Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 908.05 | 187.80 | 187.80 |
Net Site Energy | 908.05 | 187.80 | 187.80 |
Total Source Energy | 2737.85 | 566.24 | 566.24 |
Net Source Energy | 2737.85 | 566.24 | 566.24 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 66.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 52.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 841.83 | 66.22 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 66.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 51.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.07 | 13.70 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 174.11 | 13.70 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.07 | 13.70 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 174.11 | 13.70 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 841.826 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 841.826 | 100.00 |
Total On-Site and Utility Electric Sources | 841.826 | 100.00 |
Total Electricity End Uses | 841.826 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.33 |
Time Setpoint Not Met During Occupied Cooling | 4.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 218.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-12:00 | 03-JAN-06:19 | - | - | - | 26-JUN-11:30 |
Heating | 0.00 | 27783.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13712.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6389.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1745.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 67579.49 | 27783.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 27783.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13712.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4084.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1745.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 71.79 | 0.00 | 0.00 | 0.00 |
Cooling | 61.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2666.06 | 71.79 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.85 | 0.00 | 0.00 | 0.00 |
Cooling | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 551.39 | 14.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.85 | 0.00 | 0.00 | 0.00 |
Cooling | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 551.39 | 14.85 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.19 |
ZONE2 FINE STORAGE DIRECT AIR | 2.49 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.23 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.23 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 50196.65 |
PSZ-OFFICE HEATING COIL | 29320.49 |
PSZ-FINE STORAGE HEATING COIL | 77241.82 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 50196.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.00 | 1.19 |
PSZ-FINE STORAGE | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 1.00 | 1.00 | 2.49 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.19 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.49 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 1.19 | 19716.58 | 29320.49 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.49 | 2.49 | 2.49 | 2.49 | 49516.07 | 77241.82 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.19 | 0.595540 | 1.19 | 19716.60 | 19716.58 | 9858.29 | 19716.58 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.49 | 1.25 | 2.49 | 46805.32 | 49516.07 | 24758.03 | 49516.07 | 0.737157 | 0.737160 | 0.737160 | 0.737160 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.19 | 1357.96 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.49 | 2726.31 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.61 | 28 | 1 | VerySmooth | 5.835 | 0.610 | 0.474 | 0.611 |
2 | SKYLIGHT_U_1.02_SHGC_0.61 | 29 | 1 | VerySmooth | 5.779 | 0.610 | 0.474 | 0.611 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47380 | 6.33198E-002 | 6.33198E-002 | 0.61000 | 0.13062 | 0.15121 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47380 | 6.63306E-002 | 6.63306E-002 | 0.61000 | 0.13062 | 0.15121 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11841.02124 | 14209.22549 | 0.99257 | 1.19108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.20219E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8377.66624 | 10053.19949 | 0.23949 | 0.28738 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 31768.11084 | 38121.73301 | 2.07576 | 2.49091 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.20219E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 21778.14289 | 26133.77146 | 0.52471 | 0.62965 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30000 | 8.20219E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 41830.54182 | 50196.65018 | 1.02627 | 1.23152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17744.50 | 1.19108 | 1.19108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8940.29 | 0.28738 | 0.28738 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 45415.85 | 2.49091 | 2.49091 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 23217.68 | 0.62965 | 0.62965 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19108 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.49091 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23152 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.23152 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 50196.65136 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 50196.65018 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19108 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19108 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19108 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19108 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19108 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.19108 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.49091 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.49091 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.49091 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.49091 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.49091 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.49091 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.19108 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.49091 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19108 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19108 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19108 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19108 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19108 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19108 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59554 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19108 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19716.60321 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19716.58000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9858.29000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19716.58000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19716.58000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29320.49006 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19108 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1357.96064 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29320.49006 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.49091 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.49091 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.49091 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.49091 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.49091 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.49091 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24546 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.49091 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 46805.31867 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 49516.07000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24758.03500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 49516.07000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73716 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73716 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73716 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73716 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49516.07000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 77241.81537 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.49091 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2726.31247 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 77241.81537 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18792.3 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 47581.9 | 13.73 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.9454300038E-002 | 2.4226472786E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1226094008 | 0.1584216608 | Pass | Pass | 0.4569076208 | 2.6973043472 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.6419945067E-002 | 3.8633201397E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.61 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.610 | 0.611 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.61 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.610 | 0.611 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.61 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.610 | 0.611 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.61 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.610 | 0.611 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.570 | 0.571 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.610 | 0.611 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.564 | 0.565 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.75 | 83.75 | 123.53 | |
Exterior Lighting Total | 7857.24 | 123.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19716.58 | 15746.84 | 3969.74 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49516.07 | 36501.27 | 13014.80 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18792.3 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 47581.9 | 13.73 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 50196.65 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29320.49 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 77241.82 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.23 | 114.42 | 92.91 | 1.00 | 3.94 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.19 | 1357.96 | 1140.11 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.49 | 2726.31 | 1094.51 | 1.00 | 1.26 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11841.02 | 14209.23 | 59.98 | 0.993 | 1.191 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00810 | 30.29 | 0.00820 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 31768.11 | 38121.73 | 27.36 | 2.076 | 2.491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00802 | 31.30 | 0.00820 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00385 | 31.30 | 0.00820 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8377.67 | 10053.20 | 42.44 | 0.239 | 0.287 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00774 | 3.80 | 0.00506 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 21778.14 | 26133.77 | 18.76 | 0.525 | 0.630 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00666 | 3.80 | 0.00506 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 41830.54 | 50196.65 | 15.66 | 1.026 | 1.232 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00778 | 3.80 | 0.00506 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.19 | 1.19 | 0.29 | 0.29 | 1.1911 | 1.1911 | 1.1911 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.49 | 2.49 | 0.63 | 0.63 | 2.4909 | 2.4909 | 2.4909 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 50196.651 | 50196.651 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 50196.65 | 50196.65 | 1.231523 | 5.90 | 5.90 | 0.00597959 | 43.33 | 26.86 | 0.01600000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00777570 | 100.0000 | 50196.65 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19716.580 | 0.000 | 1.191080 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 19716.58 | 19328.28 | 1.191080 | 24.55 | 16.04 | 0.00811366 | 12.00 | 11.09 | 0.00800000 | 30.29 | 0.00820219 | 18.07 | 10.1030 | 23.90 | 0.00810372 | 43.0982 | 11841.02 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29320.490 | 29320.490 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29320.49 | 29320.49 | 1.191079 | 13.80 | 10.42 | 0.00661696 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.1031 | 21.10 | 0.00773966 | 48.8261 | 8377.67 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 49516.070 | 0.000 | 2.490910 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 49516.07 | 49179.79 | 2.490910 | 27.35 | 16.96 | 0.00804628 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00820219 | 18.40 | 14.2088 | 26.70 | 0.00802046 | 36.1154 | 31768.11 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 77241.815 | 77241.815 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 77241.82 | 77241.82 | 2.490908 | 8.95 | 7.26 | 0.00575930 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 14.2088 | 15.56 | 0.00665898 | 59.5848 | 21778.14 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 50196.651 | 50196.651 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1818 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.231523 | 1.45538703 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 50196.65 | 50196.65 | 1.0000 | 1.45538703 | 1.231523 | 5.90 | 5.90 | 0.00597959 | 20949.2 | 43.33 | 26.86 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50196.65 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00777570 | 10.00 | 0.00777570 | 100.0000 | 50196.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19716.580 | 0.000 | 1.191080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9229 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 19716.58 | 19328.28 | 1.0000 | 1.40759293 | 1.191080 | 24.55 | 16.04 | 0.00811366 | 45326.1 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19716.58 | 30.29 | 0.00820219 | 18.07 | 0.12033533 | 10.1030 | 23.90 | 0.00810372 | 23.90 | 0.00810372 | 43.0982 | 11841.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29320.490 | 29320.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.191079 | 1.40759143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29320.49 | 29320.49 | 1.0000 | 1.40759143 | 1.191079 | 13.80 | 10.42 | 0.00661696 | 30588.4 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29320.49 | 3.80 | 0.00505843 | 3.80 | 0.12033533 | 10.1031 | 21.01 | 0.00773966 | 21.10 | 0.00773966 | 48.8261 | 8377.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49516.070 | 0.000 | 2.490910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7976 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 49516.07 | 49179.79 | 1.0000 | 2.94370429 | 2.490910 | 27.35 | 16.96 | 0.00804628 | 48018.3 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49516.07 | 31.30 | 0.00820219 | 18.40 | 0.35392745 | 14.2088 | 26.70 | 0.00802046 | 26.70 | 0.00802046 | 36.1154 | 31768.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 77241.815 | 77241.815 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.490908 | 2.94370190 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 77241.82 | 77241.82 | 1.0000 | 2.94370190 | 2.490908 | 8.95 | 7.26 | 0.00575930 | 23491.5 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77241.82 | 3.80 | 0.00505843 | 3.80 | 0.35392745 | 14.2088 | 15.56 | 0.00665898 | 15.56 | 0.00665898 | 59.5848 | 21778.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.19 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.49 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1580.33 | 1793.67 | 218.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 1580.33 | 1793.67 | 218.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 5.33 | 69.17 | 5.33 | 4.67 |
ZONE2 FINE STORAGE | 2.50 | 3.50 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.83 | 72.67 | 5.33 | 4.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 1.640 | 0.374 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
Electricity:Building | 621.74 | 4992.32 | 01-JAN-00:10 | 48037.94 | 19-JUL-10:10 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 422.14 | 2759.73 | 01-JAN-00:10 | 33963.13 | 19-JUL-10:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.40 | 483.00 | 05-JAN-06:10 | 1805.18 | 13-FEB-12:20 |
WaterSystems:Electricity | 25.40 | 483.00 | 05-JAN-06:10 | 1805.18 | 13-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 25.40 | 483.00 | 05-JAN-06:10 | 1805.18 | 13-FEB-12:20 |
Fans:Electricity | 52.13 | 0.00 | 01-JAN-00:10 | 6389.57 | 17-AUG-14:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.50 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-OCT-13:30 |
Ventilation (simple):Fans:Electricity | 0.50 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-OCT-13:30 |
ElectricityPurchased:Facility | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
ElectricityPurchased:Plant | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
Cogeneration:ElectricityPurchased | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
ElectricityNet:Plant | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
Cogeneration:ElectricityNet | 841.83 | 5475.32 | 01-JAN-07:00 | 67579.49 | 29-SEP-13:00 |
Electricity:HVAC | 71.16 | 0.00 | 01-JAN-00:10 | 18603.96 | 16-OCT-11:20 |
General:Fans:Electricity | 51.63 | 0.00 | 01-JAN-00:10 | 4084.27 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 19.52 | 0.00 | 01-JAN-00:10 | 14519.69 | 16-OCT-11:20 |
ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:00 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:00 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 66.22 | 2000.00 | 12-APR-17:20 | 27783.16 | 03-JAN-06:20 |
Gas:HVAC | 66.22 | 2000.00 | 12-APR-17:20 | 27783.16 | 03-JAN-06:20 |
Heating:Gas | 66.22 | 2000.00 | 12-APR-17:20 | 27783.16 | 03-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 176.42 | 0.00 | 01-JAN-00:10 | 76221.94 | 16-OCT-12:00 |
EnergyTransfer:Building | 101.47 | 0.00 | 01-JAN-00:10 | 33221.13 | 16-OCT-12:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 50.30 | 0.00 | 01-JAN-00:10 | 13473.28 | 03-JAN-06:10 |
Heating:EnergyTransfer | 7.80 | 0.00 | 01-JAN-00:10 | 18553.04 | 03-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.00 | 0.00 | 01-JAN-00:10 | 13473.28 | 03-JAN-06:10 |
Cooling:EnergyTransfer | 93.67 | 0.00 | 01-JAN-00:10 | 33221.13 | 16-OCT-12:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 47.30 | 0.00 | 01-JAN-00:10 | 11051.41 | 26-MAY-17:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 51.17 | 0.00 | 01-JAN-00:10 | 23662.09 | 30-SEP-13:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 4.80 | 0.00 | 01-JAN-00:10 | 15634.22 | 03-JAN-02:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 46.37 | 0.00 | 01-JAN-00:10 | 23662.09 | 30-SEP-13:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 74.95 | 0.00 | 01-JAN-00:10 | 45660.86 | 18-AUG-14:40 |
HeatingCoils:EnergyTransfer | 2.12 | 0.00 | 01-JAN-00:10 | 18042.49 | 03-JAN-06:20 |
CoolingCoils:EnergyTransfer | 72.82 | 0.00 | 01-JAN-00:10 | 45660.86 | 18-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 3.001 | -47.295 | 0.000 | 0.000 | 3.631 | 30.994 | 31.946 | 27.676 | 0.000 | 0.216 | 0.000 | 0.000 | -11.974 | 0.000 | -12.384 | -25.812 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 4.802 | -46.371 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.391 | 0.001 | 0.000 | 0.000 | 0.000 | -69.141 | -26.337 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 46.340 | 0.000 | 5.334 | 0.012 | 0.000 | -20.264 | 0.000 | -345.222 | -107.834 |
Total Facility | 0.000 | 0.000 | 7.803 | -93.667 | 0.000 | 0.000 | 3.631 | 481.960 | 139.282 | 74.016 | 0.000 | 5.941 | 0.013 | 0.000 | -32.237 | 0.000 | -426.747 | -159.983 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-JUL-16:19 | 0.00 | 0.00 | 0.00 | -23989.88 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 5394.35 | 0.00 | 0.00 | 17562.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -49689.02 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 48489.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-17:41 | 0.00 | 0.00 | 0.00 | -68389.70 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 3347.80 | 0.00 | 0.00 | 58697.67 | 0.00 | -389.80 | 0.00 | -308.31 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:01 | 0.00 | 0.00 | 29604.51 | 0.00 | 0.00 | 0.00 | 54.38 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1117.95 | 0.00 | -1283.36 | -28417.77 |
ZONE2 FINE STORAGE | 30-MAR-05:07 | 0.00 | 0.00 | 60628.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6547.50 | -55281.07 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-MAR-05:07 | 0.00 | 0.00 | 67586.55 | 0.00 | 0.00 | 0.00 | 53.87 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2353.62 | 0.00 | -32400.65 | -40055.98 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1911 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1911 | 0.1010 | 1.0000 | 0.1203 | 0.1010 | ||
PSZ-FINE STORAGE | 2.4909 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4909 | 0.1421 | 1.0000 | 0.3539 | 0.1421 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1911 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1911 | 1.0000 | 1.0000 | 0.1203 | 0.1010 | ||
PSZ-FINE STORAGE | 2.4909 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4909 | 1.0000 | 1.0000 | 0.3539 | 0.1421 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1911 | 1.1911 | 1.1911 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4909 | 2.4909 | 2.4909 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1911 | 1.1911 | 1.1911 | 1.1911 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4909 | 2.4909 | 2.4909 | 2.4909 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1911 | 1.1911 | 1.1911 | 0.1203 | 0.4187 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4909 | 2.4909 | 2.4909 | 0.3539 | 0.5621 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1911 | 1.1911 | 1.1911 | 1.1911 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4909 | 2.4909 | 2.4909 | 2.4909 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 5.33 |
Number of hours cooling loads not met | 4.67 |
Number of hours not met | 10.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 66.22 | 27783.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 19.52 | 14519.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.53 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.50 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.63 | 4084.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.40 | 1805.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 841.83 |
Natural Gas | 0.00 | 66.22 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 908.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 4.04 |
Fans (All) | 10.78 |
Service Water Heating | 5.25 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 174.11 |
Subtotal | 174.11 |
Natural Gas [MJ/m2] | |
Space Heating | 13.70 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 13.70 |
Subtotal | 13.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 53.08 |
Space Heating | 7.29 |
Space Cooling | 2.15 |
Fans (All) | 5.74 |
Service Water Heating | 2.80 |
Receptacle Equipment | 15.34 |
Miscellaneous | 13.60 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.688073E+10 |
February | 0.000 | 0.520940E+10 |
March | 0.000 | 0.601520E+10 |
April | 0.000 | 0.521868E+10 |
May | 0.000 | 0.535716E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535680E+10 |
November | 0.000 | 0.529604E+10 |
December | 0.000 | 0.580882E+10 |
Annual Sum or Average | 0.662244E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.688073E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104942E+10 | 4260.45 | 21-JAN-15:30 | 14.00 | 10.94 | 0.236100E+09 | 301.61 | 18-JAN-15:00 | 22.00 | 15.38 |
February | 0.961310E+09 | 4407.01 | 03-FEB-15:10 | 22.67 | 9.05 | 0.218892E+09 | 301.64 | 01-FEB-13:50 | 19.83 | 15.74 |
March | 0.130109E+10 | 16422.59 | 22-MAR-17:15 | 17.33 | 15.23 | 0.255940E+09 | 301.60 | 24-MAR-14:30 | 18.50 | 15.66 |
April | 0.334385E+10 | 20969.73 | 28-APR-17:10 | 14.67 | 11.89 | 0.246465E+09 | 301.62 | 13-APR-13:30 | 20.50 | 15.06 |
May | 0.411464E+10 | 22102.82 | 26-MAY-17:15 | 15.33 | 10.33 | 0.257796E+09 | 301.65 | 24-MAY-10:00 | 21.00 | 15.41 |
June | 0.615988E+10 | 21975.64 | 05-JUN-00:02 | 13.83 | 12.17 | 0.258731E+09 | 301.61 | 03-JUN-15:09 | 19.00 | 14.24 |
July | 0.805330E+10 | 23991.56 | 04-JUL-16:19 | 20.33 | 15.75 | 0.248879E+09 | 301.64 | 25-JUL-15:20 | 23.67 | 19.20 |
August | 0.821096E+10 | 20811.50 | 28-AUG-00:01 | 15.08 | 14.77 | 0.268805E+09 | 301.64 | 15-AUG-15:00 | 23.00 | 19.54 |
September | 0.604277E+10 | 20706.65 | 05-SEP-00:02 | 14.83 | 13.63 | 0.248867E+09 | 301.63 | 09-SEP-13:30 | 23.00 | 18.41 |
October | 0.507344E+10 | 21185.65 | 16-OCT-00:01 | 21.67 | 10.86 | 0.248087E+09 | 301.65 | 18-OCT-12:20 | 23.67 | 17.92 |
November | 0.172377E+10 | 4649.05 | 18-NOV-15:10 | 23.83 | 14.19 | 0.234297E+09 | 301.63 | 30-NOV-15:09 | 20.50 | 12.90 |
December | 0.126181E+10 | 4598.63 | 05-DEC-15:20 | 24.33 | 12.94 | 0.240028E+09 | 301.62 | 20-DEC-14:50 | 19.20 | 11.86 |
Annual Sum or Average | 0.472962E+11 | 0.296289E+10 | ||||||||
Minimum of Months | 0.961310E+09 | 4260.45 | 13.83 | 9.05 | 0.218892E+09 | 301.60 | 18.50 | 11.86 | ||
Maximum of Months | 0.821096E+10 | 23991.56 | 24.33 | 15.75 | 0.268805E+09 | 301.65 | 23.67 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262756E+09 | 7122.77 | 24-JAN-07:10 | 13.67 | 10.11 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.272888E+09 | 7168.90 | 28-FEB-07:10 | 11.33 | 9.16 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.562920E+09 | 10468.96 | 10-MAR-07:10 | 10.67 | 7.38 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.209375E+10 | 47249.77 | 30-APR-15:31 | 22.33 | 16.10 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.247741E+10 | 13660.73 | 03-MAY-13:00 | 24.00 | 15.03 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.623018E+10 | 45240.25 | 25-JUN-13:51 | 22.00 | 16.83 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.118458E+11 | 49693.06 | 04-JUL-16:51 | 19.00 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.115683E+11 | 44038.64 | 19-AUG-18:00 | 23.00 | 17.25 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.608494E+10 | 46548.82 | 03-SEP-12:41 | 22.00 | 16.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.431233E+10 | 45701.80 | 15-OCT-17:01 | 26.33 | 14.08 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.339949E+09 | 7056.84 | 09-NOV-07:10 | 14.67 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.320033E+09 | 8043.19 | 27-DEC-07:10 | 9.50 | 2.95 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.463712E+11 | 0.00 | ||||||||
Minimum of Months | 0.262756E+09 | 7056.84 | 9.50 | 2.95 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.118458E+11 | 49693.06 | 26.33 | 17.25 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 | 14.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.43 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775261E+09 | 29604.66 | 09-JAN-06:01 | 2.17 |
February | 0.420622E+09 | 29146.08 | 28-FEB-06:01 | 10.17 |
March | 0.587731E+09 | 29594.44 | 30-MAR-05:01 | 4.97 |
April | 0.141218E+09 | 29306.33 | 01-APR-05:01 | 7.83 |
May | 0.111707E+09 | 1816.29 | 15-MAY-06:15 | 11.67 |
June | 65438917.90 | 1830.59 | 22-JUN-06:03 | 14.50 |
July | 17569245.97 | 3049.39 | 19-JUL-06:05 | 17.50 |
August | 25807080.48 | 2889.31 | 12-AUG-06:05 | 18.00 |
September | 64983036.06 | 1782.83 | 15-SEP-06:03 | 14.00 |
October | 72148407.49 | 1657.50 | 19-OCT-06:20 | 11.67 |
November | 0.230734E+09 | 24239.26 | 27-NOV-06:02 | 10.67 |
December | 0.487833E+09 | 29350.08 | 15-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.300105E+10 | |||
Minimum of Months | 17569245.97 | 1657.50 | 2.17 | |
Maximum of Months | 0.775261E+09 | 29604.66 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123439E+10 | 31268.44 | 03-JAN-02:15 | 3.67 |
February | 0.359990E+09 | 2930.87 | 27-FEB-08:00 | 9.00 |
March | 0.393085E+09 | 60628.79 | 30-MAR-05:07 | 4.97 |
April | 0.303291E+09 | 2626.86 | 21-APR-07:00 | 13.00 |
May | 0.218886E+09 | 2895.22 | 25-MAY-07:00 | 14.00 |
June | 0.199003E+09 | 2714.79 | 06-JUN-07:00 | 17.00 |
July | 0.142999E+09 | 2514.98 | 08-JUL-06:15 | 16.33 |
August | 0.202454E+09 | 2586.06 | 21-AUG-07:00 | 17.00 |
September | 0.204353E+09 | 2693.18 | 27-SEP-07:00 | 16.00 |
October | 0.284005E+09 | 3132.81 | 14-OCT-08:65 | 27.67 |
November | 0.478230E+09 | 2760.99 | 01-NOV-07:00 | 11.00 |
December | 0.781573E+09 | 2979.07 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.480226E+10 | |||
Minimum of Months | 0.142999E+09 | 2514.98 | 3.67 | |
Maximum of Months | 0.123439E+10 | 60628.79 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3480691.21 | 0.127053E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410820.57 | 0.132316E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17214.89 | 0.167934E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4426005.94 | 0.110212E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63803.74 | 0.119928E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204350.95 | 0.821223E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30690362.25 | 0.512602E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31053643.24 | 0.581415E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48803528.93 | 0.711547E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89196475.76 | 0.751331E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189273.95 | 0.122343E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4675313.86 | 0.120780E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.216211E+09 | 0.123838E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17214.89 | 0.512602E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89196475.76 | 0.167934E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18650745.26 | 0.505435E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43095.01 | 0.637664E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779903E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1028188.72 | 0.643196E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785219E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554016E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7081461.93 | 0.426088E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4297365.28 | 0.486491E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96491950.69 | 0.445710E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243249E+09 | 0.541509E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10738954.35 | 0.571690E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8998905.30 | 0.537177E+10 |
Annual Sum or Average | 0.136656E+12 | 0.390580E+09 | 0.691410E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426088E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243249E+09 | 0.785219E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404938E+09 | 0.136336E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29828324.31 | 0.191757E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15738696.46 | 0.240691E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52430249.80 | 0.216267E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278380E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227748E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212509E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229064E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47351178.04 | 0.193113E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406945E+09 | 0.209033E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105114E+09 | 0.178301E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414245E+09 | 0.154332E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.147659E+10 | 0.246753E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136336E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414245E+09 | 0.278380E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 735.98 | 18-JAN-13:00 | 6898.49 | 09-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.11 | 01-FEB-12:10 | 5384.23 | 09-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 11-MAR-14:00 | 6320.07 | 30-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 741.54 | 26-APR-11:10 | 4481.28 | 17-APR-16:05 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 04-MAY-12:00 | 4309.70 | 26-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.66 | 29-JUN-11:10 | 3797.39 | 05-JUN-06:01 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.24 | 19-JUL-12:00 | 3230.78 | 17-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.68 | 18-AUG-12:00 | 3565.60 | 28-AUG-07:00 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.48 | 29-SEP-12:00 | 3987.90 | 20-SEP-06:03 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.52 | 16-OCT-11:10 | 4787.73 | 12-OCT-06:03 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 | 28-NOV-14:00 | 5111.84 | 30-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 738.95 | 19-DEC-13:00 | 6034.98 | 22-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 3230.78 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.52 | 6898.49 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.19 | 15-JAN-10:00 | 8471.88 | 27-JAN-05:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.83 | 01-FEB-12:00 | 9766.27 | 25-FEB-16:05 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 14324.94 | 28-MAR-15:05 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.79 | 02-APR-12:00 | 14544.02 | 17-APR-16:05 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 13541.18 | 12-MAY-16:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 8485.97 | 12-JUN-16:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.47 | 31-JUL-13:00 | 8115.88 | 20-JUL-17:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.32 | 17-AUG-13:55 | 6423.50 | 21-AUG-17:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4615.78 | 29-SEP-15:10 | 7658.14 | 02-SEP-15:10 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4454.37 | 14-OCT-15:10 | 8972.14 | 23-OCT-15:05 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.77 | 19-NOV-13:00 | 8466.23 | 30-NOV-07:10 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.08 | 25-DEC-12:00 | 8616.04 | 12-DEC-16:05 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6423.50 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4615.78 | 14544.02 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8263.56 | 15-JAN-10:00 | 24004.67 | 27-JAN-05:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4468.65 | 01-FEB-12:00 | 32547.61 | 25-FEB-13:05 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1453.37 | 11-MAR-11:00 | 37839.20 | 28-MAR-14:10 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3532.84 | 01-APR-12:00 | 43167.02 | 17-APR-16:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 41393.73 | 12-MAY-16:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 25077.15 | 12-JUN-16:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 31027.38 | 20-JUL-15:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 22435.64 | 22-AUG-16:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.94 | 29-SEP-09:42 | 28714.74 | 02-SEP-15:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16457.47 | 14-OCT-10:00 | 29233.63 | 07-OCT-08:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4754.49 | 19-NOV-13:00 | 23378.99 | 01-NOV-08:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10610.65 | 18-DEC-11:00 | 28466.03 | 12-DEC-13:05 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22435.64 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16457.47 | 43167.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4260.45 | 21-JAN-15:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.21 |
February | 4407.01 | 03-FEB-15:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 |
March | 16422.59 | 22-MAR-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.25 |
April | 20969.73 | 28-APR-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.53 |
May | 22102.82 | 26-MAY-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.56 |
June | 21975.64 | 05-JUN-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 |
July | 23991.56 | 04-JUL-16:19 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20811.50 | 28-AUG-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 |
September | 20706.65 | 05-SEP-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21185.65 | 16-OCT-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 |
November | 4649.05 | 18-NOV-15:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
December | 4598.63 | 05-DEC-15:20 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4260.45 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23991.56 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 | 725.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7122.77 | 24-JAN-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.23 |
February | 7168.90 | 28-FEB-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3137.80 |
March | 10468.96 | 10-MAR-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.77 |
April | 47249.77 | 30-APR-15:31 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2700.43 |
May | 13660.73 | 03-MAY-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.10 |
June | 45240.25 | 25-JUN-13:51 | 0.00 | 9599.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3363.95 |
July | 49693.06 | 04-JUL-16:51 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44038.64 | 19-AUG-18:00 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.53 |
September | 46548.82 | 03-SEP-12:41 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2840.77 |
October | 45701.80 | 15-OCT-17:01 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.72 |
November | 7056.84 | 09-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.41 |
December | 8043.19 | 27-DEC-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2794.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7056.84 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49693.06 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3363.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7481.50 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7684.81 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11715.78 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8268.38 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6258.64 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5050.85 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6704.03 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7372.59 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11154.41 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8803.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11715.78 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.701861E+11 | 55321.89 | 07-JAN-16:00 | 0.688073E+10 | 27783.16 | 03-JAN-06:19 |
February | 0.634282E+11 | 52822.93 | 01-FEB-11:00 | 0.520940E+10 | 11494.50 | 28-FEB-06:10 |
March | 0.720634E+11 | 53432.41 | 23-MAR-14:20 | 0.601520E+10 | 23637.03 | 30-MAR-05:10 |
April | 0.674218E+11 | 58770.86 | 26-APR-12:00 | 0.521868E+10 | 11819.27 | 01-APR-05:10 |
May | 0.692593E+11 | 57067.86 | 04-MAY-12:09 | 0.535716E+10 | 2426.94 | 15-MAY-06:19 |
June | 0.700214E+11 | 59974.56 | 27-JUN-13:09 | 0.518400E+10 | 2000.00 | 01-JUN-00:10 |
July | 0.727420E+11 | 65376.35 | 31-JUL-13:30 | 0.535680E+10 | 2000.00 | 01-JUL-00:10 |
August | 0.771043E+11 | 65891.40 | 17-AUG-14:09 | 0.535680E+10 | 2000.00 | 01-AUG-00:10 |
September | 0.700657E+11 | 67579.49 | 29-SEP-12:00 | 0.518400E+10 | 2000.00 | 01-SEP-00:10 |
October | 0.718457E+11 | 67363.11 | 16-OCT-10:00 | 0.535680E+10 | 2000.00 | 01-OCT-00:10 |
November | 0.673066E+11 | 55417.74 | 18-NOV-16:49 | 0.529604E+10 | 8338.74 | 27-NOV-06:10 |
December | 0.703817E+11 | 55856.09 | 05-DEC-16:49 | 0.580882E+10 | 12596.77 | 15-DEC-07:10 |
Annual Sum or Average | 0.841826E+12 | 0.662244E+11 | ||||
Minimum of Months | 0.634282E+11 | 52822.93 | 0.518400E+10 | 2000.00 | ||
Maximum of Months | 0.771043E+11 | 67579.49 | 0.688073E+10 | 27783.16 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.121724E+11 | 0.115358E+11 | 0.00 | 0.407389E+10 | 0.00 | 0.00 | 0.122220E+09 | 0.00 | 0.00 | 0.00 | 0.217838E+10 | 0.00 |
February | 0.366966E+11 | 0.104046E+11 | 0.105871E+11 | 0.00 | 0.372489E+10 | 0.00 | 0.00 | 36290167.28 | 0.00 | 0.00 | 0.00 | 0.197878E+10 | 0.00 |
March | 0.423649E+11 | 0.106638E+11 | 0.123357E+11 | 0.00 | 0.437682E+10 | 0.00 | 0.00 | 98074837.99 | 0.00 | 0.00 | 0.00 | 0.222405E+10 | 0.00 |
April | 0.397216E+11 | 0.948055E+10 | 0.114862E+11 | 0.00 | 0.411668E+10 | 0.00 | 0.00 | 0.516807E+09 | 0.00 | 0.00 | 0.00 | 0.209995E+10 | 0.00 |
May | 0.412341E+11 | 0.905154E+10 | 0.119357E+11 | 0.00 | 0.431375E+10 | 0.00 | 0.00 | 0.569022E+09 | 0.00 | 0.00 | 0.00 | 0.215512E+10 | 0.00 |
June | 0.408524E+11 | 0.839153E+10 | 0.118862E+11 | 0.00 | 0.461400E+10 | 0.00 | 0.00 | 0.218851E+10 | 0.00 | 0.00 | 0.00 | 0.208880E+10 | 0.00 |
July | 0.401034E+11 | 0.883468E+10 | 0.115358E+11 | 0.00 | 0.487939E+10 | 0.00 | 0.00 | 0.528890E+10 | 0.00 | 0.00 | 0.00 | 0.209991E+10 | 0.00 |
August | 0.423649E+11 | 0.946169E+10 | 0.123357E+11 | 0.00 | 0.514279E+10 | 0.00 | 0.00 | 0.564938E+10 | 0.00 | 0.00 | 0.00 | 0.214984E+10 | 0.00 |
September | 0.397216E+11 | 0.996141E+10 | 0.114862E+11 | 0.00 | 0.448813E+10 | 0.00 | 0.00 | 0.234816E+10 | 0.00 | 0.00 | 0.00 | 0.206019E+10 | 0.00 |
October | 0.401034E+11 | 0.111636E+11 | 0.115358E+11 | 0.00 | 0.446728E+10 | 0.00 | 0.00 | 0.245088E+10 | 0.00 | 0.00 | 0.00 | 0.212488E+10 | 0.00 |
November | 0.385909E+11 | 0.115643E+11 | 0.110862E+11 | 0.00 | 0.388336E+10 | 0.00 | 0.00 | 0.108952E+09 | 0.00 | 0.00 | 0.00 | 0.207292E+10 | 0.00 |
December | 0.401034E+11 | 0.123799E+11 | 0.115358E+11 | 0.00 | 0.404953E+10 | 0.00 | 0.00 | 0.146075E+09 | 0.00 | 0.00 | 0.00 | 0.216705E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123530E+12 | 0.139282E+12 | 0.521305E+11 | 0.00 | 0.195233E+11 | 0.253999E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.839153E+10 | 0.105871E+11 | 0.00 | 0.372489E+10 | 0.00 | 0.00 | 36290167.28 | 0.00 | 0.00 | 0.00 | 0.197878E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.123799E+11 | 0.123357E+11 | 0.00 | 0.514279E+10 | 0.00 | 0.00 | 0.564938E+10 | 0.00 | 0.00 | 0.00 | 0.222405E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.688073E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.520940E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.601520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.521868E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.535716E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.535680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.535680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.535680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.529604E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.580882E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662244E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.688073E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4084.27 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4084.27 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4084.27 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4084.27 | 01-APR-06:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4084.27 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4660.60 | 27-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6389.57 | 19-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6389.57 | 17-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6389.57 | 29-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6389.57 | 16-OCT-15:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4084.27 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4084.27 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4084.27 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6389.57 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1515.30 | 14-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1805.09 | 26-JAN-12:50 | 0.00 |
February | 1305.90 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 1805.18 | 13-FEB-12:20 | 0.00 |
March | 2396.62 | 23-MAR-17:19 | 0.00 | 0.00 | 0.00 | 1803.55 | 06-MAR-12:30 | 0.00 |
April | 7221.94 | 26-APR-13:09 | 0.00 | 0.00 | 0.00 | 1796.98 | 03-APR-11:09 | 0.00 |
May | 5497.73 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1789.42 | 02-MAY-11:09 | 0.00 |
June | 8372.71 | 29-JUN-13:09 | 0.00 | 0.00 | 0.00 | 1781.20 | 01-JUN-11:09 | 0.00 |
July | 12241.70 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1775.07 | 01-JUL-11:50 | 0.00 |
August | 12226.72 | 18-AUG-14:39 | 0.00 | 0.00 | 0.00 | 1774.18 | 31-AUG-11:09 | 0.00 |
September | 13908.74 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1779.26 | 29-SEP-11:09 | 0.00 |
October | 14519.69 | 16-OCT-11:20 | 0.00 | 0.00 | 0.00 | 1787.88 | 31-OCT-11:39 | 0.00 |
November | 1648.43 | 18-NOV-14:09 | 0.00 | 0.00 | 0.00 | 1795.81 | 29-NOV-12:50 | 0.00 |
December | 1642.93 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1801.98 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1305.90 | 0.00 | 0.00 | 0.00 | 1774.18 | 0.00 | ||
Maximum of Months | 14519.69 | 0.00 | 0.00 | 0.00 | 1805.18 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55321.89 | 07-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4084.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52822.93 | 01-FEB-11:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4084.27 | 0.00 | 0.00 | 1274.89 | 0.00 |
March | 53432.41 | 23-MAR-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4084.27 | 0.00 | 0.00 | 1853.78 | 0.00 |
April | 58770.86 | 26-APR-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4084.27 | 0.00 | 0.00 | 7199.03 | 0.00 |
May | 57067.86 | 04-MAY-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4084.27 | 0.00 | 0.00 | 5497.73 | 0.00 |
June | 59974.56 | 27-JUN-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4545.33 | 0.00 | 0.00 | 7986.12 | 0.00 |
July | 65376.35 | 31-JUL-13:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6389.57 | 0.00 | 0.00 | 11546.10 | 0.00 |
August | 65891.40 | 17-AUG-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6389.57 | 0.00 | 0.00 | 12029.80 | 0.00 |
September | 67579.49 | 29-SEP-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6389.57 | 0.00 | 0.00 | 13712.04 | 0.00 |
October | 67363.11 | 16-OCT-10:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6389.57 | 0.00 | 0.00 | 13524.88 | 0.00 |
November | 55417.74 | 18-NOV-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4084.27 | 0.00 | 0.00 | 98.49 | 0.00 |
December | 55856.09 | 05-DEC-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4084.27 | 0.00 | 0.00 | 535.84 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52822.93 | 31660.41 | 10112.62 | 0.00 | 0.00 | 4084.27 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67579.49 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6389.57 | 0.00 | 0.00 | 13712.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 27783.16 | 03-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11494.50 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 23637.03 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 11819.27 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2426.94 | 15-MAY-06:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2000.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 8338.74 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 12596.77 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 27783.16 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.25 | 2.17 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.44 | 0.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.36 | 1.50 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.51 | 0.33 | 20.51 | 4.33 | 24.52 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.56 | 1.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.68 | 0.50 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 24.56 | 1.67 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.51 | 1.00 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.51 | 0.33 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.33 | 20.34 | 5.33 | 20.34 | 69.17 | 24.56 | 4.67 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.51 | 2.17 | 20.51 | 15.17 | 24.68 | 1.67 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 14.97 | 0.00 | 3.50 | 27.38 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 15.00 | 0.00 | 0.00 | 1.33 | 27.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.67 | 22.91 | 54.00 | 21.19 | 54.00 | 21.19 |
February | 262.00 | 22.98 | 27.67 | 21.21 | 27.17 | 21.17 |
March | 295.67 | 22.92 | 47.00 | 21.89 | 33.83 | 21.11 |
April | 133.67 | 23.30 | 97.33 | 23.80 | 3.33 | 21.11 |
May | 100.50 | 23.47 | 120.67 | 23.90 | 0.00 | 0.00 |
June | 27.17 | 23.68 | 227.50 | 23.90 | 0.50 | 23.90 |
July | 11.00 | 23.81 | 284.33 | 23.90 | 9.83 | 23.90 |
August | 19.83 | 23.84 | 306.33 | 23.90 | 18.50 | 23.90 |
September | 22.67 | 23.82 | 226.33 | 23.90 | 10.00 | 23.92 |
October | 98.17 | 23.57 | 132.33 | 23.90 | 9.50 | 23.90 |
November | 243.33 | 23.24 | 17.33 | 21.87 | 12.83 | 21.16 |
December | 294.00 | 23.12 | 39.50 | 21.27 | 38.67 | 21.21 |
Annual Sum or Average | 1793.67 | 23.14 | 1580.33 | 23.61 | 218.17 | 21.78 |
Minimum of Months | 11.00 | 22.91 | 17.33 | 21.19 | 0.00 | 0.00 |
Maximum of Months | 295.67 | 23.84 | 306.33 | 23.90 | 54.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.449989E+09 | 0.122220E+09 | 78.33 | 0.431709E+09 | 18279490.01 | 0.00 | 0.33 | 14-JAN-15:00 | 0.00 | 01-JAN-00:05 | 5504.55 | 18-JAN-14:20 | 5504.55 | 18-JAN-14:20 | 839.73 | 17-JAN-14:00 | 1515.30 | 14-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.133666E+09 | 36290167.28 | 64.83 | 0.132552E+09 | 1113367.48 | 0.00 | 0.30 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4856.89 | 03-FEB-15:00 | 4856.89 | 03-FEB-15:00 | 285.02 | 01-FEB-13:40 | 1305.90 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.367046E+09 | 98074794.32 | 82.17 | 0.310675E+09 | 56371468.96 | 0.00 | 1.00 | 22-MAR-17:15 | 0.00 | 01-MAR-00:10 | 20314.09 | 23-MAR-17:15 | 13529.12 | 23-MAR-17:15 | 7287.94 | 22-MAR-17:15 | 4793.24 | 23-MAR-17:15 | 0.00 | 01-MAR-00:10 |
April | 0.150564E+10 | 0.398048E+09 | 174.06 | 0.122565E+10 | 0.279984E+09 | 0.00 | 1.00 | 03-APR-17:20 | 0.00 | 01-APR-00:10 | 20709.17 | 26-APR-17:10 | 15705.29 | 26-APR-17:10 | 7763.38 | 26-APR-19:05 | 4873.84 | 26-APR-17:10 | 0.00 | 01-APR-00:10 |
May | 0.175937E+10 | 0.461760E+09 | 204.33 | 0.145228E+10 | 0.307085E+09 | 0.00 | 1.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:05 | 20409.89 | 02-MAY-17:10 | 17167.24 | 26-MAY-17:15 | 7518.37 | 01-MAY-00:03 | 4813.05 | 02-MAY-17:10 | 0.00 | 01-MAY-00:03 |
June | 0.493809E+10 | 0.126584E+10 | 241.82 | 0.366183E+10 | 0.127626E+10 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 21769.82 | 29-JUN-17:42 | 16916.84 | 24-JUN-17:10 | 9732.39 | 30-JUN-03:10 | 5076.07 | 29-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.914355E+10 | 0.230868E+10 | 268.88 | 0.641287E+10 | 0.273067E+10 | 0.00 | 1.00 | 01-JUL-02:30 | 0.00 | 01-JUL-00:10 | 22476.96 | 23-JUL-16:27 | 16909.47 | 09-JUL-16:01 | 10918.29 | 28-JUL-05:40 | 5206.37 | 23-JUL-16:27 | 0.00 | 01-JUL-00:10 |
August | 0.975880E+10 | 0.246310E+10 | 281.93 | 0.671546E+10 | 0.304334E+10 | 0.00 | 1.00 | 01-AUG-00:35 | 0.00 | 01-AUG-00:10 | 22318.86 | 18-AUG-17:08 | 17151.92 | 19-AUG-17:08 | 11466.69 | 07-AUG-03:25 | 5172.81 | 18-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.524209E+10 | 0.137767E+10 | 242.01 | 0.387605E+10 | 0.136605E+10 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:05 | 22560.28 | 21-SEP-22:20 | 19461.88 | 29-SEP-21:01 | 10854.96 | 22-SEP-01:30 | 5213.66 | 21-SEP-22:20 | 0.00 | 01-SEP-00:05 |
October | 0.482439E+10 | 0.128585E+10 | 238.09 | 0.397444E+10 | 0.849948E+09 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:05 | 22315.25 | 04-OCT-17:11 | 19391.73 | 16-OCT-17:41 | 10889.02 | 05-OCT-17:11 | 5172.19 | 04-OCT-17:11 | 0.00 | 01-OCT-00:05 |
November | 0.402083E+09 | 0.108952E+09 | 109.50 | 0.392599E+09 | 9484034.93 | 0.00 | 0.35 | 18-NOV-14:20 | 0.00 | 01-NOV-00:10 | 6086.95 | 18-NOV-14:30 | 6086.95 | 18-NOV-14:30 | 813.59 | 10-NOV-13:10 | 1648.43 | 18-NOV-14:10 | 0.00 | 01-NOV-00:10 |
December | 0.537830E+09 | 0.146075E+09 | 103.06 | 0.534619E+09 | 3211268.12 | 0.00 | 0.36 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 6094.39 | 05-DEC-15:00 | 6094.39 | 05-DEC-15:00 | 534.31 | 07-DEC-14:00 | 1642.93 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.390625E+11 | 0.100726E+11 | 2089.01 | 0.291207E+11 | 0.994180E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.133666E+09 | 36290167.28 | 64.83 | 0.132552E+09 | 1113367.48 | 0.00 | 0.30 | 0.00 | 4856.89 | 4856.89 | 285.02 | 1305.90 | 0.00 | |||||||
Maximum of Months | 0.975880E+10 | 0.246310E+10 | 281.93 | 0.671546E+10 | 0.304334E+10 | 0.00 | 1.00 | 0.00 | 22560.28 | 19461.88 | 11466.69 | 5213.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 149.83 | 43.67 | 0.33 | 111.78 | 38.05 | 0.00 | 0.00 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 | 0.16 | 23-MAR-15:10 | 0.12 | 23-MAR-15:10 | 0.04 | 23-MAR-15:10 | 0.05 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 |
April | 0.418124E+09 | 0.118759E+09 | 40.82 | 0.351905E+09 | 66219802.29 | 0.00 | 1.00 | 30-APR-11:01 | 0.00 | 01-APR-00:10 | 52329.77 | 30-APR-12:41 | 45484.68 | 30-APR-11:01 | 10591.97 | 30-APR-15:31 | 13276.53 | 30-APR-11:01 | 0.00 | 01-APR-00:10 |
May | 0.374523E+09 | 0.107262E+09 | 48.17 | 0.311889E+09 | 62633729.66 | 0.00 | 0.27 | 04-MAY-12:00 | 0.00 | 01-MAY-00:03 | 12405.19 | 04-MAY-12:00 | 10742.79 | 03-MAY-13:00 | 2120.83 | 04-MAY-12:30 | 3503.17 | 04-MAY-12:00 | 0.00 | 01-MAY-00:03 |
June | 0.332474E+10 | 0.922669E+09 | 125.40 | 0.234192E+10 | 0.982814E+09 | 0.00 | 1.00 | 18-JUN-11:21 | 0.00 | 01-JUN-00:10 | 55350.38 | 29-JUN-17:51 | 40694.00 | 25-JUN-12:00 | 21311.40 | 29-JUN-17:51 | 13648.32 | 29-JUN-17:51 | 0.00 | 01-JUN-00:10 |
July | 0.109444E+11 | 0.298022E+10 | 212.64 | 0.743795E+10 | 0.350648E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 57343.90 | 31-JUL-17:08 | 42497.54 | 02-JUL-12:11 | 25528.23 | 29-JUL-17:11 | 14214.38 | 23-JUL-10:57 | 0.00 | 01-JUL-00:10 |
August | 0.116685E+11 | 0.318628E+10 | 220.11 | 0.775791E+10 | 0.391062E+10 | 0.00 | 1.00 | 03-AUG-17:12 | 0.00 | 01-AUG-00:10 | 57253.97 | 06-AUG-10:20 | 40780.48 | 27-AUG-15:12 | 25333.11 | 18-AUG-17:26 | 14252.83 | 06-AUG-12:52 | 0.00 | 01-AUG-00:10 |
September | 0.323335E+10 | 0.970484E+09 | 134.39 | 0.269461E+10 | 0.538739E+09 | 0.00 | 1.00 | 03-SEP-12:41 | 0.00 | 01-SEP-00:05 | 55235.72 | 10-SEP-10:51 | 43562.50 | 30-SEP-17:11 | 19977.77 | 10-SEP-12:01 | 13626.83 | 10-SEP-10:51 | 0.00 | 01-SEP-00:05 |
October | 0.379824E+10 | 0.116503E+10 | 120.05 | 0.341587E+10 | 0.382366E+09 | 0.00 | 1.00 | 01-OCT-10:51 | 0.00 | 01-OCT-00:05 | 57504.96 | 01-OCT-11:55 | 47978.97 | 15-OCT-17:01 | 23661.48 | 01-OCT-15:40 | 14370.85 | 01-OCT-11:55 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.337619E+11 | 0.945071E+10 | 901.91 | 0.243121E+11 | 0.944987E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.116685E+11 | 0.318628E+10 | 220.11 | 0.775791E+10 | 0.391062E+10 | 0.00 | 1.00 | 0.00 | 57504.96 | 47978.97 | 25528.23 | 14370.85 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.87 | 102.06 | 98.81 | 242.01 | 143.46 | 1.33 | 0.00 | 744.00 |
February | 236.97 | 109.00 | 127.97 | 270.87 | 134.42 | 4.50 | 0.00 | 672.00 |
March | 270.97 | 119.11 | 151.87 | 313.67 | 141.23 | 7.83 | 0.00 | 744.00 |
April | 372.79 | 192.74 | 180.05 | 457.64 | 128.02 | 1.83 | 0.00 | 720.00 |
May | 366.42 | 167.80 | 198.62 | 434.40 | 119.09 | 0.00 | 0.00 | 744.00 |
June | 388.54 | 193.07 | 195.47 | 481.04 | 94.32 | 0.00 | 0.00 | 720.00 |
July | 411.46 | 219.05 | 192.41 | 529.50 | 86.33 | 0.00 | 0.00 | 744.00 |
August | 385.47 | 207.61 | 177.86 | 502.02 | 90.47 | 0.00 | 0.00 | 744.00 |
September | 330.21 | 175.65 | 154.56 | 419.20 | 102.96 | 0.00 | 0.00 | 720.00 |
October | 253.68 | 138.37 | 115.31 | 328.79 | 113.56 | 0.00 | 0.00 | 744.00 |
November | 229.84 | 120.35 | 109.48 | 275.10 | 143.14 | 2.33 | 0.00 | 720.00 |
December | 203.68 | 109.69 | 94.00 | 245.73 | 149.39 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 304.51 | 154.74 | 149.77 | 375.49 | 120.46 | 19.00 | 0.00 | 8760.00 |
Minimum of Months | 200.87 | 102.06 | 94.00 | 242.01 | 86.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 411.46 | 219.05 | 198.62 | 529.50 | 149.39 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.87 | 102.06 | 98.81 | 242.01 | 143.46 | 1.33 | 0.00 | 744.00 |
February | 236.97 | 109.00 | 127.97 | 270.87 | 134.42 | 4.50 | 0.00 | 672.00 |
March | 270.97 | 119.11 | 151.87 | 313.67 | 141.23 | 7.83 | 0.00 | 744.00 |
April | 372.79 | 192.74 | 180.05 | 457.64 | 128.02 | 1.83 | 0.00 | 720.00 |
May | 366.42 | 167.80 | 198.62 | 434.40 | 119.09 | 0.00 | 0.00 | 744.00 |
June | 388.54 | 193.07 | 195.47 | 481.04 | 94.32 | 0.00 | 0.00 | 720.00 |
July | 411.46 | 219.05 | 192.41 | 529.50 | 86.33 | 0.00 | 0.00 | 744.00 |
August | 385.47 | 207.61 | 177.86 | 502.02 | 90.47 | 0.00 | 0.00 | 744.00 |
September | 330.21 | 175.65 | 154.56 | 419.20 | 102.96 | 0.00 | 0.00 | 720.00 |
October | 253.68 | 138.37 | 115.31 | 328.79 | 113.56 | 0.00 | 0.00 | 744.00 |
November | 229.84 | 120.35 | 109.48 | 275.10 | 143.14 | 2.33 | 0.00 | 720.00 |
December | 203.68 | 109.69 | 94.00 | 245.73 | 149.39 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 304.51 | 154.74 | 149.77 | 375.49 | 120.46 | 19.00 | 0.00 | 8760.00 |
Minimum of Months | 200.87 | 102.06 | 94.00 | 242.01 | 86.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 411.46 | 219.05 | 198.62 | 529.50 | 149.39 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.27 | 0.00 | 45.27 | 36.52 | 86.29 | 1.67 | 0.00 | 744.00 |
February | 56.83 | 0.00 | 56.83 | 43.09 | 80.99 | 4.50 | 0.00 | 672.00 |
March | 69.65 | 0.00 | 69.65 | 57.71 | 84.54 | 7.83 | 0.00 | 744.00 |
April | 80.74 | 0.76 | 79.97 | 69.02 | 74.70 | 1.83 | 0.00 | 720.00 |
May | 98.78 | 6.80 | 91.97 | 89.06 | 67.33 | 0.00 | 0.00 | 744.00 |
June | 105.40 | 12.71 | 92.69 | 105.84 | 53.26 | 0.00 | 0.00 | 720.00 |
July | 99.75 | 10.61 | 89.15 | 105.36 | 49.35 | 0.00 | 0.00 | 744.00 |
August | 81.95 | 2.75 | 79.20 | 83.54 | 51.80 | 0.00 | 0.00 | 744.00 |
September | 68.42 | 0.04 | 68.37 | 64.83 | 61.95 | 0.00 | 0.00 | 720.00 |
October | 54.24 | 0.00 | 54.24 | 55.22 | 68.12 | 0.00 | 0.00 | 744.00 |
November | 49.11 | 0.00 | 49.11 | 37.93 | 86.43 | 2.33 | 0.00 | 720.00 |
December | 42.15 | 0.00 | 42.15 | 32.01 | 90.51 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 71.09 | 2.82 | 68.26 | 65.14 | 71.22 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 42.15 | 0.00 | 42.15 | 32.01 | 49.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 105.40 | 12.71 | 92.69 | 105.84 | 90.51 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.27 | 0.00 | 45.27 | 36.52 | 86.29 | 1.67 | 0.00 | 744.00 |
February | 56.83 | 0.00 | 56.83 | 43.09 | 80.99 | 4.50 | 0.00 | 672.00 |
March | 69.65 | 0.00 | 69.65 | 57.70 | 84.54 | 7.83 | 0.00 | 744.00 |
April | 80.73 | 0.76 | 79.97 | 69.01 | 74.70 | 1.83 | 0.00 | 720.00 |
May | 98.77 | 6.80 | 91.97 | 89.05 | 67.33 | 0.00 | 0.00 | 744.00 |
June | 105.40 | 12.71 | 92.69 | 105.84 | 53.26 | 0.00 | 0.00 | 720.00 |
July | 99.75 | 10.61 | 89.14 | 105.35 | 49.35 | 0.00 | 0.00 | 744.00 |
August | 81.95 | 2.75 | 79.20 | 83.54 | 51.80 | 0.00 | 0.00 | 744.00 |
September | 68.41 | 0.04 | 68.37 | 64.83 | 61.95 | 0.00 | 0.00 | 720.00 |
October | 54.24 | 0.00 | 54.24 | 55.22 | 68.12 | 0.00 | 0.00 | 744.00 |
November | 49.11 | 0.00 | 49.11 | 37.93 | 86.43 | 2.33 | 0.00 | 720.00 |
December | 42.15 | 0.00 | 42.15 | 32.01 | 90.50 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 71.09 | 2.82 | 68.26 | 65.14 | 71.22 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 42.15 | 0.00 | 42.15 | 32.01 | 49.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 105.40 | 12.71 | 92.69 | 105.84 | 90.50 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.71 | 44.70 | 23.01 | 87.91 | 68.73 | 12.33 | 0.00 | 744.00 |
February | 76.98 | 43.35 | 33.64 | 95.32 | 61.43 | 3.17 | 0.00 | 672.00 |
March | 99.48 | 56.25 | 43.22 | 128.28 | 61.61 | 29.33 | 0.00 | 744.00 |
April | 148.54 | 107.20 | 41.34 | 193.59 | 61.91 | 3.33 | 0.00 | 720.00 |
May | 148.22 | 94.35 | 53.87 | 187.80 | 60.54 | 0.00 | 0.00 | 744.00 |
June | 157.19 | 107.27 | 49.92 | 201.23 | 53.46 | 0.00 | 0.00 | 720.00 |
July | 172.24 | 128.19 | 44.06 | 221.47 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 159.64 | 121.67 | 37.97 | 206.03 | 60.92 | 0.00 | 0.00 | 744.00 |
September | 123.14 | 87.12 | 36.02 | 156.76 | 63.22 | 0.50 | 0.00 | 720.00 |
October | 88.47 | 61.05 | 27.43 | 112.29 | 70.88 | 0.00 | 0.00 | 744.00 |
November | 72.13 | 46.29 | 25.84 | 89.95 | 72.33 | 8.50 | 0.00 | 720.00 |
December | 63.18 | 43.07 | 20.10 | 79.49 | 76.45 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 114.94 | 78.57 | 36.37 | 146.95 | 64.24 | 66.50 | 0.00 | 8760.00 |
Minimum of Months | 63.18 | 43.07 | 20.10 | 79.49 | 53.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.24 | 128.19 | 53.87 | 221.47 | 76.45 | 29.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.538013E+09 | 0.273354E+09 | 0.264659E+09 | 0.648196E+09 | 0.384237E+09 |
February | 0.573274E+09 | 0.263690E+09 | 0.309584E+09 | 0.655277E+09 | 0.325184E+09 |
March | 0.725775E+09 | 0.319011E+09 | 0.406764E+09 | 0.840125E+09 | 0.378272E+09 |
April | 0.966283E+09 | 0.499589E+09 | 0.466695E+09 | 0.118620E+10 | 0.331822E+09 |
May | 0.981407E+09 | 0.449427E+09 | 0.531980E+09 | 0.116350E+10 | 0.318966E+09 |
June | 0.100710E+10 | 0.500441E+09 | 0.506661E+09 | 0.124687E+10 | 0.244479E+09 |
July | 0.110206E+10 | 0.586701E+09 | 0.515364E+09 | 0.141821E+10 | 0.231223E+09 |
August | 0.103244E+10 | 0.556070E+09 | 0.476370E+09 | 0.134461E+10 | 0.242319E+09 |
September | 0.855901E+09 | 0.455276E+09 | 0.400624E+09 | 0.108658E+10 | 0.266872E+09 |
October | 0.679469E+09 | 0.370613E+09 | 0.308855E+09 | 0.880628E+09 | 0.304163E+09 |
November | 0.595740E+09 | 0.311958E+09 | 0.283783E+09 | 0.713051E+09 | 0.371017E+09 |
December | 0.545542E+09 | 0.293782E+09 | 0.251760E+09 | 0.658162E+09 | 0.400137E+09 |
Annual Sum or Average | 0.960301E+10 | 0.487991E+10 | 0.472310E+10 | 0.118414E+11 | 0.379869E+10 |
Minimum of Months | 0.538013E+09 | 0.263690E+09 | 0.251760E+09 | 0.648196E+09 | 0.231223E+09 |
Maximum of Months | 0.110206E+10 | 0.586701E+09 | 0.531980E+09 | 0.141821E+10 | 0.400137E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.538013E+09 | 0.273354E+09 | 0.264659E+09 | 0.648196E+09 | 0.384237E+09 |
February | 0.573274E+09 | 0.263690E+09 | 0.309584E+09 | 0.655277E+09 | 0.325184E+09 |
March | 0.725775E+09 | 0.319011E+09 | 0.406764E+09 | 0.840125E+09 | 0.378272E+09 |
April | 0.966283E+09 | 0.499589E+09 | 0.466695E+09 | 0.118620E+10 | 0.331822E+09 |
May | 0.981407E+09 | 0.449427E+09 | 0.531980E+09 | 0.116350E+10 | 0.318966E+09 |
June | 0.100710E+10 | 0.500441E+09 | 0.506661E+09 | 0.124687E+10 | 0.244479E+09 |
July | 0.110206E+10 | 0.586701E+09 | 0.515364E+09 | 0.141821E+10 | 0.231223E+09 |
August | 0.103244E+10 | 0.556070E+09 | 0.476370E+09 | 0.134461E+10 | 0.242319E+09 |
September | 0.855901E+09 | 0.455276E+09 | 0.400624E+09 | 0.108658E+10 | 0.266872E+09 |
October | 0.679469E+09 | 0.370613E+09 | 0.308855E+09 | 0.880628E+09 | 0.304163E+09 |
November | 0.595740E+09 | 0.311958E+09 | 0.283783E+09 | 0.713051E+09 | 0.371017E+09 |
December | 0.545542E+09 | 0.293782E+09 | 0.251760E+09 | 0.658162E+09 | 0.400137E+09 |
Annual Sum or Average | 0.960301E+10 | 0.487991E+10 | 0.472310E+10 | 0.118414E+11 | 0.379869E+10 |
Minimum of Months | 0.538013E+09 | 0.263690E+09 | 0.251760E+09 | 0.648196E+09 | 0.231223E+09 |
Maximum of Months | 0.110206E+10 | 0.586701E+09 | 0.531980E+09 | 0.141821E+10 | 0.400137E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121263E+09 | 0.00 | 0.121263E+09 | 97817427.06 | 0.231116E+09 |
February | 0.137487E+09 | 0.00 | 0.137487E+09 | 0.104250E+09 | 0.195928E+09 |
March | 0.186558E+09 | 11739.75 | 0.186547E+09 | 0.154561E+09 | 0.226440E+09 |
April | 0.209266E+09 | 1977118.13 | 0.207289E+09 | 0.178888E+09 | 0.193615E+09 |
May | 0.264563E+09 | 18217443.91 | 0.246346E+09 | 0.238525E+09 | 0.180324E+09 |
June | 0.273203E+09 | 32944738.31 | 0.240258E+09 | 0.274345E+09 | 0.138041E+09 |
July | 0.267179E+09 | 28407933.38 | 0.238771E+09 | 0.282187E+09 | 0.132188E+09 |
August | 0.219502E+09 | 7375638.38 | 0.212127E+09 | 0.223752E+09 | 0.138749E+09 |
September | 0.177332E+09 | 116564.98 | 0.177215E+09 | 0.168049E+09 | 0.160582E+09 |
October | 0.145273E+09 | 0.00 | 0.145273E+09 | 0.147896E+09 | 0.182444E+09 |
November | 0.127292E+09 | 0.00 | 0.127292E+09 | 98324962.03 | 0.224017E+09 |
December | 0.112886E+09 | 0.00 | 0.112886E+09 | 85733597.99 | 0.242410E+09 |
Annual Sum or Average | 0.224180E+10 | 89051176.83 | 0.215275E+10 | 0.205433E+10 | 0.224585E+10 |
Minimum of Months | 0.112886E+09 | 0.00 | 0.112886E+09 | 85733597.99 | 0.132188E+09 |
Maximum of Months | 0.273203E+09 | 32944738.31 | 0.246346E+09 | 0.282187E+09 | 0.242410E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121260E+09 | 0.00 | 0.121260E+09 | 97813997.62 | 0.231115E+09 |
February | 0.137483E+09 | 0.00 | 0.137483E+09 | 0.104246E+09 | 0.195927E+09 |
March | 0.186553E+09 | 11739.20 | 0.186541E+09 | 0.154554E+09 | 0.226439E+09 |
April | 0.209261E+09 | 1977025.46 | 0.207284E+09 | 0.178882E+09 | 0.193614E+09 |
May | 0.264555E+09 | 18216590.03 | 0.246339E+09 | 0.238515E+09 | 0.180323E+09 |
June | 0.273194E+09 | 32943194.15 | 0.240251E+09 | 0.274334E+09 | 0.138040E+09 |
July | 0.267171E+09 | 28406601.86 | 0.238765E+09 | 0.282178E+09 | 0.132187E+09 |
August | 0.219497E+09 | 7375292.67 | 0.212122E+09 | 0.223746E+09 | 0.138748E+09 |
September | 0.177327E+09 | 116559.52 | 0.177211E+09 | 0.168044E+09 | 0.160581E+09 |
October | 0.145270E+09 | 0.00 | 0.145270E+09 | 0.147892E+09 | 0.182443E+09 |
November | 0.127288E+09 | 0.00 | 0.127288E+09 | 98321292.22 | 0.224016E+09 |
December | 0.112883E+09 | 0.00 | 0.112883E+09 | 85730747.66 | 0.242408E+09 |
Annual Sum or Average | 0.224174E+10 | 89047002.89 | 0.215270E+10 | 0.205426E+10 | 0.224584E+10 |
Minimum of Months | 0.112883E+09 | 0.00 | 0.112883E+09 | 85730747.66 | 0.132187E+09 |
Maximum of Months | 0.273194E+09 | 32943194.15 | 0.246339E+09 | 0.282178E+09 | 0.242408E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181347E+09 | 0.119716E+09 | 61630919.77 | 0.235452E+09 | 0.184098E+09 |
February | 0.186236E+09 | 0.104862E+09 | 81373495.60 | 0.230599E+09 | 0.148605E+09 |
March | 0.266443E+09 | 0.150673E+09 | 0.115770E+09 | 0.343590E+09 | 0.165020E+09 |
April | 0.385015E+09 | 0.277859E+09 | 0.107156E+09 | 0.501793E+09 | 0.160464E+09 |
May | 0.396990E+09 | 0.252708E+09 | 0.144282E+09 | 0.503008E+09 | 0.162140E+09 |
June | 0.407430E+09 | 0.278037E+09 | 0.129393E+09 | 0.521590E+09 | 0.138566E+09 |
July | 0.461340E+09 | 0.343333E+09 | 0.118007E+09 | 0.593189E+09 | 0.157873E+09 |
August | 0.427582E+09 | 0.325877E+09 | 0.101705E+09 | 0.551832E+09 | 0.163156E+09 |
September | 0.319172E+09 | 0.225805E+09 | 93367161.82 | 0.406312E+09 | 0.163868E+09 |
October | 0.236966E+09 | 0.163508E+09 | 73458627.40 | 0.300757E+09 | 0.189835E+09 |
November | 0.186967E+09 | 0.119996E+09 | 66971083.52 | 0.233154E+09 | 0.187468E+09 |
December | 0.169211E+09 | 0.115367E+09 | 53844398.11 | 0.212904E+09 | 0.204773E+09 |
Annual Sum or Average | 0.362470E+10 | 0.247774E+10 | 0.114696E+10 | 0.463418E+10 | 0.202587E+10 |
Minimum of Months | 0.169211E+09 | 0.104862E+09 | 53844398.11 | 0.212904E+09 | 0.138566E+09 |
Maximum of Months | 0.461340E+09 | 0.343333E+09 | 0.144282E+09 | 0.593189E+09 | 0.204773E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 553.09 | 455.52 | 492.29 | 204.12 | 288.17 | 0.00 | 0.00 |
February | 623.67 | 426.57 | 587.60 | 218.00 | 369.60 | 0.00 | 0.00 |
March | 738.39 | 447.19 | 681.25 | 238.22 | 443.03 | 0.00 | 0.00 |
April | 1051.04 | 403.16 | 907.06 | 387.01 | 520.05 | 0.00 | 0.00 |
May | 1042.41 | 368.33 | 930.38 | 349.20 | 581.18 | 0.00 | 0.00 |
June | 1170.62 | 292.01 | 987.89 | 411.56 | 576.32 | 0.00 | 0.00 |
July | 1267.53 | 269.18 | 1022.43 | 459.31 | 563.12 | 0.00 | 0.00 |
August | 1169.33 | 282.77 | 934.84 | 420.73 | 514.11 | 0.00 | 0.00 |
September | 964.13 | 325.88 | 797.25 | 351.38 | 445.86 | 0.00 | 0.00 |
October | 764.63 | 359.97 | 615.85 | 276.74 | 339.10 | 0.00 | 0.00 |
November | 620.72 | 453.79 | 557.89 | 240.71 | 317.19 | 0.00 | 0.00 |
December | 550.63 | 474.95 | 491.66 | 219.37 | 272.29 | 0.00 | 0.00 |
Annual Sum or Average | 877.60 | 379.68 | 751.19 | 315.13 | 436.06 | 0.00 | 0.00 |
Minimum of Months | 550.63 | 269.18 | 491.66 | 204.12 | 272.29 | 0.00 | 0.00 |
Maximum of Months | 1267.53 | 474.95 | 1022.43 | 459.31 | 581.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 879.08 | 687.34 | 677.07 | 446.97 | 230.10 | 0.00 | 0.00 |
February | 953.20 | 614.27 | 769.82 | 433.46 | 336.37 | 0.00 | 0.00 |
March | 1282.81 | 616.12 | 994.78 | 562.55 | 432.24 | 0.00 | 0.00 |
April | 1935.93 | 619.08 | 1485.40 | 1071.99 | 413.41 | 0.00 | 0.00 |
May | 1878.02 | 605.36 | 1482.19 | 943.50 | 538.69 | 0.00 | 0.00 |
June | 2012.30 | 534.59 | 1571.88 | 1072.68 | 499.20 | 0.00 | 0.00 |
July | 2214.71 | 589.43 | 1722.45 | 1281.86 | 440.59 | 0.00 | 0.00 |
August | 2060.30 | 609.15 | 1596.41 | 1216.69 | 379.72 | 0.00 | 0.00 |
September | 1567.56 | 632.21 | 1231.38 | 871.16 | 360.21 | 0.00 | 0.00 |
October | 1122.90 | 708.76 | 884.73 | 610.47 | 274.26 | 0.00 | 0.00 |
November | 899.50 | 723.26 | 721.32 | 462.95 | 258.38 | 0.00 | 0.00 |
December | 794.89 | 764.54 | 631.76 | 430.73 | 201.03 | 0.00 | 0.00 |
Annual Sum or Average | 1469.49 | 642.40 | 1149.39 | 785.69 | 363.70 | 0.00 | 0.00 |
Minimum of Months | 794.89 | 534.59 | 631.76 | 430.73 | 201.03 | 0.00 | 0.00 |
Maximum of Months | 2214.71 | 764.54 | 1722.45 | 1281.86 | 538.69 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148139E+10 | 0.122007E+10 | 0.131855E+10 | 0.546708E+09 | 0.771841E+09 | 0.00 | 0.00 |
February | 0.150879E+10 | 0.103197E+10 | 0.142152E+10 | 0.527381E+09 | 0.894137E+09 | 0.00 | 0.00 |
March | 0.197769E+10 | 0.119775E+10 | 0.182466E+10 | 0.638046E+09 | 0.118662E+10 | 0.00 | 0.00 |
April | 0.272429E+10 | 0.104500E+10 | 0.235109E+10 | 0.100313E+10 | 0.134796E+10 | 0.00 | 0.00 |
May | 0.279199E+10 | 0.986529E+09 | 0.249193E+10 | 0.935289E+09 | 0.155664E+10 | 0.00 | 0.00 |
June | 0.303425E+10 | 0.756878E+09 | 0.256060E+10 | 0.106677E+10 | 0.149383E+10 | 0.00 | 0.00 |
July | 0.339494E+10 | 0.720982E+09 | 0.273848E+10 | 0.123022E+10 | 0.150826E+10 | 0.00 | 0.00 |
August | 0.313194E+10 | 0.757361E+09 | 0.250388E+10 | 0.112689E+10 | 0.137699E+10 | 0.00 | 0.00 |
September | 0.249904E+10 | 0.844692E+09 | 0.206646E+10 | 0.910786E+09 | 0.115568E+10 | 0.00 | 0.00 |
October | 0.204797E+10 | 0.964141E+09 | 0.164948E+10 | 0.741227E+09 | 0.908254E+09 | 0.00 | 0.00 |
November | 0.160890E+10 | 0.117622E+10 | 0.144606E+10 | 0.623915E+09 | 0.822145E+09 | 0.00 | 0.00 |
December | 0.147480E+10 | 0.127210E+10 | 0.131685E+10 | 0.587564E+09 | 0.729289E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276760E+11 | 0.119737E+11 | 0.236896E+11 | 0.993792E+10 | 0.137516E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147480E+10 | 0.720982E+09 | 0.131685E+10 | 0.527381E+09 | 0.729289E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339494E+10 | 0.127210E+10 | 0.273848E+10 | 0.123022E+10 | 0.155664E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.235452E+10 | 0.184098E+10 | 0.181347E+10 | 0.119716E+10 | 0.616309E+09 | 0.00 | 0.00 |
February | 0.230598E+10 | 0.148605E+10 | 0.186236E+10 | 0.104862E+10 | 0.813735E+09 | 0.00 | 0.00 |
March | 0.343589E+10 | 0.165020E+10 | 0.266443E+10 | 0.150673E+10 | 0.115770E+10 | 0.00 | 0.00 |
April | 0.501793E+10 | 0.160464E+10 | 0.385015E+10 | 0.277859E+10 | 0.107156E+10 | 0.00 | 0.00 |
May | 0.503008E+10 | 0.162140E+10 | 0.396990E+10 | 0.252708E+10 | 0.144282E+10 | 0.00 | 0.00 |
June | 0.521589E+10 | 0.138566E+10 | 0.407430E+10 | 0.278037E+10 | 0.129393E+10 | 0.00 | 0.00 |
July | 0.593189E+10 | 0.157872E+10 | 0.461340E+10 | 0.343333E+10 | 0.118007E+10 | 0.00 | 0.00 |
August | 0.551832E+10 | 0.163155E+10 | 0.427582E+10 | 0.325877E+10 | 0.101705E+10 | 0.00 | 0.00 |
September | 0.406311E+10 | 0.163868E+10 | 0.319172E+10 | 0.225805E+10 | 0.933672E+09 | 0.00 | 0.00 |
October | 0.300757E+10 | 0.189834E+10 | 0.236966E+10 | 0.163508E+10 | 0.734586E+09 | 0.00 | 0.00 |
November | 0.233150E+10 | 0.187468E+10 | 0.186967E+10 | 0.119996E+10 | 0.669711E+09 | 0.00 | 0.00 |
December | 0.212903E+10 | 0.204773E+10 | 0.169211E+10 | 0.115367E+10 | 0.538444E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.463417E+11 | 0.202586E+11 | 0.362470E+11 | 0.247774E+11 | 0.114696E+11 | 0.00 | 0.00 |
Minimum of Months | 0.212903E+10 | 0.138566E+10 | 0.169211E+10 | 0.104862E+10 | 0.538444E+09 | 0.00 | 0.00 |
Maximum of Months | 0.593189E+10 | 0.204773E+10 | 0.461340E+10 | 0.343333E+10 | 0.144282E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.60 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.19 | 7.03 | 3.12 | 2.95 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.60 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.61 | 10.61 | 2.62 | 4.75 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.64 | 10.56 | 2.92 | 6.16 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.02 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.75 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.61 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.49 | 13.65 | 2.19 | 8.98 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.71 | 9.60 | 2.71 | 7.73 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.42 | 6.22 | 2.47 | 2.40 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.80 | 3.19 | 2.50 | 0.04 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.75 | 10.02 | 2.59 | 5.48 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.80 | 3.19 | 2.19 | 0.04 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.44 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.65 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.80 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.11 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.03 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.58 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.48 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.18 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.88 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.83 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.94 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.06 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.06 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.18 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.2 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.20 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.32 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.55 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.53 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.2 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.02 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.40 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.31 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.58 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.18 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.18 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.84 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.08 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.63 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.63 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.84 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.84 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.33 | 3.77 | 8.01 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.02 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.46 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.91 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.63 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.91 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.884810E+09 | -742388752.3 | 0.00 | 0.00 | 744.00 | 0.00 | -142420795.8 | 58.99 | 0.00 | 0.00 |
February | 0.810379E+09 | -682812905.6 | 0.00 | 0.00 | 672.00 | 0.00 | -127566180.5 | 58.99 | 0.00 | 0.00 |
March | 0.929960E+09 | -789359913.9 | 0.00 | 0.00 | 744.00 | 0.00 | -140599690.0 | 58.99 | 0.00 | 0.00 |
April | 0.848408E+09 | -718025451.6 | 0.00 | 0.00 | 720.00 | 0.00 | -130382860.0 | 58.99 | 0.00 | 0.00 |
May | 0.861281E+09 | -727630138.6 | 0.00 | 0.00 | 744.00 | 0.00 | -133650502.7 | 58.99 | 0.00 | 0.00 |
June | 0.836802E+09 | -708287160.0 | 0.00 | 0.00 | 720.00 | 0.00 | -128514436.8 | 58.99 | 0.00 | 0.00 |
July | 0.805962E+09 | -674427731.2 | 0.00 | 0.00 | 744.00 | 0.00 | -131534445.1 | 58.99 | 0.00 | 0.00 |
August | 0.855700E+09 | -723276609.1 | 0.00 | 0.00 | 744.00 | 0.00 | -132423212.0 | 58.99 | 0.00 | 0.00 |
September | 0.808697E+09 | -680505158.4 | 0.00 | 0.00 | 720.00 | 0.00 | -128192267.2 | 58.99 | 0.00 | 0.00 |
October | 0.830529E+09 | -697695291.6 | 0.00 | 0.00 | 744.00 | 0.00 | -132834049.3 | 58.99 | 0.00 | 0.00 |
November | 0.821357E+09 | -687585876.4 | 0.00 | 0.00 | 720.00 | 0.00 | -133771506.6 | 58.99 | 0.00 | 0.00 |
December | 0.873072E+09 | -732063956.0 | 0.00 | 0.00 | 744.00 | 0.00 | -141008088.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.101670E+11 | -.856406E+10 | 8760.00 | -.160290E+10 | 58.99 | |||||
Minimum of Months | 0.805962E+09 | -789359913.9 | 0.00 | 0.00 | 672.00 | 0.00 | -142420795.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.929960E+09 | -674427731.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127566180.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | ||||||||||
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561826E+09 | 29320.49 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249385E+09 | 29320.49 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408988E+09 | 29320.49 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23509248.61 | 29320.49 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 230335.02 | 311.94 | 15-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74077531.42 | 24525.68 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305413E+09 | 29320.49 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162343E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561826E+09 | 29320.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.464371E+09 | 30700.91 | 03-JAN-02:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36409256.05 | 59566.83 | 30-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500780E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464371E+09 | 59566.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.449989E+09 | 0.431709E+09 | 5504.55 | 18-JAN-14:20 | 5504.55 | 0.00 |
February | 0.00 | 0.00 | 0.133666E+09 | 0.132552E+09 | 4856.89 | 03-FEB-15:00 | 4856.89 | 0.00 |
March | 0.00 | 0.00 | 0.367046E+09 | 0.310675E+09 | 20314.09 | 23-MAR-17:15 | 13529.12 | 0.00 |
April | 0.00 | 0.00 | 0.150564E+10 | 0.122565E+10 | 20709.17 | 26-APR-17:10 | 15705.29 | 0.00 |
May | 0.00 | 0.00 | 0.175937E+10 | 0.145228E+10 | 20409.89 | 02-MAY-17:10 | 13743.12 | 0.00 |
June | 0.00 | 0.00 | 0.493809E+10 | 0.366183E+10 | 21769.82 | 29-JUN-17:42 | 14198.90 | 0.00 |
July | 0.00 | 0.00 | 0.914355E+10 | 0.641287E+10 | 22476.96 | 23-JUL-16:27 | 16453.30 | 0.00 |
August | 0.00 | 0.00 | 0.975880E+10 | 0.671546E+10 | 22318.86 | 18-AUG-17:08 | 12906.27 | 0.00 |
September | 0.00 | 0.00 | 0.524209E+10 | 0.387605E+10 | 22560.28 | 21-SEP-22:20 | 12474.16 | 0.00 |
October | 0.00 | 0.00 | 0.482439E+10 | 0.397444E+10 | 22315.25 | 04-OCT-17:11 | 12049.92 | 0.00 |
November | 0.00 | 0.00 | 0.402083E+09 | 0.392599E+09 | 6086.95 | 18-NOV-14:30 | 6086.95 | 0.00 |
December | 0.00 | 0.00 | 0.537830E+09 | 0.534619E+09 | 6094.39 | 05-DEC-15:00 | 6094.39 | 0.00 |
Annual Sum or Average | 0.390625E+11 | 0.291207E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.133666E+09 | 0.132552E+09 | 4856.89 | 4856.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.975880E+10 | 0.671546E+10 | 22560.28 | 16453.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 149.83 | 111.78 | 0.16 | 23-MAR-15:10 | 0.12 | 0.00 |
April | 0.00 | 0.00 | 0.418124E+09 | 0.351905E+09 | 52329.77 | 30-APR-12:41 | 42969.40 | 0.00 |
May | 0.00 | 0.00 | 0.374523E+09 | 0.311889E+09 | 12405.19 | 04-MAY-12:00 | 10409.11 | 0.00 |
June | 0.00 | 0.00 | 0.332474E+10 | 0.234192E+10 | 55350.38 | 29-JUN-17:51 | 34038.98 | 0.00 |
July | 0.00 | 0.00 | 0.109444E+11 | 0.743795E+10 | 57343.90 | 31-JUL-17:08 | 34533.42 | 0.00 |
August | 0.00 | 0.00 | 0.116685E+11 | 0.775791E+10 | 57253.97 | 06-AUG-10:20 | 34428.22 | 0.00 |
September | 0.00 | 0.00 | 0.323335E+10 | 0.269461E+10 | 55235.72 | 10-SEP-10:51 | 36233.46 | 0.00 |
October | 0.00 | 0.00 | 0.379824E+10 | 0.341587E+10 | 57504.96 | 01-OCT-11:55 | 35748.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.337619E+11 | 0.243121E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.116685E+11 | 0.775791E+10 | 57504.96 | 42969.40 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135541E+10 | 0.36 | 1357.96 | 07-JAN-07:40 | 0.95 |
February | 0.124177E+10 | 0.37 | 1357.96 | 16-FEB-17:00 | 0.95 |
March | 0.146031E+10 | 0.39 | 1357.96 | 17-MAR-13:50 | 0.94 |
April | 0.141276E+10 | 0.40 | 1357.96 | 01-APR-11:10 | 0.95 |
May | 0.150674E+10 | 0.42 | 1357.96 | 13-MAY-08:15 | 0.95 |
June | 0.173857E+10 | 0.53 | 1357.96 | 08-JUN-14:50 | 0.94 |
July | 0.188537E+10 | 0.55 | 1357.96 | 21-JUL-08:70 | 0.94 |
August | 0.203538E+10 | 0.59 | 1357.96 | 16-AUG-08:00 | 0.94 |
September | 0.164251E+10 | 0.52 | 1357.96 | 16-SEP-09:40 | 0.94 |
October | 0.155812E+10 | 0.43 | 1357.96 | 16-OCT-06:40 | 0.95 |
November | 0.129227E+10 | 0.35 | 1357.96 | 01-NOV-14:50 | 0.95 |
December | 0.135049E+10 | 0.36 | 1357.96 | 04-DEC-15:00 | 0.95 |
Annual Sum or Average | 0.184797E+11 | 0.44 | |||
Minimum of Months | 0.124177E+10 | 0.35 | 1357.96 | 0.94 | |
Maximum of Months | 0.203538E+10 | 0.59 | 1357.96 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271847E+10 | 0.36 | 2726.31 | 02-JAN-07:10 | 0.91 |
February | 0.248313E+10 | 0.34 | 2726.31 | 01-FEB-07:10 | 0.91 |
March | 0.291651E+10 | 0.37 | 2726.31 | 01-MAR-07:05 | 0.91 |
April | 0.270392E+10 | 0.35 | 2726.31 | 08-APR-13:40 | 0.91 |
May | 0.280701E+10 | 0.35 | 2726.31 | 03-MAY-10:00 | 0.91 |
June | 0.286363E+10 | 0.37 | 2726.31 | 06-JUN-12:30 | 0.91 |
July | 0.289402E+10 | 0.36 | 2726.31 | 01-JUL-14:50 | 0.90 |
August | 0.301828E+10 | 0.38 | 2726.31 | 01-AUG-09:50 | 0.90 |
September | 0.272252E+10 | 0.35 | 2726.31 | 01-SEP-10:30 | 0.91 |
October | 0.273483E+10 | 0.35 | 2726.31 | 03-OCT-13:02 | 0.90 |
November | 0.259109E+10 | 0.33 | 2726.31 | 01-NOV-06:03 | 0.91 |
December | 0.269905E+10 | 0.34 | 2726.31 | 01-DEC-07:03 | 0.91 |
Annual Sum or Average | 0.331525E+11 | 0.35 | |||
Minimum of Months | 0.248313E+10 | 0.33 | 2726.31 | 0.90 | |
Maximum of Months | 0.301828E+10 | 0.38 | 2726.31 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.33 | 2.02 |
February | 1.14 | 1.39 |
March | 1.28 | 1.62 |
April | 2.10 | 2.19 |
May | 3.65 | 0.80 |
June | 9.58 | 0.06 |
July | 17.11 | 0.06 |
August | 23.47 | 0.04 |
September | 14.65 | 0.00 |
October | 11.18 | 0.18 |
November | 0.67 | 4.02 |
December | 1.54 | 1.85 |
Annual Sum or Average | 87.70 | 0.27 |
Minimum of Months | 0.67 | 0.00 |
Maximum of Months | 23.47 | 4.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 2.03 | 0.00 |
July | 3.10 | 0.00 |
August | 2.88 | 0.00 |
September | 0.50 | 0.00 |
October | 0.47 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.06 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.10 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 3.17 | 0.00 |
August | 1.24 | 0.00 |
September | 0.00 | 0.00 |
October | 0.18 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 4.58 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.17 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147763E+10 | 0.822111E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127806E+10 | 0.371004E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155839E+10 | 0.603423E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181080E+10 | 34684979.65 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196850E+10 | 359191.54 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.300441E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.419405E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.449848E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.302019E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.284397E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.140122E+10 | 0.112041E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149656E+10 | 0.452023E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.285523E+11 | 0.239565E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127806E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.449848E+10 | 0.822111E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.271847E+10 | 0.701815E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.248313E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.291651E+10 | 54974357.94 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.282268E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.291427E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.378630E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.587425E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.620457E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.369300E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.389986E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.259109E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.269905E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.426032E+11 | 0.756790E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.248313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.620457E+10 | 0.701815E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135541E+10 | 0.449989E+09 | 0.561826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124177E+10 | 0.133666E+09 | 0.249385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146031E+10 | 0.367046E+09 | 0.408988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141276E+10 | 0.150564E+10 | 23509248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150674E+10 | 0.175937E+10 | 230335.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173857E+10 | 0.493809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188537E+10 | 0.914355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203538E+10 | 0.975880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164251E+10 | 0.524209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155812E+10 | 0.482439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129227E+10 | 0.402083E+09 | 74077531.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135049E+10 | 0.537830E+09 | 0.305413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184797E+11 | 0.390625E+11 | 0.162343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124177E+10 | 0.133666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203538E+10 | 0.975880E+10 | 0.561826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271847E+10 | 0.00 | 0.464371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291651E+10 | 149.83 | 36409256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270392E+10 | 0.418124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280701E+10 | 0.374523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286363E+10 | 0.332474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289402E+10 | 0.109444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.301828E+10 | 0.116685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272252E+10 | 0.323335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273483E+10 | 0.379824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331525E+11 | 0.337619E+11 | 0.500780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.248313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301828E+10 | 0.116685E+11 | 0.464371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.135541E+10 | 0.00 | 0.00 | 0.00 | 0.122220E+09 | 0.00 | 0.822111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124177E+10 | 0.00 | 0.00 | 0.00 | 36290167.28 | 0.00 | 0.371004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146031E+10 | 0.00 | 0.00 | 0.00 | 98074794.32 | 0.00 | 0.603423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141276E+10 | 0.00 | 0.00 | 0.00 | 0.398048E+09 | 0.00 | 34684979.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150674E+10 | 0.00 | 0.00 | 0.00 | 0.461760E+09 | 0.00 | 359191.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173857E+10 | 0.00 | 0.00 | 0.00 | 0.126584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188537E+10 | 0.00 | 0.00 | 0.00 | 0.230868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203538E+10 | 0.00 | 0.00 | 0.00 | 0.246310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164251E+10 | 0.00 | 0.00 | 0.00 | 0.137767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155812E+10 | 0.00 | 0.00 | 0.00 | 0.128585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129227E+10 | 0.00 | 0.00 | 0.00 | 0.108952E+09 | 0.00 | 0.112041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135049E+10 | 0.00 | 0.00 | 0.00 | 0.146075E+09 | 0.00 | 0.452023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184797E+11 | 0.00 | 0.00 | 0.00 | 0.100726E+11 | 0.00 | 0.239565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124177E+10 | 0.00 | 0.00 | 0.00 | 36290167.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203538E+10 | 0.00 | 0.00 | 0.00 | 0.246310E+10 | 0.00 | 0.822111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.271847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291651E+10 | 0.00 | 0.00 | 0.00 | 43.67 | 0.00 | 54974357.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270392E+10 | 0.00 | 0.00 | 0.00 | 0.118759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280701E+10 | 0.00 | 0.00 | 0.00 | 0.107262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286363E+10 | 0.00 | 0.00 | 0.00 | 0.922669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289402E+10 | 0.00 | 0.00 | 0.00 | 0.298022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.301828E+10 | 0.00 | 0.00 | 0.00 | 0.318628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272252E+10 | 0.00 | 0.00 | 0.00 | 0.970484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273483E+10 | 0.00 | 0.00 | 0.00 | 0.116503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331525E+11 | 0.00 | 0.00 | 0.00 | 0.945071E+10 | 0.00 | 0.756790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.248313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301828E+10 | 0.00 | 0.00 | 0.00 | 0.318628E+10 | 0.00 | 0.701815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400792E+09 | 16246498.25 | 0.00 | 1598388.55 | 0.00 | 83523315.92 | 0.133324E+10 | 0.00 | 0.37 |
February | 0.461329E+09 | 7863350.53 | 0.00 | 1532215.12 | 0.00 | 17061498.48 | 0.145696E+10 | 0.00 | 0.37 |
March | 0.539551E+09 | 1863147.76 | 0.00 | 2087696.47 | 0.00 | 40821558.50 | 0.173737E+10 | 0.00 | 0.40 |
April | 80618243.86 | 18156023.83 | 0.00 | 5975726.25 | 0.00 | 0.00 | 0.330492E+10 | 0.00 | 0.81 |
May | 45732281.07 | 14000394.99 | 0.00 | 7663743.28 | 0.00 | 0.00 | 0.398995E+10 | 0.00 | 0.91 |
June | 21018008.87 | 0.236950E+09 | 0.00 | 11480991.35 | 0.00 | 0.00 | 0.357024E+10 | 0.00 | 1.23 |
July | 23053237.12 | 0.860050E+09 | 0.00 | 13451686.09 | 0.00 | 0.00 | 0.230702E+10 | 0.00 | 1.17 |
August | 28482539.76 | 0.106792E+10 | 0.00 | 10352803.28 | 40485.48 | 0.00 | 0.232362E+10 | 0.00 | 1.25 |
September | 25444639.65 | 0.284046E+09 | 0.00 | 9145325.91 | 0.00 | 0.00 | 0.313739E+10 | 0.00 | 1.12 |
October | 33407748.94 | 0.421467E+09 | 0.00 | 6840859.01 | 0.00 | 0.00 | 0.241823E+10 | 0.00 | 0.89 |
November | 0.216840E+09 | 6547919.16 | 0.00 | 2866028.27 | 0.00 | 0.00 | 0.232707E+10 | 0.00 | 0.53 |
December | 0.383932E+09 | 7875342.37 | 0.00 | 2031807.07 | 0.00 | 19653440.16 | 0.150158E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.226020E+10 | 0.294299E+10 | 0.00 | 75027270.64 | 40485.48 | 0.161060E+09 | 0.294076E+11 | 0.00 | 0.80 |
Minimum of Months | 21018008.87 | 1863147.76 | 0.00 | 1532215.12 | 0.00 | 0.00 | 0.133324E+10 | 0.00 | 0.37 |
Maximum of Months | 0.539551E+09 | 0.106792E+10 | 0.00 | 13451686.09 | 40485.48 | 83523315.92 | 0.398995E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188510E+10 | 0.00 | 0.00 | 0.00 | 34412888.68 | 0.00 | 0.00 | 0.00 | 0.15 |
February | 0.208887E+10 | 0.00 | 0.00 | 0.00 | 8320935.36 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 0.265096E+10 | 0.00 | 0.00 | 119403.60 | 501537.61 | 0.00 | 0.147949E+09 | 0.00 | 0.17 |
April | 0.188136E+10 | 2374539.24 | 0.00 | 2903664.84 | 1741673.93 | 0.00 | 0.201959E+10 | 0.00 | 0.26 |
May | 0.183051E+10 | 2108883.15 | 0.00 | 3435789.71 | 0.00 | 0.00 | 0.266719E+10 | 0.00 | 0.29 |
June | 0.908448E+09 | 13816103.97 | 0.00 | 12582412.37 | 0.00 | 0.00 | 0.473510E+10 | 0.00 | 0.52 |
July | 0.145809E+09 | 0.641799E+09 | 0.00 | 24701339.97 | 0.00 | 0.00 | 0.491579E+10 | 0.00 | 0.69 |
August | 0.260206E+09 | 0.724545E+09 | 0.00 | 21167943.12 | 0.00 | 0.00 | 0.399499E+10 | 0.00 | 0.71 |
September | 0.685907E+09 | 0.183320E+09 | 0.00 | 7898164.61 | 82992.75 | 0.00 | 0.481876E+10 | 0.00 | 0.47 |
October | 0.984449E+09 | 0.447680E+09 | 0.00 | 3275222.64 | 7264470.08 | 0.00 | 0.207152E+10 | 0.00 | 0.33 |
November | 0.216996E+10 | 0.00 | 0.00 | 0.00 | 4983299.04 | 0.00 | 0.00 | 0.00 | 0.15 |
December | 0.180296E+10 | 0.00 | 0.00 | 0.00 | 28992278.79 | 0.00 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.172945E+11 | 0.201564E+10 | 0.00 | 76083940.86 | 86300076.23 | 0.00 | 0.253709E+11 | 0.00 | 0.34 |
Minimum of Months | 0.145809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Maximum of Months | 0.265096E+10 | 0.724545E+09 | 0.00 | 24701339.97 | 34412888.68 | 0.00 | 0.491579E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |