Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1092.34 | 225.92 | 225.92 |
Net Site Energy | 1092.34 | 225.92 | 225.92 |
Total Source Energy | 2885.78 | 596.84 | 596.84 |
Net Source Energy | 2885.78 | 596.84 | 596.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 275.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.99 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 816.94 | 275.40 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 275.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.99 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.99 | 56.96 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 168.96 | 56.96 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.99 | 56.96 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 168.96 | 56.96 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 816.938 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 816.938 | 100.00 |
Total On-Site and Utility Electric Sources | 816.938 | 100.00 |
Total Electricity End Uses | 816.938 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 59.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2080.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 10-JAN-06:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 143188.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7185.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1783.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57943.87 | 143188.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 143188.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7185.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1783.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 298.53 | 0.00 | 0.00 | 0.00 |
Cooling | 8.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2587.24 | 298.53 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 61.74 | 0.00 | 0.00 | 0.00 |
Cooling | 1.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.09 | 61.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 61.74 | 0.00 | 0.00 | 0.00 |
Cooling | 1.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.09 | 61.74 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.970535 |
ZONE2 FINE STORAGE DIRECT AIR | 1.95 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.89 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.89 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 77761.74 |
PSZ-OFFICE HEATING COIL | 25120.57 |
PSZ-FINE STORAGE HEATING COIL | 67203.84 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 77761.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.970535 | 0.970535 | 0.970535 | 0.970535 | 0.970535 | 0.970535 | 1.00 | 1.000000 | 0.970535 |
PSZ-FINE STORAGE | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.00 | 1.00 | 1.95 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.970535 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.95 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.970535 | 0.970535 | 0.970535 | 0.970535 | 16065.81 | 25120.57 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.95 | 1.95 | 1.95 | 1.95 | 35969.76 | 67203.84 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.970540 | 0.485270 | 0.970540 | 16065.88 | 16065.81 | 8032.90 | 16065.81 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.95 | 0.975815 | 1.95 | 33917.27 | 35969.76 | 17984.88 | 35969.76 | 0.761211 | 0.761210 | 0.761210 | 0.761210 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.970535 | 1106.52 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.95 | 2136.07 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.72529422E-12 | -0.16659653E-15 | 0.22267608E-14 | 0.12345853E-15 |
13 | 3 | -0.36555712E-03 | 0.52642428E-06 | -0.52844486E-04 | 0.13919492E-12 |
14 | 2 | 1.6938492 | 0.11754276E-01 | 1.1057222 | -0.70081836E-04 |
15 | 1 | -7.1898979 | 0.30855302 | -16.875743 | 0.32460476 |
16 | 0 | 6.0151594 | 0.19843725 | 16.288819 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22267608E-14 | -0.16659653E-15 | 0.72529422E-12 | 0.12345853E-15 |
85 | 3 | -0.52844486E-04 | 0.52642428E-06 | -0.36555712E-03 | 0.13919492E-12 |
86 | 2 | 1.1057222 | 0.11754276E-01 | 1.6938492 | -0.70081836E-04 |
87 | 1 | -16.875743 | 0.30855302 | -7.1898979 | 0.32460476 |
88 | 0 | 16.288819 | 0.19843725 | 6.0151594 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9726.98758 | 11672.38509 | 0.80878 | 0.97054 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.38408E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9434.03987 | 11320.84784 | 0.26758 | 0.32109 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 25092.44172 | 30110.93006 | 1.62636 | 1.95163 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.38408E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 27742.39520 | 33290.87424 | 0.66302 | 0.79563 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40000 | 8.38408E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 64801.45062 | 77761.74075 | 1.57693 | 1.89232 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13976.30 | 0.97054 | 0.97054 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10388.17 | 0.32109 | 0.32109 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34192.66 | 1.95163 | 1.95163 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 33377.71 | 0.79563 | 0.79563 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97054 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95163 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.89232 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.89232 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 77761.74292 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 77761.74075 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97054 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97054 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97054 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97054 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97054 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.97054 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95163 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95163 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95163 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95163 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.95163 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.95163 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.97054 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.95163 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97054 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97054 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97054 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97054 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97054 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97054 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48527 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97054 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16065.88313 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16065.81000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8032.90500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16065.81000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16065.81000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25120.56655 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97054 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1106.51710 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25120.56655 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.95163 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.95163 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.95163 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.95163 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.95163 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.95163 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97582 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.95163 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33917.26846 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 35969.76000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17984.88000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 35969.76000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76121 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76121 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76121 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76121 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35969.76000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67203.84371 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.95163 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2136.06929 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 67203.84371 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15312.7 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 34454.8 | 14.81 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1652679347 | 0.1661827468 | Pass | Pass | 0.6842121911 | 6.9285214398 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4441131635 | 0.4099314668 | Pass | Pass | 0.3458989439 | 0.7004753491 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 9.7730761417E-005 | 2.4765350134E-004 | Pass | Pass | 8.5659306615E-002 | 0.1234009954 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.54 | 83.54 | 123.21 | |
Exterior Lighting Total | 7857.24 | 123.21 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16065.81 | 12831.12 | 3234.69 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35969.76 | 27380.54 | 8589.22 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15312.7 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 34454.8 | 14.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 77761.74 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25120.57 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 67203.84 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.89 | 175.82 | 92.91 | 1.00 | 3.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.97 | 1106.52 | 1140.11 | 1.00 | 1.37 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.95 | 2136.07 | 1094.51 | 1.00 | 1.29 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9726.99 | 11672.39 | 49.28 | 0.809 | 0.971 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00813 | 25.13 | 0.00838 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 25092.44 | 30110.93 | 21.61 | 1.626 | 1.952 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00803 | 26.40 | 0.00838 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00382 | 26.40 | 0.00838 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9434.04 | 11320.85 | 47.79 | 0.268 | 0.321 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00787 | -4.30 | 0.00266 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27742.40 | 33290.87 | 23.89 | 0.663 | 0.796 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00687 | -4.30 | 0.00266 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 64801.45 | 77761.74 | 24.26 | 1.577 | 1.892 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00771 | -4.30 | 0.00266 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.97 | 0.97 | 0.32 | 0.32 | 0.9705 | 0.9705 | 0.9705 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.95 | 1.95 | 0.80 | 0.80 | 1.9516 | 1.9516 | 1.9516 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 77761.743 | 77761.743 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 77761.74 | 77761.74 | 1.892321 | 2.62 | 2.62 | 0.00510243 | 43.33 | 26.97 | 0.01600000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 9.99 | 0.00771113 | 99.9996 | 77761.74 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16065.810 | 0.000 | 0.970540 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16065.81 | 15615.30 | 0.970540 | 24.03 | 15.98 | 0.00815592 | 12.00 | 11.16 | 0.00800000 | 25.13 | 0.00838408 | 16.56 | 10.5390 | 23.90 | 0.00812904 | 43.5815 | 9726.99 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25120.567 | 25120.567 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25120.57 | 25120.57 | 0.970535 | 12.98 | 9.69 | 0.00620957 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 10.5390 | 21.10 | 0.00787000 | 50.0400 | 9434.04 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 35969.760 | 0.000 | 1.951630 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 35969.76 | 35393.73 | 1.951630 | 26.63 | 16.85 | 0.00810475 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00838408 | 17.00 | 21.7619 | 26.70 | 0.00802705 | 36.4381 | 25092.44 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 67203.844 | 67203.844 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67203.84 | 67203.84 | 1.951630 | 4.96 | 3.89 | 0.00462035 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.7620 | 15.56 | 0.00686779 | 61.9321 | 27742.40 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 77761.743 | 77761.743 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1914 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.892321 | 2.25445770 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 77761.74 | 77761.74 | 1.0000 | 2.25445770 | 1.892321 | 2.62 | 2.62 | 0.00510243 | 15413.5 | 43.33 | 26.97 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77761.74 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 9.99 | 0.00771113 | 9.99 | 0.00771113 | 99.9996 | 77761.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16065.810 | 0.000 | 0.970540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0015 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16065.81 | 15615.30 | 1.0000 | 1.15627419 | 0.970540 | 24.03 | 15.98 | 0.00815592 | 44907.1 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16065.81 | 25.13 | 0.00838408 | 16.56 | 0.10228487 | 10.5390 | 23.90 | 0.00812904 | 23.90 | 0.00812904 | 43.5815 | 9726.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25120.567 | 25120.567 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.970535 | 1.15626881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25120.57 | 25120.57 | 1.0000 | 1.15626881 | 0.970535 | 12.98 | 9.69 | 0.00620957 | 28717.9 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25120.57 | -4.30 | 0.00265759 | -4.30 | 0.10228487 | 10.5390 | 21.05 | 0.00787000 | 21.10 | 0.00787000 | 50.0400 | 9434.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35969.760 | 0.000 | 1.951630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9063 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 35969.76 | 35393.73 | 1.0000 | 2.32511736 | 1.951630 | 26.63 | 16.85 | 0.00810475 | 47434.4 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35969.76 | 26.40 | 0.00838408 | 17.00 | 0.42471267 | 21.7619 | 26.70 | 0.00802705 | 26.70 | 0.00802705 | 36.4381 | 25092.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67203.844 | 67203.844 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.951630 | 2.32511684 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67203.84 | 67203.84 | 1.0000 | 2.32511684 | 1.951630 | 4.96 | 3.89 | 0.00462035 | 16579.3 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67203.84 | -4.30 | 0.00265759 | -4.30 | 0.42471267 | 21.7620 | 15.56 | 0.00686779 | 15.56 | 0.00686779 | 61.9321 | 27742.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2134.00 | 3373.67 | 2080.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2134.00 | 3373.67 | 2080.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 63.17 | 9.50 | 59.83 | 0.00 |
ZONE2 FINE STORAGE | 364.50 | 0.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 414.50 | 9.83 | 59.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.344 | 0.237 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
Electricity:Building | 621.24 | 4992.32 | 01-JAN-00:10 | 45732.65 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 421.65 | 2759.73 | 01-JAN-00:10 | 31657.83 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.99 | 483.00 | 11-MAY-05:10 | 2497.92 | 14-FEB-12:20 |
WaterSystems:Electricity | 26.99 | 483.00 | 11-MAY-05:10 | 2497.92 | 14-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 26.99 | 483.00 | 11-MAY-05:10 | 2497.92 | 14-FEB-12:20 |
Fans:Electricity | 42.72 | 0.00 | 06-JAN-18:40 | 3418.40 | 04-JAN-08:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
ElectricityNet:Plant | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 816.94 | 5475.32 | 15-JAN-10:50 | 57943.87 | 22-JUL-15:00 |
Electricity:HVAC | 45.49 | 0.00 | 06-JAN-18:40 | 10492.96 | 22-JUL-15:10 |
General:Fans:Electricity | 42.72 | 0.00 | 06-JAN-18:40 | 3418.40 | 04-JAN-08:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.77 | 0.00 | 01-JAN-00:10 | 7250.37 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 275.40 | 0.00 | 06-JAN-18:40 | 143188.34 | 10-JAN-06:10 |
Gas:HVAC | 275.40 | 0.00 | 06-JAN-18:40 | 143188.34 | 10-JAN-06:10 |
Heating:Gas | 275.40 | 0.00 | 06-JAN-18:40 | 143188.34 | 10-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 430.28 | 0.00 | 06-JAN-18:40 | 220530.20 | 10-JAN-06:10 |
EnergyTransfer:Building | 219.24 | 0.00 | 06-JAN-18:40 | 109797.68 | 10-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 33.69 | 0.00 | 01-JAN-00:10 | 17563.43 | 10-JAN-06:10 |
Heating:EnergyTransfer | 193.35 | 0.00 | 06-JAN-18:40 | 109797.68 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.83 | 0.00 | 01-JAN-00:10 | 17563.43 | 10-JAN-06:10 |
Cooling:EnergyTransfer | 25.89 | 0.00 | 01-JAN-00:10 | 21780.05 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.86 | 0.00 | 01-JAN-00:10 | 6825.69 | 22-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 104.73 | 0.00 | 01-JAN-00:40 | 38117.79 | 30-DEC-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 87.70 | 0.00 | 01-JAN-00:40 | 38117.79 | 30-DEC-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.03 | 0.00 | 01-JAN-00:10 | 15249.33 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.82 | 0.00 | 02-JAN-08:40 | 59976.34 | 10-JAN-06:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.82 | 0.00 | 02-JAN-08:40 | 59976.34 | 10-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 211.04 | 0.00 | 06-JAN-18:40 | 110732.51 | 10-JAN-06:10 |
HeatingCoils:EnergyTransfer | 199.66 | 0.00 | 06-JAN-18:40 | 110732.51 | 10-JAN-06:10 |
CoolingCoils:EnergyTransfer | 11.38 | 0.00 | 01-JAN-00:10 | 26850.01 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 24.829 | -8.856 | 0.000 | 0.000 | 3.984 | 30.994 | 31.946 | 7.986 | 0.000 | 0.017 | 0.000 | 0.000 | -9.376 | 0.000 | -15.827 | -65.696 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 87.697 | -17.031 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.019 | 0.000 | 0.000 | 0.000 | 0.000 | -81.895 | -125.446 |
ZONE3 BULK STORAGE | 80.821 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 27.798 | 0.000 | 0.190 | 0.000 | 0.000 | -18.575 | 0.000 | -293.834 | -218.046 |
Total Facility | 80.821 | 0.000 | 112.526 | -25.888 | 0.000 | 0.000 | 3.984 | 481.960 | 139.282 | 35.784 | 0.000 | 0.227 | 0.000 | 0.000 | -27.951 | 0.000 | -391.557 | -409.189 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 21-JUL-17:12 | 0.00 | 0.00 | 0.00 | -13808.59 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 3288.00 | 0.00 | 121.57 | 9366.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-11:31 | 0.00 | 0.00 | 0.00 | -35951.94 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37045.33 | 0.00 | -0.00 | 0.00 | -2293.28 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-17:12 | 0.00 | 0.00 | 0.00 | -47442.31 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 5582.88 | 0.00 | 132.17 | 35737.94 | 0.00 | 0.00 | 0.00 | -1053.04 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-NOV-06:01 | 0.00 | 0.00 | 24694.00 | 0.00 | 0.00 | 0.00 | 56.49 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -326.20 | 0.00 | -198.23 | -25386.25 |
ZONE2 FINE STORAGE | 30-DEC-00:02 | 0.00 | 0.00 | 69554.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8554.17 | -62200.33 |
ZONE3 BULK STORAGE | 10-JAN-05:52 | 59992.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1794.55 | 0.00 | -26818.39 | -36189.54 |
Total Facility | 10-JAN-06:01 | 58640.10 | 0.00 | 91258.52 | 0.00 | 0.00 | 0.00 | 58.99 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2587.24 | 0.00 | -34922.33 | -119617.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9705 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9705 | 0.1054 | 1.0000 | 0.1023 | 0.1054 | ||
PSZ-FINE STORAGE | 1.9516 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.9516 | 0.2176 | 1.0000 | 0.4247 | 0.2176 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9705 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9705 | 1.0000 | 1.0000 | 0.1023 | 0.1054 | ||
PSZ-FINE STORAGE | 1.9516 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.9516 | 1.0000 | 1.0000 | 0.4247 | 0.2176 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9705 | 0.9705 | 0.9705 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.9516 | 1.9516 | 1.9516 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9705 | 0.9705 | 0.9705 | 0.9705 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9516 | 1.9516 | 1.9516 | 1.9516 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9705 | 0.9705 | 0.9705 | 0.1023 | 0.3186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.9516 | 1.9516 | 1.9516 | 0.4247 | 0.5338 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9705 | 0.9705 | 0.9705 | 0.9705 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9516 | 1.9516 | 1.9516 | 1.9516 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 59.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 59.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 275.40 | 143188.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 2.77 | 7250.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.21 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.72 | 3418.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.99 | 2497.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 816.94 |
Natural Gas | 0.00 | 275.40 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1092.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 0.57 |
Fans (All) | 8.84 |
Service Water Heating | 5.58 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 168.96 |
Subtotal | 168.96 |
Natural Gas [MJ/m2] | |
Space Heating | 56.96 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 56.96 |
Subtotal | 56.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 44.12 |
Space Heating | 25.21 |
Space Cooling | 0.25 |
Fans (All) | 3.91 |
Service Water Heating | 2.47 |
Receptacle Equipment | 12.75 |
Miscellaneous | 11.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.627293E+11 |
February | 0.000 | 0.475732E+11 |
March | 0.000 | 0.249023E+11 |
April | 0.000 | 0.453306E+10 |
May | 0.000 | 0.278802E+10 |
June | 0.000 | 0.249956E+09 |
July | 0.000 | 0.745188E+08 |
August | 0.000 | 7138732.534 |
September | 0.000 | 0.361889E+09 |
October | 0.000 | 0.785057E+10 |
November | 0.000 | 0.333855E+11 |
December | 0.000 | 0.909459E+11 |
Annual Sum or Average | 0.275401E+12 | |
Minimum of Months | 0.000 | 7138732.534 |
Maximum of Months | 0.000 | 0.909459E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3545715.13 | 467.97 | 19-JAN-15:40 | 8.33 | 7.46 | 0.195003E+09 | 236.59 | 19-JAN-15:39 | 8.33 | 7.46 |
February | 3825780.33 | 475.59 | 04-FEB-15:30 | 8.00 | 6.07 | 0.179380E+09 | 236.59 | 18-FEB-10:09 | 5.00 | 4.09 |
March | 3191805.47 | 282.11 | 23-MAR-16:00 | 10.00 | 6.64 | 0.210770E+09 | 249.90 | 25-MAR-13:50 | 12.33 | 9.61 |
April | 0.261300E+09 | 6052.24 | 29-APR-17:25 | 20.00 | 12.53 | 0.210312E+09 | 301.59 | 28-APR-15:09 | 20.08 | 13.46 |
May | 0.475025E+09 | 7111.96 | 24-MAY-17:33 | 14.33 | 10.70 | 0.225652E+09 | 301.60 | 25-MAY-15:00 | 18.00 | 13.89 |
June | 0.154200E+10 | 13275.40 | 13-JUN-17:10 | 26.48 | 17.36 | 0.250033E+09 | 301.60 | 13-JUN-15:09 | 26.08 | 17.79 |
July | 0.265854E+10 | 13808.54 | 21-JUL-17:12 | 26.67 | 16.46 | 0.245855E+09 | 301.60 | 12-JUL-15:50 | 21.67 | 15.73 |
August | 0.267132E+10 | 11971.96 | 14-AUG-17:10 | 27.00 | 14.26 | 0.266309E+09 | 301.60 | 19-AUG-15:00 | 20.00 | 15.65 |
September | 0.117081E+10 | 7550.49 | 13-SEP-17:15 | 21.33 | 15.42 | 0.240019E+09 | 302.21 | 23-SEP-08:00 | 17.00 | 13.95 |
October | 56521563.50 | 1452.58 | 07-OCT-16:00 | 18.00 | 9.64 | 0.204118E+09 | 301.58 | 04-OCT-15:00 | 14.00 | 10.27 |
November | 10061827.08 | 513.97 | 04-NOV-16:00 | 7.00 | 5.55 | 0.187485E+09 | 254.22 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 | 3.53 | 0.194977E+09 | 236.59 | 04-DEC-16:00 | 8.00 | 6.47 |
Annual Sum or Average | 0.885614E+10 | 0.260991E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.179380E+09 | 236.59 | 5.00 | 4.09 | ||
Maximum of Months | 0.267132E+10 | 13808.54 | 27.00 | 17.36 | 0.266309E+09 | 302.21 | 26.08 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817709E+09 | 3865.86 | 21-JAN-11:00 | 5.00 | 4.51 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.125221E+10 | 3953.80 | 23-FEB-15:30 | 4.50 | 4.26 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.155391E+10 | 3686.02 | 08-MAR-13:00 | 4.00 | 2.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.181645E+10 | 8587.60 | 22-APR-06:10 | 7.17 | 5.78 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.196630E+10 | 6484.97 | 04-MAY-06:10 | 7.33 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.200448E+10 | 8709.55 | 21-JUN-06:10 | 13.67 | 12.04 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.244397E+10 | 35954.51 | 23-JUL-11:31 | 21.00 | 15.98 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.153514E+10 | 8870.70 | 01-AUG-06:10 | 13.50 | 12.18 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.113290E+10 | 8153.50 | 08-SEP-06:10 | 8.33 | 7.70 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.104674E+10 | 5451.13 | 13-OCT-06:10 | 10.00 | 10.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.998656E+09 | 4560.28 | 09-NOV-07:10 | 9.00 | 9.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.462741E+09 | 3019.53 | 06-DEC-10:30 | 5.50 | 4.15 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.170312E+11 | 0.00 | ||||||||
Minimum of Months | 0.462741E+09 | 3019.53 | 4.00 | 2.71 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.244397E+10 | 35954.51 | 21.00 | 15.98 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 | 5.79 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 | 1.83 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.461463E+10 | 24359.20 | 17-JAN-06:01 | 6.07 |
February | 0.375857E+10 | 24356.72 | 22-FEB-06:01 | 6.83 |
March | 0.378112E+10 | 24519.51 | 18-MAR-05:01 | 9.00 |
April | 0.139435E+10 | 24197.44 | 10-APR-05:01 | 6.17 |
May | 0.943356E+09 | 24445.65 | 19-MAY-05:01 | 9.00 |
June | 0.180953E+09 | 23930.59 | 08-JUN-05:01 | 6.17 |
July | 61574375.58 | 23782.27 | 05-JUL-05:01 | 7.33 |
August | 17696595.47 | 1568.38 | 24-AUG-06:10 | 8.83 |
September | 0.241341E+09 | 23754.39 | 07-SEP-05:02 | 8.83 |
October | 0.174024E+10 | 24659.90 | 20-OCT-05:01 | 11.00 |
November | 0.329617E+10 | 24693.92 | 24-NOV-06:01 | 10.17 |
December | 0.479907E+10 | 24500.29 | 28-DEC-06:32 | 1.00 |
Annual Sum or Average | 0.248291E+11 | |||
Minimum of Months | 17696595.47 | 1568.38 | 1.00 | |
Maximum of Months | 0.479907E+10 | 24693.92 | 11.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175947E+11 | 69467.40 | 10-JAN-05:22 | -4.0 |
February | 0.153434E+11 | 68604.13 | 18-FEB-00:53 | -2.0 |
March | 0.104058E+11 | 68193.44 | 04-MAR-05:23 | 3.00 |
April | 0.165655E+10 | 61949.00 | 06-APR-05:07 | 4.17 |
May | 0.103880E+10 | 49580.63 | 20-MAY-05:01 | 4.50 |
June | 0.161824E+09 | 2277.13 | 28-JUN-07:00 | 11.00 |
July | 0.168461E+09 | 2245.88 | 11-JUL-07:00 | 13.00 |
August | 0.167550E+09 | 2285.98 | 19-AUG-07:00 | 12.00 |
September | 0.198040E+09 | 2200.98 | 27-SEP-06:50 | 9.67 |
October | 0.355475E+10 | 67159.03 | 30-OCT-05:05 | 7.00 |
November | 0.131786E+11 | 68599.64 | 28-NOV-22:03 | 0.67 |
December | 0.242294E+11 | 69554.46 | 30-DEC-00:02 | -2.8 |
Annual Sum or Average | 0.876979E+11 | |||
Minimum of Months | 0.161824E+09 | 2200.98 | -4.0 | |
Maximum of Months | 0.242294E+11 | 69554.46 | 13.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214980E+11 | 59992.76 | 10-JAN-05:52 | -4.0 |
February | 0.143954E+11 | 43120.89 | 17-FEB-04:00 | -2.0 |
March | 0.212723E+10 | 21737.44 | 04-MAR-05:53 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.652355E+10 | 39027.27 | 29-NOV-03:54 | -1.0 |
December | 0.362770E+11 | 59428.04 | 30-DEC-01:00 | -2.0 |
Annual Sum or Average | 0.808211E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.362770E+11 | 59992.76 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151657E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143321E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144876E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110061E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2181.34 | 0.156605E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4635278.04 | 0.124332E+10 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9290300.62 | 0.103964E+10 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3406801.86 | 0.941947E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981928E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119837E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151701E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183975E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 17334561.86 | 0.158272E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941947E+09 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9290300.62 | 0.183975E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421605E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584913E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376675E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421052E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101385E+11 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290174.17 | 0.905935E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17979666.24 | 0.885945E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737493.67 | 0.736289E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615874E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510044E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694303E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102302E+11 |
Annual Sum or Average | 0.136656E+12 | 19007334.08 | 0.818950E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376675E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17979666.24 | 0.102302E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30492991.00 | 0.855492E+10 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113535E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796616E+10 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9319390.20 | 0.127309E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17819743.49 | 0.316886E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19241591.25 | 0.293227E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9555844.51 | 0.296000E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6908522.98 | 0.249487E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318716.59 | 0.201055E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138046E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36712774.71 | 0.123694E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13082087.26 | 0.180879E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.143452E+09 | 0.220533E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796616E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36712774.71 | 0.316886E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6602.62 | 10-JAN-18:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5790.08 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5084.36 | 31-MAR-07:00 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4145.48 | 19-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 22-MAY-15:00 | 4699.51 | 01-MAY-16:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 738.36 | 13-JUN-17:00 | 3718.48 | 08-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.00 | 21-JUL-17:00 | 2951.28 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 724.33 | 14-AUG-17:00 | 2919.20 | 24-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3761.16 | 20-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4572.71 | 04-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5888.00 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5973.52 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2919.20 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.00 | 6602.62 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14734.97 | 10-JAN-18:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9305.98 | 01-FEB-16:10 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 14858.84 | 31-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 8898.39 | 24-APR-15:05 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 18862.58 | 01-MAY-15:03 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.73 | 13-JUN-17:00 | 12463.78 | 07-JUN-15:05 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.44 | 22-JUL-15:10 | 9694.84 | 30-JUL-19:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.61 | 14-AUG-18:00 | 11620.62 | 22-AUG-16:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11983.82 | 29-SEP-15:05 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8577.05 | 31-OCT-15:05 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12996.40 | 15-NOV-07:10 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21636.44 | 02-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8577.05 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.44 | 21636.44 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4389.09 | 29-JAN-06:00 | 31515.91 | 10-JAN-16:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 16444.78 | 01-FEB-16:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27720.66 | 31-MAR-08:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.88 | 30-APR-19:00 | 23678.21 | 24-APR-12:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.78 | 22-MAY-15:00 | 52101.17 | 01-MAY-13:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2068.97 | 12-JUN-18:00 | 35291.10 | 07-JUN-15:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.27 | 22-JUL-19:00 | 30972.55 | 01-JUL-12:10 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1422.50 | 14-AUG-18:00 | 34240.88 | 22-AUG-16:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.79 | 24-SEP-16:00 | 27249.45 | 29-SEP-15:05 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22342.93 | 01-OCT-24:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6444.82 | 24-NOV-12:00 | 18968.82 | 28-NOV-08:70 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5920.14 | 23-DEC-11:00 | 26117.65 | 28-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16444.78 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6444.82 | 52101.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 467.97 | 19-JAN-15:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.13 |
February | 475.59 | 04-FEB-15:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.13 |
March | 282.11 | 23-MAR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.93 |
April | 6052.24 | 29-APR-17:25 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7111.96 | 24-MAY-17:33 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.62 |
June | 13275.40 | 13-JUN-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 | 0.00 |
July | 13808.54 | 21-JUL-17:12 | 0.00 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 121.57 | 0.00 |
August | 11971.96 | 14-AUG-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 147.27 | 0.00 |
September | 7550.49 | 13-SEP-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 |
October | 1452.58 | 07-OCT-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 513.97 | 04-NOV-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.01 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13808.54 | 659.25 | 2753.73 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 147.27 | 813.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3865.86 | 21-JAN-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3953.80 | 23-FEB-15:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.75 |
March | 3686.02 | 08-MAR-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.42 |
April | 8587.60 | 22-APR-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6484.97 | 04-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.47 |
June | 8709.55 | 21-JUN-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35954.51 | 23-JUL-11:31 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2293.28 |
August | 8870.70 | 01-AUG-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.61 |
September | 8153.50 | 08-SEP-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.28 |
October | 5451.13 | 13-OCT-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4560.28 | 09-NOV-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3019.53 | 06-DEC-10:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 981.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3019.53 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35954.51 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2293.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3955.70 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3089.90 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4443.42 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9803.92 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11806.84 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20242.11 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.37 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11130.08 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15306.68 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5815.85 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3153.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 11038.92 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20242.11 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.714141E+11 | 54705.70 | 07-JAN-08:09 | 0.627293E+11 | 143188.34 | 10-JAN-06:10 |
February | 0.641440E+11 | 50966.37 | 15-FEB-13:20 | 0.475732E+11 | 98535.06 | 18-FEB-06:19 |
March | 0.717622E+11 | 50957.45 | 01-MAR-15:00 | 0.249023E+11 | 77667.89 | 04-MAR-06:10 |
April | 0.657251E+11 | 51744.53 | 29-APR-14:00 | 0.453306E+10 | 32196.21 | 01-APR-05:10 |
May | 0.668666E+11 | 51816.27 | 22-MAY-14:00 | 0.278802E+10 | 33093.63 | 06-MAY-05:10 |
June | 0.657371E+11 | 55039.08 | 13-JUN-14:00 | 0.249956E+09 | 11729.30 | 08-JUN-05:10 |
July | 0.655989E+11 | 57943.87 | 22-JUL-14:00 | 74518819.82 | 9464.82 | 05-JUL-05:10 |
August | 0.699362E+11 | 53699.13 | 14-AUG-14:00 | 7138732.53 | 1959.12 | 24-AUG-06:19 |
September | 0.667345E+11 | 52130.77 | 13-SEP-14:00 | 0.361889E+09 | 8196.41 | 07-SEP-05:10 |
October | 0.688995E+11 | 51190.79 | 07-OCT-14:00 | 0.785057E+10 | 34587.03 | 23-OCT-05:19 |
November | 0.680884E+11 | 54492.31 | 30-NOV-16:40 | 0.333855E+11 | 103910.70 | 28-NOV-06:10 |
December | 0.720313E+11 | 54704.98 | 28-DEC-08:09 | 0.909459E+11 | 122291.01 | 28-DEC-06:49 |
Annual Sum or Average | 0.816938E+12 | 0.275401E+12 | ||||
Minimum of Months | 0.641440E+11 | 50957.45 | 7138732.53 | 1959.12 | ||
Maximum of Months | 0.720313E+11 | 57943.87 | 0.909459E+11 | 143188.34 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.134689E+11 | 0.115358E+11 | 0.00 | 0.398806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231805E+10 | 0.00 |
February | 0.366966E+11 | 0.110834E+11 | 0.105871E+11 | 0.00 | 0.366377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211313E+10 | 0.00 |
March | 0.423649E+11 | 0.107864E+11 | 0.123357E+11 | 0.00 | 0.389456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238067E+10 | 0.00 |
April | 0.397216E+11 | 0.893840E+10 | 0.114862E+11 | 0.00 | 0.328723E+10 | 0.00 | 0.00 | 45895391.37 | 0.00 | 0.00 | 0.00 | 0.224578E+10 | 0.00 |
May | 0.412341E+11 | 0.792010E+10 | 0.119357E+11 | 0.00 | 0.338644E+10 | 0.00 | 0.00 | 89539651.32 | 0.00 | 0.00 | 0.00 | 0.230063E+10 | 0.00 |
June | 0.408524E+11 | 0.696309E+10 | 0.118862E+11 | 0.00 | 0.335151E+10 | 0.00 | 0.00 | 0.463519E+09 | 0.00 | 0.00 | 0.00 | 0.222042E+10 | 0.00 |
July | 0.401034E+11 | 0.750524E+10 | 0.115358E+11 | 0.00 | 0.325384E+10 | 0.00 | 0.00 | 0.980920E+09 | 0.00 | 0.00 | 0.00 | 0.221972E+10 | 0.00 |
August | 0.423649E+11 | 0.865082E+10 | 0.123357E+11 | 0.00 | 0.348286E+10 | 0.00 | 0.00 | 0.831803E+09 | 0.00 | 0.00 | 0.00 | 0.227014E+10 | 0.00 |
September | 0.397216E+11 | 0.978698E+10 | 0.114862E+11 | 0.00 | 0.321542E+10 | 0.00 | 0.00 | 0.349483E+09 | 0.00 | 0.00 | 0.00 | 0.217483E+10 | 0.00 |
October | 0.401034E+11 | 0.116539E+11 | 0.115358E+11 | 0.00 | 0.334958E+10 | 0.00 | 0.00 | 6182981.73 | 0.00 | 0.00 | 0.00 | 0.225074E+10 | 0.00 |
November | 0.385909E+11 | 0.126250E+11 | 0.110862E+11 | 0.00 | 0.358770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219861E+10 | 0.00 |
December | 0.401034E+11 | 0.138319E+11 | 0.115358E+11 | 0.00 | 0.425859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230166E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123214E+12 | 0.139282E+12 | 0.427196E+11 | 0.00 | 0.276734E+10 | 0.269944E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.696309E+10 | 0.105871E+11 | 0.00 | 0.321542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211313E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.138319E+11 | 0.123357E+11 | 0.00 | 0.425859E+10 | 0.00 | 0.00 | 0.980920E+09 | 0.00 | 0.00 | 0.00 | 0.238067E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.627293E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.475732E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.249023E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453306E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.278802E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.249956E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 74518819.82 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7138732.53 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.361889E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.785057E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.333855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.909459E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275401E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 7138732.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.909459E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3418.40 | 04-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3418.40 | 18-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3418.40 | 04-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3242.59 | 01-APR-06:49 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3242.59 | 05-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3242.59 | 13-JUN-12:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3242.59 | 10-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3242.59 | 05-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3242.59 | 13-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3242.59 | 04-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3418.40 | 17-NOV-07:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3418.40 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3242.59 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3418.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2490.01 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2497.92 | 14-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2489.90 | 01-MAR-12:50 | 0.00 |
April | 1016.45 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2427.88 | 03-APR-11:00 | 0.00 |
May | 1097.83 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2330.25 | 02-MAY-11:30 | 0.00 |
June | 4738.50 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2206.60 | 01-JUN-11:50 | 0.00 |
July | 7250.37 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2082.97 | 05-JUL-11:00 | 0.00 |
August | 3285.55 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2023.01 | 01-AUG-11:00 | 0.00 |
September | 1433.96 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2088.27 | 29-SEP-11:00 | 0.00 |
October | 455.28 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 2214.20 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2333.22 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2432.86 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2023.01 | 0.00 | ||
Maximum of Months | 7250.37 | 0.00 | 0.00 | 0.00 | 2497.92 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54705.70 | 07-JAN-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3418.40 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50966.37 | 15-FEB-13:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50957.45 | 01-MAR-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51744.53 | 29-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 962.85 | 0.00 |
May | 51816.27 | 22-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 1041.91 | 0.00 |
June | 55039.08 | 13-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 4461.19 | 0.00 |
July | 57943.87 | 22-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 7185.35 | 0.00 |
August | 53699.13 | 14-AUG-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 2942.16 | 0.00 |
September | 52130.77 | 13-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 1371.72 | 0.00 |
October | 51190.79 | 07-OCT-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 426.68 | 0.00 |
November | 54492.31 | 30-NOV-16:40 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54704.98 | 28-DEC-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3418.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50957.45 | 31660.41 | 10112.62 | 0.00 | 0.00 | 3242.59 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57943.87 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 3418.40 | 0.00 | 0.00 | 7185.35 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 143188.34 | 10-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 98535.06 | 18-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 77667.89 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 32196.21 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 33093.63 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 11729.30 | 08-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 9464.82 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1959.12 | 24-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 8196.41 | 07-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 34587.03 | 23-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 103910.70 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 122291.01 | 28-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1959.12 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 143188.34 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 19.08 | 8.33 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.67 | 19.13 | 8.17 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9.00 | 19.77 | 9.00 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.67 | 20.16 | 5.67 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4.50 | 20.32 | 4.50 | 20.32 | 0.33 | 24.52 | 0.00 | 0.00 |
June | 0.33 | 20.46 | 0.33 | 20.46 | 0.67 | 24.55 | 0.00 | 0.00 |
July | 0.17 | 20.52 | 0.17 | 20.52 | 4.33 | 24.55 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.51 | 0.00 | 0.00 |
September | 0.50 | 20.50 | 0.50 | 20.50 | 0.17 | 24.52 | 0.00 | 0.00 |
October | 6.33 | 20.20 | 6.33 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.83 | 19.87 | 7.83 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.67 | 18.74 | 9.00 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 19.55 | 59.83 | 19.80 | 9.50 | 24.53 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 20.52 | 9.00 | 20.52 | 4.33 | 24.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.83 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79.17 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42.50 | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.33 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.83 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9.00 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102.50 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 364.50 | 14.72 | 0.00 | 0.33 | 27.26 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.50 | 14.97 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.07 | 324.00 | 21.07 | 324.00 | 21.07 |
April | 300.00 | 21.79 | 196.83 | 21.18 | 196.83 | 21.18 |
May | 309.17 | 22.08 | 137.50 | 21.15 | 137.50 | 21.15 |
June | 276.50 | 23.14 | 23.50 | 21.81 | 17.67 | 21.13 |
July | 188.00 | 23.41 | 40.33 | 23.49 | 5.83 | 21.09 |
August | 227.67 | 23.48 | 13.00 | 23.90 | 0.00 | 0.00 |
September | 284.33 | 23.16 | 22.67 | 21.10 | 22.67 | 21.10 |
October | 300.00 | 21.50 | 214.17 | 21.11 | 214.17 | 21.11 |
November | 288.00 | 21.08 | 286.00 | 21.07 | 286.00 | 21.07 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3373.67 | 21.90 | 2134.00 | 21.15 | 2080.67 | 21.08 |
Minimum of Months | 188.00 | 21.05 | 13.00 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.48 | 324.00 | 23.90 | 324.00 | 21.18 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.188894E+09 | 45895391.37 | 30.83 | 0.188878E+09 | 15237.51 | 0.00 | 0.50 | 29-APR-17:25 | 0.00 | 01-APR-00:05 | 6596.44 | 29-APR-17:25 | 6596.44 | 29-APR-17:25 | 4.00 | 28-APR-10:00 | 1637.94 | 29-APR-17:25 | 0.00 | 01-APR-00:05 |
May | 0.369412E+09 | 89539651.32 | 53.81 | 0.342639E+09 | 26772941.46 | 0.00 | 0.55 | 24-MAY-17:33 | 0.00 | 01-MAY-00:10 | 7448.74 | 24-MAY-17:33 | 7448.74 | 24-MAY-17:33 | 514.06 | 23-MAY-16:00 | 1822.54 | 24-MAY-17:33 | 0.00 | 01-MAY-00:10 |
June | 0.177266E+10 | 0.426422E+09 | 182.83 | 0.159124E+10 | 0.181417E+09 | 0.00 | 1.00 | 13-JUN-17:10 | 0.00 | 01-JUN-00:10 | 16289.31 | 13-JUN-17:10 | 15380.82 | 13-JUN-17:10 | 2164.40 | 26-JUN-17:15 | 3591.58 | 13-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.326038E+10 | 0.783953E+09 | 255.76 | 0.295390E+10 | 0.306476E+09 | 0.00 | 1.00 | 21-JUL-17:10 | 0.00 | 01-JUL-00:10 | 16890.01 | 24-JUL-00:03 | 15767.40 | 21-JUL-17:12 | 2750.88 | 24-JUL-00:03 | 3628.84 | 22-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.341200E+10 | 0.816391E+09 | 272.22 | 0.307516E+10 | 0.336841E+09 | 0.00 | 0.92 | 14-AUG-17:10 | 0.00 | 01-AUG-00:10 | 13898.23 | 14-AUG-17:10 | 13898.23 | 14-AUG-17:10 | 1332.21 | 17-AUG-17:10 | 3205.49 | 14-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.145067E+10 | 0.349483E+09 | 170.22 | 0.131217E+10 | 0.138505E+09 | 0.00 | 0.60 | 13-SEP-17:15 | 0.00 | 01-SEP-00:10 | 8498.91 | 13-SEP-17:15 | 8279.84 | 13-SEP-17:15 | 735.31 | 12-SEP-14:20 | 2041.03 | 13-SEP-17:15 | 0.00 | 01-SEP-00:10 |
October | 25090809.54 | 6182981.73 | 9.83 | 25072394.36 | 18415.17 | 0.00 | 0.14 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 | 1863.92 | 07-OCT-15:40 | 1863.92 | 07-OCT-15:40 | 5.50 | 02-OCT-15:30 | 455.28 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.104791E+11 | 0.251787E+10 | 975.51 | 0.948906E+10 | 0.990045E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.341200E+10 | 0.816391E+09 | 272.22 | 0.307516E+10 | 0.336841E+09 | 0.00 | 1.00 | 0.00 | 16890.01 | 15767.40 | 2750.88 | 3628.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.135398E+09 | 37097485.21 | 6.00 | 0.117392E+09 | 18005583.54 | 0.00 | 0.31 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 10427.15 | 13-JUN-16:00 | 9355.38 | 13-JUN-16:00 | 1356.76 | 13-JUN-15:00 | 2861.35 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.710969E+09 | 0.196967E+09 | 28.76 | 0.694710E+09 | 16259707.75 | 0.00 | 1.00 | 21-JUL-17:12 | 0.00 | 01-JUL-00:10 | 38173.28 | 23-JUL-16:31 | 36237.52 | 21-JUL-17:12 | 10175.70 | 23-JUL-16:31 | 9234.00 | 22-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 55043660.94 | 15412275.73 | 13.50 | 52831237.12 | 2212423.82 | 0.00 | 0.18 | 14-AUG-16:40 | 0.00 | 01-AUG-00:10 | 5639.96 | 14-AUG-16:00 | 5639.96 | 14-AUG-16:00 | 387.38 | 14-AUG-14:30 | 1600.42 | 14-AUG-16:40 | 0.00 | 01-AUG-00:10 |
September | 13.06 | 3.61 | 0.83 | 11.40 | 1.66 | 0.00 | 0.00 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 0.01 | 13-SEP-14:20 | 0.00 | 13-SEP-14:20 | 0.00 | 13-SEP-14:20 | 0.00 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.901411E+09 | 0.249477E+09 | 49.10 | 0.864933E+09 | 36477716.77 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.710969E+09 | 0.196967E+09 | 28.76 | 0.694710E+09 | 18005583.54 | 0.00 | 1.00 | 0.00 | 38173.28 | 36237.52 | 10175.70 | 9234.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.48 | 129.08 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.92 | 121.29 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.62 | 95.56 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.71 | 82.68 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 186.05 | 72.39 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 213.31 | 63.44 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 225.41 | 62.65 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 189.11 | 69.92 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 147.29 | 81.95 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.93 | 93.06 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 21.19 | 113.44 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.26 | 146.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.87 | 94.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.26 | 62.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 225.41 | 146.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.48 | 129.08 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.92 | 121.29 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.62 | 95.56 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.71 | 82.68 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 186.05 | 72.39 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 213.31 | 63.44 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 225.41 | 62.65 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 189.11 | 69.92 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 147.29 | 81.95 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.93 | 93.06 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 21.19 | 113.44 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.26 | 146.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.87 | 94.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.26 | 62.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 225.41 | 146.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.82 | 79.65 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.94 | 74.20 | 0.00 | 0.00 | 672.00 |
March | 29.69 | 0.00 | 29.69 | 7.87 | 58.32 | 0.00 | 0.00 | 744.00 |
April | 48.40 | 0.26 | 48.14 | 25.77 | 48.96 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.55 | 29.18 | 40.84 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 38.91 | 35.35 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.83 | 34.85 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 31.47 | 40.36 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 21.32 | 48.93 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 8.06 | 55.53 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 1.05 | 68.04 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.02 | 86.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 17.18 | 55.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.02 | 34.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 38.91 | 86.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.82 | 79.65 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.94 | 74.20 | 0.00 | 0.00 | 672.00 |
March | 29.68 | 0.00 | 29.68 | 7.87 | 58.32 | 0.00 | 0.00 | 744.00 |
April | 48.39 | 0.26 | 48.13 | 25.77 | 48.96 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.54 | 29.18 | 40.84 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 38.91 | 35.35 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.83 | 34.85 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 31.47 | 40.36 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 21.32 | 48.93 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 8.06 | 55.53 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 1.05 | 68.04 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.02 | 86.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 17.18 | 55.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.02 | 34.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 38.91 | 86.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.67 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 96.00 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 19.83 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.84 | 56.87 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.49 | 54.26 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.53 | 48.42 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.98 | 62.11 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.44 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.62 | 63.07 | 74.67 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.40 | 55.53 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.15 | 58.89 | 456.33 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 60211757.57 | 0.345739E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.132852E+09 | 0.293422E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.106113E+09 | 0.255958E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.419155E+09 | 0.214295E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.498308E+09 | 0.193882E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.552891E+09 | 0.164435E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.603733E+09 | 0.167796E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.506512E+09 | 0.187273E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.381776E+09 | 0.212426E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.165876E+09 | 0.249243E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54924740.97 | 0.294035E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 14090776.67 | 0.392329E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.349644E+10 | 0.297083E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 14090776.67 | 0.164435E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.603733E+09 | 0.392329E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 60211757.57 | 0.345739E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.132852E+09 | 0.293422E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.106113E+09 | 0.255958E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.419155E+09 | 0.214295E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.498308E+09 | 0.193882E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.552891E+09 | 0.164435E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.603733E+09 | 0.167796E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.506512E+09 | 0.187273E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.381776E+09 | 0.212426E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.165876E+09 | 0.249243E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54924740.97 | 0.294035E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 14090776.67 | 0.392329E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.349644E+10 | 0.297083E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 14090776.67 | 0.164435E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.603733E+09 | 0.392329E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36791156.70 | 0.00 | 36791156.70 | 2208890.05 | 0.213346E+09 |
February | 51891179.80 | 0.00 | 51891179.80 | 4693019.50 | 0.179493E+09 |
March | 79510218.25 | 1082.28 | 79509135.97 | 21068800.88 | 0.156202E+09 |
April | 0.125442E+09 | 672185.46 | 0.124770E+09 | 66789151.08 | 0.126895E+09 |
May | 0.162527E+09 | 8394302.97 | 0.154133E+09 | 78153721.40 | 0.109398E+09 |
June | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.100866E+09 | 91625973.70 |
July | 0.169605E+09 | 9572638.44 | 0.160033E+09 | 0.104005E+09 | 93352316.94 |
August | 0.133998E+09 | 2586120.74 | 0.131412E+09 | 84300289.21 | 0.108106E+09 |
September | 98322315.72 | 57709.22 | 98264606.49 | 55257638.18 | 0.126839E+09 |
October | 65057880.40 | 0.00 | 65057880.40 | 21588524.14 | 0.148737E+09 |
November | 37829128.19 | 0.00 | 37829128.19 | 2718973.77 | 0.176356E+09 |
December | 26620254.24 | 0.00 | 26620254.24 | 52708.99 | 0.232426E+09 |
Annual Sum or Average | 0.116024E+10 | 31825410.22 | 0.112841E+10 | 0.541703E+09 | 0.176278E+10 |
Minimum of Months | 26620254.24 | 0.00 | 26620254.24 | 52708.99 | 91625973.70 |
Maximum of Months | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.104005E+09 | 0.232426E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36789895.72 | 0.00 | 36789895.72 | 2208586.95 | 0.213346E+09 |
February | 51889446.94 | 0.00 | 51889446.94 | 4692330.86 | 0.179493E+09 |
March | 79507385.95 | 1082.23 | 79506303.72 | 21066730.58 | 0.156202E+09 |
April | 0.125438E+09 | 672153.95 | 0.124766E+09 | 66785709.30 | 0.126895E+09 |
May | 0.162522E+09 | 8393909.51 | 0.154128E+09 | 78149308.18 | 0.109398E+09 |
June | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.100861E+09 | 91625774.97 |
July | 0.169600E+09 | 9572189.75 | 0.160028E+09 | 0.104000E+09 | 93352028.59 |
August | 0.133994E+09 | 2585999.52 | 0.131408E+09 | 84296852.85 | 0.108106E+09 |
September | 98319441.92 | 57706.52 | 98261735.41 | 55255258.35 | 0.126838E+09 |
October | 65055758.06 | 0.00 | 65055758.06 | 21587038.63 | 0.148736E+09 |
November | 37827828.36 | 0.00 | 37827828.36 | 2718568.25 | 0.176356E+09 |
December | 26619327.93 | 0.00 | 26619327.93 | 52686.68 | 0.232425E+09 |
Annual Sum or Average | 0.116020E+10 | 31823918.52 | 0.112838E+10 | 0.541674E+09 | 0.176277E+10 |
Minimum of Months | 26619327.93 | 0.00 | 26619327.93 | 52686.68 | 91625774.97 |
Maximum of Months | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.104000E+09 | 0.232425E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49413455.37 | 0.173205E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88600723.97 | 0.151450E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128376E+09 | 0.128516E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346901E+09 | 0.147400E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411111E+09 | 0.145336E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431639E+09 | 0.125507E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451664E+09 | 0.141272E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388327E+09 | 0.166368E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274348E+09 | 0.177394E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130218E+09 | 0.168920E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52878922.95 | 0.143923E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.188000E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277985E+10 | 0.185729E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26372273.86 | 0.125507E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451664E+09 | 0.188000E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.35 | 411.21 | 121.63 | 30.77 | 90.86 | 0.00 | 0.00 |
February | 107.89 | 385.15 | 209.44 | 70.75 | 138.70 | 0.00 | 0.00 |
March | 91.46 | 304.26 | 209.46 | 28.85 | 180.61 | 0.00 | 0.00 |
April | 372.48 | 260.79 | 449.98 | 140.46 | 309.52 | 0.00 | 0.00 |
May | 428.83 | 224.84 | 535.54 | 174.15 | 361.39 | 0.00 | 0.00 |
June | 502.88 | 196.02 | 581.33 | 192.99 | 388.34 | 0.00 | 0.00 |
July | 526.94 | 193.46 | 583.05 | 208.46 | 374.59 | 0.00 | 0.00 |
August | 439.92 | 219.31 | 483.14 | 167.60 | 315.54 | 0.00 | 0.00 |
September | 334.64 | 259.20 | 385.97 | 140.21 | 245.76 | 0.00 | 0.00 |
October | 137.49 | 294.69 | 213.25 | 59.41 | 153.84 | 0.00 | 0.00 |
November | 41.11 | 359.58 | 118.32 | 26.24 | 92.08 | 0.00 | 0.00 |
December | 8.28 | 464.23 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 253.22 | 297.33 | 330.49 | 104.24 | 226.25 | 0.00 | 0.00 |
Minimum of Months | 8.28 | 193.46 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 526.94 | 464.23 | 583.05 | 208.46 | 388.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.49 | 646.67 | 200.87 | 56.92 | 143.96 | 0.00 | 0.00 |
February | 366.24 | 626.04 | 348.12 | 125.15 | 222.96 | 0.00 | 0.00 |
March | 479.30 | 479.82 | 433.46 | 82.42 | 351.04 | 0.00 | 0.00 |
April | 1338.35 | 568.67 | 1049.90 | 560.55 | 489.34 | 0.00 | 0.00 |
May | 1534.91 | 542.62 | 1257.06 | 692.31 | 564.75 | 0.00 | 0.00 |
June | 1665.27 | 484.21 | 1339.19 | 719.68 | 619.50 | 0.00 | 0.00 |
July | 1686.32 | 527.45 | 1357.45 | 787.72 | 569.72 | 0.00 | 0.00 |
August | 1449.85 | 621.15 | 1170.04 | 704.34 | 465.70 | 0.00 | 0.00 |
September | 1058.44 | 684.39 | 863.49 | 513.63 | 349.86 | 0.00 | 0.00 |
October | 486.17 | 630.67 | 443.60 | 194.56 | 249.04 | 0.00 | 0.00 |
November | 204.01 | 555.26 | 219.13 | 65.04 | 154.10 | 0.00 | 0.00 |
December | 98.46 | 701.91 | 139.87 | 35.38 | 104.49 | 0.00 | 0.00 |
Annual Sum or Average | 881.48 | 588.94 | 736.91 | 379.27 | 357.63 | 0.00 | 0.00 |
Minimum of Months | 98.46 | 479.82 | 139.87 | 35.38 | 104.49 | 0.00 | 0.00 |
Maximum of Months | 1686.32 | 701.91 | 1357.45 | 787.72 | 619.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108061E+09 | 0.110139E+10 | 0.325765E+09 | 82409848.99 | 0.243355E+09 | 0.00 | 0.00 |
February | 0.261017E+09 | 0.931757E+09 | 0.506682E+09 | 0.171147E+09 | 0.335535E+09 | 0.00 | 0.00 |
March | 0.244966E+09 | 0.814927E+09 | 0.561028E+09 | 77284367.67 | 0.483744E+09 | 0.00 | 0.00 |
April | 0.965473E+09 | 0.675968E+09 | 0.116634E+10 | 0.364067E+09 | 0.802271E+09 | 0.00 | 0.00 |
May | 0.114857E+10 | 0.602211E+09 | 0.143439E+10 | 0.466452E+09 | 0.967942E+09 | 0.00 | 0.00 |
June | 0.130346E+10 | 0.508072E+09 | 0.150682E+10 | 0.500235E+09 | 0.100658E+10 | 0.00 | 0.00 |
July | 0.141134E+10 | 0.518169E+09 | 0.156164E+10 | 0.558335E+09 | 0.100330E+10 | 0.00 | 0.00 |
August | 0.117827E+10 | 0.587409E+09 | 0.129405E+10 | 0.448906E+09 | 0.845141E+09 | 0.00 | 0.00 |
September | 0.867375E+09 | 0.671840E+09 | 0.100044E+10 | 0.363434E+09 | 0.637010E+09 | 0.00 | 0.00 |
October | 0.368265E+09 | 0.789298E+09 | 0.571168E+09 | 0.159132E+09 | 0.412036E+09 | 0.00 | 0.00 |
November | 0.106548E+09 | 0.932043E+09 | 0.306692E+09 | 68021679.19 | 0.238671E+09 | 0.00 | 0.00 |
December | 22181895.15 | 0.124340E+10 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.798553E+10 | 0.937649E+10 | 0.104223E+11 | 0.328733E+10 | 0.713500E+10 | 0.00 | 0.00 |
Minimum of Months | 22181895.15 | 0.508072E+09 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141134E+10 | 0.124340E+10 | 0.156164E+10 | 0.558335E+09 | 0.100658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.494129E+09 | 0.173205E+10 | 0.538015E+09 | 0.152445E+09 | 0.385570E+09 | 0.00 | 0.00 |
February | 0.886007E+09 | 0.151450E+10 | 0.842166E+09 | 0.302772E+09 | 0.539394E+09 | 0.00 | 0.00 |
March | 0.128376E+10 | 0.128515E+10 | 0.116097E+10 | 0.220758E+09 | 0.940214E+09 | 0.00 | 0.00 |
April | 0.346900E+10 | 0.147400E+10 | 0.272133E+10 | 0.145295E+10 | 0.126838E+10 | 0.00 | 0.00 |
May | 0.411111E+10 | 0.145336E+10 | 0.336691E+10 | 0.185427E+10 | 0.151263E+10 | 0.00 | 0.00 |
June | 0.431639E+10 | 0.125506E+10 | 0.347118E+10 | 0.186542E+10 | 0.160576E+10 | 0.00 | 0.00 |
July | 0.451664E+10 | 0.141272E+10 | 0.363578E+10 | 0.210983E+10 | 0.152595E+10 | 0.00 | 0.00 |
August | 0.388327E+10 | 0.166368E+10 | 0.313383E+10 | 0.188650E+10 | 0.124733E+10 | 0.00 | 0.00 |
September | 0.274348E+10 | 0.177394E+10 | 0.223817E+10 | 0.133133E+10 | 0.906831E+09 | 0.00 | 0.00 |
October | 0.130215E+10 | 0.168920E+10 | 0.118814E+10 | 0.521110E+09 | 0.667026E+09 | 0.00 | 0.00 |
November | 0.528789E+09 | 0.143923E+10 | 0.567991E+09 | 0.168571E+09 | 0.399420E+09 | 0.00 | 0.00 |
December | 0.263722E+09 | 0.188000E+10 | 0.374626E+09 | 94759210.05 | 0.279867E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277984E+11 | 0.185729E+11 | 0.232391E+11 | 0.119607E+11 | 0.112784E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263722E+09 | 0.125506E+10 | 0.374626E+09 | 94759210.05 | 0.279867E+09 | 0.00 | 0.00 |
Maximum of Months | 0.451664E+10 | 0.188000E+10 | 0.363578E+10 | 0.210983E+10 | 0.160576E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.102481E+10 | -869212026.3 | 0.00 | 0.00 | 744.00 | 0.00 | -155593276.8 | 58.99 | 0.00 | 0.00 |
February | 0.944328E+09 | -803828929.7 | 0.00 | 0.00 | 672.00 | 0.00 | -140499437.4 | 58.99 | 0.00 | 0.00 |
March | 0.108707E+10 | -933238895.0 | 0.00 | 0.00 | 744.00 | 0.00 | -153832449.8 | 58.99 | 0.00 | 0.00 |
April | 0.993608E+09 | -850505593.5 | 0.00 | 0.00 | 720.00 | 0.00 | -143102790.0 | 58.99 | 0.00 | 0.00 |
May | 0.100676E+10 | -860908731.4 | 0.00 | 0.00 | 744.00 | 0.00 | -145855111.3 | 58.99 | 0.00 | 0.00 |
June | 0.968523E+09 | -834447989.3 | 0.00 | 0.00 | 720.00 | 0.00 | -134075191.2 | 58.99 | 0.00 | 0.00 |
July | 0.925641E+09 | -789591529.8 | 0.00 | 0.00 | 744.00 | 0.00 | -136049817.3 | 58.99 | 0.00 | 0.00 |
August | 0.976655E+09 | -841423824.9 | 0.00 | 0.00 | 744.00 | 0.00 | -135230896.4 | 58.99 | 0.00 | 0.00 |
September | 0.923032E+09 | -787984279.6 | 0.00 | 0.00 | 720.00 | 0.00 | -135047829.4 | 58.99 | 0.00 | 0.00 |
October | 0.957019E+09 | -806762060.5 | 0.00 | 0.00 | 744.00 | 0.00 | -150256986.8 | 58.99 | 0.00 | 0.00 |
November | 0.946067E+09 | -796615285.2 | 0.00 | 0.00 | 720.00 | 0.00 | -149451588.9 | 58.99 | 0.00 | 0.00 |
December | 0.100806E+10 | -851916269.6 | 0.00 | 0.00 | 744.00 | 0.00 | -156138897.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.117616E+11 | -.100264E+11 | 8760.00 | -.173513E+10 | 58.99 | |||||
Minimum of Months | 0.923032E+09 | -933238895.0 | 0.00 | 0.00 | 672.00 | 0.00 | -156138897.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.108707E+10 | -787984279.6 | 0.00 | 0.00 | 744.00 | 0.00 | -134075191.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.552622E+10 | 25120.57 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450112E+10 | 25120.57 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447502E+10 | 25120.57 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159857E+10 | 25120.57 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104146E+10 | 25120.57 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170018E+09 | 25120.57 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50830510.88 | 25120.57 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4610341.58 | 1857.30 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243768E+09 | 25120.57 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192425E+10 | 25120.57 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383667E+10 | 25120.57 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568458E+10 | 25120.57 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290571E+11 | |||||||
Minimum of Months | 4610341.58 | 1857.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568458E+10 | 25120.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191231E+11 | 67203.84 | 01-JAN-17:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159116E+11 | 67203.84 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106877E+11 | 67203.84 | 04-MAR-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147316E+10 | 61063.53 | 06-APR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841600E+09 | 48643.71 | 20-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336361E+10 | 66278.55 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134628E+11 | 67203.84 | 17-NOV-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257802E+11 | 67203.84 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906437E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257802E+11 | 67203.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212839E+11 | 59817.00 | 10-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142036E+11 | 42945.17 | 17-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207025E+10 | 21561.83 | 04-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.645243E+10 | 38851.45 | 29-NOV-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359526E+11 | 59251.89 | 30-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799628E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359526E+11 | 59817.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.188894E+09 | 0.188878E+09 | 6596.44 | 29-APR-17:25 | 6596.44 | 0.00 |
May | 0.00 | 0.00 | 0.369412E+09 | 0.342639E+09 | 7448.74 | 24-MAY-17:33 | 7448.74 | 0.00 |
June | 0.00 | 0.00 | 0.177266E+10 | 0.159124E+10 | 16289.31 | 13-JUN-17:10 | 15380.82 | 0.00 |
July | 0.00 | 0.00 | 0.326038E+10 | 0.295390E+10 | 16890.01 | 24-JUL-00:03 | 14139.14 | 0.00 |
August | 0.00 | 0.00 | 0.341200E+10 | 0.307516E+10 | 13898.23 | 14-AUG-17:10 | 13898.23 | 0.00 |
September | 0.00 | 0.00 | 0.145067E+10 | 0.131217E+10 | 8498.91 | 13-SEP-17:15 | 8279.84 | 0.00 |
October | 0.00 | 0.00 | 25090809.54 | 25072394.36 | 1863.92 | 07-OCT-15:40 | 1863.92 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.104791E+11 | 0.948906E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.341200E+10 | 0.307516E+10 | 16890.01 | 15380.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135398E+09 | 0.117392E+09 | 10427.15 | 13-JUN-16:00 | 9355.38 | 0.00 |
July | 0.00 | 0.00 | 0.710969E+09 | 0.694710E+09 | 38173.28 | 23-JUL-16:31 | 27997.58 | 0.00 |
August | 0.00 | 0.00 | 55043660.94 | 52831237.12 | 5639.96 | 14-AUG-16:00 | 5639.96 | 0.00 |
September | 0.00 | 0.00 | 13.06 | 11.40 | 0.01 | 13-SEP-14:20 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.901411E+09 | 0.864933E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.710969E+09 | 0.694710E+09 | 38173.28 | 27997.58 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.213568E+09 | 0.03 | 175.82 | 01-JAN-00:03 | 0.08 |
February | 0.190745E+09 | 0.03 | 175.82 | 01-FEB-00:03 | 0.08 |
March | 56707804.42 | 0.01 | 175.82 | 01-MAR-00:50 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 70683445.80 | 0.01 | 175.82 | 05-NOV-05:50 | 0.08 |
December | 0.322685E+09 | 0.05 | 175.82 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.854388E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322685E+09 | 0.05 | 175.82 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114349E+10 | 0.42 | 1106.52 | 02-JAN-15:10 | 0.94 |
February | 0.104688E+10 | 0.40 | 1106.52 | 01-FEB-12:30 | 0.94 |
March | 0.122232E+10 | 0.41 | 1106.52 | 01-MAR-13:20 | 0.94 |
April | 0.111901E+10 | 0.39 | 1106.52 | 01-APR-10:20 | 0.94 |
May | 0.115659E+10 | 0.38 | 1106.52 | 01-MAY-13:50 | 0.94 |
June | 0.115222E+10 | 0.39 | 1106.52 | 01-JUN-06:45 | 0.94 |
July | 0.112677E+10 | 0.39 | 1106.52 | 05-JUL-16:30 | 0.94 |
August | 0.119898E+10 | 0.40 | 1106.52 | 01-AUG-08:00 | 0.94 |
September | 0.110071E+10 | 0.37 | 1106.52 | 01-SEP-12:00 | 0.94 |
October | 0.111957E+10 | 0.37 | 1106.52 | 04-OCT-07:50 | 0.94 |
November | 0.108457E+10 | 0.38 | 1106.52 | 01-NOV-09:10 | 0.94 |
December | 0.114170E+10 | 0.41 | 1106.52 | 01-DEC-12:30 | 0.94 |
Annual Sum or Average | 0.136128E+11 | 0.39 | |||
Minimum of Months | 0.104688E+10 | 0.37 | 1106.52 | 0.94 | |
Maximum of Months | 0.122232E+10 | 0.42 | 1106.52 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.263100E+10 | 0.74 | 2136.07 | 05-JAN-07:30 | 0.91 |
February | 0.242615E+10 | 0.75 | 2136.07 | 01-FEB-12:00 | 0.90 |
March | 0.261554E+10 | 0.70 | 2136.07 | 03-MAR-10:30 | 0.91 |
April | 0.216822E+10 | 0.42 | 2136.07 | 01-APR-06:05 | 0.91 |
May | 0.222985E+10 | 0.39 | 2136.07 | 05-MAY-06:05 | 0.91 |
June | 0.219930E+10 | 0.36 | 2136.07 | 13-JUN-12:50 | 0.90 |
July | 0.212707E+10 | 0.34 | 2136.07 | 10-JUL-11:30 | 0.90 |
August | 0.228389E+10 | 0.36 | 2136.07 | 16-AUG-13:50 | 0.90 |
September | 0.211471E+10 | 0.34 | 2136.07 | 13-SEP-14:50 | 0.90 |
October | 0.223001E+10 | 0.48 | 2136.07 | 14-OCT-07:30 | 0.90 |
November | 0.243245E+10 | 0.70 | 2136.07 | 02-NOV-09:10 | 0.91 |
December | 0.279421E+10 | 0.78 | 2136.07 | 02-DEC-10:40 | 0.90 |
Annual Sum or Average | 0.282524E+11 | 0.53 | |||
Minimum of Months | 0.211471E+10 | 0.34 | 2136.07 | 0.90 | |
Maximum of Months | 0.279421E+10 | 0.78 | 2136.07 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.95 | 0.00 |
February | 2.89 | 0.00 |
March | 2.58 | 0.00 |
April | 0.83 | 1.44 |
May | 0.60 | 1.75 |
June | 0.92 | 4.38 |
July | 0.83 | 4.26 |
August | 1.25 | 5.00 |
September | 0.83 | 1.99 |
October | 0.47 | 0.56 |
November | 1.92 | 0.00 |
December | 2.79 | 0.00 |
Annual Sum or Average | 18.87 | 0.95 |
Minimum of Months | 0.47 | 0.00 |
Maximum of Months | 2.95 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.17 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114349E+10 | 0.801431E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104688E+10 | 0.655358E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122232E+10 | 0.652436E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116490E+10 | 0.232410E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.124613E+10 | 0.152250E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.157864E+10 | 0.249956E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.191072E+10 | 74518819.82 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.201537E+10 | 7138732.53 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145020E+10 | 0.361889E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.112575E+10 | 0.281575E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108457E+10 | 0.560223E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114170E+10 | 0.826386E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161307E+11 | 0.423142E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104688E+10 | 7138732.53 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201537E+10 | 0.826386E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.263100E+10 | 0.278584E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.242615E+10 | 0.230971E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.261554E+10 | 0.157656E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.216822E+10 | 0.220895E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222985E+10 | 0.126552E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.223639E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.232404E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.229930E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.211471E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.223001E+10 | 0.503482E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.243245E+10 | 0.196414E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.279421E+10 | 0.373159E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.285019E+11 | 0.132188E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.211471E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279421E+10 | 0.373159E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114349E+10 | 0.00 | 0.552622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104688E+10 | 0.00 | 0.450112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122232E+10 | 0.00 | 0.447502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111901E+10 | 0.188894E+09 | 0.159857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115659E+10 | 0.369412E+09 | 0.104146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115222E+10 | 0.177266E+10 | 0.170018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112677E+10 | 0.326038E+10 | 50830510.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119898E+10 | 0.341200E+10 | 4610341.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110071E+10 | 0.145067E+10 | 0.243768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111957E+10 | 25090809.54 | 0.192425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108457E+10 | 0.00 | 0.383667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114170E+10 | 0.00 | 0.568458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136128E+11 | 0.104791E+11 | 0.290571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104688E+10 | 0.00 | 4610341.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122232E+10 | 0.341200E+10 | 0.568458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.263100E+10 | 0.00 | 0.191231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242615E+10 | 0.00 | 0.159116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261554E+10 | 0.00 | 0.106877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216822E+10 | 0.00 | 0.147316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222985E+10 | 0.00 | 0.841600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219930E+10 | 0.135398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.212707E+10 | 0.710969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.228389E+10 | 55043660.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211471E+10 | 13.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223001E+10 | 0.00 | 0.336361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243245E+10 | 0.00 | 0.134628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279421E+10 | 0.00 | 0.257802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282524E+11 | 0.901411E+09 | 0.906437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.211471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279421E+10 | 0.710969E+09 | 0.257802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.114349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111901E+10 | 0.00 | 0.00 | 0.00 | 45895391.37 | 0.00 | 0.232410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115659E+10 | 0.00 | 0.00 | 0.00 | 89539651.32 | 0.00 | 0.152250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115222E+10 | 0.00 | 0.00 | 0.00 | 0.426422E+09 | 0.00 | 0.249956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112677E+10 | 0.00 | 0.00 | 0.00 | 0.783953E+09 | 0.00 | 74518819.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119898E+10 | 0.00 | 0.00 | 0.00 | 0.816391E+09 | 0.00 | 7138732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110071E+10 | 0.00 | 0.00 | 0.00 | 0.349483E+09 | 0.00 | 0.361889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111957E+10 | 0.00 | 0.00 | 0.00 | 6182981.73 | 0.00 | 0.281575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136128E+11 | 0.00 | 0.00 | 0.00 | 0.251787E+10 | 0.00 | 0.423142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.104688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7138732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122232E+10 | 0.00 | 0.00 | 0.00 | 0.816391E+09 | 0.00 | 0.826386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.263100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219930E+10 | 0.00 | 0.00 | 0.00 | 37097485.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.212707E+10 | 0.00 | 0.00 | 0.00 | 0.196967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.228389E+10 | 0.00 | 0.00 | 0.00 | 15412275.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211471E+10 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282524E+11 | 0.00 | 0.00 | 0.00 | 0.249477E+09 | 0.00 | 0.132188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.211471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279421E+10 | 0.00 | 0.00 | 0.00 | 0.196967E+09 | 0.00 | 0.373159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26320318.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211499E+10 | 0.00 | 0.00 | 0.14 |
February | 30399686.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183166E+10 | 0.00 | 0.00 | 0.14 |
March | 55842083.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195837E+10 | 0.00 | 0.00 | 0.15 |
April | 0.667876E+09 | 0.00 | 0.00 | 265130.52 | 531554.78 | 0.691176E+09 | 0.113962E+09 | 0.00 | 0.14 |
May | 0.824096E+09 | 156895.49 | 0.00 | 509886.62 | 0.00 | 0.424463E+09 | 0.190336E+09 | 0.00 | 0.14 |
June | 0.437828E+09 | 14738750.28 | 0.00 | 2188025.97 | 0.00 | 67303321.38 | 0.593971E+09 | 0.00 | 0.15 |
July | 0.171284E+09 | 19379447.75 | 0.00 | 4145603.50 | 0.00 | 19700074.18 | 0.608624E+09 | 0.00 | 0.14 |
August | 0.129957E+09 | 1589287.27 | 0.00 | 4611682.88 | 0.00 | 12182660.98 | 0.569236E+09 | 0.00 | 0.15 |
September | 0.358461E+09 | 294824.90 | 0.00 | 1860414.14 | 0.00 | 0.107258E+09 | 0.484647E+09 | 0.00 | 0.14 |
October | 0.493111E+09 | 0.00 | 0.00 | 35408.90 | 0.00 | 0.875050E+09 | 45162401.29 | 0.00 | 0.14 |
November | 84195646.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161786E+10 | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209332E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.327937E+10 | 36159205.69 | 0.00 | 13616152.54 | 531554.78 | 0.118133E+11 | 0.260594E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12182660.98 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.824096E+09 | 19379447.75 | 0.00 | 4611682.88 | 531554.78 | 0.211499E+10 | 0.608624E+09 | 0.00 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278248E+10 | 0.00 | 0.00 | 0.17 |
February | 0.268228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133452E+10 | 0.00 | 0.00 | 0.18 |
March | 0.342334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854445E+09 | 0.00 | 0.00 | 0.19 |
April | 0.360262E+10 | 0.00 | 0.00 | 0.00 | 8668088.15 | 6150140.64 | 0.00 | 0.00 | 0.18 |
May | 0.374892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7212284.09 | 0.00 | 0.00 | 0.18 |
June | 0.350009E+10 | 108664.41 | 0.00 | 300271.27 | 1614041.50 | 0.00 | 0.137562E+09 | 0.00 | 0.21 |
July | 0.280831E+10 | 11081718.23 | 0.00 | 1452214.90 | 2005725.40 | 0.00 | 0.697784E+09 | 0.00 | 0.21 |
August | 0.277492E+10 | 0.00 | 0.00 | 557188.58 | 0.00 | 0.00 | 0.544823E+09 | 0.00 | 0.21 |
September | 0.271815E+10 | 0.00 | 0.00 | 3367.94 | 0.00 | 0.00 | 8438446.07 | 0.00 | 0.18 |
October | 0.275036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151382E+09 | 0.00 | 0.00 | 0.17 |
November | 0.235541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114015E+10 | 0.00 | 0.00 | 0.17 |
December | 0.118901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333892E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.335750E+11 | 11190382.63 | 0.00 | 2313042.69 | 12287855.05 | 0.961525E+10 | 0.138861E+10 | 0.00 | 0.19 |
Minimum of Months | 0.118901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.374892E+10 | 11081718.23 | 0.00 | 1452214.90 | 8668088.15 | 0.333892E+10 | 0.697784E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |