Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:11:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1400.25 | 289.60 | 289.60 |
Net Site Energy | 1400.25 | 289.60 | 289.60 |
Total Source Energy | 2549.37 | 527.26 | 527.26 |
Net Source Energy | 2549.37 | 527.26 | 527.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 905.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 495.20 | 905.05 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 905.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 41.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.44 | 187.18 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 102.42 | 187.18 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.44 | 187.18 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 102.42 | 187.18 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 495.199 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 495.199 | 100.00 |
Total On-Site and Utility Electric Sources | 495.199 | 100.00 |
Total Electricity End Uses | 495.199 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.83 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2319.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.8889 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8323 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8323 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-13:00 | 05-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 289701.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 18095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5066.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1734.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42380.18 | 289701.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 289701.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 18095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2761.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1734.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 981.07 | 0.00 | 0.00 | 0.00 |
Cooling | 17.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 719.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 134.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1568.30 | 981.07 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 202.90 | 0.00 | 0.00 | 0.00 |
Cooling | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 324.35 | 202.90 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 202.90 | 0.00 | 0.00 | 0.00 |
Cooling | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 324.35 | 202.90 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.875867 |
ZONE2 FINE STORAGE DIRECT AIR | 1.67 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 4.24 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 4.24 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 154216.04 |
PSZ-OFFICE HEATING COIL | 22830.12 |
PSZ-FINE STORAGE HEATING COIL | 62712.34 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 154216.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.875867 | 0.875867 | 0.875867 | 0.875867 | 0.875867 | 0.875867 | 1.00 | 1.00 | 0.875867 |
PSZ-FINE STORAGE | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.00 | 1.000000 | 1.67 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.875867 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.67 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.875867 | 0.875867 | 0.875867 | 0.875867 | 14498.71 | 22830.12 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.67 | 33766.50 | 62712.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.875870 | 0.437935 | 0.583913 | 14498.76 | 14498.71 | 7249.35 | 7249.35 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.67 | 0.837235 | 1.12 | 29072.91 | 33766.50 | 16883.25 | 16883.25 | 0.732803 | 0.732800 | 0.732800 | 0.732800 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.875867 | 969.72 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.67 | 1791.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 6.889 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.963 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1631.841 | 6.889 | 326.368 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1631.841 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 10348.991 | 7.427 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.991 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 11383.890 | 3.552 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.890 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.2948 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5734 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.045 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5734 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.293 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.644 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4889 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.644 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.81987457E-12 | -0.55300542E-16 | 0.55369647E-14 | 0.11108823E-15 |
8 | 3 | -0.39745255E-03 | 0.21013160E-06 | -0.57778445E-04 | 0.15730253E-12 |
9 | 2 | 1.7695129 | 0.45329532E-02 | 1.1632534 | -0.76198706E-04 |
10 | 1 | -7.0895412 | 0.11645204 | -17.243381 | 0.33915991 |
11 | 0 | 5.5152410 | 0.73830080E-01 | 16.275001 | |
12 | 4 | 0.76342465E-12 | 0.16474507E-15 | -0.23733433E-14 | 0.11984663E-15 |
13 | 3 | -0.37867847E-03 | 0.39972734E-06 | -0.54871579E-04 | 0.14649615E-12 |
14 | 2 | 1.7252338 | 0.87962070E-02 | 1.1295743 | -0.72598522E-04 |
15 | 1 | -7.1476348 | 0.22881135 | -17.028658 | 0.33064781 |
16 | 0 | 5.8066602 | 0.14627247 | 16.283019 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0454545 | 2.0454545 | 2.0454545 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23733433E-14 | 0.16474507E-15 | 0.76342465E-12 | 0.11984663E-15 |
85 | 3 | -0.54871579E-04 | 0.39972734E-06 | -0.37867847E-03 | 0.14649615E-12 |
86 | 2 | 1.1295743 | 0.87962070E-02 | 1.7252338 | -0.72598522E-04 |
87 | 1 | -17.028658 | 0.22881135 | -7.1476348 | 0.33064781 |
88 | 0 | 16.283019 | 0.14627247 | 5.8066602 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.34_SHGC_0.38 | 28 | 1 | VerySmooth | 1.931 | 0.374 | 0.294 | 0.381 |
2 | SKYLIGHT_U_0.47_SHGC_0.4 | 29 | 1 | VerySmooth | 2.672 | 0.394 | 0.315 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 30 | 1 | VerySmooth | 4.262 | 0.554 | 0.413 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.84193E-002 | 0.29373 | 0.50285 | 0.50285 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11150 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.330 | 7.271E-004 | 4.749E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 7759.59845 | 9311.51814 | 0.72989 | 0.87587 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10267.81709 | 12321.38051 | 0.32960 | 0.39552 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 19031.74493 | 22838.09392 | 1.39539 | 1.67447 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.26593E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 34640.50821 | 41568.60985 | 0.93649 | 1.12379 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 128513.36123 | 154216.03347 | 3.53726 | 4.24472 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 11815.56 | 0.87587 | 0.87587 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13197.65 | 0.39552 | 0.39552 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 28857.14 | 1.67447 | 1.67447 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 48467.10 | 1.12379 | 1.12379 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87587 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67447 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.24472 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 4.24472 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 154216.04260 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 154216.03347 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87587 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87587 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87587 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87587 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87587 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.87587 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67447 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67447 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67447 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67447 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67447 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.67447 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.87587 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.67447 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87587 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87587 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87587 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87587 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87587 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87587 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43794 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58391 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14498.75848 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14498.71000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7249.35500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7249.35500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14498.71000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22830.12041 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87587 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 969.72410 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 22830.12041 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67447 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67447 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67447 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67447 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67447 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67447 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83724 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11631 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 29072.90686 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33766.50000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16883.25000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16883.25000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73280 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73280 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73280 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73280 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33766.50000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62712.34271 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67447 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1791.75992 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 62712.34271 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 13819.1 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 32466.2 | 16.50 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1792335585 | 0.1763888178 | Pass | Pass | 1.2503822403 | 11.0441511736 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4107111725 | 0.3961960877 | Pass | Pass | 0.3983255386 | 0.7429211130 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.7854207111E-003 | 6.3763006007E-003 | Pass | Pass | 6.3095314593E-002 | 0.1195339424 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.282 | 0.295 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.528 | 0.573 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.931 | 0.374 | 0.381 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.931 | 0.374 | 0.381 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.34_SHGC_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.931 | 0.374 | 0.381 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.34_SHGC_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.931 | 0.374 | 0.381 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.996 | 0.457 | 0.458 | ||||||||||||
North Total or Average | 6.51 | 1.931 | 0.374 | 0.381 | ||||||||||||
Non-North Total or Average | 26.02 | 3.263 | 0.477 | 0.478 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.566 | 2.045 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 6.8889 | 236.88 | 1631.84 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 56.91 | 168.00 | 33.25 | 0.0000 | Y | 10.18 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 7.4271 | 1393.41 | 10348.99 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 53.69 | 0.0000 | Y | 104.31 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.5521 | 3204.84 | 11383.89 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 52.69 | 0.0000 | Y | 112.60 |
Interior Lighting Total | 4.8323 | 4835.13 | 23364.72 | 227.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1631.84 | 473.23 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1631.84 | 163.18 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 11383.89 | 1320.53 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 42.11 | 42.11 | 0.90 | |
EXTERIOR_LIGHTS_B | 3955.00 | AstronomicalClock | - | 83.57 | 62.84 | 46.65 | |
EXTERIOR_LIGHTS_C | 1004.90 | AstronomicalClock | - | 83.57 | 49.89 | 9.41 | |
Exterior Lighting Total | 5073.70 | 56.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14498.71 | 11579.54 | 2919.17 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33766.50 | 24744.09 | 9022.41 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 13819.1 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 32466.2 | 16.50 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 154216.04 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 22830.12 | 0.81 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 62712.34 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.24 | 394.38 | 92.91 | 1.00 | 3.21 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.88 | 969.72 | 1107.16 | 1.00 | 1.44 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.67 | 1791.76 | 1070.05 | 1.00 | 1.34 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7759.60 | 9311.52 | 39.31 | 0.730 | 0.876 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00810 | 31.16 | 0.00627 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 19031.74 | 22838.09 | 16.39 | 1.395 | 1.674 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 26.70 | 26.70 | 0.00768 | 31.37 | 0.00627 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10267.82 | 12321.38 | 52.02 | 0.330 | 0.396 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00776 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34640.51 | 41568.61 | 29.83 | 0.936 | 1.124 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00636 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 128513.36 | 154216.03 | 48.12 | 3.537 | 4.245 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00873 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.88 | 0.88 | 0.40 | 0.40 | 0.8759 | 0.8759 | 0.8759 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.67 | 1.67 | 1.12 | 1.12 | 1.6745 | 1.6745 | 1.6745 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 154216.043 | 154216.043 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 154216.04 | 154216.04 | 4.244717 | 1.34 | 1.34 | 0.00680298 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.99 | 0.00873434 | 100.0000 | 154216.03 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 7249.355 | 0.000 | 0.875870 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7249.35 | 7249.35 | 0.875870 | 24.75 | 14.74 | 0.00788762 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 11.6781 | 23.90 | 0.00810204 | 38.3988 | 7759.60 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 22830.120 | 22830.120 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 22830.12 | 22830.12 | 0.875867 | 8.47 | 6.24 | 0.00584312 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 11.6781 | 21.10 | 0.00776201 | 43.6358 | 10267.82 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 16883.250 | 0.000 | 1.674470 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 16883.25 | 16883.25 | 1.674470 | 28.41 | 15.60 | 0.00742617 | 12.00 | 10.08 | 0.00800000 | 33.40 | 0.00626594 | 16.30 | 25.3640 | 26.70 | 0.00767726 | 30.8225 | 18883.05 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 62712.343 | 62712.343 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62712.34 | 62712.34 | 1.674468 | -0.75 | -0.75 | 0.00408781 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 25.3640 | 15.55 | 0.00636358 | 50.7771 | 34640.51 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 154216.043 | 154216.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 4.244717 | 4.47028055 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 154216.04 | 154216.04 | 1.0000 | 4.47028055 | 4.244717 | 1.34 | 1.34 | 0.00680298 | 18375.4 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 154216.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.99 | 0.00873434 | 9.99 | 0.00873434 | 100.0000 | 154216.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7249.355 | 0.000 | 0.875870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5027 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7249.35 | 7249.35 | 1.0000 | 0.92241363 | 0.875870 | 24.75 | 14.74 | 0.00788762 | 44956.6 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7249.35 | 31.16 | 0.00626593 | 15.56 | 0.10228487 | 11.6781 | 23.90 | 0.00810204 | 23.90 | 0.00810204 | 38.3988 | 7759.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22830.120 | 22830.120 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.875867 | 0.92241075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 22830.12 | 22830.12 | 1.0000 | 0.92241075 | 0.875867 | 8.47 | 6.24 | 0.00584312 | 23215.5 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22830.12 | -27.60 | 0.00034190 | -27.60 | 0.10228487 | 11.6781 | 21.05 | 0.00776201 | 21.10 | 0.00776201 | 43.6358 | 10267.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16883.250 | 0.000 | 1.674470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6449 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 16883.25 | 16883.25 | 1.0000 | 1.76345113 | 1.674470 | 28.41 | 15.60 | 0.00742617 | 47515.2 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16883.25 | 33.40 | 0.00626594 | 16.30 | 0.42471267 | 25.3640 | 26.70 | 0.00782462 | 26.70 | 0.00767726 | 30.8225 | 18883.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62712.343 | 62712.343 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.674468 | 1.76344903 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62712.34 | 62712.34 | 1.0000 | 1.76344903 | 1.674468 | -0.75 | -0.75 | 0.00408781 | 9459.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62712.34 | -27.60 | 0.00034190 | -27.60 | 0.42471267 | 25.3640 | 15.56 | 0.00636358 | 15.55 | 0.00636358 | 50.7771 | 34640.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.67 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2483.50 | 3104.00 | 2319.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2483.50 | 3104.00 | 2319.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 93.83 | 0.67 | 66.83 | 0.67 |
ZONE2 FINE STORAGE | 523.33 | 2.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2.50 | 0.00 | 0.00 | 0.00 |
Facility | 597.67 | 3.33 | 66.83 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.307 | 0.255 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
Electricity:Building | 364.57 | 1510.77 | 01-JAN-00:10 | 30865.15 | 07-AUG-09:30 |
Electricity:Zone:ZONE1 OFFICE | 39.35 | 520.87 | 01-JAN-00:10 | 2861.51 | 02-JAN-08:10 |
InteriorLights:Electricity | 227.09 | 1040.90 | 01-JAN-00:10 | 19422.15 | 19-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.18 | 51.00 | 01-JAN-00:10 | 1026.46 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 227.09 | 1040.90 | 01-JAN-00:10 | 19422.15 | 19-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 220.91 | 689.93 | 01-JAN-00:10 | 19361.67 | 07-AUG-09:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 112.60 | 689.93 | 01-JAN-00:10 | 9622.24 | 19-JAN-09:10 |
InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.64 | 481.00 | 05-JAN-20:00 | 2852.40 | 15-FEB-12:40 |
WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.40 | 15-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.40 | 15-FEB-12:40 |
Fans:Electricity | 42.50 | 0.00 | 01-JAN-14:00 | 5066.78 | 17-JUL-11:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.98 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-JUL-16:30 |
Ventilation (simple):Fans:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 2305.29 | 17-JUL-16:30 |
ElectricityPurchased:Facility | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
ElectricityPurchased:Plant | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
Cogeneration:ElectricityPurchased | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
ElectricityNet:Plant | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
Cogeneration:ElectricityNet | 495.20 | 1991.77 | 01-JAN-14:00 | 42380.18 | 17-JUL-14:00 |
Electricity:HVAC | 47.02 | 0.00 | 01-JAN-14:00 | 11788.56 | 17-JUL-16:00 |
General:Fans:Electricity | 41.52 | 0.00 | 01-JAN-14:00 | 3155.86 | 03-JAN-09:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.50 | 0.00 | 01-JAN-00:10 | 9027.07 | 17-JUL-16:00 |
ExteriorLights:Electricity | 56.96 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 56.96 | 0.00 | 01-JAN-08:20 | 5073.70 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 905.05 | 0.00 | 01-JAN-12:40 | 289701.43 | 05-JAN-17:10 |
Gas:HVAC | 905.05 | 0.00 | 01-JAN-12:40 | 289701.43 | 05-JAN-17:10 |
Heating:Gas | 905.05 | 0.00 | 01-JAN-12:40 | 289701.43 | 05-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1428.69 | 0.00 | 01-JAN-14:00 | 444286.59 | 05-JAN-17:10 |
EnergyTransfer:Building | 706.40 | 0.00 | 01-JAN-14:00 | 213124.54 | 05-JAN-17:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 49.48 | 0.00 | 01-JAN-00:10 | 21532.26 | 11-JAN-07:10 |
Heating:EnergyTransfer | 679.71 | 0.00 | 01-JAN-14:00 | 213124.54 | 05-JAN-17:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 39.94 | 0.00 | 01-JAN-00:10 | 21532.26 | 11-JAN-07:10 |
Cooling:EnergyTransfer | 26.69 | 0.00 | 01-JAN-00:10 | 23383.96 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 9.54 | 0.00 | 01-JAN-00:10 | 7767.01 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 156.49 | 0.00 | 01-JAN-00:40 | 50151.44 | 05-JAN-22:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.34 | 0.00 | 01-JAN-00:40 | 50151.44 | 05-JAN-22:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.15 | 0.00 | 01-JAN-00:10 | 16510.58 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 500.43 | 0.00 | 01-JAN-12:50 | 155903.78 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 500.43 | 0.00 | 01-JAN-12:50 | 155903.78 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 722.29 | 0.00 | 01-JAN-12:40 | 231162.06 | 05-JAN-17:10 |
HeatingCoils:EnergyTransfer | 698.48 | 0.00 | 01-JAN-12:40 | 231162.06 | 05-JAN-17:10 |
CoolingCoils:EnergyTransfer | 23.81 | 0.00 | 01-JAN-00:10 | 32367.12 | 17-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 39.943 | -9.540 | 0.000 | 0.000 | 4.015 | 10.185 | 29.165 | 9.622 | 0.000 | 0.437 | 0.000 | 0.000 | -9.223 | 0.000 | -19.139 | -55.463 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 139.339 | -17.150 | 0.000 | 0.000 | 0.000 | 104.309 | 0.000 | 0.000 | 0.000 | 1.561 | 0.001 | 0.000 | 0.000 | 0.000 | -119.516 | -108.543 |
ZONE3 BULK STORAGE | 500.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 112.600 | 107.336 | 32.008 | 0.000 | 28.307 | 0.000 | 0.000 | -13.259 | 0.000 | -514.790 | -252.633 |
Total Facility | 500.431 | 0.000 | 179.282 | -26.690 | 0.000 | 0.000 | 4.015 | 227.094 | 136.501 | 41.630 | 0.000 | 30.306 | 0.001 | 0.000 | -22.483 | 0.000 | -653.445 | -416.640 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-AUG-05:01 | 0.00 | 0.00 | 0.00 | -13077.04 | 0.00 | 0.00 | 32.75 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 13147.12 | 0.00 | -353.47 | 0.00 | -350.87 | 0.00 |
ZONE2 FINE STORAGE | 08-AUG-20:01 | 0.00 | 0.00 | 0.00 | -30490.43 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 30199.65 | 0.00 | -0.00 | 0.00 | -9.20 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-20:01 | 0.00 | 0.00 | 0.00 | -30490.43 | 0.00 | 0.00 | 0.00 | 1040.90 | 2519.91 | 0.00 | 0.00 | 0.00 | 30550.61 | 0.00 | -655.91 | 0.00 | -2965.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 10-FEB-06:31 | 0.00 | 0.00 | 24475.22 | 0.00 | 0.00 | 0.00 | 54.96 | 306.60 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.27 | 0.00 | -1456.58 | -22904.45 |
ZONE2 FINE STORAGE | 28-JAN-03:21 | 0.00 | 0.00 | 65710.61 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12059.35 | -53951.23 |
ZONE3 BULK STORAGE | 05-JAN-16:00 | 155895.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9341.73 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1131.04 | 0.00 | -170981.00 | -1325.55 |
Total Facility | 06-JAN-06:52 | 151742.62 | 0.00 | 86992.20 | 0.00 | 0.00 | 0.00 | 55.44 | 2479.89 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3109.95 | 0.00 | -115719.73 | -125041.02 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8759 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8759 | 0.1168 | 1.0000 | 0.1023 | 0.1168 | ||
PSZ-FINE STORAGE | 1.6745 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6745 | 0.2536 | 1.0000 | 0.4247 | 0.2536 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8759 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8759 | 1.0000 | 1.0000 | 0.1023 | 0.1168 | ||
PSZ-FINE STORAGE | 1.6745 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6745 | 1.0000 | 1.0000 | 0.4247 | 0.2536 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8759 | 0.8759 | 0.8759 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6745 | 1.6745 | 1.6745 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8759 | 0.8759 | 0.8759 | 0.8759 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6745 | 1.6745 | 1.6745 | 1.6745 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8759 | 0.8759 | 0.8759 | 0.1023 | 0.2586 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6745 | 1.6745 | 1.6745 | 0.4247 | 0.3779 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8759 | 0.8759 | 0.8759 | 0.8759 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6745 | 1.6745 | 1.6745 | 1.6745 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.83 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 67.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 905.05 | 289701.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 5.50 | 9027.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 227.09 | 19422.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 56.96 | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.50 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.98 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 41.52 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.64 | 2852.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.50 | 495.20 |
Natural Gas | 0.00 | 905.05 |
Additional | 0.00 | 0.00 |
Total | 136.50 | 1400.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.97 |
Space Heating | 0.00 |
Space Cooling | 1.14 |
Fans (All) | 8.79 |
Service Water Heating | 5.51 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 102.42 |
Subtotal | 102.42 |
Natural Gas [MJ/m2] | |
Space Heating | 187.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 187.18 |
Subtotal | 187.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.22 |
Space Heating | 64.63 |
Space Cooling | 0.39 |
Fans (All) | 3.04 |
Service Water Heating | 1.90 |
Receptacle Equipment | 9.75 |
Miscellaneous | 4.07 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 2967. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288926E+12 |
February | 0.000 | 0.162082E+12 |
March | 0.000 | 0.117024E+12 |
April | 0.000 | 0.282785E+11 |
May | 0.000 | 0.176739E+11 |
June | 0.000 | 0.169588E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 2745062.633 |
September | 0.000 | 0.962495E+09 |
October | 0.000 | 0.655849E+10 |
November | 0.000 | 0.839351E+11 |
December | 0.000 | 0.199435E+12 |
Annual Sum or Average | 0.905047E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.288926E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194918E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.8 | 0.179380E+09 | 241.92 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 | 0.210548E+09 | 236.59 | 06-MAR-10:20 | -5.9 | -7.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.195892E+09 | 268.72 | 07-APR-14:00 | 21.70 | 8.87 |
May | 45349610.99 | 1685.91 | 20-MAY-16:00 | 30.00 | 15.19 | 0.213980E+09 | 303.75 | 30-MAY-14:00 | 19.40 | 10.84 |
June | 0.130552E+10 | 4870.29 | 30-JUN-16:50 | 30.18 | 14.48 | 0.248996E+09 | 302.94 | 09-JUN-12:00 | 18.90 | 9.38 |
July | 0.359040E+10 | 12962.00 | 17-JUL-05:01 | 16.47 | 12.07 | 0.248709E+09 | 301.60 | 01-JUL-07:30 | 17.75 | 14.24 |
August | 0.325073E+10 | 13077.05 | 09-AUG-05:01 | 16.42 | 10.95 | 0.267623E+09 | 301.59 | 05-AUG-10:00 | 27.20 | 16.08 |
September | 0.129506E+10 | 13040.97 | 05-SEP-05:01 | 18.40 | 11.39 | 0.231525E+09 | 301.60 | 07-SEP-10:50 | 17.62 | 16.50 |
October | 52886041.51 | 873.69 | 18-OCT-16:00 | 24.40 | 10.99 | 0.205598E+09 | 304.63 | 19-OCT-13:39 | 21.10 | 10.13 |
November | 92953.19 | 45.08 | 09-NOV-15:40 | 8.80 | 3.64 | 0.187546E+09 | 259.31 | 04-NOV-15:20 | 16.50 | 7.80 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.1 | 0.194959E+09 | 236.59 | 04-DEC-08:30 | 2.50 | -0.3 |
Annual Sum or Average | 0.954004E+10 | 0.257967E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.179380E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.359040E+10 | 13077.05 | 30.18 | 15.19 | 0.267623E+09 | 304.63 | 27.20 | 16.50 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67016235.00 | 1718.09 | 14-JAN-10:50 | 7.85 | 3.81 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.235486E+09 | 3731.76 | 28-FEB-10:50 | 3.43 | 0.86 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.767847E+09 | 4046.17 | 25-MAR-12:00 | 1.10 | -1.5 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.758486E+09 | 5309.16 | 27-APR-11:55 | -1.1 | -3.5 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.956729E+09 | 6157.54 | 31-MAY-06:10 | 11.75 | 7.74 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.131350E+10 | 10788.83 | 30-JUN-17:50 | 29.50 | 14.56 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.467769E+10 | 29673.61 | 19-JUL-18:03 | 25.82 | 15.22 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.400467E+10 | 30490.84 | 08-AUG-20:01 | 26.83 | 14.73 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.203454E+10 | 22133.51 | 03-SEP-13:05 | 33.40 | 15.96 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.130600E+10 | 6125.70 | 05-OCT-07:05 | -2.5 | -2.9 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.781952E+09 | 4361.10 | 20-NOV-15:30 | 1.95 | -2.7 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.246844E+09 | 3162.75 | 09-DEC-13:20 | 4.60 | 1.29 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.171508E+11 | 0.00 | ||||||||
Minimum of Months | 67016235.00 | 1718.09 | -2.5 | -3.5 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.467769E+10 | 30490.84 | 33.40 | 15.96 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872155E+10 | 24426.51 | 31-JAN-06:31 | -8.2 |
February | 0.614519E+10 | 24475.19 | 10-FEB-06:31 | -19.6 |
March | 0.603379E+10 | 23578.09 | 06-MAR-06:11 | -17.1 |
April | 0.374013E+10 | 23708.75 | 06-APR-05:42 | 5.50 |
May | 0.255656E+10 | 23444.57 | 08-MAY-05:12 | -2.8 |
June | 0.220844E+09 | 23010.77 | 17-JUN-05:01 | 2.35 |
July | 27867205.96 | 1131.73 | 03-JUL-06:10 | 14.55 |
August | 60106180.52 | 1800.38 | 18-AUG-06:10 | 8.17 |
September | 0.520948E+09 | 23201.98 | 19-SEP-05:42 | 2.20 |
October | 0.161374E+10 | 23422.80 | 10-OCT-05:12 | -6.1 |
November | 0.393459E+10 | 23495.37 | 27-NOV-06:12 | -14.4 |
December | 0.636738E+10 | 23485.76 | 28-DEC-06:12 | -22.8 |
Annual Sum or Average | 0.399427E+11 | |||
Minimum of Months | 27867205.96 | 1131.73 | -22.8 | |
Maximum of Months | 0.872155E+10 | 24475.19 | 14.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384766E+11 | 65710.59 | 28-JAN-03:21 | -29.4 |
February | 0.236635E+11 | 65179.72 | 04-FEB-02:62 | -21.7 |
March | 0.189335E+11 | 65185.22 | 04-MAR-22:42 | -22.7 |
April | 0.789980E+10 | 63641.51 | 29-APR-03:42 | -7.6 |
May | 0.456862E+10 | 63731.99 | 08-MAY-04:12 | -2.4 |
June | 0.432438E+09 | 3255.08 | 20-JUN-16:20 | 29.40 |
July | 0.172462E+09 | 1958.32 | 10-JUL-15:30 | 26.95 |
August | 0.236790E+09 | 2079.51 | 21-AUG-16:30 | 26.70 |
September | 0.616217E+09 | 24627.28 | 19-SEP-05:38 | 2.20 |
October | 0.249780E+10 | 60382.85 | 10-OCT-05:12 | -6.1 |
November | 0.140005E+11 | 65208.07 | 27-NOV-04:02 | -15.8 |
December | 0.278412E+11 | 65690.27 | 31-DEC-06:41 | -27.9 |
Annual Sum or Average | 0.139339E+12 | |||
Minimum of Months | 0.172462E+09 | 1958.32 | -29.4 | |
Maximum of Months | 0.384766E+11 | 65710.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170441E+12 | 155903.78 | 05-JAN-16:00 | -19.4 |
February | 0.914701E+11 | 110829.55 | 03-FEB-18:57 | -16.7 |
March | 0.623437E+11 | 115129.08 | 06-MAR-03:51 | -18.3 |
April | 0.870671E+10 | 54635.44 | 29-APR-04:52 | -7.8 |
May | 0.638460E+10 | 46375.78 | 08-MAY-06:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.705136E+09 | 21281.90 | 11-OCT-06:00 | 0.00 |
November | 0.450367E+11 | 99916.26 | 27-NOV-05:00 | -15.6 |
December | 0.115343E+12 | 154686.35 | 31-DEC-03:00 | -24.4 |
Annual Sum or Average | 0.500431E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.170441E+12 | 155903.78 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.937755E+09 | 1026.46 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.806325E+09 | 1001.86 | 02-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.875215E+09 | 1019.52 | 17-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.814164E+09 | 996.89 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.809034E+09 | 973.33 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.793810E+09 | 915.89 | 16-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.789009E+09 | 953.48 | 07-JUL-07:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.860989E+09 | 965.19 | 17-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.822148E+09 | 990.66 | 11-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.858619E+09 | 1026.46 | 30-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.874473E+09 | 1026.46 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.943076E+09 | 1026.46 | 01-DEC-16:40 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.101846E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.789009E+09 | 915.89 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.943076E+09 | 1026.46 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.862930E+10 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.792548E+10 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.925537E+10 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.860339E+10 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.894234E+10 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.891642E+10 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.862930E+10 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.925537E+10 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.860339E+10 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.862930E+10 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.829035E+10 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.862930E+10 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104309E+12 | ||||
Minimum of Months | 0.792548E+10 | 8796.64 | 0.00 | 0.00 | |
Maximum of Months | 0.925537E+10 | 8796.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.962641E+10 | 9622.24 | 19-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.873189E+10 | 9521.14 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.984839E+10 | 9509.03 | 16-MAR-08:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.913507E+10 | 9235.38 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.939750E+10 | 8979.30 | 11-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.931899E+10 | 9127.74 | 30-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.911464E+10 | 8994.45 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.976421E+10 | 9242.87 | 04-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.924137E+10 | 9321.06 | 21-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.947521E+10 | 9544.56 | 28-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.924060E+10 | 9557.32 | 13-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.970574E+10 | 9569.07 | 26-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.112600E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.873189E+10 | 8979.30 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.984839E+10 | 9622.24 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.937755E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339243E+10 |
February | 0.500553E+09 | 0.806325E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241499E+10 |
March | 0.587605E+09 | 0.875215E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224266E+10 |
April | 0.544079E+09 | 0.814164E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003924.91 | 0.135405E+10 |
May | 0.565842E+09 | 0.809034E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11585805.46 | 0.127579E+10 |
June | 0.565842E+09 | 0.793810E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76186529.97 | 0.691323E+09 |
July | 0.544079E+09 | 0.789009E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180407E+09 | 0.393294E+09 |
August | 0.587605E+09 | 0.860989E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134401E+09 | 0.587240E+09 |
September | 0.544079E+09 | 0.822148E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31222409.76 | 0.948308E+09 |
October | 0.544079E+09 | 0.858619E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2309393.02 | 0.127902E+10 |
November | 0.522316E+09 | 0.874473E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192894E+10 |
December | 0.544079E+09 | 0.943076E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263074E+10 |
Annual Sum or Average | 0.659424E+10 | 0.101846E+11 | 0.291647E+11 | 0.437116E+09 | 0.191388E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.789009E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393294E+09 |
Maximum of Months | 0.587605E+09 | 0.943076E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180407E+09 | 0.339243E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214440E+11 |
February | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37029.91 | 0.149717E+11 |
March | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133324E+11 |
April | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45208505.53 | 0.756289E+10 |
May | 0.00 | 0.894234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171772E+09 | 0.723254E+10 |
June | 0.00 | 0.891642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185729E+09 | 0.469995E+10 |
July | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464273E+09 | 0.376780E+10 |
August | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411093E+09 | 0.448661E+10 |
September | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220259E+09 | 0.639501E+10 |
October | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62731774.32 | 0.713181E+10 |
November | 0.00 | 0.829035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117466E+11 |
December | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167447E+11 |
Annual Sum or Average | 0.104309E+12 | 0.156110E+10 | 0.119516E+12 | ||||||
Minimum of Months | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376780E+10 |
Maximum of Months | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464273E+09 | 0.214440E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.962641E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680009E+11 |
February | 0.00 | 0.873189E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617946E+09 | 0.397344E+11 |
March | 0.00 | 0.984839E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82358406.15 | 0.348898E+11 |
April | 0.00 | 0.913507E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205354E+10 | 0.170261E+11 |
May | 0.00 | 0.939750E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300284E+10 | 0.176297E+11 |
June | 0.00 | 0.931899E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134111E+10 | 0.149981E+11 |
July | 0.00 | 0.911464E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740764E+09 | 0.161394E+11 |
August | 0.00 | 0.976421E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457851E+09 | 0.195410E+11 |
September | 0.00 | 0.924137E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169437E+10 | 0.221024E+11 |
October | 0.00 | 0.947521E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229539E+10 | 0.180168E+11 |
November | 0.00 | 0.924060E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137042E+10 | 0.287178E+11 |
December | 0.00 | 0.970574E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255504E+09 | 0.464789E+11 |
Annual Sum or Average | 0.112600E+12 | 0.107336E+12 | 0.139121E+11 | 0.343275E+12 | |||||
Minimum of Months | 0.00 | 0.873189E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149981E+11 |
Maximum of Months | 0.00 | 0.984839E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300284E+10 | 0.680009E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1026.46 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 12054.79 | 27-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1001.86 | 02-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 10623.55 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1019.52 | 17-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9514.29 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 996.89 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 16-APR-14:00 | 5401.04 | 28-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 973.33 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.80 | 19-MAY-16:10 | 6212.76 | 22-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 915.89 | 16-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.52 | 29-JUN-16:10 | 4114.90 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 953.48 | 07-JUL-07:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 17-JUL-16:10 | 2986.39 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 965.19 | 17-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.17 | 10-AUG-17:00 | 3497.87 | 17-AUG-16:03 |
September | 659.25 | 01-SEP-07:10 | 990.66 | 11-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 955.05 | 01-SEP-16:10 | 4337.88 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1026.46 | 30-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.90 | 15-OCT-14:00 | 6290.72 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1026.46 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8315.91 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1026.46 | 01-DEC-16:40 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10926.84 | 29-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 915.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2986.39 | |||||
Maximum of Months | 659.25 | 1026.46 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.08 | 12054.79 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 39428.99 | 05-JAN-16:10 |
February | 0.00 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 26-FEB-15:00 | 21004.16 | 01-FEB-17:00 |
March | 0.00 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18271.96 | 30-MAR-08:00 |
April | 0.00 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.05 | 16-APR-16:00 | 13248.08 | 28-APR-16:00 |
May | 0.00 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3743.71 | 19-MAY-15:10 | 24373.81 | 22-MAY-06:10 |
June | 0.00 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4573.30 | 29-JUN-15:10 | 9356.84 | 14-JUN-08:00 |
July | 0.00 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.06 | 25-JUL-15:10 | 7507.62 | 08-JUL-07:00 |
August | 0.00 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.47 | 09-AUG-17:00 | 14639.35 | 17-AUG-15:05 |
September | 0.00 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4540.55 | 02-SEP-15:10 | 12554.18 | 12-SEP-03:00 |
October | 0.00 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2573.15 | 15-OCT-14:00 | 10848.37 | 31-OCT-16:00 |
November | 0.00 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17981.74 | 28-NOV-08:00 |
December | 0.00 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 20536.64 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7507.62 | |||
Maximum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.06 | 39428.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 9622.24 | 19-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 121691.03 | 05-JAN-16:00 |
February | 0.00 | 9521.14 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10578.57 | 27-FEB-13:10 | 66429.05 | 01-FEB-15:00 |
March | 0.00 | 9509.03 | 16-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5998.92 | 14-MAR-12:10 | 53735.26 | 03-MAR-09:00 |
April | 0.00 | 9235.38 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21188.53 | 07-APR-12:10 | 37776.94 | 27-APR-11:00 |
May | 0.00 | 8979.30 | 11-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27437.44 | 19-MAY-16:00 | 60027.22 | 22-MAY-08:00 |
June | 0.00 | 9127.74 | 30-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13369.96 | 29-JUN-13:00 | 30875.43 | 14-JUN-08:00 |
July | 0.00 | 8994.45 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8840.59 | 13-JUL-16:00 | 25420.07 | 08-JUL-10:00 |
August | 0.00 | 9242.87 | 04-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8281.27 | 25-AUG-16:00 | 58125.54 | 17-AUG-12:05 |
September | 0.00 | 9321.06 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15150.99 | 23-SEP-14:00 | 45309.87 | 12-SEP-11:00 |
October | 0.00 | 9544.56 | 28-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21040.56 | 12-OCT-12:10 | 27444.38 | 03-OCT-09:00 |
November | 0.00 | 9557.32 | 13-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14396.39 | 17-NOV-14:00 | 49614.94 | 27-NOV-11:00 |
December | 0.00 | 9569.07 | 26-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10880.93 | 10-DEC-02:00 | 86460.80 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 8979.30 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25420.07 | ||||
Maximum of Months | 0.00 | 9622.24 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27437.44 | 121691.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.58 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.37 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.16 |
April | 0.00 | 01-APR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.80 |
May | 1685.91 | 20-MAY-16:00 | 659.25 | 666.46 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 200.95 | 0.00 |
June | 4870.29 | 30-JUN-16:50 | 210.96 | 496.03 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.19 | 0.00 |
July | 12962.00 | 17-JUL-05:01 | 507.62 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.71 |
August | 13077.05 | 09-AUG-05:01 | 507.62 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.87 |
September | 13040.97 | 05-SEP-05:01 | 580.14 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.24 |
October | 873.69 | 18-OCT-16:00 | 659.25 | 664.36 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
November | 45.08 | 09-NOV-15:40 | 659.25 | 675.48 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.08 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13077.05 | 659.25 | 675.48 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.19 | 772.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1718.09 | 14-JAN-10:50 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.31 |
February | 3731.76 | 28-FEB-10:50 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.68 |
March | 4046.17 | 25-MAR-12:00 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.23 |
April | 5309.16 | 27-APR-11:55 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4222.28 |
May | 6157.54 | 31-MAY-06:10 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2395.05 |
June | 10788.83 | 30-JUN-17:50 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.08 | 0.00 |
July | 29673.61 | 19-JUL-18:03 | 0.00 | 1799.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.14 |
August | 30490.84 | 08-AUG-20:01 | 0.00 | 2399.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
September | 22133.51 | 03-SEP-13:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3680.12 | 0.00 |
October | 6125.70 | 05-OCT-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.57 |
November | 4361.10 | 20-NOV-15:30 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.25 |
December | 3162.75 | 09-DEC-13:20 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1718.09 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30490.84 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3680.12 | 4222.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2069.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4938.76 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38422.31 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7905.42 |
April | 0.00 | 01-APR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10141.89 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10495.21 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.81 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5828.64 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5483.85 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5707.03 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12859.81 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11637.37 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2759.73 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29379.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.81 | |
Maximum of Months | 0.00 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38422.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.442054E+11 | 37256.82 | 21-JAN-08:09 | 0.288926E+12 | 289701.43 | 05-JAN-17:10 |
February | 0.392916E+11 | 34610.82 | 01-FEB-15:50 | 0.162082E+12 | 193216.21 | 01-FEB-17:00 |
March | 0.437724E+11 | 34148.16 | 16-MAR-08:20 | 0.117024E+12 | 195351.27 | 06-MAR-03:49 |
April | 0.392084E+11 | 33896.26 | 01-APR-08:09 | 0.282785E+11 | 114531.21 | 29-APR-05:10 |
May | 0.395618E+11 | 33442.30 | 08-MAY-08:20 | 0.176739E+11 | 104914.45 | 08-MAY-05:10 |
June | 0.392281E+11 | 37041.50 | 29-JUN-14:00 | 0.169588E+09 | 8342.88 | 17-JUN-05:10 |
July | 0.405760E+11 | 42380.18 | 17-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.432980E+11 | 41940.31 | 10-AUG-14:00 | 2745062.63 | 1140.84 | 18-AUG-06:10 |
September | 0.398549E+11 | 38615.45 | 02-SEP-14:00 | 0.962495E+09 | 24565.64 | 20-SEP-06:10 |
October | 0.408299E+11 | 36841.02 | 30-OCT-07:10 | 0.655849E+10 | 58152.50 | 11-OCT-05:10 |
November | 0.411603E+11 | 37208.63 | 30-NOV-16:49 | 0.839351E+11 | 177204.36 | 27-NOV-04:10 |
December | 0.442122E+11 | 37251.69 | 28-DEC-08:09 | 0.199435E+12 | 248272.96 | 31-DEC-02:00 |
Annual Sum or Average | 0.495199E+12 | 0.905047E+12 | ||||
Minimum of Months | 0.392084E+11 | 33442.30 | 0.00 | 0.00 | ||
Maximum of Months | 0.442122E+11 | 42380.18 | 0.288926E+12 | 289701.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.191935E+11 | 0.667234E+10 | 0.112984E+11 | 0.00 | 0.470814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233307E+10 | 0.00 |
February | 0.174637E+11 | 0.536132E+10 | 0.103734E+11 | 0.00 | 0.395554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213764E+10 | 0.00 |
March | 0.199790E+11 | 0.500411E+10 | 0.121016E+11 | 0.00 | 0.427668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241112E+10 | 0.00 |
April | 0.185526E+11 | 0.390776E+10 | 0.112578E+11 | 0.00 | 0.323366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225656E+10 | 0.00 |
May | 0.191489E+11 | 0.328850E+10 | 0.117000E+11 | 0.00 | 0.311475E+10 | 0.00 | 0.00 | 27285669.08 | 0.00 | 0.00 | 0.00 | 0.228242E+10 | 0.00 |
June | 0.190292E+11 | 0.286092E+10 | 0.116594E+11 | 0.00 | 0.284587E+10 | 0.00 | 0.00 | 0.659827E+09 | 0.00 | 0.00 | 0.00 | 0.217292E+10 | 0.00 |
July | 0.185329E+11 | 0.307744E+10 | 0.112984E+11 | 0.00 | 0.324086E+10 | 0.00 | 0.00 | 0.228456E+10 | 0.00 | 0.00 | 0.00 | 0.214187E+10 | 0.00 |
August | 0.198806E+11 | 0.368084E+10 | 0.121016E+11 | 0.00 | 0.356184E+10 | 0.00 | 0.00 | 0.189123E+10 | 0.00 | 0.00 | 0.00 | 0.218192E+10 | 0.00 |
September | 0.186669E+11 | 0.443112E+10 | 0.112578E+11 | 0.00 | 0.277411E+10 | 0.00 | 0.00 | 0.630715E+09 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
October | 0.189631E+11 | 0.554598E+10 | 0.112984E+11 | 0.00 | 0.283398E+10 | 0.00 | 0.00 | 5744944.90 | 0.00 | 0.00 | 0.00 | 0.218274E+10 | 0.00 |
November | 0.184054E+11 | 0.621808E+10 | 0.108562E+11 | 0.00 | 0.352235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215827E+10 | 0.00 |
December | 0.192781E+11 | 0.691283E+10 | 0.112984E+11 | 0.00 | 0.443203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229085E+10 | 0.00 |
Annual Sum or Average | 0.227094E+12 | 0.569612E+11 | 0.136501E+12 | 0.424998E+11 | 0.00 | 0.549937E+10 | 0.266436E+11 | ||||||
Minimum of Months | 0.174637E+11 | 0.286092E+10 | 0.103734E+11 | 0.00 | 0.277411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209424E+10 | 0.00 |
Maximum of Months | 0.199790E+11 | 0.691283E+10 | 0.121016E+11 | 0.00 | 0.470814E+10 | 0.00 | 0.00 | 0.228456E+10 | 0.00 | 0.00 | 0.00 | 0.241112E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.288926E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.162082E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.117024E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.282785E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.176739E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169588E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2745062.63 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.962495E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.655849E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.839351E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.199435E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.905047E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.288926E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 19422.15 | 19-JAN-09:09 | 5073.70 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3155.86 | 03-JAN-09:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 19282.16 | 01-FEB-09:09 | 5073.70 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3155.86 | 02-FEB-09:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 19271.42 | 16-MAR-08:09 | 5073.70 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3155.86 | 04-MAR-13:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19000.23 | 01-APR-08:09 | 5073.70 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 3155.86 | 15-APR-07:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 18632.55 | 02-MAY-08:09 | 5073.70 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 3155.86 | 03-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 18816.77 | 30-JUN-08:09 | 4571.25 | 01-JUN-20:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 2761.48 | 01-JUN-06:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 18707.53 | 07-JUL-08:09 | 4571.25 | 01-JUL-20:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 5066.78 | 17-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 18956.60 | 04-AUG-08:09 | 5073.70 | 03-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 5066.78 | 05-AUG-13:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 19034.01 | 16-SEP-08:09 | 5073.70 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 2761.48 | 01-SEP-06:49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 19313.45 | 28-OCT-08:09 | 5073.70 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 3155.86 | 10-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 19285.92 | 03-NOV-08:09 | 5073.70 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3155.86 | 16-NOV-07:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19346.49 | 26-DEC-09:09 | 5073.70 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3155.86 | 01-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 18632.55 | 4571.25 | 10035.17 | 0.00 | 2761.48 | 0.00 | 0.00 | |||||
Maximum of Months | 19422.15 | 5073.70 | 10035.17 | 0.00 | 5066.78 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2832.59 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2852.40 | 15-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2840.98 | 04-MAR-12:00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2749.21 | 01-APR-11:20 | 0.00 |
May | 779.86 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2559.46 | 01-MAY-11:50 | 0.00 |
June | 4979.21 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2244.88 | 06-JUN-11:30 | 0.00 |
July | 9027.07 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2028.85 | 01-JUL-11:00 | 0.00 |
August | 7436.67 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1829.17 | 05-AUG-11:00 | 0.00 |
September | 6329.74 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1963.11 | 30-SEP-11:00 | 0.00 |
October | 410.98 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2217.25 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2472.13 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2702.56 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1829.17 | 0.00 | ||
Maximum of Months | 9027.07 | 0.00 | 0.00 | 0.00 | 2852.40 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 37256.82 | 21-JAN-08:09 | 17326.12 | 10035.17 | 5073.70 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34610.82 | 01-FEB-15:50 | 19060.21 | 10035.17 | 0.00 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34148.16 | 16-MAR-08:20 | 19248.44 | 10035.17 | 0.00 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33896.26 | 01-APR-08:09 | 19000.23 | 10035.17 | 0.00 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33442.30 | 08-MAY-08:20 | 18559.04 | 10035.17 | 0.00 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37041.50 | 29-JUN-14:00 | 17976.64 | 10035.17 | 0.00 | 0.00 | 2761.48 | 0.00 | 0.00 | 4486.96 | 0.00 |
July | 42380.18 | 17-JUL-13:00 | 18095.39 | 10035.17 | 0.00 | 0.00 | 5066.78 | 0.00 | 0.00 | 7447.99 | 0.00 |
August | 41940.31 | 10-AUG-14:00 | 17976.64 | 10035.17 | 0.00 | 0.00 | 5066.78 | 0.00 | 0.00 | 7095.13 | 0.00 |
September | 38615.45 | 02-SEP-14:00 | 18293.83 | 10035.17 | 0.00 | 0.00 | 2761.48 | 0.00 | 0.00 | 5757.68 | 0.00 |
October | 36841.02 | 30-OCT-07:10 | 17326.12 | 10035.17 | 5073.70 | 0.00 | 2761.48 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37208.63 | 30-NOV-16:49 | 17326.12 | 10035.17 | 5073.70 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37251.69 | 28-DEC-08:09 | 17326.12 | 10035.17 | 5073.70 | 0.00 | 3155.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 33442.30 | 17326.12 | 10035.17 | 0.00 | 0.00 | 2761.48 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42380.18 | 19248.44 | 10035.17 | 5073.70 | 0.00 | 5066.78 | 0.00 | 0.00 | 7447.99 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 289701.43 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 193216.21 | 01-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 195351.27 | 06-MAR-03:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 114531.21 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 104914.45 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8342.88 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1140.84 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24565.64 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 58152.50 | 11-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 177204.36 | 27-NOV-04:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 248272.96 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 289701.43 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 16.57 | 10.00 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.50 | 18.61 | 8.50 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.33 | 18.01 | 9.67 | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.67 | 19.50 | 8.33 | 19.68 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7.17 | 19.70 | 7.00 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.67 | 20.34 | 1.67 | 20.34 | 0.33 | 24.48 | 0.33 | 24.48 |
October | 4.33 | 20.18 | 4.33 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.33 | 19.24 | 8.17 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.50 | 18.05 | 8.83 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.83 | 18.22 | 66.83 | 19.54 | 0.67 | 24.51 | 0.67 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.00 | 20.53 | 10.00 | 20.53 | 0.33 | 24.54 | 0.33 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.50 | 14.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90.33 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88.17 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35.17 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21.50 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.30 | 0.00 | 0.00 |
September | 0.17 | 15.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 0.00 |
October | 7.50 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57.33 | 14.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 110.67 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 523.33 | 14.47 | 0.00 | 2.67 | 27.30 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.50 | 15.00 | 0.00 | 0.00 | 1.50 | 27.31 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 8.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 8.88 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 8.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.10 | 295.67 | 21.09 | 295.67 | 21.09 |
May | 312.00 | 21.59 | 235.83 | 21.10 | 235.83 | 21.10 |
June | 253.83 | 23.10 | 24.83 | 21.17 | 24.17 | 21.09 |
July | 75.67 | 23.76 | 82.50 | 23.90 | 0.00 | 0.00 |
August | 148.17 | 23.64 | 43.50 | 23.91 | 0.00 | 0.00 |
September | 226.33 | 22.55 | 98.00 | 22.19 | 60.67 | 21.14 |
October | 300.00 | 21.58 | 216.83 | 21.15 | 216.83 | 21.15 |
November | 288.00 | 21.08 | 286.33 | 21.07 | 286.33 | 21.07 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3104.00 | 21.63 | 2483.50 | 21.26 | 2319.50 | 21.07 |
Minimum of Months | 75.67 | 21.03 | 24.83 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.76 | 324.00 | 23.91 | 324.00 | 21.15 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.121284E+09 | 27285669.08 | 23.67 | 0.121284E+09 | 0.00 | 0.00 | 0.50 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 3323.18 | 20-MAY-16:00 | 3323.18 | 20-MAY-16:00 | 0.00 | 20-MAY-14:10 | 779.86 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.185593E+10 | 0.401209E+09 | 175.53 | 0.180998E+10 | 45947424.21 | 0.00 | 0.96 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 | 6620.74 | 30-JUN-16:00 | 6620.74 | 30-JUN-16:00 | 706.85 | 20-JUN-17:00 | 1511.34 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 0.467975E+10 | 0.100397E+10 | 274.99 | 0.460052E+10 | 79236082.26 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15329.91 | 19-JUL-05:02 | 14455.54 | 17-JUL-05:01 | 2110.23 | 19-JUL-05:03 | 3063.21 | 19-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.412056E+10 | 0.883682E+09 | 274.45 | 0.410906E+10 | 11500434.20 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 14579.46 | 09-AUG-05:01 | 14579.46 | 09-AUG-05:01 | 307.72 | 01-AUG-14:00 | 2931.89 | 09-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.165236E+10 | 0.347306E+09 | 136.07 | 0.156528E+10 | 87071878.22 | 0.00 | 1.00 | 02-SEP-05:03 | 0.00 | 01-SEP-00:10 | 15604.13 | 08-SEP-05:03 | 14478.77 | 05-SEP-05:01 | 3323.12 | 08-SEP-05:03 | 3108.51 | 08-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 26096036.58 | 5744944.90 | 8.17 | 26096036.58 | 0.00 | 0.00 | 0.29 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 1897.82 | 18-OCT-16:00 | 1897.82 | 18-OCT-16:00 | 0.00 | 18-OCT-15:50 | 410.98 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.124560E+11 | 0.266920E+10 | 892.87 | 0.122322E+11 | 0.223756E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.467975E+10 | 0.100397E+10 | 274.99 | 0.460052E+10 | 87071878.22 | 0.00 | 1.00 | 0.00 | 15604.13 | 14579.46 | 3323.12 | 3108.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.102734E+10 | 0.258618E+09 | 44.92 | 0.101584E+10 | 11500005.57 | 0.00 | 0.85 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 | 13728.75 | 29-JUN-15:10 | 13728.75 | 29-JUN-15:10 | 468.01 | 22-JUN-13:40 | 3467.88 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 0.514737E+10 | 0.128060E+10 | 171.01 | 0.506170E+10 | 85676699.39 | 0.00 | 1.00 | 16-JUL-11:21 | 0.00 | 01-JUL-00:10 | 34904.56 | 16-JUL-11:21 | 32212.86 | 19-JUL-17:42 | 5960.82 | 16-JUL-11:30 | 8277.94 | 17-JUL-17:43 | 0.00 | 01-JUL-00:10 |
August | 0.403550E+10 | 0.100755E+10 | 132.12 | 0.402605E+10 | 9453533.53 | 0.00 | 1.00 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 | 32412.89 | 08-AUG-20:01 | 32412.89 | 08-AUG-20:01 | 1156.98 | 08-AUG-12:00 | 7887.37 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.113977E+10 | 0.283408E+09 | 42.37 | 0.105501E+10 | 84767199.40 | 0.00 | 0.99 | 02-SEP-15:30 | 0.00 | 01-SEP-00:10 | 24754.50 | 03-SEP-13:05 | 24754.50 | 03-SEP-13:05 | 4370.90 | 07-SEP-15:40 | 6520.91 | 03-SEP-13:05 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.113500E+11 | 0.283018E+10 | 390.42 | 0.111586E+11 | 0.191397E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.514737E+10 | 0.128060E+10 | 171.01 | 0.506170E+10 | 85676699.39 | 0.00 | 1.00 | 0.00 | 34904.56 | 32412.89 | 5960.82 | 8277.94 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.41 | 22.91 | 33.49 | 23.20 | 198.53 | 0.00 | 0.00 | 744.00 |
February | 95.56 | 47.03 | 48.53 | 66.31 | 136.40 | 0.00 | 0.00 | 672.00 |
March | 122.68 | 45.06 | 77.62 | 91.64 | 107.42 | 0.00 | 0.00 | 744.00 |
April | 159.87 | 70.63 | 89.25 | 153.25 | 68.79 | 0.00 | 0.00 | 720.00 |
May | 197.75 | 90.19 | 107.55 | 205.30 | 54.05 | 0.00 | 0.00 | 744.00 |
June | 214.97 | 98.69 | 116.28 | 237.93 | 42.72 | 0.00 | 0.00 | 720.00 |
July | 220.45 | 111.43 | 109.02 | 257.26 | 43.03 | 0.00 | 0.00 | 744.00 |
August | 186.81 | 91.43 | 95.38 | 210.21 | 46.47 | 0.00 | 0.00 | 744.00 |
September | 150.43 | 76.02 | 74.42 | 157.88 | 59.51 | 0.00 | 0.00 | 720.00 |
October | 107.72 | 53.54 | 54.18 | 97.54 | 78.12 | 0.00 | 0.00 | 744.00 |
November | 76.13 | 37.77 | 38.35 | 52.88 | 111.53 | 0.00 | 0.00 | 720.00 |
December | 51.07 | 21.52 | 29.55 | 21.71 | 164.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 136.84 | 63.91 | 72.93 | 131.58 | 92.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 51.07 | 21.52 | 29.55 | 21.71 | 42.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 220.45 | 111.43 | 116.28 | 257.26 | 198.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.41 | 22.91 | 33.49 | 23.20 | 198.53 | 0.00 | 0.00 | 744.00 |
February | 95.56 | 47.03 | 48.53 | 66.31 | 136.40 | 0.00 | 0.00 | 672.00 |
March | 122.68 | 45.06 | 77.62 | 91.64 | 107.42 | 0.00 | 0.00 | 744.00 |
April | 159.87 | 70.63 | 89.25 | 153.25 | 68.79 | 0.00 | 0.00 | 720.00 |
May | 197.75 | 90.19 | 107.55 | 205.30 | 54.05 | 0.00 | 0.00 | 744.00 |
June | 214.97 | 98.69 | 116.28 | 237.93 | 42.72 | 0.00 | 0.00 | 720.00 |
July | 220.45 | 111.43 | 109.02 | 257.26 | 43.03 | 0.00 | 0.00 | 744.00 |
August | 186.81 | 91.43 | 95.38 | 210.21 | 46.47 | 0.00 | 0.00 | 744.00 |
September | 150.43 | 76.02 | 74.42 | 157.88 | 59.51 | 0.00 | 0.00 | 720.00 |
October | 107.72 | 53.54 | 54.18 | 97.54 | 78.12 | 0.00 | 0.00 | 744.00 |
November | 76.13 | 37.77 | 38.35 | 52.88 | 111.53 | 0.00 | 0.00 | 720.00 |
December | 51.07 | 21.52 | 29.55 | 21.71 | 164.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 136.84 | 63.91 | 72.93 | 131.58 | 92.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 51.07 | 21.52 | 29.55 | 21.71 | 42.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 220.45 | 111.43 | 116.28 | 257.26 | 198.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.72 | 0.00 | 15.72 | 0.54 | 121.85 | 0.00 | 0.00 | 744.00 |
February | 22.20 | 0.00 | 22.20 | 4.32 | 85.44 | 0.00 | 0.00 | 672.00 |
March | 36.06 | 0.00 | 36.06 | 12.78 | 64.69 | 0.00 | 0.00 | 744.00 |
April | 41.24 | 0.31 | 40.93 | 24.00 | 40.49 | 0.00 | 0.00 | 720.00 |
May | 53.95 | 3.15 | 50.80 | 38.78 | 30.67 | 0.00 | 0.00 | 744.00 |
June | 62.79 | 7.16 | 55.63 | 53.36 | 22.48 | 0.00 | 0.00 | 720.00 |
July | 57.35 | 5.29 | 52.06 | 54.43 | 23.06 | 0.00 | 0.00 | 744.00 |
August | 46.50 | 1.67 | 44.83 | 42.18 | 26.26 | 0.00 | 0.00 | 744.00 |
September | 34.50 | 0.03 | 34.48 | 26.45 | 35.09 | 0.00 | 0.00 | 720.00 |
October | 25.14 | 0.00 | 25.14 | 12.05 | 46.87 | 0.00 | 0.00 | 744.00 |
November | 17.09 | 0.00 | 17.09 | 3.37 | 69.40 | 0.00 | 0.00 | 720.00 |
December | 13.18 | 0.00 | 13.18 | 0.31 | 102.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.55 | 1.48 | 34.07 | 22.82 | 55.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.18 | 0.00 | 13.18 | 0.31 | 22.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 62.79 | 7.16 | 55.63 | 54.43 | 121.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.72 | 0.00 | 15.72 | 0.54 | 121.85 | 0.00 | 0.00 | 744.00 |
February | 22.20 | 0.00 | 22.20 | 4.32 | 85.44 | 0.00 | 0.00 | 672.00 |
March | 36.06 | 0.00 | 36.06 | 12.78 | 64.69 | 0.00 | 0.00 | 744.00 |
April | 41.24 | 0.31 | 40.93 | 24.00 | 40.49 | 0.00 | 0.00 | 720.00 |
May | 53.95 | 3.15 | 50.80 | 38.78 | 30.67 | 0.00 | 0.00 | 744.00 |
June | 62.79 | 7.16 | 55.62 | 53.36 | 22.48 | 0.00 | 0.00 | 720.00 |
July | 57.35 | 5.29 | 52.06 | 54.43 | 23.06 | 0.00 | 0.00 | 744.00 |
August | 46.50 | 1.67 | 44.83 | 42.18 | 26.26 | 0.00 | 0.00 | 744.00 |
September | 34.50 | 0.03 | 34.47 | 26.45 | 35.09 | 0.00 | 0.00 | 720.00 |
October | 25.14 | 0.00 | 25.14 | 12.05 | 46.87 | 0.00 | 0.00 | 744.00 |
November | 17.09 | 0.00 | 17.09 | 3.37 | 69.40 | 0.00 | 0.00 | 720.00 |
December | 13.18 | 0.00 | 13.18 | 0.31 | 102.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.55 | 1.48 | 34.07 | 22.82 | 55.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.18 | 0.00 | 13.18 | 0.31 | 22.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 62.79 | 7.16 | 55.62 | 54.43 | 121.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.13 | 11.95 | 17.17 | 16.88 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 48.25 | 26.42 | 21.83 | 45.93 | 56.13 | 0.00 | 0.00 | 672.00 |
March | 79.45 | 37.88 | 41.57 | 88.93 | 44.14 | 0.00 | 0.00 | 744.00 |
April | 98.62 | 55.22 | 43.41 | 120.59 | 28.75 | 0.00 | 0.00 | 720.00 |
May | 126.57 | 72.28 | 54.29 | 161.68 | 23.49 | 0.00 | 0.00 | 744.00 |
June | 152.43 | 97.95 | 54.49 | 195.34 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 157.86 | 110.55 | 47.31 | 200.70 | 31.45 | 0.00 | 0.00 | 744.00 |
August | 131.49 | 89.75 | 41.75 | 163.51 | 33.38 | 0.00 | 0.00 | 744.00 |
September | 91.21 | 57.89 | 33.32 | 111.74 | 32.50 | 0.00 | 0.00 | 720.00 |
October | 56.54 | 31.36 | 25.18 | 64.59 | 35.90 | 0.00 | 0.00 | 744.00 |
November | 34.04 | 16.60 | 17.44 | 31.59 | 45.59 | 0.00 | 0.00 | 720.00 |
December | 22.79 | 8.76 | 14.03 | 12.83 | 67.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 85.92 | 51.53 | 34.39 | 101.50 | 42.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.79 | 8.76 | 14.03 | 12.83 | 23.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 157.86 | 110.55 | 54.49 | 200.70 | 81.74 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151082E+09 | 61373978.15 | 89707848.97 | 62136114.17 | 0.531744E+09 |
February | 0.231184E+09 | 0.113776E+09 | 0.117408E+09 | 0.160407E+09 | 0.329977E+09 |
March | 0.328590E+09 | 0.120694E+09 | 0.207897E+09 | 0.245454E+09 | 0.287719E+09 |
April | 0.414392E+09 | 0.183062E+09 | 0.231330E+09 | 0.397217E+09 | 0.178310E+09 |
May | 0.529643E+09 | 0.241572E+09 | 0.288070E+09 | 0.549887E+09 | 0.144775E+09 |
June | 0.557215E+09 | 0.255808E+09 | 0.301407E+09 | 0.616712E+09 | 0.110742E+09 |
July | 0.590456E+09 | 0.298448E+09 | 0.292008E+09 | 0.689034E+09 | 0.115263E+09 |
August | 0.500360E+09 | 0.244886E+09 | 0.255473E+09 | 0.563031E+09 | 0.124468E+09 |
September | 0.389927E+09 | 0.197038E+09 | 0.192889E+09 | 0.409228E+09 | 0.154242E+09 |
October | 0.288519E+09 | 0.143415E+09 | 0.145105E+09 | 0.261259E+09 | 0.209236E+09 |
November | 0.197318E+09 | 97905869.73 | 99412313.77 | 0.137065E+09 | 0.289081E+09 |
December | 0.136783E+09 | 57640862.75 | 79142485.73 | 58160582.80 | 0.440974E+09 |
Annual Sum or Average | 0.431547E+10 | 0.201562E+10 | 0.229985E+10 | 0.414959E+10 | 0.291653E+10 |
Minimum of Months | 0.136783E+09 | 57640862.75 | 79142485.73 | 58160582.80 | 0.110742E+09 |
Maximum of Months | 0.590456E+09 | 0.298448E+09 | 0.301407E+09 | 0.689034E+09 | 0.531744E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151082E+09 | 61373978.15 | 89707848.97 | 62136114.17 | 0.531744E+09 |
February | 0.231184E+09 | 0.113776E+09 | 0.117408E+09 | 0.160407E+09 | 0.329977E+09 |
March | 0.328590E+09 | 0.120694E+09 | 0.207897E+09 | 0.245454E+09 | 0.287719E+09 |
April | 0.414392E+09 | 0.183062E+09 | 0.231330E+09 | 0.397217E+09 | 0.178310E+09 |
May | 0.529643E+09 | 0.241572E+09 | 0.288070E+09 | 0.549887E+09 | 0.144775E+09 |
June | 0.557215E+09 | 0.255808E+09 | 0.301407E+09 | 0.616712E+09 | 0.110742E+09 |
July | 0.590456E+09 | 0.298448E+09 | 0.292008E+09 | 0.689034E+09 | 0.115263E+09 |
August | 0.500360E+09 | 0.244886E+09 | 0.255473E+09 | 0.563031E+09 | 0.124468E+09 |
September | 0.389927E+09 | 0.197038E+09 | 0.192889E+09 | 0.409228E+09 | 0.154242E+09 |
October | 0.288519E+09 | 0.143415E+09 | 0.145105E+09 | 0.261259E+09 | 0.209236E+09 |
November | 0.197318E+09 | 97905869.73 | 99412313.77 | 0.137065E+09 | 0.289081E+09 |
December | 0.136783E+09 | 57640862.75 | 79142485.73 | 58160582.80 | 0.440974E+09 |
Annual Sum or Average | 0.431547E+10 | 0.201562E+10 | 0.229985E+10 | 0.414959E+10 | 0.291653E+10 |
Minimum of Months | 0.136783E+09 | 57640862.75 | 79142485.73 | 58160582.80 | 0.110742E+09 |
Maximum of Months | 0.590456E+09 | 0.298448E+09 | 0.301407E+09 | 0.689034E+09 | 0.531744E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42108649.19 | 0.00 | 42108649.19 | 1435696.17 | 0.326376E+09 |
February | 53701106.73 | 0.00 | 53701106.73 | 10455937.06 | 0.206688E+09 |
March | 96592997.19 | 4816.83 | 96588180.36 | 34232093.64 | 0.173278E+09 |
April | 0.106889E+09 | 801246.13 | 0.106088E+09 | 62215995.01 | 0.104938E+09 |
May | 0.144498E+09 | 8441031.82 | 0.136057E+09 | 0.103863E+09 | 82145601.54 |
June | 0.162749E+09 | 18568572.38 | 0.144180E+09 | 0.138309E+09 | 58269988.71 |
July | 0.153607E+09 | 14174444.61 | 0.139432E+09 | 0.145777E+09 | 61775488.18 |
August | 0.124548E+09 | 4479755.28 | 0.120068E+09 | 0.112983E+09 | 70339299.49 |
September | 89435934.16 | 76376.10 | 89359558.06 | 68566191.42 | 90956659.16 |
October | 67345408.63 | 0.00 | 67345408.63 | 32281992.38 | 0.125530E+09 |
November | 44305195.36 | 0.00 | 44305195.36 | 8731959.74 | 0.179874E+09 |
December | 35310475.43 | 0.00 | 35310475.43 | 828390.21 | 0.273238E+09 |
Annual Sum or Average | 0.112109E+10 | 46546243.15 | 0.107454E+10 | 0.719681E+09 | 0.175341E+10 |
Minimum of Months | 35310475.43 | 0.00 | 35310475.43 | 828390.21 | 58269988.71 |
Maximum of Months | 0.162749E+09 | 18568572.38 | 0.144180E+09 | 0.145777E+09 | 0.326376E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42107291.32 | 0.00 | 42107291.32 | 1435523.15 | 0.326376E+09 |
February | 53699489.55 | 0.00 | 53699489.55 | 10455279.83 | 0.206688E+09 |
March | 96589946.41 | 4816.60 | 96585129.81 | 34229820.85 | 0.173278E+09 |
April | 0.106886E+09 | 801208.58 | 0.106085E+09 | 62213317.70 | 0.104938E+09 |
May | 0.144494E+09 | 8440636.18 | 0.136053E+09 | 0.103859E+09 | 82145526.41 |
June | 0.162744E+09 | 18567702.05 | 0.144176E+09 | 0.138305E+09 | 58269726.04 |
July | 0.153602E+09 | 14173780.24 | 0.139429E+09 | 0.145773E+09 | 61774974.88 |
August | 0.124544E+09 | 4479545.30 | 0.120065E+09 | 0.112980E+09 | 70338927.05 |
September | 89433375.53 | 76372.52 | 89357003.01 | 68564034.58 | 90956282.08 |
October | 67343369.15 | 0.00 | 67343369.15 | 32280434.71 | 0.125529E+09 |
November | 44303805.99 | 0.00 | 44303805.99 | 8731403.04 | 0.179873E+09 |
December | 35309321.31 | 0.00 | 35309321.31 | 828270.71 | 0.273238E+09 |
Annual Sum or Average | 0.112106E+10 | 46544061.46 | 0.107451E+10 | 0.719655E+09 | 0.175340E+10 |
Minimum of Months | 35309321.31 | 0.00 | 35309321.31 | 828270.71 | 58269726.04 |
Maximum of Months | 0.162744E+09 | 18567702.05 | 0.144176E+09 | 0.145773E+09 | 0.326376E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78014842.87 | 32019038.12 | 45995804.75 | 45204977.52 | 0.218929E+09 |
February | 0.116735E+09 | 63914258.30 | 52820577.27 | 0.111119E+09 | 0.135797E+09 |
March | 0.212786E+09 | 0.101445E+09 | 0.111341E+09 | 0.238202E+09 | 0.118218E+09 |
April | 0.255632E+09 | 0.143123E+09 | 0.112510E+09 | 0.312558E+09 | 74522915.98 |
May | 0.339011E+09 | 0.193607E+09 | 0.145404E+09 | 0.433054E+09 | 62922986.53 |
June | 0.395111E+09 | 0.253881E+09 | 0.141230E+09 | 0.506327E+09 | 63488074.10 |
July | 0.422803E+09 | 0.296087E+09 | 0.126716E+09 | 0.537548E+09 | 84228688.35 |
August | 0.352196E+09 | 0.240383E+09 | 0.111813E+09 | 0.437943E+09 | 89393012.17 |
September | 0.236426E+09 | 0.150058E+09 | 86368496.07 | 0.289629E+09 | 84227287.44 |
October | 0.151447E+09 | 84003537.57 | 67443765.44 | 0.172988E+09 | 96158077.77 |
November | 88242172.78 | 43029184.63 | 45212988.14 | 81877271.47 | 0.118172E+09 |
December | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 0.179862E+09 |
Annual Sum or Average | 0.270943E+10 | 0.162500E+10 | 0.108443E+10 | 0.320082E+10 | 0.132592E+10 |
Minimum of Months | 61028446.81 | 23452693.28 | 37575753.53 | 34368517.17 | 62922986.53 |
Maximum of Months | 0.422803E+09 | 0.296087E+09 | 0.145404E+09 | 0.537548E+09 | 0.218929E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 39.46 | 632.76 | 144.26 | 45.83 | 98.43 | 0.00 | 0.00 |
February | 133.75 | 436.17 | 235.52 | 94.06 | 141.46 | 0.00 | 0.00 |
March | 205.77 | 341.16 | 317.49 | 90.13 | 227.36 | 0.00 | 0.00 |
April | 353.41 | 217.46 | 402.22 | 141.87 | 260.35 | 0.00 | 0.00 |
May | 487.46 | 168.74 | 503.39 | 186.69 | 316.70 | 0.00 | 0.00 |
June | 579.84 | 127.68 | 555.53 | 211.71 | 343.82 | 0.00 | 0.00 |
July | 620.66 | 129.49 | 555.60 | 233.44 | 322.16 | 0.00 | 0.00 |
August | 504.33 | 145.01 | 466.63 | 186.21 | 280.42 | 0.00 | 0.00 |
September | 367.73 | 188.26 | 369.88 | 152.09 | 217.78 | 0.00 | 0.00 |
October | 216.74 | 247.52 | 265.73 | 107.09 | 158.64 | 0.00 | 0.00 |
November | 105.30 | 354.65 | 186.44 | 75.54 | 110.89 | 0.00 | 0.00 |
December | 36.26 | 525.53 | 128.50 | 43.04 | 85.46 | 0.00 | 0.00 |
Annual Sum or Average | 305.11 | 292.47 | 344.78 | 130.78 | 214.00 | 0.00 | 0.00 |
Minimum of Months | 36.26 | 127.68 | 128.50 | 43.04 | 85.46 | 0.00 | 0.00 |
Maximum of Months | 620.66 | 632.76 | 555.60 | 233.44 | 343.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.78 | 817.39 | 291.27 | 119.55 | 171.73 | 0.00 | 0.00 |
February | 459.32 | 561.33 | 482.53 | 264.20 | 218.34 | 0.00 | 0.00 |
March | 889.34 | 441.37 | 794.45 | 378.75 | 415.70 | 0.00 | 0.00 |
April | 1205.86 | 287.51 | 986.23 | 552.17 | 434.06 | 0.00 | 0.00 |
May | 1616.84 | 234.93 | 1265.72 | 722.85 | 542.88 | 0.00 | 0.00 |
June | 1953.42 | 244.94 | 1524.35 | 979.48 | 544.87 | 0.00 | 0.00 |
July | 2006.97 | 314.47 | 1578.57 | 1105.46 | 473.10 | 0.00 | 0.00 |
August | 1635.09 | 333.76 | 1314.95 | 897.49 | 417.46 | 0.00 | 0.00 |
September | 1117.39 | 324.95 | 912.14 | 578.93 | 333.21 | 0.00 | 0.00 |
October | 645.86 | 359.01 | 565.44 | 313.63 | 251.81 | 0.00 | 0.00 |
November | 315.88 | 455.91 | 340.44 | 166.01 | 174.43 | 0.00 | 0.00 |
December | 128.32 | 671.53 | 227.85 | 87.56 | 140.29 | 0.00 | 0.00 |
Annual Sum or Average | 1014.97 | 420.45 | 859.16 | 515.29 | 343.87 | 0.00 | 0.00 |
Minimum of Months | 128.32 | 234.93 | 227.85 | 87.56 | 140.29 | 0.00 | 0.00 |
Maximum of Months | 2006.97 | 817.39 | 1578.57 | 1105.46 | 544.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105687E+09 | 0.169478E+10 | 0.386380E+09 | 0.122748E+09 | 0.263632E+09 | 0.00 | 0.00 |
February | 0.323574E+09 | 0.105518E+10 | 0.569768E+09 | 0.227552E+09 | 0.342216E+09 | 0.00 | 0.00 |
March | 0.551132E+09 | 0.913757E+09 | 0.850363E+09 | 0.241397E+09 | 0.608966E+09 | 0.00 | 0.00 |
April | 0.916029E+09 | 0.563660E+09 | 0.104256E+10 | 0.367726E+09 | 0.674834E+09 | 0.00 | 0.00 |
May | 0.130562E+10 | 0.451962E+09 | 0.134828E+10 | 0.500026E+09 | 0.848252E+09 | 0.00 | 0.00 |
June | 0.150295E+10 | 0.330935E+09 | 0.143992E+10 | 0.548752E+09 | 0.891170E+09 | 0.00 | 0.00 |
July | 0.166238E+10 | 0.346835E+09 | 0.148812E+10 | 0.625245E+09 | 0.862877E+09 | 0.00 | 0.00 |
August | 0.135080E+10 | 0.388387E+09 | 0.124981E+10 | 0.498732E+09 | 0.751079E+09 | 0.00 | 0.00 |
September | 0.953153E+09 | 0.487963E+09 | 0.958723E+09 | 0.394228E+09 | 0.564494E+09 | 0.00 | 0.00 |
October | 0.580512E+09 | 0.662963E+09 | 0.711727E+09 | 0.286829E+09 | 0.424898E+09 | 0.00 | 0.00 |
November | 0.272945E+09 | 0.919261E+09 | 0.483245E+09 | 0.195812E+09 | 0.287434E+09 | 0.00 | 0.00 |
December | 97130530.50 | 0.140758E+10 | 0.344186E+09 | 0.115282E+09 | 0.228905E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962190E+10 | 0.922326E+10 | 0.108731E+11 | 0.412433E+10 | 0.674876E+10 | 0.00 | 0.00 |
Minimum of Months | 97130530.50 | 0.330935E+09 | 0.344186E+09 | 0.115282E+09 | 0.228905E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166238E+10 | 0.169478E+10 | 0.148812E+10 | 0.625245E+09 | 0.891170E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452050E+09 | 0.218929E+10 | 0.780148E+09 | 0.320190E+09 | 0.459958E+09 | 0.00 | 0.00 |
February | 0.111119E+10 | 0.135797E+10 | 0.116735E+10 | 0.639143E+09 | 0.528206E+09 | 0.00 | 0.00 |
March | 0.238201E+10 | 0.118218E+10 | 0.212786E+10 | 0.101445E+10 | 0.111341E+10 | 0.00 | 0.00 |
April | 0.312558E+10 | 0.745225E+09 | 0.255632E+10 | 0.143123E+10 | 0.112510E+10 | 0.00 | 0.00 |
May | 0.433054E+10 | 0.629230E+09 | 0.339011E+10 | 0.193607E+10 | 0.145404E+10 | 0.00 | 0.00 |
June | 0.506327E+10 | 0.634880E+09 | 0.395111E+10 | 0.253881E+10 | 0.141230E+10 | 0.00 | 0.00 |
July | 0.537548E+10 | 0.842287E+09 | 0.422803E+10 | 0.296087E+10 | 0.126716E+10 | 0.00 | 0.00 |
August | 0.437943E+10 | 0.893930E+09 | 0.352196E+10 | 0.240383E+10 | 0.111813E+10 | 0.00 | 0.00 |
September | 0.289629E+10 | 0.842273E+09 | 0.236426E+10 | 0.150058E+10 | 0.863685E+09 | 0.00 | 0.00 |
October | 0.172988E+10 | 0.961581E+09 | 0.151447E+10 | 0.840035E+09 | 0.674438E+09 | 0.00 | 0.00 |
November | 0.818773E+09 | 0.118172E+10 | 0.882422E+09 | 0.430292E+09 | 0.452130E+09 | 0.00 | 0.00 |
December | 0.343685E+09 | 0.179862E+10 | 0.610284E+09 | 0.234527E+09 | 0.375758E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.320082E+11 | 0.132592E+11 | 0.270943E+11 | 0.162500E+11 | 0.108443E+11 | 0.00 | 0.00 |
Minimum of Months | 0.343685E+09 | 0.629230E+09 | 0.610284E+09 | 0.234527E+09 | 0.375758E+09 | 0.00 | 0.00 |
Maximum of Months | 0.537548E+10 | 0.218929E+10 | 0.422803E+10 | 0.296087E+10 | 0.145404E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104524E+10 | -957256558.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87987745.5 | 58.99 | 0.00 | 0.00 |
February | 0.973971E+09 | -894743866.3 | 0.00 | 0.00 | 672.00 | 0.00 | -79227304.6 | 58.99 | 0.00 | 0.00 |
March | 0.112222E+10 | -.103500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87220760.8 | 58.99 | 0.00 | 0.00 |
April | 0.100999E+10 | -926365797.9 | 0.00 | 0.00 | 720.00 | 0.00 | -83627687.2 | 58.99 | 0.00 | 0.00 |
May | 0.994080E+09 | -910525428.6 | 0.00 | 0.00 | 744.00 | 0.00 | -83554647.9 | 58.99 | 0.00 | 0.00 |
June | 0.925801E+09 | -851140739.2 | 0.00 | 0.00 | 720.00 | 0.00 | -74660291.1 | 58.99 | 0.00 | 0.00 |
July | 0.853811E+09 | -780889871.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72920873.0 | 58.99 | 0.00 | 0.00 |
August | 0.893424E+09 | -819666563.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73757901.8 | 58.99 | 0.00 | 0.00 |
September | 0.847439E+09 | -772428618.3 | 0.00 | 0.00 | 720.00 | 0.00 | -75010534.7 | 58.99 | 0.00 | 0.00 |
October | 0.894191E+09 | -810583742.0 | 0.00 | 0.00 | 744.00 | 0.00 | -83607611.9 | 59.00 | 0.00 | 0.00 |
November | 0.911490E+09 | -827633952.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83855570.7 | 58.99 | 0.00 | 0.00 |
December | 0.100238E+10 | -914639557.7 | 0.00 | 0.00 | 744.00 | 0.00 | -87738059.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114740E+11 | -.105009E+11 | 8760.00 | -973168988.4 | 58.99 | |||||
Minimum of Months | 0.847439E+09 | -.103500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -87987745.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112222E+10 | -772428618.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72920873.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.94 | 0.88 | 03-JAN-11:30 | 114.44 | 8.42 | 0.00 | 31.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.94 | 0.88 | 02-FEB-10:30 | 120.66 | 8.89 | 0.00 | 35.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.91 | 0.88 | 02-MAR-08:50 | 223.98 | 11.94 | 0.00 | 161.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.91 | 0.88 | 01-APR-08:00 | 233.75 | 11.89 | 0.00 | 180.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.90 | 0.88 | 01-MAY-07:49 | 1042.03 | 13.10 | 18.67 | 250.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.91 | 0.88 | 01-JUN-13:39 | 3245.72 | 14.22 | 51.33 | 267.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.91 | 0.88 | 01-JUL-06:00 | 2559.10 | 13.83 | 33.83 | 253.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.91 | 0.88 | 01-AUG-08:50 | 215.01 | 11.33 | 0.00 | 176.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.92 | 0.88 | 02-SEP-13:30 | 174.06 | 10.58 | 0.00 | 111.17 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.93 | 0.88 | 01-OCT-09:20 | 136.93 | 9.31 | 0.00 | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.94 | 0.88 | 01-NOV-09:00 | 104.26 | 8.02 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.95 | 0.88 | 04-DEC-10:30 | 86.88 | 7.18 | 0.00 | 7.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.92 | 838.80 | 11.14 | 103.83 | 1555.83 | ||||||
Minimum of Months | 226.83 | 0.90 | 0.88 | 86.88 | 7.18 | 0.00 | 7.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 434.17 | 0.95 | 0.88 | 3245.72 | 14.22 | 51.33 | 267.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.84 | 0.64 | 30-JAN-15:20 | 174.08 | 19.81 | 78.67 | 2.33 | 96.92 | 19.80 | 72.67 | 0.00 |
February | 275.00 | 0.80 | 0.61 | 21-FEB-15:30 | 276.00 | 22.50 | 131.50 | 30.33 | 119.25 | 20.67 | 111.67 | 0.00 |
March | 304.00 | 0.74 | 0.61 | 01-MAR-15:09 | 443.02 | 24.25 | 199.17 | 94.83 | 332.84 | 24.79 | 220.83 | 41.00 |
April | 325.17 | 0.74 | 0.61 | 01-APR-15:09 | 406.28 | 22.52 | 177.17 | 97.50 | 430.44 | 23.64 | 212.50 | 67.33 |
May | 385.83 | 0.72 | 0.61 | 01-MAY-14:00 | 328.59 | 21.73 | 213.00 | 121.67 | 539.39 | 22.89 | 258.17 | 93.17 |
June | 434.17 | 0.73 | 0.61 | 01-JUN-14:20 | 319.01 | 21.44 | 219.17 | 132.50 | 298.76 | 22.68 | 286.83 | 93.67 |
July | 417.33 | 0.73 | 0.61 | 01-JUL-14:39 | 327.17 | 21.78 | 213.83 | 135.33 | 451.78 | 22.91 | 268.83 | 104.33 |
August | 421.33 | 0.75 | 0.61 | 01-AUG-14:20 | 319.11 | 21.39 | 195.50 | 104.33 | 424.04 | 22.55 | 241.00 | 85.17 |
September | 352.17 | 0.76 | 0.61 | 01-SEP-15:09 | 482.48 | 23.43 | 178.33 | 87.83 | 425.08 | 24.54 | 204.33 | 52.67 |
October | 317.67 | 0.78 | 0.61 | 02-OCT-14:39 | 471.53 | 24.14 | 167.33 | 58.50 | 186.48 | 22.87 | 164.67 | 19.17 |
November | 269.50 | 0.82 | 0.64 | 01-NOV-15:20 | 265.26 | 22.99 | 121.00 | 28.17 | 98.85 | 19.88 | 89.33 | 0.00 |
December | 236.83 | 0.85 | 0.66 | 04-DEC-14:30 | 182.73 | 21.81 | 87.33 | 13.17 | 81.10 | 19.16 | 45.33 | 0.00 |
Annual Sum or Average | 3965.83 | 0.76 | 341.14 | 22.30 | 1982.00 | 906.50 | 316.64 | 22.43 | 2176.17 | 556.50 | ||
Minimum of Months | 226.83 | 0.72 | 0.61 | 174.08 | 19.81 | 78.67 | 2.33 | 81.10 | 19.16 | 45.33 | 0.00 | |
Maximum of Months | 434.17 | 0.85 | 0.66 | 482.48 | 24.25 | 219.17 | 135.33 | 539.39 | 24.79 | 286.83 | 104.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104808E+11 | 22830.12 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717961E+10 | 22830.12 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685111E+10 | 22830.12 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392989E+10 | 22830.12 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256040E+10 | 22830.12 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115520E+09 | 22830.12 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1789842.99 | 829.13 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.443963E+09 | 22830.12 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164510E+10 | 22830.12 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445955E+10 | 22830.12 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.764124E+10 | 22830.12 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453089E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104808E+11 | 22830.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453351E+11 | 62712.34 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274880E+11 | 62712.34 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213904E+11 | 62712.34 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.832225E+10 | 62712.34 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430115E+10 | 62712.34 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211924E+09 | 24198.44 | 19-SEP-05:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228709E+10 | 60252.28 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154140E+11 | 62712.34 | 12-NOV-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325048E+11 | 62712.34 | 01-DEC-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157255E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453351E+11 | 62712.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169410E+12 | 154216.04 | 05-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906565E+11 | 110435.17 | 03-FEB-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615565E+11 | 114734.84 | 06-MAR-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.845100E+10 | 54241.30 | 29-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.624896E+10 | 45981.43 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.680697E+09 | 20887.41 | 11-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445348E+11 | 99521.84 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114381E+12 | 154216.04 | 31-DEC-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495919E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169410E+12 | 154216.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.121284E+09 | 0.121284E+09 | 3323.18 | 20-MAY-16:00 | 3323.18 | 0.00 |
June | 0.00 | 0.00 | 0.185593E+10 | 0.180998E+10 | 6620.74 | 30-JUN-16:00 | 6620.74 | 0.00 |
July | 0.00 | 0.00 | 0.467975E+10 | 0.460052E+10 | 15329.91 | 19-JUL-05:02 | 13427.61 | 0.00 |
August | 0.00 | 0.00 | 0.412056E+10 | 0.410906E+10 | 14579.46 | 09-AUG-05:01 | 14579.46 | 0.00 |
September | 0.00 | 0.00 | 0.165236E+10 | 0.156528E+10 | 15604.13 | 08-SEP-05:03 | 12281.01 | 0.00 |
October | 0.00 | 0.00 | 26096036.58 | 26096036.58 | 1897.82 | 18-OCT-16:00 | 1897.82 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.124560E+11 | 0.122322E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.467975E+10 | 0.460052E+10 | 15604.13 | 14579.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.102734E+10 | 0.101584E+10 | 13728.75 | 29-JUN-15:10 | 13728.75 | 0.00 |
July | 0.00 | 0.00 | 0.514737E+10 | 0.506170E+10 | 34904.56 | 16-JUL-11:21 | 29012.68 | 0.00 |
August | 0.00 | 0.00 | 0.403550E+10 | 0.402605E+10 | 32412.89 | 08-AUG-20:01 | 32412.89 | 0.00 |
September | 0.00 | 0.00 | 0.113977E+10 | 0.105501E+10 | 24754.50 | 03-SEP-13:05 | 24754.50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.113500E+11 | 0.111586E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.514737E+10 | 0.506170E+10 | 34904.56 | 32412.89 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103061E+10 | 0.09 | 394.38 | 01-JAN-00:03 | 0.09 |
February | 0.812578E+09 | 0.07 | 394.38 | 01-FEB-00:02 | 0.09 |
March | 0.784892E+09 | 0.06 | 394.38 | 01-MAR-00:10 | 0.09 |
April | 0.254059E+09 | 0.02 | 394.38 | 01-APR-00:10 | 0.09 |
May | 0.135114E+09 | 0.01 | 394.38 | 01-MAY-00:10 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 24293718.00 | 0.00 | 394.38 | 10-OCT-01:07 | 0.09 |
November | 0.500999E+09 | 0.04 | 394.38 | 09-NOV-05:00 | 0.09 |
December | 0.960529E+09 | 0.08 | 394.38 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.450307E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103061E+10 | 0.09 | 394.38 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106650E+10 | 0.66 | 969.72 | 09-JAN-17:40 | 1.04 |
February | 0.946063E+09 | 0.57 | 969.72 | 02-FEB-11:10 | 1.04 |
March | 0.109264E+10 | 0.53 | 969.72 | 02-MAR-07:30 | 1.04 |
April | 0.991532E+09 | 0.43 | 969.72 | 08-APR-06:25 | 1.04 |
May | 0.102384E+10 | 0.44 | 969.72 | 01-MAY-14:00 | 1.04 |
June | 0.100063E+10 | 0.42 | 969.72 | 03-JUN-10:10 | 1.03 |
July | 0.974961E+09 | 0.39 | 969.72 | 12-JUL-09:00 | 1.04 |
August | 0.104723E+10 | 0.42 | 969.72 | 05-AUG-13:35 | 1.03 |
September | 0.970650E+09 | 0.41 | 969.72 | 08-SEP-11:30 | 1.03 |
October | 0.976657E+09 | 0.41 | 969.72 | 07-OCT-10:40 | 1.03 |
November | 0.958382E+09 | 0.45 | 969.72 | 01-NOV-08:20 | 1.04 |
December | 0.102447E+10 | 0.56 | 969.72 | 06-DEC-16:50 | 1.04 |
Annual Sum or Average | 0.120736E+11 | 0.47 | |||
Minimum of Months | 0.946063E+09 | 0.39 | 969.72 | 1.03 | |
Maximum of Months | 0.109264E+10 | 0.66 | 969.72 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261103E+10 | 0.88 | 1791.76 | 02-JAN-09:40 | 1.01 |
February | 0.219690E+10 | 0.85 | 1791.76 | 02-FEB-09:40 | 1.01 |
March | 0.239914E+10 | 0.84 | 1791.76 | 04-MAR-10:10 | 1.01 |
April | 0.198807E+10 | 0.69 | 1791.76 | 01-APR-06:50 | 1.01 |
May | 0.195579E+10 | 0.52 | 1791.76 | 01-MAY-07:00 | 1.01 |
June | 0.184524E+10 | 0.40 | 1791.76 | 21-JUN-13:50 | 0.99 |
July | 0.183028E+10 | 0.39 | 1791.76 | 01-JUL-15:00 | 0.99 |
August | 0.197234E+10 | 0.42 | 1791.76 | 01-AUG-14:30 | 1.00 |
September | 0.180346E+10 | 0.40 | 1791.76 | 01-SEP-10:20 | 1.00 |
October | 0.183303E+10 | 0.46 | 1791.76 | 04-OCT-07:10 | 1.00 |
November | 0.206297E+10 | 0.75 | 1791.76 | 02-NOV-09:30 | 1.01 |
December | 0.244703E+10 | 0.88 | 1791.76 | 21-DEC-13:30 | 1.01 |
Annual Sum or Average | 0.249453E+11 | 0.62 | |||
Minimum of Months | 0.180346E+10 | 0.39 | 1791.76 | 0.99 | |
Maximum of Months | 0.261103E+10 | 0.88 | 1791.76 | 1.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.72 | 0.00 |
February | 3.84 | 0.00 |
March | 3.14 | 0.00 |
April | 1.34 | 0.00 |
May | 0.40 | 0.11 |
June | 0.35 | 0.22 |
July | 1.57 | 0.00 |
August | 1.49 | 0.24 |
September | 1.03 | 0.55 |
October | 0.69 | 0.32 |
November | 2.06 | 0.00 |
December | 2.61 | 0.00 |
Annual Sum or Average | 21.24 | 0.06 |
Minimum of Months | 0.35 | 0.00 |
Maximum of Months | 3.84 | 0.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.08 | 0.00 |
August | 0.38 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.46 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.38 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106650E+10 | 0.146007E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.946063E+09 | 0.101402E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109264E+10 | 0.978047E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.991532E+09 | 0.566575E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.105113E+10 | 0.369564E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.140184E+10 | 0.169588E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.197893E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.193092E+10 | 2745062.63 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131796E+10 | 0.647886E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.982402E+09 | 0.238822E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.958382E+09 | 0.639521E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.102447E+10 | 0.108139E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.147428E+11 | 0.643002E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.946063E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.197893E+10 | 0.146007E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.261103E+10 | 0.625635E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.219690E+10 | 0.386209E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.239914E+10 | 0.302976E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.198807E+10 | 0.120490E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.195579E+10 | 0.616703E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.210386E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.311087E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.297990E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.208687E+10 | 0.314608E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183303E+10 | 0.331939E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.206297E+10 | 0.218714E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.244703E+10 | 0.456449E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.277755E+11 | 0.220848E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183303E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.311087E+10 | 0.625635E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106650E+10 | 0.00 | 0.104808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.946063E+09 | 0.00 | 0.717961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109264E+10 | 0.00 | 0.685111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.991532E+09 | 0.00 | 0.392989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102384E+10 | 0.121284E+09 | 0.256040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100063E+10 | 0.185593E+10 | 0.115520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.974961E+09 | 0.467975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104723E+10 | 0.412056E+10 | 1789842.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.970650E+09 | 0.165236E+10 | 0.443963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976657E+09 | 26096036.58 | 0.164510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958382E+09 | 0.00 | 0.445955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102447E+10 | 0.00 | 0.764124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120736E+11 | 0.124560E+11 | 0.453089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.946063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109264E+10 | 0.467975E+10 | 0.104808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261103E+10 | 0.00 | 0.453351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219690E+10 | 0.00 | 0.274880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239914E+10 | 0.00 | 0.213904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198807E+10 | 0.00 | 0.832225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195579E+10 | 0.00 | 0.430115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184524E+10 | 0.102734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183028E+10 | 0.514737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197234E+10 | 0.403550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180346E+10 | 0.113977E+10 | 0.211924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183303E+10 | 0.00 | 0.228709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206297E+10 | 0.00 | 0.154140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244703E+10 | 0.00 | 0.325048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249453E+11 | 0.113500E+11 | 0.157255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261103E+10 | 0.514737E+10 | 0.453351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.106650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.946063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.991532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102384E+10 | 0.00 | 0.00 | 0.00 | 27285669.08 | 0.00 | 0.369564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100063E+10 | 0.00 | 0.00 | 0.00 | 0.401209E+09 | 0.00 | 0.169588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.974961E+09 | 0.00 | 0.00 | 0.00 | 0.100397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104723E+10 | 0.00 | 0.00 | 0.00 | 0.883682E+09 | 0.00 | 2745062.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.970650E+09 | 0.00 | 0.00 | 0.00 | 0.347306E+09 | 0.00 | 0.647886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976657E+09 | 0.00 | 0.00 | 0.00 | 5744944.90 | 0.00 | 0.238822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120736E+11 | 0.00 | 0.00 | 0.00 | 0.266920E+10 | 0.00 | 0.643002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.946063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109264E+10 | 0.00 | 0.00 | 0.00 | 0.100397E+10 | 0.00 | 0.146007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.261103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184524E+10 | 0.00 | 0.00 | 0.00 | 0.258618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183028E+10 | 0.00 | 0.00 | 0.00 | 0.128060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197234E+10 | 0.00 | 0.00 | 0.00 | 0.100755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180346E+10 | 0.00 | 0.00 | 0.00 | 0.283408E+09 | 0.00 | 0.314608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249453E+11 | 0.00 | 0.00 | 0.00 | 0.283018E+10 | 0.00 | 0.220848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.180346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261103E+10 | 0.00 | 0.00 | 0.00 | 0.128060E+10 | 0.00 | 0.625635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289325E+10 | 0.00 | 0.00 | 0.12 |
February | 1424083.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205065E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198910E+10 | 0.00 | 0.00 | 0.13 |
April | 35797870.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124354E+10 | 0.00 | 0.00 | 0.13 |
May | 0.188167E+09 | 3450222.96 | 3251629.77 | 27719.84 | 586194.94 | 0.859103E+09 | 11096126.86 | 14746.23 | 0.13 |
June | 0.350519E+09 | 76164173.72 | 0.00 | 1057423.48 | 0.00 | 11823356.28 | 0.207429E+09 | 0.00 | 0.13 |
July | 5635247.69 | 0.181528E+09 | 0.00 | 2545622.11 | 0.00 | 0.00 | 0.231684E+09 | 0.00 | 0.12 |
August | 52822050.66 | 0.138400E+09 | 0.00 | 2582493.84 | 0.00 | 0.00 | 0.348032E+09 | 0.00 | 0.13 |
September | 0.351975E+09 | 56417102.13 | 0.00 | 1032983.96 | 33152.03 | 0.178100E+09 | 0.206293E+09 | 0.00 | 0.13 |
October | 0.460341E+09 | 425772.33 | 0.00 | 7032.31 | 228173.91 | 0.661528E+09 | 3683985.00 | 0.00 | 0.12 |
November | 35405949.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153162E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237512E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.148209E+10 | 0.456386E+09 | 3251629.77 | 7253275.53 | 847520.88 | 0.137938E+11 | 0.100822E+10 | 14746.23 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.460341E+09 | 0.181528E+09 | 3251629.77 | 2582493.84 | 586194.94 | 0.289325E+10 | 0.348032E+09 | 14746.23 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905932E+10 | 0.00 | 0.00 | 0.17 |
February | 0.932846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521061E+10 | 0.00 | 0.00 | 0.17 |
March | 0.210239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339868E+10 | 0.00 | 0.00 | 0.19 |
April | 0.209832E+10 | 0.00 | 0.00 | 0.00 | 26555230.43 | 0.105655E+10 | 0.00 | 0.00 | 0.18 |
May | 0.224503E+10 | 0.00 | 0.00 | 0.00 | 91418579.81 | 0.437014E+09 | 0.00 | 0.00 | 0.18 |
June | 0.177333E+10 | 0.107324E+09 | 0.00 | 303631.52 | 78578028.13 | 0.00 | 85211193.55 | 0.00 | 0.20 |
July | 0.860923E+09 | 0.463482E+09 | 0.00 | 2483256.84 | 3970867.97 | 0.00 | 0.950959E+09 | 0.00 | 0.28 |
August | 0.139783E+10 | 0.376835E+09 | 0.00 | 1247374.48 | 6044919.01 | 0.00 | 0.643168E+09 | 0.00 | 0.26 |
September | 0.206162E+10 | 98326005.93 | 0.00 | 523111.69 | 44223892.98 | 19222742.93 | 0.245292E+09 | 0.00 | 0.21 |
October | 0.263310E+10 | 0.00 | 0.00 | 0.00 | 30579417.72 | 0.228418E+09 | 0.00 | 0.00 | 0.18 |
November | 0.197177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221703E+10 | 0.00 | 0.00 | 0.17 |
December | 0.913546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629838E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.192830E+11 | 0.104597E+10 | 0.00 | 4557374.52 | 0.281371E+09 | 0.279252E+11 | 0.192463E+10 | 0.00 | 0.20 |
Minimum of Months | 0.292278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.263310E+10 | 0.463482E+09 | 0.00 | 2483256.84 | 91418579.81 | 0.905932E+10 | 0.950959E+09 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |