Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1251.61 | 258.86 | 258.86 |
Net Site Energy | 1251.61 | 258.86 | 258.86 |
Total Source Energy | 3203.40 | 662.53 | 662.53 |
Net Source Energy | 3203.40 | 662.53 | 662.53 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 365.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.98 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 886.54 | 365.08 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 365.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 6.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 68.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.98 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 29.33 | 75.50 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 183.35 | 75.50 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 29.33 | 75.50 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 183.35 | 75.50 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 886.535 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 886.535 | 100.00 |
Total On-Site and Utility Electric Sources | 886.535 | 100.00 |
Total Electricity End Uses | 886.535 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 40.50 |
Time Setpoint Not Met During Occupied Cooling | 2.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1437.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 14-DEC-04:10 | - | - | - | 20-MAY-11:50 |
Heating | 0.00 | 187787.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19291.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7410.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1729.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74163.97 | 187787.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 187787.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19291.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5104.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1729.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 395.74 | 0.00 | 0.00 | 0.00 |
Cooling | 128.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 238.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2807.66 | 395.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.85 | 0.00 | 0.00 | 0.00 |
Cooling | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 580.68 | 81.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.85 | 0.00 | 0.00 | 0.00 |
Cooling | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 580.68 | 81.85 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.33 |
ZONE2 FINE STORAGE DIRECT AIR | 3.28 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.21 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.21 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 109726.16 |
PSZ-OFFICE HEATING COIL | 28615.69 |
PSZ-FINE STORAGE HEATING COIL | 87937.82 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 109726.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
PSZ-FINE STORAGE | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 1.00 | 1.00 | 3.28 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.33 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.28 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 1.33 | 22074.01 | 28615.69 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.28 | 3.28 | 3.28 | 3.28 | 62616.46 | 87937.82 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.33 | 0.666745 | 1.33 | 22073.99 | 22074.01 | 11037.00 | 22074.01 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 3.28 | 1.64 | 3.28 | 54620.53 | 62616.46 | 31308.23 | 62616.46 | 0.749315 | 0.749320 | 0.749320 | 0.749320 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.33 | 1520.33 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.28 | 3584.53 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.71045622E-12 | 0.18350169E-15 | 0.20920636E-14 | 0.12692337E-15 |
13 | 3 | -0.36041595E-03 | 0.57471575E-06 | -0.52051292E-04 | 0.13635641E-12 |
14 | 2 | 1.6814491 | 0.12908092E-01 | 1.0963028 | -0.69095641E-04 |
15 | 1 | -7.2068525 | 0.34008243 | -16.815156 | 0.32221486 |
16 | 0 | 6.0979960 | 0.21924101 | 16.291138 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20920636E-14 | 0.18350169E-15 | 0.71045622E-12 | 0.12692337E-15 |
85 | 3 | -0.52051292E-04 | 0.57471575E-06 | -0.36041595E-03 | 0.13635641E-12 |
86 | 2 | 1.0963028 | 0.12908092E-01 | 1.6814491 | -0.69095641E-04 |
87 | 1 | -16.815156 | 0.34008243 | -7.2068525 | 0.32221486 |
88 | 0 | 16.291138 | 0.21924101 | 6.0979960 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 28 | 1 | VerySmooth | 3.241 | 0.385 | 0.305 | 0.391 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11110.26855 | 13332.32226 | 1.11124 | 1.33349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10145.96203 | 12175.15444 | 0.34635 | 0.41562 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 35006.96750 | 42008.36100 | 2.72918 | 3.27502 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 37556.39609 | 45067.67530 | 1.07960 | 1.29552 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10000 | 5.65324E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 91438.45713 | 109726.14856 | 2.67649 | 3.21179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16907.36 | 1.33349 | 1.33349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11305.35 | 0.41562 | 0.41562 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 50873.72 | 3.27502 | 3.27502 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 39779.56 | 1.29552 | 1.29552 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33349 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.27502 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.21179 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.21179 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 109726.15584 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 109726.14856 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33349 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33349 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33349 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33349 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33349 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.33349 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.27502 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.27502 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.27502 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.27502 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.27502 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.27502 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.33349 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.27502 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33349 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33349 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33349 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33349 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33349 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33349 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66675 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33349 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22073.99437 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22074.01000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11037.00500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22074.01000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22074.01000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28615.68655 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33349 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1520.32602 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28615.68655 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.27502 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.27502 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.27502 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.27502 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.27502 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.27502 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.63751 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.27502 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 54620.53172 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 62616.46000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31308.23000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 62616.46000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74932 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74932 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74932 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74932 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62616.46000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87937.81988 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.27502 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3584.52686 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 87937.81988 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21039.3 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 60073.8 | 13.22 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 16 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1094278657 | 0.1151761552 | Pass | Pass | 0.1282593167 | 0.6738620968 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4305906725 | 0.5142793448 | Pass | Pass | 1.1606596645 | 4.5698019476 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.2874378679E-002 | 6.6837637617E-002 | Pass | Pass | 0.1506588032 | 1.2056850445 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.494 | 0.497 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.385 | 0.391 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.510 | 0.512 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.71 | 83.71 | 123.46 | |
Exterior Lighting Total | 7857.24 | 123.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22074.01 | 17629.63 | 4444.38 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62616.46 | 46919.77 | 15696.69 | 0.75 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21039.3 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 60073.8 | 13.22 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 109726.16 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28615.69 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 87937.82 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.21 | 298.41 | 92.91 | 1.00 | 3.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.33 | 1520.33 | 1140.11 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.28 | 3584.53 | 1094.51 | 1.00 | 1.23 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11110.27 | 13332.32 | 56.28 | 1.111 | 1.333 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00803 | 33.21 | 0.00565 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 35006.97 | 42008.36 | 30.15 | 2.729 | 3.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00780 | 35.10 | 0.00565 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00460 | 35.10 | 0.00565 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10145.96 | 12175.15 | 51.40 | 0.346 | 0.416 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00765 | -7.90 | 0.00234 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 37556.40 | 45067.68 | 32.34 | 1.080 | 1.296 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00619 | -7.90 | 0.00234 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 91438.46 | 109726.15 | 34.24 | 2.676 | 3.212 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00930 | -7.90 | 0.00234 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.33 | 1.33 | 0.42 | 0.42 | 1.3335 | 1.3335 | 1.3335 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.28 | 3.28 | 1.30 | 1.30 | 3.2750 | 3.2750 | 3.2750 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 109726.156 | 109726.156 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 109726.16 | 109726.16 | 3.211787 | 5.46 | 5.46 | 0.00753618 | 43.33 | 24.55 | 0.01600000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 9.99 | 0.00929920 | 100.0000 | 109726.15 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22074.010 | 0.000 | 1.333490 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22074.01 | 22074.01 | 1.333490 | 24.74 | 14.05 | 0.00781686 | 12.00 | 9.53 | 0.00800000 | 33.21 | 0.00565324 | 15.09 | 9.0241 | 23.90 | 0.00803148 | 35.8007 | 11110.27 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28615.687 | 28615.687 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28615.69 | 28615.69 | 1.333491 | 12.67 | 7.90 | 0.00611082 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 9.0241 | 21.10 | 0.00764623 | 40.4331 | 10145.96 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 62616.460 | 0.000 | 3.275020 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 62616.46 | 62616.46 | 3.275020 | 27.61 | 14.81 | 0.00757176 | 12.00 | 9.53 | 0.00800000 | 35.10 | 0.00565324 | 15.70 | 10.8069 | 26.70 | 0.00780421 | 29.4597 | 35006.97 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 87937.820 | 87937.820 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 87937.82 | 87937.82 | 3.275020 | 9.15 | 5.27 | 0.00513763 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 10.8069 | 15.55 | 0.00618801 | 46.4518 | 37556.40 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 109726.156 | 109726.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 0.9904 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.211787 | 3.18098272 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 109726.16 | 109726.16 | 1.0000 | 3.18098272 | 3.211787 | 5.46 | 5.46 | 0.00753618 | 24407.6 | 43.33 | 24.55 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 109726.16 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 9.99 | 0.00929920 | 9.99 | 0.00929920 | 100.0000 | 109726.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22074.010 | 0.000 | 1.333490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3712 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22074.01 | 22074.01 | 1.0000 | 1.32070036 | 1.333490 | 24.74 | 14.05 | 0.00781686 | 44768.7 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22074.01 | 33.21 | 0.00565324 | 15.09 | 0.12033533 | 9.0241 | 23.90 | 0.00803148 | 23.90 | 0.00803148 | 35.8007 | 11110.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28615.687 | 28615.687 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.333491 | 1.32070113 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28615.69 | 28615.69 | 1.0000 | 1.32070113 | 1.333491 | 12.67 | 7.90 | 0.00611082 | 28156.2 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28615.69 | -7.90 | 0.00234317 | -7.90 | 0.12033533 | 9.0241 | 21.05 | 0.00764623 | 21.10 | 0.00764623 | 40.4331 | 10145.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62616.460 | 0.000 | 3.275020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9155 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 62616.46 | 62616.46 | 1.0000 | 3.24360894 | 3.275020 | 27.61 | 14.81 | 0.00757176 | 47067.2 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62616.46 | 35.10 | 0.00565324 | 15.70 | 0.35392745 | 10.8069 | 26.70 | 0.00780421 | 26.70 | 0.00780421 | 29.4597 | 35006.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87937.820 | 87937.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.275020 | 3.24360846 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 87937.82 | 87937.82 | 1.0000 | 3.24360846 | 3.275020 | 9.15 | 5.27 | 0.00513763 | 22127.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87937.82 | -7.90 | 0.00234317 | -7.90 | 0.35392745 | 10.8069 | 15.55 | 0.00618801 | 15.55 | 0.00618801 | 46.4518 | 37556.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.33 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 3.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2369.17 | 2347.50 | 1437.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2369.17 | 2347.50 | 1437.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 44.83 | 108.33 | 40.50 | 2.00 |
ZONE2 FINE STORAGE | 344.67 | 58.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 377.67 | 139.50 | 40.50 | 2.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.890 | 0.393 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 886.54 | 5475.32 | 01-JAN-09:00 | 74163.97 | 22-JUL-15:00 |
Electricity:Building | 627.87 | 4992.32 | 01-JAN-00:10 | 48037.94 | 19-MAY-13:00 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 428.27 | 2759.73 | 01-JAN-00:10 | 33963.13 | 19-MAY-12:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.98 | 483.00 | 06-FEB-06:30 | 2430.73 | 06-FEB-13:00 |
WaterSystems:Electricity | 25.98 | 483.00 | 06-FEB-06:30 | 2430.73 | 06-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.98 | 483.00 | 06-FEB-06:30 | 2430.73 | 06-FEB-13:00 |
Fans:Electricity | 75.19 | 0.00 | 01-JAN-09:00 | 7410.15 | 28-JUN-14:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
Ventilation (simple):Fans:Electricity | 6.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
ElectricityPurchased:Facility | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
ElectricityNet:Plant | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 886.54 | 5475.32 | 17-SEP-13:20 | 74163.97 | 22-JUL-15:00 |
Electricity:HVAC | 109.23 | 0.00 | 01-JAN-09:00 | 25682.11 | 22-JUL-15:10 |
General:Fans:Electricity | 68.56 | 0.00 | 01-JAN-09:00 | 5403.26 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40.67 | 0.00 | 01-JAN-00:10 | 20577.25 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 365.08 | 3750.00 | 17-MAY-18:50 | 187787.36 | 14-DEC-04:10 |
Gas:HVAC | 365.08 | 3750.00 | 17-MAY-18:50 | 187787.36 | 14-DEC-04:10 |
Heating:Gas | 365.08 | 3750.00 | 17-MAY-18:50 | 187787.36 | 14-DEC-04:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 634.32 | 0.00 | 01-JAN-09:00 | 290405.36 | 14-DEC-04:10 |
EnergyTransfer:Building | 314.65 | 0.00 | 01-JAN-09:00 | 146061.55 | 14-DEC-04:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.15 | 0.00 | 01-JAN-00:10 | 18367.00 | 06-FEB-06:10 |
Heating:EnergyTransfer | 194.38 | 0.00 | 01-JAN-09:00 | 146061.55 | 14-DEC-04:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 18.88 | 0.00 | 01-JAN-00:10 | 18367.00 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 120.27 | 0.00 | 01-JAN-00:10 | 48568.00 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 42.27 | 0.00 | 01-JAN-00:10 | 12232.38 | 28-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 160.60 | 0.00 | 01-JAN-00:40 | 54646.64 | 14-DEC-04:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 82.60 | 0.00 | 01-JAN-00:40 | 54646.64 | 14-DEC-04:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 78.00 | 0.00 | 01-JAN-00:10 | 39239.58 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 92.91 | 0.00 | 01-JAN-08:40 | 93196.59 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 92.91 | 0.00 | 01-JAN-08:40 | 93196.59 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 319.66 | 0.00 | 01-JAN-09:00 | 144343.81 | 14-DEC-04:10 |
HeatingCoils:EnergyTransfer | 183.76 | 0.00 | 01-JAN-09:00 | 144343.81 | 14-DEC-04:10 |
CoolingCoils:EnergyTransfer | 135.91 | 0.00 | 01-JAN-00:10 | 59398.61 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 18.876 | -42.272 | 0.000 | 0.000 | 3.831 | 30.994 | 31.946 | 13.459 | 0.000 | 1.937 | 0.000 | 0.000 | -9.794 | 0.000 | -16.850 | -32.128 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 82.596 | -77.996 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 5.206 | 0.002 | 0.000 | 0.000 | 0.000 | -100.108 | -46.355 |
ZONE3 BULK STORAGE | 92.909 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 47.781 | 0.000 | 7.961 | 0.000 | 0.000 | -22.290 | 0.000 | -479.030 | -68.978 |
Total Facility | 92.909 | 0.000 | 101.472 | -120.268 | 0.000 | 0.000 | 3.831 | 481.960 | 139.282 | 61.241 | 0.000 | 15.105 | 0.002 | 0.000 | -32.084 | 0.000 | -595.988 | -147.461 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-JUN-00:01 | 0.00 | 0.00 | 0.00 | -25510.45 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 25055.43 | 0.00 | -462.19 | 0.00 | -115.49 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-10:31 | 0.00 | 0.00 | 0.00 | -60908.33 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 60454.47 | 0.00 | -0.00 | 0.00 | -746.03 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-19:01 | 0.00 | 0.00 | 0.00 | -76068.65 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 60.61 | 81255.08 | 0.00 | -882.42 | 0.00 | -11406.97 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-06:11 | 0.00 | 0.00 | 29595.30 | 0.00 | 0.00 | 0.00 | 46.49 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -917.50 | 0.00 | -2450.80 | -27433.69 |
ZONE2 FINE STORAGE | 04-FEB-23:22 | 0.00 | 0.00 | 91119.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16189.98 | -76129.72 |
ZONE3 BULK STORAGE | 14-DEC-03:52 | 93199.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1585.83 | 0.00 | -84195.99 | -12227.78 |
Total Facility | 06-FEB-06:01 | 72165.25 | 0.00 | 117864.66 | 0.00 | 0.00 | 0.00 | 58.01 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2775.52 | 0.00 | -57853.28 | -136628.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3335 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3335 | 0.0902 | 1.0000 | 0.1203 | 0.0902 | ||
PSZ-FINE STORAGE | 3.2750 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.2750 | 0.1081 | 1.0000 | 0.3539 | 0.1081 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3335 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3335 | 1.0000 | 1.0000 | 0.1203 | 0.0902 | ||
PSZ-FINE STORAGE | 3.2750 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.2750 | 1.0000 | 1.0000 | 0.3539 | 0.1081 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3335 | 1.3335 | 1.3335 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2750 | 3.2750 | 3.2750 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3335 | 1.3335 | 1.3335 | 1.3335 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.2750 | 3.2750 | 3.2750 | 3.2750 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3335 | 1.3335 | 1.3335 | 0.1203 | 0.2895 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2750 | 3.2750 | 3.2750 | 0.3539 | 0.2732 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3335 | 1.3335 | 1.3335 | 1.3335 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.2750 | 3.2750 | 3.2750 | 3.2750 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 40.50 |
Number of hours cooling loads not met | 2.00 |
Number of hours not met | 42.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 365.08 | 187787.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 40.67 | 20577.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.46 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 6.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 68.56 | 5403.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.98 | 2430.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 886.54 |
Natural Gas | 0.00 | 365.08 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1251.61 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 8.41 |
Fans (All) | 15.55 |
Service Water Heating | 5.37 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 183.35 |
Subtotal | 183.35 |
Natural Gas [MJ/m2] | |
Space Heating | 75.50 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 75.50 |
Subtotal | 75.50 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.51 |
Space Heating | 29.17 |
Space Cooling | 3.25 |
Fans (All) | 6.01 |
Service Water Heating | 2.08 |
Receptacle Equipment | 11.13 |
Miscellaneous | 9.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.925879E+11 |
February | 0.000 | 0.641902E+11 |
March | 0.000 | 0.242340E+11 |
April | 0.000 | 0.108539E+11 |
May | 0.000 | 0.101477E+11 |
June | 0.000 | 0.972306E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972000E+10 |
October | 0.000 | 0.112332E+11 |
November | 0.000 | 0.242605E+11 |
December | 0.000 | 0.880368E+11 |
Annual Sum or Average | 0.365075E+12 | |
Minimum of Months | 0.000 | 0.972000E+10 |
Maximum of Months | 0.000 | 0.925879E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 907802.66 | 192.37 | 06-JAN-17:00 | 5.60 | 0.63 | 0.198334E+09 | 285.72 | 05-JAN-16:10 | 15.63 | 6.61 |
February | 16456339.32 | 1103.02 | 15-FEB-16:30 | 16.95 | 6.15 | 0.185301E+09 | 301.59 | 13-FEB-15:00 | 21.70 | 7.18 |
March | 37412874.22 | 1497.84 | 08-MAR-16:40 | 22.40 | 8.49 | 0.227967E+09 | 301.59 | 27-MAR-15:00 | 18.90 | 7.40 |
April | 0.132348E+10 | 21141.52 | 29-APR-19:21 | 20.85 | 7.66 | 0.234457E+09 | 301.59 | 17-APR-13:50 | 24.13 | 9.50 |
May | 0.361642E+10 | 25179.02 | 15-MAY-00:03 | 15.68 | 5.16 | 0.254866E+09 | 301.64 | 23-MAY-14:30 | 18.05 | 13.92 |
June | 0.789770E+10 | 25510.26 | 12-JUN-00:01 | 17.38 | 9.60 | 0.258603E+09 | 301.61 | 24-JUN-12:39 | 29.63 | 17.87 |
July | 0.991168E+10 | 22997.66 | 24-JUL-00:01 | 22.80 | 14.35 | 0.248812E+09 | 301.61 | 29-JUL-13:39 | 32.23 | 18.95 |
August | 0.990122E+10 | 22429.20 | 07-AUG-00:01 | 23.03 | 14.79 | 0.268781E+09 | 301.65 | 28-AUG-14:09 | 23.40 | 17.49 |
September | 0.674008E+10 | 23324.68 | 11-SEP-00:01 | 18.03 | 11.68 | 0.248861E+09 | 301.61 | 22-SEP-10:50 | 24.13 | 14.41 |
October | 0.275212E+10 | 23754.28 | 02-OCT-00:01 | 18.48 | 12.10 | 0.237468E+09 | 301.61 | 07-OCT-14:09 | 23.98 | 14.16 |
November | 63800951.37 | 2061.61 | 02-NOV-15:50 | 16.78 | 9.69 | 0.203015E+09 | 301.59 | 06-NOV-16:00 | 14.40 | 4.25 |
December | 11964684.48 | 316.12 | 05-DEC-15:30 | 6.10 | 0.20 | 0.196889E+09 | 289.17 | 02-DEC-15:00 | 11.10 | 3.04 |
Annual Sum or Average | 0.422732E+11 | 0.276335E+10 | ||||||||
Minimum of Months | 907802.66 | 192.37 | 5.60 | 0.20 | 0.185301E+09 | 285.72 | 11.10 | 3.04 | ||
Maximum of Months | 0.991168E+10 | 25510.26 | 23.03 | 14.79 | 0.268781E+09 | 301.65 | 32.23 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207139E+09 | 2372.32 | 20-JAN-13:00 | -0.6 | -0.8 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.235892E+09 | 2096.72 | 06-FEB-11:00 | 0.60 | -3.3 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 76856777.91 | 1861.58 | 10-MAR-09:15 | 5.17 | 0.19 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.431840E+09 | 7410.15 | 28-APR-14:10 | 24.50 | 10.28 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.384968E+10 | 58805.69 | 21-MAY-11:11 | 24.97 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.160909E+11 | 60219.30 | 18-JUN-08:11 | 23.73 | 11.66 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.236148E+11 | 56573.92 | 20-JUL-23:21 | 25.55 | 12.87 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.204778E+11 | 59022.50 | 16-AUG-21:21 | 24.75 | 13.35 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.988046E+10 | 58174.87 | 15-SEP-17:11 | 24.83 | 14.00 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.235274E+10 | 60909.25 | 01-OCT-10:31 | 22.97 | 13.27 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.279791E+09 | 6050.16 | 08-NOV-07:10 | 10.50 | 4.85 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.502416E+09 | 3176.65 | 21-DEC-09:50 | -3.6 | -5.1 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.780003E+11 | 0.00 | ||||||||
Minimum of Months | 76856777.91 | 1861.58 | -3.6 | -5.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.236148E+11 | 60909.25 | 25.55 | 14.00 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.2 | -5.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2.47 | -0.6 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 | 8.94 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 | 14.89 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.85 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 | 14.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 17.33 | 10.87 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 | 1.83 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.85 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467202E+10 | 29595.32 | 17-JAN-06:11 | -3.5 |
February | 0.375080E+10 | 29135.14 | 06-FEB-06:01 | -4.6 |
March | 0.254154E+10 | 29060.75 | 04-MAR-06:12 | -1.7 |
April | 0.676686E+09 | 28959.93 | 07-APR-05:01 | 4.22 |
May | 0.205868E+09 | 28479.62 | 05-MAY-05:01 | 5.68 |
June | 37454565.85 | 4204.08 | 07-JUN-05:30 | 19.75 |
July | 3921972.16 | 3206.92 | 14-JUL-06:05 | 20.37 |
August | 16428861.91 | 3432.89 | 03-AUG-06:05 | 19.18 |
September | 59864077.97 | 1820.55 | 11-SEP-06:04 | 15.37 |
October | 0.573677E+09 | 28979.59 | 26-OCT-05:01 | -2.5 |
November | 0.195896E+10 | 29156.71 | 27-NOV-06:12 | -4.4 |
December | 0.437905E+10 | 29177.36 | 18-DEC-06:22 | -3.4 |
Annual Sum or Average | 0.188763E+11 | |||
Minimum of Months | 3921972.16 | 1820.55 | -4.6 | |
Maximum of Months | 0.467202E+10 | 29595.32 | 20.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236830E+11 | 90998.22 | 17-JAN-22:02 | -1.6 |
February | 0.173159E+11 | 91121.76 | 04-FEB-23:22 | -0.6 |
March | 0.770240E+10 | 89490.78 | 04-MAR-00:12 | 1.50 |
April | 0.140582E+10 | 46097.67 | 07-APR-22:03 | 4.40 |
May | 0.603699E+09 | 3727.44 | 04-MAY-06:50 | 6.52 |
June | 0.269049E+09 | 3378.22 | 15-JUN-06:12 | 20.57 |
July | 87962766.96 | 3388.73 | 17-JUL-07:00 | 19.40 |
August | 0.204682E+09 | 3371.41 | 31-AUG-06:10 | 13.63 |
September | 0.352780E+09 | 3907.74 | 01-SEP-07:00 | 18.90 |
October | 0.104265E+10 | 71911.99 | 27-OCT-05:01 | 0.50 |
November | 0.788215E+10 | 91066.51 | 26-NOV-05:32 | 0.77 |
December | 0.220456E+11 | 91034.32 | 24-DEC-06:12 | -3.1 |
Annual Sum or Average | 0.825957E+11 | |||
Minimum of Months | 87962766.96 | 3371.41 | -3.1 | |
Maximum of Months | 0.236830E+11 | 91121.76 | 20.57 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351651E+11 | 91312.17 | 16-JAN-18:00 | -1.7 |
February | 0.214537E+11 | 83216.50 | 06-FEB-05:00 | -4.4 |
March | 0.171335E+10 | 37163.13 | 04-MAR-06:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 17.33 |
November | 0.151207E+10 | 33632.28 | 26-NOV-06:43 | 0.10 |
December | 0.330652E+11 | 93201.28 | 14-DEC-03:52 | -1.1 |
Annual Sum or Average | 0.929094E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.351651E+11 | 93201.28 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266924E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228025E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204802E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15892741.82 | 0.129797E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95462666.99 | 0.103106E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546935E+09 | 0.447790E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614370E+09 | 0.168188E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454534E+09 | 0.314156E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176516E+09 | 0.558075E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33540289.03 | 0.135422E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203370E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264742E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.193725E+10 | 0.168501E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168188E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614370E+09 | 0.266924E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137539E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127887E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50329.46 | 0.112429E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14493186.82 | 0.821595E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165135E+09 | 0.764405E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161890E+10 | 0.451893E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209417E+10 | 0.278719E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107585E+10 | 0.392129E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225902E+09 | 0.508875E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11762735.87 | 0.784941E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998525E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123112E+11 |
Annual Sum or Average | 0.136656E+12 | 0.520626E+10 | 0.100108E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278719E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209417E+10 | 0.137539E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78204090.87 | 0.277800E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244928E+09 | 0.264205E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487081E+09 | 0.243870E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505137E+09 | 0.228666E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236894E+09 | 0.278155E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126301E+09 | 0.199261E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112599E+09 | 0.154495E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11464436.78 | 0.197900E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2190450.81 | 0.216453E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90081368.84 | 0.269138E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16103811.69 | 0.230419E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3251431.70 | 0.257242E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.191424E+10 | 0.281760E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2190450.81 | 0.154495E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505137E+09 | 0.278155E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10066.12 | 17-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 9647.10 | 06-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7893.41 | 10-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.10 | 13-APR-17:00 | 6358.88 | 06-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2139.16 | 19-MAY-17:00 | 5611.03 | 05-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.49 | 28-JUN-16:10 | 4474.93 | 09-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4200.95 | 21-JUL-17:00 | 1795.72 | 28-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3391.49 | 01-AUG-16:10 | 3322.37 | 31-AUG-06:01 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.66 | 20-SEP-17:00 | 4003.72 | 27-SEP-06:03 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.17 | 06-OCT-16:05 | 7999.96 | 27-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8494.59 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9874.12 | 15-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.72 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.49 | 10066.12 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 30193.82 | 16-JAN-18:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23777.12 | 05-FEB-01:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 12-MAR-17:00 | 24261.38 | 14-MAR-07:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.24 | 01-APR-17:30 | 26182.34 | 15-APR-15:03 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.46 | 19-MAY-15:10 | 16852.93 | 05-MAY-08:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.52 | 17-JUN-16:00 | 11392.19 | 01-JUN-17:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9405.44 | 04-JUL-15:10 | 7617.10 | 15-JUL-18:55 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6348.69 | 02-AUG-17:00 | 8522.64 | 25-AUG-19:55 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.85 | 03-SEP-14:35 | 10567.32 | 07-SEP-15:10 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.61 | 01-OCT-15:57 | 26030.87 | 24-OCT-15:02 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21806.29 | 26-NOV-06:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 30927.23 | 14-DEC-03:51 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7617.10 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.52 | 30927.23 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5229.15 | 24-JAN-15:00 | 60121.80 | 17-JAN-08:70 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10400.29 | 14-FEB-17:00 | 47681.30 | 05-FEB-01:40 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12399.96 | 08-MAR-17:00 | 48903.38 | 21-MAR-10:55 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10931.44 | 01-APR-17:00 | 75748.28 | 15-APR-12:05 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5459.65 | 07-MAY-18:00 | 54748.25 | 05-MAY-08:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.46 | 12-JUN-16:00 | 36999.42 | 08-JUN-12:10 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.12 | 04-JUL-16:51 | 30776.56 | 15-JUL-18:55 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.74 | 20-AUG-17:20 | 33956.08 | 22-AUG-20:53 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.30 | 03-SEP-13:53 | 36944.25 | 07-SEP-15:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9208.83 | 31-OCT-15:00 | 73829.09 | 24-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4096.55 | 09-NOV-14:00 | 41155.38 | 03-NOV-21:25 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.24 | 24-DEC-15:00 | 61927.68 | 14-DEC-03:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 637.74 | 30776.56 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 12399.96 | 75748.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 192.37 | 06-JAN-17:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.84 |
February | 1103.02 | 15-FEB-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.67 |
March | 1497.84 | 08-MAR-16:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.85 |
April | 21141.52 | 29-APR-19:21 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 |
May | 25179.02 | 15-MAY-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.83 |
June | 25510.26 | 12-JUN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.49 |
July | 22997.66 | 24-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 |
August | 22429.20 | 07-AUG-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.36 |
September | 23324.68 | 11-SEP-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.77 |
October | 23754.28 | 02-OCT-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.79 |
November | 2061.61 | 02-NOV-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.10 |
December | 316.12 | 05-DEC-15:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 192.37 | 0.00 | 1835.82 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 | |
Maximum of Months | 25510.26 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2372.32 | 20-JAN-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2735.77 |
February | 2096.72 | 06-FEB-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.57 |
March | 1861.58 | 10-MAR-09:15 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3514.73 |
April | 7410.15 | 28-APR-14:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.72 |
May | 58805.69 | 21-MAY-11:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.16 |
June | 60219.30 | 18-JUN-08:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.24 |
July | 56573.92 | 20-JUL-23:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.68 |
August | 59022.50 | 16-AUG-21:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.99 |
September | 58174.87 | 15-SEP-17:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.57 |
October | 60909.25 | 01-OCT-10:31 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.03 |
November | 6050.16 | 08-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2380.67 |
December | 3176.65 | 21-DEC-09:50 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1861.58 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60909.25 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3514.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11650.29 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267.00 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3615.95 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5457.29 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12212.40 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12907.50 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10693.50 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8542.10 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9609.39 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 13798.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8883.04 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3005.03 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4253.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3005.03 | |
Maximum of Months | 0.00 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.726542E+11 | 52904.09 | 17-JAN-11:09 | 0.925879E+11 | 183022.66 | 16-JAN-17:49 |
February | 0.654503E+11 | 52914.63 | 14-FEB-15:00 | 0.641902E+11 | 168129.90 | 06-FEB-06:10 |
March | 0.735198E+11 | 53146.03 | 08-MAR-15:00 | 0.242340E+11 | 103339.19 | 04-MAR-06:19 |
April | 0.682402E+11 | 56245.22 | 28-APR-14:50 | 0.108539E+11 | 34670.69 | 08-APR-05:10 |
May | 0.717138E+11 | 64100.14 | 19-MAY-14:39 | 0.101477E+11 | 11551.47 | 05-MAY-05:10 |
June | 0.792813E+11 | 73829.76 | 28-JUN-14:00 | 0.972306E+10 | 6659.91 | 07-JUN-05:30 |
July | 0.835997E+11 | 74163.97 | 22-JUL-14:00 | 0.100440E+11 | 3750.00 | 01-JUL-00:10 |
August | 0.850129E+11 | 70083.27 | 01-AUG-14:00 | 0.100440E+11 | 3750.00 | 01-AUG-00:10 |
September | 0.741561E+11 | 66928.14 | 02-SEP-14:00 | 0.972000E+10 | 3750.00 | 01-SEP-00:10 |
October | 0.714025E+11 | 63415.19 | 06-OCT-14:00 | 0.112332E+11 | 36208.73 | 27-OCT-05:10 |
November | 0.687085E+11 | 56347.12 | 24-NOV-16:00 | 0.242605E+11 | 95468.04 | 26-NOV-06:00 |
December | 0.727959E+11 | 56650.13 | 14-DEC-16:00 | 0.880368E+11 | 187787.36 | 14-DEC-04:10 |
Annual Sum or Average | 0.886535E+12 | 0.365075E+12 | ||||
Minimum of Months | 0.654503E+11 | 52904.09 | 0.972000E+10 | 3750.00 | ||
Maximum of Months | 0.850129E+11 | 74163.97 | 0.925879E+11 | 187787.36 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.123044E+11 | 0.115358E+11 | 0.00 | 0.640937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230126E+10 | 0.00 |
February | 0.366966E+11 | 0.104800E+11 | 0.105871E+11 | 0.00 | 0.558929E+10 | 0.00 | 0.00 | 860924.41 | 0.00 | 0.00 | 0.00 | 0.209645E+10 | 0.00 |
March | 0.423649E+11 | 0.106874E+11 | 0.123357E+11 | 0.00 | 0.578541E+10 | 0.00 | 0.00 | 3744726.01 | 0.00 | 0.00 | 0.00 | 0.234271E+10 | 0.00 |
April | 0.397216E+11 | 0.940512E+10 | 0.114862E+11 | 0.00 | 0.509209E+10 | 0.00 | 0.00 | 0.355166E+09 | 0.00 | 0.00 | 0.00 | 0.218000E+10 | 0.00 |
May | 0.412341E+11 | 0.891954E+10 | 0.119357E+11 | 0.00 | 0.541908E+10 | 0.00 | 0.00 | 0.201067E+10 | 0.00 | 0.00 | 0.00 | 0.219469E+10 | 0.00 |
June | 0.408524E+11 | 0.820767E+10 | 0.118862E+11 | 0.00 | 0.753314E+10 | 0.00 | 0.00 | 0.871364E+10 | 0.00 | 0.00 | 0.00 | 0.208839E+10 | 0.00 |
July | 0.401034E+11 | 0.870268E+10 | 0.115358E+11 | 0.00 | 0.849105E+10 | 0.00 | 0.00 | 0.126921E+11 | 0.00 | 0.00 | 0.00 | 0.207477E+10 | 0.00 |
August | 0.423649E+11 | 0.935797E+10 | 0.123357E+11 | 0.00 | 0.810123E+10 | 0.00 | 0.00 | 0.107368E+11 | 0.00 | 0.00 | 0.00 | 0.211628E+10 | 0.00 |
September | 0.397216E+11 | 0.994727E+10 | 0.114862E+11 | 0.00 | 0.597184E+10 | 0.00 | 0.00 | 0.498529E+10 | 0.00 | 0.00 | 0.00 | 0.204395E+10 | 0.00 |
October | 0.401034E+11 | 0.112296E+11 | 0.115358E+11 | 0.00 | 0.522359E+10 | 0.00 | 0.00 | 0.116753E+10 | 0.00 | 0.00 | 0.00 | 0.214268E+10 | 0.00 |
November | 0.385909E+11 | 0.116869E+11 | 0.110862E+11 | 0.00 | 0.521175E+10 | 0.00 | 0.00 | 992.41 | 0.00 | 0.00 | 0.00 | 0.213278E+10 | 0.00 |
December | 0.401034E+11 | 0.125307E+11 | 0.115358E+11 | 0.00 | 0.635980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226625E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123459E+12 | 0.139282E+12 | 0.751876E+11 | 0.00 | 0.406658E+11 | 0.259802E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.820767E+10 | 0.105871E+11 | 0.00 | 0.509209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204395E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.125307E+11 | 0.123357E+11 | 0.00 | 0.849105E+10 | 0.00 | 0.00 | 0.126921E+11 | 0.00 | 0.00 | 0.00 | 0.234271E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.925879E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.641902E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.242340E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108539E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.101477E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.972306E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.100440E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100440E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.972000E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112332E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.242605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.880368E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365075E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.972000E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.925879E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5403.26 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5403.26 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5403.26 | 04-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5104.85 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7410.15 | 19-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7410.15 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7410.15 | 12-JUL-10:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7410.15 | 01-AUG-09:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7410.15 | 01-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7410.15 | 06-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5403.26 | 27-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5403.26 | 04-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5104.85 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 7410.15 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2424.22 | 30-JAN-12:00 | 0.00 |
February | 263.62 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2430.73 | 06-FEB-12:00 | 0.00 |
March | 485.58 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2387.96 | 02-MAR-12:39 | 0.00 |
April | 3630.71 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 2194.30 | 03-APR-11:50 | 0.00 |
May | 10248.23 | 19-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1911.83 | 01-MAY-11:00 | 0.00 |
June | 20237.38 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1787.88 | 01-JUN-11:09 | 0.00 |
July | 20577.25 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1768.53 | 01-JUL-11:30 | 0.00 |
August | 16228.19 | 01-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1762.28 | 31-AUG-11:20 | 0.00 |
September | 12242.30 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1777.25 | 30-SEP-11:30 | 0.00 |
October | 8574.92 | 02-OCT-14:39 | 0.00 | 0.00 | 0.00 | 1801.43 | 30-OCT-11:39 | 0.00 |
November | 0.17 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2083.00 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2310.82 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1762.28 | 0.00 | ||
Maximum of Months | 20577.25 | 0.00 | 0.00 | 0.00 | 2430.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52904.09 | 17-JAN-11:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5403.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52914.63 | 14-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5104.85 | 0.00 | 0.00 | 263.62 | 0.00 |
March | 53146.03 | 08-MAR-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5104.85 | 0.00 | 0.00 | 485.58 | 0.00 |
April | 56245.22 | 28-APR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5104.85 | 0.00 | 0.00 | 3630.71 | 0.00 |
May | 64100.14 | 19-MAY-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 9255.33 | 0.00 |
June | 73829.76 | 28-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 18949.63 | 0.00 |
July | 74163.97 | 22-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 19291.73 | 0.00 |
August | 70083.27 | 01-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 15212.85 | 0.00 |
September | 66928.14 | 02-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 12053.98 | 0.00 |
October | 63415.19 | 06-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7410.15 | 0.00 | 0.00 | 8525.55 | 0.00 |
November | 56347.12 | 24-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5104.85 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56650.13 | 14-DEC-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5403.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52904.09 | 31660.41 | 10112.62 | 0.00 | 0.00 | 5104.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74163.97 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 7410.15 | 0.00 | 0.00 | 19291.73 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 183022.66 | 16-JAN-17:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 168129.90 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 103339.19 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 34670.69 | 08-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11551.47 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6659.91 | 07-JUN-05:30 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 36208.73 | 27-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 95468.04 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 187787.36 | 14-DEC-04:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 187787.36 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 18.43 | 9.00 | 19.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.67 | 18.91 | 7.33 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.00 | 19.91 | 7.00 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.00 | 20.20 | 2.00 | 20.20 | 1.00 | 24.52 | 0.00 | 0.00 |
May | 0.33 | 20.43 | 0.33 | 20.43 | 8.50 | 24.61 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 24.81 | 0.50 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 24.84 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 24.82 | 0.67 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 24.65 | 0.67 | 24.48 |
October | 1.17 | 20.11 | 1.17 | 20.11 | 2.67 | 24.54 | 0.17 | 24.49 |
November | 5.50 | 19.82 | 5.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.00 | 19.18 | 8.33 | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.83 | 19.21 | 40.50 | 19.66 | 108.33 | 24.78 | 2.00 | 24.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 20.43 | 9.00 | 20.43 | 30.33 | 24.84 | 0.67 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.50 | 14.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73.67 | 14.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33.00 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.17 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.69 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.82 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.70 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 0.00 | 0.00 |
October | 1.83 | 14.86 | 0.00 | 0.00 | 1.00 | 27.46 | 0.00 | 0.00 |
November | 35.83 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99.67 | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 344.67 | 14.44 | 0.00 | 58.17 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.67 | 14.86 | 0.00 | 0.00 | 22.67 | 27.82 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.19 | 293.00 | 21.15 | 293.00 | 21.15 |
February | 276.00 | 21.36 | 243.00 | 21.12 | 243.00 | 21.12 |
March | 324.00 | 21.83 | 227.33 | 21.21 | 227.33 | 21.21 |
April | 297.67 | 22.95 | 84.17 | 21.28 | 84.17 | 21.28 |
May | 211.00 | 23.41 | 21.17 | 21.96 | 15.67 | 21.29 |
June | 51.17 | 23.68 | 144.67 | 23.90 | 0.00 | 0.00 |
July | 19.67 | 23.78 | 281.67 | 23.90 | 17.17 | 23.87 |
August | 20.33 | 23.83 | 300.33 | 23.90 | 17.83 | 23.92 |
September | 44.33 | 23.87 | 189.83 | 23.90 | 5.83 | 23.90 |
October | 215.33 | 22.88 | 101.67 | 22.54 | 51.33 | 21.20 |
November | 288.00 | 21.81 | 191.83 | 21.20 | 191.83 | 21.20 |
December | 300.00 | 21.14 | 290.50 | 21.09 | 290.50 | 21.09 |
Annual Sum or Average | 2347.50 | 22.09 | 2369.17 | 22.29 | 1437.67 | 21.24 |
Minimum of Months | 19.67 | 21.14 | 21.17 | 21.09 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.87 | 300.33 | 23.90 | 293.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 3108473.28 | 860924.41 | 6.00 | 3108473.28 | 0.00 | 0.00 | 0.05 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 | 954.22 | 14-FEB-16:00 | 954.22 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 | 263.62 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 |
March | 13599272.10 | 3744726.01 | 17.00 | 13599272.10 | 0.00 | 0.00 | 0.10 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 | 1769.98 | 08-MAR-16:00 | 1769.98 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 | 485.58 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 |
April | 0.114218E+10 | 0.305743E+09 | 127.02 | 0.114218E+10 | 9.43 | 0.00 | 1.00 | 11-APR-17:11 | 0.00 | 01-APR-00:10 | 20306.43 | 11-APR-18:01 | 20306.43 | 11-APR-18:01 | 0.01 | 15-APR-08:30 | 4822.75 | 28-APR-18:40 | 0.00 | 01-APR-00:10 |
May | 0.338603E+10 | 0.919565E+09 | 218.02 | 0.337235E+10 | 13689090.88 | 0.00 | 1.00 | 02-MAY-17:11 | 0.00 | 01-MAY-00:10 | 21324.42 | 22-MAY-00:01 | 20753.85 | 27-MAY-19:11 | 3651.41 | 27-MAY-20:05 | 5143.19 | 19-MAY-17:08 | 0.00 | 01-MAY-00:10 |
June | 0.908933E+10 | 0.264107E+10 | 341.50 | 0.894276E+10 | 0.146568E+09 | 0.00 | 1.00 | 02-JUN-17:11 | 0.00 | 01-JUN-00:05 | 22159.63 | 29-JUN-05:41 | 21142.56 | 30-JUN-21:01 | 7965.59 | 05-JUN-00:03 | 5663.93 | 27-JUN-17:05 | 0.00 | 01-JUN-00:05 |
July | 0.130317E+11 | 0.367143E+10 | 385.35 | 0.116274E+11 | 0.140432E+10 | 0.00 | 1.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:05 | 24326.14 | 01-JUL-17:10 | 21024.86 | 06-JUL-00:21 | 11565.96 | 01-JUL-03:01 | 5701.82 | 21-JUL-17:05 | 0.00 | 01-JUL-00:05 |
August | 0.123815E+11 | 0.340302E+10 | 382.47 | 0.110324E+11 | 0.134912E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 23372.38 | 14-AUG-01:09 | 22337.94 | 13-AUG-17:51 | 11094.63 | 26-AUG-05:20 | 5732.86 | 13-AUG-17:51 | 0.00 | 01-AUG-00:01 |
September | 0.688812E+10 | 0.185686E+10 | 264.05 | 0.644493E+10 | 0.443181E+09 | 0.00 | 1.00 | 01-SEP-00:40 | 0.00 | 01-SEP-00:05 | 22435.83 | 23-SEP-17:11 | 21207.73 | 18-SEP-17:08 | 9904.90 | 05-SEP-05:25 | 5447.21 | 02-SEP-17:06 | 0.00 | 01-SEP-00:05 |
October | 0.218702E+10 | 0.579539E+09 | 152.19 | 0.207966E+10 | 0.107357E+09 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:02 | 22730.44 | 02-OCT-17:10 | 20923.68 | 03-OCT-17:08 | 7256.00 | 02-OCT-17:16 | 5363.74 | 02-OCT-17:10 | 0.00 | 01-OCT-00:02 |
November | 3562.62 | 992.41 | 7.36 | 3562.62 | 0.00 | 0.00 | 0.00 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 0.63 | 02-NOV-15:00 | 0.63 | 02-NOV-15:00 | 0.00 | 02-NOV-14:20 | 0.17 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.481226E+11 | 0.133818E+11 | 1900.97 | 0.446584E+11 | 0.346423E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.130317E+11 | 0.367143E+10 | 385.35 | 0.116274E+11 | 0.140432E+10 | 0.00 | 1.00 | 0.00 | 24326.14 | 22337.94 | 11565.96 | 5732.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.165514E+09 | 49422273.51 | 20.50 | 0.165514E+09 | 0.00 | 0.00 | 0.13 | 28-APR-14:40 | 0.00 | 01-APR-00:10 | 6375.86 | 28-APR-14:40 | 6375.86 | 28-APR-14:40 | 0.00 | 28-APR-13:20 | 1881.47 | 28-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.363399E+10 | 0.109111E+10 | 124.70 | 0.362982E+10 | 4177172.85 | 0.00 | 1.00 | 14-MAY-12:11 | 0.00 | 01-MAY-00:10 | 61166.52 | 28-MAY-12:21 | 59171.80 | 21-MAY-11:11 | 5584.13 | 28-MAY-12:28 | 15778.26 | 29-MAY-14:51 | 0.00 | 01-MAY-00:10 |
June | 0.187738E+11 | 0.607256E+10 | 267.16 | 0.186207E+11 | 0.153121E+09 | 0.00 | 1.00 | 03-JUN-17:21 | 0.00 | 01-JUN-00:05 | 62857.55 | 25-JUN-08:11 | 59921.84 | 28-JUN-23:07 | 8898.26 | 25-JUN-08:17 | 17772.46 | 25-JUN-15:32 | 0.00 | 01-JUN-00:05 |
July | 0.287120E+11 | 0.902068E+10 | 330.69 | 0.269168E+11 | 0.179523E+10 | 0.00 | 1.00 | 02-JUL-09:00 | 0.00 | 01-JUL-00:05 | 68941.71 | 16-JUL-08:31 | 60056.37 | 23-JUL-18:41 | 26034.16 | 16-JUL-08:31 | 18219.60 | 23-JUL-14:02 | 0.00 | 01-JUL-00:05 |
August | 0.239916E+11 | 0.733380E+10 | 307.10 | 0.223753E+11 | 0.161629E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:01 | 68246.39 | 13-AUG-08:25 | 60095.50 | 06-AUG-11:01 | 28892.38 | 13-AUG-08:25 | 17764.73 | 20-AUG-15:22 | 0.00 | 01-AUG-00:01 |
September | 0.105109E+11 | 0.312842E+10 | 191.95 | 0.100328E+11 | 0.478119E+09 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:05 | 65008.14 | 04-SEP-10:41 | 59767.05 | 10-SEP-15:31 | 16048.19 | 10-SEP-11:28 | 17295.85 | 03-SEP-13:53 | 0.00 | 01-SEP-00:05 |
October | 0.199716E+10 | 0.587993E+09 | 60.98 | 0.195152E+10 | 45647690.08 | 0.00 | 1.00 | 01-OCT-10:31 | 0.00 | 01-OCT-00:02 | 60228.28 | 01-OCT-11:20 | 59506.39 | 01-OCT-13:11 | 3120.61 | 01-OCT-10:31 | 16043.44 | 01-OCT-13:11 | 0.00 | 01-OCT-00:02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.877850E+11 | 0.272840E+11 | 1303.08 | 0.836924E+11 | 0.409258E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.287120E+11 | 0.902068E+10 | 330.69 | 0.269168E+11 | 0.179523E+10 | 0.00 | 1.00 | 0.00 | 68941.71 | 60095.50 | 28892.38 | 18219.60 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.75 | 69.38 | 52.37 | 93.65 | 166.17 | 0.00 | 0.00 | 744.00 |
February | 156.30 | 90.11 | 66.19 | 135.99 | 147.44 | 0.00 | 0.00 | 672.00 |
March | 175.30 | 93.34 | 81.96 | 168.31 | 111.81 | 0.00 | 0.00 | 744.00 |
April | 223.34 | 118.71 | 104.63 | 228.50 | 82.49 | 0.00 | 0.00 | 720.00 |
May | 212.81 | 109.94 | 102.87 | 226.38 | 69.32 | 0.00 | 0.00 | 744.00 |
June | 226.85 | 126.39 | 100.45 | 280.69 | 50.70 | 0.00 | 0.00 | 720.00 |
July | 204.99 | 100.32 | 104.68 | 262.13 | 34.16 | 0.00 | 0.00 | 744.00 |
August | 209.25 | 96.61 | 112.64 | 255.98 | 39.35 | 0.00 | 0.00 | 744.00 |
September | 189.88 | 100.24 | 89.64 | 214.66 | 67.32 | 0.00 | 0.00 | 720.00 |
October | 172.96 | 107.44 | 65.52 | 173.88 | 109.22 | 0.00 | 0.00 | 744.00 |
November | 135.68 | 79.73 | 55.95 | 112.64 | 131.47 | 0.00 | 0.00 | 720.00 |
December | 117.38 | 73.55 | 43.83 | 86.53 | 173.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 178.90 | 97.10 | 81.79 | 186.78 | 98.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.38 | 69.38 | 43.83 | 86.53 | 34.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 226.85 | 126.39 | 112.64 | 280.69 | 173.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.75 | 69.38 | 52.37 | 93.65 | 166.17 | 0.00 | 0.00 | 744.00 |
February | 156.30 | 90.11 | 66.19 | 135.99 | 147.44 | 0.00 | 0.00 | 672.00 |
March | 175.30 | 93.34 | 81.96 | 168.31 | 111.81 | 0.00 | 0.00 | 744.00 |
April | 223.34 | 118.71 | 104.63 | 228.50 | 82.49 | 0.00 | 0.00 | 720.00 |
May | 212.81 | 109.94 | 102.87 | 226.38 | 69.32 | 0.00 | 0.00 | 744.00 |
June | 226.85 | 126.39 | 100.45 | 280.69 | 50.70 | 0.00 | 0.00 | 720.00 |
July | 204.99 | 100.32 | 104.68 | 262.13 | 34.16 | 0.00 | 0.00 | 744.00 |
August | 209.25 | 96.61 | 112.64 | 255.98 | 39.35 | 0.00 | 0.00 | 744.00 |
September | 189.88 | 100.24 | 89.64 | 214.66 | 67.32 | 0.00 | 0.00 | 720.00 |
October | 172.96 | 107.44 | 65.52 | 173.88 | 109.22 | 0.00 | 0.00 | 744.00 |
November | 135.68 | 79.73 | 55.95 | 112.64 | 131.47 | 0.00 | 0.00 | 720.00 |
December | 117.38 | 73.55 | 43.83 | 86.53 | 173.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 178.90 | 97.10 | 81.79 | 186.78 | 98.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.38 | 69.38 | 43.83 | 86.53 | 34.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 226.85 | 126.39 | 112.64 | 280.69 | 173.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.89 | 0.00 | 24.89 | 2.95 | 102.38 | 0.00 | 0.00 | 744.00 |
February | 31.11 | 0.00 | 31.11 | 7.71 | 90.01 | 0.00 | 0.00 | 672.00 |
March | 39.25 | 0.00 | 39.25 | 19.97 | 67.20 | 0.00 | 0.00 | 744.00 |
April | 49.88 | 0.51 | 49.37 | 30.70 | 48.66 | 0.00 | 0.00 | 720.00 |
May | 54.23 | 3.57 | 50.66 | 38.81 | 39.40 | 0.00 | 0.00 | 744.00 |
June | 61.50 | 10.08 | 51.42 | 62.16 | 26.83 | 0.00 | 0.00 | 720.00 |
July | 56.31 | 4.56 | 51.75 | 67.92 | 18.65 | 0.00 | 0.00 | 744.00 |
August | 52.55 | 1.36 | 51.19 | 58.12 | 21.87 | 0.00 | 0.00 | 744.00 |
September | 41.90 | 0.02 | 41.88 | 37.29 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 31.24 | 0.00 | 31.24 | 14.34 | 65.86 | 0.00 | 0.00 | 744.00 |
November | 26.53 | 0.00 | 26.53 | 4.23 | 81.67 | 0.00 | 0.00 | 720.00 |
December | 21.19 | 0.00 | 21.19 | 0.57 | 109.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.92 | 1.68 | 39.24 | 28.85 | 59.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.19 | 0.00 | 21.19 | 0.57 | 18.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 61.50 | 10.08 | 51.75 | 67.92 | 109.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.89 | 0.00 | 24.89 | 2.95 | 102.38 | 0.00 | 0.00 | 744.00 |
February | 31.11 | 0.00 | 31.11 | 7.71 | 90.01 | 0.00 | 0.00 | 672.00 |
March | 39.25 | 0.00 | 39.25 | 19.97 | 67.20 | 0.00 | 0.00 | 744.00 |
April | 49.88 | 0.51 | 49.37 | 30.70 | 48.66 | 0.00 | 0.00 | 720.00 |
May | 54.23 | 3.57 | 50.66 | 38.81 | 39.40 | 0.00 | 0.00 | 744.00 |
June | 61.50 | 10.08 | 51.42 | 62.16 | 26.83 | 0.00 | 0.00 | 720.00 |
July | 56.31 | 4.56 | 51.75 | 67.91 | 18.65 | 0.00 | 0.00 | 744.00 |
August | 52.55 | 1.36 | 51.19 | 58.11 | 21.87 | 0.00 | 0.00 | 744.00 |
September | 41.90 | 0.02 | 41.88 | 37.29 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 31.24 | 0.00 | 31.24 | 14.34 | 65.86 | 0.00 | 0.00 | 744.00 |
November | 26.53 | 0.00 | 26.53 | 4.23 | 81.67 | 0.00 | 0.00 | 720.00 |
December | 21.19 | 0.00 | 21.19 | 0.57 | 109.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.92 | 1.68 | 39.24 | 28.85 | 59.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.19 | 0.00 | 21.19 | 0.57 | 18.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 61.50 | 10.08 | 51.75 | 67.91 | 109.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.20 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.70 | 66.18 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.14 | 62.90 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.01 | 62.62 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.82 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.91 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.91 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.22 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.63 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.34 | 92.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.34 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.95 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326100E+09 | 0.185837E+09 | 0.140263E+09 | 0.250840E+09 | 0.445065E+09 |
February | 0.378128E+09 | 0.217999E+09 | 0.160129E+09 | 0.328995E+09 | 0.356691E+09 |
March | 0.469536E+09 | 0.250005E+09 | 0.219531E+09 | 0.450796E+09 | 0.299472E+09 |
April | 0.578891E+09 | 0.307684E+09 | 0.271207E+09 | 0.592268E+09 | 0.213814E+09 |
May | 0.570002E+09 | 0.294473E+09 | 0.275529E+09 | 0.606348E+09 | 0.185677E+09 |
June | 0.587985E+09 | 0.327607E+09 | 0.260378E+09 | 0.727555E+09 | 0.131410E+09 |
July | 0.549056E+09 | 0.268690E+09 | 0.280366E+09 | 0.702086E+09 | 91503513.61 |
August | 0.560453E+09 | 0.258765E+09 | 0.301689E+09 | 0.685622E+09 | 0.105397E+09 |
September | 0.492167E+09 | 0.259813E+09 | 0.232354E+09 | 0.556406E+09 | 0.174505E+09 |
October | 0.463246E+09 | 0.287755E+09 | 0.175491E+09 | 0.465730E+09 | 0.292528E+09 |
November | 0.351683E+09 | 0.206649E+09 | 0.145034E+09 | 0.291959E+09 | 0.340767E+09 |
December | 0.314389E+09 | 0.196995E+09 | 0.117393E+09 | 0.231750E+09 | 0.464719E+09 |
Annual Sum or Average | 0.564164E+10 | 0.306227E+10 | 0.257937E+10 | 0.589036E+10 | 0.310155E+10 |
Minimum of Months | 0.314389E+09 | 0.185837E+09 | 0.117393E+09 | 0.231750E+09 | 91503513.61 |
Maximum of Months | 0.587985E+09 | 0.327607E+09 | 0.301689E+09 | 0.727555E+09 | 0.464719E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326100E+09 | 0.185837E+09 | 0.140263E+09 | 0.250840E+09 | 0.445065E+09 |
February | 0.378128E+09 | 0.217999E+09 | 0.160129E+09 | 0.328995E+09 | 0.356691E+09 |
March | 0.469536E+09 | 0.250005E+09 | 0.219531E+09 | 0.450796E+09 | 0.299472E+09 |
April | 0.578891E+09 | 0.307684E+09 | 0.271207E+09 | 0.592268E+09 | 0.213814E+09 |
May | 0.570002E+09 | 0.294473E+09 | 0.275529E+09 | 0.606348E+09 | 0.185677E+09 |
June | 0.587985E+09 | 0.327607E+09 | 0.260378E+09 | 0.727555E+09 | 0.131410E+09 |
July | 0.549056E+09 | 0.268690E+09 | 0.280366E+09 | 0.702086E+09 | 91503513.61 |
August | 0.560453E+09 | 0.258765E+09 | 0.301689E+09 | 0.685622E+09 | 0.105397E+09 |
September | 0.492167E+09 | 0.259813E+09 | 0.232354E+09 | 0.556406E+09 | 0.174505E+09 |
October | 0.463246E+09 | 0.287755E+09 | 0.175491E+09 | 0.465730E+09 | 0.292528E+09 |
November | 0.351683E+09 | 0.206649E+09 | 0.145034E+09 | 0.291959E+09 | 0.340767E+09 |
December | 0.314389E+09 | 0.196995E+09 | 0.117393E+09 | 0.231750E+09 | 0.464719E+09 |
Annual Sum or Average | 0.564164E+10 | 0.306227E+10 | 0.257937E+10 | 0.589036E+10 | 0.310155E+10 |
Minimum of Months | 0.314389E+09 | 0.185837E+09 | 0.117393E+09 | 0.231750E+09 | 91503513.61 |
Maximum of Months | 0.587985E+09 | 0.327607E+09 | 0.301689E+09 | 0.727555E+09 | 0.464719E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66668715.52 | 0.00 | 66668715.52 | 7902179.45 | 0.274227E+09 |
February | 75261013.53 | 0.00 | 75261013.53 | 18647836.68 | 0.217761E+09 |
March | 0.105132E+09 | 9801.61 | 0.105123E+09 | 53494961.83 | 0.179979E+09 |
April | 0.129298E+09 | 1334270.03 | 0.127964E+09 | 79577268.72 | 0.126133E+09 |
May | 0.145259E+09 | 9570705.24 | 0.135689E+09 | 0.103951E+09 | 0.105534E+09 |
June | 0.159414E+09 | 26139100.09 | 0.133275E+09 | 0.161121E+09 | 69546366.99 |
July | 0.150816E+09 | 12214909.61 | 0.138601E+09 | 0.181906E+09 | 49960698.45 |
August | 0.140762E+09 | 3650596.68 | 0.137112E+09 | 0.155656E+09 | 58575832.92 |
September | 0.108612E+09 | 63444.33 | 0.108548E+09 | 96662688.30 | 0.102495E+09 |
October | 83680666.13 | 0.00 | 83680666.13 | 38418377.24 | 0.176390E+09 |
November | 68772274.29 | 0.00 | 68772274.29 | 10972585.48 | 0.211678E+09 |
December | 56745150.82 | 0.00 | 56745150.82 | 1514991.83 | 0.293673E+09 |
Annual Sum or Average | 0.129042E+10 | 52982827.59 | 0.123744E+10 | 0.909824E+09 | 0.186595E+10 |
Minimum of Months | 56745150.82 | 0.00 | 56745150.82 | 1514991.83 | 49960698.45 |
Maximum of Months | 0.159414E+09 | 26139100.09 | 0.138601E+09 | 0.181906E+09 | 0.293673E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66666900.10 | 0.00 | 66666900.10 | 7901627.75 | 0.274227E+09 |
February | 75259048.18 | 0.00 | 75259048.18 | 18646845.48 | 0.217760E+09 |
March | 0.105130E+09 | 9801.15 | 0.105120E+09 | 53492918.76 | 0.179978E+09 |
April | 0.129295E+09 | 1334207.49 | 0.127961E+09 | 79574874.57 | 0.126132E+09 |
May | 0.145256E+09 | 9570256.65 | 0.135685E+09 | 0.103948E+09 | 0.105533E+09 |
June | 0.159410E+09 | 26137874.92 | 0.133272E+09 | 0.161117E+09 | 69545501.64 |
July | 0.150812E+09 | 12214337.08 | 0.138598E+09 | 0.181902E+09 | 49959897.74 |
August | 0.140759E+09 | 3650425.57 | 0.137108E+09 | 0.155653E+09 | 58575100.98 |
September | 0.108609E+09 | 63441.36 | 0.108546E+09 | 96660516.48 | 0.102494E+09 |
October | 83678661.98 | 0.00 | 83678661.98 | 38417319.77 | 0.176389E+09 |
November | 68770440.92 | 0.00 | 68770440.92 | 10971774.59 | 0.211677E+09 |
December | 56743714.95 | 0.00 | 56743714.95 | 1514807.67 | 0.293673E+09 |
Annual Sum or Average | 0.129039E+10 | 52980344.22 | 0.123741E+10 | 0.909802E+09 | 0.186594E+10 |
Minimum of Months | 56743714.95 | 0.00 | 56743714.95 | 1514807.67 | 49959897.74 |
Maximum of Months | 0.159410E+09 | 26137874.92 | 0.138598E+09 | 0.181902E+09 | 0.293673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200636E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194009E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384886E+09 | 0.177255E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500608E+09 | 0.163046E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559801E+09 | 0.167727E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590163E+09 | 0.155065E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605076E+09 | 0.139668E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558499E+09 | 0.141707E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427632E+09 | 0.176708E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313970E+09 | 0.222282E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210356E+09 | 0.198627E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.248958E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222815E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169660E+09 | 0.139668E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605076E+09 | 0.248958E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.95 | 528.85 | 293.29 | 138.77 | 154.52 | 0.00 | 0.00 |
February | 280.51 | 468.02 | 374.82 | 180.22 | 194.60 | 0.00 | 0.00 |
March | 373.29 | 354.74 | 429.11 | 186.69 | 242.42 | 0.00 | 0.00 |
April | 515.87 | 259.77 | 546.44 | 238.44 | 308.00 | 0.00 | 0.00 |
May | 528.93 | 215.99 | 534.09 | 227.03 | 307.06 | 0.00 | 0.00 |
June | 683.14 | 152.49 | 576.70 | 272.95 | 303.74 | 0.00 | 0.00 |
July | 659.00 | 104.55 | 522.60 | 209.76 | 312.85 | 0.00 | 0.00 |
August | 627.83 | 122.08 | 523.61 | 195.95 | 327.66 | 0.00 | 0.00 |
September | 503.28 | 213.11 | 463.56 | 200.52 | 263.04 | 0.00 | 0.00 |
October | 372.44 | 346.14 | 408.40 | 214.87 | 193.53 | 0.00 | 0.00 |
November | 225.63 | 418.15 | 324.42 | 159.45 | 164.97 | 0.00 | 0.00 |
December | 159.61 | 551.73 | 277.13 | 147.10 | 130.03 | 0.00 | 0.00 |
Annual Sum or Average | 426.79 | 310.57 | 439.63 | 197.57 | 242.06 | 0.00 | 0.00 |
Minimum of Months | 159.61 | 104.55 | 277.13 | 138.77 | 130.03 | 0.00 | 0.00 |
Maximum of Months | 683.14 | 551.73 | 576.70 | 272.95 | 327.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 749.09 | 907.60 | 629.81 | 431.71 | 198.10 | 0.00 | 0.00 |
February | 1062.07 | 801.95 | 850.90 | 605.57 | 245.33 | 0.00 | 0.00 |
March | 1437.00 | 661.79 | 1101.83 | 763.98 | 337.85 | 0.00 | 0.00 |
April | 1931.36 | 629.04 | 1480.30 | 1065.20 | 415.10 | 0.00 | 0.00 |
May | 2090.05 | 626.22 | 1606.63 | 1211.17 | 395.46 | 0.00 | 0.00 |
June | 2276.86 | 598.24 | 1702.38 | 1341.53 | 360.85 | 0.00 | 0.00 |
July | 2259.09 | 521.46 | 1656.07 | 1244.99 | 411.08 | 0.00 | 0.00 |
August | 2085.20 | 529.07 | 1552.86 | 1114.01 | 438.85 | 0.00 | 0.00 |
September | 1649.81 | 681.74 | 1265.51 | 924.43 | 341.07 | 0.00 | 0.00 |
October | 1172.22 | 829.90 | 962.24 | 747.88 | 214.36 | 0.00 | 0.00 |
November | 811.55 | 766.30 | 683.93 | 483.14 | 200.79 | 0.00 | 0.00 |
December | 633.43 | 929.50 | 562.96 | 423.24 | 139.72 | 0.00 | 0.00 |
Annual Sum or Average | 1515.16 | 706.54 | 1172.69 | 864.20 | 308.50 | 0.00 | 0.00 |
Minimum of Months | 633.43 | 521.46 | 562.96 | 423.24 | 139.72 | 0.00 | 0.00 |
Maximum of Months | 2276.86 | 929.50 | 1702.38 | 1341.53 | 438.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495368E+09 | 0.141647E+10 | 0.785536E+09 | 0.371674E+09 | 0.413862E+09 | 0.00 | 0.00 |
February | 0.678604E+09 | 0.113222E+10 | 0.906776E+09 | 0.435998E+09 | 0.470778E+09 | 0.00 | 0.00 |
March | 0.999823E+09 | 0.950145E+09 | 0.114933E+10 | 0.500030E+09 | 0.649304E+09 | 0.00 | 0.00 |
April | 0.133713E+10 | 0.673333E+09 | 0.141638E+10 | 0.618037E+09 | 0.798339E+09 | 0.00 | 0.00 |
May | 0.141668E+10 | 0.578509E+09 | 0.143052E+10 | 0.608086E+09 | 0.822433E+09 | 0.00 | 0.00 |
June | 0.177069E+10 | 0.395257E+09 | 0.149479E+10 | 0.707490E+09 | 0.787304E+09 | 0.00 | 0.00 |
July | 0.176507E+10 | 0.280019E+09 | 0.139974E+10 | 0.561810E+09 | 0.837932E+09 | 0.00 | 0.00 |
August | 0.168158E+10 | 0.326973E+09 | 0.140243E+10 | 0.524830E+09 | 0.877597E+09 | 0.00 | 0.00 |
September | 0.130451E+10 | 0.552370E+09 | 0.120156E+10 | 0.519753E+09 | 0.681802E+09 | 0.00 | 0.00 |
October | 0.997555E+09 | 0.927096E+09 | 0.109385E+10 | 0.575511E+09 | 0.518341E+09 | 0.00 | 0.00 |
November | 0.584831E+09 | 0.108386E+10 | 0.840909E+09 | 0.413297E+09 | 0.427611E+09 | 0.00 | 0.00 |
December | 0.427500E+09 | 0.147775E+10 | 0.742266E+09 | 0.393991E+09 | 0.348275E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134593E+11 | 0.979400E+10 | 0.138641E+11 | 0.623051E+10 | 0.763358E+10 | 0.00 | 0.00 |
Minimum of Months | 0.427500E+09 | 0.280019E+09 | 0.742266E+09 | 0.371674E+09 | 0.348275E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177069E+10 | 0.147775E+10 | 0.149479E+10 | 0.707490E+09 | 0.877597E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200636E+10 | 0.243092E+10 | 0.168688E+10 | 0.115628E+10 | 0.530597E+09 | 0.00 | 0.00 |
February | 0.256937E+10 | 0.194008E+10 | 0.205850E+10 | 0.146500E+10 | 0.593495E+09 | 0.00 | 0.00 |
March | 0.384885E+10 | 0.177255E+10 | 0.295113E+10 | 0.204624E+10 | 0.904898E+09 | 0.00 | 0.00 |
April | 0.500607E+10 | 0.163046E+10 | 0.383694E+10 | 0.276100E+10 | 0.107594E+10 | 0.00 | 0.00 |
May | 0.559800E+10 | 0.167727E+10 | 0.430320E+10 | 0.324399E+10 | 0.105921E+10 | 0.00 | 0.00 |
June | 0.590162E+10 | 0.155065E+10 | 0.441257E+10 | 0.347724E+10 | 0.935333E+09 | 0.00 | 0.00 |
July | 0.605075E+10 | 0.139667E+10 | 0.443561E+10 | 0.333458E+10 | 0.110103E+10 | 0.00 | 0.00 |
August | 0.558499E+10 | 0.141706E+10 | 0.415918E+10 | 0.298376E+10 | 0.117541E+10 | 0.00 | 0.00 |
September | 0.427632E+10 | 0.176708E+10 | 0.328019E+10 | 0.239614E+10 | 0.884057E+09 | 0.00 | 0.00 |
October | 0.313968E+10 | 0.222282E+10 | 0.257727E+10 | 0.200313E+10 | 0.574135E+09 | 0.00 | 0.00 |
November | 0.210354E+10 | 0.198626E+10 | 0.177276E+10 | 0.125231E+10 | 0.520451E+09 | 0.00 | 0.00 |
December | 0.169658E+10 | 0.248958E+10 | 0.150784E+10 | 0.113360E+10 | 0.374237E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.477821E+11 | 0.222814E+11 | 0.369821E+11 | 0.272533E+11 | 0.972879E+10 | 0.00 | 0.00 |
Minimum of Months | 0.169658E+10 | 0.139667E+10 | 0.150784E+10 | 0.113360E+10 | 0.374237E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605075E+10 | 0.248958E+10 | 0.443561E+10 | 0.347724E+10 | 0.117541E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.2 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.20 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.66 | -5.5 | 4.72 | -6.1 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.69 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.40 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.39 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.11 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.38 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.86 | 7.70 | 3.48 | 8.21 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.78 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.53 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.11 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.80 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.83 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.65 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.28 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.68 | -1.5 | 8.93 | 13.33 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.11 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.67 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.27 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.73 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.23 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.79 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 3.99 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 3.99 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.73 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.1 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.6 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.2 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -0.7 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.53 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.76 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.7 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.82 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.83 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.65 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.92 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.05 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.75 | 167.00 | 0.00 |
June | 18.16 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.19 | 01-JUL-00:00 | 21.20 | 13.50 | 3.60 | 17.57 | 0.00 | 0.00 |
August | 19.17 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.18 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.15 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.79 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.90 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.90 | 12.80 | -10.0 | 2.10 | -0.1 | 0.00 | 0.00 | |
Maximum of Months | 19.19 | 31.70 | 15.60 | 13.40 | 19.17 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.71 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.78 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.70 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.04 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.58 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.03 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.37 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.04 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100767E+10 | -852326686.1 | 0.00 | 0.00 | 744.00 | 0.00 | -155344202.0 | 58.99 | 0.00 | 0.00 |
February | 0.928113E+09 | -789007033.6 | 0.00 | 0.00 | 672.00 | 0.00 | -139105746.8 | 58.99 | 0.00 | 0.00 |
March | 0.104911E+10 | -899384626.2 | 0.00 | 0.00 | 744.00 | 0.00 | -149727589.7 | 58.99 | 0.00 | 0.00 |
April | 0.927690E+09 | -791278553.3 | 0.00 | 0.00 | 720.00 | 0.00 | -136410998.3 | 58.99 | 0.00 | 0.00 |
May | 0.900696E+09 | -765543258.0 | 0.00 | 0.00 | 744.00 | 0.00 | -135153059.5 | 58.99 | 0.00 | 0.00 |
June | 0.836617E+09 | -707997656.8 | 0.00 | 0.00 | 720.00 | 0.00 | -128619840.2 | 58.99 | 0.00 | 0.00 |
July | 0.780961E+09 | -649632357.6 | 0.00 | 0.00 | 744.00 | 0.00 | -131328840.6 | 58.99 | 0.00 | 0.00 |
August | 0.822537E+09 | -690150384.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132386268.1 | 58.99 | 0.00 | 0.00 |
September | 0.791832E+09 | -663767649.3 | 0.00 | 0.00 | 720.00 | 0.00 | -128064647.3 | 58.99 | 0.00 | 0.00 |
October | 0.848542E+09 | -710537586.9 | 0.00 | 0.00 | 744.00 | 0.00 | -138004349.8 | 58.99 | 0.00 | 0.00 |
November | 0.880889E+09 | -735514352.3 | 0.00 | 0.00 | 720.00 | 0.00 | -145374770.3 | 58.99 | 0.00 | 0.00 |
December | 0.972376E+09 | -817176591.5 | 0.00 | 0.00 | 744.00 | 0.00 | -155199187.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.107470E+11 | -.907232E+10 | 8760.00 | -.167472E+10 | 58.99 | |||||
Minimum of Months | 0.780961E+09 | -899384626.2 | 0.00 | 0.00 | 672.00 | 0.00 | -155344202.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.104911E+10 | -649632357.6 | 0.00 | 0.00 | 744.00 | 0.00 | -128064647.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | ||||||||||
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.474400E+10 | 28615.69 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371578E+10 | 28615.69 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211078E+10 | 28615.69 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.465673E+09 | 28615.69 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69511681.04 | 28615.69 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2015347.37 | 3849.97 | 07-JUN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.448454E+09 | 28615.69 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176342E+10 | 28615.69 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466220E+10 | 28615.69 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179818E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.474400E+10 | 28615.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227243E+11 | 87937.82 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162702E+11 | 87937.82 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610041E+10 | 87937.82 | 03-MAR-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300205E+09 | 45271.95 | 07-APR-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348095E+09 | 70795.59 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684311E+10 | 87937.82 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213633E+11 | 87937.82 | 03-DEC-18:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739497E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227243E+11 | 87937.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.347661E+11 | 91013.77 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212270E+11 | 82918.03 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168321E+10 | 36864.73 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148402E+10 | 33333.87 | 26-NOV-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326635E+11 | 92902.87 | 14-DEC-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918239E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347661E+11 | 92902.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3108473.28 | 3108473.28 | 954.22 | 14-FEB-16:00 | 954.22 | 0.00 |
March | 0.00 | 0.00 | 13599272.10 | 13599272.10 | 1769.98 | 08-MAR-16:00 | 1769.98 | 0.00 |
April | 0.00 | 0.00 | 0.114218E+10 | 0.114218E+10 | 20306.43 | 11-APR-18:01 | 20306.43 | 0.00 |
May | 0.00 | 0.00 | 0.338603E+10 | 0.337235E+10 | 21324.42 | 22-MAY-00:01 | 19527.58 | 0.00 |
June | 0.00 | 0.00 | 0.908933E+10 | 0.894276E+10 | 22159.63 | 29-JUN-05:41 | 19381.60 | 0.00 |
July | 0.00 | 0.00 | 0.130317E+11 | 0.116274E+11 | 24326.14 | 01-JUL-17:10 | 14404.26 | 0.00 |
August | 0.00 | 0.00 | 0.123815E+11 | 0.110324E+11 | 23372.38 | 14-AUG-01:09 | 13600.01 | 0.00 |
September | 0.00 | 0.00 | 0.688812E+10 | 0.644493E+10 | 22435.83 | 23-SEP-17:11 | 15149.02 | 0.00 |
October | 0.00 | 0.00 | 0.218702E+10 | 0.207966E+10 | 22730.44 | 02-OCT-17:10 | 15482.39 | 0.00 |
November | 0.00 | 0.00 | 3562.62 | 3562.62 | 0.63 | 02-NOV-15:00 | 0.63 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.481226E+11 | 0.446584E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130317E+11 | 0.116274E+11 | 24326.14 | 20306.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.165514E+09 | 0.165514E+09 | 6375.86 | 28-APR-14:40 | 6375.86 | 0.00 |
May | 0.00 | 0.00 | 0.363399E+10 | 0.362982E+10 | 61166.52 | 28-MAY-12:21 | 55690.80 | 0.00 |
June | 0.00 | 0.00 | 0.187738E+11 | 0.186207E+11 | 62857.55 | 25-JUN-08:11 | 54212.61 | 0.00 |
July | 0.00 | 0.00 | 0.287120E+11 | 0.269168E+11 | 68941.71 | 16-JUL-08:31 | 42907.55 | 0.00 |
August | 0.00 | 0.00 | 0.239916E+11 | 0.223753E+11 | 68246.39 | 13-AUG-08:25 | 39354.01 | 0.00 |
September | 0.00 | 0.00 | 0.105109E+11 | 0.100328E+11 | 65008.14 | 04-SEP-10:41 | 50694.94 | 0.00 |
October | 0.00 | 0.00 | 0.199716E+10 | 0.195152E+10 | 60228.28 | 01-OCT-11:20 | 58205.05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.877850E+11 | 0.836924E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287120E+11 | 0.269168E+11 | 68941.71 | 58205.05 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.396487E+09 | 0.05 | 298.41 | 01-JAN-00:03 | 0.09 |
February | 0.225409E+09 | 0.03 | 298.41 | 01-FEB-00:02 | 0.09 |
March | 30025873.02 | 0.00 | 298.41 | 01-MAR-03:10 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 27975805.96 | 0.00 | 298.41 | 25-NOV-05:50 | 0.09 |
December | 0.400038E+09 | 0.05 | 298.41 | 03-DEC-07:40 | 0.09 |
Annual Sum or Average | 0.107993E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400038E+09 | 0.05 | 298.41 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156736E+10 | 0.52 | 1520.33 | 02-JAN-08:50 | 1.14 |
February | 0.143822E+10 | 0.51 | 1520.33 | 01-FEB-14:40 | 1.14 |
March | 0.166255E+10 | 0.49 | 1520.33 | 02-MAR-09:00 | 1.14 |
April | 0.152925E+10 | 0.46 | 1520.33 | 01-APR-07:30 | 1.14 |
May | 0.164659E+10 | 0.50 | 1520.33 | 01-MAY-08:30 | 1.13 |
June | 0.186862E+10 | 0.65 | 1520.33 | 01-JUN-08:20 | 1.13 |
July | 0.196901E+10 | 0.67 | 1520.33 | 01-JUL-07:50 | 1.12 |
August | 0.208914E+10 | 0.69 | 1520.33 | 02-AUG-06:40 | 1.13 |
September | 0.186739E+10 | 0.62 | 1520.33 | 01-SEP-16:30 | 1.13 |
October | 0.162174E+10 | 0.48 | 1520.33 | 02-OCT-11:40 | 1.13 |
November | 0.147208E+10 | 0.45 | 1520.33 | 04-NOV-10:40 | 1.14 |
December | 0.155432E+10 | 0.48 | 1520.33 | 01-DEC-07:50 | 1.14 |
Annual Sum or Average | 0.202863E+11 | 0.54 | |||
Minimum of Months | 0.143822E+10 | 0.45 | 1520.33 | 1.12 | |
Maximum of Months | 0.208914E+10 | 0.69 | 1520.33 | 1.14 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.444552E+10 | 0.90 | 3584.53 | 05-JAN-07:10 | 1.09 |
February | 0.392567E+10 | 0.84 | 3584.53 | 01-FEB-16:40 | 1.09 |
March | 0.409283E+10 | 0.66 | 3584.53 | 01-MAR-07:20 | 1.09 |
April | 0.356285E+10 | 0.43 | 3584.53 | 27-APR-11:40 | 1.09 |
May | 0.372576E+10 | 0.44 | 3584.53 | 10-MAY-15:20 | 1.10 |
June | 0.395046E+10 | 0.53 | 3584.53 | 06-JUN-15:40 | 1.08 |
July | 0.401128E+10 | 0.55 | 3584.53 | 18-JUL-08:65 | 1.08 |
August | 0.414586E+10 | 0.54 | 3584.53 | 12-AUG-09:55 | 1.08 |
September | 0.364167E+10 | 0.44 | 3584.53 | 06-SEP-11:30 | 1.08 |
October | 0.357898E+10 | 0.42 | 3584.53 | 02-OCT-15:50 | 1.08 |
November | 0.371169E+10 | 0.68 | 3584.53 | 10-NOV-07:05 | 1.09 |
December | 0.440545E+10 | 0.91 | 3584.53 | 21-DEC-17:10 | 1.09 |
Annual Sum or Average | 0.471980E+11 | 0.61 | |||
Minimum of Months | 0.356285E+10 | 0.42 | 3584.53 | 1.08 | |
Maximum of Months | 0.444552E+10 | 0.91 | 3584.53 | 1.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.02 | 0.05 |
February | 1.43 | 0.05 |
March | 0.67 | 0.80 |
April | 2.76 | 0.89 |
May | 8.67 | 0.47 |
June | 14.55 | 0.07 |
July | 18.78 | 0.11 |
August | 23.41 | 0.05 |
September | 14.97 | 0.03 |
October | 6.53 | 0.42 |
November | 1.88 | 1.47 |
December | 2.33 | 0.06 |
Annual Sum or Average | 99.00 | 0.18 |
Minimum of Months | 0.67 | 0.03 |
Maximum of Months | 23.41 | 1.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.14 | 0.00 |
February | 0.25 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 1.28 | 0.00 |
June | 1.38 | 0.00 |
July | 2.75 | 0.00 |
August | 2.65 | 0.00 |
September | 3.03 | 0.00 |
October | 0.39 | 0.00 |
November | 0.00 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 12.01 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.03 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 3.33 | 0.00 |
July | 7.39 | 0.00 |
August | 6.88 | 0.00 |
September | 1.46 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 19.06 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.39 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156736E+10 | 0.689374E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143908E+10 | 0.541079E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166630E+10 | 0.307761E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183499E+10 | 0.686624E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.256616E+10 | 0.103694E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.450969E+10 | 3057396.81 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.564044E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.549216E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.372425E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.220128E+10 | 0.661564E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147209E+10 | 0.258069E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155432E+10 | 0.678137E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336681E+11 | 0.261991E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143908E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.564044E+10 | 0.689374E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.444552E+10 | 0.329694E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.392567E+10 | 0.236480E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.409283E+10 | 0.904600E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361227E+10 | 0.447325E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.481687E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100230E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.130320E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114797E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.677010E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.416697E+10 | 0.527678E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.371169E+10 | 0.101379E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.440545E+10 | 0.311120E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.744820E+11 | 0.107888E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.361227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130320E+11 | 0.329694E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156736E+10 | 0.00 | 0.474400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143822E+10 | 3108473.28 | 0.371578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166255E+10 | 13599272.10 | 0.211078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152925E+10 | 0.114218E+10 | 0.465673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164659E+10 | 0.338603E+10 | 69511681.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186862E+10 | 0.908933E+10 | 2015347.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196901E+10 | 0.130317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208914E+10 | 0.123815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186739E+10 | 0.688812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162174E+10 | 0.218702E+10 | 0.448454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147208E+10 | 3562.62 | 0.176342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155432E+10 | 0.00 | 0.466220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202863E+11 | 0.481226E+11 | 0.179818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208914E+10 | 0.130317E+11 | 0.474400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.444552E+10 | 0.00 | 0.227243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392567E+10 | 0.00 | 0.162702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409283E+10 | 0.00 | 0.610041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356285E+10 | 0.165514E+09 | 0.300205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372576E+10 | 0.363399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395046E+10 | 0.187738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.401128E+10 | 0.287120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414586E+10 | 0.239916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364167E+10 | 0.105109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357898E+10 | 0.199716E+10 | 0.348095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371169E+10 | 0.00 | 0.684311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440545E+10 | 0.00 | 0.213633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471980E+11 | 0.877850E+11 | 0.739497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.356285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.444552E+10 | 0.287120E+11 | 0.227243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143822E+10 | 0.00 | 0.00 | 0.00 | 860924.41 | 0.00 | 0.541079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166255E+10 | 0.00 | 0.00 | 0.00 | 3744726.01 | 0.00 | 0.307761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152925E+10 | 0.00 | 0.00 | 0.00 | 0.305743E+09 | 0.00 | 0.686624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164659E+10 | 0.00 | 0.00 | 0.00 | 0.919565E+09 | 0.00 | 0.103694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186862E+10 | 0.00 | 0.00 | 0.00 | 0.264107E+10 | 0.00 | 3057396.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196901E+10 | 0.00 | 0.00 | 0.00 | 0.367143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208914E+10 | 0.00 | 0.00 | 0.00 | 0.340302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186739E+10 | 0.00 | 0.00 | 0.00 | 0.185686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162174E+10 | 0.00 | 0.00 | 0.00 | 0.579539E+09 | 0.00 | 0.661564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147208E+10 | 0.00 | 0.00 | 0.00 | 992.41 | 0.00 | 0.258069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202863E+11 | 0.00 | 0.00 | 0.00 | 0.133818E+11 | 0.00 | 0.261991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208914E+10 | 0.00 | 0.00 | 0.00 | 0.367143E+10 | 0.00 | 0.689374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.444552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356285E+10 | 0.00 | 0.00 | 0.00 | 49422273.51 | 0.00 | 0.447325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372576E+10 | 0.00 | 0.00 | 0.00 | 0.109111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395046E+10 | 0.00 | 0.00 | 0.00 | 0.607256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.401128E+10 | 0.00 | 0.00 | 0.00 | 0.902068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414586E+10 | 0.00 | 0.00 | 0.00 | 0.733380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364167E+10 | 0.00 | 0.00 | 0.00 | 0.312842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357898E+10 | 0.00 | 0.00 | 0.00 | 0.587993E+09 | 0.00 | 0.527678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471980E+11 | 0.00 | 0.00 | 0.00 | 0.272840E+11 | 0.00 | 0.107888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.356285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.444552E+10 | 0.00 | 0.00 | 0.00 | 0.902068E+10 | 0.00 | 0.329694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142652E+10 | 0.00 | 0.00 | 0.14 |
February | 0.261135E+09 | 0.00 | 0.00 | 23499.18 | 0.00 | 0.117943E+10 | 55741850.27 | 0.00 | 0.17 |
March | 0.556395E+09 | 0.00 | 0.00 | 61386.60 | 0.00 | 0.650321E+09 | 0.165571E+09 | 0.00 | 0.20 |
April | 0.439830E+09 | 5000125.38 | 0.00 | 1822321.39 | 0.00 | 95252996.53 | 0.114327E+10 | 0.00 | 0.45 |
May | 0.170255E+09 | 42458934.16 | 0.00 | 4653851.36 | 0.00 | 10293729.45 | 0.185494E+10 | 0.00 | 0.63 |
June | 22077853.00 | 0.387405E+09 | 0.00 | 5708556.84 | 0.00 | 0.00 | 0.133245E+10 | 0.00 | 0.65 |
July | 1067377.84 | 0.104608E+10 | 0.00 | 4774274.96 | 1688007.59 | 0.00 | 0.446261E+09 | 0.00 | 0.63 |
August | 15354960.94 | 0.777182E+09 | 0.00 | 6371618.81 | 980419.65 | 0.00 | 0.982097E+09 | 0.00 | 0.78 |
September | 22085578.75 | 0.158209E+09 | 0.00 | 8631624.11 | 0.00 | 0.00 | 0.215142E+10 | 0.00 | 0.85 |
October | 0.327732E+09 | 21290894.92 | 0.00 | 4400388.74 | 0.00 | 0.143457E+09 | 0.186674E+10 | 0.00 | 0.58 |
November | 0.726705E+09 | 0.00 | 0.00 | 60327.40 | 0.00 | 0.584825E+09 | 0.104440E+09 | 0.00 | 0.15 |
December | 0.274156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165719E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.308835E+10 | 0.243763E+10 | 0.00 | 36507849.40 | 2668427.24 | 0.574728E+10 | 0.101029E+11 | 0.00 | 0.45 |
Minimum of Months | 1067377.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.726705E+09 | 0.104608E+10 | 0.00 | 8631624.11 | 1688007.59 | 0.165719E+10 | 0.215142E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125829E+10 | 0.00 | 0.00 | 0.14 |
February | 0.217832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720127E+09 | 0.00 | 0.00 | 0.15 |
March | 0.218062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209232E+09 | 0.00 | 0.00 | 0.16 |
April | 0.203170E+10 | 0.00 | 0.00 | 476642.88 | 1137102.54 | 0.00 | 0.466406E+09 | 0.00 | 0.24 |
May | 0.130915E+10 | 33176824.07 | 0.00 | 5041094.44 | 2374594.52 | 0.00 | 0.208952E+10 | 0.00 | 0.41 |
June | 0.400216E+09 | 0.735531E+09 | 0.00 | 6477650.51 | 0.00 | 0.00 | 0.164944E+10 | 0.00 | 0.40 |
July | 52955614.37 | 0.141521E+10 | 0.00 | 7649756.95 | 0.00 | 0.00 | 0.130491E+10 | 0.00 | 0.42 |
August | 0.144273E+09 | 0.956409E+09 | 0.00 | 11766752.11 | 180030.18 | 0.00 | 0.216285E+10 | 0.00 | 0.52 |
September | 0.405566E+09 | 0.148047E+09 | 0.00 | 13185635.46 | 0.00 | 0.00 | 0.265374E+10 | 0.00 | 0.53 |
October | 0.205434E+10 | 5298829.62 | 0.00 | 4109314.91 | 0.00 | 36816363.13 | 0.115200E+10 | 0.00 | 0.30 |
November | 0.263277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158453E+09 | 0.00 | 0.00 | 0.14 |
December | 0.284717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112464E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.183471E+11 | 0.329368E+10 | 0.00 | 48706847.26 | 3691727.24 | 0.350755E+10 | 0.114789E+11 | 0.00 | 0.30 |
Minimum of Months | 52955614.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.284717E+10 | 0.141521E+10 | 0.00 | 13185635.46 | 2374594.52 | 0.125829E+10 | 0.265374E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |