Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:11:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1409.25 | 291.46 | 291.46 |
Net Site Energy | 1409.25 | 291.46 | 291.46 |
Total Source Energy | 2581.67 | 533.94 | 533.94 |
Net Source Energy | 2581.67 | 533.94 | 533.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 903.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 506.02 | 903.23 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 903.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 237.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.60 | 186.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 104.66 | 186.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.60 | 186.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 104.66 | 186.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 506.023 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 506.023 | 100.00 |
Total On-Site and Utility Electric Sources | 506.023 | 100.00 |
Total Electricity End Uses | 506.023 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.00 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2297.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.5035 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0541 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0541 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:09 | 05-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 291176.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7543.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 18848.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5110.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1772.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 43310.54 | 291176.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 291176.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7543.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 18848.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2805.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1772.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 979.10 | 0.00 | 0.00 | 0.00 |
Cooling | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 751.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1602.57 | 979.10 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 202.50 | 0.00 | 0.00 | 0.00 |
Cooling | 3.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 155.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 331.44 | 202.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 202.50 | 0.00 | 0.00 | 0.00 |
Cooling | 3.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 155.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 331.44 | 202.50 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.907442 |
ZONE2 FINE STORAGE DIRECT AIR | 1.68 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 4.25 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 4.25 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 154449.91 |
PSZ-OFFICE HEATING COIL | 23463.29 |
PSZ-FINE STORAGE HEATING COIL | 62922.03 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 154449.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.907442 | 0.907442 | 0.907442 | 0.907442 | 0.907442 | 0.907442 | 1.00 | 1.000000 | 0.907442 |
PSZ-FINE STORAGE | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.00 | 1.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.907442 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.68 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.907442 | 0.907442 | 0.907442 | 0.907442 | 15021.38 | 23463.29 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.68 | 33915.64 | 62922.03 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.907440 | 0.453720 | 0.604960 | 15021.35 | 15021.38 | 7510.69 | 7510.69 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.68 | 0.841285 | 1.12 | 29211.04 | 33915.64 | 16957.82 | 16957.82 | 0.732929 | 0.732930 | 0.732930 | 0.732930 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.907442 | 1004.68 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.68 | 1800.43 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 8.503 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.577 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2014.304 | 8.503 | 402.861 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2014.304 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 10348.991 | 7.427 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.991 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 12073.822 | 3.767 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.822 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.2948 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5734 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.045 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5734 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.293 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.644 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4889 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.644 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.81987457E-12 | -0.55300542E-16 | 0.55369647E-14 | 0.11108823E-15 |
8 | 3 | -0.39745255E-03 | 0.21013160E-06 | -0.57778445E-04 | 0.15730253E-12 |
9 | 2 | 1.7695129 | 0.45329532E-02 | 1.1632534 | -0.76198706E-04 |
10 | 1 | -7.0895412 | 0.11645204 | -17.243381 | 0.33915991 |
11 | 0 | 5.5152410 | 0.73830080E-01 | 16.275001 | |
12 | 4 | 0.76342465E-12 | 0.16474507E-15 | -0.23733433E-14 | 0.11984663E-15 |
13 | 3 | -0.37867847E-03 | 0.39972734E-06 | -0.54871579E-04 | 0.14649615E-12 |
14 | 2 | 1.7252338 | 0.87962070E-02 | 1.1295743 | -0.72598522E-04 |
15 | 1 | -7.1476348 | 0.22881135 | -17.028658 | 0.33064781 |
16 | 0 | 5.8066602 | 0.14627247 | 16.283019 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0454545 | 2.0454545 | 2.0454545 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23733433E-14 | 0.16474507E-15 | 0.76342465E-12 | 0.11984663E-15 |
85 | 3 | -0.54871579E-04 | 0.39972734E-06 | -0.37867847E-03 | 0.14649615E-12 |
86 | 2 | 1.1295743 | 0.87962070E-02 | 1.7252338 | -0.72598522E-04 |
87 | 1 | -17.028658 | 0.22881135 | -7.1476348 | 0.33064781 |
88 | 0 | 16.283019 | 0.14627247 | 5.8066602 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 28 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.441 |
2 | SKYLIGHT_U_0.5_SHGC_0.4 | 29 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 30 | 1 | VerySmooth | 4.827 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.13907 | 0.13907 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 5.00274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.330 | 7.271E-004 | 4.749E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8039.32718 | 9647.19261 | 0.75620 | 0.90744 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10325.45259 | 12390.54311 | 0.33146 | 0.39775 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 19123.87700 | 22948.65241 | 1.40215 | 1.68257 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.26593E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 34652.01910 | 41582.42292 | 0.93680 | 1.12416 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 128708.25200 | 154449.90240 | 3.54263 | 4.25115 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12213.17 | 0.90744 | 0.90744 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13242.26 | 0.39775 | 0.39775 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 28983.71 | 1.68257 | 1.68257 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 48476.76 | 1.12416 | 1.12416 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90744 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.68257 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.25115 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 4.25115 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 154449.91152 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 154449.90240 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90744 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90744 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90744 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90744 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90744 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.90744 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.68257 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.68257 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.68257 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.68257 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.68257 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.68257 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.90744 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.68257 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90744 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90744 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90744 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90744 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90744 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90744 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45372 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60496 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15021.35408 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15021.38000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7510.69000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7510.69000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15021.38000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23463.28611 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90744 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1004.68182 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23463.28611 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.68257 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.68257 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.68257 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.68257 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.68257 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.68257 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.84129 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12171 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 29211.04011 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33915.64000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16957.82000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16957.82000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73293 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73293 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73293 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73293 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33915.64000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62922.03287 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.68257 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1800.43376 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 62922.03287 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14317.2 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 32609.1 | 16.66 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1860371981 | 0.1806202629 | Pass | Pass | 1.3335305856 | 11.0092445323 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4105939066 | 0.3967152249 | Pass | Pass | 0.3957858874 | 0.7365120110 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.7910908846E-003 | 6.3680935034E-003 | Pass | Pass | 6.3969534766E-002 | 0.1229684438 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.045 | 0.394 | 0.441 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.045 | 0.394 | 0.441 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.045 | 0.394 | 0.441 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.045 | 0.394 | 0.441 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.316 | 0.465 | 0.491 | ||||||||||||
North Total or Average | 6.51 | 2.045 | 0.394 | 0.441 | ||||||||||||
Non-North Total or Average | 26.02 | 3.634 | 0.483 | 0.504 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 8.5035 | 236.88 | 2014.30 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 56.91 | 168.00 | 33.84 | 0.0000 | Y | 12.80 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 7.4271 | 1393.41 | 10348.99 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 53.69 | 0.0000 | Y | 104.31 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.7674 | 3204.84 | 12073.82 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 52.97 | 0.0000 | Y | 120.05 |
Interior Lighting Total | 5.0541 | 4835.13 | 24437.12 | 237.15 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2014.30 | 584.15 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2014.30 | 201.43 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 12073.82 | 1400.56 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 42.11 | 42.11 | 0.90 | |
EXTERIOR_LIGHTS_B | 3955.00 | AstronomicalClock | - | 83.57 | 62.84 | 46.65 | |
EXTERIOR_LIGHTS_C | 1004.90 | AstronomicalClock | - | 83.57 | 49.89 | 9.41 | |
Exterior Lighting Total | 5073.70 | 56.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15021.38 | 11996.98 | 3024.40 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33915.64 | 24857.79 | 9057.85 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14317.2 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 32609.1 | 16.66 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 154449.91 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23463.29 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 62922.03 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.25 | 394.98 | 92.91 | 1.00 | 3.21 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1004.68 | 1107.16 | 1.00 | 1.43 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1800.43 | 1070.05 | 1.00 | 1.34 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8039.33 | 9647.19 | 40.73 | 0.756 | 0.907 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00810 | 31.16 | 0.00627 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 19123.88 | 22948.65 | 16.47 | 1.402 | 1.683 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 26.70 | 26.70 | 0.00768 | 31.37 | 0.00627 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10325.45 | 12390.54 | 52.31 | 0.331 | 0.398 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00777 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34652.02 | 41582.42 | 29.84 | 0.937 | 1.124 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00636 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 128708.25 | 154449.90 | 48.19 | 3.543 | 4.251 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00873 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.91 | 0.91 | 0.40 | 0.40 | 0.9074 | 0.9074 | 0.9074 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.68 | 1.68 | 1.12 | 1.12 | 1.6826 | 1.6826 | 1.6826 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 154449.912 | 154449.912 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 154449.91 | 154449.91 | 4.251152 | 1.35 | 1.35 | 0.00680589 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.99 | 0.00873433 | 100.0000 | 154449.90 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 7510.690 | 0.000 | 0.907440 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7510.69 | 7510.69 | 0.907440 | 24.72 | 14.74 | 0.00789167 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 11.2718 | 23.90 | 0.00809820 | 38.3808 | 8039.33 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23463.286 | 23463.286 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23463.29 | 23463.29 | 0.907442 | 8.54 | 6.29 | 0.00585618 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 11.2718 | 21.10 | 0.00776514 | 43.6532 | 10325.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 16957.820 | 0.000 | 1.682570 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 16957.82 | 16957.82 | 1.682570 | 28.40 | 15.60 | 0.00742869 | 12.00 | 10.08 | 0.00800000 | 33.40 | 0.00626594 | 16.30 | 25.2419 | 26.70 | 0.00767822 | 30.8264 | 18975.52 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 62922.033 | 62922.033 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62922.03 | 62922.03 | 1.682574 | -0.75 | -0.75 | 0.00408883 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 25.2418 | 15.55 | 0.00636400 | 50.7805 | 34652.02 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 154449.912 | 154449.912 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 4.251152 | 4.47705747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 154449.91 | 154449.91 | 1.0000 | 4.47705747 | 4.251152 | 1.35 | 1.35 | 0.00680589 | 18396.0 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 154449.91 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.99 | 0.00873433 | 9.99 | 0.00873433 | 100.0000 | 154449.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7510.690 | 0.000 | 0.907440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5102 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7510.69 | 7510.69 | 1.0000 | 0.95566125 | 0.907440 | 24.72 | 14.74 | 0.00789167 | 44936.8 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7510.69 | 31.16 | 0.00626593 | 15.56 | 0.10228487 | 11.2718 | 23.90 | 0.00809820 | 23.90 | 0.00809820 | 38.3808 | 8039.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23463.286 | 23463.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.907442 | 0.95566287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23463.29 | 23463.29 | 1.0000 | 0.95566287 | 0.907442 | 8.54 | 6.29 | 0.00585618 | 23319.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23463.29 | -27.60 | 0.00034190 | -27.60 | 0.10228487 | 11.2718 | 21.05 | 0.00776514 | 21.10 | 0.00776514 | 43.6532 | 10325.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16957.820 | 0.000 | 1.682570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6496 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 16957.82 | 16957.82 | 1.0000 | 1.77198157 | 1.682570 | 28.40 | 15.60 | 0.00742869 | 47513.2 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16957.82 | 33.40 | 0.00626594 | 16.30 | 0.42471267 | 25.2419 | 26.70 | 0.00782541 | 26.70 | 0.00767822 | 30.8264 | 18975.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62922.033 | 62922.033 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.682574 | 1.77198582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62922.03 | 62922.03 | 1.0000 | 1.77198582 | 1.682574 | -0.75 | -0.75 | 0.00408883 | 9467.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62922.03 | -27.60 | 0.00034190 | -27.60 | 0.42471267 | 25.2418 | 15.56 | 0.00636400 | 15.55 | 0.00636400 | 50.7805 | 34652.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.68 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2478.17 | 3088.50 | 2297.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2478.17 | 3088.50 | 2297.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 93.67 | 0.67 | 66.00 | 0.67 |
ZONE2 FINE STORAGE | 522.00 | 2.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2.50 | 0.00 | 0.00 | 0.00 |
Facility | 598.33 | 3.33 | 66.00 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.307 | 0.255 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
Electricity:Building | 374.68 | 1510.77 | 01-JAN-00:10 | 31750.76 | 25-JUL-10:40 |
Electricity:Zone:ZONE1 OFFICE | 41.96 | 520.87 | 01-JAN-00:10 | 3102.09 | 02-JAN-08:10 |
InteriorLights:Electricity | 237.15 | 1040.90 | 01-JAN-00:10 | 20326.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 12.80 | 51.00 | 01-JAN-00:10 | 1267.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 237.15 | 1040.90 | 01-JAN-00:10 | 20326.42 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 228.41 | 689.93 | 01-JAN-00:10 | 19974.51 | 25-JUL-10:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 120.05 | 689.93 | 01-JAN-00:10 | 10262.75 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.64 | 481.00 | 05-JAN-20:00 | 2852.09 | 15-FEB-12:40 |
WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.09 | 15-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.09 | 15-FEB-12:40 |
Fans:Electricity | 43.06 | 0.00 | 01-JAN-13:20 | 5110.41 | 17-JUL-11:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-JUL-16:30 |
Ventilation (simple):Fans:Electricity | 1.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-JUL-16:30 |
ElectricityPurchased:Facility | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
ElectricityPurchased:Plant | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
Cogeneration:ElectricityPurchased | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
ElectricityNet:Plant | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
Cogeneration:ElectricityNet | 506.02 | 1991.77 | 01-JAN-13:20 | 43310.54 | 17-JUL-14:10 |
Electricity:HVAC | 47.74 | 0.00 | 01-JAN-13:20 | 11931.99 | 17-JUL-16:00 |
General:Fans:Electricity | 42.04 | 0.00 | 01-JAN-13:20 | 3200.09 | 01-FEB-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.70 | 0.00 | 01-JAN-00:10 | 9126.87 | 17-JUL-16:00 |
ExteriorLights:Electricity | 56.96 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 56.96 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 903.23 | 0.00 | 01-JAN-13:20 | 291176.02 | 05-JAN-17:10 |
Gas:HVAC | 903.23 | 0.00 | 01-JAN-13:20 | 291176.02 | 05-JAN-17:10 |
Heating:Gas | 903.23 | 0.00 | 01-JAN-13:20 | 291176.02 | 05-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1422.24 | 0.00 | 01-JAN-13:20 | 444431.02 | 05-JAN-17:10 |
EnergyTransfer:Building | 703.24 | 0.00 | 01-JAN-13:20 | 213218.12 | 05-JAN-17:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 49.00 | 0.00 | 01-JAN-00:40 | 21528.28 | 11-JAN-07:10 |
Heating:EnergyTransfer | 675.77 | 0.00 | 01-JAN-13:20 | 213218.12 | 05-JAN-17:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 38.88 | 0.00 | 01-JAN-00:40 | 21528.28 | 11-JAN-07:10 |
Cooling:EnergyTransfer | 27.47 | 0.00 | 01-JAN-00:10 | 23710.11 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 10.12 | 0.00 | 01-JAN-00:10 | 7955.86 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 156.40 | 0.00 | 01-JAN-00:40 | 50186.95 | 05-JAN-22:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.05 | 0.00 | 01-JAN-00:40 | 50186.95 | 05-JAN-22:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.35 | 0.00 | 01-JAN-00:10 | 16631.00 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 497.84 | 0.00 | 01-JAN-12:50 | 156128.79 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 497.84 | 0.00 | 01-JAN-12:50 | 156128.79 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 719.00 | 0.00 | 01-JAN-13:20 | 231212.90 | 05-JAN-17:10 |
HeatingCoils:EnergyTransfer | 694.25 | 0.00 | 01-JAN-13:20 | 231212.90 | 05-JAN-17:10 |
CoolingCoils:EnergyTransfer | 24.75 | 0.00 | 01-JAN-00:10 | 32736.91 | 17-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 38.882 | -10.120 | 0.000 | 0.000 | 4.009 | 12.797 | 29.165 | 10.220 | 0.000 | 0.436 | 0.000 | 0.000 | -9.673 | 0.000 | -19.171 | -56.544 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 139.050 | -17.347 | 0.000 | 0.000 | 0.000 | 104.309 | 0.000 | 0.000 | 0.000 | 1.553 | 0.001 | 0.000 | 0.000 | 0.000 | -119.629 | -107.935 |
ZONE3 BULK STORAGE | 497.841 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 120.048 | 107.336 | 32.612 | 0.000 | 27.996 | 0.000 | 0.000 | -14.447 | 0.000 | -516.443 | -254.943 |
Total Facility | 497.841 | 0.000 | 177.932 | -27.467 | 0.000 | 0.000 | 4.009 | 237.154 | 136.501 | 42.831 | 0.000 | 29.984 | 0.001 | 0.000 | -24.120 | 0.000 | -655.244 | -419.422 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-AUG-05:01 | 0.00 | 0.00 | 0.00 | -13548.06 | 0.00 | 0.00 | 32.65 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 13637.00 | 0.00 | -371.70 | 0.00 | -351.41 | 0.00 |
ZONE2 FINE STORAGE | 20-JUL-18:51 | 0.00 | 0.00 | 0.00 | -31644.25 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 32149.86 | 0.00 | -0.00 | 0.00 | -805.58 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-18:51 | 0.00 | 0.00 | 0.00 | -31644.25 | 0.00 | 0.00 | 0.00 | 1040.90 | 2519.91 | 1651.81 | 0.00 | 0.00 | 38607.98 | 0.00 | -92.38 | 0.00 | -12083.97 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-NOV-06:31 | 0.00 | 0.00 | 25143.65 | 0.00 | 0.00 | 0.00 | 55.00 | 378.46 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.42 | 0.00 | -1614.99 | -23563.22 |
ZONE2 FINE STORAGE | 28-JAN-03:21 | 0.00 | 0.00 | 65929.49 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12060.21 | -54169.26 |
ZONE3 BULK STORAGE | 05-JAN-16:00 | 156120.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10262.75 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1269.60 | 0.00 | -171132.51 | -2181.49 |
Total Facility | 06-JAN-06:52 | 151737.48 | 0.00 | 87811.07 | 0.00 | 0.00 | 0.00 | 55.42 | 2620.75 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3361.90 | 0.00 | -115724.03 | -125739.33 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9074 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9074 | 0.1127 | 1.0000 | 0.1023 | 0.1127 | ||
PSZ-FINE STORAGE | 1.6826 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6826 | 0.2524 | 1.0000 | 0.4247 | 0.2524 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9074 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9074 | 1.0000 | 1.0000 | 0.1023 | 0.1127 | ||
PSZ-FINE STORAGE | 1.6826 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6826 | 1.0000 | 1.0000 | 0.4247 | 0.2524 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9074 | 0.9074 | 0.9074 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6826 | 1.6826 | 1.6826 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9074 | 0.9074 | 0.9074 | 0.9074 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6826 | 1.6826 | 1.6826 | 1.6826 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9074 | 0.9074 | 0.9074 | 0.1023 | 0.2572 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6826 | 1.6826 | 1.6826 | 0.4247 | 0.3778 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9074 | 0.9074 | 0.9074 | 0.9074 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6826 | 1.6826 | 1.6826 | 1.6826 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.00 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 66.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 903.23 | 291176.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 5.70 | 9126.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 237.15 | 20326.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 56.96 | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.50 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.02 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.04 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.64 | 2852.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.50 | 506.02 |
Natural Gas | 0.00 | 903.23 |
Additional | 0.00 | 0.00 |
Total | 136.50 | 1409.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 49.05 |
Space Heating | 0.00 |
Space Cooling | 1.18 |
Fans (All) | 8.91 |
Service Water Heating | 5.51 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 104.66 |
Subtotal | 104.66 |
Natural Gas [MJ/m2] | |
Space Heating | 186.81 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 186.81 |
Subtotal | 186.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.83 |
Space Heating | 64.09 |
Space Cooling | 0.40 |
Fans (All) | 3.06 |
Service Water Heating | 1.89 |
Receptacle Equipment | 9.69 |
Miscellaneous | 4.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 2967. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.289177E+12 |
February | 0.000 | 0.161922E+12 |
March | 0.000 | 0.116628E+12 |
April | 0.000 | 0.278931E+11 |
May | 0.000 | 0.174361E+11 |
June | 0.000 | 0.149438E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1954891.617 |
September | 0.000 | 0.907274E+09 |
October | 0.000 | 0.636750E+10 |
November | 0.000 | 0.834944E+11 |
December | 0.000 | 0.199251E+12 |
Annual Sum or Average | 0.903227E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.289177E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194926E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.8 | 0.179398E+09 | 244.74 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 | 0.210546E+09 | 236.59 | 06-MAR-10:20 | -5.9 | -7.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.196210E+09 | 272.84 | 07-APR-14:00 | 21.70 | 8.87 |
May | 59223931.06 | 1860.88 | 20-MAY-16:00 | 30.00 | 15.19 | 0.215014E+09 | 301.58 | 19-MAY-13:30 | 26.65 | 14.94 |
June | 0.142491E+10 | 5089.04 | 30-JUN-16:00 | 31.10 | 14.59 | 0.250064E+09 | 306.61 | 26-JUN-07:10 | 17.67 | 12.35 |
July | 0.375856E+10 | 13439.37 | 17-JUL-05:01 | 16.47 | 12.07 | 0.248745E+09 | 301.60 | 01-JUL-07:30 | 17.75 | 14.24 |
August | 0.342419E+10 | 13548.06 | 09-AUG-05:01 | 16.42 | 10.95 | 0.267769E+09 | 301.59 | 05-AUG-10:00 | 27.20 | 16.08 |
September | 0.138548E+10 | 13500.96 | 05-SEP-05:01 | 18.40 | 11.39 | 0.232719E+09 | 301.60 | 07-SEP-10:50 | 17.62 | 16.50 |
October | 66081631.48 | 1076.09 | 18-OCT-16:00 | 24.40 | 10.99 | 0.207177E+09 | 306.61 | 18-OCT-13:50 | 24.90 | 11.27 |
November | 1165389.72 | 296.10 | 09-NOV-16:20 | 8.57 | 3.45 | 0.187704E+09 | 263.14 | 04-NOV-15:20 | 16.50 | 7.80 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.1 | 0.194959E+09 | 236.59 | 04-DEC-08:30 | 2.50 | -0.3 |
Annual Sum or Average | 0.101196E+11 | 0.258523E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.179398E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.375856E+10 | 13548.06 | 31.10 | 15.19 | 0.267769E+09 | 306.61 | 27.20 | 16.50 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67770584.70 | 1712.72 | 14-JAN-10:50 | 7.85 | 3.81 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.237893E+09 | 3754.53 | 28-FEB-10:40 | 2.97 | 0.61 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.772437E+09 | 4071.07 | 25-MAR-12:00 | 1.10 | -1.5 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.762983E+09 | 5291.17 | 27-APR-13:45 | -1.1 | -3.5 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.958497E+09 | 5724.27 | 31-MAY-06:10 | 11.75 | 7.74 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.134207E+10 | 14268.96 | 30-JUN-17:43 | 29.50 | 14.56 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.473475E+10 | 31644.12 | 20-JUL-18:51 | 25.60 | 13.27 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.405926E+10 | 30623.04 | 08-AUG-20:01 | 26.83 | 14.73 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.205888E+10 | 22274.76 | 03-SEP-12:55 | 33.30 | 15.90 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.131673E+10 | 6128.58 | 05-OCT-07:05 | -2.5 | -2.9 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.786890E+09 | 4357.30 | 20-NOV-15:30 | 1.95 | -2.7 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.249502E+09 | 6102.36 | 09-DEC-09:35 | -2.9 | -4.0 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.173477E+11 | 0.00 | ||||||||
Minimum of Months | 67770584.70 | 1712.72 | -2.9 | -4.0 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.473475E+10 | 31644.12 | 33.30 | 15.90 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860763E+10 | 25055.92 | 07-JAN-06:31 | -20.8 |
February | 0.601277E+10 | 25139.41 | 10-FEB-06:31 | -19.6 |
March | 0.588534E+10 | 24219.98 | 06-MAR-06:11 | -17.1 |
April | 0.359753E+10 | 24691.35 | 03-APR-05:32 | 0.77 |
May | 0.245861E+10 | 24080.61 | 08-MAY-05:12 | -2.8 |
June | 0.205603E+09 | 23628.58 | 17-JUN-05:01 | 2.35 |
July | 26247072.61 | 1178.51 | 03-JUL-06:10 | 14.55 |
August | 60312942.25 | 1891.68 | 18-AUG-06:10 | 8.17 |
September | 0.486228E+09 | 23806.39 | 19-SEP-05:01 | 2.20 |
October | 0.152333E+10 | 24052.73 | 10-OCT-05:12 | -6.1 |
November | 0.379428E+10 | 25143.58 | 27-NOV-06:31 | -14.0 |
December | 0.622447E+10 | 24122.85 | 26-DEC-06:12 | -8.0 |
Annual Sum or Average | 0.388823E+11 | |||
Minimum of Months | 26247072.61 | 1178.51 | -20.8 | |
Maximum of Months | 0.860763E+10 | 25143.58 | 14.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384527E+11 | 65929.46 | 28-JAN-03:21 | -29.4 |
February | 0.236386E+11 | 65395.03 | 04-FEB-02:62 | -21.7 |
March | 0.188931E+11 | 65399.76 | 04-MAR-22:42 | -22.7 |
April | 0.786930E+10 | 63844.71 | 29-APR-03:42 | -7.6 |
May | 0.453411E+10 | 63936.84 | 08-MAY-04:12 | -2.4 |
June | 0.422962E+09 | 3245.88 | 20-JUN-16:20 | 29.40 |
July | 0.170926E+09 | 1947.43 | 10-JUL-15:30 | 26.95 |
August | 0.234521E+09 | 2074.94 | 21-AUG-16:30 | 26.70 |
September | 0.607640E+09 | 50413.34 | 21-SEP-05:03 | 6.60 |
October | 0.247555E+10 | 60277.87 | 10-OCT-05:12 | -6.1 |
November | 0.139557E+11 | 65421.43 | 27-NOV-04:02 | -15.8 |
December | 0.277946E+11 | 65908.96 | 31-DEC-06:41 | -27.9 |
Annual Sum or Average | 0.139050E+12 | |||
Minimum of Months | 0.170926E+09 | 1947.43 | -29.4 | |
Maximum of Months | 0.384527E+11 | 65929.46 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170018E+12 | 156128.79 | 05-JAN-16:00 | -19.4 |
February | 0.910503E+11 | 110792.89 | 03-FEB-18:57 | -16.7 |
March | 0.618743E+11 | 115180.97 | 06-MAR-03:51 | -18.3 |
April | 0.845650E+10 | 54449.85 | 29-APR-04:52 | -7.8 |
May | 0.627196E+10 | 46218.90 | 08-MAY-06:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.661503E+09 | 20832.85 | 11-OCT-06:00 | 0.00 |
November | 0.446495E+11 | 99927.01 | 27-NOV-05:00 | -15.6 |
December | 0.114860E+12 | 154916.88 | 31-DEC-03:00 | -24.4 |
Annual Sum or Average | 0.497842E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.170018E+12 | 156128.79 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117713E+10 | 1267.03 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.101534E+10 | 1267.03 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.109783E+10 | 1267.03 | 02-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.102443E+10 | 1267.03 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.101990E+10 | 1267.03 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.996707E+09 | 1144.55 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.988471E+09 | 1267.03 | 07-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.108514E+10 | 1267.03 | 04-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.103517E+10 | 1267.03 | 05-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.107745E+10 | 1267.03 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.109791E+10 | 1267.03 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.118176E+10 | 1267.03 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.127972E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.988471E+09 | 1144.55 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.118176E+10 | 1267.03 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.862930E+10 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.792548E+10 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.925537E+10 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.860339E+10 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.894234E+10 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.891642E+10 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.862930E+10 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.925537E+10 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.860339E+10 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.862930E+10 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.829035E+10 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.862930E+10 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104309E+12 | ||||
Minimum of Months | 0.792548E+10 | 8796.64 | 0.00 | 0.00 | |
Maximum of Months | 0.925537E+10 | 8796.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.102789E+11 | 10262.75 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.933961E+10 | 10262.75 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.104931E+11 | 10262.75 | 06-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.972203E+10 | 9865.92 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.997602E+10 | 9865.92 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.986944E+10 | 9865.92 | 23-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.966330E+10 | 9865.92 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.104247E+11 | 9865.92 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.987533E+10 | 10262.75 | 16-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.101274E+11 | 10262.75 | 10-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.990023E+10 | 10262.75 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.103775E+11 | 10262.75 | 01-DEC-14:20 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.120048E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.933961E+10 | 9865.92 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.104931E+11 | 10262.75 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.117713E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339301E+10 |
February | 0.500553E+09 | 0.101534E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241561E+10 |
March | 0.587605E+09 | 0.109783E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224316E+10 |
April | 0.544079E+09 | 0.102443E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 935227.26 | 0.135626E+10 |
May | 0.565842E+09 | 0.101990E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11270415.13 | 0.128060E+10 |
June | 0.565842E+09 | 0.996707E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75986631.95 | 0.697135E+09 |
July | 0.544079E+09 | 0.988471E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180093E+09 | 0.395080E+09 |
August | 0.587605E+09 | 0.108514E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134293E+09 | 0.589991E+09 |
September | 0.544079E+09 | 0.103517E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31075855.19 | 0.953909E+09 |
October | 0.544079E+09 | 0.107745E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2248841.61 | 0.128583E+10 |
November | 0.522316E+09 | 0.109791E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192996E+10 |
December | 0.544079E+09 | 0.118176E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263091E+10 |
Annual Sum or Average | 0.659424E+10 | 0.127972E+11 | 0.291647E+11 | 0.435903E+09 | 0.191714E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.988471E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395080E+09 |
Maximum of Months | 0.587605E+09 | 0.118176E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180093E+09 | 0.339301E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214442E+11 |
February | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33214.11 | 0.149723E+11 |
March | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133331E+11 |
April | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44596265.46 | 0.756659E+10 |
May | 0.00 | 0.894234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168457E+09 | 0.724630E+10 |
June | 0.00 | 0.891642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183993E+09 | 0.472429E+10 |
July | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464137E+09 | 0.377787E+10 |
August | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410685E+09 | 0.449972E+10 |
September | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219310E+09 | 0.641518E+10 |
October | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61681583.45 | 0.715478E+10 |
November | 0.00 | 0.829035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117493E+11 |
December | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167456E+11 |
Annual Sum or Average | 0.104309E+12 | 0.155289E+10 | 0.119629E+12 | ||||||
Minimum of Months | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377787E+10 |
Maximum of Months | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464137E+09 | 0.214442E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.102789E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680059E+11 |
February | 0.00 | 0.933961E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608637E+09 | 0.397446E+11 |
March | 0.00 | 0.104931E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80137670.58 | 0.349278E+11 |
April | 0.00 | 0.972203E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202757E+10 | 0.170961E+11 |
May | 0.00 | 0.997602E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295588E+10 | 0.177128E+11 |
June | 0.00 | 0.986944E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130643E+10 | 0.151231E+11 |
July | 0.00 | 0.966330E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721108E+09 | 0.162498E+11 |
August | 0.00 | 0.104247E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422488E+09 | 0.196721E+11 |
September | 0.00 | 0.987533E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165492E+10 | 0.222693E+11 |
October | 0.00 | 0.101274E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224736E+10 | 0.181675E+11 |
November | 0.00 | 0.990023E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133834E+10 | 0.287854E+11 |
December | 0.00 | 0.103775E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250227E+09 | 0.464900E+11 |
Annual Sum or Average | 0.120048E+12 | 0.107336E+12 | 0.136131E+11 | 0.344244E+12 | |||||
Minimum of Months | 0.00 | 0.933961E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151231E+11 |
Maximum of Months | 0.00 | 0.104931E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295588E+10 | 0.680059E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1267.03 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 12054.79 | 27-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1267.03 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 10623.55 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1267.03 | 02-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9514.29 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1267.03 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.69 | 16-APR-14:00 | 5401.04 | 28-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1267.03 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.80 | 19-MAY-16:10 | 6212.76 | 22-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1144.55 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.52 | 29-JUN-16:10 | 4114.90 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 1267.03 | 07-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 17-JUL-16:10 | 3003.53 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1267.03 | 04-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.17 | 10-AUG-17:00 | 3524.29 | 17-AUG-16:03 |
September | 659.25 | 01-SEP-07:10 | 1267.03 | 05-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 955.05 | 01-SEP-16:10 | 4337.88 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1267.03 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.67 | 15-OCT-14:00 | 6290.72 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1267.03 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8315.91 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1267.03 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10926.84 | 29-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1144.55 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3003.53 | |||||
Maximum of Months | 659.25 | 1267.03 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 12054.79 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 39428.99 | 05-JAN-16:10 |
February | 0.00 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 | 26-FEB-15:00 | 21004.16 | 01-FEB-17:00 |
March | 0.00 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18271.96 | 30-MAR-08:00 |
April | 0.00 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.43 | 16-APR-16:00 | 13248.08 | 28-APR-16:00 |
May | 0.00 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3707.21 | 19-MAY-15:10 | 24373.81 | 22-MAY-06:10 |
June | 0.00 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4573.30 | 29-JUN-15:10 | 9388.74 | 14-JUN-08:00 |
July | 0.00 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.06 | 25-JUL-15:10 | 7531.73 | 08-JUL-07:00 |
August | 0.00 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.47 | 09-AUG-17:00 | 14664.92 | 17-AUG-15:05 |
September | 0.00 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4540.55 | 02-SEP-15:10 | 12573.20 | 12-SEP-03:00 |
October | 0.00 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2557.70 | 15-OCT-14:00 | 10848.36 | 31-OCT-16:00 |
November | 0.00 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17981.74 | 28-NOV-08:00 |
December | 0.00 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 20536.64 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7531.73 | |||
Maximum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.06 | 39428.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10262.75 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 121798.86 | 05-JAN-16:00 |
February | 0.00 | 10262.75 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10488.56 | 27-FEB-13:10 | 66429.05 | 01-FEB-15:00 |
March | 0.00 | 10262.75 | 06-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5891.66 | 14-MAR-12:10 | 53735.26 | 03-MAR-09:00 |
April | 0.00 | 9865.92 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21031.42 | 07-APR-12:10 | 37776.93 | 27-APR-11:00 |
May | 0.00 | 9865.92 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27212.63 | 19-MAY-16:00 | 60210.75 | 22-MAY-08:00 |
June | 0.00 | 9865.92 | 23-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13182.71 | 29-JUN-13:00 | 30964.56 | 14-JUN-08:00 |
July | 0.00 | 9865.92 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8727.87 | 13-JUL-16:00 | 25632.65 | 08-JUL-10:00 |
August | 0.00 | 9865.92 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8130.42 | 25-AUG-16:00 | 58278.87 | 17-AUG-12:05 |
September | 0.00 | 10262.75 | 16-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14875.08 | 23-SEP-14:00 | 45471.39 | 12-SEP-11:00 |
October | 0.00 | 10262.75 | 10-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20827.46 | 12-OCT-12:10 | 27581.84 | 03-OCT-09:00 |
November | 0.00 | 10262.75 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14181.45 | 17-NOV-14:00 | 49614.93 | 27-NOV-11:00 |
December | 0.00 | 10262.75 | 01-DEC-14:20 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10903.47 | 10-DEC-02:00 | 86460.80 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 9865.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25632.65 | ||||
Maximum of Months | 0.00 | 10262.75 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27212.63 | 121798.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.26 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.36 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.35 |
April | 0.00 | 01-APR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.00 |
May | 1860.88 | 20-MAY-16:00 | 659.25 | 815.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 200.95 | 0.00 |
June | 5089.04 | 30-JUN-16:00 | 659.25 | 815.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 279.81 | 0.00 |
July | 13439.37 | 17-JUL-05:01 | 507.62 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.69 |
August | 13548.06 | 09-AUG-05:01 | 507.62 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.41 |
September | 13500.96 | 05-SEP-05:01 | 580.14 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.78 |
October | 1076.09 | 18-OCT-16:00 | 659.25 | 815.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
November | 296.10 | 09-NOV-16:20 | 659.25 | 899.59 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.04 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13548.06 | 659.25 | 899.59 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 279.81 | 772.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1712.72 | 14-JAN-10:50 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.73 |
February | 3754.53 | 28-FEB-10:40 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.10 |
March | 4071.07 | 25-MAR-12:00 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.23 |
April | 5291.17 | 27-APR-13:45 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4112.94 |
May | 5724.27 | 31-MAY-06:10 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2421.71 |
June | 14268.96 | 30-JUN-17:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.44 | 0.00 |
July | 31644.12 | 20-JUL-18:51 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.58 |
August | 30623.04 | 08-AUG-20:01 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
September | 22274.76 | 03-SEP-12:55 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.76 | 0.00 |
October | 6128.58 | 05-OCT-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.67 |
November | 4357.30 | 20-NOV-15:30 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.54 |
December | 6102.36 | 09-DEC-09:35 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1712.72 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31644.12 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.76 | 4112.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2069.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4938.76 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38422.31 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7905.42 |
April | 0.00 | 01-APR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10141.89 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 2069.80 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10495.23 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.78 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5888.80 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5500.19 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5763.47 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12965.35 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11733.99 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2759.73 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29379.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.78 | |
Maximum of Months | 0.00 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38422.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.451455E+11 | 38059.07 | 21-JAN-08:09 | 0.289177E+12 | 291176.02 | 05-JAN-17:10 |
February | 0.401488E+11 | 35634.01 | 01-FEB-15:50 | 0.161922E+12 | 193538.99 | 01-FEB-17:00 |
March | 0.446843E+11 | 35271.60 | 06-MAR-09:39 | 0.116628E+12 | 196145.36 | 06-MAR-03:49 |
April | 0.400431E+11 | 34869.84 | 01-APR-08:09 | 0.278931E+11 | 115038.49 | 29-APR-05:10 |
May | 0.403996E+11 | 34341.62 | 02-MAY-08:09 | 0.174361E+11 | 105438.84 | 08-MAY-05:10 |
June | 0.400641E+11 | 37834.77 | 29-JUN-14:00 | 0.149438E+09 | 8318.97 | 17-JUN-05:10 |
July | 0.414376E+11 | 43310.54 | 17-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.443336E+11 | 42719.00 | 10-AUG-14:00 | 1954891.62 | 1006.20 | 18-AUG-06:19 |
September | 0.407754E+11 | 39534.53 | 02-SEP-14:00 | 0.907274E+09 | 24536.71 | 20-SEP-06:10 |
October | 0.417443E+11 | 37642.91 | 31-OCT-07:10 | 0.636750E+10 | 58017.26 | 11-OCT-05:10 |
November | 0.420823E+11 | 38010.89 | 30-NOV-16:40 | 0.834944E+11 | 175980.45 | 27-NOV-04:10 |
December | 0.451642E+11 | 38054.04 | 28-DEC-08:09 | 0.199251E+12 | 249306.60 | 31-DEC-02:00 |
Annual Sum or Average | 0.506023E+12 | 0.903227E+12 | ||||
Minimum of Months | 0.400431E+11 | 34341.62 | 0.00 | 0.00 | ||
Maximum of Months | 0.451642E+11 | 43310.54 | 0.289177E+12 | 291176.02 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.200853E+11 | 0.667234E+10 | 0.112984E+11 | 0.00 | 0.475634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233306E+10 | 0.00 |
February | 0.182804E+11 | 0.536132E+10 | 0.103734E+11 | 0.00 | 0.399600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213763E+10 | 0.00 |
March | 0.208463E+11 | 0.500411E+10 | 0.121016E+11 | 0.00 | 0.432118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241110E+10 | 0.00 |
April | 0.193498E+11 | 0.390776E+10 | 0.112578E+11 | 0.00 | 0.327118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225653E+10 | 0.00 |
May | 0.199383E+11 | 0.328850E+10 | 0.117000E+11 | 0.00 | 0.315764E+10 | 0.00 | 0.00 | 32870035.87 | 0.00 | 0.00 | 0.00 | 0.228235E+10 | 0.00 |
June | 0.197826E+11 | 0.286092E+10 | 0.116594E+11 | 0.00 | 0.289068E+10 | 0.00 | 0.00 | 0.697863E+09 | 0.00 | 0.00 | 0.00 | 0.217274E+10 | 0.00 |
July | 0.192811E+11 | 0.307744E+10 | 0.112984E+11 | 0.00 | 0.328882E+10 | 0.00 | 0.00 | 0.235000E+10 | 0.00 | 0.00 | 0.00 | 0.214188E+10 | 0.00 |
August | 0.207652E+11 | 0.368084E+10 | 0.121016E+11 | 0.00 | 0.365100E+10 | 0.00 | 0.00 | 0.195315E+10 | 0.00 | 0.00 | 0.00 | 0.218182E+10 | 0.00 |
September | 0.195139E+11 | 0.443112E+10 | 0.112578E+11 | 0.00 | 0.281726E+10 | 0.00 | 0.00 | 0.661161E+09 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
October | 0.198342E+11 | 0.554598E+10 | 0.112984E+11 | 0.00 | 0.287547E+10 | 0.00 | 0.00 | 8104228.88 | 0.00 | 0.00 | 0.00 | 0.218222E+10 | 0.00 |
November | 0.192885E+11 | 0.621808E+10 | 0.108562E+11 | 0.00 | 0.356135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215819E+10 | 0.00 |
December | 0.201885E+11 | 0.691283E+10 | 0.112984E+11 | 0.00 | 0.447357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229091E+10 | 0.00 |
Annual Sum or Average | 0.237154E+12 | 0.569612E+11 | 0.136501E+12 | 0.430605E+11 | 0.00 | 0.570314E+10 | 0.266427E+11 | ||||||
Minimum of Months | 0.182804E+11 | 0.286092E+10 | 0.103734E+11 | 0.00 | 0.281726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
Maximum of Months | 0.208463E+11 | 0.691283E+10 | 0.121016E+11 | 0.00 | 0.475634E+10 | 0.00 | 0.00 | 0.235000E+10 | 0.00 | 0.00 | 0.00 | 0.241110E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.289177E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.161922E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116628E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.278931E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.174361E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149438E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1954891.62 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.907274E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.636750E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.834944E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.199251E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.903227E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.289177E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20326.42 | 02-JAN-09:09 | 5073.70 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3200.09 | 03-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20326.42 | 01-FEB-09:09 | 5073.70 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3200.09 | 01-FEB-12:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 20326.42 | 06-MAR-09:09 | 5073.70 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3200.09 | 04-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19929.60 | 01-APR-08:09 | 5073.70 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 3200.09 | 20-APR-13:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19807.12 | 02-MAY-08:09 | 5073.70 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 3200.09 | 01-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 19807.12 | 23-JUN-08:09 | 4571.25 | 01-JUN-20:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 2805.12 | 21-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 19929.60 | 07-JUL-08:09 | 4571.25 | 01-JUL-20:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 5110.41 | 17-JUL-10:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 19807.12 | 01-AUG-08:09 | 5073.70 | 03-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 5110.41 | 04-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 20203.94 | 16-SEP-08:09 | 5073.70 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 2805.12 | 05-SEP-12:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20326.42 | 11-OCT-08:09 | 5073.70 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 3200.09 | 10-OCT-06:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20326.42 | 02-NOV-08:09 | 5073.70 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3200.09 | 27-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20326.42 | 05-DEC-15:00 | 5073.70 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3200.09 | 02-DEC-16:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 19807.12 | 4571.25 | 10035.17 | 0.00 | 2805.12 | 0.00 | 0.00 | |||||
Maximum of Months | 20326.42 | 5073.70 | 10035.17 | 0.00 | 5110.41 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2832.58 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2852.09 | 15-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2841.92 | 04-MAR-12:09 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2740.37 | 03-APR-11:50 | 0.00 |
May | 827.51 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2558.98 | 01-MAY-11:50 | 0.00 |
June | 5062.55 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2245.26 | 06-JUN-11:39 | 0.00 |
July | 9126.87 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2028.64 | 01-JUL-11:00 | 0.00 |
August | 7506.21 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1842.46 | 02-AUG-11:00 | 0.00 |
September | 6414.82 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1950.82 | 28-SEP-11:00 | 0.00 |
October | 475.90 | 18-OCT-13:50 | 0.00 | 0.00 | 0.00 | 2226.20 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2490.49 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2703.80 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1842.46 | 0.00 | ||
Maximum of Months | 9126.87 | 0.00 | 0.00 | 0.00 | 2852.09 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 38059.07 | 21-JAN-08:09 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35634.01 | 01-FEB-15:50 | 20039.23 | 10035.17 | 0.00 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35271.60 | 06-MAR-09:39 | 20326.42 | 10035.17 | 0.00 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34869.84 | 01-APR-08:09 | 19929.60 | 10035.17 | 0.00 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34341.62 | 02-MAY-08:09 | 19807.12 | 10035.17 | 0.00 | 0.00 | 2805.12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37834.77 | 29-JUN-14:00 | 18641.80 | 10035.17 | 0.00 | 0.00 | 2805.12 | 0.00 | 0.00 | 4571.45 | 0.00 |
July | 43310.54 | 17-JUL-14:09 | 18848.75 | 10035.17 | 0.00 | 0.00 | 5110.41 | 0.00 | 0.00 | 7543.61 | 0.00 |
August | 42719.00 | 10-AUG-14:00 | 18641.80 | 10035.17 | 0.00 | 0.00 | 5110.41 | 0.00 | 0.00 | 7165.24 | 0.00 |
September | 39534.53 | 02-SEP-14:00 | 19080.86 | 10035.17 | 0.00 | 0.00 | 2805.12 | 0.00 | 0.00 | 5846.25 | 0.00 |
October | 37642.91 | 31-OCT-07:10 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 2805.12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38010.89 | 30-NOV-16:40 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38054.04 | 28-DEC-08:09 | 18084.14 | 10035.17 | 5073.70 | 0.00 | 3200.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 34341.62 | 18084.14 | 10035.17 | 0.00 | 0.00 | 2805.12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43310.54 | 20326.42 | 10035.17 | 5073.70 | 0.00 | 5110.41 | 0.00 | 0.00 | 7543.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 291176.02 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 193538.99 | 01-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 196145.36 | 06-MAR-03:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 115038.49 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 105438.84 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8318.97 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1006.20 | 18-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24536.71 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 58017.26 | 11-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 175980.45 | 27-NOV-04:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 249306.60 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 291176.02 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 16.57 | 9.67 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.50 | 18.55 | 8.33 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.50 | 18.06 | 9.67 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.67 | 19.46 | 8.17 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7.33 | 19.61 | 6.83 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.83 | 20.35 | 1.83 | 20.35 | 0.33 | 24.52 | 0.33 | 24.52 |
October | 4.17 | 20.19 | 4.17 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.33 | 19.35 | 8.33 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 18.03 | 8.83 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.67 | 18.23 | 66.00 | 19.59 | 0.67 | 24.56 | 0.67 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.50 | 20.54 | 9.67 | 20.54 | 0.33 | 24.60 | 0.33 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.50 | 14.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90.33 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88.83 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33.83 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20.83 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.30 | 0.00 | 0.00 |
September | 0.33 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7.17 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57.67 | 14.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 110.50 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 522.00 | 14.47 | 0.00 | 2.67 | 27.30 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.50 | 14.97 | 0.00 | 0.00 | 1.50 | 27.30 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 8.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 8.91 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 8.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.12 | 293.67 | 21.09 | 293.67 | 21.09 |
May | 312.00 | 21.63 | 231.17 | 21.12 | 231.17 | 21.12 |
June | 250.50 | 23.15 | 24.17 | 21.25 | 22.83 | 21.09 |
July | 70.83 | 23.76 | 92.83 | 23.90 | 0.00 | 0.00 |
August | 141.67 | 23.65 | 48.17 | 23.91 | 0.00 | 0.00 |
September | 225.50 | 22.62 | 96.17 | 22.25 | 57.50 | 21.14 |
October | 300.00 | 21.66 | 206.17 | 21.16 | 206.17 | 21.16 |
November | 288.00 | 21.09 | 285.83 | 21.08 | 285.83 | 21.08 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3088.50 | 21.64 | 2478.17 | 21.28 | 2297.17 | 21.07 |
Minimum of Months | 70.83 | 21.03 | 24.17 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.76 | 324.00 | 23.91 | 324.00 | 21.16 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.146799E+09 | 32870035.87 | 27.00 | 0.146799E+09 | 0.00 | 0.00 | 0.51 | 20-MAY-16:00 | 0.00 | 01-MAY-00:03 | 3533.07 | 20-MAY-16:00 | 3533.07 | 20-MAY-16:00 | 0.00 | 20-MAY-16:40 | 827.51 | 20-MAY-16:00 | 0.00 | 01-MAY-00:03 |
June | 0.200857E+10 | 0.433637E+09 | 184.81 | 0.196003E+10 | 48539362.57 | 0.00 | 0.96 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 | 6878.89 | 30-JUN-16:00 | 6878.89 | 30-JUN-16:00 | 726.72 | 20-JUN-17:00 | 1564.55 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 0.488713E+10 | 0.104732E+10 | 276.47 | 0.480551E+10 | 81620902.57 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15884.49 | 19-JUL-05:02 | 15007.19 | 17-JUL-05:01 | 2169.32 | 19-JUL-05:03 | 3173.96 | 19-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.433197E+10 | 0.928133E+09 | 276.69 | 0.432011E+10 | 11853375.62 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 15124.48 | 09-AUG-05:01 | 15124.48 | 09-AUG-05:01 | 312.76 | 01-AUG-14:10 | 3041.40 | 09-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.176863E+10 | 0.371829E+09 | 143.08 | 0.167983E+10 | 88797209.31 | 0.00 | 1.00 | 02-SEP-05:03 | 0.00 | 01-SEP-00:10 | 16162.44 | 08-SEP-05:02 | 15007.73 | 05-SEP-05:01 | 3411.94 | 08-SEP-05:02 | 3219.89 | 08-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 36955847.60 | 8104228.88 | 11.00 | 36955847.60 | 0.00 | 0.00 | 0.32 | 18-OCT-13:50 | 0.00 | 01-OCT-00:10 | 2186.64 | 18-OCT-13:50 | 2186.64 | 18-OCT-13:50 | 0.00 | 18-OCT-14:50 | 475.90 | 18-OCT-13:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.131800E+11 | 0.282190E+10 | 919.05 | 0.129492E+11 | 0.230811E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.488713E+10 | 0.104732E+10 | 276.69 | 0.480551E+10 | 88797209.31 | 0.00 | 1.00 | 0.00 | 16162.44 | 15124.48 | 3411.94 | 3219.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 |
June | 0.105068E+10 | 0.264226E+09 | 46.72 | 0.103842E+10 | 12255836.73 | 0.00 | 0.99 | 30-JUN-17:43 | 0.00 | 01-JUN-00:10 | 16892.14 | 30-JUN-17:43 | 16892.14 | 30-JUN-17:43 | 480.81 | 22-JUN-13:40 | 3926.36 | 30-JUN-17:43 | 0.00 | 01-JUN-00:10 |
July | 0.524153E+10 | 0.130267E+10 | 171.43 | 0.515379E+10 | 87736201.53 | 0.00 | 1.00 | 15-JUL-17:10 | 0.00 | 01-JUL-00:10 | 35068.52 | 16-JUL-11:21 | 32344.23 | 19-JUL-17:42 | 5968.36 | 16-JUL-11:29 | 8315.51 | 17-JUL-17:43 | 0.00 | 01-JUL-00:10 |
August | 0.410762E+10 | 0.102501E+10 | 134.31 | 0.409786E+10 | 9765465.30 | 0.00 | 1.00 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 | 32580.10 | 08-AUG-20:01 | 32580.10 | 08-AUG-20:01 | 1100.71 | 08-AUG-12:00 | 7923.28 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.116545E+10 | 0.289332E+09 | 43.29 | 0.107896E+10 | 86493866.92 | 0.00 | 0.99 | 02-SEP-15:30 | 0.00 | 01-SEP-00:10 | 24922.31 | 03-SEP-12:55 | 24922.31 | 03-SEP-12:55 | 4401.00 | 07-SEP-15:40 | 6549.21 | 03-SEP-12:55 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.115653E+11 | 0.288124E+10 | 395.75 | 0.113690E+11 | 0.196251E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.524153E+10 | 0.130267E+10 | 171.43 | 0.515379E+10 | 87736201.53 | 0.00 | 1.00 | 0.00 | 35068.52 | 32580.10 | 5968.36 | 8315.51 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 24.98 | 208.03 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 70.80 | 142.86 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 97.70 | 112.55 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 162.69 | 72.14 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 217.59 | 56.82 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 251.99 | 45.07 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 272.53 | 45.30 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 222.88 | 48.90 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 167.44 | 62.65 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 103.57 | 82.14 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 56.54 | 116.91 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 23.45 | 172.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 139.69 | 97.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 23.45 | 45.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 272.53 | 208.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 24.98 | 208.03 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 70.80 | 142.86 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 97.70 | 112.55 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 162.69 | 72.14 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 217.59 | 56.82 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 251.99 | 45.07 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 272.53 | 45.30 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 222.88 | 48.90 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 167.44 | 62.65 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 103.57 | 82.14 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 56.54 | 116.91 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 23.45 | 172.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 139.69 | 97.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 23.45 | 45.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 272.53 | 208.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.83 | 0.00 | 16.83 | 0.60 | 127.63 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 4.68 | 89.45 | 0.00 | 0.00 | 672.00 |
March | 38.60 | 0.00 | 38.59 | 13.79 | 67.72 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 25.64 | 42.43 | 0.00 | 0.00 | 720.00 |
May | 57.74 | 3.37 | 54.36 | 41.26 | 32.21 | 0.00 | 0.00 | 744.00 |
June | 67.20 | 7.67 | 59.53 | 56.73 | 23.71 | 0.00 | 0.00 | 720.00 |
July | 61.38 | 5.66 | 55.71 | 57.84 | 24.28 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 44.79 | 27.61 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 28.08 | 36.92 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 12.83 | 49.24 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 3.63 | 72.67 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.35 | 106.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.47 | 24.30 | 58.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.35 | 23.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.20 | 7.67 | 59.53 | 57.84 | 127.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.82 | 0.00 | 16.82 | 0.60 | 127.63 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 4.68 | 89.45 | 0.00 | 0.00 | 672.00 |
March | 38.59 | 0.00 | 38.59 | 13.79 | 67.72 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 25.64 | 42.43 | 0.00 | 0.00 | 720.00 |
May | 57.73 | 3.37 | 54.36 | 41.26 | 32.21 | 0.00 | 0.00 | 744.00 |
June | 67.19 | 7.67 | 59.53 | 56.72 | 23.71 | 0.00 | 0.00 | 720.00 |
July | 61.37 | 5.66 | 55.71 | 57.83 | 24.28 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 44.79 | 27.61 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 28.08 | 36.92 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 12.83 | 49.24 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 3.63 | 72.67 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.35 | 106.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.46 | 24.30 | 58.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.35 | 23.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.19 | 7.67 | 59.53 | 57.83 | 127.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 17.90 | 89.47 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 47.78 | 61.22 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 90.40 | 48.03 | 0.00 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 122.61 | 31.19 | 0.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 164.14 | 25.58 | 0.00 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 197.86 | 26.80 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 202.92 | 34.25 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 165.38 | 36.39 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 113.84 | 35.42 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 66.92 | 38.98 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 33.40 | 49.41 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 14.14 | 73.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 103.41 | 45.81 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 14.14 | 25.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 202.92 | 89.47 | 0.50 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 66904705.95 | 0.557178E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.171283E+09 | 0.345613E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.261682E+09 | 0.301441E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.421690E+09 | 0.186992E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.582801E+09 | 0.152200E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.653154E+09 | 0.116826E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.729946E+09 | 0.121340E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.596974E+09 | 0.130978E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.434009E+09 | 0.162388E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.277412E+09 | 0.220015E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.146546E+09 | 0.303036E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 62821649.50 | 0.461887E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.440522E+10 | 0.305989E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 62821649.50 | 0.116826E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.729946E+09 | 0.557178E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 66904705.95 | 0.557178E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.171283E+09 | 0.345613E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.261682E+09 | 0.301441E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.421690E+09 | 0.186992E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.582801E+09 | 0.152200E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.653154E+09 | 0.116826E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.729946E+09 | 0.121340E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.596974E+09 | 0.130978E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.434009E+09 | 0.162388E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.277412E+09 | 0.220015E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.146546E+09 | 0.303036E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 62821649.50 | 0.461887E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.440522E+10 | 0.305989E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 62821649.50 | 0.116826E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.729946E+09 | 0.557178E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45064288.41 | 0.00 | 45064288.41 | 1594511.22 | 0.341843E+09 |
February | 57470429.67 | 0.00 | 57470429.67 | 11321562.26 | 0.216407E+09 |
March | 0.103373E+09 | 5154.92 | 0.103368E+09 | 36943465.03 | 0.181379E+09 |
April | 0.114392E+09 | 857486.23 | 0.113534E+09 | 66462914.18 | 0.109966E+09 |
May | 0.154641E+09 | 9033514.49 | 0.145607E+09 | 0.110505E+09 | 86273763.69 |
June | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.147032E+09 | 61453093.48 |
July | 0.164389E+09 | 15169360.03 | 0.149219E+09 | 0.154909E+09 | 65038193.78 |
August | 0.133290E+09 | 4794192.82 | 0.128496E+09 | 0.119975E+09 | 73958755.71 |
September | 95713512.75 | 81737.00 | 95631775.75 | 72784119.92 | 95684096.32 |
October | 72072435.85 | 0.00 | 72072435.85 | 34363972.21 | 0.131878E+09 |
November | 47415011.88 | 0.00 | 47415011.88 | 9403306.97 | 0.188364E+09 |
December | 37788945.48 | 0.00 | 37788945.48 | 933221.16 | 0.286066E+09 |
Annual Sum or Average | 0.119978E+10 | 49813360.58 | 0.114997E+10 | 0.766228E+09 | 0.183831E+10 |
Minimum of Months | 37788945.48 | 0.00 | 37788945.48 | 933221.16 | 61453093.48 |
Maximum of Months | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.154909E+09 | 0.341843E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45062835.23 | 0.00 | 45062835.23 | 1594320.55 | 0.341843E+09 |
February | 57468698.97 | 0.00 | 57468698.97 | 11320847.48 | 0.216407E+09 |
March | 0.103370E+09 | 5154.68 | 0.103365E+09 | 36941032.55 | 0.181379E+09 |
April | 0.114389E+09 | 857446.04 | 0.113531E+09 | 66460049.69 | 0.109966E+09 |
May | 0.154636E+09 | 9033091.07 | 0.145603E+09 | 0.110501E+09 | 86273677.45 |
June | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.147027E+09 | 61452822.79 |
July | 0.164384E+09 | 15168649.02 | 0.149215E+09 | 0.154905E+09 | 65037656.14 |
August | 0.133286E+09 | 4793968.11 | 0.128492E+09 | 0.119972E+09 | 73958371.36 |
September | 95710774.52 | 81733.17 | 95629041.36 | 72781819.66 | 95683707.66 |
October | 72070253.22 | 0.00 | 72070253.22 | 34362306.09 | 0.131878E+09 |
November | 47413524.99 | 0.00 | 47413524.99 | 9402710.88 | 0.188364E+09 |
December | 37787710.35 | 0.00 | 37787710.35 | 933090.81 | 0.286065E+09 |
Annual Sum or Average | 0.119975E+10 | 49811025.76 | 0.114993E+10 | 0.766201E+09 | 0.183831E+10 |
Minimum of Months | 37787710.35 | 0.00 | 37787710.35 | 933090.81 | 61452822.79 |
Maximum of Months | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.154905E+09 | 0.341843E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 47939404.83 | 0.239635E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.115590E+09 | 0.148107E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.242140E+09 | 0.128631E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.317811E+09 | 80831994.64 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.439622E+09 | 68514767.11 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.512858E+09 | 69460979.62 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.543511E+09 | 91743987.83 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.442951E+09 | 97477046.24 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.295068E+09 | 91813854.48 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.179236E+09 | 0.104395E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 86576357.05 | 0.128069E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 0.195981E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.326118E+10 | 0.144466E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 37878456.87 | 68514767.11 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.543511E+09 | 0.239635E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.73 | 662.89 | 154.38 | 49.05 | 105.34 | 0.00 | 0.00 |
February | 143.08 | 456.75 | 252.05 | 100.66 | 151.39 | 0.00 | 0.00 |
March | 219.79 | 357.33 | 339.77 | 96.45 | 243.32 | 0.00 | 0.00 |
April | 375.53 | 228.00 | 430.45 | 151.83 | 278.63 | 0.00 | 0.00 |
May | 516.95 | 177.32 | 538.72 | 199.79 | 338.93 | 0.00 | 0.00 |
June | 614.42 | 134.55 | 594.52 | 226.57 | 367.95 | 0.00 | 0.00 |
July | 657.77 | 136.21 | 594.60 | 249.82 | 344.77 | 0.00 | 0.00 |
August | 534.86 | 152.54 | 499.38 | 199.28 | 300.10 | 0.00 | 0.00 |
September | 390.05 | 198.14 | 395.84 | 162.77 | 233.07 | 0.00 | 0.00 |
October | 230.22 | 260.18 | 284.38 | 114.61 | 169.77 | 0.00 | 0.00 |
November | 112.80 | 371.63 | 199.52 | 80.85 | 118.68 | 0.00 | 0.00 |
December | 39.35 | 550.25 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Annual Sum or Average | 324.06 | 306.73 | 368.98 | 139.96 | 229.02 | 0.00 | 0.00 |
Minimum of Months | 39.35 | 134.55 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Maximum of Months | 657.77 | 662.89 | 594.60 | 249.82 | 367.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.99 | 894.70 | 283.29 | 117.94 | 165.35 | 0.00 | 0.00 |
February | 477.80 | 612.22 | 467.44 | 257.22 | 210.23 | 0.00 | 0.00 |
March | 904.05 | 480.25 | 764.72 | 364.47 | 400.25 | 0.00 | 0.00 |
April | 1226.12 | 311.85 | 948.14 | 530.20 | 417.94 | 0.00 | 0.00 |
May | 1641.36 | 255.80 | 1216.64 | 693.94 | 522.70 | 0.00 | 0.00 |
June | 1978.62 | 267.98 | 1464.89 | 940.27 | 524.62 | 0.00 | 0.00 |
July | 2029.24 | 342.53 | 1516.66 | 1061.13 | 455.52 | 0.00 | 0.00 |
August | 1653.79 | 363.94 | 1263.13 | 861.18 | 401.95 | 0.00 | 0.00 |
September | 1138.38 | 354.22 | 877.08 | 556.25 | 320.83 | 0.00 | 0.00 |
October | 669.19 | 389.77 | 546.34 | 303.89 | 242.45 | 0.00 | 0.00 |
November | 334.01 | 494.09 | 330.79 | 162.84 | 167.95 | 0.00 | 0.00 |
December | 141.42 | 731.71 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Annual Sum or Average | 1034.11 | 458.10 | 827.17 | 496.08 | 331.09 | 0.00 | 0.00 |
Minimum of Months | 141.42 | 255.80 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Maximum of Months | 2029.24 | 894.70 | 1516.66 | 1061.13 | 524.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114449E+09 | 0.177549E+10 | 0.413500E+09 | 0.131364E+09 | 0.282136E+09 | 0.00 | 0.00 |
February | 0.346128E+09 | 0.110496E+10 | 0.609760E+09 | 0.243524E+09 | 0.366237E+09 | 0.00 | 0.00 |
March | 0.588695E+09 | 0.957086E+09 | 0.910051E+09 | 0.258341E+09 | 0.651710E+09 | 0.00 | 0.00 |
April | 0.973372E+09 | 0.590986E+09 | 0.111574E+10 | 0.393537E+09 | 0.722201E+09 | 0.00 | 0.00 |
May | 0.138459E+10 | 0.474933E+09 | 0.144291E+10 | 0.535123E+09 | 0.907791E+09 | 0.00 | 0.00 |
June | 0.159256E+10 | 0.348755E+09 | 0.154099E+10 | 0.587270E+09 | 0.953721E+09 | 0.00 | 0.00 |
July | 0.176177E+10 | 0.364823E+09 | 0.159257E+10 | 0.669131E+09 | 0.923443E+09 | 0.00 | 0.00 |
August | 0.143257E+10 | 0.408550E+09 | 0.133754E+10 | 0.533738E+09 | 0.803798E+09 | 0.00 | 0.00 |
September | 0.101102E+10 | 0.513578E+09 | 0.102602E+10 | 0.421900E+09 | 0.604117E+09 | 0.00 | 0.00 |
October | 0.616632E+09 | 0.696867E+09 | 0.761684E+09 | 0.306962E+09 | 0.454722E+09 | 0.00 | 0.00 |
November | 0.292369E+09 | 0.963271E+09 | 0.517165E+09 | 0.209556E+09 | 0.307609E+09 | 0.00 | 0.00 |
December | 0.105383E+09 | 0.147378E+10 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102196E+11 | 0.967308E+10 | 0.116363E+11 | 0.441382E+10 | 0.722246E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105383E+09 | 0.348755E+09 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176177E+10 | 0.177549E+10 | 0.159257E+10 | 0.669131E+09 | 0.953721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479394E+09 | 0.239635E+10 | 0.758763E+09 | 0.315896E+09 | 0.442867E+09 | 0.00 | 0.00 |
February | 0.115590E+10 | 0.148107E+10 | 0.113083E+10 | 0.622256E+09 | 0.508579E+09 | 0.00 | 0.00 |
March | 0.242140E+10 | 0.128631E+10 | 0.204823E+10 | 0.976190E+09 | 0.107204E+10 | 0.00 | 0.00 |
April | 0.317811E+10 | 0.808320E+09 | 0.245757E+10 | 0.137428E+10 | 0.108329E+10 | 0.00 | 0.00 |
May | 0.439621E+10 | 0.685144E+09 | 0.325866E+10 | 0.185865E+10 | 0.140001E+10 | 0.00 | 0.00 |
June | 0.512858E+10 | 0.694610E+09 | 0.379700E+10 | 0.243718E+10 | 0.135982E+10 | 0.00 | 0.00 |
July | 0.543511E+10 | 0.917436E+09 | 0.406221E+10 | 0.284214E+10 | 0.122008E+10 | 0.00 | 0.00 |
August | 0.442950E+10 | 0.974770E+09 | 0.338316E+10 | 0.230658E+10 | 0.107658E+10 | 0.00 | 0.00 |
September | 0.295068E+10 | 0.918135E+09 | 0.227340E+10 | 0.144180E+10 | 0.831592E+09 | 0.00 | 0.00 |
October | 0.179236E+10 | 0.104395E+10 | 0.146332E+10 | 0.813939E+09 | 0.649377E+09 | 0.00 | 0.00 |
November | 0.865764E+09 | 0.128069E+10 | 0.857411E+09 | 0.422081E+09 | 0.435329E+09 | 0.00 | 0.00 |
December | 0.378785E+09 | 0.195981E+10 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.326118E+11 | 0.144466E+11 | 0.260856E+11 | 0.156442E+11 | 0.104414E+11 | 0.00 | 0.00 |
Minimum of Months | 0.378785E+09 | 0.685144E+09 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Maximum of Months | 0.543511E+10 | 0.239635E+10 | 0.406221E+10 | 0.284214E+10 | 0.140001E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104523E+10 | -957256877.0 | 0.00 | 0.00 | 744.00 | 0.00 | -87977713.8 | 58.99 | 0.00 | 0.00 |
February | 0.973957E+09 | -894744129.9 | 0.00 | 0.00 | 672.00 | 0.00 | -79212873.9 | 58.99 | 0.00 | 0.00 |
March | 0.112220E+10 | -.103500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87206050.0 | 58.99 | 0.00 | 0.00 |
April | 0.100995E+10 | -926366198.3 | 0.00 | 0.00 | 720.00 | 0.00 | -83578894.9 | 58.99 | 0.00 | 0.00 |
May | 0.993968E+09 | -910525271.5 | 0.00 | 0.00 | 744.00 | 0.00 | -83443025.2 | 58.99 | 0.00 | 0.00 |
June | 0.925674E+09 | -851141942.6 | 0.00 | 0.00 | 720.00 | 0.00 | -74532390.9 | 58.99 | 0.00 | 0.00 |
July | 0.853743E+09 | -780889180.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72853334.3 | 58.99 | 0.00 | 0.00 |
August | 0.893357E+09 | -819676424.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73680729.0 | 58.99 | 0.00 | 0.00 |
September | 0.847326E+09 | -772426873.4 | 0.00 | 0.00 | 720.00 | 0.00 | -74898892.9 | 58.99 | 0.00 | 0.00 |
October | 0.894057E+09 | -810587630.6 | 0.00 | 0.00 | 744.00 | 0.00 | -83469402.0 | 58.99 | 0.00 | 0.00 |
November | 0.911466E+09 | -827627988.5 | 0.00 | 0.00 | 720.00 | 0.00 | -83837676.9 | 59.00 | 0.00 | 0.00 |
December | 0.100238E+10 | -914649556.8 | 0.00 | 0.00 | 744.00 | 0.00 | -87729201.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114733E+11 | -.105009E+11 | 8760.00 | -972420184.9 | 58.99 | |||||
Minimum of Months | 0.847326E+09 | -.103500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -87977713.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112220E+10 | -772426873.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72853334.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.96 | 0.88 | 04-JAN-11:20 | 114.34 | 8.41 | 0.00 | 31.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.95 | 0.88 | 03-FEB-11:09 | 120.54 | 8.88 | 0.00 | 35.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.92 | 0.88 | 02-MAR-09:09 | 223.65 | 11.94 | 0.00 | 160.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.92 | 0.88 | 01-APR-09:09 | 233.38 | 11.89 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.91 | 0.88 | 01-MAY-08:20 | 1038.58 | 13.10 | 18.67 | 249.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.92 | 0.88 | 01-JUN-13:39 | 3234.11 | 14.22 | 51.33 | 267.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.91 | 0.88 | 01-JUL-07:19 | 2549.80 | 13.82 | 33.83 | 252.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.93 | 0.88 | 01-AUG-08:00 | 214.67 | 11.33 | 0.00 | 176.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.93 | 0.88 | 03-SEP-08:39 | 173.80 | 10.57 | 0.00 | 111.17 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.95 | 0.88 | 01-OCT-12:39 | 136.77 | 9.31 | 0.00 | 64.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.96 | 0.88 | 01-NOV-10:30 | 104.16 | 8.02 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.97 | 0.88 | 04-DEC-11:30 | 86.81 | 7.18 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.93 | 836.06 | 11.13 | 103.83 | 1552.67 | ||||||
Minimum of Months | 226.83 | 0.91 | 0.88 | 86.81 | 7.18 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 434.17 | 0.97 | 0.88 | 3234.11 | 14.22 | 51.33 | 267.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.88 | 0.64 | 14-JAN-15:30 | 201.52 | 20.46 | 104.17 | 8.83 | 112.18 | 20.46 | 96.67 | 0.00 |
February | 275.00 | 0.84 | 0.61 | 21-FEB-16:10 | 319.51 | 23.11 | 145.83 | 50.33 | 138.01 | 21.31 | 132.67 | 1.17 |
March | 304.00 | 0.76 | 0.61 | 01-MAR-15:20 | 512.88 | 24.82 | 223.00 | 128.00 | 385.30 | 25.35 | 248.00 | 62.83 |
April | 325.17 | 0.77 | 0.61 | 01-APR-15:20 | 470.32 | 23.11 | 204.00 | 124.83 | 498.30 | 24.21 | 242.33 | 81.33 |
May | 385.83 | 0.75 | 0.61 | 01-MAY-15:09 | 380.36 | 22.32 | 246.33 | 167.50 | 624.44 | 23.46 | 290.67 | 106.50 |
June | 434.17 | 0.76 | 0.61 | 01-JUN-14:20 | 369.27 | 22.05 | 261.17 | 177.50 | 345.82 | 23.26 | 323.00 | 113.00 |
July | 417.33 | 0.75 | 0.61 | 01-JUL-14:50 | 378.70 | 22.38 | 250.50 | 174.17 | 522.99 | 23.48 | 314.67 | 117.83 |
August | 421.33 | 0.78 | 0.61 | 01-AUG-14:39 | 369.40 | 22.01 | 226.83 | 137.83 | 490.89 | 23.14 | 274.00 | 100.83 |
September | 352.17 | 0.79 | 0.61 | 01-SEP-15:20 | 558.57 | 24.02 | 204.33 | 111.67 | 492.11 | 25.12 | 234.67 | 69.00 |
October | 317.67 | 0.82 | 0.61 | 02-OCT-14:00 | 545.92 | 24.73 | 187.00 | 78.33 | 215.85 | 23.47 | 187.50 | 26.17 |
November | 269.50 | 0.86 | 0.64 | 01-NOV-14:09 | 307.09 | 23.60 | 140.83 | 33.50 | 114.40 | 20.54 | 114.67 | 0.00 |
December | 236.83 | 0.89 | 0.68 | 01-DEC-15:09 | 211.54 | 22.44 | 107.83 | 14.33 | 93.87 | 19.85 | 73.67 | 0.00 |
Annual Sum or Average | 3965.83 | 0.80 | 394.92 | 22.90 | 2301.83 | 1206.83 | 366.55 | 23.03 | 2532.50 | 678.67 | ||
Minimum of Months | 226.83 | 0.75 | 0.61 | 201.52 | 20.46 | 104.17 | 8.83 | 93.87 | 19.85 | 73.67 | 0.00 | |
Maximum of Months | 434.17 | 0.89 | 0.68 | 558.57 | 24.82 | 261.17 | 177.50 | 624.44 | 25.35 | 323.00 | 117.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103298E+11 | 23463.29 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701476E+10 | 23463.29 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.666511E+10 | 23463.29 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375482E+10 | 23463.29 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244445E+10 | 23463.29 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100421E+09 | 23463.29 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1257984.95 | 878.80 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.405402E+09 | 23463.29 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152796E+10 | 23463.29 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428560E+10 | 23463.29 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.746327E+10 | 23463.29 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439928E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103298E+11 | 23463.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453014E+11 | 62922.03 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274534E+11 | 62922.03 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213378E+11 | 62922.03 | 02-MAR-21:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.828449E+10 | 62922.03 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.426388E+10 | 62922.03 | 01-MAY-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204947E+09 | 49629.44 | 21-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226073E+10 | 60143.83 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153600E+11 | 62922.03 | 12-NOV-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324471E+11 | 62922.03 | 01-DEC-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156914E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453014E+11 | 62922.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168985E+12 | 154449.91 | 05-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902367E+11 | 110397.92 | 03-FEB-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610899E+11 | 114786.14 | 06-MAR-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820678E+10 | 54055.11 | 29-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.613828E+10 | 45823.95 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638202E+09 | 20437.76 | 11-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441500E+11 | 99531.99 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113900E+12 | 154449.91 | 31-DEC-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493346E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168985E+12 | 154449.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.146799E+09 | 0.146799E+09 | 3533.07 | 20-MAY-16:00 | 3533.07 | 0.00 |
June | 0.00 | 0.00 | 0.200857E+10 | 0.196003E+10 | 6878.89 | 30-JUN-16:00 | 6878.89 | 0.00 |
July | 0.00 | 0.00 | 0.488713E+10 | 0.480551E+10 | 15884.49 | 19-JUL-05:02 | 13939.02 | 0.00 |
August | 0.00 | 0.00 | 0.433197E+10 | 0.432011E+10 | 15124.48 | 09-AUG-05:01 | 15124.48 | 0.00 |
September | 0.00 | 0.00 | 0.176863E+10 | 0.167983E+10 | 16162.44 | 08-SEP-05:02 | 12750.50 | 0.00 |
October | 0.00 | 0.00 | 36955847.60 | 36955847.60 | 2186.64 | 18-OCT-13:50 | 2186.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.131800E+11 | 0.129492E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.488713E+10 | 0.480551E+10 | 16162.44 | 15124.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.105068E+10 | 0.103842E+10 | 16892.14 | 30-JUN-17:43 | 16892.14 | 0.00 |
July | 0.00 | 0.00 | 0.524153E+10 | 0.515379E+10 | 35068.52 | 16-JUL-11:21 | 29188.86 | 0.00 |
August | 0.00 | 0.00 | 0.410762E+10 | 0.409786E+10 | 32580.10 | 08-AUG-20:01 | 32580.10 | 0.00 |
September | 0.00 | 0.00 | 0.116545E+10 | 0.107896E+10 | 24922.31 | 03-SEP-12:55 | 24922.31 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.115653E+11 | 0.113690E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.524153E+10 | 0.515379E+10 | 35068.52 | 32580.10 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103156E+10 | 0.09 | 394.98 | 01-JAN-00:03 | 0.09 |
February | 0.811914E+09 | 0.07 | 394.98 | 01-FEB-00:02 | 0.09 |
March | 0.782330E+09 | 0.06 | 394.98 | 01-MAR-00:10 | 0.09 |
April | 0.248322E+09 | 0.02 | 394.98 | 01-APR-00:10 | 0.09 |
May | 0.133131E+09 | 0.01 | 394.98 | 01-MAY-00:03 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 23145617.93 | 0.00 | 394.98 | 10-OCT-01:10 | 0.09 |
November | 0.498480E+09 | 0.04 | 394.98 | 09-NOV-05:20 | 0.09 |
December | 0.957897E+09 | 0.08 | 394.98 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.448678E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103156E+10 | 0.09 | 394.98 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110388E+10 | 0.67 | 1004.68 | 02-JAN-07:20 | 1.04 |
February | 0.978749E+09 | 0.57 | 1004.68 | 01-FEB-07:40 | 1.04 |
March | 0.113087E+10 | 0.53 | 1004.68 | 23-MAR-13:30 | 1.04 |
April | 0.102664E+10 | 0.44 | 1004.68 | 06-APR-09:50 | 1.04 |
May | 0.106045E+10 | 0.44 | 1004.68 | 01-MAY-06:20 | 1.04 |
June | 0.103653E+10 | 0.42 | 1004.68 | 01-JUN-07:00 | 1.03 |
July | 0.101002E+10 | 0.39 | 1004.68 | 01-JUL-06:10 | 1.03 |
August | 0.108555E+10 | 0.42 | 1004.68 | 01-AUG-07:00 | 1.03 |
September | 0.100529E+10 | 0.41 | 1004.68 | 20-SEP-08:00 | 1.04 |
October | 0.101112E+10 | 0.41 | 1004.68 | 13-OCT-07:10 | 1.04 |
November | 0.992276E+09 | 0.45 | 1004.68 | 06-NOV-16:20 | 1.04 |
December | 0.105991E+10 | 0.56 | 1004.68 | 01-DEC-07:20 | 1.04 |
Annual Sum or Average | 0.125013E+11 | 0.47 | |||
Minimum of Months | 0.978749E+09 | 0.39 | 1004.68 | 1.03 | |
Maximum of Months | 0.113087E+10 | 0.67 | 1004.68 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.262090E+10 | 0.88 | 1800.43 | 03-JAN-07:10 | 1.01 |
February | 0.220534E+10 | 0.85 | 1800.43 | 01-FEB-12:40 | 1.01 |
March | 0.240798E+10 | 0.84 | 1800.43 | 04-MAR-09:10 | 1.01 |
April | 0.199622E+10 | 0.69 | 1800.43 | 11-APR-08:70 | 1.01 |
May | 0.196406E+10 | 0.52 | 1800.43 | 01-MAY-08:20 | 1.01 |
June | 0.185415E+10 | 0.40 | 1800.43 | 21-JUN-16:00 | 0.99 |
July | 0.183965E+10 | 0.39 | 1800.43 | 14-JUL-10:30 | 1.00 |
August | 0.198308E+10 | 0.42 | 1800.43 | 03-AUG-15:50 | 1.00 |
September | 0.181197E+10 | 0.40 | 1800.43 | 05-SEP-12:40 | 1.00 |
October | 0.184121E+10 | 0.46 | 1800.43 | 04-OCT-08:00 | 1.00 |
November | 0.207060E+10 | 0.75 | 1800.43 | 06-NOV-17:40 | 1.01 |
December | 0.245576E+10 | 0.88 | 1800.43 | 02-DEC-16:50 | 1.00 |
Annual Sum or Average | 0.250509E+11 | 0.62 | |||
Minimum of Months | 0.181197E+10 | 0.39 | 1800.43 | 0.99 | |
Maximum of Months | 0.262090E+10 | 0.88 | 1800.43 | 1.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.94 | 0.00 |
February | 4.03 | 0.00 |
March | 3.04 | 0.00 |
April | 1.38 | 0.02 |
May | 0.60 | 0.02 |
June | 0.54 | 0.14 |
July | 1.77 | 0.00 |
August | 1.60 | 0.22 |
September | 0.72 | 0.31 |
October | 0.69 | 0.32 |
November | 2.26 | 0.03 |
December | 2.83 | 0.00 |
Annual Sum or Average | 22.42 | 0.04 |
Minimum of Months | 0.54 | 0.00 |
Maximum of Months | 4.03 | 0.32 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.08 | 0.00 |
August | 0.50 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.58 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.50 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110388E+10 | 0.146246E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.978749E+09 | 0.100620E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113087E+10 | 0.965956E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.102664E+10 | 0.548985E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109332E+10 | 0.357408E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.147016E+10 | 0.149438E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.205735E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.201369E+10 | 1954891.62 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.137711E+10 | 0.599833E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101922E+10 | 0.224717E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.992276E+09 | 0.623632E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105991E+10 | 0.107256E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153232E+11 | 0.633703E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.978749E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.205735E+10 | 0.146246E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.262090E+10 | 0.633205E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.220534E+10 | 0.390644E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.240798E+10 | 0.306060E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.199622E+10 | 0.121448E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196406E+10 | 0.618917E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211838E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.314232E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.300810E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.210131E+10 | 0.307441E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184121E+10 | 0.332258E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.207060E+10 | 0.220706E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.245576E+10 | 0.461495E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.279322E+11 | 0.223175E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.184121E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.314232E+10 | 0.633205E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110388E+10 | 0.00 | 0.103298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.978749E+09 | 0.00 | 0.701476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113087E+10 | 0.00 | 0.666511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102664E+10 | 0.00 | 0.375482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106045E+10 | 0.146799E+09 | 0.244445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103653E+10 | 0.200857E+10 | 0.100421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101002E+10 | 0.488713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108555E+10 | 0.433197E+10 | 1257984.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100529E+10 | 0.176863E+10 | 0.405402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101112E+10 | 36955847.60 | 0.152796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.992276E+09 | 0.00 | 0.428560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105991E+10 | 0.00 | 0.746327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125013E+11 | 0.131800E+11 | 0.439928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.978749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113087E+10 | 0.488713E+10 | 0.103298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.262090E+10 | 0.00 | 0.453014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220534E+10 | 0.00 | 0.274534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240798E+10 | 0.00 | 0.213378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199622E+10 | 0.00 | 0.828449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196406E+10 | 0.00 | 0.426388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185415E+10 | 0.105068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183965E+10 | 0.524153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198308E+10 | 0.410762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181197E+10 | 0.116545E+10 | 0.204947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184121E+10 | 0.00 | 0.226073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207060E+10 | 0.00 | 0.153600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245576E+10 | 0.00 | 0.324471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250509E+11 | 0.115653E+11 | 0.156914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262090E+10 | 0.524153E+10 | 0.453014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.110388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.978749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106045E+10 | 0.00 | 0.00 | 0.00 | 32870035.87 | 0.00 | 0.357408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103653E+10 | 0.00 | 0.00 | 0.00 | 0.433637E+09 | 0.00 | 0.149438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101002E+10 | 0.00 | 0.00 | 0.00 | 0.104732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108555E+10 | 0.00 | 0.00 | 0.00 | 0.928133E+09 | 0.00 | 1954891.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100529E+10 | 0.00 | 0.00 | 0.00 | 0.371829E+09 | 0.00 | 0.599833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101112E+10 | 0.00 | 0.00 | 0.00 | 8104228.88 | 0.00 | 0.224717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.992276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125013E+11 | 0.00 | 0.00 | 0.00 | 0.282190E+10 | 0.00 | 0.633703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.978749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113087E+10 | 0.00 | 0.00 | 0.00 | 0.104732E+10 | 0.00 | 0.146246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.262090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185415E+10 | 0.00 | 0.00 | 0.00 | 0.264226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183965E+10 | 0.00 | 0.00 | 0.00 | 0.130267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198308E+10 | 0.00 | 0.00 | 0.00 | 0.102501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181197E+10 | 0.00 | 0.00 | 0.00 | 0.289332E+09 | 0.00 | 0.307441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250509E+11 | 0.00 | 0.00 | 0.00 | 0.288124E+10 | 0.00 | 0.223175E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262090E+10 | 0.00 | 0.00 | 0.00 | 0.130267E+10 | 0.00 | 0.633205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289302E+10 | 0.00 | 0.00 | 0.12 |
February | 2347652.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204958E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198876E+10 | 0.00 | 0.00 | 0.13 |
April | 59427920.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122156E+10 | 0.00 | 0.00 | 0.13 |
May | 0.208772E+09 | 3588090.28 | 2356431.52 | 41123.59 | 1270553.03 | 0.839818E+09 | 15094243.88 | 11285.43 | 0.13 |
June | 0.327600E+09 | 76824321.31 | 0.00 | 1191631.00 | 0.00 | 10858210.33 | 0.236234E+09 | 0.00 | 0.13 |
July | 3232530.56 | 0.182259E+09 | 0.00 | 2696913.04 | 0.00 | 0.00 | 0.233474E+09 | 0.00 | 0.12 |
August | 46924080.16 | 0.138686E+09 | 0.00 | 2764142.23 | 0.00 | 0.00 | 0.353411E+09 | 0.00 | 0.13 |
September | 0.370209E+09 | 57140081.81 | 0.00 | 1132236.05 | 0.00 | 0.146408E+09 | 0.225425E+09 | 0.00 | 0.13 |
October | 0.544163E+09 | 508413.95 | 0.00 | 12299.24 | 126171.73 | 0.582941E+09 | 7682569.21 | 0.00 | 0.12 |
November | 57385775.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151027E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237478E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.162006E+10 | 0.459006E+09 | 2356431.52 | 7838345.13 | 1396724.76 | 0.136180E+11 | 0.107132E+10 | 11285.43 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.544163E+09 | 0.182259E+09 | 2356431.52 | 2764142.23 | 1270553.03 | 0.289302E+10 | 0.353411E+09 | 11285.43 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905932E+10 | 0.00 | 0.00 | 0.17 |
February | 0.936942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520667E+10 | 0.00 | 0.00 | 0.17 |
March | 0.210558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339661E+10 | 0.00 | 0.00 | 0.19 |
April | 0.212011E+10 | 0.00 | 0.00 | 0.00 | 26173766.52 | 0.103837E+10 | 0.00 | 0.00 | 0.18 |
May | 0.225320E+10 | 0.00 | 0.00 | 0.00 | 90008229.86 | 0.434564E+09 | 0.00 | 0.00 | 0.18 |
June | 0.178926E+10 | 0.106947E+09 | 0.00 | 310394.63 | 77795375.39 | 0.00 | 91718038.31 | 0.00 | 0.21 |
July | 0.860150E+09 | 0.463800E+09 | 0.00 | 2590446.66 | 3693207.00 | 0.00 | 0.927427E+09 | 0.00 | 0.27 |
August | 0.139085E+10 | 0.378224E+09 | 0.00 | 1263121.19 | 5336141.99 | 0.00 | 0.645884E+09 | 0.00 | 0.26 |
September | 0.207666E+10 | 99810717.88 | 0.00 | 532984.27 | 43076776.97 | 19221763.01 | 0.240172E+09 | 0.00 | 0.21 |
October | 0.265103E+10 | 0.00 | 0.00 | 0.00 | 29792176.59 | 0.225207E+09 | 0.00 | 0.00 | 0.18 |
November | 0.197427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221686E+10 | 0.00 | 0.00 | 0.17 |
December | 0.906434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630575E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.193569E+11 | 0.104878E+10 | 0.00 | 4696946.75 | 0.275876E+09 | 0.279026E+11 | 0.190520E+10 | 0.00 | 0.20 |
Minimum of Months | 0.292358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.265103E+10 | 0.463800E+09 | 0.00 | 2590446.66 | 90008229.86 | 0.905932E+10 | 0.927427E+09 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |