Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1196.14 | 247.39 | 247.39 |
Net Site Energy | 1196.14 | 247.39 | 247.39 |
Total Source Energy | 3000.38 | 620.54 | 620.54 |
Net Source Energy | 3000.38 | 620.54 | 620.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 378.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.99 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 817.94 | 378.20 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 378.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 3.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 481.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 43.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.99 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.20 | 78.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 169.17 | 78.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.20 | 78.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 169.17 | 78.22 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 817.936 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 817.936 | 100.00 |
Total On-Site and Utility Electric Sources | 817.936 | 100.00 |
Total Electricity End Uses | 817.936 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 60.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2094.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.66 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7639 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.6111 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.6111 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.7166 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 10-JAN-06:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 145218.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7800.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1783.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 58598.07 | 145218.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 145218.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7800.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1783.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 409.97 | 0.00 | 0.00 | 0.00 |
Cooling | 10.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2590.40 | 409.97 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.79 | 0.00 | 0.00 | 0.00 |
Cooling | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.75 | 84.79 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.79 | 0.00 | 0.00 | 0.00 |
Cooling | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.75 | 84.79 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.998228 |
ZONE2 FINE STORAGE DIRECT AIR | 1.96 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.89 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.89 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 77762.11 |
PSZ-OFFICE HEATING COIL | 26296.58 |
PSZ-FINE STORAGE HEATING COIL | 65709.32 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 77762.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.998228 | 0.998228 | 0.998228 | 0.998228 | 0.998228 | 0.998228 | 1.00 | 1.00 | 0.998228 |
PSZ-FINE STORAGE | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.00 | 1.96 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.998228 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 1.96 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.998228 | 0.998228 | 0.998228 | 0.998228 | 16524.21 | 26296.58 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.96 | 36046.47 | 65709.32 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.998230 | 0.499115 | 0.998230 | 16524.25 | 16524.21 | 8262.10 | 16524.21 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.96 | 0.979030 | 1.96 | 33986.17 | 36046.47 | 18023.24 | 36046.47 | 0.761594 | 0.761590 | 0.761590 | 0.761590 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.998228 | 1138.09 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.96 | 2143.11 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.764 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.838 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.611 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.170 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2549.751 | 10.764 | 509.950 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2549.751 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11998.830 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11998.830 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27597.308 | 8.611 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27597.308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.977 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.7680 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2514 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.203 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.72529422E-12 | -0.16659653E-15 | 0.22267608E-14 | 0.12345853E-15 |
13 | 3 | -0.36555712E-03 | 0.52642428E-06 | -0.52844486E-04 | 0.13919492E-12 |
14 | 2 | 1.6938492 | 0.11754276E-01 | 1.1057222 | -0.70081836E-04 |
15 | 1 | -7.1898979 | 0.30855302 | -16.875743 | 0.32460476 |
16 | 0 | 6.0151594 | 0.19843725 | 16.288819 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9772727 | 3.9772727 | 3.9772727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22267608E-14 | -0.16659653E-15 | 0.72529422E-12 | 0.12345853E-15 |
85 | 3 | -0.52844486E-04 | 0.52642428E-06 | -0.36555712E-03 | 0.13919492E-12 |
86 | 2 | 1.1057222 | 0.11754276E-01 | 1.6938492 | -0.70081836E-04 |
87 | 1 | -16.875743 | 0.30855302 | -7.1898979 | 0.32460476 |
88 | 0 | 16.288819 | 0.19843725 | 6.0151594 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 28 | 1 | VerySmooth | 3.241 | 0.487 | 0.409 | 0.491 |
2 | SKYLIGHT_U_1.02_SHGC_0.49 | 29 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 30 | 1 | VerySmooth | 5.779 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10004.52708 | 12005.43250 | 0.83186 | 0.99823 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.38408E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9515.31408 | 11418.37690 | 0.26989 | 0.32387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 25175.15835 | 30210.19002 | 1.63172 | 1.95806 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.38408E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 27757.69388 | 33309.23266 | 0.66339 | 0.79606 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40000 | 8.38408E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 64801.75659 | 77762.10791 | 1.57694 | 1.89233 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14397.30 | 0.99823 | 0.99823 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10998.90 | 0.32387 | 0.32387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34331.29 | 1.95806 | 1.95806 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 31707.77 | 0.79606 | 0.79606 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99823 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95806 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.89233 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.89233 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 77762.11009 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 77762.10791 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99823 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99823 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99823 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99823 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99823 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.99823 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95806 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95806 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95806 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95806 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.95806 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.95806 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.99823 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.95806 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99823 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99823 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99823 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99823 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99823 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99823 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49912 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99823 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16524.25095 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16524.21000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8262.10500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16524.21000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16524.21000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26296.57566 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99823 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1138.08921 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26296.57566 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.95806 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.95806 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.95806 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.95806 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.95806 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.95806 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97903 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.95806 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33986.17119 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 36046.47000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18023.23500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 36046.47000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76159 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76159 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76159 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76159 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36046.47000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65709.32477 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.95806 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2143.11079 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65709.32477 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15749.6 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 34526.5 | 14.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1692101020 | 0.1684152881 | Pass | Pass | 0.7115305207 | 7.2365992774 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4440493004 | 0.4112650546 | Pass | Pass | 0.3397162854 | 0.6950919741 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 9.7801554584E-005 | 2.4887230396E-004 | Pass | Pass | 7.5864378826E-002 | 9.2730720568E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.689 | 0.768 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.19 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.487 | 0.491 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.241 | 0.487 | 0.491 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.487 | 0.491 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.241 | 0.487 | 0.491 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.550 | 0.551 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.32 | 4.922 | 0.529 | 0.531 | ||||||||||||
North Total or Average | 6.51 | 3.241 | 0.487 | 0.491 | ||||||||||||
Non-North Total or Average | 45.81 | 5.161 | 0.535 | 0.536 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.689 | 8.239 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.493 | 3.977 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.7639 | 236.88 | 2549.75 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.99 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.6111 | 1393.41 | 11998.83 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 136.66 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.6111 | 3204.84 | 27597.31 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 314.31 |
Interior Lighting Total | 8.7166 | 4835.13 | 42145.89 | 481.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.24 | AstronomicalClock | - | 83.54 | 83.54 | 123.21 | |
Exterior Lighting Total | 7857.24 | 123.21 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16524.21 | 13197.23 | 3326.98 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36046.47 | 27452.63 | 8593.84 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15749.6 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 34526.5 | 14.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 77762.11 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26296.58 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65709.32 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.89 | 175.82 | 92.91 | 1.00 | 3.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.00 | 1138.09 | 1140.11 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.96 | 2143.11 | 1094.51 | 1.00 | 1.29 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10004.53 | 12005.43 | 50.68 | 0.832 | 0.998 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00813 | 25.13 | 0.00838 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 25175.16 | 30210.19 | 21.68 | 1.632 | 1.958 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00803 | 26.40 | 0.00838 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00382 | 26.40 | 0.00838 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9515.31 | 11418.38 | 48.20 | 0.270 | 0.324 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00787 | -4.30 | 0.00266 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 27757.69 | 33309.23 | 23.90 | 0.663 | 0.796 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00687 | -4.30 | 0.00266 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 64801.76 | 77762.11 | 24.26 | 1.577 | 1.892 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00771 | -4.30 | 0.00266 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.00 | 1.00 | 0.32 | 0.32 | 0.9982 | 0.9982 | 0.9982 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.96 | 1.96 | 0.80 | 0.80 | 1.9581 | 1.9581 | 1.9581 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 77762.110 | 77762.110 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 77762.11 | 77762.11 | 1.892329 | 3.85 | 3.85 | 0.00553722 | 43.33 | 26.97 | 0.01600000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 9.99 | 0.00771113 | 99.9996 | 77762.11 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16524.210 | 0.000 | 0.998230 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16524.21 | 16059.28 | 0.998230 | 24.05 | 15.98 | 0.00815668 | 12.00 | 11.16 | 0.00800000 | 25.13 | 0.00838408 | 16.56 | 12.0549 | 23.90 | 0.00812551 | 43.5628 | 10004.53 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26296.576 | 26296.576 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26296.58 | 26296.58 | 0.998228 | 11.63 | 8.78 | 0.00593581 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 12.0549 | 21.10 | 0.00787403 | 50.0652 | 9515.31 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 36046.470 | 0.000 | 1.958060 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 36046.47 | 35541.44 | 1.958060 | 26.65 | 16.84 | 0.00809152 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00838408 | 17.00 | 18.0754 | 26.70 | 0.00802697 | 36.4377 | 25175.16 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65709.325 | 65709.325 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 65709.32 | 65709.32 | 1.958063 | 6.73 | 5.30 | 0.00499622 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 18.0754 | 15.56 | 0.00686827 | 61.9364 | 27757.69 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 77762.110 | 77762.110 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1914 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.892329 | 2.25446834 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 77762.11 | 77762.11 | 1.0000 | 2.25446834 | 1.892329 | 3.85 | 3.85 | 0.00553722 | 17751.5 | 43.33 | 26.97 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77762.11 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 9.99 | 0.00771113 | 9.99 | 0.00771113 | 99.9996 | 77762.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16524.210 | 0.000 | 0.998230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0029 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 16524.21 | 16059.28 | 1.0000 | 1.18926328 | 0.998230 | 24.05 | 15.98 | 0.00815668 | 44927.9 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16524.21 | 25.13 | 0.00838408 | 16.56 | 0.12033533 | 12.0549 | 23.90 | 0.00812551 | 23.90 | 0.00812551 | 43.5628 | 10004.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26296.576 | 26296.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.998228 | 1.18926048 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26296.58 | 26296.58 | 1.0000 | 1.18926048 | 0.998228 | 11.63 | 8.78 | 0.00593581 | 26661.5 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26296.58 | -4.30 | 0.00265759 | -4.30 | 0.12033533 | 12.0549 | 21.05 | 0.00787403 | 21.10 | 0.00787403 | 50.0652 | 9515.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36046.470 | 0.000 | 1.958060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8817 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 36046.47 | 35541.44 | 1.0000 | 2.33277788 | 1.958060 | 26.65 | 16.84 | 0.00809152 | 47411.9 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36046.47 | 26.40 | 0.00838408 | 17.00 | 0.35392745 | 18.0754 | 26.70 | 0.00802697 | 26.70 | 0.00802697 | 36.4377 | 25175.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65709.325 | 65709.325 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.958063 | 2.33278154 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 65709.32 | 65709.32 | 1.0000 | 2.33278154 | 1.958063 | 6.73 | 5.30 | 0.00499622 | 19319.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65709.32 | -4.30 | 0.00265759 | -4.30 | 0.35392745 | 18.0754 | 15.56 | 0.00686827 | 15.56 | 0.00686827 | 61.9364 | 27757.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 1.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2166.67 | 3341.50 | 2094.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2166.67 | 3341.50 | 2094.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 63.50 | 11.50 | 60.50 | 0.00 |
ZONE2 FINE STORAGE | 358.83 | 0.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 408.50 | 11.67 | 60.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.405 | 0.366 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
Electricity:Building | 621.24 | 4992.32 | 01-JAN-00:10 | 45732.65 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.94 | 1032.71 | 01-JAN-00:10 | 3875.81 | 02-JAN-08:10 |
InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.99 | 458.96 | 01-JAN-00:10 | 1963.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 481.96 | 4418.57 | 01-JAN-00:10 | 35620.03 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 136.66 | 1199.88 | 01-JAN-00:10 | 10199.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 421.65 | 2759.73 | 01-JAN-00:10 | 31657.83 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 314.31 | 2759.73 | 01-JAN-00:10 | 23457.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.99 | 483.00 | 26-APR-05:10 | 2497.52 | 11-FEB-12:50 |
WaterSystems:Electricity | 26.99 | 483.00 | 26-APR-05:10 | 2497.52 | 11-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.99 | 483.00 | 26-APR-05:10 | 2497.52 | 11-FEB-12:50 |
Fans:Electricity | 43.24 | 0.00 | 06-JAN-18:40 | 3457.02 | 02-JAN-08:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
ElectricityNet:Plant | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 817.94 | 5475.32 | 15-JAN-10:50 | 58598.07 | 22-JUL-15:00 |
Electricity:HVAC | 46.48 | 0.00 | 06-JAN-18:40 | 11156.57 | 22-JUL-15:10 |
General:Fans:Electricity | 43.24 | 0.00 | 06-JAN-18:40 | 3457.02 | 02-JAN-08:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3.25 | 0.00 | 01-JAN-00:10 | 7875.37 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.24 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 378.20 | 3250.00 | 06-JAN-18:40 | 145218.14 | 10-JAN-06:10 |
Gas:HVAC | 378.20 | 3250.00 | 06-JAN-18:40 | 145218.14 | 10-JAN-06:10 |
Heating:Gas | 378.20 | 3250.00 | 06-JAN-18:40 | 145218.14 | 10-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 433.58 | 0.00 | 06-JAN-18:40 | 222908.42 | 10-JAN-06:10 |
EnergyTransfer:Building | 219.24 | 0.00 | 06-JAN-18:40 | 110794.09 | 10-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 38.66 | 0.00 | 01-JAN-00:10 | 18587.45 | 10-JAN-06:10 |
Heating:EnergyTransfer | 197.51 | 0.00 | 06-JAN-18:40 | 110794.09 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 29.63 | 0.00 | 01-JAN-00:10 | 18587.45 | 10-JAN-06:10 |
Cooling:EnergyTransfer | 21.73 | 0.00 | 01-JAN-00:10 | 22246.80 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 9.03 | 0.00 | 01-JAN-00:10 | 7426.12 | 21-JUL-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 99.68 | 0.00 | 01-JAN-00:40 | 37896.70 | 30-DEC-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 86.98 | 0.00 | 01-JAN-00:40 | 37896.70 | 30-DEC-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 12.70 | 0.00 | 01-JAN-00:10 | 16860.82 | 23-JUL-13:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.90 | 0.00 | 02-JAN-08:40 | 59987.12 | 10-JAN-06:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.90 | 0.00 | 02-JAN-08:40 | 59987.12 | 10-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 214.34 | 0.00 | 06-JAN-18:40 | 112114.33 | 10-JAN-06:10 |
HeatingCoils:EnergyTransfer | 203.40 | 0.00 | 06-JAN-18:40 | 112114.33 | 10-JAN-06:10 |
CoolingCoils:EnergyTransfer | 10.94 | 0.00 | 01-JAN-00:10 | 27257.84 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 29.633 | -9.027 | 0.000 | 0.000 | 3.995 | 30.994 | 31.946 | 10.834 | 0.000 | 0.025 | 0.000 | 0.000 | -10.193 | 0.000 | -22.518 | -65.689 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 86.977 | -12.703 | 0.000 | 0.000 | 0.000 | 136.656 | 0.000 | 0.000 | 0.000 | 0.019 | 0.000 | 0.000 | 0.000 | 0.000 | -82.664 | -128.284 |
ZONE3 BULK STORAGE | 80.899 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 314.310 | 107.336 | 27.795 | 0.000 | 0.190 | 0.000 | 0.000 | -18.582 | 0.000 | -294.051 | -217.896 |
Total Facility | 80.899 | 0.000 | 116.609 | -21.730 | 0.000 | 0.000 | 3.995 | 481.960 | 139.282 | 38.629 | 0.000 | 0.234 | 0.000 | 0.000 | -28.776 | 0.000 | -399.233 | -411.870 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 21-JUL-18:23 | 0.00 | 0.00 | 0.00 | -15313.05 | 0.00 | 0.00 | 0.00 | 458.96 | 573.75 | 2345.83 | 0.00 | 0.00 | 11972.80 | 0.00 | -0.00 | 0.00 | -38.28 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-11:31 | 0.00 | 0.00 | 0.00 | -36110.89 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37216.49 | 0.00 | -0.00 | 0.00 | -2305.48 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-17:12 | 0.00 | 0.00 | 0.00 | -44740.73 | 0.00 | 0.00 | 0.00 | 4418.57 | 2623.78 | 6336.27 | 0.00 | 224.23 | 32177.26 | 0.00 | 0.00 | 0.00 | -1039.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-NOV-06:01 | 0.00 | 0.00 | 25714.69 | 0.00 | 0.00 | 0.00 | 56.49 | 586.44 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -375.17 | 0.00 | -357.89 | -26198.31 |
ZONE2 FINE STORAGE | 30-DEC-00:02 | 0.00 | 0.00 | 68118.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8544.80 | -60773.84 |
ZONE3 BULK STORAGE | 10-JAN-06:00 | 59988.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1793.80 | 0.00 | -26818.39 | -36185.93 |
Total Facility | 10-JAN-06:01 | 58650.52 | 0.00 | 90577.43 | 0.00 | 0.00 | 0.00 | 57.56 | 4546.06 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2682.96 | 0.00 | -35404.28 | -118368.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9982 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.9982 | 0.1205 | 1.0000 | 0.1203 | 0.1205 | ||
PSZ-FINE STORAGE | 1.9581 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 1.9581 | 0.1808 | 1.0000 | 0.3539 | 0.1808 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9982 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.9982 | 1.0000 | 1.0000 | 0.1203 | 0.1205 | ||
PSZ-FINE STORAGE | 1.9581 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 1.9581 | 1.0000 | 1.0000 | 0.3539 | 0.1808 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9982 | 0.9982 | 0.9982 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.9581 | 1.9581 | 1.9581 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9982 | 0.9982 | 0.9982 | 0.9982 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 1.9581 | 1.9581 | 1.9581 | 1.9581 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9982 | 0.9982 | 0.9982 | 0.1203 | 0.3716 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.9581 | 1.9581 | 1.9581 | 0.3539 | 0.4446 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9982 | 0.9982 | 0.9982 | 0.9982 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 1.9581 | 1.9581 | 1.9581 | 1.9581 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 60.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 60.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 378.20 | 145218.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 3.25 | 7875.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 481.96 | 35620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.21 | 7857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 43.24 | 3457.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.99 | 2497.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 817.94 |
Natural Gas | 0.00 | 378.20 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1196.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.68 |
Space Heating | 0.00 |
Space Cooling | 0.67 |
Fans (All) | 8.94 |
Service Water Heating | 5.58 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 169.17 |
Subtotal | 169.17 |
Natural Gas [MJ/m2] | |
Space Heating | 78.22 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 78.22 |
Subtotal | 78.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 40.29 |
Space Heating | 31.62 |
Space Cooling | 0.27 |
Fans (All) | 3.61 |
Service Water Heating | 2.26 |
Receptacle Equipment | 11.64 |
Miscellaneous | 10.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708657E+11 |
February | 0.000 | 0.551552E+11 |
March | 0.000 | 0.340878E+11 |
April | 0.000 | 0.134248E+11 |
May | 0.000 | 0.119162E+11 |
June | 0.000 | 0.880958E+10 |
July | 0.000 | 0.882620E+10 |
August | 0.000 | 0.876433E+10 |
September | 0.000 | 0.896016E+10 |
October | 0.000 | 0.170576E+11 |
November | 0.000 | 0.420074E+11 |
December | 0.000 | 0.983289E+11 |
Annual Sum or Average | 0.378204E+12 | |
Minimum of Months | 0.000 | 0.876433E+10 |
Maximum of Months | 0.000 | 0.983289E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3245105.86 | 1001.08 | 21-JAN-16:40 | 4.70 | 4.08 | 0.194992E+09 | 236.59 | 10-JAN-11:09 | -1.8 | -1.8 |
February | 4986471.87 | 942.81 | 18-FEB-16:50 | 5.17 | 3.38 | 0.179372E+09 | 236.59 | 18-FEB-10:09 | 5.00 | 4.09 |
March | 6900541.60 | 671.69 | 11-MAR-14:30 | 7.50 | 4.94 | 0.210741E+09 | 249.86 | 25-MAR-13:39 | 12.67 | 9.93 |
April | 0.331785E+09 | 6887.16 | 29-APR-17:20 | 20.00 | 12.60 | 0.208814E+09 | 301.59 | 28-APR-15:09 | 20.08 | 13.46 |
May | 0.545908E+09 | 5614.13 | 23-MAY-17:25 | 18.00 | 13.13 | 0.223434E+09 | 301.60 | 25-MAY-15:00 | 18.00 | 13.89 |
June | 0.157685E+10 | 14229.98 | 13-JUN-17:43 | 24.42 | 16.66 | 0.248091E+09 | 301.60 | 13-JUN-15:09 | 26.08 | 17.79 |
July | 0.266164E+10 | 15313.03 | 21-JUL-18:23 | 22.00 | 15.39 | 0.245014E+09 | 301.65 | 06-JUL-12:09 | 19.17 | 13.28 |
August | 0.261555E+10 | 13038.94 | 14-AUG-17:10 | 27.00 | 14.26 | 0.265631E+09 | 301.61 | 19-AUG-15:00 | 20.00 | 15.65 |
September | 0.117665E+10 | 7846.03 | 13-SEP-17:15 | 21.33 | 15.42 | 0.238356E+09 | 301.60 | 13-SEP-15:00 | 23.00 | 16.21 |
October | 90881827.81 | 1620.71 | 07-OCT-15:50 | 18.17 | 9.72 | 0.202824E+09 | 301.58 | 05-OCT-15:00 | 16.00 | 9.11 |
November | 12324423.31 | 603.11 | 04-NOV-14:50 | 9.00 | 6.58 | 0.187355E+09 | 249.11 | 10-NOV-15:39 | 11.33 | 8.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 | 3.53 | 0.194975E+09 | 236.59 | 04-DEC-16:19 | 8.00 | 5.92 |
Annual Sum or Average | 0.902673E+10 | 0.259960E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.38 | 0.179372E+09 | 236.59 | -1.8 | -1.8 | ||
Maximum of Months | 0.266164E+10 | 15313.03 | 27.00 | 16.66 | 0.265631E+09 | 301.65 | 26.08 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.608214E+09 | 3023.79 | 21-JAN-11:00 | 5.00 | 4.51 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.981521E+09 | 3109.34 | 23-FEB-15:30 | 4.50 | 4.26 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.115030E+10 | 2800.24 | 08-MAR-13:00 | 4.00 | 2.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.129930E+10 | 8802.54 | 22-APR-06:10 | 7.17 | 5.78 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.142321E+10 | 6704.45 | 04-MAY-06:10 | 7.33 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.151949E+10 | 8041.27 | 13-JUN-15:00 | 26.00 | 17.81 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.210755E+10 | 36113.48 | 23-JUL-11:31 | 21.00 | 15.98 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.116740E+10 | 9029.66 | 01-AUG-06:10 | 13.50 | 12.18 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.745240E+09 | 8285.76 | 08-SEP-06:10 | 8.33 | 7.70 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.656922E+09 | 5580.88 | 13-OCT-06:10 | 10.00 | 10.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.690587E+09 | 2483.48 | 16-NOV-09:10 | 4.83 | 4.15 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.353492E+09 | 2607.35 | 06-DEC-10:10 | 4.50 | 3.47 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.127032E+11 | 0.00 | ||||||||
Minimum of Months | 0.353492E+09 | 2483.48 | 4.00 | 2.71 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.210755E+10 | 36113.48 | 26.00 | 17.81 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 | 5.79 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 | 4.28 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540679E+10 | 25322.47 | 17-JAN-06:01 | 6.07 |
February | 0.438900E+10 | 25323.03 | 22-FEB-06:01 | 6.83 |
March | 0.447093E+10 | 25509.35 | 18-MAR-05:01 | 9.00 |
April | 0.172528E+10 | 25127.38 | 10-APR-05:01 | 6.17 |
May | 0.123190E+10 | 25421.65 | 19-MAY-05:01 | 9.00 |
June | 0.256764E+09 | 24722.43 | 08-JUN-05:01 | 6.17 |
July | 90116886.72 | 24672.13 | 05-JUL-05:01 | 7.33 |
August | 49702277.75 | 3754.70 | 30-AUG-06:10 | 9.50 |
September | 0.344348E+09 | 24666.46 | 07-SEP-05:02 | 8.83 |
October | 0.213339E+10 | 25681.87 | 20-OCT-05:01 | 11.00 |
November | 0.394195E+10 | 25714.57 | 24-NOV-06:01 | 10.17 |
December | 0.559326E+10 | 25205.58 | 05-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.296334E+11 | |||
Minimum of Months | 49702277.75 | 3754.70 | 6.00 | |
Maximum of Months | 0.559326E+10 | 25714.57 | 11.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174734E+11 | 68038.62 | 10-JAN-05:22 | -4.0 |
February | 0.152530E+11 | 67175.05 | 18-FEB-00:53 | -2.0 |
March | 0.102208E+11 | 66585.42 | 04-MAR-06:01 | 3.00 |
April | 0.155116E+10 | 66494.21 | 15-APR-05:01 | 5.17 |
May | 0.969496E+09 | 30970.24 | 05-MAY-04:55 | 6.00 |
June | 0.170309E+09 | 2221.81 | 28-JUN-07:00 | 11.00 |
July | 0.177162E+09 | 2293.70 | 11-JUL-06:50 | 12.83 |
August | 0.178020E+09 | 2295.69 | 19-AUG-07:00 | 12.00 |
September | 0.233588E+09 | 2209.79 | 27-SEP-06:50 | 9.67 |
October | 0.344721E+10 | 66610.21 | 30-OCT-05:05 | 7.00 |
November | 0.130446E+11 | 67169.28 | 28-NOV-22:03 | 0.67 |
December | 0.242582E+11 | 68118.60 | 30-DEC-00:02 | -2.8 |
Annual Sum or Average | 0.869770E+11 | |||
Minimum of Months | 0.170309E+09 | 2209.79 | -4.0 | |
Maximum of Months | 0.242582E+11 | 68118.60 | 12.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215853E+11 | 59988.51 | 10-JAN-06:00 | -4.0 |
February | 0.143967E+11 | 43201.65 | 17-FEB-03:52 | -2.0 |
March | 0.213877E+10 | 21783.36 | 04-MAR-05:53 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.651745E+10 | 39016.61 | 29-NOV-03:54 | -1.0 |
December | 0.362610E+11 | 59428.22 | 30-DEC-01:00 | -2.0 |
Annual Sum or Average | 0.808992E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.362610E+11 | 59988.51 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.259236E+10 | 1963.31 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.236435E+10 | 1963.31 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.270141E+10 | 1963.31 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.255271E+10 | 1963.31 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.264689E+10 | 1963.31 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.260723E+10 | 1963.31 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.259236E+10 | 1963.31 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.270141E+10 | 1963.31 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.255271E+10 | 1963.31 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.259236E+10 | 1963.31 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.249819E+10 | 1963.31 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.259236E+10 | 1963.31 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.309943E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.236435E+10 | 1963.31 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.270141E+10 | 1963.31 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.113670E+11 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.104037E+11 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.120192E+11 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.112633E+11 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.116931E+11 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.115894E+11 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.113670E+11 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.120192E+11 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.112633E+11 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.113670E+11 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.109372E+11 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.113670E+11 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136656E+12 | ||||
Minimum of Months | 0.104037E+11 | 10199.01 | 0.00 | 0.00 | |
Maximum of Months | 0.120192E+11 | 10199.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261440E+11 | 23457.71 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.239285E+11 | 23457.71 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.276442E+11 | 23457.71 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.259056E+11 | 23457.71 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.268941E+11 | 23457.71 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.266557E+11 | 23457.71 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.261440E+11 | 23457.71 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.276442E+11 | 23457.71 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.259056E+11 | 23457.71 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.261440E+11 | 23457.71 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.251555E+11 | 23457.71 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.261440E+11 | 23457.71 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.239285E+11 | 23457.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.276442E+11 | 23457.71 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234928E+10 |
February | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213006E+10 |
March | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223629E+10 |
April | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162356E+10 |
May | 0.565842E+09 | 0.264689E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3432.41 | 0.209750E+10 |
June | 0.565842E+09 | 0.260723E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6912860.32 | 0.162921E+10 |
July | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13117352.18 | 0.134017E+10 |
August | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5110842.23 | 0.125167E+10 |
September | 0.544079E+09 | 0.255271E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132301E+10 |
October | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172304E+10 |
November | 0.522316E+09 | 0.249819E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220214E+10 |
December | 0.544079E+09 | 0.259236E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261191E+10 |
Annual Sum or Average | 0.659424E+10 | 0.309943E+11 | 0.319458E+11 | 25144487.14 | 0.225178E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.236435E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125167E+10 |
Maximum of Months | 0.587605E+09 | 0.270141E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13117352.18 | 0.261191E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422246E+10 |
February | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586370E+10 |
March | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379084E+10 |
April | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427160E+10 |
May | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102702E+11 |
June | 0.00 | 0.115894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252019.26 | 0.920439E+10 |
July | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18002341.93 | 0.897611E+10 |
August | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675460.93 | 0.747540E+10 |
September | 0.00 | 0.112633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625508E+10 |
October | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514275E+10 |
November | 0.00 | 0.109372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695861E+10 |
December | 0.00 | 0.113670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102328E+11 |
Annual Sum or Average | 0.136656E+12 | 18929822.11 | 0.826640E+11 | ||||||
Minimum of Months | 0.00 | 0.104037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379084E+10 |
Maximum of Months | 0.00 | 0.120192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18002341.93 | 0.102702E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30395711.77 | 0.855584E+10 |
February | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113537E+11 |
March | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796723E+10 |
April | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9159934.05 | 0.127396E+11 |
May | 0.00 | 0.268941E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17598092.28 | 0.317394E+11 |
June | 0.00 | 0.266557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19232128.80 | 0.293619E+11 |
July | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9725425.63 | 0.295909E+11 |
August | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6904985.98 | 0.249841E+11 |
September | 0.00 | 0.259056E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310838.84 | 0.201155E+11 |
October | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138216E+11 |
November | 0.00 | 0.251555E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36645703.20 | 0.123762E+11 |
December | 0.00 | 0.261440E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13086130.30 | 0.180886E+11 |
Annual Sum or Average | 0.314310E+12 | 0.107336E+12 | 0.143059E+09 | 0.220695E+12 | |||||
Minimum of Months | 0.00 | 0.239285E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796723E+10 |
Maximum of Months | 0.00 | 0.276442E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36645703.20 | 0.317394E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1963.31 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10254.10 | 10-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1963.31 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9474.68 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1963.31 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 8076.75 | 08-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1963.31 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6707.34 | 20-APR-06:05 |
May | 659.25 | 01-MAY-07:10 | 1963.31 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 22-MAY-15:00 | 6660.19 | 01-MAY-16:03 |
June | 659.25 | 01-JUN-07:10 | 1963.31 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.03 | 13-JUN-17:00 | 5647.84 | 08-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1963.31 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 21-JUL-17:00 | 4587.68 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1963.31 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.98 | 14-AUG-17:00 | 4625.49 | 24-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1963.31 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5890.76 | 20-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1963.31 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7161.82 | 04-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1963.31 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 9138.76 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1963.31 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9343.48 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.68 | |||||
Maximum of Months | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 10254.10 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10199.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14734.97 | 10-JAN-18:00 |
February | 0.00 | 10199.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9306.04 | 01-FEB-16:10 |
March | 0.00 | 10199.01 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 14858.83 | 31-MAR-08:00 |
April | 0.00 | 10199.01 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 9137.11 | 24-APR-15:05 |
May | 0.00 | 10199.01 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 19288.88 | 01-MAY-15:03 |
June | 0.00 | 10199.01 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.73 | 13-JUN-17:00 | 12774.89 | 07-JUN-15:05 |
July | 0.00 | 10199.01 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.44 | 22-JUL-15:10 | 9792.39 | 30-JUL-19:00 |
August | 0.00 | 10199.01 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.56 | 14-AUG-18:00 | 11907.45 | 22-AUG-16:00 |
September | 0.00 | 10199.01 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 12303.04 | 29-SEP-15:05 |
October | 0.00 | 10199.01 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8767.90 | 31-OCT-15:05 |
November | 0.00 | 10199.01 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13759.73 | 15-NOV-07:07 |
December | 0.00 | 10199.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21636.46 | 02-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8767.90 | |||
Maximum of Months | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.44 | 21636.46 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23457.71 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4381.82 | 29-JAN-06:00 | 31515.91 | 10-JAN-16:00 |
February | 0.00 | 23457.71 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 16454.10 | 01-FEB-16:00 |
March | 0.00 | 23457.71 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 27746.97 | 31-MAR-08:00 |
April | 0.00 | 23457.71 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.34 | 30-APR-19:00 | 23697.04 | 24-APR-12:10 |
May | 0.00 | 23457.71 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976.32 | 22-MAY-15:00 | 52176.01 | 01-MAY-13:00 |
June | 0.00 | 23457.71 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2068.06 | 12-JUN-18:00 | 35310.68 | 07-JUN-15:00 |
July | 0.00 | 23457.71 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.94 | 22-JUL-19:00 | 31002.48 | 01-JUL-12:10 |
August | 0.00 | 23457.71 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.96 | 14-AUG-18:00 | 34313.75 | 22-AUG-16:00 |
September | 0.00 | 23457.71 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.74 | 24-SEP-16:00 | 27265.95 | 29-SEP-15:05 |
October | 0.00 | 23457.71 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22350.93 | 01-OCT-24:00 |
November | 0.00 | 23457.71 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6443.10 | 24-NOV-12:00 | 18968.82 | 28-NOV-08:70 |
December | 0.00 | 23457.71 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5921.69 | 23-DEC-11:00 | 26117.65 | 28-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16454.10 | ||||
Maximum of Months | 0.00 | 23457.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6443.10 | 52176.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1001.08 | 21-JAN-16:40 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.97 |
February | 942.81 | 18-FEB-16:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.68 |
March | 671.69 | 11-MAR-14:30 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6887.16 | 29-APR-17:20 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5614.13 | 23-MAY-17:25 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.25 |
June | 14229.98 | 13-JUN-17:43 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
July | 15313.03 | 21-JUL-18:23 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 |
August | 13038.94 | 14-AUG-17:10 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 212.69 | 0.00 |
September | 7846.03 | 13-SEP-17:15 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.73 |
October | 1620.71 | 07-OCT-15:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
November | 603.11 | 04-NOV-14:50 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.67 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1376.87 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 917.91 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15313.03 | 659.25 | 1963.31 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 212.69 | 530.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3023.79 | 21-JAN-11:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3109.34 | 23-FEB-15:30 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1594.01 |
March | 2800.24 | 08-MAR-13:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.95 |
April | 8802.54 | 22-APR-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6704.45 | 04-MAY-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.42 |
June | 8041.27 | 13-JUN-15:00 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.73 |
July | 36113.48 | 23-JUL-11:31 | 0.00 | 8399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.48 |
August | 9029.66 | 01-AUG-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.97 |
September | 8285.76 | 08-SEP-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.36 |
October | 5580.88 | 13-OCT-06:10 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2483.48 | 16-NOV-09:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2607.35 | 06-DEC-10:10 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2483.48 | 0.00 | 7199.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36113.48 | 0.00 | 10199.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 11038.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3955.70 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3089.90 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4445.17 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9822.57 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11817.42 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20265.88 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9466.22 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2759.73 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11129.10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15311.01 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5519.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5818.40 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8279.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3153.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 11038.92 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20265.88 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.714629E+11 | 54744.32 | 07-JAN-08:09 | 0.708657E+11 | 145218.14 | 10-JAN-06:10 |
February | 0.641877E+11 | 51004.43 | 11-FEB-15:39 | 0.551552E+11 | 102285.09 | 17-FEB-06:10 |
March | 0.718073E+11 | 50995.10 | 02-MAR-15:00 | 0.340878E+11 | 80055.83 | 04-MAR-06:10 |
April | 0.657709E+11 | 52060.43 | 29-APR-14:00 | 0.134248E+11 | 38601.24 | 01-APR-05:10 |
May | 0.669178E+11 | 52191.80 | 22-MAY-14:00 | 0.119162E+11 | 36429.36 | 06-MAY-05:10 |
June | 0.658572E+11 | 55906.93 | 13-JUN-14:00 | 0.880958E+10 | 16228.02 | 08-JUN-06:10 |
July | 0.658107E+11 | 58598.07 | 22-JUL-14:00 | 0.882620E+10 | 13148.60 | 05-JUL-05:10 |
August | 0.701365E+11 | 53988.52 | 14-AUG-14:39 | 0.876433E+10 | 8233.15 | 24-AUG-06:10 |
September | 0.668280E+11 | 52565.09 | 13-SEP-14:00 | 0.896016E+10 | 14823.23 | 21-SEP-06:10 |
October | 0.689369E+11 | 51167.47 | 07-OCT-14:30 | 0.170576E+11 | 38345.63 | 23-OCT-05:19 |
November | 0.681311E+11 | 54530.86 | 30-NOV-16:00 | 0.420074E+11 | 106732.60 | 28-NOV-06:10 |
December | 0.720890E+11 | 54743.69 | 29-DEC-08:09 | 0.983289E+11 | 124040.61 | 28-DEC-07:10 |
Annual Sum or Average | 0.817936E+12 | 0.378204E+12 | ||||
Minimum of Months | 0.641877E+11 | 50995.10 | 0.876433E+10 | 8233.15 | ||
Maximum of Months | 0.720890E+11 | 58598.07 | 0.983289E+11 | 145218.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.401034E+11 | 0.134689E+11 | 0.115358E+11 | 0.00 | 0.403630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231862E+10 | 0.00 |
February | 0.366966E+11 | 0.110834E+11 | 0.105871E+11 | 0.00 | 0.370809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211244E+10 | 0.00 |
March | 0.423649E+11 | 0.107864E+11 | 0.123357E+11 | 0.00 | 0.393932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238102E+10 | 0.00 |
April | 0.397216E+11 | 0.893840E+10 | 0.114862E+11 | 0.00 | 0.332299E+10 | 0.00 | 0.00 | 56073403.15 | 0.00 | 0.00 | 0.00 | 0.224568E+10 | 0.00 |
May | 0.412341E+11 | 0.792010E+10 | 0.119357E+11 | 0.00 | 0.342456E+10 | 0.00 | 0.00 | 0.102509E+09 | 0.00 | 0.00 | 0.00 | 0.230075E+10 | 0.00 |
June | 0.408524E+11 | 0.696309E+10 | 0.118862E+11 | 0.00 | 0.339263E+10 | 0.00 | 0.00 | 0.542357E+09 | 0.00 | 0.00 | 0.00 | 0.222062E+10 | 0.00 |
July | 0.401034E+11 | 0.750524E+10 | 0.115358E+11 | 0.00 | 0.329840E+10 | 0.00 | 0.00 | 0.114899E+10 | 0.00 | 0.00 | 0.00 | 0.221893E+10 | 0.00 |
August | 0.423649E+11 | 0.865082E+10 | 0.123357E+11 | 0.00 | 0.352582E+10 | 0.00 | 0.00 | 0.989028E+09 | 0.00 | 0.00 | 0.00 | 0.227023E+10 | 0.00 |
September | 0.397216E+11 | 0.978698E+10 | 0.114862E+11 | 0.00 | 0.325364E+10 | 0.00 | 0.00 | 0.404126E+09 | 0.00 | 0.00 | 0.00 | 0.217550E+10 | 0.00 |
October | 0.401034E+11 | 0.116539E+11 | 0.115358E+11 | 0.00 | 0.338709E+10 | 0.00 | 0.00 | 6044313.93 | 0.00 | 0.00 | 0.00 | 0.225081E+10 | 0.00 |
November | 0.385909E+11 | 0.126250E+11 | 0.110862E+11 | 0.00 | 0.363065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219831E+10 | 0.00 |
December | 0.401034E+11 | 0.138319E+11 | 0.115358E+11 | 0.00 | 0.431631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230169E+10 | 0.00 |
Annual Sum or Average | 0.481960E+12 | 0.123214E+12 | 0.139282E+12 | 0.432358E+11 | 0.00 | 0.324912E+10 | 0.269946E+11 | ||||||
Minimum of Months | 0.366966E+11 | 0.696309E+10 | 0.105871E+11 | 0.00 | 0.325364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211244E+10 | 0.00 |
Maximum of Months | 0.423649E+11 | 0.138319E+11 | 0.123357E+11 | 0.00 | 0.431631E+10 | 0.00 | 0.00 | 0.114899E+10 | 0.00 | 0.00 | 0.00 | 0.238102E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.708657E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.551552E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.340878E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.134248E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.119162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.880958E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.882620E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.876433E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.896016E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.170576E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.420074E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.983289E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378204E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.876433E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.983289E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35620.03 | 02-JAN-09:09 | 7857.24 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3457.02 | 02-JAN-07:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35620.03 | 01-FEB-09:09 | 7857.24 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3457.02 | 03-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35620.03 | 01-MAR-09:09 | 7857.24 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3457.02 | 06-MAR-07:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35620.03 | 01-APR-08:09 | 7857.24 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3281.20 | 01-APR-06:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35620.03 | 01-MAY-08:09 | 7857.24 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3281.20 | 05-MAY-07:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35620.03 | 01-JUN-08:09 | 7857.24 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3281.20 | 13-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35620.03 | 01-JUL-08:09 | 7857.24 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3281.20 | 10-JUL-10:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35620.03 | 01-AUG-08:09 | 7857.24 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3281.20 | 05-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35620.03 | 01-SEP-08:09 | 7857.24 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3281.20 | 13-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35620.03 | 02-OCT-08:09 | 7857.24 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3281.20 | 12-OCT-07:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35620.03 | 01-NOV-08:09 | 7857.24 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3457.02 | 17-NOV-07:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35620.03 | 01-DEC-09:09 | 7857.24 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3457.02 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3281.20 | 0.00 | 0.00 | |||||
Maximum of Months | 35620.03 | 7857.24 | 10112.62 | 0.00 | 3457.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2491.03 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2497.52 | 11-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2489.08 | 02-MAR-12:50 | 0.00 |
April | 1315.00 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2434.77 | 01-APR-11:00 | 0.00 |
May | 1434.37 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2332.89 | 02-MAY-11:20 | 0.00 |
June | 5437.56 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2208.17 | 01-JUN-11:00 | 0.00 |
July | 7875.37 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2086.56 | 03-JUL-11:09 | 0.00 |
August | 3888.17 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2023.94 | 30-AUG-11:50 | 0.00 |
September | 1845.92 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2088.82 | 30-SEP-11:00 | 0.00 |
October | 591.39 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 2203.12 | 28-OCT-11:30 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2333.43 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2432.84 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2023.94 | 0.00 | ||
Maximum of Months | 7875.37 | 0.00 | 0.00 | 0.00 | 2497.52 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54744.32 | 07-JAN-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3457.02 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51004.43 | 11-FEB-15:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50995.10 | 02-MAR-15:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52060.43 | 29-APR-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 1240.08 | 0.00 |
May | 52191.80 | 22-MAY-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 1378.95 | 0.00 |
June | 55906.93 | 13-JUN-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 5100.92 | 0.00 |
July | 58598.07 | 22-JUL-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 7800.26 | 0.00 |
August | 53988.52 | 14-AUG-14:39 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 3213.23 | 0.00 |
September | 52565.09 | 13-SEP-14:00 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 1766.96 | 0.00 |
October | 51167.47 | 07-OCT-14:30 | 35620.03 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 417.45 | 0.00 |
November | 54530.86 | 30-NOV-16:00 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54743.69 | 29-DEC-08:09 | 31660.41 | 10112.62 | 7857.24 | 0.00 | 3457.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50995.10 | 31660.41 | 10112.62 | 0.00 | 0.00 | 3281.20 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58598.07 | 35620.03 | 10112.62 | 7857.24 | 0.00 | 3457.02 | 0.00 | 0.00 | 7800.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 145218.14 | 10-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 102285.09 | 17-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 80055.83 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 38601.24 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 36429.36 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 16228.02 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 13148.60 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 8233.15 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 14823.23 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 38345.63 | 23-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 106732.60 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 124040.61 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 8233.15 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 145218.14 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 19.14 | 8.50 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.83 | 19.02 | 8.17 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9.00 | 19.76 | 9.00 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.67 | 20.14 | 5.67 | 20.14 | 0.17 | 24.53 | 0.00 | 0.00 |
May | 5.00 | 20.33 | 5.00 | 20.33 | 0.50 | 24.49 | 0.00 | 0.00 |
June | 0.50 | 20.47 | 0.50 | 20.47 | 1.83 | 24.52 | 0.00 | 0.00 |
July | 0.17 | 20.51 | 0.17 | 20.51 | 4.50 | 24.55 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 0.00 | 0.00 |
September | 0.67 | 20.50 | 0.67 | 20.50 | 0.17 | 24.46 | 0.00 | 0.00 |
October | 6.33 | 20.17 | 6.33 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.83 | 19.85 | 7.83 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.00 | 18.84 | 8.67 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.50 | 19.57 | 60.50 | 19.79 | 11.50 | 24.52 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 20.51 | 9.00 | 20.51 | 4.50 | 24.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78.17 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40.83 | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.83 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.83 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.67 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52.83 | 14.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102.17 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 358.83 | 14.72 | 0.00 | 0.17 | 27.27 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.17 | 14.98 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.07 | 324.00 | 21.07 | 324.00 | 21.07 |
April | 300.00 | 21.72 | 199.50 | 21.14 | 199.50 | 21.14 |
May | 307.33 | 21.96 | 141.33 | 21.11 | 141.33 | 21.11 |
June | 268.83 | 22.99 | 25.50 | 22.11 | 16.50 | 21.13 |
July | 180.67 | 23.29 | 50.33 | 23.59 | 5.67 | 21.11 |
August | 214.50 | 23.38 | 17.83 | 23.90 | 0.00 | 0.00 |
September | 282.17 | 23.05 | 24.67 | 21.21 | 23.67 | 21.10 |
October | 300.00 | 21.44 | 221.00 | 21.10 | 221.00 | 21.10 |
November | 288.00 | 21.07 | 286.50 | 21.07 | 286.50 | 21.07 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3341.50 | 21.83 | 2166.67 | 21.17 | 2094.17 | 21.07 |
Minimum of Months | 180.67 | 21.04 | 17.83 | 21.04 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.38 | 324.00 | 23.90 | 324.00 | 21.14 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.185885E+09 | 56073403.15 | 28.75 | 0.185849E+09 | 36028.76 | 0.00 | 0.55 | 29-APR-17:20 | 0.00 | 01-APR-00:10 | 7570.16 | 29-APR-17:20 | 7570.16 | 29-APR-17:20 | 12.86 | 28-APR-10:10 | 2307.74 | 29-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.340242E+09 | 0.102509E+09 | 49.42 | 0.314798E+09 | 25443778.58 | 0.00 | 0.45 | 23-MAY-17:25 | 0.00 | 01-MAY-00:10 | 6205.72 | 23-MAY-17:25 | 5957.85 | 23-MAY-17:25 | 542.23 | 23-MAY-16:00 | 1924.46 | 23-MAY-17:25 | 0.00 | 01-MAY-00:10 |
June | 0.168103E+10 | 0.502719E+09 | 173.47 | 0.150192E+10 | 0.179110E+09 | 0.00 | 1.00 | 13-JUN-17:10 | 0.00 | 01-JUN-00:10 | 17116.17 | 13-JUN-17:43 | 15838.42 | 13-JUN-17:10 | 3175.04 | 26-JUN-17:10 | 4599.34 | 13-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.316246E+10 | 0.946803E+09 | 249.79 | 0.285542E+10 | 0.307044E+09 | 0.00 | 1.00 | 21-JUL-17:08 | 0.00 | 01-JUL-00:10 | 17430.64 | 24-JUL-17:10 | 16642.22 | 21-JUL-18:23 | 2868.91 | 24-JUL-00:03 | 4641.51 | 22-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.326477E+10 | 0.971873E+09 | 268.19 | 0.292654E+10 | 0.338236E+09 | 0.00 | 0.96 | 14-AUG-17:10 | 0.00 | 01-AUG-00:10 | 15216.77 | 14-AUG-17:10 | 15216.77 | 14-AUG-17:10 | 1602.74 | 17-AUG-17:10 | 4302.53 | 14-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.134940E+10 | 0.404126E+09 | 159.75 | 0.121429E+10 | 0.135118E+09 | 0.00 | 0.61 | 13-SEP-17:15 | 0.00 | 01-SEP-00:10 | 8857.87 | 13-SEP-17:15 | 8580.62 | 13-SEP-17:15 | 810.02 | 12-SEP-14:20 | 2638.51 | 13-SEP-17:15 | 0.00 | 01-SEP-00:10 |
October | 19772216.74 | 6044313.93 | 7.50 | 19769066.70 | 3150.04 | 0.00 | 0.14 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 | 1949.06 | 07-OCT-15:40 | 1949.06 | 07-OCT-15:40 | 2.34 | 02-OCT-15:40 | 591.39 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.100036E+11 | 0.299015E+10 | 936.87 | 0.901858E+10 | 0.984991E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.326477E+10 | 0.971873E+09 | 268.19 | 0.292654E+10 | 0.338236E+09 | 0.00 | 1.00 | 0.00 | 17430.64 | 16642.22 | 3175.04 | 4641.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.144907E+09 | 39638470.59 | 6.50 | 0.125314E+09 | 19592945.33 | 0.00 | 0.32 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 10790.70 | 13-JUN-16:00 | 9687.91 | 13-JUN-16:00 | 1400.52 | 13-JUN-15:00 | 2956.66 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.730844E+09 | 0.202182E+09 | 30.15 | 0.713063E+09 | 17781542.94 | 0.00 | 1.00 | 21-JUL-17:12 | 0.00 | 01-JUL-00:10 | 38291.24 | 23-JUL-16:21 | 36302.65 | 21-JUL-17:12 | 10007.60 | 23-JUL-16:21 | 9258.99 | 22-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 61407991.54 | 17155495.48 | 14.50 | 58481000.21 | 2926991.33 | 0.00 | 0.19 | 14-AUG-16:40 | 0.00 | 01-AUG-00:10 | 5936.22 | 14-AUG-16:00 | 5936.22 | 14-AUG-16:00 | 422.83 | 14-AUG-14:30 | 1678.98 | 14-AUG-16:40 | 0.00 | 01-AUG-00:10 |
September | 4.31 | 1.19 | 1.17 | 3.75 | 0.56 | 0.00 | 0.00 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 | 0.00 | 13-SEP-14:10 | 0.00 | 13-SEP-14:10 | 0.00 | 13-SEP-14:10 | 0.00 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.937159E+09 | 0.258976E+09 | 52.31 | 0.896858E+09 | 40301480.16 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.730844E+09 | 0.202182E+09 | 30.15 | 0.713063E+09 | 19592945.33 | 0.00 | 1.00 | 0.00 | 38291.24 | 36302.65 | 10007.60 | 9258.99 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.10 | 19.97 | 41.13 | 32.94 | 139.32 | 0.00 | 0.00 | 744.00 |
February | 108.07 | 45.91 | 62.17 | 76.57 | 131.29 | 0.00 | 0.00 | 672.00 |
March | 97.40 | 18.72 | 78.68 | 57.29 | 102.92 | 0.00 | 0.00 | 744.00 |
April | 229.19 | 90.81 | 138.38 | 214.39 | 90.30 | 0.00 | 0.00 | 720.00 |
May | 268.77 | 108.94 | 159.83 | 246.92 | 79.54 | 0.00 | 0.00 | 744.00 |
June | 290.80 | 119.96 | 170.84 | 280.55 | 69.76 | 0.00 | 0.00 | 720.00 |
July | 296.17 | 130.63 | 165.54 | 294.78 | 69.08 | 0.00 | 0.00 | 744.00 |
August | 248.59 | 107.51 | 141.08 | 247.57 | 77.17 | 0.00 | 0.00 | 744.00 |
September | 201.24 | 90.96 | 110.28 | 194.69 | 90.13 | 0.00 | 0.00 | 720.00 |
October | 106.86 | 38.55 | 68.30 | 84.95 | 101.51 | 0.00 | 0.00 | 744.00 |
November | 57.84 | 17.03 | 40.81 | 31.21 | 123.09 | 0.00 | 0.00 | 720.00 |
December | 32.48 | 6.76 | 25.72 | 9.18 | 159.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 166.71 | 66.33 | 100.38 | 147.81 | 102.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.48 | 6.76 | 25.72 | 9.18 | 69.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 296.17 | 130.63 | 170.84 | 294.78 | 159.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.10 | 19.97 | 41.13 | 32.94 | 139.32 | 0.00 | 0.00 | 744.00 |
February | 108.07 | 45.91 | 62.17 | 76.57 | 131.29 | 0.00 | 0.00 | 672.00 |
March | 97.40 | 18.72 | 78.68 | 57.29 | 102.92 | 0.00 | 0.00 | 744.00 |
April | 229.19 | 90.81 | 138.38 | 214.39 | 90.30 | 0.00 | 0.00 | 720.00 |
May | 268.77 | 108.94 | 159.83 | 246.92 | 79.54 | 0.00 | 0.00 | 744.00 |
June | 290.80 | 119.96 | 170.84 | 280.55 | 69.76 | 0.00 | 0.00 | 720.00 |
July | 296.17 | 130.63 | 165.54 | 294.78 | 69.08 | 0.00 | 0.00 | 744.00 |
August | 248.59 | 107.51 | 141.08 | 247.57 | 77.17 | 0.00 | 0.00 | 744.00 |
September | 201.24 | 90.96 | 110.28 | 194.69 | 90.13 | 0.00 | 0.00 | 720.00 |
October | 106.86 | 38.55 | 68.30 | 84.95 | 101.51 | 0.00 | 0.00 | 744.00 |
November | 57.84 | 17.03 | 40.81 | 31.21 | 123.09 | 0.00 | 0.00 | 720.00 |
December | 32.48 | 6.76 | 25.72 | 9.18 | 159.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 166.71 | 66.33 | 100.38 | 147.81 | 102.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.48 | 6.76 | 25.72 | 9.18 | 69.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 296.17 | 130.63 | 170.84 | 294.78 | 159.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.83 | 0.00 | 17.83 | 1.73 | 85.66 | 0.00 | 0.00 | 744.00 |
February | 27.84 | 0.00 | 27.84 | 4.33 | 79.61 | 0.00 | 0.00 | 672.00 |
March | 38.53 | 0.00 | 38.53 | 13.26 | 62.46 | 0.00 | 0.00 | 744.00 |
April | 62.81 | 0.34 | 62.47 | 37.61 | 53.14 | 0.00 | 0.00 | 720.00 |
May | 78.75 | 4.07 | 74.69 | 44.16 | 44.14 | 0.00 | 0.00 | 744.00 |
June | 86.45 | 5.28 | 81.17 | 57.12 | 38.85 | 0.00 | 0.00 | 720.00 |
July | 82.18 | 4.64 | 77.55 | 56.07 | 38.19 | 0.00 | 0.00 | 744.00 |
August | 64.93 | 1.25 | 63.68 | 44.37 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 49.23 | 0.03 | 49.20 | 30.75 | 53.56 | 0.00 | 0.00 | 720.00 |
October | 31.52 | 0.00 | 31.52 | 12.96 | 60.27 | 0.00 | 0.00 | 744.00 |
November | 18.94 | 0.00 | 18.94 | 2.43 | 73.40 | 0.00 | 0.00 | 720.00 |
December | 12.90 | 0.00 | 12.90 | 0.19 | 93.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.75 | 1.31 | 46.44 | 25.52 | 60.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 12.90 | 0.00 | 12.90 | 0.19 | 38.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.45 | 5.28 | 81.17 | 57.12 | 93.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.83 | 0.00 | 17.83 | 1.73 | 85.66 | 0.00 | 0.00 | 744.00 |
February | 27.84 | 0.00 | 27.84 | 4.33 | 79.61 | 0.00 | 0.00 | 672.00 |
March | 38.53 | 0.00 | 38.53 | 13.25 | 62.46 | 0.00 | 0.00 | 744.00 |
April | 62.81 | 0.34 | 62.47 | 37.61 | 53.14 | 0.00 | 0.00 | 720.00 |
May | 78.75 | 4.07 | 74.68 | 44.16 | 44.14 | 0.00 | 0.00 | 744.00 |
June | 86.44 | 5.28 | 81.17 | 57.12 | 38.85 | 0.00 | 0.00 | 720.00 |
July | 82.18 | 4.64 | 77.54 | 56.07 | 38.19 | 0.00 | 0.00 | 744.00 |
August | 64.93 | 1.25 | 63.67 | 44.37 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 49.23 | 0.03 | 49.20 | 30.75 | 53.56 | 0.00 | 0.00 | 720.00 |
October | 31.52 | 0.00 | 31.52 | 12.96 | 60.27 | 0.00 | 0.00 | 744.00 |
November | 18.94 | 0.00 | 18.94 | 2.43 | 73.40 | 0.00 | 0.00 | 720.00 |
December | 12.90 | 0.00 | 12.90 | 0.19 | 93.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.75 | 1.31 | 46.44 | 25.52 | 60.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 12.90 | 0.00 | 12.90 | 0.19 | 38.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.44 | 5.28 | 81.17 | 57.12 | 93.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.09 | 5.69 | 14.40 | 18.45 | 64.67 | 118.83 | 0.00 | 744.00 |
February | 34.81 | 12.52 | 22.30 | 36.62 | 62.60 | 95.83 | 0.00 | 672.00 |
March | 43.35 | 8.24 | 35.10 | 47.93 | 47.98 | 20.00 | 0.00 | 744.00 |
April | 104.99 | 56.06 | 48.93 | 133.82 | 56.89 | 0.00 | 0.00 | 720.00 |
May | 125.71 | 69.23 | 56.48 | 153.45 | 54.32 | 7.17 | 0.00 | 744.00 |
June | 133.92 | 71.97 | 61.95 | 166.50 | 48.47 | 5.33 | 0.00 | 720.00 |
July | 135.74 | 78.77 | 56.97 | 168.63 | 52.74 | 0.17 | 0.00 | 744.00 |
August | 117.00 | 70.43 | 46.57 | 144.96 | 62.17 | 1.50 | 0.00 | 744.00 |
September | 86.35 | 51.36 | 34.99 | 105.84 | 68.46 | 37.17 | 0.00 | 720.00 |
October | 44.36 | 19.46 | 24.90 | 48.61 | 63.12 | 74.17 | 0.00 | 744.00 |
November | 21.91 | 6.50 | 15.41 | 20.39 | 55.55 | 53.67 | 0.00 | 720.00 |
December | 13.99 | 3.54 | 10.45 | 9.85 | 70.19 | 42.17 | 0.00 | 744.00 |
Annual Sum or Average | 73.69 | 37.93 | 35.76 | 88.14 | 58.92 | 456.00 | 0.00 | 8760.00 |
Minimum of Months | 13.99 | 3.54 | 10.45 | 9.85 | 47.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 135.74 | 78.77 | 61.95 | 168.63 | 70.19 | 118.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163647E+09 | 53477549.73 | 0.110170E+09 | 88214629.73 | 0.373154E+09 |
February | 0.261452E+09 | 0.111061E+09 | 0.150391E+09 | 0.185244E+09 | 0.317606E+09 |
March | 0.260873E+09 | 50150108.43 | 0.210723E+09 | 0.153454E+09 | 0.275660E+09 |
April | 0.594061E+09 | 0.235378E+09 | 0.358682E+09 | 0.555696E+09 | 0.234051E+09 |
May | 0.719878E+09 | 0.291797E+09 | 0.428081E+09 | 0.661362E+09 | 0.213029E+09 |
June | 0.753743E+09 | 0.310933E+09 | 0.442810E+09 | 0.727185E+09 | 0.180823E+09 |
July | 0.793262E+09 | 0.349892E+09 | 0.443370E+09 | 0.789541E+09 | 0.185020E+09 |
August | 0.665830E+09 | 0.287949E+09 | 0.377881E+09 | 0.663083E+09 | 0.206703E+09 |
September | 0.521605E+09 | 0.235765E+09 | 0.285839E+09 | 0.504638E+09 | 0.233605E+09 |
October | 0.286210E+09 | 0.103264E+09 | 0.182945E+09 | 0.227543E+09 | 0.271882E+09 |
November | 0.149924E+09 | 44140752.30 | 0.105783E+09 | 80907548.59 | 0.319047E+09 |
December | 87002262.43 | 18105838.10 | 68896424.33 | 24598768.36 | 0.426587E+09 |
Annual Sum or Average | 0.525749E+10 | 0.209191E+10 | 0.316557E+10 | 0.466147E+10 | 0.323717E+10 |
Minimum of Months | 87002262.43 | 18105838.10 | 68896424.33 | 24598768.36 | 0.180823E+09 |
Maximum of Months | 0.793262E+09 | 0.349892E+09 | 0.443370E+09 | 0.789541E+09 | 0.426587E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163647E+09 | 53477549.73 | 0.110170E+09 | 88214629.73 | 0.373154E+09 |
February | 0.261452E+09 | 0.111061E+09 | 0.150391E+09 | 0.185244E+09 | 0.317606E+09 |
March | 0.260873E+09 | 50150108.43 | 0.210723E+09 | 0.153454E+09 | 0.275660E+09 |
April | 0.594061E+09 | 0.235378E+09 | 0.358682E+09 | 0.555696E+09 | 0.234051E+09 |
May | 0.719878E+09 | 0.291797E+09 | 0.428081E+09 | 0.661362E+09 | 0.213029E+09 |
June | 0.753743E+09 | 0.310933E+09 | 0.442810E+09 | 0.727185E+09 | 0.180823E+09 |
July | 0.793262E+09 | 0.349892E+09 | 0.443370E+09 | 0.789541E+09 | 0.185020E+09 |
August | 0.665830E+09 | 0.287949E+09 | 0.377881E+09 | 0.663083E+09 | 0.206703E+09 |
September | 0.521605E+09 | 0.235765E+09 | 0.285839E+09 | 0.504638E+09 | 0.233605E+09 |
October | 0.286210E+09 | 0.103264E+09 | 0.182945E+09 | 0.227543E+09 | 0.271882E+09 |
November | 0.149924E+09 | 44140752.30 | 0.105783E+09 | 80907548.59 | 0.319047E+09 |
December | 87002262.43 | 18105838.10 | 68896424.33 | 24598768.36 | 0.426587E+09 |
Annual Sum or Average | 0.525749E+10 | 0.209191E+10 | 0.316557E+10 | 0.466147E+10 | 0.323717E+10 |
Minimum of Months | 87002262.43 | 18105838.10 | 68896424.33 | 24598768.36 | 0.180823E+09 |
Maximum of Months | 0.793262E+09 | 0.349892E+09 | 0.443370E+09 | 0.789541E+09 | 0.426587E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47749169.22 | 0.00 | 47749169.22 | 4642152.95 | 0.229427E+09 |
February | 67346638.35 | 0.00 | 67346638.35 | 10481597.45 | 0.192584E+09 |
March | 0.103192E+09 | 1404.63 | 0.103190E+09 | 35503263.95 | 0.167299E+09 |
April | 0.162804E+09 | 872391.63 | 0.161931E+09 | 97495953.72 | 0.137726E+09 |
May | 0.210935E+09 | 10894492.83 | 0.200040E+09 | 0.118277E+09 | 0.118220E+09 |
June | 0.224068E+09 | 13681051.59 | 0.210387E+09 | 0.148056E+09 | 0.100696E+09 |
July | 0.220121E+09 | 12423788.04 | 0.207697E+09 | 0.150180E+09 | 0.102291E+09 |
August | 0.173908E+09 | 3356380.39 | 0.170552E+09 | 0.118844E+09 | 0.118238E+09 |
September | 0.127607E+09 | 74897.55 | 0.127532E+09 | 79712488.25 | 0.138827E+09 |
October | 84434957.15 | 0.00 | 84434957.15 | 34724292.38 | 0.161418E+09 |
November | 49096293.92 | 0.00 | 49096293.92 | 6306288.32 | 0.190261E+09 |
December | 34548928.01 | 0.00 | 34548928.01 | 514567.21 | 0.251593E+09 |
Annual Sum or Average | 0.150581E+10 | 41304406.65 | 0.146451E+10 | 0.804737E+09 | 0.190858E+10 |
Minimum of Months | 34548928.01 | 0.00 | 34548928.01 | 514567.21 | 0.100696E+09 |
Maximum of Months | 0.224068E+09 | 13681051.59 | 0.210387E+09 | 0.150180E+09 | 0.251593E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47747532.65 | 0.00 | 47747532.65 | 4641601.64 | 0.229427E+09 |
February | 67344389.37 | 0.00 | 67344389.37 | 10480329.19 | 0.192584E+09 |
March | 0.103188E+09 | 1404.56 | 0.103187E+09 | 35500235.82 | 0.167299E+09 |
April | 0.162799E+09 | 872350.74 | 0.161926E+09 | 97491247.66 | 0.137726E+09 |
May | 0.210928E+09 | 10893982.19 | 0.200034E+09 | 0.118271E+09 | 0.118220E+09 |
June | 0.224061E+09 | 13680410.34 | 0.210380E+09 | 0.148048E+09 | 0.100696E+09 |
July | 0.220114E+09 | 12423205.72 | 0.207691E+09 | 0.150173E+09 | 0.102291E+09 |
August | 0.173903E+09 | 3356223.07 | 0.170547E+09 | 0.118839E+09 | 0.118237E+09 |
September | 0.127603E+09 | 74894.04 | 0.127528E+09 | 79709197.37 | 0.138826E+09 |
October | 84432202.69 | 0.00 | 84432202.69 | 34722156.50 | 0.161417E+09 |
November | 49094606.94 | 0.00 | 49094606.94 | 6305537.73 | 0.190261E+09 |
December | 34547725.80 | 0.00 | 34547725.80 | 514428.89 | 0.251593E+09 |
Annual Sum or Average | 0.150576E+10 | 41302470.66 | 0.146446E+10 | 0.804696E+09 | 0.190858E+10 |
Minimum of Months | 34547725.80 | 0.00 | 34547725.80 | 514428.89 | 0.100696E+09 |
Maximum of Months | 0.224061E+09 | 13680410.34 | 0.210380E+09 | 0.150173E+09 | 0.251593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53801498.39 | 15244471.38 | 38557027.01 | 49414645.17 | 0.173225E+09 |
February | 84216616.44 | 30277181.59 | 53939434.85 | 88599172.24 | 0.151438E+09 |
March | 0.116097E+09 | 22075806.15 | 94021353.33 | 0.128382E+09 | 0.128498E+09 |
April | 0.272133E+09 | 0.145295E+09 | 0.126838E+09 | 0.346859E+09 | 0.147458E+09 |
May | 0.336691E+09 | 0.185427E+09 | 0.151263E+09 | 0.411003E+09 | 0.145488E+09 |
June | 0.347118E+09 | 0.186542E+09 | 0.160576E+09 | 0.431556E+09 | 0.125640E+09 |
July | 0.363578E+09 | 0.210983E+09 | 0.152595E+09 | 0.451671E+09 | 0.141253E+09 |
August | 0.313383E+09 | 0.188650E+09 | 0.124733E+09 | 0.388254E+09 | 0.166522E+09 |
September | 0.223817E+09 | 0.133133E+09 | 90683135.21 | 0.274327E+09 | 0.177436E+09 |
October | 0.118814E+09 | 52111045.43 | 66702568.31 | 0.130194E+09 | 0.169058E+09 |
November | 56799052.04 | 16857086.00 | 39941966.04 | 52863709.54 | 0.143986E+09 |
December | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.187999E+09 |
Annual Sum or Average | 0.232391E+10 | 0.119607E+10 | 0.112784E+10 | 0.277950E+10 | 0.185800E+10 |
Minimum of Months | 37462594.34 | 9475921.00 | 27986673.33 | 26371956.76 | 0.125640E+09 |
Maximum of Months | 0.363578E+09 | 0.210983E+09 | 0.160576E+09 | 0.451671E+09 | 0.187999E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.63 | 443.25 | 157.85 | 39.93 | 117.92 | 0.00 | 0.00 |
February | 156.54 | 416.51 | 271.82 | 91.82 | 180.01 | 0.00 | 0.00 |
March | 137.53 | 327.19 | 271.85 | 37.45 | 234.40 | 0.00 | 0.00 |
April | 501.69 | 284.55 | 584.00 | 182.29 | 401.71 | 0.00 | 0.00 |
May | 579.96 | 245.15 | 695.05 | 226.02 | 469.03 | 0.00 | 0.00 |
June | 672.36 | 214.24 | 754.48 | 250.47 | 504.01 | 0.00 | 0.00 |
July | 699.09 | 211.93 | 756.71 | 270.55 | 486.16 | 0.00 | 0.00 |
August | 582.58 | 241.35 | 627.04 | 217.52 | 409.52 | 0.00 | 0.00 |
September | 448.35 | 284.83 | 500.93 | 181.98 | 318.96 | 0.00 | 0.00 |
October | 193.44 | 321.16 | 276.76 | 77.11 | 199.66 | 0.00 | 0.00 |
November | 64.10 | 389.79 | 153.56 | 34.06 | 119.51 | 0.00 | 0.00 |
December | 16.32 | 503.98 | 90.76 | 13.52 | 77.24 | 0.00 | 0.00 |
Annual Sum or Average | 343.55 | 323.23 | 428.92 | 135.29 | 293.64 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 211.93 | 90.76 | 13.52 | 77.24 | 0.00 | 0.00 |
Maximum of Months | 699.09 | 503.98 | 756.71 | 270.55 | 504.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.49 | 646.75 | 200.87 | 56.92 | 143.96 | 0.00 | 0.00 |
February | 366.23 | 625.98 | 348.12 | 125.15 | 222.96 | 0.00 | 0.00 |
March | 479.32 | 479.75 | 433.46 | 82.42 | 351.04 | 0.00 | 0.00 |
April | 1338.19 | 568.90 | 1049.90 | 560.55 | 489.34 | 0.00 | 0.00 |
May | 1534.51 | 543.19 | 1257.06 | 692.31 | 564.75 | 0.00 | 0.00 |
June | 1664.95 | 484.72 | 1339.19 | 719.68 | 619.50 | 0.00 | 0.00 |
July | 1686.34 | 527.38 | 1357.45 | 787.72 | 569.72 | 0.00 | 0.00 |
August | 1449.58 | 621.72 | 1170.04 | 704.34 | 465.70 | 0.00 | 0.00 |
September | 1058.36 | 684.55 | 863.49 | 513.63 | 349.86 | 0.00 | 0.00 |
October | 486.08 | 631.19 | 443.60 | 194.56 | 249.04 | 0.00 | 0.00 |
November | 203.95 | 555.50 | 219.13 | 65.04 | 154.10 | 0.00 | 0.00 |
December | 98.46 | 701.91 | 139.87 | 35.38 | 104.49 | 0.00 | 0.00 |
Annual Sum or Average | 881.37 | 589.17 | 736.91 | 379.27 | 357.63 | 0.00 | 0.00 |
Minimum of Months | 98.46 | 479.75 | 139.87 | 35.38 | 104.49 | 0.00 | 0.00 |
Maximum of Months | 1686.34 | 701.91 | 1357.45 | 787.72 | 619.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167746E+09 | 0.118720E+10 | 0.422791E+09 | 0.106955E+09 | 0.315836E+09 | 0.00 | 0.00 |
February | 0.378700E+09 | 0.100763E+10 | 0.657594E+09 | 0.222122E+09 | 0.435472E+09 | 0.00 | 0.00 |
March | 0.368350E+09 | 0.876357E+09 | 0.728127E+09 | 0.100303E+09 | 0.627824E+09 | 0.00 | 0.00 |
April | 0.130037E+10 | 0.737549E+09 | 0.151372E+10 | 0.472502E+09 | 0.104122E+10 | 0.00 | 0.00 |
May | 0.155337E+10 | 0.656599E+09 | 0.186162E+10 | 0.605382E+09 | 0.125624E+10 | 0.00 | 0.00 |
June | 0.174275E+10 | 0.555312E+09 | 0.195561E+10 | 0.649227E+09 | 0.130639E+10 | 0.00 | 0.00 |
July | 0.187244E+10 | 0.567624E+09 | 0.202676E+10 | 0.724632E+09 | 0.130213E+10 | 0.00 | 0.00 |
August | 0.156039E+10 | 0.646421E+09 | 0.167947E+10 | 0.582610E+09 | 0.109686E+10 | 0.00 | 0.00 |
September | 0.116212E+10 | 0.738283E+09 | 0.129842E+10 | 0.471680E+09 | 0.826739E+09 | 0.00 | 0.00 |
October | 0.518122E+09 | 0.860188E+09 | 0.741287E+09 | 0.206529E+09 | 0.534758E+09 | 0.00 | 0.00 |
November | 0.166148E+09 | 0.101034E+10 | 0.398039E+09 | 88281504.61 | 0.309757E+09 | 0.00 | 0.00 |
December | 43722045.89 | 0.134986E+10 | 0.243101E+09 | 36211676.21 | 0.206890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108342E+11 | 0.101934E+11 | 0.135265E+11 | 0.426644E+10 | 0.926011E+10 | 0.00 | 0.00 |
Minimum of Months | 43722045.89 | 0.555312E+09 | 0.243101E+09 | 36211676.21 | 0.206890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187244E+10 | 0.134986E+10 | 0.202676E+10 | 0.724632E+09 | 0.130639E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.494141E+09 | 0.173225E+10 | 0.538015E+09 | 0.152445E+09 | 0.385570E+09 | 0.00 | 0.00 |
February | 0.885992E+09 | 0.151438E+10 | 0.842166E+09 | 0.302772E+09 | 0.539394E+09 | 0.00 | 0.00 |
March | 0.128382E+10 | 0.128497E+10 | 0.116097E+10 | 0.220758E+09 | 0.940214E+09 | 0.00 | 0.00 |
April | 0.346858E+10 | 0.147458E+10 | 0.272133E+10 | 0.145295E+10 | 0.126838E+10 | 0.00 | 0.00 |
May | 0.411003E+10 | 0.145488E+10 | 0.336691E+10 | 0.185427E+10 | 0.151263E+10 | 0.00 | 0.00 |
June | 0.431556E+10 | 0.125640E+10 | 0.347118E+10 | 0.186542E+10 | 0.160576E+10 | 0.00 | 0.00 |
July | 0.451670E+10 | 0.141253E+10 | 0.363578E+10 | 0.210983E+10 | 0.152595E+10 | 0.00 | 0.00 |
August | 0.388254E+10 | 0.166522E+10 | 0.313383E+10 | 0.188650E+10 | 0.124733E+10 | 0.00 | 0.00 |
September | 0.274327E+10 | 0.177436E+10 | 0.223817E+10 | 0.133133E+10 | 0.906831E+09 | 0.00 | 0.00 |
October | 0.130191E+10 | 0.169058E+10 | 0.118814E+10 | 0.521110E+09 | 0.667026E+09 | 0.00 | 0.00 |
November | 0.528637E+09 | 0.143986E+10 | 0.567991E+09 | 0.168571E+09 | 0.399420E+09 | 0.00 | 0.00 |
December | 0.263719E+09 | 0.187999E+10 | 0.374626E+09 | 94759210.05 | 0.279867E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277949E+11 | 0.185800E+11 | 0.232391E+11 | 0.119607E+11 | 0.112784E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263719E+09 | 0.125640E+10 | 0.374626E+09 | 94759210.05 | 0.279867E+09 | 0.00 | 0.00 |
Maximum of Months | 0.451670E+10 | 0.187999E+10 | 0.363578E+10 | 0.210983E+10 | 0.160576E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.102487E+10 | -869208638.4 | 0.00 | 0.00 | 744.00 | 0.00 | -155659300.8 | 58.99 | 0.00 | 0.00 |
February | 0.944380E+09 | -803825790.7 | 0.00 | 0.00 | 672.00 | 0.00 | -140553968.5 | 58.99 | 0.00 | 0.00 |
March | 0.108710E+10 | -933243906.9 | 0.00 | 0.00 | 744.00 | 0.00 | -153858396.1 | 58.99 | 0.00 | 0.00 |
April | 0.993611E+09 | -850506795.8 | 0.00 | 0.00 | 720.00 | 0.00 | -143104695.2 | 58.99 | 0.00 | 0.00 |
May | 0.100674E+10 | -860910026.5 | 0.00 | 0.00 | 744.00 | 0.00 | -145833554.9 | 58.99 | 0.00 | 0.00 |
June | 0.968544E+09 | -834454803.4 | 0.00 | 0.00 | 720.00 | 0.00 | -134089312.0 | 58.99 | 0.00 | 0.00 |
July | 0.925574E+09 | -789598230.4 | 0.00 | 0.00 | 744.00 | 0.00 | -135975861.1 | 58.99 | 0.00 | 0.00 |
August | 0.976585E+09 | -841423578.3 | 0.00 | 0.00 | 744.00 | 0.00 | -135161774.9 | 58.99 | 0.00 | 0.00 |
September | 0.923074E+09 | -787971228.4 | 0.00 | 0.00 | 720.00 | 0.00 | -135102824.3 | 58.99 | 0.00 | 0.00 |
October | 0.957117E+09 | -806778718.3 | 0.00 | 0.00 | 744.00 | 0.00 | -150338142.5 | 58.99 | 0.00 | 0.00 |
November | 0.946108E+09 | -796617685.9 | 0.00 | 0.00 | 720.00 | 0.00 | -149490331.8 | 58.99 | 0.00 | 0.00 |
December | 0.100815E+10 | -851916346.1 | 0.00 | 0.00 | 744.00 | 0.00 | -156232578.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.117619E+11 | -.100265E+11 | 8760.00 | -.173540E+10 | 58.99 | |||||
Minimum of Months | 0.923074E+09 | -933243906.9 | 0.00 | 0.00 | 672.00 | 0.00 | -156232578.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.108710E+10 | -787971228.4 | 0.00 | 0.00 | 744.00 | 0.00 | -134089312.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.664658E+10 | 26296.58 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.541341E+10 | 26296.58 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546191E+10 | 26296.58 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205384E+10 | 26296.58 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142188E+10 | 26296.58 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260114E+09 | 26296.58 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81748864.57 | 26296.58 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38766305.63 | 4278.27 | 30-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.362123E+09 | 26296.58 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246826E+10 | 26296.58 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.473545E+10 | 26296.58 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.680162E+10 | 26296.58 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357457E+11 | |||||||
Minimum of Months | 38766305.63 | 4278.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680162E+10 | 26296.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184169E+11 | 65709.32 | 01-JAN-17:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154297E+11 | 65709.32 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102337E+11 | 65709.32 | 04-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136296E+10 | 65709.32 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.759949E+09 | 30473.87 | 05-MAY-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.320770E+10 | 65709.32 | 21-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130617E+11 | 65709.32 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251372E+11 | 65709.32 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876097E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251372E+11 | 65709.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213711E+11 | 59812.69 | 10-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142051E+11 | 43026.15 | 17-FEB-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208193E+10 | 21607.74 | 04-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644660E+10 | 38840.78 | 29-NOV-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359368E+11 | 59252.08 | 30-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800415E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359368E+11 | 59812.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.185885E+09 | 0.185849E+09 | 7570.16 | 29-APR-17:20 | 7570.16 | 0.00 |
May | 0.00 | 0.00 | 0.340242E+09 | 0.314798E+09 | 6205.72 | 23-MAY-17:25 | 5957.85 | 0.00 |
June | 0.00 | 0.00 | 0.168103E+10 | 0.150192E+10 | 17116.17 | 13-JUN-17:43 | 15784.35 | 0.00 |
July | 0.00 | 0.00 | 0.316246E+10 | 0.285542E+10 | 17430.64 | 24-JUL-17:10 | 14630.47 | 0.00 |
August | 0.00 | 0.00 | 0.326477E+10 | 0.292654E+10 | 15216.77 | 14-AUG-17:10 | 15216.77 | 0.00 |
September | 0.00 | 0.00 | 0.134940E+10 | 0.121429E+10 | 8857.87 | 13-SEP-17:15 | 8580.62 | 0.00 |
October | 0.00 | 0.00 | 19772216.74 | 19769066.70 | 1949.06 | 07-OCT-15:40 | 1949.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.100036E+11 | 0.901858E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.326477E+10 | 0.292654E+10 | 17430.64 | 15784.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144907E+09 | 0.125314E+09 | 10790.70 | 13-JUN-16:00 | 9687.91 | 0.00 |
July | 0.00 | 0.00 | 0.730844E+09 | 0.713063E+09 | 38291.24 | 23-JUL-16:21 | 28283.64 | 0.00 |
August | 0.00 | 0.00 | 61407991.54 | 58481000.21 | 5936.22 | 14-AUG-16:00 | 5936.22 | 0.00 |
September | 0.00 | 0.00 | 4.31 | 3.75 | 0.00 | 13-SEP-14:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.937159E+09 | 0.896858E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.730844E+09 | 0.713063E+09 | 38291.24 | 28283.64 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.213586E+09 | 0.03 | 175.82 | 01-JAN-00:03 | 0.08 |
February | 0.190498E+09 | 0.03 | 175.82 | 01-FEB-00:03 | 0.08 |
March | 56665876.01 | 0.01 | 175.82 | 01-MAR-02:00 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 70430602.76 | 0.01 | 175.82 | 05-NOV-06:00 | 0.08 |
December | 0.322519E+09 | 0.05 | 175.82 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.853700E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322519E+09 | 0.05 | 175.82 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117597E+10 | 0.41 | 1138.09 | 02-JAN-07:40 | 0.95 |
February | 0.107624E+10 | 0.40 | 1138.09 | 01-FEB-10:10 | 0.94 |
March | 0.125686E+10 | 0.41 | 1138.09 | 01-MAR-08:50 | 0.94 |
April | 0.115047E+10 | 0.39 | 1138.09 | 01-APR-07:40 | 0.94 |
May | 0.118944E+10 | 0.38 | 1138.09 | 01-MAY-06:40 | 0.94 |
June | 0.118608E+10 | 0.40 | 1138.09 | 01-JUN-06:30 | 0.94 |
July | 0.116242E+10 | 0.40 | 1138.09 | 01-JUL-10:00 | 0.94 |
August | 0.123441E+10 | 0.40 | 1138.09 | 01-AUG-08:00 | 0.94 |
September | 0.113196E+10 | 0.37 | 1138.09 | 01-SEP-06:30 | 0.94 |
October | 0.115133E+10 | 0.37 | 1138.09 | 02-OCT-16:55 | 0.94 |
November | 0.111590E+10 | 0.38 | 1138.09 | 01-NOV-06:05 | 0.94 |
December | 0.117506E+10 | 0.41 | 1138.09 | 01-DEC-07:10 | 0.94 |
Annual Sum or Average | 0.140061E+11 | 0.39 | |||
Minimum of Months | 0.107624E+10 | 0.37 | 1138.09 | 0.94 | |
Maximum of Months | 0.125686E+10 | 0.41 | 1138.09 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264675E+10 | 0.74 | 2143.11 | 05-JAN-15:00 | 0.91 |
February | 0.244136E+10 | 0.75 | 2143.11 | 02-FEB-10:50 | 0.91 |
March | 0.262579E+10 | 0.69 | 2143.11 | 03-MAR-10:20 | 0.91 |
April | 0.217252E+10 | 0.42 | 2143.11 | 01-APR-06:30 | 0.91 |
May | 0.223512E+10 | 0.39 | 2143.11 | 05-MAY-06:20 | 0.91 |
June | 0.220655E+10 | 0.36 | 2143.11 | 26-JUN-13:30 | 0.90 |
July | 0.213598E+10 | 0.34 | 2143.11 | 27-JUL-15:00 | 0.90 |
August | 0.229141E+10 | 0.36 | 2143.11 | 28-AUG-16:00 | 0.90 |
September | 0.212168E+10 | 0.34 | 2143.11 | 13-SEP-14:00 | 0.90 |
October | 0.223576E+10 | 0.48 | 2143.11 | 04-OCT-06:10 | 0.91 |
November | 0.244432E+10 | 0.70 | 2143.11 | 27-NOV-10:30 | 0.91 |
December | 0.281874E+10 | 0.78 | 2143.11 | 01-DEC-10:50 | 0.91 |
Annual Sum or Average | 0.283760E+11 | 0.53 | |||
Minimum of Months | 0.212168E+10 | 0.34 | 2143.11 | 0.90 | |
Maximum of Months | 0.281874E+10 | 0.78 | 2143.11 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.24 | 0.01 |
February | 2.23 | 0.00 |
March | 2.03 | 0.00 |
April | 0.64 | 1.39 |
May | 1.12 | 2.36 |
June | 1.94 | 2.94 |
July | 1.71 | 4.11 |
August | 1.64 | 4.80 |
September | 1.35 | 2.26 |
October | 0.90 | 0.76 |
November | 2.27 | 0.02 |
December | 2.92 | 0.00 |
Annual Sum or Average | 22.00 | 1.27 |
Minimum of Months | 0.64 | 0.00 |
Maximum of Months | 3.24 | 4.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.17 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117597E+10 | 0.954983E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107624E+10 | 0.782323E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125686E+10 | 0.790867E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120654E+10 | 0.297929E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129194E+10 | 0.207894E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168880E+10 | 0.385577E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210922E+10 | 0.121405E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.220628E+10 | 59528766.88 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.153608E+10 | 0.536163E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115737E+10 | 0.359911E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111590E+10 | 0.686574E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117506E+10 | 0.980380E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.169963E+11 | 0.517113E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107624E+10 | 59528766.88 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.220628E+10 | 0.980380E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.264675E+10 | 0.265376E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.244136E+10 | 0.221389E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.262579E+10 | 0.149343E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.217252E+10 | 0.202151E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.223512E+10 | 0.113247E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.224619E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233816E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.230857E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.212168E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.223576E+10 | 0.475368E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.244432E+10 | 0.188526E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.281874E+10 | 0.359762E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.286349E+11 | 0.126347E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.212168E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.281874E+10 | 0.359762E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117597E+10 | 0.00 | 0.664658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107624E+10 | 0.00 | 0.541341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125686E+10 | 0.00 | 0.546191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115047E+10 | 0.185885E+09 | 0.205384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118944E+10 | 0.340242E+09 | 0.142188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118608E+10 | 0.168103E+10 | 0.260114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116242E+10 | 0.316246E+10 | 81748864.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123441E+10 | 0.326477E+10 | 38766305.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113196E+10 | 0.134940E+10 | 0.362123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115133E+10 | 19772216.74 | 0.246826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111590E+10 | 0.00 | 0.473545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117506E+10 | 0.00 | 0.680162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140061E+11 | 0.100036E+11 | 0.357457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107624E+10 | 0.00 | 38766305.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125686E+10 | 0.326477E+10 | 0.680162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264675E+10 | 0.00 | 0.184169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244136E+10 | 0.00 | 0.154297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262579E+10 | 0.00 | 0.102337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217252E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223512E+10 | 0.00 | 0.759949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220655E+10 | 0.144907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213598E+10 | 0.730844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229141E+10 | 61407991.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212168E+10 | 4.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223576E+10 | 0.00 | 0.320770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244432E+10 | 0.00 | 0.130617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281874E+10 | 0.00 | 0.251372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283760E+11 | 0.937159E+09 | 0.876097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281874E+10 | 0.730844E+09 | 0.251372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.117597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115047E+10 | 0.00 | 0.00 | 0.00 | 56073403.15 | 0.00 | 0.297929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118944E+10 | 0.00 | 0.00 | 0.00 | 0.102509E+09 | 0.00 | 0.207894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118608E+10 | 0.00 | 0.00 | 0.00 | 0.502719E+09 | 0.00 | 0.385577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116242E+10 | 0.00 | 0.00 | 0.00 | 0.946803E+09 | 0.00 | 0.121405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123441E+10 | 0.00 | 0.00 | 0.00 | 0.971873E+09 | 0.00 | 59528766.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113196E+10 | 0.00 | 0.00 | 0.00 | 0.404126E+09 | 0.00 | 0.536163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115133E+10 | 0.00 | 0.00 | 0.00 | 6044313.93 | 0.00 | 0.359911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140061E+11 | 0.00 | 0.00 | 0.00 | 0.299015E+10 | 0.00 | 0.517113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.107624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59528766.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125686E+10 | 0.00 | 0.00 | 0.00 | 0.971873E+09 | 0.00 | 0.980380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.264675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220655E+10 | 0.00 | 0.00 | 0.00 | 39638470.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213598E+10 | 0.00 | 0.00 | 0.00 | 0.202182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229141E+10 | 0.00 | 0.00 | 0.00 | 17155495.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212168E+10 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283760E+11 | 0.00 | 0.00 | 0.00 | 0.258976E+09 | 0.00 | 0.126347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.212168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281874E+10 | 0.00 | 0.00 | 0.00 | 0.202182E+09 | 0.00 | 0.359762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24493655.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246568E+10 | 0.00 | 0.00 | 0.17 |
February | 39941832.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212559E+10 | 0.00 | 0.00 | 0.17 |
March | 61450493.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227572E+10 | 0.00 | 0.00 | 0.18 |
April | 0.720691E+09 | 0.00 | 0.00 | 287919.70 | 397351.33 | 0.848340E+09 | 0.122844E+09 | 0.00 | 0.17 |
May | 0.907751E+09 | 205305.59 | 0.00 | 498231.54 | 0.00 | 0.550689E+09 | 0.200883E+09 | 0.00 | 0.17 |
June | 0.525366E+09 | 15781080.03 | 0.00 | 2170739.65 | 0.00 | 0.102670E+09 | 0.645406E+09 | 0.00 | 0.18 |
July | 0.229382E+09 | 23270083.98 | 0.00 | 4113410.27 | 0.00 | 37468149.49 | 0.680042E+09 | 0.00 | 0.17 |
August | 0.147815E+09 | 1292536.04 | 0.00 | 4553733.25 | 0.00 | 38559149.33 | 0.655855E+09 | 0.00 | 0.18 |
September | 0.425418E+09 | 268940.72 | 0.00 | 1810813.55 | 0.00 | 0.139517E+09 | 0.528451E+09 | 0.00 | 0.17 |
October | 0.514919E+09 | 0.00 | 0.00 | 31754.17 | 0.00 | 0.106845E+10 | 42918724.01 | 0.00 | 0.16 |
November | 77278230.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190592E+10 | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244249E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.367451E+10 | 40817946.36 | 0.00 | 13466602.14 | 397351.33 | 0.140011E+11 | 0.287640E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37468149.49 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.907751E+09 | 23270083.98 | 0.00 | 4553733.25 | 397351.33 | 0.246568E+10 | 0.680042E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229302E+10 | 0.00 | 0.00 | 0.14 |
February | 0.229692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107330E+10 | 0.00 | 0.00 | 0.15 |
March | 0.293091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678100E+09 | 0.00 | 0.00 | 0.16 |
April | 0.308358E+10 | 0.00 | 0.00 | 0.00 | 6663766.26 | 5120462.02 | 0.00 | 0.00 | 0.15 |
May | 0.320546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6012417.85 | 0.00 | 0.00 | 0.15 |
June | 0.298799E+10 | 161354.59 | 0.00 | 331444.99 | 1543120.99 | 0.00 | 0.157311E+09 | 0.00 | 0.18 |
July | 0.230223E+10 | 8545843.69 | 0.00 | 1616753.35 | 1578277.55 | 0.00 | 0.843532E+09 | 0.00 | 0.19 |
August | 0.229768E+10 | 0.00 | 0.00 | 661481.03 | 0.00 | 0.00 | 0.650620E+09 | 0.00 | 0.19 |
September | 0.230482E+10 | 0.00 | 0.00 | 6389.05 | 0.00 | 0.00 | 12831917.38 | 0.00 | 0.15 |
October | 0.235091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113119E+09 | 0.00 | 0.00 | 0.15 |
November | 0.200697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924149E+09 | 0.00 | 0.00 | 0.14 |
December | 0.100407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276736E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.285029E+11 | 8707198.28 | 0.00 | 2616068.42 | 9785164.80 | 0.786018E+10 | 0.166430E+10 | 0.00 | 0.16 |
Minimum of Months | 0.100407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.320546E+10 | 8545843.69 | 0.00 | 1616753.35 | 6663766.26 | 0.276736E+10 | 0.843532E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |