Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1705.47 | 352.72 | 352.72 |
Net Site Energy | 1705.47 | 352.72 | 352.72 |
Total Source Energy | 3332.30 | 689.18 | 689.18 |
Net Source Energy | 3332.30 | 689.18 | 689.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 993.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 398.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 712.23 | 993.24 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 993.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 398.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 83.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 55.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.26 | 205.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.30 | 205.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.26 | 205.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.30 | 205.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 712.227 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 712.227 | 100.00 |
Total On-Site and Utility Electric Sources | 712.227 | 100.00 |
Total Electricity End Uses | 712.227 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 61.83 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2194.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.6875 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:00 | 05-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 334825.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10975.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28324.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6058.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1772.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57185.38 | 334825.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 334825.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10975.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28324.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3753.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1772.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1076.68 | 0.00 | 0.00 | 0.00 |
Cooling | 29.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1261.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 264.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2255.62 | 1076.68 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 222.68 | 0.00 | 0.00 | 0.00 |
Cooling | 6.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 260.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 466.51 | 222.68 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 222.68 | 0.00 | 0.00 | 0.00 |
Cooling | 6.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 260.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 466.51 | 222.68 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.03 |
ZONE2 FINE STORAGE DIRECT AIR | 2.45 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 5.02 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 5.02 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 182568.98 |
PSZ-OFFICE HEATING COIL | 25828.74 |
PSZ-FINE STORAGE HEATING COIL | 82696.42 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 182568.97 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-FINE STORAGE | 2.45 | 2.45 | 2.45 | 2.45 | 2.45 | 2.45 | 1.00 | 1.00 | 2.45 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.03 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.45 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 16974.01 | 25828.74 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.45 | 2.45 | 2.45 | 2.45 | 47963.21 | 82696.42 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.03 | 0.512700 | 0.683600 | 16974.01 | 16974.01 | 8487.00 | 8487.00 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.45 | 1.22 | 1.63 | 42275.10 | 47963.21 | 23981.60 | 23981.60 | 0.741496 | 0.741500 | 0.741500 | 0.741500 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.03 | 1135.28 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.45 | 2618.40 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 9.688 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.761 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2294.776 | 9.688 | 458.955 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2294.776 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 14248.610 | 10.226 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.610 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 20008.048 | 6.243 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.048 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4332 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.309 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.53503428E-11 | 0.43487872E-15 | 0.25437469E-15 | 0.0000000 |
5 | 1 | -5.2159992 | 0.41060176E-04 | -0.36984335E-04 | 0.68788638E-11 |
6 | 0 | 5.6491605 | 0.43312021 | 0.43319826 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.709 | 8.453E-004 | 5.521E-004 | 0.276 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9084.36655 | 10901.23986 | 0.85450 | 1.02540 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11740.61515 | 14088.73818 | 0.37698 | 0.45238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27811.96659 | 33374.35991 | 2.03916 | 2.44699 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.26593E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 44523.97550 | 53428.77059 | 1.20368 | 1.44442 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 152140.80747 | 182568.96897 | 4.18735 | 5.02481 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13698.61 | 1.02540 | 1.02540 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14337.72 | 0.45238 | 0.45238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 41037.78 | 2.44699 | 2.44699 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 56761.38 | 1.44442 | 1.44442 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02540 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.44699 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.02481 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.02481 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 182568.97818 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 182568.96897 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02540 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02540 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02540 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02540 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02540 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.02540 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44699 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.44699 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.44699 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44699 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.44699 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.44699 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.02540 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.44699 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02540 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02540 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02540 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02540 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02540 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02540 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51270 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68360 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16974.01093 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16974.01000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8487.00500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8487.00500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16974.01000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25828.73811 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02540 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1135.28061 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25828.73811 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.44699 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.44699 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.44699 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.44699 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.44699 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.44699 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22350 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.63133 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 42275.10163 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 47963.21000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 23981.60500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23981.60500 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74150 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74150 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74150 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74150 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47963.21000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 82696.41588 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.44699 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2618.39817 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 82696.41588 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16178.3 | 11.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 46063.2 | 15.33 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1649410661 | 0.1593263232 | Pass | Pass | 7.4177745309 | 55.7492006952 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4792514290 | 0.4712558898 | Pass | Pass | 0.9250532571 | 2.8669792412 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.8685221529E-003 | 1.1714408107E-002 | Pass | Pass | 6.2680768277E-002 | 0.1354243668 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.409 | 0.433 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.788 | 0.497 | 0.500 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 45.81 | 5.064 | 0.512 | 0.514 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 9.6875 | 236.88 | 2294.78 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 58.77 | 168.00 | 50.55 | 0.0000 | Y | 21.77 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 10.2257 | 1393.41 | 14248.61 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 6.2431 | 3204.84 | 20008.05 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 57.07 | 0.0000 | Y | 214.34 |
Interior Lighting Total | 7.5596 | 4835.13 | 36551.43 | 398.39 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.05 | 2320.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 42.11 | 42.11 | 0.90 | |
EXTERIOR_LIGHTS_B | 6197.40 | AstronomicalClock | - | 83.57 | 71.13 | 82.75 | |
Exterior Lighting Total | 6311.20 | 83.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16974.01 | 13556.46 | 3417.55 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47963.21 | 35564.72 | 12398.49 | 0.74 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16178.3 | 11.41 | ||||
PSZ-FINE STORAGE COOLING COIL | 46063.2 | 15.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 182568.98 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25828.74 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 82696.42 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.02 | 466.86 | 92.91 | 1.00 | 3.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1135.28 | 1107.16 | 1.00 | 1.40 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.45 | 2618.40 | 1070.05 | 1.00 | 1.29 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9084.37 | 10901.24 | 46.02 | 0.855 | 1.025 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00809 | 31.16 | 0.00627 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27811.97 | 33374.36 | 23.95 | 2.039 | 2.447 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00788 | 33.24 | 0.00627 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11740.62 | 14088.74 | 59.48 | 0.377 | 0.452 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00782 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 44523.98 | 53428.77 | 38.34 | 1.204 | 1.444 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00665 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 152140.81 | 182568.97 | 56.97 | 4.187 | 5.025 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00873 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.03 | 1.03 | 0.45 | 0.45 | 1.0254 | 1.0254 | 1.0254 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.45 | 2.45 | 1.44 | 1.44 | 2.4470 | 2.4470 | 2.4470 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 182568.978 | 182568.978 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 182568.98 | 182568.98 | 5.024815 | 2.68 | 2.68 | 0.00710186 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.99 | 0.00873315 | 100.0000 | 182568.97 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 8487.005 | 0.000 | 1.025400 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8487.00 | 8487.00 | 1.025400 | 24.62 | 14.72 | 0.00790460 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 9.9751 | 23.90 | 0.00808617 | 38.3245 | 9084.37 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25828.738 | 25828.738 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25828.74 | 25828.74 | 1.025400 | 10.05 | 7.29 | 0.00613178 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 9.9751 | 21.10 | 0.00782339 | 43.9761 | 11740.62 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 23981.605 | 0.000 | 2.446990 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23981.60 | 23981.60 | 2.446990 | 27.86 | 15.56 | 0.00759750 | 12.00 | 10.08 | 0.00800000 | 33.40 | 0.00626594 | 16.30 | 17.3565 | 26.70 | 0.00787775 | 31.6179 | 27782.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 82696.416 | 82696.416 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82696.42 | 82696.42 | 2.446993 | 2.87 | 2.20 | 0.00479800 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 17.3565 | 15.55 | 0.00665399 | 53.0702 | 44523.98 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 182568.978 | 182568.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 5.024815 | 5.29183267 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 182568.98 | 182568.98 | 1.0000 | 5.29183267 | 5.024815 | 2.68 | 2.68 | 0.00710186 | 20489.2 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 182568.98 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.99 | 0.00873315 | 9.99 | 0.00873315 | 100.0000 | 182568.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8487.005 | 0.000 | 1.025400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5343 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8487.00 | 8487.00 | 1.0000 | 1.07988963 | 1.025400 | 24.62 | 14.72 | 0.00790460 | 44873.8 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8487.00 | 31.16 | 0.00626593 | 15.56 | 0.10228487 | 9.9751 | 23.90 | 0.00808617 | 23.90 | 0.00808617 | 38.3245 | 9084.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25828.738 | 25828.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.025400 | 1.07988967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25828.74 | 25828.74 | 1.0000 | 1.07988967 | 1.025400 | 10.05 | 7.29 | 0.00613178 | 25548.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25828.74 | -27.60 | 0.00034190 | -27.60 | 0.10228487 | 9.9751 | 21.05 | 0.00782339 | 21.10 | 0.00782339 | 43.9761 | 11740.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23981.605 | 0.000 | 2.446990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9634 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23981.60 | 23981.60 | 1.0000 | 2.57702276 | 2.446990 | 27.86 | 15.56 | 0.00759750 | 47393.8 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23981.60 | 33.40 | 0.00626594 | 16.30 | 0.42471267 | 17.3565 | 26.70 | 0.00787752 | 26.70 | 0.00787775 | 31.6179 | 27782.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82696.416 | 82696.416 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.446993 | 2.57702590 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82696.42 | 82696.42 | 1.0000 | 2.57702590 | 2.446993 | 2.87 | 2.20 | 0.00479800 | 14905.2 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82696.42 | -27.60 | 0.00034190 | -27.60 | 0.42471267 | 17.3565 | 15.56 | 0.00665399 | 15.55 | 0.00665399 | 53.0702 | 44523.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.03 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.45 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2406.67 | 3045.83 | 2194.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2406.67 | 3045.83 | 2194.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 113.00 | 46.50 | 61.83 | 2.17 |
ZONE2 FINE STORAGE | 535.17 | 14.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1.67 | 0.00 | 0.00 | 0.00 |
Facility | 618.50 | 56.67 | 61.83 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.585 | 0.255 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
Electricity:Building | 536.87 | 4004.31 | 08-JAN-11:00 | 41507.48 | 07-AUG-09:30 |
Electricity:Zone:ZONE1 OFFICE | 51.49 | 810.73 | 01-JAN-14:00 | 3365.36 | 02-JAN-08:10 |
InteriorLights:Electricity | 398.39 | 3515.76 | 08-JAN-11:00 | 30629.63 | 04-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.77 | 322.19 | 01-JAN-14:00 | 1511.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 398.39 | 3515.76 | 08-JAN-11:00 | 30629.63 | 04-JAN-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 323.09 | 1768.71 | 08-JAN-10:50 | 26197.06 | 17-JUL-09:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 214.34 | 1768.71 | 08-JAN-10:50 | 17006.84 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.64 | 481.00 | 05-JAN-18:10 | 2852.58 | 16-FEB-12:20 |
WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-18:10 | 2852.58 | 16-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-18:10 | 2852.58 | 16-FEB-12:20 |
Fans:Electricity | 57.32 | 0.00 | 01-JAN-12:40 | 6058.97 | 10-AUG-12:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.42 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-19:20 |
Ventilation (simple):Fans:Electricity | 1.42 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-19:20 |
ElectricityPurchased:Facility | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
ElectricityPurchased:Plant | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
Cogeneration:ElectricityPurchased | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
ElectricityNet:Plant | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
Cogeneration:ElectricityNet | 712.23 | 4485.31 | 12-FEB-12:40 | 57185.38 | 17-JUL-15:00 |
Electricity:HVAC | 65.07 | 0.00 | 01-JAN-12:40 | 16291.29 | 17-JUL-16:00 |
General:Fans:Electricity | 55.90 | 0.00 | 01-JAN-12:40 | 4220.54 | 02-JAN-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 9.17 | 0.00 | 01-JAN-00:10 | 12537.62 | 17-JUL-16:00 |
ExteriorLights:Electricity | 83.65 | 0.00 | 01-JAN-08:20 | 6311.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 83.65 | 0.00 | 01-JAN-08:20 | 6311.20 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 993.24 | 0.00 | 01-JAN-12:40 | 334825.71 | 05-JAN-17:10 |
Gas:HVAC | 993.24 | 0.00 | 01-JAN-12:40 | 334825.71 | 05-JAN-17:10 |
Heating:Gas | 993.24 | 0.00 | 01-JAN-12:40 | 334825.71 | 05-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1597.77 | 0.00 | 01-JAN-12:40 | 509805.93 | 05-JAN-17:10 |
EnergyTransfer:Building | 796.69 | 0.00 | 01-JAN-12:40 | 246273.06 | 05-JAN-17:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 55.75 | 0.00 | 01-JAN-00:10 | 22748.20 | 09-JAN-07:10 |
Heating:EnergyTransfer | 751.35 | 0.00 | 01-JAN-12:40 | 246273.06 | 05-JAN-17:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 39.73 | 0.00 | 01-JAN-00:10 | 22748.20 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 45.34 | 0.00 | 01-JAN-00:10 | 33589.20 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.02 | 0.00 | 01-JAN-00:10 | 10305.51 | 05-SEP-00:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 187.69 | 0.00 | 01-JAN-00:40 | 58110.94 | 06-JAN-06:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 158.36 | 0.00 | 01-JAN-00:40 | 58110.94 | 06-JAN-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 29.33 | 0.00 | 01-JAN-00:10 | 25612.84 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 553.25 | 0.00 | 01-JAN-12:20 | 184483.28 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 553.25 | 0.00 | 01-JAN-12:20 | 184483.28 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 801.08 | 0.00 | 01-JAN-12:40 | 263532.87 | 05-JAN-17:10 |
HeatingCoils:EnergyTransfer | 763.00 | 0.00 | 01-JAN-12:40 | 263532.87 | 05-JAN-17:10 |
CoolingCoils:EnergyTransfer | 38.08 | 0.00 | 01-JAN-00:10 | 43564.18 | 17-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 39.734 | -16.016 | 0.000 | 0.000 | 3.986 | 21.774 | 29.720 | 9.605 | 0.000 | 0.448 | 0.000 | 0.000 | -13.113 | 0.000 | -19.304 | -56.835 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 158.357 | -29.328 | 0.000 | 0.000 | 0.000 | 162.279 | 0.000 | 0.000 | 0.000 | 1.259 | 0.000 | 0.000 | 0.000 | 0.000 | -123.431 | -169.136 |
ZONE3 BULK STORAGE | 553.253 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 214.341 | 107.336 | 31.595 | 0.000 | 24.625 | 0.000 | 0.000 | -27.339 | 0.000 | -590.627 | -313.185 |
Total Facility | 553.253 | 0.000 | 198.091 | -45.344 | 0.000 | 0.000 | 3.986 | 398.394 | 137.056 | 41.200 | 0.000 | 26.333 | 0.000 | 0.000 | -40.452 | 0.000 | -733.362 | -539.156 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 28-AUG-00:03 | 0.00 | 0.00 | 0.00 | -21674.96 | 0.00 | 0.00 | 0.00 | 413.06 | 488.55 | 0.00 | 0.00 | 0.00 | 21512.42 | 0.00 | -583.90 | 0.00 | -155.16 | 0.00 |
ZONE2 FINE STORAGE | 27-JUL-17:22 | 0.00 | 0.00 | 0.00 | -50735.59 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 50864.99 | 0.00 | -0.00 | 0.00 | -1554.26 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-17:20 | 0.00 | 0.00 | 0.00 | -62835.03 | 0.00 | 0.00 | 0.00 | 3515.76 | 2538.58 | 3991.10 | 0.00 | 7.29 | 69533.55 | 0.00 | 0.00 | 0.00 | -16751.25 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-JAN-06:31 | 0.00 | 0.00 | 27969.80 | 0.00 | 0.00 | 0.00 | 55.89 | 451.48 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1540.94 | 0.00 | -1839.60 | -25652.80 |
ZONE2 FINE STORAGE | 06-JAN-06:41 | 0.00 | 0.00 | 87785.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17367.27 | -71842.99 |
ZONE3 BULK STORAGE | 05-JAN-16:00 | 184473.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2795.58 | 0.00 | -192494.05 | -14391.32 |
Total Facility | 06-JAN-06:51 | 173188.30 | 0.00 | 110186.75 | 0.00 | 0.00 | 0.00 | 56.11 | 3877.14 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5797.67 | 0.00 | -125449.73 | -158667.10 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0254 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0254 | 0.0998 | 1.0000 | 0.1023 | 0.0998 | ||
PSZ-FINE STORAGE | 2.4470 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.4470 | 0.1736 | 1.0000 | 0.4247 | 0.1736 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0254 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0254 | 1.0000 | 1.0000 | 0.1023 | 0.0998 | ||
PSZ-FINE STORAGE | 2.4470 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.4470 | 1.0000 | 1.0000 | 0.4247 | 0.1736 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0254 | 1.0254 | 1.0254 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4470 | 2.4470 | 2.4470 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0254 | 1.0254 | 1.0254 | 1.0254 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4470 | 2.4470 | 2.4470 | 2.4470 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0254 | 1.0254 | 1.0254 | 0.1023 | 0.2261 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4470 | 2.4470 | 2.4470 | 0.4247 | 0.2940 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0254 | 1.0254 | 1.0254 | 1.0254 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4470 | 2.4470 | 2.4470 | 2.4470 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 61.83 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 64.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 993.24 | 334825.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 9.17 | 12537.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 398.39 | 30629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 83.65 | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.42 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 55.90 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.64 | 2852.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 712.23 |
Natural Gas | 0.00 | 993.24 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 1705.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 82.40 |
Space Heating | 0.00 |
Space Cooling | 1.90 |
Fans (All) | 11.85 |
Service Water Heating | 5.51 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 147.30 |
Subtotal | 147.30 |
Natural Gas [MJ/m2] | |
Space Heating | 205.42 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 205.42 |
Subtotal | 205.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.36 |
Space Heating | 58.24 |
Space Cooling | 0.54 |
Fans (All) | 3.36 |
Service Water Heating | 1.56 |
Receptacle Equipment | 8.04 |
Miscellaneous | 4.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3065. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.326445E+12 |
February | 0.000 | 0.178128E+12 |
March | 0.000 | 0.123454E+12 |
April | 0.000 | 0.248558E+11 |
May | 0.000 | 0.159934E+11 |
June | 0.000 | 0.515994E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2071706.066 |
September | 0.000 | 0.729976E+09 |
October | 0.000 | 0.667492E+10 |
November | 0.000 | 0.929213E+11 |
December | 0.000 | 0.223986E+12 |
Annual Sum or Average | 0.993243E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.326445E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194905E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 170899.59 | 61.56 | 28-FEB-17:00 | 10.00 | 4.29 | 0.179603E+09 | 260.50 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 114531.50 | 51.86 | 02-MAR-16:20 | 9.83 | 4.43 | 0.210563E+09 | 239.11 | 02-MAR-16:10 | 10.22 | 4.58 |
April | 781431.86 | 140.60 | 26-APR-16:00 | 9.40 | 4.23 | 0.198833E+09 | 298.67 | 07-APR-15:09 | 21.60 | 8.84 |
May | 0.273949E+09 | 16518.87 | 20-MAY-19:21 | 21.40 | 12.72 | 0.221367E+09 | 301.59 | 20-MAY-10:09 | 21.28 | 13.17 |
June | 0.277639E+10 | 18985.28 | 26-JUN-00:01 | 17.02 | 11.92 | 0.254403E+09 | 301.61 | 20-JUN-10:00 | 23.90 | 15.47 |
July | 0.564875E+10 | 20234.58 | 24-JUL-00:02 | 13.62 | 9.69 | 0.248778E+09 | 301.61 | 03-JUL-12:50 | 19.07 | 13.97 |
August | 0.504886E+10 | 21677.64 | 28-AUG-00:03 | 11.93 | 7.06 | 0.267990E+09 | 301.60 | 05-AUG-10:09 | 24.45 | 14.54 |
September | 0.212713E+10 | 19388.44 | 08-SEP-18:21 | 17.20 | 9.39 | 0.235550E+09 | 301.60 | 06-SEP-10:00 | 18.90 | 15.65 |
October | 0.133116E+09 | 2235.21 | 18-OCT-16:00 | 24.40 | 10.99 | 0.212624E+09 | 301.59 | 16-OCT-13:50 | 21.10 | 9.49 |
November | 6631114.10 | 332.62 | 06-NOV-15:40 | 7.40 | 2.69 | 0.188493E+09 | 278.19 | 04-NOV-15:20 | 16.50 | 7.80 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.194965E+09 | 236.59 | 04-DEC-08:30 | 2.50 | -0.3 |
Annual Sum or Average | 0.160159E+11 | 0.260807E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.1 | 0.179603E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.564875E+10 | 21677.64 | 24.40 | 12.72 | 0.267990E+09 | 301.61 | 24.45 | 15.65 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113675E+09 | 2443.68 | 21-JAN-14:40 | 3.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.402407E+09 | 5294.53 | 23-FEB-14:30 | -2.0 | -4.4 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.974759E+09 | 4959.32 | 25-MAR-11:00 | -0.6 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.891357E+09 | 6205.23 | 08-APR-06:10 | 8.30 | 5.01 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.993701E+09 | 8143.92 | 18-MAY-06:10 | 6.57 | 5.24 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.339726E+10 | 49114.40 | 25-JUN-13:01 | 23.07 | 12.99 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.970616E+10 | 50736.59 | 27-JUL-17:22 | 21.40 | 12.19 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.754260E+10 | 45515.86 | 10-AUG-20:11 | 24.30 | 10.40 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.311968E+10 | 44402.19 | 01-SEP-18:11 | 25.57 | 12.73 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.115796E+10 | 6845.57 | 17-OCT-06:10 | 3.98 | 1.75 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.722619E+09 | 4644.41 | 25-NOV-13:55 | -1.7 | -3.0 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.306449E+09 | 4094.69 | 21-DEC-12:10 | 0.68 | -3.0 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.293286E+11 | 0.00 | ||||||||
Minimum of Months | 0.113675E+09 | 2443.68 | -2.0 | -4.4 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.970616E+10 | 50736.59 | 25.57 | 12.99 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943506E+10 | 27969.70 | 26-JAN-06:31 | -22.2 |
February | 0.642744E+10 | 26542.32 | 10-FEB-06:12 | -19.8 |
March | 0.587443E+10 | 26603.57 | 06-MAR-06:12 | -17.1 |
April | 0.319937E+10 | 26311.07 | 29-APR-05:22 | -7.5 |
May | 0.199294E+10 | 26348.90 | 08-MAY-05:12 | -2.8 |
June | 0.126636E+09 | 25609.27 | 17-JUN-05:02 | 2.35 |
July | 29286387.75 | 1305.41 | 13-JUL-06:03 | 13.77 |
August | 68095628.66 | 2398.00 | 18-AUG-06:03 | 8.17 |
September | 0.414519E+09 | 26142.88 | 19-SEP-05:01 | 2.20 |
October | 0.137551E+10 | 26318.15 | 10-OCT-05:22 | -6.1 |
November | 0.390147E+10 | 26541.92 | 27-NOV-06:12 | -14.4 |
December | 0.688972E+10 | 27447.38 | 23-DEC-06:31 | -10.8 |
Annual Sum or Average | 0.397345E+11 | |||
Minimum of Months | 29286387.75 | 1305.41 | -22.2 | |
Maximum of Months | 0.943506E+10 | 27969.70 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457312E+11 | 87785.32 | 06-JAN-06:41 | -25.5 |
February | 0.269505E+11 | 85463.00 | 09-FEB-22:02 | -20.6 |
March | 0.206085E+11 | 86289.14 | 05-MAR-02:61 | -21.8 |
April | 0.734166E+10 | 84193.06 | 29-APR-04:32 | -7.8 |
May | 0.412790E+10 | 83240.77 | 01-MAY-05:11 | -0.4 |
June | 0.271728E+09 | 2594.79 | 01-JUN-07:00 | 11.70 |
July | 0.160945E+09 | 2437.34 | 08-JUL-07:00 | 11.70 |
August | 0.229752E+09 | 2489.95 | 17-AUG-07:00 | 8.30 |
September | 0.654977E+09 | 24113.75 | 19-SEP-05:33 | 2.20 |
October | 0.276129E+10 | 83306.45 | 11-OCT-05:01 | -0.5 |
November | 0.164366E+11 | 86337.05 | 27-NOV-04:01 | -15.8 |
December | 0.330823E+11 | 86303.59 | 28-DEC-04:01 | -22.7 |
Annual Sum or Average | 0.158357E+12 | |||
Minimum of Months | 0.160945E+09 | 2437.34 | -25.5 | |
Maximum of Months | 0.457312E+11 | 87785.32 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191719E+12 | 184483.28 | 05-JAN-16:00 | -19.4 |
February | 0.100853E+12 | 125564.38 | 03-FEB-18:57 | -16.7 |
March | 0.665362E+11 | 131540.33 | 06-MAR-03:51 | -18.3 |
April | 0.776121E+10 | 60762.95 | 29-APR-05:00 | -7.8 |
May | 0.630606E+10 | 51585.30 | 08-MAY-06:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.107314E+10 | 27233.50 | 11-OCT-06:00 | 0.00 |
November | 0.499997E+11 | 114693.59 | 27-NOV-05:00 | -15.6 |
December | 0.129006E+12 | 179839.84 | 31-DEC-03:00 | -24.4 |
Annual Sum or Average | 0.553254E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.191719E+12 | 184483.28 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191099E+10 | 1511.47 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.169321E+10 | 1511.47 | 01-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.187845E+10 | 1511.47 | 13-MAR-07:10 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.176705E+10 | 1511.47 | 01-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.179663E+10 | 1456.05 | 03-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.175085E+10 | 1345.21 | 16-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.176657E+10 | 1345.21 | 07-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.184925E+10 | 1400.63 | 04-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.177838E+10 | 1511.47 | 11-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.184605E+10 | 1511.47 | 04-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.181957E+10 | 1511.47 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.191657E+10 | 1511.47 | 01-DEC-08:09 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.217735E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.169321E+10 | 1345.21 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.191657E+10 | 1511.47 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.134983E+11 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138856E+11 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | ||||
Minimum of Months | 0.123544E+11 | 12111.32 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.183914E+11 | 17006.84 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.166870E+11 | 17006.84 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.186558E+11 | 17006.84 | 06-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.173607E+11 | 16349.24 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.178037E+11 | 16349.24 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.175592E+11 | 16349.24 | 23-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.173138E+11 | 16349.24 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.185276E+11 | 16349.24 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.176281E+11 | 17006.84 | 16-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.181282E+11 | 17006.84 | 10-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.177276E+11 | 17006.84 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.185578E+11 | 17006.84 | 01-DEC-14:20 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.214341E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.166870E+11 | 16349.24 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.186558E+11 | 17006.84 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.191099E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339253E+10 |
February | 0.500553E+09 | 0.169321E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241699E+10 |
March | 0.587605E+09 | 0.187845E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224668E+10 |
April | 0.544079E+09 | 0.176705E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374160.07 | 0.137917E+10 |
May | 0.565842E+09 | 0.179663E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9105409.02 | 0.133085E+10 |
June | 0.565842E+09 | 0.175085E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77993918.83 | 0.734016E+09 |
July | 0.544079E+09 | 0.176657E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187507E+09 | 0.371058E+09 |
August | 0.587605E+09 | 0.184925E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140660E+09 | 0.576730E+09 |
September | 0.544079E+09 | 0.177838E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31055230.27 | 0.969660E+09 |
October | 0.544079E+09 | 0.184605E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558809.43 | 0.132053E+10 |
November | 0.522316E+09 | 0.181957E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193495E+10 |
December | 0.544079E+09 | 0.191657E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263054E+10 |
Annual Sum or Average | 0.659424E+10 | 0.217735E+11 | 0.297195E+11 | 0.448255E+09 | 0.193037E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.169321E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371058E+09 |
Maximum of Months | 0.587605E+09 | 0.191657E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187507E+09 | 0.339253E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214267E+11 |
February | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150245E+11 |
March | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134682E+11 |
April | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8604502.14 | 0.788640E+10 |
May | 0.00 | 0.138856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40129413.00 | 0.800374E+10 |
June | 0.00 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139500E+09 | 0.562409E+10 |
July | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446836E+09 | 0.402150E+10 |
August | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405703E+09 | 0.479444E+10 |
September | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189119E+09 | 0.692249E+10 |
October | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29272403.48 | 0.761341E+10 |
November | 0.00 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118866E+11 |
December | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167595E+11 |
Annual Sum or Average | 0.162279E+12 | 0.125916E+10 | 0.123431E+12 | ||||||
Minimum of Months | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402150E+10 |
Maximum of Months | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446836E+09 | 0.214267E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.183914E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791171E+11 |
February | 0.00 | 0.166870E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535973E+09 | 0.463364E+11 |
March | 0.00 | 0.186558E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58295106.75 | 0.411507E+11 |
April | 0.00 | 0.173607E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182195E+10 | 0.208898E+11 |
May | 0.00 | 0.178037E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239765E+10 | 0.220197E+11 |
June | 0.00 | 0.175592E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778810E+09 | 0.200077E+11 |
July | 0.00 | 0.173138E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359757E+09 | 0.206118E+11 |
August | 0.00 | 0.185276E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326865E+09 | 0.235440E+11 |
September | 0.00 | 0.176281E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132237E+10 | 0.269838E+11 |
October | 0.00 | 0.181282E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206004E+10 | 0.218526E+11 |
November | 0.00 | 0.177276E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125767E+10 | 0.337856E+11 |
December | 0.00 | 0.185578E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234421E+09 | 0.541532E+11 |
Annual Sum or Average | 0.214341E+12 | 0.107336E+12 | 0.111538E+11 | 0.410453E+12 | |||||
Minimum of Months | 0.00 | 0.166870E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200077E+11 |
Maximum of Months | 0.00 | 0.186558E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239765E+10 | 0.791171E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1511.47 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 12054.79 | 27-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1511.47 | 01-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 10623.55 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1511.47 | 13-MAR-07:10 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 9514.28 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1511.47 | 01-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 16-APR-14:00 | 5401.04 | 28-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1456.05 | 03-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.82 | 19-MAY-16:10 | 6212.76 | 22-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1345.21 | 16-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.52 | 29-JUN-16:10 | 4114.90 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 1345.21 | 07-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 17-JUL-16:10 | 3026.80 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1400.63 | 04-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.17 | 10-AUG-17:00 | 3529.35 | 17-AUG-16:03 |
September | 659.25 | 01-SEP-07:10 | 1511.47 | 11-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 955.05 | 01-SEP-16:10 | 4337.88 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1511.47 | 04-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 | 15-OCT-14:00 | 6290.72 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1511.47 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8315.91 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1511.47 | 01-DEC-08:09 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 10926.84 | 29-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1345.21 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3026.80 | |||||
Maximum of Months | 659.25 | 1511.47 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 12054.79 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 39428.98 | 05-JAN-16:10 |
February | 0.00 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21004.15 | 01-FEB-17:00 |
March | 0.00 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 18271.96 | 30-MAR-08:00 |
April | 0.00 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.64 | 16-APR-16:00 | 13248.08 | 28-APR-16:00 |
May | 0.00 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.03 | 20-MAY-16:00 | 24373.80 | 22-MAY-06:10 |
June | 0.00 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4573.30 | 29-JUN-15:05 | 10876.17 | 06-JUN-16:53 |
July | 0.00 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.07 | 25-JUL-15:10 | 7995.98 | 08-JUL-07:00 |
August | 0.00 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.48 | 09-AUG-17:00 | 15290.48 | 17-AUG-15:05 |
September | 0.00 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4540.57 | 02-SEP-15:10 | 12913.25 | 18-SEP-15:05 |
October | 0.00 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1868.62 | 15-OCT-14:00 | 10849.10 | 31-OCT-16:00 |
November | 0.00 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17981.74 | 28-NOV-08:00 |
December | 0.00 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 20536.54 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7995.98 | |||
Maximum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.07 | 39428.98 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 17006.84 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 142755.01 | 05-JAN-16:00 |
February | 0.00 | 17006.84 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10313.13 | 27-FEB-13:10 | 77224.33 | 01-FEB-15:00 |
March | 0.00 | 17006.84 | 06-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5060.12 | 14-MAR-12:10 | 62467.12 | 03-MAR-09:00 |
April | 0.00 | 16349.24 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20760.00 | 07-APR-12:10 | 44121.48 | 27-APR-11:00 |
May | 0.00 | 16349.24 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25484.47 | 19-MAY-16:00 | 71036.39 | 22-MAY-08:00 |
June | 0.00 | 16349.24 | 23-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11203.42 | 29-JUN-13:00 | 38607.61 | 26-JUN-13:00 |
July | 0.00 | 16349.24 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8060.55 | 13-JUL-16:00 | 31972.14 | 08-JUL-10:00 |
August | 0.00 | 16349.24 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7397.55 | 25-AUG-16:00 | 66616.13 | 17-AUG-12:05 |
September | 0.00 | 17006.84 | 16-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13931.38 | 23-SEP-14:00 | 52574.69 | 12-SEP-11:00 |
October | 0.00 | 17006.84 | 10-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21393.97 | 12-OCT-12:10 | 32302.20 | 03-OCT-09:00 |
November | 0.00 | 17006.84 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13781.65 | 17-NOV-14:00 | 57677.36 | 27-NOV-11:00 |
December | 0.00 | 17006.84 | 01-DEC-14:20 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12120.21 | 10-DEC-01:55 | 100510.69 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 16349.24 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31972.14 | ||||
Maximum of Months | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25484.47 | 142755.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1239.18 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 |
February | 61.56 | 28-FEB-17:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.23 |
March | 51.86 | 02-MAR-16:20 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.73 |
April | 140.60 | 26-APR-16:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.03 |
May | 16518.87 | 20-MAY-19:21 | 0.00 | 4130.60 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 |
June | 18985.28 | 26-JUN-00:01 | 0.00 | 4130.60 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 |
July | 20234.58 | 24-JUL-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 |
August | 21677.64 | 28-AUG-00:03 | 0.00 | 1652.24 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 |
September | 19388.44 | 08-SEP-18:21 | 0.00 | 3827.69 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.87 |
October | 2235.21 | 18-OCT-16:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
November | 332.62 | 06-NOV-15:40 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.74 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1178.95 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21677.64 | 659.25 | 4130.60 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 691.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2443.68 | 21-JAN-14:40 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3507.99 |
February | 5294.53 | 23-FEB-14:30 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1757.45 |
March | 4959.32 | 25-MAR-11:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6205.23 | 08-APR-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2620.36 |
May | 8143.92 | 18-MAY-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2092.94 |
June | 49114.40 | 25-JUN-13:01 | 0.00 | 14248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.19 |
July | 50736.59 | 27-JUL-17:22 | 0.00 | 12823.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1554.26 |
August | 45515.86 | 10-AUG-20:11 | 0.00 | 14248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.92 |
September | 44402.19 | 01-SEP-18:11 | 0.00 | 14248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.71 |
October | 6845.57 | 17-OCT-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.71 |
November | 4644.41 | 25-NOV-13:55 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4987.97 |
December | 4094.69 | 21-DEC-12:10 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2443.68 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50736.59 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4987.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 6002.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5741.32 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 12004.83 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44666.04 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9190.05 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11789.98 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12200.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.89 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8079.67 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4001.61 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6656.24 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7378.97 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15885.09 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13359.57 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 10004.02 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34153.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.89 | |
Maximum of Months | 0.00 | 0.00 | 12004.83 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44666.04 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.630745E+11 | 49455.68 | 21-JAN-08:09 | 0.326445E+12 | 334825.71 | 05-JAN-17:10 |
February | 0.561264E+11 | 46941.97 | 07-FEB-15:00 | 0.178128E+12 | 218242.99 | 04-FEB-06:10 |
March | 0.622807E+11 | 46558.84 | 06-MAR-09:30 | 0.123454E+12 | 228297.00 | 06-MAR-03:49 |
April | 0.562129E+11 | 45779.40 | 20-APR-08:09 | 0.248558E+11 | 124677.96 | 29-APR-05:19 |
May | 0.568723E+11 | 46006.49 | 20-MAY-14:00 | 0.159934E+11 | 115433.72 | 08-MAY-05:10 |
June | 0.567859E+11 | 50947.66 | 29-JUN-14:00 | 51599421.32 | 6282.56 | 17-JUN-05:10 |
July | 0.596021E+11 | 57185.38 | 17-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.625433E+11 | 55918.40 | 10-AUG-14:00 | 2071706.07 | 1220.90 | 18-AUG-06:10 |
September | 0.576530E+11 | 54845.14 | 02-SEP-14:30 | 0.729976E+09 | 25569.74 | 20-SEP-05:30 |
October | 0.588637E+11 | 48843.49 | 30-OCT-07:10 | 0.667492E+10 | 73534.34 | 10-OCT-05:30 |
November | 0.590762E+11 | 49407.70 | 30-NOV-16:00 | 0.929213E+11 | 205096.91 | 27-NOV-04:10 |
December | 0.631360E+11 | 49450.59 | 28-DEC-08:09 | 0.223986E+12 | 292829.94 | 31-DEC-02:00 |
Annual Sum or Average | 0.712227E+12 | 0.993243E+12 | ||||
Minimum of Months | 0.561264E+11 | 45779.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.631360E+11 | 57185.38 | 0.326445E+12 | 334825.71 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.338007E+11 | 0.941800E+10 | 0.113456E+11 | 0.00 | 0.617715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233305E+10 | 0.00 |
February | 0.307346E+11 | 0.767900E+10 | 0.104160E+11 | 0.00 | 0.515914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213768E+10 | 0.00 |
March | 0.348071E+11 | 0.734288E+10 | 0.121485E+11 | 0.00 | 0.557120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241098E+10 | 0.00 |
April | 0.325029E+11 | 0.593518E+10 | 0.113034E+11 | 0.00 | 0.421533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225614E+10 | 0.00 |
May | 0.334859E+11 | 0.513264E+10 | 0.117471E+11 | 0.00 | 0.414528E+10 | 0.00 | 0.00 | 80857222.40 | 0.00 | 0.00 | 0.00 | 0.228055E+10 | 0.00 |
June | 0.330725E+11 | 0.449296E+10 | 0.117048E+11 | 0.00 | 0.398321E+10 | 0.00 | 0.00 | 0.136075E+10 | 0.00 | 0.00 | 0.00 | 0.217170E+10 | 0.00 |
July | 0.325786E+11 | 0.483633E+10 | 0.113456E+11 | 0.00 | 0.486166E+10 | 0.00 | 0.00 | 0.383639E+10 | 0.00 | 0.00 | 0.00 | 0.214351E+10 | 0.00 |
August | 0.346497E+11 | 0.566536E+10 | 0.121485E+11 | 0.00 | 0.497402E+10 | 0.00 | 0.00 | 0.292258E+10 | 0.00 | 0.00 | 0.00 | 0.218307E+10 | 0.00 |
September | 0.327817E+11 | 0.659407E+10 | 0.113034E+11 | 0.00 | 0.392180E+10 | 0.00 | 0.00 | 0.957823E+09 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
October | 0.334726E+11 | 0.801692E+10 | 0.113456E+11 | 0.00 | 0.383638E+10 | 0.00 | 0.00 | 10657493.55 | 0.00 | 0.00 | 0.00 | 0.218162E+10 | 0.00 |
November | 0.325351E+11 | 0.881688E+10 | 0.109019E+11 | 0.00 | 0.466413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215818E+10 | 0.00 |
December | 0.339726E+11 | 0.971715E+10 | 0.113456E+11 | 0.00 | 0.581010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229060E+10 | 0.00 |
Annual Sum or Average | 0.398394E+12 | 0.836474E+11 | 0.137056E+12 | 0.573194E+11 | 0.00 | 0.916906E+10 | 0.266413E+11 | ||||||
Minimum of Months | 0.307346E+11 | 0.449296E+10 | 0.104160E+11 | 0.00 | 0.383638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
Maximum of Months | 0.348071E+11 | 0.971715E+10 | 0.121485E+11 | 0.00 | 0.617715E+10 | 0.00 | 0.00 | 0.383639E+10 | 0.00 | 0.00 | 0.00 | 0.241098E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.326445E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.178128E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.123454E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248558E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.159934E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 51599421.32 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2071706.07 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729976E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.667492E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.929213E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223986E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.993243E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.326445E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30629.63 | 04-JAN-15:00 | 6311.20 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 4220.54 | 02-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30574.21 | 01-FEB-09:09 | 6311.20 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 4220.54 | 01-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30574.21 | 06-MAR-09:09 | 6311.20 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 4220.54 | 01-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29916.61 | 01-APR-08:09 | 6311.20 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 4220.54 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29694.93 | 02-MAY-08:09 | 6311.20 | 01-MAY-05:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 4220.54 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29805.77 | 23-JUN-08:09 | 6311.20 | 01-JUN-20:10 | 10054.01 | 01-JUN-07:10 | 0.00 | 6058.97 | 29-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29805.77 | 07-JUL-08:09 | 6311.20 | 01-JUL-20:30 | 10054.01 | 01-JUL-07:10 | 0.00 | 6058.97 | 14-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29861.19 | 04-AUG-08:09 | 6311.20 | 01-AUG-19:00 | 10054.01 | 01-AUG-07:10 | 0.00 | 6058.97 | 10-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30518.79 | 16-SEP-08:09 | 6311.20 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 6058.97 | 02-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30574.21 | 11-OCT-08:09 | 6311.20 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 4220.54 | 10-OCT-06:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30574.21 | 03-NOV-08:09 | 6311.20 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 4220.54 | 10-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30629.63 | 12-DEC-09:09 | 6311.20 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 4220.54 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29694.93 | 6311.20 | 10054.01 | 0.00 | 4220.54 | 0.00 | 0.00 | |||||
Maximum of Months | 30629.63 | 6311.20 | 10054.01 | 0.00 | 6058.97 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2830.49 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2852.58 | 16-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2846.47 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2750.10 | 01-APR-11:30 | 0.00 |
May | 2424.39 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2560.39 | 01-MAY-11:20 | 0.00 |
June | 7439.44 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2253.66 | 05-JUN-11:30 | 0.00 |
July | 12537.62 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2012.49 | 03-JUL-11:00 | 0.00 |
August | 9977.25 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1845.06 | 01-AUG-11:00 | 0.00 |
September | 8769.58 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1958.26 | 29-SEP-11:30 | 0.00 |
October | 762.57 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2181.71 | 26-OCT-11:30 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2490.54 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2697.93 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1845.06 | 0.00 | ||
Maximum of Months | 12537.62 | 0.00 | 0.00 | 0.00 | 2852.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49455.68 | 21-JAN-08:09 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46941.97 | 07-FEB-15:00 | 30297.11 | 10054.01 | 0.00 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46558.84 | 06-MAR-09:30 | 30574.21 | 10054.01 | 0.00 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45779.40 | 20-APR-08:09 | 29805.77 | 10054.01 | 0.00 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46006.49 | 20-MAY-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 3753.68 | 0.00 | 0.00 | 2008.40 | 0.00 |
June | 50947.66 | 29-JUN-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 3753.68 | 0.00 | 0.00 | 7033.91 | 0.00 |
July | 57185.38 | 17-JUL-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 6058.97 | 0.00 | 0.00 | 10975.12 | 0.00 |
August | 55918.40 | 10-AUG-14:00 | 28324.31 | 10054.01 | 0.00 | 0.00 | 6058.97 | 0.00 | 0.00 | 9714.29 | 0.00 |
September | 54845.14 | 02-SEP-14:30 | 28981.91 | 10054.01 | 0.00 | 0.00 | 6058.97 | 0.00 | 0.00 | 7983.81 | 0.00 |
October | 48843.49 | 30-OCT-07:10 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 3753.68 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49407.70 | 30-NOV-16:00 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49450.59 | 28-DEC-08:09 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 4220.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 45779.40 | 27203.97 | 10054.01 | 0.00 | 0.00 | 3753.68 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57185.38 | 30574.21 | 10054.01 | 6311.20 | 0.00 | 6058.97 | 0.00 | 0.00 | 10975.12 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 334825.71 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 218242.99 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 228297.00 | 06-MAR-03:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 124677.96 | 29-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 115433.72 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6282.56 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1220.90 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 25569.74 | 20-SEP-05:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 73534.34 | 10-OCT-05:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 205096.91 | 27-NOV-04:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 292829.94 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 334825.71 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 15.91 | 9.67 | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14.83 | 17.39 | 8.17 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16.33 | 17.47 | 9.50 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.33 | 19.56 | 8.00 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.33 | 19.51 | 5.83 | 19.90 | 0.17 | 24.46 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.57 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.63 | 1.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 24.61 | 0.33 | 24.53 |
September | 1.17 | 20.34 | 1.17 | 20.34 | 4.33 | 24.55 | 0.50 | 24.48 |
October | 3.50 | 19.92 | 3.50 | 19.92 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.00 | 19.03 | 7.50 | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16.33 | 17.27 | 8.50 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.00 | 17.42 | 61.83 | 19.49 | 46.50 | 24.61 | 2.17 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.17 | 20.34 | 9.67 | 20.34 | 17.83 | 24.63 | 1.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.17 | 13.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91.17 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90.83 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36.67 | 14.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.42 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.47 | 0.00 | 0.00 |
September | 0.50 | 14.97 | 0.00 | 0.00 | 3.33 | 27.41 | 0.00 | 0.00 |
October | 9.50 | 14.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64.67 | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 111.33 | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 535.17 | 14.31 | 0.00 | 14.33 | 27.43 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.17 | 14.97 | 0.00 | 0.00 | 6.17 | 27.47 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 8.99 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.06 | 276.00 | 21.06 | 276.00 | 21.06 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.25 | 276.50 | 21.13 | 276.50 | 21.13 |
May | 312.00 | 21.92 | 195.33 | 21.13 | 195.33 | 21.13 |
June | 217.83 | 23.37 | 34.83 | 23.20 | 8.50 | 21.04 |
July | 64.33 | 23.82 | 101.33 | 23.90 | 0.00 | 0.00 |
August | 134.67 | 23.70 | 49.50 | 23.90 | 0.00 | 0.00 |
September | 229.00 | 22.83 | 88.50 | 22.40 | 53.67 | 21.42 |
October | 300.00 | 21.91 | 179.67 | 21.16 | 179.67 | 21.16 |
November | 288.00 | 21.13 | 281.00 | 21.10 | 281.00 | 21.10 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3045.83 | 21.72 | 2406.67 | 21.34 | 2194.67 | 21.09 |
Minimum of Months | 64.33 | 21.02 | 34.83 | 21.02 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.82 | 324.00 | 23.90 | 324.00 | 21.42 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.300699E+09 | 69011529.33 | 44.07 | 0.300541E+09 | 158313.03 | 0.00 | 1.00 | 19-MAY-18:51 | 0.00 | 01-MAY-00:05 | 16367.61 | 20-MAY-18:01 | 16367.61 | 20-MAY-18:01 | 102.25 | 20-MAY-19:21 | 3486.52 | 20-MAY-18:01 | 0.00 | 01-MAY-00:05 |
June | 0.253654E+10 | 0.573505E+09 | 207.89 | 0.245480E+10 | 81743504.83 | 0.00 | 1.00 | 02-JUN-17:35 | 0.00 | 01-JUN-00:10 | 17606.82 | 20-JUN-22:11 | 16443.27 | 23-JUN-19:41 | 5413.54 | 21-JUN-23:25 | 3713.94 | 20-JUN-22:11 | 0.00 | 01-JUN-00:10 |
July | 0.583143E+10 | 0.132780E+10 | 292.57 | 0.564653E+10 | 0.184896E+09 | 0.00 | 1.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:05 | 18053.40 | 18-JUL-22:21 | 16408.78 | 14-JUL-22:21 | 7499.10 | 01-JUL-01:00 | 4005.46 | 17-JUL-17:43 | 0.00 | 01-JUL-00:05 |
August | 0.475124E+10 | 0.108191E+10 | 271.09 | 0.472185E+10 | 29393307.62 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:05 | 16612.99 | 08-AUG-21:01 | 16377.52 | 21-AUG-18:40 | 3930.01 | 01-AUG-01:30 | 3888.75 | 05-AUG-17:08 | 0.00 | 01-AUG-00:05 |
September | 0.168494E+10 | 0.375795E+09 | 134.68 | 0.155376E+10 | 0.131178E+09 | 0.00 | 1.00 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 18294.84 | 07-SEP-18:21 | 16216.05 | 27-SEP-18:00 | 6563.65 | 08-SEP-00:40 | 3887.98 | 02-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 46775389.42 | 10657493.55 | 17.67 | 46775389.42 | 0.00 | 0.00 | 0.44 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 3424.81 | 18-OCT-16:00 | 3424.81 | 18-OCT-16:00 | 0.00 | 18-OCT-13:40 | 762.57 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.151516E+11 | 0.343868E+10 | 967.95 | 0.147243E+11 | 0.427370E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.583143E+10 | 0.132780E+10 | 292.57 | 0.564653E+10 | 0.184896E+09 | 0.00 | 1.00 | 0.00 | 18294.84 | 16443.27 | 7499.10 | 4005.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 44683409.33 | 11845693.07 | 5.33 | 44683409.33 | 0.00 | 0.00 | 0.21 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 | 4501.77 | 20-MAY-16:00 | 4501.77 | 20-MAY-16:00 | 0.00 | 20-MAY-15:40 | 1218.92 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 0.319161E+10 | 0.787248E+09 | 88.30 | 0.309443E+10 | 97180977.25 | 0.00 | 1.00 | 22-JUN-18:11 | 0.00 | 01-JUN-00:10 | 49961.98 | 22-JUN-18:11 | 46096.34 | 23-JUN-19:21 | 9643.39 | 22-JUN-18:18 | 11382.98 | 22-JUN-18:11 | 0.00 | 01-JUN-00:10 |
July | 0.100618E+11 | 0.250859E+10 | 220.76 | 0.989295E+10 | 0.168797E+09 | 0.00 | 1.00 | 01-JUL-17:27 | 0.00 | 01-JUL-00:05 | 50194.42 | 16-JUL-10:04 | 46445.34 | 19-JUL-17:41 | 12425.27 | 16-JUL-09:48 | 12029.68 | 17-JUL-17:06 | 0.00 | 01-JUL-00:05 |
August | 0.731161E+10 | 0.184068E+10 | 179.84 | 0.729299E+10 | 18621662.65 | 0.00 | 1.00 | 03-AUG-17:11 | 0.00 | 01-AUG-00:05 | 45906.46 | 05-AUG-19:51 | 45906.46 | 05-AUG-19:51 | 1571.51 | 08-AUG-12:00 | 11744.09 | 06-AUG-17:03 | 0.00 | 01-AUG-00:05 |
September | 0.232358E+10 | 0.582028E+09 | 60.89 | 0.215955E+10 | 0.164030E+09 | 0.00 | 1.00 | 01-SEP-18:11 | 0.00 | 01-SEP-00:10 | 51853.23 | 06-SEP-18:11 | 45784.85 | 03-SEP-19:01 | 15394.48 | 06-SEP-18:27 | 11713.42 | 06-SEP-17:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.229332E+11 | 0.573039E+10 | 555.11 | 0.224846E+11 | 0.448629E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100618E+11 | 0.250859E+10 | 220.76 | 0.989295E+10 | 0.168797E+09 | 0.00 | 1.00 | 0.00 | 51853.23 | 46445.34 | 15394.48 | 12029.68 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.10 | 278.89 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.20 | 192.59 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.45 | 152.84 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.36 | 99.70 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.48 | 81.98 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 244.02 | 65.47 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 273.11 | 57.65 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 221.90 | 63.56 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 162.80 | 85.75 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 96.05 | 112.86 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.27 | 157.70 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.61 | 230.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.89 | 131.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.61 | 57.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 273.11 | 278.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.10 | 278.89 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.20 | 192.59 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.45 | 152.84 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.36 | 99.70 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.48 | 81.98 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 244.02 | 65.47 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 273.11 | 57.65 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 221.90 | 63.56 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 162.80 | 85.75 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 96.05 | 112.86 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.27 | 157.70 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.61 | 230.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.89 | 131.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.61 | 57.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 273.11 | 278.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.83 | 0.00 | 16.83 | 0.19 | 170.43 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.83 | 120.95 | 0.00 | 0.00 | 672.00 |
March | 38.60 | 0.00 | 38.59 | 8.87 | 92.31 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.12 | 59.33 | 0.00 | 0.00 | 720.00 |
May | 57.74 | 3.37 | 54.36 | 34.48 | 47.07 | 0.00 | 0.00 | 744.00 |
June | 67.20 | 7.67 | 59.53 | 49.77 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 61.38 | 5.66 | 55.71 | 55.55 | 30.47 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 42.74 | 36.13 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 24.71 | 50.51 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 8.99 | 68.01 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.30 | 98.29 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.10 | 142.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.47 | 21.00 | 79.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.10 | 30.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.20 | 7.67 | 59.53 | 55.55 | 170.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.82 | 0.00 | 16.82 | 0.19 | 170.43 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.83 | 120.95 | 0.00 | 0.00 | 672.00 |
March | 38.59 | 0.00 | 38.59 | 8.87 | 92.31 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.12 | 59.33 | 0.00 | 0.00 | 720.00 |
May | 57.73 | 3.37 | 54.36 | 34.48 | 47.07 | 0.00 | 0.00 | 744.00 |
June | 67.19 | 7.67 | 59.53 | 49.77 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 61.37 | 5.66 | 55.71 | 55.54 | 30.47 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 42.74 | 36.13 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 24.71 | 50.51 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 8.99 | 68.01 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.30 | 98.29 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.10 | 142.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.46 | 21.00 | 79.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.10 | 30.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.19 | 7.67 | 59.53 | 55.54 | 170.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.33 | 11.79 | 16.53 | 12.63 | 182.82 | 0.00 | 0.00 | 744.00 |
February | 46.74 | 25.72 | 21.02 | 43.16 | 120.35 | 0.00 | 0.00 | 672.00 |
March | 76.47 | 36.45 | 40.03 | 85.98 | 90.97 | 1.67 | 0.00 | 744.00 |
April | 94.81 | 53.02 | 41.79 | 119.93 | 56.50 | 3.50 | 0.00 | 720.00 |
May | 121.66 | 69.39 | 52.27 | 162.09 | 46.90 | 5.67 | 0.00 | 744.00 |
June | 146.49 | 94.03 | 52.46 | 194.61 | 50.42 | 0.00 | 0.00 | 720.00 |
July | 151.67 | 106.11 | 45.55 | 198.95 | 61.14 | 0.00 | 0.00 | 744.00 |
August | 126.31 | 86.12 | 40.19 | 162.52 | 63.37 | 0.00 | 0.00 | 744.00 |
September | 87.71 | 55.63 | 32.08 | 111.64 | 62.47 | 0.00 | 0.00 | 720.00 |
October | 54.63 | 30.39 | 24.24 | 65.32 | 68.93 | 0.00 | 0.00 | 744.00 |
November | 33.08 | 16.28 | 16.80 | 30.57 | 92.03 | 0.00 | 0.00 | 720.00 |
December | 22.22 | 8.71 | 13.51 | 11.14 | 144.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.72 | 49.61 | 33.11 | 100.19 | 86.68 | 10.83 | 0.00 | 8760.00 |
Minimum of Months | 22.22 | 8.71 | 13.51 | 11.14 | 46.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 151.67 | 106.11 | 52.46 | 198.95 | 182.82 | 5.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56507435.27 | 0.746977E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155319E+09 | 0.465907E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.234231E+09 | 0.409355E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397506E+09 | 0.258435E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.555704E+09 | 0.219578E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.632506E+09 | 0.169688E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.731500E+09 | 0.154398E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.594340E+09 | 0.170230E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.421971E+09 | 0.222275E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.257253E+09 | 0.302295E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.132887E+09 | 0.408760E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52534774.00 | 0.617430E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.422226E+10 | 0.414533E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52534774.00 | 0.154398E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.731500E+09 | 0.746977E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56507435.27 | 0.746977E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155319E+09 | 0.465907E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.234231E+09 | 0.409355E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397506E+09 | 0.258435E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.555704E+09 | 0.219578E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.632506E+09 | 0.169688E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.731500E+09 | 0.154398E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.594340E+09 | 0.170230E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.421971E+09 | 0.222275E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.257253E+09 | 0.302295E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.132887E+09 | 0.408760E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52534774.00 | 0.617430E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.422226E+10 | 0.414533E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52534774.00 | 0.154398E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.731500E+09 | 0.746977E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45064288.41 | 0.00 | 45064288.41 | 499407.54 | 0.456476E+09 |
February | 57470429.67 | 0.00 | 57470429.67 | 6857345.21 | 0.292606E+09 |
March | 0.103373E+09 | 5154.92 | 0.103368E+09 | 23766342.86 | 0.247230E+09 |
April | 0.114392E+09 | 857486.23 | 0.113534E+09 | 52143234.08 | 0.153783E+09 |
May | 0.154641E+09 | 9033514.49 | 0.145607E+09 | 92348385.72 | 0.126069E+09 |
June | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.129012E+09 | 89019643.84 |
July | 0.164389E+09 | 15169360.03 | 0.149219E+09 | 0.148773E+09 | 81611436.43 |
August | 0.133290E+09 | 4794192.82 | 0.128496E+09 | 0.114477E+09 | 96770388.00 |
September | 95713512.75 | 81737.00 | 95631775.75 | 64058193.95 | 0.130911E+09 |
October | 72072435.85 | 0.00 | 72072435.85 | 24089981.36 | 0.182156E+09 |
November | 47415011.88 | 0.00 | 47415011.88 | 5962360.52 | 0.254756E+09 |
December | 37788945.48 | 0.00 | 37788945.48 | 279360.80 | 0.381556E+09 |
Annual Sum or Average | 0.119978E+10 | 49813360.58 | 0.114997E+10 | 0.662267E+09 | 0.249294E+10 |
Minimum of Months | 37788945.48 | 0.00 | 37788945.48 | 279360.80 | 81611436.43 |
Maximum of Months | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.148773E+09 | 0.456476E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45062835.23 | 0.00 | 45062835.23 | 499311.39 | 0.456476E+09 |
February | 57468698.97 | 0.00 | 57468698.97 | 6856953.13 | 0.292606E+09 |
March | 0.103370E+09 | 5154.68 | 0.103365E+09 | 23764496.27 | 0.247231E+09 |
April | 0.114389E+09 | 857446.04 | 0.113531E+09 | 52140813.51 | 0.153783E+09 |
May | 0.154636E+09 | 9033091.07 | 0.145603E+09 | 92344639.67 | 0.126069E+09 |
June | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.129007E+09 | 89019501.00 |
July | 0.164384E+09 | 15168649.02 | 0.149215E+09 | 0.148769E+09 | 81610845.45 |
August | 0.133286E+09 | 4793968.11 | 0.128492E+09 | 0.114474E+09 | 96769965.10 |
September | 95710774.52 | 81733.17 | 95629041.36 | 64056123.85 | 0.130911E+09 |
October | 72070253.22 | 0.00 | 72070253.22 | 24088731.45 | 0.182156E+09 |
November | 47413524.99 | 0.00 | 47413524.99 | 5961897.88 | 0.254756E+09 |
December | 37787710.35 | 0.00 | 37787710.35 | 279319.61 | 0.381556E+09 |
Annual Sum or Average | 0.119975E+10 | 49811025.76 | 0.114993E+10 | 0.662243E+09 | 0.249294E+10 |
Minimum of Months | 37787710.35 | 0.00 | 37787710.35 | 279319.61 | 81610845.45 |
Maximum of Months | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.148769E+09 | 0.456476E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75876288.62 | 31589610.53 | 44286678.10 | 33822117.34 | 0.489657E+09 |
February | 0.113083E+09 | 62225556.23 | 50857853.57 | 0.104422E+09 | 0.291140E+09 |
March | 0.204823E+09 | 97618966.73 | 0.107204E+09 | 0.230298E+09 | 0.243644E+09 |
April | 0.245757E+09 | 0.137428E+09 | 0.108329E+09 | 0.310870E+09 | 0.146458E+09 |
May | 0.325866E+09 | 0.185865E+09 | 0.140001E+09 | 0.434132E+09 | 0.125623E+09 |
June | 0.379700E+09 | 0.243718E+09 | 0.135982E+09 | 0.504436E+09 | 0.130700E+09 |
July | 0.406221E+09 | 0.284214E+09 | 0.122008E+09 | 0.532857E+09 | 0.163745E+09 |
August | 0.338316E+09 | 0.230658E+09 | 0.107658E+09 | 0.435304E+09 | 0.169732E+09 |
September | 0.227340E+09 | 0.144180E+09 | 83159188.19 | 0.289382E+09 | 0.161935E+09 |
October | 0.146332E+09 | 81393924.25 | 64937668.69 | 0.174944E+09 | 0.184613E+09 |
November | 85741055.69 | 42208106.05 | 43532949.64 | 79245926.59 | 0.238547E+09 |
December | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.387801E+09 |
Annual Sum or Average | 0.260856E+10 | 0.156442E+10 | 0.104414E+10 | 0.315956E+10 | 0.273360E+10 |
Minimum of Months | 59503264.95 | 23323763.14 | 36179501.80 | 29847652.96 | 0.125623E+09 |
Maximum of Months | 0.406221E+09 | 0.284214E+09 | 0.140001E+09 | 0.532857E+09 | 0.489657E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 31.61 | 887.68 | 154.38 | 49.05 | 105.34 | 0.00 | 0.00 |
February | 123.69 | 616.69 | 252.05 | 100.66 | 151.39 | 0.00 | 0.00 |
March | 187.75 | 485.38 | 339.77 | 96.45 | 243.32 | 0.00 | 0.00 |
April | 344.24 | 315.35 | 430.45 | 151.83 | 278.63 | 0.00 | 0.00 |
May | 482.52 | 256.71 | 538.72 | 199.79 | 338.93 | 0.00 | 0.00 |
June | 585.20 | 197.23 | 594.52 | 226.57 | 367.95 | 0.00 | 0.00 |
July | 654.97 | 173.89 | 594.60 | 249.82 | 344.77 | 0.00 | 0.00 |
August | 528.50 | 198.59 | 499.38 | 199.28 | 300.10 | 0.00 | 0.00 |
September | 373.17 | 270.66 | 395.84 | 162.77 | 233.07 | 0.00 | 0.00 |
October | 205.37 | 357.03 | 284.38 | 114.61 | 169.77 | 0.00 | 0.00 |
November | 96.57 | 501.41 | 199.52 | 80.85 | 118.68 | 0.00 | 0.00 |
December | 29.73 | 736.25 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Annual Sum or Average | 304.58 | 415.80 | 368.98 | 139.96 | 229.02 | 0.00 | 0.00 |
Minimum of Months | 29.73 | 173.89 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Maximum of Months | 654.97 | 887.68 | 594.60 | 249.82 | 367.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.28 | 1828.17 | 283.29 | 117.94 | 165.35 | 0.00 | 0.00 |
February | 431.64 | 1203.45 | 467.44 | 257.22 | 210.23 | 0.00 | 0.00 |
March | 859.83 | 909.66 | 764.72 | 364.47 | 400.25 | 0.00 | 0.00 |
April | 1199.34 | 565.04 | 948.14 | 530.20 | 417.94 | 0.00 | 0.00 |
May | 1620.86 | 469.02 | 1216.64 | 693.94 | 522.70 | 0.00 | 0.00 |
June | 1946.13 | 504.24 | 1464.89 | 940.27 | 524.62 | 0.00 | 0.00 |
July | 1989.46 | 611.35 | 1516.66 | 1061.13 | 455.52 | 0.00 | 0.00 |
August | 1625.24 | 633.70 | 1263.13 | 861.18 | 401.95 | 0.00 | 0.00 |
September | 1116.44 | 624.75 | 877.08 | 556.25 | 320.83 | 0.00 | 0.00 |
October | 653.16 | 689.26 | 546.34 | 303.89 | 242.45 | 0.00 | 0.00 |
November | 305.73 | 920.32 | 330.79 | 162.84 | 167.95 | 0.00 | 0.00 |
December | 111.44 | 1447.88 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Annual Sum or Average | 1001.89 | 866.82 | 827.17 | 496.08 | 331.09 | 0.00 | 0.00 |
Minimum of Months | 111.44 | 469.02 | 222.16 | 87.08 | 135.08 | 0.00 | 0.00 |
Maximum of Months | 1989.46 | 1828.17 | 1516.66 | 1061.13 | 524.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 84659692.13 | 0.237755E+10 | 0.413500E+09 | 0.131364E+09 | 0.282136E+09 | 0.00 | 0.00 |
February | 0.299224E+09 | 0.149190E+10 | 0.609760E+09 | 0.243524E+09 | 0.366237E+09 | 0.00 | 0.00 |
March | 0.502860E+09 | 0.130004E+10 | 0.910051E+09 | 0.258341E+09 | 0.651710E+09 | 0.00 | 0.00 |
April | 0.892261E+09 | 0.817399E+09 | 0.111574E+10 | 0.393537E+09 | 0.722201E+09 | 0.00 | 0.00 |
May | 0.129239E+10 | 0.687582E+09 | 0.144291E+10 | 0.535123E+09 | 0.907791E+09 | 0.00 | 0.00 |
June | 0.151684E+10 | 0.511222E+09 | 0.154099E+10 | 0.587270E+09 | 0.953721E+09 | 0.00 | 0.00 |
July | 0.175427E+10 | 0.465749E+09 | 0.159257E+10 | 0.669131E+09 | 0.923443E+09 | 0.00 | 0.00 |
August | 0.141554E+10 | 0.531913E+09 | 0.133754E+10 | 0.533738E+09 | 0.803798E+09 | 0.00 | 0.00 |
September | 0.967248E+09 | 0.701563E+09 | 0.102602E+10 | 0.421900E+09 | 0.604117E+09 | 0.00 | 0.00 |
October | 0.550058E+09 | 0.956277E+09 | 0.761684E+09 | 0.306962E+09 | 0.454722E+09 | 0.00 | 0.00 |
November | 0.250317E+09 | 0.129965E+10 | 0.517165E+09 | 0.209556E+09 | 0.307609E+09 | 0.00 | 0.00 |
December | 79624880.00 | 0.197197E+10 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.960530E+10 | 0.131128E+11 | 0.116363E+11 | 0.441382E+10 | 0.722246E+10 | 0.00 | 0.00 |
Minimum of Months | 79624880.00 | 0.465749E+09 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175427E+10 | 0.237755E+10 | 0.159257E+10 | 0.669131E+09 | 0.953721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338217E+09 | 0.489657E+10 | 0.758763E+09 | 0.315896E+09 | 0.442867E+09 | 0.00 | 0.00 |
February | 0.104422E+10 | 0.291140E+10 | 0.113083E+10 | 0.622256E+09 | 0.508579E+09 | 0.00 | 0.00 |
March | 0.230298E+10 | 0.243644E+10 | 0.204823E+10 | 0.976190E+09 | 0.107204E+10 | 0.00 | 0.00 |
April | 0.310869E+10 | 0.146458E+10 | 0.245757E+10 | 0.137428E+10 | 0.108329E+10 | 0.00 | 0.00 |
May | 0.434132E+10 | 0.125623E+10 | 0.325866E+10 | 0.185865E+10 | 0.140001E+10 | 0.00 | 0.00 |
June | 0.504436E+10 | 0.130700E+10 | 0.379700E+10 | 0.243718E+10 | 0.135982E+10 | 0.00 | 0.00 |
July | 0.532857E+10 | 0.163744E+10 | 0.406221E+10 | 0.284214E+10 | 0.122008E+10 | 0.00 | 0.00 |
August | 0.435304E+10 | 0.169731E+10 | 0.338316E+10 | 0.230658E+10 | 0.107658E+10 | 0.00 | 0.00 |
September | 0.289381E+10 | 0.161935E+10 | 0.227340E+10 | 0.144180E+10 | 0.831592E+09 | 0.00 | 0.00 |
October | 0.174944E+10 | 0.184613E+10 | 0.146332E+10 | 0.813939E+09 | 0.649377E+09 | 0.00 | 0.00 |
November | 0.792459E+09 | 0.238547E+10 | 0.857411E+09 | 0.422081E+09 | 0.435329E+09 | 0.00 | 0.00 |
December | 0.298476E+09 | 0.387801E+10 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.315956E+11 | 0.273359E+11 | 0.260856E+11 | 0.156442E+11 | 0.104414E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298476E+09 | 0.125623E+10 | 0.595033E+09 | 0.233238E+09 | 0.361795E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532857E+10 | 0.489657E+10 | 0.406221E+10 | 0.284214E+10 | 0.140001E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104526E+10 | -957256506.3 | 0.00 | 0.00 | 744.00 | 0.00 | -88007211.0 | 58.99 | 0.00 | 0.00 |
February | 0.973909E+09 | -894741840.1 | 0.00 | 0.00 | 672.00 | 0.00 | -79166708.5 | 58.99 | 0.00 | 0.00 |
March | 0.112209E+10 | -.103500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87095304.3 | 58.99 | 0.00 | 0.00 |
April | 0.100928E+10 | -926361166.1 | 0.00 | 0.00 | 720.00 | 0.00 | -82918844.2 | 58.99 | 0.00 | 0.00 |
May | 0.992617E+09 | -910532405.0 | 0.00 | 0.00 | 744.00 | 0.00 | -82084858.0 | 58.99 | 0.00 | 0.00 |
June | 0.924853E+09 | -851150364.8 | 0.00 | 0.00 | 720.00 | 0.00 | -73702404.9 | 58.99 | 0.00 | 0.00 |
July | 0.855160E+09 | -780891943.0 | 0.00 | 0.00 | 744.00 | 0.00 | -74267813.0 | 58.99 | 0.00 | 0.00 |
August | 0.894496E+09 | -819667171.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74828635.0 | 58.99 | 0.00 | 0.00 |
September | 0.847166E+09 | -772425842.9 | 0.00 | 0.00 | 720.00 | 0.00 | -74739742.5 | 58.99 | 0.00 | 0.00 |
October | 0.893242E+09 | -810584639.2 | 0.00 | 0.00 | 744.00 | 0.00 | -82657231.2 | 59.00 | 0.00 | 0.00 |
November | 0.911337E+09 | -827630525.7 | 0.00 | 0.00 | 720.00 | 0.00 | -83706665.2 | 58.99 | 0.00 | 0.00 |
December | 0.100241E+10 | -914642986.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87766507.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114718E+11 | -.105009E+11 | 8760.00 | -970941925.7 | 58.99 | |||||
Minimum of Months | 0.847166E+09 | -.103500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88007211.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112209E+10 | -772425842.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73702404.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.96 | 0.88 | 04-JAN-11:20 | 114.34 | 8.41 | 0.00 | 31.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.95 | 0.88 | 03-FEB-11:09 | 120.54 | 8.88 | 0.00 | 35.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.92 | 0.88 | 02-MAR-09:09 | 223.65 | 11.94 | 0.00 | 160.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.92 | 0.88 | 01-APR-09:09 | 233.38 | 11.89 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.91 | 0.88 | 01-MAY-08:20 | 1038.58 | 13.10 | 18.67 | 249.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.92 | 0.88 | 01-JUN-13:39 | 3234.11 | 14.22 | 51.33 | 267.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.91 | 0.88 | 01-JUL-07:19 | 2549.80 | 13.82 | 33.83 | 252.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.93 | 0.88 | 01-AUG-08:00 | 214.67 | 11.33 | 0.00 | 176.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.93 | 0.88 | 03-SEP-08:39 | 173.80 | 10.57 | 0.00 | 111.17 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.95 | 0.88 | 01-OCT-12:39 | 136.77 | 9.31 | 0.00 | 64.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.96 | 0.88 | 01-NOV-10:30 | 104.16 | 8.02 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.97 | 0.88 | 04-DEC-11:30 | 86.81 | 7.18 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.93 | 836.06 | 11.13 | 103.83 | 1552.67 | ||||||
Minimum of Months | 226.83 | 0.91 | 0.88 | 86.81 | 7.18 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 434.17 | 0.97 | 0.88 | 3234.11 | 14.22 | 51.33 | 267.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.84 | 0.78 | 01-JAN-13:00 | 685.96 | 21.62 | 64.67 | 96.83 | 685.75 | 21.51 | 75.67 | 168.50 |
February | 275.00 | 0.83 | 0.78 | 01-FEB-14:09 | 777.19 | 21.13 | 74.17 | 126.67 | 1037.44 | 23.58 | 119.83 | 193.83 |
March | 304.00 | 0.81 | 0.78 | 01-MAR-09:30 | 869.82 | 20.65 | 81.50 | 217.83 | 2155.85 | 25.69 | 184.50 | 283.67 |
April | 325.17 | 0.81 | 0.78 | 01-APR-09:30 | 688.77 | 18.63 | 41.17 | 213.67 | 2567.33 | 25.19 | 175.33 | 305.00 |
May | 385.83 | 0.80 | 0.78 | 01-MAY-08:20 | 499.02 | 17.44 | 7.83 | 288.50 | 2635.54 | 23.64 | 204.17 | 367.50 |
June | 434.17 | 0.81 | 0.78 | 01-JUN-13:39 | 481.38 | 16.86 | 2.33 | 311.17 | 2760.28 | 22.64 | 204.33 | 377.50 |
July | 417.33 | 0.81 | 0.78 | 01-JUL-06:00 | 476.81 | 17.32 | 6.67 | 263.67 | 3235.15 | 23.92 | 192.83 | 364.83 |
August | 421.33 | 0.82 | 0.78 | 01-AUG-09:09 | 430.48 | 16.91 | 19.17 | 232.17 | 2425.33 | 23.76 | 178.33 | 333.17 |
September | 352.17 | 0.82 | 0.78 | 01-SEP-13:30 | 579.50 | 18.46 | 49.83 | 186.50 | 2491.06 | 25.76 | 166.50 | 283.83 |
October | 317.67 | 0.83 | 0.78 | 01-OCT-12:39 | 1045.22 | 21.71 | 90.17 | 165.17 | 1476.66 | 24.10 | 141.67 | 230.83 |
November | 269.50 | 0.84 | 0.78 | 01-NOV-10:50 | 719.56 | 22.45 | 86.33 | 114.67 | 909.28 | 23.26 | 102.17 | 181.33 |
December | 236.83 | 0.85 | 0.78 | 01-DEC-12:20 | 480.02 | 21.71 | 69.67 | 80.33 | 478.39 | 19.34 | 27.33 | 154.17 |
Annual Sum or Average | 3965.83 | 0.82 | 626.18 | 19.18 | 593.50 | 2297.17 | 2073.47 | 23.67 | 1772.67 | 3244.17 | ||
Minimum of Months | 226.83 | 0.80 | 0.78 | 430.48 | 16.86 | 2.33 | 80.33 | 478.39 | 19.34 | 27.33 | 154.17 | |
Maximum of Months | 434.17 | 0.85 | 0.78 | 1045.22 | 22.45 | 90.17 | 311.17 | 3235.15 | 25.76 | 204.33 | 377.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110040E+11 | 25828.74 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729569E+10 | 25828.74 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650781E+10 | 25828.74 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324739E+10 | 25828.74 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196285E+10 | 25828.74 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34282503.26 | 25828.74 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1333825.82 | 1334.36 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321997E+09 | 25828.74 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131928E+10 | 25828.74 | 04-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426423E+10 | 25828.74 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797867E+10 | 25828.74 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439376E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110040E+11 | 25828.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515505E+11 | 82696.42 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298437E+11 | 82696.42 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221258E+11 | 82696.42 | 02-MAR-22:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.724831E+10 | 82696.42 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369811E+10 | 82696.42 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166536E+09 | 23636.19 | 19-SEP-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231590E+10 | 82696.42 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172481E+11 | 82696.42 | 11-NOV-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367775E+11 | 82696.42 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170975E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515505E+11 | 82696.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190504E+12 | 182568.98 | 05-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999125E+11 | 125097.53 | 03-FEB-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656409E+11 | 131073.70 | 06-MAR-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.751776E+10 | 60296.03 | 29-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.616607E+10 | 51118.34 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104004E+10 | 26766.45 | 11-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.494184E+11 | 114226.65 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127885E+12 | 179373.00 | 31-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548085E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190504E+12 | 182568.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.300699E+09 | 0.300541E+09 | 16367.61 | 20-MAY-18:01 | 16367.61 | 0.00 |
June | 0.00 | 0.00 | 0.253654E+10 | 0.245480E+10 | 17606.82 | 20-JUN-22:11 | 14360.16 | 0.00 |
July | 0.00 | 0.00 | 0.583143E+10 | 0.564653E+10 | 18053.40 | 18-JUL-22:21 | 10669.90 | 0.00 |
August | 0.00 | 0.00 | 0.475124E+10 | 0.472185E+10 | 16612.99 | 08-AUG-21:01 | 16332.00 | 0.00 |
September | 0.00 | 0.00 | 0.168494E+10 | 0.155376E+10 | 18294.84 | 07-SEP-18:21 | 13131.28 | 0.00 |
October | 0.00 | 0.00 | 46775389.42 | 46775389.42 | 3424.81 | 18-OCT-16:00 | 3424.81 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.151516E+11 | 0.147243E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.583143E+10 | 0.564653E+10 | 18294.84 | 16367.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 44683409.33 | 44683409.33 | 4501.77 | 20-MAY-16:00 | 4501.77 | 0.00 |
June | 0.00 | 0.00 | 0.319161E+10 | 0.309443E+10 | 49961.98 | 22-JUN-18:11 | 40580.52 | 0.00 |
July | 0.00 | 0.00 | 0.100618E+11 | 0.989295E+10 | 50194.42 | 16-JUL-10:04 | 38324.52 | 0.00 |
August | 0.00 | 0.00 | 0.731161E+10 | 0.729299E+10 | 45906.46 | 05-AUG-19:51 | 45906.46 | 0.00 |
September | 0.00 | 0.00 | 0.232358E+10 | 0.215955E+10 | 51853.23 | 06-SEP-18:11 | 36960.37 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.229332E+11 | 0.224846E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100618E+11 | 0.989295E+10 | 51853.23 | 45906.46 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121346E+10 | 0.08 | 466.86 | 01-JAN-00:03 | 0.09 |
February | 0.938711E+09 | 0.07 | 466.86 | 01-FEB-00:02 | 0.09 |
March | 0.892520E+09 | 0.06 | 466.86 | 01-MAR-00:03 | 0.09 |
April | 0.242108E+09 | 0.02 | 466.86 | 01-APR-00:10 | 0.09 |
May | 0.139539E+09 | 0.01 | 466.86 | 01-MAY-00:05 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 32983501.91 | 0.00 | 466.86 | 10-OCT-00:35 | 0.09 |
November | 0.579646E+09 | 0.04 | 466.86 | 03-NOV-04:57 | 0.09 |
December | 0.111878E+10 | 0.08 | 466.86 | 01-DEC-00:02 | 0.09 |
Annual Sum or Average | 0.515774E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121346E+10 | 0.08 | 466.86 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125292E+10 | 0.71 | 1135.28 | 02-JAN-15:00 | 1.04 |
February | 0.111107E+10 | 0.59 | 1135.28 | 01-FEB-08:40 | 1.04 |
March | 0.127656E+10 | 0.53 | 1135.28 | 01-MAR-11:00 | 1.04 |
April | 0.115497E+10 | 0.43 | 1135.28 | 04-APR-12:30 | 1.04 |
May | 0.119437E+10 | 0.44 | 1135.28 | 01-MAY-14:20 | 1.04 |
June | 0.124931E+10 | 0.46 | 1135.28 | 02-JUN-14:00 | 1.04 |
July | 0.137105E+10 | 0.52 | 1135.28 | 05-JUL-08:30 | 1.03 |
August | 0.141886E+10 | 0.53 | 1135.28 | 02-AUG-16:00 | 1.04 |
September | 0.121663E+10 | 0.46 | 1135.28 | 08-SEP-07:20 | 1.03 |
October | 0.113922E+10 | 0.41 | 1135.28 | 03-OCT-08:70 | 1.04 |
November | 0.112084E+10 | 0.46 | 1135.28 | 01-NOV-07:30 | 1.04 |
December | 0.120742E+10 | 0.60 | 1135.28 | 05-DEC-16:10 | 1.04 |
Annual Sum or Average | 0.147132E+11 | 0.51 | |||
Minimum of Months | 0.111107E+10 | 0.41 | 1135.28 | 1.03 | |
Maximum of Months | 0.141886E+10 | 0.71 | 1135.28 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371077E+10 | 0.88 | 2618.40 | 03-JAN-11:20 | 1.01 |
February | 0.310936E+10 | 0.85 | 2618.40 | 01-FEB-07:30 | 1.01 |
March | 0.340212E+10 | 0.84 | 2618.40 | 01-MAR-09:00 | 1.01 |
April | 0.281826E+10 | 0.65 | 2618.40 | 01-APR-07:10 | 1.01 |
May | 0.281138E+10 | 0.50 | 2618.40 | 01-MAY-07:40 | 1.01 |
June | 0.272076E+10 | 0.41 | 2618.40 | 06-JUN-14:30 | 0.99 |
July | 0.276649E+10 | 0.42 | 2618.40 | 03-JUL-14:20 | 1.00 |
August | 0.291507E+10 | 0.43 | 2618.40 | 01-AUG-15:20 | 1.00 |
September | 0.266505E+10 | 0.41 | 2618.40 | 02-SEP-16:50 | 1.00 |
October | 0.266417E+10 | 0.46 | 2618.40 | 10-OCT-09:50 | 1.01 |
November | 0.296364E+10 | 0.75 | 2618.40 | 02-NOV-07:20 | 1.01 |
December | 0.348390E+10 | 0.87 | 2618.40 | 01-DEC-08:00 | 1.01 |
Annual Sum or Average | 0.360310E+11 | 0.62 | |||
Minimum of Months | 0.266417E+10 | 0.41 | 2618.40 | 0.99 | |
Maximum of Months | 0.371077E+10 | 0.88 | 2618.40 | 1.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.17 | 0.00 |
February | 2.83 | 0.00 |
March | 2.45 | 0.00 |
April | 0.83 | 0.03 |
May | 0.85 | 0.29 |
June | 6.44 | 0.03 |
July | 18.94 | 0.05 |
August | 14.32 | 0.03 |
September | 4.84 | 0.07 |
October | 0.69 | 0.37 |
November | 1.76 | 0.00 |
December | 2.25 | 0.00 |
Annual Sum or Average | 59.39 | 0.04 |
Minimum of Months | 0.69 | 0.00 |
Maximum of Months | 18.94 | 0.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.25 | 0.00 |
July | 2.51 | 0.00 |
August | 0.22 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.32 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.51 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.24 | 0.00 |
August | 0.52 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.84 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.52 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125292E+10 | 0.156477E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111107E+10 | 0.105114E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127656E+10 | 0.946526E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115497E+10 | 0.476149E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.126338E+10 | 0.287953E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182281E+10 | 51599421.32 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.269885E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.250077E+10 | 2071706.07 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.159243E+10 | 0.478224E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114988E+10 | 0.194540E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112084E+10 | 0.622181E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120742E+10 | 0.115104E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181519E+11 | 0.634748E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111107E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.269885E+10 | 0.156477E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.371077E+10 | 0.726672E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.310936E+10 | 0.427263E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.340212E+10 | 0.319377E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.281826E+10 | 0.106971E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.282322E+10 | 0.540626E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.350801E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.527508E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.475574E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.324708E+10 | 0.251752E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.266417E+10 | 0.342948E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.296364E+10 | 0.249265E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.348390E+10 | 0.526190E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.417614E+11 | 0.244661E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.266417E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.527508E+10 | 0.726672E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125292E+10 | 0.00 | 0.110040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111107E+10 | 0.00 | 0.729569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127656E+10 | 0.00 | 0.650781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115497E+10 | 0.00 | 0.324739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119437E+10 | 0.300699E+09 | 0.196285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124931E+10 | 0.253654E+10 | 34282503.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137105E+10 | 0.583143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141886E+10 | 0.475124E+10 | 1333825.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121663E+10 | 0.168494E+10 | 0.321997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113922E+10 | 46775389.42 | 0.131928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112084E+10 | 0.00 | 0.426423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120742E+10 | 0.00 | 0.797867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147132E+11 | 0.151516E+11 | 0.439376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141886E+10 | 0.583143E+10 | 0.110040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.371077E+10 | 0.00 | 0.515505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310936E+10 | 0.00 | 0.298437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340212E+10 | 0.00 | 0.221258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281826E+10 | 0.00 | 0.724831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281138E+10 | 44683409.33 | 0.369811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.272076E+10 | 0.319161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276649E+10 | 0.100618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.291507E+10 | 0.731161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266505E+10 | 0.232358E+10 | 0.166536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266417E+10 | 0.00 | 0.231590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296364E+10 | 0.00 | 0.172481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348390E+10 | 0.00 | 0.367775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360310E+11 | 0.229332E+11 | 0.170975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.266417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371077E+10 | 0.100618E+11 | 0.515505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.125292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119437E+10 | 0.00 | 0.00 | 0.00 | 69011529.33 | 0.00 | 0.287953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124931E+10 | 0.00 | 0.00 | 0.00 | 0.573505E+09 | 0.00 | 51599421.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137105E+10 | 0.00 | 0.00 | 0.00 | 0.132780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141886E+10 | 0.00 | 0.00 | 0.00 | 0.108191E+10 | 0.00 | 2071706.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121663E+10 | 0.00 | 0.00 | 0.00 | 0.375795E+09 | 0.00 | 0.478224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113922E+10 | 0.00 | 0.00 | 0.00 | 10657493.55 | 0.00 | 0.194540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147132E+11 | 0.00 | 0.00 | 0.00 | 0.343868E+10 | 0.00 | 0.634748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.111107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141886E+10 | 0.00 | 0.00 | 0.00 | 0.132780E+10 | 0.00 | 0.156477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.371077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281138E+10 | 0.00 | 0.00 | 0.00 | 11845693.07 | 0.00 | 0.540626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.272076E+10 | 0.00 | 0.00 | 0.00 | 0.787248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276649E+10 | 0.00 | 0.00 | 0.00 | 0.250859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.291507E+10 | 0.00 | 0.00 | 0.00 | 0.184068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266505E+10 | 0.00 | 0.00 | 0.00 | 0.582028E+09 | 0.00 | 0.251752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360310E+11 | 0.00 | 0.00 | 0.00 | 0.573039E+10 | 0.00 | 0.244661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.266417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371077E+10 | 0.00 | 0.00 | 0.00 | 0.250859E+10 | 0.00 | 0.726672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289196E+10 | 0.00 | 0.00 | 0.12 |
February | 22415283.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203008E+10 | 0.00 | 0.00 | 0.13 |
March | 8809129.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197886E+10 | 0.00 | 0.00 | 0.13 |
April | 0.179712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111627E+10 | 0.00 | 0.00 | 0.13 |
May | 0.348016E+09 | 4594958.03 | 1069207.99 | 298433.86 | 2144054.18 | 0.701273E+09 | 0.214739E+09 | 6266.96 | 0.21 |
June | 0.201715E+09 | 87335822.02 | 0.00 | 3213197.41 | 0.00 | 8856181.28 | 0.153922E+10 | 0.00 | 0.48 |
July | 14348403.72 | 0.211946E+09 | 0.00 | 6746543.65 | 0.00 | 0.00 | 0.166668E+10 | 0.00 | 0.57 |
August | 46820772.13 | 0.140359E+09 | 0.00 | 6405768.85 | 0.00 | 0.00 | 0.201655E+10 | 0.00 | 0.62 |
September | 0.373492E+09 | 61603067.23 | 0.00 | 3204708.99 | 0.00 | 0.107852E+09 | 0.134071E+10 | 0.00 | 0.42 |
October | 0.642684E+09 | 1023824.94 | 0.00 | 88767.40 | 0.00 | 0.479382E+09 | 0.145917E+09 | 0.00 | 0.16 |
November | 0.146552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142438E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237367E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.198456E+10 | 0.506863E+09 | 1069207.99 | 19957420.17 | 2144054.18 | 0.131126E+11 | 0.692383E+10 | 6266.96 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.642684E+09 | 0.211946E+09 | 1069207.99 | 6746543.65 | 2144054.18 | 0.289196E+10 | 0.201655E+10 | 6266.96 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895074E+10 | 0.00 | 0.00 | 0.17 |
February | 0.132914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487647E+10 | 0.00 | 0.00 | 0.17 |
March | 0.275669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290975E+10 | 0.00 | 0.00 | 0.19 |
April | 0.292091E+10 | 0.00 | 0.00 | 0.00 | 4392344.47 | 0.573784E+09 | 0.00 | 0.00 | 0.18 |
May | 0.291618E+10 | 3020214.49 | 0.00 | 0.00 | 23787815.63 | 0.307717E+09 | 0.00 | 0.00 | 0.19 |
June | 0.210002E+10 | 0.195333E+09 | 0.00 | 2183037.29 | 1260504.49 | 0.00 | 0.718874E+09 | 0.00 | 0.28 |
July | 0.600961E+09 | 0.478405E+09 | 0.00 | 8688894.97 | 0.00 | 0.00 | 0.235744E+10 | 0.00 | 0.41 |
August | 0.111522E+10 | 0.375456E+09 | 0.00 | 4721615.36 | 0.00 | 0.00 | 0.209763E+10 | 0.00 | 0.38 |
September | 0.223463E+10 | 0.131814E+09 | 0.00 | 1547458.75 | 4186463.31 | 10920770.00 | 0.720272E+09 | 0.00 | 0.25 |
October | 0.305981E+10 | 0.00 | 0.00 | 0.00 | 8347196.18 | 0.162429E+09 | 0.00 | 0.00 | 0.18 |
November | 0.236124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198659E+10 | 0.00 | 0.00 | 0.17 |
December | 0.115134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609226E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.229557E+11 | 0.118403E+10 | 0.00 | 17141006.37 | 41974324.09 | 0.258707E+11 | 0.589421E+10 | 0.00 | 0.23 |
Minimum of Months | 0.409527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.305981E+10 | 0.478405E+09 | 0.00 | 8688894.97 | 23787815.63 | 0.895074E+10 | 0.235744E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |