Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2020-06-03 19:10:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1158.12 | 239.52 | 239.52 |
Net Site Energy | 1158.12 | 239.52 | 239.52 |
Total Source Energy | 3552.80 | 734.79 | 734.79 |
Net Source Energy | 3552.80 | 734.79 | 734.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 198.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.41 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1102.93 | 55.19 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 198.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 26.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 109.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.41 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 74.04 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 228.11 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 74.04 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 228.11 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1102.928 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1102.928 | 100.00 |
Total On-Site and Utility Electric Sources | 1102.928 | 100.00 |
Total Electricity End Uses | 1102.928 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 26.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 9.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-SEP-14:00 | 01-JAN-00:10 | - | - | - | 19-JAN-12:39 |
Heating | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 24655.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10444.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1687.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 82520.52 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 24655.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8138.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1687.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 59.82 | 0.00 | 0.00 | 0.00 |
Cooling | 629.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 430.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3492.97 | 59.82 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 130.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 722.42 | 12.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 130.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 722.42 | 12.37 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.20 |
ZONE2 FINE STORAGE DIRECT AIR | 3.55 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.814033 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.814033 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 33800.34 |
PSZ-OFFICE HEATING COIL | 28296.41 |
PSZ-FINE STORAGE HEATING COIL | 104564.29 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.000000 | 1.20 |
PSZ-FINE STORAGE | 3.55 | 3.55 | 3.55 | 3.55 | 3.55 | 3.55 | 1.00 | 1.000000 | 3.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.20 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.55 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 1.20 | 23188.56 | 28296.41 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.55 | 3.55 | 3.55 | 3.55 | 82034.91 | 104564.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.20 | 0.600885 | 1.20 | 22630.05 | 23188.56 | 11594.28 | 23188.56 | 0.746413 | 0.746410 | 0.746410 | 0.746410 |
PSZ-FINE STORAGE COOLING COIL | 3.55 | 1.77 | 3.55 | 78424.39 | 82034.91 | 41017.46 | 82034.91 | 0.694047 | 0.694050 | 0.694050 | 0.694050 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.20 | 1370.15 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.55 | 6768.58 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.20 | 24.80 | 23.70 | 22.50 | 22.80 | 23.20 | 23.80 | 25.20 | 25.90 | 26.90 | 27.10 | 26.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 | 21.32 | -157.93 | -10.00 | 2.00 | 101301 | 1.2040 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.92 | 4.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 28 | 1 | VerySmooth | 5.835 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12171.08522 | 14605.30227 | 1.00147 | 1.20177 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.20600 | 1.43490E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5014.52822 | 6017.43386 | 0.14042 | 0.16851 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | 16.20000 | 1.15180E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 46060.22363 | 55272.26836 | 2.95474 | 3.54568 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20000 | 1.43490E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 5135.26966 | 6162.32359 | 0.12145 | 0.35393 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 06:10:00 | 16.20000 | 1.15180E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20000 | 1.43490E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20000 | 1.15180E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18364.40 | 1.20177 | 1.20177 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 4571.13 | 0.16851 | 0.16851 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 65403.33 | 3.54568 | 3.54568 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10191.33 | 0.35393 | 0.35393 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20177 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.54568 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 33800.34408 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20177 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20177 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20177 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20177 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20177 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.20177 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.54568 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.54568 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.54568 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.54568 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.54568 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.54568 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.20177 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.54568 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20177 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20177 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20177 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20177 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20177 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20177 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60089 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20177 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22630.05179 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23188.56000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11594.28000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23188.56000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74641 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74641 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74641 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74641 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23188.56000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28296.40612 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20177 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1370.14525 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28296.40612 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.54568 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.54568 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.54568 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.54568 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.54568 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.54568 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.77284 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.54568 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 78424.39338 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 82034.91000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 41017.45500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 82034.91000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69405 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69405 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69405 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69405 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 82034.91000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 104564.29097 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.54568 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6768.58371 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 104564.29097 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22255.5 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 79279.9 | 12.61 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.1475899218E-002 | 2.9938975516E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1948589831 | 0.3383930914 | Pass | Pass | 0.2404702704 | 0.7630350588 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1675124415 | 0.1866644424 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.835 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.835 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.798 | 0.449 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 5.835 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.793 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.86 | 83.86 | 123.69 | |
Exterior Lighting Total | 7857.24 | 123.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23188.56 | 17308.17 | 5880.39 | 0.75 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 82034.91 | 56936.33 | 25098.58 | 0.69 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22255.5 | 10.32 | ||||
PSZ-FINE STORAGE COOLING COIL | 79279.9 | 12.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 33800.34 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28296.41 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 104564.29 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.20 | 1370.15 | 1140.11 | 1.00 | 1.32 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.55 | 6768.58 | 1908.96 | 1.00 | 1.15 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12171.09 | 14605.30 | 61.66 | 1.001 | 1.202 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00841 | 31.21 | 0.01435 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 46060.22 | 55272.27 | 39.67 | 2.955 | 3.546 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00872 | 32.20 | 0.01435 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 32.20 | 0.01435 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5014.53 | 6017.43 | 25.40 | 0.140 | 0.169 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | 21.10 | 21.10 | 0.00917 | 16.20 | 0.01152 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 5135.27 | 6162.32 | 4.42 | 0.121 | 0.354 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 06:10:00 | 15.56 | 15.56 | 0.01030 | 16.20 | 0.01152 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 0.00 | 10.00 | 0.01600 | 16.20 | 0.01152 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.20 | 1.20 | 0.17 | 0.17 | 1.2018 | 1.2018 | 1.2018 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.55 | 3.55 | 0.35 | 0.35 | 3.5457 | 3.5457 | 3.5457 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 33800.344 | 33800.344 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 33800.34 | 33800.34 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 43.33 | 27.11 | 0.01600000 | 16.20 | 0.01151798 | 16.20 | 0.0000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23188.560 | 0.000 | 1.201770 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23188.56 | 19636.88 | 1.201770 | 24.63 | 17.02 | 0.00900916 | 12.00 | 11.25 | 0.00800000 | 31.21 | 0.01434903 | 23.03 | 10.0132 | 23.90 | 0.00841497 | 45.5768 | 12171.09 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28296.406 | 28296.406 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | 28296.41 | 28296.41 | 1.201766 | 17.58 | 16.11 | 0.01084773 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 10.0132 | 21.10 | 0.00917337 | 58.8156 | 5014.53 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 82034.910 | 0.000 | 3.545680 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 82034.91 | 68735.64 | 3.545680 | 27.25 | 18.13 | 0.00927976 | 12.00 | 11.25 | 0.00800000 | 32.20 | 0.01434902 | 23.30 | 9.9819 | 26.70 | 0.00871764 | 39.9567 | 45116.24 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 104564.291 | 104564.291 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 104564.29 | 103607.01 | 3.545684 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 9.9819 | 15.56 | 0.01029976 | 93.3359 | 4995.14 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33800.344 | 33800.344 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2040 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.814033 | 0.98011478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 33800.34 | 33800.34 | 1.0000 | 0.98011478 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 50360.9 | 43.33 | 27.11 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33800.34 | 16.20 | 0.01151798 | 16.20 | 0.00000000 | 0.0000 | 10.00 | 0.01600000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23188.560 | 0.000 | 1.201770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5876 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23188.56 | 19636.88 | 1.0000 | 1.44695895 | 1.201770 | 24.63 | 17.02 | 0.00900916 | 47693.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23188.56 | 31.21 | 0.01434903 | 23.03 | 0.12033533 | 10.0132 | 23.90 | 0.00841497 | 23.90 | 0.00841497 | 45.5768 | 12171.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28296.406 | 28296.406 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.201766 | 1.44695408 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:00:00 | 28296.41 | 28296.41 | 1.0000 | 1.44695408 | 1.201766 | 17.58 | 16.11 | 0.01084773 | 45147.4 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28296.41 | 16.20 | 0.01151798 | 16.20 | 0.12033533 | 10.0132 | 21.02 | 0.00917337 | 21.10 | 0.00917337 | 58.8156 | 5014.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 82034.910 | 0.000 | 3.545680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0906 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 82034.91 | 68735.64 | 1.0000 | 4.26908094 | 3.545680 | 27.25 | 18.13 | 0.00927976 | 51056.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82034.91 | 32.20 | 0.01434902 | 23.30 | 0.35392745 | 9.9819 | 26.70 | 0.00871764 | 26.70 | 0.00871764 | 39.9567 | 45116.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 104564.291 | 104564.291 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.545684 | 4.26908539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 104564.29 | 103607.01 | 1.0000 | 4.26908539 | 3.545684 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 104564.29 | 16.20 | 0.01151798 | 16.20 | 0.35392745 | 9.9819 | 15.56 | 0.01033501 | 15.56 | 0.01029976 | 93.3359 | 4995.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3473.17 | 18.17 | 9.33 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3473.17 | 18.17 | 9.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 580.17 | 0.00 | 26.33 |
ZONE2 FINE STORAGE | 0.00 | 212.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 728.17 | 0.00 | 26.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.407 | 0.401 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
Electricity:Building | 647.80 | 4992.32 | 01-JAN-00:10 | 48037.94 | 02-JAN-10:00 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 448.20 | 2759.73 | 01-JAN-00:10 | 33963.13 | 02-JAN-10:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 23.41 | 483.00 | 09-JAN-00:10 | 1732.55 | 17-JAN-12:30 |
WaterSystems:Electricity | 23.41 | 483.00 | 09-JAN-00:10 | 1732.55 | 17-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 23.41 | 483.00 | 09-JAN-00:10 | 1732.55 | 17-JAN-12:30 |
Fans:Electricity | 135.93 | 0.00 | 01-JAN-00:10 | 10444.02 | 06-MAR-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 26.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-JAN-10:00 |
Ventilation (simple):Fans:Electricity | 26.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-JAN-10:00 |
ElectricityPurchased:Facility | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
ElectricityPurchased:Plant | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
Cogeneration:ElectricityPurchased | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
ElectricityNet:Plant | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
Cogeneration:ElectricityNet | 1102.93 | 5475.32 | 01-JAN-07:20 | 82520.52 | 05-SEP-15:00 |
Electricity:HVAC | 308.03 | 0.00 | 01-JAN-00:10 | 34771.50 | 05-SEP-15:40 |
General:Fans:Electricity | 109.37 | 0.00 | 01-JAN-00:10 | 8138.73 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 198.66 | 0.00 | 01-JAN-00:10 | 26632.77 | 05-SEP-15:40 |
ExteriorLights:Electricity | 123.69 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.69 | 0.00 | 01-JAN-07:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 55.19 | 1750.00 | 09-JAN-00:10 | 1750.00 | 01-JAN-00:10 |
Gas:HVAC | 55.19 | 1750.00 | 09-JAN-00:10 | 1750.00 | 01-JAN-00:10 |
Heating:Gas | 55.19 | 1750.00 | 09-JAN-00:10 | 1750.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JAN-12:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1094.30 | 0.00 | 01-JAN-00:10 | 150265.61 | 05-SEP-15:30 |
EnergyTransfer:Building | 406.64 | 0.00 | 01-JAN-00:10 | 58663.90 | 05-SEP-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 114.36 | 0.00 | 01-JAN-00:10 | 14530.16 | 05-SEP-00:10 |
Heating:EnergyTransfer | 2.03 | 0.00 | 01-JAN-00:10 | 5346.42 | 11-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.02 | 0.00 | 01-JAN-00:10 | 842.99 | 28-DEC-07:10 |
Cooling:EnergyTransfer | 404.61 | 0.00 | 01-JAN-00:10 | 58663.90 | 05-SEP-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 114.34 | 0.00 | 01-JAN-00:10 | 14530.16 | 05-SEP-00:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 292.28 | 0.00 | 01-JAN-00:10 | 47174.69 | 05-SEP-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.01 | 0.00 | 01-JAN-00:10 | 5119.93 | 13-FEB-07:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 290.28 | 0.00 | 01-JAN-00:10 | 47174.69 | 05-SEP-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 687.66 | 0.00 | 01-JAN-00:10 | 92668.95 | 05-SEP-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 687.66 | 0.00 | 01-JAN-00:10 | 92668.95 | 05-SEP-15:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.023 | -114.335 | 0.000 | 0.000 | 3.577 | 30.994 | 31.946 | 13.284 | 0.000 | 5.446 | 35.652 | 0.000 | -4.742 | 0.000 | -1.845 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.007 | -290.270 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 11.834 | 175.354 | 0.000 | 0.000 | 0.000 | -35.582 | 0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 45.411 | 0.000 | 0.001 | 2059.493 | 0.000 | -12.741 | 0.000 | -2513.810 | 0.000 |
Total Facility | 0.000 | 0.000 | 2.030 | -404.605 | 0.000 | 0.000 | 3.577 | 481.960 | 139.282 | 58.695 | 0.000 | 17.281 | 2270.498 | 0.000 | -17.483 | 0.000 | -2551.236 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-DEC-00:01 | 0.00 | 0.00 | 0.00 | -19693.25 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 0.00 | 0.00 | 0.00 | 19492.12 | 0.00 | -640.73 | 0.00 | -190.84 | 0.00 |
ZONE2 FINE STORAGE | 26-MAR-13:32 | 0.00 | 0.00 | 0.00 | -66832.04 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 65997.89 | 0.00 | -0.00 | 0.00 | -365.73 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-MAY-17:06 | 0.00 | 0.00 | 0.00 | -81198.67 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 2965.75 | 0.00 | 234.20 | 251583.65 | 0.00 | 0.00 | 0.00 | -180627.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 28-DEC-07:05 | 0.00 | 0.00 | 1685.71 | 0.00 | 0.00 | 0.00 | 74.79 | 1070.90 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -189.40 | 0.00 | -420.18 | -3178.07 |
ZONE2 FINE STORAGE | 17-NOV-07:23 | 0.00 | 0.00 | 5482.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4312.97 | -8368.90 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-07:05 | 0.00 | 0.00 | 6374.78 | 0.00 | 0.00 | 0.00 | 74.86 | 24828.58 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -861.22 | 0.00 | -6482.76 | -26940.52 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2018 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.2018 | 0.1001 | 1.0000 | 0.1203 | 0.1001 | ||
PSZ-FINE STORAGE | 3.5457 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.5457 | 0.0998 | 1.0000 | 0.3539 | 0.0998 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2018 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.2018 | 1.0000 | 1.0000 | 0.1203 | 0.1001 | ||
PSZ-FINE STORAGE | 3.5457 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.5457 | 1.0000 | 1.0000 | 0.3539 | 0.0998 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2018 | 1.2018 | 1.2018 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.5457 | 3.5457 | 3.5457 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2018 | 1.2018 | 1.2018 | 1.2018 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.5457 | 3.5457 | 3.5457 | 3.5457 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2018 | 1.2018 | 1.2018 | 0.1203 | 0.7141 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.5457 | 3.5457 | 3.5457 | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2018 | 1.2018 | 1.2018 | 1.2018 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.5457 | 3.5457 | 3.5457 | 3.5457 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 26.33 |
Number of hours not met | 26.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 55.19 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 198.66 | 26632.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.69 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 26.56 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 109.37 | 8138.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.41 | 1732.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1102.93 |
Natural Gas | 0.00 | 55.19 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1158.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 41.09 |
Fans (All) | 28.11 |
Service Water Heating | 4.84 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 228.11 |
Subtotal | 228.11 |
Natural Gas [MJ/m2] | |
Space Heating | 11.41 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.41 |
Subtotal | 11.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 41.62 |
Space Heating | 4.77 |
Space Cooling | 17.15 |
Fans (All) | 11.74 |
Service Water Heating | 2.02 |
Receptacle Equipment | 12.03 |
Miscellaneous | 10.68 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.690112E+10 | 18991.31 | 23-JAN-00:01 | 21.70 | 16.59 | 0.248925E+09 | 301.60 | 20-JAN-13:00 | 25.00 | 16.56 |
February | 0.710664E+10 | 18675.40 | 13-FEB-00:01 | 22.20 | 18.60 | 0.228997E+09 | 301.61 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.885064E+10 | 19522.69 | 27-MAR-00:01 | 18.80 | 16.37 | 0.268838E+09 | 301.59 | 11-MAR-08:09 | 22.25 | 19.99 |
April | 0.869478E+10 | 19519.53 | 03-APR-00:01 | 21.70 | 17.10 | 0.248933E+09 | 301.61 | 29-APR-15:39 | 26.47 | 18.00 |
May | 0.104054E+11 | 19373.66 | 22-MAY-00:01 | 20.60 | 18.12 | 0.258903E+09 | 301.58 | 13-MAY-07:10 | 23.68 | 20.85 |
June | 0.108236E+11 | 19006.76 | 05-JUN-00:01 | 24.18 | 20.13 | 0.258911E+09 | 301.58 | 24-JUN-07:10 | 25.52 | 21.11 |
July | 0.113704E+11 | 18421.62 | 31-JUL-00:01 | 24.90 | 20.06 | 0.248979E+09 | 301.59 | 22-JUL-09:09 | 27.52 | 24.21 |
August | 0.121125E+11 | 17958.65 | 14-AUG-00:01 | 25.00 | 20.86 | 0.268885E+09 | 301.59 | 26-AUG-07:10 | 22.35 | 20.88 |
September | 0.113248E+11 | 18029.03 | 18-SEP-05:23 | 23.60 | 20.38 | 0.248976E+09 | 301.59 | 23-SEP-07:10 | 24.37 | 22.58 |
October | 0.101445E+11 | 17822.00 | 02-OCT-04:03 | 21.70 | 20.21 | 0.248954E+09 | 301.59 | 28-OCT-07:10 | 22.85 | 20.29 |
November | 0.872374E+10 | 18437.78 | 27-NOV-00:01 | 18.80 | 16.72 | 0.238976E+09 | 301.59 | 25-NOV-08:09 | 23.58 | 21.24 |
December | 0.787810E+10 | 19695.19 | 26-DEC-00:01 | 19.08 | 15.75 | 0.248924E+09 | 301.59 | 30-DEC-08:09 | 20.33 | 19.03 |
Annual Sum or Average | 0.114336E+12 | 0.301720E+10 | ||||||||
Minimum of Months | 0.690112E+10 | 17822.00 | 18.80 | 15.75 | 0.228997E+09 | 301.58 | 20.33 | 16.32 | ||
Maximum of Months | 0.121125E+11 | 19695.19 | 25.00 | 20.86 | 0.268885E+09 | 301.61 | 27.52 | 24.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106134E+11 | 60286.69 | 29-JAN-15:53 | 26.70 | 20.94 | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 |
February | 0.127082E+11 | 62535.68 | 26-FEB-13:02 | 27.80 | 20.36 | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 15.61 |
March | 0.178614E+11 | 66836.60 | 26-MAR-13:32 | 26.87 | 19.24 | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 | 19.93 |
April | 0.193246E+11 | 63575.94 | 09-APR-16:42 | 27.38 | 20.25 | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 |
May | 0.285274E+11 | 63568.35 | 22-MAY-17:06 | 28.12 | 20.17 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 19.63 |
June | 0.301111E+11 | 63689.23 | 04-JUN-14:42 | 28.13 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 |
July | 0.369185E+11 | 62929.79 | 01-JUL-17:06 | 29.72 | 21.29 | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 |
August | 0.384230E+11 | 62265.16 | 15-AUG-17:06 | 27.70 | 21.11 | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 |
September | 0.351589E+11 | 61015.76 | 17-SEP-17:42 | 26.97 | 21.52 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 |
October | 0.284908E+11 | 60564.51 | 08-OCT-16:23 | 29.75 | 21.78 | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 | 22.40 |
November | 0.186361E+11 | 62326.12 | 12-NOV-13:43 | 27.80 | 21.22 | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 |
December | 0.135031E+11 | 60424.75 | 10-DEC-15:13 | 28.77 | 21.75 | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 | 21.52 |
Annual Sum or Average | 0.290277E+12 | 0.00 | ||||||||
Minimum of Months | 0.106134E+11 | 60286.69 | 26.70 | 19.24 | 0.00 | 0.00 | 20.60 | 15.61 | ||
Maximum of Months | 0.384230E+11 | 66836.60 | 29.75 | 21.78 | 0.00 | 0.00 | 25.60 | 22.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 20.60 | 15.61 | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 15.61 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 21.18 | 19.93 | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 | 19.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 | 19.63 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.30 | 22.40 | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 | 22.40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.70 | 21.52 | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 | 21.52 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 20.60 | 15.61 | 0.00 | 0.00 | 20.60 | 15.61 | ||
Maximum of Months | 0.00 | 0.00 | 25.60 | 22.40 | 0.00 | 0.00 | 25.60 | 22.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5438170.56 | 1609.63 | 12-JAN-07:05 | 22.30 |
February | 4525909.93 | 1474.09 | 14-FEB-07:05 | 20.60 |
March | 7511023.88 | 669.73 | 21-MAR-06:10 | 18.90 |
April | 1392940.65 | 982.52 | 03-APR-06:10 | 20.68 |
May | 269187.73 | 897.29 | 01-MAY-06:10 | 21.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.30 |
November | 651920.16 | 463.08 | 27-NOV-07:10 | 16.47 |
December | 2765564.90 | 1685.98 | 28-DEC-07:05 | 22.88 |
Annual Sum or Average | 22554717.81 | |||
Minimum of Months | 0.00 | 0.00 | 16.47 | |
Maximum of Months | 7511023.88 | 1685.98 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547517E+09 | 5218.13 | 12-JAN-07:33 | 22.60 |
February | 0.357829E+09 | 5315.72 | 13-FEB-08:65 | 23.98 |
March | 0.396691E+09 | 4678.73 | 03-MAR-08:00 | 21.70 |
April | 0.251383E+09 | 4905.84 | 17-APR-06:33 | 22.80 |
May | 33440007.82 | 4983.23 | 31-MAY-06:23 | 22.75 |
June | 12557879.43 | 4571.54 | 10-JUN-06:05 | 24.08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 |
August | 833813.49 | 1389.69 | 26-AUG-06:10 | 21.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 |
October | 41534704.56 | 3836.95 | 21-OCT-06:05 | 21.70 |
November | 96130728.42 | 5482.49 | 17-NOV-07:23 | 23.90 |
December | 0.269484E+09 | 5166.84 | 27-DEC-07:33 | 22.80 |
Annual Sum or Average | 0.200740E+10 | |||
Minimum of Months | 0.00 | 0.00 | 21.70 | |
Maximum of Months | 0.547517E+09 | 5482.49 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 20.60 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 21.18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.12 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.70 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 20.60 | |
Maximum of Months | 0.00 | 0.00 | 25.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144120E+09 | 0.356104E+09 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158495E+09 | 0.241525E+09 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266600E+09 | 0.275224E+09 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290445E+09 | 0.233181E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506900E+09 | 0.111597E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569699E+09 | 58375718.89 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729312E+09 | 44175174.46 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853829E+09 | 40565615.64 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677629E+09 | 31467752.83 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622051E+09 | 98647355.29 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383677E+09 | 0.129915E+09 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243228E+09 | 0.223834E+09 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.544598E+10 | 0.184461E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144120E+09 | 31467752.83 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853829E+09 | 0.356104E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83649825.61 | 0.472965E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79460159.63 | 0.353010E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253221E+09 | 0.421336E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346972E+09 | 0.421376E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894620E+09 | 0.269688E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109760E+10 | 0.263109E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219760E+10 | 0.200624E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247625E+10 | 0.161007E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190676E+10 | 0.139647E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158755E+10 | 0.150716E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726209E+09 | 0.319620E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184061E+09 | 0.385064E+10 |
Annual Sum or Average | 0.136656E+12 | 0.118340E+11 | 0.355816E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79460159.63 | 0.139647E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247625E+10 | 0.472965E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189651E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165907E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230552E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262539E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245562E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296650E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302356E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265709E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253064E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161531E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201948E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433847.92 | 0.178579E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 433847.92 | 0.275405E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161531E+11 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433847.92 | 0.302356E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1971.69 | 06-JAN-13:00 | 2273.20 | 30-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.64 | 22-FEB-12:55 | 3360.34 | 08-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1999.24 | 30-MAR-16:10 | 3144.66 | 08-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.55 | 05-APR-12:00 | 1722.45 | 27-APR-06:20 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2500.14 | 24-MAY-11:10 | 1610.34 | 23-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513.34 | 29-JUN-11:10 | 485.48 | 09-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2881.73 | 10-JUL-11:55 | 317.30 | 26-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.81 | 11-AUG-16:10 | 935.84 | 24-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.64 | 01-SEP-16:10 | 567.32 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.49 | 11-OCT-12:00 | 1708.88 | 19-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.69 | 06-NOV-13:00 | 2724.00 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2286.92 | 13-DEC-13:00 | 2211.99 | 21-DEC-07:20 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.64 | 317.30 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.64 | 3360.34 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.75 | 01-JAN-14:15 | 6976.76 | 11-JAN-17:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.34 | 26-FEB-16:00 | 6558.14 | 10-FEB-18:00 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116.06 | 15-MAR-15:10 | 6488.09 | 22-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3273.24 | 09-APR-13:50 | 8981.84 | 01-APR-08:00 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4657.28 | 17-MAY-15:10 | 4720.68 | 31-MAY-06:20 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4313.42 | 18-JUN-14:00 | 4311.92 | 13-JUN-06:10 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708.29 | 15-JUL-15:05 | 4119.14 | 13-JUL-06:10 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7654.93 | 09-AUG-15:10 | 3415.10 | 03-AUG-22:53 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8316.85 | 05-SEP-15:10 | 3562.75 | 29-SEP-22:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6668.25 | 03-OCT-15:10 | 3456.27 | 19-OCT-07:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5351.39 | 05-NOV-12:58 | 6983.94 | 25-NOV-18:00 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.35 | 10-DEC-13:58 | 7004.53 | 20-DEC-08:30 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.75 | 3415.10 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8316.85 | 8981.84 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 35641.98 | 11-JAN-16:45 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 36418.06 | 06-FEB-10:10 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 27544.98 | 17-MAR-12:10 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 43450.14 | 01-APR-08:40 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 31844.07 | 30-MAY-14:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 33163.87 | 19-JUN-13:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 33351.90 | 19-JUL-13:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 30586.31 | 28-AUG-13:40 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 30724.71 | 06-SEP-14:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 25602.85 | 05-OCT-13:30 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32580.52 | 16-NOV-13:10 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.78 | 01-DEC-06:45 | 32800.49 | 20-DEC-09:50 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25602.85 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 205.78 | 43450.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18991.31 | 23-JAN-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.19 |
February | 18675.40 | 13-FEB-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
March | 19522.69 | 27-MAR-00:01 | 0.00 | 4130.60 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.75 |
April | 19519.53 | 03-APR-00:01 | 0.00 | 4130.60 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.90 |
May | 19373.66 | 22-MAY-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.97 |
June | 19006.76 | 05-JUN-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.02 |
July | 18421.62 | 31-JUL-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.18 |
August | 17958.65 | 14-AUG-00:01 | 0.00 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 |
September | 18029.03 | 18-SEP-05:23 | 217.55 | 1759.33 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
October | 17822.00 | 02-OCT-04:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 |
November | 18437.78 | 27-NOV-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.18 |
December | 19695.19 | 26-DEC-00:01 | 0.00 | 3671.64 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17822.00 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | |
Maximum of Months | 19695.19 | 217.55 | 4589.55 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 60286.69 | 29-JAN-15:53 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.43 |
February | 62535.68 | 26-FEB-13:02 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.53 | 0.00 |
March | 66836.60 | 26-MAR-13:32 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.73 |
April | 63575.94 | 09-APR-16:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 |
May | 63568.35 | 22-MAY-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.07 | 0.00 |
June | 63689.23 | 04-JUN-14:42 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.55 | 0.00 |
July | 62929.79 | 01-JUL-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1507.15 | 0.00 |
August | 62265.16 | 15-AUG-17:06 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.02 | 0.00 |
September | 61015.76 | 17-SEP-17:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.86 |
October | 60564.51 | 08-OCT-16:23 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.03 | 0.00 |
November | 62326.12 | 12-NOV-13:43 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 | 0.00 |
December | 60424.75 | 10-DEC-15:13 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.55 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 60286.69 | 0.00 | 3599.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66836.60 | 0.00 | 5999.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.03 | 470.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3851.97 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2999.95 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2576.29 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11429.40 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10142.11 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11098.83 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7472.27 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7204.79 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.34 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 8279.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6816.15 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7817.82 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.55 | |
Maximum of Months | 0.00 | 0.00 | 27597.31 | 20500.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11429.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.835381E+11 | 74262.87 | 04-JAN-13:50 | 0.468720E+10 | 1750.00 | 01-JAN-00:10 |
February | 0.786309E+11 | 75330.89 | 23-FEB-14:09 | 0.423360E+10 | 1750.00 | 01-FEB-00:10 |
March | 0.913128E+11 | 76340.85 | 13-MAR-14:00 | 0.468720E+10 | 1750.00 | 01-MAR-00:10 |
April | 0.865543E+11 | 75679.67 | 24-APR-14:09 | 0.453600E+10 | 1750.00 | 01-APR-00:10 |
May | 0.952221E+11 | 78058.16 | 17-MAY-13:50 | 0.468720E+10 | 1750.00 | 01-MAY-00:10 |
June | 0.955524E+11 | 78275.27 | 26-JUN-14:20 | 0.453600E+10 | 1750.00 | 01-JUN-00:10 |
July | 0.995894E+11 | 80233.01 | 17-JUL-12:30 | 0.468720E+10 | 1750.00 | 01-JUL-00:10 |
August | 0.104670E+12 | 81381.51 | 28-AUG-13:50 | 0.468720E+10 | 1750.00 | 01-AUG-00:10 |
September | 0.991083E+11 | 82520.52 | 05-SEP-14:00 | 0.453600E+10 | 1750.00 | 01-SEP-00:10 |
October | 0.957009E+11 | 80221.21 | 06-OCT-13:20 | 0.468720E+10 | 1750.00 | 01-OCT-00:10 |
November | 0.868488E+11 | 78250.36 | 06-NOV-14:30 | 0.453600E+10 | 1750.00 | 01-NOV-00:10 |
December | 0.862003E+11 | 75557.07 | 06-DEC-13:30 | 0.468720E+10 | 1750.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.110293E+13 | 0.551880E+11 | ||||
Minimum of Months | 0.786309E+11 | 74262.87 | 0.423360E+10 | 1750.00 | ||
Maximum of Months | 0.104670E+12 | 82520.52 | 0.468720E+10 | 1750.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.115219E+11 | 0.115358E+11 | 0.00 | 0.956464E+10 | 0.00 | 0.00 | 0.880863E+10 | 0.00 | 0.00 | 0.00 | 0.200382E+10 | 0.00 |
February | 0.366966E+11 | 0.100557E+11 | 0.105871E+11 | 0.00 | 0.919867E+10 | 0.00 | 0.00 | 0.102773E+11 | 0.00 | 0.00 | 0.00 | 0.181558E+10 | 0.00 |
March | 0.423649E+11 | 0.106214E+11 | 0.123357E+11 | 0.00 | 0.111047E+11 | 0.00 | 0.00 | 0.128530E+11 | 0.00 | 0.00 | 0.00 | 0.203310E+10 | 0.00 |
April | 0.397216E+11 | 0.974455E+10 | 0.114862E+11 | 0.00 | 0.106674E+11 | 0.00 | 0.00 | 0.130061E+11 | 0.00 | 0.00 | 0.00 | 0.192841E+10 | 0.00 |
May | 0.412341E+11 | 0.963140E+10 | 0.119357E+11 | 0.00 | 0.120647E+11 | 0.00 | 0.00 | 0.183755E+11 | 0.00 | 0.00 | 0.00 | 0.198062E+10 | 0.00 |
June | 0.408524E+11 | 0.911283E+10 | 0.118862E+11 | 0.00 | 0.122264E+11 | 0.00 | 0.00 | 0.195536E+11 | 0.00 | 0.00 | 0.00 | 0.192108E+10 | 0.00 |
July | 0.401034E+11 | 0.947583E+10 | 0.115358E+11 | 0.00 | 0.130203E+11 | 0.00 | 0.00 | 0.235104E+11 | 0.00 | 0.00 | 0.00 | 0.194361E+10 | 0.00 |
August | 0.423649E+11 | 0.988127E+10 | 0.123357E+11 | 0.00 | 0.134996E+11 | 0.00 | 0.00 | 0.246021E+11 | 0.00 | 0.00 | 0.00 | 0.198658E+10 | 0.00 |
September | 0.397216E+11 | 0.100604E+11 | 0.114862E+11 | 0.00 | 0.127871E+11 | 0.00 | 0.00 | 0.231422E+11 | 0.00 | 0.00 | 0.00 | 0.191079E+10 | 0.00 |
October | 0.401034E+11 | 0.109090E+11 | 0.115358E+11 | 0.00 | 0.117981E+11 | 0.00 | 0.00 | 0.193826E+11 | 0.00 | 0.00 | 0.00 | 0.197213E+10 | 0.00 |
November | 0.385909E+11 | 0.110269E+11 | 0.110862E+11 | 0.00 | 0.101823E+11 | 0.00 | 0.00 | 0.140428E+11 | 0.00 | 0.00 | 0.00 | 0.191974E+10 | 0.00 |
December | 0.401034E+11 | 0.116444E+11 | 0.115358E+11 | 0.00 | 0.981229E+10 | 0.00 | 0.00 | 0.111054E+11 | 0.00 | 0.00 | 0.00 | 0.199904E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123686E+12 | 0.139282E+12 | 0.135926E+12 | 0.00 | 0.198660E+12 | 0.234145E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.911283E+10 | 0.105871E+11 | 0.00 | 0.919867E+10 | 0.00 | 0.00 | 0.880863E+10 | 0.00 | 0.00 | 0.00 | 0.181558E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.116444E+11 | 0.123357E+11 | 0.00 | 0.134996E+11 | 0.00 | 0.00 | 0.246021E+11 | 0.00 | 0.00 | 0.00 | 0.203310E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551880E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10444.02 | 02-JAN-09:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10444.02 | 01-FEB-09:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10444.02 | 06-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10444.02 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10444.02 | 01-MAY-08:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10444.02 | 29-JUN-13:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10444.02 | 15-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10444.02 | 01-AUG-07:49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10444.02 | 01-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10444.02 | 18-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10444.02 | 08-NOV-12:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10444.02 | 01-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 10444.02 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 10444.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 16471.83 | 04-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1732.55 | 17-JAN-12:30 | 0.00 |
February | 17489.86 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1732.02 | 02-FEB-12:20 | 0.00 |
March | 18912.32 | 15-MAR-15:39 | 0.00 | 0.00 | 0.00 | 1729.28 | 01-MAR-12:09 | 0.00 |
April | 17812.50 | 24-APR-14:20 | 0.00 | 0.00 | 0.00 | 1723.84 | 01-APR-11:50 | 0.00 |
May | 20415.52 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1717.45 | 01-MAY-11:50 | 0.00 |
June | 20904.61 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1711.98 | 01-JUN-11:20 | 0.00 |
July | 23406.19 | 05-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1708.59 | 03-JUL-11:20 | 0.00 |
August | 23780.84 | 09-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1711.33 | 31-AUG-11:30 | 0.00 |
September | 26632.77 | 05-SEP-15:39 | 0.00 | 0.00 | 0.00 | 1716.55 | 30-SEP-11:50 | 0.00 |
October | 22883.43 | 02-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1722.96 | 31-OCT-11:00 | 0.00 |
November | 20399.75 | 06-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1728.52 | 30-NOV-12:30 | 0.00 |
December | 17773.44 | 06-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1731.89 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 16471.83 | 0.00 | 0.00 | 0.00 | 1708.59 | 0.00 | ||
Maximum of Months | 26632.77 | 0.00 | 0.00 | 0.00 | 1732.55 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 74262.87 | 04-JAN-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 16381.14 | 0.00 |
February | 75330.89 | 23-FEB-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 17475.92 | 0.00 |
March | 76340.85 | 13-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 18463.22 | 0.00 |
April | 75679.67 | 24-APR-14:09 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 17809.13 | 0.00 |
May | 78058.16 | 17-MAY-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 20214.40 | 0.00 |
June | 78275.27 | 26-JUN-14:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 20413.05 | 0.00 |
July | 80233.01 | 17-JUL-12:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 22371.22 | 0.00 |
August | 81381.51 | 28-AUG-13:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 23540.31 | 0.00 |
September | 82520.52 | 05-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 24655.85 | 0.00 |
October | 80221.21 | 06-OCT-13:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 22375.19 | 0.00 |
November | 78250.36 | 06-NOV-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 20399.75 | 0.00 |
December | 75557.07 | 06-DEC-13:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 17677.36 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 74262.87 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 16381.14 | 0.00 | |
Maximum of Months | 82520.52 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10444.02 | 0.00 | 0.00 | 24655.85 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1750.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1750.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1750.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1750.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1750.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1750.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1750.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1750.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.56 | 0.67 | 24.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 24.61 | 0.33 | 24.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 24.63 | 1.00 | 24.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 24.59 | 0.50 | 24.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 24.61 | 1.67 | 24.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 24.65 | 3.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 24.70 | 5.00 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 | 24.68 | 4.50 | 24.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 | 24.76 | 4.83 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 66.50 | 24.63 | 3.17 | 24.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 24.57 | 1.33 | 24.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.52 | 0.33 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 580.17 | 24.66 | 26.33 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.52 | 0.33 | 24.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 | 24.76 | 5.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.54 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.72 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.64 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.66 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.67 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.69 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.81 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.76 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.81 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.79 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.77 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 212.67 | 27.74 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.50 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.81 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 23.86 | 245.33 | 23.90 | 0.00 | 0.00 |
February | 7.17 | 23.83 | 249.50 | 23.90 | 4.83 | 23.90 |
March | 3.17 | 23.86 | 291.50 | 23.90 | 1.50 | 23.90 |
April | 0.00 | 0.00 | 280.33 | 23.90 | 0.00 | 0.00 |
May | 0.50 | 23.90 | 311.00 | 23.91 | 0.50 | 23.90 |
June | 0.00 | 0.00 | 312.00 | 23.91 | 0.00 | 0.00 |
July | 1.50 | 23.90 | 300.00 | 23.91 | 1.50 | 23.90 |
August | 0.00 | 0.00 | 324.00 | 23.91 | 0.00 | 0.00 |
September | 1.00 | 23.90 | 300.00 | 23.91 | 1.00 | 23.90 |
October | 0.00 | 0.00 | 296.83 | 23.91 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 283.50 | 23.90 | 0.00 | 0.00 |
December | 0.67 | 23.83 | 279.17 | 23.90 | 0.00 | 0.00 |
Annual Sum or Average | 18.17 | 23.85 | 3473.17 | 23.91 | 9.33 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 245.33 | 23.90 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 23.90 | 324.00 | 23.91 | 4.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.106696E+11 | 0.287226E+10 | 435.94 | 0.853897E+10 | 0.213060E+10 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 | 28517.57 | 02-JAN-00:01 | 20527.53 | 23-JAN-00:01 | 11384.40 | 02-JAN-00:06 | 6434.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 |
February | 0.117116E+11 | 0.312418E+10 | 424.36 | 0.875426E+10 | 0.295730E+10 | 0.00 | 1.00 | 06-FEB-00:01 | 0.00 | 01-FEB-00:05 | 28744.95 | 21-FEB-00:01 | 20254.28 | 13-FEB-00:01 | 11808.81 | 21-FEB-00:07 | 6464.90 | 21-FEB-00:01 | 0.00 | 01-FEB-00:05 |
March | 0.137400E+11 | 0.370294E+10 | 503.14 | 0.108439E+11 | 0.289616E+10 | 0.00 | 1.00 | 06-MAR-00:01 | 0.00 | 01-MAR-00:10 | 28249.33 | 13-MAR-00:01 | 21286.03 | 21-MAR-18:23 | 10835.15 | 13-MAR-00:06 | 6396.55 | 13-MAR-00:01 | 0.00 | 01-MAR-00:05 |
April | 0.131587E+11 | 0.355756E+10 | 486.86 | 0.106049E+11 | 0.255383E+10 | 0.00 | 1.00 | 03-APR-00:01 | 0.00 | 01-APR-00:15 | 27185.77 | 17-APR-00:01 | 21288.97 | 29-APR-17:08 | 9324.52 | 17-APR-00:04 | 6237.62 | 17-APR-00:01 | 0.00 | 01-APR-00:10 |
May | 0.162684E+11 | 0.444107E+10 | 522.94 | 0.127881E+11 | 0.348024E+10 | 0.00 | 1.00 | 01-MAY-00:01 | 0.00 | 01-MAY-00:06 | 28273.33 | 15-MAY-00:01 | 20550.28 | 30-MAY-19:03 | 10786.25 | 15-MAY-00:06 | 6399.95 | 15-MAY-00:01 | 0.00 | 01-MAY-00:01 |
June | 0.171724E+11 | 0.467151E+10 | 531.29 | 0.132732E+11 | 0.389923E+10 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:15 | 27818.26 | 19-JUN-00:01 | 20418.62 | 05-JUN-00:01 | 9595.10 | 19-JUN-00:07 | 6389.55 | 19-JUN-00:01 | 0.00 | 01-JUN-00:10 |
July | 0.183572E+11 | 0.504750E+10 | 524.92 | 0.140171E+11 | 0.434004E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:13 | 29095.81 | 24-JUL-00:01 | 20294.17 | 01-JUL-17:42 | 12267.04 | 24-JUL-00:07 | 6572.47 | 24-JUL-00:01 | 0.00 | 01-JUL-00:10 |
August | 0.195239E+11 | 0.541546E+10 | 560.29 | 0.150136E+11 | 0.451029E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:13 | 28021.04 | 07-AUG-00:01 | 19762.60 | 07-AUG-05:23 | 10029.86 | 07-AUG-00:07 | 6465.34 | 21-AUG-00:01 | 0.00 | 01-AUG-00:10 |
September | 0.185408E+11 | 0.507444E+10 | 529.08 | 0.139352E+11 | 0.460563E+10 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 28730.86 | 11-SEP-00:01 | 20159.79 | 18-SEP-22:23 | 11622.31 | 11-SEP-00:08 | 6894.76 | 03-SEP-13:38 | 0.00 | 01-SEP-00:10 |
October | 0.165801E+11 | 0.457574E+10 | 511.34 | 0.126316E+11 | 0.394849E+10 | 0.00 | 1.00 | 02-OCT-00:01 | 0.00 | 01-OCT-00:03 | 29122.71 | 10-OCT-00:01 | 19680.66 | 02-OCT-04:03 | 12068.93 | 10-OCT-00:07 | 6514.57 | 10-OCT-00:01 | 0.00 | 01-OCT-00:03 |
November | 0.142589E+11 | 0.386361E+10 | 473.39 | 0.107985E+11 | 0.346035E+10 | 0.00 | 1.00 | 01-NOV-17:10 | 0.00 | 01-NOV-00:13 | 28419.95 | 06-NOV-00:01 | 19893.57 | 06-NOV-06:03 | 11118.03 | 20-NOV-00:06 | 6480.60 | 06-NOV-00:01 | 0.00 | 01-NOV-00:10 |
December | 0.126864E+11 | 0.342091E+10 | 471.07 | 0.976988E+10 | 0.291647E+10 | 0.00 | 1.00 | 04-DEC-00:01 | 0.00 | 01-DEC-00:10 | 27982.77 | 18-DEC-00:01 | 20862.75 | 26-DEC-00:01 | 11003.50 | 18-DEC-00:04 | 6358.29 | 18-DEC-00:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.182668E+12 | 0.497672E+11 | 5974.61 | 0.140969E+12 | 0.416986E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.106696E+11 | 0.287226E+10 | 424.36 | 0.853897E+10 | 0.213060E+10 | 0.00 | 1.00 | 0.00 | 27185.77 | 19680.66 | 9324.52 | 6237.62 | 0.00 | |||||||
Maximum of Months | 0.195239E+11 | 0.541546E+10 | 560.29 | 0.150136E+11 | 0.460563E+10 | 0.00 | 1.00 | 0.00 | 29122.71 | 21288.97 | 12267.04 | 6894.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.202618E+11 | 0.593637E+10 | 265.52 | 0.160310E+11 | 0.423081E+10 | 0.00 | 1.00 | 01-JAN-10:53 | 0.00 | 01-JAN-00:10 | 94144.33 | 01-JAN-10:53 | 69937.38 | 29-JAN-15:53 | 30047.66 | 01-JAN-10:53 | 24652.78 | 01-JAN-10:53 | 0.00 | 01-JAN-00:10 |
February | 0.247714E+11 | 0.715309E+10 | 262.15 | 0.182501E+11 | 0.652129E+10 | 0.00 | 1.00 | 19-FEB-10:53 | 0.00 | 01-FEB-00:05 | 95286.12 | 20-FEB-10:53 | 73451.83 | 26-FEB-15:43 | 33191.26 | 19-FEB-10:53 | 25117.57 | 19-FEB-10:53 | 0.00 | 01-FEB-00:05 |
March | 0.313643E+11 | 0.915004E+10 | 320.79 | 0.245765E+11 | 0.678781E+10 | 0.00 | 1.00 | 05-MAR-13:43 | 0.00 | 01-MAR-00:05 | 96318.44 | 12-MAR-11:53 | 74767.88 | 26-MAR-13:32 | 34827.00 | 12-MAR-11:53 | 24978.53 | 12-MAR-11:53 | 0.00 | 01-MAR-00:05 |
April | 0.322855E+11 | 0.944852E+10 | 321.49 | 0.258598E+11 | 0.642571E+10 | 0.00 | 1.00 | 09-APR-10:03 | 0.00 | 01-APR-00:10 | 93003.66 | 09-APR-10:03 | 75159.40 | 30-APR-14:13 | 27480.36 | 09-APR-09:23 | 24448.27 | 09-APR-12:43 | 0.00 | 01-APR-00:10 |
May | 0.472151E+11 | 0.139344E+11 | 410.66 | 0.368969E+11 | 0.103182E+11 | 0.00 | 1.00 | 07-MAY-10:13 | 0.00 | 01-MAY-00:01 | 99076.30 | 15-MAY-00:07 | 72920.00 | 21-MAY-10:53 | 38687.63 | 15-MAY-00:07 | 24764.26 | 14-MAY-14:32 | 0.00 | 01-MAY-00:01 |
June | 0.508076E+11 | 0.148821E+11 | 418.69 | 0.386785E+11 | 0.121291E+11 | 0.00 | 1.00 | 02-JUN-17:06 | 0.00 | 01-JUN-00:10 | 96255.98 | 25-JUN-08:53 | 74689.45 | 04-JUN-14:42 | 33458.70 | 25-JUN-08:53 | 24758.27 | 25-JUN-13:32 | 0.00 | 01-JUN-00:10 |
July | 0.622233E+11 | 0.184630E+11 | 497.93 | 0.466095E+11 | 0.156138E+11 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:10 | 97300.16 | 23-JUL-08:43 | 73061.13 | 30-JUL-14:12 | 37294.52 | 23-JUL-08:43 | 25513.99 | 23-JUL-10:43 | 0.00 | 01-JUL-00:10 |
August | 0.642463E+11 | 0.191867E+11 | 511.76 | 0.487367E+11 | 0.155096E+11 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:25 | 95149.17 | 20-AUG-08:33 | 71802.50 | 13-AUG-14:32 | 32921.78 | 20-AUG-08:33 | 25470.58 | 20-AUG-13:52 | 0.00 | 01-AUG-00:10 |
September | 0.613201E+11 | 0.180678E+11 | 498.30 | 0.447044E+11 | 0.166156E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 98836.86 | 10-SEP-08:53 | 70682.72 | 03-SEP-15:02 | 40498.06 | 10-SEP-08:53 | 25854.18 | 03-SEP-13:02 | 0.00 | 01-SEP-00:10 |
October | 0.494677E+11 | 0.148068E+11 | 420.49 | 0.373223E+11 | 0.121453E+11 | 0.00 | 1.00 | 01-OCT-08:53 | 0.00 | 01-OCT-00:13 | 95731.66 | 01-OCT-08:53 | 72214.60 | 01-OCT-14:12 | 35318.14 | 22-OCT-09:13 | 25528.97 | 01-OCT-12:52 | 0.00 | 01-OCT-00:03 |
November | 0.346693E+11 | 0.101792E+11 | 316.80 | 0.257385E+11 | 0.893074E+10 | 0.00 | 1.00 | 05-NOV-10:13 | 0.00 | 01-NOV-00:10 | 99341.38 | 06-NOV-00:06 | 70188.69 | 12-NOV-14:23 | 39946.43 | 06-NOV-00:06 | 25106.38 | 05-NOV-13:32 | 0.00 | 01-NOV-00:10 |
December | 0.263590E+11 | 0.768451E+10 | 288.84 | 0.197923E+11 | 0.656671E+10 | 0.00 | 1.00 | 10-DEC-11:13 | 0.00 | 01-DEC-00:05 | 98990.35 | 17-DEC-12:42 | 68841.20 | 10-DEC-14:32 | 37395.79 | 17-DEC-12:42 | 24813.88 | 10-DEC-11:13 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.504991E+12 | 0.148892E+12 | 4533.42 | 0.383197E+12 | 0.121795E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.202618E+11 | 0.593637E+10 | 262.15 | 0.160310E+11 | 0.423081E+10 | 0.00 | 1.00 | 0.00 | 93003.66 | 68841.20 | 27480.36 | 24448.27 | 0.00 | |||||||
Maximum of Months | 0.642463E+11 | 0.191867E+11 | 511.76 | 0.487367E+11 | 0.166156E+11 | 0.00 | 1.00 | 0.00 | 99341.38 | 75159.40 | 40498.06 | 25854.18 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.58 | 13.11 | 24.47 | 91.42 | 71.67 | 0.00 | 0.00 | 744.00 |
February | 57.69 | 25.92 | 31.77 | 149.39 | 71.21 | 0.00 | 0.00 | 672.00 |
March | 63.68 | 26.43 | 37.25 | 171.74 | 67.12 | 0.00 | 0.00 | 744.00 |
April | 59.97 | 23.85 | 36.12 | 162.73 | 55.42 | 0.00 | 0.00 | 720.00 |
May | 57.03 | 20.22 | 36.81 | 169.13 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 62.96 | 25.03 | 37.92 | 186.41 | 33.30 | 0.00 | 0.00 | 720.00 |
July | 63.30 | 26.94 | 36.36 | 199.95 | 27.30 | 0.00 | 0.00 | 744.00 |
August | 63.66 | 28.40 | 35.26 | 208.02 | 29.45 | 0.00 | 0.00 | 744.00 |
September | 74.79 | 33.64 | 41.15 | 233.35 | 27.60 | 0.00 | 0.00 | 720.00 |
October | 46.20 | 16.43 | 29.76 | 150.94 | 42.56 | 0.00 | 0.00 | 744.00 |
November | 44.52 | 17.86 | 26.66 | 128.27 | 49.91 | 0.00 | 0.00 | 720.00 |
December | 37.21 | 14.26 | 22.95 | 96.61 | 56.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.65 | 22.62 | 33.02 | 162.27 | 47.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.21 | 13.11 | 22.95 | 91.42 | 27.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.79 | 33.64 | 41.15 | 233.35 | 71.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.58 | 13.11 | 24.47 | 91.42 | 71.67 | 0.00 | 0.00 | 744.00 |
February | 57.69 | 25.92 | 31.77 | 149.39 | 71.21 | 0.00 | 0.00 | 672.00 |
March | 63.68 | 26.43 | 37.25 | 171.74 | 67.12 | 0.00 | 0.00 | 744.00 |
April | 59.97 | 23.85 | 36.12 | 162.73 | 55.42 | 0.00 | 0.00 | 720.00 |
May | 57.03 | 20.22 | 36.81 | 169.13 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 62.96 | 25.03 | 37.92 | 186.41 | 33.30 | 0.00 | 0.00 | 720.00 |
July | 63.30 | 26.94 | 36.36 | 199.95 | 27.30 | 0.00 | 0.00 | 744.00 |
August | 63.66 | 28.40 | 35.26 | 208.02 | 29.45 | 0.00 | 0.00 | 744.00 |
September | 74.79 | 33.64 | 41.15 | 233.35 | 27.60 | 0.00 | 0.00 | 720.00 |
October | 46.20 | 16.43 | 29.76 | 150.94 | 42.56 | 0.00 | 0.00 | 744.00 |
November | 44.52 | 17.86 | 26.66 | 128.27 | 49.91 | 0.00 | 0.00 | 720.00 |
December | 37.21 | 14.26 | 22.95 | 96.61 | 56.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.65 | 22.62 | 33.02 | 162.27 | 47.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.21 | 13.11 | 22.95 | 91.42 | 27.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.79 | 33.64 | 41.15 | 233.35 | 71.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.35 | 0.00 | 12.35 | 24.27 | 43.27 | 0.00 | 0.00 | 744.00 |
February | 14.75 | 0.00 | 14.75 | 32.78 | 42.66 | 0.00 | 0.00 | 672.00 |
March | 16.86 | 0.00 | 16.85 | 39.69 | 40.15 | 0.00 | 0.00 | 744.00 |
April | 18.31 | 0.30 | 18.02 | 42.36 | 32.88 | 0.00 | 0.00 | 720.00 |
May | 23.26 | 2.77 | 20.49 | 65.08 | 24.76 | 0.00 | 0.00 | 744.00 |
June | 27.28 | 5.13 | 22.15 | 75.42 | 18.94 | 0.00 | 0.00 | 720.00 |
July | 24.91 | 3.98 | 20.93 | 76.01 | 15.34 | 0.00 | 0.00 | 744.00 |
August | 19.41 | 1.27 | 18.13 | 64.41 | 16.25 | 0.00 | 0.00 | 744.00 |
September | 17.91 | 0.03 | 17.88 | 55.62 | 15.41 | 0.00 | 0.00 | 720.00 |
October | 14.84 | 0.00 | 14.84 | 49.78 | 24.26 | 0.00 | 0.00 | 744.00 |
November | 13.37 | 0.00 | 13.37 | 35.37 | 29.19 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 25.59 | 33.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.93 | 1.13 | 16.80 | 48.96 | 27.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 24.27 | 15.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 27.28 | 5.13 | 22.15 | 76.01 | 43.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.35 | 0.00 | 12.35 | 24.27 | 43.27 | 0.00 | 0.00 | 744.00 |
February | 14.75 | 0.00 | 14.75 | 32.78 | 42.66 | 0.00 | 0.00 | 672.00 |
March | 16.86 | 0.00 | 16.85 | 39.69 | 40.15 | 0.00 | 0.00 | 744.00 |
April | 18.31 | 0.30 | 18.01 | 42.36 | 32.88 | 0.00 | 0.00 | 720.00 |
May | 23.26 | 2.77 | 20.49 | 65.07 | 24.76 | 0.00 | 0.00 | 744.00 |
June | 27.28 | 5.13 | 22.15 | 75.41 | 18.94 | 0.00 | 0.00 | 720.00 |
July | 24.91 | 3.98 | 20.93 | 76.01 | 15.34 | 0.00 | 0.00 | 744.00 |
August | 19.41 | 1.27 | 18.13 | 64.41 | 16.25 | 0.00 | 0.00 | 744.00 |
September | 17.91 | 0.03 | 17.88 | 55.62 | 15.41 | 0.00 | 0.00 | 720.00 |
October | 14.84 | 0.00 | 14.84 | 49.77 | 24.26 | 0.00 | 0.00 | 744.00 |
November | 13.37 | 0.00 | 13.37 | 35.37 | 29.19 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 25.59 | 33.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.93 | 1.13 | 16.80 | 48.96 | 27.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 24.27 | 15.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 27.28 | 5.13 | 22.15 | 76.01 | 43.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.76 | 50.28 | 30.48 | 99.36 | 42.30 | 38.00 | 0.00 | 744.00 |
February | 96.40 | 58.57 | 37.83 | 119.57 | 42.29 | 81.67 | 0.00 | 672.00 |
March | 115.25 | 69.68 | 45.57 | 143.51 | 43.89 | 16.17 | 0.00 | 744.00 |
April | 126.30 | 77.85 | 48.45 | 157.37 | 42.59 | 0.33 | 0.00 | 720.00 |
May | 136.81 | 86.54 | 50.27 | 171.39 | 40.13 | 0.00 | 0.00 | 744.00 |
June | 141.71 | 91.23 | 50.49 | 176.82 | 38.34 | 0.00 | 0.00 | 720.00 |
July | 143.39 | 97.94 | 45.45 | 179.73 | 35.93 | 0.00 | 0.00 | 744.00 |
August | 143.02 | 100.72 | 42.31 | 179.95 | 39.60 | 1.00 | 0.00 | 744.00 |
September | 128.88 | 81.11 | 47.77 | 162.18 | 37.25 | 0.17 | 0.00 | 720.00 |
October | 104.39 | 66.53 | 37.86 | 132.48 | 43.15 | 17.33 | 0.00 | 744.00 |
November | 87.44 | 52.86 | 34.58 | 109.24 | 39.86 | 10.00 | 0.00 | 720.00 |
December | 77.06 | 48.36 | 28.70 | 94.89 | 39.06 | 59.50 | 0.00 | 744.00 |
Annual Sum or Average | 115.21 | 73.57 | 41.64 | 143.99 | 40.36 | 224.17 | 0.00 | 8760.00 |
Minimum of Months | 77.06 | 48.36 | 28.70 | 94.89 | 35.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 143.39 | 100.72 | 50.49 | 179.95 | 43.89 | 81.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100652E+09 | 35123428.30 | 65528743.33 | 0.244856E+09 | 0.191958E+09 |
February | 0.139569E+09 | 62707073.55 | 76861936.63 | 0.361401E+09 | 0.172281E+09 |
March | 0.170550E+09 | 70784918.78 | 99765187.86 | 0.459994E+09 | 0.179782E+09 |
April | 0.155443E+09 | 61829141.79 | 93614026.37 | 0.421791E+09 | 0.143650E+09 |
May | 0.152748E+09 | 54159374.21 | 98588883.39 | 0.453000E+09 | 0.116487E+09 |
June | 0.163185E+09 | 64888052.64 | 98297090.31 | 0.483181E+09 | 86310985.14 |
July | 0.169552E+09 | 72154968.73 | 97396560.42 | 0.535545E+09 | 73107325.03 |
August | 0.170520E+09 | 76071518.29 | 94448204.38 | 0.557161E+09 | 78882931.04 |
September | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.604844E+09 | 71533995.62 |
October | 0.123734E+09 | 44014127.74 | 79719829.56 | 0.404291E+09 | 0.114004E+09 |
November | 0.115402E+09 | 46292988.10 | 69108663.62 | 0.332482E+09 | 0.129378E+09 |
December | 99654494.96 | 38183108.14 | 61471386.82 | 0.258760E+09 | 0.150599E+09 |
Annual Sum or Average | 0.175486E+10 | 0.713391E+09 | 0.104147E+10 | 0.511731E+10 | 0.150797E+10 |
Minimum of Months | 99654494.96 | 35123428.30 | 61471386.82 | 0.244856E+09 | 71533995.62 |
Maximum of Months | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.604844E+09 | 0.191958E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100652E+09 | 35123428.30 | 65528743.33 | 0.244856E+09 | 0.191958E+09 |
February | 0.139569E+09 | 62707073.55 | 76861936.63 | 0.361401E+09 | 0.172281E+09 |
March | 0.170550E+09 | 70784918.78 | 99765187.86 | 0.459994E+09 | 0.179782E+09 |
April | 0.155443E+09 | 61829141.79 | 93614026.37 | 0.421791E+09 | 0.143650E+09 |
May | 0.152748E+09 | 54159374.21 | 98588883.39 | 0.453000E+09 | 0.116487E+09 |
June | 0.163185E+09 | 64888052.64 | 98297090.31 | 0.483181E+09 | 86310985.14 |
July | 0.169552E+09 | 72154968.73 | 97396560.42 | 0.535545E+09 | 73107325.03 |
August | 0.170520E+09 | 76071518.29 | 94448204.38 | 0.557161E+09 | 78882931.04 |
September | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.604844E+09 | 71533995.62 |
October | 0.123734E+09 | 44014127.74 | 79719829.56 | 0.404291E+09 | 0.114004E+09 |
November | 0.115402E+09 | 46292988.10 | 69108663.62 | 0.332482E+09 | 0.129378E+09 |
December | 99654494.96 | 38183108.14 | 61471386.82 | 0.258760E+09 | 0.150599E+09 |
Annual Sum or Average | 0.175486E+10 | 0.713391E+09 | 0.104147E+10 | 0.511731E+10 | 0.150797E+10 |
Minimum of Months | 99654494.96 | 35123428.30 | 61471386.82 | 0.244856E+09 | 71533995.62 |
Maximum of Months | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.604844E+09 | 0.191958E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33080144.57 | 0.00 | 33080144.57 | 65003103.86 | 0.115893E+09 |
February | 35695166.18 | 0.00 | 35695166.18 | 79294138.53 | 0.103209E+09 |
March | 45146086.44 | 6170.68 | 45139915.76 | 0.106312E+09 | 0.107539E+09 |
April | 47470323.51 | 774548.27 | 46695775.24 | 0.109795E+09 | 85218701.59 |
May | 62310203.44 | 7432260.62 | 54877942.82 | 0.174298E+09 | 66328164.08 |
June | 70703773.58 | 13300481.38 | 57403292.21 | 0.195480E+09 | 49103788.43 |
July | 66720540.30 | 10657015.94 | 56063524.36 | 0.203595E+09 | 41074535.98 |
August | 51976255.69 | 3409928.06 | 48566327.64 | 0.172513E+09 | 43530152.10 |
September | 46414507.28 | 67395.19 | 46347112.08 | 0.144178E+09 | 39936048.65 |
October | 39739363.98 | 0.00 | 39739363.98 | 0.133318E+09 | 64966760.56 |
November | 34651637.58 | 0.00 | 34651637.58 | 91683927.08 | 75667035.41 |
December | 31469428.72 | 0.00 | 31469428.72 | 68546843.85 | 89882459.27 |
Annual Sum or Average | 0.565377E+09 | 35647800.13 | 0.529730E+09 | 0.154402E+10 | 0.882349E+09 |
Minimum of Months | 31469428.72 | 0.00 | 31469428.72 | 65003103.86 | 39936048.65 |
Maximum of Months | 70703773.58 | 13300481.38 | 57403292.21 | 0.203595E+09 | 0.115893E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33079207.10 | 0.00 | 33079207.10 | 65001481.76 | 0.115892E+09 |
February | 35694148.56 | 0.00 | 35694148.56 | 79292163.69 | 0.103208E+09 |
March | 45144818.18 | 6170.39 | 45138647.79 | 0.106310E+09 | 0.107538E+09 |
April | 47468995.48 | 774511.97 | 46694483.51 | 0.109792E+09 | 85217431.84 |
May | 62308277.13 | 7431912.26 | 54876364.87 | 0.174293E+09 | 66327023.39 |
June | 70701457.27 | 13299857.96 | 57401599.31 | 0.195474E+09 | 49102682.15 |
July | 66718451.47 | 10656516.43 | 56061935.05 | 0.203591E+09 | 41073507.93 |
August | 51974856.26 | 3409768.23 | 48565088.04 | 0.172510E+09 | 43528943.81 |
September | 46413249.40 | 67392.03 | 46345857.36 | 0.144175E+09 | 39934923.41 |
October | 39738276.34 | 0.00 | 39738276.34 | 0.133316E+09 | 64965258.43 |
November | 34650652.93 | 0.00 | 34650652.93 | 91682068.89 | 75665690.31 |
December | 31468542.51 | 0.00 | 31468542.51 | 68545289.43 | 89880989.42 |
Annual Sum or Average | 0.565361E+09 | 35646129.27 | 0.529715E+09 | 0.154398E+10 | 0.882334E+09 |
Minimum of Months | 31468542.51 | 0.00 | 31468542.51 | 65001481.76 | 39934923.41 |
Maximum of Months | 70701457.27 | 13299857.96 | 57401599.31 | 0.203591E+09 | 0.115892E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216307E+09 | 0.134658E+09 | 81649034.27 | 0.266128E+09 | 0.113294E+09 |
February | 0.233211E+09 | 0.141698E+09 | 91513915.15 | 0.289269E+09 | 0.102303E+09 |
March | 0.308683E+09 | 0.186620E+09 | 0.122063E+09 | 0.384376E+09 | 0.117567E+09 |
April | 0.327378E+09 | 0.201792E+09 | 0.125586E+09 | 0.407895E+09 | 0.110399E+09 |
May | 0.366436E+09 | 0.231793E+09 | 0.134644E+09 | 0.459065E+09 | 0.107476E+09 |
June | 0.367322E+09 | 0.236460E+09 | 0.130862E+09 | 0.458316E+09 | 99372269.74 |
July | 0.384050E+09 | 0.262327E+09 | 0.121724E+09 | 0.481392E+09 | 96231955.17 |
August | 0.383076E+09 | 0.269761E+09 | 0.113315E+09 | 0.481988E+09 | 0.106060E+09 |
September | 0.334051E+09 | 0.210236E+09 | 0.123815E+09 | 0.420366E+09 | 96562367.18 |
October | 0.279609E+09 | 0.178201E+09 | 0.101408E+09 | 0.354824E+09 | 0.115575E+09 |
November | 0.226640E+09 | 0.137009E+09 | 89631410.02 | 0.283140E+09 | 0.103314E+09 |
December | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 0.104609E+09 |
Annual Sum or Average | 0.363316E+10 | 0.232008E+10 | 0.131308E+10 | 0.454091E+10 | 0.127276E+10 |
Minimum of Months | 0.206397E+09 | 0.129529E+09 | 76868390.67 | 0.254152E+09 | 96231955.17 |
Maximum of Months | 0.384050E+09 | 0.269761E+09 | 0.134644E+09 | 0.481988E+09 | 0.117567E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.02 | 228.52 | 99.86 | 26.23 | 73.63 | 0.00 | 0.00 |
February | 362.27 | 225.69 | 144.89 | 51.84 | 93.05 | 0.00 | 0.00 |
March | 421.39 | 213.07 | 161.06 | 52.86 | 108.20 | 0.00 | 0.00 |
April | 407.82 | 174.25 | 156.57 | 48.31 | 108.26 | 0.00 | 0.00 |
May | 465.86 | 133.96 | 160.59 | 45.99 | 114.60 | 0.00 | 0.00 |
June | 522.60 | 103.43 | 180.47 | 60.33 | 120.14 | 0.00 | 0.00 |
July | 551.02 | 84.36 | 176.43 | 61.84 | 114.59 | 0.00 | 0.00 |
August | 543.92 | 90.47 | 166.14 | 59.35 | 106.79 | 0.00 | 0.00 |
September | 577.73 | 85.79 | 185.39 | 67.32 | 118.07 | 0.00 | 0.00 |
October | 401.30 | 133.50 | 122.07 | 32.87 | 89.20 | 0.00 | 0.00 |
November | 326.54 | 157.47 | 115.78 | 35.72 | 80.06 | 0.00 | 0.00 |
December | 243.40 | 178.56 | 97.91 | 28.51 | 69.40 | 0.00 | 0.00 |
Annual Sum or Average | 421.23 | 150.36 | 147.15 | 47.50 | 99.64 | 0.00 | 0.00 |
Minimum of Months | 230.02 | 84.36 | 97.91 | 26.23 | 69.40 | 0.00 | 0.00 |
Maximum of Months | 577.73 | 228.52 | 185.39 | 67.32 | 120.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 993.60 | 422.99 | 807.60 | 502.75 | 304.84 | 0.00 | 0.00 |
February | 1195.72 | 422.87 | 964.00 | 585.72 | 378.28 | 0.00 | 0.00 |
March | 1435.09 | 438.92 | 1152.49 | 696.76 | 455.73 | 0.00 | 0.00 |
April | 1573.66 | 425.92 | 1263.03 | 778.52 | 484.51 | 0.00 | 0.00 |
May | 1713.94 | 401.26 | 1368.12 | 865.42 | 502.70 | 0.00 | 0.00 |
June | 1768.18 | 383.38 | 1417.14 | 912.27 | 504.87 | 0.00 | 0.00 |
July | 1797.31 | 359.29 | 1433.88 | 979.42 | 454.46 | 0.00 | 0.00 |
August | 1799.53 | 395.98 | 1430.24 | 1007.17 | 423.07 | 0.00 | 0.00 |
September | 1621.78 | 372.53 | 1288.78 | 811.10 | 477.68 | 0.00 | 0.00 |
October | 1324.75 | 431.50 | 1043.94 | 665.33 | 378.61 | 0.00 | 0.00 |
November | 1092.35 | 398.58 | 874.38 | 528.58 | 345.80 | 0.00 | 0.00 |
December | 948.89 | 390.56 | 770.60 | 483.61 | 286.99 | 0.00 | 0.00 |
Annual Sum or Average | 1439.91 | 403.58 | 1152.07 | 735.69 | 416.37 | 0.00 | 0.00 |
Minimum of Months | 948.89 | 359.29 | 770.60 | 483.61 | 286.99 | 0.00 | 0.00 |
Maximum of Months | 1799.53 | 438.92 | 1433.88 | 1007.17 | 504.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616080E+09 | 0.612066E+09 | 0.267464E+09 | 70246856.60 | 0.197217E+09 | 0.00 | 0.00 |
February | 0.876409E+09 | 0.545999E+09 | 0.350527E+09 | 0.125414E+09 | 0.225113E+09 | 0.00 | 0.00 |
March | 0.112866E+10 | 0.570693E+09 | 0.431391E+09 | 0.141582E+09 | 0.289809E+09 | 0.00 | 0.00 |
April | 0.105708E+10 | 0.451648E+09 | 0.405826E+09 | 0.125207E+09 | 0.280618E+09 | 0.00 | 0.00 |
May | 0.124776E+10 | 0.358795E+09 | 0.430115E+09 | 0.123183E+09 | 0.306932E+09 | 0.00 | 0.00 |
June | 0.135457E+10 | 0.268082E+09 | 0.467776E+09 | 0.156376E+09 | 0.311399E+09 | 0.00 | 0.00 |
July | 0.147586E+10 | 0.225949E+09 | 0.472542E+09 | 0.165623E+09 | 0.306919E+09 | 0.00 | 0.00 |
August | 0.145684E+10 | 0.242321E+09 | 0.444991E+09 | 0.158963E+09 | 0.286028E+09 | 0.00 | 0.00 |
September | 0.149746E+10 | 0.222361E+09 | 0.480539E+09 | 0.174500E+09 | 0.306039E+09 | 0.00 | 0.00 |
October | 0.107484E+10 | 0.357567E+09 | 0.326946E+09 | 88028255.48 | 0.238917E+09 | 0.00 | 0.00 |
November | 0.846404E+09 | 0.408163E+09 | 0.300106E+09 | 92585976.19 | 0.207520E+09 | 0.00 | 0.00 |
December | 0.651909E+09 | 0.478259E+09 | 0.262247E+09 | 76366216.28 | 0.185881E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132839E+11 | 0.474190E+10 | 0.464047E+10 | 0.149808E+10 | 0.314239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.616080E+09 | 0.222361E+09 | 0.262247E+09 | 70246856.60 | 0.185881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149746E+10 | 0.612066E+09 | 0.480539E+09 | 0.174500E+09 | 0.311399E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266127E+10 | 0.113294E+10 | 0.216307E+10 | 0.134658E+10 | 0.816490E+09 | 0.00 | 0.00 |
February | 0.289268E+10 | 0.102301E+10 | 0.233211E+10 | 0.141698E+10 | 0.915139E+09 | 0.00 | 0.00 |
March | 0.384373E+10 | 0.117559E+10 | 0.308683E+10 | 0.186620E+10 | 0.122063E+10 | 0.00 | 0.00 |
April | 0.407893E+10 | 0.110399E+10 | 0.327378E+10 | 0.201792E+10 | 0.125586E+10 | 0.00 | 0.00 |
May | 0.459062E+10 | 0.107474E+10 | 0.366436E+10 | 0.231793E+10 | 0.134644E+10 | 0.00 | 0.00 |
June | 0.458312E+10 | 0.993723E+09 | 0.367322E+10 | 0.236460E+10 | 0.130862E+10 | 0.00 | 0.00 |
July | 0.481391E+10 | 0.962309E+09 | 0.384050E+10 | 0.262327E+10 | 0.121724E+10 | 0.00 | 0.00 |
August | 0.481985E+10 | 0.106058E+10 | 0.383076E+10 | 0.269761E+10 | 0.113315E+10 | 0.00 | 0.00 |
September | 0.420364E+10 | 0.965609E+09 | 0.334051E+10 | 0.210236E+10 | 0.123815E+10 | 0.00 | 0.00 |
October | 0.354822E+10 | 0.115574E+10 | 0.279609E+10 | 0.178201E+10 | 0.101408E+10 | 0.00 | 0.00 |
November | 0.283138E+10 | 0.103313E+10 | 0.226640E+10 | 0.137009E+10 | 0.896314E+09 | 0.00 | 0.00 |
December | 0.254152E+10 | 0.104608E+10 | 0.206397E+10 | 0.129529E+10 | 0.768684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.454089E+11 | 0.127274E+11 | 0.363316E+11 | 0.232008E+11 | 0.131308E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254152E+10 | 0.962309E+09 | 0.206397E+10 | 0.129529E+10 | 0.768684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.481985E+10 | 0.117559E+10 | 0.384050E+10 | 0.269761E+10 | 0.134644E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 22.49 | 18.25 | 15.90 | 4.15 | 13.31 | 59.87 | 181.51 | 0.00 |
February | 22.80 | 19.74 | 18.20 | 3.70 | 14.21 | 74.30 | 182.84 | 0.03 |
March | 23.17 | 18.99 | 16.85 | 4.23 | 14.23 | 89.51 | 186.76 | 0.02 |
April | 23.76 | 19.01 | 16.50 | 4.83 | 14.94 | 95.22 | 199.35 | 0.00 |
May | 25.23 | 20.49 | 18.23 | 4.38 | 17.08 | 98.73 | 213.00 | 0.00 |
June | 25.87 | 20.89 | 18.70 | 5.87 | 17.20 | 99.16 | 227.55 | 0.00 |
July | 26.90 | 21.77 | 19.49 | 5.98 | 18.80 | 89.26 | 241.04 | 0.00 |
August | 27.06 | 21.88 | 19.61 | 5.21 | 18.26 | 83.09 | 253.22 | 0.00 |
September | 26.87 | 22.30 | 20.37 | 5.44 | 18.71 | 93.82 | 214.78 | 0.00 |
October | 26.22 | 21.67 | 19.68 | 3.78 | 17.26 | 74.41 | 199.79 | 0.00 |
November | 24.76 | 20.57 | 18.62 | 5.17 | 16.20 | 67.97 | 175.93 | 0.00 |
December | 23.69 | 19.64 | 17.67 | 4.42 | 14.96 | 56.37 | 177.80 | 0.00 |
Annual Sum or Average | 24.91 | 20.44 | 18.32 | 4.77 | 16.27 | 81.79 | 204.64 | 0.00 |
Minimum of Months | 22.49 | 18.25 | 15.90 | 3.70 | 13.31 | 56.37 | 175.93 | 0.00 |
Maximum of Months | 27.06 | 22.30 | 20.37 | 5.98 | 18.80 | 99.16 | 253.22 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.40 | 03-JAN-12:00 | 22.05 | 18.90 | 3.60 | 19.35 | 145.50 | 575.00 |
February | 28.90 | 19-FEB-10:00 | 22.34 | 19.40 | 3.10 | 18.28 | 204.00 | 595.50 |
March | 30.00 | 29-MAR-12:00 | 20.05 | 15.00 | 6.70 | 20.22 | 350.50 | 543.50 |
April | 30.00 | 09-APR-13:00 | 20.06 | 15.00 | 7.20 | 17.39 | 126.00 | 778.50 |
May | 31.10 | 17-MAY-13:20 | 21.31 | 16.70 | 7.87 | 22.12 | 283.17 | 716.50 |
June | 30.60 | 26-JUN-13:00 | 21.72 | 17.80 | 6.70 | 20.40 | 162.00 | 756.50 |
July | 32.20 | 09-JUL-11:00 | 23.42 | 20.00 | 6.20 | 23.49 | 235.00 | 733.00 |
August | 32.80 | 11-AUG-13:00 | 23.28 | 19.40 | 6.20 | 23.99 | 228.00 | 563.00 |
September | 33.30 | 02-SEP-12:00 | 23.47 | 19.40 | 5.70 | 23.32 | 185.00 | 789.00 |
October | 33.30 | 01-OCT-12:00 | 23.04 | 18.90 | 6.20 | 23.15 | 143.50 | 854.50 |
November | 30.60 | 03-NOV-12:00 | 22.49 | 18.90 | 7.70 | 20.57 | 148.00 | 798.50 |
December | 30.60 | 13-DEC-13:00 | 22.11 | 18.30 | 5.70 | 18.64 | 59.00 | 832.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 20.05 | 15.00 | 3.10 | 17.39 | 59.00 | 543.50 | |
Maximum of Months | 33.30 | 23.47 | 20.00 | 7.87 | 23.99 | 350.50 | 854.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.20 | 07-JAN-06:00 | 15.82 | 15.00 | 1.50 | 3.89 | 0.00 | 0.00 |
February | 13.30 | 12-FEB-06:00 | 12.64 | 12.20 | 3.10 | 0.73 | 0.00 | 0.00 |
March | 15.00 | 08-MAR-03:00 | 13.29 | 12.20 | 0.00 | 1.16 | 0.00 | 0.00 |
April | 17.80 | 22-APR-02:00 | 16.39 | 15.60 | 0.00 | 6.75 | 0.00 | 0.00 |
May | 18.90 | 23-MAY-05:00 | 17.45 | 16.70 | 2.10 | 9.33 | 110.00 | 159.50 |
June | 21.10 | 06-JUN-04:00 | 19.20 | 18.30 | 2.60 | 9.52 | 0.00 | 0.00 |
July | 22.20 | 09-JUL-03:00 | 20.00 | 18.90 | 1.50 | 11.84 | 0.00 | 0.00 |
August | 21.10 | 18-AUG-05:00 | 19.93 | 19.40 | 2.10 | 8.54 | 0.00 | 0.00 |
September | 22.20 | 19-SEP-04:00 | 20.25 | 19.40 | 2.60 | 11.84 | 0.00 | 0.00 |
October | 19.40 | 19-OCT-05:00 | 17.58 | 16.70 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 16.10 | 27-NOV-06:00 | 15.39 | 15.00 | 2.60 | 5.74 | 50.00 | 566.00 |
December | 16.70 | 26-DEC-01:00 | 15.01 | 13.90 | 2.60 | 4.31 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 12.64 | 12.20 | 0.00 | 0.73 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 20.25 | 19.40 | 3.10 | 11.84 | 110.00 | 566.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.03 | 01-JAN-15:00 | 27.80 | 21.10 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 24.57 | 18-FEB-13:00 | 27.80 | 23.30 | 4.10 | 21.44 | 268.00 | 307.00 |
March | 23.81 | 13-MAR-12:00 | 27.80 | 22.20 | 5.70 | 22.47 | 468.50 | 259.00 |
April | 22.82 | 24-APR-11:00 | 28.30 | 20.60 | 4.60 | 19.87 | 357.00 | 446.00 |
May | 23.35 | 08-MAY-15:00 | 28.90 | 21.10 | 6.20 | 22.13 | 182.00 | 323.50 |
June | 23.02 | 20-JUN-13:00 | 28.90 | 20.60 | 7.70 | 21.96 | 370.50 | 346.50 |
July | 24.68 | 20-JUL-13:00 | 26.70 | 23.90 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 25.47 | 19-AUG-14:00 | 31.70 | 23.30 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 25.16 | 23-SEP-14:00 | 27.20 | 24.40 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 24.72 | 15-OCT-13:00 | 31.70 | 22.20 | 5.20 | 22.98 | 151.50 | 527.00 |
November | 23.46 | 02-NOV-09:00 | 29.40 | 21.10 | 6.20 | 20.57 | 236.50 | 546.50 |
December | 23.69 | 03-DEC-10:00 | 26.10 | 22.80 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.82 | 26.10 | 20.60 | 4.10 | 19.87 | 91.00 | 3.00 | |
Maximum of Months | 25.47 | 31.70 | 24.40 | 8.20 | 25.33 | 468.50 | 546.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 01-JAN-15:00 | 27.80 | 23.03 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 23.30 | 16-FEB-17:00 | 24.40 | 23.65 | 3.10 | 22.98 | 29.50 | 4.00 |
March | 22.20 | 13-MAR-10:00 | 27.20 | 23.57 | 4.60 | 21.78 | 336.00 | 148.00 |
April | 21.10 | 24-APR-23:00 | 22.80 | 21.58 | 1.50 | 18.82 | 0.00 | 0.00 |
May | 22.20 | 09-MAY-23:00 | 24.40 | 22.88 | 1.50 | 22.64 | 0.00 | 0.00 |
June | 20.80 | 09-JUN-00:10 | 22.15 | 21.03 | 3.78 | 18.14 | 0.00 | 0.00 |
July | 23.90 | 20-JUL-13:00 | 26.70 | 24.68 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 23.30 | 19-AUG-14:00 | 31.70 | 25.47 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 24.40 | 23-SEP-14:00 | 27.20 | 25.16 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 22.80 | 24-OCT-12:00 | 26.10 | 23.69 | 4.10 | 19.70 | 259.00 | 474.50 |
November | 21.70 | 29-NOV-17:00 | 26.10 | 22.98 | 3.10 | 22.13 | 0.00 | 0.00 |
December | 22.80 | 03-DEC-10:00 | 26.10 | 23.69 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.80 | 22.15 | 21.03 | 1.50 | 18.14 | 0.00 | 0.00 | |
Maximum of Months | 24.40 | 31.70 | 25.47 | 8.20 | 25.33 | 336.00 | 474.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 26.59 | 31.34 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 26.78 | 37.09 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 27.35 | 43.34 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 28.17 | 47.38 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.01 | 50.82 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.64 | 52.70 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.71 | 53.00 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.13 | 48.47 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.31 | 39.62 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.47 | 33.78 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 26.84 | 30.10 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.25 | 43.42 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 26.59 | 30.10 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.710219E+09 | -578590385.7 | 0.00 | 0.00 | 744.00 | 0.00 | -131628221.0 | 58.99 | 0.00 | 0.00 |
February | 0.647317E+09 | -528527386.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118789514.4 | 58.99 | 0.00 | 0.00 |
March | 0.738870E+09 | -606835576.1 | 0.00 | 0.00 | 744.00 | 0.00 | -132034412.2 | 58.99 | 0.00 | 0.00 |
April | 0.676483E+09 | -549202811.8 | 0.00 | 0.00 | 720.00 | 0.00 | -127280574.5 | 58.99 | 0.00 | 0.00 |
May | 0.686659E+09 | -555605684.8 | 0.00 | 0.00 | 744.00 | 0.00 | -131053547.1 | 58.99 | 0.00 | 0.00 |
June | 0.669337E+09 | -542163437.7 | 0.00 | 0.00 | 720.00 | 0.00 | -127173571.0 | 58.99 | 0.00 | 0.00 |
July | 0.649609E+09 | -519426081.5 | 0.00 | 0.00 | 744.00 | 0.00 | -130183086.2 | 58.99 | 0.00 | 0.00 |
August | 0.692851E+09 | -561509890.5 | 0.00 | 0.00 | 744.00 | 0.00 | -131341579.1 | 58.99 | 0.00 | 0.00 |
September | 0.658657E+09 | -532315498.3 | 0.00 | 0.00 | 720.00 | 0.00 | -126341457.2 | 58.99 | 0.00 | 0.00 |
October | 0.678632E+09 | -548228092.8 | 0.00 | 0.00 | 744.00 | 0.00 | -130403669.3 | 58.99 | 0.00 | 0.00 |
November | 0.667301E+09 | -540714942.7 | 0.00 | 0.00 | 720.00 | 0.00 | -126585943.8 | 58.99 | 0.00 | 0.00 |
December | 0.705403E+09 | -574019250.7 | 0.00 | 0.00 | 744.00 | 0.00 | -131383386.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.818134E+10 | -.663714E+10 | 8760.00 | -.154420E+10 | 58.99 | |||||
Minimum of Months | 0.647317E+09 | -606835576.1 | 0.00 | 0.00 | 672.00 | 0.00 | -132034412.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.738870E+09 | -519426081.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118789514.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 326.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 316.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 318.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4207.17 | ||||||||||
Minimum of Months | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.106696E+11 | 0.853897E+10 | 28517.57 | 02-JAN-00:01 | 17588.45 | 0.00 |
February | 0.00 | 0.00 | 0.117116E+11 | 0.875426E+10 | 28744.95 | 21-FEB-00:01 | 17468.84 | 0.00 |
March | 0.00 | 0.00 | 0.137400E+11 | 0.108439E+11 | 28249.33 | 13-MAR-00:01 | 18132.41 | 0.00 |
April | 0.00 | 0.00 | 0.131587E+11 | 0.106049E+11 | 27185.77 | 17-APR-00:01 | 18389.73 | 0.00 |
May | 0.00 | 0.00 | 0.162684E+11 | 0.127881E+11 | 28273.33 | 15-MAY-00:01 | 18184.86 | 0.00 |
June | 0.00 | 0.00 | 0.171724E+11 | 0.132732E+11 | 27818.26 | 19-JUN-00:01 | 19242.25 | 0.00 |
July | 0.00 | 0.00 | 0.183572E+11 | 0.140171E+11 | 29095.81 | 24-JUL-00:01 | 17334.04 | 0.00 |
August | 0.00 | 0.00 | 0.195239E+11 | 0.150136E+11 | 28021.04 | 07-AUG-00:01 | 18859.34 | 0.00 |
September | 0.00 | 0.00 | 0.185408E+11 | 0.139352E+11 | 28730.86 | 11-SEP-00:01 | 17695.18 | 0.00 |
October | 0.00 | 0.00 | 0.165801E+11 | 0.126316E+11 | 29122.71 | 10-OCT-00:01 | 17609.61 | 0.00 |
November | 0.00 | 0.00 | 0.142589E+11 | 0.107985E+11 | 28419.95 | 06-NOV-00:01 | 18087.62 | 0.00 |
December | 0.00 | 0.00 | 0.126864E+11 | 0.976988E+10 | 27982.77 | 18-DEC-00:01 | 17328.81 | 0.00 |
Annual Sum or Average | 0.182668E+12 | 0.140969E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.106696E+11 | 0.853897E+10 | 27185.77 | 17328.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195239E+11 | 0.150136E+11 | 29122.71 | 19242.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202618E+11 | 0.160310E+11 | 94144.33 | 01-JAN-10:53 | 64096.67 | 0.00 |
February | 0.00 | 0.00 | 0.247714E+11 | 0.182501E+11 | 95286.12 | 20-FEB-10:53 | 63229.37 | 0.00 |
March | 0.00 | 0.00 | 0.313643E+11 | 0.245765E+11 | 96318.44 | 12-MAR-11:53 | 61491.44 | 0.00 |
April | 0.00 | 0.00 | 0.322855E+11 | 0.258598E+11 | 93003.66 | 09-APR-10:03 | 67176.41 | 0.00 |
May | 0.00 | 0.00 | 0.472151E+11 | 0.368969E+11 | 99076.30 | 15-MAY-00:07 | 60388.67 | 0.00 |
June | 0.00 | 0.00 | 0.508076E+11 | 0.386785E+11 | 96255.98 | 25-JUN-08:53 | 62797.29 | 0.00 |
July | 0.00 | 0.00 | 0.622233E+11 | 0.466095E+11 | 97300.16 | 23-JUL-08:43 | 60005.64 | 0.00 |
August | 0.00 | 0.00 | 0.642463E+11 | 0.487367E+11 | 95149.17 | 20-AUG-08:33 | 62227.38 | 0.00 |
September | 0.00 | 0.00 | 0.613201E+11 | 0.447044E+11 | 98836.86 | 10-SEP-08:53 | 58338.80 | 0.00 |
October | 0.00 | 0.00 | 0.494677E+11 | 0.373223E+11 | 95731.66 | 01-OCT-08:53 | 60426.07 | 0.00 |
November | 0.00 | 0.00 | 0.346693E+11 | 0.257385E+11 | 99341.38 | 06-NOV-00:06 | 59394.95 | 0.00 |
December | 0.00 | 0.00 | 0.263590E+11 | 0.197923E+11 | 98990.35 | 17-DEC-12:42 | 61594.56 | 0.00 |
Annual Sum or Average | 0.504991E+12 | 0.383197E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.202618E+11 | 0.160310E+11 | 93003.66 | 58338.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.642463E+11 | 0.487367E+11 | 99341.38 | 67176.41 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151631E+10 | 0.57 | 1370.15 | 24-JAN-08:28 | 0.93 |
February | 0.143186E+10 | 0.62 | 1370.15 | 07-FEB-10:10 | 0.93 |
March | 0.169684E+10 | 0.67 | 1370.15 | 15-MAR-06:10 | 0.93 |
April | 0.158432E+10 | 0.66 | 1370.15 | 01-APR-07:00 | 0.93 |
May | 0.169878E+10 | 0.69 | 1370.15 | 01-MAY-06:30 | 0.93 |
June | 0.172193E+10 | 0.72 | 1370.15 | 01-JUN-06:20 | 0.92 |
July | 0.170624E+10 | 0.69 | 1370.15 | 01-JUL-06:10 | 0.93 |
August | 0.182908E+10 | 0.74 | 1370.15 | 01-AUG-06:15 | 0.92 |
September | 0.172089E+10 | 0.72 | 1370.15 | 01-SEP-06:30 | 0.92 |
October | 0.164946E+10 | 0.67 | 1370.15 | 02-OCT-06:10 | 0.93 |
November | 0.154267E+10 | 0.65 | 1370.15 | 17-NOV-07:45 | 0.92 |
December | 0.156184E+10 | 0.62 | 1370.15 | 22-DEC-10:03 | 0.93 |
Annual Sum or Average | 0.196602E+11 | 0.67 | |||
Minimum of Months | 0.143186E+10 | 0.57 | 1370.15 | 0.92 | |
Maximum of Months | 0.182908E+10 | 0.74 | 1370.15 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.683539E+10 | 0.63 | 6768.58 | 02-JAN-11:30 | 1.55 |
February | 0.638274E+10 | 0.67 | 6768.58 | 01-FEB-08:35 | 1.54 |
March | 0.755758E+10 | 0.74 | 6768.58 | 01-MAR-07:55 | 1.54 |
April | 0.706357E+10 | 0.74 | 6768.58 | 01-APR-11:40 | 1.56 |
May | 0.771843E+10 | 0.89 | 6768.58 | 01-MAY-08:00 | 1.55 |
June | 0.780071E+10 | 0.94 | 6768.58 | 02-JUN-08:33 | 1.54 |
July | 0.820204E+10 | 1.09 | 6768.58 | 01-JUL-09:45 | 1.55 |
August | 0.857624E+10 | 1.12 | 6768.58 | 02-AUG-11:30 | 1.55 |
September | 0.822758E+10 | 1.13 | 6768.58 | 01-SEP-07:10 | 1.54 |
October | 0.764331E+10 | 0.92 | 6768.58 | 02-OCT-07:30 | 1.54 |
November | 0.683162E+10 | 0.71 | 6768.58 | 06-NOV-09:05 | 1.54 |
December | 0.686794E+10 | 0.65 | 6768.58 | 01-DEC-10:30 | 1.55 |
Annual Sum or Average | 0.897071E+11 | 0.85 | |||
Minimum of Months | 0.638274E+10 | 0.63 | 6768.58 | 1.54 | |
Maximum of Months | 0.857624E+10 | 1.13 | 6768.58 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.17 | 0.00 |
March | 0.00 | 0.00 |
April | 0.14 | 0.00 |
May | 0.22 | 0.00 |
June | 0.00 | 0.00 |
July | 0.14 | 0.00 |
August | 0.03 | 0.00 |
September | 0.15 | 0.00 |
October | 0.08 | 0.00 |
November | 0.14 | 0.00 |
December | 0.22 | 0.00 |
Annual Sum or Average | 1.29 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.22 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 13.74 | 0.00 |
February | 9.43 | 0.00 |
March | 9.78 | 0.00 |
April | 7.39 | 0.00 |
May | 7.68 | 0.00 |
June | 6.01 | 0.00 |
July | 9.49 | 0.00 |
August | 9.30 | 0.00 |
September | 6.12 | 0.00 |
October | 5.33 | 0.00 |
November | 7.82 | 0.00 |
December | 9.61 | 0.00 |
Annual Sum or Average | 101.72 | |
Minimum of Months | 5.33 | 0.00 |
Maximum of Months | 13.74 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.438857E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.455604E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.539978E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.514188E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.613985E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.639344E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.675374E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.724454E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.679533E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.622520E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.540629E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.498276E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.694274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438857E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.724454E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127718E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135358E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167076E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.165121E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.216528E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226828E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.266650E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.277629E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.262953E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224501E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170108E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145524E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238600E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127718E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.277629E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151631E+10 | 0.106696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143186E+10 | 0.117116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169684E+10 | 0.137400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158432E+10 | 0.131587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169878E+10 | 0.162684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172193E+10 | 0.171724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170624E+10 | 0.183572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182908E+10 | 0.195239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172089E+10 | 0.185408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164946E+10 | 0.165801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154267E+10 | 0.142589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156184E+10 | 0.126864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196602E+11 | 0.182668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143186E+10 | 0.106696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182908E+10 | 0.195239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.683539E+10 | 0.202618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.638274E+10 | 0.247714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755758E+10 | 0.313643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706357E+10 | 0.322855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.771843E+10 | 0.472151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.780071E+10 | 0.508076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820204E+10 | 0.622233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.857624E+10 | 0.642463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.822758E+10 | 0.613201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764331E+10 | 0.494677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683162E+10 | 0.346693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686794E+10 | 0.263590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897071E+11 | 0.504991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.638274E+10 | 0.202618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.857624E+10 | 0.642463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.151631E+10 | 0.00 | 0.00 | 0.00 | 0.287226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143186E+10 | 0.00 | 0.00 | 0.00 | 0.312418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169684E+10 | 0.00 | 0.00 | 0.00 | 0.370294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158432E+10 | 0.00 | 0.00 | 0.00 | 0.355756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169878E+10 | 0.00 | 0.00 | 0.00 | 0.444107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172193E+10 | 0.00 | 0.00 | 0.00 | 0.467151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170624E+10 | 0.00 | 0.00 | 0.00 | 0.504750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182908E+10 | 0.00 | 0.00 | 0.00 | 0.541546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172089E+10 | 0.00 | 0.00 | 0.00 | 0.507444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164946E+10 | 0.00 | 0.00 | 0.00 | 0.457574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154267E+10 | 0.00 | 0.00 | 0.00 | 0.386361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156184E+10 | 0.00 | 0.00 | 0.00 | 0.342091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196602E+11 | 0.00 | 0.00 | 0.00 | 0.497672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143186E+10 | 0.00 | 0.00 | 0.00 | 0.287226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182908E+10 | 0.00 | 0.00 | 0.00 | 0.541546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.683539E+10 | 0.00 | 0.00 | 0.00 | 0.593637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.638274E+10 | 0.00 | 0.00 | 0.00 | 0.715309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755758E+10 | 0.00 | 0.00 | 0.00 | 0.915004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706357E+10 | 0.00 | 0.00 | 0.00 | 0.944852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.771843E+10 | 0.00 | 0.00 | 0.00 | 0.139344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.780071E+10 | 0.00 | 0.00 | 0.00 | 0.148821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820204E+10 | 0.00 | 0.00 | 0.00 | 0.184630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.857624E+10 | 0.00 | 0.00 | 0.00 | 0.191867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.822758E+10 | 0.00 | 0.00 | 0.00 | 0.180678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764331E+10 | 0.00 | 0.00 | 0.00 | 0.148068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683162E+10 | 0.00 | 0.00 | 0.00 | 0.101792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686794E+10 | 0.00 | 0.00 | 0.00 | 0.768451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897071E+11 | 0.00 | 0.00 | 0.00 | 0.148892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.638274E+10 | 0.00 | 0.00 | 0.00 | 0.593637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.857624E+10 | 0.00 | 0.00 | 0.00 | 0.191867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1594373.28 | 0.101167E+10 | 0.00 | 2646044.11 | 1505212.45 | 0.00 | 23149539.19 | 0.00 | 0.18 |
February | 4491687.78 | 0.155151E+10 | 0.00 | 1551452.31 | 703699.66 | 0.00 | 13474737.40 | 0.00 | 0.19 |
March | 7402263.50 | 0.152147E+10 | 0.00 | 1800665.68 | 523195.29 | 0.00 | 16666778.40 | 0.00 | 0.20 |
April | 79488.55 | 0.138700E+10 | 0.00 | 903398.20 | 724406.16 | 0.00 | 5822738.86 | 0.00 | 0.19 |
May | 0.00 | 0.218510E+10 | 0.00 | 585189.41 | 91301.66 | 0.00 | 53092.64 | 0.00 | 0.20 |
June | 0.00 | 0.235010E+10 | 0.00 | 240350.47 | 0.00 | 0.00 | 78784.03 | 0.00 | 0.21 |
July | 0.00 | 0.277722E+10 | 0.00 | 142887.13 | 0.00 | 0.00 | 15153.47 | 0.00 | 0.20 |
August | 0.00 | 0.305539E+10 | 0.00 | 107974.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.295799E+10 | 0.00 | 52865.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.265453E+10 | 0.00 | 314153.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
November | 559338.61 | 0.198260E+10 | 0.00 | 716045.87 | 122811.76 | 0.00 | 1237404.87 | 0.00 | 0.19 |
December | 1804832.06 | 0.164541E+10 | 0.00 | 1603027.84 | 641693.54 | 0.00 | 5754185.79 | 0.00 | 0.18 |
Annual Sum or Average | 15931983.78 | 0.250800E+11 | 0.00 | 10664053.99 | 4312320.52 | 0.00 | 66252414.65 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.101167E+10 | 0.00 | 52865.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 7402263.50 | 0.305539E+10 | 0.00 | 2646044.11 | 1505212.45 | 0.00 | 23149539.19 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.363087E+09 | 0.146027E+10 | 0.00 | 6166651.65 | 995189.86 | 0.00 | 0.209979E+09 | 0.00 | 0.17 |
February | 0.239351E+09 | 0.246671E+10 | 0.00 | 4884314.78 | 1613626.09 | 0.00 | 0.118146E+09 | 0.00 | 0.17 |
March | 0.324325E+09 | 0.233649E+10 | 0.00 | 3534103.29 | 0.00 | 0.00 | 0.125233E+09 | 0.00 | 0.19 |
April | 0.185363E+09 | 0.218752E+10 | 0.00 | 3988918.35 | 0.00 | 0.00 | 0.118653E+09 | 0.00 | 0.18 |
May | 24350738.28 | 0.411085E+10 | 0.00 | 2365324.04 | 0.00 | 0.00 | 64797792.71 | 0.00 | 0.19 |
June | 4504877.87 | 0.417778E+10 | 0.00 | 1589459.85 | 0.00 | 0.00 | 33601817.35 | 0.00 | 0.20 |
July | 0.00 | 0.550176E+10 | 0.00 | 1838106.11 | 0.00 | 0.00 | 26409877.05 | 0.00 | 0.20 |
August | 1948459.76 | 0.613031E+10 | 0.00 | 1233101.13 | 0.00 | 0.00 | 25666812.24 | 0.00 | 0.21 |
September | 0.00 | 0.581119E+10 | 0.00 | 598166.60 | 0.00 | 0.00 | 11295924.11 | 0.00 | 0.21 |
October | 45150858.18 | 0.535007E+10 | 0.00 | 879554.78 | 0.00 | 0.00 | 73179298.41 | 0.00 | 0.19 |
November | 57030687.85 | 0.329222E+10 | 0.00 | 1238482.39 | 53339.90 | 0.00 | 41186744.11 | 0.00 | 0.17 |
December | 0.171053E+09 | 0.255124E+10 | 0.00 | 4191555.32 | 328309.54 | 0.00 | 0.116864E+09 | 0.00 | 0.17 |
Annual Sum or Average | 0.141616E+10 | 0.453764E+11 | 0.00 | 32507738.28 | 2990465.39 | 0.00 | 0.965013E+09 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.146027E+10 | 0.00 | 598166.60 | 0.00 | 0.00 | 11295924.11 | 0.00 | 0.17 |
Maximum of Months | 0.363087E+09 | 0.613031E+10 | 0.00 | 6166651.65 | 1613626.09 | 0.00 | 0.209979E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |