Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1128.98 | 233.50 | 233.50 |
Net Site Energy | 1128.98 | 233.50 | 233.50 |
Total Source Energy | 2943.47 | 608.77 | 608.77 |
Net Source Energy | 2943.47 | 608.77 | 608.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 303.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 825.56 | 303.42 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 303.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 47.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.77 | 62.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 170.74 | 62.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.77 | 62.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 170.74 | 62.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 825.563 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 825.563 | 100.00 |
Total On-Site and Utility Electric Sources | 825.563 | 100.00 |
Total Electricity End Uses | 825.563 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 53.67 |
Time Setpoint Not Met During Occupied Cooling | 0.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1819.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:50 | 19-FEB-07:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 166324.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10155.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5883.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1761.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 63533.53 | 166324.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 166324.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10155.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3578.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1761.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 328.91 | 0.00 | 0.00 | 0.00 |
Cooling | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2614.56 | 328.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 68.02 | 0.00 | 0.00 | 0.00 |
Cooling | 4.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 540.74 | 68.02 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 68.02 | 0.00 | 0.00 | 0.00 |
Cooling | 4.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 540.74 | 68.02 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.02 |
ZONE2 FINE STORAGE DIRECT AIR | 2.20 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.71 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.71 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 111098.94 |
PSZ-OFFICE HEATING COIL | 26207.30 |
PSZ-FINE STORAGE HEATING COIL | 74259.09 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 111098.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-FINE STORAGE | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 1.00 | 1.000000 | 2.20 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.02 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.20 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 16937.16 | 26207.30 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.20 | 2.20 | 2.20 | 2.20 | 43683.90 | 74259.09 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.02 | 0.511585 | 1.02 | 16937.10 | 16937.16 | 8468.58 | 16937.16 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.20 | 1.10 | 2.20 | 41346.71 | 43683.90 | 21841.95 | 43683.90 | 0.737998 | 0.738000 | 0.738000 | 0.738000 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.02 | 1166.53 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.20 | 2411.81 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.71045622E-12 | 0.18350169E-15 | 0.20920636E-14 | 0.12692337E-15 |
13 | 3 | -0.36041595E-03 | 0.57471575E-06 | -0.52051292E-04 | 0.13635641E-12 |
14 | 2 | 1.6814491 | 0.12908092E-01 | 1.0963028 | -0.69095641E-04 |
15 | 1 | -7.2068525 | 0.34008243 | -16.815156 | 0.32221486 |
16 | 0 | 6.0979960 | 0.21924101 | 16.291138 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20920636E-14 | 0.18350169E-15 | 0.71045622E-12 | 0.12692337E-15 |
85 | 3 | -0.52051292E-04 | 0.57471575E-06 | -0.36041595E-03 | 0.13635641E-12 |
86 | 2 | 1.0963028 | 0.12908092E-01 | 1.6814491 | -0.69095641E-04 |
87 | 1 | -16.815156 | 0.34008243 | -7.2068525 | 0.32221486 |
88 | 0 | 16.291138 | 0.21924101 | 6.0979960 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10216.60840 | 12259.93008 | 0.85265 | 1.02317 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.79438E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10094.18587 | 12113.02305 | 0.28739 | 0.34487 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 28226.93493 | 33872.32192 | 1.83630 | 2.20356 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.79438E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38792.04135 | 46550.44962 | 0.93042 | 1.11650 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 92582.44547 | 111098.93457 | 2.26113 | 2.71335 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15015.58 | 1.02317 | 1.02317 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10875.64 | 0.34487 | 0.34487 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 40003.48 | 2.20356 | 2.20356 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 42562.17 | 1.11650 | 1.11650 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02317 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.20356 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.71335 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.71335 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 111098.93870 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 111098.93457 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02317 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02317 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02317 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02317 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02317 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.02317 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.20356 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.20356 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.20356 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.20356 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.20356 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.20356 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.02317 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.20356 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02317 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02317 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02317 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02317 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02317 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02317 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51159 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02317 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16937.09651 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16937.16000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8468.58000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16937.16000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16937.16000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26207.30128 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02317 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1166.53086 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26207.30128 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.20356 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.20356 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.20356 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.20356 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.20356 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.20356 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.10178 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.20356 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41346.70569 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 43683.90000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 21841.95000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 43683.90000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73800 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73800 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73800 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73800 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43683.90000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 74259.08542 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.20356 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2411.81344 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 74259.08542 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16143.2 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 41972.9 | 13.62 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1509785336 | 0.1645515693 | Pass | Pass | 0.4351745273 | 2.4307136118 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5118362922 | 0.4885217997 | Pass | Pass | 0.5729197616 | 0.6989664006 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.6010961560E-005 | 5.4706198270E-005 | Pass | Pass | 5.7359380696E-002 | 6.9278752591E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.826 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.092 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.55 | 83.55 | 123.22 | |
Exterior Lighting Total | 7857.24 | 123.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16937.16 | 13527.03 | 3410.13 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43683.90 | 32238.72 | 11445.18 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16143.2 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 41972.9 | 13.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 111098.94 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26207.30 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 74259.09 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.71 | 252.10 | 92.91 | 1.00 | 3.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.02 | 1166.53 | 1140.11 | 1.00 | 1.36 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.20 | 2411.81 | 1094.51 | 1.00 | 1.27 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10216.61 | 12259.93 | 51.76 | 0.853 | 1.023 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00814 | 27.94 | 0.00879 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 28226.93 | 33872.32 | 24.31 | 1.836 | 2.204 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00809 | 29.40 | 0.00879 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00383 | 29.40 | 0.00879 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10094.19 | 12113.02 | 51.14 | 0.287 | 0.345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00738 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38792.04 | 46550.45 | 33.41 | 0.930 | 1.117 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00576 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 92582.45 | 111098.93 | 34.67 | 2.261 | 2.713 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00774 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.02 | 1.02 | 0.34 | 0.34 | 1.0232 | 1.0232 | 1.0232 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.20 | 2.20 | 1.12 | 1.12 | 2.2036 | 2.2036 | 2.2036 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 111098.939 | 111098.939 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 111098.94 | 111098.94 | 2.713352 | 4.88 | 4.88 | 0.00592120 | 43.33 | 26.92 | 0.01600000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 9.99 | 0.00773867 | 99.9999 | 111098.93 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16937.160 | 0.000 | 1.023170 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16937.16 | 16324.04 | 1.023170 | 24.30 | 16.08 | 0.00820792 | 12.00 | 11.13 | 0.00800000 | 27.94 | 0.00879438 | 17.82 | 9.9969 | 23.90 | 0.00814278 | 43.4944 | 10216.61 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26207.301 | 26207.301 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26207.30 | 26207.30 | 1.023174 | 13.56 | 9.68 | 0.00599147 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 9.9968 | 21.10 | 0.00738338 | 46.8142 | 10094.19 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 43683.900 | 0.000 | 2.203560 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 43683.90 | 42247.19 | 2.203560 | 27.22 | 17.11 | 0.00822749 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00879438 | 18.30 | 19.2739 | 26.70 | 0.00809214 | 36.5952 | 28226.93 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 74259.085 | 74259.085 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 74259.09 | 74259.09 | 2.203564 | 8.04 | 5.43 | 0.00459419 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.2739 | 15.55 | 0.00576304 | 51.8872 | 38792.04 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 111098.939 | 111098.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1870 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.713352 | 3.22072369 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 111098.94 | 111098.94 | 1.0000 | 3.22072369 | 2.713352 | 4.88 | 4.88 | 0.00592120 | 19768.3 | 43.33 | 26.92 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111098.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 9.99 | 0.00773867 | 9.99 | 0.00773867 | 99.9999 | 111098.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16937.160 | 0.000 | 1.023170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0981 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16937.16 | 16324.04 | 1.0000 | 1.21449336 | 1.023170 | 24.30 | 16.08 | 0.00820792 | 45319.8 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16937.16 | 27.94 | 0.00879438 | 17.82 | 0.10228487 | 9.9969 | 23.90 | 0.00814278 | 23.90 | 0.00814278 | 43.4944 | 10216.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26207.301 | 26207.301 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.023174 | 1.21449818 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26207.30 | 26207.30 | 1.0000 | 1.21449818 | 1.023174 | 13.56 | 9.68 | 0.00599147 | 28762.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26207.30 | -4.20 | 0.00269032 | -4.20 | 0.10228487 | 9.9968 | 21.05 | 0.00738338 | 21.10 | 0.00738338 | 46.8142 | 10094.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43683.900 | 0.000 | 2.203560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1345 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 43683.90 | 42247.19 | 1.0000 | 2.61560541 | 2.203560 | 27.22 | 17.11 | 0.00822749 | 48344.7 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43683.90 | 29.40 | 0.00879438 | 18.30 | 0.42471267 | 19.2739 | 26.70 | 0.00809214 | 26.70 | 0.00809214 | 36.5952 | 28226.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 74259.085 | 74259.085 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.203564 | 2.61561074 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 74259.09 | 74259.09 | 1.0000 | 2.61561074 | 2.203564 | 8.04 | 5.43 | 0.00459419 | 19636.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 74259.09 | -4.20 | 0.00269032 | -4.20 | 0.42471267 | 19.2739 | 15.55 | 0.00576304 | 15.55 | 0.00576304 | 51.8872 | 38792.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.20 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2041.17 | 3053.17 | 1819.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2041.17 | 3053.17 | 1819.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 58.17 | 32.17 | 53.67 | 0.33 |
ZONE2 FINE STORAGE | 406.00 | 1.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 450.33 | 33.33 | 53.67 | 0.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.344 | 0.267 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
Electricity:Building | 621.40 | 4992.32 | 01-JAN-00:10 | 48037.94 | 24-JUL-13:00 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 421.81 | 2759.73 | 01-JAN-00:10 | 33963.13 | 24-JUL-13:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.55 | 483.00 | 14-APR-05:10 | 2403.97 | 14-FEB-12:10 |
WaterSystems:Electricity | 26.55 | 483.00 | 14-APR-05:10 | 2403.97 | 14-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 26.55 | 483.00 | 14-APR-05:10 | 2403.97 | 14-FEB-12:10 |
Fans:Electricity | 47.75 | 0.00 | 02-JAN-18:40 | 5883.64 | 24-JUL-13:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.16 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-AUG-17:50 |
Ventilation (simple):Fans:Electricity | 0.16 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-AUG-17:50 |
ElectricityPurchased:Facility | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
ElectricityPurchased:Plant | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
Cogeneration:ElectricityPurchased | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
ElectricityNet:Plant | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
Cogeneration:ElectricityNet | 825.56 | 5475.32 | 08-JAN-13:20 | 63533.53 | 10-AUG-14:50 |
Electricity:HVAC | 54.39 | 0.00 | 02-JAN-18:40 | 13986.38 | 10-AUG-15:10 |
General:Fans:Electricity | 47.59 | 0.00 | 02-JAN-18:40 | 3830.44 | 06-DEC-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 6.80 | 0.00 | 01-JAN-00:10 | 10408.04 | 10-AUG-15:10 |
ExteriorLights:Electricity | 123.22 | 0.00 | 01-JAN-08:10 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.22 | 0.00 | 01-JAN-08:10 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 303.42 | 0.00 | 02-JAN-18:40 | 166324.40 | 19-FEB-07:10 |
Gas:HVAC | 303.42 | 0.00 | 02-JAN-18:40 | 166324.40 | 19-FEB-07:10 |
Heating:Gas | 303.42 | 0.00 | 02-JAN-18:40 | 166324.40 | 19-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 499.50 | 0.00 | 02-JAN-18:40 | 255604.74 | 19-FEB-07:10 |
EnergyTransfer:Building | 251.66 | 0.00 | 02-JAN-18:40 | 128491.76 | 19-FEB-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 37.51 | 0.00 | 01-JAN-00:40 | 18499.63 | 17-JAN-06:10 |
Heating:EnergyTransfer | 218.46 | 0.00 | 02-JAN-18:40 | 128491.76 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 22.59 | 0.00 | 01-JAN-00:40 | 18499.63 | 17-JAN-06:10 |
Cooling:EnergyTransfer | 33.20 | 0.00 | 01-JAN-00:10 | 27995.01 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.92 | 0.00 | 01-JAN-00:10 | 8455.37 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 115.13 | 0.00 | 01-JAN-00:40 | 41647.04 | 19-FEB-04:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 96.86 | 0.00 | 01-JAN-00:40 | 41647.04 | 19-FEB-04:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.28 | 0.00 | 01-JAN-00:10 | 20433.85 | 10-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 99.01 | 0.00 | 02-JAN-09:10 | 84805.42 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 99.01 | 0.00 | 02-JAN-09:10 | 84805.42 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 247.84 | 0.00 | 02-JAN-18:40 | 127112.98 | 19-FEB-07:10 |
HeatingCoils:EnergyTransfer | 221.24 | 0.00 | 02-JAN-18:40 | 127112.98 | 19-FEB-07:10 |
CoolingCoils:EnergyTransfer | 26.60 | 0.00 | 01-JAN-00:10 | 36572.92 | 10-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 22.592 | -14.921 | 0.000 | 0.000 | 3.940 | 30.994 | 31.946 | 8.171 | 0.000 | 0.152 | 0.000 | 0.000 | -8.641 | 0.000 | -17.324 | -56.908 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 96.855 | -18.275 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.327 | 0.002 | 0.000 | 0.000 | 0.000 | -118.528 | -97.035 |
ZONE3 BULK STORAGE | 99.014 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 27.795 | 0.000 | 3.088 | 0.000 | 0.000 | -16.424 | 0.000 | -386.054 | -149.064 |
Total Facility | 99.014 | 0.000 | 119.446 | -33.197 | 0.000 | 0.000 | 3.940 | 481.960 | 139.282 | 35.966 | 0.000 | 3.567 | 0.002 | 0.000 | -25.066 | 0.000 | -521.906 | -303.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-00:01 | 0.00 | 0.00 | 0.00 | -16350.65 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 15846.99 | 0.00 | -358.97 | 0.00 | -170.08 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-18:11 | 0.00 | 0.00 | 0.00 | -42739.48 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 42480.29 | 0.00 | -0.00 | 0.00 | -940.68 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-18:21 | 0.00 | 0.00 | 0.00 | -54928.68 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 2194.25 | 0.00 | 413.86 | 49109.54 | 0.00 | -23.28 | 0.00 | -3808.04 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-FEB-06:01 | 0.00 | 0.00 | 26132.06 | 0.00 | 0.00 | 0.00 | 55.22 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -159.99 | 0.00 | -288.24 | -26899.25 |
ZONE2 FINE STORAGE | 19-FEB-04:02 | 0.00 | 0.00 | 77481.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11537.57 | -67143.44 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 84805.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1913.83 | 0.00 | -48130.47 | -37520.51 |
Total Facility | 19-FEB-06:42 | 84484.04 | 0.00 | 76222.14 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2817.08 | 0.00 | -63972.26 | -98909.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0232 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0232 | 0.1000 | 1.0000 | 0.1023 | 0.1000 | ||
PSZ-FINE STORAGE | 2.2036 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.2036 | 0.1927 | 1.0000 | 0.4247 | 0.1927 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0232 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0232 | 1.0000 | 1.0000 | 0.1023 | 0.1000 | ||
PSZ-FINE STORAGE | 2.2036 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.2036 | 1.0000 | 1.0000 | 0.4247 | 0.1927 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0232 | 1.0232 | 1.0232 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.2036 | 2.2036 | 2.2036 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0232 | 1.0232 | 1.0232 | 1.0232 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2036 | 2.2036 | 2.2036 | 2.2036 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0232 | 1.0232 | 1.0232 | 0.1023 | 0.2966 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.2036 | 2.2036 | 2.2036 | 0.4247 | 0.3804 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0232 | 1.0232 | 1.0232 | 1.0232 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2036 | 2.2036 | 2.2036 | 2.2036 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 53.67 |
Number of hours cooling loads not met | 0.33 |
Number of hours not met | 54.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 303.42 | 166324.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 6.80 | 10408.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.22 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.16 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 47.59 | 3830.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.55 | 2403.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 825.56 |
Natural Gas | 0.00 | 303.42 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1128.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 1.41 |
Fans (All) | 9.88 |
Service Water Heating | 5.49 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 170.74 |
Subtotal | 170.74 |
Natural Gas [MJ/m2] | |
Space Heating | 62.75 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 62.75 |
Subtotal | 62.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 42.69 |
Space Heating | 26.88 |
Space Cooling | 0.60 |
Fans (All) | 4.23 |
Service Water Heating | 2.35 |
Receptacle Equipment | 12.34 |
Miscellaneous | 10.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.999005E+11 |
February | 0.000 | 0.696452E+11 |
March | 0.000 | 0.190523E+11 |
April | 0.000 | 0.720584E+10 |
May | 0.000 | 0.605424E+09 |
June | 0.000 | 0.112071E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.755610E+08 |
October | 0.000 | 0.466657E+10 |
November | 0.000 | 0.278337E+11 |
December | 0.000 | 0.743235E+11 |
Annual Sum or Average | 0.303421E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.999005E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 5.92 | 4.99 | 0.194972E+09 | 236.59 | 09-JAN-08:20 | 0.20 | -0.8 |
February | 596653.99 | 112.23 | 28-FEB-11:30 | 11.40 | 10.33 | 0.180586E+09 | 293.02 | 27-FEB-16:10 | 19.32 | 12.37 |
March | 12726802.42 | 380.33 | 11-MAR-15:00 | 8.30 | 7.17 | 0.214206E+09 | 301.58 | 18-MAR-15:00 | 20.60 | 10.40 |
April | 0.222504E+09 | 7140.59 | 27-APR-17:20 | 26.10 | 16.50 | 0.209722E+09 | 301.60 | 29-APR-15:39 | 20.73 | 14.70 |
May | 0.948792E+09 | 7746.71 | 15-MAY-17:15 | 23.30 | 12.89 | 0.243465E+09 | 301.60 | 04-MAY-13:09 | 22.48 | 15.27 |
June | 0.222688E+10 | 14547.92 | 28-JUN-17:10 | 26.52 | 16.71 | 0.254185E+09 | 301.60 | 21-JUN-12:39 | 21.33 | 14.94 |
July | 0.422063E+10 | 16350.56 | 24-JUL-00:01 | 19.22 | 14.35 | 0.248037E+09 | 301.61 | 25-JUL-15:00 | 23.90 | 17.57 |
August | 0.485297E+10 | 15637.36 | 14-AUG-00:01 | 20.33 | 15.33 | 0.268003E+09 | 301.60 | 23-AUG-13:20 | 27.63 | 18.37 |
September | 0.220925E+10 | 12544.04 | 14-SEP-17:10 | 24.45 | 16.69 | 0.244108E+09 | 301.60 | 14-SEP-15:50 | 24.32 | 17.01 |
October | 0.209885E+09 | 3202.75 | 04-OCT-16:00 | 21.10 | 11.38 | 0.211879E+09 | 301.59 | 06-OCT-15:09 | 17.30 | 12.20 |
November | 16910297.26 | 1124.96 | 04-NOV-15:50 | 20.18 | 15.91 | 0.189657E+09 | 301.58 | 04-NOV-14:09 | 21.10 | 15.93 |
December | 168583.88 | 53.43 | 02-DEC-15:50 | 10.78 | 4.71 | 0.195010E+09 | 239.56 | 02-DEC-15:20 | 11.33 | 5.19 |
Annual Sum or Average | 0.149213E+11 | 0.265383E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.71 | 0.180586E+09 | 236.59 | 0.20 | -0.8 | ||
Maximum of Months | 0.485297E+10 | 16350.56 | 26.52 | 16.71 | 0.268003E+09 | 301.61 | 27.63 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257479E+09 | 5211.43 | 07-JAN-12:05 | -0.4 | -0.5 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.470837E+09 | 3783.69 | 18-FEB-11:20 | 2.07 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.100062E+10 | 3304.85 | 01-MAR-09:10 | 4.37 | 0.89 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.911336E+09 | 5489.50 | 05-APR-06:10 | 7.98 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.125416E+10 | 7367.46 | 31-MAY-06:10 | 12.30 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.164436E+10 | 40452.92 | 28-JUN-17:31 | 25.97 | 16.66 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.416641E+10 | 42738.98 | 23-JUL-18:11 | 25.53 | 15.84 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.488598E+10 | 41998.25 | 15-AUG-18:01 | 25.30 | 15.98 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.184836E+10 | 10253.67 | 14-SEP-14:40 | 23.90 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.736291E+09 | 5873.70 | 11-OCT-06:10 | 7.80 | 6.13 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.606862E+09 | 3857.82 | 06-NOV-07:10 | 12.20 | 8.81 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.492903E+09 | 4038.80 | 06-DEC-12:00 | 3.30 | 3.23 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.182756E+11 | 0.00 | ||||||||
Minimum of Months | 0.257479E+09 | 3304.85 | -0.4 | -0.5 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.488598E+10 | 42738.98 | 25.97 | 17.00 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514619E+10 | 25746.14 | 11-JAN-06:01 | 9.90 |
February | 0.393138E+10 | 26132.10 | 24-FEB-06:01 | 13.90 |
March | 0.289852E+10 | 25765.70 | 08-MAR-06:01 | 10.18 |
April | 0.155339E+10 | 25542.08 | 10-APR-05:01 | 8.80 |
May | 0.416534E+09 | 25190.66 | 30-MAY-05:01 | 10.60 |
June | 87630497.93 | 15112.09 | 15-JUN-05:03 | 8.98 |
July | 10125891.69 | 499.76 | 24-JUL-06:10 | 17.48 |
August | 11565173.62 | 608.12 | 25-AUG-06:10 | 18.30 |
September | 61770020.68 | 17026.60 | 28-SEP-05:03 | 8.30 |
October | 0.120027E+10 | 25749.49 | 23-OCT-05:01 | 10.60 |
November | 0.290089E+10 | 25975.35 | 27-NOV-06:01 | 11.70 |
December | 0.437336E+10 | 25826.27 | 16-DEC-06:01 | 10.60 |
Annual Sum or Average | 0.225916E+11 | |||
Minimum of Months | 10125891.69 | 499.76 | 8.30 | |
Maximum of Months | 0.514619E+10 | 26132.10 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265958E+11 | 76646.41 | 15-JAN-04:42 | -2.9 |
February | 0.192903E+11 | 77480.86 | 19-FEB-04:02 | -5.1 |
March | 0.986571E+10 | 75229.59 | 24-MAR-04:23 | 3.05 |
April | 0.361164E+10 | 75177.25 | 11-APR-03:53 | 5.00 |
May | 0.245032E+09 | 2606.33 | 17-MAY-07:00 | 8.90 |
June | 0.226183E+09 | 2468.27 | 13-JUN-07:00 | 11.70 |
July | 0.180911E+09 | 2413.47 | 14-JUL-07:00 | 14.40 |
August | 0.216260E+09 | 2612.52 | 31-AUG-07:00 | 14.00 |
September | 0.205524E+09 | 2566.63 | 27-SEP-07:00 | 8.90 |
October | 0.216483E+10 | 60309.57 | 21-OCT-05:08 | 10.50 |
November | 0.120586E+11 | 76303.07 | 29-NOV-20:42 | 4.90 |
December | 0.221942E+11 | 76277.34 | 25-DEC-02:62 | 1.10 |
Annual Sum or Average | 0.968550E+11 | |||
Minimum of Months | 0.180911E+09 | 2413.47 | -5.1 | |
Maximum of Months | 0.265958E+11 | 77480.86 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405297E+11 | 59665.61 | 15-JAN-01:52 | -1.7 |
February | 0.274196E+11 | 84806.23 | 19-FEB-07:00 | -5.0 |
March | 65293094.57 | 7290.21 | 25-MAR-05:25 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.418304E+10 | 31234.22 | 29-NOV-21:00 | 5.00 |
December | 0.268163E+11 | 45092.02 | 25-DEC-01:52 | 1.10 |
Annual Sum or Average | 0.990139E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.405297E+11 | 84806.23 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218609E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184377E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180774E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8108793.10 | 0.147765E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 763737.40 | 0.136417E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6455379.12 | 0.112660E+10 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36711415.51 | 0.819793E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98465049.24 | 0.759165E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298635.13 | 0.838534E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140675E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173939E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195445E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.151803E+09 | 0.173241E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759165E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98465049.24 | 0.218609E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149039E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125796E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109567E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90073229.67 | 0.977398E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969429E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309311.09 | 0.921077E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58776257.20 | 0.830320E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178197E+09 | 0.750947E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522601E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826823E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998552E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121158E+11 |
Annual Sum or Average | 0.136656E+12 | 0.327356E+09 | 0.118528E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522601E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178197E+09 | 0.149039E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78993669.84 | 0.252097E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290428E+09 | 0.219710E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196386E+09 | 0.219990E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108338E+10 | 0.238368E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4884469.91 | 0.306178E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295705E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 694882.54 | 0.295073E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34508723.87 | 0.290844E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188796E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225717E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97388864.00 | 0.175505E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27731259.55 | 0.186361E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.181439E+10 | 0.289434E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175505E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108338E+10 | 0.306178E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5834.39 | 06-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5795.63 | 13-FEB-18:00 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 5689.35 | 24-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.27 | 27-APR-16:10 | 4875.40 | 19-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.11 | 05-MAY-16:10 | 4080.85 | 18-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.75 | 28-JUN-17:00 | 3238.78 | 14-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.02 | 24-JUL-16:10 | 2795.41 | 12-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.93 | 10-AUG-17:00 | 3190.74 | 01-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.75 | 14-SEP-17:00 | 3096.48 | 27-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4019.75 | 16-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5363.38 | 29-NOV-18:00 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5888.34 | 26-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2795.41 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.93 | 5888.34 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 20718.50 | 28-JAN-08:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 17959.39 | 13-FEB-08:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 16377.80 | 24-MAR-06:10 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4287.02 | 01-APR-16:00 | 13781.94 | 08-APR-07:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15631.68 | 10-MAY-15:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.52 | 28-JUN-17:50 | 13434.37 | 13-JUN-03:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.74 | 24-JUL-15:10 | 10060.04 | 03-JUL-15:05 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3590.70 | 08-AUG-17:00 | 12829.97 | 11-AUG-04:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 9820.98 | 26-SEP-15:10 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12378.54 | 31-OCT-20:27 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19433.92 | 29-NOV-18:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14389.65 | 22-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9820.98 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4287.02 | 20718.50 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6908.90 | 11-JAN-14:00 | 29089.87 | 14-JAN-19:52 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5595.82 | 24-FEB-04:00 | 36639.02 | 13-FEB-11:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9179.22 | 18-MAR-16:00 | 34601.31 | 22-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30378.46 | 01-APR-16:00 | 29482.24 | 18-APR-16:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.70 | 05-MAY-16:00 | 41869.90 | 10-MAY-15:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 43138.15 | 13-JUN-10:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.37 | 24-JUL-15:00 | 30509.02 | 03-JUL-16:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2283.30 | 29-AUG-14:55 | 41825.41 | 11-AUG-04:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 28901.47 | 26-SEP-15:50 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 23595.56 | 14-OCT-11:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7450.50 | 27-NOV-02:55 | 26512.26 | 29-NOV-17:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6667.65 | 14-DEC-12:00 | 37342.50 | 26-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23595.56 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 30378.46 | 43138.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.99 |
February | 112.23 | 28-FEB-11:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.79 |
March | 380.33 | 11-MAR-15:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.03 |
April | 7140.59 | 27-APR-17:20 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 0.00 |
May | 7746.71 | 15-MAY-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
June | 14547.92 | 28-JUN-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 | 0.00 |
July | 16350.56 | 24-JUL-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.08 |
August | 15637.36 | 14-AUG-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.89 |
September | 12544.04 | 14-SEP-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 | 0.00 |
October | 3202.75 | 04-OCT-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.80 |
November | 1124.96 | 04-NOV-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
December | 53.43 | 02-DEC-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16350.56 | 659.25 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 | 602.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5211.43 | 07-JAN-12:05 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.75 |
February | 3783.69 | 18-FEB-11:20 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3271.59 |
March | 3304.85 | 01-MAR-09:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.56 |
April | 5489.50 | 05-APR-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.21 |
May | 7367.46 | 31-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.08 |
June | 40452.92 | 28-JUN-17:31 | 0.00 | 9599.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.48 |
July | 42738.98 | 23-JUL-18:11 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.68 |
August | 41998.25 | 15-AUG-18:01 | 0.00 | 10798.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.61 |
September | 10253.67 | 14-SEP-14:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.42 |
October | 5873.70 | 11-OCT-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.85 |
November | 3857.82 | 06-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.62 |
December | 4038.80 | 06-DEC-12:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3304.85 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.48 | |
Maximum of Months | 42738.98 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 13798.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13224.76 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.91 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10013.80 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7111.77 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17872.33 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5959.64 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8370.92 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11283.90 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13251.58 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6622.13 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8647.89 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5487.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.91 | |
Maximum of Months | 0.00 | 0.00 | 13798.65 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17872.33 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.721581E+11 | 55081.28 | 24-JAN-16:00 | 0.999005E+11 | 129110.53 | 09-JAN-06:19 |
February | 0.645942E+11 | 51446.38 | 13-FEB-13:00 | 0.696452E+11 | 166324.40 | 19-FEB-07:10 |
March | 0.720111E+11 | 51178.38 | 01-MAR-13:30 | 0.190523E+11 | 55265.31 | 24-MAR-05:10 |
April | 0.661504E+11 | 52426.46 | 27-APR-14:00 | 0.720584E+10 | 43911.02 | 12-APR-05:10 |
May | 0.673645E+11 | 52481.27 | 06-MAY-14:09 | 0.605424E+09 | 11198.17 | 18-MAY-05:10 |
June | 0.663778E+11 | 56416.62 | 28-JUN-14:00 | 0.112071E+09 | 5626.41 | 14-JUN-06:10 |
July | 0.670878E+11 | 62545.43 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.725945E+11 | 63533.53 | 10-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.674254E+11 | 55539.54 | 14-SEP-14:39 | 75561020.29 | 6290.25 | 27-SEP-06:10 |
October | 0.691529E+11 | 52029.64 | 04-OCT-14:00 | 0.466657E+10 | 31821.03 | 30-OCT-05:19 |
November | 0.683405E+11 | 55076.71 | 29-NOV-16:30 | 0.278337E+11 | 86261.45 | 29-NOV-20:49 |
December | 0.723057E+11 | 55079.47 | 26-DEC-16:19 | 0.743235E+11 | 103255.08 | 26-DEC-06:49 |
Annual Sum or Average | 0.825563E+12 | 0.303421E+12 | ||||
Minimum of Months | 0.645942E+11 | 51178.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.725945E+11 | 63533.53 | 0.999005E+11 | 166324.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.133982E+11 | 0.115358E+11 | 0.00 | 0.482205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229878E+10 | 0.00 |
February | 0.366966E+11 | 0.110457E+11 | 0.105871E+11 | 0.00 | 0.417133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209340E+10 | 0.00 |
March | 0.423649E+11 | 0.107817E+11 | 0.123357E+11 | 0.00 | 0.417476E+10 | 0.00 | 0.00 | 289071.44 | 0.00 | 0.00 | 0.00 | 0.235378E+10 | 0.00 |
April | 0.397216E+11 | 0.898083E+10 | 0.114862E+11 | 0.00 | 0.367636E+10 | 0.00 | 0.00 | 70350660.86 | 0.00 | 0.00 | 0.00 | 0.221503E+10 | 0.00 |
May | 0.412341E+11 | 0.797667E+10 | 0.119357E+11 | 0.00 | 0.369554E+10 | 0.00 | 0.00 | 0.266465E+09 | 0.00 | 0.00 | 0.00 | 0.225597E+10 | 0.00 |
June | 0.408524E+11 | 0.701966E+10 | 0.118862E+11 | 0.00 | 0.370657E+10 | 0.00 | 0.00 | 0.742683E+09 | 0.00 | 0.00 | 0.00 | 0.217038E+10 | 0.00 |
July | 0.401034E+11 | 0.757595E+10 | 0.115358E+11 | 0.00 | 0.367685E+10 | 0.00 | 0.00 | 0.202895E+10 | 0.00 | 0.00 | 0.00 | 0.216695E+10 | 0.00 |
August | 0.423649E+11 | 0.869796E+10 | 0.123357E+11 | 0.00 | 0.407455E+10 | 0.00 | 0.00 | 0.290688E+10 | 0.00 | 0.00 | 0.00 | 0.221454E+10 | 0.00 |
September | 0.397216E+11 | 0.980112E+10 | 0.114862E+11 | 0.00 | 0.356218E+10 | 0.00 | 0.00 | 0.729021E+09 | 0.00 | 0.00 | 0.00 | 0.212529E+10 | 0.00 |
October | 0.401034E+11 | 0.116303E+11 | 0.115358E+11 | 0.00 | 0.362445E+10 | 0.00 | 0.00 | 50851318.18 | 0.00 | 0.00 | 0.00 | 0.220820E+10 | 0.00 |
November | 0.385909E+11 | 0.125732E+11 | 0.110862E+11 | 0.00 | 0.391885E+10 | 0.00 | 0.00 | 4775485.67 | 0.00 | 0.00 | 0.00 | 0.216666E+10 | 0.00 |
December | 0.401034E+11 | 0.137423E+11 | 0.115358E+11 | 0.00 | 0.464751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227678E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123224E+12 | 0.139282E+12 | 0.477510E+11 | 0.00 | 0.680026E+10 | 0.265458E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.701966E+10 | 0.105871E+11 | 0.00 | 0.356218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209340E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.137423E+11 | 0.123357E+11 | 0.00 | 0.482205E+10 | 0.00 | 0.00 | 0.290688E+10 | 0.00 | 0.00 | 0.00 | 0.235378E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.999005E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.696452E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.190523E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.720584E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.605424E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112071E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 75561020.29 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.466657E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.278337E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.743235E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303421E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.999005E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3830.44 | 03-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3830.44 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3830.44 | 24-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3578.34 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3578.34 | 05-MAY-13:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3578.34 | 10-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 5883.64 | 24-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 5883.64 | 08-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3578.34 | 08-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3578.34 | 13-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3830.44 | 24-NOV-07:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3830.44 | 06-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3578.34 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5883.64 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2397.36 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2403.97 | 14-FEB-12:09 | 0.00 |
March | 145.70 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2387.08 | 02-MAR-12:30 | 0.00 |
April | 1406.76 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2296.03 | 01-APR-11:00 | 0.00 |
May | 1410.34 | 15-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2120.23 | 05-MAY-11:00 | 0.00 |
June | 7051.44 | 28-JUN-17:49 | 0.00 | 0.00 | 0.00 | 1965.59 | 01-JUN-11:00 | 0.00 |
July | 9317.27 | 24-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1808.15 | 01-JUL-11:00 | 0.00 |
August | 10408.04 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1800.83 | 30-AUG-11:09 | 0.00 |
September | 4468.67 | 14-SEP-14:50 | 0.00 | 0.00 | 0.00 | 1822.51 | 26-SEP-11:00 | 0.00 |
October | 961.94 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2020.83 | 31-OCT-11:20 | 0.00 |
November | 555.82 | 04-NOV-15:30 | 0.00 | 0.00 | 0.00 | 2175.81 | 27-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2326.24 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1800.83 | 0.00 | ||
Maximum of Months | 10408.04 | 0.00 | 0.00 | 0.00 | 2403.97 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55081.28 | 24-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3830.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51446.38 | 13-FEB-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3830.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51178.38 | 01-MAR-13:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52426.46 | 27-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 1322.05 | 0.00 |
May | 52481.27 | 06-MAY-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 1381.00 | 0.00 |
June | 56416.62 | 28-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 5336.92 | 0.00 |
July | 62545.43 | 24-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5883.64 | 0.00 | 0.00 | 9166.26 | 0.00 |
August | 63533.53 | 10-AUG-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5883.64 | 0.00 | 0.00 | 10155.60 | 0.00 |
September | 55539.54 | 14-SEP-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 4463.25 | 0.00 |
October | 52029.64 | 04-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 947.28 | 0.00 |
November | 55076.71 | 29-NOV-16:30 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3830.44 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55079.47 | 26-DEC-16:19 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3830.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51178.38 | 31660.41 | 10112.62 | 0.00 | 0.00 | 3578.34 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63533.53 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 5883.64 | 0.00 | 0.00 | 10155.60 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 129110.53 | 09-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 166324.40 | 19-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 55265.31 | 24-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 43911.02 | 12-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11198.17 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5626.41 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6290.25 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 31821.03 | 30-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 86261.45 | 29-NOV-20:49 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 103255.08 | 26-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 166324.40 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.74 | 8.83 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.67 | 18.71 | 7.83 | 19.58 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8.67 | 19.95 | 8.67 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.50 | 20.16 | 6.50 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.17 | 20.47 | 1.17 | 20.47 | 0.83 | 24.51 | 0.00 | 0.00 |
June | 0.50 | 20.49 | 0.50 | 20.49 | 3.83 | 24.53 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.60 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 24.59 | 0.33 | 24.47 |
September | 0.33 | 20.51 | 0.33 | 20.51 | 3.00 | 24.49 | 0.00 | 0.00 |
October | 4.17 | 20.27 | 4.17 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.33 | 19.88 | 7.17 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.33 | 19.27 | 8.50 | 19.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.17 | 19.47 | 53.67 | 19.85 | 32.17 | 24.57 | 0.33 | 24.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 20.51 | 8.83 | 20.51 | 13.67 | 24.60 | 0.33 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 107.33 | 14.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76.83 | 14.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42.33 | 14.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14.17 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.33 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.33 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56.50 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102.50 | 14.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.00 | 14.64 | 0.00 | 1.67 | 27.32 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.33 | 14.92 | 0.00 | 0.00 | 1.17 | 27.33 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.11 | 262.83 | 21.06 | 262.83 | 21.06 |
March | 324.00 | 21.22 | 295.17 | 21.11 | 295.17 | 21.11 |
April | 300.00 | 21.76 | 188.17 | 21.14 | 188.17 | 21.14 |
May | 293.67 | 22.85 | 46.17 | 21.11 | 46.17 | 21.11 |
June | 244.00 | 23.34 | 13.83 | 23.39 | 2.33 | 20.90 |
July | 116.00 | 23.63 | 78.00 | 23.90 | 0.00 | 0.00 |
August | 90.17 | 23.58 | 105.17 | 23.90 | 0.00 | 0.00 |
September | 221.33 | 23.34 | 30.33 | 23.59 | 3.33 | 21.06 |
October | 300.00 | 21.86 | 162.33 | 21.12 | 162.33 | 21.12 |
November | 288.00 | 21.19 | 259.17 | 21.08 | 259.17 | 21.08 |
December | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
Annual Sum or Average | 3053.17 | 21.93 | 2041.17 | 21.39 | 1819.50 | 21.08 |
Minimum of Months | 90.17 | 21.05 | 13.83 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.63 | 300.00 | 23.90 | 300.00 | 21.14 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 1164462.30 | 289071.44 | 0.83 | 1164462.30 | 0.00 | 0.00 | 0.04 | 18-MAR-16:00 | 0.00 | 01-MAR-00:05 | 587.88 | 18-MAR-16:00 | 587.88 | 18-MAR-16:00 | 0.00 | 18-MAR-15:50 | 145.70 | 18-MAR-16:00 | 0.00 | 01-MAR-00:05 |
April | 0.287006E+09 | 70350660.86 | 28.83 | 0.273033E+09 | 13972856.46 | 0.00 | 0.58 | 27-APR-17:20 | 0.00 | 01-APR-00:10 | 8372.29 | 27-APR-17:20 | 8372.29 | 27-APR-17:20 | 430.20 | 28-APR-13:40 | 2105.45 | 27-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.110594E+10 | 0.266462E+09 | 127.56 | 0.104152E+10 | 64417699.93 | 0.00 | 0.61 | 15-MAY-17:15 | 0.00 | 01-MAY-00:10 | 8681.38 | 15-MAY-17:15 | 8681.38 | 15-MAY-17:15 | 673.40 | 06-MAY-13:30 | 2091.61 | 06-MAY-17:33 | 0.00 | 01-MAY-00:10 |
June | 0.268305E+10 | 0.646178E+09 | 237.92 | 0.258193E+10 | 0.101118E+09 | 0.00 | 1.00 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 | 16838.44 | 28-JUN-17:10 | 16838.44 | 28-JUN-17:10 | 671.33 | 12-JUN-14:40 | 3728.07 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.530910E+10 | 0.127206E+10 | 322.64 | 0.491507E+10 | 0.394031E+09 | 0.00 | 1.00 | 15-JUL-17:10 | 0.00 | 01-JUL-00:10 | 17971.92 | 31-JUL-00:01 | 17423.37 | 24-JUL-00:01 | 2381.67 | 27-JUL-18:23 | 3874.31 | 31-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.636151E+10 | 0.153707E+10 | 357.07 | 0.578052E+10 | 0.580987E+09 | 0.00 | 1.00 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 | 18108.45 | 14-AUG-00:01 | 16949.91 | 15-AUG-18:23 | 2001.42 | 14-AUG-00:04 | 3974.75 | 29-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.274485E+10 | 0.655921E+09 | 223.22 | 0.247759E+10 | 0.267251E+09 | 0.00 | 0.90 | 14-SEP-17:10 | 0.00 | 01-SEP-00:10 | 15107.63 | 14-SEP-17:10 | 14268.66 | 14-SEP-17:10 | 1157.15 | 14-SEP-12:20 | 3323.16 | 14-SEP-17:10 | 0.00 | 01-SEP-00:10 |
October | 0.208793E+09 | 50851318.18 | 34.33 | 0.206630E+09 | 2163239.81 | 0.00 | 0.28 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 | 4024.35 | 04-OCT-16:00 | 4024.35 | 04-OCT-16:00 | 78.99 | 06-OCT-15:00 | 961.94 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 19661019.49 | 4775485.67 | 3.67 | 16014639.58 | 3646379.91 | 0.00 | 0.15 | 04-NOV-15:30 | 0.00 | 01-NOV-00:10 | 2296.16 | 04-NOV-15:30 | 1878.34 | 04-NOV-15:30 | 417.81 | 04-NOV-15:30 | 555.82 | 04-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.187211E+11 | 0.450396E+10 | 1336.07 | 0.172935E+11 | 0.142759E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.636151E+10 | 0.153707E+10 | 357.07 | 0.578052E+10 | 0.580987E+09 | 0.00 | 1.00 | 0.00 | 18108.45 | 17423.37 | 2381.67 | 3974.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 10310.79 | 3040.80 | 4.17 | 9602.41 | 708.39 | 0.00 | 0.00 | 15-MAY-15:00 | 0.00 | 01-MAY-00:10 | 1.41 | 06-MAY-13:50 | 1.40 | 15-MAY-15:00 | 0.29 | 06-MAY-13:40 | 0.41 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 0.332560E+09 | 96505067.84 | 27.79 | 0.317801E+09 | 14759536.25 | 0.00 | 1.00 | 28-JUN-17:31 | 0.00 | 01-JUN-00:10 | 44694.30 | 28-JUN-17:31 | 41759.44 | 28-JUN-17:31 | 3477.20 | 28-JUN-17:45 | 11566.43 | 28-JUN-17:31 | 0.00 | 01-JUN-00:10 |
July | 0.261683E+10 | 0.756885E+09 | 100.28 | 0.230973E+10 | 0.307102E+09 | 0.00 | 1.00 | 20-JUL-17:41 | 0.00 | 01-JUL-00:10 | 47827.13 | 27-JUL-17:10 | 43333.72 | 23-JUL-17:01 | 11822.20 | 27-JUL-17:18 | 12116.31 | 31-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.467953E+10 | 0.136981E+10 | 114.50 | 0.414927E+10 | 0.530263E+09 | 0.00 | 1.00 | 08-AUG-17:08 | 0.00 | 01-AUG-00:10 | 46860.48 | 13-AUG-13:52 | 43685.32 | 08-AUG-18:21 | 8953.14 | 13-AUG-11:17 | 12297.69 | 10-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.254053E+09 | 73100271.79 | 26.67 | 0.201586E+09 | 52467235.63 | 0.00 | 0.23 | 14-SEP-14:40 | 0.00 | 01-SEP-00:10 | 9448.59 | 14-SEP-14:40 | 7502.00 | 14-SEP-14:40 | 2016.58 | 14-SEP-13:50 | 2673.04 | 14-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.788299E+10 | 0.229631E+10 | 273.40 | 0.697840E+10 | 0.904592E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.467953E+10 | 0.136981E+10 | 114.50 | 0.414927E+10 | 0.530263E+09 | 0.00 | 1.00 | 0.00 | 47827.13 | 43685.32 | 11822.20 | 12297.69 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.49 | 132.62 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.59 | 112.25 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.84 | 88.27 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 136.88 | 71.85 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 188.50 | 68.20 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 178.98 | 59.20 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 248.40 | 58.53 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 207.89 | 57.97 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 153.01 | 76.57 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.59 | 82.35 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.73 | 101.44 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.44 | 132.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 112.50 | 86.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.49 | 57.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 248.40 | 132.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.49 | 132.62 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.59 | 112.25 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.84 | 88.27 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 136.88 | 71.85 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 188.50 | 68.20 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 178.98 | 59.20 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 248.40 | 58.53 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 207.89 | 57.97 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 153.01 | 76.57 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.59 | 82.35 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.73 | 101.44 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.44 | 132.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 112.50 | 86.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.49 | 57.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 248.40 | 132.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 0.32 | 81.42 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.38 | 69.80 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 11.01 | 53.34 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.37 | 42.13 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.72 | 36.18 | 38.94 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 38.47 | 32.62 | 0.00 | 0.00 | 720.00 |
July | 57.43 | 4.51 | 52.91 | 39.78 | 32.39 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 35.20 | 32.78 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 19.11 | 45.64 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.83 | 49.30 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.77 | 61.74 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.20 | 80.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.39 | 51.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.20 | 32.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 39.78 | 81.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.75 | 0.00 | 13.75 | 0.32 | 81.42 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.38 | 69.80 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 11.01 | 53.34 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.37 | 42.13 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.71 | 36.18 | 38.94 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 38.47 | 32.62 | 0.00 | 0.00 | 720.00 |
July | 57.42 | 4.51 | 52.91 | 39.78 | 32.39 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 35.19 | 32.78 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 19.11 | 45.64 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.83 | 49.30 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.77 | 61.74 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.20 | 80.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.39 | 51.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.20 | 32.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 39.78 | 81.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 4.48 | 15.02 | 15.70 | 60.56 | 31.50 | 0.00 | 744.00 |
February | 34.74 | 12.44 | 22.30 | 37.43 | 55.20 | 36.50 | 0.00 | 672.00 |
March | 58.90 | 25.53 | 33.37 | 70.12 | 46.43 | 12.17 | 0.00 | 744.00 |
April | 92.64 | 46.96 | 45.68 | 119.12 | 42.22 | 7.67 | 0.00 | 720.00 |
May | 119.55 | 61.01 | 58.54 | 151.79 | 48.10 | 0.00 | 0.00 | 744.00 |
June | 130.50 | 75.76 | 54.75 | 164.80 | 45.06 | 0.00 | 0.00 | 720.00 |
July | 136.17 | 89.21 | 46.97 | 174.00 | 50.56 | 0.00 | 0.00 | 744.00 |
August | 109.90 | 69.58 | 40.32 | 138.13 | 55.66 | 0.00 | 0.00 | 744.00 |
September | 78.29 | 43.64 | 34.65 | 92.44 | 63.24 | 0.83 | 0.00 | 720.00 |
October | 47.04 | 22.51 | 24.53 | 53.86 | 52.63 | 14.17 | 0.00 | 744.00 |
November | 23.24 | 6.31 | 16.93 | 22.79 | 45.24 | 51.83 | 0.00 | 720.00 |
December | 17.05 | 4.82 | 12.24 | 14.08 | 59.89 | 57.17 | 0.00 | 744.00 |
Annual Sum or Average | 72.51 | 38.68 | 33.82 | 88.14 | 52.07 | 211.83 | 0.00 | 8760.00 |
Minimum of Months | 17.05 | 4.48 | 12.24 | 14.08 | 42.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 136.17 | 89.21 | 58.54 | 174.00 | 63.24 | 57.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30785478.07 | 0.355206E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 98187187.41 | 0.271553E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.195086E+09 | 0.236418E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.354785E+09 | 0.186240E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.504875E+09 | 0.182661E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.463922E+09 | 0.153435E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.665304E+09 | 0.156756E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.556800E+09 | 0.155258E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.396602E+09 | 0.198466E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.189058E+09 | 0.220558E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 51142745.89 | 0.262944E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 41354181.20 | 0.355299E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.354790E+10 | 0.273479E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30785478.07 | 0.153435E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.665304E+09 | 0.355299E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30785478.07 | 0.355206E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 98187187.41 | 0.271553E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.195086E+09 | 0.236418E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.354785E+09 | 0.186240E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.504875E+09 | 0.182661E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.463922E+09 | 0.153435E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.665304E+09 | 0.156756E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.556800E+09 | 0.155258E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.396602E+09 | 0.198466E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.189058E+09 | 0.220558E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 51142745.89 | 0.262944E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 41354181.20 | 0.355299E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.354790E+10 | 0.273479E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30785478.07 | 0.153435E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.665304E+09 | 0.355299E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36842037.10 | 0.00 | 36842037.10 | 844416.31 | 0.218076E+09 |
February | 51779429.29 | 0.00 | 51779429.29 | 8181866.32 | 0.168862E+09 |
March | 84474702.76 | 1613.93 | 84473088.83 | 29483722.84 | 0.142867E+09 |
April | 0.115855E+09 | 556829.82 | 0.115298E+09 | 65771490.75 | 0.109205E+09 |
May | 0.153715E+09 | 4484182.11 | 0.149231E+09 | 96907897.49 | 0.104292E+09 |
June | 0.156481E+09 | 10281295.54 | 0.146200E+09 | 99710570.48 | 84550842.04 |
July | 0.153810E+09 | 12086982.54 | 0.141723E+09 | 0.106546E+09 | 86749249.67 |
August | 0.124946E+09 | 3796729.99 | 0.121149E+09 | 94268410.82 | 87804771.11 |
September | 93576000.29 | 59143.22 | 93516857.08 | 49527901.57 | 0.118309E+09 |
October | 66218358.03 | 0.00 | 66218358.03 | 23639122.14 | 0.132054E+09 |
November | 40365490.15 | 0.00 | 40365490.15 | 4591358.17 | 0.160042E+09 |
December | 31306230.85 | 0.00 | 31306230.85 | 523883.25 | 0.215479E+09 |
Annual Sum or Average | 0.110937E+10 | 31266777.14 | 0.107810E+10 | 0.579997E+09 | 0.162829E+10 |
Minimum of Months | 31306230.85 | 0.00 | 31306230.85 | 523883.25 | 84550842.04 |
Maximum of Months | 0.156481E+09 | 12086982.54 | 0.149231E+09 | 0.106546E+09 | 0.218076E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36840747.14 | 0.00 | 36840747.14 | 844277.18 | 0.218076E+09 |
February | 51777702.37 | 0.00 | 51777702.37 | 8181185.02 | 0.168862E+09 |
March | 84471960.57 | 1613.86 | 84470346.71 | 29481704.58 | 0.142867E+09 |
April | 0.115851E+09 | 556803.72 | 0.115294E+09 | 65768361.89 | 0.109204E+09 |
May | 0.153710E+09 | 4483971.93 | 0.149226E+09 | 96903465.37 | 0.104292E+09 |
June | 0.156476E+09 | 10280813.64 | 0.146196E+09 | 99706175.96 | 84550649.37 |
July | 0.153805E+09 | 12086416.00 | 0.141719E+09 | 0.106542E+09 | 86749025.57 |
August | 0.124942E+09 | 3796552.03 | 0.121145E+09 | 94265337.49 | 87804415.42 |
September | 93573172.24 | 59140.44 | 93514031.80 | 49525555.61 | 0.118308E+09 |
October | 66216244.03 | 0.00 | 66216244.03 | 23637576.19 | 0.132054E+09 |
November | 40364087.23 | 0.00 | 40364087.23 | 4590870.56 | 0.160042E+09 |
December | 31305150.45 | 0.00 | 31305150.45 | 523819.46 | 0.215479E+09 |
Annual Sum or Average | 0.110933E+10 | 31265311.63 | 0.107807E+10 | 0.579971E+09 | 0.162829E+10 |
Minimum of Months | 31305150.45 | 0.00 | 31305150.45 | 523819.46 | 84550649.37 |
Maximum of Months | 0.156476E+09 | 12086416.00 | 0.149226E+09 | 0.106542E+09 | 0.218076E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52211105.82 | 11986693.26 | 40224412.56 | 42042659.72 | 0.162200E+09 |
February | 84043303.19 | 30105444.30 | 53937858.88 | 90546998.65 | 0.133543E+09 |
March | 0.157760E+09 | 68381875.20 | 89378269.06 | 0.187812E+09 | 0.124365E+09 |
April | 0.240130E+09 | 0.121724E+09 | 0.118406E+09 | 0.308754E+09 | 0.109432E+09 |
May | 0.320190E+09 | 0.163396E+09 | 0.156794E+09 | 0.406545E+09 | 0.128828E+09 |
June | 0.338265E+09 | 0.196365E+09 | 0.141900E+09 | 0.427159E+09 | 0.116807E+09 |
July | 0.364723E+09 | 0.238930E+09 | 0.125793E+09 | 0.466041E+09 | 0.135419E+09 |
August | 0.294366E+09 | 0.186369E+09 | 0.107997E+09 | 0.369969E+09 | 0.149092E+09 |
September | 0.202928E+09 | 0.113109E+09 | 89819164.50 | 0.239600E+09 | 0.163912E+09 |
October | 0.125998E+09 | 60303749.18 | 65693794.31 | 0.144261E+09 | 0.140953E+09 |
November | 60236404.74 | 16349601.15 | 43886803.59 | 59063498.11 | 0.117270E+09 |
December | 45678042.35 | 12903259.02 | 32774783.33 | 37704085.66 | 0.160406E+09 |
Annual Sum or Average | 0.228653E+10 | 0.121992E+10 | 0.106661E+10 | 0.277950E+10 | 0.164223E+10 |
Minimum of Months | 45678042.35 | 11986693.26 | 32774783.33 | 37704085.66 | 0.109432E+09 |
Maximum of Months | 0.364723E+09 | 0.238930E+09 | 0.156794E+09 | 0.466041E+09 | 0.163912E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.45 | 422.91 | 107.80 | 23.84 | 83.96 | 0.00 | 0.00 |
February | 82.32 | 358.49 | 185.45 | 53.14 | 132.32 | 0.00 | 0.00 |
March | 164.64 | 280.17 | 264.01 | 67.89 | 196.12 | 0.00 | 0.00 |
April | 322.98 | 226.44 | 394.41 | 116.82 | 277.59 | 0.00 | 0.00 |
May | 448.51 | 213.42 | 508.16 | 163.31 | 344.85 | 0.00 | 0.00 |
June | 433.27 | 182.01 | 498.94 | 154.76 | 344.17 | 0.00 | 0.00 |
July | 575.54 | 181.02 | 582.86 | 255.36 | 327.50 | 0.00 | 0.00 |
August | 485.55 | 180.89 | 479.69 | 199.92 | 279.77 | 0.00 | 0.00 |
September | 342.23 | 242.42 | 388.06 | 152.01 | 236.05 | 0.00 | 0.00 |
October | 156.07 | 260.55 | 229.32 | 73.59 | 155.73 | 0.00 | 0.00 |
November | 39.77 | 323.15 | 120.65 | 25.50 | 95.15 | 0.00 | 0.00 |
December | 25.98 | 420.92 | 99.31 | 26.64 | 72.67 | 0.00 | 0.00 |
Annual Sum or Average | 259.09 | 274.01 | 322.36 | 109.83 | 212.53 | 0.00 | 0.00 |
Minimum of Months | 18.45 | 180.89 | 99.31 | 23.84 | 72.67 | 0.00 | 0.00 |
Maximum of Months | 575.54 | 422.91 | 582.86 | 255.36 | 344.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 156.97 | 605.58 | 194.93 | 44.75 | 150.18 | 0.00 | 0.00 |
February | 374.28 | 552.01 | 347.40 | 124.44 | 222.96 | 0.00 | 0.00 |
March | 701.21 | 464.33 | 589.01 | 255.31 | 333.70 | 0.00 | 0.00 |
April | 1191.18 | 422.19 | 926.43 | 469.62 | 456.81 | 0.00 | 0.00 |
May | 1517.86 | 480.99 | 1195.45 | 610.05 | 585.40 | 0.00 | 0.00 |
June | 1647.99 | 450.64 | 1305.04 | 757.58 | 547.45 | 0.00 | 0.00 |
July | 1740.00 | 505.60 | 1361.72 | 892.06 | 469.66 | 0.00 | 0.00 |
August | 1381.30 | 556.65 | 1099.04 | 695.82 | 403.21 | 0.00 | 0.00 |
September | 924.38 | 632.38 | 782.90 | 436.38 | 346.52 | 0.00 | 0.00 |
October | 538.61 | 526.26 | 470.42 | 225.15 | 245.27 | 0.00 | 0.00 |
November | 227.87 | 452.43 | 232.39 | 63.08 | 169.32 | 0.00 | 0.00 |
December | 140.77 | 598.89 | 170.54 | 48.18 | 122.37 | 0.00 | 0.00 |
Annual Sum or Average | 881.37 | 520.75 | 725.05 | 386.84 | 338.22 | 0.00 | 0.00 |
Minimum of Months | 140.77 | 422.19 | 170.54 | 44.75 | 122.37 | 0.00 | 0.00 |
Maximum of Months | 1740.00 | 632.38 | 1361.72 | 892.06 | 585.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49405949.09 | 0.113271E+10 | 0.288743E+09 | 63865626.63 | 0.224877E+09 | 0.00 | 0.00 |
February | 0.199160E+09 | 0.867252E+09 | 0.448653E+09 | 0.128549E+09 | 0.320104E+09 | 0.00 | 0.00 |
March | 0.440971E+09 | 0.750403E+09 | 0.707117E+09 | 0.181836E+09 | 0.525281E+09 | 0.00 | 0.00 |
April | 0.837153E+09 | 0.586931E+09 | 0.102231E+10 | 0.302786E+09 | 0.719522E+09 | 0.00 | 0.00 |
May | 0.120128E+10 | 0.571622E+09 | 0.136105E+10 | 0.437411E+09 | 0.923642E+09 | 0.00 | 0.00 |
June | 0.112305E+10 | 0.471759E+09 | 0.129324E+10 | 0.401147E+09 | 0.892095E+09 | 0.00 | 0.00 |
July | 0.154153E+10 | 0.484849E+09 | 0.156113E+10 | 0.683948E+09 | 0.877185E+09 | 0.00 | 0.00 |
August | 0.130051E+10 | 0.484501E+09 | 0.128480E+10 | 0.535455E+09 | 0.749346E+09 | 0.00 | 0.00 |
September | 0.887052E+09 | 0.628343E+09 | 0.100586E+10 | 0.394011E+09 | 0.611846E+09 | 0.00 | 0.00 |
October | 0.418023E+09 | 0.697856E+09 | 0.614200E+09 | 0.197093E+09 | 0.417107E+09 | 0.00 | 0.00 |
November | 0.103090E+09 | 0.837595E+09 | 0.312723E+09 | 66095322.50 | 0.246628E+09 | 0.00 | 0.00 |
December | 69582738.70 | 0.112738E+10 | 0.266003E+09 | 71357373.01 | 0.194646E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.817081E+10 | 0.864120E+10 | 0.101658E+11 | 0.346355E+10 | 0.670228E+10 | 0.00 | 0.00 |
Minimum of Months | 49405949.09 | 0.471759E+09 | 0.266003E+09 | 63865626.63 | 0.194646E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154153E+10 | 0.113271E+10 | 0.156113E+10 | 0.683948E+09 | 0.923642E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420423E+09 | 0.162199E+10 | 0.522111E+09 | 0.119867E+09 | 0.402244E+09 | 0.00 | 0.00 |
February | 0.905470E+09 | 0.133543E+10 | 0.840433E+09 | 0.301054E+09 | 0.539379E+09 | 0.00 | 0.00 |
March | 0.187812E+10 | 0.124365E+10 | 0.157760E+10 | 0.683819E+09 | 0.893783E+09 | 0.00 | 0.00 |
April | 0.308753E+10 | 0.109432E+10 | 0.240130E+10 | 0.121724E+10 | 0.118406E+10 | 0.00 | 0.00 |
May | 0.406545E+10 | 0.128828E+10 | 0.320190E+10 | 0.163396E+10 | 0.156794E+10 | 0.00 | 0.00 |
June | 0.427159E+10 | 0.116806E+10 | 0.338265E+10 | 0.196365E+10 | 0.141900E+10 | 0.00 | 0.00 |
July | 0.466041E+10 | 0.135419E+10 | 0.364723E+10 | 0.238930E+10 | 0.125793E+10 | 0.00 | 0.00 |
August | 0.369968E+10 | 0.149092E+10 | 0.294366E+10 | 0.186369E+10 | 0.107997E+10 | 0.00 | 0.00 |
September | 0.239600E+10 | 0.163912E+10 | 0.202928E+10 | 0.113109E+10 | 0.898192E+09 | 0.00 | 0.00 |
October | 0.144261E+10 | 0.140953E+10 | 0.125998E+10 | 0.603037E+09 | 0.656938E+09 | 0.00 | 0.00 |
November | 0.590635E+09 | 0.117270E+10 | 0.602364E+09 | 0.163496E+09 | 0.438868E+09 | 0.00 | 0.00 |
December | 0.377038E+09 | 0.160406E+10 | 0.456780E+09 | 0.129033E+09 | 0.327748E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277950E+11 | 0.164223E+11 | 0.228653E+11 | 0.121992E+11 | 0.106661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.377038E+09 | 0.109432E+10 | 0.456780E+09 | 0.119867E+09 | 0.327748E+09 | 0.00 | 0.00 |
Maximum of Months | 0.466041E+10 | 0.163912E+10 | 0.364723E+10 | 0.238930E+10 | 0.156794E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100507E+10 | -848742022.0 | 0.00 | 0.00 | 744.00 | 0.00 | -156324065.6 | 58.99 | 0.00 | 0.00 |
February | 0.925275E+09 | -785129973.3 | 0.00 | 0.00 | 672.00 | 0.00 | -140144836.2 | 58.99 | 0.00 | 0.00 |
March | 0.105982E+10 | -907305066.0 | 0.00 | 0.00 | 744.00 | 0.00 | -152517871.0 | 58.99 | 0.00 | 0.00 |
April | 0.963259E+09 | -819656937.9 | 0.00 | 0.00 | 720.00 | 0.00 | -143601660.3 | 58.99 | 0.00 | 0.00 |
May | 0.961862E+09 | -820656995.4 | 0.00 | 0.00 | 744.00 | 0.00 | -141204869.9 | 58.99 | 0.00 | 0.00 |
June | 0.918741E+09 | -786760244.6 | 0.00 | 0.00 | 720.00 | 0.00 | -131980833.6 | 58.99 | 0.00 | 0.00 |
July | 0.872725E+09 | -739282622.3 | 0.00 | 0.00 | 744.00 | 0.00 | -133442835.2 | 58.99 | 0.00 | 0.00 |
August | 0.920778E+09 | -787243396.5 | 0.00 | 0.00 | 744.00 | 0.00 | -133534498.7 | 58.99 | 0.00 | 0.00 |
September | 0.873178E+09 | -741658100.9 | 0.00 | 0.00 | 720.00 | 0.00 | -131519833.1 | 59.00 | 0.00 | 0.00 |
October | 0.914662E+09 | -767224393.1 | 0.00 | 0.00 | 744.00 | 0.00 | -147437743.7 | 58.99 | 0.00 | 0.00 |
November | 0.914539E+09 | -766214195.0 | 0.00 | 0.00 | 720.00 | 0.00 | -148324581.1 | 58.99 | 0.00 | 0.00 |
December | 0.982880E+09 | -827211714.4 | 0.00 | 0.00 | 744.00 | 0.00 | -155668769.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.113128E+11 | -.959709E+10 | 8760.00 | -.171570E+10 | 58.99 | |||||
Minimum of Months | 0.872725E+09 | -907305066.0 | 0.00 | 0.00 | 672.00 | 0.00 | -156324065.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.105982E+10 | -739282622.3 | 0.00 | 0.00 | 744.00 | 0.00 | -131519833.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595968E+10 | 26207.30 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448175E+10 | 26207.30 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321457E+10 | 26207.30 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165315E+10 | 26207.30 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411983E+09 | 26207.30 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73808137.70 | 15881.05 | 15-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50221178.44 | 18062.79 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123871E+10 | 26207.30 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326734E+10 | 26207.30 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506335E+10 | 26207.30 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254146E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595968E+10 | 26207.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.280194E+11 | 74259.09 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199337E+11 | 74259.09 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.969306E+10 | 74259.09 | 04-MAR-20:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323708E+10 | 74259.09 | 11-APR-03:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189562E+10 | 59360.14 | 21-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122375E+11 | 74259.09 | 11-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230922E+11 | 74259.09 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.981085E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280194E+11 | 74259.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400715E+11 | 59413.60 | 15-JAN-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271250E+11 | 84554.15 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60131642.93 | 7036.23 | 25-MAR-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406164E+10 | 30982.02 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263957E+11 | 44840.08 | 25-DEC-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.977139E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400715E+11 | 84554.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1164462.30 | 1164462.30 | 587.88 | 18-MAR-16:00 | 587.88 | 0.00 |
April | 0.00 | 0.00 | 0.287006E+09 | 0.273033E+09 | 8372.29 | 27-APR-17:20 | 8372.29 | 0.00 |
May | 0.00 | 0.00 | 0.110594E+10 | 0.104152E+10 | 8681.38 | 15-MAY-17:15 | 8681.38 | 0.00 |
June | 0.00 | 0.00 | 0.268305E+10 | 0.258193E+10 | 16838.44 | 28-JUN-17:10 | 16838.44 | 0.00 |
July | 0.00 | 0.00 | 0.530910E+10 | 0.491507E+10 | 17971.92 | 31-JUL-00:01 | 16300.06 | 0.00 |
August | 0.00 | 0.00 | 0.636151E+10 | 0.578052E+10 | 18108.45 | 14-AUG-00:01 | 16669.90 | 0.00 |
September | 0.00 | 0.00 | 0.274485E+10 | 0.247759E+10 | 15107.63 | 14-SEP-17:10 | 14268.66 | 0.00 |
October | 0.00 | 0.00 | 0.208793E+09 | 0.206630E+09 | 4024.35 | 04-OCT-16:00 | 4024.35 | 0.00 |
November | 0.00 | 0.00 | 19661019.49 | 16014639.58 | 2296.16 | 04-NOV-15:30 | 1878.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.187211E+11 | 0.172935E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.636151E+10 | 0.578052E+10 | 18108.45 | 16838.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 10310.79 | 9602.41 | 1.41 | 06-MAY-13:50 | 1.13 | 0.00 |
June | 0.00 | 0.00 | 0.332560E+09 | 0.317801E+09 | 44694.30 | 28-JUN-17:31 | 41759.44 | 0.00 |
July | 0.00 | 0.00 | 0.261683E+10 | 0.230973E+10 | 47827.13 | 27-JUL-17:10 | 36254.85 | 0.00 |
August | 0.00 | 0.00 | 0.467953E+10 | 0.414927E+10 | 46860.48 | 13-AUG-13:52 | 39048.32 | 0.00 |
September | 0.00 | 0.00 | 0.254053E+09 | 0.201586E+09 | 9448.59 | 14-SEP-14:40 | 7502.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.788299E+10 | 0.697840E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.467953E+10 | 0.414927E+10 | 47827.13 | 41759.44 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.456079E+09 | 0.05 | 252.10 | 01-JAN-00:02 | 0.08 |
February | 0.293882E+09 | 0.04 | 252.10 | 01-FEB-00:03 | 0.08 |
March | 5097436.51 | 0.00 | 252.10 | 05-MAR-03:40 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.120919E+09 | 0.01 | 252.10 | 13-NOV-05:05 | 0.08 |
December | 0.419429E+09 | 0.05 | 252.10 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.129541E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.456079E+09 | 0.05 | 252.10 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121378E+10 | 0.45 | 1166.53 | 03-JAN-09:20 | 0.95 |
February | 0.111010E+10 | 0.44 | 1166.53 | 01-FEB-10:00 | 0.95 |
March | 0.128281E+10 | 0.41 | 1166.53 | 06-MAR-17:00 | 0.95 |
April | 0.117957E+10 | 0.39 | 1166.53 | 01-APR-14:30 | 0.95 |
May | 0.121233E+10 | 0.38 | 1166.53 | 02-MAY-12:30 | 0.94 |
June | 0.122229E+10 | 0.41 | 1166.53 | 01-JUN-10:30 | 0.94 |
July | 0.123093E+10 | 0.45 | 1166.53 | 08-JUL-14:10 | 0.94 |
August | 0.133932E+10 | 0.50 | 1166.53 | 01-AUG-14:20 | 0.94 |
September | 0.117449E+10 | 0.39 | 1166.53 | 05-SEP-08:70 | 0.94 |
October | 0.117266E+10 | 0.37 | 1166.53 | 06-OCT-14:00 | 0.94 |
November | 0.113831E+10 | 0.37 | 1166.53 | 03-NOV-17:00 | 0.94 |
December | 0.119685E+10 | 0.40 | 1166.53 | 01-DEC-10:00 | 0.95 |
Annual Sum or Average | 0.144735E+11 | 0.41 | |||
Minimum of Months | 0.111010E+10 | 0.37 | 1166.53 | 0.94 | |
Maximum of Months | 0.133932E+10 | 0.50 | 1166.53 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.315219E+10 | 0.78 | 2411.81 | 05-JAN-13:40 | 0.91 |
February | 0.276734E+10 | 0.73 | 2411.81 | 04-FEB-07:20 | 0.91 |
March | 0.288685E+10 | 0.65 | 2411.81 | 03-MAR-07:20 | 0.91 |
April | 0.249678E+10 | 0.46 | 2411.81 | 17-APR-07:10 | 0.91 |
May | 0.248320E+10 | 0.35 | 2411.81 | 04-MAY-14:50 | 0.91 |
June | 0.248429E+10 | 0.36 | 2411.81 | 20-JUN-15:30 | 0.91 |
July | 0.241479E+10 | 0.35 | 2411.81 | 06-JUL-16:00 | 0.91 |
August | 0.260602E+10 | 0.37 | 2411.81 | 05-AUG-13:40 | 0.91 |
September | 0.238770E+10 | 0.35 | 2411.81 | 23-SEP-15:40 | 0.90 |
October | 0.245179E+10 | 0.41 | 2411.81 | 16-OCT-07:20 | 0.91 |
November | 0.265962E+10 | 0.65 | 2411.81 | 09-NOV-07:40 | 0.91 |
December | 0.303123E+10 | 0.77 | 2411.81 | 01-DEC-09:50 | 0.91 |
Annual Sum or Average | 0.318218E+11 | 0.52 | |||
Minimum of Months | 0.238770E+10 | 0.35 | 2411.81 | 0.90 | |
Maximum of Months | 0.315219E+10 | 0.78 | 2411.81 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.61 | 0.01 |
February | 2.28 | 0.01 |
March | 1.18 | 0.06 |
April | 0.50 | 0.81 |
May | 0.83 | 2.65 |
June | 0.75 | 4.51 |
July | 0.50 | 5.00 |
August | 0.67 | 3.75 |
September | 1.08 | 4.66 |
October | 0.56 | 0.12 |
November | 2.56 | 0.01 |
December | 2.39 | 0.03 |
Annual Sum or Average | 15.90 | 1.03 |
Minimum of Months | 0.50 | 0.01 |
Maximum of Months | 2.61 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.76 | 0.00 |
August | 0.13 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.89 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.76 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121378E+10 | 0.869228E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111010E+10 | 0.653072E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128310E+10 | 0.469295E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124992E+10 | 0.240653E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147880E+10 | 0.605424E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186846E+10 | 0.112071E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.250300E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.287639E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183041E+10 | 75561020.29 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122351E+10 | 0.182180E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.114309E+10 | 0.478900E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119685E+10 | 0.739345E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.189774E+11 | 0.371198E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111010E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.287639E+10 | 0.869228E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.315219E+10 | 0.406449E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.276734E+10 | 0.288874E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.288685E+10 | 0.142834E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.249678E+10 | 0.479931E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.248321E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258079E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317168E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.397583E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246080E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.245179E+10 | 0.284476E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.265962E+10 | 0.179196E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.303123E+10 | 0.336232E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.341181E+11 | 0.143002E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.245179E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.397583E+10 | 0.406449E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121378E+10 | 0.00 | 0.595968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111010E+10 | 0.00 | 0.448175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128281E+10 | 1164462.30 | 0.321457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117957E+10 | 0.287006E+09 | 0.165315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121233E+10 | 0.110594E+10 | 0.411983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122229E+10 | 0.268305E+10 | 73808137.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123093E+10 | 0.530910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133932E+10 | 0.636151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117449E+10 | 0.274485E+10 | 50221178.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117266E+10 | 0.208793E+09 | 0.123871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113831E+10 | 19661019.49 | 0.326734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119685E+10 | 0.00 | 0.506335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144735E+11 | 0.187211E+11 | 0.254146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133932E+10 | 0.636151E+10 | 0.595968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.315219E+10 | 0.00 | 0.280194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276734E+10 | 0.00 | 0.199337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288685E+10 | 0.00 | 0.969306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249678E+10 | 0.00 | 0.323708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248320E+10 | 10310.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.248429E+10 | 0.332560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241479E+10 | 0.261683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.260602E+10 | 0.467953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238770E+10 | 0.254053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245179E+10 | 0.00 | 0.189562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265962E+10 | 0.00 | 0.122375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303123E+10 | 0.00 | 0.230922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318218E+11 | 0.788299E+10 | 0.981085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.238770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315219E+10 | 0.467953E+10 | 0.280194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.121378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128281E+10 | 0.00 | 0.00 | 0.00 | 289071.44 | 0.00 | 0.469295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117957E+10 | 0.00 | 0.00 | 0.00 | 70350660.86 | 0.00 | 0.240653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121233E+10 | 0.00 | 0.00 | 0.00 | 0.266462E+09 | 0.00 | 0.605424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122229E+10 | 0.00 | 0.00 | 0.00 | 0.646178E+09 | 0.00 | 0.112071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123093E+10 | 0.00 | 0.00 | 0.00 | 0.127206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133932E+10 | 0.00 | 0.00 | 0.00 | 0.153707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117449E+10 | 0.00 | 0.00 | 0.00 | 0.655921E+09 | 0.00 | 75561020.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117266E+10 | 0.00 | 0.00 | 0.00 | 50851318.18 | 0.00 | 0.182180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113831E+10 | 0.00 | 0.00 | 0.00 | 4775485.67 | 0.00 | 0.478900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144735E+11 | 0.00 | 0.00 | 0.00 | 0.450396E+10 | 0.00 | 0.371198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.111010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133932E+10 | 0.00 | 0.00 | 0.00 | 0.153707E+10 | 0.00 | 0.869228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.315219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248320E+10 | 0.00 | 0.00 | 0.00 | 3040.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.248429E+10 | 0.00 | 0.00 | 0.00 | 96505067.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241479E+10 | 0.00 | 0.00 | 0.00 | 0.756885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.260602E+10 | 0.00 | 0.00 | 0.00 | 0.136981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238770E+10 | 0.00 | 0.00 | 0.00 | 73100271.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318218E+11 | 0.00 | 0.00 | 0.00 | 0.229631E+10 | 0.00 | 0.143002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.238770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315219E+10 | 0.00 | 0.00 | 0.00 | 0.136981E+10 | 0.00 | 0.406449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208577E+10 | 0.00 | 0.00 | 0.14 |
February | 73110007.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164779E+10 | 0.00 | 0.00 | 0.14 |
March | 0.319643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138202E+10 | 0.00 | 0.00 | 0.15 |
April | 0.571223E+09 | 7159656.76 | 0.00 | 207721.78 | 15001.32 | 0.691728E+09 | 42554194.54 | 0.00 | 0.14 |
May | 0.646384E+09 | 7508460.17 | 0.00 | 1297587.24 | 0.00 | 0.146226E+09 | 0.379778E+09 | 0.00 | 0.14 |
June | 0.260077E+09 | 3920838.22 | 0.00 | 3696942.92 | 0.00 | 50225849.78 | 0.630845E+09 | 0.00 | 0.15 |
July | 88755229.55 | 87103601.13 | 0.00 | 5714171.25 | 0.00 | 0.00 | 0.452422E+09 | 0.00 | 0.15 |
August | 88314891.76 | 0.196652E+09 | 0.00 | 5273562.49 | 0.00 | 0.00 | 0.375159E+09 | 0.00 | 0.16 |
September | 0.286135E+09 | 22281082.96 | 0.00 | 3047558.73 | 0.00 | 34904355.88 | 0.567742E+09 | 0.00 | 0.14 |
October | 0.612125E+09 | 0.00 | 0.00 | 274960.47 | 0.00 | 0.572786E+09 | 0.121350E+09 | 0.00 | 0.14 |
November | 0.194932E+09 | 0.00 | 0.00 | 12292.07 | 0.00 | 0.136764E+10 | 3711779.29 | 0.00 | 0.14 |
December | 8731803.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194702E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.314943E+10 | 0.324626E+09 | 0.00 | 19524796.95 | 15001.32 | 0.992611E+10 | 0.257356E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.646384E+09 | 0.196652E+09 | 0.00 | 5714171.25 | 15001.32 | 0.208577E+10 | 0.630845E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.917282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364593E+10 | 0.00 | 0.00 | 0.17 |
February | 0.160600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207771E+10 | 0.00 | 0.00 | 0.18 |
March | 0.290505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631934E+09 | 0.00 | 0.00 | 0.19 |
April | 0.275608E+10 | 0.00 | 0.00 | 0.00 | 36204345.33 | 0.152796E+09 | 0.00 | 0.00 | 0.18 |
May | 0.321019E+10 | 0.00 | 0.00 | 41955.18 | 0.00 | 0.00 | 90159158.50 | 0.00 | 0.19 |
June | 0.292273E+10 | 4577852.70 | 0.00 | 902459.18 | 43168.90 | 0.00 | 0.599871E+09 | 0.00 | 0.24 |
July | 0.174347E+10 | 0.104598E+09 | 0.00 | 3823385.30 | 0.00 | 0.00 | 0.203411E+10 | 0.00 | 0.33 |
August | 0.181580E+10 | 0.292892E+09 | 0.00 | 2882055.34 | 0.00 | 0.00 | 0.119916E+10 | 0.00 | 0.31 |
September | 0.282849E+10 | 0.00 | 0.00 | 1097188.26 | 0.00 | 0.00 | 0.769578E+09 | 0.00 | 0.24 |
October | 0.269872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109463E+09 | 0.00 | 0.00 | 0.18 |
November | 0.200568E+10 | 0.00 | 0.00 | 0.00 | 109342.30 | 0.122828E+10 | 0.00 | 0.00 | 0.17 |
December | 0.139462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276579E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.268041E+11 | 0.402068E+09 | 0.00 | 8747043.26 | 36356856.53 | 0.106119E+11 | 0.469288E+10 | 0.00 | 0.21 |
Minimum of Months | 0.917282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.321019E+10 | 0.292892E+09 | 0.00 | 3823385.30 | 36204345.33 | 0.364593E+10 | 0.203411E+10 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |