October | 28.00 | 23.84 | 252.33 | 23.91 | 12.50 | 23.90 |
November | 96.00 | 23.43 | 111.83 | 23.90 | 4.33 | 23.90 |
December | 198.83 | 22.92 | 115.50 | 23.18 | 38.33 | 21.71 |
Annual Sum or Average | 1039.17 | 23.05 | 2516.50 | 23.74 | 246.17 | 22.23 |
Minimum of Months | 8.33 | 22.73 | 91.50 | 22.14 | 1.00 | 21.21 |
Maximum of Months | 248.17 | 23.90 | 324.00 | 23.91 | 65.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.218892E+10 | 0.584524E+09 | 149.65 | 0.166601E+10 | 0.522908E+09 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 | 25336.20 | 02-JAN-00:01 | 18187.36 | 02-JAN-00:01 | 7341.25 | 02-JAN-00:03 | 5884.66 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 |
February | 0.345619E+10 | 0.922431E+09 | 187.31 | 0.261573E+10 | 0.840459E+09 | 0.00 | 1.00 | 27-FEB-00:02 | 0.00 | 01-FEB-00:10 | 24447.54 | 27-FEB-00:02 | 19195.73 | 27-FEB-00:02 | 5792.76 | 28-FEB-18:10 | 5723.33 | 27-FEB-00:02 | 0.00 | 01-FEB-00:10 |
March | 0.506319E+10 | 0.135625E+10 | 257.16 | 0.394290E+10 | 0.112029E+10 | 0.00 | 1.00 | 06-MAR-00:02 | 0.00 | 01-MAR-00:05 | 25624.15 | 27-MAR-00:01 | 19131.52 | 06-MAR-00:02 | 7792.29 | 27-MAR-00:03 | 5934.31 | 27-MAR-00:01 | 0.00 | 01-MAR-00:05 |
April | 0.957518E+10 | 0.260339E+10 | 391.09 | 0.760842E+10 | 0.196676E+10 | 0.00 | 1.00 | 14-APR-17:08 | 0.00 | 01-APR-00:05 | 26559.02 | 24-APR-00:01 | 20454.51 | 17-APR-00:02 | 9265.71 | 24-APR-00:05 | 6213.77 | 28-APR-17:08 | 0.00 | 01-APR-00:05 |
May | 0.172369E+11 | 0.476600E+10 | 525.68 | 0.126705E+11 | 0.456642E+10 | 0.00 | 1.00 | 01-MAY-00:01 | 0.00 | 01-MAY-00:06 | 28628.14 | 22-MAY-00:01 | 19274.42 | 03-MAY-20:23 | 13605.72 | 22-MAY-00:05 | 6495.20 | 22-MAY-00:01 | 0.00 | 01-MAY-00:01 |
June | 0.183430E+11 | 0.512295E+10 | 533.42 | 0.135027E+11 | 0.484022E+10 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:15 | 28066.01 | 05-JUN-00:01 | 19691.60 | 12-JUN-00:01 | 12122.65 | 05-JUN-00:07 | 6461.68 | 05-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.189850E+11 | 0.526104E+10 | 515.65 | 0.134014E+11 | 0.558360E+10 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:13 | 29178.04 | 31-JUL-00:01 | 18971.17 | 18-JUL-23:43 | 14205.02 | 31-JUL-00:04 | 6602.98 | 03-JUL-00:01 | 0.00 | 01-JUL-00:05 |
August | 0.203129E+11 | 0.560344E+10 | 557.92 | 0.144344E+11 | 0.587849E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:13 | 28798.23 | 14-AUG-00:01 | 19518.78 | 30-AUG-23:03 | 13786.41 | 14-AUG-00:06 | 6537.58 | 14-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.171599E+11 | 0.463904E+10 | 516.38 | 0.121101E+11 | 0.504978E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:13 | 29456.64 | 05-SEP-00:01 | 19195.40 | 22-SEP-20:23 | 15528.36 | 05-SEP-00:05 | 6495.64 | 09-SEP-17:06 | 0.00 | 01-SEP-00:03 |
October | 0.146115E+11 | 0.398174E+10 | 480.51 | 0.108517E+11 | 0.375980E+10 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:03 | 28520.61 | 23-OCT-00:01 | 20622.30 | 02-OCT-00:01 | 12892.99 | 23-OCT-00:12 | 6448.98 | 23-OCT-00:01 | 0.00 | 01-OCT-00:03 |
November | 0.704584E+10 | 0.189165E+10 | 314.56 | 0.550738E+10 | 0.153845E+10 | 0.00 | 1.00 | 01-NOV-17:10 | 0.00 | 01-NOV-00:05 | 25749.83 | 03-NOV-17:10 | 19439.78 | 06-NOV-00:01 | 10185.07 | 03-NOV-17:10 | 6182.22 | 01-NOV-17:10 | 0.00 | 01-NOV-00:05 |
December | 0.434908E+10 | 0.116512E+10 | 216.87 | 0.331036E+10 | 0.103872E+10 | 0.00 | 1.00 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 | 25733.02 | 11-DEC-00:01 | 17731.85 | 11-DEC-00:01 | 8167.62 | 11-DEC-00:03 | 5952.74 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.138328E+12 | 0.378976E+11 | 4646.19 | 0.101622E+12 | 0.367059E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.218892E+10 | 0.584524E+09 | 149.65 | 0.166601E+10 | 0.522908E+09 | 0.00 | 1.00 | 0.00 | 24447.54 | 17731.85 | 5792.76 | 5723.33 | 0.00 | |||||||
Maximum of Months | 0.203129E+11 | 0.560344E+10 | 557.92 | 0.144344E+11 | 0.587849E+10 | 0.00 | 1.00 | 0.00 | 29456.64 | 20622.30 | 15528.36 | 6602.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.794694E+09 | 0.229148E+09 | 25.00 | 0.529839E+09 | 0.264854E+09 | 0.00 | 0.54 | 01-JAN-14:25 | 0.00 | 01-JAN-00:10 | 33763.76 | 01-JAN-14:25 | 27326.98 | 01-JAN-14:25 | 6881.29 | 01-JAN-13:10 | 9959.74 | 01-JAN-14:25 | 0.00 | 01-JAN-00:10 |
February | 0.272664E+10 | 0.778776E+09 | 58.75 | 0.185236E+10 | 0.874276E+09 | 0.00 | 0.51 | 26-FEB-14:35 | 0.00 | 01-FEB-00:10 | 32470.13 | 26-FEB-14:35 | 24975.02 | 26-FEB-14:35 | 7495.11 | 26-FEB-14:35 | 9704.38 | 26-FEB-14:35 | 0.00 | 01-FEB-00:10 |
March | 0.450188E+10 | 0.129079E+10 | 97.83 | 0.302868E+10 | 0.147320E+10 | 0.00 | 0.60 | 26-MAR-13:25 | 0.00 | 01-MAR-00:05 | 38471.33 | 26-MAR-13:25 | 29280.79 | 26-MAR-13:25 | 9859.56 | 07-MAR-11:30 | 11827.05 | 26-MAR-13:25 | 0.00 | 01-MAR-00:05 |
April | 0.154597E+11 | 0.449060E+10 | 228.22 | 0.113572E+11 | 0.410255E+10 | 0.00 | 1.00 | 23-APR-11:03 | 0.00 | 01-APR-00:05 | 81576.47 | 28-APR-17:42 | 58480.97 | 27-APR-17:08 | 29238.28 | 28-APR-17:42 | 20881.66 | 28-APR-17:08 | 0.00 | 01-APR-00:05 |
May | 0.413874E+11 | 0.121894E+11 | 417.13 | 0.282729E+11 | 0.131146E+11 | 0.00 | 1.00 | 02-MAY-17:06 | 0.00 | 01-MAY-00:01 | 84818.66 | 28-MAY-09:23 | 61031.69 | 04-MAY-17:06 | 39733.46 | 28-MAY-09:23 | 21671.05 | 28-MAY-09:23 | 0.00 | 01-MAY-00:01 |
June | 0.476306E+11 | 0.140951E+11 | 458.07 | 0.329536E+11 | 0.146770E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 85333.91 | 05-JUN-00:08 | 61774.81 | 11-JUN-15:02 | 40097.22 | 05-JUN-00:08 | 21468.28 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.529875E+11 | 0.155235E+11 | 497.60 | 0.340336E+11 | 0.189540E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 88822.93 | 31-JUL-00:01 | 55893.06 | 12-JUL-17:08 | 46169.28 | 31-JUL-00:01 | 21890.11 | 02-JUL-11:03 | 0.00 | 01-JUL-00:05 |
August | 0.518062E+11 | 0.151189E+11 | 479.23 | 0.336499E+11 | 0.181563E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 86455.75 | 14-AUG-00:07 | 58973.16 | 30-AUG-17:06 | 42101.47 | 14-AUG-00:07 | 22038.15 | 20-AUG-13:53 | 0.00 | 01-AUG-00:10 |
September | 0.406254E+11 | 0.116825E+11 | 400.20 | 0.256222E+11 | 0.150032E+11 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:05 | 86341.97 | 04-SEP-10:13 | 58283.89 | 22-SEP-17:06 | 41925.55 | 17-SEP-09:53 | 22543.11 | 10-SEP-13:43 | 0.00 | 01-SEP-00:03 |
October | 0.318845E+11 | 0.919917E+10 | 329.47 | 0.210091E+11 | 0.108754E+11 | 0.00 | 1.00 | 01-OCT-12:23 | 0.00 | 01-OCT-00:03 | 87104.89 | 08-OCT-09:53 | 60873.98 | 01-OCT-12:23 | 43839.53 | 08-OCT-09:53 | 22176.00 | 08-OCT-13:53 | 0.00 | 01-OCT-00:03 |
November | 0.733334E+10 | 0.210264E+10 | 133.40 | 0.495349E+10 | 0.237985E+10 | 0.00 | 0.86 | 02-NOV-17:10 | 0.00 | 01-NOV-00:05 | 65936.32 | 02-NOV-17:10 | 42341.12 | 02-NOV-17:10 | 23595.20 | 02-NOV-17:10 | 17586.97 | 02-NOV-17:10 | 0.00 | 01-NOV-00:05 |
December | 0.403651E+10 | 0.115650E+10 | 74.83 | 0.264716E+10 | 0.138935E+10 | 0.00 | 0.50 | 10-DEC-13:50 | 0.00 | 01-DEC-00:10 | 32726.45 | 10-DEC-13:50 | 22957.55 | 10-DEC-13:50 | 11039.66 | 15-DEC-12:00 | 9789.37 | 10-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.301174E+12 | 0.878570E+11 | 3199.75 | 0.199910E+12 | 0.101265E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.794694E+09 | 0.229148E+09 | 25.00 | 0.529839E+09 | 0.264854E+09 | 0.00 | 0.50 | 0.00 | 32470.13 | 22957.55 | 6881.29 | 9704.38 | 0.00 | |||||||
Maximum of Months | 0.529875E+11 | 0.155235E+11 | 497.60 | 0.340336E+11 | 0.189540E+11 | 0.00 | 1.00 | 0.00 | 88822.93 | 61774.81 | 46169.28 | 22543.11 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.85 | 121.54 | 2.00 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.40 | 104.37 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.81 | 94.37 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 162.25 | 64.13 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 170.76 | 19.77 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 195.88 | 17.12 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 175.79 | 12.20 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 179.43 | 17.19 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 153.68 | 25.56 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 149.88 | 44.39 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 101.51 | 91.80 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 91.18 | 110.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 141.91 | 60.02 | 2.00 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 91.18 | 12.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 195.88 | 121.54 | 2.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.85 | 121.54 | 2.00 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.40 | 104.37 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.81 | 94.37 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 162.25 | 64.13 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 170.76 | 19.77 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 195.88 | 17.12 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 175.79 | 12.20 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 179.43 | 17.19 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 153.68 | 25.56 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 149.88 | 44.39 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 101.51 | 91.80 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 91.18 | 110.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 141.91 | 60.02 | 2.00 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 91.18 | 12.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 195.88 | 121.54 | 2.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.47 | 77.04 | 2.17 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 14.09 | 65.21 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.31 | 20.48 | 57.76 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 32.07 | 38.65 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 58.35 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 69.90 | 9.36 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 66.76 | 6.82 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 61.49 | 9.54 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 47.00 | 14.85 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 36.79 | 26.69 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.64 | 56.60 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.59 | 69.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 37.03 | 36.77 | 2.17 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.47 | 6.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 69.90 | 77.04 | 2.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.47 | 77.04 | 2.17 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 14.09 | 65.21 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.30 | 20.48 | 57.76 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 32.07 | 38.65 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 58.35 | 10.81 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 69.90 | 9.36 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 66.76 | 6.82 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 61.49 | 9.54 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 47.00 | 14.85 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 36.79 | 26.69 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.64 | 56.60 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.59 | 69.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 37.03 | 36.77 | 2.17 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.47 | 6.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 69.90 | 77.04 | 2.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.94 | 66.16 | 62.67 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.81 | 61.34 | 106.00 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.88 | 59.30 | 21.83 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.82 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.01 | 35.03 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.06 | 31.00 | 10.17 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.70 | 34.46 | 17.83 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.21 | 40.22 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 24.67 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.36 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.49 | 40.50 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.70 | 49.57 | 335.67 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.00 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.01 | 66.16 | 106.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.254043E+09 | 0.325544E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.269505E+09 | 0.252484E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.307501E+09 | 0.252748E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.420541E+09 | 0.166229E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.457375E+09 | 52941532.00 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.507722E+09 | 44375228.28 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.470839E+09 | 32687095.21 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.480583E+09 | 46049386.69 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.398331E+09 | 66257216.09 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.401445E+09 | 0.118893E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.263115E+09 | 0.237952E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.244213E+09 | 0.296629E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.447521E+10 | 0.189279E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.244213E+09 | 32687095.21 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.507722E+09 | 0.325544E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.254043E+09 | 0.325544E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.269505E+09 | 0.252484E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.307501E+09 | 0.252748E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.420541E+09 | 0.166229E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.457375E+09 | 52941532.00 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.507722E+09 | 44375228.28 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.470839E+09 | 32687095.21 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.480583E+09 | 46049386.69 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.398331E+09 | 66257216.09 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.401445E+09 | 0.118893E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.263115E+09 | 0.237952E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.244213E+09 | 0.296629E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.447521E+10 | 0.189279E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.244213E+09 | 32687095.21 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.507722E+09 | 0.325544E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33861408.58 | 0.00 | 33861408.58 | 28034758.27 | 0.206343E+09 |
February | 36082321.66 | 0.00 | 36082321.66 | 34089845.48 | 0.157758E+09 |
March | 46354484.78 | 3575.08 | 46350909.71 | 54856293.13 | 0.154702E+09 |
April | 53198617.36 | 441072.73 | 52757544.64 | 83138336.11 | 0.100170E+09 |
May | 62679542.69 | 2951194.12 | 59728348.57 | 0.156282E+09 | 28967395.05 |
June | 69097649.92 | 5642484.26 | 63455165.66 | 0.181178E+09 | 24262016.22 |
July | 68960463.16 | 3179366.13 | 65781097.03 | 0.178803E+09 | 18274457.99 |
August | 61645724.73 | 829306.48 | 60816418.25 | 0.164696E+09 | 25562180.24 |
September | 51209845.83 | 15623.79 | 51194222.04 | 0.121831E+09 | 38499116.78 |
October | 45957508.77 | 0.00 | 45957508.77 | 98531834.57 | 71474006.78 |
November | 33763655.28 | 0.00 | 33763655.28 | 37944437.16 | 0.146701E+09 |
December | 31478029.14 | 0.00 | 31478029.14 | 28374574.19 | 0.186854E+09 |
Annual Sum or Average | 0.594289E+09 | 13062622.59 | 0.581227E+09 | 0.116776E+10 | 0.115957E+10 |
Minimum of Months | 31478029.14 | 0.00 | 31478029.14 | 28034758.27 | 18274457.99 |
Maximum of Months | 69097649.92 | 5642484.26 | 65781097.03 | 0.181178E+09 | 0.206343E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33860475.71 | 0.00 | 33860475.71 | 28033819.01 | 0.206342E+09 |
February | 36081361.95 | 0.00 | 36081361.95 | 34088917.62 | 0.157757E+09 |
March | 46353172.74 | 3574.91 | 46349597.83 | 54854683.88 | 0.154702E+09 |
April | 53197174.13 | 441052.05 | 52756122.07 | 83136346.67 | 0.100169E+09 |
May | 62677642.39 | 2951055.80 | 59726586.59 | 0.156279E+09 | 28966681.09 |
June | 69095517.18 | 5642219.79 | 63453297.39 | 0.181174E+09 | 24261401.31 |
July | 68958301.19 | 3179217.11 | 65779084.08 | 0.178799E+09 | 18273790.01 |
August | 61643840.91 | 829267.61 | 60814573.31 | 0.164693E+09 | 25561487.33 |
September | 51208284.33 | 15623.05 | 51192661.28 | 0.121828E+09 | 38498348.65 |
October | 45956183.62 | 0.00 | 45956183.62 | 98529688.10 | 71473193.68 |
November | 33762741.30 | 0.00 | 33762741.30 | 37943450.67 | 0.146700E+09 |
December | 31477154.35 | 0.00 | 31477154.35 | 28373776.24 | 0.186854E+09 |
Annual Sum or Average | 0.594272E+09 | 13062010.32 | 0.581210E+09 | 0.116773E+10 | 0.115956E+10 |
Minimum of Months | 31477154.35 | 0.00 | 31477154.35 | 28033819.01 | 18273790.01 |
Maximum of Months | 69095517.18 | 5642219.79 | 65779084.08 | 0.181174E+09 | 0.206342E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256980E+09 | 0.177206E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292256E+09 | 0.148392E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355899E+09 | 0.158827E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443338E+09 | 0.146135E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459810E+09 | 95943922.51 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500270E+09 | 90808583.52 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474227E+09 | 83021641.56 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446482E+09 | 92312241.25 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360837E+09 | 0.104240E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355622E+09 | 0.126972E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261048E+09 | 0.166816E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 0.172719E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443702E+10 | 0.156339E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230247E+09 | 83021641.56 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500270E+09 | 0.177206E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 201.05 | 387.59 | 143.97 | 64.19 | 79.78 | 0.00 | 0.00 |
February | 243.93 | 332.09 | 163.99 | 67.84 | 96.15 | 0.00 | 0.00 |
March | 267.00 | 300.67 | 166.83 | 58.40 | 108.44 | 0.00 | 0.00 |
April | 386.30 | 203.21 | 204.75 | 75.24 | 129.51 | 0.00 | 0.00 |
May | 457.66 | 60.60 | 183.59 | 46.70 | 136.89 | 0.00 | 0.00 |
June | 530.96 | 52.36 | 205.36 | 57.75 | 147.61 | 0.00 | 0.00 |
July | 484.74 | 37.69 | 190.23 | 40.91 | 149.32 | 0.00 | 0.00 |
August | 481.67 | 53.31 | 186.08 | 43.27 | 142.82 | 0.00 | 0.00 |
September | 401.12 | 80.60 | 168.54 | 44.20 | 124.34 | 0.00 | 0.00 |
October | 372.29 | 141.10 | 166.14 | 56.77 | 109.37 | 0.00 | 0.00 |
November | 227.65 | 292.15 | 139.58 | 57.17 | 82.42 | 0.00 | 0.00 |
December | 196.85 | 354.33 | 132.84 | 58.31 | 74.54 | 0.00 | 0.00 |
Annual Sum or Average | 354.82 | 190.53 | 170.96 | 55.77 | 115.19 | 0.00 | 0.00 |
Minimum of Months | 196.85 | 37.69 | 132.84 | 40.91 | 74.54 | 0.00 | 0.00 |
Maximum of Months | 530.96 | 387.59 | 205.36 | 75.24 | 149.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 959.45 | 661.61 | 746.97 | 501.01 | 245.96 | 0.00 | 0.00 |
February | 1208.07 | 613.39 | 942.42 | 646.81 | 295.61 | 0.00 | 0.00 |
March | 1328.76 | 592.99 | 1033.96 | 643.91 | 390.05 | 0.00 | 0.00 |
April | 1710.41 | 563.79 | 1312.00 | 852.36 | 459.64 | 0.00 | 0.00 |
May | 1716.73 | 358.20 | 1258.03 | 717.82 | 540.22 | 0.00 | 0.00 |
June | 1930.05 | 350.34 | 1388.56 | 801.00 | 587.56 | 0.00 | 0.00 |
July | 1770.56 | 309.95 | 1293.48 | 664.75 | 628.73 | 0.00 | 0.00 |
August | 1666.97 | 344.65 | 1208.54 | 605.18 | 603.36 | 0.00 | 0.00 |
September | 1392.11 | 402.15 | 1031.38 | 513.46 | 517.92 | 0.00 | 0.00 |
October | 1327.74 | 474.05 | 980.67 | 582.34 | 398.33 | 0.00 | 0.00 |
November | 1007.12 | 643.58 | 797.05 | 544.73 | 252.32 | 0.00 | 0.00 |
December | 859.64 | 644.86 | 678.10 | 448.59 | 229.52 | 0.00 | 0.00 |
Annual Sum or Average | 1406.97 | 495.75 | 1056.03 | 626.11 | 429.92 | 0.00 | 0.00 |
Minimum of Months | 859.64 | 309.95 | 678.10 | 448.59 | 229.52 | 0.00 | 0.00 |
Maximum of Months | 1930.05 | 661.61 | 1388.56 | 852.36 | 628.73 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538493E+09 | 0.103811E+10 | 0.385606E+09 | 0.171913E+09 | 0.213693E+09 | 0.00 | 0.00 |
February | 0.590110E+09 | 0.803404E+09 | 0.396729E+09 | 0.164117E+09 | 0.232612E+09 | 0.00 | 0.00 |
March | 0.715135E+09 | 0.805322E+09 | 0.446847E+09 | 0.156413E+09 | 0.290434E+09 | 0.00 | 0.00 |
April | 0.100129E+10 | 0.526733E+09 | 0.530708E+09 | 0.195010E+09 | 0.335699E+09 | 0.00 | 0.00 |
May | 0.122579E+10 | 0.162300E+09 | 0.491720E+09 | 0.125085E+09 | 0.366635E+09 | 0.00 | 0.00 |
June | 0.137625E+10 | 0.135724E+09 | 0.532290E+09 | 0.149678E+09 | 0.382613E+09 | 0.00 | 0.00 |
July | 0.129832E+10 | 0.100959E+09 | 0.509508E+09 | 0.109579E+09 | 0.399929E+09 | 0.00 | 0.00 |
August | 0.129011E+10 | 0.142779E+09 | 0.498403E+09 | 0.115883E+09 | 0.382520E+09 | 0.00 | 0.00 |
September | 0.103972E+10 | 0.208907E+09 | 0.436859E+09 | 0.114573E+09 | 0.322286E+09 | 0.00 | 0.00 |
October | 0.997155E+09 | 0.377935E+09 | 0.444977E+09 | 0.152049E+09 | 0.292928E+09 | 0.00 | 0.00 |
November | 0.590078E+09 | 0.757265E+09 | 0.361801E+09 | 0.148177E+09 | 0.213624E+09 | 0.00 | 0.00 |
December | 0.527254E+09 | 0.949047E+09 | 0.355807E+09 | 0.156168E+09 | 0.199639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111897E+11 | 0.600849E+10 | 0.539126E+10 | 0.175864E+10 | 0.363261E+10 | 0.00 | 0.00 |
Minimum of Months | 0.527254E+09 | 0.100959E+09 | 0.355807E+09 | 0.109579E+09 | 0.199639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137625E+10 | 0.103811E+10 | 0.532290E+09 | 0.195010E+09 | 0.399929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256978E+10 | 0.177206E+10 | 0.200069E+10 | 0.134192E+10 | 0.658776E+09 | 0.00 | 0.00 |
February | 0.292255E+10 | 0.148392E+10 | 0.227991E+10 | 0.156476E+10 | 0.715150E+09 | 0.00 | 0.00 |
March | 0.355896E+10 | 0.158827E+10 | 0.276936E+10 | 0.172466E+10 | 0.104470E+10 | 0.00 | 0.00 |
April | 0.443338E+10 | 0.146135E+10 | 0.340070E+10 | 0.220931E+10 | 0.119139E+10 | 0.00 | 0.00 |
May | 0.459810E+10 | 0.959415E+09 | 0.336952E+10 | 0.192260E+10 | 0.144692E+10 | 0.00 | 0.00 |
June | 0.500270E+10 | 0.908085E+09 | 0.359915E+10 | 0.207620E+10 | 0.152295E+10 | 0.00 | 0.00 |
July | 0.474227E+10 | 0.830182E+09 | 0.346446E+10 | 0.178046E+10 | 0.168400E+10 | 0.00 | 0.00 |
August | 0.446481E+10 | 0.923098E+09 | 0.323695E+10 | 0.162092E+10 | 0.161603E+10 | 0.00 | 0.00 |
September | 0.360836E+10 | 0.104238E+10 | 0.267334E+10 | 0.133088E+10 | 0.134246E+10 | 0.00 | 0.00 |
October | 0.355622E+10 | 0.126971E+10 | 0.262662E+10 | 0.155974E+10 | 0.106687E+10 | 0.00 | 0.00 |
November | 0.261047E+10 | 0.166816E+10 | 0.206596E+10 | 0.141195E+10 | 0.654011E+09 | 0.00 | 0.00 |
December | 0.230245E+10 | 0.172719E+10 | 0.181624E+10 | 0.120150E+10 | 0.614734E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443701E+11 | 0.156338E+11 | 0.333029E+11 | 0.197449E+11 | 0.135580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230245E+10 | 0.830182E+09 | 0.181624E+10 | 0.120150E+10 | 0.614734E+09 | 0.00 | 0.00 |
Maximum of Months | 0.500270E+10 | 0.177206E+10 | 0.359915E+10 | 0.220931E+10 | 0.168400E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.828607E+09 | -688253994.5 | 0.00 | 0.00 | 744.00 | 0.00 | -140353331.0 | 58.99 | 0.00 | 0.00 |
February | 0.752413E+09 | -627185772.3 | 0.00 | 0.00 | 672.00 | 0.00 | -125227356.4 | 58.99 | 0.00 | 0.00 |
March | 0.841387E+09 | -705025646.3 | 0.00 | 0.00 | 744.00 | 0.00 | -136361314.6 | 58.99 | 0.00 | 0.00 |
April | 0.742881E+09 | -614745309.3 | 0.00 | 0.00 | 720.00 | 0.00 | -128135382.1 | 58.99 | 0.00 | 0.00 |
May | 0.725486E+09 | -594415000.2 | 0.00 | 0.00 | 744.00 | 0.00 | -131071108.6 | 58.99 | 0.00 | 0.00 |
June | 0.682544E+09 | -555359314.2 | 0.00 | 0.00 | 720.00 | 0.00 | -127184573.2 | 58.99 | 0.00 | 0.00 |
July | 0.649695E+09 | -519496639.0 | 0.00 | 0.00 | 744.00 | 0.00 | -130197935.1 | 58.99 | 0.00 | 0.00 |
August | 0.695412E+09 | -564070139.7 | 0.00 | 0.00 | 744.00 | 0.00 | -131342063.7 | 58.99 | 0.00 | 0.00 |
September | 0.677975E+09 | -551534702.3 | 0.00 | 0.00 | 720.00 | 0.00 | -126440067.2 | 58.99 | 0.00 | 0.00 |
October | 0.724403E+09 | -593491926.5 | 0.00 | 0.00 | 744.00 | 0.00 | -130910595.1 | 58.99 | 0.00 | 0.00 |
November | 0.740269E+09 | -611316719.5 | 0.00 | 0.00 | 720.00 | 0.00 | -128951847.4 | 58.99 | 0.00 | 0.00 |
December | 0.808536E+09 | -671009477.3 | 0.00 | 0.00 | 744.00 | 0.00 | -137526526.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.886961E+10 | -.729590E+10 | 8760.00 | -.157370E+10 | 58.99 | |||||
Minimum of Months | 0.649695E+09 | -705025646.3 | 0.00 | 0.00 | 672.00 | 0.00 | -140353331.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.841387E+09 | -519496639.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125227356.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | ||||||||||
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.629050E+09 | 28191.09 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335599E+09 | 28191.09 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251400E+09 | 28191.09 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1478015.02 | 1748.59 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20841930.63 | 5154.88 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356117E+09 | 28191.09 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159449E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.629050E+09 | 28191.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143406E+09 | 46428.27 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234488E+09 | 63571.97 | 05-FEB-07:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7233791.61 | 14665.32 | 12-MAR-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51318999.85 | 30911.44 | 21-DEC-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436446E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234488E+09 | 63571.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.218892E+10 | 0.166601E+10 | 25336.20 | 02-JAN-00:01 | 18187.36 | 0.00 |
February | 0.00 | 0.00 | 0.345619E+10 | 0.261573E+10 | 24447.54 | 27-FEB-00:02 | 19195.73 | 0.00 |
March | 0.00 | 0.00 | 0.506319E+10 | 0.394290E+10 | 25624.15 | 27-MAR-00:01 | 18007.93 | 0.00 |
April | 0.00 | 0.00 | 0.957518E+10 | 0.760842E+10 | 26559.02 | 24-APR-00:01 | 17954.20 | 0.00 |
May | 0.00 | 0.00 | 0.172369E+11 | 0.126705E+11 | 28628.14 | 22-MAY-00:01 | 15089.11 | 0.00 |
June | 0.00 | 0.00 | 0.183430E+11 | 0.135027E+11 | 28066.01 | 05-JUN-00:01 | 16387.91 | 0.00 |
July | 0.00 | 0.00 | 0.189850E+11 | 0.134014E+11 | 29178.04 | 31-JUL-00:01 | 15105.64 | 0.00 |
August | 0.00 | 0.00 | 0.203129E+11 | 0.144344E+11 | 28798.23 | 14-AUG-00:01 | 15378.00 | 0.00 |
September | 0.00 | 0.00 | 0.171599E+11 | 0.121101E+11 | 29456.64 | 05-SEP-00:01 | 14386.04 | 0.00 |
October | 0.00 | 0.00 | 0.146115E+11 | 0.108517E+11 | 28520.61 | 23-OCT-00:01 | 15907.85 | 0.00 |
November | 0.00 | 0.00 | 0.704584E+10 | 0.550738E+10 | 25749.83 | 03-NOV-17:10 | 15564.75 | 0.00 |
December | 0.00 | 0.00 | 0.434908E+10 | 0.331036E+10 | 25733.02 | 11-DEC-00:01 | 17731.85 | 0.00 |
Annual Sum or Average | 0.138328E+12 | 0.101622E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.218892E+10 | 0.166601E+10 | 24447.54 | 14386.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203129E+11 | 0.144344E+11 | 29456.64 | 19195.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.794694E+09 | 0.529839E+09 | 33763.76 | 01-JAN-14:25 | 27326.98 | 0.00 |
February | 0.00 | 0.00 | 0.272664E+10 | 0.185236E+10 | 32470.13 | 26-FEB-14:35 | 24975.02 | 0.00 |
March | 0.00 | 0.00 | 0.450188E+10 | 0.302868E+10 | 38471.33 | 26-MAR-13:25 | 29280.79 | 0.00 |
April | 0.00 | 0.00 | 0.154597E+11 | 0.113572E+11 | 81576.47 | 28-APR-17:42 | 52338.19 | 0.00 |
May | 0.00 | 0.00 | 0.413874E+11 | 0.282729E+11 | 84818.66 | 28-MAY-09:23 | 45085.19 | 0.00 |
June | 0.00 | 0.00 | 0.476306E+11 | 0.329536E+11 | 85333.91 | 05-JUN-00:08 | 45236.69 | 0.00 |
July | 0.00 | 0.00 | 0.529875E+11 | 0.340336E+11 | 88822.93 | 31-JUL-00:01 | 42653.65 | 0.00 |
August | 0.00 | 0.00 | 0.518062E+11 | 0.336499E+11 | 86455.75 | 14-AUG-00:07 | 44354.27 | 0.00 |
September | 0.00 | 0.00 | 0.406254E+11 | 0.256222E+11 | 86341.97 | 04-SEP-10:13 | 44701.00 | 0.00 |
October | 0.00 | 0.00 | 0.318845E+11 | 0.210091E+11 | 87104.89 | 08-OCT-09:53 | 43265.36 | 0.00 |
November | 0.00 | 0.00 | 0.733334E+10 | 0.495349E+10 | 65936.32 | 02-NOV-17:10 | 42341.12 | 0.00 |
December | 0.00 | 0.00 | 0.403651E+10 | 0.264716E+10 | 32726.45 | 10-DEC-13:50 | 22957.55 | 0.00 |
Annual Sum or Average | 0.301174E+12 | 0.199910E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.794694E+09 | 0.529839E+09 | 32470.13 | 22957.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.529875E+11 | 0.340336E+11 | 88822.93 | 52338.19 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130447E+10 | 0.37 | 1299.23 | 02-JAN-08:40 | 0.93 |
February | 0.120924E+10 | 0.39 | 1299.23 | 01-FEB-08:20 | 0.92 |
March | 0.143419E+10 | 0.43 | 1299.23 | 01-MAR-10:20 | 0.93 |
April | 0.142237E+10 | 0.54 | 1299.23 | 17-APR-08:50 | 0.93 |
May | 0.163924E+10 | 0.69 | 1299.23 | 01-MAY-07:30 | 0.92 |
June | 0.166136E+10 | 0.73 | 1299.23 | 01-JUN-06:20 | 0.93 |
July | 0.162891E+10 | 0.68 | 1299.23 | 01-JUL-06:05 | 0.93 |
August | 0.175490E+10 | 0.73 | 1299.23 | 01-AUG-06:30 | 0.92 |
September | 0.159156E+10 | 0.70 | 1299.23 | 01-SEP-06:50 | 0.92 |
October | 0.153829E+10 | 0.64 | 1299.23 | 02-OCT-06:30 | 0.93 |
November | 0.131076E+10 | 0.45 | 1299.23 | 01-NOV-07:20 | 0.92 |
December | 0.132933E+10 | 0.41 | 1299.23 | 07-DEC-17:00 | 0.93 |
Annual Sum or Average | 0.178246E+11 | 0.56 | |||
Minimum of Months | 0.120924E+10 | 0.37 | 1299.23 | 0.92 | |
Maximum of Months | 0.175490E+10 | 0.73 | 1299.23 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307283E+10 | 0.34 | 3094.40 | 17-JAN-15:40 | 0.89 |
February | 0.283302E+10 | 0.35 | 3094.40 | 23-FEB-11:20 | 0.89 |
March | 0.331771E+10 | 0.36 | 3094.40 | 16-MAR-14:50 | 0.89 |
April | 0.313354E+10 | 0.38 | 3094.40 | 04-APR-11:10 | 0.89 |
May | 0.359351E+10 | 0.52 | 3094.40 | 20-MAY-13:25 | 0.88 |
June | 0.369137E+10 | 0.59 | 3094.40 | 12-JUN-08:65 | 0.88 |
July | 0.376989E+10 | 0.62 | 3094.40 | 05-JUL-13:00 | 0.89 |
August | 0.387880E+10 | 0.60 | 3094.40 | 05-AUG-07:40 | 0.88 |
September | 0.350896E+10 | 0.51 | 3094.40 | 08-SEP-08:40 | 0.88 |
October | 0.336612E+10 | 0.45 | 3094.40 | 02-OCT-08:40 | 0.89 |
November | 0.296405E+10 | 0.34 | 3094.40 | 01-NOV-14:20 | 0.88 |
December | 0.306854E+10 | 0.33 | 3094.40 | 02-DEC-16:40 | 0.89 |
Annual Sum or Average | 0.401983E+11 | 0.45 | |||
Minimum of Months | 0.283302E+10 | 0.33 | 3094.40 | 0.88 | |
Maximum of Months | 0.387880E+10 | 0.62 | 3094.40 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.76 | 3.10 |
February | 0.82 | 3.25 |
March | 1.06 | 3.22 |
April | 0.69 | 3.80 |
May | 0.25 | 0.00 |
June | 0.16 | 0.00 |
July | 0.20 | 0.00 |
August | 0.24 | 0.00 |
September | 0.08 | 0.00 |
October | 0.08 | 0.00 |
November | 0.53 | 4.38 |
December | 1.36 | 2.91 |
Annual Sum or Average | 6.23 | 2.78 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.36 | 4.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 3.02 | 0.00 |
May | 11.03 | 0.00 |
June | 14.24 | 0.00 |
July | 15.70 | 0.00 |
August | 9.94 | 0.00 |
September | 7.20 | 0.00 |
October | 4.73 | 0.00 |
November | 0.14 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 65.99 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 15.70 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188899E+10 | 0.917886E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213167E+10 | 0.489607E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.279045E+10 | 0.370188E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.402576E+10 | 2282467.62 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.640524E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.678431E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.688995E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.735834E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.623060E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.552003E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.320241E+10 | 31814977.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.249445E+10 | 0.524133E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.557222E+11 | 0.233591E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.188899E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.735834E+10 | 0.917886E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.330197E+10 | 0.219206E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.361179E+10 | 0.350901E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.460850E+10 | 11077290.30 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.762413E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157830E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.177865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.192934E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189977E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.151915E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125653E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.506669E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.422504E+10 | 78839496.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128055E+12 | 0.660024E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.330197E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192934E+11 | 0.350901E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130447E+10 | 0.218892E+10 | 0.629050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120924E+10 | 0.345619E+10 | 0.335599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143419E+10 | 0.506319E+10 | 0.251400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142237E+10 | 0.957518E+10 | 1478015.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163924E+10 | 0.172369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166136E+10 | 0.183430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162891E+10 | 0.189850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175490E+10 | 0.203129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159156E+10 | 0.171599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153829E+10 | 0.146115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131076E+10 | 0.704584E+10 | 20841930.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132933E+10 | 0.434908E+10 | 0.356117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178246E+11 | 0.138328E+12 | 0.159449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120924E+10 | 0.218892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175490E+10 | 0.203129E+11 | 0.629050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307283E+10 | 0.794694E+09 | 0.143406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283302E+10 | 0.272664E+10 | 0.234488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331771E+10 | 0.450188E+10 | 7233791.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313354E+10 | 0.154597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359351E+10 | 0.413874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.369137E+10 | 0.476306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.376989E+10 | 0.529875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387880E+10 | 0.518062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350896E+10 | 0.406254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336612E+10 | 0.318845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296405E+10 | 0.733334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306854E+10 | 0.403651E+10 | 51318999.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401983E+11 | 0.301174E+12 | 0.436446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283302E+10 | 0.794694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387880E+10 | 0.529875E+11 | 0.234488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.130447E+10 | 0.00 | 0.00 | 0.00 | 0.584524E+09 | 0.00 | 0.917886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120924E+10 | 0.00 | 0.00 | 0.00 | 0.922431E+09 | 0.00 | 0.489607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143419E+10 | 0.00 | 0.00 | 0.00 | 0.135625E+10 | 0.00 | 0.370188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142237E+10 | 0.00 | 0.00 | 0.00 | 0.260339E+10 | 0.00 | 2282467.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163924E+10 | 0.00 | 0.00 | 0.00 | 0.476600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166136E+10 | 0.00 | 0.00 | 0.00 | 0.512295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162891E+10 | 0.00 | 0.00 | 0.00 | 0.526104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175490E+10 | 0.00 | 0.00 | 0.00 | 0.560344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159156E+10 | 0.00 | 0.00 | 0.00 | 0.463904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153829E+10 | 0.00 | 0.00 | 0.00 | 0.398174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131076E+10 | 0.00 | 0.00 | 0.00 | 0.189165E+10 | 0.00 | 31814977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132933E+10 | 0.00 | 0.00 | 0.00 | 0.116512E+10 | 0.00 | 0.524133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178246E+11 | 0.00 | 0.00 | 0.00 | 0.378976E+11 | 0.00 | 0.233591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.120924E+10 | 0.00 | 0.00 | 0.00 | 0.584524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175490E+10 | 0.00 | 0.00 | 0.00 | 0.560344E+10 | 0.00 | 0.917886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.307283E+10 | 0.00 | 0.00 | 0.00 | 0.229148E+09 | 0.00 | 0.219206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283302E+10 | 0.00 | 0.00 | 0.00 | 0.778776E+09 | 0.00 | 0.350901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331771E+10 | 0.00 | 0.00 | 0.00 | 0.129079E+10 | 0.00 | 11077290.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313354E+10 | 0.00 | 0.00 | 0.00 | 0.449060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359351E+10 | 0.00 | 0.00 | 0.00 | 0.121894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.369137E+10 | 0.00 | 0.00 | 0.00 | 0.140951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.376989E+10 | 0.00 | 0.00 | 0.00 | 0.155235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387880E+10 | 0.00 | 0.00 | 0.00 | 0.151189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350896E+10 | 0.00 | 0.00 | 0.00 | 0.116825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336612E+10 | 0.00 | 0.00 | 0.00 | 0.919917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296405E+10 | 0.00 | 0.00 | 0.00 | 0.210264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306854E+10 | 0.00 | 0.00 | 0.00 | 0.115650E+10 | 0.00 | 78839496.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401983E+11 | 0.00 | 0.00 | 0.00 | 0.878570E+11 | 0.00 | 0.660024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.283302E+10 | 0.00 | 0.00 | 0.00 | 0.229148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387880E+10 | 0.00 | 0.00 | 0.00 | 0.155235E+11 | 0.00 | 0.350901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.480716E+09 | 0.164483E+09 | 0.00 | 1154238.82 | 0.00 | 0.220097E+09 | 0.305356E+09 | 0.00 | 0.14 |
February | 0.270698E+09 | 0.288734E+09 | 0.00 | 876924.54 | 846236.96 | 0.109472E+09 | 0.219981E+09 | 0.00 | 0.14 |
March | 0.302849E+09 | 0.453597E+09 | 0.00 | 1754999.22 | 1025519.50 | 81852210.26 | 0.261197E+09 | 0.00 | 0.15 |
April | 32252622.83 | 0.987639E+09 | 0.00 | 1700387.32 | 3069317.99 | 2239990.90 | 94293524.75 | 0.00 | 0.16 |
May | 0.00 | 0.283769E+10 | 0.00 | 194439.25 | 0.00 | 0.00 | 7400.57 | 0.00 | 0.17 |
June | 0.00 | 0.327455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.370916E+10 | 0.00 | 7031.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.365120E+10 | 0.00 | 10960.45 | 0.00 | 0.00 | 30333.84 | 0.00 | 0.18 |
September | 0.00 | 0.294157E+10 | 0.00 | 126513.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
October | 17791626.76 | 0.219334E+10 | 0.00 | 2773019.30 | 0.00 | 0.00 | 0.113054E+09 | 0.00 | 0.16 |
November | 82998191.36 | 0.707906E+09 | 0.00 | 2369730.62 | 130158.68 | 17262914.66 | 0.218455E+09 | 0.00 | 0.14 |
December | 0.389386E+09 | 0.474323E+09 | 127.58 | 1027668.46 | 2009339.67 | 0.145165E+09 | 0.210756E+09 | 20432.04 | 0.14 |
Annual Sum or Average | 0.157669E+10 | 0.216842E+11 | 127.58 | 11995913.68 | 7080572.81 | 0.576089E+09 | 0.142313E+10 | 20432.04 | 0.16 |
Minimum of Months | 0.00 | 0.164483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.480716E+09 | 0.370916E+10 | 127.58 | 2773019.30 | 3069317.99 | 0.220097E+09 | 0.305356E+09 | 20432.04 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316626E+10 | 46920620.52 | 0.00 | 176818.34 | 5278956.48 | 55033351.73 | 8980984.90 | 0.00 | 0.19 |
February | 0.225059E+10 | 0.292324E+09 | 0.00 | 284869.92 | 1966575.23 | 46013622.94 | 45121437.31 | 0.00 | 0.20 |
March | 0.252804E+10 | 0.582630E+09 | 0.00 | 501216.46 | 2420237.37 | 394022.31 | 0.112643E+09 | 0.00 | 0.21 |
April | 0.803084E+09 | 0.193404E+10 | 0.00 | 3303758.95 | 0.00 | 0.00 | 0.509964E+09 | 0.00 | 0.21 |
May | 4291286.06 | 0.746016E+10 | 0.00 | 269048.07 | 2708946.88 | 0.00 | 19940095.95 | 0.00 | 0.23 |
June | 10723177.27 | 0.983019E+10 | 0.00 | 179607.60 | 3604399.17 | 0.00 | 16620935.77 | 0.00 | 0.24 |
July | 0.00 | 0.113527E+11 | 0.00 | 47750.27 | 1901162.30 | 0.00 | 930633.37 | 0.00 | 0.24 |
August | 4464819.22 | 0.103445E+11 | 0.00 | 161721.79 | 0.00 | 0.00 | 14761155.98 | 0.00 | 0.25 |
September | 9989581.49 | 0.772894E+10 | 0.00 | 474907.13 | 0.00 | 0.00 | 68753714.82 | 0.00 | 0.23 |
October | 0.502391E+09 | 0.544022E+10 | 0.00 | 3099896.94 | 68656.55 | 0.00 | 0.251697E+09 | 0.00 | 0.22 |
November | 0.150259E+10 | 0.124955E+10 | 0.00 | 1374283.99 | 9569578.81 | 0.00 | 0.360654E+09 | 0.00 | 0.20 |
December | 0.250689E+10 | 0.633980E+09 | 0.00 | 417337.77 | 13548317.51 | 26447224.91 | 68004773.73 | 0.00 | 0.19 |
Annual Sum or Average | 0.132893E+11 | 0.568962E+11 | 0.00 | 10291217.21 | 41066830.29 | 0.127888E+09 | 0.147807E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 46920620.52 | 0.00 | 47750.27 | 0.00 | 0.00 | 930633.37 | 0.00 | 0.19 |
Maximum of Months | 0.316626E+10 | 0.113527E+11 | 0.00 | 3303758.95 | 13548317.51 | 55033351.73 | 0.509964E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |