Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1030.83 | 213.20 | 213.20 |
Net Site Energy | 1030.83 | 213.20 | 213.20 |
Total Source Energy | 3255.89 | 673.38 | 673.38 |
Net Source Energy | 3255.89 | 673.38 | 673.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 132.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1026.63 | 4.20 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 125.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 109.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.28 | 0.87 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 212.33 | 0.87 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.28 | 0.87 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 212.33 | 0.87 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1026.631 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1026.631 | 100.00 |
Total On-Site and Utility Electric Sources | 1026.631 | 100.00 |
Total Electricity End Uses | 1026.631 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.33 |
Time Setpoint Not Met During Occupied Cooling | 39.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 225.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:50 | 02-JAN-06:10 | - | - | - | 27-APR-11:30 |
Heating | 0.00 | 36132.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10753.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1679.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 86382.36 | 36132.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 36132.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8447.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1679.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.55 | 0.00 | 0.00 | 0.00 |
Cooling | 397.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 418.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3251.34 | 4.55 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.94 | 0.00 | 0.00 | 0.00 |
Cooling | 82.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 672.44 | 0.94 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.94 | 0.00 | 0.00 | 0.00 |
Cooling | 82.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 672.44 | 0.94 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.36 |
ZONE2 FINE STORAGE DIRECT AIR | 3.94 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.14 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.14 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 80657.00 |
PSZ-OFFICE HEATING COIL | 30625.13 |
PSZ-FINE STORAGE HEATING COIL | 112857.23 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 80657.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-FINE STORAGE | 3.94 | 3.94 | 3.94 | 3.94 | 3.94 | 3.94 | 1.00 | 1.00 | 3.94 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.36 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 3.94 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 1.36 | 24176.82 | 30625.13 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.94 | 3.94 | 3.94 | 3.94 | 85629.93 | 112857.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.36 | 0.678730 | 1.36 | 22671.34 | 24176.82 | 12088.41 | 24176.82 | 0.772712 | 0.772710 | 0.772710 | 0.772710 |
PSZ-FINE STORAGE COOLING COIL | 3.94 | 1.97 | 3.94 | 73025.18 | 85629.93 | 42814.96 | 85629.93 | 0.711143 | 0.711140 | 0.711140 | 0.711140 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.36 | 1547.66 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.94 | 6900.18 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 1.209 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7281 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.64162135E-12 | 0.65646114E-15 | -0.12904024E-14 | 0.12678731E-15 |
13 | 3 | -0.33584230E-03 | 0.79457704E-06 | -0.48268613E-04 | 0.12317170E-12 |
14 | 2 | 1.6213285 | 0.18378730E-01 | 1.0506728 | -0.64380977E-04 |
15 | 1 | -7.2911921 | 0.49313376 | -16.520002 | 0.31060912 |
16 | 0 | 6.5034338 | 0.32172104 | 16.302612 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12904024E-14 | 0.65646114E-15 | 0.64162135E-12 | 0.12678731E-15 |
85 | 3 | -0.48268613E-04 | 0.79457704E-06 | -0.33584230E-03 | 0.12317170E-12 |
86 | 2 | 1.0506728 | 0.18378730E-01 | 1.6213285 | -0.64380977E-04 |
87 | 1 | -16.520002 | 0.49313376 | -7.2911921 | 0.31060912 |
88 | 0 | 16.302612 | 0.32172104 | 6.5034338 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 28 | 1 | VerySmooth | 4.149 | 0.255 | 0.127 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.36 | 29 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.361 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.12629 | 0.51106 | 0.51106 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.73817E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12483.83516 | 14980.60219 | 1.13122 | 1.35746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8214.00094 | 9856.80113 | 0.25386 | 0.30463 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 46506.79468 | 55808.15362 | 3.28468 | 3.94161 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23101.33543 | 27721.60251 | 0.60169 | 0.72203 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80000 | 5.57864E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 67214.16287 | 80656.99544 | 1.78254 | 2.13904 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19434.46 | 1.35746 | 1.35746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8659.88 | 0.30463 | 0.30463 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 69364.07 | 3.94161 | 3.94161 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 26411.52 | 0.72203 | 0.72203 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35746 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.94161 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.13904 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.13904 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 80656.99851 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 80656.99544 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35746 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35746 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35746 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35746 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35746 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.35746 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.94161 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.94161 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.94161 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.94161 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.94161 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.94161 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.35746 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.94161 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35746 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35746 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35746 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35746 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35746 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35746 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67873 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35746 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22671.33903 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24176.82000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12088.41000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 24176.82000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77271 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77271 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77271 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77271 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24176.82000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30625.13008 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35746 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1547.65691 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 30625.13008 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.94161 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.94161 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.94161 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.94161 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.94161 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.94161 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.97081 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.94161 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 73025.18332 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 85629.93000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 42814.96500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 85629.93000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71114 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71114 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71114 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71114 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85629.93000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112857.23195 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.94161 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6900.17765 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 112857.23195 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23123.2 | 10.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 82568.1 | 12.51 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 6.0462224132E-002 | 4.3007367194E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2871640998 | 0.3557274740 | Pass | Pass | 0.4250059194 | 1.4107234426 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.9196286887E-002 | 7.3369387319E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 1.023 | 1.209 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 5.229 | 0.450 | 0.449 | ||||||||||||
North Total or Average | 6.51 | 4.149 | 0.255 | 0.250 | ||||||||||||
Non-North Total or Average | 45.81 | 5.382 | 0.478 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.493 | 3.977 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.79 | 83.79 | 123.58 | |
Exterior Lighting Total | 7857.24 | 123.58 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24176.82 | 18681.67 | 5495.15 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85629.93 | 60894.87 | 24735.06 | 0.71 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23123.2 | 10.20 | ||||
PSZ-FINE STORAGE COOLING COIL | 82568.1 | 12.51 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 80657.00 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 30625.13 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 112857.23 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.14 | 198.74 | 92.91 | 1.00 | 3.54 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.36 | 1547.66 | 1140.11 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1018.41 | 3.94 | 6900.18 | 1750.60 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12483.84 | 14980.60 | 63.24 | 1.131 | 1.357 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00801 | 38.94 | 0.00558 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 46506.79 | 55808.15 | 40.05 | 3.285 | 3.942 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00759 | 38.94 | 0.00558 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00416 | 40.80 | 0.00558 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8214.00 | 9856.80 | 41.61 | 0.254 | 0.305 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00780 | 0.50 | 0.00432 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23101.34 | 27721.60 | 19.89 | 0.602 | 0.722 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00675 | 0.50 | 0.00432 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 67214.16 | 80657.00 | 25.17 | 1.783 | 2.139 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 9.99 | 0.00841 | 0.50 | 0.00432 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.36 | 1.36 | 0.30 | 0.30 | 1.3575 | 1.3575 | 1.3575 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.94 | 3.94 | 0.72 | 0.72 | 3.9416 | 3.9416 | 3.9416 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 80656.999 | 80656.999 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 80657.00 | 80657.00 | 2.139043 | 5.66 | 5.66 | 0.00654185 | 43.33 | 25.84 | 0.01600000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 9.99 | 0.00841303 | 100.0000 | 80657.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 24176.820 | 0.000 | 1.357460 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24176.82 | 24176.82 | 1.357460 | 25.03 | 15.17 | 0.00783013 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 7.5350 | 23.90 | 0.00801361 | 39.4291 | 12483.84 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 30625.130 | 30625.130 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 30625.13 | 30625.13 | 1.357463 | 14.12 | 9.89 | 0.00663010 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.5350 | 21.10 | 0.00780006 | 45.5139 | 8214.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 85629.930 | 0.000 | 3.941610 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 85629.93 | 85629.93 | 3.941610 | 28.02 | 15.81 | 0.00737390 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 10.7751 | 26.70 | 0.00759071 | 31.6362 | 46506.79 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 112857.232 | 112857.232 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 112857.23 | 112857.23 | 3.941613 | 6.70 | 5.06 | 0.00531777 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 10.7751 | 15.56 | 0.00674941 | 55.8593 | 23101.34 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 80656.999 | 80656.999 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0932 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.139043 | 2.33838928 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 80657.00 | 80657.00 | 1.0000 | 2.33838928 | 2.139043 | 5.66 | 5.66 | 0.00654185 | 22115.2 | 43.33 | 25.84 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80657.00 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 9.99 | 0.00841303 | 9.99 | 0.00841303 | 100.0000 | 80657.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24176.820 | 0.000 | 1.357460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3958 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24176.82 | 24176.82 | 1.0000 | 1.48396742 | 1.357460 | 25.03 | 15.17 | 0.00783013 | 45101.2 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24176.82 | 38.94 | 0.00557864 | 17.93 | 0.10228487 | 7.5350 | 23.90 | 0.00801361 | 23.90 | 0.00801361 | 39.4291 | 12483.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30625.130 | 30625.130 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.357463 | 1.48397063 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 30625.13 | 30625.13 | 1.0000 | 1.48397063 | 1.357463 | 14.12 | 9.89 | 0.00663010 | 30945.9 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30625.13 | 0.50 | 0.00431558 | 0.50 | 0.10228487 | 7.5350 | 21.01 | 0.00780006 | 21.10 | 0.00780006 | 45.5139 | 8214.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85629.930 | 0.000 | 3.941610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5477 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 85629.93 | 85629.93 | 1.0000 | 4.30894526 | 3.941610 | 28.02 | 15.81 | 0.00737390 | 46981.2 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85629.93 | 38.94 | 0.00557864 | 17.93 | 0.42471267 | 10.7751 | 26.70 | 0.00759071 | 26.70 | 0.00759071 | 31.6362 | 46506.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112857.232 | 112857.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.941613 | 4.30894881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 112857.23 | 112857.23 | 1.0000 | 4.30894881 | 3.941613 | 6.70 | 5.06 | 0.00531777 | 20098.5 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112857.23 | 0.50 | 0.00431558 | 0.50 | 0.42471267 | 10.7751 | 15.56 | 0.00674941 | 15.56 | 0.00674941 | 55.8593 | 23101.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 3.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1686.50 | 1553.00 | 225.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 1686.50 | 1553.00 | 225.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 5.33 | 50.67 | 5.33 | 39.83 |
ZONE2 FINE STORAGE | 4.67 | 265.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.00 | 314.17 | 5.33 | 39.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.345 | 0.375 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
Electricity:Building | 643.90 | 4992.32 | 01-JAN-00:10 | 48037.94 | 03-APR-12:20 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 444.30 | 2759.73 | 01-JAN-00:10 | 33963.13 | 03-APR-12:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.10 | 483.00 | 27-APR-09:50 | 1795.11 | 27-JAN-12:10 |
WaterSystems:Electricity | 24.10 | 483.00 | 27-APR-09:50 | 1795.11 | 27-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 27-APR-09:50 | 1795.11 | 27-JAN-12:10 |
Fans:Electricity | 132.25 | 0.00 | 01-JAN-00:40 | 10753.13 | 04-APR-17:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 22.66 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
Ventilation (simple):Fans:Electricity | 22.66 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
ElectricityPurchased:Facility | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
ElectricityPurchased:Plant | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
Cogeneration:ElectricityPurchased | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
ElectricityNet:Plant | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
Cogeneration:ElectricityNet | 1026.63 | 5475.32 | 01-JAN-08:00 | 86382.36 | 28-JUN-14:50 |
Electricity:HVAC | 235.05 | 0.00 | 01-JAN-00:40 | 40807.45 | 30-JUN-16:10 |
General:Fans:Electricity | 109.59 | 0.00 | 01-JAN-00:40 | 8447.83 | 31-JAN-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 125.46 | 0.00 | 01-JAN-00:10 | 32359.61 | 30-JUN-16:10 |
ExteriorLights:Electricity | 123.58 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.58 | 0.00 | 01-JAN-07:30 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4.20 | 0.00 | 01-JAN-00:40 | 36132.15 | 02-JAN-06:10 |
Gas:HVAC | 4.20 | 0.00 | 01-JAN-00:40 | 36132.15 | 02-JAN-06:10 |
Heating:Gas | 4.20 | 0.00 | 01-JAN-00:40 | 36132.15 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 682.73 | 0.00 | 01-JAN-00:40 | 158173.48 | 30-JUN-16:10 |
EnergyTransfer:Building | 298.59 | 0.00 | 01-JAN-00:40 | 70584.41 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 71.00 | 0.00 | 01-JAN-00:10 | 15904.75 | 28-JUN-16:30 |
Heating:EnergyTransfer | 21.77 | 0.00 | 01-JAN-00:40 | 25940.97 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.52 | 0.00 | 01-JAN-00:10 | 14781.73 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 276.82 | 0.00 | 01-JAN-00:10 | 70584.41 | 30-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 68.48 | 0.00 | 01-JAN-00:10 | 15904.75 | 28-JUN-16:30 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 227.59 | 0.00 | 01-JAN-00:40 | 56308.56 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.25 | 0.00 | 01-JAN-00:40 | 25028.95 | 01-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 208.34 | 0.00 | 01-JAN-00:10 | 56308.56 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 384.14 | 0.00 | 01-JAN-00:40 | 87589.08 | 30-JUN-16:10 |
HeatingCoils:EnergyTransfer | 2.82 | 0.00 | 01-JAN-00:40 | 25866.98 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 381.31 | 0.00 | 01-JAN-00:10 | 87589.08 | 30-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.517 | -68.478 | 0.000 | 0.000 | 3.619 | 30.994 | 31.946 | 13.554 | 0.000 | 5.994 | 0.001 | 0.000 | -8.490 | 0.000 | -7.924 | -3.733 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 19.248 | -208.340 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 24.421 | 77.282 | 0.000 | 0.000 | 0.000 | -49.267 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 50.309 | 0.000 | 16.289 | 145.286 | 0.000 | -20.122 | 0.000 | -613.408 | -0.015 |
Total Facility | 0.000 | 0.000 | 21.765 | -276.817 | 0.000 | 0.000 | 3.619 | 481.960 | 139.282 | 63.863 | 0.000 | 46.704 | 222.569 | 0.000 | -28.612 | 0.000 | -670.598 | -3.749 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | -23234.68 | 0.00 | 0.00 | 25.77 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 22784.69 | 0.00 | -401.89 | 0.00 | -334.09 | 0.00 |
ZONE2 FINE STORAGE | 18-JUN-08:23 | 0.00 | 0.00 | 0.00 | -71164.61 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 3027.68 | 66937.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -83749.93 | 0.00 | 0.00 | 22.87 | 4546.06 | 2623.78 | 0.00 | 0.00 | 368.93 | 141777.68 | 0.00 | -529.46 | 0.00 | -65059.93 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-06:01 | 0.00 | 0.00 | 29873.66 | 0.00 | 0.00 | 0.00 | 54.08 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -591.11 | 0.00 | -697.66 | -29799.17 |
ZONE2 FINE STORAGE | 01-JAN-07:23 | 0.00 | 0.00 | 84044.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6251.88 | -78992.79 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-JAN-07:23 | 0.00 | 0.00 | 84044.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.57 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2200.39 | 0.00 | -22527.75 | -64308.97 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3575 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3575 | 0.0754 | 1.0000 | 0.1023 | 0.0754 | ||
PSZ-FINE STORAGE | 3.9416 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.9416 | 0.1078 | 1.0000 | 0.4247 | 0.1078 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3575 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.3575 | 1.0000 | 1.0000 | 0.1023 | 0.0754 | ||
PSZ-FINE STORAGE | 3.9416 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.9416 | 1.0000 | 1.0000 | 0.4247 | 0.1078 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3575 | 1.3575 | 1.3575 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.9416 | 3.9416 | 3.9416 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3575 | 1.3575 | 1.3575 | 1.3575 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.9416 | 3.9416 | 3.9416 | 3.9416 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3575 | 1.3575 | 1.3575 | 0.1023 | 0.3358 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.9416 | 3.9416 | 3.9416 | 0.4247 | 0.5882 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3575 | 1.3575 | 1.3575 | 1.3575 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.9416 | 3.9416 | 3.9416 | 3.9416 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 5.33 |
Number of hours cooling loads not met | 39.83 |
Number of hours not met | 45.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 4.20 | 36132.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 125.46 | 32359.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.58 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 22.66 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 109.59 | 8447.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1795.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1026.63 |
Natural Gas | 0.00 | 4.20 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1030.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 25.95 |
Fans (All) | 27.35 |
Service Water Heating | 4.99 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 212.33 |
Subtotal | 212.33 |
Natural Gas [MJ/m2] | |
Space Heating | 0.87 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.87 |
Subtotal | 0.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 46.75 |
Space Heating | 0.41 |
Space Cooling | 12.17 |
Fans (All) | 12.83 |
Service Water Heating | 2.34 |
Receptacle Equipment | 13.51 |
Miscellaneous | 11.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.146315E+10 |
February | 0.000 | 0.575964E+09 |
March | 0.000 | 0.490005E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.253465E+08 |
November | 0.000 | 0.150616E+09 |
December | 0.000 | 0.149605E+10 |
Annual Sum or Average | 0.420113E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.149605E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171916E+10 | 5550.29 | 31-JAN-16:30 | 29.00 | 10.69 | 0.240943E+09 | 305.14 | 11-JAN-13:09 | 18.00 | 11.14 |
February | 0.730230E+09 | 3973.17 | 25-FEB-17:00 | 17.00 | 8.56 | 0.219238E+09 | 303.40 | 04-FEB-13:39 | 14.00 | 7.26 |
March | 0.211502E+10 | 6484.31 | 18-MAR-16:00 | 27.20 | 11.06 | 0.262333E+09 | 302.80 | 07-MAR-10:50 | 15.03 | 9.75 |
April | 0.614137E+10 | 22014.64 | 17-APR-05:01 | 14.33 | 9.39 | 0.248804E+09 | 301.59 | 15-APR-08:20 | 24.67 | 14.26 |
May | 0.809185E+10 | 22031.18 | 30-MAY-05:01 | 18.00 | 8.73 | 0.259018E+09 | 301.59 | 17-MAY-08:09 | 27.17 | 13.64 |
June | 0.106912E+11 | 22764.13 | 19-JUN-05:01 | 22.17 | 10.14 | 0.259135E+09 | 301.61 | 30-JUN-07:30 | 30.00 | 19.33 |
July | 0.102159E+11 | 22746.02 | 31-JUL-05:01 | 25.83 | 15.54 | 0.249193E+09 | 301.62 | 15-JUL-13:30 | 33.50 | 21.30 |
August | 0.105754E+11 | 23234.57 | 22-AUG-05:01 | 23.00 | 15.11 | 0.269117E+09 | 301.62 | 03-AUG-15:20 | 30.33 | 20.23 |
September | 0.908355E+10 | 22962.82 | 27-SEP-05:01 | 20.00 | 13.60 | 0.249155E+09 | 301.62 | 02-SEP-15:00 | 32.20 | 21.22 |
October | 0.557849E+10 | 23084.66 | 05-OCT-05:01 | 19.00 | 12.99 | 0.247906E+09 | 301.62 | 07-OCT-08:00 | 25.50 | 18.04 |
November | 0.263517E+10 | 19508.92 | 03-NOV-05:02 | 16.00 | 12.46 | 0.235672E+09 | 301.89 | 27-NOV-09:39 | 17.17 | 7.81 |
December | 0.901541E+09 | 4509.18 | 22-DEC-16:30 | 24.50 | 9.77 | 0.234831E+09 | 305.12 | 18-DEC-14:39 | 18.00 | 8.08 |
Annual Sum or Average | 0.684789E+11 | 0.297535E+10 | ||||||||
Minimum of Months | 0.730230E+09 | 3973.17 | 14.33 | 8.56 | 0.219238E+09 | 301.59 | 14.00 | 7.26 | ||
Maximum of Months | 0.106912E+11 | 23234.57 | 29.00 | 15.54 | 0.269117E+09 | 305.14 | 33.50 | 21.30 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100388E+09 | 6443.32 | 07-JAN-07:10 | 14.50 | 8.51 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 1037442.23 | 1640.12 | 10-FEB-07:10 | 16.17 | 8.82 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.888556E+09 | 12458.49 | 18-MAR-15:00 | 27.20 | 12.50 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.163512E+11 | 66941.99 | 25-APR-17:05 | 32.83 | 15.31 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.263600E+11 | 68110.46 | 29-MAY-12:32 | 30.67 | 13.45 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.439556E+11 | 71165.43 | 18-JUN-08:23 | 31.00 | 17.18 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.415291E+11 | 69732.26 | 11-JUL-20:23 | 33.00 | 19.44 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.377819E+11 | 70095.84 | 21-AUG-17:05 | 33.92 | 17.93 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.289667E+11 | 69914.04 | 23-SEP-17:05 | 33.53 | 17.85 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.113000E+11 | 69329.98 | 04-OCT-17:42 | 33.17 | 17.36 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.110193E+10 | 13618.44 | 01-NOV-15:10 | 28.83 | 16.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 8145945.12 | 8205.93 | 21-DEC-07:10 | 11.33 | 4.23 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.208345E+12 | 0.00 | ||||||||
Minimum of Months | 1037442.23 | 1640.12 | 11.33 | 4.23 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.439556E+11 | 71165.43 | 33.92 | 19.44 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 | 1.80 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.80 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.33 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493948E+09 | 29873.64 | 03-JAN-06:01 | 8.33 |
February | 0.558505E+09 | 29414.98 | 13-FEB-06:01 | 8.00 |
March | 0.403248E+09 | 28370.30 | 27-MAR-05:02 | 2.52 |
April | 18536147.56 | 966.99 | 04-APR-06:07 | 15.33 |
May | 496927.61 | 410.04 | 01-MAY-06:25 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 33182964.33 | 4025.58 | 25-OCT-06:10 | 5.00 |
November | 0.154415E+09 | 15287.76 | 24-NOV-06:03 | 3.17 |
December | 0.855030E+09 | 29575.14 | 11-DEC-06:01 | 9.17 |
Annual Sum or Average | 0.251736E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.855030E+09 | 29873.64 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434071E+10 | 84044.47 | 01-JAN-07:23 | 1.00 |
February | 0.307818E+10 | 6606.70 | 03-FEB-07:50 | 6.83 |
March | 0.319397E+10 | 7082.88 | 16-MAR-07:00 | 12.70 |
April | 0.724735E+09 | 6599.50 | 21-APR-06:13 | 9.67 |
May | 0.267539E+09 | 6753.79 | 27-MAY-06:25 | 17.50 |
June | 6886494.93 | 6425.75 | 21-JUN-06:01 | 19.17 |
July | 3462214.60 | 6384.51 | 01-JUL-06:01 | 18.83 |
August | 6712627.83 | 6053.55 | 25-AUG-06:12 | 22.33 |
September | 0.100322E+09 | 6398.32 | 15-SEP-06:15 | 18.07 |
October | 0.974814E+09 | 7025.45 | 20-OCT-07:00 | 15.00 |
November | 0.238803E+10 | 6825.09 | 24-NOV-07:50 | 6.50 |
December | 0.416238E+10 | 48703.39 | 08-DEC-06:07 | 2.00 |
Annual Sum or Average | 0.192477E+11 | |||
Minimum of Months | 3462214.60 | 6053.55 | 1.00 | |
Maximum of Months | 0.434071E+10 | 84044.47 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16943229.84 | 0.107271E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127602E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51290023.05 | 0.124457E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440797E+09 | 0.467456E+09 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783124E+09 | 0.260003E+09 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136981E+10 | 70828148.02 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110546E+10 | 68280934.53 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109387E+10 | 0.105380E+09 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763775E+09 | 0.188184E+09 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330664E+09 | 0.721440E+09 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36307142.47 | 0.106951E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2039906.58 | 0.137944E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 0.599407E+10 | 0.792383E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68280934.53 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136981E+10 | 0.137944E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11276729.60 | 0.658717E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592752E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30017200.96 | 0.793969E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140042E+10 | 0.359842E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313881E+10 | 0.224739E+10 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667387E+10 | 0.732170E+09 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561569E+10 | 0.692025E+09 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383273E+10 | 0.109783E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279917E+10 | 0.183197E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892210E+09 | 0.530685E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20159134.14 | 0.706616E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6584422.34 | 0.623997E+10 |
Annual Sum or Average | 0.136656E+12 | 0.244209E+11 | 0.492672E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692025E+09 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667387E+10 | 0.793969E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709749E+09 | 0.135325E+11 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158121E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154426E+09 | 0.226799E+11 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304850E+09 | 0.154848E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21252066.58 | 0.119660E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192357E+09 | 0.598245E+10 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141242E+09 | 0.671941E+10 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130172E+09 | 0.817849E+10 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44587103.52 | 0.110331E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46194644.23 | 0.202932E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141339E+09 | 0.189210E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328331E+09 | 0.136274E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.221450E+10 | 0.164230E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598245E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709749E+09 | 0.226799E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.12 | 31-JAN-17:10 | 5806.40 | 12-JAN-07:03 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5963.94 | 01-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.75 | 16-MAR-16:10 | 7179.45 | 27-MAR-06:05 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3698.63 | 14-APR-16:10 | 5092.32 | 21-APR-06:02 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4513.11 | 31-MAY-16:10 | 3659.88 | 01-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.47 | 30-JUN-16:10 | 1637.88 | 21-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.12 | 20-JUL-17:00 | 622.21 | 27-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5963.15 | 25-AUG-17:00 | 1574.79 | 24-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4961.32 | 08-SEP-16:10 | 2461.57 | 22-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3737.23 | 06-OCT-16:10 | 6269.72 | 25-OCT-06:02 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.38 | 01-NOV-16:10 | 6037.92 | 24-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.96 | 21-DEC-15:00 | 7582.09 | 06-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.21 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.47 | 7582.09 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.32 | 16-JAN-12:00 | 9096.36 | 11-JAN-08:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 12601.31 | 02-FEB-16:55 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.17 | 16-MAR-16:00 | 12144.46 | 11-MAR-16:05 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7661.62 | 10-APR-16:00 | 8120.97 | 21-APR-06:10 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10607.57 | 10-MAY-16:00 | 5924.15 | 23-MAY-06:10 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20468.02 | 30-JUN-16:00 | 3895.13 | 13-JUN-06:10 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.70 | 22-JUL-16:00 | 5216.54 | 26-JUL-24:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14381.49 | 12-AUG-16:00 | 10628.87 | 28-AUG-17:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12089.36 | 01-SEP-16:00 | 6041.37 | 15-SEP-07:00 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7770.30 | 10-OCT-15:10 | 11375.37 | 22-OCT-14:00 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.95 | 01-NOV-15:40 | 11843.79 | 22-NOV-16:05 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.29 | 25-DEC-16:00 | 10103.30 | 07-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.13 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.70 | 12601.31 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11987.35 | 06-JAN-13:10 | 18371.72 | 11-JAN-08:70 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 34726.66 | 02-FEB-12:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5971.86 | 15-MAR-13:00 | 32752.47 | 24-MAR-14:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9369.95 | 01-APR-17:00 | 27508.41 | 20-APR-11:00 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.34 | 15-MAY-17:00 | 19459.37 | 23-MAY-05:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.89 | 16-JUN-16:00 | 14168.02 | 13-JUN-06:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2013.66 | 30-JUL-18:00 | 23925.82 | 17-JUL-20:00 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.41 | 25-AUG-17:00 | 35874.23 | 28-AUG-17:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2949.01 | 17-SEP-11:53 | 22525.74 | 03-SEP-05:00 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.50 | 01-OCT-12:55 | 48730.38 | 07-OCT-15:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4817.03 | 19-NOV-15:00 | 51149.70 | 22-NOV-11:55 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5999.08 | 21-DEC-14:00 | 20748.85 | 07-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14168.02 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11987.35 | 51149.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5550.29 | 31-JAN-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 0.00 |
February | 3973.17 | 25-FEB-17:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.31 |
March | 6484.31 | 18-MAR-16:00 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 0.00 |
April | 22014.64 | 17-APR-05:01 | 507.62 | 4105.10 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.74 |
May | 22031.18 | 30-MAY-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.68 |
June | 22764.13 | 19-JUN-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.02 |
July | 22746.02 | 31-JUL-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.61 |
August | 23234.57 | 22-AUG-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.09 |
September | 22962.82 | 27-SEP-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.69 |
October | 23084.66 | 05-OCT-05:01 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.32 |
November | 19508.92 | 03-NOV-05:02 | 362.59 | 2932.21 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.29 |
December | 4509.18 | 22-DEC-16:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3973.17 | 362.59 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23234.57 | 725.17 | 5864.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 729.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6443.32 | 07-JAN-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2470.61 |
February | 1640.12 | 10-FEB-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.57 |
March | 12458.49 | 18-MAR-15:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.24 | 0.00 |
April | 66941.99 | 25-APR-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.50 | 0.00 |
May | 68110.46 | 29-MAY-12:32 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.30 | 0.00 |
June | 71165.43 | 18-JUN-08:23 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.68 | 0.00 |
July | 69732.26 | 11-JUL-20:23 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3258.13 | 0.00 |
August | 70095.84 | 21-AUG-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4213.96 | 0.00 |
September | 69914.04 | 23-SEP-17:05 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4904.91 | 0.00 |
October | 69329.98 | 04-OCT-17:42 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4423.16 | 0.00 |
November | 13618.44 | 01-NOV-15:10 | 0.00 | 8999.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.32 | 0.00 |
December | 8205.93 | 21-DEC-07:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1640.12 | 0.00 | 4799.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71165.43 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4904.91 | 2470.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8279.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11083.31 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8380.80 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6617.75 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.74 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7678.22 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3190.85 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.05 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.86 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.67 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4396.58 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3618.50 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7020.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.86 | |
Maximum of Months | 0.00 | 0.00 | 8279.19 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11083.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.752345E+11 | 61900.60 | 31-JAN-15:00 | 0.146315E+10 | 36132.15 | 02-JAN-06:10 |
February | 0.676217E+11 | 57283.72 | 22-FEB-15:00 | 0.575964E+09 | 10444.63 | 09-FEB-07:10 |
March | 0.780620E+11 | 64178.69 | 18-MAR-14:00 | 0.490005E+09 | 13693.91 | 27-MAR-06:10 |
April | 0.827535E+11 | 76372.04 | 14-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.917590E+11 | 78381.80 | 18-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.103166E+12 | 86382.36 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.101455E+12 | 83340.24 | 19-JUL-13:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.103600E+12 | 83706.55 | 25-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.930785E+11 | 80637.89 | 08-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.820009E+11 | 77408.18 | 02-OCT-13:00 | 25346483.44 | 4326.79 | 25-OCT-06:40 |
November | 0.730163E+11 | 65657.12 | 01-NOV-14:00 | 0.150616E+09 | 10243.86 | 24-NOV-07:10 |
December | 0.748835E+11 | 58202.27 | 22-DEC-15:20 | 0.149605E+10 | 29584.79 | 07-DEC-06:10 |
Annual Sum or Average | 0.102663E+13 | 0.420113E+10 | ||||
Minimum of Months | 0.676217E+11 | 57283.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.103600E+12 | 86382.36 | 0.149605E+10 | 36132.15 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.121017E+11 | 0.115358E+11 | 0.00 | 0.841074E+10 | 0.00 | 0.00 | 0.929474E+09 | 0.00 | 0.00 | 0.00 | 0.215340E+10 | 0.00 |
February | 0.366966E+11 | 0.103810E+11 | 0.105871E+11 | 0.00 | 0.769969E+10 | 0.00 | 0.00 | 0.305641E+09 | 0.00 | 0.00 | 0.00 | 0.195171E+10 | 0.00 |
March | 0.423649E+11 | 0.106733E+11 | 0.123357E+11 | 0.00 | 0.903632E+10 | 0.00 | 0.00 | 0.149276E+10 | 0.00 | 0.00 | 0.00 | 0.215907E+10 | 0.00 |
April | 0.397216E+11 | 0.948997E+10 | 0.114862E+11 | 0.00 | 0.104189E+11 | 0.00 | 0.00 | 0.963867E+10 | 0.00 | 0.00 | 0.00 | 0.199816E+10 | 0.00 |
May | 0.412341E+11 | 0.908454E+10 | 0.119357E+11 | 0.00 | 0.126050E+11 | 0.00 | 0.00 | 0.148928E+11 | 0.00 | 0.00 | 0.00 | 0.200674E+10 | 0.00 |
June | 0.408524E+11 | 0.849053E+10 | 0.118862E+11 | 0.00 | 0.153216E+11 | 0.00 | 0.00 | 0.247091E+11 | 0.00 | 0.00 | 0.00 | 0.190631E+10 | 0.00 |
July | 0.401034E+11 | 0.888654E+10 | 0.115358E+11 | 0.00 | 0.151528E+11 | 0.00 | 0.00 | 0.238661E+11 | 0.00 | 0.00 | 0.00 | 0.191000E+10 | 0.00 |
August | 0.423649E+11 | 0.948055E+10 | 0.123357E+11 | 0.00 | 0.148353E+11 | 0.00 | 0.00 | 0.226277E+11 | 0.00 | 0.00 | 0.00 | 0.195609E+10 | 0.00 |
September | 0.397216E+11 | 0.995669E+10 | 0.114862E+11 | 0.00 | 0.125819E+11 | 0.00 | 0.00 | 0.174241E+11 | 0.00 | 0.00 | 0.00 | 0.190804E+10 | 0.00 |
October | 0.401034E+11 | 0.111636E+11 | 0.115358E+11 | 0.00 | 0.976138E+10 | 0.00 | 0.00 | 0.742199E+10 | 0.00 | 0.00 | 0.00 | 0.201486E+10 | 0.00 |
November | 0.385909E+11 | 0.115360E+11 | 0.110862E+11 | 0.00 | 0.803068E+10 | 0.00 | 0.00 | 0.176477E+10 | 0.00 | 0.00 | 0.00 | 0.200772E+10 | 0.00 |
December | 0.401034E+11 | 0.123327E+11 | 0.115358E+11 | 0.00 | 0.839701E+10 | 0.00 | 0.00 | 0.381868E+09 | 0.00 | 0.00 | 0.00 | 0.213280E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123577E+12 | 0.139282E+12 | 0.132251E+12 | 0.00 | 0.125455E+12 | 0.241049E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.849053E+10 | 0.105871E+11 | 0.00 | 0.769969E+10 | 0.00 | 0.00 | 0.305641E+09 | 0.00 | 0.00 | 0.00 | 0.190631E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.123327E+11 | 0.123357E+11 | 0.00 | 0.153216E+11 | 0.00 | 0.00 | 0.247091E+11 | 0.00 | 0.00 | 0.00 | 0.215907E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.146315E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.575964E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.490005E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 25346483.44 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150616E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.149605E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420113E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149605E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8447.83 | 31-JAN-12:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 8447.83 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 8447.83 | 21-MAR-10:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10753.13 | 04-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10753.13 | 02-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10753.13 | 01-JUN-07:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10753.13 | 01-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10753.13 | 01-AUG-09:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10753.13 | 02-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10753.13 | 04-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 8447.83 | 18-NOV-13:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 8447.83 | 07-DEC-07:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 8447.83 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 10753.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5962.99 | 31-JAN-16:10 | 0.00 | 0.00 | 0.00 | 1795.11 | 27-JAN-12:09 | 0.00 |
February | 1357.47 | 22-FEB-16:30 | 0.00 | 0.00 | 0.00 | 1794.88 | 02-FEB-12:50 | 0.00 |
March | 8257.15 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1784.99 | 01-MAR-12:09 | 0.00 |
April | 19113.25 | 14-APR-16:10 | 0.00 | 0.00 | 0.00 | 1763.80 | 01-APR-11:30 | 0.00 |
May | 22159.91 | 18-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.79 | 01-MAY-11:00 | 0.00 |
June | 32359.61 | 30-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1715.50 | 01-JUN-11:20 | 0.00 |
July | 28481.13 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1701.04 | 01-JUL-11:39 | 0.00 |
August | 28901.01 | 25-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1706.26 | 31-AUG-11:39 | 0.00 |
September | 24734.58 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1725.14 | 30-SEP-11:00 | 0.00 |
October | 20200.67 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1750.33 | 31-OCT-11:09 | 0.00 |
November | 9755.13 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1774.25 | 30-NOV-12:00 | 0.00 |
December | 2315.64 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 1790.15 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1357.47 | 0.00 | 0.00 | 0.00 | 1701.04 | 0.00 | ||
Maximum of Months | 32359.61 | 0.00 | 0.00 | 0.00 | 1795.11 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61900.60 | 31-JAN-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 5961.79 | 0.00 |
February | 57283.72 | 22-FEB-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 1350.46 | 0.00 |
March | 64178.69 | 18-MAR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 8257.15 | 0.00 |
April | 76372.04 | 14-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 18163.19 | 0.00 |
May | 78381.80 | 18-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 20196.64 | 0.00 |
June | 86382.36 | 28-JUN-14:50 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 28217.24 | 0.00 |
July | 83340.24 | 19-JUL-13:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 25199.58 | 0.00 |
August | 83706.55 | 25-AUG-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 25539.81 | 0.00 |
September | 80637.89 | 08-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 22464.95 | 0.00 |
October | 77408.18 | 02-OCT-13:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 19246.30 | 0.00 |
November | 65657.12 | 01-NOV-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 9755.13 | 0.00 |
December | 58202.27 | 22-DEC-15:20 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 2270.31 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 57283.72 | 35620.03 | 10112.62 | 0.00 | 0.00 | 8447.83 | 0.00 | 0.00 | 1350.46 | 0.00 | |
Maximum of Months | 86382.36 | 35620.03 | 10112.62 | 0.00 | 0.00 | 10753.13 | 0.00 | 0.00 | 28217.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 36132.15 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 10444.63 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13693.91 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 4326.79 | 25-OCT-06:40 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 10243.86 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 29584.79 | 07-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 36132.15 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.27 | 1.33 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.49 | 1.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 20.49 | 1.00 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.93 | 1.00 | 24.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.12 | 3.00 | 24.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.02 | 8.67 | 24.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.81 | 8.33 | 25.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.15 | 9.00 | 24.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.13 | 7.50 | 24.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.14 | 2.17 | 24.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
December | 1.83 | 20.26 | 1.83 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.33 | 20.35 | 5.33 | 20.35 | 50.67 | 26.01 | 39.83 | 24.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.49 | 1.83 | 20.49 | 12.83 | 26.81 | 9.00 | 25.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 14.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.77 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 27.96 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 27.85 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 27.78 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 27.66 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.57 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 14.77 | 0.00 | 265.67 | 27.80 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 14.97 | 0.00 | 0.00 | 66.00 | 27.96 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 296.83 | 23.22 | 42.33 | 21.17 | 42.33 | 21.17 |
February | 275.83 | 23.08 | 36.17 | 21.11 | 36.17 | 21.11 |
March | 282.33 | 23.28 | 26.17 | 21.39 | 24.00 | 21.17 |
April | 72.00 | 23.82 | 65.00 | 23.91 | 0.00 | 0.00 |
May | 14.33 | 23.95 | 102.00 | 23.91 | 0.00 | 0.00 |
June | 2.00 | 24.95 | 268.17 | 23.92 | 2.00 | 24.95 |
July | 5.00 | 24.88 | 292.00 | 23.93 | 5.00 | 24.88 |
August | 4.50 | 24.88 | 315.33 | 23.93 | 4.50 | 24.88 |
September | 3.33 | 24.82 | 294.67 | 23.93 | 3.33 | 24.82 |
October | 102.83 | 23.57 | 107.83 | 23.92 | 0.50 | 24.86 |
November | 194.00 | 23.37 | 47.17 | 23.03 | 17.67 | 21.58 |
December | 300.00 | 22.92 | 89.67 | 21.30 | 89.67 | 21.30 |
Annual Sum or Average | 1553.00 | 23.24 | 1686.50 | 23.59 | 225.17 | 21.50 |
Minimum of Months | 2.00 | 22.92 | 26.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 300.00 | 24.95 | 315.33 | 23.93 | 89.67 | 24.95 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.259498E+10 | 0.706702E+09 | 199.58 | 0.258887E+10 | 6107448.03 | 0.00 | 0.40 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 | 7671.47 | 31-JAN-16:30 | 7671.47 | 31-JAN-16:30 | 436.21 | 09-JAN-11:30 | 2239.29 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 |
February | 0.112230E+10 | 0.305641E+09 | 132.83 | 0.107333E+10 | 48974725.56 | 0.00 | 0.25 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 | 5054.88 | 22-FEB-16:30 | 5054.88 | 22-FEB-16:30 | 698.22 | 18-FEB-11:40 | 1357.47 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 0.306128E+10 | 0.838932E+09 | 225.83 | 0.304286E+10 | 18424849.22 | 0.00 | 0.42 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 8401.45 | 18-MAR-16:00 | 8401.45 | 18-MAR-16:00 | 595.14 | 06-MAR-13:30 | 2349.54 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.791032E+10 | 0.227393E+10 | 279.22 | 0.791032E+10 | 0.00 | 0.00 | 1.00 | 04-APR-05:02 | 0.00 | 01-APR-00:10 | 23695.75 | 26-APR-05:01 | 23695.75 | 26-APR-05:01 | 0.00 | 25-APR-05:03 | 5616.47 | 26-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.103322E+11 | 0.307172E+10 | 317.55 | 0.103322E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 23760.89 | 11-MAY-05:01 | 23760.89 | 11-MAY-05:01 | 0.00 | 15-MAY-17:00 | 5632.04 | 11-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.136024E+11 | 0.437512E+10 | 357.63 | 0.135870E+11 | 15378987.37 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 24598.52 | 19-JUN-05:01 | 24598.52 | 19-JUN-05:01 | 1087.53 | 17-JUN-17:00 | 7217.01 | 29-JUN-17:39 | 0.00 | 01-JUN-00:10 |
July | 0.139730E+11 | 0.426504E+10 | 343.67 | 0.129145E+11 | 0.105847E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28773.08 | 14-JUL-05:01 | 25014.82 | 12-JUL-05:01 | 10368.32 | 14-JUL-05:06 | 7209.08 | 20-JUL-17:40 | 0.00 | 01-JUL-00:10 |
August | 0.145818E+11 | 0.442990E+10 | 349.09 | 0.134110E+11 | 0.117074E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28200.54 | 10-AUG-05:01 | 25273.20 | 17-AUG-05:01 | 9258.69 | 10-AUG-05:05 | 7188.58 | 13-AUG-16:11 | 0.00 | 01-AUG-00:10 |
September | 0.124591E+11 | 0.366151E+10 | 311.86 | 0.114429E+11 | 0.101615E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28393.08 | 05-SEP-05:01 | 24678.31 | 27-SEP-05:01 | 8965.62 | 05-SEP-05:06 | 6565.99 | 02-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.727923E+10 | 0.205920E+10 | 272.19 | 0.708094E+10 | 0.198292E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 26781.22 | 03-OCT-05:01 | 24814.52 | 02-OCT-05:01 | 6012.23 | 03-OCT-05:05 | 6240.01 | 03-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.367548E+10 | 0.995484E+09 | 219.81 | 0.352356E+10 | 0.151916E+09 | 0.00 | 1.00 | 03-NOV-05:02 | 0.00 | 01-NOV-00:10 | 24714.54 | 03-NOV-05:02 | 21679.19 | 03-NOV-05:02 | 3035.34 | 03-NOV-05:02 | 5836.76 | 03-NOV-05:02 | 0.00 | 01-NOV-00:10 |
December | 0.139628E+10 | 0.379490E+09 | 142.83 | 0.139616E+10 | 125392.05 | 0.00 | 0.31 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 6124.09 | 22-DEC-16:30 | 6124.09 | 22-DEC-16:30 | 69.25 | 13-DEC-12:00 | 1646.45 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.919883E+11 | 0.273627E+11 | 3152.11 | 0.883037E+11 | 0.368457E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.112230E+10 | 0.305641E+09 | 132.83 | 0.107333E+10 | 0.00 | 0.00 | 0.25 | 0.00 | 5054.88 | 5054.88 | 0.00 | 1357.47 | 0.00 | |||||||
Maximum of Months | 0.145818E+11 | 0.442990E+10 | 357.63 | 0.135870E+11 | 0.117074E+10 | 0.00 | 1.00 | 0.00 | 28773.08 | 25273.20 | 10368.32 | 7217.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.717394E+09 | 0.222771E+09 | 32.83 | 0.717394E+09 | 0.00 | 0.00 | 0.17 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 | 11563.49 | 31-JAN-16:00 | 11563.49 | 31-JAN-16:00 | 0.00 | 26-JAN-15:00 | 3788.38 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.212338E+10 | 0.653823E+09 | 56.33 | 0.211727E+10 | 6115837.30 | 0.00 | 0.27 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 | 19590.63 | 18-MAR-15:00 | 19590.63 | 18-MAR-15:00 | 699.70 | 18-MAR-11:20 | 6057.85 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.226635E+11 | 0.736473E+10 | 288.27 | 0.226635E+11 | 0.00 | 0.00 | 1.00 | 12-APR-17:06 | 0.00 | 01-APR-00:10 | 76203.20 | 25-APR-17:05 | 76203.20 | 25-APR-17:05 | 0.00 | 09-APR-12:13 | 24028.30 | 14-APR-17:05 | 0.00 | 01-APR-00:10 |
May | 0.351532E+11 | 0.118211E+11 | 381.44 | 0.351532E+11 | 0.00 | 0.00 | 1.00 | 02-MAY-17:06 | 0.00 | 01-MAY-00:10 | 77596.17 | 21-MAY-18:33 | 77596.17 | 21-MAY-18:33 | 0.00 | 31-MAY-16:30 | 24654.01 | 15-MAY-17:05 | 0.00 | 01-MAY-00:10 |
June | 0.566858E+11 | 0.203340E+11 | 514.09 | 0.566114E+11 | 74492627.88 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:10 | 81988.59 | 18-JUN-08:23 | 81282.81 | 18-JUN-08:23 | 9613.61 | 17-JUN-17:06 | 27251.05 | 17-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.575831E+11 | 0.196011E+11 | 544.79 | 0.534974E+11 | 0.408579E+10 | 0.00 | 1.00 | 01-JUL-17:04 | 0.00 | 01-JUL-00:15 | 91561.16 | 17-JUL-19:42 | 79809.81 | 11-JUL-20:23 | 21731.53 | 13-JUL-19:03 | 26716.82 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.534889E+11 | 0.181978E+11 | 515.70 | 0.496621E+11 | 0.382678E+10 | 0.00 | 1.00 | 01-AUG-17:04 | 0.00 | 01-AUG-00:13 | 87837.49 | 06-AUG-14:13 | 80402.11 | 20-AUG-17:32 | 24126.14 | 01-AUG-05:07 | 26868.79 | 13-AUG-14:22 | 0.00 | 01-AUG-00:10 |
September | 0.417722E+11 | 0.137626E+11 | 430.48 | 0.383802E+11 | 0.339202E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:15 | 95817.95 | 02-SEP-05:08 | 80850.66 | 17-SEP-14:32 | 32688.60 | 02-SEP-05:08 | 25955.89 | 08-SEP-17:42 | 0.00 | 01-SEP-00:10 |
October | 0.165999E+11 | 0.536279E+10 | 226.87 | 0.160119E+11 | 0.587956E+09 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 85877.80 | 01-OCT-15:53 | 79363.11 | 04-OCT-17:42 | 9249.46 | 01-OCT-16:33 | 25283.41 | 01-OCT-13:53 | 0.00 | 01-OCT-00:10 |
November | 0.253084E+10 | 0.769287E+09 | 74.83 | 0.243895E+10 | 91896322.93 | 0.00 | 0.30 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 22239.32 | 01-NOV-15:00 | 21607.30 | 01-NOV-15:00 | 3286.49 | 14-NOV-13:20 | 7026.24 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 7637593.93 | 2378090.23 | 1.17 | 7637593.93 | 0.00 | 0.00 | 0.03 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 | 2281.69 | 22-DEC-15:30 | 2281.69 | 22-DEC-15:30 | 0.00 | 22-DEC-15:20 | 707.39 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.289326E+12 | 0.980923E+11 | 3066.80 | 0.277261E+12 | 0.120651E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.575831E+11 | 0.203340E+11 | 544.79 | 0.566114E+11 | 0.408579E+10 | 0.00 | 1.00 | 0.00 | 95817.95 | 81282.81 | 32688.60 | 27251.05 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.06 | 41.85 | 25.21 | 125.22 | 127.12 | 0.00 | 0.00 | 744.00 |
February | 53.81 | 25.97 | 27.84 | 77.78 | 121.40 | 0.00 | 0.00 | 672.00 |
March | 71.51 | 34.12 | 37.38 | 121.85 | 112.80 | 0.00 | 0.00 | 744.00 |
April | 108.91 | 61.82 | 47.09 | 239.00 | 80.02 | 0.00 | 0.00 | 720.00 |
May | 109.53 | 61.10 | 48.42 | 257.95 | 62.46 | 0.00 | 0.00 | 744.00 |
June | 116.31 | 68.23 | 48.08 | 318.10 | 31.75 | 0.00 | 0.00 | 720.00 |
July | 84.82 | 39.49 | 45.33 | 234.63 | 27.37 | 0.00 | 0.00 | 744.00 |
August | 80.97 | 40.55 | 40.42 | 225.22 | 33.75 | 0.00 | 0.00 | 744.00 |
September | 70.62 | 29.63 | 40.99 | 183.11 | 44.46 | 0.00 | 0.00 | 720.00 |
October | 72.15 | 41.17 | 30.98 | 147.22 | 102.41 | 0.00 | 0.00 | 744.00 |
November | 66.35 | 39.95 | 26.39 | 115.76 | 131.65 | 0.00 | 0.00 | 720.00 |
December | 53.97 | 30.85 | 23.12 | 86.97 | 153.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.76 | 42.96 | 36.80 | 178.16 | 85.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.81 | 25.97 | 23.12 | 77.78 | 27.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.31 | 68.23 | 48.42 | 318.10 | 153.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.06 | 41.85 | 25.21 | 125.22 | 127.12 | 0.00 | 0.00 | 744.00 |
February | 53.81 | 25.97 | 27.84 | 77.78 | 121.40 | 0.00 | 0.00 | 672.00 |
March | 71.51 | 34.12 | 37.38 | 121.85 | 112.80 | 0.00 | 0.00 | 744.00 |
April | 108.91 | 61.82 | 47.09 | 239.00 | 80.02 | 0.00 | 0.00 | 720.00 |
May | 109.53 | 61.10 | 48.42 | 257.95 | 62.46 | 0.00 | 0.00 | 744.00 |
June | 116.31 | 68.23 | 48.08 | 318.10 | 31.75 | 0.00 | 0.00 | 720.00 |
July | 84.82 | 39.49 | 45.33 | 234.63 | 27.37 | 0.00 | 0.00 | 744.00 |
August | 80.97 | 40.55 | 40.42 | 225.22 | 33.75 | 0.00 | 0.00 | 744.00 |
September | 70.62 | 29.63 | 40.99 | 183.11 | 44.46 | 0.00 | 0.00 | 720.00 |
October | 72.15 | 41.17 | 30.98 | 147.22 | 102.41 | 0.00 | 0.00 | 744.00 |
November | 66.35 | 39.95 | 26.39 | 115.76 | 131.65 | 0.00 | 0.00 | 720.00 |
December | 53.97 | 30.85 | 23.12 | 86.97 | 153.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.76 | 42.96 | 36.80 | 178.16 | 85.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.81 | 25.97 | 23.12 | 77.78 | 27.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.31 | 68.23 | 48.42 | 318.10 | 153.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.49 | 0.00 | 11.49 | 10.12 | 75.37 | 0.00 | 0.00 | 744.00 |
February | 13.09 | 0.00 | 13.09 | 6.38 | 73.59 | 0.00 | 0.00 | 672.00 |
March | 17.40 | 0.00 | 17.40 | 18.53 | 68.34 | 0.00 | 0.00 | 744.00 |
April | 21.37 | 0.39 | 20.98 | 40.93 | 46.54 | 0.00 | 0.00 | 720.00 |
May | 25.55 | 2.67 | 22.88 | 55.20 | 33.38 | 0.00 | 0.00 | 744.00 |
June | 29.64 | 6.06 | 23.58 | 90.68 | 16.72 | 0.00 | 0.00 | 720.00 |
July | 25.01 | 2.98 | 22.03 | 76.87 | 14.98 | 0.00 | 0.00 | 744.00 |
August | 20.07 | 0.69 | 19.38 | 65.54 | 19.19 | 0.00 | 0.00 | 744.00 |
September | 18.74 | 0.02 | 18.73 | 53.75 | 25.79 | 0.00 | 0.00 | 720.00 |
October | 14.49 | 0.00 | 14.49 | 22.92 | 60.98 | 0.00 | 0.00 | 744.00 |
November | 12.07 | 0.00 | 12.07 | 8.52 | 78.86 | 0.00 | 0.00 | 720.00 |
December | 10.73 | 0.00 | 10.73 | 5.66 | 91.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.32 | 1.07 | 17.25 | 38.07 | 50.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.73 | 0.00 | 10.73 | 5.66 | 14.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 29.64 | 6.06 | 23.58 | 90.68 | 91.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.49 | 0.00 | 11.49 | 10.12 | 75.37 | 0.00 | 0.00 | 744.00 |
February | 13.09 | 0.00 | 13.09 | 6.38 | 73.59 | 0.00 | 0.00 | 672.00 |
March | 17.40 | 0.00 | 17.40 | 18.53 | 68.34 | 0.00 | 0.00 | 744.00 |
April | 21.37 | 0.39 | 20.98 | 40.93 | 46.54 | 0.00 | 0.00 | 720.00 |
May | 25.55 | 2.67 | 22.87 | 55.20 | 33.38 | 0.00 | 0.00 | 744.00 |
June | 29.64 | 6.06 | 23.58 | 90.68 | 16.72 | 0.00 | 0.00 | 720.00 |
July | 25.01 | 2.98 | 22.03 | 76.87 | 14.98 | 0.00 | 0.00 | 744.00 |
August | 20.07 | 0.69 | 19.38 | 65.54 | 19.19 | 0.00 | 0.00 | 744.00 |
September | 18.74 | 0.02 | 18.72 | 53.75 | 25.79 | 0.00 | 0.00 | 720.00 |
October | 14.49 | 0.00 | 14.49 | 22.92 | 60.98 | 0.00 | 0.00 | 744.00 |
November | 12.07 | 0.00 | 12.07 | 8.51 | 78.86 | 0.00 | 0.00 | 720.00 |
December | 10.73 | 0.00 | 10.73 | 5.66 | 91.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.32 | 1.07 | 17.25 | 38.07 | 50.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.73 | 0.00 | 10.73 | 5.66 | 14.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 29.64 | 6.06 | 23.58 | 90.68 | 91.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.21 | 58.86 | 17.35 | 101.66 | 73.73 | 6.67 | 0.00 | 744.00 |
February | 74.15 | 47.67 | 26.48 | 92.41 | 60.10 | 9.17 | 0.00 | 672.00 |
March | 104.81 | 67.03 | 37.77 | 135.02 | 67.10 | 0.00 | 0.00 | 744.00 |
April | 161.91 | 125.01 | 36.89 | 216.84 | 71.31 | 0.00 | 0.00 | 720.00 |
May | 178.21 | 139.91 | 38.30 | 238.47 | 69.17 | 0.00 | 0.00 | 744.00 |
June | 187.69 | 153.42 | 34.27 | 258.99 | 51.39 | 0.00 | 0.00 | 720.00 |
July | 152.07 | 110.09 | 41.98 | 209.93 | 39.25 | 0.00 | 0.00 | 744.00 |
August | 140.14 | 103.58 | 36.56 | 194.88 | 47.54 | 0.17 | 0.00 | 744.00 |
September | 112.75 | 70.73 | 42.02 | 154.41 | 48.89 | 0.00 | 0.00 | 720.00 |
October | 100.51 | 75.56 | 24.95 | 129.36 | 78.91 | 0.00 | 0.00 | 744.00 |
November | 74.69 | 54.08 | 20.61 | 94.29 | 75.36 | 13.83 | 0.00 | 720.00 |
December | 65.93 | 48.25 | 17.69 | 84.43 | 81.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 119.29 | 88.04 | 31.26 | 159.53 | 63.77 | 29.83 | 0.00 | 8760.00 |
Minimum of Months | 65.93 | 47.67 | 17.35 | 84.43 | 39.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 187.69 | 153.42 | 42.02 | 258.99 | 81.82 | 13.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179603E+09 | 0.112089E+09 | 67514421.63 | 0.335398E+09 | 0.340472E+09 |
February | 0.130182E+09 | 62831055.64 | 67350566.25 | 0.188155E+09 | 0.293692E+09 |
March | 0.191521E+09 | 91389976.21 | 0.100131E+09 | 0.326367E+09 | 0.302128E+09 |
April | 0.282307E+09 | 0.160249E+09 | 0.122058E+09 | 0.619499E+09 | 0.207399E+09 |
May | 0.293354E+09 | 0.163656E+09 | 0.129698E+09 | 0.690901E+09 | 0.167290E+09 |
June | 0.301473E+09 | 0.176848E+09 | 0.124625E+09 | 0.824508E+09 | 82300404.98 |
July | 0.227188E+09 | 0.105777E+09 | 0.121411E+09 | 0.628432E+09 | 73306059.62 |
August | 0.216871E+09 | 0.108613E+09 | 0.108257E+09 | 0.603239E+09 | 90398603.42 |
September | 0.183050E+09 | 76805181.63 | 0.106245E+09 | 0.474617E+09 | 0.115250E+09 |
October | 0.193244E+09 | 0.110274E+09 | 82969504.49 | 0.394304E+09 | 0.274297E+09 |
November | 0.171969E+09 | 0.103561E+09 | 68407713.34 | 0.300055E+09 | 0.341227E+09 |
December | 0.144551E+09 | 82632481.39 | 61918727.12 | 0.232942E+09 | 0.410596E+09 |
Annual Sum or Average | 0.251531E+10 | 0.135473E+10 | 0.116059E+10 | 0.561842E+10 | 0.269836E+10 |
Minimum of Months | 0.130182E+09 | 62831055.64 | 61918727.12 | 0.188155E+09 | 73306059.62 |
Maximum of Months | 0.301473E+09 | 0.176848E+09 | 0.129698E+09 | 0.824508E+09 | 0.410596E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179603E+09 | 0.112089E+09 | 67514421.63 | 0.335398E+09 | 0.340472E+09 |
February | 0.130182E+09 | 62831055.64 | 67350566.25 | 0.188155E+09 | 0.293692E+09 |
March | 0.191521E+09 | 91389976.21 | 0.100131E+09 | 0.326367E+09 | 0.302128E+09 |
April | 0.282307E+09 | 0.160249E+09 | 0.122058E+09 | 0.619499E+09 | 0.207399E+09 |
May | 0.293354E+09 | 0.163656E+09 | 0.129698E+09 | 0.690901E+09 | 0.167290E+09 |
June | 0.301473E+09 | 0.176848E+09 | 0.124625E+09 | 0.824508E+09 | 82300404.98 |
July | 0.227188E+09 | 0.105777E+09 | 0.121411E+09 | 0.628432E+09 | 73306059.62 |
August | 0.216871E+09 | 0.108613E+09 | 0.108257E+09 | 0.603239E+09 | 90398603.42 |
September | 0.183050E+09 | 76805181.63 | 0.106245E+09 | 0.474617E+09 | 0.115250E+09 |
October | 0.193244E+09 | 0.110274E+09 | 82969504.49 | 0.394304E+09 | 0.274297E+09 |
November | 0.171969E+09 | 0.103561E+09 | 68407713.34 | 0.300055E+09 | 0.341227E+09 |
December | 0.144551E+09 | 82632481.39 | 61918727.12 | 0.232942E+09 | 0.410596E+09 |
Annual Sum or Average | 0.251531E+10 | 0.135473E+10 | 0.116059E+10 | 0.561842E+10 | 0.269836E+10 |
Minimum of Months | 0.130182E+09 | 62831055.64 | 61918727.12 | 0.188155E+09 | 73306059.62 |
Maximum of Months | 0.301473E+09 | 0.176848E+09 | 0.129698E+09 | 0.824508E+09 | 0.410596E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30770965.37 | 0.00 | 30770965.37 | 27093234.54 | 0.201866E+09 |
February | 31669539.27 | 0.00 | 31669539.27 | 15433830.25 | 0.178040E+09 |
March | 46614272.89 | 8632.97 | 46605639.92 | 49634900.90 | 0.183037E+09 |
April | 55398365.83 | 1006680.94 | 54391684.89 | 0.106091E+09 | 0.120629E+09 |
May | 68432653.84 | 7163623.99 | 61269029.85 | 0.147842E+09 | 89395754.28 |
June | 76833198.10 | 15701221.24 | 61131976.86 | 0.235037E+09 | 43346355.31 |
July | 66989102.56 | 7986459.08 | 59002643.49 | 0.205883E+09 | 40113712.90 |
August | 53760328.09 | 1861133.21 | 51899194.88 | 0.175532E+09 | 51394682.65 |
September | 48580604.36 | 44468.42 | 48536135.94 | 0.139332E+09 | 66858236.83 |
October | 38806286.25 | 0.00 | 38806286.25 | 61390712.44 | 0.163324E+09 |
November | 31289761.01 | 0.00 | 31289761.01 | 22071423.80 | 0.204400E+09 |
December | 28742904.03 | 0.00 | 28742904.03 | 15148832.17 | 0.246286E+09 |
Annual Sum or Average | 0.577888E+09 | 33772219.84 | 0.544116E+09 | 0.120049E+10 | 0.158869E+10 |
Minimum of Months | 28742904.03 | 0.00 | 28742904.03 | 15148832.17 | 40113712.90 |
Maximum of Months | 76833198.10 | 15701221.24 | 61269029.85 | 0.235037E+09 | 0.246286E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30770213.30 | 0.00 | 30770213.30 | 27092847.93 | 0.201864E+09 |
February | 31668652.25 | 0.00 | 31668652.25 | 15433004.65 | 0.178039E+09 |
March | 46612966.78 | 8632.56 | 46604334.22 | 49633354.30 | 0.183035E+09 |
April | 55397071.44 | 1006633.75 | 54390437.69 | 0.106090E+09 | 0.120627E+09 |
May | 68430899.39 | 7163288.22 | 61267611.18 | 0.147840E+09 | 89394103.91 |
June | 76831077.74 | 15700485.30 | 61130592.44 | 0.235035E+09 | 43345118.47 |
July | 66987209.68 | 7986084.74 | 59001124.94 | 0.205880E+09 | 40112867.00 |
August | 53758958.59 | 1861045.98 | 51897912.61 | 0.175531E+09 | 51393572.54 |
September | 48579240.77 | 44466.34 | 48534774.44 | 0.139331E+09 | 66857074.85 |
October | 38805333.58 | 0.00 | 38805333.58 | 61390020.78 | 0.163322E+09 |
November | 31288949.63 | 0.00 | 31288949.63 | 22070877.28 | 0.204399E+09 |
December | 28742162.58 | 0.00 | 28742162.58 | 15148469.59 | 0.246284E+09 |
Annual Sum or Average | 0.577873E+09 | 33770636.89 | 0.544102E+09 | 0.120048E+10 | 0.158867E+10 |
Minimum of Months | 28742162.58 | 0.00 | 28742162.58 | 15148469.59 | 40112867.00 |
Maximum of Months | 76831077.74 | 15700485.30 | 61267611.18 | 0.235035E+09 | 0.246284E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204132E+09 | 0.157661E+09 | 46470533.84 | 0.272299E+09 | 0.197477E+09 |
February | 0.179391E+09 | 0.115324E+09 | 64067266.31 | 0.223561E+09 | 0.145389E+09 |
March | 0.280710E+09 | 0.179545E+09 | 0.101165E+09 | 0.361650E+09 | 0.179723E+09 |
April | 0.419661E+09 | 0.324038E+09 | 95623639.29 | 0.562053E+09 | 0.184849E+09 |
May | 0.477316E+09 | 0.374732E+09 | 0.102584E+09 | 0.638721E+09 | 0.185278E+09 |
June | 0.486480E+09 | 0.397663E+09 | 88817208.81 | 0.671314E+09 | 0.133192E+09 |
July | 0.407315E+09 | 0.294869E+09 | 0.112446E+09 | 0.562265E+09 | 0.105135E+09 |
August | 0.375358E+09 | 0.277422E+09 | 97935675.72 | 0.521969E+09 | 0.127341E+09 |
September | 0.292249E+09 | 0.183324E+09 | 0.108925E+09 | 0.400230E+09 | 0.126719E+09 |
October | 0.269215E+09 | 0.202386E+09 | 66828801.64 | 0.346486E+09 | 0.211344E+09 |
November | 0.193604E+09 | 0.140174E+09 | 53430007.25 | 0.244397E+09 | 0.195336E+09 |
December | 0.176597E+09 | 0.129220E+09 | 47377328.65 | 0.226147E+09 | 0.219144E+09 |
Annual Sum or Average | 0.376203E+10 | 0.277636E+10 | 0.985670E+09 | 0.503109E+10 | 0.201093E+10 |
Minimum of Months | 0.176597E+09 | 0.115324E+09 | 46470533.84 | 0.223561E+09 | 0.105135E+09 |
Maximum of Months | 0.486480E+09 | 0.397663E+09 | 0.112446E+09 | 0.671314E+09 | 0.219144E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.00 | 402.29 | 157.09 | 83.70 | 73.39 | 0.00 | 0.00 |
February | 163.70 | 385.38 | 133.81 | 51.94 | 81.86 | 0.00 | 0.00 |
March | 275.89 | 357.40 | 177.82 | 68.25 | 109.57 | 0.00 | 0.00 |
April | 559.04 | 252.28 | 260.57 | 124.43 | 136.15 | 0.00 | 0.00 |
May | 625.03 | 190.40 | 270.15 | 127.55 | 142.60 | 0.00 | 0.00 |
June | 814.28 | 93.68 | 291.90 | 148.57 | 143.33 | 0.00 | 0.00 |
July | 621.33 | 83.02 | 219.67 | 84.95 | 134.72 | 0.00 | 0.00 |
August | 581.10 | 105.46 | 202.08 | 82.49 | 119.59 | 0.00 | 0.00 |
September | 473.67 | 140.46 | 178.73 | 59.30 | 119.43 | 0.00 | 0.00 |
October | 337.65 | 324.15 | 173.27 | 82.34 | 90.93 | 0.00 | 0.00 |
November | 243.85 | 416.30 | 156.84 | 79.91 | 76.93 | 0.00 | 0.00 |
December | 180.30 | 485.55 | 129.40 | 61.70 | 67.70 | 0.00 | 0.00 |
Annual Sum or Average | 429.80 | 269.23 | 196.17 | 88.06 | 108.11 | 0.00 | 0.00 |
Minimum of Months | 163.70 | 83.02 | 129.40 | 51.94 | 67.70 | 0.00 | 0.00 |
Maximum of Months | 814.28 | 485.55 | 291.90 | 148.57 | 143.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1016.64 | 737.29 | 762.14 | 588.64 | 173.50 | 0.00 | 0.00 |
February | 924.11 | 600.98 | 741.53 | 476.70 | 264.83 | 0.00 | 0.00 |
March | 1350.24 | 671.01 | 1048.05 | 670.34 | 377.71 | 0.00 | 0.00 |
April | 2168.41 | 713.15 | 1619.06 | 1250.15 | 368.92 | 0.00 | 0.00 |
May | 2384.71 | 691.74 | 1782.09 | 1399.09 | 383.00 | 0.00 | 0.00 |
June | 2589.94 | 513.85 | 1876.85 | 1534.19 | 342.66 | 0.00 | 0.00 |
July | 2099.25 | 392.52 | 1520.74 | 1100.92 | 419.83 | 0.00 | 0.00 |
August | 1948.79 | 475.43 | 1401.43 | 1035.78 | 365.65 | 0.00 | 0.00 |
September | 1544.10 | 488.88 | 1127.50 | 707.27 | 420.23 | 0.00 | 0.00 |
October | 1293.63 | 789.06 | 1005.13 | 755.62 | 249.51 | 0.00 | 0.00 |
November | 942.89 | 753.61 | 746.93 | 540.79 | 206.13 | 0.00 | 0.00 |
December | 844.33 | 818.19 | 659.34 | 482.45 | 176.89 | 0.00 | 0.00 |
Annual Sum or Average | 1595.35 | 637.66 | 1192.93 | 880.38 | 312.55 | 0.00 | 0.00 |
Minimum of Months | 844.33 | 392.52 | 659.34 | 476.70 | 173.50 | 0.00 | 0.00 |
Maximum of Months | 2589.94 | 818.19 | 1876.85 | 1534.19 | 420.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.717809E+09 | 0.107750E+10 | 0.420748E+09 | 0.224178E+09 | 0.196570E+09 | 0.00 | 0.00 |
February | 0.396027E+09 | 0.932315E+09 | 0.323701E+09 | 0.125662E+09 | 0.198039E+09 | 0.00 | 0.00 |
March | 0.738946E+09 | 0.957271E+09 | 0.476270E+09 | 0.182797E+09 | 0.293473E+09 | 0.00 | 0.00 |
April | 0.144902E+10 | 0.653899E+09 | 0.675410E+09 | 0.322512E+09 | 0.352898E+09 | 0.00 | 0.00 |
May | 0.167408E+10 | 0.509961E+09 | 0.723572E+09 | 0.341639E+09 | 0.381933E+09 | 0.00 | 0.00 |
June | 0.211060E+10 | 0.242807E+09 | 0.756611E+09 | 0.385099E+09 | 0.371512E+09 | 0.00 | 0.00 |
July | 0.166416E+10 | 0.222373E+09 | 0.588352E+09 | 0.227527E+09 | 0.360826E+09 | 0.00 | 0.00 |
August | 0.155641E+10 | 0.282459E+09 | 0.541261E+09 | 0.220949E+09 | 0.320312E+09 | 0.00 | 0.00 |
September | 0.122774E+10 | 0.364061E+09 | 0.463261E+09 | 0.153699E+09 | 0.309561E+09 | 0.00 | 0.00 |
October | 0.904365E+09 | 0.868215E+09 | 0.464099E+09 | 0.220549E+09 | 0.243551E+09 | 0.00 | 0.00 |
November | 0.632055E+09 | 0.107906E+10 | 0.406517E+09 | 0.207122E+09 | 0.199394E+09 | 0.00 | 0.00 |
December | 0.482926E+09 | 0.130051E+10 | 0.346587E+09 | 0.165265E+09 | 0.181323E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135541E+11 | 0.849043E+10 | 0.618639E+10 | 0.277700E+10 | 0.340939E+10 | 0.00 | 0.00 |
Minimum of Months | 0.396027E+09 | 0.222373E+09 | 0.323701E+09 | 0.125662E+09 | 0.181323E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211060E+10 | 0.130051E+10 | 0.756611E+09 | 0.385099E+09 | 0.381933E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272298E+10 | 0.197477E+10 | 0.204132E+10 | 0.157661E+10 | 0.464705E+09 | 0.00 | 0.00 |
February | 0.223560E+10 | 0.145389E+10 | 0.179391E+10 | 0.115324E+10 | 0.640673E+09 | 0.00 | 0.00 |
March | 0.361649E+10 | 0.179722E+10 | 0.280710E+10 | 0.179545E+10 | 0.101165E+10 | 0.00 | 0.00 |
April | 0.562053E+10 | 0.184847E+10 | 0.419661E+10 | 0.324038E+10 | 0.956236E+09 | 0.00 | 0.00 |
May | 0.638721E+10 | 0.185277E+10 | 0.477316E+10 | 0.374732E+10 | 0.102584E+10 | 0.00 | 0.00 |
June | 0.671313E+10 | 0.133190E+10 | 0.486480E+10 | 0.397663E+10 | 0.888172E+09 | 0.00 | 0.00 |
July | 0.562264E+10 | 0.105133E+10 | 0.407315E+10 | 0.294869E+10 | 0.112446E+10 | 0.00 | 0.00 |
August | 0.521965E+10 | 0.127340E+10 | 0.375358E+10 | 0.277422E+10 | 0.979357E+09 | 0.00 | 0.00 |
September | 0.400230E+10 | 0.126718E+10 | 0.292249E+10 | 0.183324E+10 | 0.108925E+10 | 0.00 | 0.00 |
October | 0.346485E+10 | 0.211343E+10 | 0.269215E+10 | 0.202386E+10 | 0.668288E+09 | 0.00 | 0.00 |
November | 0.244397E+10 | 0.195336E+10 | 0.193604E+10 | 0.140174E+10 | 0.534300E+09 | 0.00 | 0.00 |
December | 0.226146E+10 | 0.219144E+10 | 0.176597E+10 | 0.129220E+10 | 0.473773E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.503108E+11 | 0.201092E+11 | 0.376203E+11 | 0.277636E+11 | 0.985670E+10 | 0.00 | 0.00 |
Minimum of Months | 0.223560E+10 | 0.105133E+10 | 0.176597E+10 | 0.115324E+10 | 0.464705E+09 | 0.00 | 0.00 |
Maximum of Months | 0.671313E+10 | 0.219144E+10 | 0.486480E+10 | 0.397663E+10 | 0.112446E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.45 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.34 | 6.24 | 2.64 | 2.52 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.66 | 1.96 | 3.53 | 3.01 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.11 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.03 | -4.9 | 3.62 | 8.59 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.25 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.97 | 9.86 | 3.72 | 19.27 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.13 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.57 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.96 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.79 | 1.49 | 3.02 | 1.82 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.55 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.13 | 11.45 | 3.72 | 19.27 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.69 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.41 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.76 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.53 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.53 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.69 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.36 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.22 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.78 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 18.97 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.17 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.86 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.69 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.78 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.1 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.58 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.2 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.39 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.95 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.22 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.50 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.46 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.3 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.3 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.3 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.72 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.16 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.67 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.53 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.15 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.10 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.17 | 16-AUG-10:50 | 34.50 | 17.17 | 2.27 | 23.90 | 134.33 | 837.00 |
September | 22.21 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.52 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.04 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.04 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.15 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.72 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.69 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 13.98 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.74 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.15 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.10 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.16 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.15 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.859997E+09 | -720545897.5 | 0.00 | 0.00 | 744.00 | 0.00 | -139451456.8 | 58.99 | 0.00 | 0.00 |
February | 0.782927E+09 | -655389870.7 | 0.00 | 0.00 | 672.00 | 0.00 | -127537282.6 | 58.99 | 0.00 | 0.00 |
March | 0.865582E+09 | -728660819.3 | 0.00 | 0.00 | 744.00 | 0.00 | -136921366.9 | 58.99 | 0.00 | 0.00 |
April | 0.746027E+09 | -623091465.7 | 0.00 | 0.00 | 720.00 | 0.00 | -122935748.8 | 58.99 | 0.00 | 0.00 |
May | 0.712676E+09 | -587754674.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124921716.5 | 58.99 | 0.00 | 0.00 |
June | 0.654479E+09 | -535586332.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118892285.7 | 58.99 | 0.00 | 0.00 |
July | 0.616297E+09 | -494119208.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122177603.0 | 58.99 | 0.00 | 0.00 |
August | 0.661922E+09 | -538556326.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123365338.0 | 58.99 | 0.00 | 0.00 |
September | 0.656391E+09 | -537005510.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119385239.9 | 58.99 | 0.00 | 0.00 |
October | 0.720975E+09 | -592711103.2 | 0.00 | 0.00 | 744.00 | 0.00 | -128264300.3 | 58.99 | 0.00 | 0.00 |
November | 0.755497E+09 | -624737250.8 | 0.00 | 0.00 | 720.00 | 0.00 | -130759346.3 | 58.99 | 0.00 | 0.00 |
December | 0.839061E+09 | -697053242.0 | 0.00 | 0.00 | 744.00 | 0.00 | -142007784.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.887183E+10 | -.733521E+10 | 8760.00 | -.153662E+10 | 58.99 | |||||
Minimum of Months | 0.616297E+09 | -728660819.3 | 0.00 | 0.00 | 672.00 | 0.00 | -142007784.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.865582E+09 | -494119208.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118892285.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | ||||||||||
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.386292E+09 | 30625.13 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387460E+09 | 30625.13 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328879E+09 | 30625.13 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16497415.44 | 4211.23 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99544819.70 | 16168.12 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706152E+09 | 30625.13 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192482E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706152E+09 | 30625.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594677E+09 | 81802.91 | 01-JAN-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302853E+09 | 46375.43 | 08-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897530E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594677E+09 | 81802.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.259498E+10 | 0.258887E+10 | 7671.47 | 31-JAN-16:30 | 7671.47 | 0.00 |
February | 0.00 | 0.00 | 0.112230E+10 | 0.107333E+10 | 5054.88 | 22-FEB-16:30 | 5054.88 | 0.00 |
March | 0.00 | 0.00 | 0.306128E+10 | 0.304286E+10 | 8401.45 | 18-MAR-16:00 | 8401.45 | 0.00 |
April | 0.00 | 0.00 | 0.791032E+10 | 0.791032E+10 | 23695.75 | 26-APR-05:01 | 23695.75 | 0.00 |
May | 0.00 | 0.00 | 0.103322E+11 | 0.103322E+11 | 23760.89 | 11-MAY-05:01 | 23760.89 | 0.00 |
June | 0.00 | 0.00 | 0.136024E+11 | 0.135870E+11 | 24598.52 | 19-JUN-05:01 | 24598.52 | 0.00 |
July | 0.00 | 0.00 | 0.139730E+11 | 0.129145E+11 | 28773.08 | 14-JUL-05:01 | 19635.81 | 0.00 |
August | 0.00 | 0.00 | 0.145818E+11 | 0.134110E+11 | 28200.54 | 10-AUG-05:01 | 19980.67 | 0.00 |
September | 0.00 | 0.00 | 0.124591E+11 | 0.114429E+11 | 28393.08 | 05-SEP-05:01 | 20910.27 | 0.00 |
October | 0.00 | 0.00 | 0.727923E+10 | 0.708094E+10 | 26781.22 | 03-OCT-05:01 | 22494.95 | 0.00 |
November | 0.00 | 0.00 | 0.367548E+10 | 0.352356E+10 | 24714.54 | 03-NOV-05:02 | 21679.19 | 0.00 |
December | 0.00 | 0.00 | 0.139628E+10 | 0.139616E+10 | 6124.09 | 22-DEC-16:30 | 6124.09 | 0.00 |
Annual Sum or Average | 0.919883E+11 | 0.883037E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.112230E+10 | 0.107333E+10 | 5054.88 | 5054.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145818E+11 | 0.135870E+11 | 28773.08 | 24598.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.717394E+09 | 0.717394E+09 | 11563.49 | 31-JAN-16:00 | 11563.49 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212338E+10 | 0.211727E+10 | 19590.63 | 18-MAR-15:00 | 19590.63 | 0.00 |
April | 0.00 | 0.00 | 0.226635E+11 | 0.226635E+11 | 76203.20 | 25-APR-17:05 | 76203.20 | 0.00 |
May | 0.00 | 0.00 | 0.351532E+11 | 0.351532E+11 | 77596.17 | 21-MAY-18:33 | 77596.17 | 0.00 |
June | 0.00 | 0.00 | 0.566858E+11 | 0.566114E+11 | 81988.59 | 18-JUN-08:23 | 81282.81 | 0.00 |
July | 0.00 | 0.00 | 0.575831E+11 | 0.534974E+11 | 91561.16 | 17-JUL-19:42 | 74127.21 | 0.00 |
August | 0.00 | 0.00 | 0.534889E+11 | 0.496621E+11 | 87837.49 | 06-AUG-14:13 | 75485.58 | 0.00 |
September | 0.00 | 0.00 | 0.417722E+11 | 0.383802E+11 | 95817.95 | 02-SEP-05:08 | 63129.35 | 0.00 |
October | 0.00 | 0.00 | 0.165999E+11 | 0.160119E+11 | 85877.80 | 01-OCT-15:53 | 77934.78 | 0.00 |
November | 0.00 | 0.00 | 0.253084E+10 | 0.243895E+10 | 22239.32 | 01-NOV-15:00 | 21607.30 | 0.00 |
December | 0.00 | 0.00 | 7637593.93 | 7637593.93 | 2281.69 | 22-DEC-15:30 | 2281.69 | 0.00 |
Annual Sum or Average | 0.289326E+12 | 0.277261E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.575831E+11 | 0.566114E+11 | 95817.95 | 81282.81 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153700E+10 | 0.39 | 1547.66 | 06-JAN-12:50 | 1.03 |
February | 0.141501E+10 | 0.40 | 1547.66 | 02-FEB-07:03 | 1.03 |
March | 0.165865E+10 | 0.42 | 1547.66 | 01-MAR-09:20 | 1.03 |
April | 0.154915E+10 | 0.42 | 1547.66 | 01-APR-11:20 | 1.03 |
May | 0.163054E+10 | 0.45 | 1547.66 | 04-MAY-06:05 | 1.03 |
June | 0.168302E+10 | 0.53 | 1547.66 | 03-JUN-06:15 | 1.03 |
July | 0.162359E+10 | 0.49 | 1547.66 | 06-JUL-15:40 | 1.03 |
August | 0.173008E+10 | 0.49 | 1547.66 | 07-AUG-16:30 | 1.02 |
September | 0.158693E+10 | 0.45 | 1547.66 | 28-SEP-06:40 | 1.03 |
October | 0.155109E+10 | 0.40 | 1547.66 | 11-OCT-09:20 | 1.02 |
November | 0.147275E+10 | 0.38 | 1547.66 | 01-NOV-08:70 | 1.02 |
December | 0.154346E+10 | 0.40 | 1547.66 | 01-DEC-13:00 | 1.03 |
Annual Sum or Average | 0.189813E+11 | 0.43 | |||
Minimum of Months | 0.141501E+10 | 0.38 | 1547.66 | 1.02 | |
Maximum of Months | 0.173008E+10 | 0.53 | 1547.66 | 1.03 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.687374E+10 | 0.62 | 6900.18 | 31-JAN-12:50 | 1.59 |
February | 0.628468E+10 | 0.59 | 6900.18 | 01-FEB-07:03 | 1.58 |
March | 0.737767E+10 | 0.63 | 6900.18 | 21-MAR-11:00 | 1.58 |
April | 0.723361E+10 | 0.78 | 6900.18 | 06-APR-13:00 | 1.58 |
May | 0.796035E+10 | 0.91 | 6900.18 | 11-MAY-07:53 | 1.58 |
June | 0.893388E+10 | 1.20 | 6900.18 | 03-JUN-08:45 | 1.58 |
July | 0.876218E+10 | 1.22 | 6900.18 | 12-JUL-06:45 | 1.57 |
August | 0.882093E+10 | 1.16 | 6900.18 | 09-AUG-06:45 | 1.56 |
September | 0.783611E+10 | 1.03 | 6900.18 | 02-SEP-09:50 | 1.56 |
October | 0.711655E+10 | 0.71 | 6900.18 | 07-OCT-11:27 | 1.57 |
November | 0.655793E+10 | 0.58 | 6900.18 | 18-NOV-13:20 | 1.58 |
December | 0.685355E+10 | 0.61 | 6900.18 | 07-DEC-07:50 | 1.59 |
Annual Sum or Average | 0.906112E+11 | 0.84 | |||
Minimum of Months | 0.628468E+10 | 0.58 | 6900.18 | 1.56 | |
Maximum of Months | 0.893388E+10 | 1.22 | 6900.18 | 1.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 5.00 |
February | 0.39 | 1.50 |
March | 1.67 | 2.07 |
April | 3.79 | 0.20 |
May | 4.23 | 0.00 |
June | 4.27 | 0.01 |
July | 4.69 | 0.01 |
August | 4.50 | 0.01 |
September | 3.42 | 0.01 |
October | 4.10 | 1.31 |
November | 1.75 | 3.14 |
December | 0.39 | 1.00 |
Annual Sum or Average | 33.29 | 0.50 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.69 | 5.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.17 | 0.00 |
February | 0.33 | 0.00 |
March | 0.75 | 0.00 |
April | 0.67 | 0.00 |
May | 0.11 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.00 |
October | 0.58 | 0.00 |
November | 1.58 | 0.00 |
December | 0.67 | 0.00 |
Annual Sum or Average | 6.94 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 5.19 | 0.00 |
May | 4.74 | 0.00 |
June | 10.20 | 0.00 |
July | 12.54 | 0.00 |
August | 14.45 | 0.00 |
September | 8.91 | 0.00 |
October | 1.62 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 57.73 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.45 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224370E+10 | 0.572362E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.172065E+10 | 0.575964E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.249758E+10 | 0.490005E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.382308E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.470226E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.605814E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.588862E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.615998E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.524844E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.361030E+10 | 25346483.44 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246823E+10 | 0.150616E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.192295E+10 | 0.103114E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.463439E+11 | 0.284543E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172065E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.615998E+10 | 0.103114E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.709651E+10 | 0.890791E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.628468E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.803149E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145983E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.197815E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.292679E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.283633E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270187E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.215987E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124793E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.732722E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.685593E+10 | 0.464914E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188704E+12 | 0.135571E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.628468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292679E+11 | 0.890791E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153700E+10 | 0.259498E+10 | 0.386292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141501E+10 | 0.112230E+10 | 0.387460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165865E+10 | 0.306128E+10 | 0.328879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154915E+10 | 0.791032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163054E+10 | 0.103322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168302E+10 | 0.136024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162359E+10 | 0.139730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173008E+10 | 0.145818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158693E+10 | 0.124591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155109E+10 | 0.727923E+10 | 16497415.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147275E+10 | 0.367548E+10 | 99544819.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154346E+10 | 0.139628E+10 | 0.706152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189813E+11 | 0.919883E+11 | 0.192482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141501E+10 | 0.112230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173008E+10 | 0.145818E+11 | 0.706152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.687374E+10 | 0.717394E+09 | 0.594677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737767E+10 | 0.212338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.723361E+10 | 0.226635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.796035E+10 | 0.351532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.893388E+10 | 0.566858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.876218E+10 | 0.575831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.882093E+10 | 0.534889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.783611E+10 | 0.417722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711655E+10 | 0.165999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655793E+10 | 0.253084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685355E+10 | 7637593.93 | 0.302853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906112E+11 | 0.289326E+12 | 0.897530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.628468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.893388E+10 | 0.575831E+11 | 0.594677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.153700E+10 | 0.00 | 0.00 | 0.00 | 0.706702E+09 | 0.00 | 0.572362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141501E+10 | 0.00 | 0.00 | 0.00 | 0.305641E+09 | 0.00 | 0.575964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165865E+10 | 0.00 | 0.00 | 0.00 | 0.838932E+09 | 0.00 | 0.490005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154915E+10 | 0.00 | 0.00 | 0.00 | 0.227393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163054E+10 | 0.00 | 0.00 | 0.00 | 0.307172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168302E+10 | 0.00 | 0.00 | 0.00 | 0.437512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162359E+10 | 0.00 | 0.00 | 0.00 | 0.426504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173008E+10 | 0.00 | 0.00 | 0.00 | 0.442990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158693E+10 | 0.00 | 0.00 | 0.00 | 0.366151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155109E+10 | 0.00 | 0.00 | 0.00 | 0.205920E+10 | 0.00 | 25346483.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147275E+10 | 0.00 | 0.00 | 0.00 | 0.995484E+09 | 0.00 | 0.150616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154346E+10 | 0.00 | 0.00 | 0.00 | 0.379490E+09 | 0.00 | 0.103114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189813E+11 | 0.00 | 0.00 | 0.00 | 0.273627E+11 | 0.00 | 0.284543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141501E+10 | 0.00 | 0.00 | 0.00 | 0.305641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173008E+10 | 0.00 | 0.00 | 0.00 | 0.442990E+10 | 0.00 | 0.103114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.687374E+10 | 0.00 | 0.00 | 0.00 | 0.222771E+09 | 0.00 | 0.890791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737767E+10 | 0.00 | 0.00 | 0.00 | 0.653823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.723361E+10 | 0.00 | 0.00 | 0.00 | 0.736473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.796035E+10 | 0.00 | 0.00 | 0.00 | 0.118211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.893388E+10 | 0.00 | 0.00 | 0.00 | 0.203340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.876218E+10 | 0.00 | 0.00 | 0.00 | 0.196011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.882093E+10 | 0.00 | 0.00 | 0.00 | 0.181978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.783611E+10 | 0.00 | 0.00 | 0.00 | 0.137626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711655E+10 | 0.00 | 0.00 | 0.00 | 0.536279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655793E+10 | 0.00 | 0.00 | 0.00 | 0.769287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685355E+10 | 0.00 | 0.00 | 0.00 | 2378090.23 | 0.00 | 0.464914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906112E+11 | 0.00 | 0.00 | 0.00 | 0.980923E+11 | 0.00 | 0.135571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.628468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.893388E+10 | 0.00 | 0.00 | 0.00 | 0.203340E+11 | 0.00 | 0.890791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217478E+09 | 4685615.85 | 0.00 | 2685251.26 | 0.00 | 0.123183E+09 | 0.325883E+09 | 0.00 | 0.14 |
February | 0.444521E+09 | 0.00 | 0.00 | 1241389.08 | 0.00 | 0.106589E+09 | 0.418050E+09 | 0.00 | 0.14 |
March | 0.252644E+09 | 21335549.97 | 0.00 | 2831776.04 | 0.00 | 0.101132E+09 | 0.427062E+09 | 0.00 | 0.15 |
April | 41657842.89 | 0.287028E+09 | 0.00 | 5765148.57 | 0.00 | 0.00 | 0.157397E+09 | 0.00 | 0.14 |
May | 1484077.39 | 0.511111E+09 | 0.00 | 6334953.06 | 0.00 | 0.00 | 60932844.81 | 0.00 | 0.15 |
June | 0.00 | 0.109439E+10 | 0.00 | 4640105.97 | 0.00 | 0.00 | 11180062.75 | 0.00 | 0.16 |
July | 0.00 | 0.138328E+10 | 0.00 | 1760911.11 | 0.00 | 0.00 | 7055719.29 | 0.00 | 0.15 |
August | 0.00 | 0.146342E+10 | 0.00 | 2705557.87 | 0.00 | 0.00 | 5301388.89 | 0.00 | 0.16 |
September | 0.00 | 0.105021E+10 | 0.00 | 2836261.10 | 0.00 | 0.00 | 12255389.57 | 0.00 | 0.15 |
October | 79938692.15 | 0.303331E+09 | 0.00 | 4931862.28 | 0.00 | 15904619.86 | 0.272160E+09 | 0.00 | 0.14 |
November | 0.159594E+09 | 28280088.91 | 0.00 | 3620494.34 | 327027.82 | 46498137.29 | 0.409932E+09 | 0.00 | 0.14 |
December | 0.445311E+09 | 146429.38 | 0.00 | 1500260.41 | 163175.88 | 0.207607E+09 | 0.321673E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.164263E+10 | 0.614722E+10 | 0.00 | 40853971.08 | 490203.71 | 0.600914E+09 | 0.242888E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1241389.08 | 0.00 | 0.00 | 5301388.89 | 0.00 | 0.14 |
Maximum of Months | 0.445311E+09 | 0.146342E+10 | 0.00 | 6334953.06 | 327027.82 | 0.207607E+09 | 0.427062E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227949E+10 | 3441925.85 | 0.00 | 97598.47 | 179961.09 | 4815460.54 | 91013631.84 | 0.00 | 0.21 |
February | 0.315022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.256370E+10 | 25122998.50 | 0.00 | 1122077.71 | 3309544.37 | 0.00 | 0.228637E+09 | 0.00 | 0.21 |
April | 0.357713E+09 | 0.792238E+09 | 0.00 | 9488150.77 | 394213.27 | 0.00 | 0.708532E+09 | 0.00 | 0.21 |
May | 0.187469E+09 | 0.152454E+10 | 0.00 | 7010567.33 | 0.00 | 0.00 | 0.539413E+09 | 0.00 | 0.22 |
June | 9990269.03 | 0.354305E+10 | 0.00 | 1005770.99 | 0.00 | 0.00 | 0.100089E+09 | 0.00 | 0.20 |
July | 3057672.35 | 0.421666E+10 | 0.00 | 377274.15 | 0.00 | 0.00 | 44821928.25 | 0.00 | 0.18 |
August | 1833709.18 | 0.446131E+10 | 0.00 | 709158.32 | 0.00 | 0.00 | 0.194138E+09 | 0.00 | 0.21 |
September | 0.124631E+09 | 0.297346E+10 | 0.00 | 1843997.50 | 0.00 | 0.00 | 0.358581E+09 | 0.00 | 0.22 |
October | 0.106255E+10 | 0.765682E+09 | 0.00 | 4318612.62 | 0.00 | 0.00 | 0.895956E+09 | 0.00 | 0.22 |
November | 0.212361E+10 | 23520041.04 | 0.00 | 1298219.74 | 0.00 | 0.00 | 0.604084E+09 | 0.00 | 0.20 |
December | 0.272937E+10 | 0.00 | 0.00 | 0.00 | 11153541.26 | 12399877.29 | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.145936E+11 | 0.183290E+11 | 0.00 | 27271427.60 | 15037259.99 | 17215337.83 | 0.376527E+10 | 0.00 | 0.21 |
Minimum of Months | 1833709.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.315022E+10 | 0.446131E+10 | 0.00 | 9488150.77 | 11153541.26 | 12399877.29 | 0.895956E+09 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |