Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1065.80 | 220.43 | 220.43 |
Net Site Energy | 1065.80 | 220.43 | 220.43 |
Total Source Energy | 3171.49 | 655.93 | 655.93 |
Net Source Energy | 3171.49 | 655.93 | 655.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 97.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 73.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 967.91 | 97.88 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 97.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 15.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.16 | 20.24 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 200.18 | 20.24 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.16 | 20.24 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 200.18 | 20.24 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 967.913 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 967.913 | 100.00 |
Total On-Site and Utility Electric Sources | 967.913 | 100.00 |
Total Electricity End Uses | 967.913 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.33 |
Time Setpoint Not Met During Occupied Cooling | 21.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 266.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-14:00 | 21-DEC-07:10 | - | - | - | 13-JUL-11:09 |
Heating | 0.00 | 33205.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21535.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6728.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1684.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75680.34 | 33205.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 33205.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21535.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4422.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1684.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 106.11 | 0.00 | 0.00 | 0.00 |
Cooling | 396.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 234.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3065.38 | 106.11 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.94 | 0.00 | 0.00 | 0.00 |
Cooling | 81.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 633.98 | 21.94 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.94 | 0.00 | 0.00 | 0.00 |
Cooling | 81.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 633.98 | 21.94 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.16 |
ZONE2 FINE STORAGE DIRECT AIR | 2.83 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.39 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.39 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 57512.07 |
PSZ-OFFICE HEATING COIL | 29082.06 |
PSZ-FINE STORAGE HEATING COIL | 88306.88 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 57512.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 2.83 | 1.00 | 1.000000 | 2.83 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.16 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.83 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 1.16 | 23480.29 | 29082.06 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.83 | 2.83 | 2.83 | 2.83 | 69433.11 | 88306.88 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.16 | 0.581375 | 1.16 | 22938.79 | 23480.29 | 11740.15 | 23480.29 | 0.732380 | 0.732380 | 0.732380 | 0.732380 |
PSZ-FINE STORAGE COOLING COIL | 2.83 | 1.41 | 2.83 | 66579.37 | 69433.11 | 34716.56 | 69433.11 | 0.679028 | 0.679030 | 0.679030 | 0.679030 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.16 | 1325.67 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.83 | 3097.09 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11768.01041 | 14121.61250 | 0.96896 | 1.16275 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7875.41074 | 9450.49289 | 0.22109 | 0.26530 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36735.74174 | 44082.89008 | 2.35806 | 2.82967 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65138E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 19266.35889 | 23119.63066 | 0.45594 | 0.54713 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 1.65138E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 47926.72136 | 57512.06564 | 1.15491 | 1.38589 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18021.59 | 1.16275 | 1.16275 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8478.39 | 0.26530 | 0.26530 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 53364.81 | 2.82967 | 2.82967 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 20857.04 | 0.54713 | 0.54713 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16275 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.82967 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38589 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.38589 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 57512.06736 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 57512.06564 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16275 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16275 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16275 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16275 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16275 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.16275 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.82967 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.82967 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.82967 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82967 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.82967 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.82967 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.16275 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.82967 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16275 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16275 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16275 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16275 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16275 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16275 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58138 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16275 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22938.78566 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23480.29000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11740.14500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23480.29000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73238 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73238 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73238 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73238 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23480.29000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29082.05582 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16275 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1325.66833 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29082.05582 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.82967 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.82967 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.82967 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.82967 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.82967 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.82967 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.41484 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.82967 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 66579.36777 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 69433.11000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 34716.55500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 69433.11000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67903 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67903 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67903 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67903 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 69433.11000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 88306.88452 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.82967 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3097.09039 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 88306.88452 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22577.4 | 10.38 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 67233.8 | 13.48 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.8492840528E-002 | 3.8515649653E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1061319432 | 0.1421267032 | Pass | Pass | 8.7389524819E-002 | 0.6406729227 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.8031357288E-002 | 6.7401038656E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.73 | 83.73 | 123.49 | |
Exterior Lighting Total | 7857.24 | 123.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23480.29 | 17196.49 | 6283.80 | 0.73 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 69433.11 | 47147.16 | 22285.95 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22577.4 | 10.38 | ||||
PSZ-FINE STORAGE COOLING COIL | 67233.8 | 13.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 57512.07 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29082.06 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 88306.88 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.39 | 128.76 | 92.91 | 1.00 | 3.84 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.16 | 1325.67 | 1140.11 | 1.00 | 1.33 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.83 | 3097.09 | 1094.51 | 1.00 | 1.24 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11768.01 | 14121.61 | 59.62 | 0.969 | 1.163 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00831 | 32.79 | 0.01651 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 36735.74 | 44082.89 | 31.64 | 2.358 | 2.830 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00858 | 33.90 | 0.01651 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 33.90 | 0.01651 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7875.41 | 9450.49 | 39.90 | 0.221 | 0.265 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00778 | 4.60 | 0.00526 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 19266.36 | 23119.63 | 16.59 | 0.456 | 0.547 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00679 | 4.60 | 0.00526 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 47926.72 | 57512.07 | 17.95 | 1.155 | 1.386 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00764 | 4.60 | 0.00526 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.16 | 1.16 | 0.27 | 0.27 | 1.1628 | 1.1628 | 1.1628 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.83 | 2.83 | 0.55 | 0.55 | 2.8297 | 2.8297 | 2.8297 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 57512.067 | 57512.067 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 57512.07 | 57512.07 | 1.385893 | 6.83 | 6.83 | 0.00623850 | 43.33 | 27.10 | 0.01600000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00763545 | 99.9999 | 57512.07 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23480.290 | 0.000 | 1.162750 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23480.29 | 19493.97 | 1.162750 | 24.82 | 17.21 | 0.00915717 | 12.00 | 11.25 | 0.00800000 | 32.79 | 0.01651377 | 24.82 | 10.3492 | 23.90 | 0.00830793 | 44.9715 | 11768.01 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29082.056 | 29082.056 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29082.06 | 29082.06 | 1.162755 | 13.57 | 10.49 | 0.00663696 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 10.3492 | 21.10 | 0.00778233 | 49.9799 | 7875.41 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 69433.110 | 0.000 | 2.829670 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 69433.11 | 56318.30 | 2.829670 | 27.60 | 18.48 | 0.00957366 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01651378 | 25.10 | 12.5077 | 26.70 | 0.00858152 | 39.3109 | 35661.85 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 88306.885 | 88306.885 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 88306.88 | 88306.88 | 2.829671 | 8.47 | 7.21 | 0.00579830 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 12.5077 | 15.56 | 0.00678961 | 61.8381 | 19266.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 57512.067 | 57512.067 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2032 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.385893 | 1.66746003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 57512.07 | 57512.07 | 1.0000 | 1.66746003 | 1.385893 | 6.83 | 6.83 | 0.00623850 | 22540.6 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57512.07 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00763545 | 10.00 | 0.00763545 | 99.9999 | 57512.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23480.290 | 0.000 | 1.162750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8627 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23480.29 | 19493.97 | 1.0000 | 1.39898231 | 1.162750 | 24.82 | 17.21 | 0.00915717 | 48263.7 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23480.29 | 32.79 | 0.01651377 | 24.82 | 0.12033533 | 10.3492 | 23.90 | 0.00830793 | 23.90 | 0.00830793 | 44.9715 | 11768.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29082.056 | 29082.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.162755 | 1.39898818 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29082.06 | 29082.06 | 1.0000 | 1.39898818 | 1.162755 | 13.57 | 10.49 | 0.00663696 | 30399.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29082.06 | 4.60 | 0.00525715 | 4.60 | 0.12033533 | 10.3492 | 21.01 | 0.00778233 | 21.10 | 0.00778233 | 49.9799 | 7875.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 69433.110 | 0.000 | 2.829670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6370 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 69433.11 | 56318.30 | 1.0000 | 3.40456527 | 2.829670 | 27.60 | 18.48 | 0.00957366 | 52166.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69433.11 | 33.90 | 0.01651378 | 25.10 | 0.35392745 | 12.5077 | 26.70 | 0.00858152 | 26.70 | 0.00858152 | 39.3109 | 35661.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88306.885 | 88306.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.829671 | 3.40456640 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 88306.88 | 88306.88 | 1.0000 | 3.40456640 | 2.829671 | 8.47 | 7.21 | 0.00579830 | 23103.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88306.88 | 4.60 | 0.00525715 | 4.60 | 0.35392745 | 12.5077 | 15.56 | 0.00678961 | 15.56 | 0.00678961 | 61.8381 | 19266.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2532.67 | 1052.83 | 266.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2532.67 | 1052.83 | 266.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.33 | 444.67 | 3.33 | 21.00 |
ZONE2 FINE STORAGE | 1.00 | 152.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.33 | 545.33 | 3.33 | 21.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.405 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
Electricity:Building | 636.78 | 4992.32 | 01-JAN-00:10 | 48037.94 | 30-MAR-12:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 437.19 | 2759.73 | 01-JAN-00:10 | 33963.13 | 30-MAR-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.10 | 483.00 | 11-JAN-06:10 | 1781.05 | 23-JAN-12:30 |
WaterSystems:Electricity | 24.10 | 483.00 | 11-JAN-06:10 | 1781.05 | 23-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 11-JAN-06:10 | 1781.05 | 23-JAN-12:30 |
Fans:Electricity | 73.90 | 0.00 | 01-JAN-00:10 | 6728.05 | 14-APR-13:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.54 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 15.54 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
ElectricityPurchased:Plant | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
Cogeneration:ElectricityPurchased | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
ElectricityNet:Plant | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
Cogeneration:ElectricityNet | 967.91 | 5475.32 | 01-JAN-07:30 | 75680.34 | 03-AUG-15:00 |
Electricity:HVAC | 183.54 | 0.00 | 01-JAN-00:10 | 28201.96 | 03-AUG-16:10 |
General:Fans:Electricity | 58.36 | 0.00 | 01-JAN-00:10 | 4422.76 | 13-JUL-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 125.18 | 0.00 | 01-JAN-00:10 | 23779.20 | 03-AUG-16:10 |
ExteriorLights:Electricity | 123.49 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.49 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 97.88 | 3000.00 | 02-JAN-00:10 | 33205.20 | 21-DEC-07:10 |
Gas:HVAC | 97.88 | 3000.00 | 02-JAN-00:10 | 33205.20 | 21-DEC-07:10 |
Heating:Gas | 97.88 | 3000.00 | 02-JAN-00:10 | 33205.20 | 21-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 691.97 | 0.00 | 01-JAN-00:10 | 126235.86 | 03-AUG-16:10 |
EnergyTransfer:Building | 252.84 | 0.00 | 01-JAN-00:10 | 48642.86 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 84.57 | 0.00 | 01-JAN-00:10 | 14016.00 | 11-SEP-00:10 |
Heating:EnergyTransfer | 4.09 | 0.00 | 01-JAN-00:10 | 18970.90 | 05-FEB-07:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.81 | 0.00 | 01-JAN-00:10 | 12565.26 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 248.75 | 0.00 | 01-JAN-00:10 | 48642.86 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 82.77 | 0.00 | 01-JAN-00:10 | 14016.00 | 11-SEP-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 168.27 | 0.00 | 01-JAN-00:10 | 37760.70 | 03-AUG-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.28 | 0.00 | 01-JAN-00:10 | 18970.90 | 05-FEB-07:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 165.98 | 0.00 | 01-JAN-00:10 | 37760.70 | 03-AUG-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 439.13 | 0.00 | 01-JAN-00:10 | 77798.84 | 03-JUL-16:30 |
HeatingCoils:EnergyTransfer | 2.22 | 0.00 | 01-JAN-00:10 | 20811.01 | 21-DEC-07:10 |
CoolingCoils:EnergyTransfer | 436.91 | 0.00 | 01-JAN-00:10 | 77798.84 | 03-JUL-16:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.806 | -82.766 | 0.000 | 0.000 | 3.623 | 30.994 | 31.946 | 12.642 | 0.000 | 4.156 | 12.093 | 0.000 | -7.695 | 0.000 | -6.800 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.284 | -165.972 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 7.619 | 67.483 | 0.000 | 0.000 | 0.000 | -48.070 | -0.007 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 44.364 | 0.000 | 1.478 | 194.233 | 0.000 | -15.651 | 0.000 | -646.070 | -0.000 |
Total Facility | 0.000 | 0.000 | 4.090 | -248.738 | 0.000 | 0.000 | 3.623 | 481.960 | 139.282 | 57.007 | 0.000 | 13.252 | 273.809 | 0.000 | -23.346 | 0.000 | -700.939 | -0.009 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-OCT-00:01 | 0.00 | 0.00 | 0.00 | -20175.37 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 20032.57 | 0.00 | -634.58 | 0.00 | -255.33 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-12:23 | 0.00 | 0.00 | 0.00 | -55565.38 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 54507.32 | 0.00 | -0.00 | 0.00 | -141.82 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-17:05 | 0.00 | 0.00 | 0.00 | -72330.52 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5535.96 | 0.00 | 1288.78 | 104709.99 | 0.00 | 0.00 | 0.00 | -46246.55 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 27899.38 | 0.00 | 0.00 | 0.00 | 52.95 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -759.58 | 0.00 | -891.21 | -27461.73 |
ZONE2 FINE STORAGE | 05-FEB-07:43 | 0.00 | 0.00 | 56912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15331.21 | -42781.38 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-FEB-07:43 | 0.00 | 0.00 | 56912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 0.00 | 0.00 | 0.00 | 10734.97 | 0.00 | -3387.19 | 0.00 | -69252.80 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1628 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1628 | 0.1035 | 1.0000 | 0.1203 | 0.1035 | ||
PSZ-FINE STORAGE | 2.8297 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.8297 | 0.1251 | 1.0000 | 0.3539 | 0.1251 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1628 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1628 | 1.0000 | 1.0000 | 0.1203 | 0.1035 | ||
PSZ-FINE STORAGE | 2.8297 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.8297 | 1.0000 | 1.0000 | 0.3539 | 0.1251 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1628 | 1.1628 | 1.1628 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8297 | 2.8297 | 2.8297 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1628 | 1.1628 | 1.1628 | 1.1628 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.8297 | 2.8297 | 2.8297 | 2.8297 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1628 | 1.1628 | 1.1628 | 0.1203 | 0.4536 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8297 | 2.8297 | 2.8297 | 0.3539 | 0.6469 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1628 | 1.1628 | 1.1628 | 1.1628 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.8297 | 2.8297 | 2.8297 | 2.8297 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.33 |
Number of hours cooling loads not met | 21.00 |
Number of hours not met | 24.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 97.88 | 33205.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 125.18 | 23779.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.49 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 15.54 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.36 | 4422.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1781.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 967.91 |
Natural Gas | 0.00 | 97.88 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1065.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 25.89 |
Fans (All) | 15.28 |
Service Water Heating | 4.99 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 200.18 |
Subtotal | 200.18 |
Natural Gas [MJ/m2] | |
Space Heating | 20.24 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 20.24 |
Subtotal | 20.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.22 |
Space Heating | 9.18 |
Space Cooling | 11.75 |
Fans (All) | 6.93 |
Service Water Heating | 2.26 |
Receptacle Equipment | 13.07 |
Miscellaneous | 11.59 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.927526E+10 |
February | 0.000 | 0.814129E+10 |
March | 0.000 | 0.846698E+10 |
April | 0.000 | 0.778031E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781984E+10 |
December | 0.000 | 0.870693E+10 |
Annual Sum or Average | 0.978834E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.927526E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138569E+10 | 17802.81 | 02-JAN-00:01 | 17.17 | 16.96 | 0.232776E+09 | 301.94 | 06-JAN-11:50 | 16.00 | 9.31 |
February | 0.209198E+10 | 18421.36 | 27-FEB-00:02 | 17.77 | 17.47 | 0.220196E+09 | 301.93 | 14-FEB-13:20 | 18.50 | 13.50 |
March | 0.314768E+10 | 17823.61 | 06-MAR-00:02 | 19.87 | 18.29 | 0.260102E+09 | 304.43 | 13-MAR-13:30 | 20.25 | 10.33 |
April | 0.617488E+10 | 19809.21 | 17-APR-00:02 | 13.92 | 11.56 | 0.248374E+09 | 301.60 | 17-APR-09:09 | 18.67 | 12.09 |
May | 0.102797E+11 | 17414.01 | 06-MAY-19:03 | 25.40 | 20.61 | 0.258899E+09 | 301.59 | 06-MAY-07:10 | 25.28 | 22.39 |
June | 0.109724E+11 | 18774.07 | 12-JUN-00:01 | 25.50 | 21.64 | 0.258909E+09 | 301.61 | 12-JUN-15:09 | 32.88 | 21.47 |
July | 0.109053E+11 | 17390.41 | 24-JUL-00:01 | 28.30 | 26.22 | 0.248969E+09 | 301.59 | 15-JUL-07:10 | 26.38 | 24.59 |
August | 0.117813E+11 | 17814.49 | 03-AUG-21:03 | 24.42 | 19.04 | 0.268877E+09 | 301.60 | 30-AUG-15:50 | 35.70 | 23.55 |
September | 0.995575E+10 | 17262.91 | 02-SEP-17:08 | 23.02 | 21.56 | 0.248954E+09 | 301.59 | 02-SEP-07:10 | 25.97 | 24.30 |
October | 0.894443E+10 | 20177.14 | 02-OCT-00:01 | 19.95 | 15.67 | 0.248850E+09 | 301.61 | 17-OCT-12:50 | 21.83 | 15.26 |
November | 0.442749E+10 | 18789.96 | 06-NOV-00:01 | 20.95 | 18.49 | 0.237443E+09 | 301.60 | 17-NOV-16:00 | 22.20 | 14.69 |
December | 0.270076E+10 | 16798.82 | 11-DEC-00:01 | 21.17 | 19.25 | 0.238405E+09 | 301.59 | 05-DEC-16:10 | 17.83 | 12.11 |
Annual Sum or Average | 0.827673E+11 | 0.297075E+10 | ||||||||
Minimum of Months | 0.138569E+10 | 16798.82 | 13.92 | 11.56 | 0.220196E+09 | 301.59 | 16.00 | 9.31 | ||
Maximum of Months | 0.117813E+11 | 20177.14 | 28.30 | 26.22 | 0.268877E+09 | 304.43 | 35.70 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985644E+09 | 26521.95 | 01-JAN-14:15 | 25.67 | 18.11 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.182040E+10 | 23125.98 | 26-FEB-14:35 | 26.27 | 19.98 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.267480E+10 | 26040.31 | 26-MAR-13:25 | 29.70 | 20.03 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.948291E+10 | 52493.76 | 27-APR-17:08 | 29.22 | 21.95 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.230225E+11 | 54659.46 | 04-MAY-17:06 | 31.42 | 21.63 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.271173E+11 | 55119.75 | 12-JUN-17:05 | 32.02 | 21.32 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.280116E+11 | 52991.10 | 12-JUL-17:08 | 23.90 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.276598E+11 | 51442.38 | 30-AUG-17:06 | 34.67 | 23.09 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.211270E+11 | 52256.78 | 22-SEP-17:06 | 30.32 | 21.05 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.175293E+11 | 55569.70 | 01-OCT-12:23 | 26.60 | 18.42 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.408090E+10 | 38232.99 | 02-NOV-17:10 | 27.35 | 23.65 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.247109E+10 | 20717.48 | 10-DEC-13:50 | 27.00 | 20.21 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.165983E+12 | 0.00 | ||||||||
Minimum of Months | 0.985644E+09 | 20717.48 | 23.90 | 18.11 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.280116E+11 | 55569.70 | 34.67 | 23.65 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680321E+09 | 27832.91 | 11-JAN-06:01 | 8.00 |
February | 0.386868E+09 | 27899.35 | 07-FEB-06:01 | 8.62 |
March | 0.287695E+09 | 27650.56 | 13-MAR-05:01 | 6.68 |
April | 20002832.34 | 2114.72 | 11-APR-06:30 | 10.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 6464449.46 | 708.75 | 31-OCT-06:10 | 18.00 |
November | 42310771.19 | 4010.33 | 15-NOV-07:10 | 7.80 |
December | 0.382349E+09 | 27436.57 | 22-DEC-06:02 | 10.00 |
Annual Sum or Average | 0.180601E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.68 | |
Maximum of Months | 0.680321E+09 | 27899.35 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613912E+09 | 21107.69 | 10-JAN-03:40 | 2.00 |
February | 0.623654E+09 | 56912.71 | 05-FEB-07:43 | -3.4 |
March | 0.330441E+09 | 14927.63 | 12-MAR-06:55 | 6.60 |
April | 44396089.23 | 1232.25 | 03-APR-10:35 | 22.73 |
May | 3006104.88 | 2007.36 | 01-MAY-06:05 | 25.18 |
June | 5170544.46 | 2378.08 | 24-JUN-06:05 | 25.28 |
July | 217748.63 | 362.91 | 15-JUL-06:10 | 24.27 |
August | 2294132.21 | 1365.14 | 16-AUG-06:10 | 23.92 |
September | 3549096.68 | 1386.82 | 14-SEP-06:10 | 24.50 |
October | 35179183.06 | 1250.33 | 19-OCT-08:65 | 23.33 |
November | 0.255088E+09 | 2265.52 | 24-NOV-16:05 | 23.43 |
December | 0.366867E+09 | 26820.60 | 21-DEC-06:33 | 0.33 |
Annual Sum or Average | 0.228378E+10 | |||
Minimum of Months | 217748.63 | 362.91 | -3.4 | |
Maximum of Months | 0.623654E+09 | 56912.71 | 25.28 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13463890.28 | 0.156541E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22710982.73 | 0.105106E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59897491.29 | 0.119652E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190293E+09 | 0.458383E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646633E+09 | 26854522.58 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757411E+09 | 22418195.74 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695513E+09 | 15512072.69 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778845E+09 | 24464104.87 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412175E+09 | 58335938.47 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432216E+09 | 0.327404E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100415E+09 | 0.747012E+09 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46300559.00 | 0.130621E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.415587E+10 | 0.679958E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13463890.28 | 15512072.69 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778845E+09 | 0.156541E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12238750.40 | 0.809579E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12508132.61 | 0.608087E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27544950.79 | 0.758050E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204698E+09 | 0.406061E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106309E+10 | 0.124509E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123110E+10 | 0.807029E+09 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148478E+10 | 0.495843E+09 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158252E+10 | 0.119565E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103622E+10 | 0.182992E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890158E+09 | 0.405656E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47258209.41 | 0.521164E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26655754.54 | 0.741013E+10 |
Annual Sum or Average | 0.136656E+12 | 0.761876E+10 | 0.480696E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12238750.40 | 0.495843E+09 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158252E+10 | 0.809579E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115446E+09 | 0.246755E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60995101.72 | 0.190407E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9750456.28 | 0.271103E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14046.02 | 0.178017E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096014.47 | 0.106241E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26085.24 | 0.724593E+10 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1130553.61 | 0.657040E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5878571.63 | 0.102224E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30784760.09 | 0.127003E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210999E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34620714.75 | 0.181525E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45707451.30 | 0.237727E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.305449E+09 | 0.199016E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657040E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115446E+09 | 0.271103E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 736.46 | 02-JAN-13:00 | 8344.88 | 05-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.71 | 02-FEB-13:00 | 7818.22 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.13 | 30-MAR-12:00 | 8483.52 | 09-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3032.07 | 28-APR-16:10 | 4997.55 | 11-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3332.41 | 10-MAY-16:10 | 678.64 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3439.38 | 28-JUN-16:10 | 975.79 | 07-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.28 | 21-JUL-16:10 | 368.90 | 13-JUL-11:04 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.82 | 03-AUG-16:10 | 803.09 | 16-AUG-17:00 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.51 | 06-SEP-16:10 | 1571.88 | 07-SEP-16:54 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257.26 | 05-OCT-17:00 | 3801.33 | 27-OCT-06:05 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.53 | 02-NOV-12:00 | 5303.14 | 15-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.73 | 13-DEC-13:00 | 8536.55 | 20-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 736.46 | 368.90 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.82 | 8536.55 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.09 | 16-JAN-15:00 | 14638.71 | 03-JAN-09:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.94 | 20-FEB-15:00 | 17980.48 | 16-FEB-18:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.98 | 27-MAR-15:10 | 15413.09 | 09-MAR-09:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.60 | 28-APR-15:10 | 11900.66 | 15-APR-17:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.75 | 18-MAY-16:40 | 3585.41 | 05-MAY-06:10 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.82 | 08-JUN-15:10 | 4465.73 | 06-JUN-20:53 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.75 | 06-JUL-15:10 | 2448.21 | 30-JUL-11:10 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.65 | 03-AUG-16:40 | 4702.83 | 25-AUG-24:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7366.38 | 09-SEP-17:00 | 4787.89 | 19-SEP-18:53 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6847.51 | 09-OCT-14:00 | 10419.71 | 27-OCT-08:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.63 | 02-NOV-15:10 | 10811.52 | 09-NOV-07:03 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.09 | 13-DEC-16:10 | 12320.98 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.09 | 2448.21 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.65 | 17980.48 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.48 | 16-JAN-15:00 | 46909.13 | 03-JAN-09:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4246.61 | 20-FEB-15:00 | 54510.73 | 04-FEB-11:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.34 | 26-MAR-13:53 | 51065.89 | 09-MAR-09:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 | 15-APR-11:55 | 39794.85 | 01-APR-16:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.63 | 27-MAY-13:43 | 25859.03 | 26-MAY-15:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.75 | 25-JUN-12:52 | 21939.60 | 01-JUN-12:52 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.17 | 02-JUL-10:53 | 26666.95 | 31-JUL-11:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.23 | 20-AUG-13:53 | 18980.14 | 25-AUG-24:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.23 | 09-SEP-17:00 | 23453.95 | 12-SEP-20:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 41145.15 | 27-OCT-11:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3765.37 | 28-NOV-13:10 | 33588.75 | 09-NOV-08:10 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2603.90 | 31-DEC-11:00 | 42121.75 | 19-DEC-12:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18980.14 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4246.61 | 54510.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17802.81 | 02-JAN-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.37 |
February | 18421.36 | 27-FEB-00:02 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17823.61 | 06-MAR-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
April | 19809.21 | 17-APR-00:02 | 0.00 | 2294.78 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.53 |
May | 17414.01 | 06-MAY-19:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.40 | 0.00 |
June | 18774.07 | 12-JUN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.20 |
July | 17390.41 | 24-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
August | 17814.49 | 03-AUG-21:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 | 0.00 |
September | 17262.91 | 02-SEP-17:08 | 0.00 | 1835.82 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 |
October | 20177.14 | 02-OCT-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.33 |
November | 18789.96 | 06-NOV-00:01 | 0.00 | 4130.60 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 |
December | 16798.82 | 11-DEC-00:01 | 0.00 | 3212.69 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16798.82 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20177.14 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 34.40 | 255.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26521.95 | 01-JAN-14:15 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.33 |
February | 23125.98 | 26-FEB-14:35 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.63 |
March | 26040.31 | 26-MAR-13:25 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.35 | 0.00 |
April | 52493.76 | 27-APR-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.87 | 0.00 |
May | 54659.46 | 04-MAY-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 | 0.00 |
June | 55119.75 | 12-JUN-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.68 | 0.00 |
July | 52991.10 | 12-JUL-17:08 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 |
August | 51442.38 | 30-AUG-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.92 | 0.00 |
September | 52256.78 | 22-SEP-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.05 | 0.00 |
October | 55569.70 | 01-OCT-12:23 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.82 |
November | 38232.99 | 02-NOV-17:10 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 | 0.00 |
December | 20717.48 | 10-DEC-13:50 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.28 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20717.48 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55569.70 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.05 | 264.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9312.73 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3877.82 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6965.53 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7958.35 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.19 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2897.75 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2781.16 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.95 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.49 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 8279.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8971.73 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.61 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8482.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.49 | |
Maximum of Months | 0.00 | 0.00 | 22077.85 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9312.73 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.708522E+11 | 59143.91 | 19-JAN-15:09 | 0.927526E+10 | 32090.51 | 10-JAN-07:19 |
February | 0.652353E+11 | 62032.58 | 27-FEB-15:30 | 0.814129E+10 | 30674.25 | 05-FEB-07:49 |
March | 0.749385E+11 | 64415.15 | 30-MAR-12:09 | 0.846698E+10 | 17649.32 | 13-MAR-06:10 |
April | 0.751220E+11 | 71755.22 | 28-APR-14:00 | 0.778031E+10 | 6706.28 | 11-APR-06:30 |
May | 0.890112E+11 | 72448.02 | 25-MAY-13:00 | 0.803520E+10 | 3000.00 | 01-MAY-00:10 |
June | 0.908204E+11 | 74380.94 | 28-JUN-14:00 | 0.777600E+10 | 3000.00 | 01-JUN-00:10 |
July | 0.919021E+11 | 75142.20 | 19-JUL-13:09 | 0.803520E+10 | 3000.00 | 01-JUL-00:10 |
August | 0.953525E+11 | 75680.34 | 03-AUG-14:00 | 0.803520E+10 | 3000.00 | 01-AUG-00:10 |
September | 0.864291E+11 | 73271.19 | 09-SEP-14:50 | 0.777600E+10 | 3000.00 | 01-SEP-00:10 |
October | 0.842709E+11 | 74045.00 | 06-OCT-12:09 | 0.803520E+10 | 3000.00 | 01-OCT-00:10 |
November | 0.714381E+11 | 68415.37 | 02-NOV-14:30 | 0.781984E+10 | 9566.63 | 15-NOV-07:19 |
December | 0.725413E+11 | 66314.90 | 15-DEC-13:00 | 0.870693E+10 | 33205.20 | 21-DEC-07:10 |
Annual Sum or Average | 0.967913E+12 | 0.978834E+11 | ||||
Minimum of Months | 0.652353E+11 | 59143.91 | 0.777600E+10 | 3000.00 | ||
Maximum of Months | 0.953525E+11 | 75680.34 | 0.927526E+10 | 33205.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.118613E+11 | 0.115358E+11 | 0.00 | 0.440748E+10 | 0.00 | 0.00 | 0.821821E+09 | 0.00 | 0.00 | 0.00 | 0.212248E+10 | 0.00 |
February | 0.366966E+11 | 0.102443E+11 | 0.105871E+11 | 0.00 | 0.406985E+10 | 0.00 | 0.00 | 0.171630E+10 | 0.00 | 0.00 | 0.00 | 0.192114E+10 | 0.00 |
March | 0.423649E+11 | 0.106356E+11 | 0.123357E+11 | 0.00 | 0.479833E+10 | 0.00 | 0.00 | 0.266866E+10 | 0.00 | 0.00 | 0.00 | 0.213537E+10 | 0.00 |
April | 0.397216E+11 | 0.960783E+10 | 0.114862E+11 | 0.00 | 0.518364E+10 | 0.00 | 0.00 | 0.712758E+10 | 0.00 | 0.00 | 0.00 | 0.199510E+10 | 0.00 |
May | 0.412341E+11 | 0.931083E+10 | 0.119357E+11 | 0.00 | 0.765041E+10 | 0.00 | 0.00 | 0.168608E+11 | 0.00 | 0.00 | 0.00 | 0.201935E+10 | 0.00 |
June | 0.408524E+11 | 0.867439E+10 | 0.118862E+11 | 0.00 | 0.838152E+10 | 0.00 | 0.00 | 0.190916E+11 | 0.00 | 0.00 | 0.00 | 0.193430E+10 | 0.00 |
July | 0.401034E+11 | 0.914111E+10 | 0.115358E+11 | 0.00 | 0.858017E+10 | 0.00 | 0.00 | 0.205982E+11 | 0.00 | 0.00 | 0.00 | 0.194355E+10 | 0.00 |
August | 0.423649E+11 | 0.964083E+10 | 0.123357E+11 | 0.00 | 0.846433E+10 | 0.00 | 0.00 | 0.205574E+11 | 0.00 | 0.00 | 0.00 | 0.198938E+10 | 0.00 |
September | 0.397216E+11 | 0.100038E+11 | 0.114862E+11 | 0.00 | 0.705426E+10 | 0.00 | 0.00 | 0.162335E+11 | 0.00 | 0.00 | 0.00 | 0.192967E+10 | 0.00 |
October | 0.401034E+11 | 0.110551E+11 | 0.115358E+11 | 0.00 | 0.640325E+10 | 0.00 | 0.00 | 0.131551E+11 | 0.00 | 0.00 | 0.00 | 0.201824E+10 | 0.00 |
November | 0.385909E+11 | 0.112956E+11 | 0.110862E+11 | 0.00 | 0.445787E+10 | 0.00 | 0.00 | 0.401489E+10 | 0.00 | 0.00 | 0.00 | 0.199269E+10 | 0.00 |
December | 0.401034E+11 | 0.120169E+11 | 0.115358E+11 | 0.00 | 0.445085E+10 | 0.00 | 0.00 | 0.233221E+10 | 0.00 | 0.00 | 0.00 | 0.210223E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123488E+12 | 0.139282E+12 | 0.739020E+11 | 0.00 | 0.125178E+12 | 0.241035E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.867439E+10 | 0.105871E+11 | 0.00 | 0.406985E+10 | 0.00 | 0.00 | 0.821821E+09 | 0.00 | 0.00 | 0.00 | 0.192114E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.120169E+11 | 0.123357E+11 | 0.00 | 0.858017E+10 | 0.00 | 0.00 | 0.205982E+11 | 0.00 | 0.00 | 0.00 | 0.213537E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.927526E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.814129E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.846698E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.778031E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.781984E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.870693E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978834E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.927526E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4422.76 | 02-JAN-11:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5191.19 | 27-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 6728.05 | 30-MAR-12:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6728.05 | 14-APR-13:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6728.05 | 01-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6728.05 | 01-JUN-10:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6728.05 | 01-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6728.05 | 01-AUG-11:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6728.05 | 01-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6728.05 | 02-OCT-12:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6728.05 | 02-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 6728.05 | 15-DEC-12:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 4422.76 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 6728.05 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7249.05 | 19-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1781.05 | 23-JAN-12:30 | 0.00 |
February | 9562.41 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1780.23 | 06-FEB-12:00 | 0.00 |
March | 10656.19 | 28-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1772.39 | 02-MAR-12:00 | 0.00 |
April | 18557.51 | 28-APR-15:39 | 0.00 | 0.00 | 0.00 | 1757.07 | 01-APR-11:20 | 0.00 |
May | 18887.10 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.54 | 01-MAY-11:39 | 0.00 |
June | 21242.72 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1721.05 | 01-JUN-11:39 | 0.00 |
July | 22027.68 | 18-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1710.29 | 01-JUL-11:30 | 0.00 |
August | 23779.20 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1714.53 | 31-AUG-11:50 | 0.00 |
September | 22720.42 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1728.70 | 30-SEP-11:39 | 0.00 |
October | 20828.99 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1747.63 | 31-OCT-11:20 | 0.00 |
November | 14235.38 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1765.10 | 30-NOV-12:09 | 0.00 |
December | 12115.15 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1777.76 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7249.05 | 0.00 | 0.00 | 0.00 | 1710.29 | 0.00 | ||
Maximum of Months | 23779.20 | 0.00 | 0.00 | 0.00 | 1781.05 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 59143.91 | 19-JAN-15:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4422.76 | 0.00 | 0.00 | 7242.72 | 0.00 |
February | 62032.58 | 27-FEB-15:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 5191.19 | 0.00 | 0.00 | 9368.29 | 0.00 |
March | 64415.15 | 30-MAR-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 10227.11 | 0.00 |
April | 71755.22 | 28-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 17582.22 | 0.00 |
May | 72448.02 | 25-MAY-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 18313.14 | 0.00 |
June | 74380.94 | 28-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 20233.08 | 0.00 |
July | 75142.20 | 19-JUL-13:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 21019.00 | 0.00 |
August | 75680.34 | 03-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 21535.15 | 0.00 |
September | 73271.19 | 09-SEP-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 19117.37 | 0.00 |
October | 74045.00 | 06-OCT-12:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 19879.21 | 0.00 |
November | 68415.37 | 02-NOV-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 14235.38 | 0.00 |
December | 66314.90 | 15-DEC-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 12115.15 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 59143.91 | 35620.03 | 10112.62 | 0.00 | 0.00 | 4422.76 | 0.00 | 0.00 | 7242.72 | 0.00 | |
Maximum of Months | 75680.34 | 35620.03 | 10112.62 | 0.00 | 0.00 | 6728.05 | 0.00 | 0.00 | 21535.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 32090.51 | 10-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 30674.25 | 05-FEB-07:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 17649.32 | 13-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6706.28 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3000.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3000.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 9566.63 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 33205.20 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 33205.20 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.36 | 1.50 | 20.36 | 1.50 | 24.54 | 0.00 | 0.00 |
February | 0.83 | 20.32 | 0.83 | 20.32 | 2.50 | 24.52 | 0.33 | 24.52 |
March | 0.50 | 20.38 | 0.50 | 20.38 | 5.50 | 24.51 | 0.17 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.58 | 0.33 | 24.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 24.62 | 1.83 | 24.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 24.67 | 3.83 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 24.78 | 4.67 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 24.68 | 4.50 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 65.33 | 24.72 | 3.17 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 24.64 | 2.17 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.51 | 0.00 | 0.00 |
December | 0.50 | 20.36 | 0.50 | 20.36 | 1.33 | 24.51 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 20.35 | 3.33 | 20.35 | 444.67 | 24.68 | 21.00 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.51 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.38 | 1.50 | 20.38 | 82.33 | 24.78 | 4.67 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 15.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 0.00 |
February | 0.83 | 14.90 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.45 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.59 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.60 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.58 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.67 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.61 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 14.92 | 0.00 | 152.67 | 27.60 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 15.00 | 0.00 | 0.00 | 33.17 | 27.67 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.33 | 22.67 | 98.67 | 22.12 | 69.00 | 21.36 |
February | 177.00 | 22.88 | 94.83 | 22.93 | 35.33 | 21.30 |
March | 183.83 | 22.94 | 116.17 | 23.18 | 30.67 | 21.17 |
April | 45.83 | 23.53 | 192.67 | 23.90 | 1.00 | 23.90 |
May | 11.67 | 23.90 | 311.50 | 23.91 | 11.67 | 23.90 |
June | 9.00 | 23.90 | 311.17 | 23.91 | 9.00 | 23.90 |
July | 17.17 | 23.90 | 299.83 | 23.91 | 17.17 | 23.90 |
August | 19.00 | 23.90 | 324.00 | 23.91 | 19.00 | 23.90 |
September | 12.50 | 23.90 | 300.00 | 23.91 | 12.50 | 23.90 |
October | 29.83 | 23.82 | 252.67 | 23.91 | 13.33 | 23.90 |
November | 98.50 | 23.40 | 111.67 | 23.90 | 5.33 | 23.90 |
December | 199.17 | 22.84 | 119.50 | 23.13 | 42.50 | 21.73 |
Annual Sum or Average | 1052.83 | 23.00 | 2532.67 | 23.73 | 266.50 | 22.24 |
Minimum of Months | 9.00 | 22.67 | 94.83 | 22.12 | 1.00 | 21.17 |
Maximum of Months | 249.33 | 23.90 | 324.00 | 23.91 | 69.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.217208E+10 | 0.580003E+09 | 142.29 | 0.162737E+10 | 0.544710E+09 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 | 26326.82 | 02-JAN-00:01 | 18665.43 | 02-JAN-00:01 | 7853.90 | 02-JAN-00:03 | 6116.52 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 |
February | 0.346459E+10 | 0.924747E+09 | 182.64 | 0.258263E+10 | 0.881959E+09 | 0.00 | 1.00 | 27-FEB-00:02 | 0.00 | 01-FEB-00:10 | 25403.91 | 27-FEB-00:02 | 19652.07 | 27-FEB-00:02 | 6022.72 | 28-FEB-18:10 | 5948.54 | 27-FEB-00:02 | 0.00 | 01-FEB-00:10 |
March | 0.508859E+10 | 0.136304E+10 | 250.35 | 0.390729E+10 | 0.118129E+10 | 0.00 | 1.00 | 06-MAR-00:02 | 0.00 | 01-MAR-00:05 | 26639.08 | 27-MAR-00:01 | 19613.68 | 06-MAR-00:02 | 8318.15 | 27-MAR-00:03 | 6170.46 | 27-MAR-00:01 | 0.00 | 01-MAR-00:05 |
April | 0.973783E+10 | 0.264869E+10 | 386.68 | 0.763898E+10 | 0.209885E+10 | 0.00 | 1.00 | 14-APR-17:08 | 0.00 | 01-APR-00:05 | 27611.92 | 24-APR-00:01 | 20883.69 | 17-APR-00:02 | 9866.27 | 24-APR-00:05 | 6474.41 | 28-APR-17:08 | 0.00 | 01-APR-00:05 |
May | 0.178202E+11 | 0.492660E+10 | 527.10 | 0.129240E+11 | 0.489627E+10 | 0.00 | 1.00 | 01-MAY-00:01 | 0.00 | 01-MAY-00:06 | 29780.49 | 22-MAY-00:01 | 19871.91 | 03-MAY-20:23 | 14252.72 | 22-MAY-00:03 | 6756.86 | 22-MAY-00:01 | 0.00 | 01-MAY-00:01 |
June | 0.190531E+11 | 0.531743E+10 | 533.50 | 0.138303E+11 | 0.522283E+10 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:15 | 29194.55 | 05-JUN-00:01 | 20285.66 | 12-JUN-00:01 | 12721.43 | 05-JUN-00:07 | 6721.85 | 05-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.197664E+11 | 0.547169E+10 | 519.05 | 0.137164E+11 | 0.605003E+10 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:13 | 30354.43 | 31-JUL-00:01 | 19511.53 | 18-JUL-23:43 | 14866.09 | 31-JUL-00:04 | 6869.19 | 03-JUL-00:01 | 0.00 | 01-JUL-00:05 |
August | 0.210347E+11 | 0.579779E+10 | 558.02 | 0.147229E+11 | 0.631189E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:13 | 29959.31 | 14-AUG-00:01 | 20097.12 | 30-AUG-23:03 | 14445.04 | 14-AUG-00:04 | 6801.16 | 14-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.177421E+11 | 0.479399E+10 | 517.22 | 0.123075E+11 | 0.543460E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:13 | 30644.26 | 05-SEP-00:01 | 19817.53 | 22-SEP-20:23 | 16098.89 | 05-SEP-00:04 | 7274.31 | 10-SEP-12:52 | 0.00 | 01-SEP-00:10 |
October | 0.150114E+11 | 0.409039E+10 | 480.07 | 0.109777E+11 | 0.403368E+10 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:03 | 29680.84 | 23-OCT-00:01 | 21146.21 | 02-OCT-00:01 | 13572.21 | 23-OCT-00:12 | 6710.17 | 23-OCT-00:01 | 0.00 | 01-OCT-00:03 |
November | 0.711492E+10 | 0.191073E+10 | 310.46 | 0.548002E+10 | 0.163490E+10 | 0.00 | 1.00 | 02-NOV-17:08 | 0.00 | 01-NOV-00:05 | 26876.15 | 03-NOV-17:10 | 19929.96 | 06-NOV-00:01 | 10873.84 | 03-NOV-17:10 | 6391.96 | 03-NOV-17:10 | 0.00 | 01-NOV-00:05 |
December | 0.437831E+10 | 0.117272E+10 | 210.28 | 0.327853E+10 | 0.109978E+10 | 0.00 | 1.00 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 | 26748.72 | 11-DEC-00:01 | 18227.55 | 11-DEC-00:01 | 8686.83 | 11-DEC-00:03 | 6189.06 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.142384E+12 | 0.389978E+11 | 4617.66 | 0.102994E+12 | 0.393908E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.217208E+10 | 0.580003E+09 | 142.29 | 0.162737E+10 | 0.544710E+09 | 0.00 | 1.00 | 0.00 | 25403.91 | 18227.55 | 6022.72 | 5948.54 | 0.00 | |||||||
Maximum of Months | 0.210347E+11 | 0.579779E+10 | 558.02 | 0.147229E+11 | 0.631189E+10 | 0.00 | 1.00 | 0.00 | 30644.26 | 21146.21 | 16098.89 | 7274.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.838329E+09 | 0.241817E+09 | 25.92 | 0.566687E+09 | 0.271642E+09 | 0.00 | 0.56 | 01-JAN-14:15 | 0.00 | 01-JAN-00:10 | 35275.09 | 01-JAN-14:15 | 28710.48 | 01-JAN-14:15 | 6778.25 | 01-JAN-13:00 | 10349.85 | 01-JAN-14:15 | 0.00 | 01-JAN-00:10 |
February | 0.277057E+10 | 0.791557E+09 | 59.75 | 0.191089E+10 | 0.859683E+09 | 0.00 | 0.52 | 26-FEB-14:35 | 0.00 | 01-FEB-00:10 | 32433.32 | 26-FEB-14:35 | 25180.18 | 26-FEB-14:35 | 7253.14 | 26-FEB-14:35 | 9688.15 | 26-FEB-14:35 | 0.00 | 01-FEB-00:10 |
March | 0.455058E+10 | 0.130562E+10 | 99.83 | 0.310972E+10 | 0.144086E+10 | 0.00 | 0.60 | 26-MAR-13:25 | 0.00 | 01-MAR-00:05 | 38515.71 | 26-MAR-13:25 | 29366.07 | 26-MAR-13:25 | 9523.38 | 07-MAR-11:30 | 11819.61 | 26-MAR-13:25 | 0.00 | 01-MAR-00:05 |
April | 0.154045E+11 | 0.447889E+10 | 231.69 | 0.114763E+11 | 0.392818E+10 | 0.00 | 1.00 | 23-APR-11:03 | 0.00 | 01-APR-00:05 | 80399.63 | 28-APR-17:42 | 58599.76 | 27-APR-17:08 | 27893.17 | 29-APR-17:08 | 20575.40 | 28-APR-17:08 | 0.00 | 01-APR-00:05 |
May | 0.404206E+11 | 0.119342E+11 | 416.55 | 0.280553E+11 | 0.123652E+11 | 0.00 | 1.00 | 02-MAY-17:06 | 0.00 | 01-MAY-00:01 | 83757.25 | 28-MAY-09:23 | 60961.96 | 04-MAY-17:06 | 39037.93 | 28-MAY-09:23 | 21417.03 | 28-MAY-09:23 | 0.00 | 01-MAY-00:01 |
June | 0.463684E+11 | 0.137742E+11 | 458.61 | 0.327240E+11 | 0.136444E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 84209.70 | 05-JUN-00:08 | 61266.44 | 11-JUN-15:02 | 39061.91 | 05-JUN-00:08 | 21160.21 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.514172E+11 | 0.151265E+11 | 497.85 | 0.337254E+11 | 0.176917E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 87779.55 | 31-JUL-00:01 | 56738.34 | 12-JUL-17:08 | 45222.57 | 31-JUL-00:01 | 21616.73 | 02-JUL-11:03 | 0.00 | 01-JUL-00:05 |
August | 0.503900E+11 | 0.147596E+11 | 479.33 | 0.333618E+11 | 0.170281E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 85319.32 | 14-AUG-00:07 | 58673.69 | 30-AUG-17:06 | 41051.43 | 14-AUG-00:07 | 21742.22 | 20-AUG-13:53 | 0.00 | 01-AUG-00:10 |
September | 0.396550E+11 | 0.114395E+11 | 400.47 | 0.255034E+11 | 0.141516E+11 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:10 | 85235.05 | 04-SEP-10:13 | 58050.09 | 22-SEP-17:06 | 40961.28 | 17-SEP-09:53 | 22216.06 | 10-SEP-13:43 | 0.00 | 01-SEP-00:10 |
October | 0.313424E+11 | 0.906472E+10 | 332.47 | 0.210112E+11 | 0.103311E+11 | 0.00 | 1.00 | 01-OCT-12:23 | 0.00 | 01-OCT-00:03 | 85969.93 | 08-OCT-09:53 | 60585.26 | 01-OCT-12:23 | 42948.35 | 08-OCT-09:53 | 21871.64 | 08-OCT-13:53 | 0.00 | 01-OCT-00:03 |
November | 0.732438E+10 | 0.210417E+10 | 139.24 | 0.505406E+10 | 0.227032E+10 | 0.00 | 0.86 | 02-NOV-17:10 | 0.00 | 01-NOV-00:05 | 64623.87 | 02-NOV-17:10 | 42502.79 | 02-NOV-17:10 | 22121.08 | 02-NOV-17:10 | 17290.16 | 02-NOV-17:10 | 0.00 | 01-NOV-00:05 |
December | 0.404245E+10 | 0.115949E+10 | 75.67 | 0.269352E+10 | 0.134893E+10 | 0.00 | 0.51 | 10-DEC-13:50 | 0.00 | 01-DEC-00:10 | 32894.65 | 10-DEC-13:50 | 23204.78 | 10-DEC-13:50 | 10572.71 | 15-DEC-12:00 | 9827.68 | 10-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.294524E+12 | 0.861802E+11 | 3217.37 | 0.199192E+12 | 0.953318E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.838329E+09 | 0.241817E+09 | 25.92 | 0.566687E+09 | 0.271642E+09 | 0.00 | 0.51 | 0.00 | 32433.32 | 23204.78 | 6778.25 | 9688.15 | 0.00 | |||||||
Maximum of Months | 0.514172E+11 | 0.151265E+11 | 497.85 | 0.337254E+11 | 0.176917E+11 | 0.00 | 1.00 | 0.00 | 87779.55 | 61266.44 | 45222.57 | 22216.06 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.57 | 28.45 | 24.12 | 101.91 | 154.80 | 8.17 | 0.00 | 744.00 |
February | 59.40 | 30.04 | 29.35 | 120.03 | 133.53 | 4.17 | 0.00 | 672.00 |
March | 58.48 | 25.80 | 32.68 | 124.75 | 121.70 | 1.50 | 0.00 | 744.00 |
April | 72.33 | 33.03 | 39.31 | 179.34 | 81.81 | 0.00 | 0.00 | 720.00 |
May | 60.54 | 19.69 | 40.85 | 197.16 | 25.23 | 0.00 | 0.00 | 744.00 |
June | 67.28 | 23.62 | 43.66 | 227.05 | 22.02 | 0.00 | 0.00 | 720.00 |
July | 61.44 | 17.09 | 44.35 | 201.96 | 15.86 | 0.00 | 0.00 | 744.00 |
August | 61.97 | 18.86 | 43.11 | 207.37 | 22.12 | 0.00 | 0.00 | 744.00 |
September | 57.07 | 19.52 | 37.55 | 175.53 | 32.53 | 0.00 | 0.00 | 720.00 |
October | 58.32 | 25.10 | 33.22 | 171.01 | 55.90 | 0.00 | 0.00 | 744.00 |
November | 50.31 | 25.36 | 24.95 | 112.44 | 116.27 | 0.00 | 0.00 | 720.00 |
December | 48.48 | 25.89 | 22.59 | 100.12 | 141.41 | 5.50 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 24.31 | 34.67 | 160.07 | 76.62 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 48.48 | 17.09 | 22.59 | 100.12 | 15.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.33 | 33.03 | 44.35 | 227.05 | 154.80 | 8.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.57 | 28.45 | 24.12 | 101.91 | 154.80 | 8.17 | 0.00 | 744.00 |
February | 59.40 | 30.04 | 29.35 | 120.03 | 133.53 | 4.17 | 0.00 | 672.00 |
March | 58.48 | 25.80 | 32.68 | 124.75 | 121.70 | 1.50 | 0.00 | 744.00 |
April | 72.33 | 33.03 | 39.31 | 179.34 | 81.81 | 0.00 | 0.00 | 720.00 |
May | 60.54 | 19.69 | 40.85 | 197.16 | 25.23 | 0.00 | 0.00 | 744.00 |
June | 67.28 | 23.62 | 43.66 | 227.05 | 22.02 | 0.00 | 0.00 | 720.00 |
July | 61.44 | 17.09 | 44.35 | 201.96 | 15.86 | 0.00 | 0.00 | 744.00 |
August | 61.97 | 18.86 | 43.11 | 207.37 | 22.12 | 0.00 | 0.00 | 744.00 |
September | 57.07 | 19.52 | 37.55 | 175.53 | 32.53 | 0.00 | 0.00 | 720.00 |
October | 58.32 | 25.10 | 33.22 | 171.01 | 55.90 | 0.00 | 0.00 | 744.00 |
November | 50.31 | 25.36 | 24.95 | 112.44 | 116.27 | 0.00 | 0.00 | 720.00 |
December | 48.48 | 25.89 | 22.59 | 100.12 | 141.41 | 5.50 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 24.31 | 34.67 | 160.07 | 76.62 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 48.48 | 17.09 | 22.59 | 100.12 | 15.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.33 | 33.03 | 44.35 | 227.05 | 154.80 | 8.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.19 | 0.00 | 11.19 | 10.96 | 99.41 | 8.17 | 0.00 | 744.00 |
February | 13.20 | 0.00 | 13.20 | 14.97 | 84.40 | 4.17 | 0.00 | 672.00 |
March | 15.32 | 0.00 | 15.32 | 21.78 | 75.20 | 1.50 | 0.00 | 744.00 |
April | 18.19 | 0.17 | 18.02 | 35.25 | 49.49 | 0.00 | 0.00 | 720.00 |
May | 20.82 | 1.08 | 19.74 | 68.65 | 13.92 | 0.00 | 0.00 | 744.00 |
June | 23.78 | 2.10 | 21.67 | 83.51 | 12.18 | 0.00 | 0.00 | 720.00 |
July | 22.90 | 1.16 | 21.74 | 78.54 | 8.90 | 0.00 | 0.00 | 744.00 |
August | 20.41 | 0.31 | 20.10 | 71.78 | 12.35 | 0.00 | 0.00 | 744.00 |
September | 17.49 | 0.01 | 17.48 | 53.61 | 19.04 | 0.00 | 0.00 | 720.00 |
October | 15.19 | 0.00 | 15.19 | 41.57 | 34.22 | 0.00 | 0.00 | 744.00 |
November | 11.53 | 0.00 | 11.53 | 15.51 | 72.58 | 0.00 | 0.00 | 720.00 |
December | 10.40 | 0.00 | 10.40 | 11.23 | 90.23 | 5.50 | 0.00 | 744.00 |
Annual Sum or Average | 16.72 | 0.40 | 16.31 | 42.45 | 47.46 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 10.40 | 0.00 | 10.40 | 10.96 | 8.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 23.78 | 2.10 | 21.74 | 83.51 | 99.41 | 8.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.19 | 0.00 | 11.19 | 10.95 | 99.41 | 8.17 | 0.00 | 744.00 |
February | 13.20 | 0.00 | 13.20 | 14.97 | 84.40 | 4.17 | 0.00 | 672.00 |
March | 15.32 | 0.00 | 15.32 | 21.78 | 75.20 | 1.50 | 0.00 | 744.00 |
April | 18.19 | 0.17 | 18.02 | 35.25 | 49.49 | 0.00 | 0.00 | 720.00 |
May | 20.82 | 1.08 | 19.74 | 68.65 | 13.92 | 0.00 | 0.00 | 744.00 |
June | 23.77 | 2.10 | 21.67 | 83.51 | 12.18 | 0.00 | 0.00 | 720.00 |
July | 22.90 | 1.16 | 21.74 | 78.54 | 8.90 | 0.00 | 0.00 | 744.00 |
August | 20.41 | 0.31 | 20.10 | 71.77 | 12.35 | 0.00 | 0.00 | 744.00 |
September | 17.49 | 0.01 | 17.48 | 53.60 | 19.04 | 0.00 | 0.00 | 720.00 |
October | 15.19 | 0.00 | 15.19 | 41.57 | 34.22 | 0.00 | 0.00 | 744.00 |
November | 11.53 | 0.00 | 11.53 | 15.51 | 72.58 | 0.00 | 0.00 | 720.00 |
December | 10.40 | 0.00 | 10.40 | 11.23 | 90.23 | 5.50 | 0.00 | 744.00 |
Annual Sum or Average | 16.72 | 0.40 | 16.31 | 42.45 | 47.46 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 10.40 | 0.00 | 10.40 | 10.95 | 8.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 23.77 | 2.10 | 21.74 | 83.51 | 99.41 | 8.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.70 | 50.10 | 24.60 | 95.85 | 66.41 | 62.17 | 0.00 | 744.00 |
February | 94.24 | 64.68 | 29.56 | 120.82 | 61.31 | 105.83 | 0.00 | 672.00 |
March | 103.40 | 64.39 | 39.00 | 132.87 | 59.31 | 22.33 | 0.00 | 744.00 |
April | 131.20 | 85.24 | 45.96 | 171.04 | 56.38 | 2.17 | 0.00 | 720.00 |
May | 125.80 | 71.78 | 54.02 | 171.67 | 35.84 | 2.00 | 0.00 | 744.00 |
June | 138.86 | 80.10 | 58.76 | 193.00 | 35.05 | 2.67 | 0.00 | 720.00 |
July | 129.35 | 66.47 | 62.87 | 177.04 | 31.03 | 9.83 | 0.00 | 744.00 |
August | 120.85 | 60.52 | 60.34 | 166.69 | 34.48 | 17.67 | 0.00 | 744.00 |
September | 103.14 | 51.35 | 51.79 | 139.22 | 40.21 | 3.00 | 0.00 | 720.00 |
October | 98.07 | 58.23 | 39.83 | 132.77 | 47.41 | 25.50 | 0.00 | 744.00 |
November | 79.71 | 54.47 | 25.23 | 100.71 | 64.35 | 42.17 | 0.00 | 720.00 |
December | 67.81 | 44.86 | 22.95 | 85.96 | 64.50 | 40.17 | 0.00 | 744.00 |
Annual Sum or Average | 105.60 | 62.61 | 42.99 | 140.69 | 49.60 | 335.50 | 0.00 | 8760.00 |
Minimum of Months | 67.81 | 44.86 | 22.95 | 85.96 | 31.03 | 2.00 | 0.00 | 672.00 |
Maximum of Months | 138.86 | 85.24 | 62.87 | 193.00 | 66.41 | 105.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140808E+09 | 76200450.24 | 64607742.86 | 0.272944E+09 | 0.414603E+09 |
February | 0.143689E+09 | 72673256.15 | 71015463.55 | 0.290369E+09 | 0.323035E+09 |
March | 0.156625E+09 | 69106870.13 | 87518177.74 | 0.334140E+09 | 0.325955E+09 |
April | 0.187491E+09 | 85609234.45 | 0.101881E+09 | 0.464840E+09 | 0.212047E+09 |
May | 0.162141E+09 | 52737379.75 | 0.109404E+09 | 0.528063E+09 | 67565450.25 |
June | 0.174391E+09 | 61214460.89 | 0.113176E+09 | 0.588523E+09 | 57069676.67 |
July | 0.164551E+09 | 45769549.63 | 0.118782E+09 | 0.540934E+09 | 42466488.51 |
August | 0.165977E+09 | 50505985.30 | 0.115471E+09 | 0.555419E+09 | 59258321.55 |
September | 0.147926E+09 | 50597272.12 | 97328712.59 | 0.454967E+09 | 84324525.05 |
October | 0.156202E+09 | 67231774.02 | 88970232.20 | 0.458045E+09 | 0.149725E+09 |
November | 0.130406E+09 | 65742039.33 | 64663952.18 | 0.291455E+09 | 0.301371E+09 |
December | 0.129836E+09 | 69339171.74 | 60497177.04 | 0.268173E+09 | 0.378760E+09 |
Annual Sum or Average | 0.186004E+10 | 0.766727E+09 | 0.109332E+10 | 0.504787E+10 | 0.241618E+10 |
Minimum of Months | 0.129836E+09 | 45769549.63 | 60497177.04 | 0.268173E+09 | 42466488.51 |
Maximum of Months | 0.187491E+09 | 85609234.45 | 0.118782E+09 | 0.588523E+09 | 0.414603E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140808E+09 | 76200450.24 | 64607742.86 | 0.272944E+09 | 0.414603E+09 |
February | 0.143689E+09 | 72673256.15 | 71015463.55 | 0.290369E+09 | 0.323035E+09 |
March | 0.156625E+09 | 69106870.13 | 87518177.74 | 0.334140E+09 | 0.325955E+09 |
April | 0.187491E+09 | 85609234.45 | 0.101881E+09 | 0.464840E+09 | 0.212047E+09 |
May | 0.162141E+09 | 52737379.75 | 0.109404E+09 | 0.528063E+09 | 67565450.25 |
June | 0.174391E+09 | 61214460.89 | 0.113176E+09 | 0.588523E+09 | 57069676.67 |
July | 0.164551E+09 | 45769549.63 | 0.118782E+09 | 0.540934E+09 | 42466488.51 |
August | 0.165977E+09 | 50505985.30 | 0.115471E+09 | 0.555419E+09 | 59258321.55 |
September | 0.147926E+09 | 50597272.12 | 97328712.59 | 0.454967E+09 | 84324525.05 |
October | 0.156202E+09 | 67231774.02 | 88970232.20 | 0.458045E+09 | 0.149725E+09 |
November | 0.130406E+09 | 65742039.33 | 64663952.18 | 0.291455E+09 | 0.301371E+09 |
December | 0.129836E+09 | 69339171.74 | 60497177.04 | 0.268173E+09 | 0.378760E+09 |
Annual Sum or Average | 0.186004E+10 | 0.766727E+09 | 0.109332E+10 | 0.504787E+10 | 0.241618E+10 |
Minimum of Months | 0.129836E+09 | 45769549.63 | 60497177.04 | 0.268173E+09 | 42466488.51 |
Maximum of Months | 0.187491E+09 | 85609234.45 | 0.118782E+09 | 0.588523E+09 | 0.414603E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29974573.29 | 0.00 | 29974573.29 | 29342667.29 | 0.266257E+09 |
February | 31940555.34 | 0.00 | 31940555.34 | 36216518.86 | 0.204184E+09 |
March | 41034272.79 | 3825.51 | 41030447.29 | 58337001.60 | 0.201409E+09 |
April | 47150691.13 | 449004.63 | 46701686.50 | 91371957.30 | 0.128279E+09 |
May | 55765350.72 | 2893015.04 | 52872335.69 | 0.183863E+09 | 37286644.46 |
June | 61625050.53 | 5453686.34 | 56171364.19 | 0.216468E+09 | 31560945.32 |
July | 61332012.36 | 3101702.51 | 58230309.85 | 0.210370E+09 | 23832736.53 |
August | 54659718.70 | 824209.12 | 53835509.58 | 0.192243E+09 | 33069522.25 |
September | 45334284.49 | 16472.13 | 45317812.36 | 0.138945E+09 | 49347947.08 |
October | 40682203.50 | 0.00 | 40682203.50 | 0.111333E+09 | 91662886.38 |
November | 29888040.75 | 0.00 | 29888040.75 | 40192031.19 | 0.188124E+09 |
December | 27864773.82 | 0.00 | 27864773.82 | 30066132.58 | 0.241665E+09 |
Annual Sum or Average | 0.527252E+09 | 12741915.28 | 0.514510E+09 | 0.133875E+10 | 0.149668E+10 |
Minimum of Months | 27864773.82 | 0.00 | 27864773.82 | 29342667.29 | 23832736.53 |
Maximum of Months | 61625050.53 | 5453686.34 | 58230309.85 | 0.216468E+09 | 0.266257E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29973747.49 | 0.00 | 29973747.49 | 29341703.82 | 0.266256E+09 |
February | 31939705.80 | 0.00 | 31939705.80 | 36215596.30 | 0.204182E+09 |
March | 41033111.32 | 3825.33 | 41029286.00 | 58335390.75 | 0.201408E+09 |
April | 47149410.81 | 448983.58 | 46700427.23 | 91369867.95 | 0.128278E+09 |
May | 55763655.40 | 2892879.44 | 52870775.96 | 0.183859E+09 | 37285764.09 |
June | 61623141.09 | 5453430.72 | 56169710.37 | 0.216464E+09 | 31560060.02 |
July | 61330085.09 | 3101557.13 | 58228527.96 | 0.210365E+09 | 23831906.88 |
August | 54658046.90 | 824170.49 | 53833876.40 | 0.192239E+09 | 33068674.06 |
September | 45332902.11 | 16471.36 | 45316430.75 | 0.138942E+09 | 49346988.04 |
October | 40681030.46 | 0.00 | 40681030.46 | 0.111331E+09 | 91661884.93 |
November | 29887231.69 | 0.00 | 29887231.69 | 40191040.66 | 0.188123E+09 |
December | 27863999.45 | 0.00 | 27863999.45 | 30065352.75 | 0.241664E+09 |
Annual Sum or Average | 0.527236E+09 | 12741318.05 | 0.514495E+09 | 0.133872E+10 | 0.149667E+10 |
Minimum of Months | 27863999.45 | 0.00 | 27863999.45 | 29341703.82 | 23831906.88 |
Maximum of Months | 61623141.09 | 5453430.72 | 58228527.96 | 0.216464E+09 | 0.266256E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200069E+09 | 0.134192E+09 | 65877606.64 | 0.256728E+09 | 0.177867E+09 |
February | 0.227991E+09 | 0.156476E+09 | 71514989.23 | 0.292279E+09 | 0.148319E+09 |
March | 0.276936E+09 | 0.172466E+09 | 0.104470E+09 | 0.355880E+09 | 0.158868E+09 |
April | 0.340070E+09 | 0.220931E+09 | 0.119139E+09 | 0.443334E+09 | 0.146146E+09 |
May | 0.336952E+09 | 0.192260E+09 | 0.144692E+09 | 0.459796E+09 | 95989543.29 |
June | 0.359915E+09 | 0.207620E+09 | 0.152295E+09 | 0.500258E+09 | 90843797.65 |
July | 0.346446E+09 | 0.178046E+09 | 0.168400E+09 | 0.474186E+09 | 83102203.43 |
August | 0.323695E+09 | 0.162092E+09 | 0.161603E+09 | 0.446474E+09 | 92348842.17 |
September | 0.267334E+09 | 0.133088E+09 | 0.134246E+09 | 0.360848E+09 | 0.104215E+09 |
October | 0.262662E+09 | 0.155974E+09 | 0.106687E+09 | 0.355615E+09 | 0.126995E+09 |
November | 0.206596E+09 | 0.141195E+09 | 65401092.52 | 0.261047E+09 | 0.166792E+09 |
December | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 0.172759E+09 |
Annual Sum or Average | 0.333029E+10 | 0.197449E+10 | 0.135580E+10 | 0.443668E+10 | 0.156425E+10 |
Minimum of Months | 0.181624E+09 | 0.120150E+09 | 61473359.58 | 0.230230E+09 | 83102203.43 |
Maximum of Months | 0.359915E+09 | 0.220931E+09 | 0.168400E+09 | 0.500258E+09 | 0.177867E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.49 | 495.18 | 127.53 | 56.90 | 70.63 | 0.00 | 0.00 |
February | 260.66 | 426.53 | 145.20 | 60.08 | 85.12 | 0.00 | 0.00 |
March | 287.90 | 388.62 | 147.59 | 51.61 | 95.99 | 0.00 | 0.00 |
April | 426.03 | 259.46 | 181.05 | 66.40 | 114.65 | 0.00 | 0.00 |
May | 530.90 | 77.59 | 162.71 | 41.54 | 121.17 | 0.00 | 0.00 |
June | 620.42 | 67.68 | 182.11 | 51.44 | 130.67 | 0.00 | 0.00 |
July | 560.57 | 49.07 | 168.67 | 36.49 | 132.18 | 0.00 | 0.00 |
August | 558.08 | 68.74 | 164.75 | 38.33 | 126.42 | 0.00 | 0.00 |
September | 457.93 | 102.80 | 149.12 | 39.05 | 110.07 | 0.00 | 0.00 |
October | 423.71 | 178.80 | 147.02 | 50.20 | 96.81 | 0.00 | 0.00 |
November | 249.61 | 371.40 | 123.68 | 50.73 | 72.96 | 0.00 | 0.00 |
December | 213.60 | 454.18 | 117.76 | 51.78 | 65.98 | 0.00 | 0.00 |
Annual Sum or Average | 400.88 | 244.00 | 151.40 | 49.43 | 101.97 | 0.00 | 0.00 |
Minimum of Months | 212.49 | 49.07 | 117.76 | 36.49 | 65.98 | 0.00 | 0.00 |
Maximum of Months | 620.42 | 495.18 | 182.11 | 66.40 | 132.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 958.51 | 664.07 | 746.97 | 501.01 | 245.96 | 0.00 | 0.00 |
February | 1208.16 | 613.09 | 942.42 | 646.81 | 295.61 | 0.00 | 0.00 |
March | 1328.69 | 593.14 | 1033.96 | 643.91 | 390.05 | 0.00 | 0.00 |
April | 1710.39 | 563.84 | 1312.00 | 852.36 | 459.64 | 0.00 | 0.00 |
May | 1716.68 | 358.37 | 1258.03 | 717.82 | 540.22 | 0.00 | 0.00 |
June | 1930.01 | 350.48 | 1388.56 | 801.00 | 587.56 | 0.00 | 0.00 |
July | 1770.41 | 310.26 | 1293.48 | 664.75 | 628.73 | 0.00 | 0.00 |
August | 1666.94 | 344.78 | 1208.54 | 605.18 | 603.36 | 0.00 | 0.00 |
September | 1392.16 | 402.05 | 1031.38 | 513.46 | 517.92 | 0.00 | 0.00 |
October | 1327.71 | 474.15 | 980.67 | 582.34 | 398.33 | 0.00 | 0.00 |
November | 1007.12 | 643.49 | 797.05 | 544.73 | 252.32 | 0.00 | 0.00 |
December | 859.57 | 645.01 | 678.10 | 448.59 | 229.52 | 0.00 | 0.00 |
Annual Sum or Average | 1406.86 | 496.01 | 1056.03 | 626.11 | 429.92 | 0.00 | 0.00 |
Minimum of Months | 859.57 | 310.26 | 678.10 | 448.59 | 229.52 | 0.00 | 0.00 |
Maximum of Months | 1930.01 | 664.07 | 1388.56 | 852.36 | 628.73 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569129E+09 | 0.132628E+10 | 0.341565E+09 | 0.152401E+09 | 0.189164E+09 | 0.00 | 0.00 |
February | 0.630594E+09 | 0.103186E+10 | 0.351258E+09 | 0.145347E+09 | 0.205911E+09 | 0.00 | 0.00 |
March | 0.771103E+09 | 0.104088E+10 | 0.395317E+09 | 0.138221E+09 | 0.257096E+09 | 0.00 | 0.00 |
April | 0.110428E+10 | 0.672508E+09 | 0.469281E+09 | 0.172116E+09 | 0.297165E+09 | 0.00 | 0.00 |
May | 0.142195E+10 | 0.207810E+09 | 0.435811E+09 | 0.111261E+09 | 0.324550E+09 | 0.00 | 0.00 |
June | 0.160814E+10 | 0.175421E+09 | 0.472030E+09 | 0.133336E+09 | 0.338694E+09 | 0.00 | 0.00 |
July | 0.150143E+10 | 0.131421E+09 | 0.451765E+09 | 97742358.90 | 0.354023E+09 | 0.00 | 0.00 |
August | 0.149477E+10 | 0.184102E+09 | 0.441273E+09 | 0.102660E+09 | 0.338612E+09 | 0.00 | 0.00 |
September | 0.118694E+10 | 0.266469E+09 | 0.386519E+09 | 0.101227E+09 | 0.285292E+09 | 0.00 | 0.00 |
October | 0.113487E+10 | 0.478887E+09 | 0.393767E+09 | 0.134464E+09 | 0.259304E+09 | 0.00 | 0.00 |
November | 0.646978E+09 | 0.962674E+09 | 0.320587E+09 | 0.131484E+09 | 0.189103E+09 | 0.00 | 0.00 |
December | 0.572104E+09 | 0.121647E+10 | 0.315401E+09 | 0.138678E+09 | 0.176723E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126423E+11 | 0.769478E+10 | 0.477457E+10 | 0.155894E+10 | 0.321564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.569129E+09 | 0.131421E+09 | 0.315401E+09 | 97742358.90 | 0.176723E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160814E+10 | 0.132628E+10 | 0.472030E+09 | 0.172116E+09 | 0.354023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256726E+10 | 0.177865E+10 | 0.200069E+10 | 0.134192E+10 | 0.658776E+09 | 0.00 | 0.00 |
February | 0.292278E+10 | 0.148319E+10 | 0.227991E+10 | 0.156476E+10 | 0.715150E+09 | 0.00 | 0.00 |
March | 0.355878E+10 | 0.158868E+10 | 0.276936E+10 | 0.172466E+10 | 0.104470E+10 | 0.00 | 0.00 |
April | 0.443334E+10 | 0.146146E+10 | 0.340070E+10 | 0.220931E+10 | 0.119139E+10 | 0.00 | 0.00 |
May | 0.459796E+10 | 0.959871E+09 | 0.336952E+10 | 0.192260E+10 | 0.144692E+10 | 0.00 | 0.00 |
June | 0.500258E+10 | 0.908436E+09 | 0.359915E+10 | 0.207620E+10 | 0.152295E+10 | 0.00 | 0.00 |
July | 0.474186E+10 | 0.830998E+09 | 0.346446E+10 | 0.178046E+10 | 0.168400E+10 | 0.00 | 0.00 |
August | 0.446474E+10 | 0.923449E+09 | 0.323695E+10 | 0.162092E+10 | 0.161603E+10 | 0.00 | 0.00 |
September | 0.360847E+10 | 0.104212E+10 | 0.267334E+10 | 0.133088E+10 | 0.134246E+10 | 0.00 | 0.00 |
October | 0.355614E+10 | 0.126995E+10 | 0.262662E+10 | 0.155974E+10 | 0.106687E+10 | 0.00 | 0.00 |
November | 0.261046E+10 | 0.166792E+10 | 0.206596E+10 | 0.141195E+10 | 0.654011E+09 | 0.00 | 0.00 |
December | 0.230228E+10 | 0.172759E+10 | 0.181624E+10 | 0.120150E+10 | 0.614734E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443667E+11 | 0.156423E+11 | 0.333029E+11 | 0.197449E+11 | 0.135580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230228E+10 | 0.830998E+09 | 0.181624E+10 | 0.120150E+10 | 0.614734E+09 | 0.00 | 0.00 |
Maximum of Months | 0.500258E+10 | 0.177865E+10 | 0.359915E+10 | 0.220931E+10 | 0.168400E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.828864E+09 | -688257376.9 | 0.00 | 0.00 | 744.00 | 0.00 | -140606924.2 | 58.99 | 0.00 | 0.00 |
February | 0.752620E+09 | -627178264.5 | 0.00 | 0.00 | 672.00 | 0.00 | -125441637.0 | 58.99 | 0.00 | 0.00 |
March | 0.841569E+09 | -705021500.7 | 0.00 | 0.00 | 744.00 | 0.00 | -136547973.4 | 58.99 | 0.00 | 0.00 |
April | 0.742928E+09 | -614744314.0 | 0.00 | 0.00 | 720.00 | 0.00 | -128183356.9 | 58.99 | 0.00 | 0.00 |
May | 0.725489E+09 | -594415118.0 | 0.00 | 0.00 | 744.00 | 0.00 | -131074174.3 | 58.99 | 0.00 | 0.00 |
June | 0.682538E+09 | -555359563.5 | 0.00 | 0.00 | 720.00 | 0.00 | -127178747.7 | 58.99 | 0.00 | 0.00 |
July | 0.649687E+09 | -519496614.5 | 0.00 | 0.00 | 744.00 | 0.00 | -130190773.5 | 58.99 | 0.00 | 0.00 |
August | 0.695409E+09 | -564070146.0 | 0.00 | 0.00 | 744.00 | 0.00 | -131339219.4 | 58.99 | 0.00 | 0.00 |
September | 0.677985E+09 | -551534666.3 | 0.00 | 0.00 | 720.00 | 0.00 | -126449954.2 | 58.99 | 0.00 | 0.00 |
October | 0.724420E+09 | -593492152.4 | 0.00 | 0.00 | 744.00 | 0.00 | -130927964.9 | 58.99 | 0.00 | 0.00 |
November | 0.740394E+09 | -611316938.9 | 0.00 | 0.00 | 720.00 | 0.00 | -129076659.2 | 58.99 | 0.00 | 0.00 |
December | 0.808782E+09 | -671011167.6 | 0.00 | 0.00 | 744.00 | 0.00 | -137770809.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.887069E+10 | -.729590E+10 | 8760.00 | -.157479E+10 | 58.99 | |||||
Minimum of Months | 0.649687E+09 | -705021500.7 | 0.00 | 0.00 | 672.00 | 0.00 | -140606924.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.841569E+09 | -519496614.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125441637.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | ||||||||||
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.718663E+09 | 29082.06 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378915E+09 | 29082.06 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286535E+09 | 29082.06 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2796471.49 | 2421.40 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28712590.57 | 4430.41 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412985E+09 | 29082.06 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182861E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718663E+09 | 29082.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124951E+09 | 22124.51 | 10-JAN-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219914E+09 | 61853.56 | 05-FEB-07:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6119686.43 | 15222.06 | 12-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41607841.59 | 28278.39 | 21-DEC-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392593E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219914E+09 | 61853.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.217208E+10 | 0.162737E+10 | 26326.82 | 02-JAN-00:01 | 18665.43 | 0.00 |
February | 0.00 | 0.00 | 0.346459E+10 | 0.258263E+10 | 25403.91 | 27-FEB-00:02 | 19652.07 | 0.00 |
March | 0.00 | 0.00 | 0.508859E+10 | 0.390729E+10 | 26639.08 | 27-MAR-00:01 | 18495.62 | 0.00 |
April | 0.00 | 0.00 | 0.973783E+10 | 0.763898E+10 | 27611.92 | 24-APR-00:01 | 18393.77 | 0.00 |
May | 0.00 | 0.00 | 0.178202E+11 | 0.129240E+11 | 29780.49 | 22-MAY-00:01 | 15578.36 | 0.00 |
June | 0.00 | 0.00 | 0.190531E+11 | 0.138303E+11 | 29194.55 | 05-JUN-00:01 | 16906.59 | 0.00 |
July | 0.00 | 0.00 | 0.197664E+11 | 0.137164E+11 | 30354.43 | 31-JUL-00:01 | 15591.42 | 0.00 |
August | 0.00 | 0.00 | 0.210347E+11 | 0.147229E+11 | 29959.31 | 14-AUG-00:01 | 15864.07 | 0.00 |
September | 0.00 | 0.00 | 0.177421E+11 | 0.123075E+11 | 30644.26 | 05-SEP-00:01 | 14940.85 | 0.00 |
October | 0.00 | 0.00 | 0.150114E+11 | 0.109777E+11 | 29680.84 | 23-OCT-00:01 | 16360.17 | 0.00 |
November | 0.00 | 0.00 | 0.711492E+10 | 0.548002E+10 | 26876.15 | 03-NOV-17:10 | 16002.32 | 0.00 |
December | 0.00 | 0.00 | 0.437831E+10 | 0.327853E+10 | 26748.72 | 11-DEC-00:01 | 18227.55 | 0.00 |
Annual Sum or Average | 0.142384E+12 | 0.102994E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.217208E+10 | 0.162737E+10 | 25403.91 | 14940.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210347E+11 | 0.147229E+11 | 30644.26 | 19652.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.838329E+09 | 0.566687E+09 | 35275.09 | 01-JAN-14:15 | 28710.48 | 0.00 |
February | 0.00 | 0.00 | 0.277057E+10 | 0.191089E+10 | 32433.32 | 26-FEB-14:35 | 25180.18 | 0.00 |
March | 0.00 | 0.00 | 0.455058E+10 | 0.310972E+10 | 38515.71 | 26-MAR-13:25 | 29366.07 | 0.00 |
April | 0.00 | 0.00 | 0.154045E+11 | 0.114763E+11 | 80399.63 | 28-APR-17:42 | 52546.66 | 0.00 |
May | 0.00 | 0.00 | 0.404206E+11 | 0.280553E+11 | 83757.25 | 28-MAY-09:23 | 44719.32 | 0.00 |
June | 0.00 | 0.00 | 0.463684E+11 | 0.327240E+11 | 84209.70 | 05-JUN-00:08 | 45147.79 | 0.00 |
July | 0.00 | 0.00 | 0.514172E+11 | 0.337254E+11 | 87779.55 | 31-JUL-00:01 | 42556.98 | 0.00 |
August | 0.00 | 0.00 | 0.503900E+11 | 0.333618E+11 | 85319.32 | 14-AUG-00:07 | 44267.90 | 0.00 |
September | 0.00 | 0.00 | 0.396550E+11 | 0.255034E+11 | 85235.05 | 04-SEP-10:13 | 44558.86 | 0.00 |
October | 0.00 | 0.00 | 0.313424E+11 | 0.210112E+11 | 85969.93 | 08-OCT-09:53 | 43021.57 | 0.00 |
November | 0.00 | 0.00 | 0.732438E+10 | 0.505406E+10 | 64623.87 | 02-NOV-17:10 | 42502.79 | 0.00 |
December | 0.00 | 0.00 | 0.404245E+10 | 0.269352E+10 | 32894.65 | 10-DEC-13:50 | 23204.78 | 0.00 |
Annual Sum or Average | 0.294524E+12 | 0.199192E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.838329E+09 | 0.566687E+09 | 32433.32 | 23204.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.514172E+11 | 0.337254E+11 | 87779.55 | 52546.66 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133144E+10 | 0.37 | 1325.67 | 03-JAN-15:30 | 0.94 |
February | 0.123278E+10 | 0.39 | 1325.67 | 07-FEB-16:00 | 0.93 |
March | 0.146066E+10 | 0.43 | 1325.67 | 03-MAR-11:00 | 0.94 |
April | 0.144412E+10 | 0.54 | 1325.67 | 07-APR-11:10 | 0.93 |
May | 0.166568E+10 | 0.69 | 1325.67 | 04-MAY-06:10 | 0.93 |
June | 0.168955E+10 | 0.73 | 1325.67 | 01-JUN-06:30 | 0.92 |
July | 0.165799E+10 | 0.68 | 1325.67 | 01-JUL-06:23 | 0.92 |
August | 0.178258E+10 | 0.73 | 1325.67 | 12-AUG-09:30 | 0.93 |
September | 0.161767E+10 | 0.70 | 1325.67 | 05-SEP-11:30 | 0.92 |
October | 0.156178E+10 | 0.64 | 1325.67 | 03-OCT-06:30 | 0.93 |
November | 0.133349E+10 | 0.45 | 1325.67 | 04-NOV-06:20 | 0.93 |
December | 0.135428E+10 | 0.40 | 1325.67 | 02-DEC-17:50 | 0.93 |
Annual Sum or Average | 0.181320E+11 | 0.56 | |||
Minimum of Months | 0.123278E+10 | 0.37 | 1325.67 | 0.92 | |
Maximum of Months | 0.178258E+10 | 0.73 | 1325.67 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307604E+10 | 0.34 | 3097.09 | 02-JAN-12:00 | 0.89 |
February | 0.283546E+10 | 0.35 | 3097.09 | 01-FEB-14:20 | 0.89 |
March | 0.332068E+10 | 0.36 | 3097.09 | 03-MAR-13:40 | 0.90 |
April | 0.313603E+10 | 0.38 | 3097.09 | 01-APR-10:50 | 0.89 |
May | 0.359548E+10 | 0.52 | 3097.09 | 10-MAY-07:10 | 0.88 |
June | 0.369643E+10 | 0.59 | 3097.09 | 01-JUN-07:00 | 0.88 |
July | 0.377014E+10 | 0.63 | 3097.09 | 28-JUL-08:00 | 0.88 |
August | 0.387974E+10 | 0.60 | 3097.09 | 01-AUG-06:20 | 0.88 |
September | 0.350954E+10 | 0.51 | 3097.09 | 13-SEP-09:30 | 0.88 |
October | 0.337219E+10 | 0.45 | 3097.09 | 13-OCT-09:40 | 0.88 |
November | 0.296674E+10 | 0.34 | 3097.09 | 01-NOV-08:70 | 0.88 |
December | 0.307121E+10 | 0.33 | 3097.09 | 02-DEC-14:10 | 0.89 |
Annual Sum or Average | 0.402297E+11 | 0.45 | |||
Minimum of Months | 0.283546E+10 | 0.33 | 3097.09 | 0.88 | |
Maximum of Months | 0.387974E+10 | 0.63 | 3097.09 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.01 | 2.64 |
February | 0.68 | 2.18 |
March | 1.08 | 3.95 |
April | 0.40 | 2.24 |
May | 0.25 | 0.00 |
June | 0.14 | 0.00 |
July | 0.20 | 0.00 |
August | 0.19 | 0.00 |
September | 0.10 | 0.00 |
October | 0.17 | 2.50 |
November | 0.51 | 4.36 |
December | 1.38 | 2.50 |
Annual Sum or Average | 6.11 | 2.52 |
Minimum of Months | 0.10 | 0.00 |
Maximum of Months | 1.38 | 4.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.17 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 3.02 | 0.00 |
May | 10.72 | 0.00 |
June | 14.10 | 0.00 |
July | 14.71 | 0.00 |
August | 9.98 | 0.00 |
September | 7.14 | 0.00 |
October | 4.81 | 0.00 |
November | 0.14 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 64.63 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.71 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191144E+10 | 0.104868E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215752E+10 | 0.553218E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.282370E+10 | 0.422438E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.409280E+10 | 4306581.32 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.659228E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.700697E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.712967E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.758037E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.641166E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.565216E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.324421E+10 | 43837655.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.252700E+10 | 0.607748E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.571298E+11 | 0.268022E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.191144E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.758037E+10 | 0.104868E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.331786E+10 | 0.191388E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.362701E+10 | 0.330470E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.462630E+10 | 9337103.92 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.761492E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.155296E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174706E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188966E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.186393E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149490E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124369E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.507091E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.423070E+10 | 63982950.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.126410E+12 | 0.595178E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.331786E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188966E+11 | 0.330470E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133144E+10 | 0.217208E+10 | 0.718663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123278E+10 | 0.346459E+10 | 0.378915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146066E+10 | 0.508859E+10 | 0.286535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144412E+10 | 0.973783E+10 | 2796471.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166568E+10 | 0.178202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168955E+10 | 0.190531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165799E+10 | 0.197664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178258E+10 | 0.210347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161767E+10 | 0.177421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156178E+10 | 0.150114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133349E+10 | 0.711492E+10 | 28712590.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135428E+10 | 0.437831E+10 | 0.412985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181320E+11 | 0.142384E+12 | 0.182861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123278E+10 | 0.217208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178258E+10 | 0.210347E+11 | 0.718663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307604E+10 | 0.838329E+09 | 0.124951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283546E+10 | 0.277057E+10 | 0.219914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332068E+10 | 0.455058E+10 | 6119686.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313603E+10 | 0.154045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359548E+10 | 0.404206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.369643E+10 | 0.463684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377014E+10 | 0.514172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387974E+10 | 0.503900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350954E+10 | 0.396550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337219E+10 | 0.313424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296674E+10 | 0.732438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307121E+10 | 0.404245E+10 | 41607841.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402297E+11 | 0.294524E+12 | 0.392593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283546E+10 | 0.838329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387974E+10 | 0.514172E+11 | 0.219914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.133144E+10 | 0.00 | 0.00 | 0.00 | 0.580003E+09 | 0.00 | 0.104868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123278E+10 | 0.00 | 0.00 | 0.00 | 0.924747E+09 | 0.00 | 0.553218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146066E+10 | 0.00 | 0.00 | 0.00 | 0.136304E+10 | 0.00 | 0.422438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144412E+10 | 0.00 | 0.00 | 0.00 | 0.264869E+10 | 0.00 | 4306581.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166568E+10 | 0.00 | 0.00 | 0.00 | 0.492660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168955E+10 | 0.00 | 0.00 | 0.00 | 0.531743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165799E+10 | 0.00 | 0.00 | 0.00 | 0.547169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178258E+10 | 0.00 | 0.00 | 0.00 | 0.579779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161767E+10 | 0.00 | 0.00 | 0.00 | 0.479399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156178E+10 | 0.00 | 0.00 | 0.00 | 0.409039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133349E+10 | 0.00 | 0.00 | 0.00 | 0.191073E+10 | 0.00 | 43837655.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135428E+10 | 0.00 | 0.00 | 0.00 | 0.117272E+10 | 0.00 | 0.607748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181320E+11 | 0.00 | 0.00 | 0.00 | 0.389978E+11 | 0.00 | 0.268022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123278E+10 | 0.00 | 0.00 | 0.00 | 0.580003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178258E+10 | 0.00 | 0.00 | 0.00 | 0.579779E+10 | 0.00 | 0.104868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.307604E+10 | 0.00 | 0.00 | 0.00 | 0.241817E+09 | 0.00 | 0.191388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283546E+10 | 0.00 | 0.00 | 0.00 | 0.791557E+09 | 0.00 | 0.330470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332068E+10 | 0.00 | 0.00 | 0.00 | 0.130562E+10 | 0.00 | 9337103.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313603E+10 | 0.00 | 0.00 | 0.00 | 0.447889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359548E+10 | 0.00 | 0.00 | 0.00 | 0.119342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.369643E+10 | 0.00 | 0.00 | 0.00 | 0.137742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377014E+10 | 0.00 | 0.00 | 0.00 | 0.151265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387974E+10 | 0.00 | 0.00 | 0.00 | 0.147596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350954E+10 | 0.00 | 0.00 | 0.00 | 0.114395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337219E+10 | 0.00 | 0.00 | 0.00 | 0.906472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296674E+10 | 0.00 | 0.00 | 0.00 | 0.210417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307121E+10 | 0.00 | 0.00 | 0.00 | 0.115949E+10 | 0.00 | 63982950.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402297E+11 | 0.00 | 0.00 | 0.00 | 0.861802E+11 | 0.00 | 0.595178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.283546E+10 | 0.00 | 0.00 | 0.00 | 0.241817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387974E+10 | 0.00 | 0.00 | 0.00 | 0.151265E+11 | 0.00 | 0.330470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565278E+09 | 0.190094E+09 | 0.00 | 1129721.59 | 0.00 | 0.277281E+09 | 0.328028E+09 | 0.00 | 0.16 |
February | 0.334914E+09 | 0.331833E+09 | 0.00 | 854467.82 | 1537299.62 | 0.135840E+09 | 0.232226E+09 | 0.00 | 0.17 |
March | 0.357664E+09 | 0.524579E+09 | 0.00 | 1642367.44 | 602334.87 | 0.101790E+09 | 0.292833E+09 | 0.00 | 0.18 |
April | 36129657.81 | 0.114481E+10 | 0.00 | 1677063.66 | 4380348.19 | 2906526.49 | 0.110187E+09 | 0.00 | 0.18 |
May | 0.00 | 0.330804E+10 | 0.00 | 200683.05 | 0.00 | 0.00 | 21670.48 | 0.00 | 0.20 |
June | 0.00 | 0.382337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.432415E+10 | 0.00 | 1889.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.425687E+10 | 0.00 | 15930.09 | 0.00 | 0.00 | 46692.25 | 0.00 | 0.22 |
September | 0.00 | 0.342099E+10 | 0.00 | 110310.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
October | 25977672.04 | 0.255470E+10 | 0.00 | 2690788.17 | 0.00 | 0.00 | 0.125302E+09 | 0.00 | 0.19 |
November | 94915929.34 | 0.821332E+09 | 0.00 | 2333436.63 | 150249.86 | 27294603.29 | 0.247863E+09 | 0.00 | 0.17 |
December | 0.478181E+09 | 0.546887E+09 | 2576.53 | 988830.89 | 3088447.02 | 0.183341E+09 | 0.205304E+09 | 27463.85 | 0.17 |
Annual Sum or Average | 0.189306E+10 | 0.252477E+11 | 2576.53 | 11645489.48 | 9758679.56 | 0.728454E+09 | 0.154181E+10 | 27463.85 | 0.19 |
Minimum of Months | 0.00 | 0.190094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.565278E+09 | 0.432415E+10 | 2576.53 | 2690788.17 | 4380348.19 | 0.277281E+09 | 0.328028E+09 | 27463.85 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269046E+10 | 45198158.11 | 0.00 | 148394.29 | 4778181.71 | 43962126.53 | 6653500.62 | 0.00 | 0.16 |
February | 0.189659E+10 | 0.265890E+09 | 0.00 | 256256.71 | 2164644.81 | 43076732.84 | 33879001.14 | 0.00 | 0.17 |
March | 0.213594E+10 | 0.516937E+09 | 0.00 | 510400.41 | 2227648.94 | 277637.11 | 99053710.79 | 0.00 | 0.18 |
April | 0.653466E+09 | 0.166794E+10 | 0.00 | 3275401.99 | 1961.94 | 0.00 | 0.433596E+09 | 0.00 | 0.17 |
May | 2664758.90 | 0.634706E+10 | 0.00 | 283575.79 | 2139827.42 | 0.00 | 16676871.62 | 0.00 | 0.19 |
June | 8316116.11 | 0.836032E+10 | 0.00 | 174199.46 | 2360944.11 | 0.00 | 13936905.69 | 0.00 | 0.20 |
July | 0.00 | 0.964017E+10 | 0.00 | 47855.26 | 1465237.33 | 0.00 | 776061.67 | 0.00 | 0.20 |
August | 3422396.14 | 0.878323E+10 | 0.00 | 159102.98 | 0.00 | 0.00 | 12113797.74 | 0.00 | 0.21 |
September | 7842333.74 | 0.658908E+10 | 0.00 | 393422.51 | 0.00 | 0.00 | 53552862.90 | 0.00 | 0.19 |
October | 0.414475E+09 | 0.463619E+10 | 0.00 | 3083250.45 | 38728.90 | 0.00 | 0.216808E+09 | 0.00 | 0.18 |
November | 0.123485E+10 | 0.108608E+10 | 0.00 | 1381432.76 | 9077313.56 | 0.00 | 0.329336E+09 | 0.00 | 0.16 |
December | 0.211941E+10 | 0.558545E+09 | 0.00 | 405004.80 | 13036119.35 | 21889658.79 | 54181528.20 | 0.00 | 0.16 |
Annual Sum or Average | 0.111674E+11 | 0.484966E+11 | 0.00 | 10118297.41 | 37290608.07 | 0.109206E+09 | 0.127056E+10 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 45198158.11 | 0.00 | 47855.26 | 0.00 | 0.00 | 776061.67 | 0.00 | 0.16 |
Maximum of Months | 0.269046E+10 | 0.964017E+10 | 0.00 | 3275401.99 | 13036119.35 | 43962126.53 | 0.433596E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |