Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2020-06-03 19:10:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1096.92 | 226.86 | 226.86 |
Net Site Energy | 1096.92 | 226.86 | 226.86 |
Total Source Energy | 3349.32 | 692.70 | 692.70 |
Net Source Energy | 3349.32 | 692.70 | 692.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1037.09 | 59.83 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 126.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 118.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.45 | 12.37 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 214.49 | 12.37 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.45 | 12.37 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 214.49 | 12.37 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1037.088 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1037.088 | 100.00 |
Total On-Site and Utility Electric Sources | 1037.088 | 100.00 |
Total Electricity End Uses | 1037.088 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.17 |
Time Setpoint Not Met During Occupied Cooling | 38.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 237.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:50 | 01-JAN-07:40 | - | - | - | 27-APR-11:30 |
Heating | 0.00 | 55722.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28292.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11424.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1679.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87129.56 | 55722.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 55722.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28292.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1679.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 64.86 | 0.00 | 0.00 | 0.00 |
Cooling | 402.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 447.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3284.46 | 64.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 13.41 | 0.00 | 0.00 | 0.00 |
Cooling | 83.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 92.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 679.29 | 13.41 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 13.41 | 0.00 | 0.00 | 0.00 |
Cooling | 83.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 92.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 679.29 | 13.41 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.39 |
ZONE2 FINE STORAGE DIRECT AIR | 3.95 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.14 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.14 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 80658.26 |
PSZ-OFFICE HEATING COIL | 31676.68 |
PSZ-FINE STORAGE HEATING COIL | 111812.08 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 80658.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.000000 | 1.39 |
PSZ-FINE STORAGE | 3.95 | 3.95 | 3.95 | 3.95 | 3.95 | 3.95 | 1.00 | 1.00 | 3.95 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.39 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.95 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 1.39 | 25040.50 | 31676.68 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.95 | 3.95 | 3.95 | 3.95 | 84825.74 | 111812.08 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.39 | 0.695640 | 1.39 | 23376.13 | 25040.50 | 12520.25 | 25040.50 | 0.769145 | 0.769150 | 0.769150 | 0.769150 |
PSZ-FINE STORAGE COOLING COIL | 3.95 | 1.97 | 3.95 | 72627.35 | 84825.74 | 42412.87 | 84825.74 | 0.714136 | 0.714140 | 0.714140 | 0.714140 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.39 | 1586.21 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.95 | 7533.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12794.82634 | 15353.79161 | 1.15940 | 1.39128 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8423.71208 | 10108.45450 | 0.26036 | 0.31243 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 46562.03707 | 55874.44448 | 3.28858 | 3.94630 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23141.33259 | 27769.59911 | 0.60273 | 0.72328 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80000 | 5.57864E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 67215.21227 | 80658.25472 | 1.78256 | 2.13908 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20174.69 | 1.39128 | 1.39128 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9220.02 | 0.31243 | 0.31243 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 68488.18 | 3.94630 | 3.94630 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 25274.22 | 0.72328 | 0.72328 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39128 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.94630 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.13908 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.13908 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 80658.25778 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 80658.25472 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39128 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39128 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39128 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39128 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39128 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.39128 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.94630 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.94630 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.94630 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.94630 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.94630 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.94630 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.39128 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.94630 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39128 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39128 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39128 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39128 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.39128 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39128 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69564 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.39128 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23376.12525 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25040.50000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12520.25000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25040.50000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76915 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76915 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76915 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76915 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25040.50000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31676.68445 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39128 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1586.21119 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31676.68445 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.94630 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.94630 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.94630 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.94630 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.94630 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.94630 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.97315 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.94630 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 72627.34997 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 84825.74000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 42412.87000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 84825.74000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71414 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71414 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71414 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71414 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 84825.74000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 111812.08352 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.94630 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7533.33681 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 111812.08352 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23960.6 | 10.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 81760.4 | 12.62 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 21 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 6.8151777346E-002 | 6.2742265043E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2996933803 | 0.3646841857 | Pass | Pass | 1.4850070026 | 12.3657498411 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.1221315861E-002 | 7.6989389978E-002 | Pass | Pass | 0.2203210643 | 2.4226329723 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.79 | 83.79 | 123.58 | |
Exterior Lighting Total | 7857.24 | 123.58 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25040.50 | 19259.90 | 5780.60 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 84825.74 | 60577.45 | 24248.29 | 0.71 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23960.6 | 10.22 | ||||
PSZ-FINE STORAGE COOLING COIL | 81760.4 | 12.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 80658.26 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31676.68 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 111812.08 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.14 | 198.74 | 92.91 | 1.00 | 3.54 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.39 | 1586.21 | 1140.11 | 1.00 | 1.29 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.95 | 7533.34 | 1908.96 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12794.83 | 15353.79 | 64.82 | 1.159 | 1.391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00801 | 38.94 | 0.00558 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 46562.04 | 55874.44 | 40.10 | 3.289 | 3.946 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00759 | 38.94 | 0.00558 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00416 | 40.80 | 0.00558 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8423.71 | 10108.45 | 42.67 | 0.260 | 0.312 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00782 | 0.50 | 0.00432 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 23141.33 | 27769.60 | 19.93 | 0.603 | 0.723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00675 | 0.50 | 0.00432 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 67215.21 | 80658.25 | 25.17 | 1.783 | 2.139 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 9.99 | 0.00841 | 0.50 | 0.00432 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.39 | 1.39 | 0.31 | 0.31 | 1.3913 | 1.3913 | 1.3913 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.95 | 3.95 | 0.72 | 0.72 | 3.9463 | 3.9463 | 3.9463 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 80658.258 | 80658.258 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 80658.26 | 80658.26 | 2.139076 | 6.38 | 6.38 | 0.00685373 | 43.33 | 25.84 | 0.01600000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 9.99 | 0.00841303 | 100.0000 | 80658.25 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25040.500 | 0.000 | 1.391280 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25040.50 | 25040.50 | 1.391280 | 25.20 | 15.21 | 0.00780257 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 8.6493 | 23.90 | 0.00801313 | 39.4268 | 12794.83 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31676.684 | 31676.684 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 31676.68 | 31676.68 | 1.391279 | 13.14 | 9.31 | 0.00646801 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 8.6493 | 21.10 | 0.00781636 | 45.6077 | 8423.71 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 84825.740 | 0.000 | 3.946300 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 84825.74 | 84825.74 | 3.946300 | 27.80 | 15.77 | 0.00741060 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 8.9686 | 26.70 | 0.00759109 | 31.6378 | 46562.04 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 111812.084 | 111812.084 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 111812.08 | 111812.08 | 3.946295 | 8.19 | 6.07 | 0.00555916 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 8.9686 | 15.56 | 0.00675082 | 55.8709 | 23141.33 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 80658.258 | 80658.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0932 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.139076 | 2.33842578 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 80658.26 | 80658.26 | 1.0000 | 2.33842578 | 2.139076 | 6.38 | 6.38 | 0.00685373 | 23633.8 | 43.33 | 25.84 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80658.26 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 9.99 | 0.00841303 | 9.99 | 0.00841303 | 100.0000 | 80658.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25040.500 | 0.000 | 1.391280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3446 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25040.50 | 25040.50 | 1.0000 | 1.52093925 | 1.391280 | 25.20 | 15.21 | 0.00780257 | 45201.7 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25040.50 | 38.94 | 0.00557864 | 17.93 | 0.12033533 | 8.6493 | 23.90 | 0.00801313 | 23.90 | 0.00801313 | 39.4268 | 12794.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31676.684 | 31676.684 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.391279 | 1.52093839 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 31676.68 | 31676.68 | 1.0000 | 1.52093839 | 1.391279 | 13.14 | 9.31 | 0.00646801 | 29533.3 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31676.68 | 0.50 | 0.00431558 | 0.50 | 0.12033533 | 8.6493 | 21.05 | 0.00781636 | 21.10 | 0.00781636 | 45.6077 | 8423.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 84825.740 | 0.000 | 3.946300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6159 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 84825.74 | 84825.74 | 1.0000 | 4.31407234 | 3.946300 | 27.80 | 15.77 | 0.00741060 | 46849.8 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84825.74 | 38.94 | 0.00557864 | 17.93 | 0.35392745 | 8.9686 | 26.70 | 0.00759109 | 26.70 | 0.00759109 | 31.6378 | 46562.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 111812.084 | 111812.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.946295 | 4.31406711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 111812.08 | 111812.08 | 1.0000 | 4.31406711 | 3.946295 | 8.19 | 6.07 | 0.00555916 | 22216.8 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111812.08 | 0.50 | 0.00431558 | 0.50 | 0.35392745 | 8.9686 | 15.56 | 0.00675082 | 15.56 | 0.00675082 | 55.8709 | 23141.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 3.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1707.50 | 1557.83 | 237.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 1707.50 | 1557.83 | 237.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 5.17 | 52.83 | 5.17 | 38.83 |
ZONE2 FINE STORAGE | 5.67 | 265.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.83 | 314.17 | 5.17 | 38.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.406 | 0.375 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
Electricity:Building | 643.89 | 4992.32 | 01-JAN-00:10 | 48037.94 | 03-APR-12:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 444.30 | 2759.73 | 01-JAN-00:10 | 33963.13 | 03-APR-12:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.11 | 483.00 | 26-APR-05:10 | 1795.24 | 23-JAN-12:10 |
WaterSystems:Electricity | 24.11 | 483.00 | 26-APR-05:10 | 1795.24 | 23-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 24.11 | 483.00 | 26-APR-05:10 | 1795.24 | 23-JAN-12:10 |
Fans:Electricity | 141.18 | 0.00 | 01-JAN-00:10 | 11424.84 | 04-APR-12:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 22.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
Ventilation (simple):Fans:Electricity | 22.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
ElectricityPurchased:Facility | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
ElectricityPurchased:Plant | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
Cogeneration:ElectricityPurchased | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
ElectricityNet:Plant | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
Cogeneration:ElectricityNet | 1037.09 | 5475.32 | 01-JAN-08:50 | 87129.56 | 28-JUN-14:50 |
Electricity:HVAC | 245.51 | 0.00 | 01-JAN-00:10 | 41559.31 | 30-JUN-16:10 |
General:Fans:Electricity | 118.53 | 0.00 | 01-JAN-00:10 | 9119.55 | 13-JAN-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 126.98 | 0.00 | 01-JAN-00:10 | 32439.76 | 30-JUN-16:10 |
ExteriorLights:Electricity | 123.58 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.58 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 59.83 | 1750.00 | 20-APR-10:20 | 55722.72 | 01-JAN-07:40 |
Gas:HVAC | 59.83 | 1750.00 | 20-APR-10:20 | 55722.72 | 01-JAN-07:40 |
Heating:Gas | 59.83 | 1750.00 | 20-APR-10:20 | 55722.72 | 01-JAN-07:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 693.71 | 0.00 | 01-JAN-00:10 | 158891.58 | 30-JUN-16:10 |
EnergyTransfer:Building | 304.12 | 0.00 | 01-JAN-00:10 | 70992.20 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 71.89 | 0.00 | 01-JAN-00:10 | 16260.15 | 28-JUN-16:20 |
Heating:EnergyTransfer | 25.98 | 0.00 | 01-JAN-00:10 | 42381.86 | 01-JAN-07:40 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.50 | 0.00 | 01-JAN-00:10 | 15217.50 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 278.14 | 0.00 | 01-JAN-00:10 | 70992.20 | 30-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 69.39 | 0.00 | 01-JAN-00:10 | 16260.15 | 28-JUN-16:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 232.06 | 0.00 | 01-JAN-00:10 | 56374.98 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.31 | 0.00 | 01-JAN-00:10 | 26157.73 | 01-JAN-07:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 208.75 | 0.00 | 01-JAN-00:10 | 56374.98 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.17 | 0.00 | 01-JAN-00:10 | 16224.12 | 01-JAN-07:40 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.17 | 0.00 | 01-JAN-00:10 | 16224.12 | 01-JAN-07:40 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 389.59 | 0.00 | 01-JAN-00:10 | 87899.38 | 30-JUN-16:10 |
HeatingCoils:EnergyTransfer | 3.15 | 0.00 | 01-JAN-00:10 | 41151.57 | 01-JAN-07:40 |
CoolingCoils:EnergyTransfer | 386.44 | 0.00 | 01-JAN-00:10 | 87899.38 | 30-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.504 | -69.387 | 0.000 | 0.000 | 3.622 | 30.994 | 31.946 | 15.423 | 0.000 | 5.991 | 0.001 | 0.000 | -10.743 | 0.000 | -7.885 | -2.465 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 23.307 | -208.748 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 24.417 | 74.175 | 0.000 | 0.000 | 0.000 | -49.808 | -0.004 |
ZONE3 BULK STORAGE | 0.171 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 50.314 | 0.000 | 16.433 | 144.411 | 0.000 | -20.110 | 0.000 | -612.864 | -0.013 |
Total Facility | 0.171 | 0.000 | 25.810 | -278.135 | 0.000 | 0.000 | 3.622 | 481.960 | 139.282 | 65.737 | 0.000 | 46.841 | 218.588 | 0.000 | -30.853 | 0.000 | -670.557 | -2.482 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | -24084.66 | 0.00 | 0.00 | 25.92 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 23726.22 | 0.00 | -498.57 | 0.00 | -329.10 | 0.00 |
ZONE2 FINE STORAGE | 18-JUN-08:23 | 0.00 | 0.00 | 0.00 | -70638.94 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 3017.39 | 66421.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -84539.35 | 0.00 | 0.00 | 22.77 | 4546.06 | 2623.78 | 0.00 | 0.00 | 368.76 | 142542.93 | 0.00 | -544.52 | 0.00 | -65020.43 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-06:01 | 0.00 | 0.00 | 30729.82 | 0.00 | 0.00 | 0.00 | 54.38 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -726.27 | 0.00 | -689.22 | -30528.91 |
ZONE2 FINE STORAGE | 01-JAN-07:33 | 0.00 | 0.00 | 87391.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6497.90 | -82093.86 |
ZONE3 BULK STORAGE | 01-JAN-07:25 | 16285.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1344.08 | 0.00 | -15399.27 | -2301.46 |
Total Facility | 01-JAN-07:33 | 16226.26 | 0.00 | 87391.87 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2332.44 | 0.00 | -22987.07 | -83290.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3913 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3913 | 0.0865 | 1.0000 | 0.1203 | 0.0865 | ||
PSZ-FINE STORAGE | 3.9463 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.9463 | 0.0897 | 1.0000 | 0.3539 | 0.0897 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3913 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3913 | 1.0000 | 1.0000 | 0.1203 | 0.0865 | ||
PSZ-FINE STORAGE | 3.9463 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.9463 | 1.0000 | 1.0000 | 0.3539 | 0.0897 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.9463 | 3.9463 | 3.9463 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.9463 | 3.9463 | 3.9463 | 3.9463 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 0.3852 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.9463 | 3.9463 | 3.9463 | 0.3539 | 0.4893 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3913 | 1.3913 | 1.3913 | 1.3913 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.9463 | 3.9463 | 3.9463 | 3.9463 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 5.17 |
Number of hours cooling loads not met | 38.83 |
Number of hours not met | 44.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 59.83 | 55722.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 126.98 | 32439.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.58 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 22.65 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 118.53 | 9119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.11 | 1795.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1037.09 |
Natural Gas | 0.00 | 59.83 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1096.92 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 26.26 |
Fans (All) | 29.20 |
Service Water Heating | 4.99 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 214.49 |
Subtotal | 214.49 |
Natural Gas [MJ/m2] | |
Space Heating | 12.37 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 12.37 |
Subtotal | 12.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 43.94 |
Space Heating | 5.45 |
Space Cooling | 11.58 |
Fans (All) | 12.87 |
Service Water Heating | 2.20 |
Receptacle Equipment | 12.70 |
Miscellaneous | 11.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647484E+10 |
February | 0.000 | 0.485511E+10 |
March | 0.000 | 0.522250E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.472421E+10 |
November | 0.000 | 0.470998E+10 |
December | 0.000 | 0.617817E+10 |
Annual Sum or Average | 0.598344E+11 | |
Minimum of Months | 0.000 | 0.453600E+10 |
Maximum of Months | 0.000 | 0.647484E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175244E+10 | 5714.95 | 31-JAN-16:30 | 29.00 | 10.69 | 0.240455E+09 | 304.77 | 11-JAN-13:09 | 18.00 | 11.14 |
February | 0.762321E+09 | 4100.12 | 25-FEB-17:00 | 17.00 | 8.56 | 0.218472E+09 | 303.14 | 11-FEB-14:30 | 15.00 | 13.12 |
March | 0.215233E+10 | 6658.30 | 18-MAR-16:00 | 27.20 | 11.06 | 0.261809E+09 | 302.84 | 10-MAR-09:20 | 17.40 | 11.72 |
April | 0.619397E+10 | 22839.25 | 17-APR-05:01 | 14.33 | 9.39 | 0.248758E+09 | 302.17 | 11-APR-07:10 | 18.00 | 8.54 |
May | 0.818962E+10 | 22854.93 | 30-MAY-05:01 | 18.00 | 8.73 | 0.259010E+09 | 301.60 | 17-MAY-08:09 | 27.17 | 13.64 |
June | 0.109006E+11 | 23592.28 | 19-JUN-05:01 | 22.17 | 10.14 | 0.259134E+09 | 301.62 | 30-JUN-07:19 | 29.67 | 19.22 |
July | 0.103744E+11 | 23541.32 | 31-JUL-05:01 | 25.83 | 15.54 | 0.249189E+09 | 301.62 | 15-JUL-14:09 | 34.17 | 21.46 |
August | 0.107249E+11 | 24084.53 | 22-AUG-05:01 | 23.00 | 15.11 | 0.269115E+09 | 301.62 | 12-AUG-12:09 | 35.17 | 21.72 |
September | 0.915997E+10 | 23626.60 | 27-SEP-05:01 | 20.00 | 13.60 | 0.249150E+09 | 301.62 | 02-SEP-15:39 | 32.73 | 21.02 |
October | 0.559513E+10 | 23947.92 | 05-OCT-05:01 | 19.00 | 12.99 | 0.247722E+09 | 301.62 | 07-OCT-08:09 | 24.92 | 17.70 |
November | 0.264507E+10 | 15912.64 | 03-NOV-05:03 | 16.00 | 12.46 | 0.235268E+09 | 301.60 | 02-NOV-12:50 | 25.83 | 15.54 |
December | 0.937504E+09 | 4677.52 | 22-DEC-16:30 | 24.50 | 9.77 | 0.233985E+09 | 305.31 | 11-DEC-14:09 | 19.17 | 7.33 |
Annual Sum or Average | 0.693882E+11 | 0.297207E+10 | ||||||||
Minimum of Months | 0.762321E+09 | 4100.12 | 14.33 | 8.56 | 0.218472E+09 | 301.60 | 15.00 | 7.33 | ||
Maximum of Months | 0.109006E+11 | 24084.53 | 29.00 | 15.54 | 0.269115E+09 | 305.31 | 35.17 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113909E+09 | 5990.58 | 07-JAN-07:10 | 14.50 | 8.51 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 5439233.26 | 7664.45 | 13-FEB-07:10 | 8.33 | 8.33 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.922931E+09 | 13168.72 | 18-MAR-17:23 | 26.35 | 12.54 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.164200E+11 | 65921.48 | 25-APR-17:05 | 32.83 | 15.31 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.263870E+11 | 67091.70 | 29-MAY-12:32 | 30.67 | 13.45 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.440415E+11 | 70638.93 | 18-JUN-08:23 | 31.00 | 17.18 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.416346E+11 | 69284.55 | 11-JUL-20:23 | 33.00 | 19.44 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.377782E+11 | 69319.77 | 21-AUG-17:04 | 33.92 | 17.93 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.289800E+11 | 69255.67 | 14-SEP-17:42 | 30.18 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.113187E+11 | 68331.18 | 04-OCT-17:42 | 33.17 | 17.36 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.113978E+10 | 13676.72 | 01-NOV-15:10 | 28.83 | 16.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 10694259.93 | 7937.92 | 21-DEC-07:10 | 11.33 | 4.23 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.208753E+12 | 0.00 | ||||||||
Minimum of Months | 5439233.26 | 5990.58 | 8.33 | 4.23 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.440415E+11 | 70638.93 | 33.92 | 19.44 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 | 1.80 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 | 11.06 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.80 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.33 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508648E+09 | 30729.79 | 03-JAN-06:01 | 8.33 |
February | 0.539405E+09 | 30219.64 | 13-FEB-06:01 | 8.00 |
March | 0.404578E+09 | 29319.68 | 27-MAR-05:01 | 2.52 |
April | 16049434.46 | 830.13 | 03-APR-06:15 | 16.67 |
May | 396303.13 | 287.13 | 01-MAY-06:25 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 33872028.38 | 4811.86 | 25-OCT-06:20 | 5.00 |
November | 0.153592E+09 | 17941.55 | 24-NOV-06:03 | 3.17 |
December | 0.846992E+09 | 30406.41 | 11-DEC-06:01 | 9.17 |
Annual Sum or Average | 0.250353E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.846992E+09 | 30729.79 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504583E+10 | 87391.52 | 01-JAN-07:33 | 0.83 |
February | 0.400415E+10 | 7424.30 | 17-FEB-07:25 | 12.00 |
March | 0.393016E+10 | 7811.08 | 16-MAR-07:00 | 12.70 |
April | 0.824331E+09 | 7362.62 | 24-APR-06:25 | 17.50 |
May | 0.279091E+09 | 7380.63 | 27-MAY-06:25 | 17.50 |
June | 7127932.34 | 7026.51 | 21-JUN-06:01 | 19.17 |
July | 3939378.62 | 6981.65 | 01-JUL-06:01 | 18.83 |
August | 6694041.40 | 6668.20 | 25-AUG-06:12 | 22.33 |
September | 0.102562E+09 | 6978.70 | 15-SEP-06:15 | 18.07 |
October | 0.119120E+10 | 7634.50 | 20-OCT-07:00 | 15.00 |
November | 0.290069E+10 | 7441.02 | 24-NOV-07:50 | 6.50 |
December | 0.501110E+10 | 60685.70 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 0.233069E+11 | |||
Minimum of Months | 3939378.62 | 6668.20 | -0.7 | |
Maximum of Months | 0.504583E+10 | 87391.52 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170750E+09 | 16285.12 | 01-JAN-07:25 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.170750E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.170750E+09 | 16285.12 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16938444.58 | 0.106789E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127152E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51242529.94 | 0.123897E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440273E+09 | 0.464983E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782735E+09 | 0.258960E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136954E+10 | 70581225.05 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110502E+10 | 67876130.73 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109295E+10 | 0.104741E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763593E+09 | 0.187174E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330526E+09 | 0.716010E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36255655.75 | 0.106236E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2018888.41 | 0.137399E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.599110E+10 | 0.788504E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67876130.73 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136954E+10 | 0.137399E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11089763.18 | 0.665511E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606759E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29865773.31 | 0.807181E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139954E+10 | 0.360943E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313891E+10 | 0.224691E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667309E+10 | 0.732277E+09 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561513E+10 | 0.691829E+09 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383274E+10 | 0.109733E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279899E+10 | 0.183255E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892106E+09 | 0.532932E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19407970.88 | 0.713009E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6297936.78 | 0.634352E+10 |
Annual Sum or Average | 0.136656E+12 | 0.244172E+11 | 0.498078E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691829E+09 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667309E+10 | 0.807181E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834525E+09 | 0.131946E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158484E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152783E+09 | 0.227028E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303245E+09 | 0.154835E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21294653.44 | 0.119627E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192236E+09 | 0.597901E+10 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141361E+09 | 0.672230E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130301E+09 | 0.817813E+10 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44474958.03 | 0.110397E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45943897.30 | 0.203036E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137772E+09 | 0.189407E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324510E+09 | 0.136711E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.232845E+10 | 0.164027E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597901E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834525E+09 | 0.227028E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.13 | 31-JAN-17:10 | 5806.80 | 12-JAN-07:03 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5964.77 | 01-FEB-07:03 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.75 | 16-MAR-16:10 | 7179.46 | 27-MAR-06:05 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3698.64 | 14-APR-16:10 | 5028.46 | 21-APR-06:02 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4513.12 | 31-MAY-16:10 | 3654.02 | 01-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.51 | 30-JUN-16:10 | 1637.88 | 21-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.11 | 20-JUL-17:00 | 622.23 | 27-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5963.15 | 25-AUG-17:00 | 1574.78 | 24-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4961.33 | 08-SEP-16:10 | 2461.58 | 22-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3737.24 | 06-OCT-16:10 | 6197.86 | 25-OCT-06:02 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.38 | 01-NOV-16:10 | 6037.87 | 24-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.96 | 21-DEC-15:00 | 7582.09 | 06-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.23 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.51 | 7582.09 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.22 | 31-JAN-16:10 | 9198.41 | 11-JAN-08:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 13061.03 | 02-FEB-16:55 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.18 | 16-MAR-16:00 | 12584.67 | 11-MAR-16:05 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7661.60 | 10-APR-16:00 | 8151.44 | 21-APR-06:10 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10607.57 | 10-MAY-16:00 | 5951.50 | 23-MAY-06:10 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20467.89 | 30-JUN-16:00 | 3897.41 | 13-JUN-06:10 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.65 | 22-JUL-16:00 | 5206.16 | 26-JUL-24:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14381.53 | 12-AUG-16:00 | 10628.87 | 28-AUG-17:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12089.50 | 01-SEP-16:00 | 6041.46 | 15-SEP-07:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7770.26 | 10-OCT-15:10 | 11438.43 | 25-OCT-17:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.00 | 01-NOV-15:40 | 12177.20 | 22-NOV-16:05 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.46 | 25-DEC-16:00 | 10200.78 | 07-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3897.41 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.65 | 13061.03 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13389.01 | 06-JAN-13:10 | 18140.40 | 11-JAN-08:70 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 34774.32 | 02-FEB-12:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5939.10 | 15-MAR-13:00 | 32772.66 | 24-MAR-14:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9352.55 | 01-APR-17:00 | 27177.46 | 20-APR-11:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.03 | 15-MAY-17:00 | 19459.46 | 23-MAY-05:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2905.66 | 16-JUN-16:00 | 14166.43 | 13-JUN-06:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 30-JUL-18:00 | 23911.64 | 17-JUL-20:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.57 | 25-AUG-17:00 | 35868.75 | 28-AUG-17:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2965.02 | 17-SEP-11:53 | 22526.26 | 03-SEP-05:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2215.54 | 01-OCT-12:55 | 48729.57 | 07-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4779.91 | 19-NOV-15:00 | 51217.45 | 22-NOV-11:55 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5968.88 | 21-DEC-14:00 | 20794.49 | 07-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14166.43 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13389.01 | 51217.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5714.95 | 31-JAN-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 0.00 |
February | 4100.12 | 25-FEB-17:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.31 |
March | 6658.30 | 18-MAR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.37 | 0.00 |
April | 22839.25 | 17-APR-05:01 | 507.62 | 4105.10 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.25 |
May | 22854.93 | 30-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.11 |
June | 23592.28 | 19-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.89 |
July | 23541.32 | 31-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.63 |
August | 24084.53 | 22-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.10 |
September | 23626.60 | 27-SEP-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.15 |
October | 23947.92 | 05-OCT-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.29 |
November | 15912.64 | 03-NOV-05:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.30 |
December | 4677.52 | 22-DEC-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4100.12 | 290.07 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24084.53 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 718.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5990.58 | 07-JAN-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2493.17 |
February | 7664.45 | 13-FEB-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.32 |
March | 13168.72 | 18-MAR-17:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.92 |
April | 65921.48 | 25-APR-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3665.01 | 0.00 |
May | 67091.70 | 29-MAY-12:32 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.52 | 0.00 |
June | 70638.93 | 18-JUN-08:23 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3017.39 | 0.00 |
July | 69284.55 | 11-JUL-20:23 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3249.77 | 0.00 |
August | 69319.77 | 21-AUG-17:04 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4230.45 | 0.00 |
September | 69255.67 | 14-SEP-17:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.58 | 0.00 |
October | 68331.18 | 04-OCT-17:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4405.80 | 0.00 |
November | 13676.72 | 01-NOV-15:10 | 0.00 | 8999.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.36 | 0.00 |
December | 7937.92 | 21-DEC-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.19 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5990.58 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70638.93 | 0.00 | 8999.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4405.80 | 2493.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9743.95 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8389.29 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6619.99 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.17 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7673.43 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2963.69 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.36 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.26 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2843.02 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4396.99 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3630.85 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7021.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.26 | |
Maximum of Months | 0.00 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9743.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.759768E+11 | 62693.79 | 31-JAN-15:39 | 0.647484E+10 | 55722.72 | 01-JAN-07:40 |
February | 0.682302E+11 | 58453.55 | 22-FEB-15:00 | 0.485511E+10 | 12720.20 | 09-FEB-07:10 |
March | 0.788482E+11 | 65132.70 | 18-MAR-14:00 | 0.522250E+10 | 16291.51 | 27-MAR-06:10 |
April | 0.836695E+11 | 77011.10 | 14-APR-14:50 | 0.453600E+10 | 1750.00 | 01-APR-00:10 |
May | 0.927626E+11 | 79188.28 | 18-MAY-14:00 | 0.468720E+10 | 1750.00 | 01-MAY-00:10 |
June | 0.104324E+12 | 87129.56 | 28-JUN-14:50 | 0.453600E+10 | 1750.00 | 01-JUN-00:10 |
July | 0.102521E+12 | 84087.31 | 20-JUL-14:00 | 0.468720E+10 | 1750.00 | 01-JUL-00:10 |
August | 0.104615E+12 | 84455.95 | 25-AUG-14:39 | 0.468720E+10 | 1750.00 | 01-AUG-00:10 |
September | 0.939910E+11 | 81402.09 | 08-SEP-14:00 | 0.453600E+10 | 1750.00 | 01-SEP-00:10 |
October | 0.828470E+11 | 78134.50 | 02-OCT-13:00 | 0.472421E+10 | 6818.83 | 25-OCT-06:00 |
November | 0.737551E+11 | 66472.00 | 01-NOV-14:50 | 0.470998E+10 | 12732.04 | 24-NOV-07:10 |
December | 0.755471E+11 | 59379.29 | 22-DEC-15:30 | 0.617817E+10 | 33510.35 | 07-DEC-06:10 |
Annual Sum or Average | 0.103709E+13 | 0.598344E+11 | ||||
Minimum of Months | 0.682302E+11 | 58453.55 | 0.453600E+10 | 1750.00 | ||
Maximum of Months | 0.104615E+12 | 87129.56 | 0.647484E+10 | 55722.72 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.121017E+11 | 0.115358E+11 | 0.00 | 0.908725E+10 | 0.00 | 0.00 | 0.995212E+09 | 0.00 | 0.00 | 0.00 | 0.215351E+10 | 0.00 |
February | 0.366966E+11 | 0.103810E+11 | 0.105871E+11 | 0.00 | 0.831200E+10 | 0.00 | 0.00 | 0.301432E+09 | 0.00 | 0.00 | 0.00 | 0.195207E+10 | 0.00 |
March | 0.423649E+11 | 0.106733E+11 | 0.123357E+11 | 0.00 | 0.975545E+10 | 0.00 | 0.00 | 0.155943E+10 | 0.00 | 0.00 | 0.00 | 0.215945E+10 | 0.00 |
April | 0.397216E+11 | 0.948997E+10 | 0.114862E+11 | 0.00 | 0.111307E+11 | 0.00 | 0.00 | 0.984272E+10 | 0.00 | 0.00 | 0.00 | 0.199833E+10 | 0.00 |
May | 0.412341E+11 | 0.908454E+10 | 0.119357E+11 | 0.00 | 0.133952E+11 | 0.00 | 0.00 | 0.151066E+11 | 0.00 | 0.00 | 0.00 | 0.200637E+10 | 0.00 |
June | 0.408524E+11 | 0.849053E+10 | 0.118862E+11 | 0.00 | 0.162267E+11 | 0.00 | 0.00 | 0.249620E+11 | 0.00 | 0.00 | 0.00 | 0.190632E+10 | 0.00 |
July | 0.401034E+11 | 0.888654E+10 | 0.115358E+11 | 0.00 | 0.160271E+11 | 0.00 | 0.00 | 0.240583E+11 | 0.00 | 0.00 | 0.00 | 0.191000E+10 | 0.00 |
August | 0.423649E+11 | 0.948055E+10 | 0.123357E+11 | 0.00 | 0.157077E+11 | 0.00 | 0.00 | 0.227701E+11 | 0.00 | 0.00 | 0.00 | 0.195612E+10 | 0.00 |
September | 0.397216E+11 | 0.995669E+10 | 0.114862E+11 | 0.00 | 0.133518E+11 | 0.00 | 0.00 | 0.175666E+11 | 0.00 | 0.00 | 0.00 | 0.190808E+10 | 0.00 |
October | 0.401034E+11 | 0.111636E+11 | 0.115358E+11 | 0.00 | 0.104585E+11 | 0.00 | 0.00 | 0.757032E+10 | 0.00 | 0.00 | 0.00 | 0.201542E+10 | 0.00 |
November | 0.385909E+11 | 0.115360E+11 | 0.110862E+11 | 0.00 | 0.866913E+10 | 0.00 | 0.00 | 0.186520E+10 | 0.00 | 0.00 | 0.00 | 0.200768E+10 | 0.00 |
December | 0.401034E+11 | 0.123327E+11 | 0.115358E+11 | 0.00 | 0.906028E+10 | 0.00 | 0.00 | 0.382102E+09 | 0.00 | 0.00 | 0.00 | 0.213285E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123577E+12 | 0.139282E+12 | 0.141182E+12 | 0.00 | 0.126980E+12 | 0.241062E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.849053E+10 | 0.105871E+11 | 0.00 | 0.831200E+10 | 0.00 | 0.00 | 0.301432E+09 | 0.00 | 0.00 | 0.00 | 0.190632E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.123327E+11 | 0.123357E+11 | 0.00 | 0.162267E+11 | 0.00 | 0.00 | 0.249620E+11 | 0.00 | 0.00 | 0.00 | 0.215945E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.647484E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.485511E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.522250E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.472421E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.470998E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.617817E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598344E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.647484E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 9119.55 | 02-JAN-07:49 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 9119.55 | 22-FEB-15:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 9119.55 | 02-MAR-14:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 11424.84 | 04-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 11424.84 | 01-MAY-15:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 11424.84 | 03-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 11424.84 | 03-JUL-16:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 11424.84 | 03-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 11424.84 | 08-SEP-10:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 11424.84 | 03-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 9119.55 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 9119.55 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 9119.55 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 11424.84 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6245.57 | 31-JAN-16:10 | 0.00 | 0.00 | 0.00 | 1795.24 | 23-JAN-12:09 | 0.00 |
February | 1848.69 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1794.56 | 01-FEB-12:39 | 0.00 |
March | 8540.02 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1784.78 | 01-MAR-12:09 | 0.00 |
April | 19272.59 | 14-APR-16:10 | 0.00 | 0.00 | 0.00 | 1763.46 | 01-APR-11:09 | 0.00 |
May | 22293.35 | 18-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.73 | 01-MAY-11:20 | 0.00 |
June | 32439.76 | 30-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1715.54 | 01-JUN-11:20 | 0.00 |
July | 28596.76 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1700.83 | 01-JUL-11:09 | 0.00 |
August | 28988.28 | 25-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1706.31 | 31-AUG-11:39 | 0.00 |
September | 24831.76 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1725.17 | 30-SEP-11:00 | 0.00 |
October | 20338.08 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1750.32 | 31-OCT-11:50 | 0.00 |
November | 9961.49 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1774.25 | 30-NOV-12:50 | 0.00 |
December | 2775.45 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 1790.34 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1848.69 | 0.00 | 0.00 | 0.00 | 1700.83 | 0.00 | ||
Maximum of Months | 32439.76 | 0.00 | 0.00 | 0.00 | 1795.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 62693.79 | 31-JAN-15:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 6084.04 | 0.00 |
February | 58453.55 | 22-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 1848.69 | 0.00 |
March | 65132.70 | 18-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 8540.02 | 0.00 |
April | 77011.10 | 14-APR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 18130.96 | 0.00 |
May | 79188.28 | 18-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 20331.36 | 0.00 |
June | 87129.56 | 28-JUN-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 28292.69 | 0.00 |
July | 84087.31 | 20-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 25253.96 | 0.00 |
August | 84455.95 | 25-AUG-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 25617.33 | 0.00 |
September | 81402.09 | 08-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 22557.41 | 0.00 |
October | 78134.50 | 02-OCT-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 19300.88 | 0.00 |
November | 66472.00 | 01-NOV-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 9898.68 | 0.00 |
December | 59379.29 | 22-DEC-15:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 2775.45 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 58453.55 | 35620.03 | 10112.62 | 0.00 | 0.00 | 9119.55 | 0.00 | 0.00 | 1848.69 | 0.00 | |
Maximum of Months | 87129.56 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11424.84 | 0.00 | 0.00 | 28292.69 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 55722.72 | 01-JAN-07:40 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 12720.20 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 16291.51 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1750.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1750.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 6818.83 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 12732.04 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 33510.35 | 07-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 55722.72 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.09 | 0.83 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.46 | 1.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.41 | 0.50 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.49 | 0.83 | 24.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.87 | 2.83 | 24.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.67 | 8.33 | 24.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.99 | 8.17 | 25.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.44 | 9.00 | 24.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.99 | 7.50 | 24.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.17 | 2.00 | 24.77 |
November | 0.33 | 20.53 | 0.33 | 20.53 | 0.17 | 24.53 | 0.17 | 24.53 |
December | 2.33 | 20.27 | 2.33 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.17 | 20.31 | 5.17 | 20.31 | 52.83 | 26.26 | 38.83 | 24.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.53 | 2.33 | 20.53 | 13.33 | 26.99 | 9.00 | 25.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.77 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 27.96 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 27.85 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 27.79 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 27.66 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.58 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 14.79 | 0.00 | 265.17 | 27.80 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 14.98 | 0.00 | 0.00 | 66.00 | 27.96 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.83 | 23.19 | 46.17 | 21.16 | 46.17 | 21.16 |
February | 275.33 | 23.04 | 38.67 | 21.12 | 38.67 | 21.12 |
March | 282.00 | 23.25 | 29.50 | 21.36 | 27.33 | 21.16 |
April | 73.83 | 23.80 | 68.33 | 23.90 | 0.00 | 0.00 |
May | 15.83 | 23.95 | 106.83 | 23.91 | 0.00 | 0.00 |
June | 2.00 | 24.90 | 269.33 | 23.92 | 2.00 | 24.90 |
July | 4.67 | 24.84 | 291.83 | 23.93 | 4.67 | 24.84 |
August | 4.50 | 24.83 | 315.33 | 23.93 | 4.50 | 24.83 |
September | 3.33 | 24.76 | 294.00 | 23.92 | 3.33 | 24.76 |
October | 104.50 | 23.53 | 108.17 | 23.92 | 0.50 | 24.82 |
November | 196.00 | 23.34 | 47.83 | 22.99 | 18.83 | 21.59 |
December | 300.00 | 22.88 | 91.50 | 21.27 | 91.50 | 21.27 |
Annual Sum or Average | 1557.83 | 23.21 | 1707.50 | 23.57 | 237.50 | 21.46 |
Minimum of Months | 2.00 | 22.88 | 29.50 | 21.12 | 0.00 | 0.00 |
Maximum of Months | 300.00 | 24.90 | 315.33 | 23.93 | 91.50 | 24.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.260392E+10 | 0.709529E+09 | 195.25 | 0.259791E+10 | 6014811.33 | 0.00 | 0.41 | 31-JAN-16:30 | 0.00 | 01-JAN-00:05 | 7975.97 | 31-JAN-16:30 | 7975.97 | 31-JAN-16:30 | 431.80 | 09-JAN-11:30 | 2327.50 | 31-JAN-16:30 | 0.00 | 01-JAN-00:05 |
February | 0.109062E+10 | 0.297117E+09 | 128.92 | 0.104190E+10 | 48716930.39 | 0.00 | 0.24 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 | 5164.71 | 22-FEB-16:30 | 5164.71 | 22-FEB-16:30 | 726.97 | 18-FEB-11:40 | 1387.55 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 0.306160E+10 | 0.839717E+09 | 220.78 | 0.304261E+10 | 18988426.24 | 0.00 | 0.42 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 8679.45 | 18-MAR-16:00 | 8679.45 | 18-MAR-16:00 | 670.00 | 06-MAR-13:15 | 2431.42 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.804568E+10 | 0.231760E+10 | 278.20 | 0.804568E+10 | 0.00 | 0.00 | 1.00 | 05-APR-05:02 | 0.00 | 01-APR-00:10 | 24466.25 | 26-APR-05:01 | 24466.25 | 26-APR-05:01 | 0.00 | 06-APR-05:01 | 5798.85 | 26-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.105765E+11 | 0.315052E+10 | 317.59 | 0.105765E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 24547.67 | 11-MAY-05:01 | 24547.67 | 11-MAY-05:01 | 0.00 | 04-MAY-14:20 | 5818.38 | 11-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.140708E+11 | 0.453356E+10 | 362.22 | 0.140533E+11 | 17563599.76 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:05 | 25402.81 | 19-JUN-05:01 | 25402.81 | 19-JUN-05:01 | 1223.25 | 17-JUN-17:00 | 7206.42 | 25-JUN-17:11 | 0.00 | 01-JUN-00:05 |
July | 0.144216E+11 | 0.440759E+10 | 345.82 | 0.132984E+11 | 0.112322E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 29805.23 | 14-JUL-05:01 | 25874.82 | 12-JUL-05:01 | 10912.18 | 14-JUL-05:06 | 6904.93 | 20-JUL-17:38 | 0.00 | 01-JUL-00:10 |
August | 0.150350E+11 | 0.457295E+10 | 351.52 | 0.137922E+11 | 0.124286E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 29155.40 | 10-AUG-05:01 | 26115.40 | 17-AUG-05:01 | 9674.70 | 10-AUG-05:05 | 7441.17 | 13-AUG-16:11 | 0.00 | 01-AUG-00:10 |
September | 0.127617E+11 | 0.375520E+10 | 312.65 | 0.116865E+11 | 0.107524E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 29345.30 | 05-SEP-05:01 | 25458.50 | 20-SEP-05:01 | 9404.80 | 05-SEP-05:06 | 6800.97 | 02-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.734942E+10 | 0.208349E+10 | 269.54 | 0.713667E+10 | 0.212755E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 27724.92 | 03-OCT-05:01 | 25503.66 | 05-OCT-05:01 | 6348.80 | 03-OCT-05:13 | 6460.58 | 03-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.365319E+10 | 0.990692E+09 | 218.17 | 0.349704E+10 | 0.156150E+09 | 0.00 | 0.83 | 03-NOV-05:03 | 0.00 | 01-NOV-00:10 | 19872.75 | 03-NOV-05:03 | 17648.82 | 03-NOV-05:03 | 2268.64 | 13-NOV-08:20 | 4959.80 | 03-NOV-05:03 | 0.00 | 01-NOV-00:10 |
December | 0.138593E+10 | 0.376821E+09 | 139.58 | 0.138586E+10 | 71683.74 | 0.00 | 0.31 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 6342.89 | 22-DEC-16:30 | 6342.89 | 22-DEC-16:30 | 55.14 | 13-DEC-12:00 | 1705.86 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.940561E+11 | 0.280348E+11 | 3140.22 | 0.901545E+11 | 0.390157E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.109062E+10 | 0.297117E+09 | 128.92 | 0.104190E+10 | 0.00 | 0.00 | 0.24 | 0.00 | 5164.71 | 5164.71 | 0.00 | 1387.55 | 0.00 | |||||||
Maximum of Months | 0.150350E+11 | 0.457295E+10 | 362.22 | 0.140533E+11 | 0.124286E+10 | 0.00 | 1.00 | 0.00 | 29805.23 | 26115.40 | 10912.18 | 7441.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.926225E+09 | 0.285683E+09 | 41.33 | 0.926149E+09 | 75691.76 | 0.00 | 0.18 | 31-JAN-16:00 | 0.00 | 01-JAN-00:05 | 12179.07 | 31-JAN-16:00 | 12179.07 | 31-JAN-16:00 | 28.53 | 09-JAN-15:00 | 3983.86 | 31-JAN-16:00 | 0.00 | 01-JAN-00:05 |
February | 14354048.42 | 4314664.03 | 2.83 | 14348730.92 | 5317.49 | 0.00 | 0.04 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2506.94 | 23-FEB-14:00 | 2506.94 | 23-FEB-14:00 | 5.55 | 22-FEB-15:20 | 752.28 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.234336E+10 | 0.719711E+09 | 60.14 | 0.233797E+10 | 5388432.30 | 0.00 | 0.28 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 | 20313.97 | 18-MAR-15:00 | 20313.97 | 18-MAR-15:00 | 672.71 | 18-MAR-11:10 | 6266.98 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.232096E+11 | 0.752512E+10 | 288.89 | 0.232096E+11 | 0.00 | 0.00 | 1.00 | 12-APR-17:06 | 0.00 | 01-APR-00:10 | 75746.41 | 25-APR-17:05 | 75746.41 | 25-APR-17:05 | 0.00 | 10-APR-14:20 | 23889.80 | 14-APR-17:05 | 0.00 | 01-APR-00:10 |
May | 0.356130E+11 | 0.119561E+11 | 382.04 | 0.356130E+11 | 0.00 | 0.00 | 1.00 | 02-MAY-17:05 | 0.00 | 01-MAY-00:10 | 77114.54 | 21-MAY-18:33 | 77114.54 | 21-MAY-18:33 | 0.00 | 19-MAY-14:10 | 24497.61 | 07-MAY-15:52 | 0.00 | 01-MAY-00:10 |
June | 0.570344E+11 | 0.204284E+11 | 514.83 | 0.569721E+11 | 62310285.52 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:10 | 81346.30 | 18-JUN-08:23 | 81346.30 | 18-JUN-08:23 | 8805.84 | 17-JUN-17:06 | 27045.17 | 28-JUN-17:42 | 0.00 | 01-JUN-00:05 |
July | 0.577897E+11 | 0.196507E+11 | 544.82 | 0.539626E+11 | 0.382718E+10 | 0.00 | 1.00 | 01-JUL-17:04 | 0.00 | 01-JUL-00:15 | 90903.86 | 17-JUL-19:42 | 79954.88 | 11-JUL-20:23 | 21502.76 | 13-JUL-19:03 | 26536.57 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.535437E+11 | 0.181972E+11 | 516.15 | 0.499775E+11 | 0.356617E+10 | 0.00 | 1.00 | 01-AUG-17:04 | 0.00 | 01-AUG-00:13 | 87291.56 | 01-AUG-05:07 | 80249.36 | 20-AUG-16:52 | 23930.09 | 01-AUG-05:07 | 26674.04 | 13-AUG-14:22 | 0.00 | 01-AUG-00:10 |
September | 0.419718E+11 | 0.138114E+11 | 431.81 | 0.387794E+11 | 0.319241E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:15 | 96149.00 | 02-SEP-05:08 | 80460.34 | 17-SEP-14:32 | 32369.65 | 02-SEP-05:08 | 25690.70 | 08-SEP-17:42 | 0.00 | 01-SEP-00:10 |
October | 0.170312E+11 | 0.548683E+10 | 229.44 | 0.164846E+11 | 0.546584E+09 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 85313.59 | 01-OCT-15:53 | 78901.33 | 04-OCT-17:42 | 9067.23 | 01-OCT-16:33 | 25394.34 | 01-OCT-13:53 | 0.00 | 01-OCT-00:10 |
November | 0.288734E+10 | 0.874507E+09 | 80.50 | 0.279172E+10 | 95612605.97 | 0.00 | 0.31 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 22642.13 | 01-NOV-14:50 | 22113.80 | 01-NOV-15:00 | 3710.35 | 14-NOV-13:10 | 7141.86 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 17036556.46 | 5281322.56 | 1.67 | 17036556.46 | 0.00 | 0.00 | 0.05 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 | 3556.50 | 22-DEC-15:30 | 3556.50 | 22-DEC-15:30 | 0.00 | 22-DEC-15:30 | 1099.46 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.292382E+12 | 0.989452E+11 | 3094.45 | 0.281086E+12 | 0.112957E+11 | 0.00 | ||||||||||||||
Minimum of Months | 14354048.42 | 4314664.03 | 1.67 | 14348730.92 | 0.00 | 0.00 | 0.04 | 0.00 | 2506.94 | 2506.94 | 0.00 | 752.28 | 0.00 | |||||||
Maximum of Months | 0.577897E+11 | 0.204284E+11 | 544.82 | 0.569721E+11 | 0.382718E+10 | 0.00 | 1.00 | 0.00 | 96149.00 | 81346.30 | 32369.65 | 27045.17 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.40 | 37.09 | 22.31 | 138.84 | 159.43 | 0.00 | 0.00 | 744.00 |
February | 47.63 | 22.99 | 24.64 | 82.44 | 155.33 | 6.50 | 0.00 | 672.00 |
March | 63.17 | 30.08 | 33.09 | 130.36 | 143.82 | 0.00 | 0.00 | 744.00 |
April | 96.14 | 54.46 | 41.68 | 267.10 | 100.81 | 0.00 | 0.00 | 720.00 |
May | 96.75 | 53.88 | 42.87 | 292.37 | 78.40 | 0.00 | 0.00 | 744.00 |
June | 102.70 | 60.13 | 42.56 | 367.73 | 39.85 | 0.00 | 0.00 | 720.00 |
July | 75.00 | 34.87 | 40.13 | 272.70 | 35.26 | 0.00 | 0.00 | 744.00 |
August | 71.56 | 35.78 | 35.78 | 262.54 | 43.36 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 26.17 | 36.28 | 212.23 | 56.39 | 0.00 | 0.00 | 720.00 |
October | 63.81 | 36.38 | 27.42 | 164.75 | 129.24 | 0.00 | 0.00 | 744.00 |
November | 58.73 | 35.37 | 23.36 | 126.22 | 166.59 | 0.00 | 0.00 | 720.00 |
December | 47.92 | 27.46 | 20.46 | 95.61 | 192.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 70.52 | 37.94 | 32.58 | 201.59 | 108.25 | 6.50 | 0.00 | 8760.00 |
Minimum of Months | 47.63 | 22.99 | 20.46 | 82.44 | 35.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.70 | 60.13 | 42.87 | 367.73 | 192.82 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.40 | 37.09 | 22.31 | 138.84 | 159.43 | 0.00 | 0.00 | 744.00 |
February | 47.63 | 22.99 | 24.64 | 82.44 | 155.33 | 6.50 | 0.00 | 672.00 |
March | 63.17 | 30.08 | 33.09 | 130.36 | 143.82 | 0.00 | 0.00 | 744.00 |
April | 96.14 | 54.46 | 41.68 | 267.10 | 100.81 | 0.00 | 0.00 | 720.00 |
May | 96.75 | 53.88 | 42.87 | 292.37 | 78.40 | 0.00 | 0.00 | 744.00 |
June | 102.70 | 60.13 | 42.56 | 367.73 | 39.85 | 0.00 | 0.00 | 720.00 |
July | 75.00 | 34.87 | 40.13 | 272.70 | 35.26 | 0.00 | 0.00 | 744.00 |
August | 71.56 | 35.78 | 35.78 | 262.54 | 43.36 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 26.17 | 36.28 | 212.23 | 56.39 | 0.00 | 0.00 | 720.00 |
October | 63.81 | 36.38 | 27.42 | 164.75 | 129.24 | 0.00 | 0.00 | 744.00 |
November | 58.73 | 35.37 | 23.36 | 126.22 | 166.59 | 0.00 | 0.00 | 720.00 |
December | 47.92 | 27.46 | 20.46 | 95.61 | 192.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 70.52 | 37.94 | 32.58 | 201.59 | 108.25 | 6.50 | 0.00 | 8760.00 |
Minimum of Months | 47.63 | 22.99 | 20.46 | 82.44 | 35.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.70 | 60.13 | 42.87 | 367.73 | 192.82 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.17 | 0.00 | 10.17 | 10.27 | 94.88 | 0.00 | 0.00 | 744.00 |
February | 11.59 | 0.00 | 11.59 | 5.79 | 94.93 | 6.50 | 0.00 | 672.00 |
March | 15.41 | 0.00 | 15.40 | 19.14 | 87.56 | 0.00 | 0.00 | 744.00 |
April | 18.97 | 0.39 | 18.58 | 46.63 | 58.14 | 0.00 | 0.00 | 720.00 |
May | 22.85 | 2.60 | 20.25 | 65.83 | 41.61 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 5.78 | 20.88 | 112.07 | 20.93 | 0.00 | 0.00 | 720.00 |
July | 22.37 | 2.87 | 19.50 | 93.57 | 19.38 | 0.00 | 0.00 | 744.00 |
August | 17.84 | 0.69 | 17.15 | 78.93 | 24.49 | 0.00 | 0.00 | 744.00 |
September | 16.59 | 0.02 | 16.58 | 63.18 | 32.69 | 0.00 | 0.00 | 720.00 |
October | 12.83 | 0.00 | 12.83 | 25.72 | 77.31 | 0.00 | 0.00 | 744.00 |
November | 10.69 | 0.00 | 10.69 | 8.59 | 100.32 | 0.00 | 0.00 | 720.00 |
December | 9.50 | 0.00 | 9.50 | 5.55 | 116.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 16.30 | 1.03 | 15.27 | 44.78 | 63.92 | 6.50 | 0.00 | 8760.00 |
Minimum of Months | 9.50 | 0.00 | 9.50 | 5.55 | 19.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 5.78 | 20.88 | 112.07 | 116.41 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.17 | 0.00 | 10.17 | 10.27 | 94.88 | 0.00 | 0.00 | 744.00 |
February | 11.59 | 0.00 | 11.59 | 5.79 | 94.93 | 6.50 | 0.00 | 672.00 |
March | 15.41 | 0.00 | 15.40 | 19.14 | 87.56 | 0.00 | 0.00 | 744.00 |
April | 18.97 | 0.39 | 18.58 | 46.63 | 58.14 | 0.00 | 0.00 | 720.00 |
May | 22.85 | 2.60 | 20.25 | 65.83 | 41.60 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 5.78 | 20.88 | 112.07 | 20.93 | 0.00 | 0.00 | 720.00 |
July | 22.37 | 2.87 | 19.50 | 93.57 | 19.38 | 0.00 | 0.00 | 744.00 |
August | 17.84 | 0.69 | 17.15 | 78.93 | 24.49 | 0.00 | 0.00 | 744.00 |
September | 16.59 | 0.02 | 16.58 | 63.18 | 32.69 | 0.00 | 0.00 | 720.00 |
October | 12.83 | 0.00 | 12.83 | 25.72 | 77.31 | 0.00 | 0.00 | 744.00 |
November | 10.69 | 0.00 | 10.69 | 8.59 | 100.32 | 0.00 | 0.00 | 720.00 |
December | 9.50 | 0.00 | 9.50 | 5.55 | 116.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 16.30 | 1.03 | 15.27 | 44.78 | 63.92 | 6.50 | 0.00 | 8760.00 |
Minimum of Months | 9.50 | 0.00 | 9.50 | 5.55 | 19.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 5.78 | 20.88 | 112.07 | 116.41 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.95 | 72.99 | 7.17 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.38 | 60.18 | 8.50 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.01 | 67.13 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.32 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.38 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.87 | 47.55 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.92 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.27 | 75.41 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.40 | 81.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.55 | 63.73 | 29.67 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.40 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.94 | 13.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159107E+09 | 99342779.76 | 59764672.05 | 0.371867E+09 | 0.427005E+09 |
February | 0.115238E+09 | 55618011.45 | 59619625.07 | 0.199440E+09 | 0.375765E+09 |
March | 0.169195E+09 | 80557711.13 | 88637623.87 | 0.349164E+09 | 0.385207E+09 |
April | 0.249195E+09 | 0.141148E+09 | 0.108047E+09 | 0.692314E+09 | 0.261290E+09 |
May | 0.259126E+09 | 0.144316E+09 | 0.114810E+09 | 0.783082E+09 | 0.209990E+09 |
June | 0.266189E+09 | 0.155870E+09 | 0.110319E+09 | 0.953155E+09 | 0.103293E+09 |
July | 0.200875E+09 | 93400271.77 | 0.107475E+09 | 0.730388E+09 | 94430028.97 |
August | 0.191660E+09 | 95829306.54 | 95830791.14 | 0.703195E+09 | 0.116126E+09 |
September | 0.161880E+09 | 67829821.56 | 94049704.14 | 0.550098E+09 | 0.146172E+09 |
October | 0.170896E+09 | 97449973.46 | 73445718.80 | 0.441277E+09 | 0.346145E+09 |
November | 0.152241E+09 | 91685138.91 | 60555425.86 | 0.327164E+09 | 0.431789E+09 |
December | 0.128355E+09 | 73543699.73 | 54811288.17 | 0.256091E+09 | 0.516453E+09 |
Annual Sum or Average | 0.222396E+10 | 0.119659E+10 | 0.102737E+10 | 0.635723E+10 | 0.341367E+10 |
Minimum of Months | 0.115238E+09 | 55618011.45 | 54811288.17 | 0.199440E+09 | 94430028.97 |
Maximum of Months | 0.266189E+09 | 0.155870E+09 | 0.114810E+09 | 0.953155E+09 | 0.516453E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159107E+09 | 99342779.76 | 59764672.05 | 0.371867E+09 | 0.427005E+09 |
February | 0.115238E+09 | 55618011.45 | 59619625.07 | 0.199440E+09 | 0.375765E+09 |
March | 0.169195E+09 | 80557711.13 | 88637623.87 | 0.349164E+09 | 0.385207E+09 |
April | 0.249195E+09 | 0.141148E+09 | 0.108047E+09 | 0.692314E+09 | 0.261290E+09 |
May | 0.259126E+09 | 0.144316E+09 | 0.114810E+09 | 0.783082E+09 | 0.209990E+09 |
June | 0.266189E+09 | 0.155870E+09 | 0.110319E+09 | 0.953155E+09 | 0.103293E+09 |
July | 0.200875E+09 | 93400271.77 | 0.107475E+09 | 0.730388E+09 | 94430028.97 |
August | 0.191660E+09 | 95829306.54 | 95830791.14 | 0.703195E+09 | 0.116126E+09 |
September | 0.161880E+09 | 67829821.56 | 94049704.14 | 0.550098E+09 | 0.146172E+09 |
October | 0.170896E+09 | 97449973.46 | 73445718.80 | 0.441277E+09 | 0.346145E+09 |
November | 0.152241E+09 | 91685138.91 | 60555425.86 | 0.327164E+09 | 0.431789E+09 |
December | 0.128355E+09 | 73543699.73 | 54811288.17 | 0.256091E+09 | 0.516453E+09 |
Annual Sum or Average | 0.222396E+10 | 0.119659E+10 | 0.102737E+10 | 0.635723E+10 | 0.341367E+10 |
Minimum of Months | 0.115238E+09 | 55618011.45 | 54811288.17 | 0.199440E+09 | 94430028.97 |
Maximum of Months | 0.266189E+09 | 0.155870E+09 | 0.114810E+09 | 0.953155E+09 | 0.516453E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27238871.48 | 0.00 | 27238871.48 | 27495290.22 | 0.254138E+09 |
February | 28034301.15 | 0.00 | 28034301.15 | 14017823.58 | 0.229661E+09 |
March | 41265155.74 | 9217.84 | 41255937.89 | 51260680.95 | 0.234523E+09 |
April | 49166540.96 | 1018291.57 | 48148249.39 | 0.120855E+09 | 0.150692E+09 |
May | 61195132.50 | 6958965.06 | 54236167.44 | 0.176316E+09 | 0.111436E+09 |
June | 69095363.08 | 14980516.79 | 54114846.29 | 0.290495E+09 | 54245731.79 |
July | 59905105.16 | 7675173.34 | 52229931.81 | 0.250626E+09 | 51908372.78 |
August | 47786844.62 | 1844980.84 | 45941863.78 | 0.211407E+09 | 65601561.59 |
September | 43011447.90 | 46609.02 | 42964838.88 | 0.163761E+09 | 84728889.03 |
October | 34351845.36 | 0.00 | 34351845.36 | 68884196.64 | 0.207071E+09 |
November | 27698116.34 | 0.00 | 27698116.34 | 22259370.36 | 0.260036E+09 |
December | 25443604.37 | 0.00 | 25443604.37 | 14870488.94 | 0.311782E+09 |
Annual Sum or Average | 0.514192E+09 | 32533754.47 | 0.481659E+09 | 0.141225E+10 | 0.201582E+10 |
Minimum of Months | 25443604.37 | 0.00 | 25443604.37 | 14017823.58 | 51908372.78 |
Maximum of Months | 69095363.08 | 14980516.79 | 54236167.44 | 0.290495E+09 | 0.311782E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27238205.74 | 0.00 | 27238205.74 | 27494959.84 | 0.254135E+09 |
February | 28033515.96 | 0.00 | 28033515.96 | 14017012.94 | 0.229660E+09 |
March | 41263999.48 | 9217.41 | 41254782.06 | 51259122.70 | 0.234521E+09 |
April | 49165389.19 | 1018243.84 | 48147145.35 | 0.120854E+09 | 0.150690E+09 |
May | 61193550.49 | 6958638.89 | 54234911.61 | 0.176314E+09 | 0.111434E+09 |
June | 69093435.42 | 14979814.63 | 54113620.78 | 0.290492E+09 | 54244171.48 |
July | 59903401.17 | 7674813.60 | 52228587.57 | 0.250623E+09 | 51907300.05 |
August | 47785623.06 | 1844894.37 | 45940728.70 | 0.211406E+09 | 65600150.47 |
September | 43010240.49 | 46606.83 | 42963633.65 | 0.163759E+09 | 84727443.27 |
October | 34351002.04 | 0.00 | 34351002.04 | 68883550.93 | 0.207068E+09 |
November | 27697398.10 | 0.00 | 27697398.10 | 22258866.20 | 0.260035E+09 |
December | 25442948.03 | 0.00 | 25442948.03 | 14870155.70 | 0.311780E+09 |
Annual Sum or Average | 0.514179E+09 | 32532229.57 | 0.481646E+09 | 0.141223E+10 | 0.201580E+10 |
Minimum of Months | 25442948.03 | 0.00 | 25442948.03 | 14017012.94 | 51907300.05 |
Maximum of Months | 69093435.42 | 14979814.63 | 54234911.61 | 0.290492E+09 | 0.311780E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.273063E+09 | 0.195507E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223489E+09 | 0.145586E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361607E+09 | 0.179804E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562051E+09 | 0.184861E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638729E+09 | 0.185268E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671313E+09 | 0.133171E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562268E+09 | 0.105129E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521953E+09 | 0.127346E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400226E+09 | 0.126744E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346478E+09 | 0.211383E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244355E+09 | 0.195459E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226060E+09 | 0.219470E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503159E+10 | 0.200973E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223489E+09 | 0.105129E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671313E+09 | 0.219470E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.43 | 504.84 | 139.15 | 74.18 | 64.97 | 0.00 | 0.00 |
February | 169.72 | 493.77 | 118.45 | 45.98 | 72.46 | 0.00 | 0.00 |
March | 293.69 | 457.44 | 157.15 | 60.16 | 96.99 | 0.00 | 0.00 |
April | 626.46 | 316.90 | 230.22 | 109.70 | 120.52 | 0.00 | 0.00 |
May | 714.16 | 237.78 | 239.19 | 112.96 | 126.23 | 0.00 | 0.00 |
June | 955.55 | 117.50 | 258.71 | 131.83 | 126.88 | 0.00 | 0.00 |
July | 730.28 | 107.01 | 194.73 | 75.47 | 119.25 | 0.00 | 0.00 |
August | 682.19 | 134.94 | 178.80 | 72.93 | 105.86 | 0.00 | 0.00 |
September | 550.74 | 178.09 | 158.09 | 52.37 | 105.72 | 0.00 | 0.00 |
October | 377.15 | 409.30 | 153.26 | 72.77 | 80.49 | 0.00 | 0.00 |
November | 262.63 | 526.83 | 138.84 | 70.74 | 68.10 | 0.00 | 0.00 |
December | 195.07 | 611.20 | 114.84 | 54.92 | 59.93 | 0.00 | 0.00 |
Annual Sum or Average | 489.07 | 340.67 | 173.65 | 77.95 | 95.70 | 0.00 | 0.00 |
Minimum of Months | 169.72 | 107.01 | 114.84 | 45.98 | 59.93 | 0.00 | 0.00 |
Maximum of Months | 955.55 | 611.20 | 258.71 | 131.83 | 126.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1019.49 | 729.94 | 762.14 | 588.64 | 173.50 | 0.00 | 0.00 |
February | 923.81 | 601.79 | 741.53 | 476.70 | 264.83 | 0.00 | 0.00 |
March | 1350.08 | 671.31 | 1048.05 | 670.34 | 377.71 | 0.00 | 0.00 |
April | 2168.41 | 713.19 | 1619.06 | 1250.15 | 368.92 | 0.00 | 0.00 |
May | 2384.74 | 691.71 | 1782.09 | 1399.09 | 383.00 | 0.00 | 0.00 |
June | 2589.93 | 513.77 | 1876.85 | 1534.19 | 342.66 | 0.00 | 0.00 |
July | 2099.27 | 392.50 | 1520.74 | 1100.92 | 419.83 | 0.00 | 0.00 |
August | 1948.74 | 475.45 | 1401.43 | 1035.78 | 365.65 | 0.00 | 0.00 |
September | 1544.08 | 488.98 | 1127.50 | 707.27 | 420.23 | 0.00 | 0.00 |
October | 1293.60 | 789.21 | 1005.13 | 755.62 | 249.51 | 0.00 | 0.00 |
November | 942.73 | 754.09 | 746.93 | 540.79 | 206.13 | 0.00 | 0.00 |
December | 844.01 | 819.41 | 659.34 | 482.45 | 176.89 | 0.00 | 0.00 |
Annual Sum or Average | 1595.50 | 637.28 | 1192.93 | 880.38 | 312.55 | 0.00 | 0.00 |
Minimum of Months | 844.01 | 392.50 | 659.34 | 476.70 | 173.50 | 0.00 | 0.00 |
Maximum of Months | 2589.93 | 819.41 | 1876.85 | 1534.19 | 420.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788610E+09 | 0.135217E+10 | 0.372692E+09 | 0.198686E+09 | 0.174006E+09 | 0.00 | 0.00 |
February | 0.410599E+09 | 0.119453E+10 | 0.286543E+09 | 0.111236E+09 | 0.175307E+09 | 0.00 | 0.00 |
March | 0.786607E+09 | 0.122522E+10 | 0.420920E+09 | 0.161134E+09 | 0.259786E+09 | 0.00 | 0.00 |
April | 0.162378E+10 | 0.821409E+09 | 0.596722E+09 | 0.284332E+09 | 0.312390E+09 | 0.00 | 0.00 |
May | 0.191280E+10 | 0.636859E+09 | 0.640642E+09 | 0.302550E+09 | 0.338092E+09 | 0.00 | 0.00 |
June | 0.247678E+10 | 0.304556E+09 | 0.670567E+09 | 0.341700E+09 | 0.328867E+09 | 0.00 | 0.00 |
July | 0.195597E+10 | 0.286626E+09 | 0.521558E+09 | 0.202151E+09 | 0.319408E+09 | 0.00 | 0.00 |
August | 0.182718E+10 | 0.361431E+09 | 0.478893E+09 | 0.195348E+09 | 0.283544E+09 | 0.00 | 0.00 |
September | 0.142753E+10 | 0.461614E+09 | 0.409781E+09 | 0.135753E+09 | 0.274028E+09 | 0.00 | 0.00 |
October | 0.101016E+10 | 0.109627E+10 | 0.410494E+09 | 0.194900E+09 | 0.215594E+09 | 0.00 | 0.00 |
November | 0.680731E+09 | 0.136553E+10 | 0.359877E+09 | 0.183370E+09 | 0.176506E+09 | 0.00 | 0.00 |
December | 0.522482E+09 | 0.163703E+10 | 0.307597E+09 | 0.147087E+09 | 0.160509E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154232E+11 | 0.107432E+11 | 0.547628E+10 | 0.245825E+10 | 0.301804E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410599E+09 | 0.286626E+09 | 0.286543E+09 | 0.111236E+09 | 0.160509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.247678E+10 | 0.163703E+10 | 0.670567E+09 | 0.341700E+09 | 0.338092E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.273062E+10 | 0.195507E+10 | 0.204132E+10 | 0.157661E+10 | 0.464705E+09 | 0.00 | 0.00 |
February | 0.223488E+10 | 0.145586E+10 | 0.179391E+10 | 0.115324E+10 | 0.640673E+09 | 0.00 | 0.00 |
March | 0.361607E+10 | 0.179804E+10 | 0.280710E+10 | 0.179545E+10 | 0.101165E+10 | 0.00 | 0.00 |
April | 0.562051E+10 | 0.184860E+10 | 0.419661E+10 | 0.324038E+10 | 0.956236E+09 | 0.00 | 0.00 |
May | 0.638729E+10 | 0.185266E+10 | 0.477316E+10 | 0.374732E+10 | 0.102584E+10 | 0.00 | 0.00 |
June | 0.671311E+10 | 0.133170E+10 | 0.486480E+10 | 0.397663E+10 | 0.888172E+09 | 0.00 | 0.00 |
July | 0.562267E+10 | 0.105127E+10 | 0.407315E+10 | 0.294869E+10 | 0.112446E+10 | 0.00 | 0.00 |
August | 0.521949E+10 | 0.127345E+10 | 0.375358E+10 | 0.277422E+10 | 0.979357E+09 | 0.00 | 0.00 |
September | 0.400226E+10 | 0.126744E+10 | 0.292249E+10 | 0.183324E+10 | 0.108925E+10 | 0.00 | 0.00 |
October | 0.346477E+10 | 0.211382E+10 | 0.269215E+10 | 0.202386E+10 | 0.668288E+09 | 0.00 | 0.00 |
November | 0.244355E+10 | 0.195459E+10 | 0.193604E+10 | 0.140174E+10 | 0.534300E+09 | 0.00 | 0.00 |
December | 0.226060E+10 | 0.219470E+10 | 0.176597E+10 | 0.129220E+10 | 0.473773E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.503158E+11 | 0.200972E+11 | 0.376203E+11 | 0.277636E+11 | 0.985670E+10 | 0.00 | 0.00 |
Minimum of Months | 0.223488E+10 | 0.105127E+10 | 0.176597E+10 | 0.115324E+10 | 0.464705E+09 | 0.00 | 0.00 |
Maximum of Months | 0.671311E+10 | 0.219470E+10 | 0.486480E+10 | 0.397663E+10 | 0.112446E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.45 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.34 | 6.24 | 2.64 | 2.52 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.66 | 1.96 | 3.53 | 3.01 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.11 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.03 | -4.9 | 3.62 | 8.59 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.25 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.97 | 9.86 | 3.72 | 19.27 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.13 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.57 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.96 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.79 | 1.49 | 3.02 | 1.82 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.55 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.13 | 11.45 | 3.72 | 19.27 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.69 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.41 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.76 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.53 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.53 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.69 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.36 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.22 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.78 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 18.97 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.17 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.86 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.69 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.78 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.1 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.58 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.2 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.39 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.95 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.22 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.50 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.46 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.3 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.3 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.3 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.72 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.16 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.67 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.53 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.15 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.10 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.17 | 16-AUG-10:50 | 34.50 | 17.17 | 2.27 | 23.90 | 134.33 | 837.00 |
September | 22.21 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.52 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.04 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.04 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.15 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.72 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.69 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 13.98 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.74 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.15 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.10 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.16 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.15 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.860217E+09 | -720549632.1 | 0.00 | 0.00 | 744.00 | 0.00 | -139667625.8 | 58.99 | 0.00 | 0.00 |
February | 0.783077E+09 | -655394001.8 | 0.00 | 0.00 | 672.00 | 0.00 | -127682709.1 | 58.99 | 0.00 | 0.00 |
March | 0.865756E+09 | -728656675.1 | 0.00 | 0.00 | 744.00 | 0.00 | -137099580.7 | 58.99 | 0.00 | 0.00 |
April | 0.746104E+09 | -623087722.5 | 0.00 | 0.00 | 720.00 | 0.00 | -123016684.2 | 58.99 | 0.00 | 0.00 |
May | 0.712739E+09 | -587761350.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124977582.6 | 58.99 | 0.00 | 0.00 |
June | 0.654482E+09 | -535584113.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118898325.0 | 58.99 | 0.00 | 0.00 |
July | 0.616299E+09 | -494115577.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122183716.1 | 58.99 | 0.00 | 0.00 |
August | 0.661934E+09 | -538556917.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123376686.6 | 58.99 | 0.00 | 0.00 |
September | 0.656433E+09 | -537004273.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119428998.4 | 58.99 | 0.00 | 0.00 |
October | 0.721170E+09 | -592711039.1 | 0.00 | 0.00 | 744.00 | 0.00 | -128458870.9 | 58.99 | 0.00 | 0.00 |
November | 0.755754E+09 | -624736129.6 | 0.00 | 0.00 | 720.00 | 0.00 | -131018261.5 | 58.99 | 0.00 | 0.00 |
December | 0.839269E+09 | -697052382.2 | 0.00 | 0.00 | 744.00 | 0.00 | -142216135.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.887323E+10 | -.733521E+10 | 8760.00 | -.153803E+10 | 58.99 | |||||
Minimum of Months | 0.616299E+09 | -728656675.1 | 0.00 | 0.00 | 672.00 | 0.00 | -142216135.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.865756E+09 | -494115577.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118898325.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | ||||||||||
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427981E+09 | 31676.68 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418289E+09 | 31676.68 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359638E+09 | 31676.68 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24160700.21 | 5289.97 | 25-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115037E+09 | 19332.55 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762184E+09 | 31676.68 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210729E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.762184E+09 | 31676.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.630523E+09 | 84715.39 | 01-JAN-07:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245810E+09 | 57622.48 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876333E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.630523E+09 | 84715.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167508E+09 | 16086.41 | 01-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167508E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167508E+09 | 16086.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.260392E+10 | 0.259791E+10 | 7975.97 | 31-JAN-16:30 | 7975.97 | 0.00 |
February | 0.00 | 0.00 | 0.109062E+10 | 0.104190E+10 | 5164.71 | 22-FEB-16:30 | 5164.71 | 0.00 |
March | 0.00 | 0.00 | 0.306160E+10 | 0.304261E+10 | 8679.45 | 18-MAR-16:00 | 8679.45 | 0.00 |
April | 0.00 | 0.00 | 0.804568E+10 | 0.804568E+10 | 24466.25 | 26-APR-05:01 | 24466.25 | 0.00 |
May | 0.00 | 0.00 | 0.105765E+11 | 0.105765E+11 | 24547.67 | 11-MAY-05:01 | 24547.67 | 0.00 |
June | 0.00 | 0.00 | 0.140708E+11 | 0.140533E+11 | 25402.81 | 19-JUN-05:01 | 25402.81 | 0.00 |
July | 0.00 | 0.00 | 0.144216E+11 | 0.132984E+11 | 29805.23 | 14-JUL-05:01 | 20141.54 | 0.00 |
August | 0.00 | 0.00 | 0.150350E+11 | 0.137922E+11 | 29155.40 | 10-AUG-05:01 | 20405.73 | 0.00 |
September | 0.00 | 0.00 | 0.127617E+11 | 0.116865E+11 | 29345.30 | 05-SEP-05:01 | 21446.24 | 0.00 |
October | 0.00 | 0.00 | 0.734942E+10 | 0.713667E+10 | 27724.92 | 03-OCT-05:01 | 23043.92 | 0.00 |
November | 0.00 | 0.00 | 0.365319E+10 | 0.349704E+10 | 19872.75 | 03-NOV-05:03 | 17648.82 | 0.00 |
December | 0.00 | 0.00 | 0.138593E+10 | 0.138586E+10 | 6342.89 | 22-DEC-16:30 | 6342.89 | 0.00 |
Annual Sum or Average | 0.940561E+11 | 0.901545E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.109062E+10 | 0.104190E+10 | 5164.71 | 5164.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150350E+11 | 0.140533E+11 | 29805.23 | 25402.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.926225E+09 | 0.926149E+09 | 12179.07 | 31-JAN-16:00 | 12179.07 | 0.00 |
February | 0.00 | 0.00 | 14354048.42 | 14348730.92 | 2506.94 | 23-FEB-14:00 | 2506.94 | 0.00 |
March | 0.00 | 0.00 | 0.234336E+10 | 0.233797E+10 | 20313.97 | 18-MAR-15:00 | 20313.97 | 0.00 |
April | 0.00 | 0.00 | 0.232096E+11 | 0.232096E+11 | 75746.41 | 25-APR-17:05 | 75746.41 | 0.00 |
May | 0.00 | 0.00 | 0.356130E+11 | 0.356130E+11 | 77114.54 | 21-MAY-18:33 | 77114.54 | 0.00 |
June | 0.00 | 0.00 | 0.570344E+11 | 0.569721E+11 | 81346.30 | 18-JUN-08:23 | 81346.30 | 0.00 |
July | 0.00 | 0.00 | 0.577897E+11 | 0.539626E+11 | 90903.86 | 17-JUL-19:42 | 74075.16 | 0.00 |
August | 0.00 | 0.00 | 0.535437E+11 | 0.499775E+11 | 87291.56 | 01-AUG-05:07 | 63361.47 | 0.00 |
September | 0.00 | 0.00 | 0.419718E+11 | 0.387794E+11 | 96149.00 | 02-SEP-05:08 | 63779.35 | 0.00 |
October | 0.00 | 0.00 | 0.170312E+11 | 0.164846E+11 | 85313.59 | 01-OCT-15:53 | 77878.52 | 0.00 |
November | 0.00 | 0.00 | 0.288734E+10 | 0.279172E+10 | 22642.13 | 01-NOV-14:50 | 22007.38 | 0.00 |
December | 0.00 | 0.00 | 17036556.46 | 17036556.46 | 3556.50 | 22-DEC-15:30 | 3556.50 | 0.00 |
Annual Sum or Average | 0.292382E+12 | 0.281086E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 14354048.42 | 14348730.92 | 2506.94 | 2506.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.577897E+11 | 0.569721E+11 | 96149.00 | 81346.30 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 3219629.02 | 0.00 | 198.74 | 01-JAN-04:00 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 3219629.02 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3219629.02 | 0.00 | 198.74 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157586E+10 | 0.39 | 1586.21 | 02-JAN-07:10 | 1.03 |
February | 0.145063E+10 | 0.40 | 1586.21 | 01-FEB-13:20 | 1.03 |
March | 0.170020E+10 | 0.42 | 1586.21 | 01-MAR-09:40 | 1.02 |
April | 0.158717E+10 | 0.42 | 1586.21 | 11-APR-08:25 | 1.03 |
May | 0.167078E+10 | 0.45 | 1586.21 | 01-MAY-07:05 | 1.03 |
June | 0.172735E+10 | 0.53 | 1586.21 | 01-JUN-06:10 | 1.03 |
July | 0.166475E+10 | 0.49 | 1586.21 | 01-JUL-06:01 | 1.03 |
August | 0.177326E+10 | 0.49 | 1586.21 | 01-AUG-06:20 | 1.02 |
September | 0.162428E+10 | 0.45 | 1586.21 | 01-SEP-06:15 | 1.02 |
October | 0.158896E+10 | 0.40 | 1586.21 | 02-OCT-06:30 | 1.02 |
November | 0.150944E+10 | 0.38 | 1586.21 | 01-NOV-06:23 | 1.03 |
December | 0.158213E+10 | 0.40 | 1586.21 | 01-DEC-07:03 | 1.03 |
Annual Sum or Average | 0.194548E+11 | 0.44 | |||
Minimum of Months | 0.145063E+10 | 0.38 | 1586.21 | 1.02 | |
Maximum of Months | 0.177326E+10 | 0.53 | 1586.21 | 1.03 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.750817E+10 | 0.68 | 7533.34 | 13-JAN-15:30 | 1.72 |
February | 0.686136E+10 | 0.65 | 7533.34 | 22-FEB-15:10 | 1.72 |
March | 0.805525E+10 | 0.69 | 7533.34 | 02-MAR-14:40 | 1.72 |
April | 0.790973E+10 | 0.85 | 7533.34 | 04-APR-12:30 | 1.73 |
May | 0.871014E+10 | 0.99 | 7533.34 | 01-MAY-15:40 | 1.73 |
June | 0.979317E+10 | 1.31 | 7533.34 | 01-JUN-06:33 | 1.72 |
July | 0.960258E+10 | 1.33 | 7533.34 | 03-JUL-08:20 | 1.73 |
August | 0.964884E+10 | 1.27 | 7533.34 | 08-AUG-06:12 | 1.70 |
September | 0.856974E+10 | 1.13 | 7533.34 | 14-SEP-16:20 | 1.71 |
October | 0.777443E+10 | 0.78 | 7533.34 | 07-OCT-09:50 | 1.71 |
November | 0.715968E+10 | 0.63 | 7533.34 | 03-NOV-14:20 | 1.72 |
December | 0.747815E+10 | 0.67 | 7533.34 | 22-DEC-14:00 | 1.73 |
Annual Sum or Average | 0.990712E+11 | 0.92 | |||
Minimum of Months | 0.686136E+10 | 0.63 | 7533.34 | 1.70 | |
Maximum of Months | 0.979317E+10 | 1.33 | 7533.34 | 1.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 5.00 |
February | 0.47 | 1.34 |
March | 2.01 | 1.91 |
April | 3.88 | 0.29 |
May | 4.54 | 0.00 |
June | 3.66 | 0.01 |
July | 4.88 | 0.00 |
August | 4.24 | 0.03 |
September | 3.77 | 0.01 |
October | 4.03 | 1.18 |
November | 1.57 | 2.93 |
December | 0.40 | 1.24 |
Annual Sum or Average | 33.54 | 0.48 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.88 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.00 | 0.00 |
February | 1.33 | 0.00 |
March | 1.17 | 0.00 |
April | 0.92 | 0.00 |
May | 0.11 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.83 | 0.00 |
November | 2.08 | 0.00 |
December | 1.50 | 0.00 |
Annual Sum or Average | 9.94 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 4.77 | 0.00 |
May | 4.90 | 0.00 |
June | 10.36 | 0.00 |
July | 12.44 | 0.00 |
August | 14.42 | 0.00 |
September | 9.30 | 0.00 |
October | 1.62 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 57.90 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.42 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.228539E+10 | 0.634519E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.174775E+10 | 0.621513E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.253991E+10 | 0.535299E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.390478E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.482129E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.626090E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.607234E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.634621E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.537949E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.367245E+10 | 37010474.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.250014E+10 | 0.173978E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.195895E+10 | 0.111354E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.474896E+11 | 0.311586E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.174775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.634621E+10 | 0.111354E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.779385E+10 | 0.945388E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.686568E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.877496E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154348E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.206662E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.302216E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.292533E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.278460E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.223811E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.132613E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.803419E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.748343E+10 | 0.377426E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.198016E+12 | 0.132281E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.686568E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.302216E+11 | 0.945388E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157586E+10 | 0.260392E+10 | 0.427981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145063E+10 | 0.109062E+10 | 0.418289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170020E+10 | 0.306160E+10 | 0.359638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158717E+10 | 0.804568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167078E+10 | 0.105765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172735E+10 | 0.140708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166475E+10 | 0.144216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177326E+10 | 0.150350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162428E+10 | 0.127617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158896E+10 | 0.734942E+10 | 24160700.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150944E+10 | 0.365319E+10 | 0.115037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158213E+10 | 0.138593E+10 | 0.762184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194548E+11 | 0.940561E+11 | 0.210729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145063E+10 | 0.109062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177326E+10 | 0.150350E+11 | 0.762184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.750817E+10 | 0.926225E+09 | 0.630523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686136E+10 | 14354048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805525E+10 | 0.234336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790973E+10 | 0.232096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871014E+10 | 0.356130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979317E+10 | 0.570344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.960258E+10 | 0.577897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.964884E+10 | 0.535437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856974E+10 | 0.419718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777443E+10 | 0.170312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715968E+10 | 0.288734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747815E+10 | 17036556.46 | 0.245810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.990712E+11 | 0.292382E+12 | 0.876333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686136E+10 | 14354048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979317E+10 | 0.577897E+11 | 0.630523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157586E+10 | 0.00 | 0.00 | 0.00 | 0.709529E+09 | 0.00 | 0.634519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145063E+10 | 0.00 | 0.00 | 0.00 | 0.297117E+09 | 0.00 | 0.621513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170020E+10 | 0.00 | 0.00 | 0.00 | 0.839717E+09 | 0.00 | 0.535299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158717E+10 | 0.00 | 0.00 | 0.00 | 0.231760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167078E+10 | 0.00 | 0.00 | 0.00 | 0.315052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172735E+10 | 0.00 | 0.00 | 0.00 | 0.453356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166475E+10 | 0.00 | 0.00 | 0.00 | 0.440759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177326E+10 | 0.00 | 0.00 | 0.00 | 0.457295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162428E+10 | 0.00 | 0.00 | 0.00 | 0.375520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158896E+10 | 0.00 | 0.00 | 0.00 | 0.208349E+10 | 0.00 | 37010474.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150944E+10 | 0.00 | 0.00 | 0.00 | 0.990692E+09 | 0.00 | 0.173978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158213E+10 | 0.00 | 0.00 | 0.00 | 0.376821E+09 | 0.00 | 0.111354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194548E+11 | 0.00 | 0.00 | 0.00 | 0.280348E+11 | 0.00 | 0.311586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.145063E+10 | 0.00 | 0.00 | 0.00 | 0.297117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177326E+10 | 0.00 | 0.00 | 0.00 | 0.457295E+10 | 0.00 | 0.111354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.750817E+10 | 0.00 | 0.00 | 0.00 | 0.285683E+09 | 0.00 | 0.945388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686136E+10 | 0.00 | 0.00 | 0.00 | 4314664.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805525E+10 | 0.00 | 0.00 | 0.00 | 0.719711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790973E+10 | 0.00 | 0.00 | 0.00 | 0.752512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871014E+10 | 0.00 | 0.00 | 0.00 | 0.119561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979317E+10 | 0.00 | 0.00 | 0.00 | 0.204284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.960258E+10 | 0.00 | 0.00 | 0.00 | 0.196507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.964884E+10 | 0.00 | 0.00 | 0.00 | 0.181972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856974E+10 | 0.00 | 0.00 | 0.00 | 0.138114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777443E+10 | 0.00 | 0.00 | 0.00 | 0.548683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715968E+10 | 0.00 | 0.00 | 0.00 | 0.874507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747815E+10 | 0.00 | 0.00 | 0.00 | 5281322.56 | 0.00 | 0.377426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.990712E+11 | 0.00 | 0.00 | 0.00 | 0.989452E+11 | 0.00 | 0.132281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.686136E+10 | 0.00 | 0.00 | 0.00 | 4314664.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979317E+10 | 0.00 | 0.00 | 0.00 | 0.204284E+11 | 0.00 | 0.945388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259227E+09 | 6179417.78 | 0.00 | 2696378.38 | 0.00 | 0.147410E+09 | 0.363654E+09 | 0.00 | 0.16 |
February | 0.525613E+09 | 0.00 | 0.00 | 1264588.11 | 0.00 | 0.128528E+09 | 0.473622E+09 | 0.00 | 0.17 |
March | 0.299896E+09 | 26780520.19 | 0.00 | 2814960.46 | 0.00 | 0.123525E+09 | 0.482560E+09 | 0.00 | 0.17 |
April | 50923757.45 | 0.346215E+09 | 0.00 | 5496567.90 | 0.00 | 0.00 | 0.179904E+09 | 0.00 | 0.17 |
May | 1735572.72 | 0.612552E+09 | 0.00 | 6248965.95 | 0.00 | 0.00 | 71815253.85 | 0.00 | 0.17 |
June | 0.00 | 0.129887E+10 | 0.00 | 4841635.00 | 0.00 | 0.00 | 12909264.18 | 0.00 | 0.18 |
July | 0.00 | 0.162964E+10 | 0.00 | 1877445.03 | 0.00 | 0.00 | 8000061.46 | 0.00 | 0.17 |
August | 0.00 | 0.172240E+10 | 0.00 | 2894881.86 | 0.00 | 0.00 | 6127977.30 | 0.00 | 0.18 |
September | 0.00 | 0.123723E+10 | 0.00 | 2972765.00 | 0.00 | 0.00 | 14397143.51 | 0.00 | 0.17 |
October | 92974760.85 | 0.360313E+09 | 0.00 | 4808922.97 | 0.00 | 22848739.24 | 0.311249E+09 | 0.00 | 0.16 |
November | 0.190677E+09 | 34559381.91 | 0.00 | 3565318.42 | 225181.67 | 57466804.22 | 0.465814E+09 | 0.00 | 0.16 |
December | 0.511339E+09 | 252752.18 | 0.00 | 1523059.31 | 180000.48 | 0.256023E+09 | 0.364352E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.193239E+10 | 0.727499E+10 | 0.00 | 41005488.39 | 405182.15 | 0.735802E+09 | 0.275440E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1264588.11 | 0.00 | 0.00 | 6127977.30 | 0.00 | 0.16 |
Maximum of Months | 0.525613E+09 | 0.172240E+10 | 0.00 | 6248965.95 | 225181.67 | 0.256023E+09 | 0.482560E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203453E+10 | 2391165.67 | 0.00 | 117841.86 | 77870.21 | 4003886.44 | 80736022.49 | 0.00 | 0.18 |
February | 0.276957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 0.231993E+10 | 21074032.26 | 0.00 | 1156390.16 | 1537347.37 | 0.00 | 0.206136E+09 | 0.00 | 0.19 |
April | 0.353079E+09 | 0.655242E+09 | 0.00 | 9700387.39 | 112970.63 | 0.00 | 0.657270E+09 | 0.00 | 0.18 |
May | 0.209104E+09 | 0.125215E+10 | 0.00 | 7014889.83 | 0.00 | 0.00 | 0.528127E+09 | 0.00 | 0.20 |
June | 8714312.21 | 0.294323E+10 | 0.00 | 1020614.36 | 0.00 | 0.00 | 89680699.64 | 0.00 | 0.17 |
July | 1911080.44 | 0.351448E+10 | 0.00 | 382970.26 | 513415.13 | 0.00 | 36551601.98 | 0.00 | 0.15 |
August | 17419093.06 | 0.372307E+10 | 0.00 | 669286.02 | 0.00 | 0.00 | 0.179329E+09 | 0.00 | 0.18 |
September | 0.143805E+09 | 0.247949E+10 | 0.00 | 1794329.56 | 0.00 | 0.00 | 0.348132E+09 | 0.00 | 0.19 |
October | 0.997489E+09 | 0.634206E+09 | 0.00 | 4357177.87 | 0.00 | 0.00 | 0.830929E+09 | 0.00 | 0.20 |
November | 0.192174E+10 | 20483130.27 | 0.00 | 1386077.65 | 0.00 | 0.00 | 0.554046E+09 | 0.00 | 0.18 |
December | 0.243033E+10 | 0.00 | 0.00 | 0.00 | 10192282.38 | 5622760.57 | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.132076E+11 | 0.152458E+11 | 0.00 | 27599964.96 | 12433885.72 | 9626647.02 | 0.351094E+10 | 0.00 | 0.18 |
Minimum of Months | 1911080.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Maximum of Months | 0.276957E+10 | 0.372307E+10 | 0.00 | 9700387.39 | 10192282.38 | 5622760.57 | 0.830929E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |