Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:11:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1879.75 | 388.77 | 388.77 |
Net Site Energy | 1879.75 | 388.77 | 388.77 |
Total Source Energy | 3077.44 | 636.48 | 636.48 |
Net Source Energy | 3077.44 | 636.48 | 636.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1380.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 236.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 57.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.46 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 499.18 | 1380.56 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1380.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 236.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 57.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 37.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.46 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.24 | 285.53 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.24 | 285.53 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.24 | 285.53 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.24 | 285.53 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 499.182 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 499.182 | 100.00 |
Total On-Site and Utility Electric Sources | 499.182 | 100.00 |
Total Electricity End Uses | 499.182 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 68.17 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2314.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.5035 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0541 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0541 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 284472.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7739.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 18641.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2336.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1810.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 40563.65 | 284472.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 284472.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7739.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 18641.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2336.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1810.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1496.53 | 0.00 | 0.00 | 0.00 |
Cooling | 13.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 749.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 86.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1580.91 | 1496.53 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 309.51 | 0.00 | 0.00 | 0.00 |
Cooling | 2.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 155.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 326.96 | 309.51 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 309.51 | 0.00 | 0.00 | 0.00 |
Cooling | 2.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 155.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 326.96 | 309.51 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.798128 |
ZONE2 FINE STORAGE DIRECT AIR | 1.31 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.59 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.59 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 142718.30 |
PSZ-OFFICE HEATING COIL | 23911.64 |
PSZ-FINE STORAGE HEATING COIL | 60947.95 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 142718.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.798128 | 0.798128 | 0.798128 | 0.798128 | 0.798128 | 0.798128 | 1.00 | 1.00 | 0.798128 |
PSZ-FINE STORAGE | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.798128 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.31 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.798128 | 0.798128 | 0.798128 | 0.798128 | 14108.15 | 23911.64 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 31281.32 | 60947.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.798130 | 0.399065 | 0.532087 | 13735.62 | 14108.15 | 7054.07 | 7054.07 | 0.775299 | 0.775300 | 0.775300 | 0.775300 |
PSZ-FINE STORAGE COOLING COIL | 1.31 | 0.655935 | 0.874580 | 30000.72 | 31281.32 | 15640.66 | 15640.66 | 0.686234 | 0.686230 | 0.686230 | 0.686230 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.798128 | 883.65 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.31 | 1452.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 8.503 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.577 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2014.304 | 8.503 | 402.861 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2014.304 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 10348.991 | 7.427 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.991 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 12073.822 | 3.767 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.822 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.2582 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.4317 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.4317 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.773 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.217 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.217 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.82798482E-12 | -0.56801693E-16 | 0.17324709E-13 | -0.10881355E-17 |
8 | 3 | -0.39991217E-03 | 0.18458975E-06 | -0.58159825E-04 | 0.15873877E-12 |
9 | 2 | 1.7752618 | 0.39719073E-02 | 1.1676282 | -0.76670311E-04 |
10 | 1 | -7.0821268 | 0.10187671 | -17.271174 | 0.34026389 |
11 | 0 | 5.4776347 | 0.64520937E-01 | 16.273974 | |
12 | 4 | 0.79196522E-12 | 0.10386829E-15 | -0.20951661E-14 | 0.11444468E-15 |
13 | 3 | -0.38823068E-03 | 0.30445924E-06 | -0.56349653E-04 | 0.15195854E-12 |
14 | 2 | 1.7478523 | 0.66314060E-02 | 1.1467743 | -0.74430390E-04 |
15 | 1 | -7.1177396 | 0.17139507 | -17.138489 | 0.33499793 |
16 | 0 | 5.6574045 | 0.10910218 | 16.278900 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20951661E-14 | 0.10386829E-15 | 0.79196522E-12 | 0.11444468E-15 |
85 | 3 | -0.56349653E-04 | 0.30445924E-06 | -0.38823068E-03 | 0.15195854E-12 |
86 | 2 | 1.1467743 | 0.66314060E-02 | 1.7478523 | -0.74430390E-04 |
87 | 1 | -17.138489 | 0.17139507 | -7.1177396 | 0.33499793 |
88 | 0 | 16.278900 | 0.10910218 | 5.6574045 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.33_SHGC_0.45 | 28 | 1 | VerySmooth | 1.875 | 0.444 | 0.367 | 0.496 |
2 | SKYLIGHT_U_0.5_SHGC_0.55 | 29 | 1 | VerySmooth | 2.843 | 0.549 | 0.472 | 0.551 |
3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 30 | 1 | VerySmooth | 4.827 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.47116 | 0.32579 | 0.32579 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.13907 | 0.13907 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 5.00274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.263 | 7.062E-004 | 4.613E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 7747.30603 | 9296.76724 | 0.66511 | 0.79813 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27032E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10602.77945 | 12723.33534 | 0.31059 | 0.37271 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 16335.53785 | 19602.64542 | 1.09323 | 1.31187 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27032E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 36519.92030 | 43823.90435 | 0.90107 | 1.08128 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 118931.90836 | 142718.29003 | 2.98767 | 3.58520 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 11541.78 | 0.79813 | 0.79813 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14564.18 | 0.37271 | 0.37271 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 24025.81 | 1.31187 | 1.31187 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 54412.15 | 1.08128 | 1.08128 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79813 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31187 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.58520 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.58520 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 142718.30011 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 142718.29003 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79813 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79813 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79813 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79813 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79813 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.79813 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31187 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31187 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31187 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31187 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31187 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.31187 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.79813 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.31187 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79813 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79813 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79813 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79813 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79813 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.79813 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39907 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53209 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13735.61680 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14108.15000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7054.07500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7054.07500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77530 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77530 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77530 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77530 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14108.15000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23911.64119 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.79813 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 883.65396 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23911.64119 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31187 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31187 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31187 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31187 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31187 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31187 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65594 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87458 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30000.72226 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31281.32000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15640.66000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15640.66000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68623 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68623 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68623 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68623 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31281.32000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60947.94537 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31187 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1452.45182 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 60947.94537 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 13488.7 | 12.05 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 30261.8 | 17.20 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3946838549 | 0.3832870964 | Pass | Pass | 0.9272180269 | 0.8598682512 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0084361876 | 0.9013811749 | Pass | Pass | 0.6463384048 | 0.6116063716 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.7082423834E-005 | 1.2249572537E-004 | Pass | Pass | 2.1471800247E-002 | 1.8193365366E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.249 | 0.258 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.406 | 0.432 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.406 | 0.432 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.406 | 0.432 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.875 | 0.444 | 0.496 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.875 | 0.444 | 0.496 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.33_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.875 | 0.444 | 0.496 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.33_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.875 | 0.444 | 0.496 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.224 | 0.493 | 0.521 | ||||||||||||
North Total or Average | 6.51 | 1.875 | 0.444 | 0.496 | ||||||||||||
Non-North Total or Average | 26.02 | 3.561 | 0.505 | 0.527 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 8.5035 | 236.88 | 2014.30 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 56.91 | 168.00 | 33.28 | 0.0000 | Y | 12.58 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 7.4271 | 1393.41 | 10348.99 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 53.69 | 0.0000 | Y | 104.31 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.7674 | 3204.84 | 12073.82 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 52.86 | 0.0000 | Y | 119.81 |
Interior Lighting Total | 5.0541 | 4835.13 | 24437.12 | 236.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2014.30 | 584.15 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2014.30 | 201.43 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 12073.82 | 1400.56 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 42.55 | 42.55 | 0.91 | |
EXTERIOR_LIGHTS_B | 3955.00 | AstronomicalClock | - | 83.52 | 63.04 | 46.80 | |
EXTERIOR_LIGHTS_C | 1004.90 | AstronomicalClock | - | 83.52 | 49.92 | 9.42 | |
Exterior Lighting Total | 5073.70 | 57.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14108.15 | 10938.05 | 3170.10 | 0.78 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31281.32 | 21466.18 | 9815.14 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 13488.7 | 12.05 | ||||
PSZ-FINE STORAGE COOLING COIL | 30261.8 | 17.20 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 142718.30 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23911.64 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 60947.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.59 | 333.10 | 92.91 | 1.00 | 3.28 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.80 | 883.65 | 1107.16 | 1.00 | 1.46 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1452.45 | 1107.16 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7747.31 | 9296.77 | 39.25 | 0.665 | 0.798 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00829 | 28.36 | 0.01270 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 16335.54 | 19602.65 | 14.07 | 1.093 | 1.312 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00857 | 29.98 | 0.01270 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00394 | 30.10 | 0.01270 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10602.78 | 12723.34 | 53.71 | 0.311 | 0.373 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00776 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36519.92 | 43823.90 | 31.45 | 0.901 | 1.081 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00641 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 118931.91 | 142718.29 | 44.53 | 2.988 | 3.585 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00796 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.80 | 0.80 | 0.37 | 0.37 | 0.7981 | 0.7981 | 0.7981 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.31 | 1.31 | 1.08 | 1.08 | 1.3119 | 1.3119 | 1.3119 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 142718.300 | 142718.300 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 142718.30 | 142718.30 | 3.585202 | -1.64 | -1.64 | 0.00584255 | 43.33 | 26.55 | 0.01600000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 9.99 | 0.00796193 | 99.9999 | 142718.29 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 7054.075 | 0.000 | 0.798130 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7054.07 | 6146.42 | 0.798130 | 24.47 | 16.40 | 0.00885227 | 12.00 | 10.88 | 0.00800000 | 28.36 | 0.01270325 | 20.60 | 12.8156 | 23.90 | 0.00828619 | 43.0185 | 7747.31 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23911.641 | 23911.641 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23911.64 | 23911.64 | 0.798128 | 6.30 | 5.70 | 0.00567706 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 12.8156 | 21.10 | 0.00775500 | 47.7690 | 10602.78 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 15640.660 | 0.000 | 1.311870 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 15640.66 | 12324.57 | 1.311870 | 27.80 | 18.35 | 0.00990691 | 12.00 | 10.88 | 0.00800000 | 30.10 | 0.01270324 | 21.10 | 32.3746 | 26.70 | 0.00856595 | 37.6322 | 16329.31 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 60947.945 | 60947.945 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60947.95 | 60947.95 | 1.311873 | -3.40 | -3.40 | 0.00396215 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 32.3745 | 15.55 | 0.00640651 | 56.0073 | 36519.92 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 142718.300 | 142718.300 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1539 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.585202 | 4.13705323 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 142718.30 | 142718.30 | 1.0000 | 4.13705323 | 3.585202 | -1.64 | -1.64 | 0.00584255 | 12943.8 | 43.33 | 26.55 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 142718.30 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 9.99 | 0.00796193 | 9.99 | 0.00796193 | 99.9999 | 142718.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7054.075 | 0.000 | 0.798130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2959 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7054.07 | 6146.42 | 1.0000 | 0.92098205 | 0.798130 | 24.47 | 16.40 | 0.00885227 | 47131.6 | 12.00 | 10.88 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7054.07 | 28.36 | 0.01270325 | 20.60 | 0.10228487 | 12.8156 | 23.90 | 0.00828619 | 23.90 | 0.00828619 | 43.0185 | 7747.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23911.641 | 23911.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.798128 | 0.92097930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23911.64 | 23911.64 | 1.0000 | 0.92097930 | 0.798128 | 6.30 | 5.70 | 0.00567706 | 20594.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23911.64 | -32.70 | 0.00018338 | -32.70 | 0.10228487 | 12.8156 | 21.05 | 0.00775500 | 21.10 | 0.00775500 | 47.7690 | 10602.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15640.660 | 0.000 | 1.311870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2564 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 15640.66 | 12324.57 | 1.0000 | 1.51379940 | 1.311870 | 27.80 | 18.35 | 0.00990691 | 53223.6 | 12.00 | 10.88 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15640.66 | 30.10 | 0.01270324 | 21.10 | 0.42471267 | 32.3746 | 26.70 | 0.00856746 | 26.70 | 0.00856595 | 37.6322 | 16329.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60947.945 | 60947.945 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.311873 | 1.51380304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60947.95 | 60947.95 | 1.0000 | 1.51380304 | 1.311873 | -3.40 | -3.40 | 0.00396215 | 6469.2 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60947.95 | -32.70 | 0.00018338 | -32.70 | 0.42471267 | 32.3745 | 15.56 | 0.00640651 | 15.55 | 0.00640651 | 56.0073 | 36519.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.31 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2679.33 | 3014.00 | 2314.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2679.33 | 3014.00 | 2314.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 121.17 | 1.17 | 68.17 | 1.17 |
ZONE2 FINE STORAGE | 608.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 41.17 | 0.00 | 0.00 | 0.00 |
Facility | 717.67 | 1.17 | 68.17 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.308 | 0.242 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
Electricity:Building | 373.21 | 1510.77 | 01-JAN-00:10 | 30361.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 41.75 | 520.87 | 01-JAN-00:10 | 3102.09 | 02-JAN-08:10 |
InteriorLights:Electricity | 236.71 | 1040.90 | 01-JAN-00:10 | 20326.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 12.58 | 51.00 | 01-JAN-00:10 | 1267.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 236.71 | 1040.90 | 01-JAN-00:10 | 20326.42 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 227.15 | 689.93 | 01-JAN-00:10 | 18462.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 119.81 | 689.93 | 01-JAN-00:10 | 10262.75 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.46 | 481.00 | 03-JAN-20:40 | 3104.95 | 27-FEB-12:30 |
WaterSystems:Electricity | 27.46 | 481.00 | 03-JAN-20:40 | 3104.95 | 27-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 27.46 | 481.00 | 03-JAN-20:40 | 3104.95 | 27-FEB-12:30 |
Fans:Electricity | 37.11 | 0.00 | 19-MAR-13:50 | 2669.21 | 02-JAN-07:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
ElectricityNet:Plant | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 499.18 | 1991.77 | 19-MAR-13:50 | 40563.65 | 30-JUN-15:00 |
Electricity:HVAC | 41.40 | 0.00 | 19-MAR-13:50 | 11376.10 | 29-JUN-16:00 |
General:Fans:Electricity | 37.11 | 0.00 | 19-MAR-13:50 | 2669.21 | 02-JAN-07:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 4.29 | 0.00 | 01-JAN-00:10 | 9040.00 | 29-JUN-16:00 |
ExteriorLights:Electricity | 57.12 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 57.12 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1380.56 | 0.00 | 19-MAR-13:50 | 284472.36 | 04-JAN-17:10 |
Gas:HVAC | 1380.56 | 0.00 | 19-MAR-13:50 | 284472.36 | 04-JAN-17:10 |
Heating:Gas | 1380.56 | 0.00 | 19-MAR-13:50 | 284472.36 | 04-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2125.27 | 0.00 | 19-MAR-13:50 | 435806.30 | 04-JAN-06:20 |
EnergyTransfer:Building | 1037.95 | 0.00 | 19-MAR-13:50 | 218736.99 | 04-JAN-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.63 | 0.00 | 01-JAN-00:40 | 24836.83 | 09-JAN-07:10 |
Heating:EnergyTransfer | 1016.16 | 0.00 | 19-MAR-13:50 | 218736.99 | 04-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 52.61 | 0.00 | 01-JAN-00:40 | 24836.83 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 21.79 | 0.00 | 01-JAN-00:10 | 17957.82 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 9.02 | 0.00 | 01-JAN-00:10 | 6261.89 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 211.50 | 0.00 | 01-JAN-00:40 | 61783.07 | 12-FEB-23:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 198.72 | 0.00 | 01-JAN-00:40 | 61783.07 | 12-FEB-23:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 12.77 | 0.00 | 01-JAN-00:10 | 12407.89 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 764.82 | 0.00 | 17-JAN-13:10 | 143994.26 | 18-DEC-13:20 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 764.82 | 0.00 | 17-JAN-13:10 | 143994.26 | 18-DEC-13:20 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1087.32 | 0.00 | 19-MAR-13:50 | 227577.89 | 04-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1067.21 | 0.00 | 19-MAR-13:50 | 227577.89 | 04-JAN-17:10 |
CoolingCoils:EnergyTransfer | 20.11 | 0.00 | 01-JAN-00:10 | 37087.26 | 30-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 52.612 | -9.019 | 0.000 | 0.000 | 4.013 | 12.582 | 29.165 | 10.498 | 0.000 | 0.248 | 0.000 | 0.000 | -10.935 | 0.000 | -24.263 | -64.901 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 198.723 | -12.773 | 0.000 | 0.000 | 0.000 | 104.309 | 0.000 | 0.000 | 0.000 | 0.783 | 0.002 | 0.000 | 0.000 | 0.000 | -135.461 | -155.582 |
ZONE3 BULK STORAGE | 764.819 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 119.814 | 107.336 | 27.193 | 0.000 | 14.053 | 0.000 | 0.000 | -17.584 | 0.000 | -642.277 | -373.354 |
Total Facility | 764.819 | 0.000 | 251.335 | -21.793 | 0.000 | 0.000 | 4.013 | 236.705 | 136.501 | 37.691 | 0.000 | 15.084 | 0.002 | 0.000 | -28.519 | 0.000 | -802.001 | -593.837 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 14-AUG-05:03 | 0.00 | 0.00 | 0.00 | -11816.96 | 0.00 | 0.00 | 36.09 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 11822.02 | 0.00 | -269.70 | 0.00 | -372.96 | 0.00 |
ZONE2 FINE STORAGE | 30-JUN-17:12 | 0.00 | 0.00 | 0.00 | -19208.88 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 1796.79 | 17112.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-17:12 | 0.00 | 0.00 | 0.00 | -19208.88 | 0.00 | 0.00 | 0.00 | 1040.90 | 2519.91 | 6658.53 | 0.00 | 8818.78 | 170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:31 | 0.00 | 0.00 | 25849.49 | 0.00 | 0.00 | 0.00 | 56.32 | 378.46 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.79 | 0.00 | -2625.58 | -23036.42 |
ZONE2 FINE STORAGE | 04-JAN-06:41 | 0.00 | 0.00 | 64237.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -19299.70 | -45972.84 |
ZONE3 BULK STORAGE | 18-DEC-13:20 | 143991.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9469.10 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -779.21 | 0.00 | -157076.10 | -3805.66 |
Total Facility | 04-JAN-06:21 | 143027.53 | 0.00 | 86802.62 | 0.00 | 0.00 | 0.00 | 46.49 | 2620.75 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3601.93 | 0.00 | -138588.55 | -92907.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.7981 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.7981 | 0.1282 | 1.0000 | 0.1023 | 0.1282 | ||
PSZ-FINE STORAGE | 1.3119 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.3119 | 0.3237 | 1.0000 | 0.4247 | 0.3237 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.7981 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.7981 | 1.0000 | 1.0000 | 0.1023 | 0.1282 | ||
PSZ-FINE STORAGE | 1.3119 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.3119 | 1.0000 | 1.0000 | 0.4247 | 0.3237 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.7981 | 0.7981 | 0.7981 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.3119 | 1.3119 | 1.3119 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.7981 | 0.7981 | 0.7981 | 0.7981 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.3119 | 1.3119 | 1.3119 | 1.3119 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.7981 | 0.7981 | 0.7981 | 0.1023 | 0.2744 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.3119 | 1.3119 | 1.3119 | 0.4247 | 0.3928 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.7981 | 0.7981 | 0.7981 | 0.7981 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.3119 | 1.3119 | 1.3119 | 1.3119 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 68.17 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 69.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1380.56 | 284472.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 4.29 | 9040.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 236.71 | 20326.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 57.12 | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.50 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 37.11 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.46 | 3104.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.50 | 499.18 |
Natural Gas | 0.00 | 1380.56 |
Additional | 0.00 | 0.00 |
Total | 136.50 | 1879.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.96 |
Space Heating | 0.00 |
Space Cooling | 0.89 |
Fans (All) | 7.67 |
Service Water Heating | 5.68 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 103.24 |
Subtotal | 103.24 |
Natural Gas [MJ/m2] | |
Space Heating | 285.53 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 285.53 |
Subtotal | 285.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.59 |
Space Heating | 73.44 |
Space Cooling | 0.23 |
Fans (All) | 1.97 |
Service Water Heating | 1.46 |
Receptacle Equipment | 7.26 |
Miscellaneous | 3.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 2967. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.355903E+12 |
February | 0.000 | 0.267521E+12 |
March | 0.000 | 0.192786E+12 |
April | 0.000 | 0.699887E+11 |
May | 0.000 | 0.386706E+10 |
June | 0.000 | 0.133987E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.444884E+09 |
October | 0.000 | 0.182121E+11 |
November | 0.000 | 0.139850E+12 |
December | 0.000 | 0.331857E+12 |
Annual Sum or Average | 0.138056E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.355903E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.194914E+09 | 236.59 | 18-JAN-13:30 | -3.9 | -4.0 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.179341E+09 | 236.59 | 04-FEB-10:30 | -3.0 | -4.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.2 | 0.210508E+09 | 236.59 | 20-MAR-15:09 | 0.00 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.195200E+09 | 256.90 | 13-APR-15:00 | 20.00 | 8.07 |
May | 0.303114E+09 | 2762.76 | 25-MAY-16:00 | 29.10 | 19.61 | 0.223864E+09 | 301.59 | 25-MAY-15:20 | 28.97 | 19.64 |
June | 0.132168E+10 | 9726.72 | 29-JUN-05:03 | 22.30 | 19.60 | 0.250210E+09 | 304.23 | 05-JUN-15:20 | 21.50 | 12.78 |
July | 0.334200E+10 | 11673.80 | 25-JUL-05:02 | 15.78 | 14.68 | 0.248889E+09 | 301.60 | 15-JUL-09:30 | 24.45 | 20.40 |
August | 0.302093E+10 | 11817.51 | 14-AUG-05:03 | 15.92 | 13.39 | 0.268392E+09 | 301.60 | 28-AUG-10:00 | 18.90 | 17.44 |
September | 0.998169E+09 | 11337.03 | 02-SEP-05:03 | 13.80 | 10.54 | 0.229853E+09 | 303.04 | 18-SEP-12:09 | 19.40 | 16.83 |
October | 33701297.18 | 527.48 | 24-OCT-14:00 | 9.40 | 5.33 | 0.197586E+09 | 296.86 | 21-OCT-15:00 | 20.00 | 11.44 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.187281E+09 | 247.24 | 01-NOV-15:00 | 17.80 | 13.25 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.194958E+09 | 236.59 | 30-DEC-08:30 | -4.5 | -5.2 |
Annual Sum or Average | 0.901959E+10 | 0.258100E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.179341E+09 | 236.59 | -4.5 | -5.2 | ||
Maximum of Months | 0.334200E+10 | 11817.51 | 29.10 | 19.61 | 0.268392E+09 | 304.23 | 28.97 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4875353.96 | 12791.46 | 27-JAN-14:13 | -14.4 | -15.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 97353838.07 | 7416.93 | 22-FEB-10:55 | -3.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.397266E+09 | 5646.75 | 23-MAR-14:00 | 0.00 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.758602E+09 | 4411.84 | 27-APR-16:00 | 3.30 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.104139E+10 | 5797.93 | 31-MAY-06:10 | 7.83 | 5.97 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.121028E+10 | 19212.56 | 30-JUN-17:12 | 30.73 | 21.02 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.281132E+10 | 18806.81 | 23-JUL-13:20 | 30.00 | 22.70 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.208250E+10 | 6939.74 | 08-AUG-15:30 | 30.60 | 23.16 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.206466E+10 | 7128.18 | 06-SEP-07:05 | 4.05 | 3.63 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.180286E+10 | 7669.90 | 25-OCT-07:05 | -3.2 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.502147E+09 | 6997.72 | 10-NOV-13:15 | -2.4 | -4.9 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.127733E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -14.4 | -15.5 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.281132E+10 | 19212.56 | 30.73 | 23.16 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109519E+11 | 25807.19 | 05-JAN-06:31 | -32.4 |
February | 0.872561E+10 | 25849.25 | 13-FEB-06:31 | -24.2 |
March | 0.858057E+10 | 25604.59 | 16-MAR-05:31 | -23.7 |
April | 0.502991E+10 | 24883.32 | 29-APR-05:32 | 0.00 |
May | 0.150430E+10 | 24454.94 | 01-MAY-05:22 | -3.6 |
June | 0.224413E+09 | 23937.42 | 05-JUN-05:01 | 12.07 |
July | 24977402.61 | 1105.43 | 17-JUL-06:10 | 13.07 |
August | 48818535.87 | 1101.65 | 02-AUG-06:10 | 10.97 |
September | 0.344751E+09 | 24131.49 | 29-SEP-05:01 | 7.20 |
October | 0.260356E+10 | 24424.75 | 30-OCT-05:12 | -9.8 |
November | 0.510567E+10 | 25314.55 | 29-NOV-06:32 | -19.5 |
December | 0.946782E+10 | 25518.67 | 13-DEC-06:31 | -25.3 |
Annual Sum or Average | 0.526123E+11 | |||
Minimum of Months | 24977402.61 | 1101.65 | -32.4 | |
Maximum of Months | 0.109519E+11 | 25849.25 | 13.07 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482021E+11 | 64237.59 | 04-JAN-06:41 | -29.3 |
February | 0.368227E+11 | 63258.12 | 16-FEB-00:42 | -12.2 |
March | 0.276581E+11 | 63208.63 | 06-MAR-02:62 | -15.7 |
April | 0.131552E+11 | 62598.57 | 04-APR-19:02 | -7.3 |
May | 0.155354E+10 | 61587.30 | 01-MAY-05:11 | -3.5 |
June | 0.382442E+09 | 2522.65 | 06-JUN-13:00 | 25.60 |
July | 0.128265E+09 | 1386.75 | 26-JUL-07:00 | 16.10 |
August | 0.138242E+09 | 1509.52 | 07-AUG-07:00 | 13.90 |
September | 0.134149E+09 | 1491.14 | 23-SEP-07:00 | 3.90 |
October | 0.497993E+10 | 61590.57 | 18-OCT-05:01 | 2.12 |
November | 0.208418E+11 | 63173.11 | 25-NOV-02:62 | -15.7 |
December | 0.447266E+11 | 63247.06 | 10-DEC-14:02 | -22.7 |
Annual Sum or Average | 0.198723E+12 | |||
Minimum of Months | 0.128265E+09 | 1386.75 | -29.3 | |
Maximum of Months | 0.482021E+11 | 64237.59 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203745E+12 | 143806.63 | 04-JAN-12:00 | -28.3 |
February | 0.152332E+12 | 143784.99 | 12-FEB-22:23 | -16.1 |
March | 0.103776E+12 | 122571.79 | 15-MAR-04:53 | -22.2 |
April | 0.325108E+11 | 76349.56 | 04-APR-18:54 | -7.2 |
May | 0.475106E+09 | 19258.27 | 01-MAY-03:53 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.415197E+10 | 36696.38 | 31-OCT-20:55 | -2.2 |
November | 0.766175E+11 | 100060.81 | 25-NOV-02:00 | -15.6 |
December | 0.191212E+12 | 143994.26 | 18-DEC-13:20 | -22.8 |
Annual Sum or Average | 0.764820E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.203745E+12 | 143994.26 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.114723E+10 | 1267.03 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.973804E+09 | 1267.03 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.112228E+10 | 1267.03 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.101408E+10 | 1267.03 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.970064E+09 | 1144.55 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.974127E+09 | 1267.03 | 09-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.939370E+09 | 1267.03 | 08-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.104459E+10 | 1267.03 | 01-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.100839E+10 | 1267.03 | 09-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.108534E+10 | 1267.03 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.111467E+10 | 1267.03 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.118835E+10 | 1267.03 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.125823E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.939370E+09 | 1144.55 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.118835E+10 | 1267.03 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.862930E+10 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.792548E+10 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.925537E+10 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.860339E+10 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.894234E+10 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.891642E+10 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.862930E+10 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.925537E+10 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.860339E+10 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.862930E+10 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.829035E+10 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.862930E+10 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104309E+12 | ||||
Minimum of Months | 0.792548E+10 | 8796.64 | 0.00 | 0.00 | |
Maximum of Months | 0.925537E+10 | 8796.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.103138E+11 | 10262.75 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.929994E+10 | 10262.75 | 01-FEB-10:20 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.106287E+11 | 10262.75 | 06-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.978931E+10 | 9865.92 | 04-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.993927E+10 | 9865.92 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.985969E+10 | 9469.10 | 08-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.961480E+10 | 9469.10 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.103190E+11 | 9865.92 | 03-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.980830E+10 | 10262.75 | 09-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.100446E+11 | 10262.75 | 17-OCT-13:39 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.986417E+10 | 10262.75 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.103322E+11 | 10262.75 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.119814E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.929994E+10 | 9469.10 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.106287E+11 | 10262.75 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.114723E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452924E+10 |
February | 0.500553E+09 | 0.973804E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352119E+10 |
March | 0.587605E+09 | 0.112228E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305097E+10 |
April | 0.544079E+09 | 0.101408E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7419734.32 | 0.179982E+10 |
May | 0.565842E+09 | 0.970064E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39371210.59 | 0.786433E+09 |
June | 0.565842E+09 | 0.974127E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82546051.46 | 0.434703E+09 |
July | 0.544079E+09 | 0.939370E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76586092.26 | 0.366492E+09 |
August | 0.587605E+09 | 0.104459E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40240727.89 | 0.598195E+09 |
September | 0.544079E+09 | 0.100839E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1758455.17 | 0.100294E+10 |
October | 0.544079E+09 | 0.108534E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158326E+10 |
November | 0.522316E+09 | 0.111467E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247036E+10 |
December | 0.544079E+09 | 0.118835E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411948E+10 |
Annual Sum or Average | 0.659424E+10 | 0.125823E+11 | 0.291647E+11 | 0.247922E+09 | 0.242631E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.939370E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366492E+09 |
Maximum of Months | 0.587605E+09 | 0.118835E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82546051.46 | 0.452924E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247640E+11 |
February | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206216E+11 |
March | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145694E+11 |
April | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133691E+09 | 0.101409E+11 |
May | 0.00 | 0.894234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227800E+09 | 0.379753E+10 |
June | 0.00 | 0.891642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233453E+09 | 0.245606E+10 |
July | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133886E+09 | 0.284095E+10 |
August | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42229708.35 | 0.388816E+10 |
September | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5417141.03 | 0.541173E+10 |
October | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6759018.44 | 0.701759E+10 |
November | 0.00 | 0.829035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148307E+11 |
December | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251220E+11 |
Annual Sum or Average | 0.104309E+12 | 0.783236E+09 | 0.135461E+12 | ||||||
Minimum of Months | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245606E+10 |
Maximum of Months | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233453E+09 | 0.251220E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103138E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851372E+11 |
February | 0.00 | 0.929994E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688391E+11 |
March | 0.00 | 0.106287E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2013564.37 | 0.459467E+11 |
April | 0.00 | 0.978931E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196364E+10 | 0.247592E+11 |
May | 0.00 | 0.993927E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370277E+10 | 0.910071E+10 |
June | 0.00 | 0.985969E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194428E+10 | 0.679485E+10 |
July | 0.00 | 0.961480E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391953E+09 | 0.111356E+11 |
August | 0.00 | 0.103190E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320651E+09 | 0.143758E+11 |
September | 0.00 | 0.980830E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137249E+09 | 0.187462E+11 |
October | 0.00 | 0.100446E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759321E+09 | 0.177648E+11 |
November | 0.00 | 0.986417E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283223E+09 | 0.417196E+11 |
December | 0.00 | 0.103322E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832765E+11 |
Annual Sum or Average | 0.119814E+12 | 0.107336E+12 | 0.950510E+10 | 0.427596E+12 | |||||
Minimum of Months | 0.00 | 0.929994E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679485E+10 |
Maximum of Months | 0.00 | 0.106287E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370277E+10 | 0.851372E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1267.03 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14838.15 | 05-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1267.03 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14274.35 | 14-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1267.03 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 11863.54 | 15-MAR-07:00 |
April | 659.25 | 01-APR-07:10 | 1267.03 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.78 | 23-APR-16:00 | 8057.44 | 05-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1144.55 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.90 | 25-MAY-17:00 | 5554.52 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1267.03 | 09-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.50 | 29-JUN-16:10 | 2775.57 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1267.03 | 08-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1224.92 | 28-JUL-16:10 | 2725.02 | 18-JUL-06:05 |
August | 659.25 | 01-AUG-07:10 | 1267.03 | 01-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.37 | 08-AUG-16:10 | 3180.52 | 25-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1267.03 | 09-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.46 | 01-SEP-16:10 | 4536.00 | 06-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1267.03 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7632.28 | 30-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1267.03 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9984.53 | 29-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1267.03 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14047.15 | 20-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1144.55 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2725.02 | |||||
Maximum of Months | 659.25 | 1267.03 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.50 | 14838.15 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 30502.52 | 04-JAN-16:10 |
February | 0.00 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 36849.78 | 12-FEB-23:00 |
March | 0.00 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 22719.17 | 14-MAR-15:10 |
April | 0.00 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5999.22 | 23-APR-16:00 | 18565.29 | 26-APR-15:10 |
May | 0.00 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.21 | 10-MAY-15:10 | 7977.41 | 20-MAY-06:10 |
June | 0.00 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5093.47 | 29-JUN-16:00 | 7108.83 | 09-JUN-08:00 |
July | 0.00 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3483.13 | 15-JUL-15:10 | 5521.29 | 08-JUL-15:10 |
August | 0.00 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.48 | 08-AUG-16:00 | 10460.49 | 17-AUG-15:05 |
September | 0.00 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.98 | 24-SEP-15:00 | 9008.69 | 20-SEP-06:10 |
October | 0.00 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.05 | 19-OCT-15:10 | 12212.03 | 31-OCT-17:00 |
November | 0.00 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18103.61 | 22-NOV-01:50 |
December | 0.00 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 37340.95 | 18-DEC-16:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.29 | |||
Maximum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5999.22 | 37340.95 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10262.75 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 130043.00 | 04-JAN-12:00 |
February | 0.00 | 10262.75 | 01-FEB-10:20 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 101932.67 | 12-FEB-22:52 |
March | 0.00 | 10262.75 | 06-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 702.87 | 26-MAR-16:00 | 64375.61 | 14-MAR-15:50 |
April | 0.00 | 9865.92 | 04-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30623.17 | 23-APR-16:00 | 44765.82 | 26-APR-15:00 |
May | 0.00 | 9865.92 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21113.85 | 10-MAY-15:00 | 19854.56 | 20-MAY-07:10 |
June | 0.00 | 9469.10 | 08-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15520.53 | 29-JUN-16:00 | 25912.57 | 09-JUN-09:00 |
July | 0.00 | 9469.10 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9748.81 | 15-JUL-15:00 | 28549.57 | 03-JUL-11:00 |
August | 0.00 | 9865.92 | 03-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8091.47 | 08-AUG-16:00 | 42668.79 | 17-AUG-14:00 |
September | 0.00 | 10262.75 | 09-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5530.61 | 30-SEP-15:00 | 25024.70 | 20-SEP-07:10 |
October | 0.00 | 10262.75 | 17-OCT-13:39 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17046.73 | 19-OCT-15:00 | 29708.03 | 05-OCT-08:00 |
November | 0.00 | 10262.75 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9026.98 | 01-NOV-14:00 | 54192.50 | 25-NOV-11:00 |
December | 0.00 | 10262.75 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 117277.55 | 18-DEC-15:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 9469.10 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19854.56 | ||||
Maximum of Months | 0.00 | 10262.75 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 30623.17 | 130043.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 356.97 | 3289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.30 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 305.97 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.33 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.73 |
April | 0.00 | 01-APR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.44 |
May | 2762.76 | 25-MAY-16:00 | 659.25 | 772.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 | 0.00 |
June | 9726.72 | 29-JUN-05:03 | 290.07 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 |
July | 11673.80 | 25-JUL-05:02 | 435.11 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.56 |
August | 11817.51 | 14-AUG-05:03 | 290.07 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.96 |
September | 11337.03 | 02-SEP-05:03 | 290.07 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.61 |
October | 527.48 | 24-OCT-14:00 | 659.25 | 815.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.37 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.13 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11817.51 | 659.25 | 815.13 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 | 992.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12791.46 | 27-JAN-14:13 | 0.00 | 26389.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7416.93 | 22-FEB-10:55 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2029.58 |
March | 5646.75 | 23-MAR-14:00 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4411.84 | 27-APR-16:00 | 0.00 | 7761.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5797.93 | 31-MAY-06:10 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3970.27 |
June | 19212.56 | 30-JUN-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.79 | 0.00 |
July | 18806.81 | 23-JUL-13:20 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.12 | 0.00 |
August | 6939.74 | 08-AUG-15:30 | 0.00 | 7761.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2537.30 | 0.00 |
September | 7128.18 | 06-SEP-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.53 |
October | 7669.90 | 25-OCT-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6997.72 | 10-NOV-13:15 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4362.69 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9498.65 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19212.56 | 0.00 | 26389.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2537.30 | 9498.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 4829.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31808.64 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 4139.60 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50692.82 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 2069.80 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13435.16 |
April | 0.00 | 01-APR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9396.73 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2177.29 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5660.58 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3777.97 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6627.65 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3494.61 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4999.49 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9389.76 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2759.73 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26276.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2177.29 | |
Maximum of Months | 0.00 | 0.00 | 4829.53 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50692.82 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.447419E+11 | 37535.85 | 09-JAN-08:09 | 0.355903E+12 | 284472.36 | 04-JAN-17:10 |
February | 0.398738E+11 | 35247.84 | 01-FEB-15:00 | 0.267521E+12 | 266147.57 | 01-FEB-06:10 |
March | 0.445311E+11 | 35027.10 | 03-MAR-15:00 | 0.192786E+12 | 228320.28 | 15-MAR-05:10 |
April | 0.399448E+11 | 34396.20 | 10-APR-14:30 | 0.699887E+11 | 137245.89 | 04-APR-18:30 |
May | 0.397616E+11 | 34669.37 | 25-MAY-14:39 | 0.386706E+10 | 52783.90 | 01-MAY-05:19 |
June | 0.398121E+11 | 40563.65 | 30-JUN-14:00 | 0.133987E+09 | 7930.55 | 01-JUN-05:10 |
July | 0.399285E+11 | 39342.74 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.423106E+11 | 37970.63 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.398012E+11 | 36609.87 | 01-SEP-13:39 | 0.444884E+09 | 10085.90 | 29-SEP-05:10 |
October | 0.414748E+11 | 34599.45 | 30-OCT-08:09 | 0.182121E+11 | 75500.89 | 30-OCT-07:10 |
November | 0.420638E+11 | 37486.29 | 29-NOV-16:49 | 0.139850E+12 | 174796.94 | 25-NOV-02:09 |
December | 0.449378E+11 | 37492.45 | 30-DEC-16:00 | 0.331857E+12 | 283481.68 | 18-DEC-17:49 |
Annual Sum or Average | 0.499182E+12 | 0.138056E+13 | ||||
Minimum of Months | 0.397616E+11 | 34396.20 | 0.00 | 0.00 | ||
Maximum of Months | 0.449378E+11 | 40563.65 | 0.355903E+12 | 284472.36 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.200904E+11 | 0.676671E+10 | 0.112984E+11 | 0.00 | 0.419031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239615E+10 | 0.00 |
February | 0.181992E+11 | 0.539785E+10 | 0.103734E+11 | 0.00 | 0.370151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220183E+10 | 0.00 |
March | 0.210064E+11 | 0.500715E+10 | 0.121016E+11 | 0.00 | 0.392471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249133E+10 | 0.00 |
April | 0.194068E+11 | 0.387310E+10 | 0.112578E+11 | 0.00 | 0.307068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233651E+10 | 0.00 |
May | 0.198517E+11 | 0.327919E+10 | 0.117000E+11 | 0.00 | 0.245756E+10 | 0.00 | 0.00 | 0.109989E+09 | 0.00 | 0.00 | 0.00 | 0.236319E+10 | 0.00 |
June | 0.197502E+11 | 0.283120E+10 | 0.116594E+11 | 0.00 | 0.241414E+10 | 0.00 | 0.00 | 0.904800E+09 | 0.00 | 0.00 | 0.00 | 0.225237E+10 | 0.00 |
July | 0.191835E+11 | 0.305665E+10 | 0.112984E+11 | 0.00 | 0.233641E+10 | 0.00 | 0.00 | 0.184018E+10 | 0.00 | 0.00 | 0.00 | 0.221341E+10 | 0.00 |
August | 0.206190E+11 | 0.363363E+10 | 0.121016E+11 | 0.00 | 0.250660E+10 | 0.00 | 0.00 | 0.119905E+10 | 0.00 | 0.00 | 0.00 | 0.225075E+10 | 0.00 |
September | 0.194201E+11 | 0.441895E+10 | 0.112578E+11 | 0.00 | 0.231763E+10 | 0.00 | 0.00 | 0.233596E+09 | 0.00 | 0.00 | 0.00 | 0.215316E+10 | 0.00 |
October | 0.197593E+11 | 0.557642E+10 | 0.112984E+11 | 0.00 | 0.260211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223860E+10 | 0.00 |
November | 0.192692E+11 | 0.628201E+10 | 0.108562E+11 | 0.00 | 0.344593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221047E+10 | 0.00 |
December | 0.201498E+11 | 0.700111E+10 | 0.112984E+11 | 0.00 | 0.414048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234801E+10 | 0.00 |
Annual Sum or Average | 0.236705E+12 | 0.571240E+11 | 0.136501E+12 | 0.371081E+11 | 0.00 | 0.428762E+10 | 0.274558E+11 | ||||||
Minimum of Months | 0.181992E+11 | 0.283120E+10 | 0.103734E+11 | 0.00 | 0.231763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215316E+10 | 0.00 |
Maximum of Months | 0.210064E+11 | 0.700111E+10 | 0.121016E+11 | 0.00 | 0.419031E+10 | 0.00 | 0.00 | 0.184018E+10 | 0.00 | 0.00 | 0.00 | 0.249133E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.355903E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.267521E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192786E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.699887E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.386706E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133987E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.444884E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.182121E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.139850E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.331857E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138056E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.355903E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20326.42 | 02-JAN-09:09 | 5073.70 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2669.21 | 02-JAN-07:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20203.94 | 01-FEB-10:20 | 5073.70 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2669.21 | 01-FEB-07:49 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 20203.94 | 06-MAR-09:09 | 5073.70 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2669.21 | 01-MAR-08:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19807.12 | 04-APR-08:09 | 5073.70 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2669.21 | 01-APR-10:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19807.12 | 01-MAY-08:09 | 4571.25 | 01-MAY-19:30 | 10035.17 | 01-MAY-07:10 | 0.00 | 2669.21 | 01-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 19410.29 | 09-JUN-08:09 | 4571.25 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 2336.11 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 19410.29 | 03-JUL-08:09 | 4571.25 | 01-JUL-20:19 | 10035.17 | 01-JUL-07:10 | 0.00 | 2336.11 | 03-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 19929.60 | 15-AUG-08:09 | 5073.70 | 15-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 2336.11 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 20203.94 | 09-SEP-08:09 | 5073.70 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 2336.11 | 01-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20326.42 | 18-OCT-08:09 | 5073.70 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2669.21 | 12-OCT-06:49 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20326.42 | 02-NOV-08:09 | 5073.70 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2669.21 | 03-NOV-06:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20326.42 | 01-DEC-15:00 | 5073.70 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2669.21 | 01-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 19410.29 | 4571.25 | 10035.17 | 0.00 | 2336.11 | 0.00 | 0.00 | |||||
Maximum of Months | 20326.42 | 5073.70 | 10035.17 | 0.00 | 2669.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3059.50 | 27-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3104.95 | 27-FEB-12:30 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3100.32 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3038.72 | 01-APR-11:20 | 0.00 |
May | 1124.60 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2884.96 | 01-MAY-11:20 | 0.00 |
June | 9040.00 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2653.74 | 01-JUN-11:09 | 0.00 |
July | 6751.51 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2413.70 | 01-JUL-11:39 | 0.00 |
August | 5774.95 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 2226.20 | 01-AUG-11:20 | 0.00 |
September | 3358.57 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2249.25 | 25-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2486.79 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2726.50 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2921.24 | 28-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2226.20 | 0.00 | ||
Maximum of Months | 9040.00 | 0.00 | 0.00 | 0.00 | 3104.95 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 37535.85 | 09-JAN-08:09 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35247.84 | 01-FEB-15:00 | 19916.75 | 10035.17 | 0.00 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35027.10 | 03-MAR-15:00 | 19929.60 | 10035.17 | 0.00 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34396.20 | 10-APR-14:30 | 19477.69 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34669.37 | 25-MAY-14:39 | 19080.86 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 1000.90 | 0.00 |
June | 40563.65 | 30-JUN-14:00 | 18641.80 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 7739.63 | 0.00 |
July | 39342.74 | 15-JUL-14:30 | 18641.80 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 6527.25 | 0.00 |
August | 37970.63 | 08-AUG-14:00 | 18641.80 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 5312.30 | 0.00 |
September | 36609.87 | 01-SEP-13:39 | 19642.40 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 2905.78 | 0.00 |
October | 34599.45 | 30-OCT-08:09 | 20203.94 | 10035.17 | 0.00 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37486.29 | 29-NOV-16:49 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37492.45 | 30-DEC-16:00 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 2669.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 34396.20 | 18084.14 | 10035.17 | 0.00 | 0.00 | 2336.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40563.65 | 20203.94 | 10035.17 | 5073.70 | 0.00 | 2669.21 | 0.00 | 0.00 | 7739.63 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 284472.36 | 04-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 266147.57 | 01-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 228320.28 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 137245.89 | 04-APR-18:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 52783.90 | 01-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7930.55 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10085.90 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 75500.89 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 174796.94 | 25-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 283481.68 | 18-DEC-17:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 284472.36 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 16.21 | 9.83 | 19.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.00 | 17.26 | 8.83 | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17.00 | 17.62 | 11.00 | 19.06 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10.50 | 18.71 | 8.83 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4.83 | 19.73 | 4.67 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.50 | 20.51 | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
September | 0.50 | 20.50 | 0.50 | 20.50 | 0.17 | 24.47 | 0.17 | 24.47 |
October | 6.17 | 20.10 | 6.17 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.50 | 18.82 | 8.50 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23.17 | 16.70 | 9.33 | 19.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.17 | 17.46 | 68.17 | 19.40 | 1.17 | 24.51 | 1.17 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.00 | 20.51 | 11.00 | 20.51 | 0.50 | 24.52 | 0.50 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.67 | 14.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 108.17 | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100.00 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.00 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11.00 | 14.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86.33 | 14.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121.17 | 14.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 608.67 | 14.33 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.17 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.33 | 8.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 8.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.67 | 8.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.17 | 8.55 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.33 | 8.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
May | 311.17 | 22.05 | 162.50 | 21.14 | 162.50 | 21.14 |
June | 248.00 | 23.16 | 77.67 | 23.30 | 39.50 | 22.72 |
July | 28.17 | 23.80 | 171.67 | 23.91 | 5.67 | 23.95 |
August | 64.50 | 23.64 | 147.50 | 23.90 | 0.83 | 24.02 |
September | 274.17 | 22.67 | 64.50 | 21.82 | 50.83 | 21.26 |
October | 300.00 | 21.20 | 269.00 | 21.09 | 269.00 | 21.09 |
November | 288.00 | 21.06 | 286.50 | 21.06 | 286.50 | 21.06 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3014.00 | 21.56 | 2679.33 | 21.48 | 2314.83 | 21.09 |
Minimum of Months | 28.17 | 21.03 | 64.50 | 21.03 | 0.83 | 21.03 |
Maximum of Months | 324.00 | 23.80 | 324.00 | 23.91 | 324.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.507484E+09 | 0.109989E+09 | 61.92 | 0.439538E+09 | 67945878.48 | 0.00 | 0.70 | 25-MAY-16:00 | 0.00 | 01-MAY-00:10 | 5158.23 | 25-MAY-16:00 | 4306.86 | 25-MAY-16:00 | 1217.87 | 26-MAY-12:10 | 1124.60 | 25-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.237449E+10 | 0.500207E+09 | 182.06 | 0.183529E+10 | 0.539200E+09 | 0.00 | 1.00 | 29-JUN-05:03 | 0.00 | 01-JUN-00:10 | 16750.21 | 30-JUN-05:02 | 11185.64 | 29-JUN-05:03 | 7348.17 | 30-JUN-05:05 | 3333.25 | 30-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.516049E+10 | 0.104857E+10 | 275.56 | 0.413567E+10 | 0.102482E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 16657.84 | 05-JUL-05:03 | 13046.33 | 25-JUL-05:02 | 6844.87 | 05-JUL-05:03 | 3241.02 | 05-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.444954E+10 | 0.904039E+09 | 282.76 | 0.355127E+10 | 0.898261E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 16180.78 | 09-AUG-05:03 | 13455.59 | 14-AUG-05:03 | 5420.84 | 09-AUG-05:03 | 3176.03 | 09-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 0.984060E+09 | 0.205104E+09 | 118.04 | 0.887833E+09 | 96227085.57 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 16263.61 | 01-SEP-05:03 | 12918.96 | 02-SEP-05:03 | 5784.80 | 01-SEP-05:03 | 3187.66 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.134761E+11 | 0.276791E+10 | 920.34 | 0.108496E+11 | 0.262646E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.516049E+10 | 0.104857E+10 | 282.76 | 0.413567E+10 | 0.102482E+10 | 0.00 | 1.00 | 0.00 | 16750.21 | 13455.59 | 7348.17 | 3333.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.173897E+10 | 0.404592E+09 | 41.83 | 0.113980E+10 | 0.599166E+09 | 0.00 | 1.00 | 29-JUN-12:40 | 0.00 | 01-JUN-00:10 | 31763.20 | 30-JUN-17:12 | 21203.77 | 30-JUN-17:12 | 10559.43 | 30-JUN-17:12 | 7545.68 | 29-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 0.348667E+10 | 0.791609E+09 | 126.46 | 0.231992E+10 | 0.116675E+10 | 0.00 | 1.00 | 23-JUL-13:20 | 0.00 | 01-JUL-00:10 | 35785.14 | 23-JUL-13:20 | 21067.91 | 23-JUL-13:20 | 14717.22 | 23-JUL-13:20 | 8215.18 | 23-JUL-13:20 | 0.00 | 01-JUL-00:10 |
August | 0.128628E+10 | 0.295013E+09 | 67.50 | 0.844893E+09 | 0.441389E+09 | 0.00 | 0.88 | 08-AUG-15:40 | 0.00 | 01-AUG-00:10 | 16740.76 | 08-AUG-15:40 | 10609.93 | 08-AUG-15:30 | 6134.00 | 08-AUG-15:40 | 3757.26 | 08-AUG-15:40 | 0.00 | 01-AUG-00:10 |
September | 0.123380E+09 | 28492463.29 | 6.83 | 91382433.61 | 31997195.60 | 0.00 | 0.51 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 8569.62 | 01-SEP-15:00 | 6672.22 | 01-SEP-15:00 | 2037.65 | 01-SEP-14:00 | 1968.56 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.663530E+10 | 0.151971E+10 | 242.63 | 0.439600E+10 | 0.223930E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.348667E+10 | 0.791609E+09 | 126.46 | 0.231992E+10 | 0.116675E+10 | 0.00 | 1.00 | 0.00 | 35785.14 | 21203.77 | 14717.22 | 8215.18 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.54 | 31.01 | 42.53 | 25.32 | 241.95 | 0.00 | 0.00 | 744.00 |
February | 118.89 | 54.34 | 64.56 | 68.73 | 187.34 | 0.00 | 0.00 | 672.00 |
March | 156.45 | 80.20 | 76.25 | 116.61 | 139.64 | 0.00 | 0.00 | 744.00 |
April | 199.37 | 100.97 | 98.40 | 185.95 | 76.31 | 0.00 | 0.00 | 720.00 |
May | 245.44 | 117.24 | 128.19 | 266.70 | 40.06 | 0.00 | 0.00 | 744.00 |
June | 236.47 | 102.28 | 134.19 | 263.84 | 30.79 | 0.00 | 0.00 | 720.00 |
July | 252.93 | 117.86 | 135.07 | 279.98 | 38.12 | 0.00 | 0.00 | 744.00 |
August | 207.16 | 93.81 | 113.35 | 221.20 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 162.30 | 72.79 | 89.51 | 157.59 | 60.81 | 0.00 | 0.00 | 720.00 |
October | 102.68 | 41.25 | 61.43 | 79.94 | 83.14 | 0.00 | 0.00 | 744.00 |
November | 62.65 | 21.35 | 41.30 | 27.98 | 135.30 | 0.00 | 0.00 | 720.00 |
December | 55.33 | 19.25 | 36.08 | 12.84 | 233.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 156.31 | 71.13 | 85.18 | 142.65 | 108.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 55.33 | 19.25 | 36.08 | 12.84 | 30.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 252.93 | 117.86 | 135.07 | 279.98 | 241.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.54 | 31.01 | 42.53 | 25.32 | 241.95 | 0.00 | 0.00 | 744.00 |
February | 118.89 | 54.34 | 64.56 | 68.73 | 187.34 | 0.00 | 0.00 | 672.00 |
March | 156.45 | 80.20 | 76.25 | 116.61 | 139.64 | 0.00 | 0.00 | 744.00 |
April | 199.37 | 100.97 | 98.40 | 185.95 | 76.31 | 0.00 | 0.00 | 720.00 |
May | 245.44 | 117.24 | 128.19 | 266.70 | 40.06 | 0.00 | 0.00 | 744.00 |
June | 236.47 | 102.28 | 134.19 | 263.84 | 30.79 | 0.00 | 0.00 | 720.00 |
July | 252.93 | 117.86 | 135.07 | 279.98 | 38.12 | 0.00 | 0.00 | 744.00 |
August | 207.16 | 93.81 | 113.35 | 221.20 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 162.30 | 72.79 | 89.51 | 157.59 | 60.81 | 0.00 | 0.00 | 720.00 |
October | 102.68 | 41.25 | 61.43 | 79.94 | 83.14 | 0.00 | 0.00 | 744.00 |
November | 62.65 | 21.35 | 41.30 | 27.98 | 135.30 | 0.00 | 0.00 | 720.00 |
December | 55.33 | 19.25 | 36.08 | 12.84 | 233.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 156.31 | 71.13 | 85.18 | 142.65 | 108.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 55.33 | 19.25 | 36.08 | 12.84 | 30.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 252.93 | 117.86 | 135.07 | 279.98 | 241.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.16 | 0.00 | 19.16 | 0.19 | 153.91 | 0.00 | 0.00 | 744.00 |
February | 29.43 | 0.00 | 29.43 | 2.38 | 118.87 | 0.00 | 0.00 | 672.00 |
March | 36.22 | 0.00 | 36.22 | 6.15 | 87.07 | 0.00 | 0.00 | 744.00 |
April | 47.57 | 0.46 | 47.11 | 25.03 | 45.49 | 0.00 | 0.00 | 720.00 |
May | 66.82 | 3.59 | 63.23 | 57.61 | 22.09 | 0.00 | 0.00 | 744.00 |
June | 74.47 | 8.14 | 66.33 | 71.41 | 17.00 | 0.00 | 0.00 | 720.00 |
July | 71.08 | 6.00 | 65.08 | 65.69 | 21.00 | 0.00 | 0.00 | 744.00 |
August | 54.25 | 1.09 | 53.16 | 46.71 | 25.29 | 0.00 | 0.00 | 744.00 |
September | 42.17 | 0.03 | 42.14 | 28.77 | 36.18 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 0.00 | 29.25 | 11.57 | 50.11 | 0.00 | 0.00 | 744.00 |
November | 19.37 | 0.00 | 19.37 | 1.76 | 84.10 | 0.00 | 0.00 | 720.00 |
December | 16.23 | 0.00 | 16.23 | 0.02 | 147.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.23 | 1.62 | 40.62 | 26.58 | 67.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.23 | 0.00 | 16.23 | 0.02 | 17.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.47 | 8.14 | 66.33 | 71.41 | 153.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.16 | 0.00 | 19.16 | 0.19 | 153.91 | 0.00 | 0.00 | 744.00 |
February | 29.43 | 0.00 | 29.43 | 2.37 | 118.87 | 0.00 | 0.00 | 672.00 |
March | 36.22 | 0.00 | 36.22 | 6.15 | 87.07 | 0.00 | 0.00 | 744.00 |
April | 47.57 | 0.46 | 47.11 | 25.03 | 45.49 | 0.00 | 0.00 | 720.00 |
May | 66.82 | 3.59 | 63.23 | 57.61 | 22.09 | 0.00 | 0.00 | 744.00 |
June | 74.47 | 8.14 | 66.33 | 71.41 | 17.00 | 0.00 | 0.00 | 720.00 |
July | 71.08 | 6.00 | 65.08 | 65.69 | 21.00 | 0.00 | 0.00 | 744.00 |
August | 54.25 | 1.09 | 53.15 | 46.71 | 25.29 | 0.00 | 0.00 | 744.00 |
September | 42.17 | 0.03 | 42.14 | 28.77 | 36.18 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 0.00 | 29.25 | 11.57 | 50.11 | 0.00 | 0.00 | 744.00 |
November | 19.37 | 0.00 | 19.37 | 1.76 | 84.10 | 0.00 | 0.00 | 720.00 |
December | 16.23 | 0.00 | 16.23 | 0.02 | 147.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.23 | 1.62 | 40.61 | 26.58 | 67.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.23 | 0.00 | 16.23 | 0.02 | 17.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.47 | 8.14 | 66.33 | 71.41 | 153.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.29 | 9.36 | 16.93 | 7.77 | 121.51 | 0.00 | 0.00 | 744.00 |
February | 46.38 | 21.49 | 24.89 | 35.68 | 93.70 | 0.00 | 0.00 | 672.00 |
March | 66.50 | 37.64 | 28.86 | 67.16 | 66.20 | 0.00 | 0.00 | 744.00 |
April | 96.69 | 60.84 | 35.85 | 122.39 | 36.40 | 4.33 | 0.00 | 720.00 |
May | 118.56 | 66.49 | 52.07 | 164.30 | 22.76 | 0.00 | 0.00 | 744.00 |
June | 125.09 | 71.96 | 53.13 | 171.74 | 21.83 | 32.33 | 0.00 | 720.00 |
July | 127.85 | 76.09 | 51.77 | 168.56 | 30.39 | 11.50 | 0.00 | 744.00 |
August | 101.89 | 57.40 | 44.49 | 132.06 | 30.18 | 10.00 | 0.00 | 744.00 |
September | 74.13 | 38.36 | 35.77 | 91.12 | 35.41 | 5.33 | 0.00 | 720.00 |
October | 42.74 | 16.40 | 26.34 | 48.45 | 37.36 | 16.50 | 0.00 | 744.00 |
November | 25.62 | 7.97 | 17.65 | 19.11 | 60.30 | 14.33 | 0.00 | 720.00 |
December | 20.39 | 5.33 | 15.06 | 3.43 | 114.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.81 | 39.19 | 33.62 | 86.23 | 55.76 | 94.33 | 0.00 | 8760.00 |
Minimum of Months | 20.39 | 5.33 | 15.06 | 3.43 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.85 | 76.09 | 53.13 | 171.74 | 121.51 | 32.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196982E+09 | 83064779.19 | 0.113918E+09 | 67818480.71 | 0.648040E+09 |
February | 0.287631E+09 | 0.131452E+09 | 0.156179E+09 | 0.166266E+09 | 0.453205E+09 |
March | 0.419027E+09 | 0.214795E+09 | 0.204232E+09 | 0.312335E+09 | 0.374011E+09 |
April | 0.516759E+09 | 0.261702E+09 | 0.255057E+09 | 0.481992E+09 | 0.197790E+09 |
May | 0.657380E+09 | 0.314025E+09 | 0.343355E+09 | 0.714340E+09 | 0.107309E+09 |
June | 0.612921E+09 | 0.265103E+09 | 0.347818E+09 | 0.683869E+09 | 79817629.03 |
July | 0.677437E+09 | 0.315669E+09 | 0.361768E+09 | 0.749898E+09 | 0.102110E+09 |
August | 0.554860E+09 | 0.251252E+09 | 0.303608E+09 | 0.592456E+09 | 0.118236E+09 |
September | 0.420675E+09 | 0.188670E+09 | 0.232005E+09 | 0.408467E+09 | 0.157629E+09 |
October | 0.275020E+09 | 0.110496E+09 | 0.164524E+09 | 0.214103E+09 | 0.222681E+09 |
November | 0.162384E+09 | 55330218.03 | 0.107054E+09 | 72532722.93 | 0.350698E+09 |
December | 0.148194E+09 | 51560152.96 | 96633727.19 | 34396581.43 | 0.625590E+09 |
Annual Sum or Average | 0.492927E+10 | 0.224312E+10 | 0.268615E+10 | 0.449847E+10 | 0.343712E+10 |
Minimum of Months | 0.148194E+09 | 51560152.96 | 96633727.19 | 34396581.43 | 79817629.03 |
Maximum of Months | 0.677437E+09 | 0.315669E+09 | 0.361768E+09 | 0.749898E+09 | 0.648040E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196982E+09 | 83064779.19 | 0.113918E+09 | 67818480.71 | 0.648040E+09 |
February | 0.287631E+09 | 0.131452E+09 | 0.156179E+09 | 0.166266E+09 | 0.453205E+09 |
March | 0.419027E+09 | 0.214795E+09 | 0.204232E+09 | 0.312335E+09 | 0.374011E+09 |
April | 0.516759E+09 | 0.261702E+09 | 0.255057E+09 | 0.481992E+09 | 0.197790E+09 |
May | 0.657380E+09 | 0.314025E+09 | 0.343355E+09 | 0.714340E+09 | 0.107309E+09 |
June | 0.612921E+09 | 0.265103E+09 | 0.347818E+09 | 0.683869E+09 | 79817629.03 |
July | 0.677437E+09 | 0.315669E+09 | 0.361768E+09 | 0.749898E+09 | 0.102110E+09 |
August | 0.554860E+09 | 0.251252E+09 | 0.303608E+09 | 0.592456E+09 | 0.118236E+09 |
September | 0.420675E+09 | 0.188670E+09 | 0.232005E+09 | 0.408467E+09 | 0.157629E+09 |
October | 0.275020E+09 | 0.110496E+09 | 0.164524E+09 | 0.214103E+09 | 0.222681E+09 |
November | 0.162384E+09 | 55330218.03 | 0.107054E+09 | 72532722.93 | 0.350698E+09 |
December | 0.148194E+09 | 51560152.96 | 96633727.19 | 34396581.43 | 0.625590E+09 |
Annual Sum or Average | 0.492927E+10 | 0.224312E+10 | 0.268615E+10 | 0.449847E+10 | 0.343712E+10 |
Minimum of Months | 0.148194E+09 | 51560152.96 | 96633727.19 | 34396581.43 | 79817629.03 |
Maximum of Months | 0.677437E+09 | 0.315669E+09 | 0.361768E+09 | 0.749898E+09 | 0.648040E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51321087.92 | 0.00 | 51321087.92 | 516384.22 | 0.412227E+09 |
February | 71204182.79 | 0.00 | 71204182.79 | 5745657.06 | 0.287580E+09 |
March | 97016096.23 | 6666.66 | 97009429.57 | 16467750.75 | 0.233216E+09 |
April | 0.123309E+09 | 1199240.75 | 0.122110E+09 | 64867812.73 | 0.117904E+09 |
May | 0.178969E+09 | 9617355.26 | 0.169352E+09 | 0.154313E+09 | 59167062.17 |
June | 0.193036E+09 | 21099889.06 | 0.171936E+09 | 0.185100E+09 | 44070559.89 |
July | 0.190386E+09 | 16074186.04 | 0.174312E+09 | 0.175937E+09 | 56248968.11 |
August | 0.145299E+09 | 2924583.83 | 0.142375E+09 | 0.125100E+09 | 67735161.50 |
September | 0.109298E+09 | 76927.55 | 0.109222E+09 | 74575927.59 | 93771521.18 |
October | 78342328.43 | 0.00 | 78342328.43 | 30987216.53 | 0.134225E+09 |
November | 50199242.31 | 0.00 | 50199242.31 | 4552462.73 | 0.217993E+09 |
December | 43483305.84 | 0.00 | 43483305.84 | 42834.11 | 0.393732E+09 |
Annual Sum or Average | 0.133186E+10 | 50998849.14 | 0.128087E+10 | 0.838207E+09 | 0.211787E+10 |
Minimum of Months | 43483305.84 | 0.00 | 43483305.84 | 42834.11 | 44070559.89 |
Maximum of Months | 0.193036E+09 | 21099889.06 | 0.174312E+09 | 0.185100E+09 | 0.412227E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51319393.41 | 0.00 | 51319393.41 | 516292.57 | 0.412227E+09 |
February | 71201942.39 | 0.00 | 71201942.39 | 5745040.67 | 0.287581E+09 |
March | 97013172.57 | 6666.35 | 97006506.23 | 16466307.65 | 0.233217E+09 |
April | 0.123305E+09 | 1199184.54 | 0.122106E+09 | 64864912.25 | 0.117904E+09 |
May | 0.178964E+09 | 9616904.48 | 0.169347E+09 | 0.154308E+09 | 59166730.32 |
June | 0.193029E+09 | 21098900.08 | 0.171930E+09 | 0.185094E+09 | 44070181.96 |
July | 0.190380E+09 | 16073432.62 | 0.174307E+09 | 0.175931E+09 | 56248513.82 |
August | 0.145295E+09 | 2924446.75 | 0.142370E+09 | 0.125096E+09 | 67734844.76 |
September | 0.109295E+09 | 76923.94 | 0.109218E+09 | 74572640.23 | 93771268.15 |
October | 78339715.69 | 0.00 | 78339715.69 | 30985095.08 | 0.134225E+09 |
November | 50197531.95 | 0.00 | 50197531.95 | 4551980.07 | 0.217994E+09 |
December | 43481822.99 | 0.00 | 43481822.99 | 42804.63 | 0.393733E+09 |
Annual Sum or Average | 0.133182E+10 | 50996458.76 | 0.128083E+10 | 0.838174E+09 | 0.211787E+10 |
Minimum of Months | 43481822.99 | 0.00 | 43481822.99 | 42804.63 | 44070181.96 |
Maximum of Months | 0.193029E+09 | 21098900.08 | 0.174307E+09 | 0.185094E+09 | 0.412227E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70416440.77 | 25071343.46 | 45345097.31 | 20812837.31 | 0.325442E+09 |
February | 0.112213E+09 | 51997576.17 | 60214995.22 | 86314971.58 | 0.226679E+09 |
March | 0.178109E+09 | 0.100818E+09 | 77291015.72 | 0.179883E+09 | 0.177299E+09 |
April | 0.250615E+09 | 0.157703E+09 | 92912174.16 | 0.317245E+09 | 94340815.95 |
May | 0.317539E+09 | 0.178074E+09 | 0.139465E+09 | 0.440065E+09 | 60956175.42 |
June | 0.324231E+09 | 0.186516E+09 | 0.137715E+09 | 0.445149E+09 | 56594012.96 |
July | 0.342446E+09 | 0.203796E+09 | 0.138649E+09 | 0.451474E+09 | 81390824.35 |
August | 0.272903E+09 | 0.153733E+09 | 0.119169E+09 | 0.353703E+09 | 80829330.36 |
September | 0.192138E+09 | 99419102.70 | 92719180.68 | 0.236188E+09 | 91779218.68 |
October | 0.114471E+09 | 43932772.69 | 70537742.15 | 0.129779E+09 | 0.100053E+09 |
November | 66412679.97 | 20657165.13 | 45755514.84 | 49527267.47 | 0.156288E+09 |
December | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 0.306716E+09 |
Annual Sum or Average | 0.229610E+10 | 0.123600E+10 | 0.106011E+10 | 0.271932E+10 | 0.175837E+10 |
Minimum of Months | 54610847.85 | 14277727.85 | 40333120.00 | 9182104.05 | 56594012.96 |
Maximum of Months | 0.342446E+09 | 0.203796E+09 | 0.139465E+09 | 0.451474E+09 | 0.325442E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.17 | 775.86 | 185.41 | 62.03 | 123.39 | 0.00 | 0.00 |
February | 128.49 | 598.71 | 296.65 | 108.67 | 187.98 | 0.00 | 0.00 |
March | 236.59 | 444.50 | 385.34 | 160.40 | 224.94 | 0.00 | 0.00 |
April | 419.94 | 241.57 | 493.88 | 202.86 | 291.02 | 0.00 | 0.00 |
May | 647.80 | 123.47 | 624.51 | 241.67 | 382.84 | 0.00 | 0.00 |
June | 668.34 | 93.43 | 621.88 | 220.84 | 401.04 | 0.00 | 0.00 |
July | 688.92 | 115.84 | 648.01 | 247.72 | 400.30 | 0.00 | 0.00 |
August | 535.51 | 138.57 | 522.82 | 189.80 | 333.02 | 0.00 | 0.00 |
September | 371.56 | 192.82 | 408.93 | 145.64 | 263.29 | 0.00 | 0.00 |
October | 180.87 | 264.36 | 263.86 | 82.51 | 181.35 | 0.00 | 0.00 |
November | 52.66 | 431.98 | 164.03 | 42.69 | 121.34 | 0.00 | 0.00 |
December | 14.98 | 750.41 | 143.13 | 38.50 | 104.63 | 0.00 | 0.00 |
Annual Sum or Average | 332.90 | 346.74 | 397.08 | 145.49 | 251.59 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 93.43 | 143.13 | 38.50 | 104.63 | 0.00 | 0.00 |
Maximum of Months | 688.92 | 775.86 | 648.01 | 247.72 | 401.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 77.71 | 1215.06 | 262.90 | 93.61 | 169.30 | 0.00 | 0.00 |
February | 356.79 | 937.00 | 463.84 | 214.94 | 248.90 | 0.00 | 0.00 |
March | 671.61 | 661.96 | 664.98 | 376.41 | 288.57 | 0.00 | 0.00 |
April | 1223.94 | 363.97 | 966.88 | 608.42 | 358.46 | 0.00 | 0.00 |
May | 1643.02 | 227.58 | 1185.56 | 664.85 | 520.70 | 0.00 | 0.00 |
June | 1717.39 | 218.34 | 1250.89 | 719.58 | 531.31 | 0.00 | 0.00 |
July | 1685.61 | 303.88 | 1278.55 | 760.89 | 517.66 | 0.00 | 0.00 |
August | 1320.58 | 301.78 | 1018.90 | 573.98 | 444.93 | 0.00 | 0.00 |
September | 911.22 | 354.09 | 741.27 | 383.56 | 357.71 | 0.00 | 0.00 |
October | 484.54 | 373.55 | 427.38 | 164.03 | 263.36 | 0.00 | 0.00 |
November | 191.08 | 602.96 | 256.22 | 79.70 | 176.53 | 0.00 | 0.00 |
December | 34.28 | 1145.15 | 203.89 | 53.31 | 150.59 | 0.00 | 0.00 |
Annual Sum or Average | 862.29 | 557.57 | 728.09 | 391.93 | 336.16 | 0.00 | 0.00 |
Minimum of Months | 34.28 | 218.34 | 203.89 | 53.31 | 150.59 | 0.00 | 0.00 |
Maximum of Months | 1717.39 | 1215.06 | 1278.55 | 760.89 | 531.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 94187728.40 | 0.207805E+10 | 0.496605E+09 | 0.166130E+09 | 0.330476E+09 | 0.00 | 0.00 |
February | 0.310850E+09 | 0.144840E+10 | 0.717668E+09 | 0.262903E+09 | 0.454764E+09 | 0.00 | 0.00 |
March | 0.633694E+09 | 0.119055E+10 | 0.103208E+10 | 0.429603E+09 | 0.602480E+09 | 0.00 | 0.00 |
April | 0.108848E+10 | 0.626149E+09 | 0.128013E+10 | 0.525803E+09 | 0.754331E+09 | 0.00 | 0.00 |
May | 0.173507E+10 | 0.330715E+09 | 0.167269E+10 | 0.647284E+09 | 0.102541E+10 | 0.00 | 0.00 |
June | 0.173232E+10 | 0.242168E+09 | 0.161191E+10 | 0.572405E+09 | 0.103950E+10 | 0.00 | 0.00 |
July | 0.184520E+10 | 0.310253E+09 | 0.173564E+10 | 0.663485E+09 | 0.107216E+10 | 0.00 | 0.00 |
August | 0.143430E+10 | 0.371138E+09 | 0.140031E+10 | 0.508354E+09 | 0.891961E+09 | 0.00 | 0.00 |
September | 0.963071E+09 | 0.499789E+09 | 0.105994E+10 | 0.377493E+09 | 0.682451E+09 | 0.00 | 0.00 |
October | 0.484430E+09 | 0.708063E+09 | 0.706722E+09 | 0.220992E+09 | 0.485730E+09 | 0.00 | 0.00 |
November | 0.136485E+09 | 0.111970E+10 | 0.425165E+09 | 0.110660E+09 | 0.314504E+09 | 0.00 | 0.00 |
December | 40128953.86 | 0.200990E+10 | 0.383353E+09 | 0.103120E+09 | 0.280233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104982E+11 | 0.109349E+11 | 0.125222E+11 | 0.458823E+10 | 0.793400E+10 | 0.00 | 0.00 |
Minimum of Months | 40128953.86 | 0.242168E+09 | 0.383353E+09 | 0.103120E+09 | 0.280233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184520E+10 | 0.207805E+10 | 0.173564E+10 | 0.663485E+09 | 0.107216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208126E+09 | 0.325442E+10 | 0.704164E+09 | 0.250713E+09 | 0.453451E+09 | 0.00 | 0.00 |
February | 0.863150E+09 | 0.226679E+10 | 0.112213E+10 | 0.519976E+09 | 0.602150E+09 | 0.00 | 0.00 |
March | 0.179883E+10 | 0.177299E+10 | 0.178109E+10 | 0.100818E+10 | 0.772910E+09 | 0.00 | 0.00 |
April | 0.317245E+10 | 0.943408E+09 | 0.250615E+10 | 0.157703E+10 | 0.929122E+09 | 0.00 | 0.00 |
May | 0.440065E+10 | 0.609558E+09 | 0.317539E+10 | 0.178074E+10 | 0.139465E+10 | 0.00 | 0.00 |
June | 0.445148E+10 | 0.565940E+09 | 0.324231E+10 | 0.186516E+10 | 0.137715E+10 | 0.00 | 0.00 |
July | 0.451473E+10 | 0.813908E+09 | 0.342446E+10 | 0.203796E+10 | 0.138649E+10 | 0.00 | 0.00 |
August | 0.353703E+10 | 0.808293E+09 | 0.272903E+10 | 0.153733E+10 | 0.119169E+10 | 0.00 | 0.00 |
September | 0.236187E+10 | 0.917790E+09 | 0.192138E+10 | 0.994191E+09 | 0.927192E+09 | 0.00 | 0.00 |
October | 0.129779E+10 | 0.100053E+10 | 0.114471E+10 | 0.439328E+09 | 0.705377E+09 | 0.00 | 0.00 |
November | 0.495272E+09 | 0.156288E+10 | 0.664127E+09 | 0.206572E+09 | 0.457555E+09 | 0.00 | 0.00 |
December | 91819577.36 | 0.306716E+10 | 0.546108E+09 | 0.142777E+09 | 0.403331E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271932E+11 | 0.175837E+11 | 0.229610E+11 | 0.123600E+11 | 0.106011E+11 | 0.00 | 0.00 |
Minimum of Months | 91819577.36 | 0.565940E+09 | 0.546108E+09 | 0.142777E+09 | 0.403331E+09 | 0.00 | 0.00 |
Maximum of Months | 0.451473E+10 | 0.325442E+10 | 0.342446E+10 | 0.203796E+10 | 0.139465E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.110815E+10 | -.102007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88079051.8 | 58.99 | 0.00 | 0.00 |
February | 0.103778E+10 | -958353173.6 | 0.00 | 0.00 | 672.00 | 0.00 | -79424582.8 | 59.00 | 0.00 | 0.00 |
March | 0.120339E+10 | -.111584E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87548931.6 | 58.99 | 0.00 | 0.00 |
April | 0.108951E+10 | -.100534E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84168070.6 | 58.99 | 0.00 | 0.00 |
May | 0.107500E+10 | -993233828.6 | 0.00 | 0.00 | 744.00 | 0.00 | -81767887.0 | 58.99 | 0.00 | 0.00 |
June | 0.100543E+10 | -930608589.9 | 0.00 | 0.00 | 720.00 | 0.00 | -74824216.6 | 58.99 | 0.00 | 0.00 |
July | 0.924996E+09 | -852032973.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72962629.7 | 58.99 | 0.00 | 0.00 |
August | 0.962555E+09 | -888781980.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73772726.4 | 58.99 | 0.00 | 0.00 |
September | 0.905961E+09 | -830392257.3 | 0.00 | 0.00 | 720.00 | 0.00 | -75569005.6 | 58.99 | 0.00 | 0.00 |
October | 0.950114E+09 | -864986692.6 | 0.00 | 0.00 | 744.00 | 0.00 | -85127330.5 | 58.99 | 0.00 | 0.00 |
November | 0.964050E+09 | -879496488.5 | 0.00 | 0.00 | 720.00 | 0.00 | -84553690.4 | 58.98 | 0.00 | 0.00 |
December | 0.105956E+10 | -971526167.2 | 0.00 | 0.00 | 744.00 | 0.00 | -88033599.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.122865E+11 | -.113107E+11 | 8760.00 | -975831722.8 | 58.99 | |||||
Minimum of Months | 0.905961E+09 | -.111584E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88079051.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.120339E+10 | -830392257.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72962629.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.96 | 0.88 | 08-JAN-11:20 | 113.62 | 8.44 | 0.00 | 27.83 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.95 | 0.88 | 02-FEB-11:09 | 141.44 | 9.73 | 0.00 | 64.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.94 | 0.88 | 02-MAR-10:39 | 153.04 | 10.01 | 0.00 | 97.33 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.94 | 0.88 | 01-APR-10:39 | 180.36 | 10.55 | 0.00 | 141.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.92 | 0.88 | 01-MAY-15:09 | 882.27 | 12.11 | 0.00 | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.88 | 01-JUN-07:00 | 370.41 | 12.45 | 1.83 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.91 | 0.88 | 01-JUL-07:00 | 958.81 | 13.62 | 27.67 | 271.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.91 | 0.88 | 01-AUG-07:00 | 259.48 | 12.25 | 0.00 | 221.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.93 | 0.88 | 02-SEP-09:20 | 194.28 | 11.11 | 0.00 | 138.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.94 | 0.88 | 01-OCT-09:50 | 158.56 | 10.09 | 0.00 | 93.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.96 | 0.88 | 01-NOV-10:09 | 118.75 | 8.84 | 0.00 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.96 | 0.88 | 04-DEC-10:30 | 110.11 | 8.34 | 0.00 | 8.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.93 | 355.50 | 10.96 | 29.50 | 1607.67 | ||||||
Minimum of Months | 226.33 | 0.91 | 0.88 | 110.11 | 8.34 | 0.00 | 8.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.96 | 0.88 | 958.81 | 13.62 | 27.67 | 271.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.85 | 0.64 | 17-JAN-15:09 | 301.87 | 23.55 | 145.00 | 24.17 | 123.41 | 21.25 | 120.67 | 0.00 |
February | 265.33 | 0.79 | 0.61 | 18-FEB-15:39 | 610.91 | 25.56 | 181.33 | 85.83 | 169.83 | 22.34 | 177.50 | 5.17 |
March | 254.17 | 0.77 | 0.61 | 02-MAR-16:10 | 632.96 | 25.01 | 197.50 | 103.17 | 536.50 | 25.66 | 222.33 | 55.83 |
April | 296.33 | 0.76 | 0.61 | 02-APR-14:20 | 457.09 | 23.07 | 214.00 | 123.00 | 493.90 | 24.31 | 263.50 | 79.17 |
May | 437.50 | 0.74 | 0.61 | 01-MAY-14:50 | 385.76 | 22.44 | 282.17 | 227.50 | 516.81 | 23.53 | 331.67 | 106.50 |
June | 401.83 | 0.73 | 0.61 | 01-JUN-14:00 | 420.27 | 22.63 | 279.33 | 217.17 | 511.40 | 23.83 | 338.33 | 108.50 |
July | 409.17 | 0.72 | 0.61 | 01-JUL-13:30 | 437.69 | 22.96 | 296.00 | 227.67 | 596.07 | 24.10 | 346.67 | 128.33 |
August | 352.83 | 0.73 | 0.61 | 01-AUG-13:50 | 431.54 | 23.23 | 251.17 | 181.17 | 489.56 | 24.17 | 302.17 | 104.00 |
September | 344.17 | 0.77 | 0.61 | 01-SEP-14:30 | 548.75 | 24.33 | 229.17 | 134.50 | 465.94 | 24.79 | 253.67 | 64.33 |
October | 299.00 | 0.82 | 0.61 | 01-OCT-14:20 | 389.07 | 23.80 | 184.17 | 69.33 | 165.29 | 22.50 | 185.67 | 9.00 |
November | 255.50 | 0.87 | 0.64 | 09-NOV-14:09 | 221.72 | 21.93 | 129.33 | 14.83 | 112.86 | 20.78 | 122.33 | 0.00 |
December | 226.33 | 0.89 | 0.77 | 01-DEC-10:00 | 191.83 | 20.74 | 104.67 | 0.00 | 106.71 | 20.79 | 97.50 | 0.00 |
Annual Sum or Average | 3785.50 | 0.78 | 424.29 | 23.24 | 2493.83 | 1408.33 | 388.01 | 23.34 | 2762.00 | 660.83 | ||
Minimum of Months | 226.33 | 0.72 | 0.61 | 191.83 | 20.74 | 104.67 | 0.00 | 106.71 | 20.78 | 97.50 | 0.00 | |
Maximum of Months | 437.50 | 0.89 | 0.77 | 632.96 | 25.56 | 296.00 | 227.67 | 596.07 | 25.66 | 346.67 | 128.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139987E+11 | 23911.64 | 01-JAN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108893E+11 | 23911.64 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104925E+11 | 23911.64 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.569114E+10 | 23911.64 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139486E+10 | 23911.64 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91778915.73 | 23911.64 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297347E+09 | 23911.64 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317017E+10 | 23911.64 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.636245E+10 | 23911.64 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122097E+11 | 23911.64 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645978E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139987E+11 | 23911.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.603067E+11 | 60947.95 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452281E+11 | 60947.95 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346939E+11 | 60947.95 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150524E+11 | 60947.95 | 01-APR-18:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847788E+09 | 60947.95 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578866E+10 | 60947.95 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250845E+11 | 60947.95 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555398E+11 | 60947.95 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242542E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.603067E+11 | 60947.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202854E+12 | 142718.30 | 03-JAN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151538E+12 | 142718.30 | 01-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102952E+12 | 122238.68 | 15-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320784E+11 | 76016.45 | 04-APR-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.458006E+09 | 18925.59 | 01-MAY-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399700E+10 | 36363.28 | 31-OCT-20:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.758718E+11 | 99727.70 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190318E+12 | 142718.30 | 16-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760067E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202854E+12 | 142718.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.507484E+09 | 0.439538E+09 | 5158.23 | 25-MAY-16:00 | 4306.86 | 0.00 |
June | 0.00 | 0.00 | 0.237449E+10 | 0.183529E+10 | 16750.21 | 30-JUN-05:02 | 9488.96 | 0.00 |
July | 0.00 | 0.00 | 0.516049E+10 | 0.413567E+10 | 16657.84 | 05-JUL-05:03 | 9812.97 | 0.00 |
August | 0.00 | 0.00 | 0.444954E+10 | 0.355127E+10 | 16180.78 | 09-AUG-05:03 | 10759.93 | 0.00 |
September | 0.00 | 0.00 | 0.984060E+09 | 0.887833E+09 | 16263.61 | 01-SEP-05:03 | 10478.82 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.134761E+11 | 0.108496E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.516049E+10 | 0.413567E+10 | 16750.21 | 10759.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.173897E+10 | 0.113980E+10 | 31763.20 | 30-JUN-17:12 | 21203.77 | 0.00 |
July | 0.00 | 0.00 | 0.348667E+10 | 0.231992E+10 | 35785.14 | 23-JUL-13:20 | 21067.91 | 0.00 |
August | 0.00 | 0.00 | 0.128628E+10 | 0.844893E+09 | 16740.76 | 08-AUG-15:40 | 10606.76 | 0.00 |
September | 0.00 | 0.00 | 0.123380E+09 | 91382433.61 | 8569.62 | 01-SEP-15:00 | 6672.22 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.663530E+10 | 0.439600E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.348667E+10 | 0.231992E+10 | 35785.14 | 21203.77 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.890184E+09 | 0.08 | 333.10 | 01-JAN-00:01 | 0.08 |
February | 0.793051E+09 | 0.08 | 333.10 | 01-FEB-00:02 | 0.08 |
March | 0.823730E+09 | 0.07 | 333.10 | 01-MAR-00:03 | 0.08 |
April | 0.431634E+09 | 0.04 | 333.10 | 01-APR-00:10 | 0.08 |
May | 16988236.92 | 0.00 | 333.10 | 01-MAY-00:10 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.154193E+09 | 0.01 | 333.10 | 11-OCT-22:20 | 0.08 |
November | 0.745111E+09 | 0.07 | 333.10 | 01-NOV-00:10 | 0.08 |
December | 0.892182E+09 | 0.08 | 333.10 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.474707E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892182E+09 | 0.08 | 333.10 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100080E+10 | 0.69 | 883.65 | 07-JAN-14:00 | 0.95 |
February | 0.902435E+09 | 0.65 | 883.65 | 01-FEB-14:50 | 0.95 |
March | 0.102446E+10 | 0.58 | 883.65 | 15-MAR-12:30 | 0.95 |
April | 0.918021E+09 | 0.45 | 883.65 | 01-APR-13:10 | 0.95 |
May | 0.924397E+09 | 0.39 | 883.65 | 01-MAY-15:50 | 0.95 |
June | 0.914053E+09 | 0.38 | 883.65 | 01-JUN-14:30 | 0.94 |
July | 0.886825E+09 | 0.36 | 883.65 | 01-JUL-10:40 | 0.94 |
August | 0.953639E+09 | 0.38 | 883.65 | 05-AUG-07:40 | 0.94 |
September | 0.879706E+09 | 0.37 | 883.65 | 14-SEP-14:00 | 0.94 |
October | 0.894467E+09 | 0.38 | 883.65 | 05-OCT-12:40 | 0.95 |
November | 0.881145E+09 | 0.44 | 883.65 | 02-NOV-08:50 | 0.95 |
December | 0.981688E+09 | 0.64 | 883.65 | 02-DEC-11:40 | 0.95 |
Annual Sum or Average | 0.111616E+11 | 0.48 | |||
Minimum of Months | 0.879706E+09 | 0.36 | 883.65 | 0.94 | |
Maximum of Months | 0.102446E+10 | 0.69 | 883.65 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229932E+10 | 0.84 | 1452.45 | 02-JAN-07:40 | 0.95 |
February | 0.200603E+10 | 0.83 | 1452.45 | 01-FEB-07:50 | 0.95 |
March | 0.207652E+10 | 0.81 | 1452.45 | 01-MAR-07:08 | 0.95 |
April | 0.172102E+10 | 0.70 | 1452.45 | 01-APR-07:10 | 0.95 |
May | 0.151618E+10 | 0.40 | 1452.45 | 01-MAY-07:40 | 0.95 |
June | 0.150008E+10 | 0.38 | 1452.45 | 24-JUN-14:40 | 0.93 |
July | 0.144958E+10 | 0.35 | 1452.45 | 20-JUL-10:30 | 0.93 |
August | 0.155296E+10 | 0.37 | 1452.45 | 04-AUG-13:50 | 0.94 |
September | 0.143793E+10 | 0.36 | 1452.45 | 01-SEP-11:10 | 0.93 |
October | 0.155345E+10 | 0.55 | 1452.45 | 04-OCT-07:50 | 0.95 |
November | 0.181968E+10 | 0.80 | 1452.45 | 02-NOV-08:50 | 0.95 |
December | 0.226661E+10 | 0.84 | 1452.45 | 01-DEC-07:30 | 0.95 |
Annual Sum or Average | 0.211994E+11 | 0.60 | |||
Minimum of Months | 0.143793E+10 | 0.35 | 1452.45 | 0.93 | |
Maximum of Months | 0.229932E+10 | 0.84 | 1452.45 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.40 | 0.00 |
February | 3.39 | 0.00 |
March | 3.21 | 0.00 |
April | 2.06 | 0.03 |
May | 0.26 | 0.09 |
June | 0.58 | 0.23 |
July | 0.83 | 0.00 |
August | 0.64 | 0.21 |
September | 0.25 | 0.90 |
October | 1.50 | 0.05 |
November | 2.81 | 0.00 |
December | 3.60 | 0.00 |
Annual Sum or Average | 23.54 | 0.03 |
Minimum of Months | 0.25 | 0.00 |
Maximum of Months | 4.40 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.02 | 0.00 |
February | 0.13 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.15 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.13 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100080E+10 | 0.194570E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.902435E+09 | 0.153138E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102446E+10 | 0.149172E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.918021E+09 | 0.824705E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.103439E+10 | 0.204198E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.141426E+10 | 0.133987E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.193539E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.185768E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108481E+10 | 0.444884E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.894467E+09 | 0.466309E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.881145E+09 | 0.918383E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.981688E+09 | 0.171497E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139296E+11 | 0.915526E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.881145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.193539E+10 | 0.194570E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.229932E+10 | 0.828788E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200603E+10 | 0.627847E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.207652E+10 | 0.491797E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172102E+10 | 0.216437E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151618E+10 | 0.125256E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.190468E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224119E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184797E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.146642E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155345E+10 | 0.855276E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.181968E+10 | 0.358264E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.226661E+10 | 0.768091E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227191E+11 | 0.338928E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146642E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.229932E+10 | 0.828788E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100080E+10 | 0.00 | 0.139987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902435E+09 | 0.00 | 0.108893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102446E+10 | 0.00 | 0.104925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918021E+09 | 0.00 | 0.569114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.924397E+09 | 0.507484E+09 | 0.139486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914053E+09 | 0.237449E+10 | 91778915.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.886825E+09 | 0.516049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.953639E+09 | 0.444954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.879706E+09 | 0.984060E+09 | 0.297347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894467E+09 | 0.00 | 0.317017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881145E+09 | 0.00 | 0.636245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.981688E+09 | 0.00 | 0.122097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111616E+11 | 0.134761E+11 | 0.645978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.879706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102446E+10 | 0.516049E+10 | 0.139987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229932E+10 | 0.00 | 0.603067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200603E+10 | 0.00 | 0.452281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207652E+10 | 0.00 | 0.346939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172102E+10 | 0.00 | 0.150524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151618E+10 | 0.00 | 0.847788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150008E+10 | 0.173897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144958E+10 | 0.348667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155296E+10 | 0.128628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143793E+10 | 0.123380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155345E+10 | 0.00 | 0.578866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181968E+10 | 0.00 | 0.250845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226661E+10 | 0.00 | 0.555398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211994E+11 | 0.663530E+10 | 0.242542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229932E+10 | 0.348667E+10 | 0.603067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.100080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.924397E+09 | 0.00 | 0.00 | 0.00 | 0.109989E+09 | 0.00 | 0.204198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914053E+09 | 0.00 | 0.00 | 0.00 | 0.500207E+09 | 0.00 | 0.133987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.886825E+09 | 0.00 | 0.00 | 0.00 | 0.104857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.953639E+09 | 0.00 | 0.00 | 0.00 | 0.904039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.879706E+09 | 0.00 | 0.00 | 0.00 | 0.205104E+09 | 0.00 | 0.444884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.981688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111616E+11 | 0.00 | 0.00 | 0.00 | 0.276791E+10 | 0.00 | 0.915526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.879706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102446E+10 | 0.00 | 0.00 | 0.00 | 0.104857E+10 | 0.00 | 0.194570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.229932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150008E+10 | 0.00 | 0.00 | 0.00 | 0.404592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144958E+10 | 0.00 | 0.00 | 0.00 | 0.791609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155296E+10 | 0.00 | 0.00 | 0.00 | 0.295013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143793E+10 | 0.00 | 0.00 | 0.00 | 28492463.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211994E+11 | 0.00 | 0.00 | 0.00 | 0.151971E+10 | 0.00 | 0.338928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229932E+10 | 0.00 | 0.00 | 0.00 | 0.791609E+09 | 0.00 | 0.828788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411952E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312906E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301629E+10 | 0.00 | 0.00 | 0.13 |
April | 12446836.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165462E+10 | 0.00 | 0.00 | 0.13 |
May | 0.297386E+09 | 42344452.67 | 52611.91 | 167667.81 | 6957861.10 | 0.423359E+09 | 44239085.12 | 569.00 | 0.13 |
June | 0.267935E+09 | 0.329945E+09 | 0.00 | 631776.27 | 545416.46 | 2132090.10 | 0.145813E+09 | 0.00 | 0.13 |
July | 459474.46 | 0.562317E+09 | 0.00 | 1709487.69 | 0.00 | 0.00 | 0.172894E+09 | 0.00 | 0.13 |
August | 33209816.81 | 0.313412E+09 | 0.00 | 2200887.51 | 0.00 | 0.00 | 0.290338E+09 | 0.00 | 0.14 |
September | 0.589612E+09 | 12373178.55 | 0.00 | 1125167.90 | 0.00 | 80257956.55 | 0.345407E+09 | 0.00 | 0.13 |
October | 0.234411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134369E+10 | 0.00 | 0.00 | 0.12 |
November | 5073833.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221596E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379978E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.144053E+10 | 0.126039E+10 | 52611.91 | 5834987.19 | 7503277.56 | 0.197847E+11 | 0.998692E+09 | 569.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.589612E+09 | 0.562317E+09 | 52611.91 | 2200887.51 | 6957861.10 | 0.411952E+10 | 0.345407E+09 | 569.00 | 0.14 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17557233.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141779E+11 | 0.00 | 0.00 | 0.17 |
February | 0.552481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976264E+10 | 0.00 | 0.00 | 0.17 |
March | 0.137689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799913E+10 | 0.00 | 0.00 | 0.19 |
April | 0.189012E+10 | 0.00 | 0.00 | 0.00 | 7510918.86 | 0.245055E+10 | 0.00 | 0.00 | 0.18 |
May | 0.185603E+10 | 0.00 | 0.00 | 0.00 | 0.304440E+09 | 58015761.87 | 0.00 | 0.00 | 0.19 |
June | 0.131163E+10 | 0.534386E+09 | 0.00 | 13185.96 | 60122440.31 | 0.00 | 13145873.91 | 0.00 | 0.20 |
July | 0.105985E+10 | 0.779769E+09 | 0.00 | 903554.92 | 4056965.32 | 0.00 | 0.686625E+09 | 0.00 | 0.24 |
August | 0.198503E+10 | 0.255553E+09 | 0.00 | 553302.53 | 3460917.51 | 0.00 | 0.418987E+09 | 0.00 | 0.24 |
September | 0.313839E+10 | 2063515.97 | 0.00 | 131744.88 | 1166905.73 | 0.00 | 46058223.92 | 0.00 | 0.19 |
October | 0.330067E+10 | 0.00 | 0.00 | 0.00 | 12694925.96 | 0.802629E+09 | 0.00 | 0.00 | 0.17 |
November | 0.164621E+10 | 0.00 | 0.00 | 0.00 | 782537.95 | 0.485654E+10 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128604E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.181349E+11 | 0.157177E+10 | 0.00 | 1601788.28 | 0.394236E+09 | 0.529678E+11 | 0.116482E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.330067E+10 | 0.779769E+09 | 0.00 | 903554.92 | 0.304440E+09 | 0.141779E+11 | 0.686625E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |