Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2315.36 | 478.86 | 478.86 |
Net Site Energy | 2315.36 | 478.86 | 478.86 |
Total Source Energy | 4279.71 | 885.13 | 885.13 |
Net Source Energy | 4279.71 | 885.13 | 885.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1465.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 849.67 | 1465.69 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1465.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 59.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.72 | 303.13 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 175.73 | 303.13 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.72 | 303.13 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 175.73 | 303.13 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 849.671 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 849.671 | 100.00 |
Total On-Site and Utility Electric Sources | 849.671 | 100.00 |
Total Electricity End Uses | 849.671 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.00 |
Time Setpoint Not Met During Occupied Cooling | 2.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1996.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUL-14:39 | 07-FEB-08:09 | - | - | - | 12-AUG-11:00 |
Heating | 0.00 | 411179.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15361.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6143.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1766.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 69003.44 | 411179.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 411179.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15361.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3837.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1766.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1588.81 | 0.00 | 0.00 | 0.00 |
Cooling | 56.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2690.91 | 1588.81 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 328.60 | 0.00 | 0.00 | 0.00 |
Cooling | 11.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 556.53 | 328.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 328.60 | 0.00 | 0.00 | 0.00 |
Cooling | 11.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 556.53 | 328.60 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.07 |
ZONE2 FINE STORAGE DIRECT AIR | 2.39 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.50 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.50 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 222624.23 |
PSZ-OFFICE HEATING COIL | 29190.72 |
PSZ-FINE STORAGE HEATING COIL | 82326.60 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 222624.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-FINE STORAGE | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 1.00 | 1.00 | 2.39 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.07 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.39 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 1.07 | 19429.24 | 29190.72 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.39 | 2.39 | 2.39 | 2.39 | 54186.83 | 82326.60 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.07 | 0.534295 | 1.07 | 18933.10 | 19429.24 | 9714.62 | 19429.24 | 0.765724 | 0.765720 | 0.765720 | 0.765720 |
PSZ-FINE STORAGE COOLING COIL | 2.39 | 1.20 | 2.39 | 51778.29 | 54186.83 | 27093.42 | 54186.83 | 0.699802 | 0.699800 | 0.699800 | 0.699800 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.07 | 1218.31 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.39 | 2619.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.72529422E-12 | -0.16659653E-15 | 0.22267608E-14 | 0.12345853E-15 |
13 | 3 | -0.36555712E-03 | 0.52642428E-06 | -0.52844486E-04 | 0.13919492E-12 |
14 | 2 | 1.6938492 | 0.11754276E-01 | 1.1057222 | -0.70081836E-04 |
15 | 1 | -7.1898979 | 0.30855302 | -16.875743 | 0.32460476 |
16 | 0 | 6.0151594 | 0.19843725 | 16.288819 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22267608E-14 | -0.16659653E-15 | 0.72529422E-12 | 0.12345853E-15 |
85 | 3 | -0.52844486E-04 | 0.52642428E-06 | -0.36555712E-03 | 0.13919492E-12 |
86 | 2 | 1.1057222 | 0.11754276E-01 | 1.6938492 | -0.70081836E-04 |
87 | 1 | -16.875743 | 0.30855302 | -7.1898979 | 0.32460476 |
88 | 0 | 16.288819 | 0.19843725 | 6.0151594 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 28 | 1 | VerySmooth | 3.241 | 0.487 | 0.409 | 0.491 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10552.06723 | 12662.48068 | 0.89049 | 1.06859 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33455E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13327.82629 | 15993.39155 | 0.38390 | 0.46068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 30314.72351 | 36377.66821 | 1.99440 | 2.39328 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33455E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 66416.89342 | 79700.27211 | 1.61049 | 1.93259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30000 | 1.33455E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 185520.17254 | 222624.20705 | 4.58022 | 5.49627 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -16.30000 | 9.24091E-004 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15722.94 | 1.06859 | 1.06859 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15600.38 | 0.46068 | 0.46068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 42998.13 | 2.39328 | 2.39328 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 69039.02 | 1.93259 | 1.93259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06859 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.39328 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.49627 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.49627 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 222624.22704 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 222624.20705 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06859 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06859 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06859 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06859 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06859 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.06859 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.39328 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.39328 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.39328 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.39328 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.39328 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.39328 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.06859 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.39328 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06859 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06859 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06859 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06859 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06859 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06859 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53430 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06859 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18933.10083 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19429.24000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9714.62000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19429.24000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76572 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76572 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76572 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76572 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19429.24000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29190.72341 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06859 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1218.31225 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29190.72341 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.39328 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.39328 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.39328 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.39328 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.39328 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.39328 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19664 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.39328 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 51778.29330 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54186.83000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27093.41500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 54186.83000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69980 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69980 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69980 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69980 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54186.83000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 82326.60039 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.39328 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2619.45396 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 82326.60039 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18599.8 | 10.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 52327.4 | 13.56 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2232855307 | 0.1996645681 | Pass | Pass | 1.6331779503 | 7.8998691147 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6664798473 | 0.6482080190 | Pass | Pass | 0.7690598697 | 0.8152682479 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.7663555718E-005 | 7.4911167065E-005 | Pass | Pass | 3.0804942222E-002 | 2.2671129282E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.487 | 0.491 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.487 | 0.491 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.487 | 0.491 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.487 | 0.491 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.529 | 0.531 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.487 | 0.491 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.535 | 0.536 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.67 | 83.67 | 123.40 | |
Exterior Lighting Total | 7857.24 | 123.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19429.24 | 14877.36 | 4551.88 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 54186.83 | 37919.94 | 16266.89 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18599.8 | 10.23 | ||||
PSZ-FINE STORAGE COOLING COIL | 52327.4 | 13.56 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 222624.23 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29190.72 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 82326.60 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.50 | 510.66 | 92.91 | 1.00 | 3.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.07 | 1218.31 | 1140.11 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.39 | 2619.45 | 1094.51 | 1.00 | 1.26 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10552.07 | 12662.48 | 53.46 | 0.890 | 1.069 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00837 | 29.00 | 0.01335 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 30314.72 | 36377.67 | 26.11 | 1.994 | 2.393 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00875 | 30.30 | 0.01335 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00387 | 30.30 | 0.01335 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13327.83 | 15993.39 | 67.52 | 0.384 | 0.461 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00726 | -16.30 | 0.00092 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 66416.89 | 79700.27 | 57.20 | 1.610 | 1.933 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00553 | -16.30 | 0.00092 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 185520.17 | 222624.21 | 69.46 | 4.580 | 5.496 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00782 | -16.30 | 0.00092 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.07 | 1.07 | 0.46 | 0.46 | 1.0686 | 1.0686 | 1.0686 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.39 | 2.39 | 1.93 | 1.93 | 2.3933 | 2.3933 | 2.3933 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 222624.227 | 222624.227 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 222624.23 | 222624.23 | 5.496270 | 6.09 | 6.09 | 0.00679993 | 43.33 | 26.78 | 0.01600000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 9.98 | 0.00782148 | 99.9997 | 222624.21 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19429.240 | 0.000 | 1.068590 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19429.24 | 16698.52 | 1.068590 | 24.47 | 16.64 | 0.00892708 | 12.00 | 11.03 | 0.00800000 | 29.00 | 0.01334551 | 21.43 | 11.2611 | 23.90 | 0.00836637 | 44.1833 | 10552.07 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29190.723 | 29190.723 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29190.72 | 29190.72 | 1.068592 | 11.29 | 8.13 | 0.00560725 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 11.2611 | 21.10 | 0.00726309 | 45.5566 | 13327.83 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 54186.830 | 0.000 | 2.393280 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 54186.83 | 44746.37 | 2.393280 | 27.23 | 17.97 | 0.00942614 | 12.00 | 11.03 | 0.00800000 | 30.30 | 0.01334551 | 21.80 | 14.7884 | 26.70 | 0.00874593 | 39.0806 | 29090.39 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 82326.600 | 82326.600 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82326.60 | 82326.60 | 2.393276 | 9.72 | 6.31 | 0.00469044 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.7884 | 15.54 | 0.00553483 | 49.3232 | 66416.89 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 222624.227 | 222624.227 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1739 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.496270 | 6.45221001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 222624.23 | 222624.23 | 1.0000 | 6.45221001 | 5.496270 | 6.09 | 6.09 | 0.00679993 | 23203.1 | 43.33 | 26.78 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 222624.23 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 9.98 | 0.00782148 | 9.98 | 0.00782148 | 99.9997 | 222624.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19429.240 | 0.000 | 1.068590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4350 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19429.24 | 16698.52 | 1.0000 | 1.25444485 | 1.068590 | 24.47 | 16.64 | 0.00892708 | 47323.8 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19429.24 | 29.00 | 0.01334551 | 21.43 | 0.12033533 | 11.2611 | 23.90 | 0.00836637 | 23.90 | 0.00836637 | 44.1833 | 10552.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29190.723 | 29190.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.068592 | 1.25444714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29190.72 | 29190.72 | 1.0000 | 1.25444714 | 1.068592 | 11.29 | 8.13 | 0.00560725 | 25488.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29190.72 | -16.30 | 0.00092409 | -16.30 | 0.12033533 | 11.2611 | 21.05 | 0.00726309 | 21.10 | 0.00726309 | 45.5566 | 13327.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54186.830 | 0.000 | 2.393280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3627 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 54186.83 | 44746.37 | 1.0000 | 2.80953197 | 2.393280 | 27.23 | 17.97 | 0.00942614 | 51413.5 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54186.83 | 30.30 | 0.01334551 | 21.80 | 0.35392745 | 14.7884 | 26.70 | 0.00874593 | 26.70 | 0.00874593 | 39.0806 | 29090.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82326.600 | 82326.600 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.393276 | 2.80952752 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82326.60 | 82326.60 | 1.0000 | 2.80952752 | 2.393276 | 9.72 | 6.31 | 0.00469044 | 21578.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82326.60 | -16.30 | 0.00092409 | -16.30 | 0.35392745 | 14.7884 | 15.55 | 0.00553483 | 15.54 | 0.00553483 | 49.3232 | 66416.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.39 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2611.83 | 2741.50 | 1996.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2611.83 | 2741.50 | 1996.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 140.00 | 65.67 | 66.00 | 2.50 |
ZONE2 FINE STORAGE | 616.00 | 9.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 711.50 | 73.00 | 66.00 | 2.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.406 | 0.434 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
Electricity:Building | 621.97 | 4992.32 | 01-JAN-00:10 | 48037.94 | 27-JUN-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 422.37 | 2759.73 | 01-JAN-00:10 | 33963.13 | 27-JUN-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.04 | 483.00 | 04-JAN-06:40 | 2760.69 | 13-FEB-12:50 |
WaterSystems:Electricity | 27.04 | 483.00 | 04-JAN-06:40 | 2760.69 | 13-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 27.04 | 483.00 | 04-JAN-06:40 | 2760.69 | 13-FEB-12:50 |
Fans:Electricity | 60.28 | 0.00 | 11-JAN-18:40 | 6143.06 | 20-JUL-14:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity | 0.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
ElectricityPurchased:Facility | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
ElectricityPurchased:Plant | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
Cogeneration:ElectricityPurchased | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
ElectricityNet:Plant | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
Cogeneration:ElectricityNet | 849.67 | 5475.32 | 12-MAR-09:20 | 69003.44 | 19-JUL-14:40 |
Electricity:HVAC | 77.26 | 0.00 | 11-JAN-18:40 | 20142.46 | 19-JUL-15:10 |
General:Fans:Electricity | 59.55 | 0.00 | 11-JAN-18:40 | 4348.43 | 02-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 17.71 | 0.00 | 01-JAN-00:10 | 16304.69 | 19-JUL-15:10 |
ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-08:00 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1465.69 | 5000.00 | 11-JAN-18:40 | 411179.17 | 07-FEB-08:10 |
Gas:HVAC | 1465.69 | 5000.00 | 11-JAN-18:40 | 411179.17 | 07-FEB-08:10 |
Heating:Gas | 1465.69 | 5000.00 | 11-JAN-18:40 | 411179.17 | 07-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-AUG-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2113.03 | 0.00 | 11-JAN-18:40 | 637736.06 | 13-FEB-06:10 |
EnergyTransfer:Building | 1041.64 | 0.00 | 11-JAN-18:40 | 318399.62 | 13-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 71.78 | 0.00 | 01-JAN-00:40 | 26134.52 | 13-FEB-07:10 |
Heating:EnergyTransfer | 994.72 | 0.00 | 11-JAN-18:40 | 318399.62 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 50.44 | 0.00 | 01-JAN-00:40 | 26134.52 | 13-FEB-07:10 |
Cooling:EnergyTransfer | 46.92 | 0.00 | 01-JAN-00:10 | 35689.46 | 19-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 21.34 | 0.00 | 01-JAN-00:10 | 9194.29 | 17-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 299.35 | 0.00 | 01-JAN-00:40 | 85413.91 | 13-FEB-07:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 273.78 | 0.00 | 01-JAN-00:40 | 85413.91 | 13-FEB-07:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.57 | 0.00 | 01-JAN-00:10 | 27278.39 | 19-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 670.51 | 0.00 | 06-JAN-10:50 | 223826.04 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 670.51 | 0.00 | 06-JAN-10:50 | 223826.04 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1071.39 | 0.00 | 11-JAN-18:40 | 324897.45 | 07-FEB-08:10 |
HeatingCoils:EnergyTransfer | 1007.60 | 0.00 | 11-JAN-18:40 | 324897.45 | 07-FEB-08:10 |
CoolingCoils:EnergyTransfer | 63.79 | 0.00 | 01-JAN-00:10 | 57287.33 | 19-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 50.435 | -21.342 | 0.000 | 0.000 | 3.960 | 30.994 | 31.946 | 11.354 | 0.000 | 0.497 | 0.000 | 0.000 | -11.384 | 0.000 | -34.073 | -62.387 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 273.780 | -25.573 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.926 | 0.002 | 0.000 | 0.000 | 0.000 | -232.916 | -152.873 |
ZONE3 BULK STORAGE | 670.505 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 29.807 | 0.000 | 8.515 | 0.000 | 0.000 | -21.370 | 0.000 | -812.330 | -296.773 |
Total Facility | 670.505 | 0.000 | 324.214 | -46.915 | 0.000 | 0.000 | 3.960 | 481.960 | 139.282 | 41.161 | 0.000 | 9.939 | 0.002 | 0.000 | -32.755 | 0.000 | -1079.319 | -512.034 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-AUG-18:23 | 0.00 | 0.00 | 0.00 | -17548.02 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 1141.02 | 0.00 | 0.00 | 15422.34 | 0.00 | -0.00 | 0.00 | -48.04 | 0.00 |
ZONE2 FINE STORAGE | 17-AUG-17:10 | 0.00 | 0.00 | 0.00 | -44727.89 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 57.07 | 43470.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-17:08 | 0.00 | 0.00 | 0.00 | -58580.97 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5721.10 | 0.00 | 1003.79 | 50297.75 | 0.00 | 0.00 | 0.00 | -5484.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-NOV-06:01 | 0.00 | 0.00 | 29452.92 | 0.00 | 0.00 | 0.00 | 53.68 | 586.44 | 573.75 | 15.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -49.24 | -30633.04 |
ZONE2 FINE STORAGE | 21-FEB-06:01 | 0.00 | 0.00 | 90145.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -35506.89 | -55838.07 |
ZONE3 BULK STORAGE | 06-FEB-10:00 | 223827.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1314.41 | 0.00 | -210778.02 | -43393.05 |
Total Facility | 13-FEB-06:01 | 210709.99 | 0.00 | 115834.29 | 0.00 | 0.00 | 0.00 | 58.01 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3274.29 | 0.00 | -208863.10 | -121634.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0686 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0686 | 0.1126 | 1.0000 | 0.1203 | 0.1126 | ||
PSZ-FINE STORAGE | 2.3933 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.3933 | 0.1479 | 1.0000 | 0.3539 | 0.1479 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0686 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0686 | 1.0000 | 1.0000 | 0.1203 | 0.1126 | ||
PSZ-FINE STORAGE | 2.3933 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.3933 | 1.0000 | 1.0000 | 0.3539 | 0.1479 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0686 | 1.0686 | 1.0686 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3933 | 2.3933 | 2.3933 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0686 | 1.0686 | 1.0686 | 1.0686 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.3933 | 2.3933 | 2.3933 | 2.3933 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0686 | 1.0686 | 1.0686 | 0.1203 | 0.2612 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3933 | 2.3933 | 2.3933 | 0.3539 | 0.1831 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0686 | 1.0686 | 1.0686 | 1.0686 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.3933 | 2.3933 | 2.3933 | 2.3933 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.00 |
Number of hours cooling loads not met | 2.50 |
Number of hours not met | 68.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1465.69 | 411179.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 17.71 | 16304.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.40 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.72 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 59.55 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.04 | 2760.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 849.67 |
Natural Gas | 0.00 | 1465.69 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2315.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 3.66 |
Fans (All) | 12.47 |
Service Water Heating | 5.59 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 175.73 |
Subtotal | 175.73 |
Natural Gas [MJ/m2] | |
Space Heating | 303.13 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 303.13 |
Subtotal | 303.13 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.82 |
Space Heating | 63.30 |
Space Cooling | 0.76 |
Fans (All) | 2.60 |
Service Water Heating | 1.17 |
Receptacle Equipment | 6.02 |
Miscellaneous | 5.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.362892E+12 |
February | 0.000 | 0.365269E+12 |
March | 0.000 | 0.165674E+12 |
April | 0.000 | 0.528937E+11 |
May | 0.000 | 0.152413E+11 |
June | 0.000 | 0.130335E+11 |
July | 0.000 | 0.133920E+11 |
August | 0.000 | 0.133921E+11 |
September | 0.000 | 0.131032E+11 |
October | 0.000 | 0.251452E+11 |
November | 0.000 | 0.811473E+11 |
December | 0.000 | 0.344504E+12 |
Annual Sum or Average | 0.146569E+13 | |
Minimum of Months | 0.000 | 0.130335E+11 |
Maximum of Months | 0.000 | 0.365269E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.194909E+09 | 236.59 | 14-JAN-08:09 | 3.40 | 2.64 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.6 | 0.179232E+09 | 236.59 | 09-FEB-11:09 | -2.7 | -3.2 |
March | 25562720.03 | 1394.43 | 15-MAR-15:10 | 25.50 | 16.17 | 0.214351E+09 | 301.59 | 16-MAR-15:30 | 17.50 | 14.96 |
April | 15515809.52 | 494.72 | 29-APR-15:05 | 9.40 | 8.17 | 0.200206E+09 | 301.59 | 08-APR-15:39 | 18.33 | 12.82 |
May | 0.554438E+09 | 7046.26 | 27-MAY-18:00 | 18.90 | 10.28 | 0.235305E+09 | 301.60 | 31-MAY-15:00 | 22.20 | 14.45 |
June | 0.407505E+10 | 17298.93 | 24-JUN-17:43 | 23.30 | 14.82 | 0.256586E+09 | 301.61 | 22-JUN-12:00 | 20.60 | 15.48 |
July | 0.698101E+10 | 17351.42 | 06-JUL-18:23 | 22.20 | 13.24 | 0.248710E+09 | 301.61 | 12-JUL-15:20 | 22.03 | 15.82 |
August | 0.669018E+10 | 17548.08 | 01-AUG-18:23 | 22.75 | 14.23 | 0.268323E+09 | 301.61 | 19-AUG-15:00 | 22.80 | 16.32 |
September | 0.280144E+10 | 14704.52 | 18-SEP-00:03 | 14.50 | 11.50 | 0.244697E+09 | 301.60 | 21-SEP-15:00 | 26.10 | 17.16 |
October | 0.193346E+09 | 2034.56 | 11-OCT-16:00 | 21.70 | 14.50 | 0.208337E+09 | 301.59 | 05-OCT-15:00 | 18.90 | 12.93 |
November | 6252304.03 | 389.62 | 03-NOV-15:00 | 10.00 | 5.46 | 0.188207E+09 | 276.38 | 04-NOV-15:20 | 18.30 | 13.64 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.06 | 0.194895E+09 | 236.59 | 12-DEC-16:00 | -0.6 | -0.8 |
Annual Sum or Average | 0.213428E+11 | 0.263376E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.6 | 0.179232E+09 | 236.59 | -2.7 | -3.2 | ||
Maximum of Months | 0.698101E+10 | 17548.08 | 25.50 | 16.17 | 0.268323E+09 | 301.61 | 26.10 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 8909287.06 | 2375.53 | 18-FEB-15:20 | 2.60 | 0.37 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.273710E+09 | 2181.20 | 21-MAR-13:30 | 4.70 | 1.48 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.438016E+09 | 2722.89 | 17-APR-11:10 | 2.88 | 0.05 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.324742E+09 | 6710.86 | 05-MAY-06:10 | 10.10 | 5.75 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.360124E+10 | 34148.25 | 27-JUN-17:10 | 26.52 | 22.65 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.104502E+11 | 42850.69 | 14-JUL-17:10 | 27.80 | 17.34 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.853902E+10 | 44726.88 | 17-AUG-17:10 | 26.83 | 16.53 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.107443E+10 | 12555.16 | 16-SEP-13:40 | 27.20 | 19.69 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.577687E+09 | 2859.00 | 24-OCT-10:00 | 3.30 | 0.73 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.249823E+09 | 2498.38 | 24-NOV-11:50 | 3.43 | 0.68 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 36205849.65 | 2715.87 | 16-DEC-12:00 | 4.40 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.255740E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.104502E+11 | 44726.88 | 27.80 | 22.65 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.6 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -4.9 | -6.8 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.00 | 0.00 | 01-APR-00:03 | 4.10 | 3.71 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.06 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.8 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113959E+11 | 28373.43 | 20-JAN-06:31 | -0.9 |
February | 0.107150E+11 | 28561.40 | 13-FEB-06:31 | -9.4 |
March | 0.721064E+10 | 28898.89 | 02-MAR-06:31 | 1.10 |
April | 0.367548E+10 | 28652.43 | 07-APR-05:01 | 10.60 |
May | 0.917331E+09 | 28233.76 | 05-MAY-05:01 | 10.50 |
June | 59291671.69 | 5424.53 | 15-JUN-06:03 | 9.97 |
July | 6331757.17 | 1079.11 | 29-JUL-06:05 | 20.68 |
August | 8673651.37 | 851.55 | 07-AUG-06:10 | 20.68 |
September | 99183271.20 | 27144.72 | 30-SEP-05:02 | 7.20 |
October | 0.190290E+10 | 28719.88 | 26-OCT-05:01 | 15.50 |
November | 0.439206E+10 | 29452.53 | 27-NOV-06:01 | 18.30 |
December | 0.100524E+11 | 28560.47 | 01-DEC-06:01 | 10.10 |
Annual Sum or Average | 0.504352E+11 | |||
Minimum of Months | 6331757.17 | 851.55 | -9.4 | |
Maximum of Months | 0.113959E+11 | 29452.53 | 20.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.657902E+11 | 89798.01 | 12-JAN-06:01 | -7.4 |
February | 0.657276E+11 | 90144.78 | 21-FEB-06:01 | -13.4 |
March | 0.338138E+11 | 85733.51 | 26-MAR-09:42 | -1.1 |
April | 0.139492E+11 | 85610.90 | 16-APR-09:02 | -3.3 |
May | 0.964932E+09 | 64121.56 | 02-MAY-05:06 | 7.30 |
June | 0.316542E+09 | 2690.08 | 03-JUN-07:00 | 11.70 |
July | 0.156223E+09 | 2498.48 | 15-JUL-07:00 | 22.80 |
August | 0.217217E+09 | 2708.60 | 24-AUG-07:00 | 15.00 |
September | 0.396421E+09 | 2765.83 | 28-SEP-07:00 | 12.20 |
October | 0.623751E+10 | 84664.94 | 30-OCT-05:32 | -0.4 |
November | 0.221383E+11 | 84388.69 | 24-NOV-04:02 | -3.2 |
December | 0.640722E+11 | 89792.29 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.273780E+12 | |||
Minimum of Months | 0.156223E+09 | 2498.48 | -13.4 | |
Maximum of Months | 0.657902E+11 | 90144.78 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189238E+12 | 223602.27 | 12-JAN-09:00 | -11.1 |
February | 0.194456E+12 | 223826.04 | 06-FEB-10:00 | -15.0 |
March | 0.731206E+11 | 123735.26 | 05-MAR-01:00 | -7.2 |
April | 0.113529E+11 | 85253.09 | 16-APR-06:51 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.152849E+09 | 19775.75 | 30-OCT-04:56 | 0.00 |
November | 0.232949E+11 | 52830.67 | 25-NOV-07:00 | -1.7 |
December | 0.178891E+12 | 200385.69 | 09-DEC-17:00 | -7.2 |
Annual Sum or Average | 0.670507E+12 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.194456E+12 | 223826.04 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578222E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568026E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6050048.17 | 0.403807E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269367E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3489700.64 | 0.163868E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84513625.98 | 0.102435E+10 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226425E+09 | 0.455977E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165821E+09 | 0.693114E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10559614.29 | 0.113781E+10 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377506.42 | 0.221475E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98400.87 | 0.315319E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556119E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.497335E+09 | 0.340733E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455977E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226425E+09 | 0.578222E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403859E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433740E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64314398.16 | 0.248491E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162628E+11 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31385615.87 | 0.886371E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105902E+09 | 0.835632E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349086E+09 | 0.538931E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276997E+09 | 0.630757E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2059595.83 | 0.782531E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33125290.38 | 0.112188E+11 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63533443.21 | 0.181633E+11 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419197E+11 |
Annual Sum or Average | 0.136656E+12 | 0.926404E+09 | 0.232916E+12 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538931E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349086E+09 | 0.433740E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164457.47 | 0.101072E+12 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78315250.10 | 0.111719E+12 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171057E+10 | 0.575163E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681256E+09 | 0.322931E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399237E+09 | 0.247057E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177153E+09 | 0.294575E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2012531.29 | 0.261071E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2030413.97 | 0.281691E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262548E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973752E+09 | 0.278202E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220649E+10 | 0.328994E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138918E+09 | 0.102420E+12 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.637689E+10 | 0.600434E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247057E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220649E+10 | 0.111719E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 16124.51 | 12-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 18009.60 | 06-FEB-17:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 401.67 | 15-MAR-16:10 | 14606.58 | 07-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 10162.02 | 17-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.38 | 10-MAY-15:10 | 6829.92 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213.97 | 27-JUN-12:00 | 5705.09 | 13-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.16 | 19-JUL-16:10 | 4197.80 | 03-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.62 | 18-AUG-17:00 | 4649.03 | 03-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 771.76 | 15-SEP-12:00 | 5714.90 | 06-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.88 | 22-OCT-12:00 | 9560.41 | 17-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 27-NOV-06:00 | 9732.56 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 16223.79 | 26-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4197.80 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.16 | 18009.60 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 68007.67 | 12-JAN-09:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 63049.40 | 06-FEB-17:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.61 | 14-MAR-15:10 | 33752.27 | 03-MAR-18:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 31671.10 | 04-APR-17:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.84 | 14-MAY-15:00 | 16213.63 | 11-MAY-15:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3990.60 | 12-JUN-15:10 | 19542.90 | 13-JUN-15:03 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105.24 | 15-JUL-15:10 | 10161.86 | 06-JUL-02:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5100.97 | 13-AUG-13:00 | 11449.69 | 30-AUG-17:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.78 | 16-SEP-13:00 | 12909.78 | 29-SEP-15:05 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1735.31 | 22-OCT-12:00 | 17234.86 | 23-OCT-15:05 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2765.37 | 27-NOV-06:01 | 32172.33 | 17-NOV-09:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63710.79 | 09-DEC-17:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10161.86 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105.24 | 68007.67 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2650.21 | 11-JAN-16:00 | 170352.96 | 12-JAN-09:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8501.29 | 22-FEB-18:40 | 169057.97 | 07-FEB-11:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29413.71 | 14-MAR-14:00 | 79120.74 | 01-MAR-15:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14532.21 | 07-APR-14:00 | 58082.04 | 16-APR-06:52 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14989.65 | 14-MAY-15:00 | 40216.82 | 11-MAY-15:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6608.48 | 17-JUN-16:00 | 54764.94 | 13-JUN-12:05 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2004.54 | 15-JUL-13:55 | 34667.73 | 06-JUL-02:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.07 | 13-AUG-12:43 | 35077.35 | 30-AUG-15:55 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 37100.77 | 28-SEP-14:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15103.65 | 22-OCT-12:00 | 41190.21 | 23-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21341.97 | 27-NOV-06:01 | 49297.08 | 17-NOV-09:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14126.17 | 01-DEC-11:00 | 151209.96 | 09-DEC-15:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34667.73 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 29413.71 | 170352.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.85 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.42 |
March | 1394.43 | 15-MAR-15:10 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 | 0.00 |
April | 494.72 | 29-APR-15:05 | 1318.50 | 3926.62 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.34 |
May | 7046.26 | 27-MAY-18:00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.56 |
June | 17298.93 | 24-JUN-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
July | 17351.42 | 06-JUL-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.13 |
August | 17548.08 | 01-AUG-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
September | 14704.52 | 18-SEP-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.90 |
October | 2034.56 | 11-OCT-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 |
November | 389.62 | 03-NOV-15:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.80 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17548.08 | 1318.50 | 3926.62 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 | 808.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10740.62 |
February | 2375.53 | 18-FEB-15:20 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6841.35 |
March | 2181.20 | 21-MAR-13:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6422.26 |
April | 2722.89 | 17-APR-11:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5271.27 |
May | 6710.86 | 05-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2577.82 |
June | 34148.25 | 27-JUN-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.78 |
July | 42850.69 | 14-JUL-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.18 | 0.00 |
August | 44726.88 | 17-AUG-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 0.00 |
September | 12555.16 | 16-SEP-13:40 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.63 | 0.00 |
October | 2859.00 | 24-OCT-10:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.18 |
November | 2498.38 | 24-NOV-11:50 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.80 |
December | 2715.87 | 16-DEC-12:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44726.88 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.18 | 10740.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 16558.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21341.69 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28661.91 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25260.58 |
April | 0.00 | 01-APR-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6853.77 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4180.95 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.71 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14086.52 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9959.44 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12696.25 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8088.79 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11154.45 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 11038.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13164.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4180.95 | |
Maximum of Months | 0.00 | 0.00 | 16558.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28661.91 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.738173E+11 | 55607.03 | 13-JAN-16:00 | 0.362892E+12 | 405897.85 | 12-JAN-08:00 |
February | 0.666815E+11 | 52365.00 | 13-FEB-15:00 | 0.365269E+12 | 411179.17 | 07-FEB-08:09 |
March | 0.737765E+11 | 52643.77 | 15-MAR-14:50 | 0.165674E+12 | 230248.64 | 06-MAR-06:19 |
April | 0.671272E+11 | 52211.65 | 04-APR-14:00 | 0.528937E+11 | 178818.65 | 16-APR-03:49 |
May | 0.680160E+11 | 52706.51 | 10-MAY-14:00 | 0.152413E+11 | 39838.76 | 01-MAY-05:10 |
June | 0.695112E+11 | 67080.01 | 27-JUN-12:00 | 0.130335E+11 | 12797.61 | 14-JUN-06:19 |
July | 0.736338E+11 | 69003.44 | 19-JUL-14:39 | 0.133920E+11 | 5000.00 | 01-JUL-00:10 |
August | 0.763888E+11 | 65884.98 | 10-AUG-14:20 | 0.133921E+11 | 5227.68 | 31-AUG-06:00 |
September | 0.683747E+11 | 59593.40 | 16-SEP-13:39 | 0.131032E+11 | 12645.70 | 29-SEP-06:19 |
October | 0.693763E+11 | 52087.84 | 11-OCT-14:00 | 0.251452E+11 | 91922.28 | 30-OCT-05:10 |
November | 0.689622E+11 | 55600.20 | 30-NOV-16:49 | 0.811473E+11 | 136000.90 | 25-NOV-06:10 |
December | 0.740050E+11 | 55605.23 | 29-DEC-16:49 | 0.344504E+12 | 370282.72 | 09-DEC-16:00 |
Annual Sum or Average | 0.849671E+12 | 0.146569E+13 | ||||
Minimum of Months | 0.666815E+11 | 52087.84 | 0.130335E+11 | 5000.00 | ||
Maximum of Months | 0.763888E+11 | 69003.44 | 0.365269E+12 | 411179.17 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.129597E+11 | 0.115358E+11 | 0.00 | 0.684503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237339E+10 | 0.00 |
February | 0.366966E+11 | 0.108147E+11 | 0.105871E+11 | 0.00 | 0.641249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217059E+10 | 0.00 |
March | 0.423649E+11 | 0.107440E+11 | 0.123357E+11 | 0.00 | 0.587593E+10 | 0.00 | 0.00 | 16008820.67 | 0.00 | 0.00 | 0.00 | 0.244006E+10 | 0.00 |
April | 0.397216E+11 | 0.915526E+10 | 0.114862E+11 | 0.00 | 0.447745E+10 | 0.00 | 0.00 | 1878233.80 | 0.00 | 0.00 | 0.00 | 0.228484E+10 | 0.00 |
May | 0.412341E+11 | 0.836796E+10 | 0.119357E+11 | 0.00 | 0.397914E+10 | 0.00 | 0.00 | 0.194149E+09 | 0.00 | 0.00 | 0.00 | 0.230494E+10 | 0.00 |
June | 0.408524E+11 | 0.757124E+10 | 0.118862E+11 | 0.00 | 0.405519E+10 | 0.00 | 0.00 | 0.295304E+10 | 0.00 | 0.00 | 0.00 | 0.219325E+10 | 0.00 |
July | 0.401034E+11 | 0.803324E+10 | 0.115358E+11 | 0.00 | 0.449023E+10 | 0.00 | 0.00 | 0.730030E+10 | 0.00 | 0.00 | 0.00 | 0.217093E+10 | 0.00 |
August | 0.423649E+11 | 0.897140E+10 | 0.123357E+11 | 0.00 | 0.463794E+10 | 0.00 | 0.00 | 0.586656E+10 | 0.00 | 0.00 | 0.00 | 0.221231E+10 | 0.00 |
September | 0.397216E+11 | 0.986241E+10 | 0.114862E+11 | 0.00 | 0.383029E+10 | 0.00 | 0.00 | 0.134715E+10 | 0.00 | 0.00 | 0.00 | 0.212699E+10 | 0.00 |
October | 0.401034E+11 | 0.114653E+11 | 0.115358E+11 | 0.00 | 0.401603E+10 | 0.00 | 0.00 | 29960152.15 | 0.00 | 0.00 | 0.00 | 0.222592E+10 | 0.00 |
November | 0.385909E+11 | 0.122007E+11 | 0.110862E+11 | 0.00 | 0.488233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220201E+10 | 0.00 |
December | 0.401034E+11 | 0.132567E+11 | 0.115358E+11 | 0.00 | 0.677395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233518E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123403E+12 | 0.139282E+12 | 0.602760E+11 | 0.00 | 0.177091E+11 | 0.270404E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.757124E+10 | 0.105871E+11 | 0.00 | 0.383029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212699E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.132567E+11 | 0.123357E+11 | 0.00 | 0.684503E+10 | 0.00 | 0.00 | 0.730030E+10 | 0.00 | 0.00 | 0.00 | 0.244006E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.362892E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.365269E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.165674E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.528937E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.152413E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130335E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.133920E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.133921E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.131032E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.251452E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.811473E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.344504E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146569E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.130335E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.365269E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4348.43 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4348.43 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4348.43 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4348.43 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3837.77 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6143.06 | 27-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6143.06 | 20-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6143.06 | 04-AUG-12:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3837.77 | 01-SEP-09:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4348.43 | 30-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4348.43 | 03-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4348.43 | 01-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3837.77 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6143.06 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2747.40 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2760.69 | 13-FEB-12:50 | 0.00 |
March | 856.59 | 15-MAR-14:50 | 0.00 | 0.00 | 0.00 | 2748.60 | 01-MAR-12:00 | 0.00 |
April | 239.94 | 08-APR-14:30 | 0.00 | 0.00 | 0.00 | 2627.41 | 03-APR-11:50 | 0.00 |
May | 1357.76 | 27-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2437.18 | 01-MAY-11:30 | 0.00 |
June | 13428.63 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 2151.82 | 01-JUN-11:00 | 0.00 |
July | 16304.69 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1827.57 | 10-JUL-11:00 | 0.00 |
August | 12631.77 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1800.27 | 01-AUG-11:09 | 0.00 |
September | 8292.37 | 16-SEP-13:39 | 0.00 | 0.00 | 0.00 | 1846.88 | 26-SEP-11:00 | 0.00 |
October | 851.67 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2147.91 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2421.87 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2628.10 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1800.27 | 0.00 | ||
Maximum of Months | 16304.69 | 0.00 | 0.00 | 0.00 | 2760.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55607.03 | 13-JAN-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52365.00 | 13-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52643.77 | 15-MAR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3837.77 | 0.00 | 0.00 | 856.59 | 0.00 |
April | 52211.65 | 04-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52706.51 | 10-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3837.77 | 0.00 | 0.00 | 1328.82 | 0.00 |
June | 67080.01 | 27-JUN-12:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6143.06 | 0.00 | 0.00 | 13428.63 | 0.00 |
July | 69003.44 | 19-JUL-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6143.06 | 0.00 | 0.00 | 15361.70 | 0.00 |
August | 65884.98 | 10-AUG-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6143.06 | 0.00 | 0.00 | 12248.00 | 0.00 |
September | 59593.40 | 16-SEP-13:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3837.77 | 0.00 | 0.00 | 8292.37 | 0.00 |
October | 52087.84 | 11-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3837.77 | 0.00 | 0.00 | 738.49 | 0.00 |
November | 55600.20 | 30-NOV-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55605.23 | 29-DEC-16:49 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 4348.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52087.84 | 31660.41 | 10112.62 | 0.00 | 0.00 | 3837.77 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69003.44 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 6143.06 | 0.00 | 0.00 | 15361.70 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 405897.85 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 411179.17 | 07-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 230248.64 | 06-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 178818.65 | 16-APR-03:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 39838.76 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 12797.61 | 14-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5227.68 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 12645.70 | 29-SEP-06:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 91922.28 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 136000.90 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 370282.72 | 09-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 5000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 411179.17 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 16.28 | 10.00 | 19.02 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40.83 | 16.10 | 12.17 | 19.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.83 | 17.88 | 9.33 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.17 | 19.74 | 8.00 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3.00 | 20.28 | 3.00 | 20.28 | 0.17 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.57 | 0.67 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 24.62 | 1.00 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 24.62 | 0.67 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.53 | 0.17 | 24.67 |
October | 4.83 | 20.11 | 4.83 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.17 | 19.57 | 7.83 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31.00 | 16.39 | 10.83 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.00 | 17.02 | 66.00 | 19.43 | 65.67 | 24.60 | 2.50 | 24.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.83 | 20.28 | 12.17 | 20.28 | 25.17 | 24.62 | 1.00 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.33 | 13.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 129.83 | 13.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86.50 | 14.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50.67 | 14.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.38 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.42 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21.67 | 14.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83.67 | 14.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 122.00 | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 616.00 | 13.93 | 0.00 | 9.17 | 27.39 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.83 | 14.98 | 0.00 | 0.00 | 5.50 | 27.42 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.01 | 276.00 | 21.01 | 276.00 | 21.01 |
March | 324.00 | 21.21 | 293.67 | 21.04 | 293.67 | 21.04 |
April | 300.00 | 21.31 | 262.17 | 21.10 | 262.17 | 21.10 |
May | 310.83 | 22.53 | 89.00 | 21.19 | 89.00 | 21.19 |
June | 130.33 | 23.37 | 110.00 | 23.86 | 5.83 | 23.19 |
July | 19.17 | 23.55 | 244.67 | 23.90 | 4.00 | 23.90 |
August | 32.83 | 23.44 | 221.00 | 23.90 | 1.50 | 23.90 |
September | 160.33 | 23.22 | 55.67 | 23.74 | 4.17 | 21.69 |
October | 300.00 | 21.69 | 181.67 | 21.12 | 181.67 | 21.12 |
November | 288.00 | 21.11 | 278.00 | 21.07 | 278.00 | 21.07 |
December | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
Annual Sum or Average | 2741.50 | 21.61 | 2611.83 | 21.74 | 1996.00 | 21.07 |
Minimum of Months | 19.17 | 21.01 | 55.67 | 21.01 | 1.50 | 21.01 |
Maximum of Months | 324.00 | 23.55 | 300.00 | 23.90 | 300.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 57445876.46 | 16008820.67 | 10.00 | 51583679.05 | 5862197.42 | 0.00 | 0.18 | 15-MAR-14:50 | 0.00 | 01-MAR-00:02 | 3073.75 | 15-MAR-15:10 | 2857.06 | 15-MAR-14:50 | 267.76 | 14-MAR-14:30 | 856.59 | 15-MAR-14:50 | 0.00 | 01-MAR-00:02 |
April | 6781270.57 | 1878233.80 | 3.83 | 6535687.59 | 245582.98 | 0.00 | 0.05 | 08-APR-14:30 | 0.00 | 01-APR-00:03 | 868.06 | 08-APR-14:30 | 826.56 | 08-APR-14:30 | 42.86 | 08-APR-14:50 | 239.94 | 08-APR-14:30 | 0.00 | 01-APR-00:03 |
May | 0.713443E+09 | 0.194149E+09 | 89.83 | 0.669796E+09 | 43647060.90 | 0.00 | 0.49 | 27-MAY-18:00 | 0.00 | 01-MAY-00:10 | 7666.34 | 27-MAY-18:00 | 7666.34 | 27-MAY-18:00 | 834.36 | 10-MAY-15:10 | 2131.94 | 27-MAY-18:00 | 0.00 | 01-MAY-00:10 |
June | 0.587456E+10 | 0.157314E+10 | 319.48 | 0.485506E+10 | 0.101950E+10 | 0.00 | 1.00 | 12-JUN-00:02 | 0.00 | 01-JUN-00:10 | 22283.60 | 19-JUN-00:02 | 19171.94 | 24-JUN-17:43 | 8021.53 | 19-JUN-00:02 | 5231.86 | 27-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.107320E+11 | 0.286871E+10 | 432.76 | 0.843067E+10 | 0.230134E+10 | 0.00 | 1.00 | 03-JUL-00:01 | 0.00 | 01-JUL-00:10 | 23514.62 | 17-JUL-00:01 | 19050.77 | 06-JUL-17:43 | 9279.20 | 17-JUL-00:07 | 5337.40 | 17-JUL-00:01 | 0.00 | 01-JUL-00:10 |
August | 0.947231E+10 | 0.254178E+10 | 428.05 | 0.797550E+10 | 0.149681E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:15 | 24077.48 | 14-AUG-00:01 | 19293.44 | 01-AUG-18:23 | 10625.51 | 14-AUG-00:06 | 5416.35 | 14-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.389813E+10 | 0.104206E+10 | 248.32 | 0.328195E+10 | 0.616180E+09 | 0.00 | 1.00 | 18-SEP-00:03 | 0.00 | 01-SEP-00:10 | 20911.47 | 18-SEP-00:03 | 16279.78 | 16-SEP-17:10 | 5331.21 | 18-SEP-00:03 | 4901.44 | 18-SEP-00:03 | 0.00 | 01-SEP-00:10 |
October | 0.109447E+09 | 29960152.15 | 21.58 | 0.100055E+09 | 9392186.68 | 0.00 | 0.19 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 | 3146.27 | 11-OCT-16:00 | 2943.95 | 11-OCT-16:00 | 516.62 | 12-OCT-15:00 | 851.67 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.308641E+11 | 0.826768E+10 | 1553.85 | 0.253711E+11 | 0.549298E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.107320E+11 | 0.286871E+10 | 432.76 | 0.843067E+10 | 0.230134E+10 | 0.00 | 1.00 | 0.00 | 24077.48 | 19293.44 | 10625.51 | 5416.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.482085E+10 | 0.137990E+10 | 96.54 | 0.363682E+10 | 0.118403E+10 | 0.00 | 1.00 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 | 64200.01 | 27-JUN-17:10 | 38073.98 | 27-JUN-17:10 | 26126.02 | 27-JUN-17:10 | 16011.74 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.155363E+11 | 0.443159E+10 | 228.40 | 0.114034E+11 | 0.413288E+10 | 0.00 | 1.00 | 16-JUL-10:33 | 0.00 | 01-JUL-00:10 | 62445.76 | 16-JUL-10:33 | 47210.17 | 14-JUL-17:10 | 23716.24 | 16-JUL-10:33 | 16135.19 | 16-JUL-10:33 | 0.00 | 01-JUL-00:10 |
August | 0.115137E+11 | 0.332478E+10 | 200.67 | 0.943016E+10 | 0.208357E+10 | 0.00 | 1.00 | 06-AUG-14:43 | 0.00 | 01-AUG-00:10 | 62137.46 | 13-AUG-16:03 | 49140.56 | 17-AUG-17:10 | 23382.69 | 13-AUG-16:03 | 16257.53 | 13-AUG-14:43 | 0.00 | 01-AUG-00:10 |
September | 0.105920E+10 | 0.305096E+09 | 32.33 | 0.822843E+09 | 0.236356E+09 | 0.00 | 0.39 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 | 20250.47 | 16-SEP-13:40 | 15571.86 | 16-SEP-13:40 | 5822.47 | 15-SEP-11:30 | 5855.46 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.329301E+11 | 0.944137E+10 | 557.94 | 0.252932E+11 | 0.763684E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.155363E+11 | 0.443159E+10 | 228.40 | 0.114034E+11 | 0.413288E+10 | 0.00 | 1.00 | 0.00 | 64200.01 | 49140.56 | 26126.02 | 16257.53 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.43 | 15.88 | 51.54 | 14.01 | 222.98 | 0.00 | 0.00 | 744.00 |
February | 109.25 | 28.19 | 81.05 | 37.75 | 207.84 | 0.00 | 0.00 | 672.00 |
March | 171.75 | 73.84 | 97.91 | 123.84 | 134.16 | 0.00 | 0.00 | 744.00 |
April | 208.93 | 85.52 | 123.41 | 181.96 | 89.68 | 0.00 | 0.00 | 720.00 |
May | 246.61 | 111.34 | 135.27 | 245.34 | 62.66 | 0.00 | 0.00 | 744.00 |
June | 297.93 | 140.14 | 157.79 | 318.57 | 52.41 | 0.00 | 0.00 | 720.00 |
July | 266.05 | 116.46 | 149.59 | 299.30 | 39.46 | 0.00 | 0.00 | 744.00 |
August | 240.39 | 101.94 | 138.45 | 265.30 | 51.18 | 0.00 | 0.00 | 744.00 |
September | 189.31 | 81.80 | 107.50 | 187.36 | 76.60 | 0.00 | 0.00 | 720.00 |
October | 122.66 | 43.21 | 79.45 | 96.68 | 96.10 | 0.00 | 0.00 | 744.00 |
November | 72.10 | 20.47 | 51.63 | 38.55 | 125.44 | 0.00 | 0.00 | 720.00 |
December | 62.89 | 13.63 | 49.27 | 13.27 | 213.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 171.56 | 69.57 | 101.99 | 152.44 | 113.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.89 | 13.63 | 49.27 | 13.27 | 39.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 297.93 | 140.14 | 157.79 | 318.57 | 222.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.43 | 15.88 | 51.54 | 14.01 | 222.98 | 0.00 | 0.00 | 744.00 |
February | 109.25 | 28.19 | 81.05 | 37.75 | 207.84 | 0.00 | 0.00 | 672.00 |
March | 171.75 | 73.84 | 97.91 | 123.84 | 134.16 | 0.00 | 0.00 | 744.00 |
April | 208.93 | 85.52 | 123.41 | 181.96 | 89.68 | 0.00 | 0.00 | 720.00 |
May | 246.61 | 111.34 | 135.27 | 245.34 | 62.66 | 0.00 | 0.00 | 744.00 |
June | 297.93 | 140.14 | 157.79 | 318.57 | 52.41 | 0.00 | 0.00 | 720.00 |
July | 266.05 | 116.46 | 149.59 | 299.30 | 39.46 | 0.00 | 0.00 | 744.00 |
August | 240.39 | 101.94 | 138.45 | 265.30 | 51.18 | 0.00 | 0.00 | 744.00 |
September | 189.31 | 81.80 | 107.50 | 187.36 | 76.60 | 0.00 | 0.00 | 720.00 |
October | 122.66 | 43.21 | 79.45 | 96.68 | 96.10 | 0.00 | 0.00 | 744.00 |
November | 72.10 | 20.47 | 51.63 | 38.55 | 125.44 | 0.00 | 0.00 | 720.00 |
December | 62.89 | 13.63 | 49.27 | 13.27 | 213.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 171.56 | 69.57 | 101.99 | 152.44 | 113.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.89 | 13.63 | 49.27 | 13.27 | 39.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 297.93 | 140.14 | 157.79 | 318.57 | 222.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.00 | 0.00 | 25.00 | 0.21 | 139.34 | 0.00 | 0.00 | 744.00 |
February | 38.09 | 0.00 | 38.09 | 1.40 | 129.85 | 0.00 | 0.00 | 672.00 |
March | 46.20 | 0.00 | 46.20 | 13.90 | 85.70 | 0.00 | 0.00 | 744.00 |
April | 58.90 | 0.28 | 58.62 | 30.98 | 53.90 | 0.00 | 0.00 | 720.00 |
May | 68.42 | 2.94 | 65.48 | 48.15 | 35.05 | 0.00 | 0.00 | 744.00 |
June | 82.25 | 6.98 | 75.27 | 68.71 | 28.40 | 0.00 | 0.00 | 720.00 |
July | 76.61 | 5.20 | 71.41 | 74.13 | 21.25 | 0.00 | 0.00 | 744.00 |
August | 66.33 | 1.27 | 65.05 | 61.60 | 29.10 | 0.00 | 0.00 | 744.00 |
September | 50.27 | 0.02 | 50.25 | 36.27 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 37.57 | 0.00 | 37.57 | 17.12 | 57.96 | 0.00 | 0.00 | 744.00 |
November | 25.24 | 0.00 | 25.24 | 5.60 | 75.91 | 0.00 | 0.00 | 720.00 |
December | 23.40 | 0.00 | 23.40 | 0.29 | 130.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 49.91 | 1.40 | 48.51 | 30.04 | 69.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.40 | 0.00 | 23.40 | 0.21 | 21.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.25 | 6.98 | 75.27 | 74.13 | 139.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.00 | 0.00 | 25.00 | 0.21 | 139.34 | 0.00 | 0.00 | 744.00 |
February | 38.09 | 0.00 | 38.09 | 1.40 | 129.85 | 0.00 | 0.00 | 672.00 |
March | 46.20 | 0.00 | 46.20 | 13.89 | 85.70 | 0.00 | 0.00 | 744.00 |
April | 58.90 | 0.28 | 58.62 | 30.98 | 53.90 | 0.00 | 0.00 | 720.00 |
May | 68.41 | 2.94 | 65.48 | 48.15 | 35.05 | 0.00 | 0.00 | 744.00 |
June | 82.25 | 6.98 | 75.27 | 68.71 | 28.40 | 0.00 | 0.00 | 720.00 |
July | 76.61 | 5.20 | 71.40 | 74.13 | 21.25 | 0.00 | 0.00 | 744.00 |
August | 66.33 | 1.27 | 65.05 | 61.60 | 29.10 | 0.00 | 0.00 | 744.00 |
September | 50.27 | 0.02 | 50.25 | 36.27 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 37.56 | 0.00 | 37.56 | 17.12 | 57.96 | 0.00 | 0.00 | 744.00 |
November | 25.24 | 0.00 | 25.24 | 5.59 | 75.91 | 0.00 | 0.00 | 720.00 |
December | 23.40 | 0.00 | 23.40 | 0.29 | 130.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 49.91 | 1.40 | 48.51 | 30.03 | 69.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.40 | 0.00 | 23.40 | 0.21 | 21.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.25 | 6.98 | 75.27 | 74.13 | 139.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.02 | 9.07 | 20.95 | 14.82 | 119.13 | 3.83 | 0.00 | 744.00 |
February | 47.40 | 13.95 | 33.45 | 34.44 | 116.26 | 0.00 | 0.00 | 672.00 |
March | 73.73 | 38.21 | 35.52 | 83.21 | 73.91 | 33.83 | 0.00 | 744.00 |
April | 96.97 | 51.50 | 45.47 | 123.05 | 45.88 | 19.33 | 0.00 | 720.00 |
May | 124.15 | 76.42 | 47.73 | 160.18 | 42.91 | 9.00 | 0.00 | 744.00 |
June | 143.65 | 89.98 | 53.67 | 187.30 | 44.11 | 8.67 | 0.00 | 720.00 |
July | 133.60 | 81.17 | 52.43 | 174.21 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 113.63 | 63.11 | 50.52 | 144.95 | 52.22 | 3.83 | 0.00 | 744.00 |
September | 84.13 | 45.61 | 38.52 | 103.60 | 59.42 | 12.17 | 0.00 | 720.00 |
October | 52.61 | 22.73 | 29.88 | 61.29 | 54.08 | 15.00 | 0.00 | 744.00 |
November | 30.35 | 9.39 | 20.96 | 31.31 | 54.95 | 14.17 | 0.00 | 720.00 |
December | 26.39 | 5.76 | 20.63 | 12.22 | 108.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.89 | 42.40 | 37.49 | 94.52 | 67.76 | 119.83 | 0.00 | 8760.00 |
Minimum of Months | 26.39 | 5.76 | 20.63 | 12.22 | 42.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.65 | 89.98 | 53.67 | 187.30 | 119.13 | 33.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180591E+09 | 42535153.91 | 0.138056E+09 | 37527963.77 | 0.597234E+09 |
February | 0.264293E+09 | 68208374.49 | 0.196085E+09 | 91335513.44 | 0.502799E+09 |
March | 0.460023E+09 | 0.197768E+09 | 0.262255E+09 | 0.331692E+09 | 0.359336E+09 |
April | 0.541547E+09 | 0.221666E+09 | 0.319881E+09 | 0.471638E+09 | 0.232461E+09 |
May | 0.660525E+09 | 0.298216E+09 | 0.362309E+09 | 0.657115E+09 | 0.167840E+09 |
June | 0.772229E+09 | 0.363237E+09 | 0.408992E+09 | 0.825745E+09 | 0.135858E+09 |
July | 0.712591E+09 | 0.311927E+09 | 0.400665E+09 | 0.801641E+09 | 0.105688E+09 |
August | 0.643862E+09 | 0.273048E+09 | 0.370813E+09 | 0.710590E+09 | 0.137076E+09 |
September | 0.490682E+09 | 0.212035E+09 | 0.278647E+09 | 0.485643E+09 | 0.198543E+09 |
October | 0.328533E+09 | 0.115727E+09 | 0.212806E+09 | 0.258948E+09 | 0.257393E+09 |
November | 0.186878E+09 | 53059322.03 | 0.133819E+09 | 99919598.64 | 0.325143E+09 |
December | 0.168457E+09 | 36505543.55 | 0.131952E+09 | 35542513.87 | 0.570553E+09 |
Annual Sum or Average | 0.541021E+10 | 0.219393E+10 | 0.321628E+10 | 0.480734E+10 | 0.358993E+10 |
Minimum of Months | 0.168457E+09 | 36505543.55 | 0.131952E+09 | 35542513.87 | 0.105688E+09 |
Maximum of Months | 0.772229E+09 | 0.363237E+09 | 0.408992E+09 | 0.825745E+09 | 0.597234E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180591E+09 | 42535153.91 | 0.138056E+09 | 37527963.77 | 0.597234E+09 |
February | 0.264293E+09 | 68208374.49 | 0.196085E+09 | 91335513.44 | 0.502799E+09 |
March | 0.460023E+09 | 0.197768E+09 | 0.262255E+09 | 0.331692E+09 | 0.359336E+09 |
April | 0.541547E+09 | 0.221666E+09 | 0.319881E+09 | 0.471638E+09 | 0.232461E+09 |
May | 0.660525E+09 | 0.298216E+09 | 0.362309E+09 | 0.657115E+09 | 0.167840E+09 |
June | 0.772229E+09 | 0.363237E+09 | 0.408992E+09 | 0.825745E+09 | 0.135858E+09 |
July | 0.712591E+09 | 0.311927E+09 | 0.400665E+09 | 0.801641E+09 | 0.105688E+09 |
August | 0.643862E+09 | 0.273048E+09 | 0.370813E+09 | 0.710590E+09 | 0.137076E+09 |
September | 0.490682E+09 | 0.212035E+09 | 0.278647E+09 | 0.485643E+09 | 0.198543E+09 |
October | 0.328533E+09 | 0.115727E+09 | 0.212806E+09 | 0.258948E+09 | 0.257393E+09 |
November | 0.186878E+09 | 53059322.03 | 0.133819E+09 | 99919598.64 | 0.325143E+09 |
December | 0.168457E+09 | 36505543.55 | 0.131952E+09 | 35542513.87 | 0.570553E+09 |
Annual Sum or Average | 0.541021E+10 | 0.219393E+10 | 0.321628E+10 | 0.480734E+10 | 0.358993E+10 |
Minimum of Months | 0.168457E+09 | 36505543.55 | 0.131952E+09 | 35542513.87 | 0.105688E+09 |
Maximum of Months | 0.772229E+09 | 0.363237E+09 | 0.408992E+09 | 0.825745E+09 | 0.597234E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66963890.62 | 0.00 | 66963890.62 | 549273.60 | 0.373214E+09 |
February | 92154193.27 | 0.00 | 92154193.27 | 3376377.08 | 0.314126E+09 |
March | 0.123751E+09 | 4189.80 | 0.123747E+09 | 37218697.96 | 0.229542E+09 |
April | 0.152667E+09 | 728759.54 | 0.151938E+09 | 80312972.11 | 0.139718E+09 |
May | 0.183247E+09 | 7869012.26 | 0.175378E+09 | 0.128978E+09 | 93889078.42 |
June | 0.213203E+09 | 18098544.39 | 0.195104E+09 | 0.178095E+09 | 73623513.36 |
July | 0.205187E+09 | 13932719.45 | 0.191254E+09 | 0.198562E+09 | 56927870.11 |
August | 0.177653E+09 | 3414589.50 | 0.174239E+09 | 0.164986E+09 | 77946822.86 |
September | 0.130312E+09 | 56082.07 | 0.130256E+09 | 94009682.37 | 0.118569E+09 |
October | 0.100614E+09 | 0.00 | 0.100614E+09 | 45851165.81 | 0.155228E+09 |
November | 65429337.32 | 0.00 | 65429337.32 | 14503291.26 | 0.196768E+09 |
December | 62676171.96 | 0.00 | 62676171.96 | 772697.50 | 0.350185E+09 |
Annual Sum or Average | 0.157386E+10 | 44103897.01 | 0.152975E+10 | 0.947215E+09 | 0.217974E+10 |
Minimum of Months | 62676171.96 | 0.00 | 62676171.96 | 549273.60 | 56927870.11 |
Maximum of Months | 0.213203E+09 | 18098544.39 | 0.195104E+09 | 0.198562E+09 | 0.373214E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66961600.38 | 0.00 | 66961600.38 | 549134.38 | 0.373215E+09 |
February | 92151055.70 | 0.00 | 92151055.70 | 3375586.80 | 0.314128E+09 |
March | 0.123747E+09 | 4189.60 | 0.123743E+09 | 37216054.62 | 0.229543E+09 |
April | 0.152662E+09 | 728725.38 | 0.151934E+09 | 80308837.53 | 0.139718E+09 |
May | 0.183242E+09 | 7868643.43 | 0.175373E+09 | 0.128973E+09 | 93888755.33 |
June | 0.213196E+09 | 18097696.08 | 0.195098E+09 | 0.178089E+09 | 73622988.51 |
July | 0.205181E+09 | 13932066.41 | 0.191249E+09 | 0.198555E+09 | 56927293.30 |
August | 0.177648E+09 | 3414429.46 | 0.174234E+09 | 0.164981E+09 | 77946327.13 |
September | 0.130308E+09 | 56079.45 | 0.130252E+09 | 94005988.06 | 0.118569E+09 |
October | 0.100611E+09 | 0.00 | 0.100611E+09 | 45848491.92 | 0.155228E+09 |
November | 65427094.82 | 0.00 | 65427094.82 | 14502207.45 | 0.196768E+09 |
December | 62673978.76 | 0.00 | 62673978.76 | 772551.93 | 0.350186E+09 |
Annual Sum or Average | 0.157381E+10 | 44101829.80 | 0.152971E+10 | 0.947177E+09 | 0.217974E+10 |
Minimum of Months | 62673978.76 | 0.00 | 62673978.76 | 549134.38 | 56927293.30 |
Maximum of Months | 0.213196E+09 | 18097696.08 | 0.195098E+09 | 0.198555E+09 | 0.373215E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80412995.31 | 24302201.47 | 56110793.84 | 39705921.46 | 0.319075E+09 |
February | 0.114665E+09 | 33741813.93 | 80923557.51 | 83311704.77 | 0.281266E+09 |
March | 0.197485E+09 | 0.102353E+09 | 95132561.85 | 0.222879E+09 | 0.197955E+09 |
April | 0.251345E+09 | 0.133497E+09 | 0.117849E+09 | 0.318952E+09 | 0.118921E+09 |
May | 0.332524E+09 | 0.204681E+09 | 0.127842E+09 | 0.429020E+09 | 0.114924E+09 |
June | 0.372336E+09 | 0.233224E+09 | 0.139112E+09 | 0.485472E+09 | 0.114321E+09 |
July | 0.357827E+09 | 0.217408E+09 | 0.140419E+09 | 0.466609E+09 | 0.118270E+09 |
August | 0.304358E+09 | 0.169040E+09 | 0.135318E+09 | 0.388249E+09 | 0.139866E+09 |
September | 0.218055E+09 | 0.118218E+09 | 99837602.18 | 0.268519E+09 | 0.154014E+09 |
October | 0.140905E+09 | 60871883.17 | 80033088.89 | 0.164161E+09 | 0.144848E+09 |
November | 78676769.39 | 24338592.33 | 54338177.06 | 81164177.35 | 0.142443E+09 |
December | 70679479.69 | 15424886.46 | 55254593.23 | 32741498.50 | 0.290855E+09 |
Annual Sum or Average | 0.251927E+10 | 0.133710E+10 | 0.118217E+10 | 0.298078E+10 | 0.213676E+10 |
Minimum of Months | 70679479.69 | 15424886.46 | 54338177.06 | 32741498.50 | 0.114321E+09 |
Maximum of Months | 0.372336E+09 | 0.233224E+09 | 0.140419E+09 | 0.485472E+09 | 0.319075E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.06 | 716.28 | 184.85 | 31.76 | 153.09 | 0.00 | 0.00 |
February | 67.06 | 664.13 | 294.68 | 56.39 | 238.29 | 0.00 | 0.00 |
March | 262.76 | 427.01 | 435.91 | 147.68 | 288.23 | 0.00 | 0.00 |
April | 422.44 | 283.73 | 535.66 | 171.60 | 364.06 | 0.00 | 0.00 |
May | 585.79 | 194.24 | 630.05 | 228.56 | 401.50 | 0.00 | 0.00 |
June | 771.58 | 158.65 | 760.36 | 294.24 | 466.12 | 0.00 | 0.00 |
July | 744.29 | 118.86 | 685.32 | 243.32 | 441.99 | 0.00 | 0.00 |
August | 653.39 | 160.15 | 613.44 | 206.44 | 407.00 | 0.00 | 0.00 |
September | 445.31 | 242.74 | 479.16 | 163.65 | 315.51 | 0.00 | 0.00 |
October | 224.77 | 305.28 | 320.45 | 86.42 | 234.03 | 0.00 | 0.00 |
November | 84.12 | 398.54 | 194.68 | 40.94 | 153.74 | 0.00 | 0.00 |
December | 19.69 | 680.10 | 172.59 | 27.26 | 145.33 | 0.00 | 0.00 |
Annual Sum or Average | 360.04 | 361.00 | 442.93 | 141.94 | 300.99 | 0.00 | 0.00 |
Minimum of Months | 19.69 | 118.86 | 172.59 | 27.26 | 145.33 | 0.00 | 0.00 |
Maximum of Months | 771.58 | 716.28 | 760.36 | 294.24 | 466.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.24 | 1191.29 | 300.23 | 90.73 | 209.49 | 0.00 | 0.00 |
February | 344.38 | 1162.64 | 473.98 | 139.48 | 334.51 | 0.00 | 0.00 |
March | 832.13 | 739.08 | 737.33 | 382.14 | 355.18 | 0.00 | 0.00 |
April | 1230.52 | 458.80 | 969.70 | 515.03 | 454.66 | 0.00 | 0.00 |
May | 1601.78 | 429.08 | 1241.50 | 764.19 | 477.31 | 0.00 | 0.00 |
June | 1872.96 | 441.05 | 1436.48 | 899.78 | 536.70 | 0.00 | 0.00 |
July | 1742.12 | 441.57 | 1335.97 | 811.71 | 524.27 | 0.00 | 0.00 |
August | 1449.55 | 522.20 | 1136.34 | 631.12 | 505.22 | 0.00 | 0.00 |
September | 1035.95 | 594.19 | 841.26 | 456.09 | 385.18 | 0.00 | 0.00 |
October | 612.91 | 540.80 | 526.08 | 227.27 | 298.81 | 0.00 | 0.00 |
November | 313.13 | 549.55 | 303.54 | 93.90 | 209.64 | 0.00 | 0.00 |
December | 122.24 | 1085.93 | 263.89 | 57.59 | 206.30 | 0.00 | 0.00 |
Annual Sum or Average | 945.20 | 677.56 | 798.86 | 423.99 | 374.86 | 0.00 | 0.00 |
Minimum of Months | 122.24 | 429.08 | 263.89 | 57.59 | 206.30 | 0.00 | 0.00 |
Maximum of Months | 1872.96 | 1191.29 | 1436.48 | 899.78 | 536.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 53732234.27 | 0.191848E+10 | 0.495108E+09 | 85070307.82 | 0.410038E+09 | 0.00 | 0.00 |
February | 0.162232E+09 | 0.160666E+10 | 0.712891E+09 | 0.136417E+09 | 0.576474E+09 | 0.00 | 0.00 |
March | 0.703778E+09 | 0.114372E+10 | 0.116754E+10 | 0.395543E+09 | 0.771999E+09 | 0.00 | 0.00 |
April | 0.109496E+10 | 0.735417E+09 | 0.138842E+10 | 0.444789E+09 | 0.943633E+09 | 0.00 | 0.00 |
May | 0.156897E+10 | 0.520248E+09 | 0.168754E+10 | 0.612170E+09 | 0.107537E+10 | 0.00 | 0.00 |
June | 0.199994E+10 | 0.411232E+09 | 0.197086E+10 | 0.762669E+09 | 0.120819E+10 | 0.00 | 0.00 |
July | 0.199352E+10 | 0.318349E+09 | 0.183555E+10 | 0.651718E+09 | 0.118383E+10 | 0.00 | 0.00 |
August | 0.175004E+10 | 0.428937E+09 | 0.164303E+10 | 0.552926E+09 | 0.109010E+10 | 0.00 | 0.00 |
September | 0.115425E+10 | 0.629173E+09 | 0.124198E+10 | 0.424182E+09 | 0.817802E+09 | 0.00 | 0.00 |
October | 0.602020E+09 | 0.817665E+09 | 0.858292E+09 | 0.231454E+09 | 0.626838E+09 | 0.00 | 0.00 |
November | 0.218036E+09 | 0.103301E+10 | 0.504612E+09 | 0.106119E+09 | 0.398494E+09 | 0.00 | 0.00 |
December | 52726161.25 | 0.182157E+10 | 0.462264E+09 | 73011087.10 | 0.389253E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113542E+11 | 0.113845E+11 | 0.139681E+11 | 0.447607E+10 | 0.949202E+10 | 0.00 | 0.00 |
Minimum of Months | 52726161.25 | 0.318349E+09 | 0.462264E+09 | 73011087.10 | 0.389253E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199994E+10 | 0.191848E+10 | 0.197086E+10 | 0.762669E+09 | 0.120819E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397059E+09 | 0.319075E+10 | 0.804130E+09 | 0.243022E+09 | 0.561108E+09 | 0.00 | 0.00 |
February | 0.833113E+09 | 0.281266E+10 | 0.114665E+10 | 0.337418E+09 | 0.809236E+09 | 0.00 | 0.00 |
March | 0.222878E+10 | 0.197955E+10 | 0.197485E+10 | 0.102353E+10 | 0.951326E+09 | 0.00 | 0.00 |
April | 0.318951E+10 | 0.118921E+10 | 0.251345E+10 | 0.133497E+10 | 0.117849E+10 | 0.00 | 0.00 |
May | 0.429020E+10 | 0.114924E+10 | 0.332524E+10 | 0.204681E+10 | 0.127842E+10 | 0.00 | 0.00 |
June | 0.485471E+10 | 0.114321E+10 | 0.372336E+10 | 0.233224E+10 | 0.139112E+10 | 0.00 | 0.00 |
July | 0.466609E+10 | 0.118270E+10 | 0.357827E+10 | 0.217408E+10 | 0.140419E+10 | 0.00 | 0.00 |
August | 0.388247E+10 | 0.139866E+10 | 0.304358E+10 | 0.169040E+10 | 0.135318E+10 | 0.00 | 0.00 |
September | 0.268519E+10 | 0.154014E+10 | 0.218055E+10 | 0.118218E+10 | 0.998376E+09 | 0.00 | 0.00 |
October | 0.164161E+10 | 0.144848E+10 | 0.140905E+10 | 0.608719E+09 | 0.800331E+09 | 0.00 | 0.00 |
November | 0.811642E+09 | 0.142443E+10 | 0.786768E+09 | 0.243386E+09 | 0.543382E+09 | 0.00 | 0.00 |
December | 0.327415E+09 | 0.290855E+10 | 0.706795E+09 | 0.154249E+09 | 0.552546E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298078E+11 | 0.213676E+11 | 0.251927E+11 | 0.133710E+11 | 0.118217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327415E+09 | 0.114321E+10 | 0.706795E+09 | 0.154249E+09 | 0.543382E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485471E+10 | 0.319075E+10 | 0.372336E+10 | 0.233224E+10 | 0.140419E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.3 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.73 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.65 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.46 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.38 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.38 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.41 | 11.22 | 4.10 | 7.07 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.35 | 4.97 | 4.79 | 0.12 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.71 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.35 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.3 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.38 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.13 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.16 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.04 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.42 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.82 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.22 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.71 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.23 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.51 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.12 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.84 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.40 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.16 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.71 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.2 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.3 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.4 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.82 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.76 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.17 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.74 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.41 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.22 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.95 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.40 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.96 | 4.80 | 10.49 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.96 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108022E+10 | -922981307.1 | 0.00 | 0.00 | 744.00 | 0.00 | -157233733.8 | 58.99 | 0.00 | 0.00 |
February | 0.100203E+10 | -860094140.4 | 0.00 | 0.00 | 672.00 | 0.00 | -141931484.3 | 58.99 | 0.00 | 0.00 |
March | 0.114615E+10 | -991587660.0 | 0.00 | 0.00 | 744.00 | 0.00 | -154563607.8 | 58.99 | 0.00 | 0.00 |
April | 0.103259E+10 | -884838415.8 | 0.00 | 0.00 | 720.00 | 0.00 | -147750812.5 | 58.99 | 0.00 | 0.00 |
May | 0.101131E+10 | -868063527.1 | 0.00 | 0.00 | 744.00 | 0.00 | -143245146.6 | 58.99 | 0.00 | 0.00 |
June | 0.940976E+09 | -811353190.7 | 0.00 | 0.00 | 720.00 | 0.00 | -129622910.1 | 58.99 | 0.00 | 0.00 |
July | 0.877589E+09 | -745938637.2 | 0.00 | 0.00 | 744.00 | 0.00 | -131650514.1 | 58.99 | 0.00 | 0.00 |
August | 0.918550E+09 | -786003653.5 | 0.00 | 0.00 | 744.00 | 0.00 | -132546182.0 | 58.99 | 0.00 | 0.00 |
September | 0.874470E+09 | -743972092.2 | 0.00 | 0.00 | 720.00 | 0.00 | -130498308.6 | 58.99 | 0.00 | 0.00 |
October | 0.932190E+09 | -783156148.9 | 0.00 | 0.00 | 744.00 | 0.00 | -149034292.0 | 58.99 | 0.00 | 0.00 |
November | 0.950339E+09 | -800548380.4 | 0.00 | 0.00 | 720.00 | 0.00 | -149790396.0 | 58.99 | 0.00 | 0.00 |
December | 0.104118E+10 | -884023437.5 | 0.00 | 0.00 | 744.00 | 0.00 | -157151580.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.118076E+11 | -.100826E+11 | 8760.00 | -.172502E+10 | 58.99 | |||||
Minimum of Months | 0.874470E+09 | -991587660.0 | 0.00 | 0.00 | 672.00 | 0.00 | -157233733.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114615E+10 | -743972092.2 | 0.00 | 0.00 | 744.00 | 0.00 | -129622910.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | ||||||||||
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138938E+11 | 29190.72 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131219E+11 | 29190.72 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.871097E+10 | 29190.72 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426571E+10 | 29190.72 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.902949E+09 | 29190.72 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48320810.62 | 6084.51 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87540.23 | 145.90 | 31-AUG-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95003728.50 | 29190.72 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216547E+10 | 29190.72 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.521955E+10 | 29190.72 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123023E+11 | 29190.72 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607260E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138938E+11 | 29190.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.690968E+11 | 82326.60 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.689224E+11 | 82326.60 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350105E+11 | 82326.60 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137099E+11 | 82326.60 | 01-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350992E+09 | 63162.09 | 02-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568573E+10 | 82326.60 | 16-OCT-21:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222886E+11 | 82326.60 | 02-NOV-17:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668160E+11 | 82326.60 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281881E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.690968E+11 | 82326.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187908E+12 | 222624.23 | 12-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193246E+12 | 222624.23 | 06-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723050E+11 | 123224.62 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111176E+11 | 84742.85 | 16-APR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142290E+09 | 19265.41 | 30-OCT-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227026E+11 | 52319.98 | 25-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177570E+12 | 199874.59 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.664992E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193246E+12 | 222624.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 57445876.46 | 51583679.05 | 3073.75 | 15-MAR-15:10 | 2851.86 | 0.00 |
April | 0.00 | 0.00 | 6781270.57 | 6535687.59 | 868.06 | 08-APR-14:30 | 826.56 | 0.00 |
May | 0.00 | 0.00 | 0.713443E+09 | 0.669796E+09 | 7666.34 | 27-MAY-18:00 | 7666.34 | 0.00 |
June | 0.00 | 0.00 | 0.587456E+10 | 0.485506E+10 | 22283.60 | 19-JUN-00:02 | 14262.07 | 0.00 |
July | 0.00 | 0.00 | 0.107320E+11 | 0.843067E+10 | 23514.62 | 17-JUL-00:01 | 14764.12 | 0.00 |
August | 0.00 | 0.00 | 0.947231E+10 | 0.797550E+10 | 24077.48 | 14-AUG-00:01 | 13735.87 | 0.00 |
September | 0.00 | 0.00 | 0.389813E+10 | 0.328195E+10 | 20911.47 | 18-SEP-00:03 | 15580.26 | 0.00 |
October | 0.00 | 0.00 | 0.109447E+09 | 0.100055E+09 | 3146.27 | 11-OCT-16:00 | 2943.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.308641E+11 | 0.253711E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107320E+11 | 0.843067E+10 | 24077.48 | 15580.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.482085E+10 | 0.363682E+10 | 64200.01 | 27-JUN-17:10 | 38073.98 | 0.00 |
July | 0.00 | 0.00 | 0.155363E+11 | 0.114034E+11 | 62445.76 | 16-JUL-10:33 | 38729.52 | 0.00 |
August | 0.00 | 0.00 | 0.115137E+11 | 0.943016E+10 | 62137.46 | 13-AUG-16:03 | 38754.77 | 0.00 |
September | 0.00 | 0.00 | 0.105920E+10 | 0.822843E+09 | 20250.47 | 16-SEP-13:40 | 15571.86 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.329301E+11 | 0.252932E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155363E+11 | 0.114034E+11 | 64200.01 | 38754.77 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132974E+10 | 0.08 | 510.66 | 01-JAN-00:02 | 0.08 |
February | 0.120912E+10 | 0.08 | 510.66 | 01-FEB-00:02 | 0.08 |
March | 0.814147E+09 | 0.05 | 510.66 | 01-MAR-00:02 | 0.08 |
April | 0.234741E+09 | 0.01 | 510.66 | 01-APR-00:03 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 10494080.86 | 0.00 | 510.66 | 30-OCT-01:10 | 0.08 |
November | 0.591580E+09 | 0.03 | 510.66 | 02-NOV-20:25 | 0.08 |
December | 0.132047E+10 | 0.08 | 510.66 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.551028E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132974E+10 | 0.08 | 510.66 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138230E+10 | 0.72 | 1218.31 | 14-JAN-16:00 | 0.96 |
February | 0.128382E+10 | 0.72 | 1218.31 | 22-FEB-15:10 | 0.96 |
March | 0.139511E+10 | 0.55 | 1218.31 | 10-MAR-14:20 | 0.96 |
April | 0.124705E+10 | 0.42 | 1218.31 | 01-APR-08:00 | 0.96 |
May | 0.126907E+10 | 0.39 | 1218.31 | 27-MAY-09:40 | 0.96 |
June | 0.132875E+10 | 0.48 | 1218.31 | 01-JUN-07:40 | 0.95 |
July | 0.139652E+10 | 0.59 | 1218.31 | 01-JUL-06:20 | 0.95 |
August | 0.146099E+10 | 0.60 | 1218.31 | 26-AUG-06:20 | 0.95 |
September | 0.123703E+10 | 0.41 | 1218.31 | 01-SEP-09:40 | 0.95 |
October | 0.122715E+10 | 0.38 | 1218.31 | 11-OCT-13:20 | 0.95 |
November | 0.119396E+10 | 0.39 | 1218.31 | 28-NOV-11:00 | 0.96 |
December | 0.135452E+10 | 0.64 | 1218.31 | 01-DEC-09:00 | 0.95 |
Annual Sum or Average | 0.157763E+11 | 0.52 | |||
Minimum of Months | 0.119396E+10 | 0.38 | 1218.31 | 0.95 | |
Maximum of Months | 0.146099E+10 | 0.72 | 1218.31 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.413300E+10 | 0.82 | 2619.45 | 06-JAN-10:50 | 0.93 |
February | 0.391956E+10 | 0.82 | 2619.45 | 01-FEB-00:02 | 0.93 |
March | 0.366667E+10 | 0.76 | 2619.45 | 21-MAR-12:20 | 0.92 |
April | 0.299566E+10 | 0.63 | 2619.45 | 14-APR-13:00 | 0.92 |
May | 0.271007E+10 | 0.37 | 2619.45 | 01-MAY-06:10 | 0.92 |
June | 0.270915E+10 | 0.37 | 2619.45 | 02-JUN-12:20 | 0.91 |
July | 0.270460E+10 | 0.40 | 2619.45 | 01-JUL-06:05 | 0.91 |
August | 0.286018E+10 | 0.40 | 2619.45 | 01-AUG-06:03 | 0.91 |
September | 0.259326E+10 | 0.35 | 2619.45 | 21-SEP-13:40 | 0.91 |
October | 0.277839E+10 | 0.52 | 2619.45 | 28-OCT-06:50 | 0.92 |
November | 0.309679E+10 | 0.73 | 2619.45 | 02-NOV-11:10 | 0.92 |
December | 0.409897E+10 | 0.82 | 2619.45 | 02-DEC-12:30 | 0.92 |
Annual Sum or Average | 0.382663E+11 | 0.58 | |||
Minimum of Months | 0.259326E+10 | 0.35 | 2619.45 | 0.91 | |
Maximum of Months | 0.413300E+10 | 0.82 | 2619.45 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.37 | 0.00 |
February | 2.92 | 0.03 |
March | 2.91 | 0.10 |
April | 1.59 | 0.27 |
May | 1.44 | 1.60 |
June | 0.92 | 2.44 |
July | 0.86 | 1.48 |
August | 1.08 | 2.52 |
September | 1.57 | 3.40 |
October | 1.17 | 0.99 |
November | 2.28 | 0.00 |
December | 3.29 | 0.01 |
Annual Sum or Average | 23.41 | 0.68 |
Minimum of Months | 0.86 | 0.00 |
Maximum of Months | 3.37 | 3.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.41 | 0.00 |
February | 2.32 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.41 | 0.00 |
Annual Sum or Average | 3.31 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.32 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.89 | 0.00 |
August | 0.56 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.44 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.89 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.138230E+10 | 0.196543E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128382E+10 | 0.185024E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.141112E+10 | 0.124733E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124893E+10 | 0.618765E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.146322E+10 | 0.131723E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.290188E+10 | 73459315.08 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.426524E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.400276E+10 | 136610.91 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.227909E+10 | 0.143203E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125711E+10 | 0.316080E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119396E+10 | 0.758296E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135452E+10 | 0.174499E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.240439E+11 | 0.865453E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.426524E+10 | 0.196543E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.413300E+10 | 0.969583E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.391956E+10 | 0.951668E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.366667E+10 | 0.501963E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.299566E+10 | 0.199672E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.271007E+10 | 0.532114E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.408905E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.713619E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.618496E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.289836E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.277839E+10 | 0.841605E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.309679E+10 | 0.324674E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.409897E+10 | 0.935871E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.477077E+11 | 0.397291E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.271007E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.713619E+10 | 0.969583E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138230E+10 | 0.00 | 0.138938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128382E+10 | 0.00 | 0.131219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139511E+10 | 57445876.46 | 0.871097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124705E+10 | 6781270.57 | 0.426571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126907E+10 | 0.713443E+09 | 0.902949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132875E+10 | 0.587456E+10 | 48320810.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139652E+10 | 0.107320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146099E+10 | 0.947231E+10 | 87540.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123703E+10 | 0.389813E+10 | 95003728.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122715E+10 | 0.109447E+09 | 0.216547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119396E+10 | 0.00 | 0.521955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135452E+10 | 0.00 | 0.123023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157763E+11 | 0.308641E+11 | 0.607260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146099E+10 | 0.107320E+11 | 0.138938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.413300E+10 | 0.00 | 0.690968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391956E+10 | 0.00 | 0.689224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366667E+10 | 0.00 | 0.350105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.299566E+10 | 0.00 | 0.137099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271007E+10 | 0.00 | 0.350992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270915E+10 | 0.482085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270460E+10 | 0.155363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286018E+10 | 0.115137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259326E+10 | 0.105920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277839E+10 | 0.00 | 0.568573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309679E+10 | 0.00 | 0.222886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409897E+10 | 0.00 | 0.668160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382663E+11 | 0.329301E+11 | 0.281881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413300E+10 | 0.155363E+11 | 0.690968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.138230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139511E+10 | 0.00 | 0.00 | 0.00 | 16008820.67 | 0.00 | 0.124733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124705E+10 | 0.00 | 0.00 | 0.00 | 1878233.80 | 0.00 | 0.618765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126907E+10 | 0.00 | 0.00 | 0.00 | 0.194149E+09 | 0.00 | 0.131723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132875E+10 | 0.00 | 0.00 | 0.00 | 0.157314E+10 | 0.00 | 73459315.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139652E+10 | 0.00 | 0.00 | 0.00 | 0.286871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146099E+10 | 0.00 | 0.00 | 0.00 | 0.254178E+10 | 0.00 | 136610.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123703E+10 | 0.00 | 0.00 | 0.00 | 0.104206E+10 | 0.00 | 0.143203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122715E+10 | 0.00 | 0.00 | 0.00 | 29960152.15 | 0.00 | 0.316080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157763E+11 | 0.00 | 0.00 | 0.00 | 0.826768E+10 | 0.00 | 0.865453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.119396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146099E+10 | 0.00 | 0.00 | 0.00 | 0.286871E+10 | 0.00 | 0.196543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.413300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.299566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270915E+10 | 0.00 | 0.00 | 0.00 | 0.137990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270460E+10 | 0.00 | 0.00 | 0.00 | 0.443159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286018E+10 | 0.00 | 0.00 | 0.00 | 0.332478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259326E+10 | 0.00 | 0.00 | 0.00 | 0.305096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382663E+11 | 0.00 | 0.00 | 0.00 | 0.944137E+10 | 0.00 | 0.397291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.259326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413300E+10 | 0.00 | 0.00 | 0.00 | 0.443159E+10 | 0.00 | 0.969583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391732E+10 | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 22836.31 | 0.00 | 0.00 | 0.373655E+10 | 0.00 | 26489.54 | 0.18 |
March | 89870643.46 | 2716308.24 | 0.00 | 66.06 | 1683915.48 | 0.283518E+10 | 407527.49 | 0.00 | 0.18 |
April | 0.278453E+09 | 0.00 | 0.00 | 2462.50 | 0.00 | 0.162206E+10 | 7605758.14 | 0.00 | 0.17 |
May | 0.670036E+09 | 6558939.89 | 0.00 | 797068.36 | 136981.08 | 0.316192E+09 | 0.232946E+09 | 0.00 | 0.17 |
June | 0.156076E+09 | 0.384358E+09 | 0.00 | 3835374.72 | 142039.39 | 30589308.23 | 0.443877E+09 | 0.00 | 0.18 |
July | 35628644.97 | 0.114595E+10 | 0.00 | 2702726.37 | 1931835.03 | 0.00 | 75153536.32 | 0.00 | 0.19 |
August | 74228300.03 | 0.606439E+09 | 0.00 | 4650335.16 | 1225094.65 | 953848.13 | 0.183266E+09 | 0.00 | 0.19 |
September | 0.224561E+09 | 0.175936E+09 | 0.00 | 2939371.74 | 524246.64 | 58422990.67 | 0.465973E+09 | 0.00 | 0.17 |
October | 0.722194E+09 | 0.00 | 0.00 | 109979.32 | 0.00 | 0.884458E+09 | 55611136.61 | 207.53 | 0.16 |
November | 91923905.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197982E+10 | 0.00 | 101275.23 | 0.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365300E+10 | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.234297E+10 | 0.232195E+10 | 22836.31 | 15037384.24 | 5644112.27 | 0.190345E+11 | 0.146484E+10 | 127972.29 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.722194E+09 | 0.114595E+10 | 22836.31 | 4650335.16 | 1931835.03 | 0.391732E+10 | 0.465973E+09 | 101275.23 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697446E+10 | 0.00 | 0.00 | 0.14 |
February | 79726709.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651973E+10 | 0.00 | 0.00 | 0.15 |
March | 0.109356E+10 | 0.00 | 0.00 | 0.00 | 45894622.44 | 0.376893E+10 | 0.00 | 0.00 | 0.15 |
April | 0.189252E+10 | 0.00 | 0.00 | 0.00 | 2088150.17 | 0.106286E+10 | 0.00 | 0.00 | 0.15 |
May | 0.228241E+10 | 0.00 | 0.00 | 0.00 | 12320279.69 | 2544775.91 | 0.00 | 0.00 | 0.16 |
June | 0.156405E+10 | 0.318850E+09 | 0.00 | 2202542.28 | 4838158.75 | 0.00 | 0.635390E+09 | 0.00 | 0.19 |
July | 0.272803E+09 | 0.122182E+10 | 0.00 | 3733948.12 | 0.00 | 0.00 | 0.107815E+10 | 0.00 | 0.21 |
August | 0.736830E+09 | 0.585639E+09 | 0.00 | 6585871.42 | 0.00 | 0.00 | 0.904445E+09 | 0.00 | 0.19 |
September | 0.194283E+10 | 69086832.76 | 0.00 | 540530.52 | 69812.55 | 0.00 | 0.290233E+09 | 0.00 | 0.17 |
October | 0.243968E+10 | 0.00 | 0.00 | 0.00 | 892296.68 | 0.232827E+09 | 0.00 | 0.00 | 0.15 |
November | 0.108697E+10 | 0.00 | 0.00 | 0.00 | 6804593.79 | 0.219811E+10 | 0.00 | 0.00 | 0.14 |
December | 0.122943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632188E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.135143E+11 | 0.219539E+10 | 0.00 | 13062892.33 | 72907914.07 | 0.270813E+11 | 0.290822E+10 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.243968E+10 | 0.122182E+10 | 0.00 | 6585871.42 | 45894622.44 | 0.697446E+10 | 0.107815E+10 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |