Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2583.55 | 534.33 | 534.33 |
Net Site Energy | 2583.55 | 534.33 | 534.33 |
Total Source Energy | 4251.15 | 879.22 | 879.22 |
Net Source Energy | 4251.15 | 879.22 | 879.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1887.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 84.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 696.39 | 1887.16 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1887.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 402.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 84.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.00 | 390.30 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 144.03 | 390.30 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.00 | 390.30 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 144.03 | 390.30 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 696.388 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 696.388 | 100.00 |
Total On-Site and Utility Electric Sources | 696.388 | 100.00 |
Total Electricity End Uses | 696.388 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 77.50 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2589.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 20.62 |
Skylight-Roof Ratio [%] | 0.45 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.6875 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5596 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-15:20 | 28-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 304155.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2690.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 52616.28 | 304155.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 304155.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2690.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2045.68 | 0.00 | 0.00 | 0.00 |
Cooling | 6.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1274.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 266.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 133.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2205.46 | 2045.68 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 423.09 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 263.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 456.13 | 423.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 423.09 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 263.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 456.13 | 423.09 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.806712 |
ZONE2 FINE STORAGE DIRECT AIR | 1.57 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.86 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.86 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 157751.51 |
PSZ-OFFICE HEATING COIL | 25878.53 |
PSZ-FINE STORAGE HEATING COIL | 74754.02 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 157763.75 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.806712 | 0.806712 | 0.806712 | 0.806712 | 0.806712 | 0.806712 | 1.00 | 1.00 | 0.806712 |
PSZ-FINE STORAGE | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.000000 | 1.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.806712 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.57 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.806712 | 0.806712 | 0.806712 | 0.806712 | 13353.94 | 25878.53 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.57 | 29233.34 | 74754.02 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.806710 | 0.403355 | 0.537807 | 13353.91 | 13353.94 | 6676.97 | 6676.97 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.57 | 0.784585 | 1.05 | 26033.50 | 29233.34 | 14616.67 | 14616.67 | 0.757681 | 0.757680 | 0.757680 | 0.757680 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.806712 | 893.16 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.57 | 1679.08 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 9.688 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.761 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2294.776 | 9.688 | 458.955 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2294.776 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 14248.610 | 10.226 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.610 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 20008.048 | 6.243 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.048 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 28 | 1 | VerySmooth | 2.443 | 0.445 | 0.367 | 0.451 |
2 | SKYLIGHT_U_0.98_SHGC_0.49 | 29 | 1 | VerySmooth | 5.556 | 0.489 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.36619 | 0.42642 | 0.42642 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.13808 | 0.13808 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.14909 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.263 | 7.062E-004 | 4.613E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8044.83496 | 9653.80196 | 0.67226 | 0.80671 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 25.63200 | 6.97981E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12045.83468 | 14455.00161 | 0.34357 | 0.41228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 20074.91978 | 24089.90374 | 1.30764 | 1.56917 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 6.97981E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 36404.50059 | 43685.40071 | 0.87443 | 1.04932 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40000 | 6.97982E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 131469.79117 | 157763.74940 | 3.21533 | 3.85840 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 11680.74 | 0.80671 | 0.80671 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16975.74 | 0.41228 | 0.41228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 27663.26 | 1.56917 | 1.56917 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 59619.25 | 1.04932 | 1.04932 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80671 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56917 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.85840 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.85840 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 157751.51198 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 157763.74940 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80671 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80671 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80671 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80671 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80671 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.80671 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56917 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56917 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56917 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56917 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56917 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.56917 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.80671 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.56917 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80671 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80671 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80671 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80671 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80671 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80671 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40336 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53781 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13353.91491 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13353.94000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6676.97000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6676.97000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13353.94000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25878.52945 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80671 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 893.15771 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25878.52945 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56917 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56917 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56917 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56917 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56917 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56917 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78459 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04611 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26033.49556 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29233.34000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14616.67000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14616.67000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75768 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75768 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75768 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75768 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29233.34000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 74754.01804 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56917 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1679.08498 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 74754.01804 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 12728.0 | 11.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 28015.2 | 16.59 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3818623656 | 0.3548196805 | Pass | Pass | 2.0569083545 | 6.2923402224 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.8231142140 | 0.7454963207 | Pass | Pass | 0.6820462621 | 0.6438533572 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.0982258978E-005 | 3.1504449775E-005 | Pass | Pass | 2.0530637326E-002 | 1.9088102971E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3184.23 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.443 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.43_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.443 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.443 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.43_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.443 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 0.58 | 0.00 | 2.06 | 2.06 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 38.28 | 4.240 | 0.502 | 0.505 | ||||||||||||
North Total or Average | 6.51 | 2.443 | 0.445 | 0.451 | ||||||||||||
Non-North Total or Average | 31.77 | 4.608 | 0.513 | 0.516 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 9.6875 | 236.88 | 2294.78 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 58.77 | 168.00 | 51.74 | 0.0000 | Y | 22.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 10.2257 | 1393.41 | 14248.61 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 6.2431 | 3204.84 | 20008.05 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 58.04 | 0.0000 | Y | 217.99 |
Interior Lighting Total | 7.5596 | 4835.13 | 36551.43 | 402.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2294.78 | 252.43 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.05 | 2320.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 44.84 | 44.84 | 0.96 | |
EXTERIOR_LIGHTS_B | 6197.40 | AstronomicalClock | - | 83.06 | 71.59 | 83.29 | |
Exterior Lighting Total | 6311.20 | 84.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13353.94 | 10665.26 | 2688.68 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29233.34 | 22149.52 | 7083.82 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 12728.0 | 11.41 | ||||
PSZ-FINE STORAGE COOLING COIL | 28015.2 | 16.59 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 157751.51 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25878.53 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 74754.02 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.86 | 358.49 | 92.91 | 1.00 | 3.25 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.81 | 893.16 | 1107.16 | 1.00 | 1.46 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1679.08 | 1070.05 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8044.83 | 9653.80 | 40.75 | 0.672 | 0.807 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 23.90 | 23.90 | 0.00811 | 25.63 | 0.00698 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20074.92 | 24089.90 | 17.29 | 1.308 | 1.569 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00793 | 26.99 | 0.00698 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00384 | 27.40 | 0.00698 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12045.83 | 14455.00 | 61.02 | 0.344 | 0.412 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00810 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36404.50 | 43685.40 | 31.35 | 0.874 | 1.049 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 15.56 | 15.56 | 0.00778 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 131469.79 | 157763.75 | 49.23 | 3.215 | 3.858 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | 10.00 | 10.00 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.81 | 0.81 | 0.41 | 0.41 | 0.8067 | 0.8067 | 0.8067 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.57 | 1.57 | 1.05 | 1.05 | 1.5692 | 1.5692 | 1.5692 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 157751.512 | 157751.512 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | 157751.51 | 157751.51 | 3.858398 | -3.14 | -3.14 | 0.00580555 | 43.33 | 26.90 | 0.01600000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00775175 | 100.0000 | 157763.75 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 6676.970 | 0.000 | 0.806710 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 6676.97 | 6676.97 | 0.806710 | 24.16 | 15.82 | 0.00798448 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00697981 | 15.59 | 12.6793 | 23.90 | 0.00810983 | 43.2637 | 8040.01 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25878.529 | 25878.529 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25878.53 | 25878.53 | 0.806712 | 5.43 | 5.43 | 0.00610757 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 12.6792 | 21.10 | 0.00810153 | 51.2341 | 12045.83 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 14616.670 | 0.000 | 1.569170 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 14616.67 | 14616.67 | 1.569170 | 26.83 | 16.49 | 0.00766949 | 12.00 | 11.12 | 0.00800000 | 27.20 | 0.00697982 | 16.03 | 27.0661 | 26.70 | 0.00792651 | 35.8078 | 20027.43 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 74754.018 | 74754.018 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 74754.02 | 74754.02 | 1.569169 | -7.70 | -7.70 | 0.00465510 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 27.0661 | 15.56 | 0.00777656 | 69.6648 | 36404.50 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 157751.512 | 157751.512 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1854 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.858398 | 4.57389651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:40:00 | 157751.51 | 157751.51 | 1.0000 | 4.57389651 | 3.858398 | -3.14 | -3.14 | 0.00580555 | 11328.1 | 43.33 | 26.90 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 157751.51 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 9.99 | 0.00775175 | 10.00 | 0.00775175 | 100.0000 | 157763.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6676.970 | 0.000 | 0.806710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6828 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 6676.97 | 6676.97 | 1.0000 | 0.95630573 | 0.806710 | 24.16 | 15.82 | 0.00798448 | 44606.9 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6676.97 | 25.97 | 0.00697981 | 15.59 | 0.10228487 | 12.6793 | 23.90 | 0.00813047 | 23.90 | 0.00810983 | 43.2637 | 8040.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25878.529 | 25878.529 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.806712 | 0.95630754 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25878.53 | 25878.53 | 1.0000 | 0.95630754 | 0.806712 | 5.43 | 5.43 | 0.00610757 | 20796.3 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25878.53 | -41.90 | 0.00006450 | -41.90 | 0.10228487 | 12.6792 | 21.05 | 0.00810153 | 21.10 | 0.00810153 | 51.2341 | 12045.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14616.670 | 0.000 | 1.569170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0972 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 14616.67 | 14616.67 | 1.0000 | 1.86015578 | 1.569170 | 26.83 | 16.49 | 0.00766949 | 46528.1 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14616.67 | 27.20 | 0.00697982 | 16.03 | 0.42471267 | 27.0661 | 26.70 | 0.00792627 | 26.70 | 0.00792651 | 35.8078 | 20027.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 74754.018 | 74754.018 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.569169 | 1.86015456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 74754.02 | 74754.02 | 1.0000 | 1.86015456 | 1.569169 | -7.70 | -7.70 | 0.00465510 | 3840.9 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 74754.02 | -41.90 | 0.00006450 | -41.90 | 0.42471267 | 27.0661 | 15.56 | 0.00777656 | 15.56 | 0.00777656 | 69.6648 | 36404.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2609.67 | 3379.17 | 2589.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2609.67 | 3379.17 | 2589.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 172.33 | 20.50 | 77.50 | 1.33 |
ZONE2 FINE STORAGE | 704.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 20.33 | 0.00 | 0.00 | 0.00 |
Facility | 837.33 | 20.50 | 77.50 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.309 | 0.226 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
Electricity:Building | 539.62 | 4004.31 | 05-MAR-11:00 | 40683.64 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 52.01 | 810.73 | 12-FEB-14:10 | 3365.36 | 02-JAN-08:10 |
InteriorLights:Electricity | 402.56 | 3515.76 | 05-MAR-11:00 | 30629.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 22.29 | 322.19 | 12-FEB-14:10 | 1511.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 402.56 | 3515.76 | 05-MAR-11:00 | 30629.63 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 325.33 | 1768.71 | 05-MAR-11:00 | 25206.96 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 217.99 | 1768.71 | 05-MAR-11:00 | 17006.84 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 28.37 | 481.00 | 02-JAN-06:40 | 3130.15 | 11-JAN-13:00 |
WaterSystems:Electricity | 28.37 | 481.00 | 02-JAN-06:40 | 3130.15 | 11-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 28.37 | 481.00 | 02-JAN-06:40 | 3130.15 | 11-JAN-13:00 |
Fans:Electricity | 42.17 | 0.00 | 19-MAR-12:30 | 2930.73 | 02-JAN-07:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
ElectricityPurchased:Plant | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
Cogeneration:ElectricityPurchased | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
ElectricityNet:Plant | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
Cogeneration:ElectricityNet | 696.39 | 4485.31 | 19-MAR-12:30 | 52616.28 | 09-JAN-15:20 |
Electricity:HVAC | 44.16 | 0.00 | 19-MAR-12:30 | 7025.26 | 29-JUL-16:00 |
General:Fans:Electricity | 42.17 | 0.00 | 19-MAR-12:30 | 2930.73 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.99 | 0.00 | 01-JAN-00:10 | 4453.01 | 29-JUL-16:00 |
ExteriorLights:Electricity | 84.25 | 0.00 | 01-JAN-11:20 | 6311.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 84.25 | 0.00 | 01-JAN-11:20 | 6311.20 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1887.16 | 0.00 | 19-MAR-12:20 | 304155.05 | 28-JAN-17:10 |
Gas:HVAC | 1887.16 | 0.00 | 19-MAR-12:20 | 304155.05 | 28-JAN-17:10 |
Heating:Gas | 1887.16 | 0.00 | 19-MAR-12:20 | 304155.05 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2865.64 | 0.00 | 19-MAR-12:30 | 473995.71 | 29-JAN-00:10 |
EnergyTransfer:Building | 1400.06 | 0.00 | 19-MAR-12:30 | 236931.37 | 29-JAN-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 79.07 | 0.00 | 01-JAN-00:40 | 26843.67 | 27-FEB-07:10 |
Heating:EnergyTransfer | 1378.58 | 0.00 | 19-MAR-12:30 | 236931.37 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 71.98 | 0.00 | 01-JAN-00:40 | 26843.67 | 27-FEB-07:10 |
Cooling:EnergyTransfer | 21.48 | 0.00 | 01-JAN-00:10 | 14458.72 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 7.09 | 0.00 | 01-JAN-00:10 | 4907.67 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 265.43 | 0.00 | 01-JAN-00:40 | 73813.36 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 251.04 | 0.00 | 01-JAN-00:40 | 73813.36 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 14.39 | 0.00 | 01-JAN-00:10 | 9551.05 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1055.56 | 0.00 | 18-MAR-09:30 | 159227.32 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1055.56 | 0.00 | 18-MAR-09:30 | 159227.32 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1465.58 | 0.00 | 19-MAR-12:20 | 241027.33 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1456.59 | 0.00 | 19-MAR-12:20 | 241027.33 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 9.00 | 0.00 | 01-JAN-00:10 | 19139.46 | 29-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 71.979 | -7.088 | 0.000 | 0.000 | 4.061 | 22.287 | 29.720 | 7.057 | 0.000 | 0.031 | 0.000 | 0.000 | -18.462 | 0.000 | -26.573 | -83.011 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 251.039 | -14.390 | 0.000 | 0.000 | 0.000 | 162.279 | 0.000 | 0.000 | 0.000 | 0.031 | 0.001 | 0.000 | 0.000 | 0.000 | -93.815 | -305.144 |
ZONE3 BULK STORAGE | 1055.560 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 217.993 | 107.336 | 18.136 | 0.000 | 0.922 | 0.000 | 0.000 | -33.270 | 0.000 | -446.072 | -920.607 |
Total Facility | 1055.560 | 0.000 | 323.018 | -21.478 | 0.000 | 0.000 | 4.061 | 402.560 | 137.056 | 25.194 | 0.000 | 0.984 | 0.001 | 0.000 | -51.732 | 0.000 | -566.461 | -1308.762 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-00:02 | 0.00 | 0.00 | 0.00 | -11807.70 | 0.00 | 0.00 | 0.00 | 413.06 | 488.55 | 0.00 | 0.00 | 0.00 | 11426.43 | 0.00 | -395.00 | 0.00 | -125.33 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-13:51 | 0.00 | 0.00 | 0.00 | -29709.19 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 28586.52 | 0.00 | -0.00 | 0.00 | -302.19 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-13:51 | 0.00 | 0.00 | 0.00 | -29709.19 | 0.00 | 0.00 | 0.00 | 3593.12 | 488.55 | 5828.44 | 0.00 | 0.00 | 22001.41 | 0.00 | 0.00 | 0.00 | -2202.33 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-DEC-06:31 | 0.00 | 0.00 | 27571.65 | 0.00 | 0.00 | 0.00 | 55.31 | 451.48 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1420.98 | 0.00 | -1548.94 | -25664.68 |
ZONE2 FINE STORAGE | 25-FEB-06:41 | 0.00 | 0.00 | 78410.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17209.49 | -62626.03 |
ZONE3 BULK STORAGE | 28-JAN-15:00 | 159224.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2406.03 | 0.00 | -168635.62 | -13390.23 |
Total Facility | 24-FEB-06:11 | 158106.42 | 0.00 | 102595.51 | 0.00 | 0.00 | 0.00 | 46.49 | 3877.14 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4441.58 | 0.00 | -108073.23 | -154716.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8067 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8067 | 0.1268 | 1.0000 | 0.1023 | 0.1268 | ||
PSZ-FINE STORAGE | 1.5692 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.5692 | 0.2707 | 1.0000 | 0.4247 | 0.2707 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8067 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8067 | 1.0000 | 1.0000 | 0.1023 | 0.1268 | ||
PSZ-FINE STORAGE | 1.5692 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.5692 | 1.0000 | 1.0000 | 0.4247 | 0.2707 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8067 | 0.8067 | 0.8067 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.5692 | 1.5692 | 1.5692 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8067 | 0.8067 | 0.8067 | 0.8067 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.5692 | 1.5692 | 1.5692 | 1.5692 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8067 | 0.8067 | 0.8067 | 0.1023 | 0.2481 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.5692 | 1.5692 | 1.5692 | 0.4247 | 0.4048 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8067 | 0.8067 | 0.8067 | 0.8067 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.5692 | 1.5692 | 1.5692 | 1.5692 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 77.50 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 78.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1887.16 | 304155.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 1.99 | 4453.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 402.56 | 30629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 84.25 | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.17 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.37 | 3130.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 696.39 |
Natural Gas | 0.00 | 1887.16 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 2583.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 83.26 |
Space Heating | 0.00 |
Space Cooling | 0.41 |
Fans (All) | 8.72 |
Service Water Heating | 5.87 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 144.03 |
Subtotal | 144.03 |
Natural Gas [MJ/m2] | |
Space Heating | 390.30 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 390.30 |
Subtotal | 390.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.58 |
Space Heating | 73.05 |
Space Cooling | 0.08 |
Fans (All) | 1.63 |
Service Water Heating | 1.10 |
Receptacle Equipment | 5.30 |
Miscellaneous | 3.26 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3065. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.375081E+12 |
February | 0.000 | 0.305771E+12 |
March | 0.000 | 0.271435E+12 |
April | 0.000 | 0.112550E+12 |
May | 0.000 | 0.442586E+10 |
June | 0.000 | 0.890294E+08 |
July | 0.000 | 2049084.899 |
August | 0.000 | 0.941909E+08 |
September | 0.000 | 0.949235E+10 |
October | 0.000 | 0.153003E+12 |
November | 0.000 | 0.285606E+12 |
December | 0.000 | 0.369612E+12 |
Annual Sum or Average | 0.188716E+13 | |
Minimum of Months | 0.000 | 2049084.899 |
Maximum of Months | 0.000 | 0.375081E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.194803E+09 | 236.59 | 19-JAN-08:30 | -5.0 | -5.5 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.179314E+09 | 236.59 | 14-FEB-13:30 | -2.5 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.1 | 0.210520E+09 | 236.59 | 17-MAR-07:30 | -4.7 | -6.0 |
April | 379931.65 | 86.09 | 20-APR-16:00 | 13.30 | 5.79 | 0.195053E+09 | 252.51 | 22-APR-15:00 | 15.00 | 6.58 |
May | 35281752.56 | 581.46 | 20-MAY-14:00 | 9.40 | 6.03 | 0.211342E+09 | 301.58 | 13-MAY-15:20 | 20.00 | 9.29 |
June | 0.158177E+10 | 7800.39 | 21-JUN-17:15 | 25.93 | 14.27 | 0.252540E+09 | 301.59 | 30-JUN-09:30 | 18.30 | 15.23 |
July | 0.303318E+10 | 11808.00 | 24-JUL-00:02 | 15.40 | 13.50 | 0.247705E+09 | 301.61 | 03-JUL-15:09 | 19.50 | 17.42 |
August | 0.228042E+10 | 9408.89 | 07-AUG-00:03 | 11.60 | 10.75 | 0.262830E+09 | 301.59 | 03-AUG-12:09 | 18.48 | 15.31 |
September | 0.157336E+09 | 1370.84 | 02-SEP-16:00 | 16.70 | 10.41 | 0.201883E+09 | 301.58 | 01-SEP-15:50 | 15.50 | 10.80 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 1.42 | 0.11 | 0.194995E+09 | 236.59 | 07-OCT-07:30 | 4.45 | 3.82 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.187141E+09 | 236.59 | 18-NOV-08:30 | -11.4 | -11.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.194935E+09 | 236.59 | 23-DEC-08:30 | -2.2 | -3.6 |
Annual Sum or Average | 0.708837E+10 | 0.253306E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.179314E+09 | 236.59 | -11.4 | -11.8 | ||
Maximum of Months | 0.303318E+10 | 11808.00 | 25.93 | 14.27 | 0.262830E+09 | 301.61 | 20.00 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.239329E+09 | 9723.38 | 28-MAR-10:55 | -8.3 | -10.6 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.148831E+10 | 5728.50 | 13-APR-11:00 | 1.10 | -2.0 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.143808E+10 | 6838.63 | 13-MAY-06:10 | 10.87 | 4.37 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.175836E+10 | 7889.69 | 01-JUN-06:10 | 7.57 | 5.43 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.292091E+10 | 29710.57 | 23-JUL-13:51 | 25.00 | 15.24 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.294860E+10 | 7504.32 | 30-AUG-07:05 | 0.78 | -1.0 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.281891E+10 | 6482.96 | 16-SEP-07:05 | -0.1 | -0.4 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.777159E+09 | 7147.51 | 18-OCT-10:35 | -2.8 | -3.3 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.143897E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.294860E+10 | 29710.57 | 25.00 | 15.24 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.1 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 1.42 | 0.11 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125865E+11 | 27491.05 | 17-JAN-06:31 | -7.2 |
February | 0.111825E+11 | 27562.41 | 14-FEB-06:31 | -16.1 |
March | 0.110268E+11 | 27544.82 | 04-MAR-06:31 | -26.8 |
April | 0.571150E+10 | 27443.11 | 04-APR-05:31 | -11.3 |
May | 0.173540E+10 | 26214.18 | 01-MAY-05:12 | 7.40 |
June | 0.152245E+09 | 25845.01 | 01-JUN-05:01 | 7.20 |
July | 58528074.63 | 1769.41 | 05-JUL-06:25 | 8.30 |
August | 0.137902E+09 | 16962.75 | 31-AUG-05:03 | -1.2 |
September | 0.177182E+10 | 26119.25 | 25-SEP-05:01 | -1.2 |
October | 0.582560E+10 | 27443.70 | 31-OCT-05:31 | -18.0 |
November | 0.994037E+10 | 27522.05 | 13-NOV-06:31 | -17.6 |
December | 0.118505E+11 | 27571.62 | 13-DEC-06:31 | -25.6 |
Annual Sum or Average | 0.719797E+11 | |||
Minimum of Months | 58528074.63 | 1769.41 | -26.8 | |
Maximum of Months | 0.125865E+11 | 27571.62 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492709E+11 | 77626.55 | 29-JAN-12:01 | -23.3 |
February | 0.406525E+11 | 78410.81 | 25-FEB-06:41 | -24.4 |
March | 0.359532E+11 | 77695.96 | 02-MAR-04:41 | -26.6 |
April | 0.173542E+11 | 77099.51 | 02-APR-19:02 | -10.9 |
May | 0.135647E+10 | 64092.89 | 04-MAY-05:07 | 2.48 |
June | 0.149575E+09 | 1631.26 | 02-JUN-07:00 | 9.40 |
July | 0.124307E+09 | 1700.30 | 20-JUL-07:00 | 14.40 |
August | 0.160386E+09 | 1730.58 | 29-AUG-07:00 | 7.80 |
September | 0.195524E+10 | 65019.23 | 25-SEP-05:01 | -1.2 |
October | 0.202955E+11 | 76914.59 | 31-OCT-04:22 | -18.1 |
November | 0.365623E+11 | 76990.74 | 10-NOV-02:42 | -18.2 |
December | 0.472045E+11 | 77089.14 | 28-DEC-03:22 | -27.2 |
Annual Sum or Average | 0.251039E+12 | |||
Minimum of Months | 0.124307E+09 | 1631.26 | -27.2 | |
Maximum of Months | 0.492709E+11 | 78410.81 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213749E+12 | 159227.32 | 28-JAN-15:00 | -20.0 |
February | 0.173274E+12 | 158424.96 | 24-FEB-01:00 | -24.4 |
March | 0.151537E+12 | 142907.12 | 02-MAR-04:57 | -26.7 |
April | 0.600384E+11 | 125570.29 | 02-APR-20:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.221317E+10 | 34355.00 | 30-SEP-05:00 | -4.4 |
October | 0.847102E+11 | 110106.40 | 27-OCT-04:00 | -17.8 |
November | 0.159258E+12 | 121717.95 | 29-NOV-08:00 | -28.9 |
December | 0.210782E+12 | 139929.88 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.105556E+13 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.213749E+12 | 159227.32 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.207142E+10 | 1511.47 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.178476E+10 | 1511.47 | 01-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.189934E+10 | 1511.47 | 01-MAR-08:09 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.174401E+10 | 1456.05 | 04-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.176651E+10 | 1345.21 | 06-MAY-07:49 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.171064E+10 | 1345.21 | 08-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.172578E+10 | 1345.21 | 01-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.182343E+10 | 1345.21 | 25-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.178196E+10 | 1456.05 | 19-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.192054E+10 | 1511.47 | 02-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.196794E+10 | 1511.47 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.209055E+10 | 1511.47 | 01-DEC-08:09 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.222869E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.171064E+10 | 1345.21 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.209055E+10 | 1511.47 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.134983E+11 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138856E+11 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | ||||
Minimum of Months | 0.123544E+11 | 12111.32 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.189474E+11 | 17006.84 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.171601E+11 | 17006.84 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.192452E+11 | 17006.84 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.176307E+11 | 16349.24 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.179571E+11 | 16349.24 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.175082E+11 | 16349.24 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.173328E+11 | 16349.24 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.185949E+11 | 17006.84 | 30-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.179125E+11 | 17006.84 | 18-SEP-14:20 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.185695E+11 | 17006.84 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.181805E+11 | 17006.84 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.189544E+11 | 17006.84 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.217993E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.171601E+11 | 16349.24 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.192452E+11 | 17006.84 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.207142E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384759E+10 |
February | 0.500553E+09 | 0.178476E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300723E+10 |
March | 0.587605E+09 | 0.189934E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341775E+10 |
April | 0.544079E+09 | 0.174401E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207791E+10 |
May | 0.565842E+09 | 0.176651E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13659.45 | 0.109831E+10 |
June | 0.565842E+09 | 0.171064E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9737333.38 | 0.718189E+09 |
July | 0.544079E+09 | 0.172578E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17397061.65 | 0.573792E+09 |
August | 0.587605E+09 | 0.182343E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3929267.24 | 0.966593E+09 |
September | 0.544079E+09 | 0.178196E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126972E+10 |
October | 0.544079E+09 | 0.192054E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248355E+10 |
November | 0.522316E+09 | 0.196794E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334150E+10 |
December | 0.544079E+09 | 0.209055E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377124E+10 |
Annual Sum or Average | 0.659424E+10 | 0.222869E+11 | 0.297195E+11 | 31077321.72 | 0.265734E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.171064E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573792E+09 |
Maximum of Months | 0.587605E+09 | 0.209055E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17397061.65 | 0.384759E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114963E+11 |
February | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951385E+10 |
March | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137089E+11 |
April | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121102E+11 |
May | 0.00 | 0.138856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4242769.64 | 0.573284E+10 |
June | 0.00 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2671441.26 | 0.434427E+10 |
July | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22206221.70 | 0.387401E+10 |
August | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520532.89 | 0.499357E+10 |
September | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429772E+10 |
October | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106742E+11 |
November | 0.00 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430320E+10 |
December | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876610E+10 |
Annual Sum or Average | 0.162279E+12 | 30640965.48 | 0.938152E+11 | ||||||
Minimum of Months | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387401E+10 |
Maximum of Months | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22206221.70 | 0.137089E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.189474E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389954E+11 |
February | 0.00 | 0.171601E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316764E+11 |
March | 0.00 | 0.192452E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434716E+11 |
April | 0.00 | 0.176307E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23800269.08 | 0.318769E+11 |
May | 0.00 | 0.179571E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324145E+09 | 0.153141E+11 |
June | 0.00 | 0.175082E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105879E+09 | 0.134500E+11 |
July | 0.00 | 0.173328E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55043588.15 | 0.142175E+11 |
August | 0.00 | 0.185949E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77440904.95 | 0.179763E+11 |
September | 0.00 | 0.179125E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129961E+11 |
October | 0.00 | 0.185695E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26602190.90 | 0.308260E+11 |
November | 0.00 | 0.181805E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143154E+11 |
December | 0.00 | 0.189544E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312553E+11 |
Annual Sum or Average | 0.217993E+12 | 0.107336E+12 | 0.612911E+09 | 0.296371E+12 | |||||
Minimum of Months | 0.00 | 0.171601E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129961E+11 |
Maximum of Months | 0.00 | 0.192452E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324145E+09 | 0.434716E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1511.47 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15694.77 | 12-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1511.47 | 01-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14906.77 | 27-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1511.47 | 01-MAR-08:09 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 13131.73 | 01-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1456.05 | 04-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11167.84 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1345.21 | 06-MAY-07:49 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 30-MAY-18:00 | 4657.27 | 16-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1345.21 | 08-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.40 | 29-JUN-16:10 | 3144.33 | 02-JUN-06:05 |
July | 659.25 | 01-JUL-07:10 | 1345.21 | 01-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 21-JUL-16:10 | 3468.42 | 17-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1345.21 | 25-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.98 | 11-AUG-16:10 | 5570.99 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1456.05 | 19-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6471.47 | 29-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1511.47 | 02-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 10755.88 | 31-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1511.47 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13325.83 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1511.47 | 01-DEC-08:09 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 14274.95 | 15-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1345.21 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3144.33 | |||||
Maximum of Months | 659.25 | 1511.47 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 15694.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 39817.78 | 28-JAN-17:00 |
February | 0.00 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 24061.30 | 23-FEB-17:00 |
March | 0.00 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 18292.65 | 25-MAR-15:10 |
April | 0.00 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20561.37 | 01-APR-18:52 |
May | 0.00 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.91 | 30-MAY-18:00 | 10573.92 | 27-MAY-08:00 |
June | 0.00 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.94 | 30-JUN-15:10 | 9171.18 | 24-JUN-21:00 |
July | 0.00 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.73 | 21-JUL-16:00 | 5673.58 | 04-JUL-17:00 |
August | 0.00 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.78 | 23-AUG-18:00 | 9200.81 | 29-AUG-20:00 |
September | 0.00 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5874.43 | 29-SEP-07:00 |
October | 0.00 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 13656.34 | 27-OCT-06:10 |
November | 0.00 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13371.25 | 03-NOV-20:00 |
December | 0.00 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15525.64 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5673.58 | |||
Maximum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.73 | 39817.78 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 17006.84 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 119008.88 | 28-JAN-15:00 |
February | 0.00 | 17006.84 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 79473.39 | 25-FEB-12:00 |
March | 0.00 | 17006.84 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 57055.70 | 25-MAR-09:00 |
April | 0.00 | 16349.24 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.37 | 17-APR-18:00 | 54427.74 | 01-APR-18:52 |
May | 0.00 | 16349.24 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7278.47 | 30-MAY-18:00 | 36865.90 | 27-MAY-11:00 |
June | 0.00 | 16349.24 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4559.21 | 03-JUN-16:00 | 28803.32 | 24-JUN-21:00 |
July | 0.00 | 16349.24 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7249.71 | 21-JUL-16:00 | 17912.88 | 04-JUL-17:00 |
August | 0.00 | 17006.84 | 30-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4119.15 | 23-AUG-18:00 | 33156.50 | 31-AUG-09:00 |
September | 0.00 | 17006.84 | 18-SEP-14:20 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16186.79 | 21-SEP-14:00 |
October | 0.00 | 17006.84 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2953.51 | 01-OCT-17:00 | 40557.15 | 31-OCT-09:00 |
November | 0.00 | 17006.84 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 41183.83 | 01-NOV-09:00 |
December | 0.00 | 17006.84 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 58750.87 | 22-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 16349.24 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16186.79 | ||||
Maximum of Months | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7278.47 | 119008.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2478.36 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.03 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.70 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2478.36 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.90 |
April | 86.09 | 20-APR-16:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.87 |
May | 581.46 | 20-MAY-14:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.92 |
June | 7800.39 | 21-JUN-17:15 | 0.00 | 644.37 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 | 0.00 |
July | 11808.00 | 24-JUL-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.33 |
August | 9408.89 | 07-AUG-00:03 | 0.00 | 1239.18 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1370.84 | 02-SEP-16:00 | 659.25 | 1178.95 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.68 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 1239.18 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.11 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 413.06 | 488.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.34 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2065.30 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 413.06 | 488.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11808.00 | 659.25 | 2478.36 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 | 509.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7477.03 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 7124.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5693.08 |
March | 9723.38 | 28-MAR-10:55 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5728.50 | 13-APR-11:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6838.63 | 13-MAY-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3423.18 |
June | 7889.69 | 01-JUN-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.64 |
July | 29710.57 | 23-JUL-13:51 | 0.00 | 9974.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.19 |
August | 7504.32 | 30-AUG-07:05 | 0.00 | 21372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4787.84 |
September | 6482.96 | 16-SEP-07:05 | 0.00 | 21372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4500.59 |
October | 7147.51 | 18-OCT-10:35 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.57 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6326.33 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 7124.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29710.57 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7477.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 12004.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21455.03 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 10004.02 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16864.26 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 12004.83 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8408.25 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.75 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3901.64 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2893.69 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4288.94 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8305.42 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4817.67 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 6002.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9135.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17147.51 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 10004.02 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 12004.83 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.75 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.650175E+11 | 52616.28 | 09-JAN-15:20 | 0.375081E+12 | 304155.05 | 28-JAN-17:10 |
February | 0.569478E+11 | 51654.34 | 03-FEB-09:09 | 0.305771E+12 | 294932.07 | 24-FEB-08:30 |
March | 0.620650E+11 | 48181.04 | 16-MAR-07:10 | 0.271435E+12 | 247343.94 | 02-MAR-04:49 |
April | 0.548906E+11 | 45314.88 | 07-APR-14:50 | 0.112550E+12 | 211523.07 | 02-APR-19:49 |
May | 0.535712E+11 | 45010.11 | 09-MAY-12:20 | 0.442586E+10 | 28711.08 | 02-MAY-05:10 |
June | 0.517295E+11 | 46252.04 | 30-JUN-14:50 | 89029405.55 | 8014.47 | 01-JUN-05:10 |
July | 0.521421E+11 | 47794.33 | 29-JUL-14:39 | 2049084.90 | 958.13 | 05-JUL-06:30 |
August | 0.567689E+11 | 46011.96 | 11-AUG-14:20 | 94190927.61 | 7533.70 | 31-AUG-06:10 |
September | 0.555978E+11 | 45182.32 | 30-SEP-14:50 | 0.949235E+10 | 75543.39 | 30-SEP-05:19 |
October | 0.603261E+11 | 51636.47 | 31-OCT-08:09 | 0.153003E+12 | 199412.75 | 31-OCT-05:10 |
November | 0.614138E+11 | 52469.02 | 30-NOV-15:39 | 0.285606E+12 | 227015.82 | 29-NOV-08:09 |
December | 0.659181E+11 | 52616.19 | 29-DEC-15:50 | 0.369612E+12 | 250367.84 | 15-DEC-12:09 |
Annual Sum or Average | 0.696388E+12 | 0.188716E+13 | ||||
Minimum of Months | 0.517295E+11 | 45010.11 | 2049084.90 | 958.13 | ||
Maximum of Months | 0.659181E+11 | 52616.28 | 0.375081E+12 | 304155.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345171E+11 | 0.122580E+11 | 0.113456E+11 | 0.00 | 0.446686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242993E+10 | 0.00 |
February | 0.312993E+11 | 0.896649E+10 | 0.104160E+11 | 0.00 | 0.405489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221122E+10 | 0.00 |
March | 0.354174E+11 | 0.754358E+10 | 0.121485E+11 | 0.00 | 0.444823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250724E+10 | 0.00 |
April | 0.327498E+11 | 0.497975E+10 | 0.113034E+11 | 0.00 | 0.347533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238229E+10 | 0.00 |
May | 0.336092E+11 | 0.306140E+10 | 0.117471E+11 | 0.00 | 0.269516E+10 | 0.00 | 0.00 | 1013881.93 | 0.00 | 0.00 | 0.00 | 0.245732E+10 | 0.00 |
June | 0.329813E+11 | 0.157122E+10 | 0.117048E+11 | 0.00 | 0.267650E+10 | 0.00 | 0.00 | 0.433792E+09 | 0.00 | 0.00 | 0.00 | 0.236187E+10 | 0.00 |
July | 0.325569E+11 | 0.225843E+10 | 0.113456E+11 | 0.00 | 0.263548E+10 | 0.00 | 0.00 | 0.101351E+10 | 0.00 | 0.00 | 0.00 | 0.233218E+10 | 0.00 |
August | 0.346911E+11 | 0.420964E+10 | 0.121485E+11 | 0.00 | 0.280055E+10 | 0.00 | 0.00 | 0.539865E+09 | 0.00 | 0.00 | 0.00 | 0.237914E+10 | 0.00 |
September | 0.330697E+11 | 0.629871E+10 | 0.113034E+11 | 0.00 | 0.265617E+10 | 0.00 | 0.00 | 2433335.75 | 0.00 | 0.00 | 0.00 | 0.226747E+10 | 0.00 |
October | 0.339883E+11 | 0.889922E+10 | 0.113456E+11 | 0.00 | 0.375669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233634E+10 | 0.00 |
November | 0.331363E+11 | 0.109791E+11 | 0.109019E+11 | 0.00 | 0.410854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228796E+10 | 0.00 |
December | 0.345433E+11 | 0.132199E+11 | 0.113456E+11 | 0.00 | 0.439666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241274E+10 | 0.00 |
Annual Sum or Average | 0.402560E+12 | 0.842454E+11 | 0.137056E+12 | 0.421711E+11 | 0.00 | 0.199062E+10 | 0.283657E+11 | ||||||
Minimum of Months | 0.312993E+11 | 0.157122E+10 | 0.104160E+11 | 0.00 | 0.263548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221122E+10 | 0.00 |
Maximum of Months | 0.354174E+11 | 0.132199E+11 | 0.121485E+11 | 0.00 | 0.446686E+10 | 0.00 | 0.00 | 0.101351E+10 | 0.00 | 0.00 | 0.00 | 0.250724E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.375081E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.305771E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.271435E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.112550E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.442586E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 89029405.55 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2049084.90 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 94190927.61 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.949235E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.153003E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.285606E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.369612E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188716E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 2049084.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.375081E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30629.63 | 02-JAN-09:09 | 6311.20 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 2930.73 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30629.63 | 01-FEB-09:09 | 6311.20 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 2930.73 | 01-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30518.79 | 03-MAR-09:09 | 6311.20 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 2930.73 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29805.77 | 03-APR-08:09 | 6311.20 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 2930.73 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29805.77 | 06-MAY-08:09 | 6311.20 | 01-MAY-21:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 2572.24 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29694.93 | 07-JUN-08:09 | 6311.20 | 01-JUN-22:49 | 10054.01 | 01-JUN-07:10 | 0.00 | 2572.24 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29805.77 | 29-JUL-08:09 | 6311.20 | 11-JUL-22:00 | 10054.01 | 01-JUL-07:10 | 0.00 | 2572.24 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30463.37 | 30-AUG-08:09 | 6311.20 | 01-AUG-21:00 | 10054.01 | 01-AUG-07:10 | 0.00 | 2572.24 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30518.79 | 21-SEP-08:09 | 6311.20 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 2930.73 | 28-SEP-06:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30629.63 | 19-OCT-08:09 | 6311.20 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 2930.73 | 02-OCT-06:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30629.63 | 01-NOV-08:09 | 6311.20 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 2930.73 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30629.63 | 01-DEC-09:09 | 6311.20 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 2930.73 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29694.93 | 6311.20 | 10054.01 | 0.00 | 2572.24 | 0.00 | 0.00 | |||||
Maximum of Months | 30629.63 | 6311.20 | 10054.01 | 0.00 | 2930.73 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3130.15 | 11-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3129.63 | 08-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3129.62 | 28-MAR-11:20 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3129.55 | 20-APR-11:00 | 0.00 |
May | 190.30 | 13-MAY-15:50 | 0.00 | 0.00 | 0.00 | 3129.63 | 06-MAY-11:00 | 0.00 |
June | 2897.78 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3032.91 | 02-JUN-11:20 | 0.00 |
July | 4453.01 | 29-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2865.80 | 06-JUL-11:20 | 0.00 |
August | 2244.54 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2753.45 | 04-AUG-11:50 | 0.00 |
September | 314.54 | 02-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2743.64 | 30-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2840.24 | 28-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2998.22 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3128.98 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2743.64 | 0.00 | ||
Maximum of Months | 4453.01 | 0.00 | 0.00 | 0.00 | 3130.15 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52616.28 | 09-JAN-15:20 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51654.34 | 03-FEB-09:09 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48181.04 | 16-MAR-07:10 | 27203.97 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45314.88 | 07-APR-14:50 | 29639.51 | 10054.01 | 0.00 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45010.11 | 09-MAY-12:20 | 29694.93 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46252.04 | 30-JUN-14:50 | 28324.31 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 2876.88 | 0.00 |
July | 47794.33 | 29-JUL-14:39 | 28981.91 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 3896.42 | 0.00 |
August | 46011.96 | 11-AUG-14:20 | 29639.51 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 1497.65 | 0.00 |
September | 45182.32 | 30-SEP-14:50 | 30297.11 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51636.47 | 31-OCT-08:09 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52469.02 | 30-NOV-15:39 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52616.19 | 29-DEC-15:50 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 45010.11 | 27203.97 | 10054.01 | 0.00 | 0.00 | 2572.24 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52616.28 | 30629.63 | 10054.01 | 6311.20 | 0.00 | 2930.73 | 0.00 | 0.00 | 3896.42 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 304155.05 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 294932.07 | 24-FEB-08:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 247343.94 | 02-MAR-04:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 211523.07 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 28711.08 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8014.47 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 958.13 | 05-JUL-06:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7533.70 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 75543.39 | 30-SEP-05:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 199412.75 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 227015.82 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 250367.84 | 15-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 958.13 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 304155.05 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 16.16 | 12.17 | 19.19 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.83 | 15.68 | 8.83 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25.33 | 16.57 | 10.00 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13.00 | 18.33 | 9.83 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.00 | 20.20 | 6.00 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.50 | 0.83 | 24.48 |
August | 0.17 | 20.54 | 0.17 | 20.54 | 6.33 | 24.52 | 0.50 | 24.53 |
September | 4.33 | 20.20 | 4.33 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10.67 | 18.79 | 8.67 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.17 | 17.96 | 8.67 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.67 | 17.67 | 8.83 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.33 | 16.91 | 77.50 | 19.33 | 20.50 | 24.51 | 1.33 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.83 | 20.54 | 12.17 | 20.54 | 10.83 | 24.52 | 0.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.50 | 14.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104.00 | 14.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 105.83 | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64.50 | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.00 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6.00 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76.17 | 14.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112.17 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115.17 | 14.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 704.33 | 14.27 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.50 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.00 | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 9.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.33 | 7.97 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.00 | 9.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.01 | 300.00 | 21.01 | 300.00 | 21.01 |
February | 276.00 | 21.02 | 276.00 | 21.02 | 276.00 | 21.02 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
May | 312.00 | 21.47 | 252.83 | 21.20 | 252.83 | 21.20 |
June | 292.00 | 23.41 | 14.17 | 21.19 | 14.17 | 21.19 |
July | 144.17 | 23.69 | 15.00 | 23.90 | 0.00 | 0.00 |
August | 243.00 | 23.38 | 15.50 | 22.00 | 10.67 | 21.14 |
September | 300.00 | 21.41 | 224.17 | 21.11 | 224.17 | 21.11 |
October | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
November | 288.00 | 21.04 | 288.00 | 21.04 | 288.00 | 21.04 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3379.17 | 21.60 | 2609.67 | 21.08 | 2589.83 | 21.06 |
Minimum of Months | 144.17 | 21.01 | 14.17 | 21.01 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.69 | 324.00 | 23.90 | 324.00 | 21.20 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 4371513.06 | 1013881.93 | 2.17 | 4371513.06 | 0.00 | 0.00 | 0.14 | 13-MAY-15:50 | 0.00 | 01-MAY-00:10 | 823.79 | 13-MAY-15:50 | 823.79 | 13-MAY-15:50 | 0.00 | 13-MAY-15:20 | 190.30 | 13-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 0.181084E+10 | 0.401641E+09 | 218.39 | 0.177046E+10 | 40371289.39 | 0.00 | 0.99 | 16-JUN-17:25 | 0.00 | 01-JUN-00:10 | 9093.06 | 21-JUN-17:15 | 9093.06 | 21-JUN-17:15 | 669.47 | 30-JUN-12:00 | 1948.84 | 21-JUN-17:15 | 0.00 | 01-JUN-00:10 |
July | 0.365610E+10 | 0.797232E+09 | 302.23 | 0.349651E+10 | 0.159594E+09 | 0.00 | 1.00 | 24-JUL-00:02 | 0.00 | 01-JUL-00:10 | 13974.19 | 24-JUL-00:02 | 13305.28 | 24-JUL-00:02 | 1147.18 | 25-JUL-18:20 | 2943.64 | 24-JUL-00:02 | 0.00 | 01-JUL-00:10 |
August | 0.236855E+10 | 0.518467E+09 | 247.94 | 0.228712E+10 | 81432206.34 | 0.00 | 0.99 | 05-AUG-20:40 | 0.00 | 01-AUG-00:10 | 11084.95 | 07-AUG-00:03 | 11084.95 | 07-AUG-00:03 | 647.60 | 03-AUG-12:30 | 2311.46 | 07-AUG-00:03 | 0.00 | 01-AUG-00:10 |
September | 10536832.31 | 2433335.75 | 4.83 | 10536832.31 | 0.00 | 0.00 | 0.22 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 | 1377.67 | 02-SEP-16:00 | 1377.67 | 02-SEP-16:00 | 0.00 | 02-SEP-15:20 | 314.54 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.785039E+10 | 0.172079E+10 | 775.57 | 0.756900E+10 | 0.281398E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.365610E+10 | 0.797232E+09 | 302.23 | 0.349651E+10 | 0.159594E+09 | 0.00 | 1.00 | 0.00 | 13974.19 | 13305.28 | 1147.18 | 2943.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.133280E+09 | 32150877.87 | 22.83 | 0.129415E+09 | 3864397.38 | 0.00 | 0.47 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7010.14 | 30-JUN-15:00 | 7010.14 | 30-JUN-15:00 | 669.79 | 30-JUN-12:10 | 1696.94 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.923022E+09 | 0.216281E+09 | 76.14 | 0.916220E+09 | 6801799.92 | 0.00 | 1.00 | 23-JUL-12:41 | 0.00 | 01-JUL-00:10 | 29636.38 | 23-JUL-12:41 | 29255.53 | 23-JUL-15:11 | 1041.27 | 23-JUL-12:49 | 6563.62 | 23-JUL-15:11 | 0.00 | 01-JUL-00:10 |
August | 89856461.91 | 21398222.85 | 27.67 | 87245376.18 | 2611085.73 | 0.00 | 0.31 | 11-AUG-16:00 | 0.00 | 01-AUG-00:10 | 4289.59 | 11-AUG-16:00 | 4289.59 | 11-AUG-16:00 | 170.28 | 02-AUG-14:00 | 1026.34 | 11-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.114616E+10 | 0.269830E+09 | 126.64 | 0.113288E+10 | 13277283.03 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.923022E+09 | 0.216281E+09 | 76.14 | 0.916220E+09 | 6801799.92 | 0.00 | 1.00 | 0.00 | 29636.38 | 29255.53 | 1041.27 | 6563.62 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 364.75 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.19 | 313.22 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 40.99 | 225.06 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 200.10 | 114.25 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 216.16 | 49.34 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 244.22 | 32.53 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 198.90 | 40.99 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 151.16 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 70.67 | 97.83 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 9.51 | 194.71 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.48 | 351.98 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 387.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 94.91 | 185.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 32.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 244.22 | 387.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 364.75 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.19 | 313.22 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 40.99 | 225.06 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 200.10 | 114.25 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 216.16 | 49.34 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 244.22 | 32.53 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 198.90 | 40.99 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 151.16 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 70.67 | 97.83 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 9.51 | 194.71 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.48 | 351.98 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 387.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 94.91 | 185.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 32.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 244.22 | 387.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 214.53 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 192.76 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 0.82 | 145.02 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.88 | 14.59 | 71.33 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.63 | 50.79 | 24.88 | 0.00 | 0.00 | 744.00 |
June | 99.37 | 21.81 | 77.56 | 78.52 | 13.86 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.98 | 19.82 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 28.98 | 34.13 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.42 | 60.48 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.51 | 119.68 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 211.28 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 226.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.58 | 110.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 13.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.37 | 21.81 | 77.56 | 78.52 | 226.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 214.53 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 192.76 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 0.82 | 145.02 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.87 | 14.59 | 71.33 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.62 | 50.78 | 24.88 | 0.00 | 0.00 | 744.00 |
June | 99.36 | 21.81 | 77.56 | 78.51 | 13.86 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.98 | 19.82 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 28.98 | 34.13 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.42 | 60.48 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.51 | 119.68 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 211.28 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 226.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.58 | 110.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 13.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.36 | 21.81 | 77.56 | 78.51 | 226.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 211.27 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.01 | 182.23 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 25.93 | 119.50 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 97.15 | 60.15 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 140.64 | 30.08 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.38 | 22.42 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.53 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 92.14 | 40.51 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 43.08 | 50.49 | 0.83 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.61 | 91.61 | 10.67 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 206.76 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 225.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.51 | 105.50 | 11.50 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 22.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.38 | 225.56 | 10.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.976938E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 5298362.90 | 0.757749E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.109775E+09 | 0.602807E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.518651E+09 | 0.296148E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.578966E+09 | 0.132165E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.633013E+09 | 84313559.78 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.532742E+09 | 0.109798E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.404866E+09 | 0.164497E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.183180E+09 | 0.253578E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 25460932.71 | 0.521523E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1245963.17 | 0.912342E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.103890E+10 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.299320E+10 | 0.585076E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 84313559.78 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.633013E+09 | 0.103890E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.976938E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 5298362.90 | 0.757749E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.109775E+09 | 0.602807E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.518651E+09 | 0.296148E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.578966E+09 | 0.132165E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.633013E+09 | 84313559.78 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.532742E+09 | 0.109798E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.404866E+09 | 0.164497E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.183180E+09 | 0.253578E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 25460932.71 | 0.521523E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1245963.17 | 0.912342E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.103890E+10 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.299320E+10 | 0.585076E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 84313559.78 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.633013E+09 | 0.103890E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242543.39 | 0.00 | 6242543.39 | 0.00 | 0.574596E+09 |
February | 24924571.43 | 0.00 | 24924571.43 | 0.00 | 0.466330E+09 |
March | 74024404.27 | 24119.60 | 74000284.67 | 2184415.40 | 0.388412E+09 |
April | 0.130317E+09 | 3632441.26 | 0.126684E+09 | 37812168.50 | 0.184891E+09 |
May | 0.206426E+09 | 33332414.96 | 0.173094E+09 | 0.136028E+09 | 66643312.17 |
June | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.203513E+09 | 35920349.43 |
July | 0.224614E+09 | 36957267.76 | 0.187657E+09 | 0.171360E+09 | 53088824.50 |
August | 0.144295E+09 | 7793310.77 | 0.136502E+09 | 77617744.13 | 91412880.45 |
September | 77681748.17 | 222120.81 | 77459627.36 | 19235835.08 | 0.156765E+09 |
October | 38847535.24 | 0.00 | 38847535.24 | 1375301.03 | 0.320550E+09 |
November | 11666868.70 | 0.00 | 11666868.70 | 0.00 | 0.547642E+09 |
December | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 0.607643E+09 |
Annual Sum or Average | 0.119849E+10 | 0.138486E+09 | 0.106001E+10 | 0.649127E+09 | 0.349389E+10 |
Minimum of Months | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 35920349.43 |
Maximum of Months | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.203513E+09 | 0.607643E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242317.75 | 0.00 | 6242317.75 | 0.00 | 0.574595E+09 |
February | 24923727.57 | 0.00 | 24923727.57 | 0.00 | 0.466329E+09 |
March | 74022047.32 | 24118.47 | 73997928.85 | 2184106.13 | 0.388413E+09 |
April | 0.130313E+09 | 3632271.00 | 0.126681E+09 | 37809919.39 | 0.184892E+09 |
May | 0.206419E+09 | 33330852.62 | 0.173088E+09 | 0.136022E+09 | 66643203.12 |
June | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.203503E+09 | 35920298.92 |
July | 0.224606E+09 | 36955535.52 | 0.187651E+09 | 0.171352E+09 | 53088868.46 |
August | 0.144290E+09 | 7792945.49 | 0.136497E+09 | 77613517.69 | 91412885.66 |
September | 77679181.44 | 222110.40 | 77457071.05 | 19234378.74 | 0.156765E+09 |
October | 38846204.45 | 0.00 | 38846204.45 | 1375097.15 | 0.320550E+09 |
November | 11666447.01 | 0.00 | 11666447.01 | 0.00 | 0.547641E+09 |
December | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 0.607642E+09 |
Annual Sum or Average | 0.119845E+10 | 0.138480E+09 | 0.105997E+10 | 0.649094E+09 | 0.349389E+10 |
Minimum of Months | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 35920298.92 |
Maximum of Months | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.203503E+09 | 0.607642E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.565870E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 22877.36 | 0.440842E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 69454514.54 | 0.320067E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251812E+09 | 0.155901E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.376703E+09 | 80555433.28 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.387201E+09 | 58111394.51 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346932E+09 | 80743840.46 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.246775E+09 | 0.108494E+09 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.111670E+09 | 0.130861E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23053391.78 | 0.245378E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.535914E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.604153E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181362E+10 | 0.332689E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 58111394.51 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.387201E+09 | 0.604153E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1158.55 | 15.71 | 1.92 | 13.79 | 0.00 | 0.00 |
February | 0.58 | 1008.17 | 86.36 | 23.03 | 63.33 | 0.00 | 0.00 |
March | 66.96 | 723.52 | 252.93 | 85.62 | 167.32 | 0.00 | 0.00 |
April | 419.72 | 361.52 | 566.87 | 244.57 | 322.30 | 0.00 | 0.00 |
May | 520.12 | 134.68 | 606.89 | 231.11 | 375.78 | 0.00 | 0.00 |
June | 630.79 | 78.10 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
July | 514.20 | 110.07 | 582.60 | 184.39 | 398.21 | 0.00 | 0.00 |
August | 354.50 | 185.31 | 449.81 | 151.17 | 298.64 | 0.00 | 0.00 |
September | 151.22 | 311.66 | 266.08 | 86.22 | 179.85 | 0.00 | 0.00 |
October | 15.54 | 624.29 | 109.73 | 24.17 | 85.56 | 0.00 | 0.00 |
November | 0.13 | 1125.70 | 41.36 | 11.72 | 29.64 | 0.00 | 0.00 |
December | 0.00 | 1229.50 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Annual Sum or Average | 223.79 | 585.43 | 307.35 | 108.56 | 198.80 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 78.10 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Maximum of Months | 630.79 | 1229.50 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2112.72 | 23.59 | 2.30 | 21.30 | 0.00 | 0.00 |
February | 0.09 | 1822.27 | 120.21 | 30.60 | 89.61 | 0.00 | 0.00 |
March | 259.31 | 1194.99 | 420.16 | 180.75 | 239.40 | 0.00 | 0.00 |
April | 971.50 | 601.47 | 840.42 | 454.58 | 385.84 | 0.00 | 0.00 |
May | 1406.45 | 300.76 | 1093.06 | 622.00 | 471.06 | 0.00 | 0.00 |
June | 1493.83 | 224.19 | 1184.87 | 590.38 | 594.50 | 0.00 | 0.00 |
July | 1295.30 | 301.46 | 1063.25 | 513.90 | 549.35 | 0.00 | 0.00 |
August | 921.35 | 405.07 | 801.63 | 389.36 | 412.26 | 0.00 | 0.00 |
September | 430.83 | 504.87 | 434.84 | 173.49 | 261.35 | 0.00 | 0.00 |
October | 86.07 | 916.14 | 179.20 | 44.69 | 134.51 | 0.00 | 0.00 |
November | 0.00 | 2067.57 | 44.79 | 3.97 | 40.83 | 0.00 | 0.00 |
December | 0.00 | 2255.65 | 6.58 | 0.14 | 6.44 | 0.00 | 0.00 |
Annual Sum or Average | 575.10 | 1054.95 | 519.79 | 251.72 | 268.08 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 224.19 | 6.58 | 0.14 | 6.44 | 0.00 | 0.00 |
Maximum of Months | 1493.83 | 2255.65 | 1184.87 | 622.00 | 594.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.310307E+10 | 42075936.09 | 5145799.60 | 36930136.48 | 0.00 | 0.00 |
February | 1399935.07 | 0.243896E+10 | 0.208925E+09 | 55726085.70 | 0.153199E+09 | 0.00 | 0.00 |
March | 0.179356E+09 | 0.193788E+10 | 0.677453E+09 | 0.229314E+09 | 0.448139E+09 | 0.00 | 0.00 |
April | 0.108792E+10 | 0.937072E+09 | 0.146932E+10 | 0.633919E+09 | 0.835404E+09 | 0.00 | 0.00 |
May | 0.139308E+10 | 0.360719E+09 | 0.162550E+10 | 0.619003E+09 | 0.100650E+10 | 0.00 | 0.00 |
June | 0.163501E+10 | 0.202436E+09 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
July | 0.137723E+10 | 0.294812E+09 | 0.156045E+10 | 0.493873E+09 | 0.106657E+10 | 0.00 | 0.00 |
August | 0.949490E+09 | 0.496346E+09 | 0.120476E+10 | 0.404893E+09 | 0.799872E+09 | 0.00 | 0.00 |
September | 0.391955E+09 | 0.807813E+09 | 0.689671E+09 | 0.223494E+09 | 0.466177E+09 | 0.00 | 0.00 |
October | 41617436.55 | 0.167209E+10 | 0.293905E+09 | 64748071.85 | 0.229157E+09 | 0.00 | 0.00 |
November | 343629.92 | 0.291782E+10 | 0.107199E+09 | 30375285.84 | 76823217.62 | 0.00 | 0.00 |
December | 0.00 | 0.329309E+10 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.705741E+10 | 0.184621E+11 | 0.969273E+10 | 0.342348E+10 | 0.626925E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.202436E+09 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Maximum of Months | 0.163501E+10 | 0.329309E+10 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.565870E+10 | 63193561.21 | 6154055.20 | 57039506.01 | 0.00 | 0.00 |
February | 228773.56 | 0.440842E+10 | 0.290803E+09 | 74023328.71 | 0.216779E+09 | 0.00 | 0.00 |
March | 0.694540E+09 | 0.320067E+10 | 0.112535E+10 | 0.484131E+09 | 0.641216E+09 | 0.00 | 0.00 |
April | 0.251812E+10 | 0.155901E+10 | 0.217837E+10 | 0.117828E+10 | 0.100009E+10 | 0.00 | 0.00 |
May | 0.376703E+10 | 0.805551E+09 | 0.292765E+10 | 0.166597E+10 | 0.126168E+10 | 0.00 | 0.00 |
June | 0.387201E+10 | 0.581113E+09 | 0.307119E+10 | 0.153025E+10 | 0.154094E+10 | 0.00 | 0.00 |
July | 0.346932E+10 | 0.807436E+09 | 0.284782E+10 | 0.137643E+10 | 0.147139E+10 | 0.00 | 0.00 |
August | 0.246775E+10 | 0.108494E+10 | 0.214707E+10 | 0.104286E+10 | 0.110421E+10 | 0.00 | 0.00 |
September | 0.111670E+10 | 0.130861E+10 | 0.112710E+10 | 0.449674E+09 | 0.677431E+09 | 0.00 | 0.00 |
October | 0.230534E+09 | 0.245378E+10 | 0.479959E+09 | 0.119693E+09 | 0.360266E+09 | 0.00 | 0.00 |
November | 0.00 | 0.535914E+10 | 0.116097E+09 | 10277781.52 | 0.105819E+09 | 0.00 | 0.00 |
December | 0.00 | 0.604153E+10 | 17618689.43 | 363629.79 | 17255059.65 | 0.00 | 0.00 |
Annual Sum or Average | 0.181362E+11 | 0.332689E+11 | 0.163922E+11 | 0.793812E+10 | 0.845411E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.581113E+09 | 17618689.43 | 363629.79 | 17255059.65 | 0.00 | 0.00 |
Maximum of Months | 0.387201E+10 | 0.604153E+10 | 0.307119E+10 | 0.166597E+10 | 0.154094E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.5 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.6 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.24 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.87 | 6.41 | 3.45 | 5.65 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.84 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.69 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.46 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.84 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.6 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.5 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.58 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.01 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.76 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.27 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.32 | 11.70 | 4.67 | 18.87 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.74 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.88 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 7.99 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.5 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.0 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.5 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.32 | 11.70 | 6.20 | 18.87 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.1 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.2 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.0 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.8 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.6 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.23 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.64 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.01 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.94 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.32 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.33 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.28 | 141.00 | 225.33 |
August | 16.13 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.81 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 7.99 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.5 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.0 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.5 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.33 | 29.07 | 14.40 | 8.80 | 19.28 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.6 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.77 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.74 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.40 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.29 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.0 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.4 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.0 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114174E+10 | -.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88120201.5 | 59.00 | 0.00 | 0.00 |
February | 0.104749E+10 | -967994595.8 | 0.00 | 0.00 | 672.00 | 0.00 | -79495342.3 | 59.00 | 0.00 | 0.00 |
March | 0.121915E+10 | -.113151E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87640763.6 | 59.00 | 0.00 | 0.00 |
April | 0.113515E+10 | -.105104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84108687.0 | 59.00 | 0.00 | 0.00 |
May | 0.116877E+10 | -.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -83735937.6 | 58.99 | 0.00 | 0.00 |
June | 0.111561E+10 | -.104140E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -74209042.0 | 58.99 | 0.00 | 0.00 |
July | 0.104342E+10 | -968509677.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74913251.2 | 59.00 | 0.00 | 0.00 |
August | 0.109072E+10 | -.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -75744031.8 | 58.99 | 0.00 | 0.00 |
September | 0.102048E+10 | -939957827.2 | 0.00 | 0.00 | 720.00 | 0.00 | -80526041.3 | 58.99 | 0.00 | 0.00 |
October | 0.104812E+10 | -960934283.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87183847.2 | 58.99 | 0.00 | 0.00 |
November | 0.104117E+10 | -955931544.9 | 0.00 | 0.00 | 720.00 | 0.00 | -85240783.3 | 59.00 | 0.00 | 0.00 |
December | 0.112432E+10 | -.103625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88069992.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.131961E+11 | -.122072E+11 | 8760.00 | -988987920.8 | 59.00 | |||||
Minimum of Months | 0.102048E+10 | -.113151E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88120201.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121915E+10 | -939957827.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74209042.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 1.00 | 0.96 | 21-JAN-12:20 | 27.71 | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.98 | 0.92 | 21-FEB-11:20 | 64.42 | 6.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.96 | 0.88 | 05-MAR-10:00 | 120.59 | 9.28 | 0.00 | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.94 | 0.88 | 01-APR-09:00 | 149.08 | 10.15 | 0.00 | 91.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.94 | 0.88 | 01-MAY-07:30 | 168.43 | 10.44 | 0.00 | 179.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.93 | 0.88 | 01-JUN-07:00 | 516.17 | 10.73 | 0.00 | 280.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.93 | 0.88 | 01-JUL-08:50 | 194.17 | 10.91 | 0.00 | 242.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.94 | 0.88 | 01-AUG-07:19 | 167.43 | 10.58 | 0.00 | 154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.95 | 0.88 | 01-SEP-08:20 | 125.28 | 9.49 | 0.00 | 41.33 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.97 | 0.92 | 01-OCT-08:50 | 89.14 | 7.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.99 | 0.92 | 06-NOV-13:20 | 38.14 | 2.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 8.75 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.95 | 190.83 | 9.29 | 0.00 | 1043.00 | ||||||
Minimum of Months | 71.17 | 0.93 | 0.88 | 8.75 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 516.17 | 10.91 | 0.00 | 280.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.96 | 0.85 | 28-JAN-14:30 | 95.54 | 13.75 | 12.67 | 0.33 | 146.92 | 12.95 | 0.00 | 2.00 |
February | 205.83 | 0.87 | 0.78 | 12-FEB-14:09 | 358.13 | 21.01 | 60.17 | 38.83 | 397.43 | 20.02 | 28.83 | 91.17 |
March | 329.50 | 0.83 | 0.78 | 01-MAR-13:30 | 798.39 | 21.57 | 93.83 | 170.00 | 1033.05 | 23.49 | 141.67 | 253.17 |
April | 421.83 | 0.82 | 0.78 | 01-APR-09:50 | 1059.00 | 19.66 | 100.50 | 257.00 | 2221.14 | 24.88 | 207.67 | 350.50 |
May | 545.00 | 0.82 | 0.78 | 01-MAY-06:40 | 483.74 | 16.45 | 48.00 | 354.83 | 2184.27 | 23.56 | 230.50 | 432.83 |
June | 583.50 | 0.82 | 0.78 | 01-JUN-05:30 | 539.23 | 16.20 | 46.83 | 418.67 | 2348.35 | 23.09 | 263.00 | 470.67 |
July | 562.83 | 0.82 | 0.78 | 01-JUL-04:49 | 506.00 | 16.35 | 53.00 | 372.17 | 1995.04 | 23.15 | 242.50 | 460.50 |
August | 467.17 | 0.82 | 0.78 | 01-AUG-06:19 | 484.36 | 17.09 | 49.67 | 280.00 | 1730.20 | 23.86 | 210.33 | 375.33 |
September | 356.33 | 0.83 | 0.78 | 01-SEP-07:40 | 698.24 | 19.63 | 73.00 | 166.83 | 1074.30 | 23.80 | 145.50 | 275.00 |
October | 265.50 | 0.86 | 0.78 | 01-OCT-09:50 | 367.33 | 19.82 | 62.00 | 43.50 | 469.10 | 20.42 | 39.50 | 154.83 |
November | 135.83 | 0.93 | 0.78 | 05-NOV-14:20 | 139.97 | 15.58 | 17.50 | 3.33 | 218.07 | 14.77 | 0.00 | 21.83 |
December | 71.17 | 1.00 | 0.96 | 04-DEC-10:00 | 31.32 | 6.05 | 0.00 | 0.00 | 49.31 | 7.06 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.84 | 555.32 | 17.67 | 617.17 | 2105.50 | 1580.85 | 22.37 | 1509.50 | 2887.83 | ||
Minimum of Months | 71.17 | 0.82 | 0.78 | 31.32 | 6.05 | 0.00 | 0.00 | 49.31 | 7.06 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 0.96 | 1059.00 | 21.57 | 100.50 | 418.67 | 2348.35 | 24.88 | 263.00 | 470.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158815E+11 | 25878.53 | 01-JAN-07:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137089E+11 | 25878.53 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134614E+11 | 25878.53 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.673014E+10 | 25878.53 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175422E+10 | 25878.53 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 59973524.69 | 25878.53 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1318546.64 | 759.57 | 05-JUL-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62312750.06 | 16987.68 | 31-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226598E+10 | 25878.53 | 05-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.750636E+10 | 25878.53 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130817E+11 | 25878.53 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154025E+11 | 25878.53 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.899164E+11 | |||||||
Minimum of Months | 1318546.64 | 759.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158815E+11 | 25878.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.622522E+11 | 74754.02 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505278E+11 | 74754.02 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450887E+11 | 74754.02 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197695E+11 | 74754.02 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123381E+10 | 63464.06 | 04-MAY-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231236E+10 | 64415.82 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.258181E+11 | 74754.02 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488725E+11 | 74754.02 | 01-NOV-01:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.612097E+11 | 74754.02 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317085E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.622522E+11 | 74754.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212785E+12 | 157751.51 | 28-JAN-06:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172408E+12 | 157751.51 | 23-FEB-18:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150615E+12 | 142548.66 | 02-MAR-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595220E+11 | 125212.20 | 02-APR-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216090E+10 | 33996.45 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839432E+11 | 109747.94 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158329E+12 | 121359.49 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209821E+12 | 139571.35 | 22-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104958E+13 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212785E+12 | 157751.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4371513.06 | 4371513.06 | 823.79 | 13-MAY-15:50 | 823.79 | 0.00 |
June | 0.00 | 0.00 | 0.181084E+10 | 0.177046E+10 | 9093.06 | 21-JUN-17:15 | 9093.06 | 0.00 |
July | 0.00 | 0.00 | 0.365610E+10 | 0.349651E+10 | 13974.19 | 24-JUL-00:02 | 13305.28 | 0.00 |
August | 0.00 | 0.00 | 0.236855E+10 | 0.228712E+10 | 11084.95 | 07-AUG-00:03 | 11084.95 | 0.00 |
September | 0.00 | 0.00 | 10536832.31 | 10536832.31 | 1377.67 | 02-SEP-16:00 | 1377.67 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.785039E+10 | 0.756900E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365610E+10 | 0.349651E+10 | 13974.19 | 13305.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133280E+09 | 0.129415E+09 | 7010.14 | 30-JUN-15:00 | 7010.14 | 0.00 |
July | 0.00 | 0.00 | 0.923022E+09 | 0.916220E+09 | 29636.38 | 23-JUL-12:41 | 28661.36 | 0.00 |
August | 0.00 | 0.00 | 89856461.91 | 87245376.18 | 4289.59 | 11-AUG-16:00 | 4289.59 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.114616E+10 | 0.113288E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.923022E+09 | 0.916220E+09 | 29636.38 | 28661.36 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.960168E+09 | 0.08 | 358.49 | 01-JAN-00:02 | 0.08 |
February | 0.867248E+09 | 0.08 | 358.49 | 01-FEB-00:02 | 0.08 |
March | 0.920483E+09 | 0.07 | 358.49 | 01-MAR-00:02 | 0.08 |
April | 0.515072E+09 | 0.04 | 358.49 | 01-APR-00:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 51837000.28 | 0.00 | 358.49 | 27-SEP-23:40 | 0.08 |
October | 0.766155E+09 | 0.06 | 358.49 | 01-OCT-00:03 | 0.08 |
November | 0.929194E+09 | 0.08 | 358.49 | 01-NOV-00:10 | 0.08 |
December | 0.960168E+09 | 0.08 | 358.49 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.597032E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.960168E+09 | 0.08 | 358.49 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102586E+10 | 0.71 | 893.16 | 02-JAN-10:00 | 0.93 |
February | 0.945565E+09 | 0.72 | 893.16 | 02-FEB-16:20 | 0.93 |
March | 0.106793E+10 | 0.66 | 893.16 | 02-MAR-11:50 | 0.93 |
April | 0.936127E+09 | 0.47 | 893.16 | 06-APR-08:40 | 0.93 |
May | 0.936614E+09 | 0.38 | 893.16 | 01-MAY-10:10 | 0.92 |
June | 0.947711E+09 | 0.39 | 893.16 | 03-JUN-12:50 | 0.92 |
July | 0.971243E+09 | 0.41 | 893.16 | 01-JUL-11:30 | 0.91 |
August | 0.100527E+10 | 0.41 | 893.16 | 01-AUG-19:55 | 0.92 |
September | 0.898533E+09 | 0.38 | 893.16 | 01-SEP-06:10 | 0.92 |
October | 0.924693E+09 | 0.42 | 893.16 | 02-OCT-07:00 | 0.92 |
November | 0.939430E+09 | 0.62 | 893.16 | 01-NOV-08:50 | 0.93 |
December | 0.100389E+10 | 0.69 | 893.16 | 02-DEC-07:10 | 0.93 |
Annual Sum or Average | 0.116029E+11 | 0.52 | |||
Minimum of Months | 0.898533E+09 | 0.38 | 893.16 | 0.91 | |
Maximum of Months | 0.106793E+10 | 0.72 | 893.16 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.248083E+10 | 0.79 | 1679.08 | 07-JAN-08:00 | 0.89 |
February | 0.224207E+10 | 0.79 | 1679.08 | 04-FEB-10:00 | 0.90 |
March | 0.245982E+10 | 0.79 | 1679.08 | 01-MAR-14:00 | 0.90 |
April | 0.202413E+10 | 0.68 | 1679.08 | 01-APR-08:30 | 0.90 |
May | 0.175855E+10 | 0.40 | 1679.08 | 03-MAY-06:40 | 0.89 |
June | 0.172879E+10 | 0.35 | 1679.08 | 22-JUN-15:00 | 0.89 |
July | 0.166424E+10 | 0.33 | 1679.08 | 10-JUL-13:50 | 0.89 |
August | 0.179528E+10 | 0.35 | 1679.08 | 01-AUG-13:20 | 0.88 |
September | 0.170580E+10 | 0.41 | 1679.08 | 23-SEP-07:50 | 0.89 |
October | 0.206585E+10 | 0.72 | 1679.08 | 03-OCT-06:40 | 0.89 |
November | 0.223992E+10 | 0.79 | 1679.08 | 13-NOV-07:40 | 0.90 |
December | 0.243260E+10 | 0.80 | 1679.08 | 01-DEC-08:00 | 0.90 |
Annual Sum or Average | 0.245979E+11 | 0.60 | |||
Minimum of Months | 0.166424E+10 | 0.33 | 1679.08 | 0.88 | |
Maximum of Months | 0.248083E+10 | 0.80 | 1679.08 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.76 | 0.02 |
February | 2.78 | 0.00 |
March | 3.30 | 0.00 |
April | 1.76 | 0.01 |
May | 0.35 | 0.20 |
June | 0.00 | 0.00 |
July | 0.17 | 0.00 |
August | 0.17 | 1.60 |
September | 0.53 | 0.04 |
October | 2.21 | 0.02 |
November | 3.86 | 0.00 |
December | 4.21 | 0.00 |
Annual Sum or Average | 22.10 | 0.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.21 | 1.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.08 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102586E+10 | 0.220746E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.945565E+09 | 0.191988E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106793E+10 | 0.190127E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.936127E+09 | 0.973962E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.937628E+09 | 0.258696E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134935E+10 | 89029405.55 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176848E+10 | 2049084.90 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.152374E+10 | 94190927.61 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.900966E+09 | 0.334915E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.924693E+09 | 0.108000E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.939430E+09 | 0.182939E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100389E+10 | 0.213890E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133237E+11 | 0.126630E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.900966E+09 | 2049084.90 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.176848E+10 | 0.220746E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.248083E+10 | 0.870254E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.224207E+10 | 0.710625E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.245982E+10 | 0.641537E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202413E+10 | 0.284081E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.175855E+10 | 0.183890E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176094E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188052E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.181668E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.170580E+10 | 0.344207E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.206585E+10 | 0.372741E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.223992E+10 | 0.694004E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.243260E+10 | 0.859465E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.248677E+11 | 0.448552E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170580E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248083E+10 | 0.870254E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102586E+10 | 0.00 | 0.158815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945565E+09 | 0.00 | 0.137089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106793E+10 | 0.00 | 0.134614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936127E+09 | 0.00 | 0.673014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.936614E+09 | 4371513.06 | 0.175422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.947711E+09 | 0.181084E+10 | 59973524.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.971243E+09 | 0.365610E+10 | 1318546.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100527E+10 | 0.236855E+10 | 62312750.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.898533E+09 | 10536832.31 | 0.226598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924693E+09 | 0.00 | 0.750636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.939430E+09 | 0.00 | 0.130817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100389E+10 | 0.00 | 0.154025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116029E+11 | 0.785039E+10 | 0.899164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.898533E+09 | 0.00 | 1318546.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106793E+10 | 0.365610E+10 | 0.158815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.248083E+10 | 0.00 | 0.622522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224207E+10 | 0.00 | 0.505278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245982E+10 | 0.00 | 0.450887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202413E+10 | 0.00 | 0.197695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175855E+10 | 0.00 | 0.123381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172879E+10 | 0.133280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166424E+10 | 0.923022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179528E+10 | 89856461.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170580E+10 | 0.00 | 0.231236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206585E+10 | 0.00 | 0.258181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223992E+10 | 0.00 | 0.488725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243260E+10 | 0.00 | 0.612097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245979E+11 | 0.114616E+10 | 0.317085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248083E+10 | 0.923022E+09 | 0.622522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.102586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.936614E+09 | 0.00 | 0.00 | 0.00 | 1013881.93 | 0.00 | 0.258696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.947711E+09 | 0.00 | 0.00 | 0.00 | 0.401641E+09 | 0.00 | 89029405.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.971243E+09 | 0.00 | 0.00 | 0.00 | 0.797232E+09 | 0.00 | 2049084.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100527E+10 | 0.00 | 0.00 | 0.00 | 0.518467E+09 | 0.00 | 94190927.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.898533E+09 | 0.00 | 0.00 | 0.00 | 2433335.75 | 0.00 | 0.334915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.939430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116029E+11 | 0.00 | 0.00 | 0.00 | 0.172079E+10 | 0.00 | 0.126630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.898533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2049084.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106793E+10 | 0.00 | 0.00 | 0.00 | 0.797232E+09 | 0.00 | 0.220746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.248083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172879E+10 | 0.00 | 0.00 | 0.00 | 32150877.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166424E+10 | 0.00 | 0.00 | 0.00 | 0.216281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179528E+10 | 0.00 | 0.00 | 0.00 | 21398222.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245979E+11 | 0.00 | 0.00 | 0.00 | 0.269830E+09 | 0.00 | 0.448552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.166424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248083E+10 | 0.00 | 0.00 | 0.00 | 0.216281E+09 | 0.00 | 0.870254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439886E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353940E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357609E+10 | 0.00 | 0.00 | 0.13 |
April | 25505162.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200291E+10 | 0.00 | 0.00 | 0.13 |
May | 0.449637E+09 | 0.00 | 0.00 | 2597.73 | 0.00 | 0.619749E+09 | 3636300.67 | 0.00 | 0.13 |
June | 0.237241E+09 | 5102087.08 | 0.00 | 2118124.78 | 0.00 | 0.00 | 0.567396E+09 | 0.00 | 0.13 |
July | 66484658.44 | 18993168.66 | 0.00 | 3547411.05 | 0.00 | 0.00 | 0.478537E+09 | 0.00 | 0.13 |
August | 0.309686E+09 | 722980.16 | 0.00 | 3006221.57 | 0.00 | 6683088.42 | 0.721736E+09 | 0.00 | 0.13 |
September | 0.634140E+09 | 0.00 | 0.00 | 19286.34 | 0.00 | 0.978767E+09 | 21903690.52 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269332E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416520E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463586E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.172269E+10 | 24818235.90 | 0.00 | 8693641.47 | 0.00 | 0.266168E+11 | 0.179321E+10 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.634140E+09 | 18993168.66 | 0.00 | 3547411.05 | 0.00 | 0.463586E+10 | 0.721736E+09 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152735E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119150E+11 | 0.00 | 0.00 | 0.18 |
March | 0.846748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107591E+11 | 0.00 | 0.00 | 0.19 |
April | 0.296507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281243E+10 | 0.00 | 0.00 | 0.18 |
May | 0.289604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33543264.13 | 0.00 | 0.00 | 0.19 |
June | 0.295285E+10 | 443354.15 | 0.00 | 368400.86 | 0.00 | 0.00 | 0.315806E+09 | 0.00 | 0.21 |
July | 0.211680E+10 | 24585561.11 | 0.00 | 2393269.94 | 6428826.43 | 0.00 | 0.142087E+10 | 0.00 | 0.26 |
August | 0.364563E+10 | 0.00 | 0.00 | 879807.41 | 0.00 | 0.00 | 0.763841E+09 | 0.00 | 0.22 |
September | 0.454454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236778E+09 | 0.00 | 0.00 | 0.18 |
October | 0.241410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585426E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144206E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162532E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.223818E+11 | 25028915.27 | 0.00 | 3641478.21 | 6428826.43 | 0.775584E+11 | 0.250052E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.454454E+10 | 24585561.11 | 0.00 | 2393269.94 | 6428826.43 | 0.162532E+11 | 0.142087E+10 | 0.00 | 0.26 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |