Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2020-06-03 19:10:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1133.11 | 234.35 | 234.35 |
Net Site Energy | 1133.11 | 234.35 | 234.35 |
Total Source Energy | 3075.16 | 636.00 | 636.00 |
Net Source Energy | 3075.16 | 636.00 | 636.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 246.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.98 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 886.63 | 246.48 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 246.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 6.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.98 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 29.35 | 50.98 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 183.37 | 50.98 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 29.35 | 50.98 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 183.37 | 50.98 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 886.635 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 886.635 | 100.00 |
Total On-Site and Utility Electric Sources | 886.635 | 100.00 |
Total Electricity End Uses | 886.635 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 40.17 |
Time Setpoint Not Met During Occupied Cooling | 2.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1383.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 16-JAN-17:49 | - | - | - | 20-MAY-11:50 |
Heating | 0.00 | 182366.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19498.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7413.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1729.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74373.41 | 182366.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 182366.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19498.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5107.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1729.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 267.18 | 0.00 | 0.00 | 0.00 |
Cooling | 129.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 238.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2807.97 | 267.18 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.26 | 0.00 | 0.00 | 0.00 |
Cooling | 26.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 580.74 | 55.26 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.26 | 0.00 | 0.00 | 0.00 |
Cooling | 26.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 580.74 | 55.26 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.34 |
ZONE2 FINE STORAGE DIRECT AIR | 3.28 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.21 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.21 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 109726.01 |
PSZ-OFFICE HEATING COIL | 28130.96 |
PSZ-FINE STORAGE HEATING COIL | 89608.79 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 109726.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-FINE STORAGE | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 1.00 | 1.000000 | 3.28 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.34 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 3.28 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 22105.02 | 28130.96 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.28 | 3.28 | 3.28 | 3.28 | 63218.22 | 89608.79 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.34 | 0.667680 | 1.34 | 22104.95 | 22105.02 | 11052.51 | 22105.02 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 3.28 | 1.64 | 3.28 | 54806.55 | 63218.22 | 31609.11 | 63218.22 | 0.746359 | 0.746360 | 0.746360 | 0.746360 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.34 | 1522.46 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.28 | 3585.37 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.8442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.085 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.71045622E-12 | 0.18350169E-15 | 0.20920636E-14 | 0.12692337E-15 |
13 | 3 | -0.36041595E-03 | 0.57471575E-06 | -0.52051292E-04 | 0.13635641E-12 |
14 | 2 | 1.6814491 | 0.12908092E-01 | 1.0963028 | -0.69095641E-04 |
15 | 1 | -7.2068525 | 0.34008243 | -16.815156 | 0.32221486 |
16 | 0 | 6.0979960 | 0.21924101 | 16.291138 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20920636E-14 | 0.18350169E-15 | 0.71045622E-12 | 0.12692337E-15 |
85 | 3 | -0.52051292E-04 | 0.57471575E-06 | -0.36041595E-03 | 0.13635641E-12 |
86 | 2 | 1.0963028 | 0.12908092E-01 | 1.6814491 | -0.69095641E-04 |
87 | 1 | -16.815156 | 0.34008243 | -7.2068525 | 0.32221486 |
88 | 0 | 16.291138 | 0.21924101 | 6.0979960 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11125.87917 | 13351.05500 | 1.11280 | 1.33536 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10075.10545 | 12090.12654 | 0.34393 | 0.41271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 35015.16502 | 42018.19803 | 2.72982 | 3.27579 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 37543.03540 | 45051.64248 | 1.07921 | 1.29506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10000 | 5.65324E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 91438.33543 | 109726.00252 | 2.67649 | 3.21178 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16762.30 | 1.33536 | 1.33536 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10730.43 | 0.41271 | 0.41271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 51476.64 | 3.27579 | 3.27579 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 41420.66 | 1.29506 | 1.29506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33536 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.27579 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.21178 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.21178 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 109726.00980 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 109726.00252 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33536 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33536 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33536 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33536 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33536 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.33536 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.27579 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.27579 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.27579 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.27579 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.27579 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.27579 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.33536 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.27579 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33536 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33536 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33536 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33536 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33536 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33536 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66768 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33536 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22104.94951 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22105.02000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11052.51000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22105.02000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22105.02000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28130.95678 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33536 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1522.46216 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28130.95678 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.27579 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.27579 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.27579 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.27579 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.27579 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.27579 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.63790 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.27579 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 54806.55341 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 63218.22000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31609.11000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 63218.22000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74636 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74636 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74636 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74636 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63218.22000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89608.78841 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.27579 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3585.36625 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 89608.78841 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21068.8 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 60674.9 | 13.21 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 17 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1022509440 | 0.1126317419 | Pass | Pass | 0.3059408985 | 2.9930643391 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4333672824 | 0.5160971441 | Pass | Pass | 1.2426049745 | 6.1795969599 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.2649990705E-002 | 6.6343682418E-002 | Pass | Pass | 7.4320929528E-002 | 0.3754719615 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.749 | 0.844 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.826 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.092 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.71 | 83.71 | 123.46 | |
Exterior Lighting Total | 7857.24 | 123.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22105.02 | 17654.40 | 4450.62 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63218.22 | 47183.55 | 16034.67 | 0.75 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21068.8 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 60674.9 | 13.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 109726.01 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28130.96 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 89608.79 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.21 | 298.41 | 92.91 | 1.00 | 3.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.34 | 1522.46 | 1140.11 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.28 | 3585.37 | 1094.51 | 1.00 | 1.23 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11125.88 | 13351.06 | 56.36 | 1.113 | 1.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00803 | 33.21 | 0.00565 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 35015.17 | 42018.20 | 30.15 | 2.730 | 3.276 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00780 | 35.10 | 0.00565 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00460 | 35.10 | 0.00565 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10075.11 | 12090.13 | 51.04 | 0.344 | 0.413 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00764 | -7.90 | 0.00234 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 37543.04 | 45051.64 | 32.33 | 1.079 | 1.295 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00619 | -7.90 | 0.00234 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 91438.34 | 109726.00 | 34.24 | 2.676 | 3.212 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00930 | -7.90 | 0.00234 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.34 | 1.34 | 0.41 | 0.41 | 1.3354 | 1.3354 | 1.3354 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.28 | 3.28 | 1.30 | 1.30 | 3.2758 | 3.2758 | 3.2758 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 109726.010 | 109726.010 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 109726.01 | 109726.01 | 3.211783 | 4.55 | 4.55 | 0.00718358 | 43.33 | 24.55 | 0.01600000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 9.99 | 0.00929920 | 100.0000 | 109726.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22105.020 | 0.000 | 1.335360 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22105.02 | 22105.02 | 1.335360 | 24.61 | 14.04 | 0.00784926 | 12.00 | 9.53 | 0.00800000 | 33.21 | 0.00565324 | 15.09 | 7.6597 | 23.90 | 0.00803143 | 35.8005 | 11125.88 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28130.957 | 28130.957 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28130.96 | 28130.96 | 1.335364 | 13.88 | 8.63 | 0.00632845 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.6597 | 21.10 | 0.00764159 | 40.4089 | 10075.11 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63218.220 | 0.000 | 3.275790 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 63218.22 | 63218.22 | 3.275790 | 27.79 | 14.83 | 0.00752537 | 12.00 | 9.53 | 0.00800000 | 35.10 | 0.00565324 | 15.70 | 12.9652 | 26.70 | 0.00780425 | 29.4599 | 35015.17 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 89608.788 | 89608.788 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 89608.79 | 89608.79 | 3.275786 | 7.86 | 4.43 | 0.00492681 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 12.9652 | 15.55 | 0.00618758 | 46.4486 | 37543.04 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 109726.010 | 109726.010 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 0.9904 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.211783 | 3.18097848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 109726.01 | 109726.01 | 1.0000 | 3.18097848 | 3.211783 | 4.55 | 4.55 | 0.00718358 | 22598.7 | 43.33 | 24.55 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 109726.01 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 9.99 | 0.00929920 | 9.99 | 0.00929920 | 100.0000 | 109726.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22105.020 | 0.000 | 1.335360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4314 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22105.02 | 22105.02 | 1.0000 | 1.32255242 | 1.335360 | 24.61 | 14.04 | 0.00784926 | 44721.7 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22105.02 | 33.21 | 0.00565324 | 15.09 | 0.10228487 | 7.6597 | 23.90 | 0.00803143 | 23.90 | 0.00803143 | 35.8005 | 11125.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28130.957 | 28130.957 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.335364 | 1.32255678 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28130.96 | 28130.96 | 1.0000 | 1.32255678 | 1.335364 | 13.88 | 8.63 | 0.00632845 | 29932.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28130.96 | -7.90 | 0.00234317 | -7.90 | 0.10228487 | 7.6597 | 21.05 | 0.00764159 | 21.10 | 0.00764159 | 40.4089 | 10075.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63218.220 | 0.000 | 3.275790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8293 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 63218.22 | 63218.22 | 1.0000 | 3.24437155 | 3.275790 | 27.79 | 14.83 | 0.00752537 | 47133.5 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63218.22 | 35.10 | 0.00565324 | 15.70 | 0.42471267 | 12.9652 | 26.70 | 0.00780425 | 26.70 | 0.00780425 | 29.4599 | 35015.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89608.788 | 89608.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.275786 | 3.24436802 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 89608.79 | 89608.79 | 1.0000 | 3.24436802 | 3.275786 | 7.86 | 4.43 | 0.00492681 | 20294.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89608.79 | -7.90 | 0.00234317 | -7.90 | 0.42471267 | 12.9652 | 15.55 | 0.00618758 | 15.55 | 0.00618758 | 46.4486 | 37543.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.34 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 3.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2331.33 | 2337.33 | 1383.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2331.33 | 2337.33 | 1383.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 44.33 | 108.83 | 40.17 | 2.00 |
ZONE2 FINE STORAGE | 345.67 | 57.83 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 378.50 | 139.67 | 40.17 | 2.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.875 | 0.266 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 886.63 | 5475.32 | 01-JAN-09:20 | 74373.41 | 22-JUL-15:00 |
Electricity:Building | 627.87 | 4992.32 | 01-JAN-00:10 | 48037.94 | 19-MAY-13:00 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 428.27 | 2759.73 | 01-JAN-00:10 | 33963.13 | 19-MAY-12:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.98 | 483.00 | 06-FEB-06:30 | 2429.50 | 04-FEB-12:50 |
WaterSystems:Electricity | 25.98 | 483.00 | 06-FEB-06:30 | 2429.50 | 04-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 25.98 | 483.00 | 06-FEB-06:30 | 2429.50 | 04-FEB-12:50 |
Fans:Electricity | 75.21 | 0.00 | 01-JAN-09:20 | 7413.12 | 28-JUN-14:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
Ventilation (simple):Fans:Electricity | 6.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
ElectricityPurchased:Facility | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
ElectricityNet:Plant | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 886.63 | 5475.32 | 10-SEP-13:30 | 74373.41 | 22-JUL-15:00 |
Electricity:HVAC | 109.33 | 0.00 | 01-JAN-09:20 | 25884.83 | 22-JUL-15:10 |
General:Fans:Electricity | 68.58 | 0.00 | 01-JAN-09:20 | 5406.24 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40.75 | 0.00 | 01-JAN-00:10 | 20777.00 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 246.48 | 0.00 | 01-JAN-09:20 | 182366.42 | 16-JAN-17:50 |
Gas:HVAC | 246.48 | 0.00 | 01-JAN-09:20 | 182366.42 | 16-JAN-17:50 |
Heating:Gas | 246.48 | 0.00 | 01-JAN-09:20 | 182366.42 | 16-JAN-17:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 629.93 | 0.00 | 01-JAN-09:20 | 283279.20 | 16-JAN-17:50 |
EnergyTransfer:Building | 312.58 | 0.00 | 01-JAN-09:20 | 142409.13 | 16-JAN-17:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 58.13 | 0.00 | 01-JAN-00:10 | 17825.98 | 06-FEB-06:10 |
Heating:EnergyTransfer | 190.53 | 0.00 | 01-JAN-09:20 | 142409.13 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.80 | 0.00 | 01-JAN-00:10 | 17825.98 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 122.06 | 0.00 | 01-JAN-00:10 | 48608.16 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 42.33 | 0.00 | 01-JAN-00:10 | 12055.11 | 24-JUL-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 161.46 | 0.00 | 01-JAN-00:40 | 53243.95 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 81.73 | 0.00 | 01-JAN-00:40 | 53243.95 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 79.73 | 0.00 | 01-JAN-00:10 | 39276.43 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 92.99 | 0.00 | 01-JAN-08:40 | 93184.70 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 92.99 | 0.00 | 01-JAN-08:40 | 93184.70 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 317.35 | 0.00 | 01-JAN-09:20 | 140870.08 | 16-JAN-17:50 |
HeatingCoils:EnergyTransfer | 181.22 | 0.00 | 01-JAN-09:20 | 140870.08 | 16-JAN-17:50 |
CoolingCoils:EnergyTransfer | 136.12 | 0.00 | 01-JAN-00:10 | 59990.26 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 15.800 | -42.327 | 0.000 | 0.000 | 3.817 | 30.994 | 31.946 | 13.982 | 0.000 | 1.363 | 0.000 | 0.000 | -9.064 | 0.000 | -12.787 | -33.725 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 81.732 | -79.725 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 5.208 | 0.002 | 0.000 | 0.000 | 0.000 | -99.801 | -44.072 |
ZONE3 BULK STORAGE | 92.993 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 47.781 | 0.000 | 7.975 | 0.000 | 0.000 | -22.289 | 0.000 | -478.704 | -69.402 |
Total Facility | 92.993 | 0.000 | 97.532 | -122.052 | 0.000 | 0.000 | 3.817 | 481.960 | 139.282 | 61.764 | 0.000 | 14.546 | 0.002 | 0.000 | -31.353 | 0.000 | -591.291 | -147.198 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-JUN-00:01 | 0.00 | 0.00 | 0.00 | -25580.23 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 25097.64 | 0.00 | -434.06 | 0.00 | -116.06 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-10:31 | 0.00 | 0.00 | 0.00 | -61234.30 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 60782.46 | 0.00 | -0.00 | 0.00 | -748.04 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-19:01 | 0.00 | 0.00 | 0.00 | -76614.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 0.00 | 0.00 | 60.57 | 81789.26 | 0.00 | -875.74 | 0.00 | -11402.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-06:51 | 0.00 | 0.00 | 30538.98 | 0.00 | 0.00 | 0.00 | 55.06 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -848.20 | 0.00 | -1770.58 | -29135.46 |
ZONE2 FINE STORAGE | 04-FEB-23:22 | 0.00 | 0.00 | 92715.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16210.58 | -77704.36 |
ZONE3 BULK STORAGE | 14-DEC-04:00 | 93193.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1585.63 | 0.00 | -84196.00 | -12221.44 |
Total Facility | 06-FEB-06:01 | 72172.82 | 0.00 | 118997.67 | 0.00 | 0.00 | 0.00 | 58.01 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2712.21 | 0.00 | -57439.66 | -138246.46 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3354 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3354 | 0.0766 | 1.0000 | 0.1023 | 0.0766 | ||
PSZ-FINE STORAGE | 3.2758 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.2758 | 0.1297 | 1.0000 | 0.4247 | 0.1297 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3354 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3354 | 1.0000 | 1.0000 | 0.1023 | 0.0766 | ||
PSZ-FINE STORAGE | 3.2758 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.2758 | 1.0000 | 1.0000 | 0.4247 | 0.1297 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3354 | 1.3354 | 1.3354 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2758 | 3.2758 | 3.2758 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3354 | 1.3354 | 1.3354 | 1.3354 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2758 | 3.2758 | 3.2758 | 3.2758 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3354 | 1.3354 | 1.3354 | 0.1023 | 0.2478 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2758 | 3.2758 | 3.2758 | 0.4247 | 0.3279 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3354 | 1.3354 | 1.3354 | 1.3354 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2758 | 3.2758 | 3.2758 | 3.2758 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 40.17 |
Number of hours cooling loads not met | 2.00 |
Number of hours not met | 42.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 246.48 | 182366.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 40.75 | 20777.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.46 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 6.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 68.58 | 5406.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.98 | 2429.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 886.63 |
Natural Gas | 0.00 | 246.48 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1133.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 8.43 |
Fans (All) | 15.55 |
Service Water Heating | 5.37 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 183.37 |
Subtotal | 183.37 |
Natural Gas [MJ/m2] | |
Space Heating | 50.98 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 50.98 |
Subtotal | 50.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 42.53 |
Space Heating | 21.75 |
Space Cooling | 3.60 |
Fans (All) | 6.64 |
Service Water Heating | 2.29 |
Receptacle Equipment | 12.29 |
Miscellaneous | 10.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.829603E+11 |
February | 0.000 | 0.551982E+11 |
March | 0.000 | 0.137494E+11 |
April | 0.000 | 0.915701E+09 |
May | 0.000 | 0.590228E+08 |
June | 0.000 | 1343163.900 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.101404E+10 |
November | 0.000 | 0.140856E+11 |
December | 0.000 | 0.784955E+11 |
Annual Sum or Average | 0.246479E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.829603E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 | -1.0 | 0.199462E+09 | 291.15 | 05-JAN-16:10 | 15.63 | 6.61 |
February | 18106357.92 | 1313.85 | 15-FEB-16:30 | 16.95 | 6.15 | 0.186394E+09 | 301.59 | 13-FEB-15:50 | 21.60 | 7.23 |
March | 46333529.20 | 1587.90 | 08-MAR-16:40 | 22.40 | 8.49 | 0.230371E+09 | 301.59 | 17-MAR-14:09 | 16.10 | 5.44 |
April | 0.138945E+10 | 20613.59 | 22-APR-18:01 | 21.42 | 7.14 | 0.236606E+09 | 301.59 | 17-APR-13:50 | 24.13 | 9.50 |
May | 0.370880E+10 | 25241.59 | 15-MAY-00:03 | 15.68 | 5.16 | 0.255964E+09 | 301.64 | 23-MAY-14:39 | 16.83 | 13.83 |
June | 0.782029E+10 | 25580.04 | 12-JUN-00:01 | 17.38 | 9.60 | 0.258721E+09 | 301.61 | 29-JUN-08:09 | 29.50 | 17.96 |
July | 0.979350E+10 | 23063.45 | 24-JUL-00:01 | 22.80 | 14.35 | 0.248846E+09 | 301.61 | 29-JUL-13:30 | 31.95 | 18.95 |
August | 0.981410E+10 | 22409.34 | 07-AUG-00:01 | 23.03 | 14.79 | 0.268806E+09 | 301.65 | 28-AUG-14:09 | 23.40 | 17.49 |
September | 0.683840E+10 | 23411.02 | 11-SEP-00:01 | 18.03 | 11.68 | 0.248922E+09 | 301.61 | 22-SEP-10:50 | 24.13 | 14.41 |
October | 0.283665E+10 | 23836.70 | 02-OCT-00:01 | 18.48 | 12.10 | 0.239220E+09 | 301.61 | 07-OCT-14:09 | 23.98 | 14.16 |
November | 60770441.70 | 2282.72 | 02-NOV-15:50 | 16.78 | 9.69 | 0.206189E+09 | 301.59 | 08-NOV-16:10 | 16.02 | 6.97 |
December | 2053948.34 | 131.65 | 05-DEC-14:50 | 6.02 | 0.18 | 0.197959E+09 | 293.63 | 02-DEC-15:00 | 11.10 | 3.04 |
Annual Sum or Average | 0.423285E+11 | 0.277746E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 2.30 | -1.0 | 0.186394E+09 | 291.15 | 11.10 | 3.04 | ||
Maximum of Months | 0.981410E+10 | 25580.04 | 23.03 | 14.79 | 0.268806E+09 | 301.65 | 31.95 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399001E+09 | 3238.49 | 20-JAN-13:00 | -0.6 | -0.8 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.457327E+09 | 2927.28 | 06-FEB-11:10 | 0.97 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.207830E+09 | 2461.07 | 10-MAR-09:15 | 5.17 | 0.19 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.589019E+09 | 7358.11 | 28-APR-14:10 | 24.50 | 10.28 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.395658E+10 | 59310.66 | 21-MAY-11:11 | 24.97 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.161313E+11 | 60716.27 | 18-JUN-08:11 | 23.73 | 11.66 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.236054E+11 | 57017.92 | 05-JUL-22:11 | 25.40 | 14.40 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.205026E+11 | 59593.78 | 16-AUG-21:21 | 24.75 | 13.35 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.989739E+10 | 58454.92 | 15-SEP-17:11 | 24.83 | 14.00 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.257850E+10 | 61235.36 | 01-OCT-10:31 | 22.97 | 13.27 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.549052E+09 | 5991.09 | 08-NOV-07:10 | 10.50 | 4.85 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.855376E+09 | 3668.09 | 06-DEC-10:00 | 0.00 | -2.8 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.797293E+11 | 0.00 | ||||||||
Minimum of Months | 0.207830E+09 | 2461.07 | -0.6 | -3.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.236054E+11 | 61235.36 | 25.40 | 14.40 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.2 | -5.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 | 16.85 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 17.33 | 10.87 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 | 1.83 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.85 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399687E+10 | 30538.88 | 17-JAN-06:51 | -3.9 |
February | 0.321505E+10 | 28751.93 | 07-FEB-06:12 | -3.9 |
March | 0.218305E+10 | 28631.96 | 04-MAR-06:12 | -1.7 |
April | 0.547731E+09 | 28483.69 | 07-APR-05:01 | 4.22 |
May | 0.151905E+09 | 28010.85 | 06-MAY-05:01 | 6.02 |
June | 22661966.67 | 3744.79 | 23-JUN-06:05 | 18.95 |
July | 1776697.39 | 2568.77 | 06-JUL-06:05 | 21.97 |
August | 2567102.66 | 1746.49 | 29-AUG-06:04 | 15.60 |
September | 19625407.22 | 1847.13 | 29-SEP-06:03 | 14.37 |
October | 0.418106E+09 | 28498.28 | 26-OCT-05:01 | -2.5 |
November | 0.160519E+10 | 28937.23 | 25-NOV-06:42 | 1.10 |
December | 0.363546E+10 | 28786.80 | 14-DEC-06:12 | -3.5 |
Annual Sum or Average | 0.158000E+11 | |||
Minimum of Months | 1776697.39 | 1746.49 | -3.9 | |
Maximum of Months | 0.399687E+10 | 30538.88 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235087E+11 | 92577.61 | 17-JAN-22:02 | -1.6 |
February | 0.172503E+11 | 92717.05 | 04-FEB-23:22 | -0.6 |
March | 0.755001E+10 | 91244.04 | 05-MAR-04:52 | -1.7 |
April | 0.123892E+10 | 46061.83 | 07-APR-23:53 | 3.90 |
May | 0.496199E+09 | 3725.61 | 04-MAY-06:50 | 6.52 |
June | 0.226885E+09 | 3383.85 | 13-JUN-06:25 | 20.55 |
July | 91243698.15 | 3390.08 | 17-JUL-07:00 | 19.40 |
August | 0.192994E+09 | 3330.06 | 23-AUG-06:50 | 18.80 |
September | 0.317314E+09 | 3904.03 | 01-SEP-07:00 | 18.90 |
October | 0.967715E+09 | 51280.97 | 26-OCT-04:13 | -2.8 |
November | 0.776878E+10 | 92574.02 | 26-NOV-07:32 | 0.73 |
December | 0.221236E+11 | 92644.74 | 24-DEC-06:02 | -3.2 |
Annual Sum or Average | 0.817325E+11 | |||
Minimum of Months | 91243698.15 | 3330.06 | -3.2 | |
Maximum of Months | 0.235087E+11 | 92717.05 | 20.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351940E+11 | 91328.01 | 16-JAN-18:00 | -1.7 |
February | 0.214412E+11 | 83224.00 | 06-FEB-05:00 | -4.4 |
March | 0.170806E+10 | 37116.56 | 04-MAR-06:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 17.33 |
November | 0.151768E+10 | 33712.99 | 26-NOV-06:43 | 0.10 |
December | 0.331321E+11 | 93199.86 | 14-DEC-04:00 | -1.1 |
Annual Sum or Average | 0.929930E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.351940E+11 | 93199.86 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196658E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172192E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158537E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12034299.45 | 0.102116E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69711485.92 | 0.822751E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385435E+09 | 0.363157E+09 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437226E+09 | 0.141048E+09 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314807E+09 | 0.247315E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119932E+09 | 0.442792E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23720123.45 | 0.103330E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152770E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191345E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.136287E+10 | 0.127866E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141048E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437226E+09 | 0.196658E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137293E+11 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127577E+11 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53846.02 | 0.111968E+11 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14817059.68 | 0.816888E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166027E+09 | 0.760465E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161963E+10 | 0.451261E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209346E+10 | 0.278624E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107631E+10 | 0.391619E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226076E+09 | 0.507840E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11764932.21 | 0.781327E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994908E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122877E+11 |
Annual Sum or Average | 0.136656E+12 | 0.520814E+10 | 0.998007E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278624E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209346E+10 | 0.137293E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78737390.92 | 0.277796E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244039E+09 | 0.264209E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487714E+09 | 0.243754E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504695E+09 | 0.229000E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236175E+09 | 0.278309E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126519E+09 | 0.199147E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112997E+09 | 0.154489E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11523192.35 | 0.197900E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186918.73 | 0.216457E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90516832.75 | 0.269143E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16230933.56 | 0.230199E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3326548.94 | 0.257147E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.191466E+10 | 0.281755E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186918.73 | 0.154489E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504695E+09 | 0.278309E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6971.01 | 17-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 6403.00 | 06-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5295.36 | 10-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.95 | 13-APR-17:00 | 4076.00 | 06-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1481.42 | 19-MAY-17:00 | 3925.85 | 05-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2843.56 | 28-JUN-16:10 | 3095.46 | 09-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.92 | 21-JUL-17:00 | 1188.47 | 28-JUL-06:05 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2230.87 | 01-AUG-16:10 | 2130.11 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1433.42 | 20-SEP-17:00 | 2662.09 | 27-SEP-06:01 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 793.32 | 06-OCT-16:05 | 5287.22 | 24-OCT-17:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5378.64 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6468.59 | 22-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.47 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2843.56 | 6971.01 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 30193.08 | 16-JAN-18:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23777.12 | 05-FEB-01:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 12-MAR-17:00 | 24261.37 | 14-MAR-07:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.59 | 01-APR-17:30 | 25830.98 | 15-APR-15:03 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.48 | 19-MAY-15:10 | 16809.26 | 04-MAY-07:00 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.51 | 17-JUN-16:00 | 11272.17 | 01-JUN-17:00 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9405.42 | 04-JUL-15:10 | 7610.68 | 15-JUL-18:55 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6348.74 | 02-AUG-17:00 | 8520.92 | 25-AUG-19:55 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3077.38 | 03-SEP-14:35 | 10524.07 | 07-SEP-15:10 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.47 | 01-OCT-15:57 | 25722.63 | 24-OCT-15:02 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21806.29 | 26-NOV-06:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 31862.32 | 14-DEC-03:55 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7610.68 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.51 | 31862.32 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5230.36 | 24-JAN-15:00 | 60121.83 | 17-JAN-08:70 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10393.23 | 14-FEB-17:00 | 47681.30 | 05-FEB-01:40 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12426.38 | 08-MAR-17:00 | 48891.24 | 21-MAR-10:55 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10941.69 | 01-APR-17:00 | 75828.54 | 15-APR-12:05 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5459.99 | 07-MAY-18:00 | 54752.63 | 05-MAY-08:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.73 | 12-JUN-16:00 | 36996.95 | 08-JUN-12:10 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2968.05 | 04-JUL-16:51 | 30789.53 | 15-JUL-18:55 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.21 | 20-AUG-17:20 | 33950.86 | 22-AUG-20:53 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.64 | 03-SEP-13:53 | 36955.57 | 07-SEP-15:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9235.38 | 31-OCT-15:00 | 73851.46 | 24-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4153.07 | 09-NOV-14:00 | 41172.25 | 03-NOV-21:15 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.27 | 24-DEC-15:00 | 61927.70 | 14-DEC-03:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 638.21 | 30789.53 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 12426.38 | 75828.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.78 |
February | 1313.85 | 15-FEB-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.00 |
March | 1587.90 | 08-MAR-16:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 |
April | 20613.59 | 22-APR-18:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.26 |
May | 25241.59 | 15-MAY-00:03 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.56 |
June | 25580.04 | 12-JUN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.06 |
July | 23063.45 | 24-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.19 |
August | 22409.34 | 07-AUG-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.18 |
September | 23411.02 | 11-SEP-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 |
October | 23836.70 | 02-OCT-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.61 |
November | 2282.72 | 02-NOV-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.66 |
December | 131.65 | 05-DEC-14:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1835.82 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.19 | |
Maximum of Months | 25580.04 | 659.25 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3238.49 | 20-JAN-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2713.07 |
February | 2927.28 | 06-FEB-11:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2062.16 |
March | 2461.07 | 10-MAR-09:15 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3485.47 |
April | 7358.11 | 28-APR-14:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.72 |
May | 59310.66 | 21-MAY-11:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.24 |
June | 60716.27 | 18-JUN-08:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 949.32 |
July | 57017.92 | 05-JUL-22:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.74 |
August | 59593.78 | 16-AUG-21:21 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.19 |
September | 58454.92 | 15-SEP-17:11 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.29 |
October | 61235.36 | 01-OCT-10:31 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.04 |
November | 5991.09 | 08-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2372.31 |
December | 3668.09 | 06-DEC-10:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2461.07 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61235.36 | 0.00 | 20398.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3485.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11650.29 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13798.65 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3607.05 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5453.26 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12205.99 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12759.09 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10505.68 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8541.95 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9693.11 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8875.67 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3000.12 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3000.12 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.726385E+11 | 52906.98 | 17-JAN-11:09 | 0.829603E+11 | 182366.42 | 16-JAN-17:49 |
February | 0.654418E+11 | 52942.61 | 14-FEB-15:00 | 0.551982E+11 | 167411.90 | 05-FEB-01:30 |
March | 0.735196E+11 | 53156.87 | 08-MAR-15:00 | 0.137494E+11 | 101345.80 | 04-MAR-06:19 |
April | 0.682482E+11 | 56232.25 | 28-APR-14:50 | 0.915701E+09 | 25977.45 | 08-APR-05:19 |
May | 0.717233E+11 | 64329.29 | 19-MAY-14:00 | 59022798.51 | 7484.06 | 06-MAY-05:10 |
June | 0.793001E+11 | 73948.37 | 28-JUN-14:00 | 1343163.90 | 2238.61 | 15-JUN-05:40 |
July | 0.836091E+11 | 74373.41 | 22-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.850388E+11 | 70163.28 | 01-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.742022E+11 | 67008.68 | 02-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.714158E+11 | 63412.77 | 06-OCT-14:00 | 0.101404E+10 | 32054.40 | 26-OCT-05:10 |
November | 0.687077E+11 | 56351.40 | 30-NOV-16:00 | 0.140856E+11 | 93136.67 | 26-NOV-06:00 |
December | 0.727897E+11 | 56356.83 | 28-DEC-16:00 | 0.784955E+11 | 179694.88 | 14-DEC-04:19 |
Annual Sum or Average | 0.886635E+12 | 0.246479E+12 | ||||
Minimum of Months | 0.654418E+11 | 52906.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.850388E+11 | 74373.41 | 0.829603E+11 | 182366.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.123044E+11 | 0.115358E+11 | 0.00 | 0.639377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230115E+10 | 0.00 |
February | 0.366966E+11 | 0.104800E+11 | 0.105871E+11 | 0.00 | 0.558074E+10 | 0.00 | 0.00 | 1036241.72 | 0.00 | 0.00 | 0.00 | 0.209633E+10 | 0.00 |
March | 0.423649E+11 | 0.106874E+11 | 0.123357E+11 | 0.00 | 0.578530E+10 | 0.00 | 0.00 | 4065810.61 | 0.00 | 0.00 | 0.00 | 0.234228E+10 | 0.00 |
April | 0.397216E+11 | 0.940512E+10 | 0.114862E+11 | 0.00 | 0.509492E+10 | 0.00 | 0.00 | 0.360623E+09 | 0.00 | 0.00 | 0.00 | 0.217971E+10 | 0.00 |
May | 0.412341E+11 | 0.891954E+10 | 0.119357E+11 | 0.00 | 0.542558E+10 | 0.00 | 0.00 | 0.201382E+10 | 0.00 | 0.00 | 0.00 | 0.219447E+10 | 0.00 |
June | 0.408524E+11 | 0.820767E+10 | 0.118862E+11 | 0.00 | 0.753889E+10 | 0.00 | 0.00 | 0.872675E+10 | 0.00 | 0.00 | 0.00 | 0.208830E+10 | 0.00 |
July | 0.401034E+11 | 0.870268E+10 | 0.115358E+11 | 0.00 | 0.847691E+10 | 0.00 | 0.00 | 0.127156E+11 | 0.00 | 0.00 | 0.00 | 0.207475E+10 | 0.00 |
August | 0.423649E+11 | 0.935797E+10 | 0.123357E+11 | 0.00 | 0.811302E+10 | 0.00 | 0.00 | 0.107509E+11 | 0.00 | 0.00 | 0.00 | 0.211634E+10 | 0.00 |
September | 0.397216E+11 | 0.994727E+10 | 0.114862E+11 | 0.00 | 0.599978E+10 | 0.00 | 0.00 | 0.500370E+10 | 0.00 | 0.00 | 0.00 | 0.204364E+10 | 0.00 |
October | 0.401034E+11 | 0.112296E+11 | 0.115358E+11 | 0.00 | 0.523261E+10 | 0.00 | 0.00 | 0.117202E+10 | 0.00 | 0.00 | 0.00 | 0.214247E+10 | 0.00 |
November | 0.385909E+11 | 0.116869E+11 | 0.110862E+11 | 0.00 | 0.521170E+10 | 0.00 | 0.00 | 1414.57 | 0.00 | 0.00 | 0.00 | 0.213205E+10 | 0.00 |
December | 0.401034E+11 | 0.125307E+11 | 0.115358E+11 | 0.00 | 0.635336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226652E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123459E+12 | 0.139282E+12 | 0.752066E+11 | 0.00 | 0.407486E+11 | 0.259780E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.820767E+10 | 0.105871E+11 | 0.00 | 0.509492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204364E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.125307E+11 | 0.123357E+11 | 0.00 | 0.847691E+10 | 0.00 | 0.00 | 0.127156E+11 | 0.00 | 0.00 | 0.00 | 0.234228E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.829603E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.551982E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.137494E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.915701E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 59022798.51 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1343163.90 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101404E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.140856E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.784955E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246479E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.829603E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5406.24 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5406.24 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5406.24 | 04-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5107.83 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7413.12 | 19-MAY-13:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7413.12 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7413.12 | 11-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7413.12 | 07-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7413.12 | 02-SEP-14:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7413.12 | 06-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5406.24 | 27-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5406.24 | 04-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 5107.83 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 7413.12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2422.88 | 28-JAN-12:20 | 0.00 |
February | 288.81 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2429.50 | 04-FEB-12:50 | 0.00 |
March | 508.83 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2389.96 | 01-MAR-12:09 | 0.00 |
April | 3614.86 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 2190.42 | 03-APR-11:00 | 0.00 |
May | 10262.10 | 19-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1815.01 | 01-MAY-11:00 | 0.00 |
June | 20204.74 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1787.82 | 01-JUN-11:09 | 0.00 |
July | 20777.00 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1768.49 | 01-JUL-11:30 | 0.00 |
August | 16306.69 | 01-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1762.23 | 31-AUG-11:09 | 0.00 |
September | 12322.00 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1776.66 | 29-SEP-11:20 | 0.00 |
October | 8594.40 | 02-OCT-14:39 | 0.00 | 0.00 | 0.00 | 1801.05 | 31-OCT-11:39 | 0.00 |
November | 0.18 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2072.70 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2310.71 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1762.23 | 0.00 | ||
Maximum of Months | 20777.00 | 0.00 | 0.00 | 0.00 | 2429.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52906.98 | 17-JAN-11:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5406.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52942.61 | 14-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5107.83 | 0.00 | 0.00 | 288.81 | 0.00 |
March | 53156.87 | 08-MAR-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5107.83 | 0.00 | 0.00 | 508.83 | 0.00 |
April | 56232.25 | 28-APR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5107.83 | 0.00 | 0.00 | 3614.86 | 0.00 |
May | 64329.29 | 19-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 9576.55 | 0.00 |
June | 73948.37 | 28-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 19065.27 | 0.00 |
July | 74373.41 | 22-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 19498.21 | 0.00 |
August | 70163.28 | 01-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 15289.91 | 0.00 |
September | 67008.68 | 02-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 12131.67 | 0.00 |
October | 63412.77 | 06-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 7413.12 | 0.00 | 0.00 | 8520.48 | 0.00 |
November | 56351.40 | 30-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5107.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56356.83 | 28-DEC-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 5107.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52906.98 | 31660.41 | 10112.62 | 0.00 | 0.00 | 5107.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74373.41 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 7413.12 | 0.00 | 0.00 | 19498.21 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 182366.42 | 16-JAN-17:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 167411.90 | 05-FEB-01:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 101345.80 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 25977.45 | 08-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 7484.06 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2238.61 | 15-JUN-05:40 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 32054.40 | 26-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 93136.67 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 179694.88 | 14-DEC-04:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 182366.42 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.86 | 9.00 | 19.50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.33 | 18.67 | 7.33 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.17 | 19.93 | 7.17 | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.50 | 20.18 | 1.50 | 20.18 | 0.67 | 24.50 | 0.00 | 0.00 |
May | 0.50 | 20.47 | 0.50 | 20.47 | 9.00 | 24.61 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 24.81 | 0.83 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.84 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 24.82 | 0.33 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.66 | 0.67 | 24.53 |
October | 1.00 | 20.16 | 1.00 | 20.16 | 2.83 | 24.55 | 0.17 | 24.47 |
November | 5.00 | 19.83 | 5.00 | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.33 | 19.15 | 8.67 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.33 | 19.26 | 40.17 | 19.70 | 108.83 | 24.78 | 2.00 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 20.47 | 9.00 | 20.47 | 31.00 | 24.84 | 0.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.67 | 14.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74.00 | 14.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33.83 | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.17 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.69 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.83 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.70 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 0.00 | 0.00 |
October | 1.50 | 14.85 | 0.00 | 0.00 | 1.00 | 27.47 | 0.00 | 0.00 |
November | 35.50 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 100.00 | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.67 | 14.44 | 0.00 | 57.83 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.00 | 14.85 | 0.00 | 0.00 | 22.50 | 27.83 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.25 | 285.67 | 21.17 | 285.67 | 21.17 |
February | 276.00 | 21.42 | 237.83 | 21.14 | 237.83 | 21.14 |
March | 324.00 | 21.94 | 217.67 | 21.25 | 217.67 | 21.25 |
April | 297.33 | 23.06 | 76.67 | 21.32 | 76.67 | 21.32 |
May | 210.17 | 23.53 | 19.83 | 22.21 | 12.83 | 21.29 |
June | 49.33 | 23.75 | 153.00 | 23.90 | 0.00 | 0.00 |
July | 18.50 | 23.81 | 283.83 | 23.90 | 16.83 | 23.86 |
August | 19.00 | 23.84 | 301.50 | 23.90 | 17.00 | 23.91 |
September | 41.50 | 23.94 | 190.00 | 23.90 | 5.00 | 23.90 |
October | 213.50 | 23.01 | 97.83 | 22.63 | 46.50 | 21.24 |
November | 288.00 | 21.97 | 178.83 | 21.23 | 178.83 | 21.23 |
December | 300.00 | 21.18 | 288.67 | 21.12 | 288.67 | 21.12 |
Annual Sum or Average | 2337.33 | 22.18 | 2331.33 | 22.34 | 1383.50 | 21.26 |
Minimum of Months | 18.50 | 21.18 | 19.83 | 21.12 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.94 | 301.50 | 23.90 | 288.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 3743485.36 | 1036241.72 | 6.33 | 3743485.36 | 0.00 | 0.00 | 0.06 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 | 1046.22 | 14-FEB-16:00 | 1046.22 | 14-FEB-16:00 | 0.00 | 14-FEB-16:00 | 288.81 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 |
March | 14774441.53 | 4065810.61 | 20.00 | 14774441.53 | 0.00 | 0.00 | 0.11 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 1856.06 | 08-MAR-16:00 | 1856.06 | 08-MAR-16:00 | 0.00 | 11-MAR-14:50 | 508.83 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.116748E+10 | 0.312243E+09 | 133.50 | 0.116748E+10 | 9.65 | 0.00 | 1.00 | 11-APR-17:11 | 0.00 | 01-APR-00:10 | 20334.96 | 11-APR-18:01 | 20334.96 | 11-APR-18:01 | 0.01 | 15-APR-08:30 | 4829.53 | 28-APR-18:40 | 0.00 | 01-APR-00:10 |
May | 0.338278E+10 | 0.918851E+09 | 225.54 | 0.336615E+10 | 16633839.14 | 0.00 | 1.00 | 02-MAY-17:11 | 0.00 | 01-MAY-00:10 | 21449.75 | 23-MAY-18:33 | 20792.81 | 27-MAY-19:11 | 6305.59 | 23-MAY-18:33 | 5168.16 | 19-MAY-17:08 | 0.00 | 01-MAY-00:10 |
June | 0.887940E+10 | 0.258218E+10 | 344.06 | 0.873328E+10 | 0.146128E+09 | 0.00 | 1.00 | 02-JUN-17:11 | 0.00 | 01-JUN-00:10 | 22207.37 | 24-JUN-00:21 | 21062.26 | 30-JUN-21:01 | 7959.98 | 05-JUN-00:03 | 5704.05 | 27-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.128084E+11 | 0.360984E+10 | 387.62 | 0.114190E+11 | 0.138937E+10 | 0.00 | 1.00 | 01-JUL-00:13 | 0.00 | 01-JUL-00:10 | 24371.57 | 01-JUL-17:08 | 21085.54 | 18-JUL-23:01 | 11434.13 | 01-JUL-05:35 | 5752.92 | 21-JUL-17:05 | 0.00 | 01-JUL-00:10 |
August | 0.121870E+11 | 0.335067E+10 | 384.80 | 0.108416E+11 | 0.134545E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:05 | 23407.08 | 14-AUG-01:09 | 22378.14 | 13-AUG-17:51 | 11448.32 | 30-AUG-00:50 | 5740.30 | 13-AUG-17:51 | 0.00 | 01-AUG-00:05 |
September | 0.690921E+10 | 0.186078E+10 | 267.18 | 0.644630E+10 | 0.462907E+09 | 0.00 | 1.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:02 | 22467.38 | 23-SEP-17:11 | 21242.64 | 18-SEP-17:08 | 10058.72 | 05-SEP-05:25 | 5458.73 | 02-SEP-17:06 | 0.00 | 01-SEP-00:01 |
October | 0.219574E+10 | 0.582081E+09 | 158.00 | 0.208382E+10 | 0.111917E+09 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:05 | 22742.51 | 02-OCT-17:10 | 20964.11 | 03-OCT-17:08 | 7207.17 | 02-OCT-17:16 | 5367.14 | 02-OCT-17:10 | 0.00 | 01-OCT-00:05 |
November | 5078.17 | 1414.57 | 11.36 | 5078.17 | 0.00 | 0.00 | 0.00 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 0.65 | 02-NOV-15:00 | 0.65 | 02-NOV-15:00 | 0.00 | 06-NOV-15:40 | 0.18 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.475486E+11 | 0.132217E+11 | 1938.40 | 0.440762E+11 | 0.347240E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.128084E+11 | 0.360984E+10 | 387.62 | 0.114190E+11 | 0.138937E+10 | 0.00 | 1.00 | 0.00 | 24371.57 | 22378.14 | 11448.32 | 5752.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.161984E+09 | 48380104.78 | 21.83 | 0.161984E+09 | 0.00 | 0.00 | 0.13 | 28-APR-14:40 | 0.00 | 01-APR-00:10 | 6328.27 | 28-APR-14:40 | 6328.27 | 28-APR-14:40 | 0.00 | 13-APR-17:00 | 1868.04 | 28-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.364769E+10 | 0.109497E+10 | 123.57 | 0.364289E+10 | 4799194.59 | 0.00 | 1.00 | 14-MAY-12:11 | 0.00 | 01-MAY-00:10 | 61753.23 | 28-MAY-12:21 | 59704.31 | 21-MAY-11:11 | 5835.86 | 28-MAY-12:29 | 15916.77 | 29-MAY-14:51 | 0.00 | 01-MAY-00:10 |
June | 0.190039E+11 | 0.614457E+10 | 267.35 | 0.188393E+11 | 0.164664E+09 | 0.00 | 1.00 | 03-JUN-17:21 | 0.00 | 01-JUN-00:10 | 63465.04 | 25-JUN-08:11 | 60450.00 | 28-JUN-23:07 | 9207.50 | 25-JUN-08:17 | 17927.13 | 25-JUN-15:32 | 0.00 | 01-JUN-00:10 |
July | 0.289825E+11 | 0.910578E+10 | 330.83 | 0.271155E+11 | 0.186696E+10 | 0.00 | 1.00 | 02-JUL-09:00 | 0.00 | 01-JUL-00:10 | 69603.22 | 16-JUL-08:31 | 60356.60 | 23-JUL-18:41 | 26430.04 | 16-JUL-08:31 | 18377.75 | 23-JUL-14:02 | 0.00 | 01-JUL-00:10 |
August | 0.242161E+11 | 0.740026E+10 | 306.84 | 0.225378E+11 | 0.167826E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:05 | 68902.55 | 13-AUG-08:25 | 60525.53 | 06-AUG-11:11 | 29282.14 | 13-AUG-08:25 | 17920.54 | 20-AUG-15:22 | 0.00 | 01-AUG-00:05 |
September | 0.105571E+11 | 0.314292E+10 | 191.89 | 0.100619E+11 | 0.495186E+09 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:01 | 65633.38 | 04-SEP-10:41 | 60262.86 | 10-SEP-16:20 | 16392.62 | 10-SEP-11:28 | 17434.77 | 03-SEP-13:53 | 0.00 | 01-SEP-00:01 |
October | 0.200332E+10 | 0.589942E+09 | 59.71 | 0.195413E+10 | 49194614.17 | 0.00 | 1.00 | 01-OCT-10:31 | 0.00 | 01-OCT-00:05 | 60807.33 | 01-OCT-11:20 | 60024.00 | 01-OCT-13:11 | 3395.96 | 01-OCT-10:31 | 16183.71 | 01-OCT-13:11 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.885726E+11 | 0.275268E+11 | 1302.03 | 0.843135E+11 | 0.425907E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.289825E+11 | 0.910578E+10 | 330.83 | 0.271155E+11 | 0.186696E+10 | 0.00 | 1.00 | 0.00 | 69603.22 | 60525.53 | 29282.14 | 18377.75 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.88 | 71.74 | 54.15 | 98.88 | 153.58 | 0.00 | 0.00 | 744.00 |
February | 161.61 | 93.17 | 68.44 | 142.64 | 136.32 | 0.00 | 0.00 | 672.00 |
March | 181.25 | 96.51 | 84.74 | 175.44 | 103.78 | 0.00 | 0.00 | 744.00 |
April | 230.92 | 122.73 | 108.18 | 237.32 | 76.51 | 0.00 | 0.00 | 720.00 |
May | 220.04 | 113.67 | 106.36 | 234.43 | 64.31 | 0.00 | 0.00 | 744.00 |
June | 234.54 | 130.68 | 103.86 | 286.84 | 47.08 | 0.00 | 0.00 | 720.00 |
July | 211.95 | 103.72 | 108.23 | 267.13 | 31.77 | 0.00 | 0.00 | 744.00 |
August | 216.35 | 99.89 | 116.46 | 261.88 | 36.51 | 0.00 | 0.00 | 744.00 |
September | 196.32 | 103.64 | 92.68 | 221.06 | 62.57 | 0.00 | 0.00 | 720.00 |
October | 178.83 | 111.08 | 67.74 | 180.41 | 101.23 | 0.00 | 0.00 | 744.00 |
November | 140.28 | 82.43 | 57.85 | 118.28 | 121.82 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 76.05 | 45.32 | 91.36 | 160.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.97 | 100.40 | 84.57 | 193.13 | 91.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.36 | 71.74 | 45.32 | 91.36 | 31.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.54 | 130.68 | 116.46 | 286.84 | 160.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.88 | 71.74 | 54.15 | 98.88 | 153.58 | 0.00 | 0.00 | 744.00 |
February | 161.61 | 93.17 | 68.44 | 142.64 | 136.32 | 0.00 | 0.00 | 672.00 |
March | 181.25 | 96.51 | 84.74 | 175.44 | 103.78 | 0.00 | 0.00 | 744.00 |
April | 230.92 | 122.73 | 108.18 | 237.32 | 76.51 | 0.00 | 0.00 | 720.00 |
May | 220.04 | 113.67 | 106.36 | 234.43 | 64.31 | 0.00 | 0.00 | 744.00 |
June | 234.54 | 130.68 | 103.86 | 286.84 | 47.08 | 0.00 | 0.00 | 720.00 |
July | 211.95 | 103.72 | 108.23 | 267.13 | 31.77 | 0.00 | 0.00 | 744.00 |
August | 216.35 | 99.89 | 116.46 | 261.88 | 36.51 | 0.00 | 0.00 | 744.00 |
September | 196.32 | 103.64 | 92.68 | 221.06 | 62.57 | 0.00 | 0.00 | 720.00 |
October | 178.83 | 111.08 | 67.74 | 180.41 | 101.23 | 0.00 | 0.00 | 744.00 |
November | 140.28 | 82.43 | 57.85 | 118.28 | 121.82 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 76.05 | 45.32 | 91.36 | 160.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.97 | 100.40 | 84.57 | 193.13 | 91.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.36 | 71.74 | 45.32 | 91.36 | 31.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.54 | 130.68 | 116.46 | 286.84 | 160.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.74 | 0.00 | 25.74 | 3.95 | 94.20 | 0.00 | 0.00 | 744.00 |
February | 32.17 | 0.00 | 32.17 | 9.32 | 82.89 | 0.00 | 0.00 | 672.00 |
March | 40.58 | 0.00 | 40.58 | 22.09 | 62.22 | 0.00 | 0.00 | 744.00 |
April | 51.58 | 0.53 | 51.04 | 33.36 | 44.98 | 0.00 | 0.00 | 720.00 |
May | 56.07 | 3.69 | 52.38 | 41.52 | 36.41 | 0.00 | 0.00 | 744.00 |
June | 63.59 | 10.43 | 53.16 | 64.23 | 24.96 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 4.72 | 53.50 | 69.30 | 17.37 | 0.00 | 0.00 | 744.00 |
August | 54.34 | 1.41 | 52.93 | 59.82 | 20.25 | 0.00 | 0.00 | 744.00 |
September | 43.32 | 0.03 | 43.30 | 39.16 | 36.68 | 0.00 | 0.00 | 720.00 |
October | 32.30 | 0.00 | 32.30 | 15.92 | 60.85 | 0.00 | 0.00 | 744.00 |
November | 27.43 | 0.00 | 27.43 | 5.45 | 75.29 | 0.00 | 0.00 | 720.00 |
December | 21.91 | 0.00 | 21.91 | 0.94 | 100.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.31 | 1.74 | 40.57 | 30.54 | 54.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.91 | 0.00 | 21.91 | 0.94 | 17.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.59 | 10.43 | 53.50 | 69.30 | 100.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.74 | 0.00 | 25.74 | 3.95 | 94.20 | 0.00 | 0.00 | 744.00 |
February | 32.16 | 0.00 | 32.16 | 9.32 | 82.89 | 0.00 | 0.00 | 672.00 |
March | 40.58 | 0.00 | 40.58 | 22.09 | 62.22 | 0.00 | 0.00 | 744.00 |
April | 51.58 | 0.53 | 51.04 | 33.36 | 44.98 | 0.00 | 0.00 | 720.00 |
May | 56.07 | 3.69 | 52.38 | 41.52 | 36.41 | 0.00 | 0.00 | 744.00 |
June | 63.59 | 10.43 | 53.16 | 64.23 | 24.96 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 4.72 | 53.50 | 69.29 | 17.37 | 0.00 | 0.00 | 744.00 |
August | 54.34 | 1.41 | 52.93 | 59.81 | 20.25 | 0.00 | 0.00 | 744.00 |
September | 43.32 | 0.03 | 43.30 | 39.16 | 36.68 | 0.00 | 0.00 | 720.00 |
October | 32.30 | 0.00 | 32.30 | 15.92 | 60.85 | 0.00 | 0.00 | 744.00 |
November | 27.43 | 0.00 | 27.43 | 5.45 | 75.29 | 0.00 | 0.00 | 720.00 |
December | 21.90 | 0.00 | 21.90 | 0.94 | 100.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.31 | 1.74 | 40.57 | 30.54 | 54.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.90 | 0.00 | 21.90 | 0.94 | 17.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.59 | 10.43 | 53.50 | 69.29 | 100.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.98 | 43.17 | 19.81 | 74.91 | 90.76 | 0.00 | 0.00 | 744.00 |
February | 85.09 | 60.56 | 24.53 | 106.21 | 80.21 | 0.00 | 0.00 | 672.00 |
March | 110.18 | 76.40 | 33.79 | 143.71 | 66.16 | 0.00 | 0.00 | 744.00 |
April | 148.03 | 106.52 | 41.51 | 193.12 | 62.92 | 0.00 | 0.00 | 720.00 |
May | 160.66 | 121.12 | 39.55 | 209.00 | 62.64 | 0.00 | 0.00 | 744.00 |
June | 170.24 | 134.15 | 36.09 | 227.69 | 59.81 | 0.00 | 0.00 | 720.00 |
July | 165.61 | 124.50 | 41.11 | 225.92 | 52.15 | 0.00 | 0.00 | 744.00 |
August | 155.29 | 111.40 | 43.88 | 208.52 | 52.90 | 0.00 | 0.00 | 744.00 |
September | 126.55 | 92.44 | 34.11 | 164.98 | 68.17 | 0.00 | 0.00 | 720.00 |
October | 96.22 | 74.79 | 21.44 | 117.21 | 82.99 | 0.00 | 0.00 | 744.00 |
November | 68.39 | 48.31 | 20.08 | 81.16 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 56.30 | 42.32 | 13.97 | 63.35 | 92.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 117.27 | 86.42 | 30.85 | 151.52 | 70.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.30 | 42.32 | 13.97 | 63.35 | 52.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 170.24 | 134.15 | 43.88 | 227.69 | 92.93 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337166E+09 | 0.192143E+09 | 0.145023E+09 | 0.264837E+09 | 0.411347E+09 |
February | 0.390959E+09 | 0.225397E+09 | 0.165563E+09 | 0.345076E+09 | 0.329782E+09 |
March | 0.485470E+09 | 0.258489E+09 | 0.226980E+09 | 0.469886E+09 | 0.277965E+09 |
April | 0.598536E+09 | 0.318125E+09 | 0.280411E+09 | 0.615146E+09 | 0.198325E+09 |
May | 0.589345E+09 | 0.304465E+09 | 0.284879E+09 | 0.627887E+09 | 0.172252E+09 |
June | 0.607938E+09 | 0.338724E+09 | 0.269214E+09 | 0.743476E+09 | 0.122021E+09 |
July | 0.567688E+09 | 0.277808E+09 | 0.289880E+09 | 0.715481E+09 | 85103601.55 |
August | 0.579472E+09 | 0.267546E+09 | 0.311926E+09 | 0.701416E+09 | 97791119.41 |
September | 0.508869E+09 | 0.268630E+09 | 0.240239E+09 | 0.572984E+09 | 0.162173E+09 |
October | 0.478967E+09 | 0.297520E+09 | 0.181446E+09 | 0.483207E+09 | 0.271122E+09 |
November | 0.363617E+09 | 0.213661E+09 | 0.149956E+09 | 0.306578E+09 | 0.315757E+09 |
December | 0.325057E+09 | 0.203680E+09 | 0.121377E+09 | 0.244704E+09 | 0.428931E+09 |
Annual Sum or Average | 0.583308E+10 | 0.316619E+10 | 0.266690E+10 | 0.609068E+10 | 0.287257E+10 |
Minimum of Months | 0.325057E+09 | 0.192143E+09 | 0.121377E+09 | 0.244704E+09 | 85103601.55 |
Maximum of Months | 0.607938E+09 | 0.338724E+09 | 0.311926E+09 | 0.743476E+09 | 0.428931E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337166E+09 | 0.192143E+09 | 0.145023E+09 | 0.264837E+09 | 0.411347E+09 |
February | 0.390959E+09 | 0.225397E+09 | 0.165563E+09 | 0.345076E+09 | 0.329782E+09 |
March | 0.485470E+09 | 0.258489E+09 | 0.226980E+09 | 0.469886E+09 | 0.277965E+09 |
April | 0.598536E+09 | 0.318125E+09 | 0.280411E+09 | 0.615146E+09 | 0.198325E+09 |
May | 0.589345E+09 | 0.304465E+09 | 0.284879E+09 | 0.627887E+09 | 0.172252E+09 |
June | 0.607938E+09 | 0.338724E+09 | 0.269214E+09 | 0.743476E+09 | 0.122021E+09 |
July | 0.567688E+09 | 0.277808E+09 | 0.289880E+09 | 0.715481E+09 | 85103601.55 |
August | 0.579472E+09 | 0.267546E+09 | 0.311926E+09 | 0.701416E+09 | 97791119.41 |
September | 0.508869E+09 | 0.268630E+09 | 0.240239E+09 | 0.572984E+09 | 0.162173E+09 |
October | 0.478967E+09 | 0.297520E+09 | 0.181446E+09 | 0.483207E+09 | 0.271122E+09 |
November | 0.363617E+09 | 0.213661E+09 | 0.149956E+09 | 0.306578E+09 | 0.315757E+09 |
December | 0.325057E+09 | 0.203680E+09 | 0.121377E+09 | 0.244704E+09 | 0.428931E+09 |
Annual Sum or Average | 0.583308E+10 | 0.316619E+10 | 0.266690E+10 | 0.609068E+10 | 0.287257E+10 |
Minimum of Months | 0.325057E+09 | 0.192143E+09 | 0.121377E+09 | 0.244704E+09 | 85103601.55 |
Maximum of Months | 0.607938E+09 | 0.338724E+09 | 0.311926E+09 | 0.743476E+09 | 0.428931E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68931094.17 | 0.00 | 68931094.17 | 10591642.73 | 0.252312E+09 |
February | 77814968.69 | 0.00 | 77814968.69 | 22549306.77 | 0.200522E+09 |
March | 0.108700E+09 | 10134.22 | 0.108690E+09 | 59159324.82 | 0.166641E+09 |
April | 0.133686E+09 | 1379548.00 | 0.132306E+09 | 86467501.72 | 0.116582E+09 |
May | 0.150189E+09 | 9895483.65 | 0.140293E+09 | 0.111206E+09 | 97519705.83 |
June | 0.164824E+09 | 27026120.96 | 0.137798E+09 | 0.166478E+09 | 64705488.79 |
July | 0.155934E+09 | 12629418.14 | 0.143305E+09 | 0.185600E+09 | 46529478.75 |
August | 0.145539E+09 | 3774478.35 | 0.141764E+09 | 0.160212E+09 | 54238247.18 |
September | 0.112298E+09 | 65597.29 | 0.112232E+09 | 0.101492E+09 | 95066033.87 |
October | 86520339.15 | 0.00 | 86520339.15 | 42641452.41 | 0.162979E+09 |
November | 71106036.44 | 0.00 | 71106036.44 | 14120488.63 | 0.195146E+09 |
December | 58670776.91 | 0.00 | 58670776.91 | 2523715.60 | 0.269526E+09 |
Annual Sum or Average | 0.133421E+10 | 54780780.61 | 0.127943E+10 | 0.963042E+09 | 0.172177E+10 |
Minimum of Months | 58670776.91 | 0.00 | 58670776.91 | 2523715.60 | 46529478.75 |
Maximum of Months | 0.164824E+09 | 27026120.96 | 0.143305E+09 | 0.185600E+09 | 0.269526E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68929217.15 | 0.00 | 68929217.15 | 10590914.82 | 0.252312E+09 |
February | 77812936.66 | 0.00 | 77812936.66 | 22548156.51 | 0.200521E+09 |
March | 0.108697E+09 | 10133.75 | 0.108687E+09 | 59157113.34 | 0.166640E+09 |
April | 0.133683E+09 | 1379483.34 | 0.132303E+09 | 86464902.69 | 0.116581E+09 |
May | 0.150185E+09 | 9895019.83 | 0.140290E+09 | 0.111203E+09 | 97518904.84 |
June | 0.164819E+09 | 27024854.21 | 0.137795E+09 | 0.166475E+09 | 64704661.36 |
July | 0.155930E+09 | 12628826.18 | 0.143301E+09 | 0.185597E+09 | 46528726.99 |
August | 0.145535E+09 | 3774301.43 | 0.141761E+09 | 0.160208E+09 | 54237554.92 |
September | 0.112295E+09 | 65594.22 | 0.112229E+09 | 0.101490E+09 | 95065050.64 |
October | 86518266.99 | 0.00 | 86518266.99 | 42640264.06 | 0.162978E+09 |
November | 71104140.86 | 0.00 | 71104140.86 | 14119517.80 | 0.195145E+09 |
December | 58669292.31 | 0.00 | 58669292.31 | 2523442.03 | 0.269525E+09 |
Annual Sum or Average | 0.133418E+10 | 54778212.96 | 0.127940E+10 | 0.963018E+09 | 0.172176E+10 |
Minimum of Months | 58669292.31 | 0.00 | 58669292.31 | 2523442.03 | 46528726.99 |
Maximum of Months | 0.164819E+09 | 27024854.21 | 0.143301E+09 | 0.185597E+09 | 0.269525E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168688E+09 | 0.115628E+09 | 53059735.25 | 0.200647E+09 | 0.243093E+09 |
February | 0.205850E+09 | 0.146500E+09 | 59349461.63 | 0.256938E+09 | 0.194041E+09 |
March | 0.295113E+09 | 0.204624E+09 | 90489798.02 | 0.384903E+09 | 0.177210E+09 |
April | 0.383694E+09 | 0.276100E+09 | 0.107594E+09 | 0.500564E+09 | 0.163092E+09 |
May | 0.430320E+09 | 0.324399E+09 | 0.105921E+09 | 0.559787E+09 | 0.167776E+09 |
June | 0.441257E+09 | 0.347724E+09 | 93533290.04 | 0.590175E+09 | 0.155017E+09 |
July | 0.443561E+09 | 0.333458E+09 | 0.110103E+09 | 0.605099E+09 | 0.139675E+09 |
August | 0.415918E+09 | 0.298376E+09 | 0.117541E+09 | 0.558500E+09 | 0.141682E+09 |
September | 0.328019E+09 | 0.239614E+09 | 88405664.08 | 0.427626E+09 | 0.176710E+09 |
October | 0.257727E+09 | 0.200313E+09 | 57413502.00 | 0.313938E+09 | 0.222268E+09 |
November | 0.177276E+09 | 0.125231E+09 | 52045103.69 | 0.210378E+09 | 0.198517E+09 |
December | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.248916E+09 |
Annual Sum or Average | 0.369821E+10 | 0.272533E+10 | 0.972879E+09 | 0.477822E+10 | 0.222800E+10 |
Minimum of Months | 0.150784E+09 | 0.113360E+09 | 37423689.63 | 0.169668E+09 | 0.139675E+09 |
Maximum of Months | 0.443561E+09 | 0.347724E+09 | 0.117541E+09 | 0.605099E+09 | 0.248916E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 198.51 | 488.41 | 303.24 | 143.48 | 159.76 | 0.00 | 0.00 |
February | 298.03 | 432.52 | 387.54 | 186.34 | 201.20 | 0.00 | 0.00 |
March | 392.14 | 329.08 | 443.67 | 193.03 | 250.65 | 0.00 | 0.00 |
April | 539.16 | 240.78 | 564.98 | 246.53 | 318.45 | 0.00 | 0.00 |
May | 550.61 | 200.16 | 552.22 | 234.74 | 317.48 | 0.00 | 0.00 |
June | 699.18 | 141.13 | 596.27 | 282.21 | 314.05 | 0.00 | 0.00 |
July | 671.72 | 97.17 | 540.34 | 216.87 | 323.46 | 0.00 | 0.00 |
August | 643.00 | 113.13 | 541.37 | 202.60 | 338.78 | 0.00 | 0.00 |
September | 519.89 | 197.95 | 479.29 | 207.33 | 271.97 | 0.00 | 0.00 |
October | 389.21 | 320.70 | 422.26 | 222.16 | 200.09 | 0.00 | 0.00 |
November | 240.46 | 387.23 | 335.43 | 164.86 | 170.57 | 0.00 | 0.00 |
December | 171.83 | 508.77 | 286.53 | 152.09 | 134.44 | 0.00 | 0.00 |
Annual Sum or Average | 443.38 | 287.41 | 454.55 | 204.27 | 250.27 | 0.00 | 0.00 |
Minimum of Months | 171.83 | 97.17 | 286.53 | 143.48 | 134.44 | 0.00 | 0.00 |
Maximum of Months | 699.18 | 508.77 | 596.27 | 282.21 | 338.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 749.13 | 907.61 | 629.81 | 431.71 | 198.10 | 0.00 | 0.00 |
February | 1062.08 | 802.09 | 850.90 | 605.57 | 245.33 | 0.00 | 0.00 |
March | 1437.06 | 661.62 | 1101.83 | 763.98 | 337.85 | 0.00 | 0.00 |
April | 1931.19 | 629.21 | 1480.30 | 1065.20 | 415.10 | 0.00 | 0.00 |
May | 2090.00 | 626.40 | 1606.63 | 1211.17 | 395.46 | 0.00 | 0.00 |
June | 2276.91 | 598.06 | 1702.38 | 1341.53 | 360.85 | 0.00 | 0.00 |
July | 2259.18 | 521.48 | 1656.07 | 1244.99 | 411.08 | 0.00 | 0.00 |
August | 2085.20 | 528.98 | 1552.86 | 1114.01 | 438.85 | 0.00 | 0.00 |
September | 1649.79 | 681.75 | 1265.51 | 924.43 | 341.07 | 0.00 | 0.00 |
October | 1172.11 | 829.85 | 962.24 | 747.88 | 214.36 | 0.00 | 0.00 |
November | 811.64 | 765.88 | 683.93 | 483.14 | 200.79 | 0.00 | 0.00 |
December | 633.47 | 929.35 | 562.96 | 423.24 | 139.72 | 0.00 | 0.00 |
Annual Sum or Average | 1515.16 | 706.49 | 1172.69 | 864.20 | 308.50 | 0.00 | 0.00 |
Minimum of Months | 633.47 | 521.48 | 562.96 | 423.24 | 139.72 | 0.00 | 0.00 |
Maximum of Months | 2276.91 | 929.35 | 1702.38 | 1341.53 | 438.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.531700E+09 | 0.130816E+10 | 0.812193E+09 | 0.384287E+09 | 0.427906E+09 | 0.00 | 0.00 |
February | 0.720999E+09 | 0.104636E+10 | 0.937547E+09 | 0.450793E+09 | 0.486754E+09 | 0.00 | 0.00 |
March | 0.105030E+10 | 0.881420E+09 | 0.118834E+10 | 0.516998E+09 | 0.671338E+09 | 0.00 | 0.00 |
April | 0.139751E+10 | 0.624098E+09 | 0.146444E+10 | 0.639009E+09 | 0.825431E+09 | 0.00 | 0.00 |
May | 0.147475E+10 | 0.536104E+09 | 0.147906E+10 | 0.628721E+09 | 0.850341E+09 | 0.00 | 0.00 |
June | 0.181226E+10 | 0.365808E+09 | 0.154552E+10 | 0.731499E+09 | 0.814020E+09 | 0.00 | 0.00 |
July | 0.179914E+10 | 0.260248E+09 | 0.144724E+10 | 0.580874E+09 | 0.866367E+09 | 0.00 | 0.00 |
August | 0.172220E+10 | 0.303007E+09 | 0.145002E+10 | 0.542640E+09 | 0.907378E+09 | 0.00 | 0.00 |
September | 0.134756E+10 | 0.513090E+09 | 0.124233E+10 | 0.537390E+09 | 0.704939E+09 | 0.00 | 0.00 |
October | 0.104245E+10 | 0.858956E+09 | 0.113097E+10 | 0.595040E+09 | 0.535931E+09 | 0.00 | 0.00 |
November | 0.623285E+09 | 0.100369E+10 | 0.869445E+09 | 0.427323E+09 | 0.442122E+09 | 0.00 | 0.00 |
December | 0.460236E+09 | 0.136269E+10 | 0.767455E+09 | 0.407361E+09 | 0.360094E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139824E+11 | 0.906364E+10 | 0.143346E+11 | 0.644194E+10 | 0.789262E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460236E+09 | 0.260248E+09 | 0.767455E+09 | 0.384287E+09 | 0.360094E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181226E+10 | 0.136269E+10 | 0.154552E+10 | 0.731499E+09 | 0.907378E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200647E+10 | 0.243093E+10 | 0.168688E+10 | 0.115628E+10 | 0.530597E+09 | 0.00 | 0.00 |
February | 0.256937E+10 | 0.194041E+10 | 0.205850E+10 | 0.146500E+10 | 0.593495E+09 | 0.00 | 0.00 |
March | 0.384902E+10 | 0.177209E+10 | 0.295113E+10 | 0.204624E+10 | 0.904898E+09 | 0.00 | 0.00 |
April | 0.500564E+10 | 0.163092E+10 | 0.383694E+10 | 0.276100E+10 | 0.107594E+10 | 0.00 | 0.00 |
May | 0.559786E+10 | 0.167776E+10 | 0.430320E+10 | 0.324399E+10 | 0.105921E+10 | 0.00 | 0.00 |
June | 0.590175E+10 | 0.155017E+10 | 0.441257E+10 | 0.347724E+10 | 0.935333E+09 | 0.00 | 0.00 |
July | 0.605099E+10 | 0.139674E+10 | 0.443561E+10 | 0.333458E+10 | 0.110103E+10 | 0.00 | 0.00 |
August | 0.558500E+10 | 0.141682E+10 | 0.415918E+10 | 0.298376E+10 | 0.117541E+10 | 0.00 | 0.00 |
September | 0.427626E+10 | 0.176710E+10 | 0.328019E+10 | 0.239614E+10 | 0.884057E+09 | 0.00 | 0.00 |
October | 0.313937E+10 | 0.222267E+10 | 0.257727E+10 | 0.200313E+10 | 0.574135E+09 | 0.00 | 0.00 |
November | 0.210377E+10 | 0.198516E+10 | 0.177276E+10 | 0.125231E+10 | 0.520451E+09 | 0.00 | 0.00 |
December | 0.169667E+10 | 0.248916E+10 | 0.150784E+10 | 0.113360E+10 | 0.374237E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.477822E+11 | 0.222799E+11 | 0.369821E+11 | 0.272533E+11 | 0.972879E+10 | 0.00 | 0.00 |
Minimum of Months | 0.169667E+10 | 0.139674E+10 | 0.150784E+10 | 0.113360E+10 | 0.374237E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605099E+10 | 0.248916E+10 | 0.443561E+10 | 0.347724E+10 | 0.117541E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.2 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.20 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.66 | -5.5 | 4.72 | -6.1 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.69 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.40 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.39 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.11 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.38 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.86 | 7.70 | 3.48 | 8.21 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.78 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.53 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.11 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.80 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.83 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.65 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.28 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.68 | -1.5 | 8.93 | 13.33 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.11 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.67 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.27 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.73 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.23 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.79 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 3.99 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 3.99 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.73 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.1 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.6 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.2 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -0.7 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.53 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.76 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.7 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.82 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.83 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.65 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.92 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.05 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.75 | 167.00 | 0.00 |
June | 18.16 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.19 | 01-JUL-00:00 | 21.20 | 13.50 | 3.60 | 17.57 | 0.00 | 0.00 |
August | 19.17 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.18 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.15 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.79 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.90 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.90 | 12.80 | -10.0 | 2.10 | -0.1 | 0.00 | 0.00 | |
Maximum of Months | 19.19 | 31.70 | 15.60 | 13.40 | 19.17 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.71 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.78 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.70 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.04 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.58 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.03 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.37 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.04 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100747E+10 | -852323017.2 | 0.00 | 0.00 | 744.00 | 0.00 | -155150544.6 | 59.00 | 0.00 | 0.00 |
February | 0.927890E+09 | -789010562.2 | 0.00 | 0.00 | 672.00 | 0.00 | -138879162.3 | 58.99 | 0.00 | 0.00 |
March | 0.104877E+10 | -899371596.7 | 0.00 | 0.00 | 744.00 | 0.00 | -149393616.2 | 59.00 | 0.00 | 0.00 |
April | 0.927443E+09 | -791274760.0 | 0.00 | 0.00 | 720.00 | 0.00 | -136168615.8 | 58.99 | 0.00 | 0.00 |
May | 0.900514E+09 | -765537145.4 | 0.00 | 0.00 | 744.00 | 0.00 | -134977002.9 | 58.99 | 0.00 | 0.00 |
June | 0.836549E+09 | -707999647.1 | 0.00 | 0.00 | 720.00 | 0.00 | -128549280.5 | 58.99 | 0.00 | 0.00 |
July | 0.780949E+09 | -649633889.9 | 0.00 | 0.00 | 744.00 | 0.00 | -131315264.2 | 58.99 | 0.00 | 0.00 |
August | 0.822533E+09 | -690153729.5 | 0.00 | 0.00 | 744.00 | 0.00 | -132379107.5 | 58.99 | 0.00 | 0.00 |
September | 0.791800E+09 | -663772965.0 | 0.00 | 0.00 | 720.00 | 0.00 | -128027467.3 | 58.99 | 0.00 | 0.00 |
October | 0.848286E+09 | -710541790.7 | 0.00 | 0.00 | 744.00 | 0.00 | -137744484.3 | 58.99 | 0.00 | 0.00 |
November | 0.880465E+09 | -735516332.4 | 0.00 | 0.00 | 720.00 | 0.00 | -144948288.8 | 58.99 | 0.00 | 0.00 |
December | 0.972174E+09 | -817177191.2 | 0.00 | 0.00 | 744.00 | 0.00 | -154996890.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.107448E+11 | -.907231E+10 | 8760.00 | -.167253E+10 | 58.99 | |||||
Minimum of Months | 0.780949E+09 | -899371596.7 | 0.00 | 0.00 | 672.00 | 0.00 | -155150544.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.104877E+10 | -649633889.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128027467.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | ||||||||||
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.383417E+10 | 28130.96 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299082E+10 | 28130.96 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162661E+10 | 28130.96 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317246E+09 | 28130.96 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39693453.35 | 28130.96 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 882087.22 | 2940.29 | 15-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.281175E+09 | 28130.96 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128526E+10 | 28130.96 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366198E+10 | 28130.96 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140378E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383417E+10 | 28130.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230158E+11 | 89608.79 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165231E+11 | 89608.79 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623991E+10 | 89608.79 | 03-MAR-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300561E+09 | 45274.36 | 07-APR-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394820E+09 | 50586.16 | 26-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.696361E+10 | 89608.79 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218444E+11 | 89608.79 | 03-DEC-18:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752822E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230158E+11 | 89608.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.347951E+11 | 91029.89 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212146E+11 | 82925.54 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167809E+10 | 36818.13 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148942E+10 | 33414.58 | 26-NOV-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327274E+11 | 92901.44 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919047E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347951E+11 | 92901.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3743485.36 | 3743485.36 | 1046.22 | 14-FEB-16:00 | 1046.22 | 0.00 |
March | 0.00 | 0.00 | 14774441.53 | 14774441.53 | 1856.06 | 08-MAR-16:00 | 1856.06 | 0.00 |
April | 0.00 | 0.00 | 0.116748E+10 | 0.116748E+10 | 20334.96 | 11-APR-18:01 | 20334.96 | 0.00 |
May | 0.00 | 0.00 | 0.338278E+10 | 0.336615E+10 | 21449.75 | 23-MAY-18:33 | 15144.16 | 0.00 |
June | 0.00 | 0.00 | 0.887940E+10 | 0.873328E+10 | 22207.37 | 24-JUN-00:21 | 19365.92 | 0.00 |
July | 0.00 | 0.00 | 0.128084E+11 | 0.114190E+11 | 24371.57 | 01-JUL-17:08 | 14419.02 | 0.00 |
August | 0.00 | 0.00 | 0.121870E+11 | 0.108416E+11 | 23407.08 | 14-AUG-01:09 | 13615.86 | 0.00 |
September | 0.00 | 0.00 | 0.690921E+10 | 0.644630E+10 | 22467.38 | 23-SEP-17:11 | 15171.76 | 0.00 |
October | 0.00 | 0.00 | 0.219574E+10 | 0.208382E+10 | 22742.51 | 02-OCT-17:10 | 15547.57 | 0.00 |
November | 0.00 | 0.00 | 5078.17 | 5078.17 | 0.65 | 02-NOV-15:00 | 0.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.475486E+11 | 0.440762E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128084E+11 | 0.114190E+11 | 24371.57 | 20334.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.161984E+09 | 0.161984E+09 | 6328.27 | 28-APR-14:40 | 6328.27 | 0.00 |
May | 0.00 | 0.00 | 0.364769E+10 | 0.364289E+10 | 61753.23 | 28-MAY-12:21 | 55980.15 | 0.00 |
June | 0.00 | 0.00 | 0.190039E+11 | 0.188393E+11 | 63465.04 | 25-JUN-08:11 | 54509.28 | 0.00 |
July | 0.00 | 0.00 | 0.289825E+11 | 0.271155E+11 | 69603.22 | 16-JUL-08:31 | 43173.18 | 0.00 |
August | 0.00 | 0.00 | 0.242161E+11 | 0.225378E+11 | 68902.55 | 13-AUG-08:25 | 39620.41 | 0.00 |
September | 0.00 | 0.00 | 0.105571E+11 | 0.100619E+11 | 65633.38 | 04-SEP-10:41 | 50976.83 | 0.00 |
October | 0.00 | 0.00 | 0.200332E+10 | 0.195413E+10 | 60807.33 | 01-OCT-11:20 | 58506.58 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.885726E+11 | 0.843135E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.289825E+11 | 0.271155E+11 | 69603.22 | 58506.58 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.396558E+09 | 0.05 | 298.41 | 01-JAN-00:03 | 0.09 |
February | 0.225125E+09 | 0.03 | 298.41 | 01-FEB-00:02 | 0.09 |
March | 29921390.19 | 0.00 | 298.41 | 01-MAR-03:10 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 28217479.37 | 0.00 | 298.41 | 25-NOV-05:40 | 0.09 |
December | 0.402583E+09 | 0.05 | 298.41 | 03-DEC-07:38 | 0.09 |
Annual Sum or Average | 0.108240E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.402583E+09 | 0.05 | 298.41 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156774E+10 | 0.52 | 1522.46 | 02-JAN-09:00 | 1.14 |
February | 0.143790E+10 | 0.51 | 1522.46 | 01-FEB-10:10 | 1.14 |
March | 0.166295E+10 | 0.49 | 1522.46 | 01-MAR-09:20 | 1.14 |
April | 0.153118E+10 | 0.46 | 1522.46 | 01-APR-16:30 | 1.14 |
May | 0.165183E+10 | 0.50 | 1522.46 | 02-MAY-14:30 | 1.14 |
June | 0.187486E+10 | 0.65 | 1522.46 | 01-JUN-10:30 | 1.13 |
July | 0.196274E+10 | 0.66 | 1522.46 | 03-JUL-06:50 | 1.13 |
August | 0.209622E+10 | 0.70 | 1522.46 | 03-AUG-06:05 | 1.13 |
September | 0.189387E+10 | 0.63 | 1522.46 | 05-SEP-09:20 | 1.12 |
October | 0.162878E+10 | 0.48 | 1522.46 | 05-OCT-08:70 | 1.13 |
November | 0.147308E+10 | 0.45 | 1522.46 | 01-NOV-17:00 | 1.13 |
December | 0.155362E+10 | 0.47 | 1522.46 | 01-DEC-09:05 | 1.14 |
Annual Sum or Average | 0.203348E+11 | 0.54 | |||
Minimum of Months | 0.143790E+10 | 0.45 | 1522.46 | 1.12 | |
Maximum of Months | 0.209622E+10 | 0.70 | 1522.46 | 1.14 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.442946E+10 | 0.90 | 3585.37 | 09-JAN-07:10 | 1.09 |
February | 0.391772E+10 | 0.84 | 3585.37 | 01-FEB-16:20 | 1.09 |
March | 0.409244E+10 | 0.67 | 3585.37 | 01-MAR-07:20 | 1.09 |
April | 0.356374E+10 | 0.43 | 3585.37 | 28-APR-13:40 | 1.09 |
May | 0.372703E+10 | 0.44 | 3585.37 | 17-MAY-16:30 | 1.09 |
June | 0.395128E+10 | 0.53 | 3585.37 | 03-JUN-11:10 | 1.08 |
July | 0.400703E+10 | 0.55 | 3585.37 | 01-JUL-11:45 | 1.07 |
August | 0.414633E+10 | 0.54 | 3585.37 | 01-AUG-15:40 | 1.09 |
September | 0.364105E+10 | 0.44 | 3585.37 | 01-SEP-10:50 | 1.08 |
October | 0.358096E+10 | 0.43 | 3585.37 | 03-OCT-16:00 | 1.08 |
November | 0.371041E+10 | 0.68 | 3585.37 | 18-NOV-07:40 | 1.10 |
December | 0.439716E+10 | 0.91 | 3585.37 | 08-DEC-08:70 | 1.10 |
Annual Sum or Average | 0.471646E+11 | 0.61 | |||
Minimum of Months | 0.356374E+10 | 0.43 | 3585.37 | 1.07 | |
Maximum of Months | 0.442946E+10 | 0.91 | 3585.37 | 1.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.84 | 0.20 |
February | 1.69 | 0.01 |
March | 0.61 | 0.22 |
April | 2.49 | 0.12 |
May | 8.01 | 0.00 |
June | 14.61 | 0.04 |
July | 19.26 | 0.10 |
August | 23.18 | 0.04 |
September | 15.49 | 0.04 |
October | 5.95 | 0.07 |
November | 1.01 | 0.75 |
December | 3.07 | 0.07 |
Annual Sum or Average | 98.22 | 0.06 |
Minimum of Months | 0.61 | 0.00 |
Maximum of Months | 23.18 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.04 | 0.00 |
February | 0.04 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 1.41 | 0.00 |
June | 1.53 | 0.00 |
July | 2.36 | 0.00 |
August | 2.68 | 0.00 |
September | 3.17 | 0.00 |
October | 0.31 | 0.00 |
November | 0.00 | 0.00 |
December | 0.17 | 0.00 |
Annual Sum or Average | 11.80 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 2.69 | 0.00 |
July | 7.82 | 0.00 |
August | 7.19 | 0.00 |
September | 1.46 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 19.15 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.82 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156774E+10 | 0.560998E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143893E+10 | 0.437751E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166701E+10 | 0.237512E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.184342E+10 | 0.466403E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.257068E+10 | 59022798.51 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.445703E+10 | 1343163.90 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.557259E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.544689E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.375465E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.221086E+10 | 0.415121E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147308E+10 | 0.188266E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155362E+10 | 0.536620E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.335565E+11 | 0.205534E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143893E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.557259E+10 | 0.560998E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.442946E+10 | 0.334447E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.391772E+10 | 0.240515E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.409244E+10 | 0.925680E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361212E+10 | 0.449298E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.482200E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100958E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131128E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.115466E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.678398E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.417090E+10 | 0.598924E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.371041E+10 | 0.103236E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.439716E+10 | 0.318329E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.746914E+11 | 0.109958E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.361212E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.131128E+11 | 0.334447E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156774E+10 | 0.00 | 0.383417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143790E+10 | 3743485.36 | 0.299082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166295E+10 | 14774441.53 | 0.162661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153118E+10 | 0.116748E+10 | 0.317246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165183E+10 | 0.338278E+10 | 39693453.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187486E+10 | 0.887940E+10 | 882087.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196274E+10 | 0.128084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209622E+10 | 0.121870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189387E+10 | 0.690921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162878E+10 | 0.219574E+10 | 0.281175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147308E+10 | 5078.17 | 0.128526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155362E+10 | 0.00 | 0.366198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203348E+11 | 0.475486E+11 | 0.140378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209622E+10 | 0.128084E+11 | 0.383417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.442946E+10 | 0.00 | 0.230158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391772E+10 | 0.00 | 0.165231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409244E+10 | 0.00 | 0.623991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356374E+10 | 0.161984E+09 | 0.300561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372703E+10 | 0.364769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395128E+10 | 0.190039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400703E+10 | 0.289825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414633E+10 | 0.242161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364105E+10 | 0.105571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358096E+10 | 0.200332E+10 | 0.394820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371041E+10 | 0.00 | 0.696361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439716E+10 | 0.00 | 0.218444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471646E+11 | 0.885726E+11 | 0.752822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.356374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.442946E+10 | 0.289825E+11 | 0.230158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143790E+10 | 0.00 | 0.00 | 0.00 | 1036241.72 | 0.00 | 0.437751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166295E+10 | 0.00 | 0.00 | 0.00 | 4065810.61 | 0.00 | 0.237512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153118E+10 | 0.00 | 0.00 | 0.00 | 0.312243E+09 | 0.00 | 0.466403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165183E+10 | 0.00 | 0.00 | 0.00 | 0.918851E+09 | 0.00 | 59022798.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187486E+10 | 0.00 | 0.00 | 0.00 | 0.258218E+10 | 0.00 | 1343163.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196274E+10 | 0.00 | 0.00 | 0.00 | 0.360984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209622E+10 | 0.00 | 0.00 | 0.00 | 0.335067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189387E+10 | 0.00 | 0.00 | 0.00 | 0.186078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162878E+10 | 0.00 | 0.00 | 0.00 | 0.582081E+09 | 0.00 | 0.415121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147308E+10 | 0.00 | 0.00 | 0.00 | 1414.57 | 0.00 | 0.188266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203348E+11 | 0.00 | 0.00 | 0.00 | 0.132217E+11 | 0.00 | 0.205534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209622E+10 | 0.00 | 0.00 | 0.00 | 0.360984E+10 | 0.00 | 0.560998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.442946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356374E+10 | 0.00 | 0.00 | 0.00 | 48380104.78 | 0.00 | 0.449298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372703E+10 | 0.00 | 0.00 | 0.00 | 0.109497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395128E+10 | 0.00 | 0.00 | 0.00 | 0.614457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400703E+10 | 0.00 | 0.00 | 0.00 | 0.910578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414633E+10 | 0.00 | 0.00 | 0.00 | 0.740026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364105E+10 | 0.00 | 0.00 | 0.00 | 0.314292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358096E+10 | 0.00 | 0.00 | 0.00 | 0.589942E+09 | 0.00 | 0.598924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471646E+11 | 0.00 | 0.00 | 0.00 | 0.275268E+11 | 0.00 | 0.109958E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.356374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.442946E+10 | 0.00 | 0.00 | 0.00 | 0.910578E+10 | 0.00 | 0.334447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119502E+10 | 0.00 | 0.00 | 0.12 |
February | 0.295630E+09 | 0.00 | 0.00 | 29291.81 | 0.00 | 0.949521E+09 | 64219541.29 | 0.00 | 0.15 |
March | 0.575437E+09 | 0.00 | 0.00 | 77158.78 | 0.00 | 0.482813E+09 | 0.200391E+09 | 0.00 | 0.19 |
April | 0.387339E+09 | 4041006.99 | 0.00 | 1967017.77 | 0.00 | 58293641.63 | 0.126494E+10 | 0.00 | 0.46 |
May | 0.124305E+09 | 31990191.58 | 0.00 | 4969292.47 | 0.00 | 6027491.63 | 0.202952E+10 | 0.00 | 0.64 |
June | 16501975.24 | 0.310218E+09 | 0.00 | 6112868.63 | 48389.88 | 0.00 | 0.140826E+10 | 0.00 | 0.65 |
July | 480214.54 | 0.961102E+09 | 0.00 | 4774866.13 | 186326.64 | 0.00 | 0.425987E+09 | 0.00 | 0.61 |
August | 2637814.62 | 0.712317E+09 | 0.00 | 6567096.76 | 531418.10 | 0.00 | 0.103867E+10 | 0.00 | 0.78 |
September | 24846722.05 | 0.140672E+09 | 0.00 | 9051236.88 | 0.00 | 0.00 | 0.228938E+10 | 0.00 | 0.87 |
October | 0.288336E+09 | 19893588.24 | 0.00 | 4741918.06 | 0.00 | 99600898.22 | 0.202607E+10 | 0.00 | 0.59 |
November | 0.709051E+09 | 0.00 | 0.00 | 87617.98 | 0.00 | 0.428559E+09 | 0.160408E+09 | 0.00 | 0.14 |
December | 0.320175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134737E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.301640E+10 | 0.218023E+10 | 0.00 | 38378365.26 | 766134.61 | 0.456720E+10 | 0.109078E+11 | 0.00 | 0.44 |
Minimum of Months | 480214.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.709051E+09 | 0.961102E+09 | 0.00 | 9051236.88 | 531418.10 | 0.134737E+10 | 0.228938E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153337E+10 | 0.00 | 0.00 | 0.17 |
February | 0.256015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877802E+09 | 0.00 | 0.00 | 0.18 |
March | 0.256124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260855E+09 | 0.00 | 0.00 | 0.19 |
April | 0.237986E+10 | 0.00 | 0.00 | 464633.00 | 1392894.48 | 0.00 | 0.454975E+09 | 0.00 | 0.26 |
May | 0.155686E+10 | 40190062.37 | 0.00 | 4986830.76 | 2822438.75 | 0.00 | 0.205710E+10 | 0.00 | 0.43 |
June | 0.462260E+09 | 0.901573E+09 | 0.00 | 6337219.68 | 0.00 | 0.00 | 0.163415E+10 | 0.00 | 0.42 |
July | 71172448.07 | 0.167568E+10 | 0.00 | 7554610.22 | 0.00 | 0.00 | 0.128356E+10 | 0.00 | 0.44 |
August | 0.178976E+09 | 0.111669E+10 | 0.00 | 11495623.42 | 445232.18 | 0.00 | 0.213436E+10 | 0.00 | 0.54 |
September | 0.494292E+09 | 0.175732E+09 | 0.00 | 12767177.33 | 0.00 | 0.00 | 0.261592E+10 | 0.00 | 0.54 |
October | 0.244008E+10 | 6159905.19 | 0.00 | 4082207.54 | 0.00 | 57084661.25 | 0.110133E+10 | 0.00 | 0.32 |
November | 0.309564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199542E+09 | 0.00 | 0.00 | 0.17 |
December | 0.332564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139321E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.216036E+11 | 0.391603E+10 | 0.00 | 47688301.96 | 4660565.40 | 0.432186E+10 | 0.112814E+11 | 0.00 | 0.32 |
Minimum of Months | 71172448.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.332564E+10 | 0.167568E+10 | 0.00 | 12767177.33 | 2822438.75 | 0.153337E+10 | 0.261592E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |