Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1249.95 | 258.51 | 258.51 |
Net Site Energy | 1249.95 | 258.51 | 258.51 |
Total Source Energy | 3800.54 | 786.03 | 786.03 |
Net Source Energy | 3800.54 | 786.03 | 786.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 75.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1174.07 | 75.88 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 75.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 230.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 34.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 140.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 88.79 | 15.69 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 242.82 | 15.69 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 88.79 | 15.69 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 242.82 | 15.69 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1174.071 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1174.071 | 100.00 |
Total On-Site and Utility Electric Sources | 1174.071 | 100.00 |
Total Electricity End Uses | 1174.071 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.00 |
Time Setpoint Not Met During Occupied Cooling | 62.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 280.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-JUN-14:00 | 02-JAN-06:19 | - | - | - | 26-JAN-12:30 |
Heating | 0.00 | 88886.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39628.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12592.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1662.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 99616.09 | 88886.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 88886.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39628.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10287.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1662.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 82.25 | 0.00 | 0.00 | 0.00 |
Cooling | 731.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 554.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3718.28 | 82.25 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.01 | 0.00 | 0.00 | 0.00 |
Cooling | 151.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 769.01 | 17.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.01 | 0.00 | 0.00 | 0.00 |
Cooling | 151.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 769.01 | 17.01 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.31 |
ZONE2 FINE STORAGE DIRECT AIR | 4.68 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.85 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.85 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 155725.58 |
PSZ-OFFICE HEATING COIL | 31441.46 |
PSZ-FINE STORAGE HEATING COIL | 138870.54 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 155717.46 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-FINE STORAGE | 4.68 | 4.68 | 4.68 | 4.68 | 4.68 | 4.68 | 1.00 | 1.00 | 4.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.31 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 4.68 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 26201.34 | 31441.46 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 4.68 | 4.68 | 4.68 | 4.68 | 108698.33 | 138870.54 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.31 | 0.655345 | 1.31 | 25505.95 | 26201.34 | 13100.67 | 26201.34 | 0.735445 | 0.735440 | 0.735440 | 0.735440 |
PSZ-FINE STORAGE COOLING COIL | 4.68 | 2.34 | 4.68 | 103151.95 | 108698.33 | 54349.17 | 108698.33 | 0.693215 | 0.693210 | 0.693210 | 0.693210 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.31 | 1494.33 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.68 | 8792.81 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12941.88877 | 15530.26653 | 1.09224 | 1.31069 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 40.77133 | 9.11023E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7388.09789 | 8865.71746 | 0.21258 | 0.25510 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30000 | 6.07234E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 59323.59409 | 71188.31291 | 3.90272 | 4.68326 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.11023E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17700.73423 | 21240.88108 | 0.42940 | 0.51527 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 6.30000 | 6.07234E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 129764.54904 | 155717.45885 | 3.20524 | 3.84629 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 6.30000 | 6.07234E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20804.14 | 1.31069 | 1.31069 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7801.22 | 0.25510 | 0.25510 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 87586.24 | 4.68326 | 4.68326 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 18719.34 | 0.51527 | 0.51527 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31069 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.68326 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.84629 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.84629 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 155725.57669 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 155717.45885 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31069 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31069 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31069 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31069 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31069 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.31069 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.68326 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.68326 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.68326 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.68326 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68326 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.68326 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.31069 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.68326 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31069 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31069 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31069 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31069 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31069 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31069 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65535 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31069 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25505.94513 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26201.34000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13100.67000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26201.34000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73544 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73544 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73544 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73544 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26201.34000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31441.46093 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31069 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1494.32553 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31441.46093 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68326 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.68326 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.68326 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.68326 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.68326 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.68326 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.34163 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.68326 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 103151.94556 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 108698.33000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 54349.16500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 108698.33000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69321 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69321 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69321 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69321 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 108698.33000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 138870.54481 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.68326 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8792.80848 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 138870.54481 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 25183.6 | 10.37 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 105059.3 | 12.21 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.0974234579E-002 | 2.7987041183E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1593400918 | 0.1653112832 | Pass | Pass | 0.1780732568 | 1.0202548738 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1762421279 | 0.1943142020 | Pass | Pass | 4.2033927161E-002 | 0.2195905556 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.75 | 83.75 | 123.53 | |
Exterior Lighting Total | 7857.24 | 123.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26201.34 | 19269.51 | 6931.83 | 0.74 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 108698.33 | 75350.77 | 33347.56 | 0.69 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 25183.6 | 10.37 | ||||
PSZ-FINE STORAGE COOLING COIL | 105059.3 | 12.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 155725.58 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31441.46 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 138870.54 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.85 | 357.36 | 92.91 | 1.00 | 3.25 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.31 | 1494.33 | 1140.11 | 1.00 | 1.30 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.68 | 8792.81 | 1877.50 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12941.89 | 15530.27 | 65.56 | 1.092 | 1.311 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 23.90 | 23.90 | 0.00811 | 40.77 | 0.00911 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 59323.59 | 71188.31 | 51.09 | 3.903 | 4.683 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 26.70 | 26.70 | 0.00805 | 42.00 | 0.00911 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00387 | 42.00 | 0.00911 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7388.10 | 8865.72 | 37.43 | 0.213 | 0.255 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00814 | 6.30 | 0.00607 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 17700.73 | 21240.88 | 15.24 | 0.429 | 0.515 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 15.56 | 15.56 | 0.00776 | 6.30 | 0.00607 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 129764.55 | 155717.46 | 48.59 | 3.205 | 3.846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 10.00 | 9.99 | 0.00783 | 6.30 | 0.00607 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.31 | 1.31 | 0.26 | 0.26 | 1.3107 | 1.3107 | 1.3107 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.68 | 4.68 | 0.52 | 0.52 | 4.6833 | 4.6833 | 4.6833 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 155725.577 | 155725.577 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 155725.58 | 155725.58 | 3.846291 | 9.21 | 9.21 | 0.00745638 | 43.33 | 26.77 | 0.01600000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 9.99 | 0.00782794 | 99.9999 | 155717.46 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 26201.340 | 0.000 | 1.310690 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 26201.34 | 25346.70 | 1.310690 | 25.46 | 16.37 | 0.00820436 | 12.00 | 11.03 | 0.00800000 | 40.90 | 0.00911023 | 21.89 | 9.1811 | 23.90 | 0.00811443 | 42.8627 | 12938.49 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31441.461 | 31441.461 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31441.46 | 31441.46 | 1.310686 | 14.07 | 11.04 | 0.00716226 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 9.1811 | 21.10 | 0.00813550 | 50.9406 | 7388.10 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 108698.330 | 0.000 | 4.683260 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 108698.33 | 106746.69 | 4.683260 | 27.86 | 17.13 | 0.00812811 | 12.00 | 11.03 | 0.00800000 | 42.00 | 0.00911023 | 22.20 | 7.5573 | 26.70 | 0.00804782 | 35.9924 | 59323.59 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 138870.545 | 138870.545 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 138870.54 | 138870.54 | 4.683259 | 9.20 | 8.29 | 0.00659931 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.5573 | 15.56 | 0.00775527 | 68.7929 | 17700.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 155725.577 | 155725.577 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1738 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.846291 | 4.51472060 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 155725.58 | 155725.58 | 1.0000 | 4.51472060 | 3.846291 | 9.21 | 9.21 | 0.00745638 | 28032.0 | 43.33 | 26.77 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 155725.58 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00782794 | 9.99 | 0.00782794 | 99.9999 | 155717.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26201.340 | 0.000 | 1.310690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0915 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 26201.34 | 25346.70 | 1.0000 | 1.53846886 | 1.310690 | 25.46 | 16.37 | 0.00820436 | 46491.0 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26201.34 | 40.90 | 0.00911023 | 21.89 | 0.12033533 | 9.1811 | 23.90 | 0.00811276 | 23.90 | 0.00811443 | 42.8627 | 12938.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31441.461 | 31441.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.310686 | 1.53846361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31441.46 | 31441.46 | 1.0000 | 1.53846361 | 1.310686 | 14.07 | 11.04 | 0.00716226 | 32240.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31441.46 | 6.30 | 0.00607234 | 6.30 | 0.12033533 | 9.1811 | 21.01 | 0.00813550 | 21.10 | 0.00813550 | 50.9406 | 7388.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 108698.330 | 0.000 | 4.683260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9498 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 108698.33 | 106746.69 | 1.0000 | 5.49714249 | 4.683260 | 27.86 | 17.13 | 0.00812811 | 48739.7 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 108698.33 | 42.00 | 0.00911023 | 22.20 | 0.35392745 | 7.5573 | 26.70 | 0.00804782 | 26.70 | 0.00804782 | 35.9924 | 59323.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 138870.545 | 138870.545 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.683259 | 5.49714108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 138870.54 | 138870.54 | 1.0000 | 5.49714108 | 4.683259 | 9.20 | 8.29 | 0.00659931 | 25861.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 138870.54 | 6.30 | 0.00607234 | 6.30 | 0.35392745 | 7.5573 | 15.56 | 0.00775527 | 15.56 | 0.00775527 | 68.7929 | 17700.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2583.33 | 996.17 | 280.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2583.33 | 996.17 | 280.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 2.00 | 89.17 | 2.00 | 62.50 |
ZONE2 FINE STORAGE | 0.33 | 511.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.33 | 588.50 | 2.00 | 62.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.414 | 0.337 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1174.07 | 5475.32 | 01-JAN-08:10 | 99616.09 | 06-JUN-15:00 |
Electricity:Building | 655.65 | 4992.32 | 01-JAN-00:10 | 48037.94 | 06-FEB-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 456.05 | 2759.73 | 01-JAN-00:10 | 33963.13 | 06-FEB-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 23.38 | 483.00 | 11-MAR-06:10 | 1776.83 | 18-JAN-12:40 |
WaterSystems:Electricity | 23.38 | 483.00 | 11-MAR-06:10 | 1776.83 | 18-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.38 | 483.00 | 11-MAR-06:10 | 1776.83 | 18-JAN-12:40 |
Fans:Electricity | 174.93 | 0.00 | 01-JAN-08:10 | 12592.43 | 07-AUG-07:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 34.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity | 34.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
ElectricityPurchased:Facility | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
ElectricityPurchased:Plant | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
ElectricityNet:Plant | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
Cogeneration:ElectricityNet | 1174.07 | 5475.32 | 26-NOV-09:30 | 99616.09 | 06-JUN-15:00 |
Electricity:HVAC | 371.52 | 0.00 | 01-JAN-08:10 | 53067.49 | 06-JUN-15:10 |
General:Fans:Electricity | 140.53 | 0.00 | 01-JAN-08:10 | 10644.49 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 230.99 | 0.00 | 01-JAN-00:10 | 42780.35 | 06-JUN-15:10 |
ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 75.88 | 2250.00 | 11-MAR-06:10 | 88886.21 | 02-JAN-06:20 |
Gas:HVAC | 75.88 | 2250.00 | 11-MAR-06:10 | 88886.21 | 02-JAN-06:20 |
Heating:Gas | 75.88 | 2250.00 | 11-MAR-06:10 | 88886.21 | 02-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JAN-12:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1191.37 | 0.00 | 01-JAN-08:10 | 200069.70 | 06-JUN-15:10 |
EnergyTransfer:Building | 465.85 | 0.00 | 01-JAN-08:10 | 89734.60 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 92.04 | 0.00 | 01-JAN-00:10 | 17560.23 | 12-JUN-16:20 |
Heating:EnergyTransfer | 17.39 | 0.00 | 01-JAN-08:10 | 66632.68 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.92 | 0.00 | 01-JAN-00:10 | 13598.54 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 448.46 | 0.00 | 01-JAN-00:10 | 89734.60 | 06-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 91.11 | 0.00 | 01-JAN-00:10 | 17560.23 | 12-JUN-16:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 371.19 | 0.00 | 01-JAN-00:10 | 75298.93 | 06-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.85 | 0.00 | 01-JAN-00:10 | 13988.38 | 01-JAN-07:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 357.34 | 0.00 | 01-JAN-00:10 | 75298.93 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.62 | 0.00 | 01-JAN-08:00 | 49498.54 | 03-JAN-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.62 | 0.00 | 01-JAN-08:00 | 49498.54 | 03-JAN-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 725.52 | 0.00 | 01-JAN-08:10 | 110335.10 | 06-JUN-15:10 |
HeatingCoils:EnergyTransfer | 3.71 | 0.00 | 01-JAN-08:10 | 66251.63 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 721.81 | 0.00 | 01-JAN-00:10 | 110335.10 | 06-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.923 | -91.114 | 0.000 | 0.000 | 3.596 | 30.994 | 31.946 | 14.978 | 0.000 | 7.361 | 12.124 | 0.000 | -7.298 | 0.000 | -3.510 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 13.853 | -357.335 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 17.371 | 200.726 | 0.000 | 0.000 | 0.000 | -11.272 | -0.010 |
ZONE3 BULK STORAGE | 2.616 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 41.224 | 0.000 | 5.229 | 1465.989 | 0.000 | -14.301 | 0.000 | -1922.404 | -0.040 |
Total Facility | 2.616 | 0.000 | 14.777 | -448.450 | 0.000 | 0.000 | 3.596 | 481.960 | 139.282 | 56.202 | 0.000 | 29.961 | 1678.839 | 0.000 | -21.599 | 0.000 | -1937.185 | -0.051 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | -25224.28 | 0.00 | 0.00 | 28.61 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 25035.68 | 0.00 | -638.28 | 0.00 | -361.93 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-13:32 | 0.00 | 0.00 | 0.00 | -94133.94 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 19.26 | 92914.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | -113567.14 | 0.00 | 0.00 | 21.93 | 4546.06 | 2623.78 | 0.00 | 0.00 | 569.80 | 190692.52 | 0.00 | -1167.70 | 0.00 | -83719.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:01 | 0.00 | 0.00 | 30269.83 | 0.00 | 0.00 | 0.00 | 56.21 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -720.33 | 0.00 | -566.82 | -30199.08 |
ZONE2 FINE STORAGE | 01-JAN-06:55 | 0.00 | 0.00 | 27976.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29176.58 |
ZONE3 BULK STORAGE | 03-JAN-06:55 | 49502.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1068.09 | 0.00 | -1375.16 | -51868.55 |
Total Facility | 02-JAN-06:13 | 46377.34 | 0.00 | 44305.48 | 0.00 | 0.00 | 0.00 | 46.49 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1808.11 | 0.00 | -755.75 | -95335.30 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3107 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3107 | 0.0918 | 1.0000 | 0.1203 | 0.0918 | ||
PSZ-FINE STORAGE | 4.6833 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 4.6833 | 0.0756 | 1.0000 | 0.3539 | 0.0756 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3107 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3107 | 1.0000 | 1.0000 | 0.1203 | 0.0918 | ||
PSZ-FINE STORAGE | 4.6833 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 4.6833 | 1.0000 | 1.0000 | 0.3539 | 0.0756 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3107 | 1.3107 | 1.3107 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 4.6833 | 4.6833 | 4.6833 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3107 | 1.3107 | 1.3107 | 1.3107 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.6833 | 4.6833 | 4.6833 | 4.6833 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3107 | 1.3107 | 1.3107 | 0.1203 | 0.4717 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 4.6833 | 4.6833 | 4.6833 | 0.3539 | 0.6869 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3107 | 1.3107 | 1.3107 | 1.3107 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.6833 | 4.6833 | 4.6833 | 4.6833 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 2.00 |
Number of hours cooling loads not met | 62.50 |
Number of hours not met | 64.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 75.88 | 88886.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 230.99 | 42780.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.53 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 34.40 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 140.53 | 10644.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.38 | 1776.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1174.07 |
Natural Gas | 0.00 | 75.88 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1249.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 47.77 |
Fans (All) | 36.18 |
Service Water Heating | 4.84 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 242.82 |
Subtotal | 242.82 |
Natural Gas [MJ/m2] | |
Space Heating | 15.69 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 15.69 |
Subtotal | 15.69 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.56 |
Space Heating | 6.07 |
Space Cooling | 18.48 |
Fans (All) | 14.00 |
Service Water Heating | 1.87 |
Receptacle Equipment | 11.14 |
Miscellaneous | 9.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.105751E+11 |
February | 0.000 | 0.558102E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583228E+10 |
December | 0.000 | 0.626220E+10 |
Annual Sum or Average | 0.758786E+11 | |
Minimum of Months | 0.000 | 0.558102E+10 |
Maximum of Months | 0.000 | 0.105751E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122334E+10 | 3996.95 | 14-JAN-16:00 | 21.30 | 15.06 | 0.237403E+09 | 302.44 | 24-JAN-11:09 | 17.02 | 10.35 |
February | 0.254090E+10 | 16844.42 | 25-FEB-06:03 | 17.60 | 15.66 | 0.225446E+09 | 301.60 | 07-FEB-15:50 | 25.35 | 15.75 |
March | 0.615626E+10 | 24381.39 | 29-MAR-05:01 | 21.18 | 17.33 | 0.268681E+09 | 301.62 | 11-MAR-15:00 | 30.20 | 19.48 |
April | 0.929804E+10 | 25223.64 | 05-APR-05:01 | 19.50 | 15.11 | 0.249144E+09 | 301.61 | 01-APR-13:00 | 34.20 | 20.56 |
May | 0.120783E+11 | 24535.91 | 09-MAY-05:01 | 26.97 | 19.05 | 0.259194E+09 | 301.62 | 20-MAY-14:50 | 38.43 | 25.22 |
June | 0.124090E+11 | 23251.90 | 03-JUN-05:01 | 30.03 | 22.06 | 0.259277E+09 | 301.93 | 13-JUN-12:09 | 37.92 | 26.45 |
July | 0.112864E+11 | 20659.71 | 07-JUL-05:01 | 31.52 | 25.90 | 0.249243E+09 | 307.18 | 10-JUL-12:09 | 38.28 | 26.73 |
August | 0.112959E+11 | 19890.29 | 07-AUG-05:01 | 29.53 | 24.78 | 0.269140E+09 | 301.60 | 08-AUG-15:50 | 36.82 | 26.61 |
September | 0.968504E+10 | 22627.37 | 27-SEP-05:01 | 23.08 | 20.68 | 0.249178E+09 | 301.61 | 27-SEP-14:20 | 35.60 | 22.73 |
October | 0.828668E+10 | 25137.89 | 25-OCT-05:01 | 19.02 | 16.53 | 0.249115E+09 | 301.62 | 05-OCT-15:00 | 32.40 | 21.14 |
November | 0.479178E+10 | 23628.92 | 02-NOV-05:01 | 16.55 | 13.36 | 0.238498E+09 | 301.61 | 07-NOV-15:00 | 28.10 | 18.11 |
December | 0.206331E+10 | 5555.83 | 01-DEC-15:15 | 23.03 | 13.47 | 0.243886E+09 | 301.60 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.911149E+11 | 0.299820E+10 | ||||||||
Minimum of Months | 0.122334E+10 | 3996.95 | 16.55 | 13.36 | 0.225446E+09 | 301.60 | 17.02 | 10.35 | ||
Maximum of Months | 0.124090E+11 | 25223.64 | 31.52 | 25.90 | 0.269140E+09 | 307.18 | 38.43 | 26.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.214055E+10 | 24153.22 | 20-FEB-14:55 | 26.30 | 14.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.162283E+11 | 90819.74 | 26-MAR-12:43 | 29.67 | 16.31 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.431941E+11 | 94133.42 | 09-APR-13:32 | 26.93 | 15.53 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.629361E+11 | 89757.01 | 06-MAY-05:01 | 29.55 | 17.33 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.626174E+11 | 85237.37 | 05-JUN-05:01 | 30.05 | 20.34 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.532529E+11 | 79772.00 | 07-JUL-05:01 | 31.52 | 25.90 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.456091E+11 | 76770.37 | 03-AUG-19:03 | 31.98 | 27.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.356408E+11 | 81520.50 | 26-SEP-17:05 | 34.60 | 22.31 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.268033E+11 | 89057.21 | 22-OCT-11:32 | 27.63 | 18.06 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.855789E+10 | 60213.84 | 05-NOV-12:33 | 28.47 | 17.04 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.360830E+09 | 9487.56 | 18-DEC-14:15 | 22.57 | 15.04 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.357341E+12 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.629361E+11 | 94133.42 | 34.60 | 27.03 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601444E+09 | 30270.33 | 02-JAN-06:01 | 6.45 |
February | 0.115820E+09 | 5552.34 | 02-FEB-07:10 | 7.12 |
March | 15946897.64 | 886.74 | 22-MAR-06:10 | 17.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 20729560.66 | 744.62 | 28-NOV-07:15 | 15.43 |
December | 0.169374E+09 | 10613.88 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.923314E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.601444E+09 | 30270.33 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.550453E+10 | 27976.76 | 01-JAN-06:55 | 7.10 |
February | 0.247456E+10 | 7685.89 | 13-FEB-17:55 | 22.60 |
March | 0.738246E+09 | 6156.44 | 27-MAR-06:55 | 20.30 |
April | 27930023.56 | 5768.86 | 01-APR-06:05 | 23.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.175600E+09 | 5220.99 | 24-OCT-06:50 | 19.17 |
November | 0.100255E+10 | 6156.73 | 25-NOV-17:57 | 20.10 |
December | 0.393003E+10 | 7740.42 | 29-DEC-16:23 | 18.60 |
Annual Sum or Average | 0.138534E+11 | |||
Minimum of Months | 0.00 | 0.00 | 7.10 | |
Maximum of Months | 0.550453E+10 | 27976.76 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259259E+10 | 49502.18 | 03-JAN-06:55 | 5.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 23867603.61 | 6481.67 | 23-DEC-06:55 | 6.10 |
Annual Sum or Average | 0.261645E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 0.259259E+10 | 49502.18 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102026E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22010058.67 | 0.662340E+09 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304407E+09 | 0.374835E+09 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891451E+09 | 55864692.54 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146209E+10 | 13004888.38 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141642E+10 | 5464069.55 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101185E+10 | 8103794.98 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927351E+09 | 10718455.47 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691749E+09 | 16585072.49 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485800E+09 | 0.120569E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147668E+09 | 0.375176E+09 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387162.80 | 0.847217E+09 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.736117E+10 | 0.351014E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5464069.55 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146209E+10 | 0.102026E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242403E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186680.61 | 0.299610E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373924E+09 | 0.205633E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230094E+10 | 0.279386E+09 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439088E+10 | 0.101923E+09 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324186E+10 | 49338230.58 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337842E+10 | 27961381.50 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189321E+10 | 45834342.36 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116398E+10 | 0.121655E+09 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575773E+09 | 0.301084E+09 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50274823.81 | 0.746780E+09 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178708.46 | 0.212113E+10 |
Annual Sum or Average | 0.136656E+12 | 0.173706E+11 | 0.112715E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27961381.50 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439088E+10 | 0.299610E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151945.60 | 0.849384E+10 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9852903.79 | 0.105987E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3446064.48 | 0.993304E+10 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5508122.34 | 0.740421E+10 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29486285.59 | 0.829472E+10 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31328792.14 | 0.569456E+10 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2066959.48 | 0.665454E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559318E+10 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34316913.24 | 0.453376E+10 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3318669.60 | 0.356405E+10 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.85 | 0.355230E+10 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444209.19 | 0.590997E+10 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.137926E+09 | 0.802269E+11 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355230E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34316913.24 | 0.105987E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5858.77 | 05-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 912.19 | 22-FEB-13:00 | 4981.67 | 02-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3705.64 | 28-MAR-16:05 | 3308.37 | 20-MAR-06:05 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5819.18 | 27-APR-16:05 | 1827.66 | 11-APR-06:05 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6950.20 | 05-MAY-16:10 | 306.24 | 15-MAY-05:01 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7010.32 | 06-JUN-16:10 | 126.80 | 18-JUN-01:23 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5229.29 | 07-JUL-16:10 | 186.76 | 26-JUL-05:01 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4547.73 | 07-AUG-16:10 | 243.55 | 16-AUG-05:01 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3950.66 | 27-SEP-16:10 | 266.38 | 19-SEP-05:01 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3929.34 | 02-OCT-16:10 | 2794.47 | 31-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.09 | 09-NOV-13:00 | 4361.31 | 27-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.54 | 28-DEC-13:55 | 5632.96 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.80 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 7010.32 | 5858.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6044.33 | 31-JAN-08:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.26 | 22-FEB-15:00 | 8829.03 | 09-FEB-16:10 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.76 | 27-MAR-15:10 | 10244.97 | 24-MAR-23:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14460.94 | 15-APR-15:10 | 3351.85 | 22-APR-18:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15952.09 | 05-MAY-15:10 | 1540.05 | 15-MAY-03:05 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16239.24 | 06-JUN-15:10 | 1543.60 | 18-JUN-02:20 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8176.11 | 20-JUL-15:10 | 1239.34 | 19-JUL-03:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5206.80 | 07-AUG-15:10 | 1335.14 | 15-AUG-23:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5635.85 | 22-SEP-15:10 | 1089.09 | 08-SEP-20:40 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6481.67 | 03-OCT-15:10 | 2170.76 | 12-OCT-03:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.23 | 03-NOV-15:10 | 2906.84 | 30-NOV-09:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.54 | 24-DEC-13:53 | 7935.35 | 29-DEC-17:05 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.09 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16239.24 | 10244.97 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.07 | 12-JAN-07:45 | 27919.20 | 24-JAN-13:10 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.90 | 13-FEB-20:00 | 32467.41 | 18-FEB-11:20 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 806.90 | 30-MAR-15:20 | 23254.39 | 01-MAR-10:45 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.66 | 22-APR-15:20 | 18969.99 | 17-APR-14:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.58 | 31-MAY-14:40 | 16206.24 | 10-MAY-12:10 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3216.83 | 03-JUN-17:50 | 16548.20 | 06-JUN-14:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 613.87 | 24-JUL-17:10 | 15309.25 | 19-JUL-12:10 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 13992.94 | 31-AUG-11:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.67 | 12-SEP-12:10 | 15678.42 | 19-SEP-12:10 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.44 | 22-OCT-20:30 | 10818.93 | 17-OCT-14:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 26-NOV-18:50 | 15390.38 | 30-NOV-11:17 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.45 | 22-DEC-08:63 | 20552.88 | 31-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10818.93 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3216.83 | 32467.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3996.95 | 14-JAN-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
February | 16844.42 | 25-FEB-06:03 | 290.07 | 2345.77 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.42 |
March | 24381.39 | 29-MAR-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.41 |
April | 25223.64 | 05-APR-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 |
May | 24535.91 | 09-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.58 |
June | 23251.90 | 03-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
July | 20659.71 | 07-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
August | 19890.29 | 07-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 0.00 |
September | 22627.37 | 27-SEP-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.63 |
October | 25137.89 | 25-OCT-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.70 |
November | 23628.92 | 02-NOV-05:01 | 507.62 | 4105.10 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.00 |
December | 5555.83 | 01-DEC-15:15 | 1318.50 | 3926.62 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3996.95 | 290.07 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25223.64 | 1318.50 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 482.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24153.22 | 20-FEB-14:55 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 |
March | 90819.74 | 26-MAR-12:43 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1911.95 | 0.00 |
April | 94133.42 | 09-APR-13:32 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 0.00 |
May | 89757.01 | 06-MAY-05:01 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.37 | 0.00 |
June | 85237.37 | 05-JUN-05:01 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
July | 79772.00 | 07-JUL-05:01 | 0.00 | 11998.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.88 | 0.00 |
August | 76770.37 | 03-AUG-19:03 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.80 | 0.00 |
September | 81520.50 | 26-SEP-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.36 | 0.00 |
October | 89057.21 | 22-OCT-11:32 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 | 0.00 |
November | 60213.84 | 05-NOV-12:33 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.66 | 0.00 |
December | 9487.56 | 18-DEC-14:15 | 0.00 | 61194.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94133.42 | 0.00 | 61194.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1911.95 | 869.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5519.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.14 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.52 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.69 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5519.46 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.764583E+11 | 61555.44 | 25-JAN-14:39 | 0.105751E+11 | 88886.21 | 02-JAN-06:19 |
February | 0.719472E+11 | 70090.80 | 22-FEB-14:39 | 0.558102E+10 | 11790.35 | 02-FEB-07:10 |
March | 0.910200E+11 | 81473.14 | 28-MAR-14:50 | 0.602640E+10 | 2250.00 | 01-MAR-00:10 |
April | 0.102185E+12 | 91362.20 | 27-APR-14:00 | 0.583200E+10 | 2250.00 | 01-APR-00:10 |
May | 0.120704E+12 | 98198.53 | 03-MAY-14:00 | 0.602640E+10 | 2250.00 | 01-MAY-00:10 |
June | 0.121338E+12 | 99616.09 | 06-JUN-14:00 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.118116E+12 | 95200.67 | 06-JUL-14:20 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.117023E+12 | 92163.89 | 07-AUG-14:30 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.102887E+12 | 87351.37 | 22-SEP-14:39 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.944252E+11 | 86309.48 | 03-OCT-14:20 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.805470E+11 | 74263.94 | 09-NOV-13:00 | 0.583228E+10 | 2717.34 | 27-NOV-07:00 |
December | 0.774209E+11 | 65826.93 | 01-DEC-13:00 | 0.626220E+10 | 13233.11 | 23-DEC-06:10 |
Annual Sum or Average | 0.117407E+13 | 0.758786E+11 | ||||
Minimum of Months | 0.719472E+11 | 61555.44 | 0.558102E+10 | 2250.00 | ||
Maximum of Months | 0.121338E+12 | 99616.09 | 0.105751E+11 | 88886.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.118707E+11 | 0.115358E+11 | 0.00 | 0.102669E+11 | 0.00 | 0.00 | 0.567516E+09 | 0.00 | 0.00 | 0.00 | 0.211412E+10 | 0.00 |
February | 0.366966E+11 | 0.102726E+11 | 0.105871E+11 | 0.00 | 0.981394E+10 | 0.00 | 0.00 | 0.267509E+10 | 0.00 | 0.00 | 0.00 | 0.190189E+10 | 0.00 |
March | 0.423649E+11 | 0.106450E+11 | 0.123357E+11 | 0.00 | 0.131117E+11 | 0.00 | 0.00 | 0.104739E+11 | 0.00 | 0.00 | 0.00 | 0.208882E+10 | 0.00 |
April | 0.397216E+11 | 0.958898E+10 | 0.114862E+11 | 0.00 | 0.157802E+11 | 0.00 | 0.00 | 0.236805E+11 | 0.00 | 0.00 | 0.00 | 0.192741E+10 | 0.00 |
May | 0.412341E+11 | 0.928254E+10 | 0.119357E+11 | 0.00 | 0.193831E+11 | 0.00 | 0.00 | 0.369414E+11 | 0.00 | 0.00 | 0.00 | 0.192710E+10 | 0.00 |
June | 0.408524E+11 | 0.864611E+10 | 0.118862E+11 | 0.00 | 0.193179E+11 | 0.00 | 0.00 | 0.388094E+11 | 0.00 | 0.00 | 0.00 | 0.182622E+10 | 0.00 |
July | 0.401034E+11 | 0.911754E+10 | 0.115358E+11 | 0.00 | 0.190973E+11 | 0.00 | 0.00 | 0.364255E+11 | 0.00 | 0.00 | 0.00 | 0.183613E+10 | 0.00 |
August | 0.423649E+11 | 0.962198E+10 | 0.123357E+11 | 0.00 | 0.184059E+11 | 0.00 | 0.00 | 0.324102E+11 | 0.00 | 0.00 | 0.00 | 0.188446E+10 | 0.00 |
September | 0.397216E+11 | 0.999441E+10 | 0.114862E+11 | 0.00 | 0.151041E+11 | 0.00 | 0.00 | 0.247286E+11 | 0.00 | 0.00 | 0.00 | 0.185224E+10 | 0.00 |
October | 0.401034E+11 | 0.110693E+11 | 0.115358E+11 | 0.00 | 0.133783E+11 | 0.00 | 0.00 | 0.163735E+11 | 0.00 | 0.00 | 0.00 | 0.196490E+10 | 0.00 |
November | 0.385909E+11 | 0.113286E+11 | 0.110862E+11 | 0.00 | 0.110128E+11 | 0.00 | 0.00 | 0.656458E+10 | 0.00 | 0.00 | 0.00 | 0.196393E+10 | 0.00 |
December | 0.401034E+11 | 0.120923E+11 | 0.115358E+11 | 0.00 | 0.102591E+11 | 0.00 | 0.00 | 0.133954E+10 | 0.00 | 0.00 | 0.00 | 0.209083E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123530E+12 | 0.139282E+12 | 0.174931E+12 | 0.00 | 0.230990E+12 | 0.233780E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.864611E+10 | 0.105871E+11 | 0.00 | 0.981394E+10 | 0.00 | 0.00 | 0.567516E+09 | 0.00 | 0.00 | 0.00 | 0.182622E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.120923E+11 | 0.123357E+11 | 0.00 | 0.193831E+11 | 0.00 | 0.00 | 0.388094E+11 | 0.00 | 0.00 | 0.00 | 0.211412E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.105751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.558102E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.583228E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.626220E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758786E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.558102E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.105751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 11439.78 | 12-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 12592.43 | 21-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 12592.43 | 01-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 12592.43 | 01-APR-08:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12592.43 | 01-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12592.43 | 01-JUN-06:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12592.43 | 01-JUL-07:49 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12592.43 | 01-AUG-06:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12592.43 | 01-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12592.43 | 02-OCT-15:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 12592.43 | 01-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 11824.00 | 02-DEC-13:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 11439.78 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 12592.43 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3277.33 | 26-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1776.83 | 18-JAN-12:39 | 0.00 |
February | 10062.04 | 22-FEB-14:39 | 0.00 | 0.00 | 0.00 | 1774.85 | 01-FEB-12:30 | 0.00 |
March | 21545.23 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1761.76 | 01-MAR-12:50 | 0.00 |
April | 33891.23 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 1736.85 | 01-APR-11:39 | 0.00 |
May | 40932.48 | 05-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1709.53 | 01-MAY-11:00 | 0.00 |
June | 42780.35 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1685.28 | 01-JUN-11:00 | 0.00 |
July | 35719.46 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1671.59 | 01-JUL-11:30 | 0.00 |
August | 33263.71 | 07-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1682.30 | 31-AUG-11:39 | 0.00 |
September | 28234.67 | 22-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1704.59 | 30-SEP-11:50 | 0.00 |
October | 26711.47 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1732.62 | 31-OCT-11:50 | 0.00 |
November | 14303.32 | 09-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1757.82 | 30-NOV-12:50 | 0.00 |
December | 6584.77 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 1773.81 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3277.33 | 0.00 | 0.00 | 0.00 | 1671.59 | 0.00 | ||
Maximum of Months | 42780.35 | 0.00 | 0.00 | 0.00 | 1776.83 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61555.44 | 25-JAN-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11439.78 | 0.00 | 0.00 | 2672.16 | 0.00 |
February | 70090.80 | 22-FEB-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 10062.04 | 0.00 |
March | 81473.14 | 28-MAR-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 21435.96 | 0.00 |
April | 91362.20 | 27-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 31348.22 | 0.00 |
May | 98198.53 | 03-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 38189.21 | 0.00 |
June | 99616.09 | 06-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 39628.29 | 0.00 |
July | 95200.67 | 06-JUL-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 35222.94 | 0.00 |
August | 92163.89 | 07-AUG-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 32184.95 | 0.00 |
September | 87351.37 | 22-SEP-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 27350.38 | 0.00 |
October | 86309.48 | 03-OCT-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 26300.46 | 0.00 |
November | 74263.94 | 09-NOV-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 14226.25 | 0.00 |
December | 65826.93 | 01-DEC-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11824.00 | 0.00 | 0.00 | 6542.58 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61555.44 | 35620.03 | 10112.62 | 0.00 | 0.00 | 11439.78 | 0.00 | 0.00 | 2672.16 | 0.00 | |
Maximum of Months | 99616.09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 12592.43 | 0.00 | 0.00 | 39628.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 88886.21 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11790.35 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2250.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2250.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2250.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2717.34 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 13233.11 | 23-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 88886.21 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.33 | 1.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.51 | 0.17 | 20.51 | 0.17 | 24.50 | 0.17 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.25 | 1.17 | 24.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.71 | 7.17 | 24.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.38 | 8.67 | 25.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.38 | 9.67 | 25.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.31 | 10.50 | 25.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.40 | 9.83 | 25.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.95 | 8.50 | 25.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.33 | 6.50 | 24.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
December | 0.50 | 20.50 | 0.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.39 | 2.00 | 20.39 | 89.17 | 26.69 | 62.50 | 25.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.51 | 1.33 | 20.51 | 17.33 | 27.38 | 10.50 | 25.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.64 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 27.83 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 96.83 | 28.01 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 94.33 | 28.04 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 27.94 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 27.71 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 27.63 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.76 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.57 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 14.97 | 0.00 | 511.67 | 27.88 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 14.97 | 0.00 | 0.00 | 97.00 | 28.04 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 293.33 | 23.04 | 44.17 | 21.10 | 44.17 | 21.10 |
February | 167.83 | 23.26 | 28.00 | 23.65 | 2.33 | 20.96 |
March | 31.00 | 23.65 | 214.00 | 23.91 | 0.00 | 0.00 |
April | 2.67 | 24.83 | 295.50 | 23.92 | 2.67 | 24.83 |
May | 8.67 | 24.68 | 312.00 | 23.94 | 8.67 | 24.68 |
June | 29.17 | 24.31 | 312.00 | 23.96 | 29.17 | 24.31 |
July | 64.17 | 24.18 | 300.00 | 23.96 | 64.17 | 24.18 |
August | 75.67 | 24.12 | 324.00 | 23.95 | 75.67 | 24.12 |
September | 42.67 | 24.11 | 300.00 | 23.94 | 42.67 | 24.11 |
October | 3.67 | 24.52 | 297.00 | 23.92 | 3.67 | 24.52 |
November | 39.83 | 23.49 | 149.00 | 23.90 | 0.00 | 0.00 |
December | 237.50 | 23.26 | 7.67 | 21.00 | 7.67 | 21.00 |
Annual Sum or Average | 996.17 | 23.43 | 2583.33 | 23.88 | 280.83 | 23.59 |
Minimum of Months | 2.67 | 23.04 | 7.67 | 21.00 | 0.00 | 0.00 |
Maximum of Months | 293.33 | 24.83 | 324.00 | 23.96 | 75.67 | 24.83 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.176041E+10 | 0.478255E+09 | 159.12 | 0.164257E+10 | 0.117836E+09 | 0.00 | 0.25 | 14-JAN-15:40 | 0.00 | 01-JAN-00:05 | 5806.93 | 14-JAN-15:40 | 5266.58 | 12-JAN-15:40 | 1016.01 | 18-JAN-13:10 | 1555.69 | 14-JAN-15:40 | 0.00 | 01-JAN-00:05 |
February | 0.368116E+10 | 0.994867E+09 | 207.41 | 0.334689E+10 | 0.334272E+09 | 0.00 | 0.87 | 25-FEB-06:03 | 0.00 | 01-FEB-00:10 | 22484.52 | 25-FEB-06:03 | 18661.92 | 25-FEB-06:03 | 3822.60 | 25-FEB-06:03 | 5532.73 | 25-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.868449E+10 | 0.241885E+10 | 300.74 | 0.789891E+10 | 0.785580E+09 | 0.00 | 1.00 | 07-MAR-06:02 | 0.00 | 01-MAR-00:10 | 29350.84 | 11-MAR-06:01 | 26033.50 | 29-MAR-05:01 | 7320.76 | 11-MAR-06:03 | 6820.63 | 11-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.128899E+11 | 0.389104E+10 | 315.58 | 0.119547E+11 | 0.935274E+09 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 29481.61 | 03-APR-05:01 | 27230.32 | 29-APR-05:01 | 7210.06 | 03-APR-05:05 | 7682.71 | 30-APR-15:41 | 0.00 | 01-APR-00:10 |
May | 0.182852E+11 | 0.573686E+10 | 375.70 | 0.155910E+11 | 0.269427E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 31997.80 | 24-MAY-05:01 | 26738.16 | 09-MAY-05:01 | 13059.09 | 24-MAY-05:06 | 8195.78 | 28-MAY-15:23 | 0.00 | 01-MAY-00:10 |
June | 0.203162E+11 | 0.622186E+10 | 381.83 | 0.159799E+11 | 0.433627E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 33060.86 | 26-JUN-05:01 | 26097.57 | 07-JUN-05:01 | 15161.11 | 26-JUN-05:07 | 8407.09 | 11-JUN-15:23 | 0.00 | 01-JUN-00:10 |
July | 0.208835E+11 | 0.596439E+10 | 374.81 | 0.144191E+11 | 0.646438E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 33532.83 | 26-JUL-05:01 | 23265.82 | 07-JUL-05:01 | 17213.77 | 20-JUL-05:04 | 8388.87 | 02-JUL-16:11 | 0.00 | 01-JUL-00:10 |
August | 0.216243E+11 | 0.598652E+10 | 356.50 | 0.143999E+11 | 0.722439E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 33331.16 | 11-AUG-05:01 | 22495.58 | 06-AUG-16:11 | 15989.16 | 19-AUG-05:05 | 8000.07 | 06-AUG-14:51 | 0.00 | 01-AUG-00:10 |
September | 0.174155E+11 | 0.483154E+10 | 317.53 | 0.123328E+11 | 0.508270E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 33658.78 | 11-SEP-05:01 | 24262.97 | 27-SEP-05:01 | 16413.21 | 11-SEP-05:05 | 7562.54 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.122326E+11 | 0.344179E+10 | 309.75 | 0.104206E+11 | 0.181202E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 31021.10 | 12-OCT-05:01 | 26513.46 | 25-OCT-05:01 | 11548.34 | 12-OCT-05:05 | 7095.14 | 12-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.668540E+10 | 0.183255E+10 | 253.87 | 0.612732E+10 | 0.558078E+09 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 27895.39 | 09-NOV-06:01 | 25210.67 | 02-NOV-05:01 | 5509.83 | 09-NOV-06:03 | 6551.00 | 09-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.283115E+10 | 0.765974E+09 | 212.74 | 0.264962E+10 | 0.181540E+09 | 0.00 | 0.31 | 01-DEC-14:55 | 0.00 | 01-DEC-00:10 | 6964.97 | 02-DEC-14:55 | 6964.97 | 02-DEC-14:55 | 706.16 | 29-DEC-15:40 | 1852.56 | 02-DEC-14:55 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.147290E+12 | 0.425645E+11 | 3565.58 | 0.116763E+12 | 0.305266E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.176041E+10 | 0.478255E+09 | 159.12 | 0.164257E+10 | 0.117836E+09 | 0.00 | 0.25 | 0.00 | 5806.93 | 5266.58 | 706.16 | 1555.69 | 0.00 | |||||||
Maximum of Months | 0.216243E+11 | 0.622186E+10 | 381.83 | 0.159799E+11 | 0.722439E+10 | 0.00 | 1.00 | 0.00 | 33658.78 | 27230.32 | 17213.77 | 8407.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.298909E+09 | 89260308.99 | 25.53 | 0.279657E+09 | 19251166.44 | 0.00 | 0.07 | 26-JAN-13:52 | 0.00 | 01-JAN-00:05 | 6407.09 | 26-JAN-13:52 | 6016.02 | 26-JAN-13:52 | 722.95 | 14-JAN-15:00 | 1907.31 | 26-JAN-13:52 | 0.00 | 01-JAN-00:05 |
February | 0.563855E+10 | 0.168022E+10 | 137.17 | 0.526581E+10 | 0.372743E+09 | 0.00 | 0.32 | 20-FEB-14:55 | 0.00 | 01-FEB-00:10 | 27582.71 | 20-FEB-14:55 | 27582.71 | 20-FEB-14:55 | 3647.79 | 25-FEB-15:30 | 8904.94 | 20-FEB-14:55 | 0.00 | 01-FEB-00:10 |
March | 0.259411E+11 | 0.805506E+10 | 307.39 | 0.243244E+11 | 0.161672E+10 | 0.00 | 1.00 | 12-MAR-14:12 | 0.00 | 01-MAR-00:10 | 108558.25 | 12-MAR-14:12 | 105565.57 | 26-MAR-12:43 | 8350.59 | 12-MAR-09:32 | 31926.82 | 28-MAR-17:06 | 0.00 | 01-MAR-00:10 |
April | 0.586833E+11 | 0.197894E+11 | 498.28 | 0.561802E+11 | 0.250311E+10 | 0.00 | 1.00 | 01-APR-17:05 | 0.00 | 01-APR-00:10 | 114593.30 | 16-APR-20:23 | 108384.13 | 09-APR-13:32 | 19133.28 | 16-APR-20:23 | 35170.59 | 16-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.894711E+11 | 0.312046E+11 | 593.43 | 0.804460E+11 | 0.902516E+10 | 0.00 | 1.00 | 01-MAY-17:03 | 0.00 | 01-MAY-00:23 | 121717.80 | 19-MAY-05:01 | 104724.47 | 06-MAY-21:42 | 52418.30 | 24-MAY-05:06 | 36568.16 | 07-MAY-15:02 | 0.00 | 01-MAY-00:10 |
June | 0.945592E+11 | 0.325875E+11 | 582.30 | 0.803925E+11 | 0.141667E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:13 | 126859.50 | 24-JUN-05:01 | 102047.34 | 04-JUN-12:22 | 47406.86 | 26-JUN-22:23 | 37193.74 | 11-JUN-15:42 | 0.00 | 01-JUN-00:10 |
July | 0.943138E+11 | 0.304611E+11 | 596.02 | 0.695516E+11 | 0.247622E+11 | 0.00 | 1.00 | 01-JUL-00:23 | 0.00 | 01-JUL-00:12 | 129290.14 | 21-JUL-05:01 | 98624.23 | 04-JUL-16:22 | 58643.65 | 25-JUL-05:01 | 36594.25 | 02-JUL-15:42 | 0.00 | 01-JUL-00:10 |
August | 0.841294E+11 | 0.264237E+11 | 592.67 | 0.607331E+11 | 0.233963E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 128565.11 | 31-AUG-05:01 | 92171.76 | 06-AUG-15:42 | 58618.46 | 17-AUG-05:07 | 35148.54 | 27-AUG-13:42 | 0.00 | 01-AUG-00:10 |
September | 0.632300E+11 | 0.198971E+11 | 529.08 | 0.482816E+11 | 0.149484E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 121462.24 | 03-SEP-14:23 | 96642.37 | 26-SEP-17:05 | 44013.88 | 10-SEP-11:03 | 35050.75 | 17-SEP-19:42 | 0.00 | 01-SEP-00:10 |
October | 0.408131E+11 | 0.129317E+11 | 401.65 | 0.368690E+11 | 0.394411E+10 | 0.00 | 1.00 | 01-OCT-09:43 | 0.00 | 01-OCT-00:15 | 112206.39 | 03-OCT-17:42 | 104836.84 | 22-OCT-14:52 | 17155.43 | 03-OCT-17:42 | 33277.78 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 |
November | 0.155059E+11 | 0.473204E+10 | 229.12 | 0.146471E+11 | 0.858870E+09 | 0.00 | 0.73 | 11-NOV-12:13 | 0.00 | 01-NOV-00:10 | 73440.30 | 11-NOV-12:13 | 70048.81 | 05-NOV-12:33 | 4518.90 | 11-NOV-12:13 | 21760.43 | 11-NOV-12:13 | 0.00 | 01-NOV-00:10 |
December | 0.193132E+10 | 0.573569E+09 | 88.48 | 0.185498E+10 | 76335455.83 | 0.00 | 0.19 | 18-DEC-14:15 | 0.00 | 01-DEC-00:10 | 18547.72 | 18-DEC-14:15 | 17055.95 | 18-DEC-14:15 | 1722.57 | 16-DEC-12:30 | 5413.18 | 18-DEC-14:15 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.574516E+12 | 0.188425E+12 | 4581.14 | 0.478826E+12 | 0.956899E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.298909E+09 | 89260308.99 | 25.53 | 0.279657E+09 | 19251166.44 | 0.00 | 0.07 | 0.00 | 6407.09 | 6016.02 | 722.95 | 1907.31 | 0.00 | |||||||
Maximum of Months | 0.945592E+11 | 0.325875E+11 | 596.02 | 0.804460E+11 | 0.247622E+11 | 0.00 | 1.00 | 0.00 | 129290.14 | 108384.13 | 58643.65 | 37193.74 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.20 | 17.33 | 26.87 | 79.03 | 152.58 | 7.67 | 0.00 | 744.00 |
February | 50.38 | 18.64 | 31.74 | 105.78 | 132.58 | 0.00 | 0.00 | 672.00 |
March | 65.37 | 26.22 | 39.15 | 172.96 | 91.98 | 0.00 | 0.00 | 744.00 |
April | 78.94 | 36.86 | 42.08 | 271.90 | 43.59 | 0.00 | 0.00 | 720.00 |
May | 75.01 | 31.81 | 43.20 | 302.74 | 15.88 | 0.00 | 0.00 | 744.00 |
June | 70.89 | 27.80 | 43.09 | 300.07 | 12.81 | 0.00 | 0.00 | 720.00 |
July | 52.32 | 10.19 | 42.13 | 214.94 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 47.91 | 8.40 | 39.51 | 185.39 | 14.41 | 0.00 | 0.00 | 744.00 |
September | 52.86 | 15.59 | 37.27 | 175.98 | 32.80 | 0.00 | 0.00 | 720.00 |
October | 55.23 | 22.15 | 33.08 | 168.99 | 83.64 | 0.00 | 0.00 | 744.00 |
November | 50.18 | 21.66 | 28.53 | 122.93 | 132.29 | 0.00 | 0.00 | 720.00 |
December | 42.90 | 16.58 | 26.32 | 77.44 | 160.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.17 | 21.07 | 36.10 | 181.74 | 73.08 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 42.90 | 8.40 | 26.32 | 77.44 | 7.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.94 | 36.86 | 43.20 | 302.74 | 160.70 | 7.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.20 | 17.33 | 26.87 | 79.03 | 152.58 | 7.67 | 0.00 | 744.00 |
February | 50.38 | 18.64 | 31.74 | 105.78 | 132.58 | 0.00 | 0.00 | 672.00 |
March | 65.37 | 26.22 | 39.15 | 172.96 | 91.98 | 0.00 | 0.00 | 744.00 |
April | 78.94 | 36.86 | 42.08 | 271.90 | 43.59 | 0.00 | 0.00 | 720.00 |
May | 75.01 | 31.81 | 43.20 | 302.74 | 15.88 | 0.00 | 0.00 | 744.00 |
June | 70.89 | 27.80 | 43.09 | 300.07 | 12.81 | 0.00 | 0.00 | 720.00 |
July | 52.32 | 10.19 | 42.13 | 214.94 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 47.91 | 8.40 | 39.51 | 185.39 | 14.41 | 0.00 | 0.00 | 744.00 |
September | 52.86 | 15.59 | 37.27 | 175.98 | 32.80 | 0.00 | 0.00 | 720.00 |
October | 55.23 | 22.15 | 33.08 | 168.99 | 83.64 | 0.00 | 0.00 | 744.00 |
November | 50.18 | 21.66 | 28.53 | 122.93 | 132.29 | 0.00 | 0.00 | 720.00 |
December | 42.90 | 16.58 | 26.32 | 77.44 | 160.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.17 | 21.07 | 36.10 | 181.74 | 73.08 | 7.67 | 0.00 | 8760.00 |
Minimum of Months | 42.90 | 8.40 | 26.32 | 77.44 | 7.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.94 | 36.86 | 43.20 | 302.74 | 160.70 | 7.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.24 | 0.00 | 12.24 | 8.85 | 91.95 | 7.83 | 0.00 | 744.00 |
February | 14.51 | 0.00 | 14.51 | 18.44 | 78.87 | 0.00 | 0.00 | 672.00 |
March | 17.49 | 0.00 | 17.49 | 39.34 | 54.51 | 0.00 | 0.00 | 744.00 |
April | 19.08 | 0.15 | 18.92 | 74.58 | 25.25 | 0.00 | 0.00 | 720.00 |
May | 21.37 | 0.94 | 20.44 | 105.77 | 9.17 | 0.00 | 0.00 | 744.00 |
June | 22.03 | 1.07 | 20.95 | 113.22 | 7.53 | 0.00 | 0.00 | 720.00 |
July | 21.64 | 0.51 | 21.13 | 97.06 | 4.08 | 0.00 | 0.00 | 744.00 |
August | 19.82 | 0.16 | 19.66 | 81.93 | 8.32 | 0.00 | 0.00 | 744.00 |
September | 17.56 | 0.00 | 17.55 | 60.76 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 15.21 | 0.00 | 15.21 | 44.83 | 48.65 | 0.00 | 0.00 | 744.00 |
November | 12.88 | 0.00 | 12.88 | 21.61 | 77.93 | 0.00 | 0.00 | 720.00 |
December | 11.94 | 0.00 | 11.94 | 9.40 | 97.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.16 | 0.24 | 16.92 | 56.50 | 43.40 | 7.83 | 0.00 | 8760.00 |
Minimum of Months | 11.94 | 0.00 | 11.94 | 8.85 | 4.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 22.03 | 1.07 | 21.13 | 113.22 | 97.44 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.24 | 0.00 | 12.24 | 8.85 | 91.95 | 7.83 | 0.00 | 744.00 |
February | 14.51 | 0.00 | 14.51 | 18.44 | 78.87 | 0.00 | 0.00 | 672.00 |
March | 17.49 | 0.00 | 17.49 | 39.34 | 54.51 | 0.00 | 0.00 | 744.00 |
April | 19.08 | 0.15 | 18.92 | 74.58 | 25.24 | 0.00 | 0.00 | 720.00 |
May | 21.37 | 0.94 | 20.44 | 105.77 | 9.17 | 0.00 | 0.00 | 744.00 |
June | 22.02 | 1.07 | 20.95 | 113.22 | 7.53 | 0.00 | 0.00 | 720.00 |
July | 21.64 | 0.51 | 21.13 | 97.06 | 4.08 | 0.00 | 0.00 | 744.00 |
August | 19.82 | 0.16 | 19.66 | 81.93 | 8.32 | 0.00 | 0.00 | 744.00 |
September | 17.56 | 0.00 | 17.55 | 60.76 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 15.21 | 0.00 | 15.21 | 44.83 | 48.65 | 0.00 | 0.00 | 744.00 |
November | 12.88 | 0.00 | 12.88 | 21.61 | 77.93 | 0.00 | 0.00 | 720.00 |
December | 11.94 | 0.00 | 11.94 | 9.40 | 97.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.16 | 0.24 | 16.92 | 56.50 | 43.40 | 7.83 | 0.00 | 8760.00 |
Minimum of Months | 11.94 | 0.00 | 11.94 | 8.85 | 4.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 22.02 | 1.07 | 21.13 | 113.22 | 97.44 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.27 | 37.02 | 32.24 | 79.32 | 55.56 | 183.67 | 0.00 | 744.00 |
February | 87.08 | 48.42 | 38.66 | 103.07 | 53.92 | 46.00 | 0.00 | 672.00 |
March | 117.15 | 69.95 | 47.20 | 143.20 | 51.66 | 1.83 | 0.00 | 744.00 |
April | 150.28 | 104.87 | 45.41 | 187.46 | 48.62 | 0.00 | 0.00 | 720.00 |
May | 159.38 | 109.84 | 49.54 | 197.34 | 39.98 | 3.00 | 0.00 | 744.00 |
June | 149.19 | 94.60 | 54.59 | 185.85 | 37.26 | 16.33 | 0.00 | 720.00 |
July | 104.82 | 37.44 | 67.38 | 131.15 | 24.88 | 12.33 | 0.00 | 744.00 |
August | 90.65 | 25.77 | 64.89 | 115.18 | 24.51 | 48.17 | 0.00 | 744.00 |
September | 92.89 | 39.12 | 53.77 | 114.02 | 33.27 | 51.17 | 0.00 | 720.00 |
October | 104.26 | 66.03 | 38.23 | 129.52 | 54.55 | 7.33 | 0.00 | 744.00 |
November | 86.83 | 57.02 | 29.80 | 105.28 | 60.46 | 5.00 | 0.00 | 720.00 |
December | 67.25 | 36.24 | 31.01 | 76.79 | 59.43 | 73.50 | 0.00 | 744.00 |
Annual Sum or Average | 106.60 | 60.48 | 46.12 | 130.72 | 45.28 | 448.33 | 0.00 | 8760.00 |
Minimum of Months | 67.25 | 25.77 | 29.80 | 76.79 | 24.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.38 | 109.84 | 67.38 | 197.34 | 60.46 | 183.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118385E+09 | 46423318.77 | 71961440.09 | 0.211685E+09 | 0.408659E+09 |
February | 0.121872E+09 | 45094383.79 | 76777381.30 | 0.255894E+09 | 0.320748E+09 |
March | 0.175089E+09 | 70226937.41 | 0.104862E+09 | 0.463248E+09 | 0.246368E+09 |
April | 0.204617E+09 | 95545218.97 | 0.109072E+09 | 0.704770E+09 | 0.112973E+09 |
May | 0.200912E+09 | 85204663.52 | 0.115707E+09 | 0.810846E+09 | 42543482.61 |
June | 0.183746E+09 | 72047186.79 | 0.111699E+09 | 0.777787E+09 | 33205716.95 |
July | 0.140129E+09 | 27301148.42 | 0.112828E+09 | 0.575696E+09 | 19125213.44 |
August | 0.128312E+09 | 22488779.19 | 0.105823E+09 | 0.496542E+09 | 38591802.90 |
September | 0.137008E+09 | 40405835.23 | 96602014.12 | 0.456140E+09 | 85021160.96 |
October | 0.147937E+09 | 59327929.40 | 88609262.07 | 0.452624E+09 | 0.224023E+09 |
November | 0.130072E+09 | 56130406.70 | 73941738.39 | 0.318635E+09 | 0.342885E+09 |
December | 0.114910E+09 | 44415944.80 | 70493603.25 | 0.207421E+09 | 0.430422E+09 |
Annual Sum or Average | 0.180299E+10 | 0.664612E+09 | 0.113838E+10 | 0.573129E+10 | 0.230457E+10 |
Minimum of Months | 0.114910E+09 | 22488779.19 | 70493603.25 | 0.207421E+09 | 19125213.44 |
Maximum of Months | 0.204617E+09 | 95545218.97 | 0.115707E+09 | 0.810846E+09 | 0.430422E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118385E+09 | 46423318.77 | 71961440.09 | 0.211685E+09 | 0.408659E+09 |
February | 0.121872E+09 | 45094383.79 | 76777381.30 | 0.255894E+09 | 0.320748E+09 |
March | 0.175089E+09 | 70226937.41 | 0.104862E+09 | 0.463248E+09 | 0.246368E+09 |
April | 0.204617E+09 | 95545218.97 | 0.109072E+09 | 0.704770E+09 | 0.112973E+09 |
May | 0.200912E+09 | 85204663.52 | 0.115707E+09 | 0.810846E+09 | 42543482.61 |
June | 0.183746E+09 | 72047186.79 | 0.111699E+09 | 0.777787E+09 | 33205716.95 |
July | 0.140129E+09 | 27301148.42 | 0.112828E+09 | 0.575696E+09 | 19125213.44 |
August | 0.128312E+09 | 22488779.19 | 0.105823E+09 | 0.496542E+09 | 38591802.90 |
September | 0.137008E+09 | 40405835.23 | 96602014.12 | 0.456140E+09 | 85021160.96 |
October | 0.147937E+09 | 59327929.40 | 88609262.07 | 0.452624E+09 | 0.224023E+09 |
November | 0.130072E+09 | 56130406.70 | 73941738.39 | 0.318635E+09 | 0.342885E+09 |
December | 0.114910E+09 | 44415944.80 | 70493603.25 | 0.207421E+09 | 0.430422E+09 |
Annual Sum or Average | 0.180299E+10 | 0.664612E+09 | 0.113838E+10 | 0.573129E+10 | 0.230457E+10 |
Minimum of Months | 0.114910E+09 | 22488779.19 | 70493603.25 | 0.207421E+09 | 19125213.44 |
Maximum of Months | 0.204617E+09 | 95545218.97 | 0.115707E+09 | 0.810846E+09 | 0.430422E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32775421.19 | 0.00 | 32775421.19 | 23700671.55 | 0.246280E+09 |
February | 35104858.09 | 0.00 | 35104858.09 | 44601504.68 | 0.190809E+09 |
March | 46850198.13 | 8756.21 | 46841441.92 | 0.105365E+09 | 0.146006E+09 |
April | 49446266.00 | 394135.21 | 49052130.79 | 0.193311E+09 | 65436760.56 |
May | 57244900.67 | 2509882.88 | 54735017.79 | 0.283297E+09 | 24572810.51 |
June | 57088983.07 | 2783424.73 | 54305558.34 | 0.293457E+09 | 19528040.66 |
July | 57956094.13 | 1370910.02 | 56585184.11 | 0.259971E+09 | 10931321.69 |
August | 53077308.44 | 425163.61 | 52652144.83 | 0.219439E+09 | 22295135.71 |
September | 45511233.81 | 10588.01 | 45500645.80 | 0.157490E+09 | 49409810.67 |
October | 40732997.44 | 0.00 | 40732997.44 | 0.120073E+09 | 0.130300E+09 |
November | 33388306.95 | 0.00 | 33388306.95 | 56026000.21 | 0.201991E+09 |
December | 31973008.78 | 0.00 | 31973008.78 | 25167058.68 | 0.260994E+09 |
Annual Sum or Average | 0.541150E+09 | 7502860.67 | 0.533647E+09 | 0.178190E+10 | 0.136855E+10 |
Minimum of Months | 31973008.78 | 0.00 | 31973008.78 | 23700671.55 | 10931321.69 |
Maximum of Months | 57956094.13 | 2783424.73 | 56585184.11 | 0.293457E+09 | 0.260994E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32774418.26 | 0.00 | 32774418.26 | 23699517.21 | 0.246278E+09 |
February | 35103811.92 | 0.00 | 35103811.92 | 44600046.71 | 0.190808E+09 |
March | 46848863.71 | 8755.80 | 46840107.92 | 0.105362E+09 | 0.146004E+09 |
April | 49445006.80 | 394116.74 | 49050890.06 | 0.193310E+09 | 65435034.68 |
May | 57243360.56 | 2509765.24 | 54733595.32 | 0.283295E+09 | 24571734.95 |
June | 57087345.08 | 2783294.27 | 54304050.81 | 0.293455E+09 | 19527528.72 |
July | 57954155.25 | 1370845.76 | 56583309.48 | 0.259967E+09 | 10930812.83 |
August | 53075499.00 | 425143.68 | 52650355.32 | 0.219435E+09 | 22294322.01 |
September | 45509773.65 | 10587.52 | 45499186.13 | 0.157487E+09 | 49408517.29 |
October | 40731859.81 | 0.00 | 40731859.81 | 0.120071E+09 | 0.130298E+09 |
November | 33387382.92 | 0.00 | 33387382.92 | 56024992.13 | 0.201989E+09 |
December | 31972034.18 | 0.00 | 31972034.18 | 25165966.29 | 0.260992E+09 |
Annual Sum or Average | 0.541134E+09 | 7502509.01 | 0.533631E+09 | 0.178187E+10 | 0.136854E+10 |
Minimum of Months | 31972034.18 | 0.00 | 31972034.18 | 23699517.21 | 10930812.83 |
Maximum of Months | 57954155.25 | 2783294.27 | 56583309.48 | 0.293455E+09 | 0.260992E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185520E+09 | 99157305.63 | 86363144.24 | 0.212462E+09 | 0.148810E+09 |
February | 0.210662E+09 | 0.117140E+09 | 93522312.41 | 0.249353E+09 | 0.130435E+09 |
March | 0.313766E+09 | 0.187351E+09 | 0.126415E+09 | 0.383550E+09 | 0.138381E+09 |
April | 0.389525E+09 | 0.271813E+09 | 0.117711E+09 | 0.485897E+09 | 0.126029E+09 |
May | 0.426896E+09 | 0.294195E+09 | 0.132701E+09 | 0.528544E+09 | 0.107117E+09 |
June | 0.386709E+09 | 0.245206E+09 | 0.141503E+09 | 0.481713E+09 | 96574954.31 |
July | 0.280752E+09 | 0.100269E+09 | 0.180484E+09 | 0.351280E+09 | 66648591.92 |
August | 0.242808E+09 | 69018187.27 | 0.173790E+09 | 0.308511E+09 | 65640027.20 |
September | 0.240780E+09 | 0.101401E+09 | 0.139379E+09 | 0.295540E+09 | 86231568.45 |
October | 0.279260E+09 | 0.176858E+09 | 0.102402E+09 | 0.346904E+09 | 0.146112E+09 |
November | 0.225058E+09 | 0.147807E+09 | 77251264.25 | 0.272878E+09 | 0.156702E+09 |
December | 0.180125E+09 | 97073916.93 | 83050636.20 | 0.205675E+09 | 0.159187E+09 |
Annual Sum or Average | 0.336186E+10 | 0.190729E+10 | 0.145457E+10 | 0.412231E+10 | 0.142787E+10 |
Minimum of Months | 0.180125E+09 | 69018187.27 | 77251264.25 | 0.205675E+09 | 65640027.20 |
Maximum of Months | 0.426896E+09 | 0.294195E+09 | 0.180484E+09 | 0.528544E+09 | 0.159187E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.50 | 483.79 | 112.87 | 34.66 | 78.21 | 0.00 | 0.00 |
February | 245.93 | 420.41 | 129.78 | 37.28 | 92.49 | 0.00 | 0.00 |
March | 423.37 | 291.77 | 165.72 | 52.45 | 113.28 | 0.00 | 0.00 |
April | 692.85 | 137.55 | 196.04 | 74.03 | 122.01 | 0.00 | 0.00 |
May | 816.67 | 49.78 | 192.77 | 65.50 | 127.27 | 0.00 | 0.00 |
June | 826.45 | 40.56 | 185.83 | 57.74 | 128.09 | 0.00 | 0.00 |
July | 623.98 | 22.42 | 147.91 | 21.41 | 126.50 | 0.00 | 0.00 |
August | 534.59 | 45.42 | 135.45 | 17.11 | 118.34 | 0.00 | 0.00 |
September | 473.44 | 103.69 | 140.83 | 31.19 | 109.65 | 0.00 | 0.00 |
October | 427.51 | 264.45 | 140.88 | 44.30 | 96.58 | 0.00 | 0.00 |
November | 287.37 | 418.71 | 126.13 | 43.31 | 82.82 | 0.00 | 0.00 |
December | 166.92 | 509.54 | 109.68 | 33.17 | 76.51 | 0.00 | 0.00 |
Annual Sum or Average | 474.96 | 231.42 | 148.66 | 42.63 | 106.04 | 0.00 | 0.00 |
Minimum of Months | 166.92 | 22.42 | 109.68 | 17.11 | 76.51 | 0.00 | 0.00 |
Maximum of Months | 826.45 | 509.54 | 196.04 | 74.03 | 128.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 793.23 | 555.59 | 692.65 | 370.21 | 322.44 | 0.00 | 0.00 |
February | 1030.72 | 539.17 | 870.79 | 484.21 | 386.58 | 0.00 | 0.00 |
March | 1432.00 | 516.65 | 1171.47 | 699.49 | 471.98 | 0.00 | 0.00 |
April | 1874.60 | 486.22 | 1502.80 | 1048.66 | 454.13 | 0.00 | 0.00 |
May | 1973.36 | 399.84 | 1593.85 | 1098.40 | 495.45 | 0.00 | 0.00 |
June | 1858.46 | 372.58 | 1491.93 | 946.01 | 545.92 | 0.00 | 0.00 |
July | 1311.53 | 248.83 | 1048.21 | 374.36 | 673.85 | 0.00 | 0.00 |
August | 1151.84 | 245.07 | 906.54 | 257.68 | 648.86 | 0.00 | 0.00 |
September | 1140.20 | 332.68 | 928.94 | 391.21 | 537.73 | 0.00 | 0.00 |
October | 1295.18 | 545.52 | 1042.64 | 660.31 | 382.33 | 0.00 | 0.00 |
November | 1052.77 | 604.56 | 868.28 | 570.24 | 298.04 | 0.00 | 0.00 |
December | 767.89 | 594.33 | 672.51 | 362.43 | 310.08 | 0.00 | 0.00 |
Annual Sum or Average | 1307.17 | 452.76 | 1066.04 | 604.80 | 461.24 | 0.00 | 0.00 |
Minimum of Months | 767.89 | 245.07 | 672.51 | 257.68 | 298.04 | 0.00 | 0.00 |
Maximum of Months | 1973.36 | 604.56 | 1593.85 | 1098.40 | 673.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456675E+09 | 0.129578E+10 | 0.302319E+09 | 92846637.55 | 0.209473E+09 | 0.00 | 0.00 |
February | 0.594942E+09 | 0.101707E+10 | 0.313952E+09 | 90188767.58 | 0.223763E+09 | 0.00 | 0.00 |
March | 0.113396E+10 | 0.781481E+09 | 0.443876E+09 | 0.140471E+09 | 0.303405E+09 | 0.00 | 0.00 |
April | 0.179587E+10 | 0.356532E+09 | 0.508125E+09 | 0.191879E+09 | 0.316246E+09 | 0.00 | 0.00 |
May | 0.218738E+10 | 0.133327E+09 | 0.516311E+09 | 0.175429E+09 | 0.340882E+09 | 0.00 | 0.00 |
June | 0.214216E+10 | 0.105143E+09 | 0.481669E+09 | 0.149661E+09 | 0.332008E+09 | 0.00 | 0.00 |
July | 0.167126E+10 | 60039661.35 | 0.396169E+09 | 57344052.63 | 0.338825E+09 | 0.00 | 0.00 |
August | 0.143184E+10 | 0.121656E+09 | 0.362777E+09 | 45827865.67 | 0.316949E+09 | 0.00 | 0.00 |
September | 0.122715E+10 | 0.268754E+09 | 0.365037E+09 | 80832845.99 | 0.284204E+09 | 0.00 | 0.00 |
October | 0.114504E+10 | 0.708290E+09 | 0.377339E+09 | 0.118656E+09 | 0.258683E+09 | 0.00 | 0.00 |
November | 0.744855E+09 | 0.108528E+10 | 0.326920E+09 | 0.112261E+09 | 0.214659E+09 | 0.00 | 0.00 |
December | 0.447085E+09 | 0.136474E+10 | 0.293764E+09 | 88831889.61 | 0.204932E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149782E+11 | 0.729809E+10 | 0.468826E+10 | 0.134423E+10 | 0.334403E+10 | 0.00 | 0.00 |
Minimum of Months | 0.447085E+09 | 60039661.35 | 0.293764E+09 | 45827865.67 | 0.204932E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218738E+10 | 0.136474E+10 | 0.516311E+09 | 0.191879E+09 | 0.340882E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212460E+10 | 0.148809E+10 | 0.185520E+10 | 0.991573E+09 | 0.863631E+09 | 0.00 | 0.00 |
February | 0.249351E+10 | 0.130435E+10 | 0.210662E+10 | 0.117140E+10 | 0.935223E+09 | 0.00 | 0.00 |
March | 0.383547E+10 | 0.138379E+10 | 0.313766E+10 | 0.187351E+10 | 0.126415E+10 | 0.00 | 0.00 |
April | 0.485896E+10 | 0.126028E+10 | 0.389525E+10 | 0.271813E+10 | 0.117711E+10 | 0.00 | 0.00 |
May | 0.528544E+10 | 0.107094E+10 | 0.426896E+10 | 0.294195E+10 | 0.132701E+10 | 0.00 | 0.00 |
June | 0.481713E+10 | 0.965737E+09 | 0.386709E+10 | 0.245206E+10 | 0.141503E+10 | 0.00 | 0.00 |
July | 0.351280E+10 | 0.666457E+09 | 0.280752E+10 | 0.100269E+10 | 0.180484E+10 | 0.00 | 0.00 |
August | 0.308510E+10 | 0.656386E+09 | 0.242808E+10 | 0.690182E+09 | 0.173790E+10 | 0.00 | 0.00 |
September | 0.295539E+10 | 0.862305E+09 | 0.240780E+10 | 0.101401E+10 | 0.139379E+10 | 0.00 | 0.00 |
October | 0.346902E+10 | 0.146111E+10 | 0.279260E+10 | 0.176858E+10 | 0.102402E+10 | 0.00 | 0.00 |
November | 0.272877E+10 | 0.156702E+10 | 0.225058E+10 | 0.147807E+10 | 0.772513E+09 | 0.00 | 0.00 |
December | 0.205672E+10 | 0.159186E+10 | 0.180125E+10 | 0.970739E+09 | 0.830506E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.412229E+11 | 0.142783E+11 | 0.336186E+11 | 0.190729E+11 | 0.145457E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205672E+10 | 0.656386E+09 | 0.180125E+10 | 0.690182E+09 | 0.772513E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528544E+10 | 0.159186E+10 | 0.426896E+10 | 0.294195E+10 | 0.180484E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.820550E+09 | -679983205.7 | 0.00 | 0.00 | 744.00 | 0.00 | -140567029.7 | 58.99 | 0.00 | 0.00 |
February | 0.733043E+09 | -611536371.6 | 0.00 | 0.00 | 672.00 | 0.00 | -121506460.8 | 58.99 | 0.00 | 0.00 |
March | 0.795163E+09 | -666876917.5 | 0.00 | 0.00 | 744.00 | 0.00 | -128285967.9 | 58.99 | 0.00 | 0.00 |
April | 0.675434E+09 | -556025095.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119408470.5 | 58.99 | 0.00 | 0.00 |
May | 0.632945E+09 | -510929977.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122014682.9 | 58.99 | 0.00 | 0.00 |
June | 0.574704E+09 | -456448711.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118255574.7 | 58.99 | 0.00 | 0.00 |
July | 0.542341E+09 | -420684279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121657135.4 | 58.99 | 0.00 | 0.00 |
August | 0.590340E+09 | -467784985.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122555245.7 | 58.99 | 0.00 | 0.00 |
September | 0.600172E+09 | -481459152.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118712670.8 | 58.99 | 0.00 | 0.00 |
October | 0.670918E+09 | -546618474.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124299618.7 | 58.99 | 0.00 | 0.00 |
November | 0.712195E+09 | -586877678.4 | 0.00 | 0.00 | 720.00 | 0.00 | -125317298.0 | 58.99 | 0.00 | 0.00 |
December | 0.796766E+09 | -659811594.7 | 0.00 | 0.00 | 744.00 | 0.00 | -136953958.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.814457E+10 | -.664504E+10 | 8760.00 | -.149953E+10 | 58.99 | |||||
Minimum of Months | 0.542341E+09 | -679983205.7 | 0.00 | 0.00 | 672.00 | 0.00 | -140567029.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.820550E+09 | -420684279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118255574.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | ||||||||||
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542163E+09 | 31441.46 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90797039.95 | 6417.38 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 180049.80 | 484.62 | 27-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136616E+09 | 11246.02 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769756E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542163E+09 | 31441.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.363195E+09 | 27123.18 | 01-JAN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363195E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.363195E+09 | 27123.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255769E+10 | 49144.85 | 03-JAN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22356114.56 | 6130.48 | 23-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258004E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255769E+10 | 49144.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176041E+10 | 0.164257E+10 | 5806.93 | 14-JAN-15:40 | 5146.42 | 0.00 |
February | 0.00 | 0.00 | 0.368116E+10 | 0.334689E+10 | 22484.52 | 25-FEB-06:03 | 18661.92 | 0.00 |
March | 0.00 | 0.00 | 0.868449E+10 | 0.789891E+10 | 29350.84 | 11-MAR-06:01 | 22610.22 | 0.00 |
April | 0.00 | 0.00 | 0.128899E+11 | 0.119547E+11 | 29481.61 | 03-APR-05:01 | 23734.20 | 0.00 |
May | 0.00 | 0.00 | 0.182852E+11 | 0.155910E+11 | 31997.80 | 24-MAY-05:01 | 19756.44 | 0.00 |
June | 0.00 | 0.00 | 0.203162E+11 | 0.159799E+11 | 33060.86 | 26-JUN-05:01 | 18510.56 | 0.00 |
July | 0.00 | 0.00 | 0.208835E+11 | 0.144191E+11 | 33532.83 | 26-JUL-05:01 | 17576.78 | 0.00 |
August | 0.00 | 0.00 | 0.216243E+11 | 0.143999E+11 | 33331.16 | 11-AUG-05:01 | 17971.24 | 0.00 |
September | 0.00 | 0.00 | 0.174155E+11 | 0.123328E+11 | 33658.78 | 11-SEP-05:01 | 17511.52 | 0.00 |
October | 0.00 | 0.00 | 0.122326E+11 | 0.104206E+11 | 31021.10 | 12-OCT-05:01 | 20310.16 | 0.00 |
November | 0.00 | 0.00 | 0.668540E+10 | 0.612732E+10 | 27895.39 | 09-NOV-06:01 | 22754.56 | 0.00 |
December | 0.00 | 0.00 | 0.283115E+10 | 0.264962E+10 | 6964.97 | 02-DEC-14:55 | 6964.97 | 0.00 |
Annual Sum or Average | 0.147290E+12 | 0.116763E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.176041E+10 | 0.164257E+10 | 5806.93 | 5146.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216243E+11 | 0.159799E+11 | 33658.78 | 23734.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.298909E+09 | 0.279657E+09 | 6407.09 | 26-JAN-13:52 | 6016.02 | 0.00 |
February | 0.00 | 0.00 | 0.563855E+10 | 0.526581E+10 | 27582.71 | 20-FEB-14:55 | 27582.71 | 0.00 |
March | 0.00 | 0.00 | 0.259411E+11 | 0.243244E+11 | 108558.25 | 12-MAR-14:12 | 102623.18 | 0.00 |
April | 0.00 | 0.00 | 0.586833E+11 | 0.561802E+11 | 114593.30 | 16-APR-20:23 | 95460.02 | 0.00 |
May | 0.00 | 0.00 | 0.894711E+11 | 0.804460E+11 | 121717.80 | 19-MAY-05:01 | 84633.52 | 0.00 |
June | 0.00 | 0.00 | 0.945592E+11 | 0.803925E+11 | 126859.50 | 24-JUN-05:01 | 80669.14 | 0.00 |
July | 0.00 | 0.00 | 0.943138E+11 | 0.695516E+11 | 129290.14 | 21-JUL-05:01 | 74914.48 | 0.00 |
August | 0.00 | 0.00 | 0.841294E+11 | 0.607331E+11 | 128565.11 | 31-AUG-05:01 | 75425.58 | 0.00 |
September | 0.00 | 0.00 | 0.632300E+11 | 0.482816E+11 | 121462.24 | 03-SEP-14:23 | 87198.37 | 0.00 |
October | 0.00 | 0.00 | 0.408131E+11 | 0.368690E+11 | 112206.39 | 03-OCT-17:42 | 95050.96 | 0.00 |
November | 0.00 | 0.00 | 0.155059E+11 | 0.146471E+11 | 73440.30 | 11-NOV-12:13 | 68921.40 | 0.00 |
December | 0.00 | 0.00 | 0.193132E+10 | 0.185498E+10 | 18547.72 | 18-DEC-14:15 | 17055.95 | 0.00 |
Annual Sum or Average | 0.574516E+12 | 0.478826E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.298909E+09 | 0.279657E+09 | 6407.09 | 6016.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.945592E+11 | 0.804460E+11 | 129290.14 | 102623.18 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 34306620.52 | 0.00 | 357.36 | 01-JAN-00:05 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 1500914.65 | 0.00 | 357.36 | 23-DEC-06:00 | 0.08 |
Annual Sum or Average | 35807535.17 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34306620.52 | 0.00 | 357.36 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148668E+10 | 0.36 | 1494.33 | 02-JAN-10:20 | 0.95 |
February | 0.136209E+10 | 0.36 | 1494.33 | 01-FEB-11:50 | 0.95 |
March | 0.161360E+10 | 0.40 | 1494.33 | 01-MAR-09:07 | 0.95 |
April | 0.153031E+10 | 0.42 | 1494.33 | 04-APR-07:20 | 0.95 |
May | 0.165334E+10 | 0.50 | 1494.33 | 02-MAY-12:10 | 0.95 |
June | 0.166477E+10 | 0.52 | 1494.33 | 05-JUN-15:10 | 0.95 |
July | 0.161647E+10 | 0.49 | 1494.33 | 01-JUL-10:15 | 0.95 |
August | 0.170285E+10 | 0.46 | 1494.33 | 01-AUG-13:00 | 0.95 |
September | 0.155215E+10 | 0.42 | 1494.33 | 06-SEP-15:40 | 0.95 |
October | 0.152330E+10 | 0.40 | 1494.33 | 05-OCT-06:40 | 0.95 |
November | 0.142804E+10 | 0.36 | 1494.33 | 01-NOV-09:20 | 0.95 |
December | 0.147992E+10 | 0.35 | 1494.33 | 01-DEC-11:08 | 0.96 |
Annual Sum or Average | 0.186135E+11 | 0.42 | |||
Minimum of Months | 0.136209E+10 | 0.35 | 1494.33 | 0.95 | |
Maximum of Months | 0.170285E+10 | 0.52 | 1494.33 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.873290E+10 | 0.61 | 8792.81 | 12-JAN-13:18 | 1.57 |
February | 0.801904E+10 | 0.60 | 8792.81 | 03-FEB-16:30 | 1.58 |
March | 0.967786E+10 | 0.75 | 8792.81 | 04-MAR-09:00 | 1.57 |
April | 0.103590E+11 | 1.15 | 8792.81 | 10-APR-10:10 | 1.57 |
May | 0.121088E+11 | 1.33 | 8792.81 | 01-MAY-06:20 | 1.57 |
June | 0.121956E+11 | 1.34 | 8792.81 | 01-JUN-06:10 | 1.56 |
July | 0.119993E+11 | 1.33 | 8792.81 | 01-JUL-07:00 | 1.56 |
August | 0.117929E+11 | 1.32 | 8792.81 | 16-AUG-08:47 | 1.56 |
September | 0.103370E+11 | 1.22 | 8792.81 | 02-SEP-06:20 | 1.56 |
October | 0.949906E+10 | 0.90 | 8792.81 | 06-OCT-09:13 | 1.56 |
November | 0.845183E+10 | 0.63 | 8792.81 | 03-NOV-08:37 | 1.57 |
December | 0.870488E+10 | 0.58 | 8792.81 | 01-DEC-13:50 | 1.58 |
Annual Sum or Average | 0.121878E+12 | 0.98 | |||
Minimum of Months | 0.801904E+10 | 0.58 | 8792.81 | 1.56 | |
Maximum of Months | 0.121956E+11 | 1.34 | 8792.81 | 1.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 1.44 |
February | 1.17 | 3.10 |
March | 3.07 | 0.00 |
April | 2.56 | 0.01 |
May | 3.41 | 0.00 |
June | 3.74 | 0.02 |
July | 4.59 | 0.03 |
August | 3.19 | 0.03 |
September | 3.16 | 0.01 |
October | 3.11 | 0.01 |
November | 1.51 | 1.25 |
December | 0.60 | 4.76 |
Annual Sum or Average | 30.51 | 0.31 |
Minimum of Months | 0.42 | 0.00 |
Maximum of Months | 4.59 | 4.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 1.36 | 0.00 |
February | 0.56 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.08 | 0.00 |
December | 1.42 | 0.00 |
Annual Sum or Average | 3.42 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.42 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 17.32 | 0.00 |
February | 20.37 | 0.00 |
March | 11.34 | 0.00 |
April | 4.92 | 0.00 |
May | 3.28 | 0.00 |
June | 1.57 | 0.00 |
July | 0.78 | 0.00 |
August | 3.14 | 0.00 |
September | 3.12 | 0.00 |
October | 5.87 | 0.00 |
November | 16.39 | 0.00 |
December | 19.65 | 0.00 |
Annual Sum or Average | 107.76 | |
Minimum of Months | 0.78 | 0.00 |
Maximum of Months | 20.37 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196493E+10 | 0.799840E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.235695E+10 | 0.137819E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.403245E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.542135E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.739020E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.788663E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.758086E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.768937E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.638370E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.496509E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.326059E+10 | 280406.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.224590E+10 | 0.207914E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.611780E+11 | 0.114585E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.196493E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.788663E+10 | 0.799840E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.882216E+10 | 0.558485E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.969926E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177329E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.301484E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.433134E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.447831E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.424603E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.382166E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.302340E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224308E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131839E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.927845E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.310303E+12 | 0.558485E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.882216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.447831E+11 | 0.558485E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148668E+10 | 0.176041E+10 | 0.542163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136209E+10 | 0.368116E+10 | 90797039.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161360E+10 | 0.868449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153031E+10 | 0.128899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165334E+10 | 0.182852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166477E+10 | 0.203162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161647E+10 | 0.208835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170285E+10 | 0.216243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155215E+10 | 0.174155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152330E+10 | 0.122326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142804E+10 | 0.668540E+10 | 180049.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147992E+10 | 0.283115E+10 | 0.136616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186135E+11 | 0.147290E+12 | 0.769756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136209E+10 | 0.176041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170285E+10 | 0.216243E+11 | 0.542163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.873290E+10 | 0.298909E+09 | 0.363195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801904E+10 | 0.563855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.967786E+10 | 0.259411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103590E+11 | 0.586833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121088E+11 | 0.894711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121956E+11 | 0.945592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119993E+11 | 0.943138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117929E+11 | 0.841294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103370E+11 | 0.632300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949906E+10 | 0.408131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.845183E+10 | 0.155059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870488E+10 | 0.193132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121878E+12 | 0.574516E+12 | 0.363195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.801904E+10 | 0.298909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121956E+11 | 0.945592E+11 | 0.363195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.148668E+10 | 0.00 | 0.00 | 0.00 | 0.478255E+09 | 0.00 | 0.799840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136209E+10 | 0.00 | 0.00 | 0.00 | 0.994867E+09 | 0.00 | 0.137819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161360E+10 | 0.00 | 0.00 | 0.00 | 0.241885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153031E+10 | 0.00 | 0.00 | 0.00 | 0.389104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165334E+10 | 0.00 | 0.00 | 0.00 | 0.573686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166477E+10 | 0.00 | 0.00 | 0.00 | 0.622186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161647E+10 | 0.00 | 0.00 | 0.00 | 0.596439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170285E+10 | 0.00 | 0.00 | 0.00 | 0.598652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155215E+10 | 0.00 | 0.00 | 0.00 | 0.483154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152330E+10 | 0.00 | 0.00 | 0.00 | 0.344179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142804E+10 | 0.00 | 0.00 | 0.00 | 0.183255E+10 | 0.00 | 280406.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147992E+10 | 0.00 | 0.00 | 0.00 | 0.765974E+09 | 0.00 | 0.207914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186135E+11 | 0.00 | 0.00 | 0.00 | 0.425645E+11 | 0.00 | 0.114585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.136209E+10 | 0.00 | 0.00 | 0.00 | 0.478255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170285E+10 | 0.00 | 0.00 | 0.00 | 0.622186E+10 | 0.00 | 0.799840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.873290E+10 | 0.00 | 0.00 | 0.00 | 89260308.99 | 0.00 | 0.558485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801904E+10 | 0.00 | 0.00 | 0.00 | 0.168022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.967786E+10 | 0.00 | 0.00 | 0.00 | 0.805506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103590E+11 | 0.00 | 0.00 | 0.00 | 0.197894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121088E+11 | 0.00 | 0.00 | 0.00 | 0.312046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121956E+11 | 0.00 | 0.00 | 0.00 | 0.325875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119993E+11 | 0.00 | 0.00 | 0.00 | 0.304611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117929E+11 | 0.00 | 0.00 | 0.00 | 0.264237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103370E+11 | 0.00 | 0.00 | 0.00 | 0.198971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949906E+10 | 0.00 | 0.00 | 0.00 | 0.129317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.845183E+10 | 0.00 | 0.00 | 0.00 | 0.473204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870488E+10 | 0.00 | 0.00 | 0.00 | 0.573569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121878E+12 | 0.00 | 0.00 | 0.00 | 0.188425E+12 | 0.00 | 0.558485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.801904E+10 | 0.00 | 0.00 | 0.00 | 89260308.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121956E+11 | 0.00 | 0.00 | 0.00 | 0.325875E+11 | 0.00 | 0.558485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.436935E+09 | 0.00 | 0.00 | 3430962.66 | 0.00 | 0.206472E+09 | 0.413265E+09 | 0.00 | 0.16 |
February | 0.190657E+09 | 66071950.43 | 0.00 | 6712499.61 | 0.00 | 43334270.62 | 0.303330E+09 | 0.00 | 0.16 |
March | 37183111.56 | 0.546770E+09 | 0.00 | 6500558.44 | 1573.87 | 0.00 | 0.131966E+09 | 0.00 | 0.18 |
April | 0.00 | 0.146166E+10 | 0.00 | 1018542.84 | 0.00 | 0.00 | 3103118.78 | 0.00 | 0.17 |
May | 0.00 | 0.307530E+10 | 0.00 | 112498.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.409621E+10 | 0.00 | 58155.64 | 0.00 | 0.00 | 33868.73 | 0.00 | 0.19 |
July | 0.00 | 0.481679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.508559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.374752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.144950E+10 | 0.00 | 2504786.32 | 0.00 | 0.00 | 19887323.93 | 0.00 | 0.17 |
November | 74231310.83 | 0.323884E+09 | 0.00 | 6836894.82 | 0.00 | 762790.58 | 0.183139E+09 | 0.00 | 0.16 |
December | 0.268272E+09 | 3168708.40 | 0.00 | 6444033.44 | 0.00 | 97054421.64 | 0.513211E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.100728E+10 | 0.246725E+11 | 0.00 | 33618932.20 | 1573.87 | 0.347623E+09 | 0.156794E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.436935E+09 | 0.508559E+10 | 0.00 | 6836894.82 | 1573.87 | 0.206472E+09 | 0.513211E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46462827.23 | 0.00 | 0.00 | 0.16 |
February | 0.163935E+10 | 31740543.44 | 0.00 | 6355855.98 | 569800.76 | 0.00 | 0.400077E+09 | 0.00 | 0.17 |
March | 0.526106E+09 | 0.106766E+10 | 0.00 | 15050606.36 | 2802762.48 | 0.00 | 0.519954E+09 | 0.00 | 0.18 |
April | 14963078.45 | 0.394011E+10 | 0.00 | 3812764.59 | 3098849.40 | 0.00 | 57345882.34 | 0.00 | 0.20 |
May | 0.00 | 0.957683E+10 | 0.00 | 72425.51 | 0.00 | 0.00 | 29984.48 | 0.00 | 0.23 |
June | 0.00 | 0.135780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.157343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.157957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.108893E+11 | 0.00 | 12004.24 | 0.00 | 0.00 | 11198.44 | 0.00 | 0.20 |
October | 97987878.31 | 0.356788E+10 | 0.00 | 1872059.42 | 6773671.12 | 0.00 | 65478836.84 | 0.00 | 0.18 |
November | 0.722202E+09 | 0.495788E+09 | 0.00 | 9501779.96 | 365092.90 | 0.00 | 0.402544E+09 | 0.00 | 0.16 |
December | 0.270074E+10 | 0.00 | 0.00 | 1563265.59 | 0.00 | 0.00 | 0.213272E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.876931E+10 | 0.746773E+11 | 0.00 | 38240761.65 | 13610176.65 | 46462827.23 | 0.165871E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.306797E+10 | 0.157957E+11 | 0.00 | 15050606.36 | 6773671.12 | 46462827.23 | 0.519954E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |