Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2020-06-03 19:10:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2029.31 | 419.70 | 419.70 |
Net Site Energy | 2029.31 | 419.70 | 419.70 |
Total Source Energy | 3630.89 | 750.94 | 750.94 |
Net Source Energy | 3630.89 | 750.94 | 750.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1342.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 84.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 687.05 | 1342.26 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1342.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 84.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 36.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.76 | 277.61 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 142.10 | 277.61 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 100.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.76 | 277.61 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 142.10 | 277.61 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 687.048 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 687.048 | 100.00 |
Total On-Site and Utility Electric Sources | 687.048 | 100.00 |
Total Electricity End Uses | 687.048 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 73.67 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2486.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:10 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.8264 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5174 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5174 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JAN-15:39 | 28-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 224755.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30433.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2690.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 52098.57 | 224755.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 224755.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30433.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2690.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1455.01 | 0.00 | 0.00 | 0.00 |
Cooling | 6.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1266.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 266.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2175.88 | 1455.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 300.92 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 261.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 450.02 | 300.92 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 300.92 | 0.00 | 0.00 | 0.00 |
Cooling | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 261.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 450.02 | 300.92 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.773327 |
ZONE2 FINE STORAGE DIRECT AIR | 1.44 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.46 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.46 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 100692.48 |
PSZ-OFFICE HEATING COIL | 25124.93 |
PSZ-FINE STORAGE HEATING COIL | 71071.09 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 100692.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.773327 | 0.773327 | 0.773327 | 0.773327 | 0.773327 | 0.773327 | 1.00 | 1.00 | 0.773327 |
PSZ-FINE STORAGE | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.000000 | 1.44 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.773327 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.44 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.773327 | 0.773327 | 0.773327 | 0.773327 | 12801.31 | 25124.93 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 1.44 | 26981.21 | 71071.09 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.773330 | 0.386665 | 0.515553 | 12801.36 | 12801.31 | 6400.65 | 6400.65 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.44 | 0.721335 | 0.961780 | 23922.18 | 26981.21 | 13490.60 | 13490.60 | 0.756415 | 0.756410 | 0.756410 | 0.756410 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.773327 | 856.20 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.44 | 1543.72 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 8.826 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.900 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2090.796 | 8.826 | 418.159 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2090.796 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 14248.610 | 10.226 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.610 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 20008.048 | 6.243 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.048 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1507 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.2280 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3564 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3564 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.636 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.706 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.706 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.68857323E-13 | 0.53233684E-18 | 0.39256197E-18 | 0.0000000 |
2 | 1 | -5.2161015 | 0.66198115E-04 | -0.10631122E-03 | 0.13200917E-13 |
3 | 0 | 5.3667923 | 0.15062465 | 0.15079716 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.83431181E-12 | -0.50336875E-16 | 0.17219122E-13 | 0.10872276E-17 |
8 | 3 | -0.40194411E-03 | 0.16336896E-06 | -0.58474983E-04 | 0.15995403E-12 |
9 | 2 | 1.7800021 | 0.35079984E-02 | 1.1712360 | -0.77059901E-04 |
10 | 1 | -7.0760347 | 0.89860417E-01 | -17.294077 | 0.34117400 |
11 | 0 | 5.4466643 | 0.56861144E-01 | 16.273129 | |
12 | 4 | 0.80726987E-12 | -0.63996452E-16 | 0.53126644E-14 | 0.11245955E-15 |
13 | 3 | -0.39330081E-03 | 0.25288080E-06 | -0.57134975E-04 | 0.15488884E-12 |
14 | 2 | 1.7597822 | 0.54786934E-02 | 1.1558494 | -0.75402625E-04 |
15 | 1 | -7.1021575 | 0.14112945 | -17.196294 | 0.33729066 |
16 | 0 | 5.5790139 | 0.89636898E-01 | 16.276747 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53126644E-14 | -0.63996452E-16 | 0.80726987E-12 | 0.11245955E-15 |
85 | 3 | -0.57134975E-04 | 0.25288080E-06 | -0.39330081E-03 | 0.15488884E-12 |
86 | 2 | 1.1558494 | 0.54786934E-02 | 1.7597822 | -0.75402625E-04 |
87 | 1 | -17.196294 | 0.14112945 | -7.1021575 | 0.33729066 |
88 | 0 | 16.276747 | 0.89636898E-01 | 5.5790139 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.45 | 28 | 1 | VerySmooth | 2.159 | 0.445 | 0.367 | 0.496 |
2 | SKYLIGHT_U_0.5_SHGC_0.55 | 29 | 1 | VerySmooth | 2.843 | 0.549 | 0.472 | 0.551 |
3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 30 | 1 | VerySmooth | 4.827 | 0.550 | 0.397 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.36619 | 0.43189 | 0.43189 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.47116 | 0.32579 | 0.32579 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.13907 | 0.13907 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 5.00274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.263 | 7.062E-004 | 4.613E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 7711.86947 | 9254.24336 | 0.64444 | 0.77333 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 6.97981E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10632.58092 | 12759.09711 | 0.30318 | 0.36381 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 18456.52021 | 22147.82425 | 1.20222 | 1.44267 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 6.97981E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 27630.47560 | 33156.57072 | 0.66368 | 0.79642 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40000 | 6.97982E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 83910.39643 | 100692.47571 | 2.05206 | 2.46247 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 11214.31 | 0.77333 | 0.77333 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15881.78 | 0.36381 | 0.36381 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 25492.34 | 1.44267 | 1.44267 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 52256.34 | 0.79642 | 0.79642 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77333 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44267 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.46247 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.46247 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 100692.48077 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 100692.47571 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77333 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77333 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77333 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77333 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77333 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.77333 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44267 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44267 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44267 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44267 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44267 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.44267 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.77333 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.44267 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77333 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77333 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77333 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77333 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77333 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77333 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38667 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51555 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12801.35739 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 12801.31000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6400.65500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6400.65500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12801.31000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25124.93441 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77333 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 856.19580 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25124.93441 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44267 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44267 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44267 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44267 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44267 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44267 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72134 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96178 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23922.17624 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26981.21000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13490.60500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13490.60500 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75641 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75641 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75641 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75641 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26981.21000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71071.09191 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44267 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1543.72189 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 71071.09191 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 12201.2 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 25861.3 | 16.80 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3389913898 | 0.2857008896 | Pass | Pass | 3.8343884782 | 16.3328982346 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6723533957 | 0.6199320179 | Pass | Pass | 0.7663970810 | 0.6793265063 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.6121722601E-005 | 2.4971613726E-005 | Pass | Pass | 2.9353286416E-002 | 2.9207883237E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.148 | 0.151 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.38_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.159 | 0.445 | 0.496 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.38_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.159 | 0.445 | 0.496 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.38_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.159 | 0.445 | 0.496 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.38_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.159 | 0.445 | 0.496 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.550 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.378 | 0.493 | 0.521 | ||||||||||||
North Total or Average | 6.51 | 2.159 | 0.445 | 0.496 | ||||||||||||
Non-North Total or Average | 26.02 | 3.683 | 0.505 | 0.527 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.993 | 2.841 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.993 | 2.841 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.993 | 2.841 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 8.8264 | 236.88 | 2090.80 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 56.91 | 168.00 | 49.67 | 0.0000 | Y | 19.49 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 10.2257 | 1393.41 | 14248.61 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 6.2431 | 3204.84 | 20008.05 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 58.04 | 0.0000 | Y | 217.99 |
Interior Lighting Total | 7.5174 | 4835.13 | 36347.45 | 399.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2090.80 | 606.33 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2090.80 | 209.08 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.05 | 2320.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 44.84 | 44.84 | 0.96 | |
EXTERIOR_LIGHTS_B | 6197.40 | AstronomicalClock | - | 83.06 | 71.59 | 83.29 | |
Exterior Lighting Total | 6311.20 | 84.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12801.31 | 10223.89 | 2577.42 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26981.21 | 20408.86 | 6572.35 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 12201.2 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 25861.3 | 16.80 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 100692.48 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25124.93 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 71071.09 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.46 | 228.79 | 92.91 | 1.00 | 3.46 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.77 | 856.20 | 1107.16 | 1.00 | 1.47 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1543.72 | 1070.05 | 1.00 | 1.37 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7711.87 | 9254.24 | 39.07 | 0.644 | 0.773 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00814 | 25.97 | 0.00698 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 18456.52 | 22147.82 | 15.89 | 1.202 | 1.443 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00792 | 26.99 | 0.00698 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00384 | 27.40 | 0.00698 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10632.58 | 12759.10 | 53.86 | 0.303 | 0.364 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00810 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27630.48 | 33156.57 | 23.80 | 0.664 | 0.796 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 15.56 | 15.56 | 0.00771 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 83910.40 | 100692.48 | 31.42 | 2.052 | 2.462 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.77 | 0.77 | 0.36 | 0.36 | 0.7733 | 0.7733 | 0.7733 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.44 | 1.44 | 0.80 | 0.80 | 1.4427 | 1.4427 | 1.4427 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 100692.481 | 100692.481 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 100692.48 | 100692.48 | 2.462471 | -10.59 | -10.59 | 0.00470085 | 43.33 | 26.90 | 0.01600000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 9.99 | 0.00774936 | 100.0000 | 100692.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 6400.655 | 0.000 | 0.773330 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 6400.65 | 6400.65 | 0.773330 | 24.17 | 15.83 | 0.00798292 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00697981 | 15.59 | 13.2265 | 23.90 | 0.00813582 | 43.4006 | 7711.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25124.934 | 25124.934 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25124.93 | 25124.93 | 0.773327 | 3.35 | 3.35 | 0.00584111 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 13.2266 | 21.10 | 0.00810037 | 51.2270 | 10632.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 13490.605 | 0.000 | 1.442670 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 13490.60 | 13490.60 | 1.442670 | 26.88 | 16.49 | 0.00764246 | 12.00 | 11.12 | 0.00800000 | 27.30 | 0.00697982 | 16.06 | 29.4393 | 26.70 | 0.00792075 | 35.7821 | 18403.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 71071.092 | 71071.092 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 71071.09 | 71071.09 | 1.442667 | -15.08 | -15.08 | 0.00363191 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 29.4394 | 15.56 | 0.00770805 | 69.0586 | 27630.48 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 100692.481 | 100692.481 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1854 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.462471 | 2.91911032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 100692.48 | 100692.48 | 1.0000 | 2.91911032 | 2.462471 | -10.59 | -10.59 | 0.00470085 | 1019.7 | 43.33 | 26.90 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100692.48 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 9.99 | 0.00774936 | 9.99 | 0.00774936 | 100.0000 | 100692.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6400.655 | 0.000 | 0.773330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6799 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 6400.65 | 6400.65 | 1.0000 | 0.91673577 | 0.773330 | 24.17 | 15.83 | 0.00798292 | 44614.3 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6400.65 | 25.97 | 0.00697981 | 15.59 | 0.10228487 | 13.2265 | 23.90 | 0.00813582 | 23.90 | 0.00813582 | 43.4006 | 7711.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25124.934 | 25124.934 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.773327 | 0.91673227 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25124.93 | 25124.93 | 1.0000 | 0.91673227 | 0.773327 | 3.35 | 3.35 | 0.00584111 | 18014.0 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25124.93 | -41.90 | 0.00006450 | -41.90 | 0.10228487 | 13.2266 | 21.05 | 0.00810037 | 21.10 | 0.00810037 | 51.2270 | 10632.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13490.605 | 0.000 | 1.442670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0470 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 13490.60 | 13490.60 | 1.0000 | 1.71019771 | 1.442670 | 26.88 | 16.49 | 0.00764246 | 46501.9 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13490.60 | 27.30 | 0.00697982 | 16.06 | 0.42471267 | 29.4393 | 26.70 | 0.00792006 | 26.70 | 0.00792075 | 35.7821 | 18403.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71071.092 | 71071.092 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.442667 | 1.71019415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 71071.09 | 71071.09 | 1.0000 | 1.71019415 | 1.442667 | -15.08 | -15.08 | 0.00363191 | -6174.2 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71071.09 | -41.90 | 0.00006450 | -41.90 | 0.42471267 | 29.4394 | 15.56 | 0.00770805 | 15.56 | 0.00770805 | 69.0586 | 27630.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.44 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2581.17 | 3180.17 | 2486.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2581.17 | 3180.17 | 2486.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 114.17 | 1.00 | 73.67 | 1.00 |
ZONE2 FINE STORAGE | 640.67 | 0.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 107.50 | 0.00 | 0.00 | 0.00 |
Facility | 807.67 | 1.33 | 73.67 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.309 | 0.226 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
Electricity:Building | 536.27 | 3893.02 | 16-APR-15:10 | 40468.48 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 48.66 | 699.44 | 12-MAR-17:10 | 3150.20 | 02-JAN-08:10 |
InteriorLights:Electricity | 399.77 | 3423.14 | 14-APR-17:10 | 30433.31 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.49 | 229.57 | 12-MAR-17:10 | 1315.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 399.77 | 3423.14 | 14-APR-17:10 | 30433.31 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.32 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 325.33 | 1768.71 | 05-MAR-11:00 | 25206.96 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 217.99 | 1768.71 | 05-MAR-11:00 | 17006.84 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 28.36 | 481.00 | 19-JAN-06:30 | 3129.90 | 11-JAN-13:00 |
WaterSystems:Electricity | 28.36 | 481.00 | 19-JAN-06:30 | 3129.90 | 11-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 28.36 | 481.00 | 19-JAN-06:30 | 3129.90 | 11-JAN-13:00 |
Fans:Electricity | 36.19 | 0.00 | 18-MAR-17:10 | 2628.71 | 04-JAN-13:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
ElectricityPurchased:Plant | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
Cogeneration:ElectricityPurchased | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
ElectricityNet:Plant | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
Cogeneration:ElectricityNet | 687.05 | 4374.02 | 16-APR-15:10 | 52098.57 | 13-JAN-15:40 |
Electricity:HVAC | 38.18 | 0.00 | 18-MAR-17:10 | 6856.00 | 21-JUL-16:00 |
General:Fans:Electricity | 36.19 | 0.00 | 18-MAR-17:10 | 2628.71 | 04-JAN-13:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.99 | 0.00 | 01-JAN-00:10 | 4456.08 | 21-JUL-16:00 |
ExteriorLights:Electricity | 84.25 | 0.00 | 01-JAN-11:20 | 6311.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 84.25 | 0.00 | 01-JAN-11:20 | 6311.20 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1342.26 | 0.00 | 18-MAR-17:10 | 224755.23 | 28-JAN-17:10 |
Gas:HVAC | 1342.26 | 0.00 | 18-MAR-17:10 | 224755.23 | 28-JAN-17:10 |
Heating:Gas | 1342.26 | 0.00 | 18-MAR-17:10 | 224755.23 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2013.99 | 0.00 | 18-MAR-17:10 | 346170.11 | 29-JAN-00:10 |
EnergyTransfer:Building | 974.86 | 0.00 | 18-MAR-17:10 | 173217.45 | 29-JAN-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 67.83 | 0.00 | 01-JAN-00:40 | 25917.41 | 27-FEB-07:50 |
Heating:EnergyTransfer | 948.75 | 0.00 | 18-MAR-17:10 | 173217.45 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 60.09 | 0.00 | 01-JAN-00:40 | 25917.41 | 27-FEB-07:50 |
Cooling:EnergyTransfer | 26.11 | 0.00 | 01-JAN-00:10 | 15206.45 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 7.74 | 0.00 | 01-JAN-00:10 | 5666.35 | 03-AUG-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 195.15 | 0.00 | 01-JAN-00:40 | 68509.48 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 176.78 | 0.00 | 01-JAN-00:40 | 68509.48 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.37 | 0.00 | 01-JAN-00:10 | 10014.39 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 711.89 | 0.00 | 09-FEB-11:50 | 101619.49 | 28-JAN-09:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 711.89 | 0.00 | 09-FEB-11:50 | 101619.49 | 28-JAN-09:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1039.13 | 0.00 | 18-MAR-17:10 | 177154.20 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1029.67 | 0.00 | 18-MAR-17:10 | 177154.20 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 9.46 | 0.00 | 01-JAN-00:10 | 19659.37 | 21-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 60.088 | -7.739 | 0.000 | 0.000 | 4.047 | 19.494 | 29.165 | 7.107 | 0.000 | 0.028 | 0.000 | 0.000 | -16.896 | 0.000 | -26.770 | -68.522 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 176.777 | -18.372 | 0.000 | 0.000 | 0.000 | 162.279 | 0.000 | 0.000 | 0.000 | 0.029 | 0.001 | 0.000 | 0.000 | 0.000 | -95.727 | -224.986 |
ZONE3 BULK STORAGE | 711.886 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 217.993 | 107.336 | 18.119 | 0.000 | 1.703 | 0.000 | 0.000 | -24.339 | 0.000 | -444.809 | -587.890 |
Total Facility | 711.886 | 0.000 | 236.865 | -26.111 | 0.000 | 0.000 | 4.047 | 399.767 | 136.501 | 25.226 | 0.000 | 1.759 | 0.002 | 0.000 | -41.236 | 0.000 | -567.306 | -881.398 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-AUG-05:01 | 0.00 | 0.00 | 0.00 | -11968.57 | 0.00 | 0.00 | 33.07 | 392.84 | 550.52 | 0.00 | 0.00 | 0.00 | 11587.62 | 0.00 | -191.00 | 0.00 | -404.48 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-13:52 | 0.00 | 0.00 | 0.00 | -27518.13 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 26405.35 | 0.00 | -0.00 | 0.00 | -312.08 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-13:52 | 0.00 | 0.00 | 0.00 | -27518.13 | 0.00 | 0.00 | 0.00 | 3525.60 | 469.88 | 5760.05 | 0.00 | 0.00 | 19200.71 | 0.00 | 0.00 | 0.00 | -1438.11 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 10-JAN-06:31 | 0.00 | 0.00 | 26721.01 | 0.00 | 0.00 | 0.00 | 55.18 | 392.84 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1215.16 | 0.00 | -2053.76 | -24450.63 |
ZONE2 FINE STORAGE | 29-JAN-08:61 | 0.00 | 0.00 | 73849.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15922.76 | -59351.65 |
ZONE3 BULK STORAGE | 28-JAN-09:00 | 101617.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15006.04 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1809.42 | 0.00 | -112979.58 | -10034.31 |
Total Facility | 25-FEB-00:01 | 101099.45 | 0.00 | 99385.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3802.01 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3324.49 | 0.00 | -99924.87 | -103557.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.7733 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.7733 | 0.1323 | 1.0000 | 0.1023 | 0.1323 | ||
PSZ-FINE STORAGE | 1.4427 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.4427 | 0.2944 | 1.0000 | 0.4247 | 0.2944 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.7733 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.7733 | 1.0000 | 1.0000 | 0.1023 | 0.1323 | ||
PSZ-FINE STORAGE | 1.4427 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.4427 | 1.0000 | 1.0000 | 0.4247 | 0.2944 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.7733 | 0.7733 | 0.7733 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.4427 | 1.4427 | 1.4427 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.7733 | 0.7733 | 0.7733 | 0.7733 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4427 | 1.4427 | 1.4427 | 1.4427 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.7733 | 0.7733 | 0.7733 | 0.1023 | 0.2811 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.4427 | 1.4427 | 1.4427 | 0.4247 | 0.5333 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.7733 | 0.7733 | 0.7733 | 0.7733 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4427 | 1.4427 | 1.4427 | 1.4427 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:10:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 73.67 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 74.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1342.26 | 224755.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 1.99 | 4456.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 399.77 | 30433.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 84.25 | 6311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.50 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 36.19 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.36 | 3129.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.50 | 687.05 |
Natural Gas | 0.00 | 1342.26 |
Additional | 0.00 | 0.00 |
Total | 136.50 | 2029.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 82.68 |
Space Heating | 0.00 |
Space Cooling | 0.41 |
Fans (All) | 7.48 |
Service Water Heating | 5.86 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 142.10 |
Subtotal | 142.10 |
Natural Gas [MJ/m2] | |
Space Heating | 277.61 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 277.61 |
Subtotal | 277.61 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.70 |
Space Heating | 66.14 |
Space Cooling | 0.10 |
Fans (All) | 1.78 |
Service Water Heating | 1.40 |
Receptacle Equipment | 6.73 |
Miscellaneous | 4.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 2967. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.265185E+12 |
February | 0.000 | 0.219699E+12 |
March | 0.000 | 0.204897E+12 |
April | 0.000 | 0.887694E+11 |
May | 0.000 | 0.249182E+10 |
June | 0.000 | 0.549668E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.403254E+08 |
September | 0.000 | 0.402402E+10 |
October | 0.000 | 0.109125E+12 |
November | 0.000 | 0.189063E+12 |
December | 0.000 | 0.258907E+12 |
Annual Sum or Average | 0.134226E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.265185E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.194844E+09 | 236.59 | 19-JAN-08:20 | -5.0 | -5.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.179290E+09 | 236.59 | 14-FEB-13:30 | -2.5 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -28.9 | -29.1 | 0.210511E+09 | 236.59 | 17-MAR-07:30 | -4.7 | -6.0 |
April | 1963320.22 | 234.42 | 29-APR-15:10 | 11.83 | 5.41 | 0.195162E+09 | 254.87 | 22-APR-15:00 | 15.00 | 6.58 |
May | 0.109517E+09 | 865.66 | 13-MAY-15:50 | 20.00 | 9.29 | 0.215981E+09 | 302.30 | 13-MAY-12:39 | 18.70 | 8.69 |
June | 0.175883E+10 | 11458.49 | 22-JUN-05:02 | 14.08 | 11.46 | 0.254428E+09 | 301.69 | 22-JUN-07:10 | 16.70 | 12.22 |
July | 0.304871E+10 | 11684.67 | 15-JUL-05:02 | 11.70 | 11.40 | 0.248461E+09 | 301.61 | 03-JUL-15:09 | 19.50 | 17.42 |
August | 0.246147E+10 | 11968.53 | 03-AUG-05:01 | 14.90 | 13.03 | 0.265279E+09 | 301.59 | 03-AUG-12:09 | 18.48 | 15.31 |
September | 0.358728E+09 | 1859.72 | 02-SEP-16:00 | 16.70 | 10.41 | 0.206186E+09 | 301.58 | 01-SEP-14:09 | 15.00 | 10.76 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.11 | 0.195020E+09 | 236.59 | 07-OCT-07:40 | 4.27 | 3.76 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.187142E+09 | 236.59 | 18-NOV-08:30 | -11.4 | -11.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.194936E+09 | 236.59 | 23-DEC-08:30 | -2.2 | -3.6 |
Annual Sum or Average | 0.773922E+10 | 0.254724E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.179290E+09 | 236.59 | -11.4 | -11.8 | ||
Maximum of Months | 0.304871E+10 | 11968.53 | 20.00 | 13.03 | 0.265279E+09 | 302.30 | 19.50 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73384.34 | 92.73 | 21-JAN-13:00 | -5.6 | -6.2 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 63279573.88 | 9393.90 | 15-FEB-15:25 | -7.2 | -8.5 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.591552E+09 | 8295.34 | 27-MAR-14:50 | -5.0 | -8.0 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.192541E+10 | 6543.54 | 19-APR-07:05 | -0.7 | -2.5 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.178998E+10 | 7469.94 | 12-MAY-06:10 | 7.67 | 3.16 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.211345E+10 | 7923.30 | 01-JUN-06:10 | 7.57 | 5.43 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.350600E+10 | 27519.34 | 23-JUL-13:52 | 25.00 | 15.24 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.349291E+10 | 8301.83 | 30-AUG-07:05 | 0.78 | -1.0 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.347904E+10 | 7297.10 | 16-SEP-07:05 | -0.1 | -0.4 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.138787E+10 | 10920.70 | 25-OCT-12:13 | -10.0 | -10.4 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 22464768.40 | 1442.69 | 04-NOV-14:00 | -9.4 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.183720E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.350600E+10 | 27519.34 | 25.00 | 15.24 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -28.9 | -29.1 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.11 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105331E+11 | 26720.95 | 10-JAN-06:31 | -21.7 |
February | 0.925712E+10 | 26626.98 | 17-FEB-06:31 | -23.1 |
March | 0.912213E+10 | 26637.40 | 28-MAR-05:31 | -15.8 |
April | 0.474208E+10 | 26276.82 | 11-APR-05:32 | -5.2 |
May | 0.123208E+10 | 25433.64 | 04-MAY-05:42 | 3.62 |
June | 0.114043E+09 | 24800.58 | 01-JUN-05:02 | 7.20 |
July | 37525291.99 | 1168.56 | 26-JUL-06:07 | 11.70 |
August | 97560633.98 | 6965.73 | 31-AUG-06:05 | -1.5 |
September | 0.127807E+10 | 25412.54 | 26-SEP-05:42 | 0.10 |
October | 0.512942E+10 | 26512.64 | 31-OCT-05:32 | -18.0 |
November | 0.849283E+10 | 26708.09 | 27-NOV-06:31 | -26.7 |
December | 0.100524E+11 | 26660.93 | 12-DEC-06:31 | -23.0 |
Annual Sum or Average | 0.600884E+11 | |||
Minimum of Months | 37525291.99 | 1168.56 | -26.7 | |
Maximum of Months | 0.105331E+11 | 26720.95 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352952E+11 | 73849.55 | 29-JAN-08:61 | -26.0 |
February | 0.293863E+11 | 73822.61 | 26-FEB-04:01 | -25.6 |
March | 0.262778E+11 | 73231.43 | 02-MAR-04:42 | -26.6 |
April | 0.125453E+11 | 73268.45 | 02-APR-20:22 | -12.8 |
May | 0.547898E+09 | 63039.85 | 03-MAY-05:07 | 4.40 |
June | 0.128523E+09 | 1531.47 | 02-JUN-07:00 | 9.40 |
July | 0.107168E+09 | 1600.20 | 20-JUL-07:00 | 14.40 |
August | 0.138972E+09 | 1622.50 | 29-AUG-07:00 | 7.80 |
September | 0.886527E+09 | 58901.48 | 27-SEP-05:01 | 0.00 |
October | 0.139414E+11 | 72579.41 | 31-OCT-03:02 | -16.4 |
November | 0.242191E+11 | 72602.01 | 10-NOV-02:42 | -18.2 |
December | 0.333030E+11 | 72706.70 | 15-DEC-01:22 | -30.9 |
Annual Sum or Average | 0.176777E+12 | |||
Minimum of Months | 0.107168E+09 | 1531.47 | -30.9 | |
Maximum of Months | 0.352952E+11 | 73849.55 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142452E+12 | 101619.49 | 28-JAN-09:00 | -20.0 |
February | 0.118270E+12 | 101524.54 | 26-FEB-04:01 | -25.6 |
March | 0.110814E+12 | 101029.15 | 02-MAR-05:00 | -26.7 |
April | 0.475152E+11 | 101009.77 | 02-APR-20:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.575822E+11 | 85956.77 | 27-OCT-04:00 | -17.8 |
November | 0.966493E+11 | 91592.78 | 10-NOV-01:52 | -20.0 |
December | 0.138604E+12 | 101128.34 | 22-DEC-14:10 | -23.7 |
Annual Sum or Average | 0.711887E+12 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.142452E+12 | 101619.49 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.184508E+10 | 1315.15 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.163365E+10 | 1315.15 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.169057E+10 | 1315.15 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.147664E+10 | 1315.15 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.148426E+10 | 1188.02 | 02-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.139720E+10 | 1188.02 | 07-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.144203E+10 | 1188.02 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.156559E+10 | 1188.02 | 03-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.158341E+10 | 1315.15 | 13-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.175665E+10 | 1315.15 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.177220E+10 | 1315.15 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.184667E+10 | 1315.15 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.194940E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.139720E+10 | 1188.02 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.184667E+10 | 1315.15 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.134983E+11 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138856E+11 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | ||||
Minimum of Months | 0.123544E+11 | 12111.32 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.189474E+11 | 17006.84 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.171601E+11 | 17006.84 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.192452E+11 | 17006.84 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.176307E+11 | 16349.24 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.179571E+11 | 16349.24 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.175082E+11 | 16349.24 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.173328E+11 | 16349.24 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.185949E+11 | 17006.84 | 30-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.179125E+11 | 17006.84 | 18-SEP-14:20 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.185695E+11 | 17006.84 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.181805E+11 | 17006.84 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.189544E+11 | 17006.84 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.217993E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.171601E+11 | 16349.24 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.192452E+11 | 17006.84 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.184508E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385012E+10 |
February | 0.500553E+09 | 0.163365E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300722E+10 |
March | 0.587605E+09 | 0.169057E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341991E+10 |
April | 0.544079E+09 | 0.147664E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208741E+10 |
May | 0.565842E+09 | 0.148426E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2618.70 | 0.113380E+10 |
June | 0.565842E+09 | 0.139720E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8864085.35 | 0.753556E+09 |
July | 0.544079E+09 | 0.144203E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15341328.01 | 0.611601E+09 |
August | 0.587605E+09 | 0.156559E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3330623.00 | 0.100814E+10 |
September | 0.544079E+09 | 0.158341E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129316E+10 |
October | 0.544079E+09 | 0.175665E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249066E+10 |
November | 0.522316E+09 | 0.177220E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334226E+10 |
December | 0.544079E+09 | 0.184667E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377216E+10 |
Annual Sum or Average | 0.659424E+10 | 0.194940E+11 | 0.291647E+11 | 27538655.07 | 0.267700E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.139720E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611601E+09 |
Maximum of Months | 0.587605E+09 | 0.184667E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15341328.01 | 0.385012E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115213E+11 |
February | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953488E+10 |
March | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137408E+11 |
April | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121607E+11 |
May | 0.00 | 0.138856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4211283.69 | 0.612297E+10 |
June | 0.00 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2180743.28 | 0.464881E+10 |
July | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21996767.20 | 0.414112E+10 |
August | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249069.41 | 0.539131E+10 |
September | 0.00 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466033E+10 |
October | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107062E+11 |
November | 0.00 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431299E+10 |
December | 0.00 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878537E+10 |
Annual Sum or Average | 0.162279E+12 | 28637863.58 | 0.957268E+11 | ||||||
Minimum of Months | 0.00 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414112E+10 |
Maximum of Months | 0.00 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21996767.20 | 0.137408E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.189474E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383577E+11 |
February | 0.00 | 0.171601E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313717E+11 |
March | 0.00 | 0.192452E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434718E+11 |
April | 0.00 | 0.176307E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63612427.49 | 0.315731E+11 |
May | 0.00 | 0.179571E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627600E+09 | 0.144587E+11 |
June | 0.00 | 0.175082E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263143E+09 | 0.118291E+11 |
July | 0.00 | 0.173328E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98205585.23 | 0.137125E+11 |
August | 0.00 | 0.185949E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70745033.37 | 0.188768E+11 |
September | 0.00 | 0.179125E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150291E+11 |
October | 0.00 | 0.185695E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14585440.46 | 0.312437E+11 |
November | 0.00 | 0.181805E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143154E+11 |
December | 0.00 | 0.189544E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312532E+11 |
Annual Sum or Average | 0.217993E+12 | 0.107336E+12 | 0.113789E+10 | 0.295493E+12 | |||||
Minimum of Months | 0.00 | 0.171601E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118291E+11 |
Maximum of Months | 0.00 | 0.192452E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627600E+09 | 0.434718E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1315.15 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15694.77 | 12-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1315.15 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14760.87 | 27-FEB-07:30 |
March | 659.25 | 01-MAR-08:09 | 1315.15 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 13131.75 | 01-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1315.15 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11167.84 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1188.02 | 02-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 30-MAY-18:00 | 4657.27 | 16-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1188.02 | 07-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.41 | 29-JUN-16:10 | 3146.16 | 02-JUN-06:05 |
July | 659.25 | 01-JUL-07:10 | 1188.02 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 21-JUL-16:10 | 3630.13 | 17-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1188.02 | 03-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.98 | 11-AUG-16:10 | 5570.08 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1315.15 | 13-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6471.47 | 29-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1315.15 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 10755.88 | 31-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1315.15 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13325.83 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1315.15 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14284.50 | 15-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1188.02 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3146.16 | |||||
Maximum of Months | 659.25 | 1315.15 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 15694.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 12111.32 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 39817.78 | 28-JAN-17:00 |
February | 0.00 | 12111.32 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 24061.30 | 23-FEB-17:00 |
March | 0.00 | 12111.32 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 18292.65 | 25-MAR-15:10 |
April | 0.00 | 12111.32 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20603.27 | 01-APR-18:52 |
May | 0.00 | 12111.32 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804.19 | 30-MAY-18:00 | 10573.92 | 27-MAY-08:00 |
June | 0.00 | 12111.32 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.94 | 30-JUN-15:10 | 9806.90 | 24-JUN-21:00 |
July | 0.00 | 12111.32 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.74 | 21-JUL-16:00 | 6131.57 | 04-JUL-17:00 |
August | 0.00 | 12111.32 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.96 | 23-AUG-18:00 | 9902.32 | 29-AUG-20:00 |
September | 0.00 | 12111.32 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5874.44 | 29-SEP-07:00 |
October | 0.00 | 12111.32 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 13656.34 | 27-OCT-06:10 |
November | 0.00 | 12111.32 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13371.25 | 03-NOV-20:00 |
December | 0.00 | 12111.32 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15525.64 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5874.44 | |||
Maximum of Months | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.74 | 39817.78 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 17006.84 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 110518.68 | 28-JAN-15:00 |
February | 0.00 | 17006.84 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 76223.56 | 25-FEB-12:00 |
March | 0.00 | 17006.84 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 57056.07 | 25-MAR-09:00 |
April | 0.00 | 16349.24 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2316.07 | 22-APR-14:00 | 54427.73 | 01-APR-18:52 |
May | 0.00 | 16349.24 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8403.91 | 30-MAY-18:00 | 37601.44 | 27-MAY-11:00 |
June | 0.00 | 16349.24 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6460.43 | 03-JUN-16:00 | 28210.26 | 24-JUN-21:00 |
July | 0.00 | 16349.24 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9579.57 | 21-JUL-16:00 | 17763.51 | 04-JUL-17:00 |
August | 0.00 | 17006.84 | 30-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3802.40 | 23-AUG-18:00 | 35588.23 | 31-AUG-09:00 |
September | 0.00 | 17006.84 | 18-SEP-14:20 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 18343.02 | 21-SEP-14:00 |
October | 0.00 | 17006.84 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.62 | 01-OCT-16:30 | 40557.28 | 31-OCT-09:00 |
November | 0.00 | 17006.84 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 41183.86 | 01-NOV-09:00 |
December | 0.00 | 17006.84 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58599.12 | 22-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 16349.24 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17763.51 | ||||
Maximum of Months | 0.00 | 17006.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 9579.57 | 110518.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 1881.72 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.19 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1505.37 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.77 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 1505.37 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 |
April | 234.42 | 29-APR-15:10 | 659.25 | 846.08 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.23 |
May | 865.66 | 13-MAY-15:50 | 659.25 | 802.24 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 |
June | 11458.49 | 22-JUN-05:02 | 362.59 | 1394.57 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.35 |
July | 11684.67 | 15-JUL-05:02 | 435.11 | 1901.33 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 |
August | 11968.53 | 03-AUG-05:01 | 507.62 | 2749.86 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.48 |
September | 1859.72 | 02-SEP-16:00 | 659.25 | 846.08 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.68 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 752.69 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.13 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 376.34 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.48 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1505.37 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 376.34 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11968.53 | 659.25 | 2749.86 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 92.73 | 21-JAN-13:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9393.90 | 15-FEB-15:25 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.66 |
March | 8295.34 | 27-MAR-14:50 | 0.00 | 24222.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4100.00 |
April | 6543.54 | 19-APR-07:05 | 0.00 | 21372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7469.94 | 12-MAY-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.85 |
June | 7923.30 | 01-JUN-06:10 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.72 |
July | 27519.34 | 23-JUL-13:52 | 0.00 | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.08 |
August | 8301.83 | 30-AUG-07:05 | 0.00 | 21372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5116.81 |
September | 7297.10 | 16-SEP-07:05 | 0.00 | 21372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4860.17 |
October | 10920.70 | 25-OCT-12:13 | 0.00 | 36333.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1913.11 |
November | 1442.69 | 04-NOV-14:00 | 0.00 | 12111.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27519.34 | 0.00 | 36333.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5116.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 10004.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21455.03 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8003.22 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16864.25 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8003.22 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8408.25 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.76 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3951.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.98 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4172.59 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8428.96 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5431.62 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 4001.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9325.94 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17147.52 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8003.22 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 10004.02 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.76 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.639586E+11 | 52098.57 | 13-JAN-15:39 | 0.265185E+12 | 224755.23 | 28-JAN-17:10 |
February | 0.560576E+11 | 51137.19 | 06-FEB-09:20 | 0.219699E+12 | 218107.36 | 24-FEB-17:00 |
March | 0.610774E+11 | 47663.80 | 17-MAR-07:10 | 0.204897E+12 | 200557.21 | 16-MAR-07:00 |
April | 0.540867E+11 | 44660.54 | 08-APR-14:00 | 0.887694E+11 | 187186.54 | 02-APR-19:49 |
May | 0.530407E+11 | 44763.34 | 09-MAY-12:50 | 0.249182E+10 | 25149.55 | 01-MAY-05:10 |
June | 0.511857E+11 | 45764.73 | 30-JUN-14:50 | 54966753.10 | 6281.23 | 01-JUN-05:10 |
July | 0.515412E+11 | 47482.23 | 29-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.562370E+11 | 45852.71 | 11-AUG-14:09 | 40325402.85 | 6455.74 | 31-AUG-06:10 |
September | 0.551040E+11 | 44828.45 | 30-SEP-14:39 | 0.402402E+10 | 30393.81 | 30-SEP-05:10 |
October | 0.594646E+11 | 51119.39 | 31-OCT-08:09 | 0.109125E+12 | 160447.89 | 31-OCT-05:10 |
November | 0.604409E+11 | 51950.00 | 30-NOV-15:39 | 0.189063E+12 | 174119.11 | 29-NOV-08:09 |
December | 0.648541E+11 | 52098.15 | 30-DEC-15:39 | 0.258907E+12 | 197069.70 | 01-DEC-17:00 |
Annual Sum or Average | 0.687048E+12 | 0.134226E+13 | ||||
Minimum of Months | 0.511857E+11 | 44660.54 | 0.00 | 0.00 | ||
Maximum of Months | 0.648541E+11 | 52098.57 | 0.265185E+12 | 224755.23 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.342907E+11 | 0.122580E+11 | 0.112984E+11 | 0.00 | 0.368156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242991E+10 | 0.00 |
February | 0.311482E+11 | 0.896649E+10 | 0.103734E+11 | 0.00 | 0.335838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221123E+10 | 0.00 |
March | 0.352086E+11 | 0.754358E+10 | 0.121016E+11 | 0.00 | 0.371641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250722E+10 | 0.00 |
April | 0.324825E+11 | 0.497975E+10 | 0.112578E+11 | 0.00 | 0.298483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238187E+10 | 0.00 |
May | 0.333270E+11 | 0.306140E+10 | 0.117000E+11 | 0.00 | 0.249346E+10 | 0.00 | 0.00 | 3132096.29 | 0.00 | 0.00 | 0.00 | 0.245575E+10 | 0.00 |
June | 0.326679E+11 | 0.157122E+10 | 0.116594E+11 | 0.00 | 0.247396E+10 | 0.00 | 0.00 | 0.452199E+09 | 0.00 | 0.00 | 0.00 | 0.236113E+10 | 0.00 |
July | 0.322731E+11 | 0.225843E+10 | 0.112984E+11 | 0.00 | 0.239343E+10 | 0.00 | 0.00 | 0.987773E+09 | 0.00 | 0.00 | 0.00 | 0.233005E+10 | 0.00 |
August | 0.344333E+11 | 0.420964E+10 | 0.121016E+11 | 0.00 | 0.257330E+10 | 0.00 | 0.00 | 0.541435E+09 | 0.00 | 0.00 | 0.00 | 0.237774E+10 | 0.00 |
September | 0.328711E+11 | 0.629871E+10 | 0.112578E+11 | 0.00 | 0.240371E+10 | 0.00 | 0.00 | 6251162.50 | 0.00 | 0.00 | 0.00 | 0.226642E+10 | 0.00 |
October | 0.338244E+11 | 0.889922E+10 | 0.112984E+11 | 0.00 | 0.310672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233590E+10 | 0.00 |
November | 0.329406E+11 | 0.109791E+11 | 0.108562E+11 | 0.00 | 0.337692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228807E+10 | 0.00 |
December | 0.342994E+11 | 0.132199E+11 | 0.112984E+11 | 0.00 | 0.362391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241263E+10 | 0.00 |
Annual Sum or Average | 0.399767E+12 | 0.842454E+11 | 0.136501E+12 | 0.361866E+11 | 0.00 | 0.199079E+10 | 0.283579E+11 | ||||||
Minimum of Months | 0.311482E+11 | 0.157122E+10 | 0.103734E+11 | 0.00 | 0.239343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221123E+10 | 0.00 |
Maximum of Months | 0.352086E+11 | 0.132199E+11 | 0.121016E+11 | 0.00 | 0.371641E+10 | 0.00 | 0.00 | 0.987773E+09 | 0.00 | 0.00 | 0.00 | 0.250722E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.265185E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.219699E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.204897E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.887694E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.249182E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 54966753.10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 40325402.85 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.402402E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.109125E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189063E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.258907E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134226E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.265185E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30433.31 | 02-JAN-09:09 | 6311.20 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2628.71 | 04-JAN-13:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30433.31 | 01-FEB-09:09 | 6311.20 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2628.71 | 01-FEB-13:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30433.31 | 03-MAR-09:09 | 6311.20 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2628.71 | 03-MAR-16:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29775.71 | 04-APR-08:09 | 6311.20 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2628.71 | 01-APR-06:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29648.58 | 02-MAY-08:09 | 6311.20 | 01-MAY-21:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2399.92 | 27-MAY-06:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29648.58 | 07-JUN-08:09 | 6311.20 | 01-JUN-22:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 2399.92 | 13-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29648.58 | 06-JUL-08:09 | 6311.20 | 11-JUL-22:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 2399.92 | 07-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30306.18 | 30-AUG-08:09 | 6311.20 | 01-AUG-21:00 | 10035.17 | 01-AUG-07:10 | 0.00 | 2399.92 | 01-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30433.31 | 20-SEP-14:30 | 6311.20 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 2399.92 | 25-SEP-07:49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30433.31 | 02-OCT-08:09 | 6311.20 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2628.71 | 17-OCT-16:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30433.31 | 01-NOV-08:09 | 6311.20 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2628.71 | 02-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30433.31 | 01-DEC-09:09 | 6311.20 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2628.71 | 08-DEC-09:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29648.58 | 6311.20 | 10035.17 | 0.00 | 2399.92 | 0.00 | 0.00 | |||||
Maximum of Months | 30433.31 | 6311.20 | 10035.17 | 0.00 | 2628.71 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3129.90 | 11-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3129.63 | 27-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3129.52 | 16-MAR-11:50 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3129.60 | 22-APR-11:00 | 0.00 |
May | 269.76 | 13-MAY-15:50 | 0.00 | 0.00 | 0.00 | 3129.61 | 03-MAY-11:20 | 0.00 |
June | 2985.79 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3038.63 | 01-JUN-11:30 | 0.00 |
July | 4456.08 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2872.35 | 05-JUL-11:39 | 0.00 |
August | 2358.90 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2762.95 | 01-AUG-11:50 | 0.00 |
September | 391.83 | 02-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2740.29 | 28-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2853.95 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2988.23 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3129.24 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2740.29 | 0.00 | ||
Maximum of Months | 4456.08 | 0.00 | 0.00 | 0.00 | 3129.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52098.57 | 13-JAN-15:39 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51137.19 | 06-FEB-09:20 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47663.80 | 17-MAR-07:10 | 27007.64 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44660.54 | 08-APR-14:00 | 29306.64 | 10035.17 | 0.00 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44763.34 | 09-MAY-12:50 | 29648.58 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45764.73 | 30-JUN-14:50 | 27947.61 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 2957.47 | 0.00 |
July | 47482.23 | 29-JUL-14:00 | 28649.04 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 4109.33 | 0.00 |
August | 45852.71 | 11-AUG-14:09 | 29477.61 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 1692.11 | 0.00 |
September | 44828.45 | 30-SEP-14:39 | 30135.21 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51119.39 | 31-OCT-08:09 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51950.00 | 30-NOV-15:39 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52098.15 | 30-DEC-15:39 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44660.54 | 27007.64 | 10035.17 | 0.00 | 0.00 | 2399.92 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52098.57 | 30433.31 | 10035.17 | 6311.20 | 0.00 | 2628.71 | 0.00 | 0.00 | 4109.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 224755.23 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 218107.36 | 24-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 200557.21 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 187186.54 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 25149.55 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6281.23 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 6455.74 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 30393.81 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 160447.89 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 174119.11 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 197069.70 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 224755.23 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.33 | 17.24 | 12.00 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 16.72 | 10.00 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15.50 | 17.76 | 10.50 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9.67 | 19.14 | 8.83 | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3.17 | 20.23 | 3.17 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
September | 2.67 | 20.24 | 2.67 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9.17 | 19.28 | 8.17 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.17 | 17.54 | 8.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.67 | 17.96 | 9.50 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.17 | 17.81 | 73.67 | 19.35 | 1.00 | 24.49 | 1.00 | 24.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.33 | 20.24 | 12.00 | 20.24 | 0.50 | 24.50 | 0.50 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.67 | 14.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99.67 | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96.00 | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53.67 | 14.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.17 | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.00 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54.00 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 106.67 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114.83 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.67 | 14.52 | 0.00 | 0.33 | 27.30 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.83 | 14.98 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.00 | 7.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40.50 | 8.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.50 | 8.21 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.00 | 8.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.01 | 276.00 | 21.01 | 276.00 | 21.01 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
May | 312.00 | 21.68 | 205.33 | 21.19 | 205.33 | 21.19 |
June | 251.67 | 23.51 | 9.00 | 21.45 | 8.17 | 21.20 |
July | 49.33 | 23.63 | 58.83 | 23.91 | 0.00 | 0.00 |
August | 179.17 | 23.49 | 38.50 | 23.65 | 3.50 | 21.06 |
September | 300.00 | 21.61 | 181.50 | 21.12 | 181.50 | 21.12 |
October | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
November | 288.00 | 21.03 | 288.00 | 21.03 | 288.00 | 21.03 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3180.17 | 21.53 | 2581.17 | 21.16 | 2486.50 | 21.06 |
Minimum of Months | 49.33 | 21.01 | 9.00 | 21.01 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.63 | 324.00 | 23.91 | 324.00 | 21.20 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 14276503.18 | 3132096.29 | 6.50 | 14276503.18 | 0.00 | 0.00 | 0.21 | 13-MAY-15:50 | 0.00 | 01-MAY-00:10 | 1243.82 | 13-MAY-15:50 | 1243.82 | 13-MAY-15:50 | 0.00 | 13-MAY-14:10 | 269.76 | 13-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 0.193829E+10 | 0.405656E+09 | 220.90 | 0.188916E+10 | 49133015.58 | 0.00 | 1.00 | 22-JUN-05:02 | 0.00 | 01-JUN-00:10 | 12887.68 | 22-JUN-05:02 | 12887.68 | 22-JUN-05:02 | 693.90 | 30-JUN-12:00 | 2593.94 | 22-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.357095E+10 | 0.729552E+09 | 267.09 | 0.339621E+10 | 0.174740E+09 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 13812.09 | 26-JUL-05:02 | 13091.66 | 20-JUL-05:02 | 2101.04 | 26-JUL-05:04 | 2750.22 | 26-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.246048E+10 | 0.507479E+09 | 241.60 | 0.236721E+10 | 93271937.84 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 13488.46 | 04-AUG-05:02 | 13258.57 | 03-AUG-05:01 | 882.80 | 04-AUG-05:03 | 2696.71 | 04-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 28716344.21 | 6251162.50 | 8.33 | 28716344.21 | 0.00 | 0.00 | 0.30 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 | 1829.41 | 02-SEP-16:00 | 1829.41 | 02-SEP-16:00 | 0.00 | 02-SEP-13:40 | 391.83 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.801272E+10 | 0.165207E+10 | 744.42 | 0.769557E+10 | 0.317145E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.357095E+10 | 0.729552E+09 | 267.09 | 0.339621E+10 | 0.174740E+09 | 0.00 | 1.00 | 0.00 | 13812.09 | 13258.57 | 2101.04 | 2750.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.194915E+09 | 46543697.78 | 29.83 | 0.189438E+09 | 5476657.58 | 0.00 | 0.55 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7609.79 | 30-JUN-15:00 | 7609.79 | 30-JUN-15:00 | 903.70 | 30-JUN-12:00 | 1819.35 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.111161E+10 | 0.258222E+09 | 87.18 | 0.109853E+10 | 13080718.30 | 0.00 | 1.00 | 23-JUL-11:42 | 0.00 | 01-JUL-00:10 | 27874.87 | 23-JUL-11:42 | 27003.44 | 23-JUL-15:02 | 3053.77 | 23-JUL-11:50 | 6056.92 | 23-JUL-15:02 | 0.00 | 01-JUL-00:10 |
August | 0.144413E+09 | 33956685.67 | 36.17 | 0.139265E+09 | 5147787.94 | 0.00 | 0.38 | 11-AUG-16:00 | 0.00 | 01-AUG-00:10 | 4968.15 | 11-AUG-16:00 | 4968.15 | 11-AUG-16:00 | 286.16 | 04-AUG-12:20 | 1174.97 | 11-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.145094E+10 | 0.338722E+09 | 153.18 | 0.142724E+10 | 23705163.82 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.111161E+10 | 0.258222E+09 | 87.18 | 0.109853E+10 | 13080718.30 | 0.00 | 1.00 | 0.00 | 27874.87 | 27003.44 | 3053.77 | 6056.92 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 332.83 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.75 | 284.71 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 43.15 | 202.76 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 203.10 | 103.92 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 215.96 | 47.12 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 243.15 | 31.55 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 197.38 | 40.48 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 151.20 | 59.48 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 71.21 | 92.24 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 10.32 | 176.50 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.61 | 320.28 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 353.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 95.28 | 169.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 31.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 243.15 | 353.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 332.83 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.75 | 284.71 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 43.15 | 202.76 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 203.10 | 103.92 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 215.96 | 47.12 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 243.15 | 31.55 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 197.38 | 40.48 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 151.20 | 59.48 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 71.21 | 92.24 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 10.32 | 176.50 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.61 | 320.28 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 353.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 95.28 | 169.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 31.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 243.15 | 353.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 195.79 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 175.49 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 1.06 | 130.57 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.88 | 15.99 | 64.26 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.63 | 51.32 | 23.85 | 0.00 | 0.00 | 744.00 |
June | 99.37 | 21.81 | 77.56 | 78.47 | 13.60 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.56 | 19.75 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 29.43 | 33.13 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.70 | 56.88 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.68 | 108.53 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 192.54 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 206.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.80 | 101.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 13.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.37 | 21.81 | 77.56 | 78.47 | 206.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 195.79 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 175.49 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 1.06 | 130.57 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.87 | 15.99 | 64.26 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.62 | 51.32 | 23.85 | 0.00 | 0.00 | 744.00 |
June | 99.36 | 21.81 | 77.56 | 78.47 | 13.60 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.56 | 19.75 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 29.43 | 33.13 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.70 | 56.88 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.68 | 108.53 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 192.54 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 206.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.80 | 101.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 13.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.36 | 21.81 | 77.56 | 78.47 | 206.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.23 | 2.13 | 0.00 | 152.65 | 0.00 | 0.00 | 744.00 |
February | 12.02 | 3.06 | 8.96 | 0.06 | 129.56 | 0.00 | 0.00 | 672.00 |
March | 42.02 | 18.08 | 23.94 | 29.00 | 85.87 | 0.00 | 0.00 | 744.00 |
April | 84.04 | 45.46 | 38.58 | 96.89 | 44.24 | 0.00 | 0.00 | 720.00 |
May | 109.31 | 62.20 | 47.11 | 139.43 | 22.48 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 59.04 | 59.45 | 149.73 | 16.02 | 0.00 | 0.00 | 720.00 |
July | 106.33 | 51.39 | 54.94 | 129.20 | 22.58 | 0.00 | 0.00 | 744.00 |
August | 80.16 | 38.94 | 41.23 | 91.09 | 32.18 | 0.00 | 0.00 | 744.00 |
September | 43.48 | 17.35 | 26.14 | 41.42 | 42.53 | 0.00 | 0.00 | 720.00 |
October | 17.92 | 4.47 | 13.45 | 8.96 | 67.56 | 9.00 | 0.00 | 744.00 |
November | 4.48 | 0.40 | 4.08 | 0.00 | 149.88 | 0.00 | 0.00 | 720.00 |
December | 0.66 | 0.01 | 0.64 | 0.00 | 163.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 51.98 | 25.17 | 26.81 | 57.46 | 77.18 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 0.66 | 0.01 | 0.64 | 0.00 | 16.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 62.20 | 59.45 | 149.73 | 163.85 | 9.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.891451E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 6646378.17 | 0.688768E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.115584E+09 | 0.543070E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.526446E+09 | 0.269371E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.578424E+09 | 0.126200E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.630256E+09 | 81767819.10 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.528666E+09 | 0.108416E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.404980E+09 | 0.159316E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.184583E+09 | 0.239075E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 27633642.45 | 0.472747E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1581314.13 | 0.830164E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.947662E+09 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.300480E+10 | 0.535801E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 81767819.10 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.630256E+09 | 0.947662E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.891451E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 6646378.17 | 0.688768E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.115584E+09 | 0.543070E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.526446E+09 | 0.269371E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.578424E+09 | 0.126200E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.630256E+09 | 81767819.10 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.528666E+09 | 0.108416E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.404980E+09 | 0.159316E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.184583E+09 | 0.239075E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 27633642.45 | 0.472747E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1581314.13 | 0.830164E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.947662E+09 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.300480E+10 | 0.535801E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 81767819.10 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.630256E+09 | 0.947662E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242543.39 | 0.00 | 6242543.39 | 0.00 | 0.524397E+09 |
February | 24924571.43 | 0.00 | 24924571.43 | 0.00 | 0.424540E+09 |
March | 74024404.27 | 24119.60 | 74000284.67 | 2836433.47 | 0.349726E+09 |
April | 0.130317E+09 | 3632441.26 | 0.126684E+09 | 41445136.85 | 0.166553E+09 |
May | 0.206426E+09 | 33332414.96 | 0.173094E+09 | 0.137466E+09 | 63880969.17 |
June | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.203400E+09 | 35240168.57 |
July | 0.224614E+09 | 36957267.76 | 0.187657E+09 | 0.170252E+09 | 52897994.97 |
August | 0.144295E+09 | 7793310.77 | 0.136502E+09 | 78817736.05 | 88739432.60 |
September | 77681748.17 | 222120.81 | 77459627.36 | 19968890.17 | 0.147441E+09 |
October | 38847535.24 | 0.00 | 38847535.24 | 1814435.44 | 0.290680E+09 |
November | 11666868.70 | 0.00 | 11666868.70 | 0.00 | 0.499073E+09 |
December | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 0.554342E+09 |
Annual Sum or Average | 0.119849E+10 | 0.138486E+09 | 0.106001E+10 | 0.656001E+09 | 0.319751E+10 |
Minimum of Months | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 35240168.57 |
Maximum of Months | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.203400E+09 | 0.554342E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242317.75 | 0.00 | 6242317.75 | 0.00 | 0.524396E+09 |
February | 24923727.57 | 0.00 | 24923727.57 | 0.00 | 0.424539E+09 |
March | 74022047.32 | 24118.47 | 73997928.85 | 2836068.46 | 0.349727E+09 |
April | 0.130313E+09 | 3632271.00 | 0.126681E+09 | 41442689.24 | 0.166554E+09 |
May | 0.206419E+09 | 33330852.62 | 0.173088E+09 | 0.137459E+09 | 63880844.20 |
June | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.203391E+09 | 35240145.94 |
July | 0.224606E+09 | 36955535.52 | 0.187651E+09 | 0.170244E+09 | 52898073.31 |
August | 0.144290E+09 | 7792945.49 | 0.136497E+09 | 78813455.23 | 88739468.19 |
September | 77679181.44 | 222110.40 | 77457071.05 | 19967362.03 | 0.147441E+09 |
October | 38846204.45 | 0.00 | 38846204.45 | 1814194.39 | 0.290680E+09 |
November | 11666447.01 | 0.00 | 11666447.01 | 0.00 | 0.499072E+09 |
December | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 0.554341E+09 |
Annual Sum or Average | 0.119845E+10 | 0.138480E+09 | 0.105997E+10 | 0.655967E+09 | 0.319751E+10 |
Minimum of Months | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 35240145.94 |
Maximum of Months | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.203391E+09 | 0.554341E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6319356.12 | 615405.52 | 5703950.60 | 0.00 | 0.408863E+09 |
February | 29080264.55 | 7402332.87 | 21677931.68 | 154967.73 | 0.313442E+09 |
March | 0.112535E+09 | 48413136.32 | 64121571.91 | 77676348.31 | 0.230003E+09 |
April | 0.217837E+09 | 0.117828E+09 | 0.100009E+09 | 0.251143E+09 | 0.114668E+09 |
May | 0.292765E+09 | 0.166597E+09 | 0.126168E+09 | 0.373451E+09 | 60197663.48 |
June | 0.307119E+09 | 0.153025E+09 | 0.154094E+09 | 0.388105E+09 | 41519659.10 |
July | 0.284782E+09 | 0.137643E+09 | 0.147139E+09 | 0.346047E+09 | 60479369.80 |
August | 0.214707E+09 | 0.104286E+09 | 0.110421E+09 | 0.243970E+09 | 86180131.40 |
September | 0.112710E+09 | 44967401.07 | 67743064.69 | 0.107364E+09 | 0.110232E+09 |
October | 47995938.53 | 11969345.58 | 36026592.94 | 23991448.83 | 0.180953E+09 |
November | 11609708.57 | 1027778.15 | 10581930.41 | 0.00 | 0.388497E+09 |
December | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 0.438863E+09 |
Annual Sum or Average | 0.163922E+10 | 0.793812E+09 | 0.845411E+09 | 0.181190E+10 | 0.243390E+10 |
Minimum of Months | 1761868.94 | 36362.98 | 1725505.96 | 0.00 | 41519659.10 |
Maximum of Months | 0.307119E+09 | 0.166597E+09 | 0.154094E+09 | 0.388105E+09 | 0.438863E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1057.23 | 15.71 | 1.92 | 13.79 | 0.00 | 0.00 |
February | 1.05 | 915.95 | 86.36 | 23.03 | 63.33 | 0.00 | 0.00 |
March | 73.09 | 651.33 | 252.93 | 85.62 | 167.32 | 0.00 | 0.00 |
April | 430.22 | 328.40 | 566.87 | 244.57 | 322.30 | 0.00 | 0.00 |
May | 521.47 | 128.84 | 606.89 | 231.11 | 375.78 | 0.00 | 0.00 |
June | 629.44 | 76.48 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
July | 510.72 | 109.29 | 582.60 | 184.39 | 398.21 | 0.00 | 0.00 |
August | 355.59 | 179.56 | 449.81 | 151.17 | 298.64 | 0.00 | 0.00 |
September | 153.14 | 293.55 | 266.08 | 86.22 | 179.85 | 0.00 | 0.00 |
October | 17.62 | 565.69 | 109.73 | 24.17 | 85.56 | 0.00 | 0.00 |
November | 0.28 | 1024.70 | 41.36 | 11.72 | 29.64 | 0.00 | 0.00 |
December | 0.00 | 1121.57 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Annual Sum or Average | 225.36 | 535.78 | 307.35 | 108.56 | 198.80 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 76.48 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Maximum of Months | 629.44 | 1121.57 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1526.52 | 23.59 | 2.30 | 21.30 | 0.00 | 0.00 |
February | 0.64 | 1295.64 | 120.21 | 30.60 | 89.61 | 0.00 | 0.00 |
March | 290.01 | 858.73 | 420.16 | 180.75 | 239.40 | 0.00 | 0.00 |
April | 968.91 | 442.39 | 840.42 | 454.58 | 385.84 | 0.00 | 0.00 |
May | 1394.31 | 224.75 | 1093.06 | 622.00 | 471.06 | 0.00 | 0.00 |
June | 1497.32 | 160.18 | 1184.87 | 590.38 | 594.50 | 0.00 | 0.00 |
July | 1291.99 | 225.80 | 1063.25 | 513.90 | 549.35 | 0.00 | 0.00 |
August | 910.88 | 321.76 | 801.63 | 389.36 | 412.26 | 0.00 | 0.00 |
September | 414.21 | 425.28 | 434.84 | 173.49 | 261.35 | 0.00 | 0.00 |
October | 89.57 | 675.60 | 179.20 | 44.69 | 134.51 | 0.00 | 0.00 |
November | 0.00 | 1498.83 | 44.79 | 3.97 | 40.83 | 0.00 | 0.00 |
December | 0.00 | 1638.53 | 6.58 | 0.14 | 6.44 | 0.00 | 0.00 |
Annual Sum or Average | 574.55 | 771.78 | 519.79 | 251.72 | 268.08 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 160.18 | 6.58 | 0.14 | 6.44 | 0.00 | 0.00 |
Maximum of Months | 1497.32 | 1638.53 | 1184.87 | 622.00 | 594.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.283169E+10 | 42075936.09 | 5145799.60 | 36930136.48 | 0.00 | 0.00 |
February | 2548475.54 | 0.221587E+10 | 0.208925E+09 | 55726085.70 | 0.153199E+09 | 0.00 | 0.00 |
March | 0.195762E+09 | 0.174452E+10 | 0.677453E+09 | 0.229314E+09 | 0.448139E+09 | 0.00 | 0.00 |
April | 0.111514E+10 | 0.851206E+09 | 0.146932E+10 | 0.633919E+09 | 0.835404E+09 | 0.00 | 0.00 |
May | 0.139670E+10 | 0.345088E+09 | 0.162550E+10 | 0.619003E+09 | 0.100650E+10 | 0.00 | 0.00 |
June | 0.163151E+10 | 0.198226E+09 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
July | 0.136792E+10 | 0.292723E+09 | 0.156045E+10 | 0.493873E+09 | 0.106657E+10 | 0.00 | 0.00 |
August | 0.952415E+09 | 0.480935E+09 | 0.120476E+10 | 0.404893E+09 | 0.799872E+09 | 0.00 | 0.00 |
September | 0.396942E+09 | 0.760871E+09 | 0.689671E+09 | 0.223494E+09 | 0.466177E+09 | 0.00 | 0.00 |
October | 47186137.89 | 0.151514E+10 | 0.293905E+09 | 64748071.85 | 0.229157E+09 | 0.00 | 0.00 |
November | 719208.71 | 0.265603E+10 | 0.107199E+09 | 30375285.84 | 76823217.62 | 0.00 | 0.00 |
December | 0.00 | 0.300401E+10 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.710684E+10 | 0.168963E+11 | 0.969273E+10 | 0.342348E+10 | 0.626925E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.198226E+09 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Maximum of Months | 0.163151E+10 | 0.300401E+10 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.408863E+10 | 63193561.21 | 6154055.20 | 57039506.01 | 0.00 | 0.00 |
February | 1549677.26 | 0.313442E+10 | 0.290803E+09 | 74023328.71 | 0.216779E+09 | 0.00 | 0.00 |
March | 0.776760E+09 | 0.230003E+10 | 0.112535E+10 | 0.484131E+09 | 0.641216E+09 | 0.00 | 0.00 |
April | 0.251143E+10 | 0.114668E+10 | 0.217837E+10 | 0.117828E+10 | 0.100009E+10 | 0.00 | 0.00 |
May | 0.373451E+10 | 0.601977E+09 | 0.292765E+10 | 0.166597E+10 | 0.126168E+10 | 0.00 | 0.00 |
June | 0.388105E+10 | 0.415196E+09 | 0.307119E+10 | 0.153025E+10 | 0.154094E+10 | 0.00 | 0.00 |
July | 0.346046E+10 | 0.604794E+09 | 0.284782E+10 | 0.137643E+10 | 0.147139E+10 | 0.00 | 0.00 |
August | 0.243970E+10 | 0.861800E+09 | 0.214707E+10 | 0.104286E+10 | 0.110421E+10 | 0.00 | 0.00 |
September | 0.107364E+10 | 0.110232E+10 | 0.112710E+10 | 0.449674E+09 | 0.677431E+09 | 0.00 | 0.00 |
October | 0.239914E+09 | 0.180953E+10 | 0.479959E+09 | 0.119693E+09 | 0.360266E+09 | 0.00 | 0.00 |
November | 0.00 | 0.388497E+10 | 0.116097E+09 | 10277781.52 | 0.105819E+09 | 0.00 | 0.00 |
December | 0.00 | 0.438863E+10 | 17618689.43 | 363629.79 | 17255059.65 | 0.00 | 0.00 |
Annual Sum or Average | 0.181190E+11 | 0.243390E+11 | 0.163922E+11 | 0.793812E+10 | 0.845411E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.415196E+09 | 17618689.43 | 363629.79 | 17255059.65 | 0.00 | 0.00 |
Maximum of Months | 0.388105E+10 | 0.438863E+10 | 0.307119E+10 | 0.166597E+10 | 0.154094E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.5 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.6 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.24 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.87 | 6.41 | 3.45 | 5.65 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.84 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.69 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.46 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.84 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.6 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.5 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.58 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.01 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.76 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.27 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.32 | 11.70 | 4.67 | 18.87 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.74 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.88 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 7.99 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.5 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.0 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.5 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.32 | 11.70 | 6.20 | 18.87 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.1 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.2 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.0 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.8 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.6 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.23 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.64 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.01 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.94 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.32 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.33 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.28 | 141.00 | 225.33 |
August | 16.13 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.81 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 7.99 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.5 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.0 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.5 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.33 | 29.07 | 14.40 | 8.80 | 19.28 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.6 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.77 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.74 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.40 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.29 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.0 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.4 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.0 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114171E+10 | -.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88089149.4 | 59.00 | 0.00 | 0.00 |
February | 0.104743E+10 | -967993924.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79435829.7 | 59.00 | 0.00 | 0.00 |
March | 0.121908E+10 | -.113151E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87569451.0 | 59.00 | 0.00 | 0.00 |
April | 0.113475E+10 | -.105103E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83718881.7 | 59.00 | 0.00 | 0.00 |
May | 0.116769E+10 | -.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -82652478.1 | 59.00 | 0.00 | 0.00 |
June | 0.111446E+10 | -.104139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -73061188.4 | 59.00 | 0.00 | 0.00 |
July | 0.104162E+10 | -968512837.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73106278.8 | 59.00 | 0.00 | 0.00 |
August | 0.108919E+10 | -.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -74206066.0 | 59.00 | 0.00 | 0.00 |
September | 0.101927E+10 | -939960668.8 | 0.00 | 0.00 | 720.00 | 0.00 | -79307125.8 | 58.99 | 0.00 | 0.00 |
October | 0.104773E+10 | -960936455.9 | 0.00 | 0.00 | 744.00 | 0.00 | -86794419.8 | 58.99 | 0.00 | 0.00 |
November | 0.104113E+10 | -955931644.7 | 0.00 | 0.00 | 720.00 | 0.00 | -85200258.1 | 59.00 | 0.00 | 0.00 |
December | 0.112431E+10 | -.103625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88065094.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.131884E+11 | -.122072E+11 | 8760.00 | -981206221.6 | 59.00 | |||||
Minimum of Months | 0.101927E+10 | -.113151E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88089149.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121908E+10 | -939960668.8 | 0.00 | 0.00 | 744.00 | 0.00 | -73061188.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 1.00 | 0.96 | 21-JAN-12:20 | 27.71 | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.98 | 0.92 | 21-FEB-11:20 | 64.42 | 6.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.96 | 0.88 | 05-MAR-10:00 | 120.59 | 9.28 | 0.00 | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.94 | 0.88 | 01-APR-09:00 | 149.08 | 10.15 | 0.00 | 91.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.94 | 0.88 | 01-MAY-07:30 | 168.43 | 10.44 | 0.00 | 179.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.93 | 0.88 | 01-JUN-07:00 | 516.17 | 10.73 | 0.00 | 280.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.93 | 0.88 | 01-JUL-08:50 | 194.17 | 10.91 | 0.00 | 242.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.94 | 0.88 | 01-AUG-07:19 | 167.43 | 10.58 | 0.00 | 154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.95 | 0.88 | 01-SEP-08:20 | 125.28 | 9.49 | 0.00 | 41.33 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.97 | 0.92 | 01-OCT-08:50 | 89.14 | 7.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.99 | 0.92 | 06-NOV-13:20 | 38.14 | 2.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 8.75 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.95 | 190.83 | 9.29 | 0.00 | 1043.00 | ||||||
Minimum of Months | 71.17 | 0.93 | 0.88 | 8.75 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 516.17 | 10.91 | 0.00 | 280.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 1.00 | 0.90 | 28-JAN-12:30 | 57.30 | 13.87 | 0.00 | 0.00 | 28.07 | 13.55 | 0.00 | 0.00 |
February | 205.83 | 0.94 | 0.77 | 21-FEB-14:20 | 135.12 | 18.90 | 37.83 | 0.00 | 70.08 | 18.65 | 24.83 | 0.00 |
March | 329.50 | 0.83 | 0.61 | 12-MAR-17:10 | 390.46 | 24.14 | 193.67 | 57.67 | 164.06 | 23.06 | 189.33 | 12.33 |
April | 421.83 | 0.76 | 0.61 | 01-APR-15:30 | 679.41 | 24.49 | 266.17 | 180.33 | 529.22 | 24.63 | 309.67 | 109.83 |
May | 545.00 | 0.77 | 0.61 | 01-MAY-16:00 | 330.33 | 21.30 | 290.17 | 187.33 | 332.81 | 22.35 | 365.00 | 109.67 |
June | 583.50 | 0.76 | 0.61 | 01-JUN-15:09 | 355.00 | 21.13 | 321.33 | 272.50 | 254.81 | 22.05 | 373.83 | 104.83 |
July | 562.83 | 0.77 | 0.61 | 02-JUL-15:09 | 343.11 | 21.12 | 289.67 | 225.83 | 315.45 | 22.06 | 356.83 | 102.83 |
August | 467.17 | 0.79 | 0.61 | 01-AUG-16:10 | 471.83 | 22.96 | 255.00 | 142.00 | 390.47 | 23.54 | 290.33 | 77.17 |
September | 356.33 | 0.83 | 0.61 | 02-SEP-16:19 | 478.68 | 24.81 | 207.83 | 68.17 | 175.48 | 23.22 | 215.00 | 17.00 |
October | 265.50 | 0.91 | 0.68 | 01-OCT-15:09 | 187.82 | 21.57 | 72.50 | 12.00 | 78.83 | 19.43 | 41.67 | 0.00 |
November | 135.83 | 0.99 | 0.90 | 01-NOV-10:20 | 79.83 | 15.99 | 3.17 | 0.00 | 41.22 | 15.65 | 1.17 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 20.23 | 7.62 | 0.00 | 0.00 | 9.56 | 7.28 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.82 | 365.82 | 21.59 | 1937.33 | 1145.83 | 265.11 | 21.67 | 2167.67 | 533.67 | ||
Minimum of Months | 71.17 | 0.76 | 0.61 | 20.23 | 7.62 | 0.00 | 0.00 | 9.56 | 7.28 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 679.41 | 24.81 | 321.33 | 272.50 | 529.22 | 24.63 | 373.83 | 109.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139019E+11 | 25124.93 | 01-JAN-19:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118552E+11 | 25124.93 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116313E+11 | 25124.93 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580749E+10 | 25124.93 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125619E+10 | 25124.93 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37053867.78 | 25124.93 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26499341.70 | 6434.34 | 31-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165620E+10 | 25124.93 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.685363E+10 | 25124.93 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116965E+11 | 25124.93 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136772E+11 | 25124.93 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783992E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139019E+11 | 25124.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485627E+11 | 71071.09 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394469E+11 | 71071.09 | 01-FEB-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353250E+11 | 71071.09 | 01-MAR-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147849E+11 | 71071.09 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425732E+09 | 62449.24 | 03-MAY-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104828E+10 | 58332.87 | 27-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191118E+11 | 71071.09 | 21-OCT-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367621E+11 | 71071.09 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475944E+11 | 71071.09 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243062E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485627E+11 | 71071.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141838E+12 | 100692.48 | 02-JAN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117722E+12 | 100692.48 | 01-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110234E+12 | 100692.48 | 02-MAR-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.472002E+11 | 100692.48 | 02-APR-19:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571625E+11 | 85727.97 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.960562E+11 | 91364.17 | 10-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137992E+12 | 100692.48 | 22-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708204E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141838E+12 | 100692.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14276503.18 | 14276503.18 | 1243.82 | 13-MAY-15:50 | 1243.82 | 0.00 |
June | 0.00 | 0.00 | 0.193829E+10 | 0.188916E+10 | 12887.68 | 22-JUN-05:02 | 12887.68 | 0.00 |
July | 0.00 | 0.00 | 0.357095E+10 | 0.339621E+10 | 13812.09 | 26-JUL-05:02 | 11821.56 | 0.00 |
August | 0.00 | 0.00 | 0.246048E+10 | 0.236721E+10 | 13488.46 | 04-AUG-05:02 | 12798.53 | 0.00 |
September | 0.00 | 0.00 | 28716344.21 | 28716344.21 | 1829.41 | 02-SEP-16:00 | 1829.41 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.801272E+10 | 0.769557E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.357095E+10 | 0.339621E+10 | 13812.09 | 12887.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.194915E+09 | 0.189438E+09 | 7609.79 | 30-JUN-15:00 | 7609.79 | 0.00 |
July | 0.00 | 0.00 | 0.111161E+10 | 0.109853E+10 | 27874.87 | 23-JUL-11:42 | 24892.79 | 0.00 |
August | 0.00 | 0.00 | 0.144413E+09 | 0.139265E+09 | 4968.15 | 11-AUG-16:00 | 4968.15 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.145094E+10 | 0.142724E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111161E+10 | 0.109853E+10 | 27874.87 | 24892.79 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.612789E+09 | 0.08 | 228.79 | 01-JAN-00:02 | 0.08 |
February | 0.550879E+09 | 0.08 | 228.79 | 01-FEB-00:03 | 0.08 |
March | 0.578711E+09 | 0.07 | 228.79 | 01-MAR-00:03 | 0.08 |
April | 0.314219E+09 | 0.04 | 228.79 | 01-APR-00:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.418890E+09 | 0.05 | 228.79 | 03-OCT-06:40 | 0.08 |
November | 0.593022E+09 | 0.08 | 228.79 | 01-NOV-00:10 | 0.08 |
December | 0.612789E+09 | 0.08 | 228.79 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.368130E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.612789E+09 | 0.08 | 228.79 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.942756E+09 | 0.61 | 856.20 | 02-JAN-07:20 | 0.93 |
February | 0.870474E+09 | 0.63 | 856.20 | 01-FEB-11:10 | 0.93 |
March | 0.988756E+09 | 0.56 | 856.20 | 01-MAR-17:20 | 0.93 |
April | 0.883915E+09 | 0.43 | 856.20 | 01-APR-07:00 | 0.93 |
May | 0.894093E+09 | 0.38 | 856.20 | 01-MAY-09:00 | 0.92 |
June | 0.884541E+09 | 0.37 | 856.20 | 01-JUN-06:50 | 0.92 |
July | 0.861520E+09 | 0.35 | 856.20 | 03-JUL-13:40 | 0.92 |
August | 0.922756E+09 | 0.37 | 856.20 | 01-AUG-07:15 | 0.92 |
September | 0.856914E+09 | 0.37 | 856.20 | 01-SEP-06:20 | 0.92 |
October | 0.878565E+09 | 0.40 | 856.20 | 02-OCT-06:10 | 0.92 |
November | 0.872628E+09 | 0.51 | 856.20 | 01-NOV-08:30 | 0.93 |
December | 0.927827E+09 | 0.58 | 856.20 | 01-DEC-15:00 | 0.93 |
Annual Sum or Average | 0.107847E+11 | 0.46 | |||
Minimum of Months | 0.856914E+09 | 0.35 | 856.20 | 0.92 | |
Maximum of Months | 0.988756E+09 | 0.63 | 856.20 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212601E+10 | 0.78 | 1543.72 | 02-JAN-08:50 | 0.90 |
February | 0.193703E+10 | 0.78 | 1543.72 | 01-FEB-07:30 | 0.90 |
March | 0.214894E+10 | 0.78 | 1543.72 | 01-MAR-07:20 | 0.90 |
April | 0.178669E+10 | 0.63 | 1543.72 | 26-APR-06:30 | 0.90 |
May | 0.159937E+10 | 0.37 | 1543.72 | 27-MAY-06:40 | 0.89 |
June | 0.158942E+10 | 0.35 | 1543.72 | 13-JUN-14:10 | 0.89 |
July | 0.153191E+10 | 0.33 | 1543.72 | 20-JUL-10:20 | 0.89 |
August | 0.165055E+10 | 0.35 | 1543.72 | 01-AUG-13:20 | 0.88 |
September | 0.154680E+10 | 0.38 | 1543.72 | 25-SEP-07:50 | 0.89 |
October | 0.180926E+10 | 0.67 | 1543.72 | 02-OCT-07:50 | 0.89 |
November | 0.191127E+10 | 0.76 | 1543.72 | 01-NOV-07:00 | 0.90 |
December | 0.208329E+10 | 0.78 | 1543.72 | 01-DEC-07:20 | 0.90 |
Annual Sum or Average | 0.217205E+11 | 0.58 | |||
Minimum of Months | 0.153191E+10 | 0.33 | 1543.72 | 0.88 | |
Maximum of Months | 0.214894E+10 | 0.78 | 1543.72 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.04 | 0.00 |
February | 3.18 | 0.00 |
March | 3.54 | 0.00 |
April | 1.31 | 0.00 |
May | 0.79 | 0.70 |
June | 0.33 | 0.28 |
July | 1.28 | 0.25 |
August | 0.86 | 0.88 |
September | 1.51 | 0.71 |
October | 2.53 | 0.03 |
November | 3.61 | 0.00 |
December | 4.90 | 0.00 |
Annual Sum or Average | 26.89 | 0.11 |
Minimum of Months | 0.33 | 0.00 |
Maximum of Months | 4.90 | 0.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.08 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.942756E+09 | 0.193305E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.870474E+09 | 0.166225E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.988756E+09 | 0.164509E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.883915E+09 | 0.842329E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.897225E+09 | 0.185739E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129020E+10 | 54966753.10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.159107E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.143023E+10 | 40325402.85 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.863165E+09 | 0.245011E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.878565E+09 | 0.986893E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.872628E+09 | 0.163415E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.927827E+09 | 0.189757E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124368E+11 | 0.110416E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.863165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159107E+10 | 0.193305E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.212601E+10 | 0.685570E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.193703E+10 | 0.559245E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.214894E+10 | 0.506533E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.178669E+10 | 0.213458E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159937E+10 | 0.634428E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163596E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179013E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168450E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.154680E+10 | 0.157391E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.180926E+10 | 0.278034E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.191127E+10 | 0.526517E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208329E+10 | 0.674420E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.220593E+11 | 0.346586E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154680E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.214894E+10 | 0.685570E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.942756E+09 | 0.00 | 0.139019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870474E+09 | 0.00 | 0.118552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.988756E+09 | 0.00 | 0.116313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.883915E+09 | 0.00 | 0.580749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894093E+09 | 14276503.18 | 0.125619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884541E+09 | 0.193829E+10 | 37053867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.861520E+09 | 0.357095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.922756E+09 | 0.246048E+10 | 26499341.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856914E+09 | 28716344.21 | 0.165620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878565E+09 | 0.00 | 0.685363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872628E+09 | 0.00 | 0.116965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927827E+09 | 0.00 | 0.136772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107847E+11 | 0.801272E+10 | 0.783992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.856914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988756E+09 | 0.357095E+10 | 0.139019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.212601E+10 | 0.00 | 0.485627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193703E+10 | 0.00 | 0.394469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214894E+10 | 0.00 | 0.353250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178669E+10 | 0.00 | 0.147849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159937E+10 | 0.00 | 0.425732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158942E+10 | 0.194915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153191E+10 | 0.111161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165055E+10 | 0.144413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154680E+10 | 0.00 | 0.104828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180926E+10 | 0.00 | 0.191118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191127E+10 | 0.00 | 0.367621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208329E+10 | 0.00 | 0.475944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217205E+11 | 0.145094E+10 | 0.243062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214894E+10 | 0.111161E+10 | 0.485627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.942756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.988756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.883915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894093E+09 | 0.00 | 0.00 | 0.00 | 3132096.29 | 0.00 | 0.185739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884541E+09 | 0.00 | 0.00 | 0.00 | 0.405656E+09 | 0.00 | 54966753.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.861520E+09 | 0.00 | 0.00 | 0.00 | 0.729552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.922756E+09 | 0.00 | 0.00 | 0.00 | 0.507479E+09 | 0.00 | 40325402.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856914E+09 | 0.00 | 0.00 | 0.00 | 6251162.50 | 0.00 | 0.245011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107847E+11 | 0.00 | 0.00 | 0.00 | 0.165207E+10 | 0.00 | 0.110416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.856914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988756E+09 | 0.00 | 0.00 | 0.00 | 0.729552E+09 | 0.00 | 0.193305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.212601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158942E+10 | 0.00 | 0.00 | 0.00 | 46543697.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153191E+10 | 0.00 | 0.00 | 0.00 | 0.258222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165055E+10 | 0.00 | 0.00 | 0.00 | 33956685.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217205E+11 | 0.00 | 0.00 | 0.00 | 0.338722E+09 | 0.00 | 0.346586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.153191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214894E+10 | 0.00 | 0.00 | 0.00 | 0.258222E+09 | 0.00 | 0.685570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439906E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353924E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357578E+10 | 0.00 | 0.00 | 0.13 |
April | 46201018.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198288E+10 | 0.00 | 0.00 | 0.13 |
May | 0.654203E+09 | 0.00 | 0.00 | 11440.62 | 0.00 | 0.436439E+09 | 13314139.98 | 0.00 | 0.13 |
June | 0.181351E+09 | 5446128.49 | 0.00 | 2649510.13 | 0.00 | 0.00 | 0.627797E+09 | 0.00 | 0.13 |
July | 26942191.66 | 19236002.58 | 0.00 | 4262434.04 | 0.00 | 0.00 | 0.512757E+09 | 0.00 | 0.13 |
August | 0.214562E+09 | 713243.85 | 0.00 | 3790008.44 | 0.00 | 975585.93 | 0.827882E+09 | 0.00 | 0.13 |
September | 0.928505E+09 | 0.00 | 0.00 | 57517.53 | 0.00 | 0.691473E+09 | 42011102.91 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269331E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416510E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463586E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.205177E+10 | 25395374.92 | 0.00 | 10770910.77 | 0.00 | 0.261201E+11 | 0.202376E+10 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.928505E+09 | 19236002.58 | 0.00 | 4262434.04 | 0.00 | 0.463586E+10 | 0.827882E+09 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12677136.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152612E+11 | 0.00 | 0.00 | 0.17 |
February | 0.561138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113533E+11 | 0.00 | 0.00 | 0.18 |
March | 0.242050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918869E+10 | 0.00 | 0.00 | 0.19 |
April | 0.363497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219079E+10 | 0.00 | 0.00 | 0.18 |
May | 0.311313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27485499.65 | 0.00 | 0.00 | 0.19 |
June | 0.300101E+10 | 508197.66 | 0.00 | 609431.46 | 0.00 | 0.00 | 0.461116E+09 | 0.00 | 0.22 |
July | 0.199287E+10 | 24845738.70 | 0.00 | 3274876.49 | 5652078.28 | 0.00 | 0.185467E+10 | 0.00 | 0.27 |
August | 0.371435E+10 | 0.00 | 0.00 | 1383048.70 | 0.00 | 0.00 | 0.108691E+10 | 0.00 | 0.22 |
September | 0.501730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79436915.20 | 0.00 | 0.00 | 0.18 |
October | 0.397124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432368E+10 | 0.00 | 0.00 | 0.17 |
November | 0.527579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138923E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162535E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.279668E+11 | 25353936.36 | 0.00 | 5267356.65 | 5652078.28 | 0.725705E+11 | 0.340270E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.501730E+10 | 24845738.70 | 0.00 | 3274876.49 | 5652078.28 | 0.162535E+11 | 0.185467E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:10:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |