Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1033.39 | 213.72 | 213.72 |
Net Site Energy | 1033.39 | 213.72 | 213.72 |
Total Source Energy | 3043.56 | 629.47 | 629.47 |
Net Source Energy | 3043.56 | 629.47 | 629.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 110.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.96 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 923.37 | 110.02 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 110.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 68.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.96 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.93 | 22.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 190.97 | 22.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.93 | 22.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 190.97 | 22.75 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 923.366 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 923.366 | 100.00 |
Total On-Site and Utility Electric Sources | 923.366 | 100.00 |
Total Electricity End Uses | 923.366 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 22.33 |
Time Setpoint Not Met During Occupied Cooling | 15.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 868.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 27-DEC-06:19 | - | - | - | 25-SEP-11:30 |
Heating | 0.00 | 87719.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7650.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1710.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 76712.50 | 87719.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 87719.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5345.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1710.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 119.26 | 0.00 | 0.00 | 0.00 |
Cooling | 229.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 257.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2924.30 | 119.26 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.67 | 0.00 | 0.00 | 0.00 |
Cooling | 47.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 604.80 | 24.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.67 | 0.00 | 0.00 | 0.00 |
Cooling | 47.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 604.80 | 24.67 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.33 |
ZONE2 FINE STORAGE DIRECT AIR | 3.50 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.56 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.56 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 92120.06 |
PSZ-OFFICE HEATING COIL | 29819.03 |
PSZ-FINE STORAGE HEATING COIL | 97368.36 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 92120.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
PSZ-FINE STORAGE | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 1.00 | 1.00 | 3.50 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.33 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.50 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 1.33 | 22210.85 | 29819.03 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.50 | 3.50 | 3.50 | 3.50 | 71805.74 | 97368.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.33 | 0.666420 | 1.33 | 22063.23 | 22210.85 | 11105.42 | 22210.85 | 0.796212 | 0.796210 | 0.796210 | 0.796210 |
PSZ-FINE STORAGE COOLING COIL | 3.50 | 1.75 | 3.50 | 65511.45 | 71805.74 | 35902.87 | 71805.74 | 0.727251 | 0.727250 | 0.727250 | 0.727250 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.33 | 1519.58 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.50 | 3825.65 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 28 | 1 | VerySmooth | 3.241 | 0.385 | 0.305 | 0.391 |
2 | SKYLIGHT_U_1.02_SHGC_0.39 | 29 | 1 | VerySmooth | 5.779 | 0.390 | 0.223 | 0.391 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11709.33610 | 14051.20332 | 1.11070 | 1.33284 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28000 | 6.82376E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9309.57980 | 11171.49576 | 0.30131 | 0.36157 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 39394.65765 | 47273.58918 | 2.91277 | 3.49532 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.82375E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 30860.93059 | 37033.11671 | 0.84137 | 1.00964 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10000 | 6.82375E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 76766.71462 | 92120.05754 | 2.13108 | 2.55729 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18207.31 | 1.33284 | 1.33284 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10504.87 | 0.36157 | 0.36157 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 58155.01 | 3.49532 | 3.49532 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 33607.71 | 1.00964 | 1.00964 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33284 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.49532 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.55729 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.55729 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 92120.06091 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 92120.05754 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33284 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33284 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33284 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33284 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33284 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.33284 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.49532 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.49532 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.49532 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.49532 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.49532 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.49532 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.33284 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.49532 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33284 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33284 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33284 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33284 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33284 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33284 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66642 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33284 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22063.23456 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22210.85000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11105.42500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22210.85000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79621 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79621 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79621 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79621 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22210.85000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29819.02646 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33284 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1519.58436 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29819.02646 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.49532 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.49532 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.49532 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.49532 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.49532 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.49532 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.74766 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.49532 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 65511.45328 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 71805.74000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 35902.87000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 71805.74000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72725 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72725 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72725 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72725 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 71805.74000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 97368.35930 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.49532 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3825.64923 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 97368.35930 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21176.6 | 10.09 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 69091.3 | 12.68 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.8550426000E-002 | 3.4678986023E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1299259530 | 0.1356704995 | Pass | Pass | 0.2080845699 | 1.2548025263 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.5145717628E-002 | 5.4150822084E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.385 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.385 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.494 | 0.497 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.385 | 0.391 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.510 | 0.512 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.77 | 83.77 | 123.55 | |
Exterior Lighting Total | 7857.24 | 123.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22210.85 | 17684.50 | 4526.35 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 71805.74 | 52220.72 | 19585.02 | 0.73 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21176.6 | 10.09 | ||||
PSZ-FINE STORAGE COOLING COIL | 69091.3 | 12.68 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 92120.06 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29819.03 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 97368.36 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.56 | 237.60 | 92.91 | 1.00 | 3.44 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.33 | 1519.58 | 1140.11 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.50 | 3825.65 | 1094.51 | 1.00 | 1.22 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11709.34 | 14051.20 | 59.32 | 1.111 | 1.333 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00807 | 36.28 | 0.00682 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 39394.66 | 47273.59 | 33.93 | 2.913 | 3.495 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00792 | 38.10 | 0.00682 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00436 | 38.10 | 0.00682 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9309.58 | 11171.50 | 47.16 | 0.301 | 0.362 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00776 | -5.20 | 0.00281 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 30860.93 | 37033.12 | 26.58 | 0.841 | 1.010 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00651 | -5.20 | 0.00281 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 76766.71 | 92120.06 | 28.74 | 2.131 | 2.557 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 9.99 | 0.00881 | -5.20 | 0.00281 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.33 | 1.33 | 0.36 | 0.36 | 1.3328 | 1.3328 | 1.3328 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.50 | 3.50 | 1.01 | 1.01 | 3.4953 | 3.4953 | 3.4953 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 92120.061 | 92120.061 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 92120.06 | 92120.06 | 2.557294 | 5.16 | 5.16 | 0.00690079 | 43.33 | 25.24 | 0.01600000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 9.99 | 0.00881178 | 100.0000 | 92120.06 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22210.850 | 0.000 | 1.332840 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22210.85 | 22210.85 | 1.332840 | 25.02 | 14.81 | 0.00795498 | 12.00 | 10.00 | 0.00800000 | 36.28 | 0.00682376 | 17.55 | 9.0285 | 23.90 | 0.00806725 | 37.9162 | 11692.88 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29819.026 | 29819.026 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29819.03 | 29819.03 | 1.332840 | 12.31 | 8.19 | 0.00611118 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.0285 | 21.10 | 0.00775872 | 43.2526 | 9309.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 71805.740 | 0.000 | 3.495320 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 71805.74 | 71805.74 | 3.495320 | 27.85 | 15.64 | 0.00780739 | 12.00 | 10.00 | 0.00800000 | 38.10 | 0.00682375 | 18.10 | 10.1258 | 26.70 | 0.00791821 | 31.5125 | 39394.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 97368.359 | 97368.359 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 97368.36 | 97368.36 | 3.495322 | 8.28 | 5.36 | 0.00521348 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 10.1257 | 15.56 | 0.00651165 | 51.5081 | 30860.93 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 92120.061 | 92120.061 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0443 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.557294 | 2.67066296 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 92120.06 | 92120.06 | 1.0000 | 2.67066296 | 2.557294 | 5.16 | 5.16 | 0.00690079 | 22506.4 | 43.33 | 25.24 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92120.06 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 9.99 | 0.00881178 | 9.99 | 0.00881178 | 100.0000 | 92120.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22210.850 | 0.000 | 1.332840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6279 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22210.85 | 22210.85 | 1.0000 | 1.39192711 | 1.332840 | 25.02 | 14.81 | 0.00795498 | 45403.4 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22210.85 | 36.28 | 0.00682376 | 17.55 | 0.12033533 | 9.0285 | 23.90 | 0.00806725 | 23.90 | 0.00806725 | 37.9162 | 11692.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29819.026 | 29819.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.332840 | 1.39192737 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29819.03 | 29819.03 | 1.0000 | 1.39192737 | 1.332840 | 12.31 | 8.19 | 0.00611118 | 27797.3 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29819.03 | -5.20 | 0.00280840 | -5.20 | 0.12033533 | 9.0285 | 21.05 | 0.00775872 | 21.10 | 0.00775872 | 43.2526 | 9309.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 71805.740 | 0.000 | 3.495320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3535 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 71805.74 | 71805.74 | 1.0000 | 3.65027359 | 3.495320 | 27.85 | 15.64 | 0.00780739 | 47919.5 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71805.74 | 38.10 | 0.00682375 | 18.10 | 0.35392745 | 10.1258 | 26.70 | 0.00791821 | 26.70 | 0.00791821 | 31.5125 | 39394.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97368.359 | 97368.359 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.495322 | 3.65027577 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 97368.36 | 97368.36 | 1.0000 | 3.65027577 | 3.495322 | 8.28 | 5.36 | 0.00521348 | 21439.3 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97368.36 | -5.20 | 0.00280840 | -5.20 | 0.35392745 | 10.1257 | 15.56 | 0.00651165 | 15.56 | 0.00651165 | 51.5081 | 30860.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.33 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 3.50 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2282.00 | 1871.83 | 868.33 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2282.00 | 1871.83 | 868.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 22.33 | 18.50 | 22.33 | 15.67 |
ZONE2 FINE STORAGE | 89.17 | 151.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 107.67 | 169.33 | 22.33 | 15.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 1.003 | 0.387 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 923.37 | 5475.32 | 01-JAN-07:40 | 76712.50 | 15-JUN-15:00 |
Electricity:Building | 634.32 | 4992.32 | 01-JAN-00:10 | 48037.94 | 19-APR-13:40 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 434.72 | 2759.73 | 01-JAN-00:10 | 33963.13 | 19-APR-13:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.96 | 483.00 | 04-JAN-06:10 | 2052.98 | 31-JAN-13:00 |
WaterSystems:Electricity | 24.96 | 483.00 | 04-JAN-06:10 | 2052.98 | 31-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 24.96 | 483.00 | 04-JAN-06:10 | 2052.98 | 31-JAN-13:00 |
Fans:Electricity | 81.29 | 0.00 | 01-JAN-00:40 | 7650.53 | 19-APR-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.08 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-APR-15:30 |
Ventilation (simple):Fans:Electricity | 13.08 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-APR-15:30 |
ElectricityPurchased:Facility | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
ElectricityNet:Plant | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 923.37 | 5475.32 | 23-APR-15:10 | 76712.50 | 15-JUN-15:00 |
Electricity:HVAC | 140.54 | 0.00 | 01-JAN-00:40 | 29081.23 | 15-JUN-15:10 |
General:Fans:Electricity | 68.21 | 0.00 | 01-JAN-00:40 | 5582.83 | 27-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 72.33 | 0.00 | 01-JAN-00:10 | 23736.00 | 15-JUN-15:10 |
ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.55 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 110.02 | 2250.00 | 21-MAY-19:30 | 87719.78 | 27-DEC-06:20 |
Gas:HVAC | 110.02 | 2250.00 | 21-MAY-19:30 | 87719.78 | 27-DEC-06:20 |
Heating:Gas | 110.02 | 2250.00 | 21-MAY-19:30 | 87719.78 | 27-DEC-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 25-SEP-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 491.41 | 0.00 | 01-JAN-00:40 | 133147.58 | 31-DEC-07:00 |
EnergyTransfer:Building | 229.97 | 0.00 | 01-JAN-00:40 | 67050.24 | 31-DEC-07:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 59.95 | 0.00 | 01-JAN-00:10 | 16256.43 | 27-DEC-07:10 |
Heating:EnergyTransfer | 36.16 | 0.00 | 01-JAN-00:40 | 67050.24 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.43 | 0.00 | 01-JAN-00:10 | 16256.43 | 27-DEC-07:10 |
Cooling:EnergyTransfer | 193.80 | 0.00 | 01-JAN-00:10 | 55613.18 | 15-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 51.52 | 0.00 | 01-JAN-00:10 | 13897.66 | 07-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 168.24 | 0.00 | 01-JAN-00:40 | 43573.02 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.95 | 0.00 | 01-JAN-00:40 | 31370.76 | 09-FEB-01:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.28 | 0.00 | 01-JAN-00:10 | 43573.02 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1.78 | 0.00 | 01-JAN-00:10 | 36335.13 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1.78 | 0.00 | 01-JAN-00:10 | 36335.13 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 261.44 | 0.00 | 01-JAN-00:40 | 66826.08 | 15-JUN-16:10 |
HeatingCoils:EnergyTransfer | 26.62 | 0.00 | 01-JAN-00:40 | 66097.35 | 31-DEC-07:00 |
CoolingCoils:EnergyTransfer | 234.82 | 0.00 | 01-JAN-00:10 | 66826.08 | 15-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 8.432 | -51.519 | 0.000 | 0.000 | 3.722 | 30.994 | 31.946 | 15.547 | 0.000 | 3.007 | 0.000 | 0.000 | -7.958 | 0.000 | -12.135 | -22.035 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 25.952 | -142.277 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 10.732 | 36.233 | 0.000 | 0.000 | 0.000 | -67.296 | -0.007 |
ZONE3 BULK STORAGE | 1.779 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 51.242 | 0.000 | 13.130 | 34.040 | 0.000 | -20.562 | 0.000 | -501.275 | -0.005 |
Total Facility | 1.779 | 0.000 | 34.384 | -193.796 | 0.000 | 0.000 | 3.722 | 481.960 | 139.282 | 66.789 | 0.000 | 26.868 | 70.273 | 0.000 | -28.520 | 0.000 | -580.706 | -22.047 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-MAY-05:01 | 0.00 | 0.00 | 0.00 | -30155.15 | 0.00 | 0.00 | 30.92 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 30161.05 | 0.00 | -638.25 | 0.00 | -558.77 | 0.00 |
ZONE2 FINE STORAGE | 11-SEP-19:11 | 0.00 | 0.00 | 0.00 | -70391.23 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 69882.35 | 0.00 | -0.00 | 0.00 | -691.01 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-16:41 | 0.00 | 0.00 | 0.00 | -79581.70 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 3163.19 | 0.00 | 763.76 | 223259.44 | 0.00 | 0.00 | 0.00 | -152597.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-DEC-06:12 | 0.00 | 0.00 | 30235.84 | 0.00 | 0.00 | 0.00 | 46.49 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -971.89 | 0.00 | -1646.99 | -28823.65 |
ZONE2 FINE STORAGE | 28-JAN-06:52 | 0.00 | 0.00 | 98598.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10116.76 | -89681.35 |
ZONE3 BULK STORAGE | 31-DEC-06:52 | 36338.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1741.76 | 0.00 | -31874.19 | -5482.19 |
Total Facility | 28-DEC-06:01 | 9561.06 | 0.00 | 127401.47 | 0.00 | 0.00 | 0.00 | 57.45 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2662.61 | 0.00 | -981.24 | -140545.97 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3328 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3328 | 0.0903 | 1.0000 | 0.1203 | 0.0903 | ||
PSZ-FINE STORAGE | 3.4953 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.4953 | 0.1013 | 1.0000 | 0.3539 | 0.1013 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3328 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3328 | 1.0000 | 1.0000 | 0.1203 | 0.0903 | ||
PSZ-FINE STORAGE | 3.4953 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.4953 | 1.0000 | 1.0000 | 0.3539 | 0.1013 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3328 | 1.3328 | 1.3328 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.4953 | 3.4953 | 3.4953 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3328 | 1.3328 | 1.3328 | 1.3328 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.4953 | 3.4953 | 3.4953 | 3.4953 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3328 | 1.3328 | 1.3328 | 0.1203 | 0.3328 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.4953 | 3.4953 | 3.4953 | 0.3539 | 0.3505 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3328 | 1.3328 | 1.3328 | 1.3328 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.4953 | 3.4953 | 3.4953 | 3.4953 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 22.33 |
Number of hours cooling loads not met | 15.67 |
Number of hours not met | 38.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 110.02 | 87719.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 72.33 | 23736.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.55 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.08 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 68.21 | 5582.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.96 | 2052.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 923.37 |
Natural Gas | 0.00 | 110.02 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1033.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 14.96 |
Fans (All) | 16.81 |
Service Water Heating | 5.16 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 190.97 |
Subtotal | 190.97 |
Natural Gas [MJ/m2] | |
Space Heating | 22.75 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 22.75 |
Subtotal | 22.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 46.64 |
Space Heating | 10.65 |
Space Cooling | 7.00 |
Fans (All) | 7.87 |
Service Water Heating | 2.42 |
Receptacle Equipment | 13.48 |
Miscellaneous | 11.96 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178654E+11 |
February | 0.000 | 0.120612E+11 |
March | 0.000 | 0.819944E+10 |
April | 0.000 | 0.589472E+10 |
May | 0.000 | 0.602839E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.789379E+10 |
December | 0.000 | 0.223343E+11 |
Annual Sum or Average | 0.110020E+12 | |
Minimum of Months | 0.000 | 0.583200E+10 |
Maximum of Months | 0.000 | 0.223343E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32604736.95 | 1309.11 | 12-JAN-15:40 | 18.90 | 10.10 | 0.209032E+09 | 301.59 | 03-JAN-16:00 | 20.60 | 6.82 |
February | 0.140207E+09 | 2551.70 | 21-FEB-17:00 | 22.20 | 7.77 | 0.200108E+09 | 301.59 | 23-FEB-15:30 | 20.00 | 7.11 |
March | 0.772776E+09 | 4083.57 | 16-MAR-15:50 | 22.30 | 8.40 | 0.249484E+09 | 301.59 | 07-MAR-13:09 | 20.78 | 8.61 |
April | 0.354567E+10 | 26363.51 | 28-APR-05:03 | 14.22 | 8.84 | 0.247007E+09 | 301.61 | 25-APR-14:00 | 22.20 | 12.41 |
May | 0.676853E+10 | 30156.04 | 17-MAY-05:01 | 14.08 | 5.17 | 0.258800E+09 | 301.62 | 19-MAY-07:40 | 23.17 | 14.68 |
June | 0.900869E+10 | 29550.54 | 13-JUN-05:01 | 15.18 | 4.56 | 0.258951E+09 | 301.61 | 19-JUN-09:09 | 27.48 | 17.89 |
July | 0.890774E+10 | 23085.90 | 11-JUL-05:01 | 21.70 | 15.04 | 0.249082E+09 | 301.69 | 08-JUL-14:50 | 22.25 | 19.21 |
August | 0.908891E+10 | 25656.09 | 23-AUG-05:01 | 20.00 | 11.76 | 0.268950E+09 | 301.63 | 24-AUG-07:30 | 23.05 | 16.43 |
September | 0.765019E+10 | 29934.39 | 30-SEP-05:02 | 9.72 | 6.49 | 0.249019E+09 | 301.67 | 23-SEP-15:50 | 20.88 | 18.63 |
October | 0.451057E+10 | 27581.71 | 20-OCT-05:03 | 11.60 | 7.27 | 0.248334E+09 | 301.62 | 23-OCT-10:50 | 21.93 | 14.14 |
November | 0.106223E+10 | 5245.26 | 03-NOV-16:00 | 23.90 | 13.43 | 0.224353E+09 | 301.59 | 03-NOV-12:00 | 21.70 | 13.54 |
December | 31962362.14 | 1151.98 | 16-DEC-16:00 | 15.00 | 4.15 | 0.209046E+09 | 301.58 | 08-DEC-15:50 | 17.20 | 7.52 |
Annual Sum or Average | 0.515201E+11 | 0.287217E+10 | ||||||||
Minimum of Months | 31962362.14 | 1151.98 | 9.72 | 4.15 | 0.200108E+09 | 301.58 | 17.20 | 6.82 | ||
Maximum of Months | 0.908891E+10 | 30156.04 | 23.90 | 15.04 | 0.268950E+09 | 301.69 | 27.48 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182851E+09 | 2004.92 | 27-JAN-10:10 | 1.57 | -3.6 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.150331E+09 | 6886.32 | 21-FEB-07:10 | 4.68 | -0.0 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.159453E+09 | 7869.15 | 20-MAR-06:10 | 8.40 | 3.26 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.492463E+10 | 70322.39 | 30-APR-09:41 | 21.83 | 13.19 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.178863E+11 | 69741.82 | 21-MAY-08:21 | 23.35 | 10.21 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.321535E+11 | 68097.96 | 08-JUN-02:51 | 24.40 | 13.77 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.316113E+11 | 63693.49 | 16-JUL-04:51 | 25.00 | 15.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.284024E+11 | 66669.88 | 27-AUG-23:31 | 24.63 | 14.47 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.203301E+11 | 70389.95 | 11-SEP-19:11 | 23.30 | 11.87 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.601053E+10 | 70387.30 | 01-OCT-09:21 | 23.30 | 13.19 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.209976E+09 | 6783.42 | 22-NOV-07:10 | 5.97 | 0.46 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.262430E+09 | 2464.29 | 19-DEC-09:30 | 1.40 | -3.7 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.142284E+12 | 0.00 | ||||||||
Minimum of Months | 0.150331E+09 | 2004.92 | 1.40 | -3.7 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.321535E+11 | 70389.95 | 25.00 | 15.00 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 | 3.91 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 | 1.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.83 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.10 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227113E+10 | 30132.83 | 27-JAN-06:01 | -3.1 |
February | 0.163674E+10 | 30142.39 | 02-FEB-06:01 | -3.5 |
March | 0.102043E+10 | 30148.33 | 02-MAR-06:01 | -3.5 |
April | 0.152741E+09 | 8306.79 | 01-APR-05:03 | 11.10 |
May | 31728199.46 | 2844.35 | 19-MAY-06:05 | 20.28 |
June | 5110157.63 | 2939.07 | 01-JUN-06:05 | 19.37 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 2973136.92 | 2558.52 | 25-AUG-06:05 | 19.18 |
September | 8374374.86 | 1547.54 | 25-SEP-06:04 | 10.55 |
October | 89501520.92 | 2034.32 | 23-OCT-06:03 | 12.80 |
November | 0.795969E+09 | 30127.81 | 28-NOV-06:01 | 1.02 |
December | 0.241738E+10 | 30235.89 | 27-DEC-06:12 | -3.7 |
Annual Sum or Average | 0.843208E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.241738E+10 | 30235.89 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.695111E+10 | 98598.01 | 28-JAN-06:52 | -3.3 |
February | 0.440496E+10 | 95542.44 | 02-FEB-05:12 | -2.6 |
March | 0.232072E+10 | 97815.42 | 02-MAR-06:01 | -3.5 |
April | 0.628449E+09 | 3991.09 | 17-APR-07:00 | 11.70 |
May | 0.263661E+09 | 3777.05 | 27-MAY-06:25 | 18.05 |
June | 35370404.58 | 3543.42 | 30-JUN-06:13 | 19.80 |
July | 8588891.78 | 3384.15 | 27-JUL-06:05 | 23.90 |
August | 71818085.65 | 3589.32 | 23-AUG-06:12 | 20.57 |
September | 0.174759E+09 | 3590.43 | 30-SEP-06:10 | 8.95 |
October | 0.412100E+09 | 4075.44 | 13-OCT-07:00 | 14.40 |
November | 0.196012E+10 | 96404.67 | 28-NOV-05:03 | -0.3 |
December | 0.872059E+10 | 98557.73 | 31-DEC-06:52 | -2.8 |
Annual Sum or Average | 0.259522E+11 | |||
Minimum of Months | 8588891.78 | 3384.15 | -3.5 | |
Maximum of Months | 0.872059E+10 | 98598.01 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245702E+09 | 24194.26 | 28-JAN-06:00 | -3.3 |
February | 93150923.99 | 12193.95 | 02-FEB-07:00 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.144003E+10 | 36338.43 | 31-DEC-06:52 | -2.8 |
Annual Sum or Average | 0.177888E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.144003E+10 | 36338.43 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198816E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 473063.01 | 0.166908E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2632337.65 | 0.167506E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163715E+09 | 0.913157E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419301E+09 | 0.479632E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815053E+09 | 0.187755E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635366E+09 | 0.147264E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543205E+09 | 0.241445E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347353E+09 | 0.330541E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79490900.94 | 0.906200E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159388E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200319E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.300659E+10 | 0.121354E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147264E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815053E+09 | 0.200319E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913695E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15222310.59 | 0.798283E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3514.48 | 0.887155E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489907E+09 | 0.659188E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166402E+10 | 0.429601E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345108E+10 | 0.167428E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248704E+10 | 0.139246E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195509E+10 | 0.192945E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528821E+09 | 0.226721E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140462E+09 | 0.649139E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845871E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820291E+10 |
Annual Sum or Average | 0.136656E+12 | 0.107317E+11 | 0.672956E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139246E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345108E+10 | 0.913695E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55657188.76 | 0.211567E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685725E+09 | 0.191308E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399661E+09 | 0.244871E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914853E+09 | 0.226791E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79776737.61 | 0.209130E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173835E+09 | 0.109816E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86694075.27 | 0.975440E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38678480.38 | 0.113305E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780106.33 | 0.112436E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12710304.11 | 0.238028E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9775776.00 | 0.243302E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44211989.00 | 0.180013E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.250236E+10 | 0.217811E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780106.33 | 0.975440E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914853E+09 | 0.244871E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9352.04 | 27-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 19-FEB-14:00 | 9056.71 | 03-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.88 | 21-MAR-16:10 | 8145.12 | 02-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2915.37 | 21-APR-16:10 | 5865.74 | 12-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3852.80 | 19-MAY-16:10 | 4852.85 | 02-MAY-06:02 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5008.13 | 05-JUN-17:00 | 2260.81 | 29-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4929.30 | 03-JUL-17:00 | 2003.50 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4398.93 | 07-AUG-16:10 | 2386.45 | 31-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3011.58 | 19-SEP-16:10 | 4447.85 | 25-SEP-06:02 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.17 | 05-OCT-16:10 | 5431.28 | 25-OCT-06:03 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7476.35 | 28-NOV-07:03 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9026.08 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.50 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5008.13 | 9352.04 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 17851.09 | 25-JAN-23:05 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.15 | 20-FEB-16:00 | 24828.35 | 08-FEB-17:55 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 03-MAR-16:00 | 20023.96 | 27-MAR-06:55 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11697.46 | 21-APR-15:10 | 23786.19 | 22-APR-07:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10100.82 | 19-MAY-17:00 | 12151.03 | 01-MAY-08:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 05-JUN-17:00 | 9690.00 | 28-JUN-02:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11467.32 | 03-JUL-17:00 | 6728.94 | 18-JUL-21:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.05 | 26-AUG-15:10 | 7855.71 | 14-AUG-01:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.32 | 18-SEP-17:00 | 7357.74 | 23-SEP-17:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.03 | 01-OCT-15:00 | 12433.17 | 06-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14873.01 | 10-NOV-16:03 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 20108.77 | 18-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6728.94 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 24828.35 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8261.95 | 03-JAN-17:00 | 30984.18 | 05-JAN-09:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10875.23 | 06-FEB-22:00 | 49592.05 | 09-FEB-01:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16750.12 | 03-MAR-16:00 | 51732.19 | 27-MAR-07:10 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18428.06 | 01-APR-15:00 | 71600.91 | 22-APR-07:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2292.42 | 14-MAY-14:53 | 43555.91 | 01-MAY-10:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2687.63 | 02-JUN-16:00 | 36999.94 | 28-JUN-02:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3464.40 | 02-JUL-21:53 | 27319.43 | 08-JUL-14:52 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.77 | 07-AUG-16:00 | 29760.61 | 14-AUG-01:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.04 | 17-SEP-10:55 | 21381.58 | 23-SEP-16:55 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1428.59 | 01-OCT-14:55 | 47433.51 | 06-OCT-09:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.10 | 23-NOV-16:00 | 38727.60 | 15-NOV-09:00 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3664.59 | 10-DEC-15:00 | 38751.82 | 18-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 273.04 | 21381.58 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18428.06 | 71600.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1309.11 | 12-JAN-15:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.54 |
February | 2551.70 | 21-FEB-17:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.29 |
March | 4083.57 | 16-MAR-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.05 |
April | 26363.51 | 28-APR-05:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.54 |
May | 30156.04 | 17-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.77 |
June | 29550.54 | 13-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.24 |
July | 23085.90 | 11-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.52 |
August | 25656.09 | 23-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.92 |
September | 29934.39 | 30-SEP-05:02 | 435.11 | 3518.66 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.16 |
October | 27581.71 | 20-OCT-05:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.40 |
November | 5245.26 | 03-NOV-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
December | 1151.98 | 16-DEC-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1151.98 | 290.07 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | |
Maximum of Months | 30156.04 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2004.92 | 27-JAN-10:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3897.77 |
February | 6886.32 | 21-FEB-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2296.09 |
March | 7869.15 | 20-MAR-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3737.67 |
April | 70322.39 | 30-APR-09:41 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.98 |
May | 69741.82 | 21-MAY-08:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.47 |
June | 68097.96 | 08-JUN-02:51 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.96 |
July | 63693.49 | 16-JUL-04:51 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.31 |
August | 66669.88 | 27-AUG-23:31 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.96 |
September | 70389.95 | 11-SEP-19:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.01 |
October | 70387.30 | 01-OCT-09:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6783.42 | 22-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4481.76 |
December | 2464.29 | 19-DEC-09:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2004.92 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70389.95 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4481.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8565.16 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16245.48 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11399.49 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5234.81 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5290.92 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9724.57 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2518.63 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9397.74 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3787.73 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13236.69 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | |
Maximum of Months | 0.00 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16245.48 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.715583E+11 | 52862.77 | 28-JAN-13:30 | 0.178654E+11 | 81559.88 | 28-JAN-06:19 |
February | 0.647231E+11 | 53581.70 | 21-FEB-15:00 | 0.120612E+11 | 64189.38 | 02-FEB-06:10 |
March | 0.734925E+11 | 54155.93 | 14-MAR-14:00 | 0.819944E+10 | 48856.55 | 02-MAR-06:10 |
April | 0.710367E+11 | 67553.37 | 21-APR-14:39 | 0.589472E+10 | 7788.10 | 11-APR-06:10 |
May | 0.805637E+11 | 71849.21 | 19-MAY-13:00 | 0.602839E+10 | 4167.60 | 27-MAY-05:49 |
June | 0.888529E+11 | 76712.50 | 15-JUN-14:00 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.889716E+11 | 75558.79 | 26-JUL-14:30 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.897767E+11 | 73760.07 | 08-AUG-14:00 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.809136E+11 | 71023.62 | 01-SEP-14:00 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.732050E+11 | 70008.78 | 03-OCT-13:50 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.684615E+11 | 55484.24 | 24-NOV-16:00 | 0.789379E+10 | 43400.42 | 28-NOV-06:10 |
December | 0.718108E+11 | 56584.58 | 14-DEC-16:00 | 0.223343E+11 | 87719.78 | 27-DEC-06:19 |
Annual Sum or Average | 0.923366E+12 | 0.110020E+12 | ||||
Minimum of Months | 0.647231E+11 | 52862.77 | 0.583200E+10 | 2250.00 | ||
Maximum of Months | 0.897767E+11 | 76712.50 | 0.223343E+11 | 87719.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.121347E+11 | 0.115358E+11 | 0.00 | 0.555782E+10 | 0.00 | 0.00 | 572.78 | 0.00 | 0.00 | 0.00 | 0.222659E+10 | 0.00 |
February | 0.366966E+11 | 0.103810E+11 | 0.105871E+11 | 0.00 | 0.502009E+10 | 0.00 | 0.00 | 17416085.27 | 0.00 | 0.00 | 0.00 | 0.202090E+10 | 0.00 |
March | 0.423649E+11 | 0.106686E+11 | 0.123357E+11 | 0.00 | 0.575644E+10 | 0.00 | 0.00 | 0.121937E+09 | 0.00 | 0.00 | 0.00 | 0.224501E+10 | 0.00 |
April | 0.397216E+11 | 0.949469E+10 | 0.114862E+11 | 0.00 | 0.555671E+10 | 0.00 | 0.00 | 0.269632E+10 | 0.00 | 0.00 | 0.00 | 0.208120E+10 | 0.00 |
May | 0.412341E+11 | 0.909868E+10 | 0.119357E+11 | 0.00 | 0.747133E+10 | 0.00 | 0.00 | 0.873384E+10 | 0.00 | 0.00 | 0.00 | 0.209003E+10 | 0.00 |
June | 0.408524E+11 | 0.844810E+10 | 0.118862E+11 | 0.00 | 0.966700E+10 | 0.00 | 0.00 | 0.160123E+11 | 0.00 | 0.00 | 0.00 | 0.198697E+10 | 0.00 |
July | 0.401034E+11 | 0.888654E+10 | 0.115358E+11 | 0.00 | 0.945161E+10 | 0.00 | 0.00 | 0.170129E+11 | 0.00 | 0.00 | 0.00 | 0.198147E+10 | 0.00 |
August | 0.423649E+11 | 0.949469E+10 | 0.123357E+11 | 0.00 | 0.912421E+10 | 0.00 | 0.00 | 0.144317E+11 | 0.00 | 0.00 | 0.00 | 0.202552E+10 | 0.00 |
September | 0.397216E+11 | 0.995669E+10 | 0.114862E+11 | 0.00 | 0.730617E+10 | 0.00 | 0.00 | 0.104754E+11 | 0.00 | 0.00 | 0.00 | 0.196749E+10 | 0.00 |
October | 0.401034E+11 | 0.111541E+11 | 0.115358E+11 | 0.00 | 0.559037E+10 | 0.00 | 0.00 | 0.275122E+10 | 0.00 | 0.00 | 0.00 | 0.207011E+10 | 0.00 |
November | 0.385909E+11 | 0.115171E+11 | 0.110862E+11 | 0.00 | 0.512404E+10 | 0.00 | 0.00 | 78003392.87 | 0.00 | 0.00 | 0.00 | 0.206522E+10 | 0.00 |
December | 0.401034E+11 | 0.123139E+11 | 0.115358E+11 | 0.00 | 0.566007E+10 | 0.00 | 0.00 | 697.57 | 0.00 | 0.00 | 0.00 | 0.219774E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123549E+12 | 0.139282E+12 | 0.812859E+11 | 0.00 | 0.723311E+11 | 0.249583E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.844810E+10 | 0.105871E+11 | 0.00 | 0.502009E+10 | 0.00 | 0.00 | 572.78 | 0.00 | 0.00 | 0.00 | 0.196749E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.123139E+11 | 0.123357E+11 | 0.00 | 0.966700E+10 | 0.00 | 0.00 | 0.170129E+11 | 0.00 | 0.00 | 0.00 | 0.224501E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.178654E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120612E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.819944E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.589472E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602839E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.789379E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223343E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110020E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.223343E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5582.83 | 27-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5582.83 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5345.23 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 7650.53 | 19-APR-15:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7650.53 | 08-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7650.53 | 02-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7650.53 | 01-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7650.53 | 01-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7650.53 | 06-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7650.53 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5345.23 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5582.83 | 26-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5345.23 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 7650.53 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.15 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 2052.98 | 31-JAN-12:00 | 0.00 |
February | 723.95 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2051.69 | 03-FEB-12:00 | 0.00 |
March | 1466.24 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1907.93 | 08-MAR-12:00 | 0.00 |
April | 14304.66 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1797.62 | 01-APR-11:09 | 0.00 |
May | 17729.49 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1773.03 | 01-MAY-11:09 | 0.00 |
June | 23736.00 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1748.07 | 01-JUN-11:09 | 0.00 |
July | 20495.99 | 27-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1730.94 | 01-JUL-11:09 | 0.00 |
August | 21556.78 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1731.13 | 31-AUG-11:30 | 0.00 |
September | 16226.71 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1748.32 | 30-SEP-11:30 | 0.00 |
October | 15022.81 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1773.57 | 31-OCT-11:30 | 0.00 |
November | 1786.66 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1799.15 | 30-NOV-12:39 | 0.00 |
December | 0.05 | 16-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1911.03 | 22-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.05 | 0.00 | 0.00 | 0.00 | 1730.94 | 0.00 | ||
Maximum of Months | 23736.00 | 0.00 | 0.00 | 0.00 | 2052.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52862.77 | 28-JAN-13:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5345.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53581.70 | 21-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5345.23 | 0.00 | 0.00 | 723.95 | 0.00 |
March | 54155.93 | 14-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5345.23 | 0.00 | 0.00 | 1306.05 | 0.00 |
April | 67553.37 | 21-APR-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 12423.00 | 0.00 |
May | 71849.21 | 19-MAY-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 16768.19 | 0.00 |
June | 76712.50 | 15-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 21618.67 | 0.00 |
July | 75558.79 | 26-JUL-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 20476.67 | 0.00 |
August | 73760.07 | 08-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 18677.83 | 0.00 |
September | 71023.62 | 01-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 15936.11 | 0.00 |
October | 70008.78 | 03-OCT-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7650.53 | 0.00 | 0.00 | 14932.97 | 0.00 |
November | 55484.24 | 24-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5345.23 | 0.00 | 0.00 | 0.02 | 0.00 |
December | 56584.58 | 14-DEC-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5345.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52862.77 | 31660.41 | 10112.62 | 0.00 | 0.00 | 5345.23 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76712.50 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 7650.53 | 0.00 | 0.00 | 21618.67 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 81559.88 | 28-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 64189.38 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 48856.55 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 7788.10 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4167.60 | 27-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 43400.42 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 87719.78 | 27-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 87719.78 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.01 | 6.50 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.67 | 20.04 | 4.67 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.83 | 20.25 | 2.83 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.49 | 0.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.50 | 0.67 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.53 | 2.83 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.35 | 5.83 | 24.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.88 | 3.83 | 24.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.41 | 2.00 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.60 | 0.50 | 24.60 |
November | 1.83 | 20.20 | 1.83 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 19.94 | 6.00 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.33 | 20.06 | 22.33 | 20.06 | 18.50 | 25.57 | 15.67 | 24.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.49 | 6.50 | 20.49 | 6.50 | 26.50 | 5.83 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 14.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.00 | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.52 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.68 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.79 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 27.76 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 0.00 | 0.00 |
November | 4.67 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40.17 | 14.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.17 | 14.73 | 0.00 | 151.00 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.17 | 14.83 | 0.00 | 0.00 | 43.67 | 27.79 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.71 | 215.17 | 21.20 | 215.17 | 21.20 |
February | 276.00 | 22.12 | 152.17 | 21.22 | 152.17 | 21.22 |
March | 324.00 | 22.78 | 107.83 | 21.24 | 107.83 | 21.24 |
April | 189.50 | 23.59 | 41.50 | 23.30 | 9.33 | 21.23 |
May | 43.00 | 23.76 | 166.83 | 23.90 | 0.17 | 24.67 |
June | 3.67 | 23.95 | 278.50 | 23.89 | 2.00 | 24.48 |
July | 43.33 | 23.97 | 300.00 | 23.91 | 43.33 | 23.97 |
August | 18.00 | 24.02 | 320.33 | 23.90 | 18.00 | 24.02 |
September | 21.50 | 23.93 | 275.83 | 23.90 | 19.83 | 23.95 |
October | 84.83 | 23.67 | 126.83 | 23.89 | 4.17 | 23.89 |
November | 268.00 | 22.83 | 76.83 | 21.24 | 76.17 | 21.22 |
December | 300.00 | 21.70 | 220.17 | 21.22 | 220.17 | 21.22 |
Annual Sum or Average | 1871.83 | 22.54 | 2282.00 | 22.98 | 868.33 | 21.50 |
Minimum of Months | 3.67 | 21.70 | 41.50 | 21.20 | 0.17 | 21.20 |
Maximum of Months | 324.00 | 24.02 | 320.33 | 23.91 | 220.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 2056.20 | 572.78 | 3.00 | 2056.20 | 0.00 | 0.00 | 0.00 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 0.54 | 03-JAN-15:00 | 0.54 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 0.15 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 63510851.36 | 17416085.27 | 26.17 | 63510851.36 | 0.00 | 0.00 | 0.15 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 | 2658.56 | 21-FEB-16:00 | 2658.56 | 21-FEB-16:00 | 0.00 | 21-FEB-14:40 | 723.95 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 |
March | 0.448437E+09 | 0.121937E+09 | 104.00 | 0.448437E+09 | 160.54 | 0.00 | 0.30 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 5433.24 | 14-MAR-16:00 | 5433.24 | 14-MAR-16:00 | 0.02 | 11-MAR-13:10 | 1466.24 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.340547E+10 | 0.952103E+09 | 200.74 | 0.339649E+10 | 8978613.72 | 0.00 | 1.00 | 20-APR-05:01 | 0.00 | 01-APR-00:10 | 20601.43 | 29-APR-05:01 | 20432.31 | 21-APR-05:03 | 2174.71 | 29-APR-05:02 | 4880.20 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.793029E+10 | 0.223159E+10 | 276.03 | 0.772605E+10 | 0.204233E+09 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 22196.92 | 23-MAY-05:01 | 21236.08 | 30-MAY-05:41 | 7866.14 | 25-MAY-05:02 | 5252.93 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.115607E+11 | 0.340836E+10 | 307.79 | 0.110832E+11 | 0.477581E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 23018.12 | 28-JUN-05:01 | 21625.85 | 17-JUN-05:01 | 8646.26 | 28-JUN-05:15 | 5613.77 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.132992E+11 | 0.372348E+10 | 309.92 | 0.109888E+11 | 0.231042E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 26331.86 | 22-JUL-05:01 | 22252.01 | 03-JUL-05:01 | 15278.27 | 21-JUL-05:06 | 6124.66 | 16-JUL-18:51 | 0.00 | 01-JUL-00:05 |
August | 0.122758E+11 | 0.342682E+10 | 319.42 | 0.106731E+11 | 0.160273E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 25411.34 | 03-AUG-05:01 | 22849.43 | 13-AUG-19:11 | 12124.27 | 02-AUG-05:10 | 6017.27 | 13-AUG-13:01 | 0.00 | 01-AUG-00:10 |
September | 0.990519E+10 | 0.272622E+10 | 272.40 | 0.867057E+10 | 0.123462E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 24781.85 | 22-SEP-05:01 | 22528.27 | 04-SEP-17:01 | 12462.90 | 22-SEP-06:00 | 6061.02 | 03-SEP-13:21 | 0.00 | 01-SEP-00:10 |
October | 0.401459E+10 | 0.108052E+10 | 204.01 | 0.364346E+10 | 0.371124E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 23435.14 | 04-OCT-05:01 | 21715.48 | 02-OCT-05:01 | 10213.76 | 04-OCT-05:15 | 5511.58 | 04-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.289282E+09 | 78000683.96 | 78.97 | 0.287630E+09 | 1652317.14 | 0.00 | 0.35 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 6764.15 | 03-NOV-16:00 | 6764.15 | 03-NOV-16:00 | 218.03 | 03-NOV-12:50 | 1786.66 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 2504.19 | 697.57 | 6.00 | 2504.19 | 0.00 | 0.00 | 0.00 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 | 0.19 | 16-DEC-15:00 | 0.19 | 16-DEC-15:00 | 0.00 | 16-DEC-15:10 | 0.05 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.631925E+11 | 0.177665E+11 | 2108.44 | 0.569812E+11 | 0.621134E+10 | 0.00 | ||||||||||||||
Minimum of Months | 2056.20 | 572.78 | 3.00 | 2056.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.19 | 0.00 | 0.05 | 0.00 | |||||||
Maximum of Months | 0.132992E+11 | 0.372348E+10 | 319.42 | 0.110832E+11 | 0.231042E+10 | 0.00 | 1.00 | 0.00 | 26331.86 | 22849.43 | 15278.27 | 6124.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.550416E+10 | 0.174422E+10 | 127.62 | 0.549042E+10 | 13742559.79 | 0.00 | 1.00 | 09-APR-14:21 | 0.00 | 01-APR-00:10 | 68905.72 | 30-APR-09:41 | 67916.47 | 30-APR-12:21 | 6589.79 | 30-APR-09:41 | 18890.46 | 30-APR-12:21 | 0.00 | 01-APR-00:10 |
May | 0.203981E+11 | 0.650225E+10 | 289.60 | 0.198711E+11 | 0.527028E+09 | 0.00 | 1.00 | 07-MAY-11:01 | 0.00 | 01-MAY-00:10 | 76578.00 | 28-MAY-09:02 | 67437.10 | 29-MAY-20:21 | 23438.60 | 28-MAY-08:41 | 20531.66 | 21-MAY-15:42 | 0.00 | 01-MAY-00:10 |
June | 0.379888E+11 | 0.126040E+11 | 405.43 | 0.367119E+11 | 0.127696E+10 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:10 | 80208.99 | 19-JUN-17:56 | 68752.29 | 24-JUN-18:21 | 31206.17 | 19-JUN-18:00 | 21282.03 | 18-JUN-16:02 | 0.00 | 01-JUN-00:10 |
July | 0.420657E+11 | 0.132894E+11 | 414.00 | 0.358555E+11 | 0.621021E+10 | 0.00 | 1.00 | 01-JUL-01:11 | 0.00 | 01-JUL-00:10 | 85423.22 | 21-JUL-20:41 | 67063.63 | 24-JUL-18:23 | 42801.63 | 21-JUL-20:48 | 21929.63 | 02-JUL-15:52 | 0.00 | 01-JUL-00:05 |
August | 0.348903E+11 | 0.110049E+11 | 384.31 | 0.312541E+11 | 0.363621E+10 | 0.00 | 1.00 | 01-AUG-00:21 | 0.00 | 01-AUG-00:15 | 82463.28 | 02-AUG-00:21 | 68645.10 | 25-AUG-21:50 | 39102.93 | 01-AUG-22:42 | 21322.78 | 06-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.252962E+11 | 0.774922E+10 | 279.36 | 0.223997E+11 | 0.289646E+10 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:10 | 80334.70 | 03-SEP-08:40 | 68882.06 | 10-SEP-20:00 | 35834.89 | 03-SEP-07:35 | 20549.82 | 10-SEP-10:31 | 0.00 | 01-SEP-00:10 |
October | 0.548340E+10 | 0.167070E+10 | 137.38 | 0.491470E+10 | 0.568701E+09 | 0.00 | 1.00 | 01-OCT-09:21 | 0.00 | 01-OCT-00:10 | 79279.45 | 03-OCT-17:51 | 68589.14 | 22-OCT-14:01 | 27462.57 | 03-OCT-17:59 | 20297.03 | 03-OCT-17:51 | 0.00 | 01-OCT-00:10 |
November | 8979.64 | 2708.91 | 3.17 | 8294.99 | 684.64 | 0.00 | 0.00 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1.36 | 03-NOV-14:00 | 1.25 | 03-NOV-14:00 | 0.11 | 03-NOV-14:00 | 0.41 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171627E+12 | 0.545646E+11 | 2040.87 | 0.156497E+12 | 0.151293E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.420657E+11 | 0.132894E+11 | 414.00 | 0.367119E+11 | 0.621021E+10 | 0.00 | 1.00 | 0.00 | 85423.22 | 68882.06 | 42801.63 | 21929.63 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 129.37 | 72.86 | 56.51 | 111.60 | 119.97 | 0.00 | 0.00 | 744.00 |
February | 145.69 | 77.26 | 68.43 | 134.22 | 107.99 | 0.00 | 0.00 | 672.00 |
March | 199.04 | 106.75 | 92.29 | 202.15 | 97.77 | 0.00 | 0.00 | 744.00 |
April | 228.55 | 123.38 | 105.16 | 253.86 | 71.44 | 0.00 | 0.00 | 720.00 |
May | 246.07 | 131.59 | 114.49 | 295.15 | 53.24 | 0.00 | 0.00 | 744.00 |
June | 240.00 | 129.01 | 110.98 | 313.35 | 33.12 | 0.00 | 0.00 | 720.00 |
July | 213.18 | 106.09 | 107.09 | 276.43 | 29.75 | 0.00 | 0.00 | 744.00 |
August | 206.01 | 104.92 | 101.09 | 259.19 | 38.36 | 0.00 | 0.00 | 744.00 |
September | 211.38 | 118.03 | 93.35 | 256.29 | 64.55 | 0.00 | 0.00 | 720.00 |
October | 181.40 | 105.86 | 75.54 | 194.86 | 88.41 | 0.00 | 0.00 | 744.00 |
November | 151.11 | 91.59 | 59.52 | 139.11 | 118.64 | 0.00 | 0.00 | 720.00 |
December | 122.52 | 66.48 | 56.04 | 98.48 | 135.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.69 | 102.89 | 86.80 | 211.53 | 79.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 122.52 | 66.48 | 56.04 | 98.48 | 29.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 246.07 | 131.59 | 114.49 | 313.35 | 135.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 129.37 | 72.86 | 56.51 | 111.60 | 119.97 | 0.00 | 0.00 | 744.00 |
February | 145.69 | 77.26 | 68.43 | 134.22 | 107.99 | 0.00 | 0.00 | 672.00 |
March | 199.04 | 106.75 | 92.29 | 202.15 | 97.77 | 0.00 | 0.00 | 744.00 |
April | 228.55 | 123.38 | 105.16 | 253.86 | 71.44 | 0.00 | 0.00 | 720.00 |
May | 246.07 | 131.59 | 114.49 | 295.15 | 53.24 | 0.00 | 0.00 | 744.00 |
June | 240.00 | 129.01 | 110.98 | 313.35 | 33.12 | 0.00 | 0.00 | 720.00 |
July | 213.18 | 106.09 | 107.09 | 276.43 | 29.75 | 0.00 | 0.00 | 744.00 |
August | 206.01 | 104.92 | 101.09 | 259.19 | 38.36 | 0.00 | 0.00 | 744.00 |
September | 211.38 | 118.03 | 93.35 | 256.29 | 64.55 | 0.00 | 0.00 | 720.00 |
October | 181.40 | 105.86 | 75.54 | 194.86 | 88.41 | 0.00 | 0.00 | 744.00 |
November | 151.11 | 91.59 | 59.52 | 139.11 | 118.64 | 0.00 | 0.00 | 720.00 |
December | 122.52 | 66.48 | 56.04 | 98.48 | 135.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.69 | 102.89 | 86.80 | 211.53 | 79.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 122.52 | 66.48 | 56.04 | 98.48 | 29.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 246.07 | 131.59 | 114.49 | 313.35 | 135.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.79 | 0.00 | 26.79 | 7.82 | 73.38 | 0.00 | 0.00 | 744.00 |
February | 32.71 | 0.00 | 32.71 | 15.10 | 65.38 | 0.00 | 0.00 | 672.00 |
March | 42.82 | 0.00 | 42.82 | 26.02 | 58.80 | 0.00 | 0.00 | 744.00 |
April | 49.58 | 0.51 | 49.06 | 40.04 | 41.89 | 0.00 | 0.00 | 720.00 |
May | 58.60 | 4.21 | 54.39 | 58.15 | 29.97 | 0.00 | 0.00 | 744.00 |
June | 62.03 | 7.36 | 54.66 | 76.21 | 18.64 | 0.00 | 0.00 | 720.00 |
July | 57.25 | 5.22 | 52.02 | 70.22 | 16.83 | 0.00 | 0.00 | 744.00 |
August | 48.84 | 1.22 | 47.62 | 57.83 | 21.86 | 0.00 | 0.00 | 744.00 |
September | 42.43 | 0.04 | 42.39 | 44.71 | 37.73 | 0.00 | 0.00 | 720.00 |
October | 35.19 | 0.00 | 35.19 | 23.88 | 53.02 | 0.00 | 0.00 | 744.00 |
November | 28.41 | 0.00 | 28.41 | 8.76 | 72.75 | 0.00 | 0.00 | 720.00 |
December | 26.58 | 0.00 | 26.58 | 5.48 | 83.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.65 | 1.56 | 41.10 | 36.29 | 47.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 26.58 | 0.00 | 26.58 | 5.48 | 16.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 62.03 | 7.36 | 54.66 | 76.21 | 83.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.79 | 0.00 | 26.79 | 7.82 | 73.38 | 0.00 | 0.00 | 744.00 |
February | 32.71 | 0.00 | 32.71 | 15.10 | 65.38 | 0.00 | 0.00 | 672.00 |
March | 42.82 | 0.00 | 42.82 | 26.02 | 58.80 | 0.00 | 0.00 | 744.00 |
April | 49.57 | 0.51 | 49.06 | 40.04 | 41.89 | 0.00 | 0.00 | 720.00 |
May | 58.59 | 4.21 | 54.39 | 58.15 | 29.97 | 0.00 | 0.00 | 744.00 |
June | 62.02 | 7.36 | 54.66 | 76.21 | 18.64 | 0.00 | 0.00 | 720.00 |
July | 57.25 | 5.22 | 52.02 | 70.21 | 16.83 | 0.00 | 0.00 | 744.00 |
August | 48.84 | 1.22 | 47.62 | 57.83 | 21.86 | 0.00 | 0.00 | 744.00 |
September | 42.43 | 0.04 | 42.39 | 44.71 | 37.73 | 0.00 | 0.00 | 720.00 |
October | 35.19 | 0.00 | 35.19 | 23.88 | 53.02 | 0.00 | 0.00 | 744.00 |
November | 28.41 | 0.00 | 28.41 | 8.76 | 72.74 | 0.00 | 0.00 | 720.00 |
December | 26.58 | 0.00 | 26.58 | 5.48 | 83.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.65 | 1.56 | 41.09 | 36.29 | 47.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 26.58 | 0.00 | 26.58 | 5.48 | 16.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 62.02 | 7.36 | 54.66 | 76.21 | 83.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.18 | 49.25 | 20.93 | 87.51 | 71.11 | 1.33 | 0.00 | 744.00 |
February | 89.79 | 63.52 | 26.28 | 114.64 | 69.45 | 6.17 | 0.00 | 672.00 |
March | 125.31 | 88.44 | 36.86 | 162.51 | 71.07 | 0.00 | 0.00 | 744.00 |
April | 155.78 | 115.46 | 40.32 | 205.25 | 64.59 | 0.00 | 0.00 | 720.00 |
May | 171.77 | 127.56 | 44.21 | 228.98 | 62.26 | 0.00 | 0.00 | 744.00 |
June | 181.41 | 140.58 | 40.83 | 248.10 | 50.69 | 0.00 | 0.00 | 720.00 |
July | 156.99 | 113.08 | 43.91 | 217.09 | 40.82 | 0.00 | 0.00 | 744.00 |
August | 146.77 | 105.76 | 41.01 | 199.81 | 49.12 | 0.00 | 0.00 | 744.00 |
September | 134.41 | 100.46 | 33.96 | 180.56 | 66.27 | 0.00 | 0.00 | 720.00 |
October | 101.46 | 73.67 | 27.79 | 129.07 | 72.99 | 0.00 | 0.00 | 744.00 |
November | 79.55 | 59.07 | 20.48 | 96.25 | 82.61 | 0.00 | 0.00 | 720.00 |
December | 65.08 | 43.37 | 21.72 | 78.07 | 81.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.32 | 90.08 | 33.24 | 162.49 | 65.18 | 7.50 | 0.00 | 8760.00 |
Minimum of Months | 65.08 | 43.37 | 20.48 | 78.07 | 40.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 181.41 | 140.58 | 44.21 | 248.10 | 82.61 | 6.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.346508E+09 | 0.195157E+09 | 0.151352E+09 | 0.298910E+09 | 0.321317E+09 |
February | 0.352455E+09 | 0.186915E+09 | 0.165540E+09 | 0.324706E+09 | 0.261258E+09 |
March | 0.533111E+09 | 0.285927E+09 | 0.247184E+09 | 0.541444E+09 | 0.261856E+09 |
April | 0.592390E+09 | 0.319811E+09 | 0.272579E+09 | 0.657995E+09 | 0.185164E+09 |
May | 0.659083E+09 | 0.352438E+09 | 0.306645E+09 | 0.790524E+09 | 0.142588E+09 |
June | 0.622071E+09 | 0.334402E+09 | 0.287668E+09 | 0.812199E+09 | 85858962.29 |
July | 0.570970E+09 | 0.284147E+09 | 0.286823E+09 | 0.740384E+09 | 79694923.06 |
August | 0.551771E+09 | 0.281006E+09 | 0.270765E+09 | 0.694205E+09 | 0.102755E+09 |
September | 0.547895E+09 | 0.305925E+09 | 0.241970E+09 | 0.664296E+09 | 0.167308E+09 |
October | 0.485863E+09 | 0.283549E+09 | 0.202314E+09 | 0.521923E+09 | 0.236805E+09 |
November | 0.391667E+09 | 0.237393E+09 | 0.154274E+09 | 0.360583E+09 | 0.307516E+09 |
December | 0.328171E+09 | 0.178064E+09 | 0.150106E+09 | 0.263772E+09 | 0.363789E+09 |
Annual Sum or Average | 0.598196E+10 | 0.324474E+10 | 0.273722E+10 | 0.667094E+10 | 0.251591E+10 |
Minimum of Months | 0.328171E+09 | 0.178064E+09 | 0.150106E+09 | 0.263772E+09 | 79694923.06 |
Maximum of Months | 0.659083E+09 | 0.352438E+09 | 0.306645E+09 | 0.812199E+09 | 0.363789E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.346508E+09 | 0.195157E+09 | 0.151352E+09 | 0.298910E+09 | 0.321317E+09 |
February | 0.352455E+09 | 0.186915E+09 | 0.165540E+09 | 0.324706E+09 | 0.261258E+09 |
March | 0.533111E+09 | 0.285927E+09 | 0.247184E+09 | 0.541444E+09 | 0.261856E+09 |
April | 0.592390E+09 | 0.319811E+09 | 0.272579E+09 | 0.657995E+09 | 0.185164E+09 |
May | 0.659083E+09 | 0.352438E+09 | 0.306645E+09 | 0.790524E+09 | 0.142588E+09 |
June | 0.622071E+09 | 0.334402E+09 | 0.287668E+09 | 0.812199E+09 | 85858962.29 |
July | 0.570970E+09 | 0.284147E+09 | 0.286823E+09 | 0.740384E+09 | 79694923.06 |
August | 0.551771E+09 | 0.281006E+09 | 0.270765E+09 | 0.694205E+09 | 0.102755E+09 |
September | 0.547895E+09 | 0.305925E+09 | 0.241970E+09 | 0.664296E+09 | 0.167308E+09 |
October | 0.485863E+09 | 0.283549E+09 | 0.202314E+09 | 0.521923E+09 | 0.236805E+09 |
November | 0.391667E+09 | 0.237393E+09 | 0.154274E+09 | 0.360583E+09 | 0.307516E+09 |
December | 0.328171E+09 | 0.178064E+09 | 0.150106E+09 | 0.263772E+09 | 0.363789E+09 |
Annual Sum or Average | 0.598196E+10 | 0.324474E+10 | 0.273722E+10 | 0.667094E+10 | 0.251591E+10 |
Minimum of Months | 0.328171E+09 | 0.178064E+09 | 0.150106E+09 | 0.263772E+09 | 79694923.06 |
Maximum of Months | 0.659083E+09 | 0.352438E+09 | 0.306645E+09 | 0.812199E+09 | 0.363789E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71750028.63 | 0.00 | 71750028.63 | 20946821.76 | 0.196534E+09 |
February | 79135580.40 | 0.00 | 79135580.40 | 36534796.78 | 0.158161E+09 |
March | 0.114694E+09 | 11836.40 | 0.114683E+09 | 69703999.83 | 0.157490E+09 |
April | 0.128499E+09 | 1331165.65 | 0.127168E+09 | 0.103785E+09 | 0.108576E+09 |
May | 0.156944E+09 | 11271338.55 | 0.145673E+09 | 0.155761E+09 | 80281811.30 |
June | 0.160772E+09 | 19085875.03 | 0.141686E+09 | 0.197533E+09 | 48327454.80 |
July | 0.153332E+09 | 13989668.81 | 0.139342E+09 | 0.188065E+09 | 45082018.56 |
August | 0.130823E+09 | 3266175.99 | 0.127557E+09 | 0.154892E+09 | 58543169.26 |
September | 0.109983E+09 | 97001.69 | 0.109886E+09 | 0.115880E+09 | 97793098.94 |
October | 94263927.40 | 0.00 | 94263927.40 | 63954808.71 | 0.141997E+09 |
November | 73643994.34 | 0.00 | 73643994.34 | 22715016.42 | 0.188556E+09 |
December | 71194348.57 | 0.00 | 71194348.57 | 14667353.56 | 0.223767E+09 |
Annual Sum or Average | 0.134503E+10 | 49053062.13 | 0.129598E+10 | 0.114444E+10 | 0.150511E+10 |
Minimum of Months | 71194348.57 | 0.00 | 71194348.57 | 14667353.56 | 45082018.56 |
Maximum of Months | 0.160772E+09 | 19085875.03 | 0.145673E+09 | 0.197533E+09 | 0.223767E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71748102.10 | 0.00 | 71748102.10 | 20945711.90 | 0.196533E+09 |
February | 79133498.28 | 0.00 | 79133498.28 | 36533531.61 | 0.158160E+09 |
March | 0.114692E+09 | 11835.85 | 0.114680E+09 | 69701783.99 | 0.157489E+09 |
April | 0.128496E+09 | 1331103.26 | 0.127164E+09 | 0.103783E+09 | 0.108575E+09 |
May | 0.156940E+09 | 11270810.25 | 0.145669E+09 | 0.155758E+09 | 80280592.01 |
June | 0.160768E+09 | 19084980.45 | 0.141683E+09 | 0.197530E+09 | 48326465.55 |
July | 0.153327E+09 | 13989013.10 | 0.139338E+09 | 0.188062E+09 | 45081242.61 |
August | 0.130820E+09 | 3266022.90 | 0.127554E+09 | 0.154889E+09 | 58542317.60 |
September | 0.109980E+09 | 96997.14 | 0.109883E+09 | 0.115878E+09 | 97791998.50 |
October | 94261502.43 | 0.00 | 94261502.43 | 63952994.70 | 0.141996E+09 |
November | 73642115.83 | 0.00 | 73642115.83 | 22714092.91 | 0.188555E+09 |
December | 71192373.17 | 0.00 | 71192373.17 | 14666458.17 | 0.223766E+09 |
Annual Sum or Average | 0.134500E+10 | 49050762.94 | 0.129595E+10 | 0.114441E+10 | 0.150510E+10 |
Minimum of Months | 71192373.17 | 0.00 | 71192373.17 | 14666458.17 | 45081242.61 |
Maximum of Months | 0.160768E+09 | 19084980.45 | 0.145669E+09 | 0.197530E+09 | 0.223766E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187968E+09 | 0.131899E+09 | 56068412.54 | 0.234399E+09 | 0.190471E+09 |
February | 0.217226E+09 | 0.153656E+09 | 63570297.73 | 0.277348E+09 | 0.168015E+09 |
March | 0.335619E+09 | 0.236890E+09 | 98729396.71 | 0.435255E+09 | 0.190352E+09 |
April | 0.403789E+09 | 0.299277E+09 | 0.104512E+09 | 0.532017E+09 | 0.167407E+09 |
May | 0.460080E+09 | 0.341667E+09 | 0.118413E+09 | 0.613312E+09 | 0.166759E+09 |
June | 0.470207E+09 | 0.364384E+09 | 0.105823E+09 | 0.643076E+09 | 0.131386E+09 |
July | 0.420489E+09 | 0.302884E+09 | 0.117605E+09 | 0.581444E+09 | 0.109343E+09 |
August | 0.393113E+09 | 0.283268E+09 | 0.109845E+09 | 0.535162E+09 | 0.131553E+09 |
September | 0.348393E+09 | 0.260381E+09 | 88012375.56 | 0.468014E+09 | 0.171762E+09 |
October | 0.271760E+09 | 0.197317E+09 | 74442982.35 | 0.345703E+09 | 0.195509E+09 |
November | 0.206188E+09 | 0.153097E+09 | 53090202.32 | 0.249472E+09 | 0.214116E+09 |
December | 0.174322E+09 | 0.116161E+09 | 58161476.03 | 0.209114E+09 | 0.218844E+09 |
Annual Sum or Average | 0.388915E+10 | 0.284088E+10 | 0.104827E+10 | 0.512432E+10 | 0.205552E+10 |
Minimum of Months | 0.174322E+09 | 0.116161E+09 | 53090202.32 | 0.209114E+09 | 0.109343E+09 |
Maximum of Months | 0.470207E+09 | 0.364384E+09 | 0.118413E+09 | 0.643076E+09 | 0.218844E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.04 | 380.88 | 312.32 | 145.73 | 166.59 | 0.00 | 0.00 |
February | 294.41 | 342.51 | 356.80 | 154.53 | 202.28 | 0.00 | 0.00 |
March | 453.20 | 309.98 | 483.72 | 213.51 | 270.21 | 0.00 | 0.00 |
April | 586.20 | 225.06 | 556.24 | 247.79 | 308.45 | 0.00 | 0.00 |
May | 706.01 | 165.83 | 609.34 | 271.59 | 337.75 | 0.00 | 0.00 |
June | 778.48 | 102.91 | 604.04 | 272.75 | 331.29 | 0.00 | 0.00 |
July | 692.49 | 92.38 | 540.84 | 222.62 | 318.22 | 0.00 | 0.00 |
August | 633.64 | 120.05 | 509.70 | 212.27 | 297.43 | 0.00 | 0.00 |
September | 601.57 | 204.14 | 507.62 | 236.13 | 271.49 | 0.00 | 0.00 |
October | 435.36 | 280.73 | 433.19 | 211.73 | 221.46 | 0.00 | 0.00 |
November | 290.26 | 377.27 | 359.04 | 183.17 | 175.86 | 0.00 | 0.00 |
December | 201.16 | 431.98 | 298.21 | 132.96 | 165.25 | 0.00 | 0.00 |
Annual Sum or Average | 492.99 | 252.35 | 464.67 | 208.89 | 255.78 | 0.00 | 0.00 |
Minimum of Months | 201.16 | 92.38 | 298.21 | 132.96 | 165.25 | 0.00 | 0.00 |
Maximum of Months | 778.48 | 431.98 | 609.34 | 272.75 | 337.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 875.14 | 711.14 | 701.79 | 492.46 | 209.34 | 0.00 | 0.00 |
February | 1146.44 | 694.51 | 897.92 | 635.15 | 262.77 | 0.00 | 0.00 |
March | 1625.05 | 710.69 | 1253.06 | 884.44 | 368.61 | 0.00 | 0.00 |
April | 2052.53 | 645.86 | 1557.83 | 1154.62 | 403.21 | 0.00 | 0.00 |
May | 2289.84 | 622.61 | 1717.74 | 1275.64 | 442.10 | 0.00 | 0.00 |
June | 2481.00 | 506.89 | 1814.07 | 1405.80 | 408.27 | 0.00 | 0.00 |
July | 2170.86 | 408.24 | 1569.93 | 1130.84 | 439.09 | 0.00 | 0.00 |
August | 1998.06 | 491.15 | 1467.71 | 1057.60 | 410.12 | 0.00 | 0.00 |
September | 1805.61 | 662.66 | 1344.11 | 1004.56 | 339.55 | 0.00 | 0.00 |
October | 1290.71 | 729.95 | 1014.64 | 736.70 | 277.94 | 0.00 | 0.00 |
November | 962.47 | 826.06 | 795.48 | 590.65 | 204.82 | 0.00 | 0.00 |
December | 780.74 | 817.07 | 650.84 | 433.69 | 217.15 | 0.00 | 0.00 |
Annual Sum or Average | 1624.91 | 651.80 | 1233.24 | 900.84 | 332.41 | 0.00 | 0.00 |
Minimum of Months | 780.74 | 408.24 | 650.84 | 433.69 | 204.82 | 0.00 | 0.00 |
Maximum of Months | 2481.00 | 826.06 | 1814.07 | 1405.80 | 442.10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.624163E+09 | 0.102015E+10 | 0.836515E+09 | 0.390313E+09 | 0.446201E+09 | 0.00 | 0.00 |
February | 0.712235E+09 | 0.828591E+09 | 0.863179E+09 | 0.373830E+09 | 0.489350E+09 | 0.00 | 0.00 |
March | 0.121384E+10 | 0.830241E+09 | 0.129561E+10 | 0.571878E+09 | 0.723730E+09 | 0.00 | 0.00 |
April | 0.151943E+10 | 0.583349E+09 | 0.144177E+10 | 0.642284E+09 | 0.799491E+09 | 0.00 | 0.00 |
May | 0.189098E+10 | 0.444149E+09 | 0.163205E+10 | 0.727418E+09 | 0.904633E+09 | 0.00 | 0.00 |
June | 0.201783E+10 | 0.266744E+09 | 0.156568E+10 | 0.706975E+09 | 0.858705E+09 | 0.00 | 0.00 |
July | 0.185478E+10 | 0.247434E+09 | 0.144860E+10 | 0.596273E+09 | 0.852325E+09 | 0.00 | 0.00 |
August | 0.169713E+10 | 0.321532E+09 | 0.136518E+10 | 0.568545E+09 | 0.796640E+09 | 0.00 | 0.00 |
September | 0.155928E+10 | 0.529132E+09 | 0.131575E+10 | 0.612044E+09 | 0.703708E+09 | 0.00 | 0.00 |
October | 0.116606E+10 | 0.751914E+09 | 0.116025E+10 | 0.567098E+09 | 0.593153E+09 | 0.00 | 0.00 |
November | 0.752347E+09 | 0.977896E+09 | 0.930621E+09 | 0.474786E+09 | 0.455835E+09 | 0.00 | 0.00 |
December | 0.538782E+09 | 0.115702E+10 | 0.798728E+09 | 0.356129E+09 | 0.442599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155469E+11 | 0.795815E+10 | 0.146539E+11 | 0.658757E+10 | 0.806637E+10 | 0.00 | 0.00 |
Minimum of Months | 0.538782E+09 | 0.247434E+09 | 0.798728E+09 | 0.356129E+09 | 0.442599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201783E+10 | 0.115702E+10 | 0.163205E+10 | 0.727418E+09 | 0.904633E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234398E+10 | 0.190471E+10 | 0.187968E+10 | 0.131899E+10 | 0.560684E+09 | 0.00 | 0.00 |
February | 0.277346E+10 | 0.168015E+10 | 0.217226E+10 | 0.153656E+10 | 0.635703E+09 | 0.00 | 0.00 |
March | 0.435254E+10 | 0.190352E+10 | 0.335619E+10 | 0.236890E+10 | 0.987294E+09 | 0.00 | 0.00 |
April | 0.532017E+10 | 0.167407E+10 | 0.403789E+10 | 0.299277E+10 | 0.104512E+10 | 0.00 | 0.00 |
May | 0.613312E+10 | 0.166759E+10 | 0.460080E+10 | 0.341667E+10 | 0.118413E+10 | 0.00 | 0.00 |
June | 0.643075E+10 | 0.131386E+10 | 0.470207E+10 | 0.364384E+10 | 0.105823E+10 | 0.00 | 0.00 |
July | 0.581444E+10 | 0.109343E+10 | 0.420489E+10 | 0.302884E+10 | 0.117605E+10 | 0.00 | 0.00 |
August | 0.535161E+10 | 0.131550E+10 | 0.393113E+10 | 0.283268E+10 | 0.109845E+10 | 0.00 | 0.00 |
September | 0.468014E+10 | 0.171761E+10 | 0.348393E+10 | 0.260381E+10 | 0.880124E+09 | 0.00 | 0.00 |
October | 0.345703E+10 | 0.195509E+10 | 0.271760E+10 | 0.197317E+10 | 0.744430E+09 | 0.00 | 0.00 |
November | 0.249472E+10 | 0.214116E+10 | 0.206188E+10 | 0.153097E+10 | 0.530902E+09 | 0.00 | 0.00 |
December | 0.209113E+10 | 0.218844E+10 | 0.174322E+10 | 0.116161E+10 | 0.581615E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.512431E+11 | 0.205551E+11 | 0.388915E+11 | 0.284088E+11 | 0.104827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209113E+10 | 0.109343E+10 | 0.174322E+10 | 0.116161E+10 | 0.530902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.643075E+10 | 0.218844E+10 | 0.470207E+10 | 0.364384E+10 | 0.118413E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.32 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.73 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.69 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.47 | -2.7 | 4.72 | 3.37 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.20 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.01 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.90 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.10 | 12.00 | 3.28 | 15.47 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.80 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.00 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.23 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.89 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.89 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.90 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.36 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.84 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.49 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.18 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.19 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.18 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.16 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.85 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.82 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.87 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.43 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.94 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.94 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.16 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.3 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.4 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.3 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.5 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.97 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.40 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.97 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.88 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -2.9 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.0 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.4 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.97 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.15 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.74 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.71 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.10 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.18 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.87 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.16 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.64 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.62 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.55 | 03-NOV-13:20 | 22.07 | 7.93 | 2.10 | 9.59 | 80.17 | 943.83 |
December | 8.27 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.27 | 12.80 | -0.6 | 1.50 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.87 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 943.83 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.70 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.39 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.10 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.27 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.933278E+09 | -782884626.3 | 0.00 | 0.00 | 744.00 | 0.00 | -150393386.4 | 58.99 | 0.00 | 0.00 |
February | 0.851901E+09 | -718627212.6 | 0.00 | 0.00 | 672.00 | 0.00 | -133273929.8 | 58.99 | 0.00 | 0.00 |
March | 0.951384E+09 | -809057691.7 | 0.00 | 0.00 | 744.00 | 0.00 | -142325963.0 | 58.99 | 0.00 | 0.00 |
April | 0.829096E+09 | -701661037.8 | 0.00 | 0.00 | 720.00 | 0.00 | -127434619.8 | 58.99 | 0.00 | 0.00 |
May | 0.796441E+09 | -670057746.3 | 0.00 | 0.00 | 744.00 | 0.00 | -126383221.8 | 58.99 | 0.00 | 0.00 |
June | 0.734795E+09 | -614643023.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120151515.7 | 58.99 | 0.00 | 0.00 |
July | 0.687942E+09 | -564852985.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123089223.7 | 58.99 | 0.00 | 0.00 |
August | 0.731476E+09 | -607208609.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124267287.0 | 58.99 | 0.00 | 0.00 |
September | 0.715466E+09 | -594502534.4 | 0.00 | 0.00 | 720.00 | 0.00 | -120963328.0 | 58.99 | 0.00 | 0.00 |
October | 0.776237E+09 | -646635986.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129601323.9 | 58.99 | 0.00 | 0.00 |
November | 0.813117E+09 | -676113694.3 | 0.00 | 0.00 | 720.00 | 0.00 | -137003332.1 | 58.99 | 0.00 | 0.00 |
December | 0.904069E+09 | -753476755.6 | 0.00 | 0.00 | 744.00 | 0.00 | -150591865.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.972520E+10 | -.813972E+10 | 8760.00 | -.158548E+10 | 58.99 | |||||
Minimum of Months | 0.687942E+09 | -809057691.7 | 0.00 | 0.00 | 672.00 | 0.00 | -150591865.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.951384E+09 | -564852985.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120151515.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | ||||||||||
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205861E+10 | 29819.03 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137394E+10 | 29819.03 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.778541E+09 | 29819.03 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41154637.19 | 8123.56 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1292519.61 | 2506.11 | 27-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.586420E+09 | 29819.03 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229280E+10 | 29819.03 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.713276E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229280E+10 | 29819.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.569416E+10 | 97368.36 | 28-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302879E+10 | 95914.00 | 02-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691552E+09 | 97368.36 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.798166E+09 | 96868.10 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753243E+10 | 97368.36 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177451E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.753243E+10 | 97368.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241387E+09 | 23956.64 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88841244.02 | 11956.55 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141178E+10 | 36100.92 | 31-DEC-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174201E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141178E+10 | 36100.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2056.20 | 2056.20 | 0.54 | 03-JAN-15:00 | 0.54 | 0.00 |
February | 0.00 | 0.00 | 63510851.36 | 63510851.36 | 2658.56 | 21-FEB-16:00 | 2658.56 | 0.00 |
March | 0.00 | 0.00 | 0.448437E+09 | 0.448437E+09 | 5433.24 | 14-MAR-16:00 | 5433.24 | 0.00 |
April | 0.00 | 0.00 | 0.340547E+10 | 0.339649E+10 | 20601.43 | 29-APR-05:01 | 18557.62 | 0.00 |
May | 0.00 | 0.00 | 0.793029E+10 | 0.772605E+10 | 22196.92 | 23-MAY-05:01 | 17873.55 | 0.00 |
June | 0.00 | 0.00 | 0.115607E+11 | 0.110832E+11 | 23018.12 | 28-JUN-05:01 | 14722.50 | 0.00 |
July | 0.00 | 0.00 | 0.132992E+11 | 0.109888E+11 | 26331.86 | 22-JUL-05:01 | 12053.15 | 0.00 |
August | 0.00 | 0.00 | 0.122758E+11 | 0.106731E+11 | 25411.34 | 03-AUG-05:01 | 14878.56 | 0.00 |
September | 0.00 | 0.00 | 0.990519E+10 | 0.867057E+10 | 24781.85 | 22-SEP-05:01 | 13492.23 | 0.00 |
October | 0.00 | 0.00 | 0.401459E+10 | 0.364346E+10 | 23435.14 | 04-OCT-05:01 | 13384.64 | 0.00 |
November | 0.00 | 0.00 | 0.289282E+09 | 0.287630E+09 | 6764.15 | 03-NOV-16:00 | 6764.15 | 0.00 |
December | 0.00 | 0.00 | 2504.19 | 2504.19 | 0.19 | 16-DEC-15:00 | 0.19 | 0.00 |
Annual Sum or Average | 0.631925E+11 | 0.569812E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 2056.20 | 2056.20 | 0.19 | 0.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132992E+11 | 0.110832E+11 | 26331.86 | 18557.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.550416E+10 | 0.549042E+10 | 68905.72 | 30-APR-09:41 | 62315.93 | 0.00 |
May | 0.00 | 0.00 | 0.203981E+11 | 0.198711E+11 | 76578.00 | 28-MAY-09:02 | 53878.63 | 0.00 |
June | 0.00 | 0.00 | 0.379888E+11 | 0.367119E+11 | 80208.99 | 19-JUN-17:56 | 49156.99 | 0.00 |
July | 0.00 | 0.00 | 0.420657E+11 | 0.358555E+11 | 85423.22 | 21-JUL-20:41 | 42915.92 | 0.00 |
August | 0.00 | 0.00 | 0.348903E+11 | 0.312541E+11 | 82463.28 | 02-AUG-00:21 | 44559.18 | 0.00 |
September | 0.00 | 0.00 | 0.252962E+11 | 0.223997E+11 | 80334.70 | 03-SEP-08:40 | 48348.02 | 0.00 |
October | 0.00 | 0.00 | 0.548340E+10 | 0.491470E+10 | 79279.45 | 03-OCT-17:51 | 51936.31 | 0.00 |
November | 0.00 | 0.00 | 8979.64 | 8294.99 | 1.36 | 03-NOV-14:00 | 1.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171627E+12 | 0.156497E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.420657E+11 | 0.367119E+11 | 85423.22 | 62315.93 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 4298171.39 | 0.00 | 237.60 | 27-JAN-06:48 | 0.09 |
February | 4155611.81 | 0.00 | 237.60 | 02-FEB-03:20 | 0.09 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 28012957.80 | 0.00 | 237.60 | 22-DEC-07:00 | 0.09 |
Annual Sum or Average | 36466740.99 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28012957.80 | 0.00 | 237.60 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153549E+10 | 0.43 | 1519.58 | 25-JAN-17:20 | 1.08 |
February | 0.140691E+10 | 0.43 | 1519.58 | 01-FEB-10:20 | 1.08 |
March | 0.163838E+10 | 0.45 | 1519.58 | 03-MAR-07:30 | 1.08 |
April | 0.150961E+10 | 0.42 | 1519.58 | 01-APR-12:50 | 1.08 |
May | 0.160326E+10 | 0.44 | 1519.58 | 03-MAY-08:65 | 1.08 |
June | 0.162609E+10 | 0.47 | 1519.58 | 07-JUN-06:10 | 1.07 |
July | 0.157454E+10 | 0.45 | 1519.58 | 06-JUL-06:50 | 1.06 |
August | 0.169593E+10 | 0.47 | 1519.58 | 14-AUG-10:05 | 1.06 |
September | 0.156410E+10 | 0.44 | 1519.58 | 07-SEP-07:30 | 1.06 |
October | 0.151743E+10 | 0.40 | 1519.58 | 02-OCT-07:50 | 1.07 |
November | 0.145391E+10 | 0.41 | 1519.58 | 08-NOV-11:50 | 1.08 |
December | 0.153666E+10 | 0.43 | 1519.58 | 02-DEC-08:70 | 1.08 |
Annual Sum or Average | 0.186623E+11 | 0.44 | |||
Minimum of Months | 0.140691E+10 | 0.40 | 1519.58 | 1.06 | |
Maximum of Months | 0.169593E+10 | 0.47 | 1519.58 | 1.08 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401804E+10 | 0.61 | 3825.65 | 28-JAN-09:00 | 1.04 |
February | 0.360903E+10 | 0.50 | 3825.65 | 02-FEB-09:00 | 1.04 |
March | 0.411807E+10 | 0.44 | 3825.65 | 01-MAR-07:30 | 1.04 |
April | 0.383847E+10 | 0.42 | 3825.65 | 01-APR-16:50 | 1.04 |
May | 0.425787E+10 | 0.51 | 3825.65 | 12-MAY-14:20 | 1.03 |
June | 0.463617E+10 | 0.63 | 3825.65 | 09-JUN-08:50 | 1.03 |
July | 0.461012E+10 | 0.62 | 3825.65 | 11-JUL-09:50 | 1.03 |
August | 0.469150E+10 | 0.60 | 3825.65 | 16-AUG-11:13 | 1.02 |
September | 0.411894E+10 | 0.48 | 3825.65 | 12-SEP-16:10 | 1.03 |
October | 0.384592E+10 | 0.40 | 3825.65 | 02-OCT-10:40 | 1.02 |
November | 0.367013E+10 | 0.42 | 3825.65 | 28-NOV-07:40 | 1.04 |
December | 0.409540E+10 | 0.65 | 3825.65 | 04-DEC-08:20 | 1.03 |
Annual Sum or Average | 0.495096E+11 | 0.52 | |||
Minimum of Months | 0.360903E+10 | 0.40 | 3825.65 | 1.02 | |
Maximum of Months | 0.469150E+10 | 0.65 | 3825.65 | 1.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.11 | 1.22 |
February | 0.69 | 0.96 |
March | 0.89 | 2.02 |
April | 1.60 | 0.56 |
May | 4.72 | 0.24 |
June | 6.43 | 0.19 |
July | 6.82 | 0.19 |
August | 5.99 | 0.25 |
September | 4.14 | 0.16 |
October | 2.74 | 0.81 |
November | 1.61 | 1.81 |
December | 0.89 | 1.02 |
Annual Sum or Average | 37.62 | 0.44 |
Minimum of Months | 0.69 | 0.16 |
Maximum of Months | 6.82 | 2.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.17 | 0.00 |
March | 0.25 | 0.00 |
April | 0.90 | 0.00 |
May | 2.24 | 0.00 |
June | 5.62 | 0.00 |
July | 7.79 | 0.00 |
August | 6.68 | 0.00 |
September | 5.39 | 0.00 |
October | 1.03 | 0.00 |
November | 0.00 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 30.10 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.79 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 3.51 | 0.00 |
June | 10.53 | 0.00 |
July | 9.63 | 0.00 |
August | 9.88 | 0.00 |
September | 4.78 | 0.00 |
October | 0.58 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 38.92 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 10.53 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153549E+10 | 0.301365E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142433E+10 | 0.200605E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.176031E+10 | 0.114445E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.246172E+10 | 62719454.92 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383485E+10 | 1985606.66 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.503445E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.529802E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.512276E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.429032E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259795E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153192E+10 | 0.864270E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153666E+10 | 0.334969E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.364288E+11 | 0.104428E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142433E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.529802E+10 | 0.334969E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.401804E+10 | 0.852665E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.360903E+10 | 0.450198E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.411807E+10 | 0.102858E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.558269E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107601E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172401E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178995E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.156964E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118682E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.551662E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.367013E+10 | 0.119752E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.409540E+10 | 0.112112E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104074E+12 | 0.264660E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.360903E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.178995E+11 | 0.112112E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153549E+10 | 2056.20 | 0.205861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140691E+10 | 63510851.36 | 0.137394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163838E+10 | 0.448437E+09 | 0.778541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150961E+10 | 0.340547E+10 | 41154637.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160326E+10 | 0.793029E+10 | 1292519.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162609E+10 | 0.115607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157454E+10 | 0.132992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169593E+10 | 0.122758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156410E+10 | 0.990519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151743E+10 | 0.401459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145391E+10 | 0.289282E+09 | 0.586420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153666E+10 | 2504.19 | 0.229280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186623E+11 | 0.631925E+11 | 0.713276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140691E+10 | 2056.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169593E+10 | 0.132992E+11 | 0.229280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.401804E+10 | 0.00 | 0.569416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360903E+10 | 0.00 | 0.302879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411807E+10 | 0.00 | 0.691552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383847E+10 | 0.550416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425787E+10 | 0.203981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463617E+10 | 0.379888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461012E+10 | 0.420657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.469150E+10 | 0.348903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411894E+10 | 0.252962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384592E+10 | 0.548340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367013E+10 | 8979.64 | 0.798166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409540E+10 | 0.00 | 0.753243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495096E+11 | 0.171627E+12 | 0.177451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.469150E+10 | 0.420657E+11 | 0.753243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.153549E+10 | 0.00 | 0.00 | 0.00 | 572.78 | 0.00 | 0.301365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140691E+10 | 0.00 | 0.00 | 0.00 | 17416085.27 | 0.00 | 0.200605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163838E+10 | 0.00 | 0.00 | 0.00 | 0.121937E+09 | 0.00 | 0.114445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150961E+10 | 0.00 | 0.00 | 0.00 | 0.952103E+09 | 0.00 | 62719454.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160326E+10 | 0.00 | 0.00 | 0.00 | 0.223159E+10 | 0.00 | 1985606.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162609E+10 | 0.00 | 0.00 | 0.00 | 0.340836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157454E+10 | 0.00 | 0.00 | 0.00 | 0.372348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169593E+10 | 0.00 | 0.00 | 0.00 | 0.342682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156410E+10 | 0.00 | 0.00 | 0.00 | 0.272622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151743E+10 | 0.00 | 0.00 | 0.00 | 0.108052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145391E+10 | 0.00 | 0.00 | 0.00 | 78000683.96 | 0.00 | 0.864270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153666E+10 | 0.00 | 0.00 | 0.00 | 697.57 | 0.00 | 0.334969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186623E+11 | 0.00 | 0.00 | 0.00 | 0.177665E+11 | 0.00 | 0.104428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140691E+10 | 0.00 | 0.00 | 0.00 | 572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169593E+10 | 0.00 | 0.00 | 0.00 | 0.372348E+10 | 0.00 | 0.334969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.401804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383847E+10 | 0.00 | 0.00 | 0.00 | 0.174422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425787E+10 | 0.00 | 0.00 | 0.00 | 0.650225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463617E+10 | 0.00 | 0.00 | 0.00 | 0.126040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461012E+10 | 0.00 | 0.00 | 0.00 | 0.132894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.469150E+10 | 0.00 | 0.00 | 0.00 | 0.110049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411894E+10 | 0.00 | 0.00 | 0.00 | 0.774922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384592E+10 | 0.00 | 0.00 | 0.00 | 0.167070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367013E+10 | 0.00 | 0.00 | 0.00 | 2708.91 | 0.00 | 0.119752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495096E+11 | 0.00 | 0.00 | 0.00 | 0.545646E+11 | 0.00 | 0.264660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.360903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.469150E+10 | 0.00 | 0.00 | 0.00 | 0.132894E+11 | 0.00 | 0.112112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.660802E+09 | 0.00 | 0.00 | 23136.02 | 0.00 | 0.695354E+09 | 70565524.79 | 0.00 | 0.16 |
February | 0.631649E+09 | 0.00 | 0.00 | 216210.46 | 0.00 | 0.399199E+09 | 0.289091E+09 | 0.00 | 0.25 |
March | 0.613325E+09 | 298605.24 | 0.00 | 1180094.82 | 0.00 | 0.136905E+09 | 0.111009E+10 | 0.00 | 0.46 |
April | 87437879.07 | 0.113446E+09 | 0.00 | 3192494.61 | 0.00 | 0.00 | 0.168577E+10 | 0.00 | 0.56 |
May | 15698827.85 | 0.404818E+09 | 0.00 | 6464000.90 | 0.00 | 0.00 | 0.974654E+09 | 0.00 | 0.51 |
June | 298996.09 | 0.864268E+09 | 0.00 | 8694332.72 | 280753.96 | 0.00 | 0.246628E+09 | 0.00 | 0.37 |
July | 0.00 | 0.189108E+10 | 0.00 | 3536689.40 | 716866.38 | 0.00 | 26638889.49 | 0.00 | 0.36 |
August | 274537.79 | 0.112230E+10 | 0.00 | 7515449.19 | 162020.77 | 0.00 | 0.347980E+09 | 0.00 | 0.50 |
September | 7786850.02 | 0.852567E+09 | 0.00 | 6926711.54 | 0.00 | 0.00 | 0.651813E+09 | 0.00 | 0.51 |
October | 22715449.84 | 0.173573E+09 | 0.00 | 6270202.84 | 0.00 | 0.00 | 0.242868E+10 | 0.00 | 0.73 |
November | 0.457403E+09 | 0.00 | 0.00 | 1767147.60 | 0.00 | 0.121868E+09 | 0.153478E+10 | 0.00 | 0.44 |
December | 0.684026E+09 | 0.00 | 0.00 | 22293.54 | 0.00 | 0.773251E+09 | 65930911.23 | 0.00 | 0.15 |
Annual Sum or Average | 0.318142E+10 | 0.542235E+10 | 0.00 | 45808763.63 | 1159641.10 | 0.212658E+10 | 0.943263E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22293.54 | 0.00 | 0.00 | 26638889.49 | 0.00 | 0.15 |
Maximum of Months | 0.684026E+09 | 0.189108E+10 | 0.00 | 8694332.72 | 716866.38 | 0.773251E+09 | 0.242868E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230613E+09 | 0.00 | 0.00 | 0.14 |
February | 0.215657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85245720.50 | 0.00 | 0.00 | 0.15 |
March | 0.230740E+10 | 0.00 | 0.00 | 0.00 | 1246829.98 | 32226456.88 | 0.00 | 0.00 | 0.16 |
April | 0.115151E+10 | 0.142180E+09 | 0.00 | 3635506.93 | 11551397.10 | 0.00 | 0.135100E+10 | 0.00 | 0.37 |
May | 0.230558E+09 | 0.785976E+09 | 0.00 | 9202081.74 | 0.00 | 0.00 | 0.209018E+10 | 0.00 | 0.49 |
June | 17011355.71 | 0.183784E+10 | 0.00 | 11215618.01 | 0.00 | 0.00 | 0.146278E+10 | 0.00 | 0.46 |
July | 10768868.88 | 0.343021E+10 | 0.00 | 6907817.31 | 0.00 | 0.00 | 0.116929E+10 | 0.00 | 0.49 |
August | 34819490.72 | 0.210645E+10 | 0.00 | 12502474.83 | 0.00 | 0.00 | 0.222113E+10 | 0.00 | 0.56 |
September | 0.104447E+09 | 0.159525E+10 | 0.00 | 11256853.62 | 0.00 | 0.00 | 0.197576E+10 | 0.00 | 0.53 |
October | 0.109732E+10 | 0.286572E+09 | 0.00 | 5845150.55 | 0.00 | 0.00 | 0.336817E+10 | 0.00 | 0.49 |
November | 0.230878E+10 | 0.00 | 0.00 | 46738.36 | 0.00 | 33373627.36 | 0.102884E+09 | 0.00 | 0.16 |
December | 0.265266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307354E+09 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.145628E+11 | 0.101845E+11 | 0.00 | 60612241.34 | 12798227.08 | 0.688813E+09 | 0.137412E+11 | 0.00 | 0.35 |
Minimum of Months | 10768868.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.265266E+10 | 0.343021E+10 | 0.00 | 12502474.83 | 11551397.10 | 0.307354E+09 | 0.336817E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |