Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2020-06-03 19:12:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1913.10 | 395.67 | 395.67 |
Net Site Energy | 1913.10 | 395.67 | 395.67 |
Total Source Energy | 3086.25 | 638.30 | 638.30 |
Net Source Energy | 3086.25 | 638.30 | 638.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1427.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 58.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 486.06 | 1427.04 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1427.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 229.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 58.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.64 | 295.14 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 100.53 | 295.14 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.64 | 295.14 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 100.53 | 295.14 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 486.057 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 486.057 | 100.00 |
Total On-Site and Utility Electric Sources | 486.057 | 100.00 |
Total Electricity End Uses | 486.057 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 82.83 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2692.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.8889 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8323 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8323 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-15:20 | 28-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 214441.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19499.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2690.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 39542.03 | 214441.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 214441.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19499.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2690.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1546.91 | 0.00 | 0.00 | 0.00 |
Cooling | 3.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 727.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 185.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1539.34 | 1546.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 319.93 | 0.00 | 0.00 | 0.00 |
Cooling | 0.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 150.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 318.37 | 319.93 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 319.93 | 0.00 | 0.00 | 0.00 |
Cooling | 0.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 150.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 318.37 | 319.93 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.695900 |
ZONE2 FINE STORAGE DIRECT AIR | 1.11 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.38 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.38 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 97423.39 |
PSZ-OFFICE HEATING COIL | 23377.31 |
PSZ-FINE STORAGE HEATING COIL | 61484.03 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 97423.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.695900 | 0.695900 | 0.695900 | 0.695900 | 0.712877 | 0.712877 | 1.00 | 0.976186 | 0.712877 |
PSZ-FINE STORAGE | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 1.000000 | 1.11 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.712877 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.11 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.712877 | 0.712877 | 0.712877 | 0.712877 | 11800.64 | 23377.31 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 20929.53 | 61484.03 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.712880 | 0.356440 | 0.475253 | 11800.70 | 11800.64 | 5900.32 | 5900.32 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.11 | 0.556685 | 0.742247 | 18430.23 | 20929.53 | 10464.76 | 10464.76 | 0.754752 | 0.754750 | 0.754750 | 0.754750 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.712877 | 789.27 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.11 | 1232.68 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 6.889 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.963 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1631.841 | 6.889 | 326.368 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1631.841 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 10348.991 | 7.427 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.991 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 11383.890 | 3.552 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.890 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1507 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.2280 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3564 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.102 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3564 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.636 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.706 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4757 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.706 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.68857323E-13 | 0.53233684E-18 | 0.39256197E-18 | 0.0000000 |
2 | 1 | -5.2161015 | 0.66198115E-04 | -0.10631122E-03 | 0.13200917E-13 |
3 | 0 | 5.3667923 | 0.15062465 | 0.15079716 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.83431181E-12 | -0.50336875E-16 | 0.17219122E-13 | 0.10872276E-17 |
8 | 3 | -0.40194411E-03 | 0.16336896E-06 | -0.58474983E-04 | 0.15995403E-12 |
9 | 2 | 1.7800021 | 0.35079984E-02 | 1.1712360 | -0.77059901E-04 |
10 | 1 | -7.0760347 | 0.89860417E-01 | -17.294077 | 0.34117400 |
11 | 0 | 5.4466643 | 0.56861144E-01 | 16.273129 | |
12 | 4 | 0.80726987E-12 | -0.63996452E-16 | 0.53126644E-14 | 0.11245955E-15 |
13 | 3 | -0.39330081E-03 | 0.25288080E-06 | -0.57134975E-04 | 0.15488884E-12 |
14 | 2 | 1.7597822 | 0.54786934E-02 | 1.1558494 | -0.75402625E-04 |
15 | 1 | -7.1021575 | 0.14112945 | -17.196294 | 0.33729066 |
16 | 0 | 5.5790139 | 0.89636898E-01 | 16.276747 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1022727 | 2.1022727 | 2.1022727 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53126644E-14 | -0.63996452E-16 | 0.80726987E-12 | 0.11245955E-15 |
85 | 3 | -0.57134975E-04 | 0.25288080E-06 | -0.39330081E-03 | 0.15488884E-12 |
86 | 2 | 1.1558494 | 0.54786934E-02 | 1.7597822 | -0.75402625E-04 |
87 | 1 | -17.196294 | 0.14112945 | -7.1021575 | 0.33729066 |
88 | 0 | 16.276747 | 0.89636898E-01 | 5.5790139 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.26_SHGC_0.4 | 28 | 1 | VerySmooth | 1.476 | 0.398 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.41_SHGC_0.55 | 29 | 1 | VerySmooth | 2.330 | 0.549 | 0.472 | 0.551 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 30 | 1 | VerySmooth | 4.262 | 0.554 | 0.413 | 0.551 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.49184E-002 | 0.31435 | 0.49175 | 0.49175 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 8.94692E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 3.14065E-002 | 0.47116 | 0.33556 | 0.33556 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.12199 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.263 | 7.062E-004 | 4.613E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 7120.42827 | 8544.51392 | 0.57992 | 0.69590 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.97982E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10102.26689 | 12122.72026 | 0.28802 | 0.34563 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 14243.73037 | 17092.47644 | 0.92781 | 1.11337 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 6.97981E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 26811.23585 | 32173.48301 | 0.64400 | 0.77280 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40000 | 6.97982E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 81186.15495 | 97423.38594 | 1.98545 | 2.38254 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 10357.38 | 0.71288 | 0.71288 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15471.28 | 0.34563 | 0.34563 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 19723.16 | 1.11337 | 1.11337 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 51568.86 | 0.77280 | 0.77280 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.69590 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11337 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.38254 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.38254 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 97423.39114 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 97423.38594 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.69590 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.69590 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.69590 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.69590 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.71288 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.71288 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 0.97619 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11337 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11337 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11337 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11337 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11337 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.11337 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.71288 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.11337 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.71288 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.71288 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.71288 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.71288 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71288 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.71288 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.35644 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.47525 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 11800.69525 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 11800.64000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 5900.32000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 5900.32000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 11800.64000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23377.30611 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.71288 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 789.26773 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23377.30611 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11337 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11337 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11337 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11337 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11337 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11337 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55669 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74225 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18430.22678 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20929.53000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10464.76500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10464.76500 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75475 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75475 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75475 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75475 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20929.53000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61484.03068 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11337 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1232.67767 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 61484.03068 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 11247.5 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 20065.2 | 17.83 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3431412377 | 0.2928403983 | Pass | Pass | 3.9180785371 | 19.8464526161 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6946677591 | 0.6171770476 | Pass | Pass | 0.7542050677 | 0.6484683796 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.2862678307E-005 | 1.8710143848E-005 | Pass | Pass | 2.9302409491E-002 | 2.9097034367E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.220 | 0.228 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.148 | 0.151 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.338 | 0.356 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.26_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.476 | 0.398 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.26_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.476 | 0.398 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.26_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.476 | 0.398 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.26_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.476 | 0.398 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.554 | 0.551 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.749 | 0.470 | 0.469 | ||||||||||||
North Total or Average | 6.51 | 1.476 | 0.398 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.068 | 0.487 | 0.486 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.599 | 2.102 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.394 | 1.761 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.599 | 2.102 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 6.8889 | 236.88 | 1631.84 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 56.91 | 168.00 | 35.19 | 0.0000 | Y | 10.78 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 7.4271 | 1393.41 | 10348.99 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 53.69 | 0.0000 | Y | 104.31 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.5521 | 3204.84 | 11383.89 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 53.68 | 0.0000 | Y | 114.71 |
Interior Lighting Total | 4.8323 | 4835.13 | 23364.72 | 229.80 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1631.84 | 473.23 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1631.84 | 163.18 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 11383.89 | 1320.53 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 113.80 | AstronomicalClock | - | 44.84 | 44.84 | 0.96 | |
EXTERIOR_LIGHTS_B | 3955.00 | AstronomicalClock | - | 83.06 | 63.95 | 47.48 | |
EXTERIOR_LIGHTS_C | 1004.90 | AstronomicalClock | - | 83.06 | 54.03 | 10.19 | |
Exterior Lighting Total | 5073.70 | 58.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 11800.64 | 9424.70 | 2375.94 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20929.53 | 15796.56 | 5132.97 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 11247.5 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 20065.2 | 17.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 97423.39 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23377.31 | 0.81 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 61484.03 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.38 | 221.36 | 92.91 | 1.00 | 3.48 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.71 | 789.27 | 1107.16 | 1.00 | 1.50 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1232.68 | 1107.16 | 1.00 | 1.38 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7120.43 | 8544.51 | 36.07 | 0.580 | 0.696 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00811 | 21.79 | 0.00698 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 14243.73 | 17092.48 | 12.27 | 0.928 | 1.113 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00790 | 26.99 | 0.00698 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00384 | 27.40 | 0.00698 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10102.27 | 12122.72 | 51.18 | 0.288 | 0.346 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00810 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26811.24 | 32173.48 | 23.09 | 0.644 | 0.773 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 15.56 | 15.56 | 0.00770 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 81186.15 | 97423.39 | 30.40 | 1.985 | 2.383 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.71 | 0.71 | 0.35 | 0.35 | 0.7129 | 0.6959 | 0.7129 | 0.9762 | 1.0000 |
PSZ-FINE STORAGE | 1.11 | 1.11 | 0.77 | 0.77 | 1.1134 | 1.1134 | 1.1134 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 97423.391 | 97423.391 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 97423.39 | 97423.39 | 2.382542 | -11.28 | -11.28 | 0.00459865 | 43.33 | 26.90 | 0.01600000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 9.99 | 0.00774949 | 100.0000 | 97423.39 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 5900.320 | 0.000 | 0.712880 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 5900.32 | 5900.32 | 0.712880 | 24.20 | 15.83 | 0.00797706 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00697981 | 15.59 | 14.3481 | 23.90 | 0.00811369 | 43.2837 | 7108.98 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23377.306 | 23377.306 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23377.31 | 23377.31 | 0.712877 | 2.42 | 2.42 | 0.00572126 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 14.3482 | 21.10 | 0.00809900 | 51.2185 | 10102.27 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 10464.765 | 0.000 | 1.113370 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 10464.76 | 10464.76 | 1.113370 | 26.93 | 16.42 | 0.00754685 | 12.00 | 11.12 | 0.00800000 | 27.30 | 0.00697982 | 16.06 | 38.1466 | 26.70 | 0.00789960 | 35.6878 | 14188.72 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 61484.031 | 61484.031 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 61484.03 | 61484.03 | 1.113370 | -16.02 | -16.02 | 0.00350348 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 38.1466 | 15.56 | 0.00769944 | 68.9824 | 26811.24 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 97423.391 | 97423.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1854 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.382542 | 2.82435922 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 97423.39 | 97423.39 | 1.0000 | 2.82435922 | 2.382542 | -11.28 | -11.28 | 0.00459865 | 66.5 | 43.33 | 26.90 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97423.39 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 9.99 | 0.00774949 | 9.99 | 0.00774949 | 100.0000 | 97423.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 5900.320 | 0.000 | 0.712880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6690 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 5900.32 | 5900.32 | 1.0000 | 0.84507596 | 0.712880 | 24.20 | 15.83 | 0.00797706 | 44623.0 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5900.32 | 25.97 | 0.00697981 | 15.59 | 0.10228487 | 14.3481 | 23.90 | 0.00814412 | 23.90 | 0.00811369 | 43.2837 | 7108.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23377.306 | 23377.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.712877 | 0.84507211 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23377.31 | 23377.31 | 1.0000 | 0.84507211 | 0.712877 | 2.42 | 2.42 | 0.00572126 | 16767.9 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23377.31 | -41.90 | 0.00006450 | -41.90 | 0.10228487 | 14.3482 | 21.05 | 0.00809900 | 21.10 | 0.00809900 | 51.2185 | 10102.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10464.765 | 0.000 | 1.113370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8692 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 10464.76 | 10464.76 | 1.0000 | 1.31983255 | 1.113370 | 26.93 | 16.42 | 0.00754685 | 46311.4 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10464.76 | 27.30 | 0.00697982 | 16.06 | 0.42471267 | 38.1466 | 26.70 | 0.00789874 | 26.70 | 0.00789960 | 35.6878 | 14188.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61484.031 | 61484.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.113370 | 1.31983292 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 61484.03 | 61484.03 | 1.0000 | 1.31983292 | 1.113370 | -16.02 | -16.02 | 0.00350348 | -7438.7 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61484.03 | -41.90 | 0.00006450 | -41.90 | 0.42471267 | 38.1466 | 15.56 | 0.00769944 | 15.56 | 0.00769944 | 68.9824 | 26811.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.11 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2696.50 | 3465.33 | 2692.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2696.50 | 3465.33 | 2692.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 122.00 | 0.50 | 82.83 | 0.50 |
ZONE2 FINE STORAGE | 678.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 135.33 | 0.00 | 0.00 | 0.00 |
Facility | 871.50 | 0.50 | 82.83 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.309 | 0.226 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
Electricity:Building | 366.30 | 1510.77 | 01-JAN-00:10 | 29534.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 39.94 | 520.87 | 01-JAN-00:10 | 2861.51 | 02-JAN-08:10 |
InteriorLights:Electricity | 229.80 | 1040.90 | 01-JAN-00:10 | 19499.41 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.78 | 51.00 | 01-JAN-00:10 | 1026.46 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 229.80 | 1040.90 | 01-JAN-00:10 | 19499.41 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 104.31 | 299.97 | 01-JAN-00:10 | 8796.64 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 222.05 | 689.93 | 01-JAN-00:10 | 17876.43 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 114.71 | 689.93 | 01-JAN-00:10 | 9676.31 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.50 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 28.37 | 481.00 | 28-JAN-18:40 | 3131.30 | 11-JAN-13:00 |
WaterSystems:Electricity | 28.37 | 481.00 | 28-JAN-18:40 | 3131.30 | 11-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 28.37 | 481.00 | 28-JAN-18:40 | 3131.30 | 11-JAN-13:00 |
Fans:Electricity | 31.70 | 0.00 | 22-MAR-17:10 | 2243.31 | 02-JAN-07:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
ElectricityPurchased:Plant | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
Cogeneration:ElectricityPurchased | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
ElectricityNet:Plant | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
Cogeneration:ElectricityNet | 486.06 | 1991.77 | 09-APR-15:10 | 39542.03 | 09-JAN-15:20 |
Electricity:HVAC | 32.76 | 0.00 | 22-MAR-17:10 | 5069.78 | 21-JUL-16:00 |
General:Fans:Electricity | 31.70 | 0.00 | 22-MAR-17:10 | 2243.31 | 02-JAN-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.06 | 0.00 | 01-JAN-00:10 | 3047.84 | 21-JUL-16:00 |
ExteriorLights:Electricity | 58.63 | 0.00 | 01-JAN-11:20 | 5073.70 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 58.63 | 0.00 | 01-JAN-11:20 | 5073.70 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1427.04 | 0.00 | 22-MAR-17:10 | 214441.65 | 28-JAN-17:10 |
Gas:HVAC | 1427.04 | 0.00 | 22-MAR-17:10 | 214441.65 | 28-JAN-17:10 |
Heating:Gas | 1427.04 | 0.00 | 22-MAR-17:10 | 214441.65 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2140.05 | 0.00 | 22-MAR-17:10 | 328201.81 | 29-JAN-00:30 |
EnergyTransfer:Building | 1032.62 | 0.00 | 22-MAR-17:10 | 164718.81 | 29-JAN-00:30 |
EnergyTransfer:Zone:ZONE1 OFFICE | 68.31 | 0.00 | 01-JAN-00:40 | 24331.41 | 27-FEB-07:10 |
Heating:EnergyTransfer | 1016.55 | 0.00 | 22-MAR-17:10 | 164718.81 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.78 | 0.00 | 01-JAN-00:40 | 24331.41 | 27-FEB-07:10 |
Cooling:EnergyTransfer | 16.06 | 0.00 | 01-JAN-00:10 | 9156.45 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 4.53 | 0.00 | 01-JAN-00:10 | 4157.22 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 213.16 | 0.00 | 01-JAN-00:40 | 62360.95 | 28-JAN-23:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 201.63 | 0.00 | 01-JAN-00:40 | 62360.95 | 28-JAN-23:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.53 | 0.00 | 01-JAN-00:10 | 7699.47 | 30-AUG-07:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 751.15 | 0.00 | 18-MAR-09:10 | 98348.16 | 28-JAN-09:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 751.15 | 0.00 | 18-MAR-09:10 | 98348.16 | 28-JAN-09:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1107.43 | 0.00 | 22-MAR-17:10 | 171191.88 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1102.39 | 0.00 | 22-MAR-17:10 | 171191.88 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 5.04 | 0.00 | 01-JAN-00:10 | 13232.05 | 21-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 63.776 | -4.532 | 0.000 | 0.000 | 4.079 | 10.779 | 29.165 | 6.712 | 0.000 | 0.029 | 0.000 | 0.000 | -11.944 | 0.000 | -26.467 | -71.596 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 201.627 | -11.529 | 0.000 | 0.000 | 0.000 | 104.309 | 0.000 | 0.000 | 0.000 | 0.064 | 0.002 | 0.000 | 0.000 | 0.000 | -91.522 | -202.949 |
ZONE3 BULK STORAGE | 751.150 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 114.715 | 107.336 | 18.038 | 0.000 | 3.593 | 0.000 | 0.000 | -21.953 | 0.000 | -425.462 | -547.417 |
Total Facility | 751.150 | 0.000 | 265.403 | -16.061 | 0.000 | 0.000 | 4.079 | 229.803 | 136.501 | 24.750 | 0.000 | 3.686 | 0.002 | 0.000 | -33.897 | 0.000 | -543.451 | -821.963 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-AUG-05:03 | 0.00 | 0.00 | 0.00 | -10620.14 | 0.00 | 0.00 | 36.31 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 10429.44 | 0.00 | -93.82 | 0.00 | -353.32 | 0.00 |
ZONE2 FINE STORAGE | 19-OCT-10:25 | 0.00 | 0.00 | 0.00 | -8235.16 | 0.00 | 0.00 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.19 | 0.00 | -0.00 | 0.00 | -1703.66 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-AUG-05:03 | 0.00 | 0.00 | 0.00 | -10620.14 | 0.00 | 0.00 | 36.31 | 1040.90 | 2600.55 | 0.00 | 0.00 | 0.00 | 16367.43 | 0.00 | -263.14 | 0.00 | -9161.91 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 14-MAR-05:31 | 0.00 | 0.00 | 24871.37 | 0.00 | 0.00 | 0.00 | 55.14 | 306.60 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -816.82 | 0.00 | -1889.82 | -23076.98 |
ZONE2 FINE STORAGE | 25-FEB-06:41 | 0.00 | 0.00 | 63975.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17429.11 | -47581.19 |
ZONE3 BULK STORAGE | 28-JAN-09:00 | 98345.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8537.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1630.85 | 0.00 | -111678.88 | -1774.26 |
Total Facility | 02-MAR-05:22 | 97559.36 | 0.00 | 87043.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.90 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2925.41 | 0.00 | -51781.74 | -133456.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.6959 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.7129 | 0.1435 | 1.0000 | 0.1023 | 0.1435 | ||
PSZ-FINE STORAGE | 1.1134 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.1134 | 0.3815 | 1.0000 | 0.4247 | 0.3815 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.6959 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.6959 | 1.0000 | 1.0000 | 0.1023 | 0.1470 | ||
PSZ-FINE STORAGE | 1.1134 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.1134 | 1.0000 | 1.0000 | 0.4247 | 0.3815 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.6959 | 0.6959 | 0.6959 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.1134 | 1.1134 | 1.1134 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.6959 | 0.7129 | 0.6959 | 0.6959 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.1134 | 1.1134 | 1.1134 | 1.1134 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.6959 | 0.6959 | 0.6959 | 0.1023 | 0.2959 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.1134 | 1.1134 | 1.1134 | 0.4247 | 0.5496 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.6959 | 0.6959 | 0.6959 | 0.6959 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.1134 | 1.1134 | 1.1134 | 1.1134 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 82.83 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 83.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1427.04 | 214441.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 1.06 | 3047.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 229.80 | 19499.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 58.63 | 5073.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.50 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 31.70 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.37 | 3131.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.50 | 486.06 |
Natural Gas | 0.00 | 1427.04 |
Additional | 0.00 | 0.00 |
Total | 136.50 | 1913.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.53 |
Space Heating | 0.00 |
Space Cooling | 0.22 |
Fans (All) | 6.56 |
Service Water Heating | 5.87 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 100.53 |
Subtotal | 100.53 |
Natural Gas [MJ/m2] | |
Space Heating | 295.14 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 295.14 |
Subtotal | 295.14 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.01 |
Space Heating | 74.59 |
Space Cooling | 0.06 |
Fans (All) | 1.66 |
Service Water Heating | 1.48 |
Receptacle Equipment | 7.14 |
Miscellaneous | 3.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 2967. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.273833E+12 |
February | 0.000 | 0.229484E+12 |
March | 0.000 | 0.218512E+12 |
April | 0.000 | 0.101035E+12 |
May | 0.000 | 0.517632E+10 |
June | 0.000 | 0.149001E+09 |
July | 0.000 | 0.100016E+08 |
August | 0.000 | 0.128068E+09 |
September | 0.000 | 0.804634E+10 |
October | 0.000 | 0.123770E+12 |
November | 0.000 | 0.198961E+12 |
December | 0.000 | 0.267934E+12 |
Annual Sum or Average | 0.142704E+13 | |
Minimum of Months | 0.000 | 0.100016E+08 |
Maximum of Months | 0.000 | 0.273833E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.194750E+09 | 236.59 | 19-JAN-08:20 | -5.0 | -5.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.179295E+09 | 236.59 | 14-FEB-13:30 | -2.5 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.1 | 0.210509E+09 | 236.59 | 17-MAR-07:30 | -4.7 | -6.0 |
April | 180945.88 | 43.95 | 22-APR-15:00 | 14.40 | 6.16 | 0.194978E+09 | 240.44 | 22-APR-15:00 | 15.00 | 6.58 |
May | 13754027.56 | 369.78 | 20-MAY-14:40 | 11.67 | 6.92 | 0.206365E+09 | 289.08 | 13-MAY-15:00 | 20.00 | 9.29 |
June | 0.873482E+09 | 2974.48 | 23-JUN-16:00 | 21.10 | 11.90 | 0.247744E+09 | 301.59 | 24-JUN-07:49 | 12.30 | 12.19 |
July | 0.203471E+10 | 10022.72 | 22-JUL-05:03 | 14.68 | 12.08 | 0.246845E+09 | 301.60 | 03-JUL-15:09 | 19.50 | 17.42 |
August | 0.152608E+10 | 10620.08 | 03-AUG-05:03 | 14.90 | 13.03 | 0.259988E+09 | 301.59 | 03-AUG-08:09 | 15.00 | 13.65 |
September | 83534170.49 | 995.96 | 02-SEP-07:05 | 6.78 | 6.00 | 0.198106E+09 | 300.00 | 02-SEP-15:00 | 16.70 | 10.41 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.11 | 0.195009E+09 | 236.59 | 07-OCT-07:30 | 4.45 | 3.82 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.187147E+09 | 236.59 | 18-NOV-08:30 | -11.4 | -11.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.194907E+09 | 236.59 | 23-DEC-08:30 | -2.2 | -3.6 |
Annual Sum or Average | 0.453174E+10 | 0.251564E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.179295E+09 | 236.59 | -11.4 | -11.8 | ||
Maximum of Months | 0.203471E+10 | 10620.08 | 21.10 | 13.03 | 0.259988E+09 | 301.60 | 20.00 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.194363E+09 | 4442.10 | 22-MAR-13:00 | 4.40 | 1.55 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.129930E+10 | 5547.35 | 18-APR-08:15 | 1.67 | -0.5 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.127833E+10 | 5404.37 | 27-MAY-11:05 | 1.97 | 0.42 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.136113E+10 | 6710.97 | 09-JUN-06:10 | 11.97 | 8.43 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.165255E+10 | 6727.52 | 06-JUL-06:10 | 11.47 | 9.48 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.251431E+10 | 7842.85 | 30-AUG-07:05 | 0.78 | -1.0 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.257599E+10 | 6800.50 | 16-SEP-07:05 | -0.1 | -0.4 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.653428E+09 | 8235.16 | 19-OCT-10:25 | -3.9 | -4.1 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.115294E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.257599E+10 | 8235.16 | 11.97 | 9.48 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.1 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.11 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107904E+11 | 24820.19 | 09-JAN-06:31 | -18.3 |
February | 0.944184E+10 | 24844.38 | 06-FEB-06:31 | -13.1 |
March | 0.947916E+10 | 24871.31 | 14-MAR-05:31 | -18.0 |
April | 0.529972E+10 | 24687.88 | 04-APR-05:32 | -11.3 |
May | 0.202360E+10 | 24152.02 | 01-MAY-05:42 | 7.70 |
June | 0.202351E+09 | 23581.87 | 01-JUN-05:01 | 7.20 |
July | 63733741.38 | 2350.40 | 05-JUL-06:10 | 8.30 |
August | 0.147300E+09 | 23181.32 | 31-AUG-05:02 | -1.2 |
September | 0.201704E+10 | 23724.57 | 25-SEP-05:12 | -1.3 |
October | 0.550223E+10 | 24477.26 | 26-OCT-05:32 | -12.2 |
November | 0.865152E+10 | 24772.28 | 20-NOV-06:31 | -18.7 |
December | 0.101578E+11 | 24822.79 | 11-DEC-06:31 | -18.3 |
Annual Sum or Average | 0.637767E+11 | |||
Minimum of Months | 63733741.38 | 2350.40 | -18.7 | |
Maximum of Months | 0.107904E+11 | 24871.31 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391230E+11 | 63430.65 | 12-JAN-00:42 | -36.1 |
February | 0.323591E+11 | 63975.52 | 25-FEB-06:41 | -24.4 |
March | 0.298967E+11 | 63402.74 | 14-MAR-03:02 | -18.9 |
April | 0.155474E+11 | 63453.46 | 02-APR-19:42 | -11.9 |
May | 0.146084E+10 | 46608.65 | 28-MAY-02:23 | 0.30 |
June | 0.198504E+09 | 2081.77 | 30-JUN-15:00 | 28.30 |
July | 0.119520E+09 | 1313.35 | 20-JUL-07:00 | 14.40 |
August | 0.145406E+09 | 1622.07 | 23-AUG-17:00 | 25.00 |
September | 0.165310E+10 | 59736.47 | 23-SEP-05:01 | 1.60 |
October | 0.169516E+11 | 62954.03 | 31-OCT-03:02 | -16.4 |
November | 0.274985E+11 | 62932.26 | 09-NOV-22:02 | -21.7 |
December | 0.366736E+11 | 63274.97 | 15-DEC-02:62 | -31.2 |
Annual Sum or Average | 0.201627E+12 | |||
Minimum of Months | 0.119520E+09 | 1313.35 | -36.1 | |
Maximum of Months | 0.391230E+11 | 63975.52 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146332E+12 | 98348.16 | 28-JAN-09:00 | -20.0 |
February | 0.123538E+12 | 98205.06 | 25-FEB-12:00 | -23.9 |
March | 0.117650E+12 | 97773.83 | 16-MAR-08:00 | -21.7 |
April | 0.529584E+11 | 97763.14 | 02-APR-19:42 | -11.9 |
May | 7686658.62 | 1637.51 | 03-MAY-03:40 | 4.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.634975E+09 | 20681.96 | 30-SEP-05:00 | -4.4 |
October | 0.649913E+11 | 86794.03 | 27-OCT-04:00 | -17.8 |
November | 0.101663E+12 | 92164.30 | 10-NOV-01:52 | -20.0 |
December | 0.143374E+12 | 97997.62 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.751150E+12 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.146332E+12 | 98348.16 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.103811E+10 | 1026.46 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.906967E+09 | 1026.46 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.939633E+09 | 1026.46 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.806585E+09 | 972.11 | 04-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.812446E+09 | 897.83 | 20-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.776662E+09 | 893.52 | 08-JUN-07:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.775856E+09 | 922.87 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.864497E+09 | 915.83 | 18-AUG-15:00 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.864017E+09 | 988.57 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.960550E+09 | 1026.46 | 03-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.984449E+09 | 1026.46 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.104890E+10 | 1026.46 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.107787E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.775856E+09 | 893.52 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.104890E+10 | 1026.46 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.862930E+10 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.792548E+10 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.925537E+10 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.860339E+10 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.894234E+10 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.891642E+10 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.862930E+10 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.925537E+10 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.860339E+10 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.862930E+10 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.829035E+10 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.862930E+10 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104309E+12 | ||||
Minimum of Months | 0.792548E+10 | 8796.64 | 0.00 | 0.00 | |
Maximum of Months | 0.925537E+10 | 8796.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100135E+11 | 9676.31 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.901710E+10 | 9676.31 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.101145E+11 | 9527.08 | 03-MAR-15:00 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.923081E+10 | 9285.32 | 13-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.944797E+10 | 9236.27 | 09-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.929314E+10 | 9083.97 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.911653E+10 | 9200.55 | 29-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.979575E+10 | 9346.53 | 31-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.935183E+10 | 9424.43 | 30-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.970894E+10 | 9676.31 | 23-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.957327E+10 | 9676.31 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.100516E+11 | 9676.31 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.114715E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.901710E+10 | 9083.97 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.101145E+11 | 9676.31 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.103811E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384669E+10 |
February | 0.500553E+09 | 0.906967E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300752E+10 |
March | 0.587605E+09 | 0.939633E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341894E+10 |
April | 0.544079E+09 | 0.806585E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207772E+10 |
May | 0.565842E+09 | 0.812446E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182502.47 | 0.106916E+10 |
June | 0.565842E+09 | 0.776662E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9393548.59 | 0.679236E+09 |
July | 0.544079E+09 | 0.775856E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15584373.98 | 0.571407E+09 |
August | 0.587605E+09 | 0.864497E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3570510.62 | 0.945476E+09 |
September | 0.544079E+09 | 0.864017E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125304E+10 |
October | 0.544079E+09 | 0.960550E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248467E+10 |
November | 0.522316E+09 | 0.984449E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334221E+10 |
December | 0.544079E+09 | 0.104890E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377102E+10 |
Annual Sum or Average | 0.659424E+10 | 0.107787E+11 | 0.291647E+11 | 28730935.65 | 0.264671E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.775856E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571407E+09 |
Maximum of Months | 0.587605E+09 | 0.104890E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15584373.98 | 0.384669E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115036E+11 |
February | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952840E+10 |
March | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137296E+11 |
April | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120454E+11 |
May | 0.00 | 0.894234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14316682.97 | 0.522023E+10 |
June | 0.00 | 0.891642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13824096.12 | 0.364484E+10 |
July | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28502538.74 | 0.346507E+10 |
August | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7815199.07 | 0.454749E+10 |
September | 0.00 | 0.860339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408513E+10 |
October | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106629E+11 |
November | 0.00 | 0.829035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430928E+10 |
December | 0.00 | 0.862930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877976E+10 |
Annual Sum or Average | 0.104309E+12 | 64458516.90 | 0.915217E+11 | ||||||
Minimum of Months | 0.00 | 0.792548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346507E+10 |
Maximum of Months | 0.00 | 0.925537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28502538.74 | 0.137296E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.100135E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381782E+11 |
February | 0.00 | 0.901710E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312611E+11 |
March | 0.00 | 0.101145E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434593E+11 |
April | 0.00 | 0.923081E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117843E+09 | 0.311514E+11 |
May | 0.00 | 0.944797E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114422E+10 | 0.120999E+11 |
June | 0.00 | 0.929314E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628679E+09 | 0.941072E+10 |
July | 0.00 | 0.911653E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293763E+09 | 0.113237E+11 |
August | 0.00 | 0.979575E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190290E+09 | 0.163551E+11 |
September | 0.00 | 0.935183E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1612685.57 | 0.130470E+11 |
October | 0.00 | 0.970894E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31092173.65 | 0.307150E+11 |
November | 0.00 | 0.957327E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143154E+11 |
December | 0.00 | 0.100516E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312488E+11 |
Annual Sum or Average | 0.114715E+12 | 0.107336E+12 | 0.240750E+10 | 0.282566E+12 | |||||
Minimum of Months | 0.00 | 0.901710E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941072E+10 |
Maximum of Months | 0.00 | 0.101145E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114422E+10 | 0.434593E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1026.46 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15694.58 | 12-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1026.46 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14875.03 | 27-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1026.46 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 13131.74 | 01-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 972.11 | 04-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11167.84 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 897.83 | 20-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 30-MAY-18:00 | 4657.27 | 16-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 893.52 | 08-JUN-07:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.40 | 29-JUN-16:10 | 3144.32 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 922.87 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 21-JUL-16:10 | 3434.63 | 17-JUL-06:05 |
August | 659.25 | 01-AUG-07:10 | 915.83 | 18-AUG-15:00 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.98 | 11-AUG-16:10 | 5570.99 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 988.57 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6471.47 | 29-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1026.46 | 03-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 10755.88 | 31-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1026.46 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13325.83 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1026.46 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14265.12 | 15-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 893.52 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3144.32 | |||||
Maximum of Months | 659.25 | 1026.46 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 15694.58 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 8796.64 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 39114.59 | 28-JAN-17:00 |
February | 0.00 | 8796.64 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 24061.30 | 23-FEB-17:00 |
March | 0.00 | 8796.64 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 18292.65 | 25-MAR-15:10 |
April | 0.00 | 8796.64 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20586.68 | 01-APR-18:52 |
May | 0.00 | 8796.64 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.69 | 30-MAY-18:00 | 10573.92 | 27-MAY-08:00 |
June | 0.00 | 8796.64 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.57 | 30-JUN-15:10 | 8634.22 | 24-JUN-21:00 |
July | 0.00 | 8796.64 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.71 | 21-JUL-16:00 | 5208.32 | 04-JUL-17:00 |
August | 0.00 | 8796.64 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.68 | 23-AUG-18:00 | 8724.56 | 29-AUG-20:00 |
September | 0.00 | 8796.64 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5874.44 | 29-SEP-07:00 |
October | 0.00 | 8796.64 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 13656.34 | 27-OCT-06:10 |
November | 0.00 | 8796.64 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13371.25 | 03-NOV-20:00 |
December | 0.00 | 8796.64 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15525.64 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5208.32 | |||
Maximum of Months | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.71 | 39114.59 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 9676.31 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 108858.78 | 28-JAN-15:00 |
February | 0.00 | 9676.31 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 74984.47 | 25-FEB-12:00 |
March | 0.00 | 9527.08 | 03-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 57056.09 | 25-MAR-09:00 |
April | 0.00 | 9285.32 | 13-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3543.16 | 22-APR-16:00 | 54415.28 | 01-APR-18:52 |
May | 0.00 | 9236.27 | 09-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10181.08 | 30-MAY-18:00 | 34493.45 | 27-MAY-11:00 |
June | 0.00 | 9083.97 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8754.55 | 30-JUN-15:00 | 25389.40 | 24-JUN-21:00 |
July | 0.00 | 9200.55 | 29-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14527.77 | 21-JUL-16:00 | 15757.71 | 04-JUL-17:00 |
August | 0.00 | 9346.53 | 31-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5554.47 | 23-AUG-16:00 | 32656.67 | 31-AUG-09:00 |
September | 0.00 | 9424.43 | 30-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.80 | 17-SEP-16:00 | 15874.64 | 21-SEP-14:00 |
October | 0.00 | 9676.31 | 23-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3081.41 | 01-OCT-17:00 | 40557.27 | 31-OCT-09:00 |
November | 0.00 | 9676.31 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 41183.86 | 01-NOV-09:00 |
December | 0.00 | 9676.31 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58334.88 | 22-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 9083.97 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15757.71 | ||||
Maximum of Months | 0.00 | 9676.31 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14527.77 | 108858.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.13 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.24 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.04 |
April | 43.95 | 22-APR-15:00 | 659.25 | 626.14 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 |
May | 369.78 | 20-MAY-14:40 | 659.25 | 647.71 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.68 |
June | 2974.48 | 23-JUN-16:00 | 659.25 | 626.14 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.55 |
July | 10022.72 | 22-JUL-05:03 | 217.55 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.46 |
August | 10620.08 | 03-AUG-05:03 | 290.07 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.32 |
September | 995.96 | 02-SEP-07:05 | 1318.50 | 1844.68 | 3670.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.88 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.88 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.74 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10620.08 | 1318.50 | 1844.68 | 3670.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7478.48 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5547.33 |
March | 4442.10 | 22-MAR-13:00 | 0.00 | 8796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5547.35 | 18-APR-08:15 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777.67 |
May | 5404.37 | 27-MAY-11:05 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.54 |
June | 6710.97 | 09-JUN-06:10 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.86 |
July | 6727.52 | 06-JUL-06:10 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2134.37 |
August | 7842.85 | 30-AUG-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4661.37 |
September | 6800.50 | 16-SEP-07:05 | 0.00 | 15523.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4368.18 |
October | 8235.16 | 19-OCT-10:25 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.66 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6326.33 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8235.16 | 0.00 | 17593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7478.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 3449.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21455.03 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16864.26 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8408.25 |
April | 0.00 | 01-APR-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.76 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1379.87 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3492.06 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.45 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3562.39 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7288.81 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4872.30 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 1379.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9135.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 689.93 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17147.53 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2759.73 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3449.66 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29182.76 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.456453E+11 | 39542.03 | 09-JAN-15:20 | 0.273833E+12 | 214441.65 | 28-JAN-17:10 |
February | 0.398098E+11 | 38580.37 | 06-FEB-09:20 | 0.229484E+12 | 213302.76 | 24-FEB-17:00 |
March | 0.433893E+11 | 36359.38 | 17-MAR-07:10 | 0.218512E+12 | 198353.96 | 16-MAR-07:00 |
April | 0.381668E+11 | 33520.83 | 08-APR-14:50 | 0.101035E+12 | 180782.72 | 02-APR-19:49 |
May | 0.373674E+11 | 33555.26 | 09-MAY-12:09 | 0.517632E+10 | 27994.75 | 01-MAY-05:10 |
June | 0.361988E+11 | 33545.48 | 20-JUN-14:00 | 0.149001E+09 | 9430.41 | 01-JUN-05:10 |
July | 0.360434E+11 | 35194.80 | 29-JUL-14:00 | 10001584.68 | 1915.36 | 05-JUL-16:49 |
August | 0.395006E+11 | 33629.21 | 11-AUG-12:00 | 0.128068E+09 | 7739.00 | 31-AUG-06:10 |
September | 0.386209E+11 | 33307.95 | 30-SEP-14:39 | 0.804634E+10 | 56594.19 | 30-SEP-05:10 |
October | 0.419904E+11 | 38562.48 | 31-OCT-08:09 | 0.123770E+12 | 161768.06 | 31-OCT-07:10 |
November | 0.429398E+11 | 39393.34 | 30-NOV-15:39 | 0.198961E+12 | 177773.11 | 29-NOV-08:09 |
December | 0.463840E+11 | 39541.56 | 30-DEC-15:39 | 0.267934E+12 | 200848.68 | 01-DEC-17:00 |
Annual Sum or Average | 0.486057E+12 | 0.142704E+13 | ||||
Minimum of Months | 0.360434E+11 | 33307.95 | 10001584.68 | 1915.36 | ||
Maximum of Months | 0.463840E+11 | 39542.03 | 0.273833E+12 | 214441.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.196809E+11 | 0.895550E+10 | 0.112984E+11 | 0.00 | 0.328060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242992E+10 | 0.00 |
February | 0.178496E+11 | 0.639635E+10 | 0.103734E+11 | 0.00 | 0.297933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221123E+10 | 0.00 |
March | 0.203095E+11 | 0.516847E+10 | 0.121016E+11 | 0.00 | 0.330252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250721E+10 | 0.00 |
April | 0.186408E+11 | 0.320753E+10 | 0.112578E+11 | 0.00 | 0.267847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238222E+10 | 0.00 |
May | 0.192028E+11 | 0.187609E+10 | 0.117000E+11 | 0.00 | 0.213063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245798E+10 | 0.00 |
June | 0.189862E+11 | 0.902820E+09 | 0.116594E+11 | 0.00 | 0.208338E+10 | 0.00 | 0.00 | 0.204234E+09 | 0.00 | 0.00 | 0.00 | 0.236282E+10 | 0.00 |
July | 0.185217E+11 | 0.133382E+10 | 0.112984E+11 | 0.00 | 0.200430E+10 | 0.00 | 0.00 | 0.552984E+09 | 0.00 | 0.00 | 0.00 | 0.233226E+10 | 0.00 |
August | 0.199156E+11 | 0.263758E+10 | 0.121016E+11 | 0.00 | 0.216365E+10 | 0.00 | 0.00 | 0.303191E+09 | 0.00 | 0.00 | 0.00 | 0.237897E+10 | 0.00 |
September | 0.188192E+11 | 0.420996E+10 | 0.112578E+11 | 0.00 | 0.206548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226849E+10 | 0.00 |
October | 0.192988E+11 | 0.625528E+10 | 0.112984E+11 | 0.00 | 0.280165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233631E+10 | 0.00 |
November | 0.188481E+11 | 0.795633E+10 | 0.108562E+11 | 0.00 | 0.299124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228801E+10 | 0.00 |
December | 0.197298E+11 | 0.972874E+10 | 0.112984E+11 | 0.00 | 0.321448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241263E+10 | 0.00 |
Annual Sum or Average | 0.229803E+12 | 0.586285E+11 | 0.136501E+12 | 0.316957E+11 | 0.00 | 0.106041E+10 | 0.283680E+11 | ||||||
Minimum of Months | 0.178496E+11 | 0.902820E+09 | 0.103734E+11 | 0.00 | 0.200430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221123E+10 | 0.00 |
Maximum of Months | 0.203095E+11 | 0.972874E+10 | 0.121016E+11 | 0.00 | 0.330252E+10 | 0.00 | 0.00 | 0.552984E+09 | 0.00 | 0.00 | 0.00 | 0.250721E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.273833E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.229484E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.218512E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.101035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.517632E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149001E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 10001584.68 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.128068E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.804634E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123770E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198961E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.267934E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142704E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 10001584.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273833E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 19499.41 | 02-JAN-09:09 | 5073.70 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2243.31 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 19499.41 | 01-FEB-09:09 | 5073.70 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2243.31 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 19182.50 | 03-MAR-09:09 | 5073.70 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2243.31 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18981.18 | 13-APR-08:09 | 5073.70 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2243.31 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 18927.75 | 09-MAY-08:09 | 4571.25 | 01-MAY-21:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2021.95 | 01-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 18741.80 | 07-JUN-08:09 | 4571.25 | 01-JUN-22:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 2021.95 | 01-JUN-06:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 18879.41 | 29-JUL-08:09 | 4571.25 | 11-JUL-22:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 2021.95 | 12-JUL-16:49 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 19045.21 | 31-AUG-08:09 | 5073.70 | 24-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 2021.95 | 02-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 19147.58 | 30-SEP-08:09 | 5073.70 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 2243.31 | 29-SEP-06:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 19499.41 | 23-OCT-08:09 | 5073.70 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2243.31 | 03-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 19499.41 | 01-NOV-08:09 | 5073.70 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2243.31 | 01-NOV-06:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19499.41 | 01-DEC-09:09 | 5073.70 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2243.31 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 18741.80 | 4571.25 | 10035.17 | 0.00 | 2021.95 | 0.00 | 0.00 | |||||
Maximum of Months | 19499.41 | 5073.70 | 10035.17 | 0.00 | 2243.31 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3131.30 | 11-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3129.64 | 13-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3129.56 | 16-MAR-11:50 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3129.62 | 10-APR-11:00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 3129.24 | 02-MAY-11:00 | 0.00 |
June | 932.74 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3039.98 | 01-JUN-11:50 | 0.00 |
July | 3047.84 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2888.04 | 01-JUL-11:09 | 0.00 |
August | 947.58 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2762.90 | 01-AUG-11:39 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 2741.94 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2828.36 | 25-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2988.33 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3129.40 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2741.94 | 0.00 | ||
Maximum of Months | 3047.84 | 0.00 | 0.00 | 0.00 | 3131.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39542.03 | 09-JAN-15:20 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38580.37 | 06-FEB-09:20 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36359.38 | 17-MAR-07:10 | 17326.12 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33520.83 | 08-APR-14:50 | 18551.81 | 10035.17 | 0.00 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33555.26 | 09-MAY-12:09 | 18807.39 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33545.48 | 20-JUN-14:00 | 18343.91 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 666.82 | 0.00 |
July | 35194.80 | 29-JUL-14:00 | 18304.00 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 2545.18 | 0.00 |
August | 33629.21 | 11-AUG-12:00 | 18628.17 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 694.97 | 0.00 |
September | 33307.95 | 30-SEP-14:39 | 18992.72 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38562.48 | 31-OCT-08:09 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39393.34 | 30-NOV-15:39 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39541.56 | 30-DEC-15:39 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 33307.95 | 17326.12 | 10035.17 | 0.00 | 0.00 | 2021.95 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39542.03 | 19499.41 | 10035.17 | 5073.70 | 0.00 | 2243.31 | 0.00 | 0.00 | 2545.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 214441.65 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 213302.76 | 24-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 198353.96 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 180782.72 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 27994.75 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9430.41 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1915.36 | 05-JUL-16:49 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7739.00 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 56594.19 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 161768.06 | 31-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 177773.11 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 200848.68 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1915.36 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 214441.65 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.83 | 17.29 | 13.50 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20.83 | 16.84 | 9.33 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15.33 | 17.98 | 11.17 | 19.09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11.17 | 18.74 | 9.33 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.33 | 20.16 | 6.33 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.67 | 20.46 | 0.67 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.33 | 24.56 |
August | 0.33 | 20.51 | 0.33 | 20.51 | 0.17 | 24.51 | 0.17 | 24.51 |
September | 5.17 | 20.22 | 5.17 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9.50 | 19.12 | 8.33 | 19.70 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13.83 | 17.69 | 8.83 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.00 | 18.25 | 9.83 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.00 | 18.02 | 82.83 | 19.45 | 0.50 | 24.54 | 0.50 | 24.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.83 | 20.51 | 13.50 | 20.51 | 0.33 | 24.56 | 0.33 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 119.17 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 102.00 | 14.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100.83 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60.00 | 14.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.17 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4.17 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64.83 | 14.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 110.17 | 14.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115.17 | 14.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 678.50 | 14.49 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.17 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.00 | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58.83 | 8.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 9.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.33 | 8.14 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.00 | 9.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.01 | 300.00 | 21.01 | 300.00 | 21.01 |
February | 276.00 | 21.02 | 276.00 | 21.02 | 276.00 | 21.02 |
March | 324.00 | 21.02 | 324.00 | 21.02 | 324.00 | 21.02 |
April | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
May | 312.00 | 21.24 | 294.17 | 21.16 | 294.17 | 21.16 |
June | 311.00 | 23.19 | 28.67 | 21.22 | 28.67 | 21.22 |
July | 188.83 | 23.64 | 4.50 | 23.88 | 0.00 | 0.00 |
August | 265.50 | 23.24 | 14.67 | 21.11 | 14.67 | 21.11 |
September | 300.00 | 21.23 | 266.50 | 21.11 | 266.50 | 21.11 |
October | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
November | 288.00 | 21.04 | 288.00 | 21.04 | 288.00 | 21.04 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 3465.33 | 21.57 | 2696.50 | 21.06 | 2692.00 | 21.06 |
Minimum of Months | 188.83 | 21.01 | 4.50 | 21.01 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.64 | 324.00 | 23.88 | 324.00 | 21.22 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.961621E+09 | 0.204234E+09 | 154.92 | 0.934831E+09 | 26789889.39 | 0.00 | 0.71 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 4321.91 | 30-JUN-15:00 | 4171.56 | 30-JUN-15:00 | 586.62 | 30-JUN-12:00 | 932.74 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.241699E+10 | 0.501792E+09 | 239.11 | 0.228403E+10 | 0.132960E+09 | 0.00 | 1.00 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 | 12497.37 | 25-JUL-05:03 | 11551.01 | 22-JUL-05:03 | 1508.83 | 25-JUL-05:03 | 2496.57 | 25-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.145239E+10 | 0.303190E+09 | 187.26 | 0.138440E+10 | 67986078.55 | 0.00 | 1.00 | 03-AUG-05:03 | 0.00 | 01-AUG-00:10 | 12029.17 | 05-AUG-05:03 | 12015.27 | 03-AUG-05:03 | 845.87 | 04-AUG-05:03 | 2415.21 | 05-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.483100E+10 | 0.100922E+10 | 581.29 | 0.460326E+10 | 0.227736E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.241699E+10 | 0.501792E+09 | 239.11 | 0.228403E+10 | 0.132960E+09 | 0.00 | 1.00 | 0.00 | 12497.37 | 12015.27 | 1508.83 | 2496.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
July | 0.210616E+09 | 51191375.73 | 24.00 | 0.209550E+09 | 1065367.84 | 0.00 | 0.72 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 | 7610.19 | 21-JUL-16:00 | 7610.19 | 21-JUL-16:00 | 167.68 | 22-JUL-11:20 | 1838.13 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 4336.04 | 1051.22 | 3.17 | 4119.09 | 216.95 | 0.00 | 0.00 | 04-AUG-12:50 | 0.00 | 01-AUG-00:10 | 0.95 | 04-AUG-12:50 | 0.88 | 04-AUG-12:50 | 0.07 | 04-AUG-12:50 | 0.23 | 04-AUG-12:50 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.210620E+09 | 51192426.95 | 27.17 | 0.209554E+09 | 1065584.78 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.210616E+09 | 51191375.73 | 24.00 | 0.209550E+09 | 1065367.84 | 0.00 | 0.72 | 0.00 | 7610.19 | 7610.19 | 167.68 | 1838.13 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.71 | 0.80 | 3.91 | 0.00 | 241.57 | 0.00 | 0.00 | 744.00 |
February | 28.10 | 9.78 | 18.32 | 3.21 | 204.10 | 0.00 | 0.00 | 672.00 |
March | 84.70 | 36.65 | 48.05 | 41.55 | 141.89 | 0.00 | 0.00 | 744.00 |
April | 200.11 | 103.83 | 96.28 | 184.79 | 72.18 | 0.00 | 0.00 | 720.00 |
May | 194.39 | 88.68 | 105.71 | 197.07 | 29.97 | 0.00 | 0.00 | 744.00 |
June | 213.15 | 91.12 | 122.03 | 222.07 | 18.35 | 0.00 | 0.00 | 720.00 |
July | 178.06 | 67.40 | 110.66 | 180.17 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 146.76 | 62.41 | 84.35 | 140.10 | 37.44 | 0.00 | 0.00 | 744.00 |
September | 88.42 | 36.93 | 51.49 | 68.63 | 60.00 | 0.00 | 0.00 | 720.00 |
October | 34.55 | 10.30 | 24.25 | 10.41 | 124.09 | 0.00 | 0.00 | 744.00 |
November | 13.80 | 4.96 | 8.85 | 0.74 | 232.53 | 0.00 | 0.00 | 720.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 257.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 99.25 | 42.84 | 56.42 | 87.74 | 119.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 18.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 213.15 | 103.83 | 122.03 | 222.07 | 257.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.71 | 0.80 | 3.91 | 0.00 | 241.57 | 0.00 | 0.00 | 744.00 |
February | 28.10 | 9.78 | 18.32 | 3.21 | 204.10 | 0.00 | 0.00 | 672.00 |
March | 84.70 | 36.65 | 48.05 | 41.55 | 141.89 | 0.00 | 0.00 | 744.00 |
April | 200.11 | 103.83 | 96.28 | 184.79 | 72.18 | 0.00 | 0.00 | 720.00 |
May | 194.39 | 88.68 | 105.71 | 197.07 | 29.97 | 0.00 | 0.00 | 744.00 |
June | 213.15 | 91.12 | 122.03 | 222.07 | 18.35 | 0.00 | 0.00 | 720.00 |
July | 178.06 | 67.40 | 110.66 | 180.17 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 146.76 | 62.41 | 84.35 | 140.10 | 37.44 | 0.00 | 0.00 | 744.00 |
September | 88.42 | 36.93 | 51.49 | 68.63 | 60.00 | 0.00 | 0.00 | 720.00 |
October | 34.55 | 10.30 | 24.25 | 10.41 | 124.09 | 0.00 | 0.00 | 744.00 |
November | 13.80 | 4.96 | 8.85 | 0.74 | 232.53 | 0.00 | 0.00 | 720.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 257.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 99.25 | 42.84 | 56.42 | 87.74 | 119.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 18.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 213.15 | 103.83 | 122.03 | 222.07 | 257.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.00 | 0.00 | 2.00 | 0.00 | 141.95 | 0.00 | 0.00 | 744.00 |
February | 8.84 | 0.00 | 8.84 | 0.00 | 125.89 | 0.00 | 0.00 | 672.00 |
March | 23.70 | 0.01 | 23.69 | 1.66 | 90.96 | 0.00 | 0.00 | 744.00 |
April | 43.07 | 1.16 | 41.91 | 17.45 | 43.63 | 0.00 | 0.00 | 720.00 |
May | 65.96 | 10.54 | 55.42 | 50.76 | 15.43 | 0.00 | 0.00 | 744.00 |
June | 85.13 | 18.62 | 66.51 | 75.51 | 8.14 | 0.00 | 0.00 | 720.00 |
July | 71.83 | 11.74 | 60.08 | 61.07 | 12.31 | 0.00 | 0.00 | 744.00 |
August | 46.14 | 2.43 | 43.70 | 30.89 | 20.76 | 0.00 | 0.00 | 744.00 |
September | 25.70 | 0.07 | 25.63 | 9.98 | 36.52 | 0.00 | 0.00 | 720.00 |
October | 12.44 | 0.00 | 12.44 | 1.06 | 76.19 | 0.00 | 0.00 | 744.00 |
November | 3.86 | 0.00 | 3.86 | 0.00 | 139.87 | 0.00 | 0.00 | 720.00 |
December | 0.61 | 0.00 | 0.61 | 0.00 | 150.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.56 | 3.73 | 28.82 | 20.81 | 71.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.61 | 0.00 | 0.61 | 0.00 | 8.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.13 | 18.62 | 66.51 | 75.51 | 150.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.00 | 0.00 | 2.00 | 0.00 | 141.95 | 0.00 | 0.00 | 744.00 |
February | 8.84 | 0.00 | 8.84 | 0.00 | 125.89 | 0.00 | 0.00 | 672.00 |
March | 23.70 | 0.01 | 23.69 | 1.65 | 90.96 | 0.00 | 0.00 | 744.00 |
April | 43.07 | 1.16 | 41.91 | 17.45 | 43.63 | 0.00 | 0.00 | 720.00 |
May | 65.96 | 10.54 | 55.42 | 50.76 | 15.43 | 0.00 | 0.00 | 744.00 |
June | 85.13 | 18.61 | 66.51 | 75.51 | 8.14 | 0.00 | 0.00 | 720.00 |
July | 71.83 | 11.74 | 60.08 | 61.06 | 12.31 | 0.00 | 0.00 | 744.00 |
August | 46.14 | 2.43 | 43.70 | 30.88 | 20.76 | 0.00 | 0.00 | 744.00 |
September | 25.70 | 0.07 | 25.63 | 9.98 | 36.52 | 0.00 | 0.00 | 720.00 |
October | 12.44 | 0.00 | 12.44 | 1.06 | 76.19 | 0.00 | 0.00 | 744.00 |
November | 3.86 | 0.00 | 3.86 | 0.00 | 139.87 | 0.00 | 0.00 | 720.00 |
December | 0.61 | 0.00 | 0.61 | 0.00 | 150.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.55 | 3.73 | 28.82 | 20.81 | 71.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.61 | 0.00 | 0.61 | 0.00 | 8.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.13 | 18.61 | 66.51 | 75.51 | 150.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.43 | 0.22 | 2.21 | 0.00 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 12.32 | 3.02 | 9.31 | 0.08 | 118.52 | 0.00 | 0.00 | 672.00 |
March | 43.27 | 18.41 | 24.86 | 27.89 | 78.66 | 0.00 | 0.00 | 744.00 |
April | 87.05 | 46.98 | 40.07 | 94.48 | 40.47 | 0.00 | 0.00 | 720.00 |
May | 113.56 | 64.64 | 48.92 | 138.27 | 19.33 | 0.00 | 0.00 | 744.00 |
June | 123.19 | 61.44 | 61.74 | 149.74 | 13.27 | 0.00 | 0.00 | 720.00 |
July | 110.52 | 53.46 | 57.06 | 129.81 | 18.73 | 0.00 | 0.00 | 744.00 |
August | 83.19 | 40.38 | 42.82 | 91.68 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 44.94 | 17.80 | 27.14 | 41.98 | 36.06 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 4.48 | 13.97 | 8.78 | 61.42 | 8.83 | 0.00 | 744.00 |
November | 4.62 | 0.38 | 4.24 | 0.00 | 136.73 | 0.00 | 0.00 | 720.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 149.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.90 | 26.06 | 27.84 | 57.20 | 69.61 | 8.83 | 0.00 | 8760.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 123.19 | 64.64 | 61.74 | 149.74 | 149.15 | 8.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12623257.79 | 2141576.15 | 10481681.64 | 0.00 | 0.647017E+09 |
February | 67986272.16 | 23671541.49 | 44314730.67 | 7769825.98 | 0.493762E+09 |
March | 0.226861E+09 | 98166444.86 | 0.128695E+09 | 0.111292E+09 | 0.380044E+09 |
April | 0.518696E+09 | 0.269128E+09 | 0.249567E+09 | 0.478971E+09 | 0.187096E+09 |
May | 0.520642E+09 | 0.237509E+09 | 0.283133E+09 | 0.527825E+09 | 80261420.15 |
June | 0.552474E+09 | 0.236179E+09 | 0.316295E+09 | 0.575596E+09 | 47556898.78 |
July | 0.476925E+09 | 0.180523E+09 | 0.296402E+09 | 0.482562E+09 | 66688745.98 |
August | 0.393085E+09 | 0.167171E+09 | 0.225913E+09 | 0.375241E+09 | 0.100269E+09 |
September | 0.229179E+09 | 95715709.46 | 0.133463E+09 | 0.177885E+09 | 0.155533E+09 |
October | 92525760.84 | 27581072.04 | 64944688.80 | 27885034.21 | 0.332355E+09 |
November | 35782131.67 | 12846651.70 | 22935479.96 | 1920893.31 | 0.602729E+09 |
December | 3326085.10 | 340968.15 | 2985116.95 | 0.00 | 0.689318E+09 |
Annual Sum or Average | 0.313010E+10 | 0.135097E+10 | 0.177913E+10 | 0.276695E+10 | 0.378263E+10 |
Minimum of Months | 3326085.10 | 340968.15 | 2985116.95 | 0.00 | 47556898.78 |
Maximum of Months | 0.552474E+09 | 0.269128E+09 | 0.316295E+09 | 0.575596E+09 | 0.689318E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12623257.79 | 2141576.15 | 10481681.64 | 0.00 | 0.647017E+09 |
February | 67986272.16 | 23671541.49 | 44314730.67 | 7769825.98 | 0.493762E+09 |
March | 0.226861E+09 | 98166444.86 | 0.128695E+09 | 0.111292E+09 | 0.380044E+09 |
April | 0.518696E+09 | 0.269128E+09 | 0.249567E+09 | 0.478971E+09 | 0.187096E+09 |
May | 0.520642E+09 | 0.237509E+09 | 0.283133E+09 | 0.527825E+09 | 80261420.15 |
June | 0.552474E+09 | 0.236179E+09 | 0.316295E+09 | 0.575596E+09 | 47556898.78 |
July | 0.476925E+09 | 0.180523E+09 | 0.296402E+09 | 0.482562E+09 | 66688745.98 |
August | 0.393085E+09 | 0.167171E+09 | 0.225913E+09 | 0.375241E+09 | 0.100269E+09 |
September | 0.229179E+09 | 95715709.46 | 0.133463E+09 | 0.177885E+09 | 0.155533E+09 |
October | 92525760.84 | 27581072.04 | 64944688.80 | 27885034.21 | 0.332355E+09 |
November | 35782131.67 | 12846651.70 | 22935479.96 | 1920893.31 | 0.602729E+09 |
December | 3326085.10 | 340968.15 | 2985116.95 | 0.00 | 0.689318E+09 |
Annual Sum or Average | 0.313010E+10 | 0.135097E+10 | 0.177913E+10 | 0.276695E+10 | 0.378263E+10 |
Minimum of Months | 3326085.10 | 340968.15 | 2985116.95 | 0.00 | 47556898.78 |
Maximum of Months | 0.552474E+09 | 0.269128E+09 | 0.316295E+09 | 0.575596E+09 | 0.689318E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5353374.14 | 0.00 | 5353374.14 | 0.00 | 0.380189E+09 |
February | 21374389.86 | 0.00 | 21374389.86 | 0.00 | 0.304541E+09 |
March | 63478750.44 | 18845.46 | 63459904.98 | 4432832.05 | 0.243624E+09 |
April | 0.111646E+09 | 3005951.67 | 0.108640E+09 | 45241218.70 | 0.113097E+09 |
May | 0.176671E+09 | 28232431.06 | 0.148439E+09 | 0.135968E+09 | 41318198.58 |
June | 0.220653E+09 | 48252212.80 | 0.172401E+09 | 0.195725E+09 | 21088189.79 |
July | 0.192384E+09 | 31456547.34 | 0.160928E+09 | 0.163560E+09 | 32960873.58 |
August | 0.123573E+09 | 6513792.51 | 0.117059E+09 | 82722668.09 | 55610784.58 |
September | 66604886.35 | 178377.12 | 66426509.22 | 25870701.20 | 94666886.99 |
October | 33314208.26 | 0.00 | 33314208.26 | 2829109.11 | 0.204056E+09 |
November | 10005074.74 | 0.00 | 10005074.74 | 0.00 | 0.362532E+09 |
December | 1623932.86 | 0.00 | 1623932.86 | 0.00 | 0.402879E+09 |
Annual Sum or Average | 0.102668E+10 | 0.117658E+09 | 0.909024E+09 | 0.656349E+09 | 0.225656E+10 |
Minimum of Months | 1623932.86 | 0.00 | 1623932.86 | 0.00 | 21088189.79 |
Maximum of Months | 0.220653E+09 | 48252212.80 | 0.172401E+09 | 0.195725E+09 | 0.402879E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5353180.64 | 0.00 | 5353180.64 | 0.00 | 0.380188E+09 |
February | 21373666.20 | 0.00 | 21373666.20 | 0.00 | 0.304541E+09 |
March | 63476729.30 | 18844.58 | 63457884.72 | 4432233.25 | 0.243625E+09 |
April | 0.111642E+09 | 3005810.78 | 0.108637E+09 | 45238731.45 | 0.113098E+09 |
May | 0.176665E+09 | 28231107.77 | 0.148434E+09 | 0.135962E+09 | 41318029.30 |
June | 0.220645E+09 | 48249951.15 | 0.172395E+09 | 0.195716E+09 | 21088125.70 |
July | 0.192377E+09 | 31455072.93 | 0.160922E+09 | 0.163553E+09 | 32960833.35 |
August | 0.123568E+09 | 6513487.20 | 0.117055E+09 | 82718703.32 | 55610629.24 |
September | 66602685.78 | 178368.76 | 66424317.02 | 25869067.08 | 94666901.64 |
October | 33313067.02 | 0.00 | 33313067.02 | 2828815.24 | 0.204056E+09 |
November | 10004713.11 | 0.00 | 10004713.11 | 0.00 | 0.362531E+09 |
December | 1623871.59 | 0.00 | 1623871.59 | 0.00 | 0.402878E+09 |
Annual Sum or Average | 0.102665E+10 | 0.117653E+09 | 0.908994E+09 | 0.656318E+09 | 0.225656E+10 |
Minimum of Months | 1623871.59 | 0.00 | 1623871.59 | 0.00 | 21088125.70 |
Maximum of Months | 0.220645E+09 | 48249951.15 | 0.172395E+09 | 0.195716E+09 | 0.402878E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6514961.26 | 590881.84 | 5924079.42 | 0.00 | 0.372022E+09 |
February | 29808733.07 | 7294199.23 | 22514533.84 | 189558.57 | 0.286714E+09 |
March | 0.115898E+09 | 49301414.96 | 66596173.58 | 74712196.31 | 0.210681E+09 |
April | 0.225629E+09 | 0.121760E+09 | 0.103869E+09 | 0.244899E+09 | 0.104886E+09 |
May | 0.304162E+09 | 0.173125E+09 | 0.131037E+09 | 0.370330E+09 | 51764536.61 |
June | 0.319303E+09 | 0.159262E+09 | 0.160041E+09 | 0.388136E+09 | 34384192.34 |
July | 0.296013E+09 | 0.143196E+09 | 0.152817E+09 | 0.347672E+09 | 50166395.74 |
August | 0.222826E+09 | 0.108144E+09 | 0.114682E+09 | 0.245553E+09 | 72843631.10 |
September | 0.116488E+09 | 46130834.70 | 70357428.25 | 0.108823E+09 | 93454687.61 |
October | 49404521.69 | 11987578.13 | 37416943.56 | 23521602.53 | 0.164516E+09 |
November | 11980390.40 | 990078.51 | 10990311.90 | 0.00 | 0.354400E+09 |
December | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 0.399473E+09 |
Annual Sum or Average | 0.169985E+10 | 0.821817E+09 | 0.878038E+09 | 0.180384E+10 | 0.219530E+10 |
Minimum of Months | 1826392.17 | 34294.88 | 1792097.28 | 0.00 | 34384192.34 |
Maximum of Months | 0.319303E+09 | 0.173125E+09 | 0.160041E+09 | 0.388136E+09 | 0.399473E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 767.03 | 13.42 | 1.60 | 11.82 | 0.00 | 0.00 |
February | 2.00 | 655.55 | 73.88 | 19.57 | 54.31 | 0.00 | 0.00 |
March | 75.55 | 454.84 | 216.80 | 73.32 | 143.48 | 0.00 | 0.00 |
April | 400.12 | 227.27 | 486.37 | 209.98 | 276.39 | 0.00 | 0.00 |
May | 488.22 | 83.34 | 520.69 | 198.43 | 322.26 | 0.00 | 0.00 |
June | 588.14 | 45.95 | 596.55 | 219.47 | 377.08 | 0.00 | 0.00 |
July | 476.31 | 68.26 | 499.78 | 158.29 | 341.49 | 0.00 | 0.00 |
August | 338.08 | 112.51 | 385.79 | 129.69 | 256.10 | 0.00 | 0.00 |
September | 154.47 | 190.31 | 228.23 | 73.99 | 154.23 | 0.00 | 0.00 |
October | 19.64 | 397.26 | 93.97 | 20.60 | 73.37 | 0.00 | 0.00 |
November | 0.49 | 743.81 | 35.33 | 9.91 | 25.42 | 0.00 | 0.00 |
December | 0.00 | 815.56 | 3.70 | 0.25 | 3.44 | 0.00 | 0.00 |
Annual Sum or Average | 212.83 | 378.73 | 263.62 | 93.14 | 170.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 45.95 | 3.70 | 0.25 | 3.44 | 0.00 | 0.00 |
Maximum of Months | 588.14 | 815.56 | 596.55 | 219.47 | 377.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1388.97 | 24.32 | 2.21 | 22.12 | 0.00 | 0.00 |
February | 0.78 | 1185.16 | 123.22 | 30.15 | 93.07 | 0.00 | 0.00 |
March | 278.94 | 786.59 | 432.71 | 184.07 | 248.64 | 0.00 | 0.00 |
April | 944.83 | 404.65 | 870.48 | 469.75 | 400.73 | 0.00 | 0.00 |
May | 1382.65 | 193.27 | 1135.61 | 646.38 | 489.24 | 0.00 | 0.00 |
June | 1497.44 | 132.65 | 1231.88 | 614.44 | 617.44 | 0.00 | 0.00 |
July | 1298.06 | 187.30 | 1105.19 | 534.63 | 570.55 | 0.00 | 0.00 |
August | 916.79 | 271.97 | 831.94 | 403.76 | 428.17 | 0.00 | 0.00 |
September | 419.84 | 360.55 | 449.41 | 177.97 | 271.44 | 0.00 | 0.00 |
October | 87.82 | 614.23 | 184.46 | 44.76 | 139.70 | 0.00 | 0.00 |
November | 0.00 | 1367.28 | 46.22 | 3.82 | 42.40 | 0.00 | 0.00 |
December | 0.00 | 1491.46 | 6.82 | 0.13 | 6.69 | 0.00 | 0.00 |
Annual Sum or Average | 571.99 | 696.13 | 539.02 | 260.60 | 278.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 132.65 | 6.82 | 0.13 | 6.69 | 0.00 | 0.00 |
Maximum of Months | 1497.44 | 1491.46 | 1231.88 | 646.38 | 617.44 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.205441E+10 | 35953070.36 | 4283152.29 | 31669918.06 | 0.00 | 0.00 |
February | 4845451.67 | 0.158591E+10 | 0.178721E+09 | 47343082.99 | 0.131378E+09 | 0.00 | 0.00 |
March | 0.202364E+09 | 0.121825E+10 | 0.580678E+09 | 0.196371E+09 | 0.384308E+09 | 0.00 | 0.00 |
April | 0.103712E+10 | 0.589079E+09 | 0.126068E+10 | 0.544268E+09 | 0.716411E+09 | 0.00 | 0.00 |
May | 0.130764E+10 | 0.223217E+09 | 0.139462E+10 | 0.531482E+09 | 0.863139E+09 | 0.00 | 0.00 |
June | 0.152445E+10 | 0.119108E+09 | 0.154625E+10 | 0.568860E+09 | 0.977385E+09 | 0.00 | 0.00 |
July | 0.127575E+10 | 0.182816E+09 | 0.133861E+10 | 0.423958E+09 | 0.914653E+09 | 0.00 | 0.00 |
August | 0.905501E+09 | 0.301337E+09 | 0.103331E+10 | 0.347370E+09 | 0.685941E+09 | 0.00 | 0.00 |
September | 0.400394E+09 | 0.493283E+09 | 0.591565E+09 | 0.191788E+09 | 0.399777E+09 | 0.00 | 0.00 |
October | 52615423.33 | 0.106401E+10 | 0.251679E+09 | 55162144.09 | 0.196517E+09 | 0.00 | 0.00 |
November | 1278186.88 | 0.192796E+10 | 91574051.19 | 25693303.41 | 65880747.79 | 0.00 | 0.00 |
December | 0.00 | 0.218439E+10 | 9899974.65 | 681936.30 | 9218038.35 | 0.00 | 0.00 |
Annual Sum or Average | 0.671195E+10 | 0.119438E+11 | 0.831354E+10 | 0.293726E+10 | 0.537628E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.119108E+09 | 9899974.65 | 681936.30 | 9218038.35 | 0.00 | 0.00 |
Maximum of Months | 0.152445E+10 | 0.218439E+10 | 0.154625E+10 | 0.568860E+09 | 0.977385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.372022E+10 | 65149612.60 | 5908818.44 | 59240794.16 | 0.00 | 0.00 |
February | 1895585.74 | 0.286714E+10 | 0.298087E+09 | 72941992.27 | 0.225145E+09 | 0.00 | 0.00 |
March | 0.747120E+09 | 0.210681E+10 | 0.115898E+10 | 0.493014E+09 | 0.665962E+09 | 0.00 | 0.00 |
April | 0.244899E+10 | 0.104886E+10 | 0.225629E+10 | 0.121760E+10 | 0.103869E+10 | 0.00 | 0.00 |
May | 0.370330E+10 | 0.517644E+09 | 0.304162E+10 | 0.173125E+10 | 0.131037E+10 | 0.00 | 0.00 |
June | 0.388136E+10 | 0.343842E+09 | 0.319303E+10 | 0.159262E+10 | 0.160041E+10 | 0.00 | 0.00 |
July | 0.347672E+10 | 0.501664E+09 | 0.296013E+10 | 0.143196E+10 | 0.152817E+10 | 0.00 | 0.00 |
August | 0.245553E+10 | 0.728436E+09 | 0.222826E+10 | 0.108144E+10 | 0.114682E+10 | 0.00 | 0.00 |
September | 0.108823E+10 | 0.934546E+09 | 0.116488E+10 | 0.461308E+09 | 0.703574E+09 | 0.00 | 0.00 |
October | 0.235215E+09 | 0.164516E+10 | 0.494045E+09 | 0.119876E+09 | 0.374169E+09 | 0.00 | 0.00 |
November | 0.00 | 0.354400E+10 | 0.119804E+09 | 9900785.06 | 0.109903E+09 | 0.00 | 0.00 |
December | 0.00 | 0.399473E+10 | 18263921.67 | 342948.85 | 17920972.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.180384E+11 | 0.219530E+11 | 0.169985E+11 | 0.821817E+10 | 0.878038E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.343842E+09 | 18263921.67 | 342948.85 | 17920972.82 | 0.00 | 0.00 |
Maximum of Months | 0.388136E+10 | 0.399473E+10 | 0.319303E+10 | 0.173125E+10 | 0.160041E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.5 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.6 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.24 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.87 | 6.41 | 3.45 | 5.65 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.84 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.69 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.46 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.84 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.6 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.5 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.58 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.01 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.76 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.27 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.32 | 11.70 | 4.67 | 18.87 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.74 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.88 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 7.99 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.5 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.0 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.5 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.32 | 11.70 | 6.20 | 18.87 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.1 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.2 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.0 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.8 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.6 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.23 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.64 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.01 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.94 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.32 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.33 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.28 | 141.00 | 225.33 |
August | 16.13 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.81 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 7.99 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.5 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.0 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.5 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.33 | 29.07 | 14.40 | 8.80 | 19.28 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.6 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.77 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.74 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.40 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.29 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.0 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.4 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.0 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114172E+10 | -.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88101483.9 | 59.00 | 0.00 | 0.00 |
February | 0.104744E+10 | -967994141.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79450372.4 | 59.00 | 0.00 | 0.00 |
March | 0.121912E+10 | -.113151E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87611431.7 | 59.00 | 0.00 | 0.00 |
April | 0.113513E+10 | -.105104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84096340.5 | 59.00 | 0.00 | 0.00 |
May | 0.116951E+10 | -.108503E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -84487104.5 | 59.00 | 0.00 | 0.00 |
June | 0.111649E+10 | -.104140E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -75090010.7 | 58.99 | 0.00 | 0.00 |
July | 0.104328E+10 | -968519984.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74761193.1 | 58.99 | 0.00 | 0.00 |
August | 0.109107E+10 | -.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -76091628.9 | 58.99 | 0.00 | 0.00 |
September | 0.102120E+10 | -939958743.5 | 0.00 | 0.00 | 720.00 | 0.00 | -81244423.4 | 58.99 | 0.00 | 0.00 |
October | 0.104805E+10 | -960933095.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87118679.5 | 58.99 | 0.00 | 0.00 |
November | 0.104115E+10 | -955930403.9 | 0.00 | 0.00 | 720.00 | 0.00 | -85215176.4 | 59.00 | 0.00 | 0.00 |
December | 0.112432E+10 | -.103625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88072503.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.131985E+11 | -.122072E+11 | 8760.00 | -991340348.1 | 59.00 | |||||
Minimum of Months | 0.102120E+10 | -.113151E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88101483.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121912E+10 | -939958743.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74761193.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.99 | 0.94 | 31-JAN-11:30 | 27.75 | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.97 | 0.88 | 23-FEB-11:09 | 64.49 | 6.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.94 | 0.88 | 05-MAR-10:20 | 120.71 | 9.29 | 0.00 | 54.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.93 | 0.88 | 01-APR-09:39 | 149.27 | 10.16 | 0.00 | 92.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.92 | 0.88 | 01-MAY-06:00 | 168.68 | 10.45 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.92 | 0.88 | 01-JUN-06:19 | 516.19 | 10.74 | 0.00 | 280.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.92 | 0.88 | 01-JUL-05:30 | 194.47 | 10.91 | 0.00 | 242.83 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.92 | 0.88 | 01-AUG-06:40 | 167.67 | 10.59 | 0.00 | 154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.93 | 0.88 | 01-SEP-07:49 | 125.44 | 9.50 | 0.00 | 41.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.95 | 0.88 | 01-OCT-09:20 | 89.25 | 7.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.98 | 0.92 | 06-NOV-13:30 | 38.19 | 2.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 0.98 | 04-DEC-11:30 | 8.76 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.93 | 191.00 | 9.30 | 0.00 | 1044.83 | ||||||
Minimum of Months | 71.17 | 0.92 | 0.88 | 8.76 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 0.98 | 516.19 | 10.91 | 0.00 | 280.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.96 | 0.90 | 31-JAN-11:30 | 46.51 | 12.74 | 0.00 | 0.00 | 22.73 | 12.41 | 0.00 | 0.00 |
February | 205.83 | 0.90 | 0.76 | 28-FEB-15:20 | 109.66 | 17.91 | 17.00 | 0.00 | 56.73 | 17.63 | 4.50 | 0.00 |
March | 329.50 | 0.81 | 0.61 | 12-MAR-17:10 | 317.10 | 23.31 | 152.17 | 31.50 | 132.88 | 22.18 | 139.50 | 8.50 |
April | 421.83 | 0.75 | 0.61 | 01-APR-15:30 | 551.45 | 23.68 | 230.50 | 134.00 | 428.86 | 23.82 | 259.50 | 87.50 |
May | 545.00 | 0.76 | 0.61 | 01-MAY-16:00 | 268.18 | 20.43 | 232.00 | 99.33 | 269.80 | 21.49 | 294.83 | 83.33 |
June | 583.50 | 0.74 | 0.61 | 01-JUN-15:09 | 288.23 | 20.25 | 254.83 | 119.67 | 206.53 | 21.19 | 323.50 | 73.50 |
July | 562.83 | 0.75 | 0.61 | 02-JUL-15:09 | 278.58 | 20.24 | 233.50 | 118.67 | 255.75 | 21.20 | 287.67 | 69.17 |
August | 467.17 | 0.77 | 0.61 | 01-AUG-16:10 | 383.00 | 22.11 | 208.17 | 86.83 | 316.50 | 22.68 | 241.00 | 59.83 |
September | 356.33 | 0.81 | 0.61 | 02-SEP-16:19 | 388.78 | 23.98 | 163.83 | 50.50 | 142.15 | 22.35 | 155.50 | 11.50 |
October | 265.50 | 0.88 | 0.66 | 01-OCT-15:30 | 152.51 | 20.66 | 47.17 | 10.00 | 63.83 | 18.45 | 13.17 | 0.00 |
November | 135.83 | 0.94 | 0.85 | 06-NOV-13:30 | 64.79 | 14.94 | 0.00 | 0.00 | 33.36 | 14.56 | 0.00 | 0.00 |
December | 71.17 | 0.99 | 0.96 | 05-DEC-11:30 | 16.42 | 6.53 | 0.00 | 0.00 | 7.74 | 6.18 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.79 | 297.00 | 20.71 | 1539.17 | 650.50 | 214.86 | 20.78 | 1719.17 | 393.33 | ||
Minimum of Months | 71.17 | 0.74 | 0.61 | 16.42 | 6.53 | 0.00 | 0.00 | 7.74 | 6.18 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.99 | 0.96 | 551.45 | 23.98 | 254.83 | 134.00 | 428.86 | 23.82 | 323.50 | 87.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142199E+11 | 23377.31 | 01-JAN-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120934E+11 | 23377.31 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120538E+11 | 23377.31 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642802E+10 | 23377.31 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212998E+10 | 23377.31 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102321E+09 | 23377.31 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6546785.62 | 1548.64 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86150031.07 | 23377.31 | 31-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264896E+10 | 23377.31 | 05-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729097E+10 | 23377.31 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119168E+11 | 23377.31 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138451E+11 | 23377.31 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828219E+11 | |||||||
Minimum of Months | 6546785.62 | 1548.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142199E+11 | 23377.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527077E+11 | 61484.03 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427834E+11 | 61484.03 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.396694E+11 | 61484.03 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185041E+11 | 61484.03 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141814E+10 | 46266.86 | 28-MAY-02:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232098E+10 | 59214.22 | 23-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230739E+11 | 61484.03 | 05-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403651E+11 | 61484.03 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.512789E+11 | 61484.03 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272122E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527077E+11 | 61484.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145739E+12 | 97423.39 | 02-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123005E+12 | 97423.39 | 01-FEB-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117079E+12 | 97423.39 | 02-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.526076E+11 | 97423.39 | 01-APR-18:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4565004.47 | 1416.16 | 03-MAY-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618854E+09 | 20460.61 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645232E+11 | 86572.67 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101089E+12 | 91943.08 | 10-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142781E+12 | 97423.39 | 01-DEC-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.747447E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145739E+12 | 97423.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.961621E+09 | 0.934831E+09 | 4321.91 | 30-JUN-15:00 | 4171.56 | 0.00 |
July | 0.00 | 0.00 | 0.241699E+10 | 0.228403E+10 | 12497.37 | 25-JUL-05:03 | 10988.54 | 0.00 |
August | 0.00 | 0.00 | 0.145239E+10 | 0.138440E+10 | 12029.17 | 05-AUG-05:03 | 11984.58 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.483100E+10 | 0.460326E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241699E+10 | 0.228403E+10 | 12497.37 | 11984.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210616E+09 | 0.209550E+09 | 7610.19 | 21-JUL-16:00 | 7610.19 | 0.00 |
August | 0.00 | 0.00 | 4336.04 | 4119.09 | 0.95 | 04-AUG-12:50 | 0.88 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.210620E+09 | 0.209554E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210616E+09 | 0.209550E+09 | 7610.19 | 7610.19 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.592899E+09 | 0.08 | 221.36 | 01-JAN-00:02 | 0.08 |
February | 0.535522E+09 | 0.08 | 221.36 | 01-FEB-00:02 | 0.08 |
March | 0.570519E+09 | 0.07 | 221.36 | 01-MAR-00:02 | 0.08 |
April | 0.349884E+09 | 0.05 | 221.36 | 01-APR-00:10 | 0.08 |
May | 3121219.27 | 0.00 | 221.36 | 02-MAY-01:15 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 15938140.97 | 0.00 | 221.36 | 29-SEP-02:00 | 0.08 |
October | 0.467629E+09 | 0.06 | 221.36 | 01-OCT-00:05 | 0.08 |
November | 0.573773E+09 | 0.08 | 221.36 | 01-NOV-00:10 | 0.08 |
December | 0.592899E+09 | 0.08 | 221.36 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.370218E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592899E+09 | 0.08 | 221.36 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.883542E+09 | 0.62 | 789.27 | 02-JAN-07:30 | 0.93 |
February | 0.812914E+09 | 0.66 | 789.27 | 01-FEB-07:30 | 0.93 |
March | 0.923426E+09 | 0.59 | 789.27 | 06-MAR-15:40 | 0.93 |
April | 0.822549E+09 | 0.44 | 789.27 | 22-APR-12:30 | 0.92 |
May | 0.830093E+09 | 0.38 | 789.27 | 04-MAY-14:40 | 0.92 |
June | 0.814215E+09 | 0.37 | 789.27 | 03-JUN-15:00 | 0.92 |
July | 0.783953E+09 | 0.34 | 789.27 | 08-JUL-09:30 | 0.92 |
August | 0.845674E+09 | 0.37 | 789.27 | 28-AUG-06:50 | 0.92 |
September | 0.796252E+09 | 0.38 | 789.27 | 23-SEP-09:30 | 0.92 |
October | 0.814515E+09 | 0.41 | 789.27 | 07-OCT-08:70 | 0.92 |
November | 0.811421E+09 | 0.52 | 789.27 | 01-NOV-07:10 | 0.93 |
December | 0.864059E+09 | 0.60 | 789.27 | 29-DEC-13:20 | 0.93 |
Annual Sum or Average | 0.100026E+11 | 0.47 | |||
Minimum of Months | 0.783953E+09 | 0.34 | 789.27 | 0.92 | |
Maximum of Months | 0.923426E+09 | 0.66 | 789.27 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.180416E+10 | 0.81 | 1232.68 | 02-JAN-07:50 | 0.93 |
February | 0.163089E+10 | 0.81 | 1232.68 | 01-FEB-08:20 | 0.93 |
March | 0.180857E+10 | 0.81 | 1232.68 | 01-MAR-07:30 | 0.93 |
April | 0.150603E+10 | 0.71 | 1232.68 | 01-APR-06:40 | 0.93 |
May | 0.129742E+10 | 0.42 | 1232.68 | 01-MAY-06:30 | 0.92 |
June | 0.126916E+10 | 0.37 | 1232.68 | 01-JUN-06:10 | 0.92 |
July | 0.122035E+10 | 0.34 | 1232.68 | 12-JUL-16:50 | 0.92 |
August | 0.131798E+10 | 0.37 | 1232.68 | 02-AUG-14:40 | 0.92 |
September | 0.125329E+10 | 0.43 | 1232.68 | 16-SEP-07:15 | 0.92 |
October | 0.151951E+10 | 0.74 | 1232.68 | 02-OCT-07:20 | 0.92 |
November | 0.160605E+10 | 0.79 | 1232.68 | 01-NOV-06:20 | 0.93 |
December | 0.175753E+10 | 0.81 | 1232.68 | 01-DEC-09:00 | 0.93 |
Annual Sum or Average | 0.179909E+11 | 0.61 | |||
Minimum of Months | 0.122035E+10 | 0.34 | 1232.68 | 0.92 | |
Maximum of Months | 0.180857E+10 | 0.81 | 1232.68 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.15 | 0.04 |
February | 3.36 | 0.00 |
March | 3.52 | 0.00 |
April | 1.77 | 0.01 |
May | 0.29 | 0.00 |
June | 0.17 | 1.05 |
July | 0.08 | 1.60 |
August | 0.25 | 1.25 |
September | 0.79 | 0.00 |
October | 1.84 | 0.00 |
November | 4.14 | 0.00 |
December | 4.88 | 0.00 |
Annual Sum or Average | 24.25 | 0.03 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.88 | 1.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.23 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.23 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.23 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.883542E+09 | 0.193839E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.812914E+09 | 0.166579E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.923426E+09 | 0.167210E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.822549E+09 | 0.915489E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.830093E+09 | 0.309749E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.101845E+10 | 0.149001E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.128574E+10 | 10001584.68 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114886E+10 | 0.128068E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.796252E+09 | 0.385574E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.814515E+09 | 0.103024E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.811421E+09 | 0.163120E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.864059E+09 | 0.188216E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110118E+11 | 0.114594E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.796252E+09 | 10001584.68 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128574E+10 | 0.193839E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.180416E+10 | 0.722760E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.163089E+10 | 0.590702E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180857E+10 | 0.554417E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150603E+10 | 0.261204E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129742E+10 | 0.207313E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126916E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.127154E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.131798E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125329E+10 | 0.341703E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151951E+10 | 0.328137E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160605E+10 | 0.562877E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175753E+10 | 0.706360E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180421E+11 | 0.378136E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125329E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.180857E+10 | 0.722760E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.883542E+09 | 0.00 | 0.142199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812914E+09 | 0.00 | 0.120934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923426E+09 | 0.00 | 0.120538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.822549E+09 | 0.00 | 0.642802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.830093E+09 | 0.00 | 0.212998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814215E+09 | 0.961621E+09 | 0.102321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783953E+09 | 0.241699E+10 | 6546785.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.845674E+09 | 0.145239E+10 | 86150031.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.796252E+09 | 0.00 | 0.264896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.814515E+09 | 0.00 | 0.729097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811421E+09 | 0.00 | 0.119168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.864059E+09 | 0.00 | 0.138451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100026E+11 | 0.483100E+10 | 0.828219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.783953E+09 | 0.00 | 6546785.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.923426E+09 | 0.241699E+10 | 0.142199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.180416E+10 | 0.00 | 0.527077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163089E+10 | 0.00 | 0.427834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180857E+10 | 0.00 | 0.396694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150603E+10 | 0.00 | 0.185041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129742E+10 | 0.00 | 0.141814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122035E+10 | 0.210616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131798E+10 | 4336.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125329E+10 | 0.00 | 0.232098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151951E+10 | 0.00 | 0.230739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160605E+10 | 0.00 | 0.403651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175753E+10 | 0.00 | 0.512789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179909E+11 | 0.210620E+09 | 0.272122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180857E+10 | 0.210616E+09 | 0.527077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.883542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.822549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.830093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814215E+09 | 0.00 | 0.00 | 0.00 | 0.204234E+09 | 0.00 | 0.149001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783953E+09 | 0.00 | 0.00 | 0.00 | 0.501792E+09 | 0.00 | 10001584.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.845674E+09 | 0.00 | 0.00 | 0.00 | 0.303190E+09 | 0.00 | 0.128068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.796252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.814515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.864059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100026E+11 | 0.00 | 0.00 | 0.00 | 0.100922E+10 | 0.00 | 0.114594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.783953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10001584.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.923426E+09 | 0.00 | 0.00 | 0.00 | 0.501792E+09 | 0.00 | 0.193839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.180416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122035E+10 | 0.00 | 0.00 | 0.00 | 51191375.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131798E+10 | 0.00 | 0.00 | 0.00 | 1051.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179909E+11 | 0.00 | 0.00 | 0.00 | 51192426.95 | 0.00 | 0.378136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180857E+10 | 0.00 | 0.00 | 0.00 | 51191375.73 | 0.00 | 0.722760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439719E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353911E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357585E+10 | 0.00 | 0.00 | 0.13 |
April | 6856637.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202084E+10 | 0.00 | 0.00 | 0.13 |
May | 0.260315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781120E+09 | 0.00 | 0.00 | 0.13 |
June | 0.361214E+09 | 4145392.38 | 0.00 | 1214757.32 | 0.00 | 13499858.15 | 0.406787E+09 | 0.00 | 0.13 |
July | 97281774.59 | 17867039.84 | 0.00 | 2863849.42 | 0.00 | 1592759.05 | 0.457165E+09 | 0.00 | 0.13 |
August | 0.437743E+09 | 704496.36 | 0.00 | 2200222.33 | 0.00 | 13765298.65 | 0.577253E+09 | 0.00 | 0.13 |
September | 0.380562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122854E+10 | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269301E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416421E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463508E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.154397E+10 | 22716928.57 | 0.00 | 6278829.06 | 0.00 | 0.270638E+11 | 0.144121E+10 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1592759.05 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.437743E+09 | 17867039.84 | 0.00 | 2863849.42 | 0.00 | 0.463508E+10 | 0.577253E+09 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152708E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119173E+11 | 0.00 | 0.00 | 0.18 |
March | 0.832264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107732E+11 | 0.00 | 0.00 | 0.19 |
April | 0.262544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302325E+10 | 0.00 | 0.00 | 0.18 |
May | 0.236742E+10 | 0.00 | 0.00 | 0.00 | 2223194.01 | 62762896.51 | 0.00 | 0.00 | 0.18 |
June | 0.251061E+10 | 0.00 | 0.00 | 0.00 | 3299439.34 | 0.00 | 0.00 | 0.00 | 0.19 |
July | 0.240554E+10 | 24248902.10 | 0.00 | 170286.18 | 10077161.28 | 0.00 | 0.137059E+09 | 0.00 | 0.19 |
August | 0.356432E+10 | 0.00 | 0.00 | 43668.84 | 130914.74 | 0.00 | 66170726.01 | 0.00 | 0.19 |
September | 0.413308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287393E+09 | 0.00 | 0.00 | 0.18 |
October | 0.223436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599195E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144195E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162544E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.206730E+11 | 24248902.10 | 0.00 | 213955.02 | 15730709.36 | 0.780006E+11 | 0.203230E+09 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.413308E+10 | 24248902.10 | 0.00 | 170286.18 | 10077161.28 | 0.162544E+11 | 0.137059E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:12:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |