Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1345.27 | 278.23 | 278.23 |
Net Site Energy | 1345.27 | 278.23 | 278.23 |
Total Source Energy | 4112.66 | 850.58 | 850.58 |
Net Source Energy | 4112.66 | 850.58 | 850.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 310.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 196.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1274.31 | 70.96 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 310.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 40.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 156.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 109.49 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 263.55 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 109.49 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 263.55 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1274.309 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1274.309 | 100.00 |
Total On-Site and Utility Electric Sources | 1274.309 | 100.00 |
Total Electricity End Uses | 1274.309 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 75.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 203.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 02-JAN-07:19 | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 3914.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50809.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31660.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13470.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 483.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 106536.25 | 3914.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 3914.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50809.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31660.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11165.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 483.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 76.92 | 0.00 | 0.00 | 0.00 |
Cooling | 981.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 622.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4035.74 | 76.92 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 |
Cooling | 203.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 834.67 | 15.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 |
Cooling | 203.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 834.67 | 15.91 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.39 |
ZONE2 FINE STORAGE DIRECT AIR | 5.10 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.07 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.07 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 44614.72 |
PSZ-OFFICE HEATING COIL | 33151.60 |
PSZ-FINE STORAGE HEATING COIL | 152035.61 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 44614.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
PSZ-FINE STORAGE | 5.10 | 5.10 | 5.10 | 5.10 | 5.10 | 5.10 | 1.00 | 1.00 | 5.10 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.39 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 5.10 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 1.39 | 29142.92 | 33151.60 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 5.10 | 5.10 | 5.10 | 5.10 | 124043.90 | 152035.61 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.39 | 0.695660 | 1.39 | 28416.41 | 29142.92 | 14571.46 | 29142.92 | 0.721553 | 0.721550 | 0.721550 | 0.721550 |
PSZ-FINE STORAGE COOLING COIL | 5.10 | 2.55 | 5.10 | 118237.20 | 124043.90 | 62021.95 | 124043.90 | 0.681331 | 0.681330 | 0.681330 | 0.681330 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.39 | 1586.26 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.10 | 9579.38 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 14086.87328 | 16904.24793 | 1.15943 | 1.39132 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 41.57133 | 1.07356E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5825.77421 | 6990.92905 | 0.16332 | 0.19599 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 66266.66292 | 79519.99550 | 4.25184 | 5.10221 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 41.44200 | 1.07356E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 10132.31767 | 12158.78120 | 0.23971 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80000 | 1.07356E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 37178.93612 | 44614.72334 | 0.89562 | 1.07475 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 22595.40 | 1.39132 | 1.39132 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 5709.93 | 0.19599 | 0.19599 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 97014.27 | 5.10221 | 5.10221 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 11685.90 | 0.35393 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39132 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.10221 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07475 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.07475 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 44614.72426 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 44614.72334 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39132 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39132 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39132 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39132 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39132 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.39132 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.10221 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.10221 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.10221 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.10221 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.10221 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.10221 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.39132 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.10221 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39132 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39132 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39132 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39132 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.39132 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39132 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69566 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.39132 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28416.40573 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29142.92000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14571.46000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29142.92000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72155 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72155 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72155 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72155 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29142.92000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33151.60342 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39132 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1586.25544 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 33151.60342 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.10221 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.10221 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.10221 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.10221 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.10221 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.10221 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.55111 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.10221 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 118237.19943 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 124043.90000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 62021.95000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 124043.90000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68133 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68133 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68133 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68133 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 124043.90000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 152035.61146 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.10221 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 9579.38036 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 152035.61146 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 28062.3 | 10.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 120078.4 | 12.21 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.1778506990E-002 | 2.5166881640E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 6.6893946843E-002 | 5.0507207924E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1906646129 | 0.1525618192 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.85 | 83.85 | 123.67 | |
Exterior Lighting Total | 7857.24 | 123.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29142.92 | 21028.07 | 8114.85 | 0.72 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 124043.90 | 84514.83 | 39529.07 | 0.68 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 28062.3 | 10.43 | ||||
PSZ-FINE STORAGE COOLING COIL | 120078.4 | 12.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 44614.72 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 33151.60 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 152035.61 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.07 | 99.86 | 92.91 | 1.00 | 4.07 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.39 | 1586.26 | 1140.11 | 1.00 | 1.29 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 5.10 | 9579.38 | 1877.50 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14086.87 | 16904.25 | 71.36 | 1.159 | 1.391 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00817 | 41.57 | 0.01074 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 66266.66 | 79520.00 | 57.07 | 4.252 | 5.102 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 26.70 | 26.70 | 0.00838 | 41.44 | 0.01074 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 42.80 | 0.01074 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5825.77 | 6990.93 | 29.51 | 0.163 | 0.196 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00851 | 12.70 | 0.00915 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 10132.32 | 12158.78 | 8.73 | 0.240 | 0.354 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 15.56 | 15.56 | 0.00859 | 12.70 | 0.00915 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 37178.94 | 44614.72 | 13.92 | 0.896 | 1.075 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00763 | 12.70 | 0.00915 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.39 | 1.39 | 0.20 | 0.20 | 1.3913 | 1.3913 | 1.3913 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 5.10 | 5.10 | 0.35 | 0.35 | 5.1022 | 5.1022 | 5.1022 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 44614.724 | 44614.724 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 44614.72 | 41874.27 | 1.074750 | 12.04 | 12.04 | 0.00878467 | 43.33 | 27.10 | 0.01600000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00763322 | 99.9999 | 44614.72 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 29142.920 | 0.000 | 1.391320 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 29142.92 | 27340.49 | 1.391320 | 25.43 | 16.77 | 0.00838880 | 12.00 | 11.25 | 0.00800000 | 41.57 | 0.01073558 | 23.47 | 8.6490 | 23.90 | 0.00816661 | 44.2302 | 14086.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 33151.603 | 33151.603 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 33151.60 | 33151.60 | 1.391318 | 15.91 | 13.73 | 0.00890628 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.6490 | 21.10 | 0.00851313 | 54.6236 | 5825.77 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 124043.900 | 0.000 | 5.102210 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 124043.90 | 114857.91 | 5.102210 | 27.72 | 17.69 | 0.00854416 | 12.00 | 11.25 | 0.00800000 | 41.44 | 0.01073558 | 23.44 | 6.9367 | 26.70 | 0.00838082 | 38.4159 | 66266.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 152035.611 | 152035.611 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 152035.61 | 152035.61 | 5.102206 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.9368 | 15.56 | 0.00859468 | 78.0670 | 9938.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 44614.724 | 44614.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.074750 | 1.29356364 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 44614.72 | 41874.27 | 1.0000 | 1.29356364 | 1.074750 | 12.04 | 12.04 | 0.00878467 | 34269.1 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44614.72 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00763322 | 10.00 | 0.00763322 | 99.9999 | 44614.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29142.920 | 0.000 | 1.391320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4344 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 29142.92 | 27340.49 | 1.0000 | 1.67458577 | 1.391320 | 25.43 | 16.77 | 0.00838880 | 46927.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29142.92 | 41.57 | 0.01073558 | 23.47 | 0.12033533 | 8.6490 | 23.90 | 0.00816661 | 23.90 | 0.00816661 | 44.2302 | 14086.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33151.603 | 33151.603 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.391318 | 1.67458339 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 33151.60 | 33151.60 | 1.0000 | 1.67458339 | 1.391318 | 15.91 | 13.73 | 0.00890628 | 38525.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33151.60 | 12.70 | 0.00915345 | 12.70 | 0.12033533 | 8.6490 | 21.02 | 0.00851313 | 21.10 | 0.00851313 | 54.6236 | 5825.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 124043.900 | 0.000 | 5.102210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7232 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 124043.90 | 114857.91 | 1.0000 | 6.14099435 | 5.102210 | 27.72 | 17.69 | 0.00854416 | 49664.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 124043.90 | 41.44 | 0.01073558 | 23.44 | 0.35392745 | 6.9367 | 26.70 | 0.00838082 | 26.70 | 0.00838082 | 38.4159 | 66266.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 152035.611 | 152035.611 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.102206 | 6.14098913 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 152035.61 | 152035.61 | 1.0000 | 6.14098913 | 5.102206 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 152035.61 | 12.70 | 0.00915345 | 12.70 | 0.35392745 | 6.9368 | 15.56 | 0.00858854 | 15.56 | 0.00859468 | 78.0670 | 9938.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3207.33 | 340.17 | 203.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3207.33 | 340.17 | 203.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 119.50 | 0.00 | 75.67 |
ZONE2 FINE STORAGE | 0.00 | 621.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 725.00 | 0.00 | 75.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.415 | 0.376 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
Electricity:Building | 661.27 | 4992.32 | 01-JAN-00:10 | 48037.94 | 17-JAN-13:30 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.67 | 2759.73 | 01-JAN-00:10 | 33963.13 | 17-JAN-13:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 22.72 | 483.00 | 08-FEB-06:10 | 1745.81 | 11-JAN-13:00 |
WaterSystems:Electricity | 22.72 | 483.00 | 08-FEB-06:10 | 1745.81 | 11-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 22.72 | 483.00 | 08-FEB-06:10 | 1745.81 | 11-JAN-13:00 |
Fans:Electricity | 196.65 | 0.00 | 01-JAN-00:10 | 13470.93 | 14-APR-13:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 40.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
Ventilation (simple):Fans:Electricity | 40.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
ElectricityPurchased:Facility | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
ElectricityNet:Plant | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1274.31 | 5475.32 | 01-JAN-07:10 | 106536.25 | 10-AUG-16:00 |
Electricity:HVAC | 466.65 | 0.00 | 01-JAN-00:10 | 61974.93 | 10-AUG-16:00 |
General:Fans:Electricity | 156.63 | 0.00 | 01-JAN-00:10 | 11165.64 | 02-JAN-13:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 310.03 | 0.00 | 01-JAN-00:10 | 50809.29 | 10-AUG-16:00 |
ExteriorLights:Electricity | 123.67 | 0.00 | 01-JAN-07:10 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.67 | 0.00 | 01-JAN-07:10 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 70.96 | 2250.00 | 08-FEB-06:10 | 3914.27 | 02-JAN-07:20 |
Gas:HVAC | 70.96 | 2250.00 | 08-FEB-06:10 | 3914.27 | 02-JAN-07:20 |
Heating:Gas | 70.96 | 2250.00 | 08-FEB-06:10 | 3914.27 | 02-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1519.49 | 0.00 | 01-JAN-00:10 | 228734.12 | 10-AUG-16:00 |
EnergyTransfer:Building | 564.09 | 0.00 | 01-JAN-00:10 | 84687.82 | 21-MAY-12:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 110.20 | 0.00 | 01-JAN-00:10 | 17898.06 | 21-JUL-12:00 |
Heating:EnergyTransfer | 5.92 | 0.00 | 01-JAN-00:10 | 8187.19 | 10-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.09 | 0.00 | 01-JAN-00:10 | 1566.70 | 02-JAN-07:20 |
Cooling:EnergyTransfer | 558.17 | 0.00 | 01-JAN-00:10 | 84687.82 | 21-MAY-12:50 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 110.11 | 0.00 | 01-JAN-00:10 | 17898.06 | 21-JUL-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 453.89 | 0.00 | 01-JAN-00:10 | 80442.43 | 21-MAY-12:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 5.83 | 0.00 | 01-JAN-00:10 | 8187.19 | 10-JAN-18:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 448.06 | 0.00 | 01-JAN-00:10 | 80442.43 | 21-MAY-12:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 955.40 | 0.00 | 01-JAN-00:10 | 154026.90 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 1074.92 | 02-JAN-07:20 |
CoolingCoils:EnergyTransfer | 955.39 | 0.00 | 01-JAN-00:10 | 154026.90 | 22-AUG-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.092 | -110.108 | 0.000 | 0.000 | 3.576 | 30.994 | 31.946 | 16.964 | 0.000 | 11.078 | 23.094 | 0.000 | -5.013 | 0.000 | -2.623 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 5.828 | -448.059 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 51.763 | 274.038 | 0.000 | 0.000 | 0.000 | -20.226 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 40.766 | 0.000 | 1.895 | 1544.214 | 0.000 | -13.180 | 0.000 | -1995.340 | -0.002 |
Total Facility | 0.000 | 0.000 | 5.920 | -558.167 | 0.000 | 0.000 | 3.576 | 481.960 | 139.282 | 57.730 | 0.000 | 64.735 | 1841.345 | 0.000 | -18.193 | 0.000 | -2018.189 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-APR-05:01 | 0.00 | 0.00 | 0.00 | -27716.81 | 0.00 | 0.00 | 27.72 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 27221.50 | 0.00 | -480.35 | 0.00 | -212.24 | 0.00 |
ZONE2 FINE STORAGE | 19-NOV-12:43 | 0.00 | 0.00 | 0.00 | -102307.81 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 3653.91 | 97454.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -114794.06 | 0.00 | 0.00 | 22.02 | 4546.06 | 2623.78 | 0.00 | 0.00 | 2481.76 | 201065.49 | 0.00 | -713.29 | 0.00 | -95231.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-07:15 | 0.00 | 0.00 | 2033.52 | 0.00 | 0.00 | 0.00 | 88.59 | 1070.90 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.67 | 0.00 | -3035.34 | -546.25 |
ZONE2 FINE STORAGE | 15-FEB-07:53 | 0.00 | 0.00 | 8411.73 | 0.00 | 0.00 | 0.00 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -724.33 | -14886.70 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-FEB-07:53 | -950.22 | 950.22 | 8411.73 | -950.22 | 0.00 | 0.00 | 75.13 | 24828.58 | 3006.28 | 868.54 | 0.00 | 5138.43 | 0.00 | 0.00 | 0.00 | 0.00 | -991.23 | -40387.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3913 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3913 | 0.0865 | 1.0000 | 0.1203 | 0.0865 | ||
PSZ-FINE STORAGE | 5.1022 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 5.1022 | 0.0694 | 1.0000 | 0.3539 | 0.0694 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3913 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3913 | 1.0000 | 1.0000 | 0.1203 | 0.0865 | ||
PSZ-FINE STORAGE | 5.1022 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 5.1022 | 1.0000 | 1.0000 | 0.3539 | 0.0694 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 5.1022 | 5.1022 | 5.1022 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 5.1022 | 5.1022 | 5.1022 | 5.1022 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 0.6140 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 5.1022 | 5.1022 | 5.1022 | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 5.1022 | 5.1022 | 5.1022 | 5.1022 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 75.67 |
Number of hours not met | 75.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 70.96 | 3914.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 310.03 | 50809.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.67 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 40.02 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 156.63 | 11165.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.72 | 1745.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1274.31 |
Natural Gas | 0.00 | 70.96 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1345.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 64.12 |
Fans (All) | 40.67 |
Service Water Heating | 4.70 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 263.55 |
Subtotal | 263.55 |
Natural Gas [MJ/m2] | |
Space Heating | 14.68 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.68 |
Subtotal | 14.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.83 |
Space Heating | 5.27 |
Space Cooling | 23.05 |
Fans (All) | 14.62 |
Service Water Heating | 1.69 |
Receptacle Equipment | 10.35 |
Miscellaneous | 9.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.603249E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709621E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.603249E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363864E+10 | 21642.48 | 25-JAN-06:02 | 17.88 | 14.28 | 0.247864E+09 | 301.61 | 23-JAN-14:20 | 27.00 | 16.73 |
February | 0.444104E+10 | 24304.76 | 11-FEB-06:02 | 18.50 | 13.71 | 0.228703E+09 | 301.61 | 04-FEB-16:00 | 28.00 | 17.92 |
March | 0.669810E+10 | 27182.61 | 28-MAR-05:01 | 25.67 | 14.72 | 0.268891E+09 | 301.62 | 28-MAR-09:00 | 27.00 | 19.85 |
April | 0.803192E+10 | 27717.45 | 26-APR-05:01 | 23.17 | 12.09 | 0.249093E+09 | 301.64 | 28-APR-13:00 | 35.00 | 23.20 |
May | 0.113762E+11 | 27206.59 | 11-MAY-05:01 | 28.00 | 16.04 | 0.259158E+09 | 301.63 | 04-MAY-14:20 | 36.00 | 22.80 |
June | 0.123582E+11 | 25675.20 | 16-JUN-05:01 | 28.17 | 20.45 | 0.259195E+09 | 301.63 | 03-JUN-14:09 | 38.67 | 24.75 |
July | 0.134296E+11 | 24676.93 | 03-JUL-05:01 | 28.83 | 16.80 | 0.249314E+09 | 306.84 | 17-JUL-12:09 | 38.05 | 29.48 |
August | 0.146992E+11 | 22438.94 | 07-AUG-05:01 | 32.82 | 23.14 | 0.269331E+09 | 313.19 | 22-AUG-12:09 | 41.07 | 28.74 |
September | 0.120865E+11 | 21655.29 | 02-SEP-05:01 | 30.50 | 22.82 | 0.249229E+09 | 301.62 | 26-SEP-15:09 | 38.67 | 25.14 |
October | 0.103966E+11 | 26964.17 | 20-OCT-05:01 | 23.17 | 16.22 | 0.249186E+09 | 301.63 | 02-OCT-15:50 | 34.15 | 23.08 |
November | 0.777979E+10 | 25078.12 | 18-NOV-06:01 | 20.08 | 15.99 | 0.239135E+09 | 301.62 | 06-NOV-14:30 | 32.50 | 21.10 |
December | 0.517189E+10 | 24466.75 | 13-DEC-06:02 | 15.02 | 12.68 | 0.248831E+09 | 301.61 | 01-DEC-13:09 | 28.17 | 18.16 |
Annual Sum or Average | 0.110108E+12 | 0.301793E+10 | ||||||||
Minimum of Months | 0.363864E+10 | 21642.48 | 15.02 | 12.09 | 0.228703E+09 | 301.61 | 27.00 | 16.73 | ||
Maximum of Months | 0.146992E+11 | 27717.45 | 32.82 | 23.14 | 0.269331E+09 | 313.19 | 41.07 | 29.48 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229200E+10 | 23776.75 | 29-JAN-15:20 | 25.33 | 19.75 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.597586E+10 | 94728.06 | 05-FEB-15:13 | 32.00 | 19.21 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.149035E+11 | 97329.86 | 26-MAR-14:22 | 32.80 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.282019E+11 | 98860.08 | 23-APR-14:52 | 32.00 | 18.39 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.550764E+11 | 97211.65 | 10-MAY-17:04 | 36.83 | 20.30 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.629061E+11 | 96380.82 | 15-JUN-17:04 | 37.67 | 20.95 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.750032E+11 | 95309.20 | 04-JUL-07:42 | 32.27 | 18.65 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.775748E+11 | 88268.10 | 13-AUG-13:41 | 40.12 | 25.53 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.584062E+11 | 89630.14 | 04-SEP-12:22 | 40.80 | 24.39 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.418021E+11 | 97650.83 | 29-OCT-14:52 | 32.00 | 19.83 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.198760E+11 | 102307.07 | 19-NOV-12:43 | 30.92 | 16.51 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.604472E+10 | 62378.57 | 03-DEC-13:23 | 28.40 | 19.49 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.448063E+12 | 0.00 | ||||||||
Minimum of Months | 0.229200E+10 | 23776.75 | 25.33 | 16.51 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.775748E+11 | 102307.07 | 40.80 | 25.53 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 | 23.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.83 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39601191.13 | 2033.50 | 02-JAN-07:15 | 13.00 |
February | 22878811.36 | 891.30 | 15-FEB-07:15 | 16.67 |
March | 12026813.52 | 965.54 | 10-MAR-07:10 | 17.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 17039777.76 | 799.48 | 19-DEC-07:15 | 15.13 |
Annual Sum or Average | 91546593.77 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 39601191.13 | 2033.50 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236455E+10 | 8290.20 | 10-JAN-18:00 | 22.50 |
February | 0.118475E+10 | 8412.01 | 15-FEB-07:53 | 23.20 |
March | 0.720483E+09 | 8201.52 | 01-MAR-07:13 | 24.33 |
April | 0.185949E+09 | 6626.29 | 06-APR-06:30 | 21.65 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.169468E+09 | 6716.25 | 25-NOV-07:05 | 24.70 |
December | 0.120316E+10 | 7525.84 | 16-DEC-18:00 | 21.00 |
Annual Sum or Average | 0.582836E+10 | |||
Minimum of Months | 0.00 | 0.00 | 21.00 | |
Maximum of Months | 0.236455E+10 | 8412.01 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8791221.15 | 0.723578E+09 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94215352.93 | 0.558808E+09 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334159E+09 | 0.383667E+09 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634741E+09 | 0.174561E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137215E+10 | 31840937.76 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167180E+10 | 10443007.93 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186119E+10 | 221058.17 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210642E+10 | 136056.13 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144564E+10 | 10395999.85 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994329E+09 | 41508567.49 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480101E+09 | 0.194960E+09 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74070922.51 | 0.492944E+09 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.110776E+11 | 0.262306E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8791221.15 | 136056.13 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210642E+10 | 0.723578E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116438.60 | 0.471838E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205433E+09 | 0.485068E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778900E+09 | 0.325287E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212809E+10 | 0.150896E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622439E+10 | 0.209049E+09 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820691E+10 | 51701012.22 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107559E+11 | 0.00 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109142E+11 | 0.00 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729685E+10 | 41927258.68 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406690E+10 | 0.376225E+09 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113003E+10 | 0.147481E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52482443.24 | 0.374171E+10 |
Annual Sum or Average | 0.136656E+12 | 0.517633E+11 | 0.202263E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116438.60 | 0.00 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109142E+11 | 0.485068E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35831867.82 | 0.149415E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6122337.96 | 0.168269E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102989E+09 | 0.156664E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2378696.35 | 0.139514E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20143721.84 | 0.120633E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3846844.55 | 0.129159E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2347585.18 | 0.120111E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432349.87 | 0.122589E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4437251.82 | 0.101496E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4061168.98 | 0.867328E+10 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148504E+09 | 0.756617E+10 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3402916.65 | 0.119065E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.335498E+09 | 0.148931E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432349.87 | 0.756617E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148504E+09 | 0.168269E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.87 | 23-JAN-13:00 | 4362.96 | 19-JAN-07:05 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2566.27 | 07-FEB-13:00 | 3884.25 | 13-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5013.52 | 27-MAR-11:10 | 3388.08 | 07-MAR-07:05 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.03 | 28-APR-12:00 | 2665.15 | 05-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5817.04 | 09-MAY-12:00 | 1262.17 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6965.43 | 09-JUN-16:10 | 332.27 | 07-JUN-05:01 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7273.16 | 21-JUL-12:00 | 17.78 | 06-JUL-05:01 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7478.32 | 16-AUG-12:00 | 17.61 | 27-AUG-06:00 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5784.82 | 05-SEP-16:10 | 387.12 | 25-SEP-05:01 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.79 | 19-OCT-16:05 | 706.70 | 30-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3187.27 | 01-NOV-16:10 | 2647.34 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.41 | 01-DEC-13:00 | 3647.21 | 26-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.87 | 17.61 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 7478.32 | 4362.96 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.32 | 23-JAN-14:00 | 8656.78 | 18-JAN-16:25 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5740.36 | 05-FEB-15:15 | 10637.32 | 10-FEB-17:53 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10794.77 | 01-MAR-16:10 | 8053.27 | 25-MAR-09:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14831.26 | 28-APR-15:10 | 5450.53 | 04-APR-07:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39140.32 | 21-MAY-12:51 | 2684.42 | 01-MAY-07:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20898.58 | 09-JUN-15:40 | 1894.81 | 07-JUN-06:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20952.27 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17908.16 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15335.92 | 02-SEP-16:00 | 1253.44 | 25-SEP-05:08 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16319.30 | 19-OCT-15:10 | 3497.07 | 21-OCT-07:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6029.49 | 01-NOV-15:10 | 4357.16 | 22-NOV-07:20 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.42 | 10-DEC-12:27 | 7282.53 | 16-DEC-09:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.32 | 0.00 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39140.32 | 10637.32 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2850.67 | 29-JAN-07:00 | 33981.88 | 18-JAN-15:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3779.41 | 15-FEB-07:53 | 45312.42 | 10-FEB-15:50 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7977.67 | 01-MAR-04:00 | 61350.57 | 25-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4262.66 | 25-APR-07:53 | 28240.96 | 28-APR-13:05 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3994.11 | 28-MAY-03:53 | 47413.57 | 21-MAY-12:51 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.81 | 22-JUN-08:51 | 28509.92 | 29-JUN-13:30 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.69 | 20-JUL-20:52 | 24953.29 | 14-JUL-12:10 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1572.76 | 01-AUG-23:55 | 19934.31 | 11-AUG-15:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.95 | 13-SEP-03:55 | 20065.22 | 02-SEP-13:55 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 911.28 | 06-OCT-07:53 | 16691.48 | 19-OCT-12:40 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4577.66 | 19-NOV-19:00 | 12928.42 | 20-NOV-16:30 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 645.99 | 26-DEC-22:00 | 38858.12 | 15-DEC-12:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 596.69 | 12928.42 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7977.67 | 61350.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21642.48 | 25-JAN-06:02 | 362.59 | 2932.21 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.21 |
February | 24304.76 | 11-FEB-06:02 | 362.59 | 2932.21 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.65 |
March | 27182.61 | 28-MAR-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.02 |
April | 27717.45 | 26-APR-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 |
May | 27206.59 | 11-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
June | 25675.20 | 16-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 |
July | 24676.93 | 03-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 0.00 |
August | 22438.94 | 07-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 233.68 | 0.00 |
September | 21655.29 | 02-SEP-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 0.00 |
October | 26964.17 | 20-OCT-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.46 |
November | 25078.12 | 18-NOV-06:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 |
December | 24466.75 | 13-DEC-06:02 | 435.11 | 3518.66 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21642.48 | 362.59 | 2932.21 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27717.45 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 233.68 | 686.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23776.75 | 29-JAN-15:20 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.77 |
February | 94728.06 | 05-FEB-15:13 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5031.34 | 0.00 |
March | 97329.86 | 26-MAR-14:22 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4512.42 | 0.00 |
April | 98860.08 | 23-APR-14:52 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4015.31 | 0.00 |
May | 97211.65 | 10-MAY-17:04 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5656.68 | 0.00 |
June | 96380.82 | 15-JUN-17:04 | 0.00 | 9599.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7035.18 | 0.00 |
July | 95309.20 | 04-JUL-07:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.54 | 0.00 |
August | 88268.10 | 13-AUG-13:41 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10748.34 | 0.00 |
September | 89630.14 | 04-SEP-12:22 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.12 | 0.00 |
October | 97650.83 | 29-OCT-14:52 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4426.40 | 0.00 |
November | 102307.07 | 19-NOV-12:43 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3653.91 | 0.00 |
December | 62378.57 | 03-DEC-13:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 23776.75 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102307.07 | 0.00 | 9599.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10748.34 | 489.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.44 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.58 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.52 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1956.17 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1915.34 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.41 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.87 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.88 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.14 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.79 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2332.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | |
Maximum of Months | 0.00 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.806327E+11 | 71110.11 | 23-JAN-13:39 | 0.603249E+10 | 3914.27 | 02-JAN-07:19 |
February | 0.763493E+11 | 77907.76 | 07-FEB-13:39 | 0.544320E+10 | 2250.00 | 01-FEB-00:10 |
March | 0.922274E+11 | 84187.11 | 27-MAR-12:09 | 0.602640E+10 | 2250.00 | 01-MAR-00:10 |
April | 0.956507E+11 | 90628.46 | 28-APR-12:09 | 0.583200E+10 | 2250.00 | 01-APR-00:10 |
May | 0.117491E+12 | 94745.59 | 31-MAY-14:20 | 0.602640E+10 | 2250.00 | 01-MAY-00:10 |
June | 0.125657E+12 | 100683.77 | 09-JUN-14:20 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.135767E+12 | 103828.92 | 14-JUL-13:00 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.143019E+12 | 106536.25 | 10-AUG-15:00 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.123223E+12 | 96986.22 | 06-SEP-14:09 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.109352E+12 | 91410.80 | 07-OCT-13:39 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.908604E+11 | 86289.88 | 01-NOV-13:00 | 0.583200E+10 | 2250.00 | 01-NOV-00:10 |
December | 0.840790E+11 | 75290.81 | 06-DEC-13:20 | 0.602640E+10 | 2250.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.127431E+13 | 0.709621E+11 | ||||
Minimum of Months | 0.763493E+11 | 71110.11 | 0.544320E+10 | 2250.00 | ||
Maximum of Months | 0.143019E+12 | 106536.25 | 0.603249E+10 | 3914.27 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.117151E+11 | 0.115358E+11 | 0.00 | 0.113159E+11 | 0.00 | 0.00 | 0.392877E+10 | 0.00 | 0.00 | 0.00 | 0.203382E+10 | 0.00 |
February | 0.366966E+11 | 0.101641E+11 | 0.105871E+11 | 0.00 | 0.109408E+11 | 0.00 | 0.00 | 0.613126E+10 | 0.00 | 0.00 | 0.00 | 0.182938E+10 | 0.00 |
March | 0.423649E+11 | 0.106450E+11 | 0.123357E+11 | 0.00 | 0.137227E+11 | 0.00 | 0.00 | 0.111468E+11 | 0.00 | 0.00 | 0.00 | 0.201228E+10 | 0.00 |
April | 0.397216E+11 | 0.965498E+10 | 0.114862E+11 | 0.00 | 0.146486E+11 | 0.00 | 0.00 | 0.182728E+11 | 0.00 | 0.00 | 0.00 | 0.186652E+10 | 0.00 |
May | 0.412341E+11 | 0.945697E+10 | 0.119357E+11 | 0.00 | 0.191982E+11 | 0.00 | 0.00 | 0.337939E+11 | 0.00 | 0.00 | 0.00 | 0.187249E+10 | 0.00 |
June | 0.408524E+11 | 0.891011E+10 | 0.118862E+11 | 0.00 | 0.205423E+11 | 0.00 | 0.00 | 0.416822E+11 | 0.00 | 0.00 | 0.00 | 0.178417E+10 | 0.00 |
July | 0.401034E+11 | 0.929669E+10 | 0.115358E+11 | 0.00 | 0.219795E+11 | 0.00 | 0.00 | 0.510497E+11 | 0.00 | 0.00 | 0.00 | 0.180223E+10 | 0.00 |
August | 0.423649E+11 | 0.974455E+10 | 0.123357E+11 | 0.00 | 0.226813E+11 | 0.00 | 0.00 | 0.540418E+11 | 0.00 | 0.00 | 0.00 | 0.185082E+10 | 0.00 |
September | 0.397216E+11 | 0.100180E+11 | 0.114862E+11 | 0.00 | 0.198668E+11 | 0.00 | 0.00 | 0.403120E+11 | 0.00 | 0.00 | 0.00 | 0.181805E+10 | 0.00 |
October | 0.401034E+11 | 0.109939E+11 | 0.115358E+11 | 0.00 | 0.169382E+11 | 0.00 | 0.00 | 0.278598E+11 | 0.00 | 0.00 | 0.00 | 0.192106E+10 | 0.00 |
November | 0.385909E+11 | 0.111919E+11 | 0.110862E+11 | 0.00 | 0.130922E+11 | 0.00 | 0.00 | 0.149898E+11 | 0.00 | 0.00 | 0.00 | 0.190940E+10 | 0.00 |
December | 0.401034E+11 | 0.118801E+11 | 0.115358E+11 | 0.00 | 0.117233E+11 | 0.00 | 0.00 | 0.681672E+10 | 0.00 | 0.00 | 0.00 | 0.201965E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123671E+12 | 0.139282E+12 | 0.196650E+12 | 0.00 | 0.310026E+12 | 0.227199E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.891011E+10 | 0.105871E+11 | 0.00 | 0.109408E+11 | 0.00 | 0.00 | 0.392877E+10 | 0.00 | 0.00 | 0.00 | 0.178417E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.118801E+11 | 0.123357E+11 | 0.00 | 0.226813E+11 | 0.00 | 0.00 | 0.540418E+11 | 0.00 | 0.00 | 0.00 | 0.203382E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.603249E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709621E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.603249E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 13470.93 | 23-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 13470.93 | 01-FEB-12:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 13470.93 | 01-MAR-09:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 13470.93 | 14-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 13470.93 | 13-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 13470.93 | 09-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 13470.93 | 01-JUL-06:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 13470.93 | 07-AUG-06:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 13470.93 | 11-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 13470.93 | 02-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 13470.93 | 01-NOV-08:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 13470.93 | 01-DEC-10:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 13470.93 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 13470.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10192.08 | 23-JAN-13:50 | 0.00 | 0.00 | 0.00 | 1745.81 | 11-JAN-12:00 | 0.00 |
February | 17199.06 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 1742.94 | 01-FEB-12:20 | 0.00 |
March | 24338.99 | 27-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1730.60 | 01-MAR-12:09 | 0.00 |
April | 31636.85 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1709.30 | 01-APR-11:50 | 0.00 |
May | 38658.96 | 21-MAY-12:50 | 0.00 | 0.00 | 0.00 | 1686.78 | 01-MAY-11:00 | 0.00 |
June | 44207.35 | 09-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1667.96 | 01-JUN-11:00 | 0.00 |
July | 45175.17 | 14-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1659.16 | 31-JUL-11:30 | 0.00 |
August | 50809.29 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1670.71 | 31-AUG-11:20 | 0.00 |
September | 39125.97 | 12-SEP-16:10 | 0.00 | 0.00 | 0.00 | 1690.20 | 30-SEP-11:00 | 0.00 |
October | 31594.25 | 07-OCT-15:50 | 0.00 | 0.00 | 0.00 | 1713.56 | 31-OCT-11:50 | 0.00 |
November | 25653.59 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 | 1733.41 | 30-NOV-12:39 | 0.00 |
December | 14613.32 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1744.49 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10192.08 | 0.00 | 0.00 | 0.00 | 1659.16 | 0.00 | ||
Maximum of Months | 50809.29 | 0.00 | 0.00 | 0.00 | 1745.81 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71110.11 | 23-JAN-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 10190.85 | 0.00 |
February | 77907.76 | 07-FEB-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 16991.18 | 0.00 |
March | 84187.11 | 27-MAR-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 23294.66 | 0.00 |
April | 90628.46 | 28-APR-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 29756.62 | 0.00 |
May | 94745.59 | 31-MAY-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 33891.11 | 0.00 |
June | 100683.77 | 09-JUN-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 39832.84 | 0.00 |
July | 103828.92 | 14-JUL-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 42999.50 | 0.00 |
August | 106536.25 | 10-AUG-15:00 | 31660.41 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 50809.29 | 0.00 |
September | 96986.22 | 06-SEP-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 36126.64 | 0.00 |
October | 91410.80 | 07-OCT-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 30553.61 | 0.00 |
November | 86289.88 | 01-NOV-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 25419.11 | 0.00 |
December | 75290.81 | 06-DEC-13:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 14378.56 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 71110.11 | 31660.41 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 10190.85 | 0.00 | |
Maximum of Months | 106536.25 | 35620.03 | 10112.62 | 0.00 | 0.00 | 13470.93 | 0.00 | 0.00 | 50809.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 3914.27 | 02-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2250.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2250.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2250.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2250.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2250.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2250.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3914.27 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.50 | 24.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.61 | 2.00 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.82 | 5.50 | 24.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.27 | 8.67 | 25.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.00 | 9.33 | 25.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.95 | 11.83 | 25.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.82 | 13.50 | 25.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.45 | 8.83 | 25.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.09 | 8.17 | 25.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.87 | 6.00 | 24.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
Annual Sum or Average | 0.00 | 0.00 | 119.50 | 27.01 | 75.67 | 25.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.95 | 13.50 | 25.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.68 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.55 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.75 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 | 27.88 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 27.91 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 115.83 | 28.22 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 109.67 | 28.22 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 27.90 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 27.73 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 621.17 | 27.98 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 115.83 | 28.22 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.67 | 23.49 | 108.33 | 23.90 | 0.00 | 0.00 |
February | 28.00 | 23.51 | 180.33 | 23.90 | 0.50 | 24.14 |
March | 7.83 | 23.81 | 262.67 | 23.91 | 0.83 | 24.42 |
April | 3.33 | 24.46 | 299.17 | 23.92 | 3.33 | 24.46 |
May | 9.50 | 24.60 | 312.00 | 23.94 | 9.50 | 24.60 |
June | 29.83 | 24.34 | 312.00 | 23.95 | 29.83 | 24.34 |
July | 51.67 | 24.31 | 300.00 | 23.98 | 51.67 | 24.31 |
August | 52.50 | 24.32 | 324.00 | 23.98 | 52.50 | 24.32 |
September | 36.17 | 24.31 | 300.00 | 23.95 | 36.17 | 24.31 |
October | 14.00 | 24.40 | 300.00 | 23.94 | 14.00 | 24.40 |
November | 5.00 | 24.43 | 288.00 | 23.92 | 5.00 | 24.43 |
December | 17.67 | 23.68 | 220.83 | 23.91 | 0.33 | 24.00 |
Annual Sum or Average | 340.17 | 24.02 | 3207.33 | 23.94 | 203.67 | 24.34 |
Minimum of Months | 3.33 | 23.49 | 108.33 | 23.90 | 0.00 | 0.00 |
Maximum of Months | 84.67 | 24.60 | 324.00 | 23.98 | 52.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.561046E+10 | 0.150202E+10 | 255.02 | 0.475564E+10 | 0.854818E+09 | 0.00 | 1.00 | 23-JAN-06:02 | 0.00 | 01-JAN-00:10 | 33136.67 | 30-JAN-06:01 | 23998.16 | 25-JAN-06:02 | 10956.00 | 30-JAN-06:03 | 7671.01 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.690280E+10 | 0.186421E+10 | 246.98 | 0.575164E+10 | 0.115116E+10 | 0.00 | 1.00 | 06-FEB-06:01 | 0.00 | 01-FEB-00:10 | 34658.42 | 09-FEB-06:01 | 27000.45 | 11-FEB-06:02 | 13095.61 | 09-FEB-06:03 | 7915.27 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.997555E+10 | 0.275993E+10 | 308.34 | 0.860825E+10 | 0.136730E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 34568.07 | 29-MAR-05:01 | 29642.78 | 28-MAR-05:01 | 13016.79 | 29-MAR-05:04 | 7901.54 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.121970E+11 | 0.351056E+10 | 303.58 | 0.103961E+11 | 0.180088E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 34994.19 | 20-APR-05:01 | 29881.64 | 26-APR-05:01 | 13765.61 | 20-APR-05:04 | 7965.48 | 20-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.174813E+11 | 0.533626E+10 | 352.44 | 0.147113E+11 | 0.277003E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 36812.70 | 24-MAY-05:01 | 29864.95 | 11-MAY-05:01 | 16763.97 | 24-MAY-05:05 | 8383.98 | 23-MAY-05:01 | 0.00 | 01-MAY-00:05 |
June | 0.207797E+11 | 0.635697E+10 | 362.17 | 0.160390E+11 | 0.474069E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 37318.66 | 08-JUN-05:01 | 28257.91 | 16-JUN-05:01 | 18218.25 | 27-JUN-05:05 | 9123.31 | 11-JUN-14:51 | 0.00 | 01-JUN-00:10 |
July | 0.238372E+11 | 0.737746E+10 | 434.34 | 0.174219E+11 | 0.641527E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 36382.97 | 06-JUL-05:01 | 27254.60 | 03-JUL-05:01 | 18396.13 | 06-JUL-05:05 | 9326.21 | 16-JUL-12:51 | 0.00 | 01-JUL-00:10 |
August | 0.263847E+11 | 0.815320E+10 | 461.70 | 0.190375E+11 | 0.734721E+10 | 0.00 | 1.00 | 01-AUG-05:11 | 0.00 | 01-AUG-00:10 | 36382.97 | 31-AUG-05:01 | 26185.49 | 06-AUG-14:51 | 17671.46 | 23-AUG-05:06 | 9284.81 | 06-AUG-14:51 | 0.00 | 01-AUG-00:10 |
September | 0.211835E+11 | 0.632824E+10 | 365.97 | 0.155767E+11 | 0.560684E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 37351.39 | 23-SEP-05:01 | 24265.53 | 02-SEP-05:01 | 18852.98 | 23-SEP-05:04 | 8761.17 | 07-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 0.169957E+11 | 0.491200E+10 | 332.86 | 0.132713E+11 | 0.372446E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 37332.63 | 07-OCT-05:01 | 29006.71 | 20-OCT-05:01 | 17345.92 | 07-OCT-05:05 | 8454.45 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.125426E+11 | 0.347400E+10 | 289.61 | 0.992973E+10 | 0.261282E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 36211.80 | 03-NOV-05:01 | 26681.76 | 18-NOV-06:01 | 15152.82 | 03-NOV-05:06 | 8136.43 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.814849E+10 | 0.218304E+10 | 276.45 | 0.664450E+10 | 0.150399E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 34195.32 | 06-DEC-06:01 | 26269.52 | 13-DEC-06:02 | 13163.28 | 06-DEC-06:02 | 7843.84 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.182039E+12 | 0.537579E+11 | 3989.46 | 0.142144E+12 | 0.398955E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.561046E+10 | 0.150202E+10 | 246.98 | 0.475564E+10 | 0.854818E+09 | 0.00 | 1.00 | 0.00 | 33136.67 | 23998.16 | 10956.00 | 7671.01 | 0.00 | |||||||
Maximum of Months | 0.263847E+11 | 0.815320E+10 | 461.70 | 0.190375E+11 | 0.734721E+10 | 0.00 | 1.00 | 0.00 | 37351.39 | 29881.64 | 18852.98 | 9326.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.823953E+10 | 0.242675E+10 | 187.89 | 0.696514E+10 | 0.127439E+10 | 0.00 | 0.33 | 29-JAN-15:20 | 0.00 | 01-JAN-00:10 | 37554.64 | 29-JAN-15:20 | 27559.89 | 29-JAN-15:20 | 9994.74 | 29-JAN-15:20 | 11500.64 | 29-JAN-15:20 | 0.00 | 01-JAN-00:10 |
February | 0.142310E+11 | 0.426706E+10 | 215.14 | 0.120365E+11 | 0.219447E+10 | 0.00 | 1.00 | 05-FEB-13:53 | 0.00 | 01-FEB-00:10 | 125406.74 | 05-FEB-13:53 | 112224.38 | 05-FEB-15:13 | 14382.48 | 05-FEB-13:53 | 36412.37 | 05-FEB-13:53 | 0.00 | 01-FEB-00:10 |
March | 0.271671E+11 | 0.838689E+10 | 305.86 | 0.239066E+11 | 0.326047E+10 | 0.00 | 1.00 | 26-MAR-13:42 | 0.00 | 01-MAR-00:10 | 118622.35 | 26-MAR-13:42 | 118622.35 | 26-MAR-13:42 | 17812.67 | 28-MAR-17:08 | 36171.39 | 26-MAR-13:42 | 0.00 | 01-MAR-00:10 |
April | 0.459843E+11 | 0.147623E+11 | 407.13 | 0.396161E+11 | 0.636824E+10 | 0.00 | 1.00 | 02-APR-13:52 | 0.00 | 01-APR-00:10 | 141534.11 | 30-APR-15:42 | 120155.33 | 23-APR-14:52 | 48073.11 | 30-APR-16:23 | 39226.10 | 30-APR-11:42 | 0.00 | 01-APR-00:10 |
May | 0.842097E+11 | 0.284576E+11 | 581.86 | 0.718186E+11 | 0.123911E+11 | 0.00 | 1.00 | 01-MAY-17:42 | 0.00 | 01-MAY-00:15 | 141632.44 | 29-MAY-13:42 | 117937.21 | 07-MAY-12:52 | 49104.03 | 29-MAY-13:42 | 41555.39 | 31-MAY-17:42 | 0.00 | 01-MAY-00:05 |
June | 0.104956E+12 | 0.353252E+11 | 586.83 | 0.815285E+11 | 0.234279E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:12 | 152407.71 | 19-JUN-05:01 | 116621.48 | 15-JUN-17:42 | 71980.16 | 19-JUN-05:01 | 41709.80 | 09-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.127708E+12 | 0.436723E+11 | 610.85 | 0.962838E+11 | 0.314244E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:13 | 148337.34 | 06-JUL-05:01 | 114448.14 | 04-JUL-09:42 | 64279.94 | 06-JUL-05:01 | 43063.40 | 30-JUL-13:42 | 0.00 | 01-JUL-00:10 |
August | 0.134662E+12 | 0.458886E+11 | 617.16 | 0.998565E+11 | 0.348054E+11 | 0.00 | 1.00 | 01-AUG-02:23 | 0.00 | 01-AUG-00:12 | 153052.37 | 08-AUG-05:01 | 109577.82 | 06-AUG-09:02 | 74925.03 | 08-AUG-05:01 | 43384.37 | 10-AUG-17:42 | 0.00 | 01-AUG-00:10 |
September | 0.102674E+12 | 0.339837E+11 | 582.31 | 0.762483E+11 | 0.264256E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:12 | 147201.49 | 08-SEP-18:23 | 111649.53 | 04-SEP-12:22 | 64556.39 | 08-SEP-18:23 | 41982.70 | 04-SEP-14:21 | 0.00 | 01-SEP-00:10 |
October | 0.708236E+11 | 0.229478E+11 | 546.05 | 0.561411E+11 | 0.146825E+11 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:13 | 140953.05 | 07-OCT-17:06 | 118705.17 | 29-OCT-14:52 | 58800.85 | 08-OCT-08:23 | 39701.83 | 01-OCT-13:42 | 0.00 | 01-OCT-00:10 |
November | 0.370893E+11 | 0.115158E+11 | 346.84 | 0.299861E+11 | 0.710322E+10 | 0.00 | 1.00 | 05-NOV-13:02 | 0.00 | 01-NOV-00:15 | 129748.40 | 11-NOV-15:32 | 119985.57 | 19-NOV-12:43 | 37856.18 | 01-NOV-17:06 | 37103.43 | 05-NOV-13:42 | 0.00 | 01-NOV-00:10 |
December | 0.156108E+11 | 0.463368E+10 | 237.28 | 0.127914E+11 | 0.281939E+10 | 0.00 | 0.72 | 03-DEC-13:23 | 0.00 | 01-DEC-00:10 | 84304.29 | 03-DEC-13:23 | 72966.75 | 03-DEC-13:23 | 13945.01 | 03-DEC-14:43 | 25256.73 | 03-DEC-12:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.773356E+12 | 0.256268E+12 | 5225.20 | 0.607179E+12 | 0.166177E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.823953E+10 | 0.242675E+10 | 187.89 | 0.696514E+10 | 0.127439E+10 | 0.00 | 0.33 | 0.00 | 37554.64 | 27559.89 | 9994.74 | 11500.64 | 0.00 | |||||||
Maximum of Months | 0.134662E+12 | 0.458886E+11 | 617.16 | 0.998565E+11 | 0.348054E+11 | 0.00 | 1.00 | 0.00 | 153052.37 | 120155.33 | 74925.03 | 43384.37 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.78 | 12.39 | 30.39 | 82.27 | 109.58 | 0.00 | 0.00 | 744.00 |
February | 48.77 | 14.03 | 34.74 | 105.24 | 98.30 | 0.00 | 0.00 | 672.00 |
March | 57.55 | 17.05 | 40.49 | 146.85 | 80.78 | 0.00 | 0.00 | 744.00 |
April | 62.65 | 17.46 | 45.19 | 192.40 | 59.09 | 0.00 | 0.00 | 720.00 |
May | 68.30 | 20.39 | 47.91 | 261.29 | 23.43 | 0.00 | 0.00 | 744.00 |
June | 70.71 | 22.33 | 48.38 | 286.40 | 11.46 | 0.00 | 0.00 | 720.00 |
July | 65.01 | 18.70 | 46.30 | 304.53 | 1.93 | 0.00 | 0.00 | 744.00 |
August | 66.35 | 20.06 | 46.28 | 312.60 | 1.28 | 0.00 | 0.00 | 744.00 |
September | 63.22 | 19.83 | 43.39 | 253.38 | 14.35 | 0.00 | 0.00 | 720.00 |
October | 56.25 | 18.17 | 38.08 | 194.58 | 36.81 | 0.00 | 0.00 | 744.00 |
November | 48.49 | 15.93 | 32.56 | 136.89 | 70.31 | 0.00 | 0.00 | 720.00 |
December | 40.66 | 12.43 | 28.24 | 87.28 | 100.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.59 | 17.41 | 40.18 | 197.51 | 50.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 40.66 | 12.39 | 28.24 | 82.27 | 1.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.71 | 22.33 | 48.38 | 312.60 | 109.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.78 | 12.39 | 30.39 | 82.27 | 109.58 | 0.00 | 0.00 | 744.00 |
February | 48.77 | 14.03 | 34.74 | 105.24 | 98.30 | 0.00 | 0.00 | 672.00 |
March | 57.55 | 17.05 | 40.49 | 146.85 | 80.78 | 0.00 | 0.00 | 744.00 |
April | 62.65 | 17.46 | 45.19 | 192.40 | 59.09 | 0.00 | 0.00 | 720.00 |
May | 68.30 | 20.39 | 47.91 | 261.29 | 23.43 | 0.00 | 0.00 | 744.00 |
June | 70.71 | 22.33 | 48.38 | 286.40 | 11.46 | 0.00 | 0.00 | 720.00 |
July | 65.01 | 18.70 | 46.30 | 304.53 | 1.93 | 0.00 | 0.00 | 744.00 |
August | 66.35 | 20.06 | 46.28 | 312.60 | 1.28 | 0.00 | 0.00 | 744.00 |
September | 63.22 | 19.83 | 43.39 | 253.38 | 14.35 | 0.00 | 0.00 | 720.00 |
October | 56.25 | 18.17 | 38.08 | 194.58 | 36.81 | 0.00 | 0.00 | 744.00 |
November | 48.49 | 15.93 | 32.56 | 136.89 | 70.31 | 0.00 | 0.00 | 720.00 |
December | 40.66 | 12.43 | 28.24 | 87.28 | 100.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.59 | 17.41 | 40.18 | 197.51 | 50.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 40.66 | 12.39 | 28.24 | 82.27 | 1.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.71 | 22.33 | 48.38 | 312.60 | 109.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.98 | 0.00 | 13.98 | 18.53 | 65.31 | 0.00 | 0.00 | 744.00 |
February | 16.03 | 0.00 | 16.03 | 27.01 | 58.76 | 0.00 | 0.00 | 672.00 |
March | 18.41 | 0.00 | 18.41 | 42.17 | 47.68 | 0.00 | 0.00 | 744.00 |
April | 20.81 | 0.10 | 20.72 | 65.61 | 34.09 | 0.00 | 0.00 | 720.00 |
May | 23.70 | 1.03 | 22.67 | 102.66 | 12.88 | 0.00 | 0.00 | 744.00 |
June | 25.44 | 1.84 | 23.60 | 118.59 | 6.71 | 0.00 | 0.00 | 720.00 |
July | 23.22 | 0.93 | 22.28 | 133.05 | 1.13 | 0.00 | 0.00 | 744.00 |
August | 21.53 | 0.34 | 21.18 | 130.42 | 0.65 | 0.00 | 0.00 | 744.00 |
September | 19.46 | 0.01 | 19.45 | 95.08 | 8.10 | 0.00 | 0.00 | 720.00 |
October | 17.24 | 0.00 | 17.24 | 66.48 | 21.23 | 0.00 | 0.00 | 744.00 |
November | 14.80 | 0.00 | 14.80 | 39.91 | 40.93 | 0.00 | 0.00 | 720.00 |
December | 13.05 | 0.00 | 13.05 | 20.78 | 59.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.98 | 0.36 | 18.63 | 71.97 | 29.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.05 | 0.00 | 13.05 | 18.53 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 25.44 | 1.84 | 23.60 | 133.05 | 65.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.98 | 0.00 | 13.98 | 18.53 | 65.31 | 0.00 | 0.00 | 744.00 |
February | 16.03 | 0.00 | 16.03 | 27.01 | 58.76 | 0.00 | 0.00 | 672.00 |
March | 18.41 | 0.00 | 18.41 | 42.17 | 47.68 | 0.00 | 0.00 | 744.00 |
April | 20.81 | 0.10 | 20.71 | 65.61 | 34.09 | 0.00 | 0.00 | 720.00 |
May | 23.70 | 1.03 | 22.67 | 102.66 | 12.88 | 0.00 | 0.00 | 744.00 |
June | 25.44 | 1.84 | 23.60 | 118.59 | 6.71 | 0.00 | 0.00 | 720.00 |
July | 23.21 | 0.93 | 22.28 | 133.05 | 1.13 | 0.00 | 0.00 | 744.00 |
August | 21.52 | 0.34 | 21.18 | 130.42 | 0.65 | 0.00 | 0.00 | 744.00 |
September | 19.46 | 0.01 | 19.45 | 95.08 | 8.10 | 0.00 | 0.00 | 720.00 |
October | 17.24 | 0.00 | 17.24 | 66.47 | 21.22 | 0.00 | 0.00 | 744.00 |
November | 14.80 | 0.00 | 14.80 | 39.91 | 40.93 | 0.00 | 0.00 | 720.00 |
December | 13.05 | 0.00 | 13.05 | 20.78 | 59.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.98 | 0.36 | 18.63 | 71.97 | 29.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.05 | 0.00 | 13.05 | 18.53 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 25.44 | 1.84 | 23.60 | 133.05 | 65.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.55 | 26.29 | 42.26 | 79.20 | 44.97 | 66.17 | 0.00 | 744.00 |
February | 83.10 | 33.98 | 49.13 | 98.24 | 44.48 | 52.33 | 0.00 | 672.00 |
March | 100.46 | 42.16 | 58.30 | 121.80 | 45.71 | 16.33 | 0.00 | 744.00 |
April | 118.42 | 52.48 | 65.94 | 146.51 | 45.60 | 19.00 | 0.00 | 720.00 |
May | 134.40 | 65.35 | 69.05 | 166.87 | 39.05 | 7.17 | 0.00 | 744.00 |
June | 140.10 | 71.26 | 68.85 | 173.36 | 37.80 | 9.00 | 0.00 | 720.00 |
July | 135.90 | 68.95 | 66.95 | 169.90 | 34.25 | 3.33 | 0.00 | 744.00 |
August | 129.43 | 63.59 | 65.84 | 161.01 | 34.70 | 9.33 | 0.00 | 744.00 |
September | 116.15 | 55.72 | 60.43 | 144.22 | 39.22 | 32.83 | 0.00 | 720.00 |
October | 97.75 | 45.91 | 51.84 | 119.85 | 44.66 | 46.00 | 0.00 | 744.00 |
November | 77.69 | 33.99 | 43.70 | 93.88 | 46.31 | 43.17 | 0.00 | 720.00 |
December | 63.68 | 24.76 | 38.92 | 74.63 | 44.32 | 79.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.57 | 48.77 | 56.80 | 129.26 | 41.73 | 383.83 | 0.00 | 8760.00 |
Minimum of Months | 63.68 | 24.76 | 38.92 | 74.63 | 34.25 | 3.33 | 0.00 | 672.00 |
Maximum of Months | 140.10 | 71.26 | 69.05 | 173.36 | 46.31 | 79.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114575E+09 | 33179113.69 | 81395552.52 | 0.220339E+09 | 0.293495E+09 |
February | 0.117986E+09 | 33949881.44 | 84035784.78 | 0.254586E+09 | 0.237800E+09 |
March | 0.154131E+09 | 45669996.63 | 0.108461E+09 | 0.393320E+09 | 0.216349E+09 |
April | 0.162394E+09 | 45253894.09 | 0.117140E+09 | 0.498713E+09 | 0.153173E+09 |
May | 0.182938E+09 | 54607052.75 | 0.128331E+09 | 0.699851E+09 | 62758313.11 |
June | 0.183273E+09 | 57879065.84 | 0.125393E+09 | 0.742356E+09 | 29693186.63 |
July | 0.174120E+09 | 50098162.79 | 0.124022E+09 | 0.815657E+09 | 5175954.34 |
August | 0.177703E+09 | 53737567.12 | 0.123966E+09 | 0.837262E+09 | 3429976.03 |
September | 0.163873E+09 | 51409043.10 | 0.112464E+09 | 0.656767E+09 | 37199074.13 |
October | 0.150669E+09 | 48679733.69 | 0.101989E+09 | 0.521170E+09 | 98590852.32 |
November | 0.125683E+09 | 41286177.73 | 84396591.08 | 0.354814E+09 | 0.182244E+09 |
December | 0.108915E+09 | 33287399.47 | 75627364.87 | 0.233759E+09 | 0.269091E+09 |
Annual Sum or Average | 0.181626E+10 | 0.549037E+09 | 0.126722E+10 | 0.622859E+10 | 0.158900E+10 |
Minimum of Months | 0.108915E+09 | 33179113.69 | 75627364.87 | 0.220339E+09 | 3429976.03 |
Maximum of Months | 0.183273E+09 | 57879065.84 | 0.128331E+09 | 0.837262E+09 | 0.293495E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114575E+09 | 33179113.69 | 81395552.52 | 0.220339E+09 | 0.293495E+09 |
February | 0.117986E+09 | 33949881.44 | 84035784.78 | 0.254586E+09 | 0.237800E+09 |
March | 0.154131E+09 | 45669996.63 | 0.108461E+09 | 0.393320E+09 | 0.216349E+09 |
April | 0.162394E+09 | 45253894.09 | 0.117140E+09 | 0.498713E+09 | 0.153173E+09 |
May | 0.182938E+09 | 54607052.75 | 0.128331E+09 | 0.699851E+09 | 62758313.11 |
June | 0.183273E+09 | 57879065.84 | 0.125393E+09 | 0.742356E+09 | 29693186.63 |
July | 0.174120E+09 | 50098162.79 | 0.124022E+09 | 0.815657E+09 | 5175954.34 |
August | 0.177703E+09 | 53737567.12 | 0.123966E+09 | 0.837262E+09 | 3429976.03 |
September | 0.163873E+09 | 51409043.10 | 0.112464E+09 | 0.656767E+09 | 37199074.13 |
October | 0.150669E+09 | 48679733.69 | 0.101989E+09 | 0.521170E+09 | 98590852.32 |
November | 0.125683E+09 | 41286177.73 | 84396591.08 | 0.354814E+09 | 0.182244E+09 |
December | 0.108915E+09 | 33287399.47 | 75627364.87 | 0.233759E+09 | 0.269091E+09 |
Annual Sum or Average | 0.181626E+10 | 0.549037E+09 | 0.126722E+10 | 0.622859E+10 | 0.158900E+10 |
Minimum of Months | 0.108915E+09 | 33179113.69 | 75627364.87 | 0.220339E+09 | 3429976.03 |
Maximum of Months | 0.183273E+09 | 57879065.84 | 0.128331E+09 | 0.837262E+09 | 0.293495E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37447190.06 | 0.00 | 37447190.06 | 49625179.10 | 0.174933E+09 |
February | 38771160.50 | 0.00 | 38771160.50 | 65336877.54 | 0.142148E+09 |
March | 49317108.11 | 4220.58 | 49312887.53 | 0.112941E+09 | 0.127702E+09 |
April | 53944514.41 | 251104.59 | 53693409.82 | 0.170063E+09 | 88365308.22 |
May | 63470648.29 | 2762554.17 | 60708094.12 | 0.274970E+09 | 34510753.82 |
June | 65945518.42 | 4778059.02 | 61167459.39 | 0.307393E+09 | 17392849.83 |
July | 62180791.15 | 2501244.32 | 59679546.83 | 0.356363E+09 | 3031363.44 |
August | 57654044.63 | 921352.80 | 56732691.83 | 0.349314E+09 | 1732130.69 |
September | 50433376.11 | 23185.52 | 50410190.59 | 0.246448E+09 | 20987587.14 |
October | 46178622.83 | 0.00 | 46178622.83 | 0.178049E+09 | 56850152.55 |
November | 38364536.89 | 0.00 | 38364536.89 | 0.103448E+09 | 0.106098E+09 |
December | 34952106.77 | 0.00 | 34952106.77 | 55650306.66 | 0.159912E+09 |
Annual Sum or Average | 0.598660E+09 | 11241721.00 | 0.587418E+09 | 0.226960E+10 | 0.933664E+09 |
Minimum of Months | 34952106.77 | 0.00 | 34952106.77 | 49625179.10 | 1732130.69 |
Maximum of Months | 65945518.42 | 4778059.02 | 61167459.39 | 0.356363E+09 | 0.174933E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37445961.09 | 0.00 | 37445961.09 | 49623097.82 | 0.174932E+09 |
February | 38769911.79 | 0.00 | 38769911.79 | 65334658.26 | 0.142147E+09 |
March | 49315544.25 | 4220.38 | 49311323.86 | 0.112938E+09 | 0.127700E+09 |
April | 53942836.16 | 251092.82 | 53691743.34 | 0.170060E+09 | 88363598.04 |
May | 63468659.53 | 2762424.68 | 60706234.84 | 0.274967E+09 | 34509487.31 |
June | 65943419.39 | 4777835.07 | 61165584.32 | 0.307390E+09 | 17391849.64 |
July | 62178868.18 | 2501127.08 | 59677741.09 | 0.356360E+09 | 3031020.18 |
August | 57652292.29 | 921309.62 | 56730982.67 | 0.349312E+09 | 1731904.82 |
September | 50431845.07 | 23184.43 | 50408660.64 | 0.246446E+09 | 20986539.36 |
October | 46177190.70 | 0.00 | 46177190.70 | 0.178046E+09 | 56848294.30 |
November | 38363313.08 | 0.00 | 38363313.08 | 0.103446E+09 | 0.106096E+09 |
December | 34950959.33 | 0.00 | 34950959.33 | 55648352.00 | 0.159911E+09 |
Annual Sum or Average | 0.598641E+09 | 11241194.08 | 0.587400E+09 | 0.226957E+10 | 0.933648E+09 |
Minimum of Months | 34950959.33 | 0.00 | 34950959.33 | 49623097.82 | 1731904.82 |
Maximum of Months | 65943419.39 | 4777835.07 | 61165584.32 | 0.356360E+09 | 0.174932E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183592E+09 | 70406794.13 | 0.113185E+09 | 0.212139E+09 | 0.120448E+09 |
February | 0.201046E+09 | 82192340.77 | 0.118853E+09 | 0.237659E+09 | 0.107612E+09 |
March | 0.269075E+09 | 0.112920E+09 | 0.156155E+09 | 0.326240E+09 | 0.122436E+09 |
April | 0.306946E+09 | 0.136028E+09 | 0.170918E+09 | 0.379745E+09 | 0.118196E+09 |
May | 0.359970E+09 | 0.175037E+09 | 0.184933E+09 | 0.446951E+09 | 0.104587E+09 |
June | 0.363148E+09 | 0.184693E+09 | 0.178455E+09 | 0.449352E+09 | 97967048.02 |
July | 0.364004E+09 | 0.184687E+09 | 0.179316E+09 | 0.455063E+09 | 91729910.43 |
August | 0.346666E+09 | 0.170323E+09 | 0.176343E+09 | 0.431261E+09 | 92945968.24 |
September | 0.301058E+09 | 0.144416E+09 | 0.156642E+09 | 0.373823E+09 | 0.101667E+09 |
October | 0.261815E+09 | 0.122977E+09 | 0.138838E+09 | 0.321001E+09 | 0.119630E+09 |
November | 0.201375E+09 | 88114764.52 | 0.113260E+09 | 0.243332E+09 | 0.120027E+09 |
December | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 0.118717E+09 |
Annual Sum or Average | 0.332926E+10 | 0.153811E+10 | 0.179116E+10 | 0.407646E+10 | 0.131596E+10 |
Minimum of Months | 0.170570E+09 | 66313448.82 | 0.104256E+09 | 0.199890E+09 | 91729910.43 |
Maximum of Months | 0.364004E+09 | 0.184693E+09 | 0.184933E+09 | 0.455063E+09 | 0.122436E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 197.69 | 345.89 | 113.52 | 24.78 | 88.74 | 0.00 | 0.00 |
February | 261.60 | 311.22 | 129.59 | 28.07 | 101.53 | 0.00 | 0.00 |
March | 376.32 | 255.19 | 151.92 | 34.11 | 117.81 | 0.00 | 0.00 |
April | 515.65 | 185.99 | 166.93 | 35.11 | 131.82 | 0.00 | 0.00 |
May | 727.45 | 72.17 | 184.00 | 42.84 | 141.16 | 0.00 | 0.00 |
June | 809.66 | 36.00 | 192.30 | 48.35 | 143.95 | 0.00 | 0.00 |
July | 875.09 | 6.06 | 176.45 | 39.28 | 137.17 | 0.00 | 0.00 |
August | 886.01 | 3.83 | 175.74 | 40.81 | 134.93 | 0.00 | 0.00 |
September | 696.88 | 44.85 | 165.36 | 39.69 | 125.67 | 0.00 | 0.00 |
October | 522.10 | 116.05 | 146.99 | 36.35 | 110.64 | 0.00 | 0.00 |
November | 353.17 | 222.06 | 126.58 | 31.86 | 94.72 | 0.00 | 0.00 |
December | 213.94 | 318.18 | 107.43 | 24.86 | 82.57 | 0.00 | 0.00 |
Annual Sum or Average | 537.92 | 158.96 | 153.15 | 35.53 | 117.62 | 0.00 | 0.00 |
Minimum of Months | 197.69 | 3.83 | 107.43 | 24.78 | 82.57 | 0.00 | 0.00 |
Maximum of Months | 886.01 | 345.89 | 192.30 | 48.35 | 143.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.03 | 449.70 | 685.45 | 262.87 | 422.59 | 0.00 | 0.00 |
February | 982.38 | 444.82 | 831.04 | 339.75 | 491.29 | 0.00 | 0.00 |
March | 1218.04 | 457.12 | 1004.61 | 421.59 | 583.02 | 0.00 | 0.00 |
April | 1465.06 | 456.00 | 1184.20 | 524.80 | 659.41 | 0.00 | 0.00 |
May | 1668.72 | 390.47 | 1343.97 | 653.51 | 690.46 | 0.00 | 0.00 |
June | 1733.61 | 377.96 | 1401.04 | 712.55 | 688.48 | 0.00 | 0.00 |
July | 1699.01 | 342.47 | 1359.03 | 689.54 | 669.49 | 0.00 | 0.00 |
August | 1610.14 | 347.02 | 1294.30 | 635.91 | 658.39 | 0.00 | 0.00 |
September | 1442.22 | 392.23 | 1161.49 | 557.16 | 604.33 | 0.00 | 0.00 |
October | 1198.48 | 446.64 | 977.51 | 459.14 | 518.36 | 0.00 | 0.00 |
November | 938.78 | 463.06 | 776.91 | 339.95 | 436.96 | 0.00 | 0.00 |
December | 746.30 | 443.24 | 636.84 | 247.59 | 389.25 | 0.00 | 0.00 |
Annual Sum or Average | 1292.63 | 417.29 | 1055.70 | 487.73 | 567.97 | 0.00 | 0.00 |
Minimum of Months | 746.30 | 342.47 | 636.84 | 247.59 | 389.25 | 0.00 | 0.00 |
Maximum of Months | 1733.61 | 463.06 | 1401.04 | 712.55 | 690.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.529492E+09 | 0.926420E+09 | 0.304042E+09 | 66358227.38 | 0.237684E+09 | 0.00 | 0.00 |
February | 0.632859E+09 | 0.752911E+09 | 0.313512E+09 | 67899762.88 | 0.245613E+09 | 0.00 | 0.00 |
March | 0.100793E+10 | 0.683509E+09 | 0.406895E+09 | 91348434.22 | 0.315547E+09 | 0.00 | 0.00 |
April | 0.133656E+10 | 0.482085E+09 | 0.432675E+09 | 91009985.58 | 0.341665E+09 | 0.00 | 0.00 |
May | 0.194841E+10 | 0.193311E+09 | 0.492815E+09 | 0.114739E+09 | 0.378076E+09 | 0.00 | 0.00 |
June | 0.209863E+10 | 93301653.20 | 0.498434E+09 | 0.125314E+09 | 0.373120E+09 | 0.00 | 0.00 |
July | 0.234385E+10 | 16230301.74 | 0.472600E+09 | 0.105199E+09 | 0.367401E+09 | 0.00 | 0.00 |
August | 0.237308E+10 | 10252743.45 | 0.470713E+09 | 0.109318E+09 | 0.361395E+09 | 0.00 | 0.00 |
September | 0.180631E+10 | 0.116257E+09 | 0.428611E+09 | 0.102864E+09 | 0.325746E+09 | 0.00 | 0.00 |
October | 0.139839E+10 | 0.310833E+09 | 0.393693E+09 | 97359467.38 | 0.296334E+09 | 0.00 | 0.00 |
November | 0.915409E+09 | 0.575569E+09 | 0.328093E+09 | 82572355.45 | 0.245521E+09 | 0.00 | 0.00 |
December | 0.573026E+09 | 0.852216E+09 | 0.287733E+09 | 66574798.94 | 0.221158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169639E+11 | 0.501289E+10 | 0.482982E+10 | 0.112056E+10 | 0.370926E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529492E+09 | 10252743.45 | 0.287733E+09 | 66358227.38 | 0.221158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237308E+10 | 0.926420E+09 | 0.498434E+09 | 0.125314E+09 | 0.378076E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212138E+10 | 0.120447E+10 | 0.183592E+10 | 0.704068E+09 | 0.113185E+10 | 0.00 | 0.00 |
February | 0.237658E+10 | 0.107612E+10 | 0.201046E+10 | 0.821923E+09 | 0.118853E+10 | 0.00 | 0.00 |
March | 0.326239E+10 | 0.122436E+10 | 0.269075E+10 | 0.112920E+10 | 0.156155E+10 | 0.00 | 0.00 |
April | 0.379744E+10 | 0.118195E+10 | 0.306946E+10 | 0.136028E+10 | 0.170918E+10 | 0.00 | 0.00 |
May | 0.446951E+10 | 0.104585E+10 | 0.359970E+10 | 0.175037E+10 | 0.184933E+10 | 0.00 | 0.00 |
June | 0.449351E+10 | 0.979660E+09 | 0.363148E+10 | 0.184693E+10 | 0.178455E+10 | 0.00 | 0.00 |
July | 0.455062E+10 | 0.917285E+09 | 0.364004E+10 | 0.184687E+10 | 0.179316E+10 | 0.00 | 0.00 |
August | 0.431261E+10 | 0.929445E+09 | 0.346666E+10 | 0.170323E+10 | 0.176343E+10 | 0.00 | 0.00 |
September | 0.373823E+10 | 0.101666E+10 | 0.301058E+10 | 0.144416E+10 | 0.156642E+10 | 0.00 | 0.00 |
October | 0.321000E+10 | 0.119629E+10 | 0.261815E+10 | 0.122977E+10 | 0.138838E+10 | 0.00 | 0.00 |
November | 0.243331E+10 | 0.120026E+10 | 0.201375E+10 | 0.881148E+09 | 0.113260E+10 | 0.00 | 0.00 |
December | 0.199890E+10 | 0.118717E+10 | 0.170570E+10 | 0.663134E+09 | 0.104256E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.407645E+11 | 0.131595E+11 | 0.332926E+11 | 0.153811E+11 | 0.179116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199890E+10 | 0.917285E+09 | 0.170570E+10 | 0.663134E+09 | 0.104256E+10 | 0.00 | 0.00 |
Maximum of Months | 0.455062E+10 | 0.122436E+10 | 0.364004E+10 | 0.184693E+10 | 0.184933E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.73 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.25 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.73 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.16 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.89 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.77 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.47 | 23.16 | 3.85 | 24.13 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.01 | 24.10 | 3.89 | 24.32 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.67 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.65 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.61 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.83 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.01 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.73 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.01 | 24.10 | 3.95 | 24.32 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.53 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.25 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.80 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.14 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.72 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.53 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 21.97 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.35 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.39 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.78 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.12 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.02 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.53 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.35 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.44 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.73 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.73 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.04 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.94 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.23 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.43 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.81 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.81 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.94 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.20 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.04 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.10 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.85 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.13 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.23 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.13 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.20 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.10 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.85 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.09 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.85 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.740483E+09 | -608906532.8 | 0.00 | 0.00 | 744.00 | 0.00 | -131576000.0 | 58.99 | 0.00 | 0.00 |
February | 0.660806E+09 | -543794402.1 | 0.00 | 0.00 | 672.00 | 0.00 | -117011321.8 | 58.99 | 0.00 | 0.00 |
March | 0.718414E+09 | -590805465.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127608053.8 | 58.99 | 0.00 | 0.00 |
April | 0.613899E+09 | -493209807.7 | 0.00 | 0.00 | 720.00 | 0.00 | -120688810.7 | 58.99 | 0.00 | 0.00 |
May | 0.578962E+09 | -456696294.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122265803.8 | 58.99 | 0.00 | 0.00 |
June | 0.531910E+09 | -413932758.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117977370.0 | 58.99 | 0.00 | 0.00 |
July | 0.508779E+09 | -387617447.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121161277.3 | 58.99 | 0.00 | 0.00 |
August | 0.557178E+09 | -435316349.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121861802.0 | 58.99 | 0.00 | 0.00 |
September | 0.565845E+09 | -448184330.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117660395.4 | 58.99 | 0.00 | 0.00 |
October | 0.627379E+09 | -505179857.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122199282.6 | 58.99 | 0.00 | 0.00 |
November | 0.657275E+09 | -536758193.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120517116.7 | 58.99 | 0.00 | 0.00 |
December | 0.725535E+09 | -596889463.5 | 0.00 | 0.00 | 744.00 | 0.00 | -128645491.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.748646E+10 | -.601729E+10 | 8760.00 | -.146917E+10 | 58.99 | |||||
Minimum of Months | 0.508779E+09 | -608906532.8 | 0.00 | 0.00 | 672.00 | 0.00 | -131576000.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.740483E+09 | -387617447.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117011321.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | ||||||||||
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3920470.47 | 1469.44 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3920470.47 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3920470.47 | 1469.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.561046E+10 | 0.475564E+10 | 33136.67 | 30-JAN-06:01 | 22391.50 | 0.00 |
February | 0.00 | 0.00 | 0.690280E+10 | 0.575164E+10 | 34658.42 | 09-FEB-06:01 | 21849.43 | 0.00 |
March | 0.00 | 0.00 | 0.997555E+10 | 0.860825E+10 | 34568.07 | 29-MAR-05:01 | 22076.36 | 0.00 |
April | 0.00 | 0.00 | 0.121970E+11 | 0.103961E+11 | 34994.19 | 20-APR-05:01 | 21669.33 | 0.00 |
May | 0.00 | 0.00 | 0.174813E+11 | 0.147113E+11 | 36812.70 | 24-MAY-05:01 | 20432.81 | 0.00 |
June | 0.00 | 0.00 | 0.207797E+11 | 0.160390E+11 | 37318.66 | 08-JUN-05:01 | 19953.99 | 0.00 |
July | 0.00 | 0.00 | 0.238372E+11 | 0.174219E+11 | 36382.97 | 06-JUL-05:01 | 19201.97 | 0.00 |
August | 0.00 | 0.00 | 0.263847E+11 | 0.190375E+11 | 36382.97 | 31-AUG-05:01 | 20235.52 | 0.00 |
September | 0.00 | 0.00 | 0.211835E+11 | 0.155767E+11 | 37351.39 | 23-SEP-05:01 | 18958.68 | 0.00 |
October | 0.00 | 0.00 | 0.169957E+11 | 0.132713E+11 | 37332.63 | 07-OCT-05:01 | 20288.26 | 0.00 |
November | 0.00 | 0.00 | 0.125426E+11 | 0.992973E+10 | 36211.80 | 03-NOV-05:01 | 21666.10 | 0.00 |
December | 0.00 | 0.00 | 0.814849E+10 | 0.664450E+10 | 34195.32 | 06-DEC-06:01 | 21163.63 | 0.00 |
Annual Sum or Average | 0.182039E+12 | 0.142144E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.561046E+10 | 0.475564E+10 | 33136.67 | 18958.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.263847E+11 | 0.190375E+11 | 37351.39 | 22391.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.823953E+10 | 0.696514E+10 | 37554.64 | 29-JAN-15:20 | 27559.89 | 0.00 |
February | 0.00 | 0.00 | 0.142310E+11 | 0.120365E+11 | 125406.74 | 05-FEB-13:53 | 111024.26 | 0.00 |
March | 0.00 | 0.00 | 0.271671E+11 | 0.239066E+11 | 118622.35 | 26-MAR-13:42 | 118622.35 | 0.00 |
April | 0.00 | 0.00 | 0.459843E+11 | 0.396161E+11 | 141534.11 | 30-APR-15:42 | 94292.14 | 0.00 |
May | 0.00 | 0.00 | 0.842097E+11 | 0.718186E+11 | 141632.44 | 29-MAY-13:42 | 92528.41 | 0.00 |
June | 0.00 | 0.00 | 0.104956E+12 | 0.815285E+11 | 152407.71 | 19-JUN-05:01 | 80427.55 | 0.00 |
July | 0.00 | 0.00 | 0.127708E+12 | 0.962838E+11 | 148337.34 | 06-JUL-05:01 | 84057.41 | 0.00 |
August | 0.00 | 0.00 | 0.134662E+12 | 0.998565E+11 | 153052.37 | 08-AUG-05:01 | 78127.34 | 0.00 |
September | 0.00 | 0.00 | 0.102674E+12 | 0.762483E+11 | 147201.49 | 08-SEP-18:23 | 82645.10 | 0.00 |
October | 0.00 | 0.00 | 0.708236E+11 | 0.561411E+11 | 140953.05 | 07-OCT-17:06 | 88002.11 | 0.00 |
November | 0.00 | 0.00 | 0.370893E+11 | 0.299861E+11 | 129748.40 | 11-NOV-15:32 | 109584.86 | 0.00 |
December | 0.00 | 0.00 | 0.156108E+11 | 0.127914E+11 | 84304.29 | 03-DEC-13:23 | 72966.75 | 0.00 |
Annual Sum or Average | 0.773356E+12 | 0.607179E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.823953E+10 | 0.696514E+10 | 37554.64 | 27559.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134662E+12 | 0.998565E+11 | 153052.37 | 118622.35 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157345E+10 | 0.35 | 1586.26 | 02-JAN-14:40 | 0.93 |
February | 0.145432E+10 | 0.36 | 1586.26 | 01-FEB-12:10 | 0.93 |
March | 0.171827E+10 | 0.39 | 1586.26 | 01-MAR-08:15 | 0.92 |
April | 0.160821E+10 | 0.40 | 1586.26 | 01-APR-07:35 | 0.93 |
May | 0.172521E+10 | 0.45 | 1586.26 | 01-MAY-06:40 | 0.92 |
June | 0.174530E+10 | 0.48 | 1586.26 | 01-JUN-12:40 | 0.93 |
July | 0.175708E+10 | 0.57 | 1586.26 | 01-JUL-09:27 | 0.92 |
August | 0.188969E+10 | 0.60 | 1586.26 | 01-AUG-06:20 | 0.92 |
September | 0.170634E+10 | 0.48 | 1586.26 | 01-SEP-10:15 | 0.93 |
October | 0.165336E+10 | 0.42 | 1586.26 | 02-OCT-14:40 | 0.93 |
November | 0.154534E+10 | 0.38 | 1586.26 | 01-NOV-12:30 | 0.92 |
December | 0.158519E+10 | 0.36 | 1586.26 | 01-DEC-09:23 | 0.93 |
Annual Sum or Average | 0.199618E+11 | 0.44 | |||
Minimum of Months | 0.145432E+10 | 0.35 | 1586.26 | 0.92 | |
Maximum of Months | 0.188969E+10 | 0.60 | 1586.26 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.949430E+10 | 0.57 | 9579.38 | 02-JAN-13:45 | 1.53 |
February | 0.877663E+10 | 0.60 | 9579.38 | 01-FEB-11:13 | 1.53 |
March | 0.104580E+11 | 0.71 | 9579.38 | 02-MAR-15:03 | 1.52 |
April | 0.103873E+11 | 0.92 | 9579.38 | 01-APR-07:40 | 1.52 |
May | 0.124561E+11 | 1.27 | 9579.38 | 01-MAY-13:30 | 1.53 |
June | 0.130898E+11 | 1.32 | 9579.38 | 01-JUN-07:40 | 1.53 |
July | 0.140480E+11 | 1.32 | 9579.38 | 03-JUL-07:20 | 1.53 |
August | 0.146171E+11 | 1.33 | 9579.38 | 04-AUG-16:50 | 1.52 |
September | 0.127464E+11 | 1.31 | 9579.38 | 01-SEP-09:10 | 1.52 |
October | 0.114577E+11 | 1.19 | 9579.38 | 02-OCT-17:00 | 1.52 |
November | 0.959858E+10 | 0.78 | 9579.38 | 01-NOV-13:20 | 1.52 |
December | 0.953456E+10 | 0.59 | 9579.38 | 01-DEC-16:40 | 1.53 |
Annual Sum or Average | 0.136664E+12 | 0.99 | |||
Minimum of Months | 0.877663E+10 | 0.57 | 9579.38 | 1.52 | |
Maximum of Months | 0.146171E+11 | 1.33 | 9579.38 | 1.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.03 | 2.97 |
February | 1.10 | 1.14 |
March | 2.05 | 0.00 |
April | 2.49 | 0.01 |
May | 2.90 | 0.00 |
June | 4.03 | 0.01 |
July | 4.95 | 0.03 |
August | 4.64 | 0.02 |
September | 3.42 | 0.02 |
October | 3.23 | 0.00 |
November | 2.74 | 0.02 |
December | 0.92 | 0.45 |
Annual Sum or Average | 33.49 | 0.15 |
Minimum of Months | 0.92 | 0.00 |
Maximum of Months | 4.95 | 2.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.92 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 1.06 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.92 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 18.30 | 0.00 |
February | 15.92 | 0.00 |
March | 10.54 | 0.00 |
April | 4.62 | 0.00 |
May | 5.81 | 0.00 |
June | 3.00 | 0.00 |
July | 0.83 | 0.00 |
August | 0.63 | 0.00 |
September | 1.53 | 0.00 |
October | 1.93 | 0.00 |
November | 3.17 | 0.00 |
December | 12.79 | 0.00 |
Annual Sum or Average | 79.07 | |
Minimum of Months | 0.63 | 0.00 |
Maximum of Months | 18.30 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.307547E+10 | 6085378.18 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.331853E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.447820E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.511878E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.706146E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.810227E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.913454E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.100429E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.803458E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.656537E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.501933E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.376824E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.737197E+11 | 6085378.18 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.307547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100429E+11 | 6085378.18 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119211E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130437E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.188449E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.251495E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.409137E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.484150E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.577202E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.605057E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.467301E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.344054E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.211144E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141682E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392932E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119211E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.605057E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157345E+10 | 0.561046E+10 | 3920470.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145432E+10 | 0.690280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171827E+10 | 0.997555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160821E+10 | 0.121970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172521E+10 | 0.174813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174530E+10 | 0.207797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175708E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188969E+10 | 0.263847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170634E+10 | 0.211835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165336E+10 | 0.169957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154534E+10 | 0.125426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158519E+10 | 0.814849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199618E+11 | 0.182039E+12 | 3920470.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145432E+10 | 0.561046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188969E+10 | 0.263847E+11 | 3920470.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.949430E+10 | 0.823953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877663E+10 | 0.142310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104580E+11 | 0.271671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103873E+11 | 0.459843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124561E+11 | 0.842097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130898E+11 | 0.104956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140480E+11 | 0.127708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146171E+11 | 0.134662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127464E+11 | 0.102674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114577E+11 | 0.708236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.959858E+10 | 0.370893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.953456E+10 | 0.156108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136664E+12 | 0.773356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.877663E+10 | 0.823953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146171E+11 | 0.134662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157345E+10 | 0.00 | 0.00 | 0.00 | 0.150202E+10 | 0.00 | 6085378.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145432E+10 | 0.00 | 0.00 | 0.00 | 0.186421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171827E+10 | 0.00 | 0.00 | 0.00 | 0.275993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160821E+10 | 0.00 | 0.00 | 0.00 | 0.351056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172521E+10 | 0.00 | 0.00 | 0.00 | 0.533626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174530E+10 | 0.00 | 0.00 | 0.00 | 0.635697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175708E+10 | 0.00 | 0.00 | 0.00 | 0.737746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188969E+10 | 0.00 | 0.00 | 0.00 | 0.815320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170634E+10 | 0.00 | 0.00 | 0.00 | 0.632824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165336E+10 | 0.00 | 0.00 | 0.00 | 0.491200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154534E+10 | 0.00 | 0.00 | 0.00 | 0.347400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158519E+10 | 0.00 | 0.00 | 0.00 | 0.218304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199618E+11 | 0.00 | 0.00 | 0.00 | 0.537579E+11 | 0.00 | 6085378.18 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.145432E+10 | 0.00 | 0.00 | 0.00 | 0.150202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188969E+10 | 0.00 | 0.00 | 0.00 | 0.815320E+10 | 0.00 | 6085378.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.949430E+10 | 0.00 | 0.00 | 0.00 | 0.242675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877663E+10 | 0.00 | 0.00 | 0.00 | 0.426706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104580E+11 | 0.00 | 0.00 | 0.00 | 0.838689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103873E+11 | 0.00 | 0.00 | 0.00 | 0.147623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124561E+11 | 0.00 | 0.00 | 0.00 | 0.284576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130898E+11 | 0.00 | 0.00 | 0.00 | 0.353252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140480E+11 | 0.00 | 0.00 | 0.00 | 0.436723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146171E+11 | 0.00 | 0.00 | 0.00 | 0.458886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127464E+11 | 0.00 | 0.00 | 0.00 | 0.339837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114577E+11 | 0.00 | 0.00 | 0.00 | 0.229478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.959858E+10 | 0.00 | 0.00 | 0.00 | 0.115158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.953456E+10 | 0.00 | 0.00 | 0.00 | 0.463368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136664E+12 | 0.00 | 0.00 | 0.00 | 0.256268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.877663E+10 | 0.00 | 0.00 | 0.00 | 0.242675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146171E+11 | 0.00 | 0.00 | 0.00 | 0.458886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110649E+09 | 0.242445E+09 | 0.00 | 5480116.31 | 0.00 | 7319332.42 | 0.243850E+09 | 0.00 | 0.16 |
February | 61702095.03 | 0.446139E+09 | 0.00 | 4375398.46 | 0.00 | 0.00 | 0.105401E+09 | 0.00 | 0.17 |
March | 30330883.73 | 0.841843E+09 | 0.00 | 5467902.73 | 0.00 | 0.00 | 92679385.32 | 0.00 | 0.18 |
April | 0.00 | 0.148259E+10 | 0.00 | 5319683.46 | 0.00 | 0.00 | 42973236.41 | 0.00 | 0.17 |
May | 0.00 | 0.268577E+10 | 0.00 | 2752937.24 | 0.00 | 0.00 | 3436516.46 | 0.00 | 0.18 |
June | 0.00 | 0.396247E+10 | 0.00 | 1035742.52 | 0.00 | 0.00 | 263138.53 | 0.00 | 0.19 |
July | 0.00 | 0.519505E+10 | 0.00 | 1081242.04 | 0.00 | 0.00 | 771618.67 | 0.00 | 0.18 |
August | 0.00 | 0.582214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.428880E+10 | 0.00 | 839793.57 | 0.00 | 0.00 | 307146.87 | 0.00 | 0.18 |
October | 0.00 | 0.283564E+10 | 0.00 | 1567806.34 | 0.00 | 0.00 | 4052445.23 | 0.00 | 0.17 |
November | 0.00 | 0.170843E+10 | 0.00 | 3035750.51 | 0.00 | 0.00 | 10579193.37 | 0.00 | 0.16 |
December | 43978719.73 | 0.651347E+09 | 0.00 | 4336028.71 | 0.00 | 0.00 | 99983631.94 | 0.00 | 0.16 |
Annual Sum or Average | 0.246661E+09 | 0.301627E+11 | 0.00 | 35292401.88 | 0.00 | 7319332.42 | 0.604297E+09 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.242445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.110649E+09 | 0.582214E+10 | 0.00 | 5480116.31 | 0.00 | 7319332.42 | 0.243850E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136915E+10 | 0.146989E+09 | 0.00 | 5314148.66 | 7168393.98 | 0.00 | 0.403154E+09 | 0.00 | 0.16 |
February | 0.759675E+09 | 0.515867E+09 | 0.00 | 9117776.63 | 5726414.16 | 0.00 | 0.369193E+09 | 0.00 | 0.17 |
March | 0.553096E+09 | 0.147425E+10 | 0.00 | 9758896.28 | 294086.94 | 0.00 | 0.316920E+09 | 0.00 | 0.18 |
April | 0.228941E+09 | 0.333057E+10 | 0.00 | 5022456.18 | 0.00 | 0.00 | 0.241826E+09 | 0.00 | 0.19 |
May | 0.00 | 0.795201E+10 | 0.00 | 1892671.42 | 0.00 | 0.00 | 42843366.67 | 0.00 | 0.21 |
June | 0.00 | 0.126148E+11 | 0.00 | 368987.30 | 0.00 | 0.00 | 2569192.98 | 0.00 | 0.23 |
July | 0.00 | 0.178533E+11 | 0.00 | 621899.14 | 0.00 | 0.00 | 569633.77 | 0.00 | 0.24 |
August | 0.00 | 0.194833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.135946E+11 | 0.00 | 36411.62 | 0.00 | 0.00 | 220182.85 | 0.00 | 0.23 |
October | 0.00 | 0.766406E+10 | 0.00 | 1654473.38 | 0.00 | 0.00 | 51685566.17 | 0.00 | 0.20 |
November | 0.134939E+09 | 0.354681E+10 | 0.00 | 1470965.99 | 0.00 | 0.00 | 76421592.63 | 0.00 | 0.17 |
December | 0.756474E+09 | 0.880273E+09 | 0.00 | 5582298.14 | 8783867.37 | 0.00 | 0.307200E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.380227E+10 | 0.890568E+11 | 0.00 | 40840984.73 | 21972762.45 | 0.00 | 0.181260E+10 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.146989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.136915E+10 | 0.194833E+11 | 0.00 | 9758896.28 | 8783867.37 | 0.00 | 0.403154E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |